Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:24:50
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2350.22 | 4597.89 | 4597.89 |
Net Site Energy | 2350.22 | 4597.89 | 4597.89 |
Total Source Energy | 5956.61 | 11653.27 | 11653.27 |
Net Source Energy | 5956.61 | 11653.27 | 11653.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 707.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 208.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.37 | 243.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 68.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1636.56 | 713.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 707.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.19 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 208.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.37 | 243.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 707.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 71.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 208.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.37 | 243.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 68.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1940.54 | 477.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1033.84 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3201.71 | 1396.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1940.54 | 477.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1033.84 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3201.71 | 1396.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1636.564 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1636.564 | 100.00 |
Total On-Site and Utility Electric Sources | 1636.564 | 100.00 |
Total Electricity End Uses | 1636.564 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 3098.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7187.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 9.5182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.3127 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.5182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.3127 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 9.4622 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-10:20 | 08-JAN-11:09 | - | - | - | - | - | - | - | - | - | - | 04-JAN-07:49 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39917.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24680.63 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10725.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3387.77 | 16251.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 85378.28 | 42499.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 39917.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 23313.05 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10725.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3387.77 | 16251.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2241.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 225.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 142.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1457.82 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 659.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.70 | 264.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 215.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5183.00 | 773.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4384.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1291.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.99 | 517.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 422.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 10139.81 | 1513.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4384.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1291.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.99 | 517.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 422.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 10139.81 | 1513.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.07 |
KITCHEN DIRECT AIR | 1.67 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.07 | 4.07 | 4.07 | 4.07 | 4.07 | 4.07 | 1.00 | 1.000000 | 4.07 |
PSZ-AC_2:2 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.00 | 1.00 | 1.67 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.07 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.67 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.07 | 6958.06 |
PSZ-AC_2:2_ADDAQ FAN | 1.67 | 1784.81 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.07 | 4.07 | 4.07 | 2.69 | 101126.89 | 164646.89 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.67 | 1.67 | 1.67 | 1.10 | 41419.76 | 51107.68 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.07 | 2.04 | 2.71 | 101126.89 | 50563.44 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.67 | 0.833987 | 1.11 | 41419.76 | 20709.88 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 164646.89 |
PSZ-AC_2:2 HEATING COIL | 51107.68 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 9.518 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 74.446 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.313 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.393 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3538.380 | 9.518 | 12.631 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3538.380 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1298.236 | 9.313 | 172.457 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1298.236 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.342 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5109 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.20636098E-16 | 0.18100998E-15 | 0.17288268E-13 | -0.34766289E-16 |
24 | 3 | -0.71341822E-08 | 0.14427768E-06 | -0.58767875E-04 | 0.16137435E-12 |
25 | 2 | 0.62866063E-04 | 0.30866150E-02 | 1.1745480 | -0.77421164E-04 |
26 | 1 | -0.70719755E-01 | 0.78899699E-01 | -17.315014 | 0.34200793 |
27 | 0 | 0.20250090 | 0.49857543E-01 | 16.272369 | |
28 | 4 | 0.17288268E-13 | 0.18100998E-15 | 0.20636098E-16 | -0.34766289E-16 |
29 | 3 | -0.58767875E-04 | 0.14427768E-06 | -0.71341822E-08 | 0.16137435E-12 |
30 | 2 | 1.1745480 | 0.30866150E-02 | 0.62866063E-04 | -0.77421164E-04 |
31 | 1 | -17.315014 | 0.78899699E-01 | -0.70719755E-01 | 0.34200793 |
32 | 0 | 16.272369 | 0.49857543E-01 | 0.20250090 | |
33 | 6 | 0.21862767E-07 | 0.34448908E-09 | 0.50649605E-08 | -0.99069094E-13 |
34 | 5 | -0.15485004E-03 | 0.31008008E-05 | -0.80011323E-04 | 0.50225397E-08 |
35 | 4 | 0.24987207 | 0.15775750E-02 | 0.84530116E-01 | -0.27712185E-04 |
36 | 3 | -6.4266483 | 0.50820490E-01 | -2.0899201 | 0.24901095E-01 |
37 | 2 | 38.099035 | 0.18692275 | 14.237681 | -0.30248143 |
38 | 1 | -78.418483 | 0.86852168E-01 | -28.218840 | 1.0332909 |
39 | 0 | 46.824353 | 0.17981083E-02 | 16.314603 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.6756E-004 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1258E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 7.7302E-004 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.3813E-003 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.9271E-004 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.4306E-003 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 7.2768E-004 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0051E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.3738E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4272E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.3707E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4279E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.9238E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.9637E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0572E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0676E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2258E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.0937E-004 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0398E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.2233E-004 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.6045E-003 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.3806E-004 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0579E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.2793E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 46630.46550 | 55956.55860 | 3.39365 | 4.07238 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 0.00000 | 0.00000 | 0.00000 | 1.33138 | 00:10:00 | 20.10000 | 1.47983E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 | |
3 | KITCHEN | Cooling | 22514.91573 | 27017.89888 | 1.38998 | 1.66797 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 34.43500 | 1.71567E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 20.10000 | 1.47983E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 73088.18 | 4.07238 | 4.07238 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 32043.47 | 1.33138 | 1.33138 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 39020.50 | 1.66797 | 1.66797 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 29290.69 | 1.21700 | 1.21700 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.07238 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.66797 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.07238 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.07238 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.07238 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.07238 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.07238 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.07238 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.66797 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.66797 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.66797 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.66797 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.66797 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.66797 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.07238 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.66797 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.07238 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.07238 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6958.06109 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.07238 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.07238 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.07238 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.68777 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.07238 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.03619 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.71492 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 101126.89000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 50563.44500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 101126.89000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 164646.89175 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 164646.89175 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.66797 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.66797 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1784.81084 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.66797 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.66797 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.66797 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10086 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.66797 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83399 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11198 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41419.76000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20709.88000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41419.76000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51107.68099 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 51107.68099 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 98232.4 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40234.2 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | N/A | 6.813 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | N/A | 6.813 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | N/A | 6.813 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 6.0795159928E-002 | 0.1934070951 | Pass | Pass | 0.1672655291 | 0.4172481149 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2383935399 | 0.7541984286 | Pass | Pass | 0.1461504612 | 0.3805683741 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2368156847 | 0.2444452142 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1268.07 | -116.9 | -1825.5 | -29.6 | 3891.57 | 3187.71 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 6.813 | 0.251 | 0.252 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.5182 | 371.75 | 3538.38 | LightsWired | LTG_SCH_DINING | 93.86 | 168.00 | 77.76 | 0.0000 | Y | 51.65 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.3127 | 139.41 | 1298.24 | LightsWired | LTG_SCH_KITCHEN | 80.88 | 168.00 | 80.41 | 0.0000 | Y | 19.60 |
Interior Lighting Total | 9.4622 | 511.15 | 4836.62 | 71.25 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.52 | AstronomicalClock | - | 48.93 | 48.93 | 1.92 | |
EXTERIOR_LIGHTS_B | 3124.83 | AstronomicalClock | - | 83.83 | 73.36 | 43.03 | |
Exterior Lighting Total | 3334.35 | 44.96 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 101126.89 | 70898.04 | 30228.85 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41419.76 | 29038.57 | 12381.19 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 98232.4 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 40234.2 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 164646.89 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 51107.68 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.55 | 1983.06 | 778.12 | 1.00 | 0.59 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.07 | 6958.06 | 1708.60 | 1.00 | 1.18 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.67 | 1784.81 | 1070.05 | 1.00 | 1.34 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 46630.47 | 55956.56 | 150.52 | 3.394 | 4.072 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 24.00 | 23.99 | 0.01108 | 35.03 | 0.01716 | 1.331 | 0.00 |
KITCHEN | 22514.92 | 27017.90 | 193.81 | 1.390 | 1.668 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 26.00 | 25.99 | 0.01028 | 34.44 | 0.01716 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 0.00 | 0.00 | 0.00 | 0.000 | 1.331 | 00:10:00 | 21.00 | 21.58 | 0.01480 | 20.10 | 0.01480 | 1.331 | 0.00 | |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 30.00 | 0.00883 | 20.10 | 0.01480 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.07 | 4.07 | 1.33 | 1.33 | 4.0724 | 4.0724 | 4.0724 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.67 | 1.67 | 1.22 | 1.22 | 1.6680 | 1.6680 | 1.6680 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 101126.890 | 70898.040 | 4.072380 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 50563.44 | 29548.89 | 2.714920 | 27.65 | 21.14 | 0.01306818 | 11.42 | 11.42 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 49.0393 | 23.99 | 0.01107856 | 59.4124 | 46576.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 164646.892 | 164646.892 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 164646.89 | 164646.89 | 4.072380 | 6.57 | 6.57 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 32.6929 | 21.58 | 0.01479830 | 91.2815 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41419.760 | 29038.565 | 1.667970 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | 20709.88 | 11318.63 | 1.111980 | 32.14 | 23.91 | 0.01529655 | 11.94 | 11.74 | 0.00850000 | 34.44 | 0.01715669 | 25.64 | 109.4446 | 25.99 | 0.01027671 | 48.9815 | 22514.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 51107.681 | 51107.681 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 51107.68 | 51107.68 | 1.667974 | 14.67 | 14.67 | 0.01318598 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 72.9629 | 30.00 | 0.00883495 | 33.4028 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 101126.890 | 70898.040 | 4.072380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.1331 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.072380 | 4.90149589 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | Sensible | 50563.44 | 29548.89 | 1.0000 | 3.26766409 | 2.714920 | 27.65 | 21.14 | 0.01306818 | 61142.8 | 11.42 | 11.42 | 0.00850000 | 32914.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50563.44 | 35.20 | 0.01715815 | 25.83 | 1.33137743 | 49.0393 | 23.98 | 0.01107856 | 23.99 | 0.01107856 | 59.4124 | 46576.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 164646.892 | 164646.892 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.072380 | 4.90149589 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 164646.89 | 164646.89 | 1.0000 | 4.90149589 | 4.072380 | 6.57 | 6.57 | 0.01479830 | 43793.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 164646.89 | 20.10 | 0.01479830 | 20.10 | 1.33137743 | 32.6929 | 0.00 | 0.01479830 | 21.58 | 0.01479830 | 91.2815 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41419.760 | 29038.565 | 1.667970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.2755 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.667974 | 2.00756492 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:30:00 | Sensible | 20709.88 | 11318.63 | 1.0000 | 1.33837355 | 1.111980 | 32.14 | 23.91 | 0.01529655 | 71468.1 | 11.94 | 11.74 | 0.00850000 | 33444.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20709.88 | 34.44 | 0.01715669 | 25.64 | 1.21700195 | 109.4446 | 25.96 | 0.01027671 | 25.99 | 0.01027671 | 48.9815 | 22514.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51107.681 | 51107.681 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.667974 | 2.00756492 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 51107.68 | 51107.68 | 1.0000 | 2.00756492 | 1.667974 | 14.67 | 14.67 | 0.01318598 | 48073.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51107.68 | 20.10 | 0.01479830 | 20.10 | 1.21700195 | 72.9629 | 0.00 | 0.00883495 | 30.00 | 0.00883495 | 33.4028 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 7187.00 | 6528.33 | 6528.33 |
KITCHEN | 7187.00 | 7187.00 | 7187.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7187.00 | 7187.00 | 7187.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 371.00 | 0.00 | 6.83 |
KITCHEN | 0.00 | 3565.00 | 0.00 | 3098.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 3565.00 | 0.00 | 3098.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.377 | 0.873 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.709 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.280 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.505 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 37582868.70 | 0.00 | 37582868.70 | 6925749.94 | 44508618.65 | 41986318.57 | 1376.81 | 7383.19 | 0.00 | 1106.93 |
KITCHEN | 36002608.63 | 0.00 | 36002608.63 | 92770.86 | 36095379.50 | 38379373.44 | 1707.29 | 6625.12 | 427.59 | 1197.79 |
Total Facility | 73585477.34 | 0.00 | 73585477.34 | 7018520.81 | 80603998.14 | 80365692.01 | 2077.70 | 7405.36 | 427.59 | 1197.80 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3317 | 0.0000 | 1.3317 | 0.2658 | 1.5975 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.2085 | 0.0000 | 1.2085 | 0.0024 | 1.2109 | 1.2170 | 643.99 | 6543.01 | 0.00 |
Total Facility | 2.5402 | 0.0000 | 2.5402 | 0.2682 | 2.8084 | 2.5484 | 643.99 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 54437564.05 | 0.00 | 54437564.05 | 41986318.57 | 1180.44 | 82.54 | 7497.02 | 1106.93 |
PSZ-AC_2:2 | 52152963.91 | 0.00 | 52152963.91 | 38379373.44 | 714.43 | 11.41 | 8034.16 | 1197.79 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9289 | 0.0000 | 1.9289 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.7506 | 0.0000 | 1.7506 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 914.15 | 0.00 | 7379.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 7977.63 | 407.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.7576 | 1.6393 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
Electricity:Building | 548.42 | 4052.25 | 01-JAN-01:10 | 30253.07 | 02-JAN-11:10 |
Electricity:Zone:DINING | 176.81 | 991.88 | 01-JAN-01:10 | 9336.09 | 02-JAN-17:20 |
Electricity:SpaceType:GENERAL | 531.56 | 3643.21 | 01-JAN-01:10 | 27887.91 | 02-JAN-11:10 |
InteriorLights:Electricity | 71.25 | 557.53 | 11-NOV-06:00 | 4035.02 | 02-JAN-17:20 |
InteriorLights:Electricity:Zone:DINING | 51.65 | 395.98 | 11-NOV-06:00 | 3065.69 | 02-JAN-17:20 |
InteriorLights:Electricity:SpaceType:GENERAL | 71.25 | 557.53 | 11-NOV-06:00 | 4035.02 | 02-JAN-17:20 |
LightsWired:InteriorLights:Electricity | 71.25 | 557.53 | 11-NOV-06:00 | 4035.02 | 02-JAN-17:20 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 51.65 | 395.98 | 11-NOV-06:00 | 3065.69 | 02-JAN-17:20 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 71.25 | 557.53 | 11-NOV-06:00 | 4035.02 | 02-JAN-17:20 |
Electricity:Zone:KITCHEN | 371.61 | 3060.37 | 01-JAN-01:10 | 21021.20 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.16 | 2489.78 | 01-JAN-01:10 | 17686.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.03 | 1122.20 | 01-JAN-01:10 | 16319.14 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 68.13 | 1238.14 | 23-JAN-23:30 | 3441.39 | 02-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 127.10 | 1382.45 | 23-JAN-04:00 | 6613.01 | 14-AUG-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 17.85 | 0.00 | 01-JAN-11:10 | 1512.14 | 05-MAY-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 33.43 | 961.45 | 23-JAN-04:10 | 1076.23 | 01-JAN-04:30 |
ElectricityPurchased:Facility | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
ElectricityPurchased:Plant | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
Cogeneration:ElectricityPurchased | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
General:Cogeneration:ElectricityPurchased | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
ElectricityNet:Plant | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
Cogeneration:ElectricityNet | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
General:Cogeneration:ElectricityNet | 1636.56 | 7622.56 | 23-JAN-03:40 | 85378.28 | 15-JUN-10:20 |
Electricity:HVAC | 916.09 | 0.00 | 01-JAN-01:40 | 52741.51 | 04-MAY-13:00 |
Fans:Electricity | 208.37 | 0.00 | 01-JAN-01:40 | 10725.94 | 10-MAY-11:10 |
General:Fans:Electricity | 208.37 | 0.00 | 01-JAN-01:40 | 10725.94 | 10-MAY-11:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 707.72 | 0.00 | 01-JAN-01:40 | 42015.57 | 04-MAY-13:00 |
General:Cooling:Electricity | 707.72 | 0.00 | 01-JAN-01:40 | 42015.57 | 04-MAY-13:00 |
ExteriorLights:Electricity | 44.96 | 0.00 | 01-JAN-06:20 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.96 | 0.00 | 01-JAN-06:20 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.37 | 0.00 | 01-JAN-01:10 | 4737.03 | 30-JAN-07:20 |
Water Heater:WaterSystems:Electricity | 75.37 | 0.00 | 01-JAN-01:10 | 4737.03 | 30-JAN-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 11-MAY-15:20 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 11-MAY-15:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 713.66 | 2803.57 | 01-JAN-01:10 | 42499.65 | 08-JAN-11:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 243.87 | 993.32 | 01-JAN-00:10 | 16781.81 | 17-JAN-08:00 |
WaterSystems:NaturalGas | 243.87 | 993.32 | 01-JAN-00:10 | 16781.81 | 17-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 243.87 | 993.32 | 01-JAN-00:10 | 16781.81 | 17-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 04-JAN-07:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4116.40 | 4346.24 | 23-JAN-03:40 | 218791.39 | 10-JUN-18:10 |
EnergyTransfer:Building | 1014.95 | 2173.12 | 23-JAN-03:40 | 56181.38 | 04-JAN-13:00 |
EnergyTransfer:Zone:KITCHEN | 507.21 | 2173.12 | 23-JAN-03:40 | 24664.61 | 22-FEB-12:00 |
Refrigeration:EnergyTransfer | 169.66 | 3907.83 | 23-JAN-23:10 | 7834.84 | 01-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 84.83 | 1953.92 | 23-JAN-23:10 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 84.83 | 1953.92 | 23-JAN-23:10 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 84.83 | 1953.92 | 23-JAN-23:10 | 3917.42 | 01-JAN-11:40 |
EnergyTransfer:Plant | 246.12 | 2171.73 | 23-JAN-04:00 | 13288.92 | 11-JAN-19:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.77 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.05 | 1894.36 | 23-JAN-04:10 | 2238.70 | 01-JAN-04:30 |
EnergyTransfer:Zone:DINING | 507.74 | 0.00 | 01-JAN-01:40 | 35735.56 | 05-MAY-12:00 |
Heating:EnergyTransfer | 0.05 | 0.00 | 01-JAN-00:10 | 618.89 | 15-AUG-04:10 |
Heating:EnergyTransfer:Zone:DINING | 0.05 | 0.00 | 01-JAN-00:10 | 618.89 | 15-AUG-04:10 |
General:Heating:EnergyTransfer | 0.05 | 0.00 | 01-JAN-00:10 | 618.89 | 15-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:DINING | 0.05 | 0.00 | 01-JAN-00:10 | 618.89 | 15-AUG-04:10 |
Cooling:EnergyTransfer | 930.07 | 0.00 | 01-JAN-01:40 | 53517.40 | 04-JAN-13:00 |
Cooling:EnergyTransfer:Zone:DINING | 507.68 | 0.00 | 01-JAN-01:40 | 35735.56 | 05-MAY-12:00 |
General:Cooling:EnergyTransfer | 930.07 | 0.00 | 01-JAN-01:40 | 53517.40 | 04-JAN-13:00 |
General:Cooling:EnergyTransfer:Zone:DINING | 507.68 | 0.00 | 01-JAN-01:40 | 35735.56 | 05-MAY-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 422.38 | 0.00 | 01-JAN-01:40 | 20880.67 | 10-MAY-19:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 422.38 | 0.00 | 01-JAN-01:40 | 20880.67 | 10-MAY-19:50 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 161.29 | 0.00 | 01-JAN-01:10 | 10322.97 | 13-JAN-19:40 |
PlantLoopHeatingDemand:Plant | 161.29 | 0.00 | 01-JAN-01:10 | 10322.97 | 13-JAN-19:40 |
WaterSystems:PlantLoopHeatingDemand | 161.29 | 0.00 | 01-JAN-01:10 | 10322.97 | 13-JAN-19:40 |
General:WaterSystems:PlantLoopHeatingDemand | 161.29 | 0.00 | 01-JAN-01:10 | 10322.97 | 13-JAN-19:40 |
EnergyTransfer:HVAC | 2855.33 | 0.00 | 01-JAN-01:40 | 156248.09 | 29-MAY-03:10 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2855.33 | 0.00 | 01-JAN-01:40 | 156248.09 | 29-MAY-03:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 161.29 | 0.00 | 01-JAN-01:10 | 10322.97 | 13-JAN-19:40 |
WaterUse:WaterSystems:EnergyTransfer | 161.29 | 0.00 | 01-JAN-01:10 | 10322.97 | 13-JAN-19:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.053 | -507.687 | 0.000 | 0.000 | 206.342 | 51.650 | 93.867 | 57.105 | 0.000 | 39.731 | 63.201 | 0.000 | -3.937 | 0.000 | -0.325 | 0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -422.377 | 0.000 | 0.000 | 4.297 | 19.596 | 297.703 | 0.000 | 0.000 | 0.153 | 100.722 | 0.000 | 0.000 | 0.000 | -0.094 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.489 | 44.161 | 0.000 | 0.000 | 0.000 | -51.650 | -0.000 |
Total Facility | 0.000 | 0.000 | 0.053 | -930.064 | 0.000 | 0.000 | 210.638 | 71.246 | 391.570 | 57.105 | 0.000 | 47.374 | 208.084 | 0.000 | -3.937 | 0.000 | -52.069 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 05-MAY-12:00 | 0.00 | 0.00 | 0.00 | -35737.04 | 0.00 | 0.00 | 15583.55 | 2237.95 | 4883.68 | 4229.58 | 0.00 | 7654.05 | 1148.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 24-JAN-04:21 | 0.00 | 0.00 | 0.00 | -34204.25 | 0.00 | 0.00 | 0.00 | 161.55 | 3815.73 | 0.00 | 0.00 | 0.00 | 30275.51 | 0.00 | -0.00 | 0.00 | -48.54 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JAN-04:21 | 0.00 | 0.00 | 0.00 | -54274.42 | 0.00 | 0.00 | 0.00 | 672.49 | 4717.49 | 0.00 | 0.00 | 538.89 | 49803.18 | 0.00 | -1362.32 | 0.00 | -95.32 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 15-AUG-04:03 | 0.00 | 0.00 | 4332.51 | 0.00 | 0.00 | 0.00 | 869.74 | 681.24 | 2170.53 | 0.00 | 0.00 | 7.19 | 0.00 | 0.00 | -197.72 | 0.00 | 0.00 | -7863.48 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-AUG-04:03 | -18002.88 | 18002.88 | 4332.51 | -18002.88 | 0.00 | 0.00 | 876.07 | 896.65 | 9424.42 | 0.00 | 0.00 | 455.95 | 2219.38 | 0.00 | -197.72 | 0.00 | -4.38 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.0724 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.0724 | 0.3269 | 1.0000 | Not calculated | 1.3314 | 0.3269 | ||
PSZ-AC_2:2 | 1.6680 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6680 | 0.1095 | 1.0000 | Not calculated | 0.1826 | 0.1095 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.0724 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.0724 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3269 | ||
PSZ-AC_2:2 | 1.6680 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6680 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1095 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.0724 | 4.0724 | 4.0724 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6680 | 1.6680 | 1.6680 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.0724 | 4.0724 | 4.0724 | 4.0724 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6680 | 1.6680 | 1.6680 | 1.6680 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.0724 | 4.0724 | 4.0724 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6680 | 1.6680 | 1.6680 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.0724 | 4.0724 | 4.0724 | 4.0724 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6680 | 1.6680 | 1.6680 | 1.6680 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 511.15 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 3098.67 |
Number of hours not met | 3098.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 707.72 | 42015.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 71.25 | 4035.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.96 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.19 | 23313.05 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 208.37 | 10725.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.37 | 4737.03 | 243.87 | 16781.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.85 | 1512.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.43 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 528.45 | 1636.56 |
Natural Gas | 469.79 | 713.66 |
Additional | 0.00 | 0.00 |
Total | 998.24 | 2350.22 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 139.38 |
Space Heating | 0.00 |
Space Cooling | 1384.56 |
Fans (All) | 407.65 |
Service Water Heating | 147.45 |
Receptacle Equipment | 900.54 |
Miscellaneous (All) | 3201.71 |
Subtotal | 3201.71 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 477.10 |
Miscellaneous (All) | 1396.18 |
Subtotal | 1396.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.03 |
Space Heating | 0.00 |
Space Cooling | 30.11 |
Fans (All) | 8.87 |
Service Water Heating | 13.58 |
Receptacle Equipment | 39.58 |
Miscellaneous | 4.83 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4894. | 8760. |
LTG_SCH_KITCHEN | 4218. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 4743.33 | 3413.50 | 603.00 | 0.17 | 0.00 |
ATTIC | 3661.50 | 989.67 | 883.00 | 1173.17 | 2052.67 |
Min | 3661.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3413.50 | 883.00 | 1173.17 | 2052.67 |
Average | 5721.61 | 1467.72 | 495.33 | 391.11 | 684.22 |
Sum | 17164.83 | 4403.17 | 1486.00 | 1173.33 | 2052.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8142.17 | 9173.67 | 1916.67 | 0.50 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 9173.67 | 1916.67 | 0.50 | 0.00 |
Average | 277454.72 | 3057.89 | 638.89 | 0.17 | 0.00 |
Sum | 832364.17 | 9173.67 | 1916.67 | 0.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 677.33 | 8082.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 9.17 | 8549.67 | 201.00 | 0.17 | 0.00 |
ATTIC | 437.17 | 4254.67 | 923.00 | 608.67 | 2536.50 |
Min | 9.17 | 4254.67 | 0.00 | 0.00 | 0.00 |
Max | 677.33 | 8549.67 | 923.00 | 608.67 | 2536.50 |
Average | 374.56 | 6962.33 | 374.67 | 202.94 | 845.50 |
Sum | 1123.67 | 20887.00 | 1124.00 | 608.83 | 2536.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 60025.00 | 764197.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 18542.83 | 689.67 | 0.50 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 60025.00 | 764197.00 | 689.67 | 0.50 | 0.00 |
Average | 20008.33 | 260913.28 | 229.89 | 0.17 | 0.00 |
Sum | 60025.00 | 782739.83 | 689.67 | 0.50 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:50
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420621E+11 | 35032.55 | 04-JAN-13:00 | 34.10 | 23.67 | 0.153163E+11 | 14050.55 | 21-JAN-19:00 | 26.00 | 22.75 |
February | 0.395337E+11 | 34402.55 | 15-FEB-13:00 | 34.00 | 25.91 | 0.138707E+11 | 14050.75 | 04-FEB-19:19 | 34.00 | 25.91 |
March | 0.446864E+11 | 34391.44 | 12-MAR-00:04 | 25.90 | 23.18 | 0.155050E+11 | 14050.67 | 25-MAR-18:00 | 28.20 | 24.64 |
April | 0.440200E+11 | 34309.20 | 02-APR-00:04 | 27.47 | 25.54 | 0.148897E+11 | 14051.08 | 22-APR-18:30 | 25.95 | 24.31 |
May | 0.451299E+11 | 35738.57 | 05-MAY-12:00 | 37.00 | 25.95 | 0.154252E+11 | 14050.69 | 20-MAY-18:00 | 30.40 | 25.86 |
June | 0.443208E+11 | 33659.46 | 12-JUN-17:22 | 33.00 | 27.06 | 0.150246E+11 | 14075.42 | 10-JUN-18:19 | 33.00 | 27.06 |
July | 0.417302E+11 | 33915.84 | 15-JUL-00:04 | 26.90 | 24.09 | 0.153088E+11 | 14050.77 | 01-JUL-18:40 | 26.90 | 24.09 |
August | 0.423461E+11 | 33093.14 | 31-AUG-00:05 | 24.05 | 23.87 | 0.155253E+11 | 14051.91 | 19-AUG-18:10 | 24.05 | 23.87 |
September | 0.414619E+11 | 34203.17 | 14-SEP-00:04 | 27.77 | 25.73 | 0.148903E+11 | 14050.88 | 30-SEP-18:30 | 26.85 | 24.76 |
October | 0.409339E+11 | 32706.03 | 01-OCT-00:04 | 26.27 | 25.35 | 0.153164E+11 | 14050.93 | 21-OCT-18:49 | 26.67 | 24.86 |
November | 0.401189E+11 | 33303.33 | 24-NOV-01:05 | 24.17 | 22.00 | 0.148108E+11 | 14052.37 | 25-NOV-19:10 | 23.33 | 21.87 |
December | 0.413410E+11 | 33782.97 | 08-DEC-13:00 | 32.00 | 23.25 | 0.153084E+11 | 14051.23 | 09-DEC-19:49 | 26.02 | 25.07 |
Annual Sum or Average | 0.507685E+12 | 0.181192E+12 | ||||||||
Minimum of Months | 0.395337E+11 | 32706.03 | 24.05 | 22.00 | 0.138707E+11 | 14050.55 | 23.33 | 21.87 | ||
Maximum of Months | 0.451299E+11 | 35738.57 | 37.00 | 27.06 | 0.155253E+11 | 14075.42 | 34.00 | 27.06 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357756E+11 | 34218.03 | 24-JAN-04:21 | 19.10 | 17.42 | 0.105996E+11 | 6959.16 | 10-JAN-11:00 | 19.10 | 17.42 |
February | 0.325768E+11 | 30380.20 | 10-FEB-01:03 | 24.82 | 17.41 | 0.957977E+10 | 6963.18 | 15-FEB-11:00 | 31.00 | 25.03 |
March | 0.363830E+11 | 28633.04 | 03-MAR-05:01 | 22.83 | 20.19 | 0.106145E+11 | 6974.50 | 28-MAR-10:50 | 33.18 | 25.53 |
April | 0.350540E+11 | 21931.33 | 04-APR-04:02 | 25.97 | 23.85 | 0.103058E+11 | 6996.93 | 11-APR-10:00 | 33.00 | 26.61 |
May | 0.356580E+11 | 21775.27 | 26-MAY-04:02 | 24.00 | 23.90 | 0.106896E+11 | 7028.54 | 30-MAY-10:50 | 33.07 | 27.73 |
June | 0.348631E+11 | 23782.98 | 27-JUN-04:01 | 23.17 | 23.17 | 0.103542E+11 | 7043.64 | 15-JUN-10:50 | 23.17 | 23.17 |
July | 0.367955E+11 | 22992.07 | 20-JUL-04:02 | 23.73 | 22.60 | 0.106194E+11 | 6979.93 | 03-JUL-10:00 | 23.73 | 22.60 |
August | 0.354590E+11 | 23084.73 | 20-AUG-04:02 | 23.00 | 22.40 | 0.106720E+11 | 7033.13 | 15-AUG-10:50 | 23.00 | 22.40 |
September | 0.345673E+11 | 23249.08 | 19-SEP-04:02 | 23.08 | 22.98 | 0.103118E+11 | 7013.00 | 06-SEP-10:50 | 23.08 | 22.98 |
October | 0.352954E+11 | 23175.52 | 27-OCT-04:02 | 23.83 | 22.88 | 0.106354E+11 | 7000.06 | 16-OCT-10:50 | 23.83 | 22.88 |
November | 0.343510E+11 | 27674.59 | 25-NOV-04:22 | 22.60 | 19.59 | 0.102774E+11 | 6987.72 | 14-NOV-11:50 | 22.60 | 19.59 |
December | 0.356034E+11 | 30724.23 | 15-DEC-04:21 | 20.70 | 18.95 | 0.106033E+11 | 6971.25 | 11-DEC-11:00 | 20.70 | 18.95 |
Annual Sum or Average | 0.422382E+12 | 0.125263E+12 | ||||||||
Minimum of Months | 0.325768E+11 | 21775.27 | 19.10 | 17.41 | 0.957977E+10 | 6959.16 | 19.10 | 17.42 | ||
Maximum of Months | 0.367955E+11 | 34218.03 | 25.97 | 23.90 | 0.106896E+11 | 7043.64 | 33.18 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.00 | 0.00 | 01-APR-00:01 | 27.53 | 25.10 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 28.62 | 26.40 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 24.05 | 23.91 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.40 | 24.33 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.63 | 24.75 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.53 | 25.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.27 | 25.35 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 25.22 | 24.37 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2220482.90 | 2425.46 | 03-JAN-05:03 | 24.93 |
February | 3513018.02 | 2457.45 | 21-FEB-05:03 | 25.00 |
March | 4680895.25 | 2931.54 | 14-MAR-04:03 | 25.92 |
April | 4535307.99 | 2712.52 | 04-APR-04:03 | 25.97 |
May | 6630865.43 | 4125.75 | 02-MAY-04:03 | 27.08 |
June | 6867940.66 | 4233.39 | 06-JUN-04:03 | 26.83 |
July | 5822807.78 | 3540.81 | 15-JUL-04:03 | 25.25 |
August | 5339573.60 | 4332.22 | 15-AUG-04:03 | 26.17 |
September | 5086574.46 | 3861.28 | 05-SEP-04:03 | 26.75 |
October | 4226464.78 | 2495.06 | 17-OCT-04:03 | 25.00 |
November | 3589601.39 | 3636.87 | 24-NOV-05:03 | 24.42 |
December | 888817.62 | 1437.40 | 09-DEC-05:04 | 24.00 |
Annual Sum or Average | 53402349.89 | |||
Minimum of Months | 888817.62 | 1437.40 | 24.00 | |
Maximum of Months | 6867940.66 | 4332.22 | 27.08 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:01 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:01 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.442209E+10 | 3065.69 | 02-JAN-17:19 | 0.106297E+11 | 6993.92 | 01-JAN-11:09 |
February | 0.400129E+10 | 3065.69 | 01-FEB-17:40 | 0.960102E+10 | 6993.92 | 01-FEB-11:09 |
March | 0.442418E+10 | 3065.69 | 01-MAR-17:30 | 0.106297E+11 | 6993.92 | 01-MAR-11:09 |
April | 0.419734E+10 | 3065.69 | 01-APR-18:10 | 0.102868E+11 | 6993.92 | 01-APR-10:09 |
May | 0.436153E+10 | 3065.69 | 01-MAY-18:10 | 0.106297E+11 | 6993.92 | 01-MAY-10:09 |
June | 0.422931E+10 | 3065.69 | 01-JUN-18:10 | 0.102868E+11 | 6993.92 | 01-JUN-10:09 |
July | 0.430781E+10 | 3065.69 | 01-JUL-18:19 | 0.106297E+11 | 6993.92 | 01-JUL-10:09 |
August | 0.438853E+10 | 3065.69 | 01-AUG-18:19 | 0.106297E+11 | 6993.92 | 01-AUG-10:09 |
September | 0.424034E+10 | 3065.69 | 01-SEP-17:00 | 0.102868E+11 | 6993.92 | 01-SEP-10:09 |
October | 0.437261E+10 | 3065.69 | 02-OCT-17:49 | 0.106297E+11 | 6993.92 | 01-OCT-10:09 |
November | 0.427813E+10 | 3065.69 | 01-NOV-17:30 | 0.102868E+11 | 6993.92 | 01-NOV-10:09 |
December | 0.442685E+10 | 3065.69 | 01-DEC-17:30 | 0.106297E+11 | 6993.92 | 01-DEC-11:09 |
Annual Sum or Average | 0.516500E+11 | 0.125156E+12 | ||||
Minimum of Months | 0.400129E+10 | 3065.69 | 0.960102E+10 | 6993.92 | ||
Maximum of Months | 0.442685E+10 | 3065.69 | 0.106297E+11 | 6993.92 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165581E+10 | 969.33 | 02-JAN-10:09 | 0.284656E+11 | 17686.72 | 01-JAN-11:09 |
February | 0.149975E+10 | 969.33 | 01-FEB-10:09 | 0.257108E+11 | 17686.72 | 01-FEB-11:09 |
March | 0.168217E+10 | 969.33 | 01-MAR-10:09 | 0.284657E+11 | 17686.72 | 01-MAR-11:09 |
April | 0.160889E+10 | 969.33 | 01-APR-16:10 | 0.275474E+11 | 17686.72 | 01-APR-10:09 |
May | 0.166899E+10 | 969.33 | 01-MAY-09:09 | 0.284656E+11 | 17686.72 | 01-MAY-10:09 |
June | 0.162595E+10 | 969.33 | 01-JUN-09:09 | 0.275474E+11 | 17686.72 | 01-JUN-10:09 |
July | 0.165212E+10 | 969.33 | 01-JUL-16:10 | 0.284656E+11 | 17686.72 | 01-JUL-10:09 |
August | 0.168217E+10 | 969.33 | 01-AUG-09:09 | 0.284657E+11 | 17686.72 | 01-AUG-10:09 |
September | 0.160928E+10 | 969.33 | 01-SEP-09:09 | 0.275474E+11 | 17686.72 | 01-SEP-10:09 |
October | 0.165561E+10 | 969.33 | 02-OCT-09:09 | 0.284656E+11 | 17686.72 | 01-OCT-10:09 |
November | 0.160288E+10 | 969.33 | 01-NOV-09:09 | 0.275473E+11 | 17686.72 | 01-NOV-10:09 |
December | 0.165232E+10 | 969.33 | 01-DEC-10:09 | 0.284656E+11 | 17686.72 | 01-DEC-11:09 |
Annual Sum or Average | 0.195960E+11 | 0.335159E+12 | ||||
Minimum of Months | 0.149975E+10 | 969.33 | 0.257108E+11 | 17686.72 | ||
Maximum of Months | 0.168217E+10 | 969.33 | 0.284657E+11 | 17686.72 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.442209E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281320E+10 | 0.110766E+09 |
February | 0.272721E+11 | 0.400129E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311393E+10 | 31318358.05 |
March | 0.305458E+11 | 0.442418E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397157E+10 | 3123431.71 |
April | 0.292871E+11 | 0.419734E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429607E+10 | 316245.31 |
May | 0.303219E+11 | 0.436153E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436523E+10 | 4819490.43 |
June | 0.295292E+11 | 0.422931E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416175E+10 | 7196908.13 |
July | 0.300798E+11 | 0.430781E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298329E+10 | 7165271.14 |
August | 0.305458E+11 | 0.438853E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319815E+10 | 10721761.93 |
September | 0.292871E+11 | 0.424034E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308123E+10 | 9168797.54 |
October | 0.300980E+11 | 0.437261E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266505E+10 | 8872544.77 |
November | 0.290996E+11 | 0.427813E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257462E+10 | 39479080.28 |
December | 0.300798E+11 | 0.442685E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250717E+10 | 92399403.56 |
Annual Sum or Average | 0.356244E+12 | 0.516500E+11 | 0.125156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397312E+11 | 0.325347E+09 |
Minimum of Months | 0.272721E+11 | 0.400129E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250717E+10 | 316245.31 |
Maximum of Months | 0.305458E+11 | 0.442685E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436523E+10 | 0.110766E+09 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.165581E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 10492930.75 | 14147911.29 |
February | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 14789849.37 | 4534489.23 |
March | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 25786686.93 | 8506567.83 |
April | 0.786997E+09 | 0.160889E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 21498724.76 | 3157470.35 |
May | 0.814802E+09 | 0.166899E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 17712138.03 | 7021564.98 |
June | 0.793501E+09 | 0.162595E+10 | 0.227469E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 14201002.98 | 6461502.71 |
July | 0.808298E+09 | 0.165212E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12869204.96 | 3848162.51 |
August | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8635120.43 | 9790915.49 |
September | 0.786997E+09 | 0.160928E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 7520213.69 | 4958008.17 |
October | 0.808786E+09 | 0.165561E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 6047462.89 | 6894105.39 |
November | 0.781956E+09 | 0.160288E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 6216502.42 | 8330861.83 |
December | 0.808298E+09 | 0.165232E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 7337503.54 | 16031541.48 |
Annual Sum or Average | 0.957291E+10 | 0.195960E+11 | 0.276753E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.153107E+09 | 93683101.24 |
Minimum of Months | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 6047462.89 | 3157470.35 |
Maximum of Months | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 25786686.93 | 16031541.48 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675336E+09 | 0.440390E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879697E+09 | 0.434932E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703654E+09 | 0.496456E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660863E+09 | 0.500947E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541958E+09 | 0.415599E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423944E+09 | 0.445585E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600684E+09 | 0.438427E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548676E+09 | 0.384800E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554179E+09 | 0.427484E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561246E+09 | 0.374718E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655107E+09 | 0.388338E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683874E+09 | 0.417330E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748922E+10 | 0.516501E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423944E+09 | 0.374718E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879697E+09 | 0.500947E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3065.69 | 02-JAN-17:19 | 6993.92 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6017.02 | 04-JAN-13:00 | 1741.52 | 24-JAN-08:52 |
February | 30255.31 | 04-FEB-19:10 | 3065.69 | 01-FEB-17:40 | 6993.92 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6045.30 | 28-FEB-13:00 | 1287.76 | 21-FEB-10:00 |
March | 30255.31 | 04-MAR-19:10 | 3065.69 | 01-MAR-17:30 | 6993.92 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6526.24 | 21-MAR-13:00 | 263.32 | 15-MAR-06:10 |
April | 30255.31 | 01-APR-18:10 | 3065.69 | 01-APR-18:10 | 6993.92 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.71 | 13-APR-11:55 | 298.89 | 14-APR-16:00 |
May | 30255.31 | 06-MAY-18:10 | 3065.69 | 01-MAY-18:10 | 6993.92 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7654.05 | 05-MAY-12:00 | 1228.39 | 10-MAY-19:53 |
June | 30255.31 | 03-JUN-18:10 | 3065.69 | 01-JUN-18:10 | 6993.92 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6067.60 | 15-JUN-11:53 | 546.57 | 25-JUN-20:00 |
July | 30255.31 | 01-JUL-18:10 | 3065.69 | 01-JUL-18:19 | 6993.92 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5207.44 | 15-JUL-18:03 | 617.41 | 19-JUL-19:00 |
August | 30255.31 | 05-AUG-18:10 | 3065.69 | 01-AUG-18:19 | 6993.92 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5602.91 | 15-AUG-11:05 | 769.10 | 20-AUG-11:10 |
September | 30255.31 | 02-SEP-18:10 | 3065.69 | 01-SEP-17:00 | 6993.92 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5359.32 | 12-SEP-12:00 | 548.22 | 16-SEP-20:00 |
October | 30255.31 | 07-OCT-18:10 | 3065.69 | 02-OCT-17:49 | 6993.92 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5084.39 | 04-OCT-12:00 | 563.47 | 30-OCT-17:10 |
November | 30255.31 | 04-NOV-18:10 | 3065.69 | 01-NOV-17:30 | 6993.92 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4708.85 | 10-NOV-12:10 | 1180.45 | 25-NOV-07:10 |
December | 30255.31 | 02-DEC-19:10 | 3065.69 | 01-DEC-17:30 | 6993.92 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4878.37 | 26-DEC-13:00 | 1813.55 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4708.85 | 263.32 | |||||
Maximum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 7654.05 | 1813.55 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 969.33 | 02-JAN-10:09 | 14422.89 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 37.84 | 04-JAN-13:00 | 589.13 | 07-JAN-05:00 |
February | 813.01 | 04-FEB-19:10 | 969.33 | 01-FEB-10:09 | 14422.89 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 48.84 | 28-FEB-14:53 | 66.64 | 11-FEB-01:40 |
March | 813.01 | 04-MAR-19:10 | 969.33 | 01-MAR-10:09 | 14422.89 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 63.89 | 19-MAR-15:52 | 138.47 | 03-MAR-05:00 |
April | 813.01 | 01-APR-18:10 | 969.33 | 01-APR-16:10 | 14422.89 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 40.03 | 30-APR-24:00 | 81.07 | 01-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 969.33 | 01-MAY-09:09 | 14422.89 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 57.69 | 05-MAY-24:00 | 142.84 | 17-MAY-02:00 |
June | 813.01 | 03-JUN-18:10 | 969.33 | 01-JUN-09:09 | 14422.89 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 37.55 | 11-JUN-00:50 | 103.96 | 10-JUN-02:00 |
July | 813.01 | 01-JUL-18:10 | 969.33 | 01-JUL-16:10 | 14422.89 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 36.94 | 04-JUL-14:00 | 92.74 | 28-JUL-01:20 |
August | 813.01 | 05-AUG-18:10 | 969.33 | 01-AUG-09:09 | 14422.89 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 35.86 | 02-AUG-03:51 | 222.26 | 04-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 969.33 | 01-SEP-09:09 | 14422.89 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.94 | 10-SEP-14:52 | 108.24 | 22-SEP-01:20 |
October | 813.01 | 07-OCT-18:10 | 969.33 | 02-OCT-09:09 | 14422.89 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 30.92 | 29-OCT-13:20 | 94.54 | 14-OCT-01:20 |
November | 813.01 | 04-NOV-18:10 | 969.33 | 01-NOV-09:09 | 14422.89 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 19.94 | 10-NOV-11:10 | 84.88 | 25-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 969.33 | 01-DEC-10:09 | 14422.89 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 27.51 | 09-DEC-13:55 | 149.96 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 19.94 | 66.64 | ||||||
Maximum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 63.89 | 589.13 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.89 | 19-JAN-04:51 | 7027.72 | 16-JAN-12:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.53 | 28-FEB-06:20 | 7787.00 | 24-FEB-13:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1947.51 | 03-MAR-14:50 | 7623.69 | 08-MAR-13:45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1252.95 | 09-APR-14:00 | 7642.12 | 26-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.25 | 28-MAY-06:32 | 8659.88 | 01-MAY-12:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.74 | 23-JUN-03:51 | 6938.44 | 21-JUN-14:23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.62 | 19-JUL-01:20 | 7242.63 | 19-JUL-13:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.63 | 02-AUG-03:51 | 7247.89 | 17-AUG-12:42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.50 | 12-SEP-03:51 | 7891.89 | 11-SEP-13:42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1521.75 | 20-OCT-00:55 | 7174.62 | 07-OCT-12:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.40 | 07-NOV-04:30 | 6702.62 | 02-NOV-13:20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.88 | 25-DEC-06:35 | 6671.92 | 02-DEC-12:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.40 | 6671.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1947.51 | 8659.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35032.55 | 04-JAN-13:00 | 26893.61 | 2237.95 | 6511.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6017.02 | 0.00 |
February | 34402.55 | 15-FEB-13:00 | 26893.61 | 2237.95 | 6511.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5922.51 | 0.00 |
March | 34391.44 | 12-MAR-00:04 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 26.53 | 0.00 |
April | 34309.20 | 02-APR-00:04 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 62.29 | 0.00 |
May | 35738.57 | 05-MAY-12:00 | 53787.21 | 4475.90 | 13023.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7654.05 | 0.00 |
June | 33659.46 | 12-JUN-17:22 | 134468.03 | 11189.76 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 5321.70 | 0.00 |
July | 33915.84 | 15-JUL-00:04 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 53.89 | 0.00 |
August | 33093.14 | 31-AUG-00:05 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 34203.17 | 14-SEP-00:04 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 58.24 | 0.00 |
October | 32706.03 | 01-OCT-00:04 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 | 0.00 |
November | 33303.33 | 24-NOV-01:05 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
December | 33782.97 | 08-DEC-13:00 | 26893.61 | 2237.95 | 6511.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4762.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32706.03 | 0.00 | 2237.95 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35738.57 | 134468.03 | 11189.76 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 7654.05 | 0.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34218.03 | 24-JAN-04:21 | 0.00 | 1292.42 | 28895.80 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 48.54 |
February | 30380.20 | 10-FEB-01:03 | 0.00 | 1615.53 | 22653.40 | 5430.75 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 |
March | 28633.04 | 03-MAR-05:01 | 316.17 | 1507.82 | 47388.46 | 22809.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
April | 21931.33 | 04-APR-04:02 | 271.00 | 1292.42 | 40618.68 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 |
May | 21775.27 | 26-MAY-04:02 | 271.00 | 1292.42 | 40618.68 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 |
June | 23782.98 | 27-JUN-04:01 | 316.17 | 1507.82 | 47388.46 | 22809.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
July | 22992.07 | 20-JUL-04:02 | 271.00 | 1292.42 | 40618.68 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
August | 23084.73 | 20-AUG-04:02 | 0.00 | 969.32 | 40524.74 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
September | 23249.08 | 19-SEP-04:02 | 271.00 | 1292.42 | 40618.68 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
October | 23175.52 | 27-OCT-04:02 | 271.00 | 1292.42 | 40618.68 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
November | 27674.59 | 25-NOV-04:22 | 0.00 | 969.32 | 21671.85 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 |
December | 30724.23 | 15-DEC-04:21 | 0.00 | 1130.87 | 25283.83 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21775.27 | 0.00 | 969.32 | 21671.85 | 5430.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | |
Maximum of Months | 34218.03 | 316.17 | 1615.53 | 47388.46 | 22809.15 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.43 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.93 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.40 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.85 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.40 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.97 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.17 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.51 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.77 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.24 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.10 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.51 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.124117E+12 | 77248.71 | 12-JAN-12:00 | 0.613145E+11 | 42499.65 | 08-JAN-11:09 |
February | 0.116259E+12 | 80040.20 | 15-FEB-12:00 | 0.553072E+11 | 42478.08 | 04-FEB-11:20 |
March | 0.134031E+12 | 77907.64 | 28-MAR-11:00 | 0.611093E+11 | 42451.62 | 04-MAR-11:20 |
April | 0.141546E+12 | 81541.80 | 10-APR-18:10 | 0.586240E+11 | 42405.38 | 01-APR-10:20 |
May | 0.155385E+12 | 83394.50 | 20-MAY-10:09 | 0.602129E+11 | 42327.94 | 14-MAY-10:09 |
June | 0.150010E+12 | 85378.28 | 15-JUN-10:20 | 0.580938E+11 | 42287.88 | 04-JUN-10:30 |
July | 0.134750E+12 | 77852.56 | 15-JUL-18:19 | 0.597930E+11 | 42270.25 | 02-JUL-10:09 |
August | 0.146742E+12 | 83852.06 | 15-AUG-10:00 | 0.600905E+11 | 42293.55 | 27-AUG-10:20 |
September | 0.139930E+12 | 85101.37 | 30-SEP-10:00 | 0.583201E+11 | 42354.49 | 30-SEP-10:30 |
October | 0.138914E+12 | 80619.00 | 04-OCT-11:00 | 0.605811E+11 | 42406.63 | 28-OCT-10:20 |
November | 0.129148E+12 | 80758.86 | 17-NOV-18:00 | 0.590013E+11 | 42446.09 | 23-NOV-11:09 |
December | 0.125733E+12 | 79072.43 | 29-DEC-18:00 | 0.612129E+11 | 42484.13 | 24-DEC-11:09 |
Annual Sum or Average | 0.163656E+13 | 0.713661E+12 | ||||
Minimum of Months | 0.116259E+12 | 77248.71 | 0.553072E+11 | 42270.25 | ||
Maximum of Months | 0.155385E+12 | 85378.28 | 0.613145E+11 | 42499.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.607790E+10 | 0.403342E+10 | 0.390952E+11 | 0.00 | 0.153677E+11 | 37879553.69 | 0.00 | 0.474273E+11 | 0.00 | 0.00 | 0.00 | 0.638052E+10 | 0.00 |
February | 0.550104E+10 | 0.357719E+10 | 0.353119E+11 | 0.00 | 0.144059E+11 | 34213790.43 | 0.00 | 0.464954E+11 | 0.00 | 0.00 | 0.00 | 0.577436E+10 | 0.00 |
March | 0.610636E+10 | 0.381935E+10 | 0.390954E+11 | 0.00 | 0.166342E+11 | 37879553.69 | 0.00 | 0.561571E+11 | 0.00 | 0.00 | 0.00 | 0.644865E+10 | 0.00 |
April | 0.580623E+10 | 0.359392E+10 | 0.378342E+11 | 0.00 | 0.181454E+11 | 36657632.61 | 0.00 | 0.643182E+11 | 0.00 | 0.00 | 0.00 | 0.619142E+10 | 0.00 |
May | 0.603052E+10 | 0.363930E+10 | 0.390953E+11 | 0.00 | 0.205626E+11 | 37879553.69 | 0.00 | 0.737323E+11 | 0.00 | 0.00 | 0.00 | 0.641074E+10 | 0.00 |
June | 0.585527E+10 | 0.347388E+10 | 0.378342E+11 | 0.00 | 0.198602E+11 | 36657632.61 | 0.00 | 0.710237E+11 | 0.00 | 0.00 | 0.00 | 0.623180E+10 | 0.00 |
July | 0.595993E+10 | 0.362329E+10 | 0.390952E+11 | 0.00 | 0.168709E+11 | 37879553.69 | 0.00 | 0.569907E+11 | 0.00 | 0.00 | 0.00 | 0.637133E+10 | 0.00 |
August | 0.607070E+10 | 0.367731E+10 | 0.390954E+11 | 0.00 | 0.190493E+11 | 37879553.69 | 0.00 | 0.665100E+11 | 0.00 | 0.00 | 0.00 | 0.644706E+10 | 0.00 |
September | 0.584962E+10 | 0.366594E+10 | 0.378342E+11 | 0.00 | 0.180112E+11 | 36657632.61 | 0.00 | 0.626989E+11 | 0.00 | 0.00 | 0.00 | 0.619243E+10 | 0.00 |
October | 0.602823E+10 | 0.390338E+10 | 0.390952E+11 | 0.00 | 0.176308E+11 | 37879553.69 | 0.00 | 0.600516E+11 | 0.00 | 0.00 | 0.00 | 0.637714E+10 | 0.00 |
November | 0.588101E+10 | 0.388527E+10 | 0.378341E+11 | 0.00 | 0.162042E+11 | 36657632.61 | 0.00 | 0.535710E+11 | 0.00 | 0.00 | 0.00 | 0.617402E+10 | 0.00 |
December | 0.607917E+10 | 0.406411E+10 | 0.390952E+11 | 0.00 | 0.156314E+11 | 37879553.69 | 0.00 | 0.487439E+11 | 0.00 | 0.00 | 0.00 | 0.637228E+10 | 0.00 |
Annual Sum or Average | 0.712460E+11 | 0.449564E+11 | 0.460316E+12 | 0.00 | 0.208374E+12 | 0.446001E+09 | 0.00 | 0.707720E+12 | 0.00 | 0.00 | 0.00 | 0.753718E+11 | 0.00 |
Minimum of Months | 0.550104E+10 | 0.347388E+10 | 0.353119E+11 | 0.00 | 0.144059E+11 | 34213790.43 | 0.00 | 0.464954E+11 | 0.00 | 0.00 | 0.00 | 0.577436E+10 | 0.00 |
Maximum of Months | 0.610636E+10 | 0.406411E+10 | 0.390954E+11 | 0.00 | 0.205626E+11 | 37879553.69 | 0.00 | 0.737323E+11 | 0.00 | 0.00 | 0.00 | 0.644865E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.214147E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.192688E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.212096E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.200114E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.203132E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.194811E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.198933E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.201908E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.197074E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.206814E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.203886E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.213132E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.00 | 0.00 | 0.243874E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.192688E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.214147E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4035.02 | 02-JAN-17:19 | 3334.35 | 01-JAN-00:10 | 24680.63 | 01-JAN-11:09 | 0.00 | 9702.66 | 12-JAN-12:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4035.02 | 01-FEB-17:40 | 3334.35 | 01-FEB-00:10 | 24680.63 | 01-FEB-11:09 | 0.00 | 10127.37 | 15-FEB-12:00 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 4035.02 | 01-MAR-17:30 | 3334.35 | 01-MAR-00:10 | 24680.63 | 01-MAR-11:09 | 0.00 | 9883.86 | 27-MAR-12:00 | 17.86 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 4035.02 | 01-APR-18:10 | 3334.35 | 01-APR-05:10 | 24680.63 | 01-APR-10:09 | 0.00 | 10725.94 | 10-APR-17:19 | 17.86 | 01-APR-05:10 | 0.00 | 01-APR-00:10 |
May | 4035.02 | 01-MAY-18:10 | 3334.35 | 01-MAY-05:10 | 24680.63 | 01-MAY-10:09 | 0.00 | 10725.94 | 10-MAY-11:09 | 17.86 | 11-MAY-15:20 | 0.00 | 01-MAY-00:10 |
June | 4035.02 | 01-JUN-18:10 | 3334.35 | 01-JUN-05:10 | 24680.63 | 01-JUN-10:09 | 0.00 | 10725.94 | 05-JUN-17:10 | 17.86 | 04-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 4035.02 | 01-JUL-18:19 | 3334.35 | 01-JUL-05:10 | 24680.63 | 01-JUL-10:09 | 0.00 | 9807.46 | 26-JUL-17:10 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 4035.02 | 01-AUG-18:19 | 3334.35 | 01-AUG-05:10 | 24680.63 | 01-AUG-10:09 | 0.00 | 10725.94 | 01-AUG-11:20 | 17.86 | 03-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 4035.02 | 01-SEP-17:00 | 3334.35 | 01-SEP-05:10 | 24680.63 | 01-SEP-10:09 | 0.00 | 10725.94 | 30-SEP-10:00 | 17.86 | 14-SEP-13:09 | 0.00 | 01-SEP-00:10 |
October | 4035.02 | 02-OCT-17:49 | 3334.35 | 01-OCT-05:10 | 24680.63 | 01-OCT-10:09 | 0.00 | 10457.84 | 04-OCT-11:00 | 17.86 | 22-OCT-13:09 | 0.00 | 01-OCT-00:10 |
November | 4035.02 | 01-NOV-17:30 | 3334.35 | 01-NOV-05:10 | 24680.63 | 01-NOV-10:09 | 0.00 | 10633.76 | 10-NOV-12:00 | 17.86 | 11-NOV-15:20 | 0.00 | 01-NOV-00:10 |
December | 4035.02 | 01-DEC-17:30 | 3334.35 | 01-DEC-00:10 | 24680.63 | 01-DEC-11:09 | 0.00 | 9721.22 | 11-DEC-12:00 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 9702.66 | 17.86 | 0.00 | ||||||
Maximum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 10725.94 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 35960.49 | 12-JAN-12:00 | 0.00 | 0.00 | 0.00 | 4737.03 | 30-JAN-07:19 | 0.00 |
February | 38321.26 | 15-FEB-12:00 | 0.00 | 0.00 | 0.00 | 4737.02 | 06-FEB-19:30 | 0.00 |
March | 37579.46 | 27-MAR-12:00 | 0.00 | 0.00 | 0.00 | 4737.00 | 06-MAR-07:19 | 0.00 |
April | 39829.29 | 10-APR-12:00 | 0.00 | 0.00 | 0.00 | 4735.72 | 05-APR-18:49 | 0.00 |
May | 42015.57 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4736.78 | 12-MAY-06:00 | 0.00 |
June | 41738.24 | 15-JUN-12:00 | 0.00 | 0.00 | 0.00 | 4736.81 | 05-JUN-06:19 | 0.00 |
July | 36455.09 | 26-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.61 | 13-JUL-06:40 | 0.00 |
August | 40253.27 | 15-AUG-11:09 | 0.00 | 0.00 | 0.00 | 4736.70 | 14-AUG-06:19 | 0.00 |
September | 39840.17 | 06-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.38 | 06-SEP-06:49 | 0.00 |
October | 38631.33 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4736.12 | 10-OCT-06:19 | 0.00 |
November | 38454.30 | 10-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4736.66 | 21-NOV-07:40 | 0.00 |
December | 35646.02 | 11-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4736.97 | 11-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 35646.02 | 0.00 | 0.00 | 0.00 | 4735.72 | 0.00 | ||
Maximum of Months | 42015.57 | 0.00 | 0.00 | 0.00 | 4737.03 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 77248.71 | 12-JAN-12:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 9702.66 | 17.86 | 0.00 | 35960.49 | 0.00 |
February | 80040.20 | 15-FEB-12:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 10127.37 | 17.86 | 0.00 | 38321.26 | 0.00 |
March | 77907.64 | 28-MAR-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 9676.58 | 17.86 | 0.00 | 36703.70 | 0.00 |
April | 81541.80 | 10-APR-18:10 | 4035.02 | 19053.35 | 3334.35 | 0.00 | 10527.10 | 17.86 | 0.00 | 37808.18 | 0.00 |
May | 83394.50 | 20-MAY-10:09 | 2850.91 | 24680.63 | 0.00 | 0.00 | 10184.34 | 17.86 | 0.00 | 38236.68 | 0.00 |
June | 85378.28 | 15-JUN-10:20 | 3207.28 | 24680.63 | 0.00 | 0.00 | 10725.94 | 17.86 | 0.00 | 39917.41 | 0.00 |
July | 77852.56 | 15-JUL-18:19 | 4035.02 | 19053.35 | 3334.35 | 0.00 | 9529.28 | 17.86 | 0.00 | 35124.85 | 0.00 |
August | 83852.06 | 15-AUG-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 10349.99 | 17.86 | 0.00 | 38932.79 | 0.00 |
September | 85101.37 | 30-SEP-10:00 | 2850.91 | 24680.63 | 0.00 | 0.00 | 10725.94 | 17.86 | 0.00 | 39725.61 | 0.00 |
October | 80619.00 | 04-OCT-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 10457.84 | 17.86 | 0.00 | 38631.33 | 0.00 |
November | 80758.86 | 17-NOV-18:00 | 4035.02 | 20661.14 | 3334.35 | 0.00 | 9905.75 | 17.86 | 0.00 | 36275.13 | 0.00 |
December | 79072.43 | 29-DEC-18:00 | 4035.02 | 20661.14 | 3334.35 | 0.00 | 9561.13 | 17.86 | 0.00 | 35007.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 77248.71 | 2850.91 | 19053.35 | 0.00 | 0.00 | 9529.28 | 17.86 | 0.00 | 35007.34 | 0.00 | |
Maximum of Months | 85378.28 | 4035.02 | 24680.63 | 3334.35 | 0.00 | 10725.94 | 17.86 | 0.00 | 39917.41 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 16781.81 | 17-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 16769.46 | 03-FEB-07:00 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 16734.94 | 02-MAR-07:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 16658.08 | 03-APR-18:30 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 16586.68 | 01-MAY-06:00 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16518.52 | 05-JUN-06:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16503.13 | 19-JUL-18:30 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16532.71 | 31-AUG-18:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 16597.67 | 29-SEP-06:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 16667.34 | 31-OCT-18:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 16740.15 | 28-NOV-07:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 16777.17 | 27-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16503.13 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16781.81 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 24.74 | 0.00 | 24.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 24.79 | 0.00 | 24.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.84 | 0.00 | 24.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 24.90 | 0.00 | 24.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 24.90 | 1.33 | 24.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 24.91 | 3.67 | 24.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.83 | 0.00 | 24.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 24.84 | 1.83 | 24.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 24.85 | 0.00 | 24.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.80 | 0.00 | 24.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 24.78 | 0.00 | 24.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 24.72 | 0.00 | 24.72 |
Annual Sum or Average | 0.00 | 0.00 | 371.00 | 24.83 | 6.83 | 24.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 24.72 | 0.00 | 24.72 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 24.91 | 3.67 | 24.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 28.09 | 19.50 | 27.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 114.50 | 27.46 | 86.50 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 157.67 | 27.43 | 126.33 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 388.17 | 27.90 | 356.33 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 560.67 | 28.50 | 483.67 | 28.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 524.17 | 28.72 | 455.33 | 28.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 263.00 | 27.42 | 231.50 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 430.83 | 28.38 | 390.17 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 394.17 | 28.13 | 361.00 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 341.50 | 27.78 | 309.83 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 243.33 | 27.48 | 213.00 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 96.50 | 27.64 | 65.50 | 27.40 |
Annual Sum or Average | 0.00 | 0.00 | 3565.00 | 28.08 | 3098.67 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 27.42 | 19.50 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 560.67 | 28.72 | 483.67 | 28.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 406.83 | 24.00 | 610.00 | 24.00 | 406.83 | 24.00 |
February | 399.00 | 24.00 | 551.00 | 24.00 | 399.00 | 24.00 |
March | 479.17 | 24.00 | 612.00 | 24.00 | 479.17 | 24.00 |
April | 583.83 | 24.00 | 590.00 | 24.00 | 583.83 | 24.00 |
May | 611.00 | 24.01 | 611.00 | 24.01 | 611.00 | 24.01 |
June | 592.00 | 24.02 | 592.00 | 24.02 | 592.00 | 24.02 |
July | 606.00 | 24.00 | 609.00 | 24.00 | 606.00 | 24.00 |
August | 612.00 | 24.01 | 612.00 | 24.01 | 612.00 | 24.01 |
September | 590.00 | 24.00 | 590.00 | 24.00 | 590.00 | 24.00 |
October | 610.00 | 24.00 | 610.00 | 24.00 | 610.00 | 24.00 |
November | 570.00 | 24.00 | 591.00 | 24.00 | 570.00 | 24.00 |
December | 468.50 | 24.00 | 609.00 | 24.00 | 468.50 | 24.00 |
Annual Sum or Average | 6528.33 | 24.00 | 7187.00 | 24.00 | 6528.33 | 24.00 |
Minimum of Months | 399.00 | 24.00 | 551.00 | 24.00 | 399.00 | 24.00 |
Maximum of Months | 612.00 | 24.02 | 612.00 | 24.02 | 612.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 26.05 | 610.00 | 26.05 | 610.00 | 26.05 |
February | 551.00 | 26.19 | 551.00 | 26.19 | 551.00 | 26.19 |
March | 612.00 | 26.27 | 612.00 | 26.27 | 612.00 | 26.27 |
April | 590.00 | 27.11 | 590.00 | 27.11 | 590.00 | 27.11 |
May | 611.00 | 28.04 | 611.00 | 28.04 | 611.00 | 28.04 |
June | 592.00 | 28.18 | 592.00 | 28.18 | 592.00 | 28.18 |
July | 609.00 | 26.50 | 609.00 | 26.50 | 609.00 | 26.50 |
August | 612.00 | 27.52 | 612.00 | 27.52 | 612.00 | 27.52 |
September | 590.00 | 27.28 | 590.00 | 27.28 | 590.00 | 27.28 |
October | 610.00 | 26.86 | 610.00 | 26.86 | 610.00 | 26.86 |
November | 591.00 | 26.50 | 591.00 | 26.50 | 591.00 | 26.50 |
December | 609.00 | 26.14 | 609.00 | 26.14 | 609.00 | 26.14 |
Annual Sum or Average | 7187.00 | 26.89 | 7187.00 | 26.89 | 7187.00 | 26.89 |
Minimum of Months | 551.00 | 26.05 | 551.00 | 26.05 | 551.00 | 26.05 |
Maximum of Months | 612.00 | 28.18 | 612.00 | 28.18 | 612.00 | 28.18 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.99979 | 66.35453 | 0.74715 | 16.82137 |
February | 551.00000 | 24.00027 | 66.26333 | 0.75619 | 17.11874 |
March | 612.00000 | 24.00034 | 67.42542 | 0.76542 | 17.40660 |
April | 590.00000 | 24.00025 | 71.42195 | 0.79493 | 18.39704 |
May | 611.00000 | 24.00700 | 74.62577 | 0.00074 | 5.11276 |
June | 592.00000 | 24.01615 | 74.55762 | 0.01298 | 5.14854 |
July | 609.00000 | 24.00031 | 71.19463 | -0.0478 | 5.14263 |
August | 612.00000 | 24.00884 | 75.11996 | -0.0177 | 5.13633 |
September | 590.00000 | 24.00049 | 74.32529 | -0.0150 | 5.13393 |
October | 610.00000 | 24.00021 | 74.10696 | 0.78829 | 18.14197 |
November | 591.00000 | 24.00028 | 71.45782 | 0.77711 | 17.77971 |
December | 609.00000 | 23.99895 | 68.55132 | 0.75811 | 17.16826 |
Annual Sum or Average | 7187.00000 | 24.00275 | 71.30827 | 0.44122 | 12.34264 |
Minimum of Months | 551.00000 | 23.99895 | 66.26333 | -0.0478 | 5.11276 |
Maximum of Months | 612.00000 | 24.01615 | 75.11996 | 0.79493 | 18.39704 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 26.05191 | 61.45414 | 1.40287 | 45.75571 |
February | 551.00000 | 26.18892 | 61.91873 | 1.44826 | 48.19304 |
March | 612.00000 | 26.26740 | 63.05145 | 1.48104 | 49.93327 |
April | 590.00000 | 27.10857 | 65.57692 | 1.71379 | 61.77859 |
May | 611.00000 | 28.04090 | 66.74291 | 1.59235 | 55.91230 |
June | 592.00000 | 28.17992 | 66.48574 | 1.65239 | 58.20479 |
July | 609.00000 | 26.49703 | 63.78912 | 1.04704 | 29.57776 |
August | 612.00000 | 27.52129 | 66.26622 | 1.39308 | 46.36728 |
September | 590.00000 | 27.27722 | 66.06364 | 1.31384 | 42.74867 |
October | 610.00000 | 26.86349 | 65.65542 | 1.63224 | 57.75506 |
November | 591.00000 | 26.50398 | 64.33166 | 1.53546 | 52.79030 |
December | 609.00000 | 26.14299 | 62.64171 | 1.43232 | 47.32540 |
Annual Sum or Average | 7187.00000 | 26.88909 | 64.50818 | 1.46977 | 49.66686 |
Minimum of Months | 551.00000 | 26.05191 | 61.45414 | 1.04704 | 29.57776 |
Maximum of Months | 612.00000 | 28.17992 | 66.74291 | 1.71379 | 61.77859 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.110988E+12 | 0.291940E+11 | 700.69 | 0.604089E+11 | 0.505790E+11 | 0.00 | 1.00 | 01-JAN-01:05 | 0.00 | 01-JAN-01:01 | 95180.94 | 12-JAN-13:00 | 56895.26 | 04-JAN-13:00 | 49967.78 | 09-JAN-01:04 | 25228.37 | 12-JAN-13:00 | 0.00 | 01-JAN-00:10 |
February | 0.109446E+12 | 0.288852E+11 | 635.82 | 0.601542E+11 | 0.492920E+11 | 0.00 | 1.00 | 01-FEB-01:04 | 0.00 | 01-FEB-01:01 | 99864.72 | 15-FEB-13:00 | 57183.01 | 15-FEB-13:00 | 49758.88 | 16-FEB-01:04 | 27335.16 | 15-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 0.132537E+12 | 0.348933E+11 | 704.66 | 0.713943E+11 | 0.611428E+11 | 0.00 | 1.00 | 01-MAR-01:04 | 0.00 | 01-MAR-01:01 | 100921.49 | 28-MAR-00:04 | 58505.39 | 21-MAR-13:00 | 55642.69 | 28-MAR-00:04 | 26559.75 | 27-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.156871E+12 | 0.407067E+11 | 682.39 | 0.752642E+11 | 0.816066E+11 | 0.00 | 1.00 | 01-APR-00:04 | 0.00 | 01-APR-00:01 | 110847.09 | 02-APR-00:04 | 55990.64 | 18-APR-11:53 | 62634.97 | 19-APR-00:04 | 28957.60 | 10-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.184629E+12 | 0.477721E+11 | 704.61 | 0.789222E+11 | 0.105707E+12 | 0.00 | 1.00 | 01-MAY-00:04 | 0.00 | 01-MAY-00:01 | 110847.09 | 02-MAY-00:57 | 63743.29 | 05-MAY-11:55 | 83858.99 | 19-MAY-00:20 | 30600.32 | 04-MAY-13:00 | 0.00 | 01-MAY-00:01 |
June | 0.177953E+12 | 0.460759E+11 | 682.07 | 0.761118E+11 | 0.101841E+12 | 0.00 | 1.00 | 01-JUN-00:04 | 0.00 | 01-JUN-00:01 | 110847.09 | 10-JUN-00:20 | 56305.27 | 12-JUN-17:02 | 83198.79 | 10-JUN-02:06 | 30398.34 | 15-JUN-12:55 | 0.00 | 01-JUN-00:01 |
July | 0.134603E+12 | 0.347345E+11 | 704.25 | 0.637892E+11 | 0.708138E+11 | 0.00 | 1.00 | 01-JUL-00:05 | 0.00 | 01-JUL-00:01 | 103498.14 | 01-JUL-00:05 | 52666.47 | 14-JUL-17:10 | 59895.31 | 01-JUL-00:05 | 25768.66 | 26-JUL-17:10 | 0.00 | 01-JUL-00:01 |
August | 0.163992E+12 | 0.420357E+11 | 704.80 | 0.678537E+11 | 0.961388E+11 | 0.00 | 1.00 | 01-AUG-00:04 | 0.00 | 01-AUG-00:01 | 110847.09 | 02-AUG-00:04 | 54622.95 | 14-AUG-13:00 | 82980.69 | 11-AUG-02:07 | 29316.82 | 15-AUG-11:05 | 0.00 | 01-AUG-00:01 |
September | 0.153522E+12 | 0.393753E+11 | 681.92 | 0.658583E+11 | 0.876642E+11 | 0.00 | 1.00 | 01-SEP-00:04 | 0.00 | 01-SEP-00:01 | 110847.09 | 03-SEP-00:04 | 53994.51 | 05-SEP-11:55 | 65409.44 | 05-SEP-00:04 | 29022.96 | 06-SEP-12:05 | 0.00 | 01-SEP-00:01 |
October | 0.145052E+12 | 0.370739E+11 | 704.82 | 0.622686E+11 | 0.827832E+11 | 0.00 | 1.00 | 01-OCT-00:04 | 0.00 | 01-OCT-00:01 | 107938.33 | 01-OCT-00:04 | 53084.72 | 04-OCT-11:55 | 63281.16 | 01-OCT-00:04 | 27910.49 | 04-OCT-11:55 | 0.00 | 01-OCT-00:01 |
November | 0.128065E+12 | 0.329698E+11 | 681.28 | 0.593571E+11 | 0.687084E+11 | 0.00 | 1.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:01 | 108590.89 | 10-NOV-13:00 | 50898.34 | 13-NOV-13:00 | 64465.46 | 12-NOV-01:05 | 27971.84 | 10-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.114576E+12 | 0.298456E+11 | 699.27 | 0.582588E+11 | 0.563168E+11 | 0.00 | 1.00 | 01-DEC-01:05 | 0.00 | 01-DEC-01:01 | 105037.32 | 12-DEC-01:05 | 52523.69 | 08-DEC-14:00 | 63395.38 | 12-DEC-01:05 | 26128.12 | 12-DEC-01:05 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171223E+13 | 0.443562E+12 | 8286.59 | 0.799641E+12 | 0.912593E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.109446E+12 | 0.288852E+11 | 635.82 | 0.582588E+11 | 0.492920E+11 | 0.00 | 1.00 | 0.00 | 95180.94 | 50898.34 | 49758.88 | 25228.37 | 0.00 | |||||||
Maximum of Months | 0.184629E+12 | 0.477721E+11 | 704.82 | 0.789222E+11 | 0.105707E+12 | 0.00 | 1.00 | 0.00 | 110847.09 | 63743.29 | 83858.99 | 30600.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.785265E+11 | 0.182333E+11 | 709.10 | 0.415333E+11 | 0.369931E+11 | 0.00 | 1.00 | 01-JAN-01:03 | 0.00 | 01-JAN-01:01 | 45400.99 | 03-JAN-03:42 | 32207.67 | 04-JAN-13:00 | 30468.37 | 09-JAN-02:22 | 11002.85 | 04-JAN-13:00 | 0.00 | 01-JAN-00:10 |
February | 0.755003E+11 | 0.176103E+11 | 642.98 | 0.407709E+11 | 0.347293E+11 | 0.00 | 1.00 | 01-FEB-01:03 | 0.00 | 01-FEB-01:01 | 45400.99 | 05-FEB-17:24 | 32997.08 | 21-FEB-14:00 | 31259.10 | 14-FEB-03:02 | 11158.12 | 26-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.911003E+11 | 0.212638E+11 | 712.09 | 0.484106E+11 | 0.426897E+11 | 0.00 | 1.00 | 01-MAR-01:03 | 0.00 | 01-MAR-01:01 | 45400.99 | 02-MAR-16:56 | 35523.27 | 21-MAR-13:00 | 31683.30 | 15-MAR-03:22 | 11339.90 | 19-MAR-13:55 | 0.00 | 01-MAR-00:10 |
April | 0.101550E+12 | 0.236115E+11 | 689.50 | 0.474934E+11 | 0.540570E+11 | 0.00 | 1.00 | 01-APR-00:02 | 0.00 | 01-APR-00:01 | 45400.99 | 05-APR-19:45 | 30578.95 | 05-APR-14:53 | 31240.36 | 01-APR-02:62 | 11247.82 | 01-APR-14:00 | 0.00 | 01-APR-00:01 |
May | 0.111591E+12 | 0.259602E+11 | 712.57 | 0.449465E+11 | 0.666444E+11 | 0.00 | 1.00 | 01-MAY-00:02 | 0.00 | 01-MAY-00:01 | 45400.99 | 01-MAY-03:32 | 31471.23 | 05-MAY-12:00 | 34473.92 | 19-MAY-00:03 | 11649.99 | 06-MAY-13:00 | 0.00 | 01-MAY-00:01 |
June | 0.107314E+12 | 0.249478E+11 | 689.53 | 0.428816E+11 | 0.644328E+11 | 0.00 | 1.00 | 01-JUN-00:02 | 0.00 | 01-JUN-00:01 | 45400.99 | 14-JUN-06:47 | 27870.37 | 18-JUN-14:00 | 34076.74 | 10-JUN-02:61 | 11339.90 | 12-JUN-14:55 | 0.00 | 01-JUN-00:01 |
July | 0.969941E+11 | 0.222562E+11 | 712.48 | 0.439239E+11 | 0.530701E+11 | 0.00 | 1.00 | 01-JUL-00:02 | 0.00 | 01-JUL-00:01 | 45400.99 | 10-JUL-13:15 | 28157.65 | 13-JUL-16:00 | 32387.88 | 11-JUL-03:22 | 10855.76 | 15-JUL-15:55 | 0.00 | 01-JUL-00:01 |
August | 0.106610E+12 | 0.244743E+11 | 712.47 | 0.406598E+11 | 0.659498E+11 | 0.00 | 1.00 | 01-AUG-00:02 | 0.00 | 01-AUG-00:01 | 45400.99 | 01-AUG-07:34 | 26668.15 | 27-AUG-16:00 | 33987.41 | 11-AUG-02:62 | 10986.10 | 10-AUG-14:00 | 0.00 | 01-AUG-00:01 |
September | 0.101608E+12 | 0.233236E+11 | 689.50 | 0.404830E+11 | 0.611252E+11 | 0.00 | 1.00 | 01-SEP-00:02 | 0.00 | 01-SEP-00:01 | 45400.99 | 25-SEP-07:56 | 26279.62 | 10-SEP-12:00 | 32858.42 | 23-SEP-02:42 | 10986.10 | 06-SEP-13:55 | 0.00 | 01-SEP-00:01 |
October | 0.100639E+12 | 0.229777E+11 | 712.42 | 0.399912E+11 | 0.606475E+11 | 0.00 | 1.00 | 01-OCT-00:02 | 0.00 | 01-OCT-00:01 | 45400.99 | 01-OCT-15:07 | 25114.96 | 04-OCT-13:55 | 32930.14 | 20-OCT-03:22 | 10824.21 | 04-OCT-13:55 | 0.00 | 01-OCT-00:01 |
November | 0.898479E+11 | 0.206012E+11 | 689.16 | 0.392699E+11 | 0.505780E+11 | 0.00 | 1.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:01 | 45400.99 | 01-NOV-10:47 | 28806.52 | 18-NOV-13:00 | 32163.69 | 10-NOV-03:02 | 11036.66 | 18-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.818100E+11 | 0.188982E+11 | 708.51 | 0.396717E+11 | 0.421383E+11 | 0.00 | 1.00 | 01-DEC-00:10 | 0.00 | 01-DEC-01:01 | 45400.99 | 10-DEC-18:00 | 30951.45 | 26-DEC-12:00 | 32289.82 | 11-DEC-02:22 | 10687.51 | 13-DEC-15:53 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.114309E+13 | 0.264158E+12 | 8380.30 | 0.510036E+12 | 0.633055E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.755003E+11 | 0.176103E+11 | 642.98 | 0.392699E+11 | 0.347293E+11 | 0.00 | 1.00 | 0.00 | 45400.99 | 25114.96 | 30468.37 | 10687.51 | 0.00 | |||||||
Maximum of Months | 0.111591E+12 | 0.259602E+11 | 712.57 | 0.484106E+11 | 0.666444E+11 | 0.00 | 1.00 | 0.00 | 45400.99 | 35523.27 | 34473.92 | 11649.99 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.19 | 49.60 | 97.58 | 513.94 | 67.68 | 0.00 | 0.00 | 0.00 |
February | 166.51 | 60.76 | 105.74 | 602.98 | 50.07 | 0.00 | 0.00 | 0.00 |
March | 181.71 | 70.84 | 110.87 | 668.51 | 31.21 | 0.00 | 0.00 | 0.00 |
April | 183.22 | 69.53 | 113.68 | 704.33 | 10.18 | 0.00 | 0.00 | 0.00 |
May | 157.85 | 47.59 | 110.26 | 630.88 | 16.09 | 0.00 | 0.00 | 0.00 |
June | 168.17 | 55.22 | 112.96 | 660.28 | 16.48 | 0.00 | 0.00 | 0.00 |
July | 143.81 | 32.12 | 111.69 | 528.93 | 33.18 | 0.00 | 0.00 | 0.00 |
August | 157.90 | 46.12 | 111.78 | 538.75 | 26.54 | 0.00 | 0.00 | 0.00 |
September | 148.26 | 40.09 | 108.17 | 549.81 | 27.57 | 0.00 | 0.00 | 0.00 |
October | 139.18 | 35.44 | 103.74 | 473.22 | 38.52 | 0.00 | 0.00 | 0.00 |
November | 134.94 | 37.23 | 97.71 | 472.69 | 46.58 | 0.00 | 0.00 | 0.00 |
December | 138.11 | 44.37 | 93.73 | 478.33 | 78.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.45 | 48.96 | 106.48 | 567.96 | 36.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.94 | 32.12 | 93.73 | 472.69 | 10.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.22 | 70.84 | 113.68 | 704.33 | 78.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 285.20 | 122.05 | 163.15 | 995.47 | 94.02 | 0.00 | 0.00 | 0.00 |
February | 247.42 | 87.20 | 160.22 | 922.47 | 69.64 | 0.00 | 0.00 | 0.00 |
March | 174.18 | 33.75 | 140.44 | 704.46 | 43.87 | 0.00 | 0.00 | 0.00 |
April | 122.85 | 1.31 | 121.55 | 551.20 | 14.22 | 0.00 | 0.00 | 0.00 |
May | 121.04 | 0.00 | 121.04 | 560.22 | 22.96 | 0.00 | 0.00 | 0.00 |
June | 120.60 | 0.00 | 120.60 | 554.94 | 23.82 | 0.00 | 0.00 | 0.00 |
July | 124.24 | 0.00 | 124.24 | 492.09 | 47.18 | 0.00 | 0.00 | 0.00 |
August | 120.81 | 0.02 | 120.78 | 446.60 | 38.11 | 0.00 | 0.00 | 0.00 |
September | 135.39 | 5.74 | 129.65 | 538.96 | 38.97 | 0.00 | 0.00 | 0.00 |
October | 179.73 | 32.47 | 147.26 | 622.16 | 53.26 | 0.00 | 0.00 | 0.00 |
November | 234.34 | 76.00 | 158.34 | 818.48 | 64.42 | 0.00 | 0.00 | 0.00 |
December | 283.79 | 122.99 | 160.80 | 977.74 | 109.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 178.85 | 39.95 | 138.90 | 680.82 | 51.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.60 | 0.00 | 120.60 | 446.60 | 14.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 285.20 | 122.99 | 163.15 | 995.47 | 109.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 149.22 | 52.48 | 96.74 | 526.99 | 71.04 | 0.00 | 0.00 | 0.00 |
February | 163.69 | 57.84 | 105.86 | 596.38 | 51.97 | 0.00 | 0.00 | 0.00 |
March | 182.91 | 71.84 | 111.08 | 671.05 | 31.55 | 0.00 | 0.00 | 0.00 |
April | 183.76 | 69.89 | 113.87 | 687.17 | 9.45 | 0.00 | 0.00 | 0.00 |
May | 156.81 | 46.30 | 110.51 | 614.11 | 16.53 | 0.00 | 0.00 | 0.00 |
June | 169.83 | 58.31 | 111.52 | 652.48 | 16.98 | 0.00 | 0.00 | 0.00 |
July | 144.78 | 33.90 | 110.89 | 532.32 | 33.93 | 0.00 | 0.00 | 0.00 |
August | 157.77 | 46.60 | 111.17 | 530.32 | 26.98 | 0.00 | 0.00 | 0.00 |
September | 147.18 | 40.44 | 106.75 | 536.93 | 27.51 | 0.00 | 0.00 | 0.00 |
October | 138.48 | 35.49 | 102.99 | 463.40 | 38.30 | 0.00 | 0.00 | 0.00 |
November | 135.23 | 36.83 | 98.41 | 469.62 | 47.43 | 0.00 | 0.00 | 0.00 |
December | 138.67 | 45.44 | 93.22 | 488.29 | 82.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.59 | 49.53 | 106.07 | 563.57 | 37.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.23 | 33.90 | 93.22 | 463.40 | 9.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.76 | 71.84 | 113.87 | 687.17 | 82.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394223E+09 | 0.132857E+09 | 0.261365E+09 | 0.137653E+10 | 0.181272E+09 |
February | 0.402809E+09 | 0.146998E+09 | 0.255811E+09 | 0.145872E+10 | 0.121119E+09 |
March | 0.486694E+09 | 0.189730E+09 | 0.296964E+09 | 0.179054E+10 | 83595610.37 |
April | 0.474900E+09 | 0.180233E+09 | 0.294667E+09 | 0.182563E+10 | 26391107.89 |
May | 0.422783E+09 | 0.127461E+09 | 0.295323E+09 | 0.168976E+10 | 43100570.36 |
June | 0.435908E+09 | 0.143122E+09 | 0.292786E+09 | 0.171145E+10 | 42704380.89 |
July | 0.385175E+09 | 86027184.42 | 0.299148E+09 | 0.141669E+10 | 88864316.81 |
August | 0.422910E+09 | 0.123526E+09 | 0.299383E+09 | 0.144298E+10 | 71076412.09 |
September | 0.384289E+09 | 0.103925E+09 | 0.280364E+09 | 0.142512E+10 | 71454955.31 |
October | 0.372772E+09 | 94927998.82 | 0.277844E+09 | 0.126746E+10 | 0.103183E+09 |
November | 0.349757E+09 | 96498762.47 | 0.253259E+09 | 0.122520E+10 | 0.120748E+09 |
December | 0.369901E+09 | 0.118846E+09 | 0.251055E+09 | 0.128115E+10 | 0.210158E+09 |
Annual Sum or Average | 0.490212E+10 | 0.154415E+10 | 0.335797E+10 | 0.179112E+11 | 0.116367E+10 |
Minimum of Months | 0.349757E+09 | 86027184.42 | 0.251055E+09 | 0.122520E+10 | 26391107.89 |
Maximum of Months | 0.486694E+09 | 0.189730E+09 | 0.299383E+09 | 0.182563E+10 | 0.210158E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.763884E+09 | 0.326908E+09 | 0.436976E+09 | 0.266626E+10 | 0.251820E+09 |
February | 0.598555E+09 | 0.210957E+09 | 0.387598E+09 | 0.223164E+10 | 0.168465E+09 |
March | 0.466530E+09 | 90388417.98 | 0.376142E+09 | 0.188682E+10 | 0.117502E+09 |
April | 0.318440E+09 | 3383138.78 | 0.315057E+09 | 0.142870E+10 | 36847101.06 |
May | 0.324182E+09 | 0.00 | 0.324182E+09 | 0.150050E+10 | 61500519.57 |
June | 0.312595E+09 | 0.00 | 0.312595E+09 | 0.143840E+10 | 61728625.58 |
July | 0.332754E+09 | 0.00 | 0.332754E+09 | 0.131801E+10 | 0.126355E+09 |
August | 0.323571E+09 | 60335.41 | 0.323511E+09 | 0.119617E+10 | 0.102065E+09 |
September | 0.350923E+09 | 14878670.11 | 0.336045E+09 | 0.139699E+10 | 0.101004E+09 |
October | 0.481387E+09 | 86971804.37 | 0.394416E+09 | 0.166641E+10 | 0.142643E+09 |
November | 0.607412E+09 | 0.196988E+09 | 0.410424E+09 | 0.212150E+10 | 0.166985E+09 |
December | 0.760106E+09 | 0.329422E+09 | 0.430684E+09 | 0.261879E+10 | 0.292948E+09 |
Annual Sum or Average | 0.564034E+10 | 0.125996E+10 | 0.438038E+10 | 0.214702E+11 | 0.162986E+10 |
Minimum of Months | 0.312595E+09 | 0.00 | 0.312595E+09 | 0.119617E+10 | 36847101.06 |
Maximum of Months | 0.763884E+09 | 0.329422E+09 | 0.436976E+09 | 0.266626E+10 | 0.292948E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.399664E+09 | 0.140557E+09 | 0.259107E+09 | 0.141149E+10 | 0.190262E+09 |
February | 0.396010E+09 | 0.139918E+09 | 0.256092E+09 | 0.144276E+10 | 0.125721E+09 |
March | 0.489912E+09 | 0.192406E+09 | 0.297506E+09 | 0.179734E+10 | 84514766.31 |
April | 0.476312E+09 | 0.181166E+09 | 0.295147E+09 | 0.178114E+10 | 24489887.42 |
May | 0.420008E+09 | 0.124008E+09 | 0.296000E+09 | 0.164482E+10 | 44262689.64 |
June | 0.440199E+09 | 0.151150E+09 | 0.289049E+09 | 0.169122E+10 | 44016434.87 |
July | 0.387786E+09 | 90787026.37 | 0.296999E+09 | 0.142575E+10 | 90884207.26 |
August | 0.422575E+09 | 0.124826E+09 | 0.297748E+09 | 0.142041E+10 | 72272500.86 |
September | 0.381498E+09 | 0.104812E+09 | 0.276686E+09 | 0.139172E+10 | 71318685.04 |
October | 0.370910E+09 | 95060364.26 | 0.275849E+09 | 0.124116E+10 | 0.102585E+09 |
November | 0.350526E+09 | 95451529.21 | 0.255075E+09 | 0.121725E+10 | 0.122937E+09 |
December | 0.371405E+09 | 0.121714E+09 | 0.249691E+09 | 0.130784E+10 | 0.219794E+09 |
Annual Sum or Average | 0.490681E+10 | 0.156186E+10 | 0.334495E+10 | 0.177729E+11 | 0.119306E+10 |
Minimum of Months | 0.350526E+09 | 90787026.37 | 0.249691E+09 | 0.121725E+10 | 24489887.42 |
Maximum of Months | 0.489912E+09 | 0.192406E+09 | 0.297748E+09 | 0.179734E+10 | 0.219794E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2032.58 | 228.92 | 581.61 | 224.13 | 357.47 | 0.00 | 0.00 |
February | 2119.24 | 169.09 | 577.62 | 205.80 | 371.82 | 0.00 | 0.00 |
March | 2042.36 | 104.97 | 538.81 | 176.42 | 362.39 | 0.00 | 0.00 |
April | 1942.28 | 33.42 | 489.83 | 140.73 | 349.10 | 0.00 | 0.00 |
May | 1805.01 | 55.38 | 435.70 | 93.89 | 341.81 | 0.00 | 0.00 |
June | 1866.63 | 56.20 | 458.60 | 113.53 | 345.07 | 0.00 | 0.00 |
July | 1552.30 | 113.25 | 412.83 | 66.01 | 346.81 | 0.00 | 0.00 |
August | 1514.34 | 90.30 | 436.48 | 92.75 | 343.73 | 0.00 | 0.00 |
September | 1624.63 | 92.98 | 430.83 | 86.27 | 344.56 | 0.00 | 0.00 |
October | 1558.05 | 129.36 | 457.39 | 103.41 | 353.98 | 0.00 | 0.00 |
November | 1759.38 | 157.03 | 504.51 | 150.05 | 354.46 | 0.00 | 0.00 |
December | 1940.89 | 266.43 | 560.56 | 212.81 | 347.76 | 0.00 | 0.00 |
Annual Sum or Average | 1810.79 | 124.85 | 489.89 | 138.44 | 351.45 | 0.00 | 0.00 |
Minimum of Months | 1514.34 | 33.42 | 412.83 | 66.01 | 341.81 | 0.00 | 0.00 |
Maximum of Months | 2119.24 | 266.43 | 581.61 | 224.13 | 371.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.544406E+10 | 0.613135E+09 | 0.155777E+10 | 0.600323E+09 | 0.957448E+09 | 0.00 | 0.00 |
February | 0.512686E+10 | 0.409051E+09 | 0.139737E+10 | 0.497874E+09 | 0.899501E+09 | 0.00 | 0.00 |
March | 0.547024E+10 | 0.281149E+09 | 0.144314E+10 | 0.472524E+09 | 0.970612E+09 | 0.00 | 0.00 |
April | 0.503438E+10 | 86637548.93 | 0.126965E+10 | 0.364782E+09 | 0.904870E+09 | 0.00 | 0.00 |
May | 0.483455E+10 | 0.148333E+09 | 0.116697E+10 | 0.251469E+09 | 0.915505E+09 | 0.00 | 0.00 |
June | 0.483829E+10 | 0.145674E+09 | 0.118870E+10 | 0.294271E+09 | 0.894430E+09 | 0.00 | 0.00 |
July | 0.415769E+10 | 0.303342E+09 | 0.110571E+10 | 0.176814E+09 | 0.928901E+09 | 0.00 | 0.00 |
August | 0.405601E+10 | 0.241861E+09 | 0.116906E+10 | 0.248413E+09 | 0.920642E+09 | 0.00 | 0.00 |
September | 0.421105E+10 | 0.240995E+09 | 0.111671E+10 | 0.223616E+09 | 0.893095E+09 | 0.00 | 0.00 |
October | 0.417309E+10 | 0.346474E+09 | 0.122507E+10 | 0.276960E+09 | 0.948109E+09 | 0.00 | 0.00 |
November | 0.456031E+10 | 0.407033E+09 | 0.130770E+10 | 0.388938E+09 | 0.918757E+09 | 0.00 | 0.00 |
December | 0.519848E+10 | 0.713596E+09 | 0.150141E+10 | 0.569983E+09 | 0.931429E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.571050E+11 | 0.393728E+10 | 0.154493E+11 | 0.436597E+10 | 0.110833E+11 | 0.00 | 0.00 |
Minimum of Months | 0.405601E+10 | 86637548.93 | 0.110571E+10 | 0.176814E+09 | 0.893095E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547024E+10 | 0.713596E+09 | 0.155777E+10 | 0.600323E+09 | 0.970612E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638044E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155261661.7 | 81.21 | 0.00 | 0.00 |
February | 0.577421E+10 | -0.563427E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -139945686.8 | 81.21 | 0.00 | 0.00 |
March | 0.644855E+10 | -0.629382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154735339.8 | 81.22 | 0.00 | 0.00 |
April | 0.619123E+10 | -0.604346E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147768530.1 | 81.21 | 0.00 | 0.00 |
May | 0.641049E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150296531.4 | 81.21 | 0.00 | 0.00 |
June | 0.623176E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -145163058.2 | 81.21 | 0.00 | 0.00 |
July | 0.637123E+10 | -0.621706E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154163624.7 | 81.21 | 0.00 | 0.00 |
August | 0.644691E+10 | -0.629523E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151678992.7 | 81.21 | 0.00 | 0.00 |
September | 0.619220E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147381097.0 | 81.21 | 0.00 | 0.00 |
October | 0.637711E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153300963.7 | 81.21 | 0.00 | 0.00 |
November | 0.617380E+10 | -0.602460E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149201842.3 | 81.21 | 0.00 | 0.00 |
December | 0.637213E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155047026.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753701E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.180394E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577421E+10 | -0.629523E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155261661.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644855E+10 | -0.563427E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -139945686.8 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.150980E+11 | -0.142503E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -847687484.0 | 58.99 | 0.00 | 0.00 |
February | 0.135771E+11 | -0.128144E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -762695224.8 | 58.98 | 0.00 | 0.00 |
March | 0.149322E+11 | -0.140896E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -842562553.4 | 58.98 | 0.00 | 0.00 |
April | 0.140330E+11 | -0.132357E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -797352933.8 | 58.98 | 0.00 | 0.00 |
May | 0.142140E+11 | -0.134121E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -801902545.2 | 58.98 | 0.00 | 0.00 |
June | 0.136050E+11 | -0.128316E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -773417026.0 | 58.98 | 0.00 | 0.00 |
July | 0.138746E+11 | -0.130373E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -837300756.3 | 58.98 | 0.00 | 0.00 |
August | 0.141113E+11 | -0.132965E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -814749188.2 | 58.98 | 0.00 | 0.00 |
September | 0.137856E+11 | -0.129917E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -793866869.2 | 58.98 | 0.00 | 0.00 |
October | 0.145093E+11 | -0.136799E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -829427962.0 | 58.98 | 0.00 | 0.00 |
November | 0.143381E+11 | -0.135277E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -810449632.6 | 58.98 | 0.00 | 0.00 |
December | 0.150129E+11 | -0.141675E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -845462468.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.171091E+12 | -0.161334E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.975687E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.135771E+11 | -0.142503E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -847687484.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.150980E+11 | -0.128144E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -762695224.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.74 | 0.73 | 01-JAN-06:00 | 1362.47 | 24.54 | 201.17 | 330.17 | 1313.12 | 24.39 | 189.67 | 331.00 |
February | 321.17 | 0.74 | 0.73 | 01-FEB-06:40 | 1381.47 | 21.63 | 132.83 | 300.50 | 1291.16 | 21.08 | 124.33 | 298.00 |
March | 361.17 | 0.74 | 0.73 | 01-MAR-07:10 | 1366.49 | 19.85 | 87.50 | 343.17 | 1313.75 | 19.81 | 88.83 | 341.00 |
April | 358.33 | 0.74 | 0.73 | 01-APR-06:19 | 1274.47 | 19.65 | 57.67 | 345.00 | 1023.42 | 19.65 | 56.00 | 342.83 |
May | 376.33 | 0.74 | 0.73 | 01-MAY-06:10 | 1026.18 | 19.25 | 32.50 | 353.00 | 876.96 | 18.63 | 10.00 | 351.17 |
June | 370.50 | 0.74 | 0.73 | 01-JUN-06:49 | 997.30 | 20.96 | 56.17 | 348.83 | 923.67 | 18.99 | 0.00 | 349.33 |
July | 383.17 | 0.74 | 0.73 | 01-JUL-06:30 | 803.73 | 19.29 | 32.17 | 350.83 | 790.57 | 18.14 | 0.00 | 350.50 |
August | 369.33 | 0.74 | 0.73 | 01-AUG-06:10 | 1027.47 | 19.04 | 36.00 | 354.83 | 916.68 | 19.03 | 33.17 | 351.00 |
September | 357.83 | 0.75 | 0.73 | 01-SEP-06:10 | 1034.28 | 18.61 | 48.33 | 329.17 | 912.20 | 18.71 | 41.50 | 327.67 |
October | 356.83 | 0.74 | 0.73 | 01-OCT-06:10 | 1068.96 | 19.47 | 68.00 | 335.00 | 1018.70 | 19.60 | 63.00 | 335.83 |
November | 337.67 | 0.74 | 0.73 | 01-NOV-06:40 | 1158.79 | 21.71 | 132.33 | 320.00 | 1138.27 | 22.52 | 145.33 | 322.83 |
December | 349.33 | 0.74 | 0.73 | 01-DEC-06:19 | 1255.51 | 23.45 | 170.67 | 325.67 | 1319.55 | 24.31 | 190.50 | 326.17 |
Annual Sum or Average | 4292.33 | 0.74 | 1140.69 | 20.58 | 1055.33 | 4036.17 | 1063.60 | 20.35 | 942.33 | 4027.33 | ||
Minimum of Months | 321.17 | 0.74 | 0.73 | 803.73 | 18.61 | 32.17 | 300.50 | 790.57 | 18.14 | 0.00 | 298.00 | |
Maximum of Months | 383.17 | 0.75 | 0.73 | 1381.47 | 24.54 | 201.17 | 354.83 | 1319.55 | 24.39 | 190.50 | 351.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.110988E+12 | 0.604089E+11 | 95180.94 | 12-JAN-13:00 | 52964.40 | 0.00 |
February | 0.00 | 0.00 | 0.109446E+12 | 0.601542E+11 | 99864.72 | 15-FEB-13:00 | 57183.01 | 0.00 |
March | 0.00 | 0.00 | 0.132537E+12 | 0.713943E+11 | 100921.49 | 28-MAR-00:04 | 45278.80 | 0.00 |
April | 0.00 | 0.00 | 0.156871E+12 | 0.752642E+11 | 110847.09 | 02-APR-00:04 | 48566.07 | 0.00 |
May | 0.00 | 0.00 | 0.184629E+12 | 0.789222E+11 | 110847.09 | 02-MAY-00:57 | 31203.10 | 0.00 |
June | 0.00 | 0.00 | 0.177953E+12 | 0.761118E+11 | 110847.09 | 10-JUN-00:20 | 32382.43 | 0.00 |
July | 0.00 | 0.00 | 0.134603E+12 | 0.637892E+11 | 103498.14 | 01-JUL-00:05 | 43602.84 | 0.00 |
August | 0.00 | 0.00 | 0.163992E+12 | 0.678537E+11 | 110847.09 | 02-AUG-00:04 | 43439.61 | 0.00 |
September | 0.00 | 0.00 | 0.153522E+12 | 0.658583E+11 | 110847.09 | 03-SEP-00:04 | 47217.81 | 0.00 |
October | 0.00 | 0.00 | 0.145052E+12 | 0.622686E+11 | 107938.33 | 01-OCT-00:04 | 44657.16 | 0.00 |
November | 0.00 | 0.00 | 0.128065E+12 | 0.593571E+11 | 108590.89 | 10-NOV-13:00 | 49406.52 | 0.00 |
December | 0.00 | 0.00 | 0.114576E+12 | 0.582588E+11 | 105037.32 | 12-DEC-01:05 | 41641.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171223E+13 | 0.799641E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.109446E+12 | 0.582588E+11 | 95180.94 | 31203.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184629E+12 | 0.789222E+11 | 110847.09 | 57183.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.785265E+11 | 0.415333E+11 | 45400.99 | 03-JAN-03:42 | 21005.95 | 0.00 |
February | 0.00 | 0.00 | 0.755003E+11 | 0.407709E+11 | 45400.99 | 05-FEB-17:24 | 23347.03 | 0.00 |
March | 0.00 | 0.00 | 0.911003E+11 | 0.484106E+11 | 45400.99 | 02-MAR-16:56 | 23963.96 | 0.00 |
April | 0.00 | 0.00 | 0.101550E+12 | 0.474934E+11 | 45400.99 | 05-APR-19:45 | 21178.04 | 0.00 |
May | 0.00 | 0.00 | 0.111591E+12 | 0.449465E+11 | 45400.99 | 01-MAY-03:32 | 15081.87 | 0.00 |
June | 0.00 | 0.00 | 0.107314E+12 | 0.428816E+11 | 45400.99 | 14-JUN-06:47 | 15645.21 | 0.00 |
July | 0.00 | 0.00 | 0.969941E+11 | 0.439239E+11 | 45400.99 | 10-JUL-13:15 | 19550.83 | 0.00 |
August | 0.00 | 0.00 | 0.106610E+12 | 0.406598E+11 | 45400.99 | 01-AUG-07:34 | 16345.32 | 0.00 |
September | 0.00 | 0.00 | 0.101608E+12 | 0.404830E+11 | 45400.99 | 25-SEP-07:56 | 15330.83 | 0.00 |
October | 0.00 | 0.00 | 0.100639E+12 | 0.399912E+11 | 45400.99 | 01-OCT-15:07 | 19929.32 | 0.00 |
November | 0.00 | 0.00 | 0.898479E+11 | 0.392699E+11 | 45400.99 | 01-NOV-10:47 | 19860.25 | 0.00 |
December | 0.00 | 0.00 | 0.818100E+11 | 0.396717E+11 | 45400.99 | 10-DEC-18:00 | 17885.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114309E+13 | 0.510036E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.755003E+11 | 0.392699E+11 | 45400.99 | 15081.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111591E+12 | 0.484106E+11 | 45400.99 | 23963.96 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5787.69 | 10979.04 | 11-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 5763.95 | 10947.66 | 02-FEB-07:52 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5728.08 | 10844.66 | 02-MAR-07:47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5574.20 | 10601.38 | 03-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5475.47 | 10394.56 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5418.74 | 10199.57 | 07-JUN-18:44 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5336.22 | 10121.71 | 19-JUL-18:27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5432.99 | 10241.39 | 31-AUG-18:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5480.15 | 10432.76 | 29-SEP-18:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5575.11 | 10647.17 | 31-OCT-18:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5686.70 | 10845.91 | 29-NOV-07:35 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5756.92 | 10965.92 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 5583.70 | ||||
Minimum of Months | 0.00 | 0.00 | 5336.22 | 10121.71 | ||
Maximum of Months | 0.00 | 0.00 | 5787.69 | 10979.04 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.508311E+10 | 0.60 | 1983.06 | 01-JAN-00:10 | 0.63 |
February | 0.459218E+10 | 0.60 | 1983.06 | 01-FEB-00:10 | 0.63 |
March | 0.508525E+10 | 0.60 | 1983.06 | 01-MAR-00:10 | 0.63 |
April | 0.492236E+10 | 0.60 | 1983.06 | 01-APR-00:02 | 0.63 |
May | 0.508704E+10 | 0.60 | 1983.06 | 01-MAY-00:02 | 0.63 |
June | 0.492260E+10 | 0.60 | 1983.06 | 01-JUN-00:02 | 0.63 |
July | 0.508644E+10 | 0.60 | 1983.06 | 01-JUL-00:02 | 0.63 |
August | 0.508632E+10 | 0.60 | 1983.06 | 01-AUG-00:02 | 0.63 |
September | 0.492236E+10 | 0.60 | 1983.06 | 01-SEP-00:02 | 0.63 |
October | 0.508596E+10 | 0.60 | 1983.06 | 01-OCT-00:02 | 0.63 |
November | 0.492141E+10 | 0.60 | 1983.06 | 01-NOV-00:02 | 0.63 |
December | 0.508370E+10 | 0.60 | 1983.06 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.598787E+11 | 0.60 | |||
Minimum of Months | 0.459218E+10 | 0.60 | 1983.06 | 0.63 | |
Maximum of Months | 0.508704E+10 | 0.60 | 1983.06 | 0.63 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.725390E+10 | 0.86 | 5934.78 | 12-JAN-13:00 | 1.29 |
February | 0.693514E+10 | 0.88 | 6359.50 | 15-FEB-13:00 | 1.33 |
March | 0.807029E+10 | 0.90 | 6211.26 | 28-MAR-00:04 | 1.32 |
April | 0.927353E+10 | 0.96 | 6958.06 | 02-APR-00:04 | 1.38 |
May | 0.110823E+11 | 1.03 | 6958.06 | 01-MAY-00:04 | 1.38 |
June | 0.107179E+11 | 1.03 | 6958.06 | 02-JUN-00:04 | 1.38 |
July | 0.808408E+10 | 0.89 | 6405.13 | 01-JUL-00:05 | 1.33 |
August | 0.981962E+10 | 0.97 | 6958.06 | 01-AUG-11:15 | 1.38 |
September | 0.915366E+10 | 0.96 | 6958.06 | 03-SEP-00:04 | 1.38 |
October | 0.868196E+10 | 0.92 | 6739.21 | 01-OCT-00:04 | 1.36 |
November | 0.784480E+10 | 0.90 | 6880.64 | 10-NOV-13:00 | 1.38 |
December | 0.738559E+10 | 0.87 | 6520.94 | 12-DEC-01:05 | 1.34 |
Annual Sum or Average | 0.104303E+12 | 0.93 | |||
Minimum of Months | 0.693514E+10 | 0.86 | 5934.78 | 1.29 | |
Maximum of Months | 0.110823E+11 | 1.03 | 6958.06 | 1.38 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.303066E+10 | 0.67 | 1784.81 | 01-JAN-01:03 | 0.87 |
February | 0.287861E+10 | 0.69 | 1784.81 | 01-FEB-01:03 | 0.87 |
March | 0.347868E+10 | 0.72 | 1784.81 | 01-MAR-01:03 | 0.87 |
April | 0.394954E+10 | 0.78 | 1784.81 | 01-APR-00:02 | 0.86 |
May | 0.439326E+10 | 0.81 | 1784.81 | 01-MAY-00:02 | 0.86 |
June | 0.421972E+10 | 0.80 | 1784.81 | 01-JUN-00:02 | 0.86 |
July | 0.370041E+10 | 0.74 | 1784.81 | 01-JUL-00:02 | 0.86 |
August | 0.414339E+10 | 0.78 | 1784.81 | 01-AUG-00:02 | 0.86 |
September | 0.393515E+10 | 0.78 | 1784.81 | 01-SEP-00:02 | 0.86 |
October | 0.386284E+10 | 0.76 | 1784.81 | 01-OCT-00:02 | 0.86 |
November | 0.343795E+10 | 0.72 | 1784.81 | 01-NOV-00:02 | 0.86 |
December | 0.316211E+10 | 0.69 | 1784.81 | 01-DEC-01:02 | 0.87 |
Annual Sum or Average | 0.441923E+11 | 0.74 | |||
Minimum of Months | 0.287861E+10 | 0.67 | 1784.81 | 0.86 | |
Maximum of Months | 0.439326E+10 | 0.81 | 1784.81 | 0.87 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 52.14 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:10 | 5.36 | 5.36 | 53.09 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:10 | 5.36 | 5.36 | 53.00 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 54.41 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 55.10 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 54.49 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 55.06 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.34 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.45 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 54.93 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 54.35 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:10 | 5.36 | 5.36 | 52.98 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 52.14 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.10 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 52.14 | 59.54 | 5787.69 | 10979.04 | 11-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 53.09 | 59.07 | 5763.95 | 10947.66 | 02-FEB-07:52 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53.00 | 58.75 | 5728.08 | 10844.66 | 02-MAR-07:47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 53.43 | 53.43 | 5574.20 | 10601.38 | 03-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.62 | 53.62 | 5475.47 | 10394.56 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.14 | 53.14 | 5418.74 | 10199.57 | 07-JUN-18:44 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.02 | 54.02 | 5336.22 | 10121.71 | 19-JUL-18:27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.29 | 53.29 | 5432.99 | 10241.39 | 31-AUG-18:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.14 | 53.14 | 5480.15 | 10432.76 | 29-SEP-18:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.88 | 51.88 | 5575.11 | 10647.17 | 31-OCT-18:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.39 | 53.39 | 5686.70 | 10845.91 | 29-NOV-07:35 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 52.98 | 58.75 | 5756.92 | 10965.92 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 5583.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.88 | 51.88 | 5336.22 | 10121.71 | ||
Maximum of Months | 0.00 | 0.00 | 54.02 | 59.54 | 5787.69 | 10979.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.364479E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.358203E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.429636E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.499802E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.588545E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.567938E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.428186E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.518553E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.485290E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.457559E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.408146E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.372312E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.547865E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.358203E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.588545E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.212639E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.204889E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.247425E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.275611E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.303534E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.291675E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.259566E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.286177E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.272588E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.268406E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.240391E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.220603E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.308350E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.204889E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.303534E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.725390E+10 | 0.110988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.693514E+10 | 0.109446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807029E+10 | 0.132537E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.927353E+10 | 0.156871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110823E+11 | 0.184629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107179E+11 | 0.177953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808408E+10 | 0.134603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.981962E+10 | 0.163992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.915366E+10 | 0.153522E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.868196E+10 | 0.145052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.784480E+10 | 0.128065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.738559E+10 | 0.114576E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104303E+12 | 0.171223E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.693514E+10 | 0.109446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110823E+11 | 0.184629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.303066E+10 | 0.785265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287861E+10 | 0.755003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347868E+10 | 0.911003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394954E+10 | 0.101550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.439326E+10 | 0.111591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.421972E+10 | 0.107314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.370041E+10 | 0.969941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414339E+10 | 0.106610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.393515E+10 | 0.101608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386284E+10 | 0.100639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343795E+10 | 0.898479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316211E+10 | 0.818100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441923E+11 | 0.114309E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287861E+10 | 0.755003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.439326E+10 | 0.111591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.725390E+10 | 0.00 | 0.00 | 0.00 | 0.291940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.693514E+10 | 0.00 | 0.00 | 0.00 | 0.288852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807029E+10 | 0.00 | 0.00 | 0.00 | 0.348933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.927353E+10 | 0.00 | 0.00 | 0.00 | 0.407067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110823E+11 | 0.00 | 0.00 | 0.00 | 0.477721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107179E+11 | 0.00 | 0.00 | 0.00 | 0.460759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808408E+10 | 0.00 | 0.00 | 0.00 | 0.347345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.981962E+10 | 0.00 | 0.00 | 0.00 | 0.420357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.915366E+10 | 0.00 | 0.00 | 0.00 | 0.393753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.868196E+10 | 0.00 | 0.00 | 0.00 | 0.370739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.784480E+10 | 0.00 | 0.00 | 0.00 | 0.329698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.738559E+10 | 0.00 | 0.00 | 0.00 | 0.298456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104303E+12 | 0.00 | 0.00 | 0.00 | 0.443562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.693514E+10 | 0.00 | 0.00 | 0.00 | 0.288852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110823E+11 | 0.00 | 0.00 | 0.00 | 0.477721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.303066E+10 | 0.00 | 0.00 | 0.00 | 0.182333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287861E+10 | 0.00 | 0.00 | 0.00 | 0.176103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347868E+10 | 0.00 | 0.00 | 0.00 | 0.212638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394954E+10 | 0.00 | 0.00 | 0.00 | 0.236115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.439326E+10 | 0.00 | 0.00 | 0.00 | 0.259602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.421972E+10 | 0.00 | 0.00 | 0.00 | 0.249478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.370041E+10 | 0.00 | 0.00 | 0.00 | 0.222562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414339E+10 | 0.00 | 0.00 | 0.00 | 0.244743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.393515E+10 | 0.00 | 0.00 | 0.00 | 0.233236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386284E+10 | 0.00 | 0.00 | 0.00 | 0.229777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343795E+10 | 0.00 | 0.00 | 0.00 | 0.206012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316211E+10 | 0.00 | 0.00 | 0.00 | 0.188982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441923E+11 | 0.00 | 0.00 | 0.00 | 0.264158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287861E+10 | 0.00 | 0.00 | 0.00 | 0.176103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.439326E+10 | 0.00 | 0.00 | 0.00 | 0.259602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 479203.54 | 0.413984E+11 | 0.00 | 3828748.67 | 45928433.75 | 0.00 | 0.428686E+09 | 0.00 | 3.80 |
February | 0.00 | 0.438074E+11 | 0.00 | 804773.74 | 50122523.05 | 0.00 | 54298948.65 | 0.00 | 3.82 |
March | 0.00 | 0.575587E+11 | 0.00 | 0.00 | 68085251.88 | 0.00 | 0.00 | 0.00 | 3.89 |
April | 0.00 | 0.791235E+11 | 0.00 | 0.00 | 78012668.22 | 0.00 | 0.00 | 0.00 | 3.98 |
May | 0.00 | 0.100578E+12 | 0.00 | 0.00 | 80095410.68 | 0.00 | 0.00 | 0.00 | 4.02 |
June | 0.00 | 0.955986E+11 | 0.00 | 0.00 | 78707134.95 | 0.00 | 0.00 | 0.00 | 4.01 |
July | 0.00 | 0.612442E+11 | 0.00 | 0.00 | 68324739.48 | 0.00 | 0.00 | 0.00 | 3.92 |
August | 0.00 | 0.843809E+11 | 0.00 | 0.00 | 72062715.06 | 0.00 | 0.00 | 0.00 | 3.98 |
September | 0.00 | 0.772814E+11 | 0.00 | 0.00 | 74789667.55 | 0.00 | 0.00 | 0.00 | 3.97 |
October | 0.00 | 0.700157E+11 | 0.00 | 0.00 | 72478989.92 | 0.00 | 0.00 | 0.00 | 3.94 |
November | 0.00 | 0.570701E+11 | 0.00 | 379536.76 | 60965755.20 | 0.00 | 24550001.23 | 0.00 | 3.87 |
December | 424845.70 | 0.444176E+11 | 0.00 | 1885771.46 | 46234512.02 | 0.00 | 0.219263E+09 | 0.00 | 3.80 |
Annual Sum or Average | 904049.23 | 0.812474E+12 | 0.00 | 6898830.62 | 0.795808E+09 | 0.00 | 0.726798E+09 | 0.00 | 3.92 |
Minimum of Months | 0.00 | 0.413984E+11 | 0.00 | 0.00 | 45928433.75 | 0.00 | 0.00 | 0.00 | 3.80 |
Maximum of Months | 479203.54 | 0.100578E+12 | 0.00 | 3828748.67 | 80095410.68 | 0.00 | 0.428686E+09 | 0.00 | 4.02 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.273444E+11 | 0.00 | 10040773.26 | 0.00 | 0.00 | 0.882826E+09 | 0.00 | 9.47 |
February | 0.00 | 0.280303E+11 | 0.00 | 4301163.76 | 0.00 | 0.00 | 0.163601E+09 | 0.00 | 9.58 |
March | 0.00 | 0.379118E+11 | 0.00 | 138671.15 | 0.00 | 0.00 | 1176802.71 | 0.00 | 9.87 |
April | 0.00 | 0.490915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
May | 0.00 | 0.575658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 |
June | 0.00 | 0.545834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 |
July | 0.00 | 0.443364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 |
August | 0.00 | 0.535412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 |
September | 0.00 | 0.501836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
October | 0.00 | 0.488176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 |
November | 0.00 | 0.398513E+11 | 0.00 | 928925.91 | 0.00 | 0.00 | 77987232.00 | 0.00 | 9.87 |
December | 249636.55 | 0.308670E+11 | 0.00 | 6568464.23 | 0.00 | 0.00 | 0.558506E+09 | 0.00 | 9.51 |
Annual Sum or Average | 249636.55 | 0.522124E+12 | 0.00 | 21977998.31 | 0.00 | 0.00 | 0.168410E+10 | 0.00 | 10.11 |
Minimum of Months | 0.00 | 0.273444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 |
Maximum of Months | 249636.55 | 0.575658E+11 | 0.00 | 10040773.26 | 0.00 | 0.00 | 0.882826E+09 | 0.00 | 10.74 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:50
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.851227E+11 | -0.509983E+10 | -0.950566E+11 | -0.167155E+10 | 0.263834E+12 |
February | 0.881333E+11 | -0.562388E+10 | -0.101396E+12 | -0.183763E+10 | 0.257425E+12 |
March | 0.122395E+12 | -0.708572E+10 | -0.133738E+12 | -0.235069E+10 | 0.309303E+12 |
April | 0.122139E+12 | -0.102901E+11 | -0.172964E+12 | -0.269140E+10 | 0.351728E+12 |
May | 0.120642E+12 | -0.150306E+11 | -0.204831E+12 | -0.348236E+10 | 0.399275E+12 |
June | 0.124534E+12 | -0.139607E+11 | -0.196286E+12 | -0.316682E+10 | 0.384959E+12 |
July | 0.103351E+12 | -0.844862E+10 | -0.149417E+12 | -0.252108E+10 | 0.314777E+12 |
August | 0.132021E+12 | -0.134582E+11 | -0.186972E+12 | -0.278114E+10 | 0.364587E+12 |
September | 0.100882E+12 | -0.114992E+11 | -0.174700E+12 | -0.265648E+10 | 0.344720E+12 |
October | 0.105590E+12 | -0.109724E+11 | -0.166816E+12 | -0.256536E+10 | 0.332087E+12 |
November | 0.838671E+11 | -0.873384E+10 | -0.137904E+12 | -0.218347E+10 | 0.296810E+12 |
December | 0.793892E+11 | -0.667700E+10 | -0.105372E+12 | -0.169087E+10 | 0.272029E+12 |
Annual Sum or Average | 0.126807E+13 | -0.116880E+12 | -0.182545E+13 | -0.295989E+11 | 0.389153E+13 |
Minimum of Months | 0.793892E+11 | -0.150306E+11 | -0.204831E+12 | -0.348236E+10 | 0.257425E+12 |
Maximum of Months | 0.132021E+12 | -0.509983E+10 | -0.950566E+11 | -0.167155E+10 | 0.399275E+12 |