Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26

Tabular Output Report in Format: HTML

Building: RestaurantSitDown

Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650

Simulation Timestamp: 2023-10-16 08:26:56


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1711.04 3347.41 3347.41
Net Site Energy 1711.04 3347.41 3347.41
Total Source Energy 3526.64 6899.39 6899.39
Net Source Energy 3526.64 6899.39 6899.39


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.15
Net Conditioned Building Area 511.15
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 172.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 100.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 38.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 17.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 413.14 444.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 121.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 75.47 291.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2201.28
Refrigeration 36.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 802.63 908.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2201.28
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 172.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 100.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 38.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 17.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment Cooking 394.51 444.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 9.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 121.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 75.47 291.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 825.43
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1375.86
Refrigeration General 6.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 11.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 18.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 172.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 100.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 38.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 17.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 413.14 444.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 121.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 75.47 291.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2201.28
Refrigeration Unassigned 36.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 108.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 581.84 907.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.31
Other 879.66 869.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 1570.23 1777.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.31


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 108.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 581.84 907.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.31
Other 879.66 869.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 1570.23 1777.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.31


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 802.630 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 802.630 100.00
     
Total On-Site and Utility Electric Sources 802.630 100.00
Total Electricity End Uses 802.630 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2201.28 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2201.28 100.00
Total Water End Uses 2201.28 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.17
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3668.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE

| Environment |

ZoneCoolingSummaryMonthly

| DINING | KITCHEN | ATTIC |

ZoneHeatingSummaryMonthly

| DINING | KITCHEN | ATTIC |

ZoneElectricSummaryMonthly

| DINING | KITCHEN |

SpaceGainsMonthly

| DINING | KITCHEN | ATTIC |

PeakSpaceGainsMonthly

| DINING | KITCHEN | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| DINING | KITCHEN | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| DINING | KITCHEN | ATTIC |

ComfortReportSimple55Monthly

| DINING | KITCHEN | ATTIC |

OccupantComfortDataSummaryMonthly

| DINING PEOPLE | KITCHEN PEOPLE |

DXReportMonthly

| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |

WindowReportMonthly

| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| DINING | KITCHEN | ATTIC |

WindowEnergyZoneSummaryMonthly

| DINING | KITCHEN | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| DINING | KITCHEN | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

MechanicalVentilationLoadsMonthly

| DINING | KITCHEN |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
RunPeriod RUNPERIOD 1
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [m] 1619.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 275.72 68.93 68.93 68.93 68.93
Above Ground Wall Area [m2] 275.72 68.93 68.93 68.93 68.93
Window Opening Area [m2] 47.17 0.00 13.93 19.30 13.93
Gross Window-Wall Ratio [%] 17.11 0.00 20.22 28.00 20.22
Above Ground Window-Wall Ratio [%] 17.11 0.00 20.22 28.00 20.22


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 275.72 68.93 68.93 68.93 68.93
Above Ground Wall Area [m2] 275.72 68.93 68.93 68.93 68.93
Window Opening Area [m2] 47.17 0.00 13.93 19.30 13.93
Gross Window-Wall Ratio [%] 17.11 0.00 20.22 28.00 20.22
Above Ground Window-Wall Ratio [%] 17.11 0.00 20.22 28.00 20.22


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 569.51
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
DINING 371.75 Yes Yes 1133.39 1.00 169.19 0.00 47.17 47.17 5.1620 1.33 61.4214
KITCHEN 139.41 Yes Yes 425.02 1.00 106.53 0.00 0.00 0.00 8.3591 18.52 1000.6314
ATTIC 511.15 No No 856.26 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.15     1558.40   275.72 0.00 47.17 47.17 6.0339 1.78 317.5692
Conditioned Total 511.15     1558.40   275.72 0.00 47.17 47.17 6.0339 1.78 317.5692
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 511.15     856.26   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
DINING 371.75 Yes Yes 1.00 DINING GENERAL DINING 5.1620 1.33 61.4214  
KITCHEN 139.41 Yes Yes 1.00 KITCHEN GENERAL KITCHEN 8.3591 18.52 1000.6314  
ATTIC 511.15 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.15             6.0339 0.89 317.5692  
Conditioned Total 511.15             6.0339 0.89 317.5692  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 511.15             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.15 511.15 0.00 511.15 6.0339 1.78 317.5692
Total 511.15 511.15 0.00 511.15      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 21-JUL-17:19 15-DEC-07:49 - - - - - - - - - - 30-JAN-07:00
Heating 0.00 61108.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 25153.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1677.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 18837.19 12843.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6946.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 17.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4443.75 23541.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1144.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 58220.62 97494.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 61108.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 25153.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1677.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment Cooking 18246.39 12843.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 313.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 6946.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 17.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4443.75 23541.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 193.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 361.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 589.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 187.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 316.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 121.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 54.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1308.43 481.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 384.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 239.02 315.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 115.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2541.93 984.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 366.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 620.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 237.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 106.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2559.75 942.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 752.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 467.61 617.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 226.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4972.93 1926.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 366.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 620.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 237.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 106.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2559.75 942.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 752.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 467.61 617.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 226.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4972.93 1926.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
DINING DIRECT AIR 4.09
KITCHEN DIRECT AIR 1.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC_1:1 4.09 4.09 4.09 4.09 4.09 4.09 1.00 1.00 4.09
PSZ-AC_2:2 1.69 1.69 1.69 1.69 1.69 1.69 1.00 1.000000 1.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC_1:1_OA_CONTROLLER 4.09 1.33
PSZ-AC_2:2_OA_CONTROLLER 1.69 1.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC_1:1_ADDAQ FAN 4.09 6990.97
PSZ-AC_2:2_ADDAQ FAN 1.69 1807.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC_1:1_UNITARY_PACKAGE_DX 4.09 4.09 4.09 2.70 76549.68 115663.00 40.00 1.00
PSZ-AC_2:2_UNITARY_PACKAGE_DX 1.69 1.69 1.69 1.11 37504.13 76795.51 40.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC_1:1 COOLING COIL 4.09 2.05 2.73 76549.68 38274.84 0.800300 0.800300
PSZ-AC_2:2 COOLING COIL 1.69 0.844375 1.13 37504.13 18752.06 0.737040 0.737040
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC_1:1 HEATING COIL 115663.00
PSZ-AC_2:2 HEATING COIL 76795.51
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000140 0.016782
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000140 17.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000140
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
DINING_WALL_EAST DINING_WALL_EAST_WINDOW |
DINING_WALL_SOUTH DINING_WALL_SOUTH_WINDOW |
DINING_WALL_WEST DINING_WALL_WEST_WINDOW |
KITCHEN_WALL_EAST KITCHEN_WALL_EAST_DOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.70 7.00 2.10 2.60 4.30 8.80 13.90 17.80 23.20 25.60 24.10 20.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 35.04 -106.62 -7.00 1619.00 83328 0.9904


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 13.63 23.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 RestaurantSitDown 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 3 24 4


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 DINING 0.0 0.00 0.00 0.00 11.30 8.22 1.52 1 1 1 0.00 22.61 0.00 16.44 0.00 3.05 3.05 1133.39 TARP DOE-2 371.75 169.19 122.02 47.17 6 3 0 Yes
2 KITCHEN 0.0 0.00 0.00 0.00 11.30 19.53 1.52 1 1 1 0.00 22.61 16.44 22.61 0.00 3.05 3.05 425.02 TARP DOE-2 139.41 106.53 104.58 0.00 6 1 0 Yes
3 ATTIC 0.0 0.00 0.00 3.05 11.30 11.30 3.92 1 1 1 0.00 22.61 0.00 22.61 3.05 6.82 1.88 856.26 TARP DOE-2 511.15 0.00 0.00 0.00 6 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 DINING 371.75 280.1 1.327 0.754 5.162 61.421 0.000 0.000 0.000 0.000 66.583 No
2 KITCHEN 139.41 7.5 18.518 5.400E-002 8.359 386.416 614.215 0.000 0.000 0.000 1008.991 No
3 ATTIC 511.15 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DINING PEOPLE BLDG_OCC_SCH DINING 371.75 280.1 280.1 0.754 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 280 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 KITCHEN PEOPLE BLDG_OCC_SCH KITCHEN 139.41 7.5 7.5 5.400E-002 18.518 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 DINING_LIGHTS LTG_SCH_DINING DINING 371.75 280.1 1918.948 5.162 6.850 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1918.948
2 KITCHEN_LIGHTS LTG_SCH_KITCHEN KITCHEN 139.41 7.5 1165.301 8.359 154.798 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1165.301


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 DINING_MISCELEC_EQUIP BLDG_EQUIP_SCH DINING 371.75 280.1 22833.282 61.421 81.506 0.250 0.300 0.000 0.450 Cooking 0.000 6621.652
2 KITCHEN_MISCELEC_EQUIP BLDG_EQUIP_SCH KITCHEN 139.41 7.5 53277.659 382.178 7077.360 0.250 0.300 0.200 0.250 Cooking 0.000 15450.521
3 KITCHEN_REACH-IN-FREEZER ALWAYS_ON KITCHEN 139.41 7.5 277.500 1.991 36.863 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
4 KITCHEN_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN 139.41 7.5 313.300 2.247 41.619 0.000 0.250 0.000 0.750 ReachInRefrigerator 313.300 313.300


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 KITCHEN_MISCGAS_EQUIP REST_GAS_EQUIP_SCH KITCHEN 139.41 7.5 85624.808 614.215 11374.329 0.100 0.200 0.700 0.000 Cooking 0.000 24831.194


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 ATTICROOFDECK 6 2 4 0.167 4.706 0.900 0.900 0.700 0.700 VeryRough
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 17 2 4 0.167 0.1220 0.900 0.900 0.700 0.700 MediumSmooth
6 NONRES_ROOF_FLOOR 20 2 4 0.167 0.1220 0.900 0.900 0.700 0.700 MediumSmooth
7 NONRES_EXT_WALL_GRD 23 4 7 0.167 0.6101 0.900 0.900 0.700 0.700 Smooth
8 DINING_FLOOR_FFACTOR 42 2 7 0.167 0.1372 0.000 0.900 0.000 0.700 MediumRough
9 KITCHEN_FLOOR_FFACTOR 43 2 7 0.167 0.2338 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 F12 ASPHALT SHINGLES 0.0032 0.040 1120.000 1260.000 0.8000E-01
4 G02 16MM PLYWOOD 0.0159 0.120 544.000 1210.000 0.1325
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 8.098
8 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
9 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
10 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 8.098
11 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
12 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.405
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 7.210
16 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
17 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 4.201
18 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 4 0.12552254E-09 0.24226224E-10 0.35972174E-10 -0.14154396E-16
14 3 -0.27173896E-03 0.71777257E-04 -0.16206070E-03 0.11981077E-09
15 2 0.48258702 0.15872105 0.47241503 -0.16497355E-03
16 1 -7.8004821 2.4804491 -9.1443147 0.17387321
17 0 11.206599 1.2491899 12.560494  
18 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
19 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
20 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
21 1 -12.650482 3.3590720 -12.650482 0.19281313
22 0 16.907513 1.4507143 16.907513  
23 4 0.25903459E-16 0.19239208E-15 0.93419673E-14 -0.39937941E-16
24 3 -0.10578823E-07 0.88928291E-07 -0.59588315E-04 0.16456517E-12
25 2 0.61888179E-04 0.18849407E-02 1.1838695 -0.78434093E-04
26 1 -0.42954685E-01 0.47924477E-01 -17.374032 0.34435663
27 0 0.12288071 0.30178399E-01 16.270210  
28 4 0.93419673E-14 0.19239208E-15 0.25903459E-16 -0.39937941E-16
29 3 -0.59588315E-04 0.88928291E-07 -0.10578823E-07 0.16456517E-12
30 2 1.1838695 0.18849407E-02 0.61888179E-04 -0.78434093E-04
31 1 -17.374032 0.47924477E-01 -0.42954685E-01 0.34435663
32 0 16.270210 0.30178399E-01 0.12288071  
33 7 -0.34852869E-12 0.10767080E-14 -0.10727634E-12 0.10262983E-15
34 6 0.30635964E-07 0.17490336E-09 0.70016311E-08 -0.14578175E-12
35 5 -0.20003106E-03 0.14786583E-05 -0.10274732E-03 0.69151120E-08
36 4 0.30368338 0.71182556E-03 0.10383607 -0.35206551E-04
37 3 -7.4946273 0.21838569E-01 -2.4066693 0.30128323E-01
38 2 41.623882 0.76964729E-01 15.542587 -0.34172504
39 1 -81.122404 0.34464383E-01 -29.390349 1.0909075
40 0 46.824335 0.68808141E-03 16.285368  
41 7 -0.30956576E-08 -0.21303207E-14 0.16211864E-14 -0.47943075E-16
42 6 0.39621431E-05 0.26242558E-08 0.31947295E-02 -0.26800069E-04
43 5 -0.27788690E-03 0.15515089E-05 -0.22400076 0.19585881E-02
44 4 0.63462498E-02 0.70567942E-04 4.8341454 -0.45309197E-01
45 3 -0.55586032E-01 0.56073102E-03 -38.047399 0.39894095
46 2 0.19717555 0.93224475E-03 116.53452 -1.4186157
47 1 -0.28446589 0.28372391E-03 -143.93707 2.0495292
48 0 0.13865977 0.68942715E-05 60.838472  
49 7 -0.17992014E-08 -0.42643710E-15 0.60732754E-14 -0.80508795E-16
50 6 0.65450224E-05 0.44811019E-08 0.31871723E-02 -0.26736672E-04
51 5 -0.47085772E-03 0.26548585E-05 -0.22357125 0.19547969E-02
52 4 0.10832139E-01 0.12085242E-03 4.8269919 -0.45240433E-01
53 3 -0.95125865E-01 0.96112441E-03 -38.006990 0.39849429
54 2 0.33777835 0.15989493E-02 116.45587 -1.4175637
55 1 -0.48753632 0.48725992E-03 -143.89078 2.0487682
56 0 0.23769862 0.11769722E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359 38 1 VerySmooth 2.057 2.057 1.000 0.360    
2 NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 39 1 VerySmooth 2.057 2.057 1.000 0.360    
3 NONRESWINDOW_U_0.362_SHGC_EAST_0.359 40 1 VerySmooth 2.057 2.057 1.000 0.360    
4 NONRESWINDOW_U_0.362_SHGC_WEST_0.359 41 1 VerySmooth 2.057 2.057 1.000 0.360    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SOUTH SpectralAverage   3.63679E-002 0.27216 0.52074 0.52074 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11599 1.00000 No
2 NONRES WINDOW GLAZING LAYER NORTH SpectralAverage   3.63679E-002 0.27216 0.52074 0.52074 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11599 1.00000 No
3 NONRES WINDOW GLAZING LAYER EAST SpectralAverage   3.63679E-002 0.27216 0.52074 0.52074 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11599 1.00000 No
4 NONRES WINDOW GLAZING LAYER WEST SpectralAverage   3.63679E-002 0.27216 0.52074 0.52074 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11599 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 DINING 3 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 DINING 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.510
2 RACK2 1 0 Zone Air-Cooled 7.290


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.7570 58614.2 0.884 0.3002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 DINING_WALL_EAST 0 68.93 70.04 3.05 0 3.05 55.49 19.04 0.28 3 No No
2 DINING_WALL_EAST_WINDOW 0 68.93 70.04 3.05 0 3.05 55.49 19.04 0.28 2 No No
3 DINING_WALL_SOUTH 0 129.19 59.48 6.82 0 3.05 55.49 19.04 0.28 3 No No
4 DINING_WALL_SOUTH_WINDOW 0 129.19 59.48 6.82 0 3.05 55.49 19.04 0.28 2 No No
5 DINING_WALL_WEST 0 68.93 51.32 3.05 0 3.05 55.49 19.04 0.28 3 No No
6 DINING_WALL_WEST_WINDOW 0 68.93 51.32 3.05 0 3.05 55.49 19.04 0.28 2 No No
7 DINING_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 55.49 19.04 0.28 0 No No
8 DINING_FLOOR 0 0.00 0.00 0.00 0 3.05 55.49 19.04 0.28 0 No No
9 DINING_CEILING 0 0.00 0.00 0.00 0 3.05 55.49 19.04 0.28 0 No No
10 DINING_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 55.49 19.04 0.28 0 No No
11 KITCHEN_WALL_NORTH 0 129.19 77.58 6.82 0 3.05 34.94 9.69 0.00 0 No No
12 KITCHEN_WALL_EAST 0 68.93 70.04 3.05 0 3.05 34.94 9.69 0.00 0 No No
13 KITCHEN_WALL_EAST_DOOR 0 68.93 70.04 3.05 0 3.05 34.94 9.69 0.00 0 No No
14 KITCHEN_WALL_WEST 0 68.93 51.32 3.05 0 3.05 34.94 9.69 0.00 0 No No
15 DINING_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 3.05 34.94 9.69 0.00 0 No No
16 KITCHEN_FLOOR 0 0.00 0.00 0.00 0 3.05 34.94 9.69 0.00 0 No No
17 KITCHEN_CEILING 0 0.00 0.00 0.00 0 3.05 34.94 9.69 0.00 0 No No
18 KITCHEN_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 34.94 9.69 0.00 0 No No
19 ATTIC-FLOOR-DINNING 0 0.00 0.00 0.00 0 1.88 0.00 22.61 -999.00 0 No No
20 ATTIC-FLOOR-KITCHEN 0 0.00 0.00 0.00 0 1.88 0.00 22.61 -999.00 0 No No
21 SOUTH-ROOF 0 129.19 59.48 6.82 0 1.88 0.00 22.61 -999.00 0 No No
22 NORTH-ROOF 0 129.19 77.58 6.82 0 1.88 0.00 22.61 -999.00 0 No No
23 WEST-ROOF 0 448.99 90.43 3.77 0 1.88 0.00 22.61 -999.00 0 No No
24 EAST-ROOF 0 448.99 90.43 3.77 0 1.88 0.00 22.61 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 DINING_INFILTRATION INFIL_SCH_PNNL DINING 371.75 280.1 3.373E-002 9.073E-005 1.994E-004 0.107 0.000 0.000 0.224 0.000
2 DINING_DOOR_INFILTRATION VESTIBULE_DOOR_INFIL_SCH DINING 371.75 280.1 0.390 1.049E-003 2.304E-003 1.238 1.000 0.000 0.000 0.000
3 KITCHEN_INFILTRATION INFIL_SCH_PNNL KITCHEN 139.41 7.5 2.124E-002 1.523E-004 1.958E-004 0.180 0.000 0.000 0.224 0.000
4 ATTIC_INFILTRATION ALWAYS_ON ATTIC 511.15 0.0 0.238 4.652E-004 4.176E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 DINING Mixing/Well-Stirred
2 KITCHEN Mixing/Well-Stirred
3 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone DINING 1.2000
3 Zone KITCHEN 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone DINING 1.2000
3 Zone KITCHEN 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.4838E-003
2 Clear Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 1.4942E-002
3 Clear Turbid Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.3517E-003
4 Clear Turbid Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 1.2673E-002
5 Intermediate Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.2825E-003
6 Intermediate Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 1.2636E-002
7 Overcast Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.0691E-003
8 Overcast Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 9.8802E-003
9 Clear Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 5.0399E-002
10 Clear Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 5.0217E-002
11 Clear Turbid Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 5.6322E-002
12 Clear Turbid Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 5.6105E-002
13 Intermediate Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 2.9570E-002
14 Intermediate Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 2.9490E-002
15 Overcast Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 1.0123E-002
16 Overcast Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 1.0123E-002
17 Clear Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 1.4704E-002
18 Clear Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.4543E-003
19 Clear Turbid Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 1.2377E-002
20 Clear Turbid Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.3146E-003
21 Intermediate Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 1.2315E-002
22 Intermediate Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.2558E-003
23 Overcast Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 9.8802E-003
24 Overcast Sky 12/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.0691E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 DINING Cooling 38456.22384 46147.46861 3.40970 4.09164 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 34.96500 5.69918E-003 371.74807 280.14173 1.33138 0.00000
2 DINING Heating 5922.61713 7107.14055 0.30865 1.33138 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 -7.90000 2.34317E-003 371.74807 280.14173 1.33138 0.00000
3 KITCHEN Cooling 18707.25001 22448.70002 1.40729 1.68875 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 33.88500 5.69749E-003 139.40524 7.52790 1.21700 0.00000
4 KITCHEN Heating 0.00000 0.00000 0.00000 1.21700 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -7.90000 2.34317E-003 139.40524 7.52790 1.21700 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC_1:1 Cooling Sensible 60269.55 4.09164 4.09164 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC_1:1 Heating Sensible 63468.20 1.33138 1.33138 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC_2:2 Cooling Sensible 32138.61 1.68875 1.68875 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC_2:2 Heating Sensible 58015.80 1.21700 1.21700 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat DINING DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.09164
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat KITCHEN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.68875
3 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.09164
4 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.09164
5 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 4.09164
6 AirLoopHVAC PSZ-AC_1:1 Adjusted Heating Design Air Flow Rate [m3/s] 4.09164
7 AirLoopHVAC PSZ-AC_1:1 Adjusted Cooling Design Air Flow Rate [m3/s] 4.09164
8 AirLoopHVAC PSZ-AC_1:1 Adjusted Main Design Air Flow Rate [m3/s] 4.09164
9 AirLoopHVAC PSZ-AC_1:1 User Heating Air Flow Ratio [] 1.00000
10 AirLoopHVAC PSZ-AC_1:1 Calculated Heating Air Flow Ratio [] 1.00000
11 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.68875
12 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.68875
13 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.68875
14 AirLoopHVAC PSZ-AC_2:2 Adjusted Heating Design Air Flow Rate [m3/s] 1.68875
15 AirLoopHVAC PSZ-AC_2:2 Adjusted Cooling Design Air Flow Rate [m3/s] 1.68875
16 AirLoopHVAC PSZ-AC_2:2 Adjusted Main Design Air Flow Rate [m3/s] 1.68875
17 AirLoopHVAC PSZ-AC_2:2 User Heating Air Flow Ratio [] 1.00000
18 AirLoopHVAC PSZ-AC_2:2 Calculated Heating Air Flow Ratio [] 1.00000
19 AirLoopHVAC PSZ-AC_1:1 Design Supply Air Flow Rate [m3/s] 4.09164
20 AirLoopHVAC PSZ-AC_2:2 Design Supply Air Flow Rate [m3/s] 1.68875
21 Controller:OutdoorAir PSZ-AC_1:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.09164
22 Controller:OutdoorAir PSZ-AC_1:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.33138
23 Fan:SystemModel PSZ-AC_1:1_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 4.09164
24 Fan:SystemModel PSZ-AC_1:1_ADDAQ FAN Design Electric Power Consumption [W] 6990.97221
25 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 4.09164
26 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 4.09164
27 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 4.09164
28 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 2.70048
29 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 4.09164
30 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 2.04582
31 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 2.72776
32 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 76549.68000
33 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 38274.84000
34 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80030
35 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80030
36 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 76549.68000
37 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 115662.99923
38 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
39 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
40 Coil:Heating:Fuel PSZ-AC_1:1 HEATING COIL Design Size Nominal Capacity [W] 115662.99923
41 Controller:OutdoorAir PSZ-AC_2:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.68875
42 Controller:OutdoorAir PSZ-AC_2:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.21700
43 Fan:SystemModel PSZ-AC_2:2_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.68875
44 Fan:SystemModel PSZ-AC_2:2_ADDAQ FAN Design Electric Power Consumption [W] 1807.04154
45 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.68875
46 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.68875
47 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.68875
48 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.11457
49 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.68875
50 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.84437
51 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.12583
52 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 37504.13000
53 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 18752.06500
54 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.73704
55 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.73704
56 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 37504.13000
57 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 76795.50884
58 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
59 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
60 Coil:Heating:Fuel PSZ-AC_2:2 HEATING COIL Design Size Nominal Capacity [W] 76795.50884
61 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 1.39850E-004
62 PlantLoop SWHSYS1 Plant Loop Volume [m3] 1.67820E-002
63 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 1.39850E-004
64 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 17.86434
65 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 1.39850E-004


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL 73578.4     10.30 10.25  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL 36292.7     11.64 11.58  


Zone Surfaces

Zone Name # Surfaces
1 DINING 10
2 KITCHEN 8
3 ATTIC 6


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 DINING_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.610 0.559   36.20 50.13 36.20 90.00 90.00 16.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 DINING_WALL_EAST_WINDOW Window DINING_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.362_SHGC_EAST_0.359 N/A 2.057 No 13.93 13.93 13.93 90.00 90.00 15.24 0.91 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 DINING_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.610 0.559   49.63 68.93 49.63 180.00 90.00 22.61 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 DINING_WALL_SOUTH_WINDOW Window DINING_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359 N/A 2.057 No 19.30 19.30 19.30 180.00 90.00 21.10 0.91 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 DINING_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.610 0.559   36.20 50.13 36.20 270.00 90.00 16.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 DINING_WALL_WEST_WINDOW Window DINING_WALL_WEST Window5 Detailed Fenestration NONRESWINDOW_U_0.362_SHGC_WEST_0.359 N/A 2.057 No 13.93 13.93 13.93 270.00 90.00 15.24 0.91 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 DINING_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   68.93 68.93 68.93 0.00 90.00 22.61 3.05 0.00 DINING_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
8 DINING_FLOOR Floor   CTF - ConductionTransferFunction DINING_FLOOR_FFACTOR 0.137 0.133   371.75 371.75 371.75 0.00 180.00 22.61 16.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
9 DINING_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.122 0.119   371.75 371.75 371.75 180.00 0.00 22.61 16.44 0.00 ATTIC-FLOOR-DINNING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 DINING_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   743.50 743.50 743.50 0.00 90.00 743.50 1.00 0.00 DINING_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 KITCHEN_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.610 0.559   68.93 68.93 68.93 0.00 90.00 22.61 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 KITCHEN_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.610 0.559   16.85 18.80 16.85 90.00 90.00 6.17 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
13 KITCHEN_WALL_EAST_DOOR Door KITCHEN_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
14 KITCHEN_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.610 0.559   18.80 18.80 18.80 270.00 90.00 6.17 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
15 DINING_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   68.93 68.93 68.93 180.00 90.00 22.61 3.05 0.00 DINING_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 KITCHEN_FLOOR Floor   CTF - ConductionTransferFunction KITCHEN_FLOOR_FFACTOR 0.234 0.221   139.41 139.41 139.41 0.00 180.00 22.61 6.17 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 KITCHEN_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.122 0.119   139.41 139.41 139.41 180.00 0.00 22.61 6.17 0.00 ATTIC-FLOOR-KITCHEN Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 KITCHEN_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   278.81 278.81 278.81 0.00 90.00 278.81 1.00 0.00 KITCHEN_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 ATTIC-FLOOR-DINNING Floor   CTF - ConductionTransferFunction NONRES_ROOF_FLOOR 0.122 0.118   371.75 371.75 371.75 180.00 180.00 22.61 16.44 0.00 DINING_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
20 ATTIC-FLOOR-KITCHEN Floor   CTF - ConductionTransferFunction NONRES_ROOF_FLOOR 0.122 0.118   139.41 139.41 139.41 0.00 180.00 22.61 6.17 0.00 KITCHEN_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 SOUTH-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   60.26 60.26 60.26 180.00 45.00 12.50 22.61 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.15 0.85 0.15 0.85 3
22 NORTH-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   60.26 60.26 60.26 0.00 45.00 12.50 22.61 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.15 0.85 0.15 0.85 3
23 WEST-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   224.50 224.50 224.50 270.00 18.44 12.50 22.61 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 2.57E-002 0.97 2.57E-002 0.97 4
24 EAST-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   224.50 224.50 224.50 90.00 18.44 12.50 22.61 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 2.57E-002 0.97 2.57E-002 0.97 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 DINING RunPeriod: RUNPERIOD 1 0.1092518592 0.3058789898 Pass Pass 5.2288690359E-002 0.1221475095 Pass Pass
2 KITCHEN RunPeriod: RUNPERIOD 1 0.1920981068 0.6164088168 Pass Pass 2.6008093575E-002 8.2246440277E-002 Pass Pass
3 ATTIC RunPeriod: RUNPERIOD 1 0.4870565921 0.5128715149 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1209.07 91.06 1493.32 26.87 722.42 3542.74



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB -7.90 0.00 -7.90 Wetbulb [C] 3.20 0.00
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 35.10 13.50 15.70 Wetbulb [C] 4.40 220.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 9.00 6      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 5.00 4      
Nov 9.00 7      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.559 0.610 50.13 36.20 90.00 90.00 E
DINING_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.559 0.610 68.93 49.63 180.00 90.00 S
DINING_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.559 0.610 50.13 36.20 270.00 90.00 W
DINING_FLOOR DINING_FLOOR_FFACTOR 1.00 0.134 0.137 371.75 371.75 0.00 180.00  
KITCHEN_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.559 0.610 68.93 68.93 0.00 90.00 N
KITCHEN_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.559 0.610 18.80 16.85 90.00 90.00 E
KITCHEN_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.559 0.610 18.80 18.80 270.00 90.00 W
KITCHEN_FLOOR KITCHEN_FLOOR_FFACTOR 1.00 0.225 0.234 139.41 139.41 0.00 180.00  
SOUTH-ROOF ATTICROOFDECK 0.30 2.858 4.706 60.26 60.26 180.00 45.00  
NORTH-ROOF ATTICROOFDECK 0.30 2.858 4.706 60.26 60.26 0.00 45.00  
WEST-ROOF ATTICROOFDECK 0.30 2.858 4.706 224.50 224.50 270.00 18.44  
EAST-ROOF ATTICROOFDECK 0.30 2.858 4.706 224.50 224.50 90.00 18.44  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_NORTH INT_WALL 0.30 2.511 6.299 68.93 68.93 0.00 90.00 N
DINING_CEILING NONRES_ROOF 0.30 0.118 0.122 371.75 371.75 180.00 0.00  
DINING_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 68.93 68.93 180.00 90.00 S
KITCHEN_CEILING NONRES_ROOF 0.30 0.118 0.122 139.41 139.41 180.00 0.00  
ATTIC-FLOOR-DINNING NONRES_ROOF_FLOOR 0.30 0.118 0.122 371.75 371.75 180.00 180.00  
ATTIC-FLOOR-KITCHEN NONRES_ROOF_FLOOR 0.30 0.118 0.122 139.41 139.41 0.00 180.00  
DINING_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 743.50   0.00 90.00 N
KITCHEN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 278.81   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_EAST_WINDOW NONRESWINDOW_U_0.362_SHGC_EAST_0.359   13.93 0.00 0.00 13.93 13.93 2.057 0.360 0.396             No DINING_WALL_EAST 90.00 90.00 E
DINING_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359   19.30 0.00 0.00 19.30 19.30 2.057 0.360 0.396             No DINING_WALL_SOUTH 180.00 90.00 S
DINING_WALL_WEST_WINDOW NONRESWINDOW_U_0.362_SHGC_WEST_0.359   13.93 0.00 0.00 13.93 13.93 2.057 0.360 0.396             No DINING_WALL_WEST 270.00 90.00 W
Total or Average             47.17 2.057 0.360 0.396                      
North Total or Average             0.00 - - -                      
Non-North Total or Average             47.17 2.057 0.360 0.396                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
KITCHEN_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 KITCHEN_WALL_EAST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
DINING_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
DINING_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
DINING_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
DINING_LIGHTS DINING DINING GENERAL 5.1620 371.75 1918.95 LightsWired LTG_SCH_DINING 92.56 168.00 60.04 0.0000 Y 21.63
KITCHEN_LIGHTS KITCHEN KITCHEN GENERAL 8.3591 139.41 1165.30 LightsWired LTG_SCH_KITCHEN 79.77 168.00 76.30 0.0000 Y 16.69
Interior Lighting Total       6.0339 511.15 3084.25               38.32


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
DINING_DAYLREFPT1 DINING DINING_DAYLCTRL SplitFlux Continuous/Off 0.25 1918.95 479.74
DINING_DAYLREFPT2 DINING DINING_DAYLCTRL SplitFlux Continuous/Off 0.25 1918.95 479.74


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 204.54 AstronomicalClock -   48.81 48.81 1.87
EXTERIOR_LIGHTS_B 1305.94 AstronomicalClock -   83.71 62.76 15.39
Exterior Lighting Total 1510.48           17.26



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed   76549.68 61262.71 15286.97 0.80 3.40    
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed   37504.13 27642.04 9862.09 0.74 3.80    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC_1:1 COOLING COIL   73578.4     10.30 10.25  
PSZ-AC_2:2 COOLING COIL   36292.7     11.64 11.58  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel   115663.00 0.85
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel   76795.51 0.85


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
DINING EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 1.33 0.00 0.00 1.00 0.00 General    
KITCHEN EXHAUST FAN Fan:ZoneExhaust 0.39 124.50 2.55 824.13 323.38 1.00 1.42 General    
PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 0.60 1018.41 4.09 6990.97 1708.60 1.00 1.18 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 0.58 622.50 1.69 1807.04 1070.05 1.00 1.34 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000140 17.86 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.95 0.88 0.30



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
DINING 38456.22 46147.47 124.14 3.410 4.092 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.99 0.00852 34.97 0.00570 1.331 0.00
KITCHEN 18707.25 22448.70 161.03 1.407 1.689 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 26.00 25.99 0.00896 33.89 0.00570 1.217 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
DINING 5922.62 7107.14 19.12 0.309 1.331 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:30:00 21.00 21.00 0.00788 -7.90 0.00234 1.331 0.00
KITCHEN 0.00 0.00 0.00 0.000 1.217 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 19.00 19.63 0.00124 -7.90 0.00234 1.217 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC_1:1 4.09 4.09 1.33 1.33 4.0916 4.0916 4.0916 1.0000 1.0000
PSZ-AC_2:2 1.69 1.69 1.22 1.22 1.6887 1.6887 1.6887 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_1:1 76549.680 61262.709 4.091640 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 38274.84 35776.88 2.727760 27.60 14.86 0.00760496 11.11 8.17 0.00700000 35.10 0.00569938 15.77 48.8085 23.99 0.00852440 37.7631 38444.89 0.00 -999.00 -999.00
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_1:1 115662.999 115662.999 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 115663.00 115663.00 4.091642 11.60 7.42 0.00608139 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 32.5390 21.00 0.00788447 41.9307 5916.55 0.00 -999.00 -999.00
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_2:2 37504.130 27642.044 1.688750 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 18752.06 18752.06 1.125833 32.87 15.69 0.00649692 11.74 7.91 0.00649692 35.10 0.00569938 15.77 108.0979 25.98 0.00897168 35.2629 17818.59 0.00 -999.00 -999.00
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_2:2 76795.509 76795.509 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 76795.51 76795.51 1.688749 -5.69 -7.05 0.00204048 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 72.0653 19.94 0.00125962 7.2292 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_1:1 DINING Coincident CoolingDesignCapacity N/A No No unknown No 76549.680 61262.709 4.091640 -999.0 -999.000 -999.0000 1.00000 1.00000 1018.9772 1004.8586 0.9904 PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 4.091642 4.05239849   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 38274.84 35776.88 1.0000 2.70159776 2.727760 27.60 14.86 0.00760496 47147.4 11.11 8.17 0.00700000 28811.9 -999.0 -999.00 -999.00 -999.00 0.000 38274.84 35.10 0.00569938 15.77 1.33137743 48.8085 23.99 0.00852440 23.99 0.00852440 37.7631 38444.89 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_1:1 DINING Coincident HeatingDesignCapacity N/A Yes No unknown No 115662.999 115662.999 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 4.091642 4.05239849   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 115663.00 115663.00 1.0000 4.05239849 4.091642 11.60 7.42 0.00608139 26992.5 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 115663.00 -7.90 0.00234317 -7.90 1.33137743 32.5390 21.00 0.00788447 21.00 0.00788447 41.9307 5916.55 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_2:2 KITCHEN Coincident CoolingDesignCapacity N/A No No unknown No 37504.130 27642.044 1.688750 -999.0 -999.000 -999.0000 1.00000 1.00000 1016.9174 1004.8586 0.9904 PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 1.688749 1.67255229   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 Sensible 18752.06 18752.06 1.0000 1.11503535 1.125833 32.87 15.69 0.00649692 49672.1 11.74 7.91 0.00649692 28184.5 -999.0 -999.00 -999.00 -999.00 0.000 18752.06 35.10 0.00569938 15.77 1.21700195 108.0979 25.94 0.00897168 25.98 0.00897168 35.2629 17818.59 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_2:2 KITCHEN Coincident HeatingDesignCapacity N/A Yes No unknown No 76795.509 76795.509 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 1.688749 1.67255229   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 76795.51 76795.51 1.0000 1.67255229 1.688749 -5.69 -7.05 0.00204048 -639.2 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 76795.51 -7.90 0.00234317 -7.90 1.21700195 72.0653 0.00 0.00125962 19.94 0.00125962 7.2292 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PSZ-AC_1:1_OA_CONTROLLER DifferentialDryBulb 1.33 4.09 -      
PSZ-AC_2:2_OA_CONTROLLER DifferentialDryBulb 1.22 1.69 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
DINING 2963.67 3985.50 615.67
KITCHEN 4697.17 5809.17 3619.17
ATTIC 0.00 0.00 0.00
Facility 4744.83 6728.67 3668.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
DINING 1.17 13.50 0.17 0.00
KITCHEN 0.00 124.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1.17 136.50 0.17 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
DINING 118.20 280.14 1133.39 4.771 0.566 0.000 0.000
KITCHEN 3.18 7.53 425.02 9.748 0.011 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
DINING 118.20 280.14 1133.39 4.099 0.000 0.000 0.000
KITCHEN 3.18 7.53 425.02 9.213 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
DINING PSZ-AC_1:1 118.20 280.14 1133.39 371.75 1.3314 1.331
KITCHEN PSZ-AC_2:2 3.18 7.53 425.02 139.41 0.1826 0.112
Total Facility   121.38 287.67 1558.40 511.15 1.5140 1.443


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
DINING 39254297.44 0.00 39254297.44 4597532.95 43851830.39 41986318.57 1438.90 5461.64 1859.46 204.93
KITCHEN 30282345.32 0.00 30282345.32 55917.93 30338263.25 38379373.44 7811.01 939.66 9.33 511.48
Total Facility 69536642.76 0.00 69536642.76 4653450.88 74190093.64 80365692.01 7814.50 5465.30 1865.03 557.19


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
DINING 1.4865 0.0000 1.4865 0.1764 1.6629 1.3314 0.00 5361.88 1825.12
KITCHEN 1.1361 0.0000 1.1361 0.0013 1.1375 1.2170 6267.69 915.57 3.74
Total Facility 2.6227 0.0000 2.6227 0.1777 2.8004 2.5484 6267.69 5365.55 1827.02


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC_1:1 38504579.85 0.00 38504579.85 41986318.57 6900.21 17.82 1841.98 204.93
PSZ-AC_2:2 29703937.32 0.00 29703937.32 38379373.44 8750.67 1.04 8.30 511.39


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC_1:1 1.4581 0.0000 1.4581 1.3314 5361.55 16.34 1809.11
PSZ-AC_2:2 1.1144 0.0000 1.1144 1.2170 7183.26 0.89 2.85


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC_1:1 0.00 1486.04 452.34 5453.55 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC_2:2 0.00 0.00 330.97 1478.29 5889.14 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC_1:1 0.0000 1.9869 1.6343 1.3062 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC_2:2 0.0000 0.0000 1.1012 1.1676 1.1043 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Surfaces by Class

Total Outdoors
Wall 8 6
Floor 4 2
Roof 6 4
Internal Mass 2 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 3 3
Door 1 1
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 2
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 393
Defaulted Fields 276
Fields with Defaults 902
Autosized Fields 41
Autosizable Fields 97
Autocalculated Fields 30
Autocalculatable Fields 60



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
Electricity:Building 458.39 2350.73 01-JAN-01:20 26459.53 02-JAN-11:10
Electricity:Zone:DINING 139.98 534.11 01-JAN-01:20 7569.70 02-JAN-17:10
Electricity:SpaceType:GENERAL 451.46 2214.45 01-JAN-01:20 24316.43 02-JAN-11:10
InteriorLights:Electricity 38.32 110.04 01-JAN-01:20 2497.72 02-JAN-17:10
InteriorLights:Electricity:Zone:DINING 21.63 80.03 01-JAN-01:20 1639.63 02-JAN-17:10
InteriorLights:Electricity:SpaceType:GENERAL 38.32 110.04 01-JAN-01:20 2497.72 02-JAN-17:10
LightsWired:InteriorLights:Electricity 38.32 110.04 01-JAN-01:20 2497.72 02-JAN-17:10
LightsWired:InteriorLights:Electricity:Zone:DINING 21.63 80.03 01-JAN-01:20 1639.63 02-JAN-17:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 38.32 110.04 01-JAN-01:20 2497.72 02-JAN-17:10
Electricity:Zone:KITCHEN 318.41 1816.62 01-JAN-01:20 19025.40 02-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN 16.69 30.01 01-JAN-01:20 858.09 02-JAN-10:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN 16.69 30.01 01-JAN-01:20 858.09 02-JAN-10:10
InteriorEquipment:Electricity 413.14 2104.41 01-JAN-01:10 22638.52 01-JAN-11:10
InteriorEquipment:Electricity:Zone:DINING 118.35 454.08 01-JAN-01:10 6614.32 01-JAN-11:10
InteriorEquipment:Electricity:SpaceType:GENERAL 413.14 2104.41 01-JAN-01:10 22638.52 01-JAN-11:10
Cooking:InteriorEquipment:Electricity 394.51 1513.61 01-JAN-01:10 22047.72 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:Zone:DINING 118.35 454.08 01-JAN-01:10 6614.32 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 394.51 1513.61 01-JAN-01:10 22047.72 01-JAN-11:10
InteriorEquipment:Electricity:Zone:KITCHEN 294.79 1650.33 01-JAN-01:10 16024.20 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN 276.16 1059.53 01-JAN-01:10 15433.40 01-JAN-11:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 9.88 313.30 01-JAN-00:10 313.30 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN 9.88 313.30 01-JAN-00:10 313.30 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 9.88 313.30 01-JAN-00:10 313.30 01-JAN-00:10
Refrigeration:Electricity 36.50 595.54 05-FEB-23:30 2771.16 23-AUG-10:10
Refrigeration:Electricity:Zone:KITCHEN 6.93 85.78 01-JAN-23:30 2143.10 02-JAN-11:10
General:Refrigeration:Electricity 6.93 85.78 01-JAN-23:30 2143.10 02-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN 6.93 85.78 01-JAN-23:30 2143.10 02-JAN-11:10
Electricity:Plant 105.48 741.42 03-DEC-01:10 5838.34 31-JUL-18:30
LowTempRefrigeration:Refrigeration:Electricity 11.26 0.00 01-JAN-11:10 1035.33 22-AUG-03:20
MedTempRefrigeration:Refrigeration:Electricity 18.31 509.04 26-JAN-06:00 637.09 16-MAY-03:20
ElectricityPurchased:Facility 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
ElectricityPurchased:Plant 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
Cogeneration:ElectricityPurchased 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
General:Cogeneration:ElectricityPurchased 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
ElectricityNet:Plant 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
Cogeneration:ElectricityNet 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
General:Cogeneration:ElectricityNet 802.63 3811.86 06-FEB-01:30 58220.62 21-JUL-17:20
Electricity:HVAC 221.49 0.00 01-JAN-01:10 32415.11 21-JUL-17:10
Fans:Electricity 121.41 0.00 01-JAN-01:10 7000.40 21-JUL-17:10
General:Fans:Electricity 121.41 0.00 01-JAN-01:10 7000.40 21-JUL-17:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 100.08 0.00 01-JAN-00:10 25414.71 21-JUL-17:10
General:Cooling:Electricity 100.08 0.00 01-JAN-00:10 25414.71 21-JUL-17:10
ExteriorLights:Electricity 17.26 0.00 01-JAN-07:20 1510.48 01-JAN-06:10
General:ExteriorLights:Electricity 17.26 0.00 01-JAN-07:20 1510.48 01-JAN-06:10
WaterSystems:Electricity 75.47 0.00 01-JAN-01:10 4742.36 14-FEB-08:00
Water Heater:WaterSystems:Electricity 75.47 0.00 01-JAN-01:10 4742.36 14-FEB-08:00
Pumps:Electricity 0.45 0.00 01-JAN-01:10 17.86 08-JAN-00:10
General:Pumps:Electricity 0.45 0.00 01-JAN-01:10 17.86 08-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 908.41 2515.72 01-JAN-01:40 97494.47 15-DEC-07:50
NaturalGas:Building 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
NaturalGas:Zone:KITCHEN 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
NaturalGas:SpaceType:GENERAL 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
InteriorEquipment:NaturalGas 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
InteriorEquipment:NaturalGas:Zone:KITCHEN 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 444.42 1712.50 01-JAN-01:10 24831.19 01-JAN-11:10
NaturalGas:HVAC 172.88 0.00 01-JAN-01:10 70997.13 21-JAN-07:00
Heating:NaturalGas 172.88 0.00 01-JAN-01:10 70997.13 21-JAN-07:00
General:Heating:NaturalGas 172.88 0.00 01-JAN-01:10 70997.13 21-JAN-07:00
NaturalGas:Plant 291.11 803.23 03-JAN-01:10 25462.40 03-FEB-07:20
WaterSystems:NaturalGas 291.11 803.23 03-JAN-01:10 25462.40 03-FEB-07:20
Water Heater:WaterSystems:NaturalGas 291.11 803.23 03-JAN-01:10 25462.40 03-FEB-07:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 2201.28 0.00 01-JAN-01:10 0.00 30-JAN-08:00
Water:Plant 2201.28 0.00 01-JAN-01:10 0.00 30-JAN-08:00
WaterSystems:Water 2201.28 0.00 01-JAN-01:10 0.00 30-JAN-08:00
Water Heater:WaterSystems:Water 825.43 0.00 01-JAN-01:10 0.00 14-FEB-08:00
MainsWater:Facility 2201.28 0.00 01-JAN-01:10 0.00 30-JAN-08:00
MainsWater:Plant 2201.28 0.00 01-JAN-01:10 0.00 30-JAN-08:00
WaterSystems:MainsWater 2201.28 0.00 01-JAN-01:10 0.00 30-JAN-08:00
Water Heater:WaterSystems:MainsWater 825.43 0.00 01-JAN-01:10 0.00 14-FEB-08:00
WaterUse:WaterSystems:Water 1375.86 0.00 01-JAN-01:10 0.00 30-JAN-08:00
WaterUse:WaterSystems:MainsWater 1375.86 0.00 01-JAN-01:10 0.00 30-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1533.85 2931.09 15-DEC-01:10 143249.86 21-JUL-17:20
EnergyTransfer:Building 715.26 1465.54 15-DEC-01:10 47195.43 21-JUL-17:20
EnergyTransfer:Zone:KITCHEN 396.28 1465.54 15-DEC-01:10 21766.33 16-FEB-12:00
Refrigeration:EnergyTransfer 139.43 2620.93 05-FEB-23:30 7834.84 16-MAY-03:20
Refrigeration:EnergyTransfer:Zone:KITCHEN 69.72 1310.47 05-FEB-23:30 3917.42 16-MAY-03:20
General:Refrigeration:EnergyTransfer 69.72 1310.47 05-FEB-23:30 3917.42 16-MAY-03:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN 69.72 1310.47 05-FEB-23:30 3917.42 16-MAY-03:20
EnergyTransfer:Plant 311.35 1465.54 15-DEC-01:10 19333.32 13-FEB-19:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 12.09 0.00 01-JAN-11:10 1678.72 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 57.62 1305.23 26-JAN-06:00 2238.70 16-MAY-03:20
EnergyTransfer:Zone:DINING 318.98 0.00 01-JAN-01:10 29152.31 21-JUL-17:20
Heating:EnergyTransfer 0.35 0.00 01-JAN-00:10 9797.09 07-FEB-05:20
Heating:EnergyTransfer:Zone:DINING 0.35 0.00 01-JAN-00:10 9797.09 07-FEB-05:20
General:Heating:EnergyTransfer 0.35 0.00 01-JAN-00:10 9797.09 07-FEB-05:20
General:Heating:EnergyTransfer:Zone:DINING 0.35 0.00 01-JAN-00:10 9797.09 07-FEB-05:20
Cooling:EnergyTransfer 645.20 0.00 01-JAN-01:10 44999.68 21-JUL-17:20
Cooling:EnergyTransfer:Zone:DINING 318.63 0.00 01-JAN-01:10 29152.31 21-JUL-17:20
General:Cooling:EnergyTransfer 645.20 0.00 01-JAN-01:10 44999.68 21-JUL-17:20
General:Cooling:EnergyTransfer:Zone:DINING 318.63 0.00 01-JAN-01:10 29152.31 21-JUL-17:20
Heating:EnergyTransfer:Zone:KITCHEN 0.00 0.00 01-JAN-00:10 1545.52 28-DEC-05:10
General:Heating:EnergyTransfer:Zone:KITCHEN 0.00 0.00 01-JAN-00:10 1545.52 28-DEC-05:10
Cooling:EnergyTransfer:Zone:KITCHEN 326.57 0.00 01-JAN-01:10 19021.29 24-OCT-15:00
General:Cooling:EnergyTransfer:Zone:KITCHEN 326.57 0.00 01-JAN-01:10 19021.29 24-OCT-15:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 241.63 0.00 01-JAN-01:10 16943.77 06-FEB-07:40
PlantLoopHeatingDemand:Plant 241.63 0.00 01-JAN-01:10 16943.77 06-FEB-07:40
WaterSystems:PlantLoopHeatingDemand 241.63 0.00 01-JAN-01:10 16943.77 06-FEB-07:40
General:WaterSystems:PlantLoopHeatingDemand 241.63 0.00 01-JAN-01:10 16943.77 06-FEB-07:40
EnergyTransfer:HVAC 507.24 0.00 01-JAN-01:10 82489.76 21-JUL-17:10
HeatingCoils:EnergyTransfer 147.03 0.00 01-JAN-01:10 60383.06 21-JAN-07:00
CoolingCoils:EnergyTransfer 360.21 0.00 01-JAN-00:10 82489.76 21-JUL-17:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 241.63 0.00 01-JAN-01:10 16943.77 06-FEB-07:40
WaterUse:WaterSystems:EnergyTransfer 241.63 0.00 01-JAN-01:10 16943.77 06-FEB-07:40



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
DINING 0.000 0.000 0.350 -318.627 0.000 0.000 221.368 21.628 88.765 61.475 0.000 4.647 0.000 0.000 -19.655 0.000 -40.072 -19.878
KITCHEN 0.000 0.000 0.002 -326.553 0.000 0.000 5.653 16.690 259.402 0.000 0.000 0.018 45.468 0.000 0.000 0.000 -0.681 -0.001
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 9.341 36.650 0.000 0.000 0.000 -45.991 -0.000
Total Facility 0.000 0.000 0.351 -645.180 0.000 0.000 227.021 38.318 348.168 61.475 0.000 14.006 82.119 0.000 -19.655 0.000 -86.744 -19.879


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
DINING 22-JUL-03:01 0.00 0.00 0.00 -70548.34 0.00 0.00 0.00 80.03 851.41 0.00 0.00 0.00 70279.26 0.00 -641.03 0.00 -21.32 0.00
KITCHEN 16-MAY-03:11 0.00 0.00 0.00 -59136.54 0.00 0.00 0.00 30.01 2903.90 0.00 0.00 0.00 56233.46 0.00 -0.00 0.00 -30.83 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-MAY-03:01 0.00 0.00 0.00 -120990.73 0.00 0.00 0.00 110.04 3755.31 0.00 0.00 545.22 117843.07 0.00 -1144.46 0.00 -118.45 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
DINING 02-FEB-06:18 0.00 0.00 41366.15 0.00 0.00 0.00 2315.60 728.72 2223.78 0.00 0.00 0.00 0.00 0.00 -2093.78 0.00 -1408.01 -43132.46
KITCHEN 28-DEC-05:05 0.00 0.00 15437.22 0.00 0.00 0.00 23.13 30.01 6158.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -2.69 -21645.89
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-FEB-06:18 -8489.17 8489.17 41366.15 -8489.17 0.00 0.00 2383.60 1110.10 8845.96 0.00 0.00 781.59 0.00 0.00 -2093.78 0.00 -1427.68 -42476.77



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC_1:1 4.0916 0.0000 280.1417 1.0000 Calculated from schedules 1.3314 4.0916 0.3254 1.0000 Not calculated 1.3314 0.3254    
PSZ-AC_2:2 1.6887 0.0000 7.5279 1.0000 Calculated from schedules 0.1826 1.6887 0.1081 1.0000 Not calculated 0.1826 0.1081    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC_1:1 4.0916 0.0000 280.1417 1.0000 Calculated from schedules 1.3314 4.0916 1.0000 1.0000 Not calculated 1.3314 0.3254    
PSZ-AC_2:2 1.6887 0.0000 7.5279 1.0000 Calculated from schedules 0.1826 1.6887 0.1500 1.0000 Not calculated 0.1826 0.1081    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
DINING PSZ-AC_1:1 0.000000 280.1417 0.003581 371.75 1.3314 1.0000 1.3314 1.000 1.3314
KITCHEN PSZ-AC_2:2 0.009440 7.5279 0.000800 139.41 0.1826 1.0000 0.1826 1.000 0.1826


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC_1:1 0.000000 280.14 0.003581 371.7481 1.3314 1.3314 1.3314
PSZ-AC_2:2 0.009440 7.53 0.000800 139.4052 0.1826 0.1826 0.1826


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
DINING PSZ-AC_1:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.0916 4.0916 4.0916 No 1.3314 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN PSZ-AC_2:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.6887 1.6887 1.6887 No 0.1826 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC_1:1 4.0916 4.0916 4.0916 4.0916 1.3314 1.0000
PSZ-AC_2:2 1.6887 1.6887 1.6887 1.6887 0.1826 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
DINING PSZ-AC_1:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.0916 4.0916 4.0916 No 1.3314 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN PSZ-AC_2:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.6887 1.6887 1.6887 No 0.1826 0.1500 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC_1:1 4.0916 4.0916 4.0916 4.0916 1.3314 1.0000
PSZ-AC_2:2 1.6887 1.6887 1.6887 1.6887 0.1826 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Total gross floor area [m2] 511.15
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
DINING 371.75 371.75 0.00 137.83
KITCHEN 139.41 139.41 0.00 137.83
ATTIC 511.15 0.00 511.15 0.00
Totals 511.15 511.15 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.17
Number of hours cooling loads not met 0.00
Number of hours not met 0.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 172.88 70997.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 100.08 25414.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 38.32 2497.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 17.26 1510.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 394.51 22047.72 444.42 24831.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 9.88 313.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 121.41 7000.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.45 17.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 75.47 4742.36 291.11 25462.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 6.93 2143.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 11.26 1035.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 18.31 637.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 449.64 802.63
Natural Gas 444.42 908.41
Additional 0.00 0.00
Total 894.06 1711.04


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 74.96
Space Heating 0.00
Space Cooling 195.80
Fans (All) 237.52
Service Water Heating 147.65
Receptacle Equipment 808.26
Miscellaneous (All) 1570.23
Subtotal 1570.23


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 338.21
Service Water Heating 569.52
Miscellaneous (All) 1777.18
Subtotal 1777.18


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 2.24
Space Heating 10.10
Space Cooling 5.85
Fans (All) 7.10
Service Water Heating 21.42
Receptacle Equipment 50.12
Miscellaneous 3.17


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_DINING 4826. 8760.
LTG_SCH_KITCHEN 4159. 8760.
BLDG_EQUIP_SCH 1440. 8760.
REST_GAS_EQUIP_SCH 1442. 8760.
BLDG_OCC_SCH 2960. 7195.
INFIL_HALF_ON_SCH 5292. 8760.
INFIL_SCH_PNNL 3559. 8760.
DOOR_INFIL_SCH 3274. 6570.
VESTIBULE_DOOR_INFIL_SCH 3177. 6570.
BLDG_SWH_SCH 2744. 6935.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 7300. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 6935. 6935.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
WALKIN_OCC_LGHT_SCH_2 2785. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6935. 6935.
EXTERIOR_LIGHTING_SCHEDULE_B 8213. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 6935. 6935.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 3814. 7300.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6570. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM DINING DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH_NO_OPTIMUM DINING DUAL SP CONTROL July 24.00 365 24.00 365
HTGSETP_KITCHEN_SCH_NO_OPTIMUM KITCHEN DUAL SP CONTROL January 19.00 365 19.00 365
CLGSETP_KITCHEN_SCH_NO_OPTIMUM KITCHEN DUAL SP CONTROL July 26.00 365 26.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
DINING 8757.83 2.17 0.00 0.00 0.00
KITCHEN 8142.00 617.83 0.17 0.00 0.00
ATTIC 6521.67 665.17 567.33 836.83 169.00
Min 6521.67 2.17 0.00 0.00 0.00
Max 8757.83 665.17 567.33 836.83 169.00
Average 7807.17 428.39 189.17 278.94 56.33
Sum 23421.50 1285.17 567.50 836.83 169.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
DINING 824196.33 25.67 0.00 0.00 0.00
KITCHEN 19233.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 824196.33 25.67 0.00 0.00 0.00
Average 281143.11 8.56 0.00 0.00 0.00
Sum 843429.33 25.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
DINING 8683.33 76.67 0.00 0.00 0.00
KITCHEN 7372.33 1387.67 0.00 0.00 0.00
ATTIC 6774.33 866.67 290.17 285.83 543.00
Min 6774.33 76.67 0.00 0.00 0.00
Max 8683.33 1387.67 290.17 285.83 543.00
Average 7610.00 777.00 96.72 95.28 181.00
Sum 22830.00 2331.00 290.17 285.83 543.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
DINING 823603.67 618.33 0.00 0.00 0.00
KITCHEN 16726.00 2507.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 823603.67 2507.00 0.00 0.00 0.00
Average 280109.89 1041.78 0.00 0.00 0.00
Sum 840329.67 3125.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:56

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
DINING 0.00 8760.00 0.00 0.00
KITCHEN 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 2920.00 0.00 0.00
Sum 0.00 8760.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
DINING 0.00 824222.00 0.00 0.00
KITCHEN 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 824222.00 0.00 0.00
Average 0.00 274740.67 0.00 0.00
Sum 0.00 824222.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.196783E+11 32036.19 20-JAN-00:01 -6.9 -7.0 0.121765E+11 12821.84 05-JAN-12:00 -6.9 -7.0
February 0.186925E+11 28873.00 06-FEB-00:01 -4.4 -6.2 0.112284E+11 12849.72 13-FEB-12:00 18.90 6.57
March 0.224735E+11 26376.29 10-MAR-05:01 -1.1 -4.3 0.135184E+11 13978.31 25-MAR-18:10 17.33 5.38
April 0.247898E+11 64091.31 30-APR-03:01 14.13 4.54 0.139133E+11 13978.32 29-APR-18:10 14.13 4.54
May 0.276022E+11 65764.55 11-MAY-03:01 13.22 3.99 0.149105E+11 13978.64 27-MAY-18:00 24.40 12.44
June 0.315866E+11 68192.80 20-JUN-03:01 10.78 4.69 0.147978E+11 13978.53 17-JUN-18:30 10.78 4.69
July 0.348282E+11 70561.98 22-JUL-03:01 21.52 12.48 0.151728E+11 13979.75 01-JUL-18:49 21.52 12.48
August 0.349755E+11 62965.69 18-AUG-03:01 22.02 13.93 0.153596E+11 13980.08 26-AUG-18:00 21.70 16.13
September 0.315213E+11 68361.32 15-SEP-03:01 19.90 12.41 0.146914E+11 13980.51 23-SEP-18:19 17.80 12.90
October 0.284670E+11 62268.11 07-OCT-03:01 17.48 11.17 0.143133E+11 13978.39 07-OCT-18:49 14.40 12.59
November 0.235416E+11 25707.37 27-NOV-00:01 -1.7 -5.1 0.124468E+11 12850.22 09-NOV-12:00 -1.7 -5.1
December 0.204751E+11 29695.86 15-DEC-00:01 -5.0 -9.0 0.119359E+11 11808.97 01-DEC-12:00 -5.0 -9.0
                     
Annual Sum or Average 0.318632E+12         0.164465E+12        
Minimum of Months 0.186925E+11 25707.37   -6.9 -9.0 0.112284E+11 11808.97   -6.9 -9.0
Maximum of Months 0.349755E+11 70561.98   22.02 13.93 0.153596E+11 13980.51   24.40 16.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.270812E+11 32022.27 26-JAN-05:01 -5.5 -8.2 0.986490E+10 6527.05 05-JAN-11:00 -5.5 -8.2
February 0.240959E+11 31634.78 04-FEB-05:01 -6.2 -7.7 0.892516E+10 6568.38 14-FEB-11:00 17.20 6.01
March 0.263871E+11 36773.59 31-MAR-03:42 3.45 1.28 0.994388E+10 6568.40 08-MAR-11:00 3.45 1.28
April 0.255570E+11 55146.05 28-APR-03:01 12.12 4.05 0.967354E+10 6568.40 17-APR-10:00 12.12 4.05
May 0.268886E+11 59173.73 16-MAY-03:11 13.30 3.87 0.100269E+11 6568.47 24-MAY-10:00 17.80 14.22
June 0.273452E+11 55374.07 20-JUN-04:01 11.78 5.18 0.972242E+10 6568.47 01-JUN-10:09 11.78 5.18
July 0.290973E+11 42273.74 21-JUL-03:11 22.23 12.61 0.100442E+11 6568.41 07-JUL-10:39 22.23 12.61
August 0.291889E+11 41943.16 19-AUG-03:11 21.33 12.13 0.100501E+11 6568.43 29-AUG-10:09 20.87 15.61
September 0.276819E+11 50472.51 20-SEP-03:11 13.30 7.70 0.971863E+10 6568.47 07-SEP-10:09 13.30 7.70
October 0.282046E+11 52711.76 19-OCT-03:01 9.40 3.36 0.999281E+10 6568.44 03-OCT-10:30 9.40 3.36
November 0.273464E+11 48209.56 01-NOV-03:01 9.73 6.96 0.958823E+10 6568.44 09-NOV-11:00 16.70 9.34
December 0.276928E+11 36369.24 15-DEC-05:01 -9.1 -11.9 0.985058E+10 6513.06 01-DEC-11:00 -9.1 -11.9
                     
Annual Sum or Average 0.326567E+12         0.117401E+12        
Minimum of Months 0.240959E+11 31634.78   -9.1 -11.9 0.892516E+10 6513.06   -9.1 -11.9
Maximum of Months 0.291889E+11 59173.73   22.23 12.61 0.100501E+11 6568.47   22.23 15.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 2.30 -1.2 0.00 0.00 01-JAN-00:10 2.30 -1.2
February 0.00 0.00 01-FEB-00:01 -3.2 -5.2 0.00 0.00 01-FEB-00:10 -3.2 -5.2
March 0.00 0.00 01-MAR-00:01 2.47 -0.8 0.00 0.00 01-MAR-00:10 2.47 -0.8
April 0.00 0.00 01-APR-00:01 7.00 2.84 0.00 0.00 01-APR-00:10 7.00 2.84
May 0.00 0.00 01-MAY-00:01 14.45 4.92 0.00 0.00 01-MAY-00:10 14.45 4.92
June 0.00 0.00 01-JUN-00:01 18.42 8.96 0.00 0.00 01-JUN-00:10 18.42 8.96
July 0.00 0.00 01-JUL-00:01 21.95 14.90 0.00 0.00 01-JUL-00:10 21.95 14.90
August 0.00 0.00 01-AUG-00:01 20.95 16.86 0.00 0.00 01-AUG-00:10 20.95 16.86
September 0.00 0.00 01-SEP-00:01 21.88 14.47 0.00 0.00 01-SEP-00:10 21.88 14.47
October 0.00 0.00 01-OCT-00:01 17.33 10.88 0.00 0.00 01-OCT-00:10 17.33 10.88
November 0.00 0.00 01-NOV-00:01 12.83 5.34 0.00 0.00 01-NOV-00:10 12.83 5.34
December 0.00 0.00 01-DEC-00:02 5.13 1.84 0.00 0.00 01-DEC-00:10 5.13 1.84
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -3.2 -5.2 0.00 0.00   -3.2 -5.2
Maximum of Months 0.00 0.00   21.95 16.86 0.00 0.00   21.95 16.86



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 90029702.32 35723.97 29-JAN-05:05 -0.7
February 96472991.26 41366.02 02-FEB-06:18 -3.9
March 17540935.60 37718.70 05-MAR-05:05 -1.9
April 1912827.48 7713.17 06-APR-04:03 2.20
May 205843.71 2462.36 07-MAY-04:05 7.65
June 23371544.12 9412.12 15-JUN-03:47 17.67
July 32388014.61 6211.07 22-JUL-23:02 27.70
August 12693104.64 4248.83 20-AUG-23:02 26.20
September 298035.15 1490.18 29-SEP-03:47 15.18
October 1439518.25 7506.34 25-OCT-04:02 -2.0
November 5491131.81 8643.61 16-NOV-05:02 -1.0
December 67684619.50 40767.75 24-DEC-05:39 -3.5
         
Annual Sum or Average 0.349528E+09      
Minimum of Months 205843.71 1490.18   -3.9
Maximum of Months 96472991.26 41366.02   27.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7475.87 77.87 29-JAN-05:04 -0.7
February 609818.59 5297.88 04-FEB-05:03 -6.2
March 0.00 0.00 01-MAR-00:01 2.47
April 0.00 0.00 01-APR-00:01 7.00
May 0.00 0.00 01-MAY-00:01 14.45
June 0.00 0.00 01-JUN-00:01 18.42
July 0.00 0.00 01-JUL-00:01 21.95
August 0.00 0.00 01-AUG-00:01 20.95
September 0.00 0.00 01-SEP-00:01 21.88
October 18282.14 304.70 25-OCT-04:04 -2.0
November 0.00 0.00 01-NOV-00:01 12.83
December 954389.48 15455.17 28-DEC-05:05 -1.0
         
Annual Sum or Average 1589966.08      
Minimum of Months 0.00 0.00   -6.2
Maximum of Months 954389.48 15455.17   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 2.30
February 0.00 0.00 01-FEB-00:01 -3.2
March 0.00 0.00 01-MAR-00:01 2.47
April 0.00 0.00 01-APR-00:01 7.00
May 0.00 0.00 01-MAY-00:01 14.45
June 0.00 0.00 01-JUN-00:01 18.42
July 0.00 0.00 01-JUL-00:01 21.95
August 0.00 0.00 01-AUG-00:01 20.95
September 0.00 0.00 01-SEP-00:01 21.88
October 0.00 0.00 01-OCT-00:01 17.33
November 0.00 0.00 01-NOV-00:01 12.83
December 0.00 0.00 01-DEC-00:02 5.13
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -3.2
Maximum of Months 0.00 0.00   21.95



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196086E+10 1639.63 02-JAN-17:10 0.100519E+11 6614.32 01-JAN-11:09
February 0.174275E+10 1639.63 01-FEB-17:30 0.907918E+10 6614.32 01-FEB-11:09
March 0.186356E+10 1639.63 01-MAR-17:00 0.100520E+11 6614.32 01-MAR-11:09
April 0.169988E+10 1639.63 01-APR-18:30 0.972770E+10 6614.32 01-APR-10:09
May 0.173157E+10 1639.63 01-MAY-18:49 0.100520E+11 6614.32 01-MAY-10:09
June 0.165177E+10 1639.63 01-JUN-19:10 0.972773E+10 6614.32 01-JUN-10:09
July 0.170497E+10 1639.63 01-JUL-19:19 0.100519E+11 6614.32 01-JUL-10:09
August 0.175751E+10 1639.63 01-AUG-19:10 0.100520E+11 6614.32 01-AUG-10:09
September 0.174500E+10 1639.63 01-SEP-18:40 0.972770E+10 6614.32 01-SEP-10:09
October 0.186589E+10 1639.63 02-OCT-17:49 0.100519E+11 6614.32 01-OCT-10:09
November 0.190143E+10 1639.63 01-NOV-17:10 0.972767E+10 6614.32 01-NOV-10:09
December 0.200243E+10 1639.63 01-DEC-16:00 0.100519E+11 6614.32 01-DEC-11:09
             
Annual Sum or Average 0.216276E+11     0.118354E+12    
Minimum of Months 0.165177E+10 1639.63   0.907918E+10 6614.32  
Maximum of Months 0.200243E+10 1639.63   0.100520E+11 6614.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.140982E+10 858.09 02-JAN-10:09 0.250369E+11 16024.20 01-JAN-11:09
February 0.127710E+10 858.09 01-FEB-10:09 0.226140E+11 16024.20 01-FEB-11:09
March 0.143409E+10 858.09 01-MAR-10:09 0.250371E+11 16024.20 01-MAR-11:09
April 0.136995E+10 858.09 01-APR-16:10 0.242293E+11 16024.20 01-APR-10:09
May 0.142196E+10 858.09 01-MAY-09:09 0.250370E+11 16024.20 01-MAY-10:09
June 0.138598E+10 858.09 01-JUN-09:09 0.242294E+11 16024.20 01-JUN-10:09
July 0.140610E+10 858.09 01-JUL-16:10 0.250369E+11 16024.20 01-JUL-10:09
August 0.143409E+10 858.09 01-AUG-09:09 0.250371E+11 16024.20 01-AUG-10:09
September 0.137029E+10 858.09 01-SEP-09:09 0.242293E+11 16024.20 01-SEP-10:09
October 0.140965E+10 858.09 02-OCT-09:09 0.250369E+11 16024.20 01-OCT-10:09
November 0.136509E+10 858.09 01-NOV-09:09 0.242292E+11 16024.20 01-NOV-10:09
December 0.140627E+10 858.09 01-DEC-10:09 0.250369E+11 16024.20 01-DEC-11:09
             
Annual Sum or Average 0.166904E+11     0.294790E+12    
Minimum of Months 0.127710E+10 858.09   0.226140E+11 16024.20  
Maximum of Months 0.143409E+10 858.09   0.250371E+11 16024.20  



Table of Contents

Report: SpaceGainsMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.300980E+11 0.196086E+10 0.100519E+11 0.00 0.00 0.00 0.00 0.00 0.699999E+10
February 0.272721E+11 0.174275E+10 0.907918E+10 0.00 0.00 0.00 0.00 0.00 0.567937E+10
March 0.305458E+11 0.186356E+10 0.100520E+11 0.00 0.00 0.00 0.00 0.00 0.467535E+10
April 0.292871E+11 0.169988E+10 0.972770E+10 0.00 0.00 0.00 0.00 18320414.08 0.283035E+10
May 0.303219E+11 0.173157E+10 0.100520E+11 0.00 0.00 0.00 0.00 0.217449E+09 0.177523E+10
June 0.295292E+11 0.165177E+10 0.972773E+10 0.00 0.00 0.00 0.00 0.127182E+10 0.690021E+09
July 0.300798E+11 0.170497E+10 0.100519E+11 0.00 0.00 0.00 0.00 0.157780E+10 0.261383E+09
August 0.305458E+11 0.175751E+10 0.100520E+11 0.00 0.00 0.00 0.00 0.112855E+10 0.432961E+09
September 0.292871E+11 0.174500E+10 0.972770E+10 0.00 0.00 0.00 0.00 0.376841E+09 0.103373E+10
October 0.300980E+11 0.186589E+10 0.100519E+11 0.00 0.00 0.00 0.00 56601410.46 0.318381E+10
November 0.290996E+11 0.190143E+10 0.972767E+10 0.00 0.00 0.00 0.00 0.00 0.528966E+10
December 0.300798E+11 0.200243E+10 0.100519E+11 0.00 0.00 0.00 0.00 0.00 0.722005E+10
                   
Annual Sum or Average 0.356244E+12 0.216276E+11 0.118354E+12 0.00 0.00 0.00 0.00 0.464739E+10 0.400719E+11
Minimum of Months 0.272721E+11 0.165177E+10 0.907918E+10 0.00 0.00 0.00 0.00 0.00 0.261383E+09
Maximum of Months 0.305458E+11 0.200243E+10 0.100520E+11 0.00 0.00 0.00 0.00 0.157780E+10 0.722005E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.808786E+09 0.140982E+10 0.203460E+11 0.113235E+11 0.00 0.00 0.00 0.00 87061141.81
February 0.732850E+09 0.127710E+10 0.183771E+11 0.102277E+11 0.00 0.00 0.00 0.00 83628053.06
March 0.820818E+09 0.143409E+10 0.203461E+11 0.113235E+11 0.00 0.00 0.00 0.00 89576014.85
April 0.786997E+09 0.136995E+10 0.196897E+11 0.109583E+11 0.00 0.00 0.00 101.77 60459643.54
May 0.814802E+09 0.142196E+10 0.203461E+11 0.113235E+11 0.00 0.00 0.00 683551.38 51012299.57
June 0.793501E+09 0.138598E+10 0.196898E+11 0.109583E+11 0.00 0.00 0.00 5390531.31 30890146.22
July 0.808298E+09 0.140610E+10 0.203460E+11 0.113235E+11 0.00 0.00 0.00 6895616.76 19941165.71
August 0.820818E+09 0.143409E+10 0.203461E+11 0.113235E+11 0.00 0.00 0.00 3736624.57 26231968.50
September 0.786997E+09 0.137029E+10 0.196897E+11 0.109583E+11 0.00 0.00 0.00 937041.29 33007124.96
October 0.808786E+09 0.140965E+10 0.203460E+11 0.113235E+11 0.00 0.00 0.00 113857.60 51222610.24
November 0.781956E+09 0.136509E+10 0.196897E+11 0.109583E+11 0.00 0.00 0.00 0.00 71255967.35
December 0.808298E+09 0.140627E+10 0.203460E+11 0.113235E+11 0.00 0.00 0.00 0.00 76310109.86
                   
Annual Sum or Average 0.957291E+10 0.166904E+11 0.239558E+12 0.133326E+12 0.00 0.00 0.00 17757324.69 0.680596E+09
Minimum of Months 0.732850E+09 0.127710E+10 0.183771E+11 0.102277E+11 0.00 0.00 0.00 0.00 19941165.71
Maximum of Months 0.820818E+09 0.143409E+10 0.203461E+11 0.113235E+11 0.00 0.00 0.00 6895616.76 89576014.85



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.955423E+09 0.251558E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.699285E+09 0.286741E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.704936E+09 0.344180E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.757084E+09 0.454241E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.740564E+09 0.483485E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.636093E+09 0.485359E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.561884E+09 0.516970E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.500342E+09 0.512216E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.739741E+09 0.410397E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.916886E+09 0.335665E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100307E+10 0.268492E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112553E+10 0.249822E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.934084E+10 0.459913E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.500342E+09 0.249822E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112553E+10 0.516970E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 30255.31 07-JAN-19:10 1639.63 02-JAN-17:10 6614.32 01-JAN-11:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 9359.03 19-JAN-21:00
February 30255.31 04-FEB-19:10 1639.63 01-FEB-17:30 6614.32 01-FEB-11:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 8523.87 04-FEB-20:00
March 30255.31 04-MAR-19:10 1639.63 01-MAR-17:00 6614.32 01-MAR-11:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 6303.23 04-MAR-19:55
April 30255.31 01-APR-18:10 1639.63 01-APR-18:30 6614.32 01-APR-10:09 0.00 0.00 0.00 0.00 605.08 13-APR-17:02 5632.39 15-APR-18:10
May 30255.31 06-MAY-18:10 1639.63 01-MAY-18:49 6614.32 01-MAY-10:09 0.00 0.00 0.00 0.00 1838.98 19-MAY-17:03 4688.62 01-MAY-19:53
June 30255.31 03-JUN-18:10 1639.63 01-JUN-19:10 6614.32 01-JUN-10:09 0.00 0.00 0.00 0.00 4037.99 28-JUN-17:02 4249.82 08-JUN-19:00
July 30255.31 01-JUL-18:10 1639.63 01-JUL-19:19 6614.32 01-JUL-10:09 0.00 0.00 0.00 0.00 4108.67 21-JUL-17:03 1855.99 07-JUL-18:00
August 30255.31 05-AUG-18:10 1639.63 01-AUG-19:10 6614.32 01-AUG-10:09 0.00 0.00 0.00 0.00 2876.62 04-AUG-17:03 2234.15 25-AUG-20:00
September 30255.31 02-SEP-18:10 1639.63 01-SEP-18:40 6614.32 01-SEP-10:09 0.00 0.00 0.00 0.00 1911.55 20-SEP-17:02 3063.68 23-SEP-19:00
October 30255.31 07-OCT-18:10 1639.63 02-OCT-17:49 6614.32 01-OCT-10:09 0.00 0.00 0.00 0.00 764.72 10-OCT-12:55 6572.37 24-OCT-20:00
November 30255.31 04-NOV-18:10 1639.63 01-NOV-17:10 6614.32 01-NOV-10:09 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 6669.96 27-NOV-21:00
December 30255.31 02-DEC-19:10 1639.63 01-DEC-16:00 6614.32 01-DEC-11:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:02 8447.00 09-DEC-19:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 30255.31   1639.63   6614.32   0.00 0.00 0.00 0.00 0.00   1855.99  
Maximum of Months 30255.31   1639.63   6614.32   0.00 0.00 0.00 0.00 4108.67   9359.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 813.01 07-JAN-19:10 858.09 02-JAN-10:09 12937.52 01-JAN-11:09 7449.36 01-JAN-11:09 0.00 0.00 0.00 0.00 01-JAN-00:01 312.75 17-JAN-04:10
February 813.01 04-FEB-19:10 858.09 01-FEB-10:09 12937.52 01-FEB-11:09 7449.36 01-FEB-11:09 0.00 0.00 0.00 0.00 01-FEB-00:01 316.77 05-FEB-01:10
March 813.01 04-MAR-19:10 858.09 01-MAR-10:09 12937.52 01-MAR-11:09 7449.36 01-MAR-11:09 0.00 0.00 0.00 0.00 01-MAR-00:01 338.04 14-MAR-03:40
April 813.01 01-APR-18:10 858.09 01-APR-16:10 12937.52 01-APR-10:09 7449.36 01-APR-10:09 0.00 0.00 0.00 0.15 13-APR-16:53 313.34 23-APR-04:00
May 813.01 06-MAY-18:10 858.09 01-MAY-09:09 12937.52 01-MAY-10:09 7449.36 01-MAY-10:09 0.00 0.00 0.00 10.33 19-MAY-14:53 261.90 18-MAY-02:50
June 813.01 03-JUN-18:10 858.09 01-JUN-09:09 12937.52 01-JUN-10:09 7449.36 01-JUN-10:09 0.00 0.00 0.00 23.22 17-JUN-15:53 203.84 10-JUN-03:00
July 813.01 01-JUL-18:10 858.09 01-JUL-16:10 12937.52 01-JUL-10:09 7449.36 01-JUL-10:09 0.00 0.00 0.00 25.69 04-JUL-14:53 102.32 05-JUL-03:10
August 813.01 05-AUG-18:10 858.09 01-AUG-09:09 12937.52 01-AUG-10:09 7449.36 01-AUG-10:09 0.00 0.00 0.00 13.56 02-AUG-13:00 125.60 08-AUG-01:10
September 813.01 02-SEP-18:10 858.09 01-SEP-09:09 12937.52 01-SEP-10:09 7449.36 01-SEP-10:09 0.00 0.00 0.00 8.54 03-SEP-14:51 150.84 18-SEP-01:00
October 813.01 07-OCT-18:10 858.09 02-OCT-09:09 12937.52 01-OCT-10:09 7449.36 01-OCT-10:09 0.00 0.00 0.00 3.32 01-OCT-15:52 188.57 08-OCT-01:30
November 813.01 04-NOV-18:10 858.09 01-NOV-09:09 12937.52 01-NOV-10:09 7449.36 01-NOV-10:09 0.00 0.00 0.00 0.00 01-NOV-00:01 334.35 26-NOV-05:00
December 813.01 02-DEC-19:10 858.09 01-DEC-10:09 12937.52 01-DEC-11:09 7449.36 01-DEC-11:09 0.00 0.00 0.00 0.00 01-DEC-00:02 462.83 14-DEC-04:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 813.01   858.09   12937.52   7449.36   0.00 0.00 0.00 0.00   102.32  
Maximum of Months 813.01   858.09   12937.52   7449.36   0.00 0.00 0.00 25.69   462.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2055.68 10-JAN-23:53 5316.35 29-JAN-13:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1758.67 14-FEB-07:23 6302.24 25-FEB-13:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1568.04 08-MAR-05:00 7102.27 30-MAR-13:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1895.10 01-APR-04:00 8194.07 08-APR-13:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1898.52 09-MAY-03:55 8335.85 28-MAY-13:40
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1849.80 20-JUN-02:00 7580.34 03-JUN-13:10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1491.48 14-JUL-05:53 7316.73 28-JUL-13:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1210.95 17-AUG-04:30 7413.21 03-AUG-13:20
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1559.07 27-SEP-23:00 6961.64 09-SEP-12:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1834.37 29-OCT-22:00 6789.96 14-OCT-12:40
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1818.41 12-NOV-23:00 5894.28 12-NOV-13:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1863.73 13-DEC-02:70 5622.62 22-DEC-13:30
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1210.95   5316.35  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2055.68   8335.85  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 32036.19 20-JAN-00:01 16808.50 2732.77 6811.26 0.00 0.00 0.00 0.00 0.00 0.00
February 28873.00 06-FEB-00:01 16808.50 2732.77 6811.26 0.00 0.00 0.00 0.00 0.00 260.82
March 26376.29 10-MAR-05:01 16808.50 800.29 27369.58 0.00 0.00 0.00 0.00 0.00 35.56
April 64091.31 30-APR-03:01 0.00 800.29 11352.10 0.00 0.00 0.00 0.00 0.00 36.25
May 65764.55 11-MAY-03:01 0.00 800.29 11352.10 0.00 0.00 0.00 0.00 0.00 63.98
June 68192.80 20-JUN-03:01 0.00 800.29 11352.10 0.00 0.00 0.00 0.00 0.00 29.70
July 70561.98 22-JUL-03:01 0.00 800.29 11352.10 0.00 0.00 0.00 0.00 0.00 21.32
August 62965.69 18-AUG-03:01 0.00 640.23 9081.68 0.00 0.00 0.00 0.00 0.00 8.46
September 68361.32 15-SEP-03:01 0.00 800.29 11352.10 0.00 0.00 0.00 0.00 0.00 38.59
October 62268.11 07-OCT-03:01 0.00 800.29 11352.10 0.00 0.00 0.00 0.00 0.00 52.53
November 25707.37 27-NOV-00:01 16808.50 2732.77 6811.26 0.00 0.00 0.00 0.00 0.00 113.42
December 29695.86 15-DEC-00:01 16808.50 2732.77 6811.26 0.00 0.00 0.00 0.00 0.00 169.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 25707.37   0.00 640.23 6811.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 70561.98   16808.50 2732.77 27369.58 0.00 0.00 0.00 0.00 0.00 260.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 32022.27 26-JAN-05:01 451.67 300.11 56997.89 30824.93 0.00 0.00 0.00 0.00 19.08
February 31634.78 04-FEB-05:01 0.00 300.11 56997.89 30824.93 0.00 0.00 0.00 0.00 38.79
March 36773.59 31-MAR-03:42 0.00 180.07 16259.15 7706.23 0.00 0.00 0.00 0.00 98.48
April 55146.05 28-APR-03:01 0.00 300.11 27098.59 12843.72 0.00 0.00 0.00 0.00 49.44
May 59173.73 16-MAY-03:11 0.00 300.11 27098.59 12843.72 0.00 0.00 0.00 0.00 30.83
June 55374.07 20-JUN-04:01 451.67 300.11 56997.89 30824.93 0.00 0.00 0.00 0.00 1.99
July 42273.74 21-JUL-03:11 0.00 300.11 27098.59 12843.72 0.00 0.00 0.00 0.00 23.52
August 41943.16 19-AUG-03:11 0.00 300.11 27098.59 12843.72 0.00 0.00 0.00 0.00 30.80
September 50472.51 20-SEP-03:11 0.00 300.11 27098.59 12843.72 0.00 0.00 0.00 0.00 45.90
October 52711.76 19-OCT-03:01 0.00 300.11 27098.59 12843.72 0.00 0.00 0.00 0.00 7.11
November 48209.56 01-NOV-03:01 0.00 300.11 27098.59 12843.72 0.00 0.00 0.00 0.00 8.26
December 36369.24 15-DEC-05:01 451.67 300.11 56997.89 30824.93 0.00 0.00 0.00 0.00 2.65
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 31634.78   0.00 180.07 16259.15 7706.23 0.00 0.00 0.00 0.00 1.99
Maximum of Months 59173.73   451.67 300.11 56997.89 30824.93 0.00 0.00 0.00 0.00 98.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.07 0.00
February 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.23 0.00
March 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1150.40 0.00
April 0.00 01-APR-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1138.90 0.00
May 0.00 01-MAY-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 744.77 0.00
June 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 606.31 0.00
July 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 263.34 0.00
August 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 380.88 0.00
September 0.00 01-SEP-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 316.80 0.00
October 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 281.79 0.00
November 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 802.76 0.00
December 0.00 01-DEC-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 801.42 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.23 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1150.40 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.604605E+11 35722.54 21-JAN-11:09 0.112508E+12 94813.34 21-JAN-06:00
February 0.544439E+11 35607.93 04-FEB-11:20 0.932551E+11 93941.12 06-FEB-07:30
March 0.600706E+11 36869.68 08-MAR-18:10 0.808096E+11 78861.65 05-MAR-06:49
April 0.612576E+11 41595.06 13-APR-17:10 0.657231E+11 57993.63 08-APR-05:00
May 0.679323E+11 45677.22 23-MAY-10:00 0.628750E+11 41899.89 06-MAY-05:49
June 0.758031E+11 57790.23 28-JUN-16:10 0.587251E+11 39360.37 03-JUN-10:39
July 0.852216E+11 58220.62 21-JUL-17:19 0.594084E+11 39173.68 01-JUL-10:20
August 0.820884E+11 52067.91 17-AUG-11:09 0.594272E+11 39099.39 27-AUG-10:00
September 0.719344E+11 48103.04 03-SEP-10:00 0.579936E+11 39269.91 30-SEP-10:20
October 0.649203E+11 46773.42 11-OCT-10:00 0.667278E+11 72427.80 26-OCT-06:00
November 0.579702E+11 35584.74 04-NOV-10:20 0.787510E+11 83321.05 27-NOV-07:30
December 0.605266E+11 35706.02 21-DEC-11:09 0.112206E+12 97494.47 15-DEC-07:49
             
Annual Sum or Average 0.802630E+12     0.908409E+12    
Minimum of Months 0.544439E+11 35584.74   0.579936E+11 39099.39  
Maximum of Months 0.852216E+11 58220.62   0.112508E+12 97494.47  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.337069E+10 0.181405E+10 0.350888E+11 0.00 0.108546E+11 37879553.69 0.00 966071.00 0.00 0.00 0.00 0.639615E+10 0.00
February 0.301985E+10 0.151667E+10 0.316932E+11 0.00 0.961180E+10 34213790.43 0.00 0.139988E+09 0.00 0.00 0.00 0.578784E+10 0.00
March 0.329765E+10 0.150319E+10 0.350891E+11 0.00 0.101570E+11 37879553.69 0.00 0.510174E+09 0.00 0.00 0.00 0.645948E+10 0.00
April 0.306983E+10 0.127447E+10 0.339570E+11 0.00 0.958765E+10 36657632.61 0.00 0.411947E+10 0.00 0.00 0.00 0.619882E+10 0.00
May 0.315353E+10 0.116539E+10 0.350889E+11 0.00 0.988340E+10 37879553.69 0.00 0.898874E+10 0.00 0.00 0.00 0.641732E+10 0.00
June 0.303775E+10 0.105971E+10 0.339571E+11 0.00 0.993509E+10 36657632.61 0.00 0.183929E+11 0.00 0.00 0.00 0.623670E+10 0.00
July 0.311107E+10 0.112165E+10 0.350888E+11 0.00 0.105829E+11 37879553.69 0.00 0.256334E+11 0.00 0.00 0.00 0.637158E+10 0.00
August 0.319160E+10 0.124762E+10 0.350891E+11 0.00 0.103345E+11 37879553.69 0.00 0.224581E+11 0.00 0.00 0.00 0.644973E+10 0.00
September 0.311529E+10 0.137869E+10 0.339570E+11 0.00 0.970777E+10 36657632.61 0.00 0.143905E+11 0.00 0.00 0.00 0.619497E+10 0.00
October 0.327555E+10 0.160742E+10 0.350888E+11 0.00 0.999217E+10 37879553.69 0.00 0.539887E+10 0.00 0.00 0.00 0.638380E+10 0.00
November 0.326653E+10 0.171311E+10 0.339569E+11 0.00 0.988903E+10 36657632.61 0.00 48245757.24 0.00 0.00 0.00 0.618699E+10 0.00
December 0.340870E+10 0.185755E+10 0.350888E+11 0.00 0.108728E+11 37879553.69 0.00 963172.96 0.00 0.00 0.00 0.638912E+10 0.00
                           
Annual Sum or Average 0.383180E+11 0.172595E+11 0.413144E+12 0.00 0.121409E+12 0.446001E+09 0.00 0.100082E+12 0.00 0.00 0.00 0.754725E+11 0.00
Minimum of Months 0.301985E+10 0.105971E+10 0.316932E+11 0.00 0.958765E+10 34213790.43 0.00 963172.96 0.00 0.00 0.00 0.578784E+10 0.00
Maximum of Months 0.340870E+10 0.185755E+10 0.350891E+11 0.00 0.108728E+11 37879553.69 0.00 0.256334E+11 0.00 0.00 0.00 0.645948E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.377451E+11 0.00 0.471114E+11 0.00 0.276511E+11 0.00 0.00
February 0.340924E+11 0.00 0.339779E+11 0.00 0.251847E+11 0.00 0.00
March 0.377451E+11 0.00 0.156177E+11 0.00 0.274467E+11 0.00 0.00
April 0.365275E+11 0.00 0.410304E+10 0.00 0.250926E+11 0.00 0.00
May 0.377451E+11 0.00 0.794266E+09 0.00 0.243356E+11 0.00 0.00
June 0.365275E+11 0.00 43867479.03 0.00 0.221537E+11 0.00 0.00
July 0.377451E+11 0.00 0.00 0.00 0.216633E+11 0.00 0.00
August 0.377451E+11 0.00 0.00 0.00 0.216821E+11 0.00 0.00
September 0.365275E+11 0.00 905596.16 0.00 0.214652E+11 0.00 0.00
October 0.377451E+11 0.00 0.552934E+10 0.00 0.234534E+11 0.00 0.00
November 0.365275E+11 0.00 0.178918E+11 0.00 0.243317E+11 0.00 0.00
December 0.377451E+11 0.00 0.478089E+11 0.00 0.266519E+11 0.00 0.00
               
Annual Sum or Average 0.444418E+12 0.00 0.172879E+12 0.00 0.291112E+12 0.00 0.00
Minimum of Months 0.340924E+11 0.00 0.00 0.00 0.214652E+11 0.00 0.00
Maximum of Months 0.377451E+11 0.00 0.478089E+11 0.00 0.276511E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2497.72 02-JAN-17:10 1510.48 01-JAN-06:10 22638.52 01-JAN-11:09 0.00 6001.32 21-JAN-06:00 17.86 08-JAN-00:10 0.00 01-JAN-00:10
February 2497.72 01-FEB-17:30 1510.48 01-FEB-06:10 22638.52 01-FEB-11:09 0.00 5913.82 04-FEB-06:10 17.86 08-FEB-00:10 0.00 01-FEB-00:10
March 2497.72 01-MAR-17:00 1510.48 01-MAR-06:10 22638.52 01-MAR-11:09 0.00 5655.87 05-MAR-06:00 17.86 04-MAR-00:10 0.00 01-MAR-00:10
April 2497.72 01-APR-18:30 1510.48 01-APR-05:10 22638.52 01-APR-10:09 0.00 5193.09 08-APR-05:00 17.86 07-APR-08:00 0.00 01-APR-00:10
May 2497.72 01-MAY-18:49 1510.48 01-MAY-05:10 22638.52 01-MAY-10:09 0.00 4851.52 07-MAY-04:00 17.86 30-MAY-15:30 0.00 01-MAY-00:10
June 2497.72 01-JUN-19:10 1510.48 01-JUN-19:10 22638.52 01-JUN-10:09 0.00 6802.35 28-JUN-17:10 17.86 03-JUN-14:30 0.00 01-JUN-00:10
July 2497.72 01-JUL-19:19 1510.48 01-JUL-19:19 22638.52 01-JUL-10:09 0.00 7000.40 21-JUL-17:10 17.86 07-JUL-14:50 0.00 01-JUL-00:10
August 2497.72 01-AUG-19:10 1510.48 01-AUG-05:10 22638.52 01-AUG-10:09 0.00 5722.88 17-AUG-11:09 17.86 05-AUG-08:39 0.00 01-AUG-00:10
September 2497.72 01-SEP-18:40 1510.48 01-SEP-05:10 22638.52 01-SEP-10:09 0.00 4659.09 03-SEP-10:00 17.86 03-SEP-14:50 0.00 01-SEP-00:10
October 2497.72 02-OCT-17:49 1510.48 01-OCT-05:10 22638.52 01-OCT-10:09 0.00 5529.69 26-OCT-04:00 17.86 20-OCT-10:39 0.00 01-OCT-00:10
November 2497.72 01-NOV-17:10 1510.48 01-NOV-05:10 22638.52 01-NOV-10:09 0.00 5665.46 27-NOV-06:10 17.86 28-NOV-00:10 0.00 01-NOV-00:10
December 2497.72 01-DEC-16:00 1510.48 01-DEC-06:10 22638.52 01-DEC-11:09 0.00 5936.64 15-DEC-06:00 17.86 08-DEC-00:10 0.00 01-DEC-00:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2497.72   1510.48   22638.52   0.00 4659.09   17.86   0.00  
Maximum of Months 2497.72   1510.48   22638.52   0.00 7000.40   17.86   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 361.75 06-JAN-04:19 0.00 0.00 0.00 4742.02 25-JAN-19:00 0.00
February 4852.88 14-FEB-13:00 0.00 0.00 0.00 4742.36 14-FEB-07:00 0.00
March 7162.28 08-MAR-13:00 0.00 0.00 0.00 4741.96 10-MAR-07:49 0.00
April 11266.59 13-APR-17:10 0.00 0.00 0.00 4741.78 24-APR-06:49 0.00
May 14412.37 19-MAY-17:19 0.00 0.00 0.00 4741.45 04-MAY-06:00 0.00
June 24896.00 28-JUN-16:10 0.00 0.00 0.00 4739.16 09-JUN-06:30 0.00
July 25414.71 21-JUL-17:10 0.00 0.00 0.00 4736.71 21-JUL-06:19 0.00
August 19100.78 20-AUG-17:19 0.00 0.00 0.00 4737.29 31-AUG-06:19 0.00
September 15857.79 03-SEP-13:00 0.00 0.00 0.00 4737.75 11-SEP-06:19 0.00
October 13540.54 11-OCT-11:00 0.00 0.00 0.00 4740.58 13-OCT-06:40 0.00
November 3959.02 09-NOV-13:00 0.00 0.00 0.00 4741.87 15-NOV-07:49 0.00
December 309.76 01-DEC-04:10 0.00 0.00 0.00 4741.54 29-DEC-07:49 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 309.76   0.00 0.00 0.00 4736.71   0.00
Maximum of Months 25414.71   0.00 0.00 0.00 4742.36   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 35722.54 21-JAN-11:09 1491.48 22638.52 0.00 0.00 4811.58 17.86 0.00 0.00 0.00
February 35607.93 04-FEB-11:20 1491.48 22638.52 0.00 0.00 4861.76 17.86 0.00 0.00 0.00
March 36869.68 08-MAR-18:10 2497.72 18837.19 1510.48 0.00 4343.34 17.86 0.00 4372.13 0.00
April 41595.06 13-APR-17:10 1677.91 18837.19 0.00 0.00 4343.34 17.86 0.00 11266.59 0.00
May 45677.22 23-MAY-10:00 1677.91 22638.52 0.00 0.00 4350.21 17.86 0.00 11630.97 0.00
June 57790.23 28-JUN-16:10 1677.91 20357.72 0.00 0.00 6566.97 17.86 0.00 24896.00 0.00
July 58220.62 21-JUL-17:19 1677.91 18837.19 0.00 0.00 6946.03 17.86 0.00 25153.17 0.00
August 52067.91 17-AUG-11:09 1677.91 21117.99 0.00 0.00 5722.88 17.86 0.00 19034.50 0.00
September 48103.04 03-SEP-10:00 1305.04 22638.52 0.00 0.00 4659.09 17.86 0.00 13968.98 0.00
October 46773.42 11-OCT-10:00 1677.91 22638.52 0.00 0.00 4484.28 17.86 0.00 12592.07 0.00
November 35584.74 04-NOV-10:20 1491.48 22638.52 0.00 0.00 4744.88 17.86 0.00 0.00 0.00
December 35706.02 21-DEC-11:09 1677.91 22638.52 0.00 0.00 5147.29 17.86 0.00 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 35584.74   1305.04 18837.19 0.00 0.00 4343.34 17.86 0.00 0.00 0.00
Maximum of Months 58220.62   2497.72 22638.52 1510.48 0.00 6946.03 17.86 0.00 25153.17 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 24831.19 01-JAN-11:09 0.00 70997.13 21-JAN-06:00 0.00 25415.61 31-JAN-07:30 0.00
February 24831.19 01-FEB-11:09 0.00 67352.59 04-FEB-06:10 0.00 25462.40 03-FEB-07:19 0.00
March 24831.19 01-MAR-11:09 0.00 55529.15 05-MAR-06:00 0.00 25082.25 02-MAR-07:30 0.00
April 24831.19 01-APR-10:09 0.00 34247.41 08-APR-05:00 0.00 23309.23 03-APR-06:00 0.00
May 24831.19 01-MAY-10:09 0.00 18613.87 07-MAY-04:00 0.00 20868.35 01-MAY-06:49 0.00
June 24831.19 01-JUN-10:09 0.00 6309.07 09-JUN-04:00 0.00 17484.42 01-JUN-18:49 0.00
July 24831.19 01-JUL-10:09 0.00 0.00 01-JUL-00:10 0.00 14976.31 03-JUL-06:00 0.00
August 24831.19 01-AUG-10:09 0.00 0.00 01-AUG-00:10 0.00 14901.12 31-AUG-06:19 0.00
September 24831.19 01-SEP-10:09 0.00 724.55 09-SEP-05:00 0.00 15514.83 27-SEP-18:40 0.00
October 24831.19 01-OCT-10:09 0.00 50442.30 26-OCT-04:00 0.00 19385.81 31-OCT-06:30 0.00
November 24831.19 01-NOV-10:09 0.00 56436.70 27-NOV-06:10 0.00 22358.45 30-NOV-07:40 0.00
December 24831.19 01-DEC-11:09 0.00 68209.15 15-DEC-06:00 0.00 24396.79 29-DEC-07:19 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 24831.19   0.00 0.00   0.00 14901.12   0.00
Maximum of Months 24831.19   0.00 70997.13   0.00 25462.40   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.38 0.00 20.38 0.00 20.38 0.00 20.38
February 0.33 20.29 0.17 20.25 0.00 20.25 0.00 20.25
March 0.17 20.37 0.00 20.37 0.00 20.37 0.00 20.37
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 24.57 0.00 24.57
June 0.00 0.00 0.00 0.00 2.67 24.69 0.00 24.69
July 0.00 0.00 0.00 0.00 2.67 24.80 0.00 24.80
August 0.00 0.00 0.00 0.00 3.00 24.76 0.00 24.76
September 0.00 0.00 0.00 0.00 3.50 24.74 0.00 24.74
October 0.00 0.00 0.00 0.00 1.33 24.74 0.00 24.74
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.40 0.00 20.40 0.00 20.40 0.00 20.40
                 
Annual Sum or Average 1.17 20.36 0.17 20.34 13.50 24.35 0.00 24.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.40 0.17 20.40 3.50 24.80 0.00 24.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.17 26.80 0.00 26.80
February 0.00 0.00 0.00 0.00 1.17 27.04 0.00 27.04
March 0.00 0.00 0.00 0.00 3.67 27.33 0.00 27.33
April 0.00 0.00 0.00 0.00 5.00 27.94 0.00 27.94
May 0.00 0.00 0.00 0.00 7.33 28.88 0.00 28.88
June 0.00 0.00 0.00 0.00 19.00 30.04 0.00 30.04
July 0.00 0.00 0.00 0.00 25.83 30.50 0.00 30.50
August 0.00 0.00 0.00 0.00 25.67 30.49 0.00 30.49
September 0.00 0.00 0.00 0.00 20.50 30.23 0.00 30.23
October 0.00 0.00 0.00 0.00 10.50 29.41 0.00 29.41
November 0.00 0.00 0.00 0.00 3.50 27.25 0.00 27.25
December 0.00 0.00 0.00 0.00 0.67 26.84 0.00 26.84
                 
Annual Sum or Average 0.00   0.00   124.00 29.82 0.00 29.82
Minimum of Months 0.00 0.00 0.00 0.00 0.67 26.80 0.00 26.80
Maximum of Months 0.00 0.00 0.00 0.00 25.83 30.50 0.00 30.50



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 609.33 21.03 97.00 20.83 97.00 20.68
February 535.00 21.13 72.67 20.92 72.67 20.77
March 538.33 21.66 32.50 21.50 32.50 21.36
April 343.67 22.06 22.50 22.08 6.67 22.02
May 199.33 22.39 204.00 23.19 9.67 23.19
June 57.50 22.74 458.33 23.90 13.17 23.90
July 111.17 24.04 606.50 24.07 111.17 24.07
August 85.17 23.97 606.17 24.04 83.50 24.03
September 73.00 23.19 513.83 23.89 37.17 23.89
October 279.50 21.74 200.67 22.60 12.50 22.55
November 544.50 21.38 41.67 21.27 31.83 21.14
December 609.00 20.84 107.83 20.68 107.83 20.56
             
Annual Sum or Average 3985.50 21.56 2963.67 22.38 615.67 22.30
Minimum of Months 57.50 20.84 22.50 20.68 6.67 20.56
Maximum of Months 609.33 24.04 606.50 24.07 111.17 24.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 565.00 19.59 205.00 19.56 186.33 19.45
February 467.83 19.65 171.67 19.92 124.67 19.78
March 361.33 20.13 237.67 21.73 43.33 21.63
April 344.67 23.20 366.00 24.36 172.17 24.64
May 396.83 25.31 526.50 25.46 347.50 25.60
June 501.33 25.95 584.67 25.87 498.00 25.91
July 607.83 25.99 609.00 25.99 607.83 25.99
August 603.17 25.97 612.00 25.97 603.17 25.97
September 498.83 25.96 589.67 25.84 498.83 25.87
October 421.83 23.71 424.83 24.51 268.17 24.80
November 442.50 20.17 171.00 20.86 70.83 20.81
December 598.00 19.37 199.17 19.29 198.33 19.23
             
Annual Sum or Average 5809.17 22.98 4697.17 23.79 3619.17 24.05
Minimum of Months 344.67 19.37 171.00 19.29 43.33 19.23
Maximum of Months 607.83 25.99 612.00 25.99 607.83 25.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING PEOPLE

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 610.00000 21.03223 22.07994 -0.4269 10.11465
February 551.00000 21.20884 23.84525 -0.3686 9.47739
March 612.00000 21.93695 23.49986 -0.1875 7.75004
April 590.00000 22.86351 20.29081 0.04322 6.93913
May 611.00000 23.46274 27.85402 -0.6608 16.39943
June 592.00000 23.90379 35.70760 -0.4099 9.30828
July 609.00000 24.07429 47.29886 -0.2444 6.43705
August 612.00000 24.03958 46.59593 -0.2527 6.56669
September 590.00000 23.87660 41.49253 -0.3572 8.34110
October 610.00000 22.94672 29.20117 0.15990 8.02462
November 591.00000 21.57668 23.95228 -0.2359 7.88981
December 609.00000 20.84497 20.14646 -0.4698 10.49637
           
Annual Sum or Average 7187.00000 22.65506 30.21549 -0.2840 8.98428
Minimum of Months 551.00000 20.84497 20.14646 -0.6608 6.43705
Maximum of Months 612.00000 24.07429 47.29886 0.15990 16.39943



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN PEOPLE

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 610.00000 19.89330 29.31701 -0.4154 10.95814
February 551.00000 20.32940 30.86878 -0.3116 11.04092
March 612.00000 21.95276 29.56166 0.06194 11.25933
April 590.00000 23.79954 25.71839 0.48686 16.09177
May 611.00000 25.01684 30.74970 0.14635 11.83691
June 592.00000 25.75756 36.42198 0.48201 11.53669
July 609.00000 25.99321 45.49321 0.65675 14.45689
August 612.00000 25.95811 44.96014 0.64097 14.13373
September 590.00000 25.73075 41.29547 0.52024 12.20401
October 610.00000 23.88664 32.72119 0.59772 19.94134
November 591.00000 21.09093 29.82846 -0.0984 10.01094
December 609.00000 19.43904 27.45918 -0.5195 11.76896
           
Annual Sum or Average 7187.00000 23.25286 33.72812 0.18979 12.95636
Minimum of Months 551.00000 19.43904 25.71839 -0.5195 10.01094
Maximum of Months 612.00000 25.99321 45.49321 0.65675 19.94134



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_1:1 COOLING COIL

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01
February 0.280888E+09 92271664.55 12.17 0.280888E+09 0.00 0.00 0.36 14-FEB-14:00 0.00 01-FEB-00:01 11302.41 14-FEB-14:00 11302.41 14-FEB-14:00 0.00 14-FEB-16:08 3609.47 14-FEB-14:00 0.00 01-FEB-00:01
March 0.927265E+09 0.307482E+09 64.61 0.926891E+09 373474.29 0.00 0.51 08-MAR-14:00 0.00 01-MAR-00:01 16801.92 08-MAR-14:00 16801.92 08-MAR-14:00 151.87 16-MAR-12:25 5160.53 08-MAR-14:00 0.00 01-MAR-00:01
April 0.833567E+10 0.259969E+10 211.96 0.832970E+10 5969683.98 0.00 1.00 13-APR-03:01 0.00 01-APR-00:01 75519.88 15-APR-03:01 75519.88 30-APR-03:01 12084.82 15-APR-03:01 20233.93 15-APR-03:01 0.00 01-APR-00:01
May 0.185233E+11 0.559531E+10 345.25 0.180766E+11 0.446736E+09 0.00 1.00 09-MAY-03:01 0.00 01-MAY-00:01 75519.88 31-MAY-03:01 75519.88 10-MAY-03:01 28039.75 28-MAY-03:01 20233.93 10-MAY-03:01 0.00 01-MAY-00:01
June 0.388286E+11 0.114783E+11 463.08 0.374212E+11 0.140738E+10 0.00 1.00 01-JUN-03:01 0.00 01-JUN-00:01 75519.88 27-JUN-03:48 75519.88 18-JUN-03:01 34214.96 05-JUN-03:01 20233.93 01-JUN-03:01 0.00 01-JUN-00:01
July 0.553771E+11 0.160081E+11 562.59 0.475426E+11 0.783451E+10 0.00 1.00 01-JUL-03:02 0.00 01-JUL-00:01 75895.74 16-JUL-03:01 71583.44 21-JUL-03:13 38888.80 16-JUL-03:43 20262.43 16-JUL-03:01 0.00 01-JUL-00:01
August 0.491807E+11 0.141178E+11 533.87 0.421721E+11 0.700856E+10 0.00 1.00 01-AUG-03:01 0.00 01-AUG-00:01 75610.32 15-AUG-03:01 70808.12 19-AUG-03:19 39214.06 26-AUG-03:02 20240.80 15-AUG-03:01 0.00 01-AUG-00:01
September 0.309015E+11 0.905406E+10 437.88 0.273044E+11 0.359712E+10 0.00 1.00 01-SEP-03:01 0.00 01-SEP-00:01 75519.88 04-SEP-03:41 70949.29 21-SEP-03:01 37802.29 06-SEP-03:02 20233.93 01-SEP-03:13 0.00 01-SEP-00:01
October 0.111751E+11 0.338102E+10 234.21 0.102998E+11 0.875359E+09 0.00 1.00 01-OCT-03:01 0.00 01-OCT-00:01 75519.88 10-OCT-03:01 67060.81 06-OCT-03:01 23200.10 10-OCT-03:01 20233.93 04-OCT-03:02 0.00 01-OCT-00:01
November 47226438.30 15843799.65 4.35 43679947.22 3546491.08 0.00 0.24 09-NOV-14:00 0.00 01-NOV-00:01 7289.79 09-NOV-14:00 7007.28 09-NOV-14:00 418.55 01-NOV-03:30 2397.60 09-NOV-14:00 0.00 01-NOV-00:01
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:02 0.00 01-DEC-00:02 0.00 01-DEC-00:02 0.00 01-DEC-00:02 0.00 01-DEC-00:02 0.00 01-DEC-00:02 0.00 01-DEC-00:02
                                         
Annual Sum or Average 0.213577E+12 0.626498E+11 2869.98 0.192398E+12 0.211796E+11 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.553771E+11 0.160081E+11 562.59 0.475426E+11 0.783451E+10 0.00 1.00   0.00   75895.74   75519.88   39214.06   20262.43   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_2:2 COOLING COIL

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 3207393.40 966071.00 0.72 2561768.46 645624.94 0.00 0.20 31-JAN-04:10 0.00 01-JAN-00:01 3015.37 31-JAN-04:10 2370.17 31-JAN-04:10 743.95 03-JAN-04:10 895.01 31-JAN-04:10 0.00 01-JAN-00:01
February 0.163326E+09 47716191.52 17.43 0.162540E+09 785947.93 0.00 0.39 14-FEB-16:08 0.00 01-FEB-00:01 6043.51 14-FEB-16:08 6043.51 14-FEB-16:08 886.86 21-FEB-04:10 1714.22 14-FEB-16:08 0.00 01-FEB-00:01
March 0.690439E+09 0.202692E+09 76.88 0.684489E+09 5950010.78 0.00 1.00 14-MAR-03:41 0.00 01-MAR-00:01 18478.58 14-MAR-03:41 15971.69 28-MAR-03:41 5337.56 31-MAR-03:42 4433.67 14-MAR-03:41 0.00 01-MAR-00:01
April 0.555470E+10 0.151978E+10 237.78 0.552486E+10 29843341.54 0.00 1.00 02-APR-03:01 0.00 01-APR-00:01 36999.59 02-APR-03:01 36999.59 13-APR-03:41 9824.92 15-APR-03:21 8870.62 02-APR-03:01 0.00 01-APR-00:01
May 0.129609E+11 0.339344E+10 384.65 0.122747E+11 0.686173E+09 0.00 1.00 01-MAY-03:01 0.00 01-MAY-00:01 36999.59 28-MAY-03:01 36999.59 09-MAY-03:41 18288.38 24-MAY-03:01 8870.62 01-MAY-03:01 0.00 01-MAY-00:01
June 0.268113E+11 0.691460E+10 514.90 0.253648E+11 0.144651E+10 0.00 1.00 01-JUN-03:01 0.00 01-JUN-00:01 36999.59 30-JUN-03:51 34699.31 18-JUN-03:01 19130.99 05-JUN-03:01 9449.55 28-JUN-16:00 0.00 01-JUN-00:01
July 0.381689E+11 0.962537E+10 622.80 0.323576E+11 0.581130E+10 0.00 1.00 01-JUL-03:11 0.00 01-JUL-00:01 37383.02 01-JUL-03:11 31896.13 21-JUL-03:11 22111.28 01-JUL-03:11 9098.51 22-JUL-15:00 0.00 01-JUL-00:01
August 0.333614E+11 0.834030E+10 597.54 0.279273E+11 0.543408E+10 0.00 1.00 01-AUG-03:11 0.00 01-AUG-00:01 36999.59 10-AUG-03:25 31529.20 19-AUG-03:11 22026.05 13-AUG-03:11 8870.62 01-AUG-03:11 0.00 01-AUG-00:01
September 0.211289E+11 0.533643E+10 480.31 0.177903E+11 0.333864E+10 0.00 1.00 01-SEP-03:11 0.00 01-SEP-00:01 36999.59 03-SEP-03:40 31093.70 22-SEP-03:01 21120.17 06-SEP-03:11 8870.62 01-SEP-03:11 0.00 01-SEP-00:01
October 0.767028E+10 0.201785E+10 266.69 0.675840E+10 0.911887E+09 0.00 1.00 01-OCT-03:01 0.00 01-OCT-00:01 36999.59 01-OCT-03:01 30363.05 31-OCT-03:01 16066.14 03-OCT-03:21 8870.62 01-OCT-03:01 0.00 01-OCT-00:01
November 0.111977E+09 32401957.59 15.46 91406547.41 20570204.98 0.00 1.00 01-NOV-03:01 0.00 01-NOV-00:01 36999.59 09-NOV-04:42 27210.35 09-NOV-04:42 12677.06 01-NOV-03:01 8870.62 09-NOV-04:42 0.00 01-NOV-00:01
December 3186152.67 963172.96 0.69 2649309.71 536842.96 0.00 0.28 01-DEC-04:08 0.00 01-DEC-00:02 4253.65 01-DEC-04:08 3496.38 01-DEC-04:08 757.27 01-DEC-04:08 1239.03 01-DEC-04:08 0.00 01-DEC-00:02
                                         
Annual Sum or Average 0.146629E+12 0.374325E+11 3215.84 0.128942E+12 0.176869E+11 0.00                            
Minimum of Months 3186152.67 963172.96 0.69 2561768.46 536842.96 0.00 0.20   0.00   3015.37   2370.17   743.95   895.01   0.00  
Maximum of Months 0.381689E+11 0.962537E+10 622.80 0.323576E+11 0.581130E+10 0.00 1.00   0.00   37383.02   36999.59   22111.28   9449.55   0.00  



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 266.13 148.96 117.17 242.37 332.63 0.00 0.00 0.00
February 322.28 173.24 149.04 322.27 300.05 0.00 0.00 0.00
March 428.28 243.99 184.29 483.16 233.49 0.00 0.00 0.00
April 580.99 330.61 250.37 719.16 162.55 0.00 0.00 0.00
May 555.04 316.15 238.90 723.15 124.34 0.00 0.00 0.00
June 598.58 368.71 229.88 856.52 81.72 0.00 0.00 0.00
July 553.60 316.47 237.13 828.10 54.77 0.00 0.00 0.00
August 547.92 302.01 245.92 791.63 64.03 0.00 0.00 0.00
September 456.90 255.66 201.24 621.49 111.08 0.00 0.00 0.00
October 398.07 252.78 145.29 478.14 190.65 0.00 0.00 0.00
November 309.60 181.62 127.98 317.52 268.64 0.00 0.00 0.00
December 252.18 153.82 98.36 231.07 348.22 0.00 0.00 0.00
                 
Annual Sum or Average 439.57 254.00 185.58 552.25 188.80 0.00 0.00 0.00
Minimum of Months 252.18 148.96 98.36 231.07 54.77 0.00 0.00 0.00
Maximum of Months 598.58 368.71 250.37 856.52 348.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 980.77 762.71 218.06 1181.99 446.08 0.00 0.00 0.00
February 966.76 707.54 259.22 1189.84 408.79 0.00 0.00 0.00
March 718.88 438.66 280.21 903.40 332.60 0.00 0.00 0.00
April 552.10 226.26 325.84 717.39 240.99 0.00 0.00 0.00
May 371.57 84.06 287.51 486.60 180.69 0.00 0.00 0.00
June 310.62 37.30 273.32 476.51 121.41 0.00 0.00 0.00
July 343.84 53.95 289.89 574.76 78.84 0.00 0.00 0.00
August 467.73 147.52 320.21 742.92 93.11 0.00 0.00 0.00
September 664.01 373.78 290.23 974.65 160.13 0.00 0.00 0.00
October 894.58 658.04 236.54 1187.88 262.60 0.00 0.00 0.00
November 1009.11 776.63 232.48 1249.27 359.46 0.00 0.00 0.00
December 1069.54 882.89 186.65 1296.09 456.29 0.00 0.00 0.00
                 
Annual Sum or Average 694.24 427.65 266.59 913.52 260.99 0.00 0.00 0.00
Minimum of Months 310.62 37.30 186.65 476.51 78.84 0.00 0.00 0.00
Maximum of Months 1069.54 882.89 325.84 1296.09 456.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 274.46 156.53 117.93 274.16 351.07 0.00 0.00 0.00
February 352.60 203.45 149.15 378.29 313.87 0.00 0.00 0.00
March 393.44 208.99 184.44 446.43 246.63 0.00 0.00 0.00
April 503.35 267.89 235.46 612.84 170.28 0.00 0.00 0.00
May 478.66 247.32 231.34 616.33 128.16 0.00 0.00 0.00
June 510.04 284.05 225.99 735.34 87.64 0.00 0.00 0.00
July 460.50 225.02 235.48 696.28 57.01 0.00 0.00 0.00
August 471.04 217.55 253.49 685.74 67.09 0.00 0.00 0.00
September 427.38 225.65 201.74 585.99 116.31 0.00 0.00 0.00
October 391.12 243.62 147.50 479.17 201.72 0.00 0.00 0.00
November 305.63 179.79 125.84 321.51 278.75 0.00 0.00 0.00
December 262.44 163.88 98.56 257.06 361.20 0.00 0.00 0.00
                 
Annual Sum or Average 402.59 218.54 184.05 507.87 197.74 0.00 0.00 0.00
Minimum of Months 262.44 156.53 98.56 257.06 57.01 0.00 0.00 0.00
Maximum of Months 510.04 284.05 253.49 735.34 361.20 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.712805E+09 0.398964E+09 0.313841E+09 0.649168E+09 0.890905E+09
February 0.779667E+09 0.419108E+09 0.360559E+09 0.779626E+09 0.725872E+09
March 0.114711E+10 0.653510E+09 0.493604E+09 0.129411E+10 0.625391E+09
April 0.150592E+10 0.856953E+09 0.648964E+09 0.186406E+10 0.421321E+09
May 0.148663E+10 0.846774E+09 0.639856E+09 0.193689E+10 0.333036E+09
June 0.155153E+10 0.955684E+09 0.595844E+09 0.222011E+10 0.211816E+09
July 0.148276E+10 0.847632E+09 0.635127E+09 0.221799E+10 0.146702E+09
August 0.146756E+10 0.808896E+09 0.658660E+09 0.212029E+10 0.171498E+09
September 0.118429E+10 0.662667E+09 0.521619E+09 0.161090E+10 0.287909E+09
October 0.106619E+10 0.677054E+09 0.389140E+09 0.128066E+10 0.510633E+09
November 0.802477E+09 0.470764E+09 0.331713E+09 0.823016E+09 0.696305E+09
December 0.675447E+09 0.412003E+09 0.263444E+09 0.618908E+09 0.932680E+09
           
Annual Sum or Average 0.138624E+11 0.801001E+10 0.585237E+10 0.174157E+11 0.595407E+10
Minimum of Months 0.675447E+09 0.398964E+09 0.263444E+09 0.618908E+09 0.146702E+09
Maximum of Months 0.155153E+10 0.955684E+09 0.658660E+09 0.222011E+10 0.932680E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.262690E+10 0.204285E+10 0.584051E+09 0.316585E+10 0.119478E+10
February 0.233879E+10 0.171167E+10 0.627116E+09 0.287847E+10 0.988949E+09
March 0.192544E+10 0.117491E+10 0.750525E+09 0.241967E+10 0.890837E+09
April 0.143104E+10 0.586458E+09 0.844581E+09 0.185949E+10 0.624653E+09
May 0.995206E+09 0.225141E+09 0.770065E+09 0.130331E+10 0.483967E+09
June 0.805127E+09 96677610.19 0.708450E+09 0.123512E+10 0.314707E+09
July 0.920931E+09 0.144500E+09 0.776431E+09 0.153943E+10 0.211176E+09
August 0.125278E+10 0.395120E+09 0.857658E+09 0.198984E+10 0.249391E+09
September 0.172110E+10 0.968828E+09 0.752275E+09 0.252628E+10 0.415053E+09
October 0.239604E+10 0.176248E+10 0.633560E+09 0.318161E+10 0.703347E+09
November 0.261562E+10 0.201303E+10 0.602593E+09 0.323810E+10 0.931718E+09
December 0.286466E+10 0.236474E+10 0.499918E+09 0.347146E+10 0.122212E+10
           
Annual Sum or Average 0.218936E+11 0.134864E+11 0.840722E+10 0.288086E+11 0.823070E+10
Minimum of Months 0.805127E+09 96677610.19 0.499918E+09 0.123512E+10 0.211176E+09
Maximum of Months 0.286466E+10 0.236474E+10 0.857658E+09 0.347146E+10 0.122212E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.735112E+09 0.419238E+09 0.315874E+09 0.734300E+09 0.940301E+09
February 0.853011E+09 0.492198E+09 0.360813E+09 0.915166E+09 0.759311E+09
March 0.105378E+10 0.559764E+09 0.494016E+09 0.119571E+10 0.660564E+09
April 0.130469E+10 0.694375E+09 0.610317E+09 0.158847E+10 0.441356E+09
May 0.128204E+10 0.662414E+09 0.619626E+09 0.165077E+10 0.343270E+09
June 0.132202E+10 0.736262E+09 0.585753E+09 0.190600E+10 0.227175E+09
July 0.123339E+10 0.602689E+09 0.630702E+09 0.186492E+10 0.152691E+09
August 0.126164E+10 0.582698E+09 0.678939E+09 0.183670E+10 0.179690E+09
September 0.110778E+10 0.584882E+09 0.522898E+09 0.151888E+10 0.301480E+09
October 0.104758E+10 0.652517E+09 0.395066E+09 0.128341E+10 0.540276E+09
November 0.792181E+09 0.466008E+09 0.326173E+09 0.833350E+09 0.722512E+09
December 0.702912E+09 0.438937E+09 0.263975E+09 0.688521E+09 0.967426E+09
           
Annual Sum or Average 0.126961E+11 0.689198E+10 0.580415E+10 0.160162E+11 0.623605E+10
Minimum of Months 0.702912E+09 0.419238E+09 0.263975E+09 0.688521E+09 0.152691E+09
Maximum of Months 0.132202E+10 0.736262E+09 0.678939E+09 0.190600E+10 0.967426E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1659.69 1090.95 1521.36 1068.19 453.17 0.00 0.00
February 1858.82 991.13 1641.64 1084.23 557.41 0.00 0.00
March 1800.41 780.14 1540.60 891.65 648.95 0.00 0.00
April 2016.88 541.30 1636.44 824.76 811.68 0.00 0.00
May 1808.72 415.84 1405.27 647.52 757.75 0.00 0.00
June 2054.28 276.69 1419.24 690.06 729.18 0.00 0.00
July 2094.66 186.14 1357.93 595.44 762.49 0.00 0.00
August 2213.02 216.96 1486.70 667.08 819.62 0.00 0.00
September 2170.28 375.67 1548.29 855.08 693.21 0.00 0.00
October 2123.37 633.14 1683.77 1154.44 529.33 0.00 0.00
November 1858.34 876.88 1624.34 1138.04 486.30 0.00 0.00
December 1734.87 1116.35 1584.16 1200.60 383.56 0.00 0.00
               
Annual Sum or Average 1949.36 623.27 1536.41 900.19 636.22 0.00 0.00
Minimum of Months 1659.69 186.14 1357.93 595.44 383.56 0.00 0.00
Maximum of Months 2213.02 1116.35 1683.77 1200.60 819.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.444532E+10 0.292200E+10 0.407481E+10 0.286105E+10 0.121377E+10 0.00 0.00
February 0.449687E+10 0.239773E+10 0.397146E+10 0.262298E+10 0.134849E+10 0.00 0.00
March 0.482221E+10 0.208952E+10 0.412633E+10 0.238819E+10 0.173815E+10 0.00 0.00
April 0.522774E+10 0.140305E+10 0.424165E+10 0.213779E+10 0.210386E+10 0.00 0.00
May 0.484447E+10 0.111378E+10 0.376388E+10 0.173433E+10 0.202955E+10 0.00 0.00
June 0.532470E+10 0.717169E+09 0.367867E+10 0.178862E+10 0.189005E+10 0.00 0.00
July 0.561033E+10 0.498558E+09 0.363708E+10 0.159482E+10 0.204226E+10 0.00 0.00
August 0.592736E+10 0.581117E+09 0.398197E+10 0.178671E+10 0.219526E+10 0.00 0.00
September 0.562537E+10 0.973746E+09 0.401317E+10 0.221638E+10 0.179679E+10 0.00 0.00
October 0.568723E+10 0.169581E+10 0.450982E+10 0.309205E+10 0.141777E+10 0.00 0.00
November 0.481682E+10 0.227288E+10 0.421028E+10 0.294980E+10 0.126048E+10 0.00 0.00
December 0.464669E+10 0.299002E+10 0.424302E+10 0.321568E+10 0.102734E+10 0.00 0.00
               
Annual Sum or Average 0.614751E+11 0.196554E+11 0.484521E+11 0.283884E+11 0.200637E+11 0.00 0.00
Minimum of Months 0.444532E+10 0.498558E+09 0.363708E+10 0.159482E+10 0.102734E+10 0.00 0.00
Maximum of Months 0.592736E+10 0.299002E+10 0.450982E+10 0.321568E+10 0.219526E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 2.60 -1.3 -7.5 3.29 -12.5 38.91 220.14 0.00
February 4.28 0.13 -5.8 3.80 -10.7 48.21 247.44 0.00
March 8.76 2.64 -5.5 4.72 -6.0 66.36 249.43 0.00
April 13.90 4.70 -6.4 4.61 -1.8 81.54 308.98 0.00
May 17.82 8.42 -1.1 4.68 3.61 77.67 310.50 0.00
June 23.21 12.42 4.15 4.28 9.16 70.88 348.57 0.00
July 25.63 16.13 10.74 4.00 14.07 80.74 308.61 0.00
August 24.08 15.39 10.38 3.96 13.00 86.20 290.42 0.00
September 20.49 12.87 7.70 3.48 8.22 67.00 274.65 0.00
October 13.71 6.72 -0.1 3.54 -0.8 42.11 283.53 0.00
November 6.96 1.72 -4.9 3.43 -7.6 39.44 239.51 0.01
December 2.07 -2.2 -8.9 2.95 -13.5 27.44 240.96 0.00
                 
Annual Sum or Average 13.68 6.50 -0.6 3.90 -0.3 60.60 276.96 0.00
Minimum of Months 2.07 -2.2 -8.9 2.95 -13.5 27.44 220.14 0.00
Maximum of Months 25.63 16.13 10.74 4.72 14.07 86.20 348.57 0.01



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.10 01-JAN-14:00 5.83 -6.7 5.20 -2.3 27.00 880.00
February 22.20 14-FEB-15:00 7.86 -10.0 4.60 4.72 61.50 778.50
March 22.80 08-MAR-13:00 9.68 -2.8 3.60 4.92 122.50 851.50
April 26.10 13-APR-16:00 10.32 -4.4 5.20 7.55 95.00 507.00
May 30.00 19-MAY-15:20 12.71 -1.5 8.93 13.35 108.33 887.00
June 38.90 28-JUN-15:00 14.16 -8.9 3.10 20.75 70.00 888.00
July 38.30 22-JUL-14:00 16.71 3.30 5.20 24.16 99.00 907.50
August 35.00 01-AUG-14:00 16.30 4.40 2.60 19.52 113.00 840.50
September 32.80 03-SEP-13:00 16.76 7.80 3.60 21.78 263.50 532.50
October 28.90 01-OCT-15:00 13.26 1.70 4.10 15.94 85.00 435.00
November 19.40 09-NOV-13:00 9.81 1.70 10.80 8.35 157.50 0.00
December 13.30 24-DEC-14:00 4.02 -8.3 8.20 -2.5 40.50 792.50
                 
Annual Sum or Average                
Minimum of Months 13.30   4.02 -10.0 2.60 -2.5 27.00 0.00
Maximum of Months 38.90   16.76 7.80 10.80 24.16 263.50 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -8.3 20-JAN-01:00 -8.3 -8.3 2.10 -25.6 0.00 0.00
February -6.7 04-FEB-06:10 -8.2 -11.7 5.10 -25.0 0.00 0.00
March -3.9 05-MAR-06:00 -5.7 -9.4 1.50 -21.6 17.00 434.50
April 1.70 06-APR-05:00 -2.4 -8.3 2.60 -12.9 28.00 215.00
May 4.40 07-MAY-04:00 -1.0 -8.3 1.50 -13.7 0.00 0.00
June 7.80 09-JUN-04:40 5.54 3.30 4.83 -7.8 0.00 0.00
July 16.10 08-JUL-02:00 14.67 13.90 0.00 4.72 0.00 0.00
August 12.80 31-AUG-05:00 10.77 9.40 3.10 -1.7 24.50 228.50
September 10.60 09-SEP-05:00 9.95 9.40 2.10 -2.5 15.50 177.00
October -2.8 26-OCT-04:10 -4.1 -6.1 2.42 -17.7 0.00 0.00
November -4.4 27-NOV-05:00 -6.9 -11.7 2.60 -22.7 0.00 0.00
December -9.4 15-DEC-04:00 -12.1 -21.7 0.00 -29.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -9.4   -12.1 -21.7 0.00 -29.7 0.00 0.00
Maximum of Months 16.10   14.67 13.90 5.10 4.72 28.00 434.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 6.84 05-JAN-13:00 16.10 -2.8 3.10 -0.1 62.00 873.00
February 7.86 14-FEB-15:00 22.20 -10.0 4.60 4.72 61.50 778.50
March 9.68 08-MAR-13:00 22.80 -2.8 3.60 4.92 122.50 851.50
April 10.95 14-APR-15:00 24.40 -0.6 8.20 17.21 237.00 154.00
May 15.08 22-MAY-12:30 28.60 6.40 5.15 16.76 167.00 0.00
June 18.19 24-JUN-13:00 31.70 11.70 2.60 19.17 130.00 891.50
July 19.21 31-JUL-14:00 32.80 12.80 6.20 22.98 264.50 624.50
August 19.18 26-AUG-12:00 27.80 15.60 3.60 17.03 289.00 426.50
September 18.19 05-SEP-12:00 23.90 15.60 3.10 13.35 196.50 796.00
October 16.16 11-OCT-10:00 23.90 12.20 13.40 13.73 219.50 450.00
November 9.81 09-NOV-13:00 19.40 1.70 10.80 8.35 157.50 0.00
December 4.92 01-DEC-15:00 12.80 -3.9 2.10 1.58 50.00 276.00
                 
Annual Sum or Average                
Minimum of Months 4.92   12.80 -10.0 2.10 -0.1 50.00 0.00
Maximum of Months 19.21   32.80 15.60 13.40 22.98 289.00 891.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -0.6 28-JAN-17:00 6.10 3.01 4.60 -5.0 0.00 0.00
February 2.20 17-FEB-10:00 7.20 4.72 3.10 -4.1 212.50 561.00
March 5.60 28-MAR-17:10 8.80 7.05 4.60 3.37 35.00 0.67
April 7.20 15-APR-06:00 13.30 9.79 7.20 6.35 116.00 422.00
May 13.90 24-MAY-14:00 16.70 14.90 4.60 11.07 128.00 0.00
June 13.30 30-JUN-13:00 26.70 17.72 6.70 20.75 170.00 126.50
July 17.80 01-JUL-13:00 22.20 19.05 3.60 13.91 361.00 125.00
August 17.20 26-AUG-09:00 21.70 18.59 2.60 11.65 243.50 681.50
September 15.60 05-SEP-11:00 22.20 17.61 3.10 12.79 231.00 705.00
October 13.90 02-OCT-16:00 20.60 16.04 6.20 13.54 38.50 65.00
November 6.10 09-NOV-21:00 8.90 7.38 11.80 3.69 0.00 0.00
December 1.10 25-DEC-08:00 2.20 1.65 2.10 -4.1 54.00 0.00
                 
Annual Sum or Average                
Minimum of Months -0.6   2.20 1.65 2.10 -5.0 0.00 0.00
Maximum of Months 17.80   26.70 19.05 11.80 20.75 361.00 705.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.28 25.87 0.00
February 18.00 13.00 16.00 10.91 34.17 0.00
March 18.00 13.00 16.00 12.10 41.92 0.00
April 18.00 13.00 16.00 14.59 56.24 0.00
May 18.00 13.00 16.00 17.73 59.47 0.00
June 18.00 13.00 16.00 20.66 62.98 0.00
July 18.00 13.00 16.00 22.59 61.22 0.00
August 18.00 13.00 16.00 23.01 57.83 0.00
September 18.00 13.00 16.00 21.78 48.11 0.00
October 18.00 13.00 16.00 19.25 37.89 0.00
November 18.00 13.00 16.00 16.11 28.37 0.00
December 18.00 13.00 16.00 13.20 24.17 0.00
             
Annual Sum or Average 18.00 13.00 16.00 16.97 44.90 0.00
Minimum of Months 18.00 13.00 16.00 10.91 24.17 0.00
Maximum of Months 18.00 13.00 16.00 23.01 62.98 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.639610E+10 -0.622518E+10 0.00 0.00 744.00 0.00 -170920281.8 81.22 0.00 0.00
February 0.578767E+10 -0.563427E+10 0.00 0.00 672.00 0.00 -153395986.0 81.22 0.00 0.00
March 0.645937E+10 -0.629386E+10 0.00 0.00 744.00 0.00 -165509719.1 81.22 0.00 0.00
April 0.619868E+10 -0.604345E+10 0.00 0.00 720.00 0.00 -155225548.3 81.22 0.00 0.00
May 0.641717E+10 -0.626017E+10 0.00 0.00 744.00 0.00 -156993099.7 81.21 0.00 0.00
June 0.623652E+10 -0.608657E+10 0.00 0.00 720.00 0.00 -149948043.6 81.21 0.00 0.00
July 0.637138E+10 -0.621711E+10 0.00 0.00 744.00 0.00 -154265078.1 81.21 0.00 0.00
August 0.644957E+10 -0.629524E+10 0.00 0.00 744.00 0.00 -154325419.3 81.21 0.00 0.00
September 0.619477E+10 -0.604482E+10 0.00 0.00 720.00 0.00 -149950476.7 81.21 0.00 0.00
October 0.638376E+10 -0.622382E+10 0.00 0.00 744.00 0.00 -159945484.8 81.21 0.00 0.00
November 0.618675E+10 -0.602463E+10 0.00 0.00 720.00 0.00 -162124861.9 81.22 0.00 0.00
December 0.638908E+10 -0.621707E+10 0.00 0.00 744.00 0.00 -172009578.1 81.22 0.00 0.00
                     
Annual Sum or Average 0.754708E+11 -0.735662E+11 0.00 0.00 8760.00 0.00 -0.190461E+10 81.21 0.00 0.00
Minimum of Months 0.578767E+10 -0.629524E+10 0.00 0.00 672.00 0.00 -172009578.1 81.21 0.00 0.00
Maximum of Months 0.645937E+10 -0.563427E+10 0.00 0.00 744.00 0.00 -149948043.6 81.22 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.242243E+11 -0.232334E+11 0.00 0.00 744.00 0.00 -990892930.5 58.99 0.00 0.00
February 0.220757E+11 -0.211897E+11 0.00 0.00 672.00 0.00 -885982100.9 58.99 0.00 0.00
March 0.240271E+11 -0.230857E+11 0.00 0.00 744.00 0.00 -941363260.6 58.99 0.00 0.00
April 0.218544E+11 -0.209887E+11 0.00 0.00 720.00 0.00 -865722327.5 58.99 0.00 0.00
May 0.210718E+11 -0.202084E+11 0.00 0.00 744.00 0.00 -863348939.2 58.98 0.00 0.00
June 0.190612E+11 -0.182439E+11 0.00 0.00 720.00 0.00 -817364921.8 58.98 0.00 0.00
July 0.185310E+11 -0.176925E+11 0.00 0.00 744.00 0.00 -838538754.3 58.99 0.00 0.00
August 0.185516E+11 -0.177125E+11 0.00 0.00 744.00 0.00 -839060273.4 58.99 0.00 0.00
September 0.184100E+11 -0.175926E+11 0.00 0.00 720.00 0.00 -817475236.7 58.99 0.00 0.00
October 0.202367E+11 -0.193463E+11 0.00 0.00 744.00 0.00 -890428010.1 58.99 0.00 0.00
November 0.211344E+11 -0.202056E+11 0.00 0.00 720.00 0.00 -928854336.1 58.99 0.00 0.00
December 0.232666E+11 -0.222657E+11 0.00 0.00 744.00 0.00 -0.100087E+10 58.99 0.00 0.00
                     
Annual Sum or Average 0.252445E+12 -0.241765E+12 0.00 0.00 8760.00 0.00 -0.106799E+11 58.99 0.00 0.00
Minimum of Months 0.184100E+11 -0.232334E+11 0.00 0.00 672.00 0.00 -0.100087E+10 58.98 0.00 0.00
Maximum of Months 0.242243E+11 -0.175926E+11 0.00 0.00 744.00 0.00 -817364921.8 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.51 0.50 01-JAN-07:40 1392.16 25.06 162.33 285.00 1264.02 25.68 171.67 286.00
February 282.00 0.51 0.50 01-FEB-07:40 1714.46 24.91 172.17 271.00 1205.90 24.29 168.83 271.33
March 351.33 0.51 0.50 01-MAR-06:00 1094.83 20.57 126.50 328.83 1491.20 21.25 153.50 330.17
April 381.83 0.52 0.50 01-APR-06:30 1327.63 21.06 175.33 362.50 1379.54 21.01 155.00 360.33
May 378.00 0.51 0.50 01-MAY-06:10 1286.73 20.64 132.17 386.17 1541.03 20.65 93.00 375.33
June 412.83 0.51 0.50 01-JUN-05:40 850.41 20.63 84.83 385.00 1519.69 19.70 75.50 392.83
July 395.33 0.51 0.50 01-JUL-06:40 873.47 20.39 103.17 382.33 1377.80 20.33 122.17 382.67
August 408.83 0.52 0.50 01-AUG-05:00 1221.31 20.86 151.33 381.50 1231.63 20.86 167.17 381.33
September 359.33 0.51 0.50 01-SEP-06:19 1199.49 21.16 142.50 335.17 1075.47 20.62 121.67 337.67
October 329.00 0.52 0.50 01-OCT-06:49 1432.79 23.24 154.83 317.17 1670.86 22.94 159.83 318.67
November 284.17 0.51 0.50 01-NOV-06:49 1439.63 26.21 169.00 281.17 1500.48 25.94 173.00 280.00
December 265.67 0.51 0.50 01-DEC-07:40 1894.58 27.69 152.00 268.50 1975.37 28.39 156.33 269.33
                         
Annual Sum or Average 4149.83 0.51     1275.16 22.37 1726.17 3984.33 1425.91 22.28 1717.67 3985.67
Minimum of Months 265.67 0.51 0.50   850.41 20.39 84.83 268.50 1075.47 19.70 75.50 269.33
Maximum of Months 412.83 0.52 0.50   1894.58 27.69 175.33 386.17 1975.37 28.39 173.00 392.83



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:1 HEATING COIL

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.258647E+11 97910.98 20-JAN-04:03 0.00 0.00 0.00 0.00 0.00
February 0.189152E+11 103031.37 06-FEB-04:03 0.00 0.00 0.00 0.00 0.00
March 0.949917E+10 64318.30 05-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.283233E+10 28736.71 06-APR-04:03 0.00 0.00 0.00 0.00 0.00
May 0.628931E+09 17025.09 06-MAY-04:04 0.00 0.00 0.00 0.00 0.00
June 37309290.91 10007.16 15-JUN-03:47 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 770209.54 1745.36 29-SEP-03:47 0.00 0.00 0.00 0.00 0.00
October 0.355482E+10 33915.37 25-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.107074E+11 34749.69 27-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.264830E+11 109042.80 15-DEC-04:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.985237E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.264830E+11 109042.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:2 HEATING COIL

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.142035E+11 28414.65 22-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.998302E+10 34693.66 04-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.378372E+10 22383.17 05-MAR-05:04 0.00 0.00 0.00 0.00 0.00
April 0.657303E+09 15352.49 19-APR-04:05 0.00 0.00 0.00 0.00 0.00
May 46592258.76 7824.34 06-MAY-04:06 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:01 0.00 0.00 0.00 0.00 0.00
October 0.114788E+10 24886.71 25-OCT-04:04 0.00 0.00 0.00 0.00 0.00
November 0.450956E+10 22158.58 27-NOV-05:17 0.00 0.00 0.00 0.00 0.00
December 0.141785E+11 38525.36 28-DEC-05:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.485101E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142035E+11 38525.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:1 COOLING COIL

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00
February 0.00 0.00 0.280888E+09 0.280888E+09 11302.41 14-FEB-14:00 11302.41 0.00
March 0.00 0.00 0.927265E+09 0.926891E+09 16801.92 08-MAR-14:00 16801.92 0.00
April 0.00 0.00 0.833567E+10 0.832970E+10 75519.88 15-APR-03:01 63435.06 0.00
May 0.00 0.00 0.185233E+11 0.180766E+11 75519.88 31-MAY-03:01 65354.01 0.00
June 0.00 0.00 0.388286E+11 0.374212E+11 75519.88 27-JUN-03:48 67359.51 0.00
July 0.00 0.00 0.553771E+11 0.475426E+11 75895.74 16-JUL-03:01 37427.06 0.00
August 0.00 0.00 0.491807E+11 0.421721E+11 75610.32 15-AUG-03:01 47196.27 0.00
September 0.00 0.00 0.309015E+11 0.273044E+11 75519.88 04-SEP-03:41 56442.43 0.00
October 0.00 0.00 0.111751E+11 0.102998E+11 75519.88 10-OCT-03:01 52319.78 0.00
November 0.00 0.00 47226438.30 43679947.22 7289.79 09-NOV-14:00 7007.28 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:02 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.213577E+12 0.192398E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.553771E+11 0.475426E+11 75895.74   67359.51 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:2 COOLING COIL

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3207393.40 2561768.46 3015.37 31-JAN-04:10 2370.17 0.00
February 0.00 0.00 0.163326E+09 0.162540E+09 6043.51 14-FEB-16:08 6043.51 0.00
March 0.00 0.00 0.690439E+09 0.684489E+09 18478.58 14-MAR-03:41 15737.04 0.00
April 0.00 0.00 0.555470E+10 0.552486E+10 36999.59 02-APR-03:01 34547.72 0.00
May 0.00 0.00 0.129609E+11 0.122747E+11 36999.59 28-MAY-03:01 20799.65 0.00
June 0.00 0.00 0.268113E+11 0.253648E+11 36999.59 30-JUN-03:51 24603.79 0.00
July 0.00 0.00 0.381689E+11 0.323576E+11 37383.02 01-JUL-03:11 15271.75 0.00
August 0.00 0.00 0.333614E+11 0.279273E+11 36999.59 10-AUG-03:25 26559.88 0.00
September 0.00 0.00 0.211289E+11 0.177903E+11 36999.59 03-SEP-03:40 27447.36 0.00
October 0.00 0.00 0.767028E+10 0.675840E+10 36999.59 01-OCT-03:01 23995.73 0.00
November 0.00 0.00 0.111977E+09 91406547.41 36999.59 09-NOV-04:42 27210.35 0.00
December 0.00 0.00 3186152.67 2649309.71 4253.65 01-DEC-04:08 3496.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.146629E+12 0.128942E+12       0.00
Minimum of Months 0.00 0.00 3186152.67 2561768.46 3015.37   2370.17 0.00
Maximum of Months 0.00 0.00 0.381689E+11 0.323576E+11 37383.02   34547.72 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 9133.75 17537.39 30-JAN-07:56
February 0.00 0.00 01-FEB-00:01 9218.12 17557.31 14-FEB-07:57
March 0.00 0.00 01-MAR-00:01 9078.84 17404.44 01-MAR-08:00
April 0.00 0.00 01-APR-00:01 8557.95 16637.96 03-APR-18:30
May 0.00 0.00 01-MAY-00:01 8006.70 15681.72 01-MAY-18:17
June 0.00 0.00 01-JUN-00:01 7501.03 14539.77 01-JUN-07:00
July 0.00 0.00 01-JUL-00:01 7069.54 13645.73 03-JUL-18:53
August 0.00 0.00 01-AUG-00:01 7077.20 13425.48 31-AUG-07:00
September 0.00 0.00 01-SEP-00:01 7250.41 14034.58 29-SEP-06:57
October 0.00 0.00 01-OCT-00:01 7685.51 15094.47 31-OCT-18:50
November 0.00 0.00 01-NOV-00:01 8256.48 16200.23 30-NOV-19:55
December 0.00 0.00 01-DEC-00:02 8773.35 17054.42 29-DEC-19:57
             
Annual Sum or Average 0.00     8127.82    
Minimum of Months 0.00 0.00   7069.54 13425.48  
Maximum of Months 0.00 0.00   9218.12 17557.31  



Table of Contents

Report: FanReportMonthly

For: DINING EXHAUST FAN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:01 0.00
February 0.00 -0.0 0.00 01-FEB-00:01 0.00
March 0.00 -0.0 0.00 01-MAR-00:01 0.00
April 0.00 -0.0 0.00 01-APR-00:01 0.00
May 0.00 0.00 0.00 01-MAY-00:01 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 -0.0 0.00 01-SEP-00:01 0.00
October 0.00 -0.0 0.00 01-OCT-00:01 0.00
November 0.00 0.00 0.00 01-NOV-00:01 0.00
December 0.00 0.00 0.00 01-DEC-00:02 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN EXHAUST FAN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.185355E+10 0.27 824.13 01-JAN-00:01 0.32
February 0.168160E+10 0.27 824.13 01-FEB-00:01 0.32
March 0.189818E+10 0.28 824.13 01-MAR-00:01 0.32
April 0.185623E+10 0.28 824.13 01-APR-03:10 0.32
May 0.196456E+10 0.29 824.13 01-MAY-03:01 0.32
June 0.197396E+10 0.30 824.13 01-JUN-01:05 0.32
July 0.208324E+10 0.30 824.13 01-JUL-00:40 0.32
August 0.207854E+10 0.30 824.13 01-AUG-00:40 0.32
September 0.198978E+10 0.30 824.13 01-SEP-00:40 0.32
October 0.195245E+10 0.28 824.13 01-OCT-00:50 0.32
November 0.182982E+10 0.28 824.13 01-NOV-03:01 0.32
December 0.185157E+10 0.27 824.13 01-DEC-00:02 0.32
           
Annual Sum or Average 0.230135E+11 0.28      
Minimum of Months 0.168160E+10 0.27 824.13   0.32
Maximum of Months 0.208324E+10 0.30 824.13   0.32



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_1:1_ADDAQ FAN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.718634E+10 0.95 5917.99 20-JAN-04:03 1.71
February 0.633063E+10 0.94 6227.48 06-FEB-04:03 1.71
March 0.658635E+10 0.89 5128.93 05-MAR-05:05 1.48
April 0.614594E+10 0.87 3838.54 06-APR-04:03 1.26
May 0.627680E+10 0.87 4262.09 22-MAY-03:01 1.33
June 0.617189E+10 0.88 6990.97 29-JUN-03:01 1.69
July 0.650115E+10 0.89 6990.97 07-JUL-03:01 1.69
August 0.639513E+10 0.88 6990.97 15-AUG-03:01 1.69
September 0.609410E+10 0.88 6990.97 07-SEP-03:01 1.69
October 0.638693E+10 0.88 6183.74 02-OCT-03:01 1.60
November 0.642882E+10 0.90 4056.61 27-NOV-05:01 1.30
December 0.720704E+10 0.95 6590.83 15-DEC-04:03 1.71
           
Annual Sum or Average 0.777111E+11 0.90      
Minimum of Months 0.609410E+10 0.87 3838.54   1.26
Maximum of Months 0.720704E+10 0.95 6990.97   1.71



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_2:2_ADDAQ FAN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.181469E+10 0.58 1123.98 22-JAN-05:03 0.85
February 0.159957E+10 0.58 1212.63 04-FEB-05:03 0.88
March 0.167251E+10 0.57 1038.83 05-MAR-05:04 0.81
April 0.158548E+10 0.56 1807.04 15-APR-03:01 1.07
May 0.164204E+10 0.57 1807.04 01-MAY-03:01 1.07
June 0.178925E+10 0.62 1807.04 01-JUN-03:01 1.07
July 0.199851E+10 0.66 1807.04 01-JUL-03:11 1.06
August 0.186087E+10 0.63 1807.04 01-AUG-03:11 1.06
September 0.162388E+10 0.60 1807.04 01-SEP-03:11 1.06
October 0.165279E+10 0.57 1807.04 01-OCT-03:01 1.06
November 0.163039E+10 0.57 1688.52 01-NOV-03:01 1.04
December 0.181421E+10 0.58 1266.73 28-DEC-05:05 0.90
           
Annual Sum or Average 0.206842E+11 0.59      
Minimum of Months 0.158548E+10 0.56 1038.83   0.81
Maximum of Months 0.199851E+10 0.66 1807.04   1.07



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 37879553.69 11363866.11 17.86 01-JAN-00:01 5.36 5.36 48.99 0.14
February 34213790.43 10264137.13 17.86 01-FEB-00:01 5.36 5.36 48.01 0.14
March 37879553.69 11363866.11 17.86 01-MAR-00:01 5.36 5.36 48.22 0.14
April 36657632.61 10997289.78 17.86 01-APR-05:10 5.36 5.36 51.55 0.14
May 37879553.69 11363866.11 17.86 01-MAY-05:10 5.36 5.36 52.33 0.14
June 36657632.61 10997289.78 17.86 01-JUN-05:10 5.36 5.36 52.77 0.14
July 37879553.69 11363866.11 17.86 01-JUL-05:10 5.36 5.36 53.60 0.14
August 37879553.69 11363866.11 17.86 01-AUG-05:10 5.36 5.36 53.32 0.14
September 36657632.61 10997289.78 17.86 01-SEP-05:10 5.36 5.36 53.71 0.14
October 37879553.69 11363866.11 17.86 01-OCT-05:10 5.36 5.36 53.19 0.14
November 36657632.61 10997289.78 17.86 01-NOV-05:10 5.36 5.36 52.60 0.14
December 37879553.69 11363866.11 17.86 01-DEC-00:02 5.36 5.36 48.74 0.14
                 
Annual Sum or Average 0.446001E+09 0.133800E+09            
Minimum of Months 34213790.43 10264137.13 17.86   5.36 5.36 48.01 0.14
Maximum of Months 37879553.69 11363866.11 17.86   5.36 5.36 53.71 0.14



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 48.99 59.92 9133.75 17537.39 30-JAN-07:56
February 0.00 0.00 01-FEB-00:01 48.01 58.80 9218.12 17557.31 14-FEB-07:57
March 0.00 0.00 01-MAR-00:01 48.22 58.85 9078.84 17404.44 01-MAR-08:00
April 0.00 0.00 01-APR-00:01 49.94 49.94 8557.95 16637.96 03-APR-18:30
May 0.00 0.00 01-MAY-00:01 50.74 50.74 8006.70 15681.72 01-MAY-18:17
June 0.00 0.00 01-JUN-00:01 50.67 50.67 7501.03 14539.77 01-JUN-07:00
July 0.00 0.00 01-JUL-00:01 51.59 51.59 7069.54 13645.73 03-JUL-18:53
August 0.00 0.00 01-AUG-00:01 51.47 51.47 7077.20 13425.48 31-AUG-07:00
September 0.00 0.00 01-SEP-00:01 51.79 51.79 7250.41 14034.58 29-SEP-06:57
October 0.00 0.00 01-OCT-00:01 49.41 49.41 7685.51 15094.47 31-OCT-18:50
November 0.00 0.00 01-NOV-00:01 50.39 50.39 8256.48 16200.23 30-NOV-19:55
December 0.00 0.00 01-DEC-00:02 48.74 58.11 8773.35 17054.42 29-DEC-19:57
                 
Annual Sum or Average 0.00         8127.82    
Minimum of Months 0.00 0.00   48.01 49.41 7069.54 13425.48  
Maximum of Months 0.00 0.00   51.79 59.92 9218.12 17557.31  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_1:1

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.718634E+10 0.00 0.00
February 0.00 0.00 0.00 0.642290E+10 0.00 0.00
March 0.00 0.00 0.00 0.689383E+10 0.00 0.00
April 0.00 0.00 0.00 0.874563E+10 0.00 0.00
May 0.00 0.00 0.00 0.118721E+11 0.00 0.00
June 0.00 0.00 0.00 0.176502E+11 0.00 0.00
July 0.00 0.00 0.00 0.225092E+11 0.00 0.00
August 0.00 0.00 0.00 0.205129E+11 0.00 0.00
September 0.00 0.00 0.00 0.151482E+11 0.00 0.00
October 0.00 0.00 0.00 0.976795E+10 0.00 0.00
November 0.00 0.00 0.00 0.644466E+10 0.00 0.00
December 0.00 0.00 0.00 0.720704E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.140361E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.642290E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.225092E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_2:2

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.181566E+10 0.00 0.00
February 0.00 0.00 0.00 0.164729E+10 0.00 0.00
March 0.00 0.00 0.00 0.187520E+10 0.00 0.00
April 0.00 0.00 0.00 0.310526E+10 0.00 0.00
May 0.00 0.00 0.00 0.503548E+10 0.00 0.00
June 0.00 0.00 0.00 0.870384E+10 0.00 0.00
July 0.00 0.00 0.00 0.116239E+11 0.00 0.00
August 0.00 0.00 0.00 0.102012E+11 0.00 0.00
September 0.00 0.00 0.00 0.696032E+10 0.00 0.00
October 0.00 0.00 0.00 0.367064E+10 0.00 0.00
November 0.00 0.00 0.00 0.166279E+10 0.00 0.00
December 0.00 0.00 0.00 0.181517E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.581167E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.164729E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.116239E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_1:1

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.718634E+10 0.00 0.258647E+11 0.00 0.00 0.00 0.00 0.00
February 0.633063E+10 0.280888E+09 0.189152E+11 0.00 0.00 0.00 0.00 0.00
March 0.658635E+10 0.927265E+09 0.949917E+10 0.00 0.00 0.00 0.00 0.00
April 0.614594E+10 0.833105E+10 0.283233E+10 0.00 0.00 0.00 0.00 0.00
May 0.627680E+10 0.185033E+11 0.628931E+09 0.00 0.00 0.00 0.00 0.00
June 0.617189E+10 0.387398E+11 37309290.91 0.00 0.00 0.00 0.00 0.00
July 0.650115E+10 0.551197E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.639513E+10 0.489524E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.609410E+10 0.308412E+11 770209.54 0.00 0.00 0.00 0.00 0.00
October 0.638693E+10 0.111625E+11 0.355482E+10 0.00 0.00 0.00 0.00 0.00
November 0.642882E+10 47226438.30 0.107074E+11 0.00 0.00 0.00 0.00 0.00
December 0.720704E+10 0.00 0.264830E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.777111E+11 0.212905E+12 0.985237E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.609410E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.720704E+10 0.551197E+11 0.264830E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_2:2

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.181469E+10 3207393.40 0.142035E+11 0.00 0.00 0.00 0.00 0.00
February 0.159957E+10 0.163326E+09 0.998302E+10 0.00 0.00 0.00 0.00 0.00
March 0.167251E+10 0.690439E+09 0.378372E+10 0.00 0.00 0.00 0.00 0.00
April 0.158548E+10 0.554335E+10 0.657303E+09 0.00 0.00 0.00 0.00 0.00
May 0.164204E+10 0.129475E+11 46592258.76 0.00 0.00 0.00 0.00 0.00
June 0.178925E+10 0.267373E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.199851E+10 0.379776E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.186087E+10 0.331939E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.162388E+10 0.210822E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.165279E+10 0.766357E+10 0.114788E+10 0.00 0.00 0.00 0.00 0.00
November 0.163039E+10 0.110719E+09 0.450956E+10 0.00 0.00 0.00 0.00 0.00
December 0.181421E+10 3186152.67 0.141785E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.206842E+11 0.146116E+12 0.485101E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158548E+10 3186152.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.199851E+10 0.379776E+11 0.142035E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_1:1

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.718634E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.633063E+10 0.00 0.00 0.00 92271664.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.658635E+10 0.00 0.00 0.00 0.307482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.614594E+10 0.00 0.00 0.00 0.259969E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.627680E+10 0.00 0.00 0.00 0.559531E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.617189E+10 0.00 0.00 0.00 0.114783E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.650115E+10 0.00 0.00 0.00 0.160081E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.639513E+10 0.00 0.00 0.00 0.141178E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.609410E+10 0.00 0.00 0.00 0.905406E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.638693E+10 0.00 0.00 0.00 0.338102E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.642882E+10 0.00 0.00 0.00 15843799.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.720704E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.777111E+11 0.00 0.00 0.00 0.626498E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.609410E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.720704E+10 0.00 0.00 0.00 0.160081E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_2:2

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.181469E+10 0.00 0.00 0.00 966071.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.159957E+10 0.00 0.00 0.00 47716191.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.167251E+10 0.00 0.00 0.00 0.202692E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.158548E+10 0.00 0.00 0.00 0.151978E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.164204E+10 0.00 0.00 0.00 0.339344E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.178925E+10 0.00 0.00 0.00 0.691460E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.199851E+10 0.00 0.00 0.00 0.962537E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.186087E+10 0.00 0.00 0.00 0.834030E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.162388E+10 0.00 0.00 0.00 0.533643E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.165279E+10 0.00 0.00 0.00 0.201785E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.163039E+10 0.00 0.00 0.00 32401957.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.181421E+10 0.00 0.00 0.00 963172.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.206842E+11 0.00 0.00 0.00 0.374325E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158548E+10 0.00 0.00 0.00 963172.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.199851E+10 0.00 0.00 0.00 0.962537E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.583163E+11 0.00 0.00 1688068.30 0.00 0.257732E+10 0.232899E+10 0.00 3.54
February 0.477061E+11 0.00 0.00 6864184.35 0.00 0.162567E+10 0.400973E+10 0.00 3.61
March 0.358033E+11 0.00 0.00 28472139.96 0.00 0.365348E+09 0.132999E+11 0.00 3.83
April 0.188663E+11 0.00 0.00 67702234.99 0.00 13747236.35 0.188855E+11 0.00 4.19
May 0.938727E+10 62571720.01 0.00 0.104246E+09 0.00 3893348.08 0.198291E+11 0.00 4.29
June 0.285543E+10 0.260474E+10 0.00 0.100975E+09 1516028.77 1076162.56 0.118287E+11 0.00 4.15
July 0.534263E+09 0.541421E+10 0.00 63803345.01 17356118.32 0.00 0.513112E+10 0.00 4.19
August 0.752689E+09 0.297821E+10 0.00 93804187.52 5951092.01 0.00 0.878681E+10 0.00 4.30
September 0.266090E+10 0.446880E+09 0.00 0.134830E+09 0.00 101828.82 0.178308E+11 0.00 4.46
October 0.191551E+11 22078086.61 0.00 80643866.40 0.00 8341757.97 0.208827E+11 0.00 4.24
November 0.417383E+11 0.00 0.00 8988728.91 0.00 36846014.10 0.967070E+10 0.00 3.58
December 0.624177E+11 0.00 0.00 139208.86 0.00 0.155244E+10 0.499354E+09 0.00 3.53
                   
Annual Sum or Average 0.300194E+12 0.115287E+11 0.00 0.692157E+09 24823239.09 0.618478E+10 0.132983E+12 0.00 3.99
Minimum of Months 0.534263E+09 0.00 0.00 139208.86 0.00 0.00 0.499354E+09 0.00 3.53
Maximum of Months 0.624177E+11 0.541421E+10 0.00 0.134830E+09 17356118.32 0.257732E+10 0.208827E+11 0.00 4.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.541549E+11 0.00 0.00 866668.09 0.289201E+09 0.00 0.238958E+10 0.00 8.15
February 0.436757E+11 0.00 0.00 5838272.54 0.356091E+09 10543008.44 0.465709E+10 0.00 8.13
March 0.322996E+11 0.00 0.00 24120303.25 56483433.57 0.00 0.155983E+11 0.00 8.06
April 0.173491E+11 0.00 0.00 61136325.21 752279.43 0.00 0.226055E+11 0.00 8.08
May 0.662340E+10 0.00 0.00 0.100647E+09 0.00 0.00 0.269556E+11 0.00 8.16
June 0.124855E+10 0.115224E+10 0.00 0.126010E+09 0.00 0.00 0.186220E+11 0.00 8.43
July 5611917.68 0.235184E+10 0.00 0.127010E+09 0.00 0.00 0.989275E+10 0.00 8.69
August 16704096.11 0.218197E+10 0.00 0.137710E+09 0.00 0.00 0.141455E+11 0.00 8.58
September 0.596895E+09 0.108339E+09 0.00 0.132141E+09 0.00 0.00 0.240376E+11 0.00 8.29
October 0.159237E+11 0.00 0.00 73248839.59 23153636.45 2305267.14 0.243037E+11 0.00 8.13
November 0.376940E+11 0.00 0.00 8300038.04 28765969.13 0.00 0.105992E+11 0.00 8.01
December 0.559843E+11 0.00 0.00 295204.85 0.256841E+09 7097471.49 0.853951E+09 0.00 8.14
                   
Annual Sum or Average 0.265572E+12 0.579439E+10 0.00 0.797324E+09 0.101129E+10 19945747.07 0.174661E+12 0.00 8.24
Minimum of Months 5611917.68 0.00 0.00 295204.85 0.00 0.00 0.853951E+09 0.00 8.01
Maximum of Months 0.559843E+11 0.235184E+10 0.00 0.137710E+09 0.356091E+09 10543008.44 0.269556E+11 0.00 8.69



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:26:56

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.524655E+11 0.103339E+11 0.195867E+12 32811863.36 0.226773E+11
February 0.703023E+11 0.947189E+10 0.167312E+12 0.441585E+09 0.204733E+11
March 0.100511E+12 0.929551E+10 0.163500E+12 0.225841E+10 0.230590E+11
April 0.134659E+12 0.831666E+10 0.132236E+12 0.415616E+10 0.388301E+11
May 0.147031E+12 0.740729E+10 0.110404E+12 0.438410E+10 0.626725E+11
June 0.139346E+12 0.532902E+10 0.645214E+11 0.262766E+10 0.107750E+12
July 0.140909E+12 0.427716E+10 0.293415E+11 0.137335E+10 0.144030E+12
August 0.134225E+12 0.502370E+10 0.465100E+11 0.219256E+10 0.129419E+12
September 0.104174E+12 0.527692E+10 0.838145E+11 0.427662E+10 0.889412E+11
October 0.788331E+11 0.719951E+10 0.136208E+12 0.462766E+10 0.449752E+11
November 0.588614E+11 0.878121E+10 0.166609E+12 0.504070E+09 0.181382E+11
December 0.477499E+11 0.103462E+11 0.196992E+12 0.00 0.214493E+11
           
Annual Sum or Average 0.120907E+13 0.910590E+11 0.149332E+13 0.268750E+11 0.722414E+12
Minimum of Months 0.477499E+11 0.427716E+10 0.293415E+11 0.00 0.181382E+11
Maximum of Months 0.147031E+12 0.103462E+11 0.196992E+12 0.462766E+10 0.144030E+12