Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:25:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1912.59 | 3741.71 | 3741.71 |
Net Site Energy | 1912.59 | 3741.71 | 3741.71 |
Total Source Energy | 3997.45 | 7820.45 | 7820.45 |
Net Source Energy | 3997.45 | 7820.45 | 7820.45 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 174.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 110.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 129.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.47 | 344.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 50.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 923.77 | 988.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 174.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 110.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 63.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 129.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.47 | 344.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 174.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 110.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 63.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 129.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.47 | 344.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 50.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 211.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 617.03 | 1015.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 978.71 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1807.22 | 1934.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 211.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 617.03 | 1015.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 978.71 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1807.22 | 1934.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 923.766 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 923.766 | 100.00 |
Total On-Site and Utility Electric Sources | 923.766 | 100.00 |
Total Electricity End Uses | 923.766 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3728.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 9.5182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 10.6727 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.8331 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.8331 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.5182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 10.6727 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 9.8331 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 9.8331 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 9.8331 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-17:19 | 15-DEC-04:30 | - | - | - | - | - | - | - | - | - | - | 30-JAN-07:00 |
Heating | 0.00 | 148779.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26594.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2554.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20315.44 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7289.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4443.74 | 993.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1594.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 62809.56 | 154298.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 148779.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 26594.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2554.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19287.94 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7289.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4443.74 | 993.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 440.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 960.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 188.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 349.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 200.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 142.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1423.36 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 408.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.02 | 373.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 160.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2925.57 | 1071.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 369.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 683.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 391.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 800.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.60 | 731.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 314.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5723.46 | 2096.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 369.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 683.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 391.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 800.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.60 | 731.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 314.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5723.46 | 2096.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.40 |
KITCHEN DIRECT AIR | 1.90 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.40 | 4.40 | 4.40 | 4.40 | 4.40 | 4.40 | 1.00 | 0.999946 | 4.40 |
PSZ-AC_2:2 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.00 | 1.000000 | 1.90 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.40 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.90 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.40 | 7463.26 |
PSZ-AC_2:2_ADDAQ FAN | 1.90 | 2033.55 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.40 | 4.40 | 4.40 | 2.90 | 81221.36 | 121516.75 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.90 | 1.90 | 1.90 | 1.25 | 40825.94 | 85222.27 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.40 | 2.20 | 2.93 | 81221.36 | 40610.68 | 0.800800 | 0.800800 |
PSZ-AC_2:2 COOLING COIL | 1.90 | 0.950215 | 1.27 | 40825.94 | 20412.97 | 0.749300 | 0.749300 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 121516.75 |
PSZ-AC_2:2 HEATING COIL | 85222.27 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 9.518 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 74.446 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 10.673 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1071.313 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3538.380 | 9.518 | 12.631 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3538.380 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1487.835 | 10.673 | 197.643 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1487.835 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.8794 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1372 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2338 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9031 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.210 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.201 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.28842413E-12 | 0.14163715E-14 | -0.83625437E-13 | 0.83302026E-16 |
34 | 6 | 0.27446597E-07 | 0.24415596E-09 | 0.62976823E-08 | -0.12863247E-12 |
35 | 5 | -0.18387070E-03 | 0.21059431E-05 | -0.94655602E-04 | 0.62291981E-08 |
36 | 4 | 0.28482235 | 0.10320537E-02 | 0.97050522E-01 | -0.32540306E-04 |
37 | 3 | -7.1212123 | 0.32167701E-01 | -2.2958568 | 0.28298028E-01 |
38 | 2 | 40.392481 | 0.11496341 | 15.088345 | -0.32800964 |
39 | 1 | -80.178917 | 0.52112252E-01 | -28.983173 | 1.0708012 |
40 | 0 | 46.824341 | 0.10529732E-02 | 16.295060 | |
41 | 7 | -0.30956576E-08 | -0.21303207E-14 | 0.16211864E-14 | -0.47943075E-16 |
42 | 6 | 0.39621431E-05 | 0.26242558E-08 | 0.31947295E-02 | -0.26800069E-04 |
43 | 5 | -0.27788690E-03 | 0.15515089E-05 | -0.22400076 | 0.19585881E-02 |
44 | 4 | 0.63462498E-02 | 0.70567942E-04 | 4.8341454 | -0.45309197E-01 |
45 | 3 | -0.55586032E-01 | 0.56073102E-03 | -38.047399 | 0.39894095 |
46 | 2 | 0.19717555 | 0.93224475E-03 | 116.53452 | -1.4186157 |
47 | 1 | -0.28446589 | 0.28372391E-03 | -143.93707 | 2.0495292 |
48 | 0 | 0.13865977 | 0.68942715E-05 | 60.838472 | |
49 | 7 | -0.17992014E-08 | -0.42643710E-15 | 0.60732754E-14 | -0.80508795E-16 |
50 | 6 | 0.65450224E-05 | 0.44811019E-08 | 0.31871723E-02 | -0.26736672E-04 |
51 | 5 | -0.47085772E-03 | 0.26548585E-05 | -0.22357125 | 0.19547969E-02 |
52 | 4 | 0.10832139E-01 | 0.12085242E-03 | 4.8269919 | -0.45240433E-01 |
53 | 3 | -0.95125865E-01 | 0.96112441E-03 | -38.006990 | 0.39849429 |
54 | 2 | 0.33777835 | 0.15989493E-02 | 116.45587 | -1.4175637 |
55 | 1 | -0.48753632 | 0.48725992E-03 | -143.89078 | 2.0487682 |
56 | 0 | 0.23769862 | 0.11769722E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.419_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.419_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.419_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6522E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6647E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5051E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4119E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4280E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4078E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1904E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1008E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.6152E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.5949E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.2751E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.2510E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2945E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.2856E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.1278E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.1278E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6382E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6194E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3790E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4638E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3720E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3983E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.1008E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1904E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 41369.35845 | 49643.23014 | 3.66764 | 4.40117 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.83000 | 5.69897E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 7237.11690 | 8684.54028 | 0.37714 | 1.33138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -7.90000 | 2.34317E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 21051.46506 | 25261.75807 | 1.58369 | 1.90043 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 63709.25 | 4.40141 | 4.40141 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 63468.20 | 1.33138 | 1.33138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 34779.45 | 1.90043 | 1.90043 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 58015.80 | 1.21700 | 1.21700 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.40117 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.90043 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.40117 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.40117 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.40117 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.40117 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.40141 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.40141 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99995 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.90043 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.90043 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.90043 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.90043 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.90043 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.90043 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.40141 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.90043 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.40141 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.40141 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7463.26421 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.40141 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.40141 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.40141 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.90493 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.40141 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.20070 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.93427 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 81221.36000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 40610.68000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80080 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80080 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 81221.36000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 121516.74624 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 121516.74624 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.90043 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.90043 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2033.54994 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.90043 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.90043 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.90043 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25428 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.90043 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95022 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26695 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40825.94000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20412.97000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74930 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74930 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40825.94000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 85222.27255 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 85222.27255 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 78022.3 | 10.27 | 10.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 39459.1 | 11.40 | 11.35 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.137 | 0.133 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.234 | 0.221 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1121799936 | 0.2942830745 | Pass | Pass | 4.9877556954E-002 | 0.1145845993 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2032096762 | 0.5990794249 | Pass | Pass | 3.3601825482E-002 | 0.1053496848 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4870106959 | 0.5129841992 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1216.93 | 95.05 | 1493.25 | 32.16 | 822.82 | 3660.22 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.134 | 0.137 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.225 | 0.234 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.419_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.381 | 0.401 | 0.442 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.419_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.381 | 0.401 | 0.442 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.419_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.381 | 0.401 | 0.442 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.381 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.5182 | 371.75 | 3538.38 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 63.44 | 0.0000 | Y | 42.14 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 10.6727 | 139.41 | 1487.83 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 75.47 | 0.0000 | Y | 21.08 |
Interior Lighting Total | 9.8331 | 511.15 | 5026.21 | 63.22 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 3538.38 | 884.59 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 3538.38 | 884.59 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.52 | AstronomicalClock | - | 48.81 | 48.81 | 1.92 | |
EXTERIOR_LIGHTS_B | 3124.83 | AstronomicalClock | - | 83.71 | 73.24 | 42.96 | |
Exterior Lighting Total | 3334.35 | 44.88 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 81221.36 | 65042.07 | 16179.29 | 0.80 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40825.94 | 30590.88 | 10235.06 | 0.75 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 78022.3 | 10.27 | 10.22 | ||||
PSZ-AC_2:2 COOLING COIL | 39459.1 | 11.40 | 11.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 121516.75 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 85222.27 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.40 | 7463.26 | 1695.65 | 1.00 | 1.18 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.90 | 2033.55 | 1070.05 | 1.00 | 1.32 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 41369.36 | 49643.23 | 133.54 | 3.668 | 4.401 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00843 | 34.83 | 0.00570 | 1.331 | 0.00 |
KITCHEN | 21051.47 | 25261.76 | 181.21 | 1.584 | 1.900 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.98 | 0.00883 | 33.89 | 0.00570 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7237.12 | 8684.54 | 23.36 | 0.377 | 1.331 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00774 | -7.90 | 0.00234 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 19.56 | 0.00192 | -7.90 | 0.00234 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.40 | 4.40 | 1.33 | 1.33 | 4.4014 | 4.4012 | 4.4014 | 0.9999 | 1.0000 |
PSZ-AC_2:2 | 1.90 | 1.90 | 1.22 | 1.22 | 1.9004 | 1.9004 | 1.9004 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 81221.360 | 65042.065 | 4.401410 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40610.68 | 37946.10 | 2.934273 | 27.35 | 14.77 | 0.00760142 | 11.12 | 8.17 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 45.3733 | 23.99 | 0.00842676 | 37.3362 | 41348.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 121516.746 | 121516.746 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 121516.75 | 121516.75 | 4.401407 | 12.26 | 7.73 | 0.00610550 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 30.2489 | 21.00 | 0.00773711 | 41.1575 | 7227.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 40825.940 | 30590.877 | 1.900430 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 20412.97 | 20412.97 | 1.266953 | 32.10 | 15.62 | 0.00672590 | 11.74 | 8.15 | 0.00672590 | 35.10 | 0.00569938 | 15.77 | 96.0574 | 25.98 | 0.00882920 | 34.7118 | 21051.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 85222.273 | 85222.273 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 85222.27 | 85222.27 | 1.900430 | -5.06 | -6.39 | 0.00219803 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 64.0382 | 19.86 | 0.00193956 | 11.1729 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 81221.360 | 65042.065 | 4.401410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9707 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.401407 | 4.35919223 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 40610.68 | 37946.10 | 1.0000 | 2.90613041 | 2.934273 | 27.35 | 14.77 | 0.00760142 | 46879.7 | 11.12 | 8.17 | 0.00700000 | 28824.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40610.68 | 35.10 | 0.00569938 | 15.77 | 1.33137743 | 45.3733 | 23.99 | 0.00842676 | 23.99 | 0.00842676 | 37.3362 | 41348.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 121516.746 | 121516.746 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.401407 | 4.35919223 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 121516.75 | 121516.75 | 1.0000 | 4.35919223 | 4.401407 | 12.26 | 7.73 | 0.00610550 | 27725.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 121516.75 | -7.90 | 0.00234317 | -7.90 | 1.33137743 | 30.2489 | 21.00 | 0.00773711 | 21.00 | 0.00773711 | 41.1575 | 7227.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40825.940 | 30590.877 | 1.900430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.3431 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.900430 | 1.88220278 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 20412.97 | 20412.97 | 1.0000 | 1.25480185 | 1.266953 | 32.10 | 15.62 | 0.00672590 | 49474.9 | 11.74 | 8.15 | 0.00672590 | 28762.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20412.97 | 35.10 | 0.00569938 | 15.77 | 1.21700195 | 96.0574 | 25.94 | 0.00882920 | 25.98 | 0.00882920 | 34.7118 | 21051.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 85222.273 | 85222.273 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.900430 | 1.88220278 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 85222.27 | 85222.27 | 1.0000 | 1.88220278 | 1.900430 | -5.06 | -6.39 | 0.00219803 | 393.0 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85222.27 | -7.90 | 0.00234317 | -7.90 | 1.21700195 | 64.0382 | 0.00 | 0.00193956 | 19.86 | 0.00193956 | 11.1729 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.40 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3124.17 | 3737.00 | 571.17 |
KITCHEN | 4720.33 | 5850.33 | 3684.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4763.83 | 6608.83 | 3728.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.67 | 19.50 | 0.00 | 0.00 |
KITCHEN | 0.00 | 156.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 174.83 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.810 | 0.579 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.532 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.099 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.056 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 39548291.16 | 0.00 | 39548291.16 | 4762467.49 | 44310758.65 | 41986318.57 | 1442.20 | 5341.03 | 1976.77 | 210.79 |
KITCHEN | 32871798.99 | 0.00 | 32871798.99 | 159765.52 | 33031564.51 | 38379373.44 | 1427.20 | 5425.81 | 1906.99 | 595.11 |
Total Facility | 72420090.15 | 0.00 | 72420090.15 | 4922233.01 | 77342323.16 | 80365692.01 | 1452.84 | 5645.29 | 2220.67 | 639.65 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.4982 | 0.0000 | 1.4982 | 0.1803 | 1.6785 | 1.3314 | 0.00 | 5243.12 | 1943.88 |
KITCHEN | 1.2273 | 0.0000 | 1.2273 | 0.0038 | 1.2311 | 1.2170 | 0.00 | 5325.24 | 1861.76 |
Total Facility | 2.7255 | 0.0000 | 2.7255 | 0.1841 | 2.9096 | 2.5484 | 0.00 | 5543.53 | 2162.17 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 38793054.49 | 0.00 | 38793054.49 | 41986318.57 | 6782.77 | 19.94 | 1957.29 | 210.79 |
PSZ-AC_2:2 | 32243356.15 | 0.00 | 32243356.15 | 38379373.44 | 6851.94 | 27.06 | 1881.00 | 595.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.4696 | 0.0000 | 1.4696 | 1.3314 | 5242.66 | 19.46 | 1924.88 |
PSZ-AC_2:2 | 1.2038 | 0.0000 | 1.2038 | 1.2170 | 5324.17 | 25.22 | 1837.61 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1591.47 | 472.91 | 5333.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 2102.96 | 5679.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.9958 | 1.6301 | 1.3063 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.2328 | 1.1939 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
Electricity:Building | 519.59 | 3441.46 | 01-JAN-01:10 | 29031.14 | 02-JAN-11:10 |
Electricity:Zone:DINING | 167.25 | 983.90 | 01-JAN-01:10 | 9291.91 | 02-JAN-17:10 |
Electricity:SpaceType:GENERAL | 512.65 | 3305.18 | 01-JAN-01:10 | 26888.04 | 02-JAN-11:10 |
InteriorLights:Electricity | 63.22 | 509.70 | 29-MAY-05:00 | 4065.95 | 02-JAN-17:10 |
InteriorLights:Electricity:Zone:DINING | 42.14 | 335.93 | 29-MAY-05:00 | 3023.33 | 02-JAN-17:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 63.22 | 509.70 | 29-MAY-05:00 | 4065.95 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity | 63.22 | 509.70 | 29-MAY-05:00 | 4065.95 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 42.14 | 335.93 | 29-MAY-05:00 | 3023.33 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 63.22 | 509.70 | 29-MAY-05:00 | 4065.95 | 02-JAN-17:10 |
Electricity:Zone:KITCHEN | 352.34 | 2457.55 | 01-JAN-01:10 | 20527.60 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 21.08 | 173.76 | 01-JAN-01:10 | 1042.61 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 21.08 | 173.76 | 01-JAN-01:10 | 1042.61 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.33 | 2147.51 | 01-JAN-01:10 | 17341.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 50.84 | 852.60 | 21-JAN-23:30 | 3196.23 | 23-AUG-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 119.82 | 1033.59 | 06-MAY-00:10 | 6469.05 | 01-JUL-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 14.26 | 0.00 | 01-JAN-11:10 | 1517.85 | 06-OCT-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 29.64 | 765.07 | 12-DEC-06:00 | 1076.23 | 14-APR-03:20 |
ElectricityPurchased:Facility | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
ElectricityPurchased:Plant | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
Cogeneration:ElectricityPurchased | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
General:Cogeneration:ElectricityPurchased | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
ElectricityNet:Plant | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
Cogeneration:ElectricityNet | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
General:Cogeneration:ElectricityNet | 923.77 | 6662.43 | 06-MAY-00:10 | 62809.56 | 21-JUL-17:20 |
Electricity:HVAC | 239.48 | 0.00 | 01-JAN-01:10 | 34194.91 | 21-JUL-17:10 |
Fans:Electricity | 129.13 | 0.00 | 01-JAN-01:10 | 7342.60 | 21-JUL-17:10 |
General:Fans:Electricity | 129.13 | 0.00 | 01-JAN-01:10 | 7342.60 | 21-JUL-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 110.35 | 0.00 | 01-JAN-00:10 | 26852.31 | 21-JUL-17:10 |
General:Cooling:Electricity | 110.35 | 0.00 | 01-JAN-00:10 | 26852.31 | 21-JUL-17:10 |
ExteriorLights:Electricity | 44.88 | 0.00 | 01-JAN-07:20 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.88 | 0.00 | 01-JAN-07:20 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.47 | 0.00 | 01-JAN-01:10 | 4742.16 | 27-NOV-07:50 |
Water Heater:WaterSystems:Electricity | 75.47 | 0.00 | 01-JAN-01:10 | 4742.16 | 27-NOV-07:50 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 07-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 07-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 988.82 | 2803.57 | 01-JAN-01:10 | 154298.21 | 15-DEC-04:30 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 174.13 | 0.00 | 01-JAN-01:10 | 148779.26 | 15-DEC-04:30 |
Heating:NaturalGas | 174.13 | 0.00 | 01-JAN-01:10 | 148779.26 | 15-DEC-04:30 |
General:Heating:NaturalGas | 174.13 | 0.00 | 01-JAN-01:10 | 148779.26 | 15-DEC-04:30 |
NaturalGas:Plant | 344.91 | 993.32 | 01-JAN-00:30 | 30098.08 | 03-FEB-19:20 |
WaterSystems:NaturalGas | 344.91 | 993.32 | 01-JAN-00:30 | 30098.08 | 03-FEB-19:20 |
Water Heater:WaterSystems:NaturalGas | 344.91 | 993.32 | 01-JAN-00:30 | 30098.08 | 03-FEB-19:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1620.51 | 2930.98 | 15-DEC-01:10 | 151341.74 | 21-JUL-17:20 |
EnergyTransfer:Building | 774.83 | 1465.49 | 15-DEC-01:10 | 51066.25 | 21-JUL-17:20 |
EnergyTransfer:Zone:KITCHEN | 433.43 | 1465.49 | 15-DEC-01:10 | 25187.60 | 17-OCT-04:10 |
Refrigeration:EnergyTransfer | 139.59 | 2620.89 | 21-JAN-23:10 | 7834.84 | 14-APR-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 69.79 | 1310.45 | 21-JAN-23:10 | 3917.42 | 14-APR-03:20 |
General:Refrigeration:EnergyTransfer | 69.79 | 1310.45 | 21-JAN-23:10 | 3917.42 | 14-APR-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 69.79 | 1310.45 | 21-JAN-23:10 | 3917.42 | 14-APR-03:20 |
EnergyTransfer:Plant | 311.43 | 1465.49 | 15-DEC-01:10 | 19335.39 | 13-FEB-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.10 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 57.70 | 1305.22 | 12-DEC-06:00 | 2238.70 | 14-APR-03:20 |
EnergyTransfer:Zone:DINING | 341.41 | 0.00 | 01-JAN-01:10 | 31075.23 | 21-JUL-17:20 |
Heating:EnergyTransfer | 0.41 | 0.00 | 01-JAN-00:10 | 9885.98 | 30-JAN-06:40 |
Heating:EnergyTransfer:Zone:DINING | 0.41 | 0.00 | 01-JAN-00:10 | 9885.98 | 30-JAN-06:40 |
General:Heating:EnergyTransfer | 0.41 | 0.00 | 01-JAN-00:10 | 9885.98 | 30-JAN-06:40 |
General:Heating:EnergyTransfer:Zone:DINING | 0.41 | 0.00 | 01-JAN-00:10 | 9885.98 | 30-JAN-06:40 |
Cooling:EnergyTransfer | 704.63 | 0.00 | 01-JAN-01:10 | 48868.96 | 21-JUL-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 341.00 | 0.00 | 01-JAN-01:10 | 31075.23 | 21-JUL-17:20 |
General:Cooling:EnergyTransfer | 704.63 | 0.00 | 01-JAN-01:10 | 48868.96 | 21-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 341.00 | 0.00 | 01-JAN-01:10 | 31075.23 | 21-JUL-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 676.45 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 676.45 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 363.63 | 0.00 | 01-JAN-01:10 | 21290.72 | 17-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 363.63 | 0.00 | 01-JAN-01:10 | 21290.72 | 17-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 241.63 | 0.00 | 01-JAN-01:10 | 16946.88 | 03-FEB-07:40 |
PlantLoopHeatingDemand:Plant | 241.63 | 0.00 | 01-JAN-01:10 | 16946.88 | 03-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 241.63 | 0.00 | 01-JAN-01:10 | 16946.88 | 03-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 241.63 | 0.00 | 01-JAN-01:10 | 16946.88 | 03-FEB-07:40 |
EnergyTransfer:HVAC | 534.25 | 0.00 | 01-JAN-01:10 | 119023.41 | 15-DEC-04:30 |
HeatingCoils:EnergyTransfer | 139.31 | 0.00 | 01-JAN-01:10 | 119023.41 | 15-DEC-04:30 |
CoolingCoils:EnergyTransfer | 394.95 | 0.00 | 01-JAN-00:10 | 86663.75 | 21-JUL-17:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 241.63 | 0.00 | 01-JAN-01:10 | 16946.88 | 03-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 241.63 | 0.00 | 01-JAN-01:10 | 16946.88 | 03-FEB-07:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.410 | -340.991 | 0.000 | 0.000 | 220.608 | 42.140 | 93.832 | 67.924 | 0.000 | 4.733 | 0.001 | 0.000 | -22.437 | 0.000 | -42.077 | -24.142 |
KITCHEN | 0.000 | 0.000 | 0.001 | -363.619 | 0.000 | 0.000 | 5.646 | 21.077 | 286.918 | 0.000 | 0.000 | 0.051 | 51.889 | 0.000 | 0.000 | 0.000 | -1.962 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.304 | 36.720 | 0.000 | 0.000 | 0.000 | -46.024 | -0.000 |
Total Facility | 0.000 | 0.000 | 0.411 | -704.610 | 0.000 | 0.000 | 226.254 | 63.218 | 380.750 | 67.924 | 0.000 | 14.088 | 88.609 | 0.000 | -22.437 | 0.000 | -90.063 | -24.144 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 19-AUG-03:01 | 0.00 | 0.00 | 0.00 | -76620.53 | 0.00 | 0.00 | 0.00 | 503.90 | 900.01 | 0.00 | 0.00 | 0.00 | 76009.32 | 0.00 | -734.72 | 0.00 | -57.98 | 0.00 |
KITCHEN | 14-APR-03:51 | 0.00 | 0.00 | 0.00 | -67914.23 | 0.00 | 0.00 | 0.00 | 173.76 | 3472.64 | 0.00 | 0.00 | 0.00 | 64267.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-APR-03:01 | 0.00 | 0.00 | 0.00 | -125479.13 | 0.00 | 0.00 | 0.00 | 677.66 | 4372.65 | 0.00 | 0.00 | 506.01 | 121574.43 | 0.00 | -1620.50 | 0.00 | -31.12 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 30-JAN-06:38 | 0.00 | 0.00 | 45809.98 | 0.00 | 0.00 | 0.00 | 2315.59 | 1343.70 | 2350.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2590.42 | 0.00 | -1605.69 | -47623.88 |
KITCHEN | 06-FEB-05:03 | 0.00 | 0.00 | 6757.07 | 0.00 | 0.00 | 0.00 | 25.41 | 231.69 | 6912.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -144.49 | -13782.40 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JAN-06:38 | -9825.35 | 9825.35 | 45809.98 | -9825.35 | 0.00 | 0.00 | 2383.60 | 1807.09 | 9753.88 | 0.00 | 0.00 | 947.76 | 0.00 | 0.00 | -2590.42 | 0.00 | -1632.84 | -46653.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.4012 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.4014 | 0.3025 | 1.0000 | Not calculated | 1.3314 | 0.3025 | ||
PSZ-AC_2:2 | 1.9004 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.9004 | 0.0961 | 1.0000 | Not calculated | 0.1826 | 0.0961 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.4012 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.4012 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3025 | ||
PSZ-AC_2:2 | 1.9004 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.9004 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.0961 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4012 | 4.4012 | 4.4012 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9004 | 1.9004 | 1.9004 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.4012 | 4.4014 | 4.4012 | 4.4012 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.9004 | 1.9004 | 1.9004 | 1.9004 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4012 | 4.4012 | 4.4012 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9004 | 1.9004 | 1.9004 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.4012 | 4.4012 | 4.4012 | 4.4012 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.9004 | 1.9004 | 1.9004 | 1.9004 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 174.13 | 148779.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 110.35 | 26852.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 63.22 | 4065.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.88 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 129.13 | 7342.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.47 | 4742.16 | 344.91 | 30098.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.26 | 1517.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.64 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 500.27 | 923.77 |
Natural Gas | 469.79 | 988.82 |
Additional | 0.00 | 0.00 |
Total | 970.06 | 1912.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 123.68 |
Space Heating | 0.00 |
Space Cooling | 215.89 |
Fans (All) | 252.62 |
Service Water Heating | 147.65 |
Receptacle Equipment | 879.26 |
Miscellaneous (All) | 1807.22 |
Subtotal | 1807.22 |
Natural Gas [MJ/m2] | |
Space Heating | 340.66 |
Service Water Heating | 674.76 |
Miscellaneous (All) | 1934.49 |
Subtotal | 1934.49 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.31 |
Space Heating | 9.10 |
Space Cooling | 5.77 |
Fans (All) | 6.75 |
Service Water Heating | 21.98 |
Receptacle Equipment | 48.06 |
Miscellaneous | 5.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8100.67 | 659.00 | 0.33 | 0.00 | 0.00 |
ATTIC | 6521.67 | 664.83 | 566.83 | 837.33 | 169.33 |
Min | 6521.67 | 8.67 | 0.00 | 0.00 | 0.00 |
Max | 8751.33 | 664.83 | 566.83 | 837.33 | 169.33 |
Average | 7791.22 | 444.17 | 189.06 | 279.11 | 56.44 |
Sum | 23373.67 | 1332.50 | 567.17 | 837.33 | 169.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824191.67 | 30.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824191.67 | 30.33 | 0.00 | 0.00 | 0.00 |
Average | 281141.56 | 10.11 | 0.00 | 0.00 | 0.00 |
Sum | 843424.67 | 30.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8674.17 | 85.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7425.83 | 1334.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 6772.83 | 866.83 | 291.33 | 285.50 | 543.50 |
Min | 6772.83 | 85.83 | 0.00 | 0.00 | 0.00 |
Max | 8674.17 | 1334.17 | 291.33 | 285.50 | 543.50 |
Average | 7624.28 | 762.28 | 97.11 | 95.17 | 181.17 |
Sum | 22872.83 | 2286.83 | 291.33 | 285.50 | 543.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 823687.67 | 534.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16853.33 | 2379.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823687.67 | 2379.67 | 0.00 | 0.00 | 0.00 |
Average | 280180.33 | 971.33 | 0.00 | 0.00 | 0.00 |
Sum | 840541.00 | 2914.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:00
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208141E+11 | 31704.67 | 20-JAN-00:01 | -6.9 | -7.0 | 0.124052E+11 | 12934.85 | 24-JAN-12:00 | 13.30 | 4.20 |
February | 0.197888E+11 | 28507.11 | 06-FEB-00:01 | -4.4 | -6.2 | 0.114534E+11 | 12937.60 | 13-FEB-12:00 | 18.90 | 6.57 |
March | 0.238428E+11 | 26073.97 | 10-MAR-05:01 | -1.1 | -4.3 | 0.137953E+11 | 14049.91 | 25-MAR-18:10 | 17.33 | 5.38 |
April | 0.265835E+11 | 74456.23 | 29-APR-03:01 | 10.10 | 2.35 | 0.141396E+11 | 14049.93 | 29-APR-18:10 | 23.53 | 8.85 |
May | 0.296691E+11 | 68399.63 | 11-MAY-03:01 | 13.22 | 3.99 | 0.151026E+11 | 14050.29 | 27-MAY-18:00 | 24.40 | 12.44 |
June | 0.340460E+11 | 76344.01 | 27-JUN-03:01 | 20.92 | 11.99 | 0.149487E+11 | 14050.16 | 24-JUN-18:49 | 20.92 | 11.99 |
July | 0.375843E+11 | 75606.22 | 21-JUL-03:01 | 22.52 | 12.64 | 0.153174E+11 | 14051.42 | 01-JUL-18:49 | 22.52 | 12.64 |
August | 0.377168E+11 | 76623.56 | 19-AUG-03:01 | 21.52 | 12.18 | 0.155065E+11 | 14052.15 | 26-AUG-18:10 | 21.70 | 16.13 |
September | 0.339554E+11 | 71123.88 | 14-SEP-03:01 | 16.60 | 11.12 | 0.148433E+11 | 14052.22 | 23-SEP-18:19 | 17.80 | 12.90 |
October | 0.304581E+11 | 68386.84 | 07-OCT-03:01 | 17.48 | 11.17 | 0.145283E+11 | 14050.55 | 07-OCT-18:49 | 14.40 | 12.59 |
November | 0.248030E+11 | 25484.20 | 16-NOV-05:01 | -1.0 | -2.5 | 0.127518E+11 | 12938.20 | 09-NOV-12:00 | -1.0 | -2.5 |
December | 0.217334E+11 | 29366.97 | 15-DEC-00:01 | -5.0 | -9.0 | 0.121213E+11 | 12118.32 | 01-DEC-12:00 | -5.0 | -9.0 |
Annual Sum or Average | 0.340995E+12 | 0.166913E+12 | ||||||||
Minimum of Months | 0.197888E+11 | 25484.20 | -6.9 | -9.0 | 0.114534E+11 | 12118.32 | -5.0 | -9.0 | ||
Maximum of Months | 0.377168E+11 | 76623.56 | 22.52 | 12.64 | 0.155065E+11 | 14052.22 | 24.40 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295143E+11 | 35431.01 | 26-JAN-05:01 | -5.5 | -8.2 | 0.104157E+11 | 6892.33 | 05-JAN-11:00 | -5.5 | -8.2 |
February | 0.263826E+11 | 48468.43 | 14-FEB-04:41 | 0.28 | -2.9 | 0.942296E+10 | 6930.38 | 14-FEB-11:00 | 17.20 | 6.01 |
March | 0.291435E+11 | 39785.29 | 17-MAR-03:41 | 7.30 | 1.56 | 0.104960E+11 | 6930.39 | 08-MAR-11:00 | 7.30 | 1.56 |
April | 0.285707E+11 | 67905.93 | 14-APR-03:51 | 10.00 | 2.65 | 0.102072E+11 | 6930.39 | 17-APR-10:00 | 20.60 | 7.35 |
May | 0.302734E+11 | 66425.41 | 16-MAY-04:01 | 11.28 | 2.90 | 0.105778E+11 | 6930.46 | 24-MAY-10:00 | 17.80 | 14.22 |
June | 0.310654E+11 | 62334.94 | 20-JUN-04:01 | 11.78 | 5.18 | 0.102550E+11 | 6930.46 | 01-JUN-10:09 | 11.78 | 5.18 |
July | 0.331240E+11 | 46693.22 | 21-JUL-03:21 | 21.95 | 12.58 | 0.105944E+11 | 6930.39 | 17-JUL-10:39 | 21.95 | 12.58 |
August | 0.330745E+11 | 46334.49 | 29-AUG-03:11 | 16.10 | 12.92 | 0.106004E+11 | 6930.42 | 29-AUG-10:09 | 20.87 | 15.61 |
September | 0.311402E+11 | 56969.99 | 21-SEP-03:11 | 14.40 | 7.39 | 0.102513E+11 | 6930.46 | 07-SEP-10:09 | 14.40 | 7.39 |
October | 0.313029E+11 | 61948.31 | 08-OCT-03:11 | 9.80 | 4.81 | 0.105434E+11 | 6930.42 | 03-OCT-10:30 | 9.80 | 4.81 |
November | 0.299306E+11 | 57230.23 | 01-NOV-03:11 | 9.57 | 6.76 | 0.101217E+11 | 6930.43 | 09-NOV-11:00 | 16.70 | 9.34 |
December | 0.301101E+11 | 39127.67 | 15-DEC-05:01 | -9.1 | -11.9 | 0.104008E+11 | 6877.78 | 01-DEC-11:00 | -9.1 | -11.9 |
Annual Sum or Average | 0.363632E+12 | 0.123887E+12 | ||||||||
Minimum of Months | 0.263826E+11 | 35431.01 | -9.1 | -11.9 | 0.942296E+10 | 6877.78 | -9.1 | -11.9 | ||
Maximum of Months | 0.331240E+11 | 67905.93 | 21.95 | 12.92 | 0.106004E+11 | 6930.46 | 21.95 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 | -5.2 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 | -0.8 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 | 2.84 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 | 4.92 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 | 8.96 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 | 14.90 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 | 16.86 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 | 14.47 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 | 10.88 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 | 5.34 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 5.13 | 1.84 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.00 | 0.00 | -3.2 | -5.2 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.00 | 0.00 | 21.95 | 16.86 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118610E+09 | 45809.74 | 30-JAN-06:38 | -6.7 |
February | 0.108633E+09 | 40678.18 | 02-FEB-05:04 | -4.0 |
March | 20888806.63 | 36557.42 | 04-MAR-05:02 | -1.2 |
April | 1313197.72 | 4538.94 | 06-APR-04:03 | 2.20 |
May | 165362.40 | 2719.86 | 06-MAY-04:04 | 6.10 |
June | 19002716.08 | 10822.23 | 28-JUN-03:47 | 21.02 |
July | 37423248.96 | 10296.40 | 20-JUL-03:50 | 21.28 |
August | 15761437.80 | 10368.40 | 02-AUG-03:50 | 20.60 |
September | 511876.65 | 3412.51 | 03-SEP-03:45 | 18.80 |
October | 672782.28 | 7602.71 | 25-OCT-04:02 | -2.0 |
November | 5372152.88 | 9095.92 | 27-NOV-05:01 | -4.0 |
December | 81541413.49 | 16069.59 | 04-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.409896E+09 | |||
Minimum of Months | 165362.40 | 2719.86 | -6.7 | |
Maximum of Months | 0.118610E+09 | 45809.74 | 21.28 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 780896.45 | 6764.48 | 06-FEB-05:03 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 5.13 |
Annual Sum or Average | 780896.45 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 780896.45 | 6764.48 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.380321E+10 | 3023.33 | 02-JAN-17:10 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.338702E+10 | 3023.33 | 01-FEB-17:30 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.362779E+10 | 3023.33 | 01-MAR-17:49 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.331898E+10 | 3023.33 | 01-APR-18:30 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.338620E+10 | 3023.33 | 01-MAY-18:49 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.323222E+10 | 3023.33 | 01-JUN-16:00 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.334634E+10 | 3023.33 | 01-JUL-19:19 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.343017E+10 | 3023.33 | 01-AUG-19:10 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.340533E+10 | 3023.33 | 01-SEP-18:30 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.363130E+10 | 3023.33 | 02-OCT-17:30 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.368960E+10 | 3023.33 | 01-NOV-16:49 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.388204E+10 | 3023.33 | 01-DEC-16:40 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.421402E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.323222E+10 | 3023.33 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.388204E+10 | 3023.33 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.178099E+10 | 1042.61 | 02-JAN-10:09 | 0.275454E+11 | 17341.88 | 01-JAN-11:09 |
February | 0.161313E+10 | 1042.61 | 01-FEB-10:09 | 0.248798E+11 | 17341.88 | 01-FEB-11:09 |
March | 0.180935E+10 | 1042.61 | 01-MAR-10:09 | 0.275456E+11 | 17341.88 | 01-MAR-11:09 |
April | 0.173053E+10 | 1042.61 | 01-APR-16:10 | 0.266569E+11 | 17341.88 | 01-APR-10:09 |
May | 0.179517E+10 | 1042.61 | 01-MAY-09:09 | 0.275455E+11 | 17341.88 | 01-MAY-10:09 |
June | 0.174888E+10 | 1042.61 | 01-JUN-09:09 | 0.266570E+11 | 17341.88 | 01-JUN-10:09 |
July | 0.177703E+10 | 1042.61 | 01-JUL-16:10 | 0.275454E+11 | 17341.88 | 01-JUL-10:09 |
August | 0.180935E+10 | 1042.61 | 01-AUG-09:09 | 0.275456E+11 | 17341.88 | 01-AUG-10:09 |
September | 0.173094E+10 | 1042.61 | 01-SEP-09:09 | 0.266569E+11 | 17341.88 | 01-SEP-10:09 |
October | 0.178078E+10 | 1042.61 | 02-OCT-09:09 | 0.275454E+11 | 17341.88 | 01-OCT-10:09 |
November | 0.172406E+10 | 1042.61 | 01-NOV-09:09 | 0.266568E+11 | 17341.88 | 01-NOV-10:09 |
December | 0.177723E+10 | 1042.61 | 01-DEC-10:09 | 0.275454E+11 | 17341.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.210774E+11 | 0.324326E+12 | ||||
Minimum of Months | 0.161313E+10 | 1042.61 | 0.248798E+11 | 17341.88 | ||
Maximum of Months | 0.180935E+10 | 1042.61 | 0.275456E+11 | 17341.88 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.380321E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727376E+10 |
February | 0.272721E+11 | 0.338702E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594605E+10 |
March | 0.305458E+11 | 0.362779E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496053E+10 |
April | 0.292871E+11 | 0.331898E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18977139.06 | 0.301167E+10 |
May | 0.303219E+11 | 0.338620E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222802E+09 | 0.190975E+10 |
June | 0.295292E+11 | 0.323222E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129552E+10 | 0.758464E+09 |
July | 0.300798E+11 | 0.334634E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160767E+10 | 0.296745E+09 |
August | 0.305458E+11 | 0.343017E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114649E+10 | 0.482310E+09 |
September | 0.292871E+11 | 0.340533E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383118E+09 | 0.110740E+10 |
October | 0.300980E+11 | 0.363130E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58167339.88 | 0.333620E+10 |
November | 0.290996E+11 | 0.368960E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554301E+10 |
December | 0.300798E+11 | 0.388204E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745081E+10 |
Annual Sum or Average | 0.356244E+12 | 0.421402E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473274E+10 | 0.420767E+11 |
Minimum of Months | 0.272721E+11 | 0.323222E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296745E+09 |
Maximum of Months | 0.305458E+11 | 0.388204E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160767E+10 | 0.745081E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.178099E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250749E+09 |
February | 0.732850E+09 | 0.161313E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240916E+09 |
March | 0.820818E+09 | 0.180935E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259336E+09 |
April | 0.786997E+09 | 0.173053E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 290.80 | 0.175376E+09 |
May | 0.814802E+09 | 0.179517E+10 | 0.225868E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1953038.28 | 0.147692E+09 |
June | 0.793501E+09 | 0.174888E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 15404899.23 | 88592216.51 |
July | 0.808298E+09 | 0.177703E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 19701480.57 | 56315487.08 |
August | 0.820818E+09 | 0.180935E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 10675995.82 | 74667791.03 |
September | 0.786997E+09 | 0.173094E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2677340.77 | 94595548.11 |
October | 0.808786E+09 | 0.178078E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 325331.94 | 0.148199E+09 |
November | 0.781956E+09 | 0.172406E+10 | 0.218581E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205603E+09 |
December | 0.808298E+09 | 0.177723E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219752E+09 |
Annual Sum or Average | 0.957291E+10 | 0.210774E+11 | 0.265941E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 50738377.40 | 0.196179E+10 |
Minimum of Months | 0.732850E+09 | 0.161313E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56315487.08 |
Maximum of Months | 0.820818E+09 | 0.180935E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 19701480.57 | 0.259336E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952505E+09 | 0.251845E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697543E+09 | 0.286863E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702421E+09 | 0.344486E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754760E+09 | 0.454583E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736844E+09 | 0.483830E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632139E+09 | 0.485571E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557994E+09 | 0.517288E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496173E+09 | 0.512534E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737694E+09 | 0.410685E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913322E+09 | 0.335993E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999957E+09 | 0.268741E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112292E+10 | 0.249989E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930428E+10 | 0.460241E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496173E+09 | 0.249989E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112292E+10 | 0.517288E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3023.33 | 02-JAN-17:10 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9410.80 | 19-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 3023.33 | 01-FEB-17:30 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 8628.70 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 3023.33 | 01-MAR-17:49 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6388.21 | 04-MAR-20:00 |
April | 30255.31 | 01-APR-18:10 | 3023.33 | 01-APR-18:30 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 613.33 | 13-APR-17:02 | 5861.52 | 15-APR-18:10 |
May | 30255.31 | 06-MAY-18:10 | 3023.33 | 01-MAY-18:49 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1880.73 | 19-MAY-17:03 | 4848.34 | 01-MAY-19:53 |
June | 30255.31 | 03-JUN-18:10 | 3023.33 | 01-JUN-16:00 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.11 | 28-JUN-17:02 | 4390.36 | 08-JUN-19:00 |
July | 30255.31 | 01-JUL-18:10 | 3023.33 | 01-JUL-19:19 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4144.83 | 21-JUL-17:03 | 1889.49 | 15-JUL-19:00 |
August | 30255.31 | 05-AUG-18:10 | 3023.33 | 01-AUG-19:10 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2889.62 | 04-AUG-17:03 | 2281.99 | 25-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 3023.33 | 01-SEP-18:30 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1935.88 | 20-SEP-17:02 | 3097.11 | 23-SEP-19:00 |
October | 30255.31 | 07-OCT-18:10 | 3023.33 | 02-OCT-17:30 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 800.86 | 11-OCT-13:00 | 6651.74 | 24-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 3023.33 | 01-NOV-16:49 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 6715.61 | 27-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 3023.33 | 01-DEC-16:40 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8510.77 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3023.33 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.49 | |||||
Maximum of Months | 30255.31 | 3023.33 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4144.83 | 9410.80 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1042.61 | 02-JAN-10:09 | 14079.00 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 902.57 | 17-JAN-04:10 |
February | 813.01 | 04-FEB-19:10 | 1042.61 | 01-FEB-10:09 | 14079.00 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 905.10 | 05-FEB-01:10 |
March | 813.01 | 04-MAR-19:10 | 1042.61 | 01-MAR-10:09 | 14079.00 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 979.10 | 14-MAR-03:40 |
April | 813.01 | 01-APR-18:10 | 1042.61 | 01-APR-16:10 | 14079.00 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.42 | 13-APR-16:53 | 895.25 | 23-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 1042.61 | 01-MAY-09:09 | 14079.00 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 29.52 | 19-MAY-14:53 | 754.62 | 18-MAY-02:20 |
June | 813.01 | 03-JUN-18:10 | 1042.61 | 01-JUN-09:09 | 14079.00 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 66.34 | 17-JUN-15:53 | 601.34 | 10-JUN-02:50 |
July | 813.01 | 01-JUL-18:10 | 1042.61 | 01-JUL-16:10 | 14079.00 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 73.39 | 04-JUL-14:53 | 306.64 | 05-JUL-02:50 |
August | 813.01 | 05-AUG-18:10 | 1042.61 | 01-AUG-09:09 | 14079.00 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 38.76 | 02-AUG-13:00 | 384.62 | 08-AUG-00:50 |
September | 813.01 | 02-SEP-18:10 | 1042.61 | 01-SEP-09:09 | 14079.00 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 24.40 | 03-SEP-14:51 | 457.34 | 08-SEP-02:00 |
October | 813.01 | 07-OCT-18:10 | 1042.61 | 02-OCT-09:09 | 14079.00 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 9.49 | 01-OCT-15:52 | 554.64 | 12-OCT-03:50 |
November | 813.01 | 04-NOV-18:10 | 1042.61 | 01-NOV-09:09 | 14079.00 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 962.31 | 26-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 1042.61 | 01-DEC-10:09 | 14079.00 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1313.96 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1042.61 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 306.64 | ||||||
Maximum of Months | 813.01 | 1042.61 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 73.39 | 1313.96 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2053.99 | 10-JAN-23:53 | 5318.72 | 29-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.08 | 14-FEB-07:23 | 6304.36 | 25-FEB-13:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.61 | 08-MAR-05:00 | 7105.35 | 30-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1885.79 | 01-APR-04:00 | 8197.21 | 08-APR-13:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1921.67 | 09-MAY-03:51 | 8338.18 | 28-MAY-13:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1860.03 | 20-JUN-02:00 | 7582.65 | 03-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1491.49 | 14-JUL-05:53 | 7318.93 | 28-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.36 | 17-AUG-04:30 | 7415.57 | 03-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.00 | 27-SEP-23:00 | 6963.90 | 09-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1831.63 | 29-OCT-22:00 | 6792.92 | 14-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1816.61 | 12-NOV-23:00 | 5896.30 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1856.50 | 13-DEC-02:70 | 5624.54 | 22-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.36 | 5318.72 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2053.99 | 8338.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31704.67 | 20-JAN-00:01 | 16808.50 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28507.11 | 06-FEB-00:01 | 16808.50 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 745.07 |
March | 26073.97 | 10-MAR-05:01 | 16808.50 | 6718.68 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 |
April | 74456.23 | 29-APR-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
May | 68399.63 | 11-MAY-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.06 |
June | 76344.01 | 27-JUN-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.89 |
July | 75606.22 | 21-JUL-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.93 |
August | 76623.56 | 19-AUG-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.98 |
September | 71123.88 | 14-SEP-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.89 |
October | 68386.84 | 07-OCT-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 |
November | 25484.20 | 16-NOV-05:01 | 16808.50 | 6718.68 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29366.97 | 15-DEC-00:01 | 16808.50 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25484.20 | 0.00 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76623.56 | 16808.50 | 6718.68 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 745.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35431.01 | 26-JAN-05:01 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 |
February | 48468.43 | 14-FEB-04:41 | 0.00 | 1390.11 | 26140.16 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39785.29 | 17-MAR-03:41 | 0.00 | 1390.11 | 26140.16 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 228.43 |
April | 67905.93 | 14-APR-03:51 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66425.41 | 16-MAY-04:01 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 |
June | 62334.94 | 20-JUN-04:01 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
July | 46693.22 | 21-JUL-03:21 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 60.25 |
August | 46334.49 | 29-AUG-03:11 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 159.43 |
September | 56969.99 | 21-SEP-03:11 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 |
October | 61948.31 | 08-OCT-03:11 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 381.44 |
November | 57230.23 | 01-NOV-03:11 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
December | 39127.67 | 15-DEC-05:01 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35431.01 | 0.00 | 1390.11 | 26140.16 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67905.93 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 381.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.08 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.98 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.42 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.17 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.07 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.69 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.01 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.37 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.19 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.54 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800.88 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.42 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.701984E+11 | 39119.48 | 17-JAN-17:19 | 0.120526E+12 | 100936.83 | 21-JAN-06:00 |
February | 0.631387E+11 | 40416.81 | 14-FEB-17:49 | 0.100324E+12 | 99522.47 | 06-FEB-07:49 |
March | 0.696209E+11 | 43500.88 | 08-MAR-18:10 | 0.878949E+11 | 84106.50 | 05-MAR-06:00 |
April | 0.707594E+11 | 47675.55 | 28-APR-18:49 | 0.722664E+11 | 61908.01 | 08-APR-05:00 |
May | 0.780735E+11 | 50502.18 | 23-MAY-10:00 | 0.694444E+11 | 45600.34 | 05-MAY-06:40 |
June | 0.862158E+11 | 62493.13 | 28-JUN-16:10 | 0.649031E+11 | 43449.48 | 03-JUN-10:30 |
July | 0.966478E+11 | 62809.56 | 21-JUL-17:19 | 0.655880E+11 | 43213.94 | 02-JUL-10:09 |
August | 0.934622E+11 | 57287.98 | 17-AUG-10:00 | 0.656148E+11 | 43131.28 | 26-AUG-10:30 |
September | 0.826159E+11 | 52988.69 | 03-SEP-10:00 | 0.640603E+11 | 43338.77 | 30-SEP-10:00 |
October | 0.752810E+11 | 51665.38 | 11-OCT-10:00 | 0.731406E+11 | 77232.18 | 26-OCT-06:00 |
November | 0.674194E+11 | 40031.84 | 02-NOV-17:19 | 0.850967E+11 | 89256.67 | 27-NOV-07:30 |
December | 0.703328E+11 | 39213.47 | 21-DEC-17:10 | 0.119964E+12 | 154298.21 | 15-DEC-04:30 |
Annual Sum or Average | 0.923766E+12 | 0.988823E+12 | ||||
Minimum of Months | 0.631387E+11 | 39119.48 | 0.640603E+11 | 43131.28 | ||
Maximum of Months | 0.966478E+11 | 62809.56 | 0.120526E+12 | 154298.21 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.558420E+10 | 0.458158E+10 | 0.381711E+11 | 0.00 | 0.114618E+11 | 37879553.69 | 0.00 | 1926143.74 | 0.00 | 0.00 | 0.00 | 0.639590E+10 | 0.00 |
February | 0.500015E+10 | 0.386928E+10 | 0.344772E+11 | 0.00 | 0.101682E+11 | 34213790.43 | 0.00 | 0.180004E+09 | 0.00 | 0.00 | 0.00 | 0.578760E+10 | 0.00 |
March | 0.543714E+10 | 0.389537E+10 | 0.381714E+11 | 0.00 | 0.107693E+11 | 37879553.69 | 0.00 | 0.680294E+09 | 0.00 | 0.00 | 0.00 | 0.645919E+10 | 0.00 |
April | 0.504950E+10 | 0.337185E+10 | 0.369399E+11 | 0.00 | 0.102202E+11 | 36657632.61 | 0.00 | 0.474383E+10 | 0.00 | 0.00 | 0.00 | 0.619849E+10 | 0.00 |
May | 0.518137E+10 | 0.314790E+10 | 0.381712E+11 | 0.00 | 0.105782E+11 | 37879553.69 | 0.00 | 0.100547E+11 | 0.00 | 0.00 | 0.00 | 0.641714E+10 | 0.00 |
June | 0.498110E+10 | 0.288434E+10 | 0.369400E+11 | 0.00 | 0.106239E+11 | 36657632.61 | 0.00 | 0.200820E+11 | 0.00 | 0.00 | 0.00 | 0.623664E+10 | 0.00 |
July | 0.512336E+10 | 0.305312E+10 | 0.381711E+11 | 0.00 | 0.112913E+11 | 37879553.69 | 0.00 | 0.279711E+11 | 0.00 | 0.00 | 0.00 | 0.637166E+10 | 0.00 |
August | 0.523952E+10 | 0.333120E+10 | 0.381714E+11 | 0.00 | 0.110338E+11 | 37879553.69 | 0.00 | 0.245628E+11 | 0.00 | 0.00 | 0.00 | 0.644979E+10 | 0.00 |
September | 0.513627E+10 | 0.360192E+10 | 0.369399E+11 | 0.00 | 0.103702E+11 | 36657632.61 | 0.00 | 0.158877E+11 | 0.00 | 0.00 | 0.00 | 0.619490E+10 | 0.00 |
October | 0.541208E+10 | 0.412544E+10 | 0.381711E+11 | 0.00 | 0.106496E+11 | 37879553.69 | 0.00 | 0.612165E+10 | 0.00 | 0.00 | 0.00 | 0.638361E+10 | 0.00 |
November | 0.541367E+10 | 0.434015E+10 | 0.369398E+11 | 0.00 | 0.104820E+11 | 36657632.61 | 0.00 | 64548869.84 | 0.00 | 0.00 | 0.00 | 0.618670E+10 | 0.00 |
December | 0.565927E+10 | 0.467761E+10 | 0.381711E+11 | 0.00 | 0.114805E+11 | 37879553.69 | 0.00 | 1968734.09 | 0.00 | 0.00 | 0.00 | 0.638893E+10 | 0.00 |
Annual Sum or Average | 0.632176E+11 | 0.448798E+11 | 0.449435E+12 | 0.00 | 0.129129E+12 | 0.446001E+09 | 0.00 | 0.110353E+12 | 0.00 | 0.00 | 0.00 | 0.754706E+11 | 0.00 |
Minimum of Months | 0.498110E+10 | 0.288434E+10 | 0.344772E+11 | 0.00 | 0.101682E+11 | 34213790.43 | 0.00 | 1926143.74 | 0.00 | 0.00 | 0.00 | 0.578760E+10 | 0.00 |
Maximum of Months | 0.565927E+10 | 0.467761E+10 | 0.381714E+11 | 0.00 | 0.114805E+11 | 37879553.69 | 0.00 | 0.279711E+11 | 0.00 | 0.00 | 0.00 | 0.645919E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.478796E+11 | 0.00 | 0.327471E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.344615E+11 | 0.00 | 0.298240E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.154921E+11 | 0.00 | 0.325030E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.392957E+10 | 0.00 | 0.297242E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.711887E+09 | 0.00 | 0.288328E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 35671231.26 | 0.00 | 0.262548E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 7961869.19 | 0.00 | 0.256804E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 5117944.71 | 0.00 | 0.257100E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 652553.04 | 0.00 | 0.254470E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.544927E+10 | 0.00 | 0.277916E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.176573E+11 | 0.00 | 0.288267E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.485008E+11 | 0.00 | 0.315634E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.174132E+12 | 0.00 | 0.344905E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 652553.04 | 0.00 | 0.254470E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.485008E+11 | 0.00 | 0.327471E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4065.95 | 02-JAN-17:10 | 3334.35 | 01-JAN-00:10 | 24333.76 | 01-JAN-11:09 | 0.00 | 6288.67 | 21-JAN-06:00 | 17.86 | 07-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4065.95 | 01-FEB-17:30 | 3334.35 | 01-FEB-00:10 | 24333.76 | 01-FEB-11:09 | 0.00 | 6203.16 | 04-FEB-06:10 | 17.86 | 08-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 4065.95 | 01-MAR-17:49 | 3334.35 | 01-MAR-00:10 | 24333.76 | 01-MAR-11:09 | 0.00 | 5929.13 | 05-MAR-06:00 | 17.86 | 04-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 4065.95 | 01-APR-18:30 | 3334.35 | 01-APR-05:10 | 24333.76 | 01-APR-10:09 | 0.00 | 5460.02 | 08-APR-05:00 | 17.86 | 07-APR-08:00 | 0.00 | 01-APR-00:10 |
May | 4065.95 | 01-MAY-18:49 | 3334.35 | 01-MAY-05:10 | 24333.76 | 01-MAY-10:09 | 0.00 | 5109.49 | 06-MAY-05:00 | 17.86 | 30-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 4065.95 | 01-JUN-16:00 | 3334.35 | 01-JUN-19:10 | 24333.76 | 01-JUN-10:09 | 0.00 | 7135.90 | 28-JUN-17:10 | 17.86 | 03-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 4065.95 | 01-JUL-19:19 | 3334.35 | 01-JUL-19:19 | 24333.76 | 01-JUL-10:09 | 0.00 | 7342.60 | 21-JUL-17:10 | 17.86 | 07-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 4065.95 | 01-AUG-19:10 | 3334.35 | 01-AUG-05:10 | 24333.76 | 01-AUG-10:09 | 0.00 | 6107.01 | 17-AUG-11:09 | 17.86 | 05-AUG-08:39 | 0.00 | 01-AUG-00:10 |
September | 4065.95 | 01-SEP-18:30 | 3334.35 | 01-SEP-05:10 | 24333.76 | 01-SEP-10:09 | 0.00 | 5007.32 | 03-SEP-10:00 | 17.86 | 03-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 4065.95 | 02-OCT-17:30 | 3334.35 | 01-OCT-05:10 | 24333.76 | 01-OCT-10:09 | 0.00 | 5808.65 | 26-OCT-04:00 | 17.86 | 20-OCT-10:39 | 0.00 | 01-OCT-00:10 |
November | 4065.95 | 01-NOV-16:49 | 3334.35 | 01-NOV-05:10 | 24333.76 | 01-NOV-10:09 | 0.00 | 5949.33 | 27-NOV-06:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 4065.95 | 01-DEC-16:40 | 3334.35 | 01-DEC-00:10 | 24333.76 | 01-DEC-11:09 | 0.00 | 7310.13 | 15-DEC-04:30 | 17.86 | 08-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4065.95 | 3334.35 | 24333.76 | 0.00 | 5007.32 | 17.86 | 0.00 | ||||||
Maximum of Months | 4065.95 | 3334.35 | 24333.76 | 0.00 | 7342.60 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 352.30 | 13-JAN-04:19 | 0.00 | 0.00 | 0.00 | 4742.13 | 10-JAN-19:30 | 0.00 |
February | 5615.78 | 14-FEB-14:00 | 0.00 | 0.00 | 0.00 | 4741.86 | 07-FEB-07:49 | 0.00 |
March | 8042.87 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 4741.93 | 27-MAR-06:00 | 0.00 |
April | 12301.75 | 13-APR-17:10 | 0.00 | 0.00 | 0.00 | 4741.70 | 24-APR-06:49 | 0.00 |
May | 15553.26 | 19-MAY-17:19 | 0.00 | 0.00 | 0.00 | 4741.53 | 05-MAY-06:49 | 0.00 |
June | 26372.32 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 4740.66 | 09-JUN-06:10 | 0.00 |
July | 26852.31 | 21-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.64 | 21-JUL-06:19 | 0.00 |
August | 20477.09 | 17-AUG-11:09 | 0.00 | 0.00 | 0.00 | 4737.04 | 31-AUG-06:19 | 0.00 |
September | 17036.45 | 03-SEP-13:00 | 0.00 | 0.00 | 0.00 | 4737.65 | 11-SEP-06:19 | 0.00 |
October | 14606.05 | 11-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4741.87 | 13-OCT-06:49 | 0.00 |
November | 4588.38 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4742.16 | 27-NOV-07:49 | 0.00 |
December | 427.49 | 19-DEC-04:19 | 0.00 | 0.00 | 0.00 | 4741.60 | 05-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 352.30 | 0.00 | 0.00 | 0.00 | 4736.64 | 0.00 | ||
Maximum of Months | 26852.31 | 0.00 | 0.00 | 0.00 | 4742.16 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39119.48 | 17-JAN-17:19 | 4065.95 | 21922.77 | 3334.35 | 0.00 | 5398.92 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 40416.81 | 14-FEB-17:49 | 4065.95 | 21922.77 | 3334.35 | 0.00 | 4622.86 | 17.86 | 0.00 | 1812.55 | 0.00 |
March | 43500.88 | 08-MAR-18:10 | 4065.95 | 20315.44 | 3334.35 | 0.00 | 4622.86 | 17.86 | 0.00 | 5147.45 | 0.00 |
April | 47675.55 | 28-APR-18:49 | 4065.95 | 18708.11 | 3334.35 | 0.00 | 4622.86 | 17.86 | 0.00 | 10602.35 | 0.00 |
May | 50502.18 | 23-MAY-10:00 | 2554.28 | 24333.76 | 0.00 | 0.00 | 4659.56 | 17.86 | 0.00 | 12734.41 | 0.00 |
June | 62493.13 | 28-JUN-16:10 | 2554.28 | 21922.77 | 0.00 | 0.00 | 6907.53 | 17.86 | 0.00 | 26372.32 | 0.00 |
July | 62809.56 | 21-JUL-17:19 | 2554.28 | 20315.44 | 0.00 | 0.00 | 7289.30 | 17.86 | 0.00 | 26594.81 | 0.00 |
August | 57287.98 | 17-AUG-10:00 | 2554.28 | 24333.76 | 0.00 | 0.00 | 5439.60 | 17.86 | 0.00 | 19058.09 | 0.00 |
September | 52988.69 | 03-SEP-10:00 | 1986.67 | 24333.76 | 0.00 | 0.00 | 5007.32 | 17.86 | 0.00 | 15274.58 | 0.00 |
October | 51665.38 | 11-OCT-10:00 | 2554.28 | 24333.76 | 0.00 | 0.00 | 4797.34 | 17.86 | 0.00 | 13756.57 | 0.00 |
November | 40031.84 | 02-NOV-17:19 | 4065.95 | 20315.44 | 3334.35 | 0.00 | 4622.86 | 17.86 | 0.00 | 1622.50 | 0.00 |
December | 39213.47 | 21-DEC-17:10 | 4065.95 | 21922.77 | 3334.35 | 0.00 | 5397.22 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 39119.48 | 1986.67 | 18708.11 | 0.00 | 0.00 | 4622.86 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62809.56 | 4065.95 | 24333.76 | 3334.35 | 0.00 | 7289.30 | 17.86 | 0.00 | 26594.81 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 74146.74 | 21-JAN-06:00 | 0.00 | 30059.87 | 31-JAN-07:30 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 70421.08 | 04-FEB-06:10 | 0.00 | 30098.08 | 03-FEB-19:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 57377.84 | 05-MAR-06:00 | 0.00 | 29645.01 | 01-MAR-07:19 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 35197.90 | 08-APR-05:00 | 0.00 | 27552.55 | 03-APR-06:00 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 18686.74 | 06-MAY-05:00 | 0.00 | 24540.73 | 01-MAY-18:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 5884.03 | 09-JUN-04:00 | 0.00 | 20592.29 | 02-JUN-06:40 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 6003.94 | 20-JUL-03:49 | 0.00 | 17716.94 | 03-JUL-18:10 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 6193.98 | 02-AUG-03:49 | 0.00 | 17633.32 | 31-AUG-06:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 1087.59 | 03-SEP-03:49 | 0.00 | 18426.53 | 26-SEP-06:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 52244.60 | 26-OCT-04:00 | 0.00 | 22918.89 | 31-OCT-06:40 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 58745.93 | 27-NOV-06:10 | 0.00 | 26413.64 | 30-NOV-07:49 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 148779.26 | 15-DEC-04:30 | 0.00 | 28813.06 | 29-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 1087.59 | 0.00 | 17633.32 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 148779.26 | 0.00 | 30098.08 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.64 | 0.00 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.79 | 0.00 | 24.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.78 | 0.00 | 24.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.80 | 0.00 | 24.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.78 | 0.00 | 24.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.81 | 0.00 | 24.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.37 | 0.00 | 20.37 | 19.50 | 24.64 | 0.00 | 24.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.44 | 0.00 | 20.44 | 5.17 | 24.81 | 0.00 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.06 | 0.00 | 27.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.27 | 0.00 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.56 | 0.00 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 29.23 | 0.00 | 29.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 30.17 | 0.00 | 30.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 30.62 | 0.00 | 30.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.86 | 0.00 | 30.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 30.86 | 0.00 | 30.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 30.73 | 0.00 | 30.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 30.11 | 0.00 | 30.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.51 | 0.00 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.04 | 0.00 | 27.04 |
Annual Sum or Average | 0.00 | 0.00 | 156.83 | 30.25 | 0.00 | 30.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.04 | 0.00 | 27.04 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 30.86 | 0.00 | 30.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 602.00 | 21.07 | 94.50 | 20.87 | 94.50 | 20.72 |
February | 523.00 | 21.15 | 70.00 | 20.95 | 70.00 | 20.79 |
March | 487.33 | 21.54 | 26.67 | 21.40 | 26.67 | 21.26 |
April | 292.83 | 21.91 | 45.67 | 22.12 | 4.83 | 22.07 |
May | 173.50 | 22.36 | 257.17 | 23.33 | 8.33 | 23.33 |
June | 48.50 | 22.77 | 493.83 | 23.94 | 11.17 | 23.94 |
July | 101.67 | 24.08 | 608.67 | 24.08 | 101.67 | 24.08 |
August | 73.83 | 24.02 | 609.67 | 24.05 | 73.17 | 24.05 |
September | 60.33 | 23.28 | 525.83 | 23.93 | 34.83 | 23.92 |
October | 248.83 | 21.67 | 241.67 | 22.74 | 10.33 | 22.69 |
November | 516.17 | 21.39 | 44.83 | 21.31 | 30.00 | 21.18 |
December | 609.00 | 20.88 | 105.67 | 20.72 | 105.67 | 20.59 |
Annual Sum or Average | 3737.00 | 21.52 | 3124.17 | 22.44 | 571.17 | 22.35 |
Minimum of Months | 48.50 | 20.88 | 26.67 | 20.72 | 4.83 | 20.59 |
Maximum of Months | 609.00 | 24.08 | 609.67 | 24.08 | 105.67 | 24.08 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 559.00 | 19.57 | 202.83 | 19.59 | 178.00 | 19.48 |
February | 457.83 | 19.62 | 170.83 | 19.96 | 121.50 | 19.84 |
March | 368.83 | 20.34 | 246.83 | 21.93 | 55.33 | 21.93 |
April | 356.67 | 23.40 | 373.83 | 24.46 | 192.33 | 24.76 |
May | 408.67 | 25.36 | 533.33 | 25.48 | 361.67 | 25.62 |
June | 511.33 | 25.95 | 585.67 | 25.88 | 508.17 | 25.91 |
July | 608.83 | 26.00 | 609.00 | 26.00 | 608.83 | 26.00 |
August | 607.17 | 25.98 | 612.00 | 25.97 | 607.17 | 25.97 |
September | 505.33 | 25.96 | 590.00 | 25.84 | 505.33 | 25.88 |
October | 432.67 | 23.80 | 427.33 | 24.56 | 282.83 | 24.86 |
November | 437.17 | 20.18 | 175.50 | 20.95 | 72.33 | 20.94 |
December | 596.83 | 19.37 | 193.17 | 19.29 | 190.67 | 19.24 |
Annual Sum or Average | 5850.33 | 23.04 | 4720.33 | 23.84 | 3684.17 | 24.11 |
Minimum of Months | 356.67 | 19.37 | 170.83 | 19.29 | 55.33 | 19.24 |
Maximum of Months | 608.83 | 26.00 | 612.00 | 26.00 | 608.83 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.10549 | 22.09389 | -0.3968 | 9.79856 |
February | 551.00000 | 21.29311 | 23.82352 | -0.3343 | 9.19675 |
March | 612.00000 | 22.04144 | 23.40062 | -0.1463 | 7.61350 |
April | 590.00000 | 22.95585 | 20.19080 | 0.08529 | 7.07339 |
May | 611.00000 | 23.52305 | 27.73524 | -0.6111 | 15.02219 |
June | 592.00000 | 23.93148 | 35.58454 | -0.3659 | 8.57345 |
July | 609.00000 | 24.08255 | 46.97957 | -0.2063 | 6.10961 |
August | 612.00000 | 24.05378 | 46.28566 | -0.2127 | 6.19502 |
September | 590.00000 | 23.90771 | 41.26176 | -0.3136 | 7.69872 |
October | 610.00000 | 23.02483 | 29.04716 | 0.19734 | 8.33260 |
November | 591.00000 | 21.71009 | 23.86652 | -0.1902 | 7.70887 |
December | 609.00000 | 20.88400 | 20.18781 | -0.4471 | 10.16729 |
Annual Sum or Average | 7187.00000 | 22.71700 | 30.08907 | -0.2450 | 8.62897 |
Minimum of Months | 551.00000 | 20.88400 | 20.18781 | -0.6111 | 6.10961 |
Maximum of Months | 612.00000 | 24.08255 | 46.97957 | 0.19734 | 15.02219 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.91512 | 28.93889 | -0.4010 | 10.90183 |
February | 551.00000 | 20.35886 | 30.37814 | -0.2939 | 11.07673 |
March | 612.00000 | 22.00123 | 28.82370 | 0.08717 | 11.65752 |
April | 590.00000 | 23.84252 | 24.84070 | 0.51469 | 16.81861 |
May | 611.00000 | 25.04809 | 29.94717 | 0.18731 | 12.23060 |
June | 592.00000 | 25.76963 | 36.01519 | 0.52445 | 12.52631 |
July | 609.00000 | 25.99547 | 45.28354 | 0.69957 | 15.75488 |
August | 612.00000 | 25.96501 | 44.67161 | 0.68231 | 15.35316 |
September | 590.00000 | 25.74565 | 40.73309 | 0.55553 | 13.06896 |
October | 610.00000 | 23.90062 | 32.03566 | 0.61626 | 20.59583 |
November | 591.00000 | 21.11863 | 29.23473 | -0.0801 | 10.24933 |
December | 609.00000 | 19.44289 | 27.14748 | -0.5095 | 11.62984 |
Annual Sum or Average | 7187.00000 | 23.27407 | 33.19986 | 0.21777 | 13.51109 |
Minimum of Months | 551.00000 | 19.44289 | 24.84070 | -0.5095 | 10.24933 |
Maximum of Months | 612.00000 | 25.99547 | 45.28354 | 0.69957 | 20.59583 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.361246E+09 | 0.117987E+09 | 15.33 | 0.361246E+09 | 0.00 | 0.00 | 0.38 | 14-FEB-14:00 | 0.00 | 01-FEB-00:01 | 13021.48 | 14-FEB-14:00 | 13021.48 | 14-FEB-14:00 | 0.00 | 14-FEB-13:55 | 4129.49 | 14-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.129844E+10 | 0.429148E+09 | 75.97 | 0.129779E+10 | 649023.93 | 0.00 | 0.53 | 08-MAR-14:00 | 0.00 | 01-MAR-00:01 | 18614.62 | 08-MAR-14:00 | 18614.62 | 08-MAR-14:00 | 194.60 | 16-MAR-12:15 | 5687.93 | 08-MAR-14:00 | 0.00 | 01-MAR-00:01 |
April | 0.957253E+10 | 0.297988E+10 | 225.86 | 0.956568E+10 | 6856399.69 | 0.00 | 1.00 | 12-APR-03:01 | 0.00 | 01-APR-00:01 | 80128.70 | 27-APR-03:01 | 80128.70 | 27-APR-03:01 | 11734.45 | 15-APR-03:01 | 21468.76 | 15-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.205006E+11 | 0.619013E+10 | 360.98 | 0.199632E+11 | 0.537363E+09 | 0.00 | 1.00 | 09-MAY-03:01 | 0.00 | 01-MAY-00:01 | 80128.70 | 19-MAY-03:41 | 80128.70 | 15-MAY-03:01 | 31848.73 | 24-MAY-03:01 | 21468.76 | 10-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.416454E+11 | 0.123140E+11 | 474.08 | 0.400311E+11 | 0.161434E+10 | 0.00 | 1.00 | 01-JUN-03:02 | 0.00 | 01-JUN-00:01 | 80128.70 | 12-JUN-03:02 | 80128.70 | 21-JUN-03:01 | 35242.66 | 05-JUN-03:01 | 21468.76 | 01-JUN-03:02 | 0.00 | 01-JUN-00:01 |
July | 0.592813E+11 | 0.171336E+11 | 568.75 | 0.506690E+11 | 0.861230E+10 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 80813.24 | 16-JUL-03:01 | 79133.48 | 21-JUL-03:01 | 39878.76 | 16-JUL-03:01 | 21520.57 | 16-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.529385E+11 | 0.151900E+11 | 541.71 | 0.452048E+11 | 0.773367E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 80653.25 | 14-AUG-03:01 | 77603.34 | 19-AUG-03:01 | 39476.08 | 26-AUG-03:41 | 21508.51 | 14-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.338709E+11 | 0.991351E+10 | 448.32 | 0.298470E+11 | 0.402389E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 80128.70 | 01-SEP-03:12 | 76857.56 | 22-SEP-03:41 | 37025.76 | 24-SEP-03:01 | 21468.76 | 01-SEP-03:12 | 0.00 | 01-SEP-00:01 |
October | 0.127470E+11 | 0.385549E+10 | 252.95 | 0.117499E+11 | 0.997116E+09 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 80128.70 | 11-OCT-03:02 | 72139.02 | 06-OCT-03:01 | 27650.94 | 11-OCT-03:41 | 21468.76 | 01-OCT-03:41 | 0.00 | 01-OCT-00:01 |
November | 76371504.81 | 25596747.57 | 6.87 | 69917645.38 | 6453859.44 | 0.00 | 0.26 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 | 8570.04 | 09-NOV-14:00 | 8241.91 | 09-NOV-14:00 | 689.47 | 02-NOV-17:10 | 2802.24 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.232292E+12 | 0.681493E+11 | 2970.83 | 0.208760E+12 | 0.235326E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.592813E+11 | 0.171336E+11 | 568.75 | 0.506690E+11 | 0.861230E+10 | 0.00 | 1.00 | 0.00 | 80813.24 | 80128.70 | 39878.76 | 21520.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 6312208.87 | 1926143.74 | 1.06 | 4955426.83 | 1356782.04 | 0.00 | 0.28 | 06-JAN-04:06 | 0.00 | 01-JAN-00:01 | 4653.36 | 06-JAN-04:06 | 3736.43 | 06-JAN-04:06 | 1155.73 | 03-JAN-04:06 | 1379.20 | 06-JAN-04:06 | 0.00 | 01-JAN-00:01 |
February | 0.210099E+09 | 62016789.75 | 19.13 | 0.207332E+09 | 2766801.66 | 0.00 | 1.00 | 14-FEB-04:41 | 0.00 | 01-FEB-00:01 | 20115.26 | 15-FEB-04:01 | 16641.60 | 14-FEB-04:41 | 3739.48 | 15-FEB-04:01 | 4912.49 | 14-FEB-04:41 | 0.00 | 01-FEB-00:01 |
March | 0.843419E+09 | 0.251146E+09 | 81.58 | 0.837912E+09 | 5507029.05 | 0.00 | 1.00 | 14-MAR-03:41 | 0.00 | 01-MAR-00:01 | 20115.26 | 14-MAR-03:41 | 17542.83 | 17-MAR-03:01 | 5577.58 | 21-MAR-03:41 | 4912.49 | 14-MAR-03:41 | 0.00 | 01-MAR-00:01 |
April | 0.636193E+10 | 0.176395E+10 | 242.57 | 0.633532E+10 | 26608485.66 | 0.00 | 1.00 | 02-APR-03:01 | 0.00 | 01-APR-00:01 | 40276.72 | 13-APR-03:51 | 40276.72 | 13-APR-03:51 | 10585.74 | 15-APR-03:31 | 9828.60 | 02-APR-03:41 | 0.00 | 01-APR-00:01 |
May | 0.145576E+11 | 0.386461E+10 | 390.09 | 0.138514E+11 | 0.706198E+09 | 0.00 | 1.00 | 01-MAY-03:11 | 0.00 | 01-MAY-00:01 | 40276.72 | 18-MAY-03:01 | 40276.72 | 20-MAY-03:01 | 19921.36 | 24-MAY-03:01 | 9828.60 | 01-MAY-03:11 | 0.00 | 01-MAY-00:01 |
June | 0.296486E+11 | 0.776802E+10 | 519.57 | 0.281192E+11 | 0.152945E+10 | 0.00 | 1.00 | 01-JUN-03:11 | 0.00 | 01-JUN-00:01 | 40276.72 | 22-JUN-01:32 | 38808.92 | 28-JUN-00:53 | 20804.00 | 05-JUN-03:01 | 10240.77 | 28-JUN-15:57 | 0.00 | 01-JUN-00:01 |
July | 0.422734E+11 | 0.108375E+11 | 629.57 | 0.358091E+11 | 0.646431E+10 | 0.00 | 1.00 | 01-JUL-00:53 | 0.00 | 01-JUL-00:01 | 40848.77 | 01-JUL-03:01 | 37754.88 | 21-JUL-00:42 | 24216.44 | 01-JUL-03:01 | 9875.10 | 22-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.368648E+11 | 0.937281E+10 | 602.36 | 0.309587E+11 | 0.590601E+10 | 0.00 | 1.00 | 01-AUG-02:12 | 0.00 | 01-AUG-00:01 | 40276.72 | 20-AUG-01:22 | 35733.78 | 16-AUG-01:22 | 24030.66 | 13-AUG-03:01 | 9828.60 | 01-AUG-03:06 | 0.00 | 01-AUG-00:01 |
September | 0.232717E+11 | 0.597422E+10 | 480.04 | 0.197824E+11 | 0.348933E+10 | 0.00 | 1.00 | 01-SEP-02:12 | 0.00 | 01-SEP-00:01 | 40276.72 | 03-SEP-03:38 | 34757.08 | 22-SEP-03:41 | 22930.15 | 06-SEP-04:01 | 9828.60 | 01-SEP-03:06 | 0.00 | 01-SEP-00:01 |
October | 0.847572E+10 | 0.226617E+10 | 269.39 | 0.754846E+10 | 0.927263E+09 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 40276.72 | 03-OCT-03:01 | 33323.70 | 16-OCT-03:01 | 17658.30 | 03-OCT-03:31 | 9828.60 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.133477E+09 | 38952122.26 | 16.33 | 0.109660E+09 | 23817318.61 | 0.00 | 1.00 | 01-NOV-03:11 | 0.00 | 01-NOV-00:01 | 40276.72 | 01-NOV-03:11 | 28618.57 | 10-NOV-04:01 | 15768.22 | 03-NOV-03:41 | 9828.60 | 01-NOV-03:11 | 0.00 | 01-NOV-00:01 |
December | 6373067.33 | 1968734.09 | 1.56 | 5300180.02 | 1072887.31 | 0.00 | 0.23 | 19-DEC-04:08 | 0.00 | 01-DEC-00:02 | 3843.00 | 19-DEC-04:08 | 3347.46 | 19-DEC-04:08 | 1009.23 | 26-DEC-04:10 | 1151.92 | 19-DEC-04:08 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.162653E+12 | 0.422033E+11 | 3253.24 | 0.143570E+12 | 0.190837E+11 | 0.00 | ||||||||||||||
Minimum of Months | 6312208.87 | 1926143.74 | 1.06 | 4955426.83 | 1072887.31 | 0.00 | 0.23 | 0.00 | 3843.00 | 3347.46 | 1009.23 | 1151.92 | 0.00 | |||||||
Maximum of Months | 0.422734E+11 | 0.108375E+11 | 629.57 | 0.358091E+11 | 0.646431E+10 | 0.00 | 1.00 | 0.00 | 40848.77 | 40276.72 | 24216.44 | 10240.77 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.39 | 172.05 | 135.34 | 266.01 | 378.14 | 0.00 | 0.00 | 0.00 |
February | 372.25 | 200.10 | 172.15 | 354.40 | 341.84 | 0.00 | 0.00 | 0.00 |
March | 494.68 | 281.82 | 212.86 | 532.60 | 267.27 | 0.00 | 0.00 | 0.00 |
April | 671.05 | 381.87 | 289.19 | 794.77 | 186.45 | 0.00 | 0.00 | 0.00 |
May | 641.09 | 365.16 | 275.93 | 799.94 | 142.90 | 0.00 | 0.00 | 0.00 |
June | 691.38 | 425.86 | 265.52 | 949.88 | 94.27 | 0.00 | 0.00 | 0.00 |
July | 639.42 | 365.53 | 273.89 | 919.05 | 63.72 | 0.00 | 0.00 | 0.00 |
August | 632.87 | 348.83 | 284.04 | 877.89 | 74.40 | 0.00 | 0.00 | 0.00 |
September | 527.73 | 295.29 | 232.44 | 688.09 | 127.67 | 0.00 | 0.00 | 0.00 |
October | 459.78 | 291.97 | 167.81 | 527.88 | 218.19 | 0.00 | 0.00 | 0.00 |
November | 357.59 | 209.78 | 147.82 | 349.15 | 307.41 | 0.00 | 0.00 | 0.00 |
December | 291.28 | 177.67 | 113.61 | 254.37 | 395.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 507.72 | 293.37 | 214.35 | 610.66 | 215.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 291.28 | 172.05 | 113.61 | 254.37 | 63.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 691.38 | 425.86 | 289.19 | 949.88 | 395.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1132.82 | 880.95 | 251.86 | 1310.12 | 506.11 | 0.00 | 0.00 | 0.00 |
February | 1116.63 | 817.22 | 299.41 | 1317.78 | 465.13 | 0.00 | 0.00 | 0.00 |
March | 830.32 | 506.67 | 323.65 | 997.23 | 380.52 | 0.00 | 0.00 | 0.00 |
April | 637.69 | 261.33 | 376.36 | 789.04 | 276.65 | 0.00 | 0.00 | 0.00 |
May | 429.17 | 97.09 | 332.08 | 533.51 | 207.91 | 0.00 | 0.00 | 0.00 |
June | 358.77 | 43.08 | 315.69 | 524.43 | 140.28 | 0.00 | 0.00 | 0.00 |
July | 397.14 | 62.31 | 334.83 | 634.45 | 91.79 | 0.00 | 0.00 | 0.00 |
August | 540.24 | 170.39 | 369.85 | 821.01 | 108.37 | 0.00 | 0.00 | 0.00 |
September | 766.94 | 431.72 | 335.22 | 1079.27 | 184.30 | 0.00 | 0.00 | 0.00 |
October | 1033.26 | 760.05 | 273.21 | 1315.79 | 300.35 | 0.00 | 0.00 | 0.00 |
November | 1165.55 | 897.03 | 268.52 | 1383.92 | 410.54 | 0.00 | 0.00 | 0.00 |
December | 1235.35 | 1019.76 | 215.58 | 1437.97 | 516.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 801.87 | 493.95 | 307.92 | 1010.27 | 298.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.77 | 43.08 | 215.58 | 524.43 | 91.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1235.35 | 1019.76 | 376.36 | 1437.97 | 516.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.01 | 180.79 | 136.22 | 301.49 | 398.78 | 0.00 | 0.00 | 0.00 |
February | 407.26 | 235.00 | 172.27 | 416.79 | 357.30 | 0.00 | 0.00 | 0.00 |
March | 454.43 | 241.39 | 213.04 | 491.94 | 281.97 | 0.00 | 0.00 | 0.00 |
April | 581.39 | 309.42 | 271.96 | 676.58 | 195.19 | 0.00 | 0.00 | 0.00 |
May | 552.86 | 285.66 | 267.21 | 681.25 | 147.18 | 0.00 | 0.00 | 0.00 |
June | 589.11 | 328.09 | 261.02 | 815.50 | 101.27 | 0.00 | 0.00 | 0.00 |
July | 531.88 | 259.90 | 271.98 | 772.39 | 66.38 | 0.00 | 0.00 | 0.00 |
August | 544.07 | 251.28 | 292.78 | 760.41 | 78.05 | 0.00 | 0.00 | 0.00 |
September | 493.64 | 260.63 | 233.01 | 649.21 | 133.87 | 0.00 | 0.00 | 0.00 |
October | 451.76 | 281.39 | 170.37 | 529.71 | 230.89 | 0.00 | 0.00 | 0.00 |
November | 353.01 | 207.66 | 145.35 | 353.64 | 318.77 | 0.00 | 0.00 | 0.00 |
December | 303.12 | 189.29 | 113.84 | 283.19 | 410.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.00 | 252.42 | 212.58 | 561.51 | 226.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.12 | 180.79 | 113.84 | 283.19 | 66.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 589.11 | 328.09 | 292.78 | 815.50 | 410.01 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823309E+09 | 0.460814E+09 | 0.362495E+09 | 0.712486E+09 | 0.101281E+10 |
February | 0.900536E+09 | 0.484081E+09 | 0.416455E+09 | 0.857374E+09 | 0.826975E+09 |
March | 0.132495E+10 | 0.754821E+09 | 0.570126E+09 | 0.142651E+10 | 0.715855E+09 |
April | 0.173937E+10 | 0.989803E+09 | 0.749570E+09 | 0.206004E+10 | 0.483281E+09 |
May | 0.171710E+10 | 0.978046E+09 | 0.739051E+09 | 0.214255E+10 | 0.382753E+09 |
June | 0.179206E+10 | 0.110384E+10 | 0.688216E+09 | 0.246209E+10 | 0.244352E+09 |
July | 0.171262E+10 | 0.979037E+09 | 0.733588E+09 | 0.246159E+10 | 0.170654E+09 |
August | 0.169507E+10 | 0.934296E+09 | 0.760770E+09 | 0.235134E+10 | 0.199285E+09 |
September | 0.136788E+10 | 0.765398E+09 | 0.602484E+09 | 0.178354E+10 | 0.330913E+09 |
October | 0.123148E+10 | 0.782015E+09 | 0.449467E+09 | 0.141387E+10 | 0.584407E+09 |
November | 0.926882E+09 | 0.543745E+09 | 0.383137E+09 | 0.904990E+09 | 0.796807E+09 |
December | 0.780158E+09 | 0.475874E+09 | 0.304285E+09 | 0.681318E+09 | 0.105932E+10 |
Annual Sum or Average | 0.160114E+11 | 0.925177E+10 | 0.675964E+10 | 0.192577E+11 | 0.680741E+10 |
Minimum of Months | 0.780158E+09 | 0.460814E+09 | 0.304285E+09 | 0.681318E+09 | 0.170654E+09 |
Maximum of Months | 0.179206E+10 | 0.110384E+10 | 0.760770E+09 | 0.246209E+10 | 0.105932E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303413E+10 | 0.235954E+10 | 0.674595E+09 | 0.350903E+10 | 0.135557E+10 |
February | 0.270136E+10 | 0.197702E+10 | 0.724336E+09 | 0.318798E+10 | 0.112523E+10 |
March | 0.222393E+10 | 0.135706E+10 | 0.866876E+09 | 0.267098E+10 | 0.101918E+10 |
April | 0.165289E+10 | 0.677374E+09 | 0.975514E+09 | 0.204518E+10 | 0.717082E+09 |
May | 0.114949E+10 | 0.260044E+09 | 0.889445E+09 | 0.142896E+10 | 0.556866E+09 |
June | 0.929943E+09 | 0.111665E+09 | 0.818278E+09 | 0.135932E+10 | 0.363612E+09 |
July | 0.106370E+10 | 0.166901E+09 | 0.896798E+09 | 0.169930E+10 | 0.245858E+09 |
August | 0.144699E+10 | 0.456374E+09 | 0.990617E+09 | 0.219899E+10 | 0.290247E+09 |
September | 0.198792E+10 | 0.111902E+10 | 0.868897E+09 | 0.279748E+10 | 0.477698E+09 |
October | 0.276749E+10 | 0.203572E+10 | 0.731779E+09 | 0.352421E+10 | 0.804470E+09 |
November | 0.302111E+10 | 0.232510E+10 | 0.696011E+09 | 0.358713E+10 | 0.106413E+10 |
December | 0.330875E+10 | 0.273134E+10 | 0.577419E+09 | 0.385145E+10 | 0.138445E+10 |
Annual Sum or Average | 0.252877E+11 | 0.155771E+11 | 0.971056E+10 | 0.318600E+11 | 0.940440E+10 |
Minimum of Months | 0.929943E+09 | 0.111665E+09 | 0.577419E+09 | 0.135932E+10 | 0.245858E+09 |
Maximum of Months | 0.330875E+10 | 0.273134E+10 | 0.990617E+09 | 0.385145E+10 | 0.138445E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.849074E+09 | 0.484231E+09 | 0.364843E+09 | 0.807517E+09 | 0.106810E+10 |
February | 0.985250E+09 | 0.568501E+09 | 0.416748E+09 | 0.100830E+10 | 0.864377E+09 |
March | 0.121714E+10 | 0.646543E+09 | 0.570602E+09 | 0.131760E+10 | 0.755227E+09 |
April | 0.150695E+10 | 0.802021E+09 | 0.704932E+09 | 0.175368E+10 | 0.505931E+09 |
May | 0.148079E+10 | 0.765106E+09 | 0.715684E+09 | 0.182466E+10 | 0.394215E+09 |
June | 0.152696E+10 | 0.850402E+09 | 0.676560E+09 | 0.211378E+10 | 0.262499E+09 |
July | 0.142460E+10 | 0.696121E+09 | 0.728478E+09 | 0.206877E+10 | 0.177779E+09 |
August | 0.145722E+10 | 0.673032E+09 | 0.784193E+09 | 0.203669E+10 | 0.209061E+09 |
September | 0.127951E+10 | 0.675554E+09 | 0.603961E+09 | 0.168276E+10 | 0.346993E+09 |
October | 0.120999E+10 | 0.753674E+09 | 0.456312E+09 | 0.141877E+10 | 0.618403E+09 |
November | 0.914990E+09 | 0.538252E+09 | 0.376739E+09 | 0.916638E+09 | 0.826248E+09 |
December | 0.811882E+09 | 0.506984E+09 | 0.304898E+09 | 0.758492E+09 | 0.109817E+10 |
Annual Sum or Average | 0.146644E+11 | 0.796042E+10 | 0.670395E+10 | 0.177076E+11 | 0.712701E+10 |
Minimum of Months | 0.811882E+09 | 0.484231E+09 | 0.304898E+09 | 0.758492E+09 | 0.177779E+09 |
Maximum of Months | 0.152696E+10 | 0.850402E+09 | 0.784193E+09 | 0.211378E+10 | 0.109817E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1832.24 | 1237.65 | 1757.21 | 1233.79 | 523.42 | 0.00 | 0.00 |
February | 2051.99 | 1127.28 | 1896.14 | 1252.32 | 643.82 | 0.00 | 0.00 |
March | 1983.58 | 891.57 | 1779.43 | 1029.88 | 749.55 | 0.00 | 0.00 |
April | 2222.02 | 619.94 | 1890.13 | 952.62 | 937.51 | 0.00 | 0.00 |
May | 1993.99 | 477.29 | 1623.12 | 747.91 | 875.22 | 0.00 | 0.00 |
June | 2273.26 | 319.27 | 1639.26 | 797.03 | 842.23 | 0.00 | 0.00 |
July | 2320.57 | 216.56 | 1568.45 | 687.75 | 880.70 | 0.00 | 0.00 |
August | 2450.64 | 252.16 | 1717.17 | 770.50 | 946.68 | 0.00 | 0.00 |
September | 2402.47 | 431.73 | 1788.32 | 987.64 | 800.67 | 0.00 | 0.00 |
October | 2347.51 | 723.56 | 1944.80 | 1333.41 | 611.39 | 0.00 | 0.00 |
November | 2051.27 | 1001.28 | 1876.15 | 1314.47 | 561.68 | 0.00 | 0.00 |
December | 1917.62 | 1264.50 | 1829.75 | 1386.72 | 443.03 | 0.00 | 0.00 |
Annual Sum or Average | 2153.85 | 711.49 | 1774.59 | 1039.74 | 734.85 | 0.00 | 0.00 |
Minimum of Months | 1832.24 | 216.56 | 1568.45 | 687.75 | 443.03 | 0.00 | 0.00 |
Maximum of Months | 2450.64 | 1264.50 | 1944.80 | 1386.72 | 946.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.490746E+10 | 0.331491E+10 | 0.470652E+10 | 0.330458E+10 | 0.140193E+10 | 0.00 | 0.00 |
February | 0.496418E+10 | 0.272711E+10 | 0.458714E+10 | 0.302961E+10 | 0.155754E+10 | 0.00 | 0.00 |
March | 0.531282E+10 | 0.238799E+10 | 0.476602E+10 | 0.275842E+10 | 0.200760E+10 | 0.00 | 0.00 |
April | 0.575949E+10 | 0.160687E+10 | 0.489921E+10 | 0.246920E+10 | 0.243002E+10 | 0.00 | 0.00 |
May | 0.534070E+10 | 0.127837E+10 | 0.434737E+10 | 0.200320E+10 | 0.234418E+10 | 0.00 | 0.00 |
June | 0.589228E+10 | 0.827550E+09 | 0.424896E+10 | 0.206591E+10 | 0.218305E+10 | 0.00 | 0.00 |
July | 0.621541E+10 | 0.580035E+09 | 0.420092E+10 | 0.184206E+10 | 0.235886E+10 | 0.00 | 0.00 |
August | 0.656381E+10 | 0.675385E+09 | 0.459928E+10 | 0.206370E+10 | 0.253558E+10 | 0.00 | 0.00 |
September | 0.622721E+10 | 0.111904E+10 | 0.463532E+10 | 0.255997E+10 | 0.207534E+10 | 0.00 | 0.00 |
October | 0.628756E+10 | 0.193800E+10 | 0.520896E+10 | 0.357140E+10 | 0.163756E+10 | 0.00 | 0.00 |
November | 0.531689E+10 | 0.259532E+10 | 0.486298E+10 | 0.340709E+10 | 0.145589E+10 | 0.00 | 0.00 |
December | 0.513616E+10 | 0.338685E+10 | 0.490079E+10 | 0.371419E+10 | 0.118660E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.679240E+11 | 0.224374E+11 | 0.559635E+11 | 0.327893E+11 | 0.231742E+11 | 0.00 | 0.00 |
Minimum of Months | 0.490746E+10 | 0.580035E+09 | 0.420092E+10 | 0.184206E+10 | 0.118660E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656381E+10 | 0.338685E+10 | 0.520896E+10 | 0.371419E+10 | 0.253558E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639584E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -170669850.1 | 81.22 | 0.00 | 0.00 |
February | 0.578744E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -153158459.5 | 81.22 | 0.00 | 0.00 |
March | 0.645904E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165164870.9 | 81.22 | 0.00 | 0.00 |
April | 0.619839E+10 | -0.604349E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154902727.4 | 81.22 | 0.00 | 0.00 |
May | 0.641695E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156763038.2 | 81.21 | 0.00 | 0.00 |
June | 0.623650E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149927984.4 | 81.21 | 0.00 | 0.00 |
July | 0.637146E+10 | -0.621712E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154335841.3 | 81.21 | 0.00 | 0.00 |
August | 0.644961E+10 | -0.629524E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154364709.8 | 81.21 | 0.00 | 0.00 |
September | 0.619471E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149888443.8 | 81.21 | 0.00 | 0.00 |
October | 0.638354E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159713818.9 | 81.21 | 0.00 | 0.00 |
November | 0.618648E+10 | -0.602463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -161854558.6 | 81.22 | 0.00 | 0.00 |
December | 0.638887E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171790955.0 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754688E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190254E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578744E+10 | -0.629524E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -171790955.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645904E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149888443.8 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.242220E+11 | -0.232335E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -988566256.9 | 58.99 | 0.00 | 0.00 |
February | 0.220736E+11 | -0.211898E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -883848074.7 | 58.99 | 0.00 | 0.00 |
March | 0.240240E+11 | -0.230858E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -938197251.4 | 58.99 | 0.00 | 0.00 |
April | 0.218515E+11 | -0.209887E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -862787526.1 | 58.99 | 0.00 | 0.00 |
May | 0.210700E+11 | -0.202087E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -861338223.2 | 58.99 | 0.00 | 0.00 |
June | 0.190610E+11 | -0.182439E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -817132271.7 | 58.98 | 0.00 | 0.00 |
July | 0.185318E+11 | -0.176928E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839048221.7 | 58.98 | 0.00 | 0.00 |
August | 0.185519E+11 | -0.177127E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839237331.6 | 58.98 | 0.00 | 0.00 |
September | 0.184094E+11 | -0.175925E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -816897479.4 | 58.99 | 0.00 | 0.00 |
October | 0.202346E+11 | -0.193463E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -888332600.1 | 58.99 | 0.00 | 0.00 |
November | 0.211320E+11 | -0.202055E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -926462931.0 | 58.99 | 0.00 | 0.00 |
December | 0.232646E+11 | -0.222657E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -998850302.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.252427E+12 | -0.241766E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.106607E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.184094E+11 | -0.232335E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -998850302.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.242220E+11 | -0.175925E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -816897479.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.51 | 0.50 | 01-JAN-07:40 | 1550.97 | 25.38 | 172.33 | 287.50 | 1408.19 | 25.98 | 182.67 | 287.17 |
February | 282.00 | 0.52 | 0.50 | 01-FEB-07:40 | 1910.06 | 25.21 | 179.67 | 272.67 | 1343.42 | 24.59 | 179.67 | 273.83 |
March | 351.33 | 0.52 | 0.50 | 01-MAR-06:00 | 1219.69 | 20.91 | 146.33 | 333.00 | 1661.33 | 21.59 | 168.00 | 332.50 |
April | 381.83 | 0.52 | 0.50 | 01-APR-06:40 | 1479.08 | 21.39 | 196.17 | 365.67 | 1536.91 | 21.33 | 182.17 | 362.67 |
May | 378.00 | 0.52 | 0.50 | 01-MAY-06:10 | 1433.52 | 20.98 | 159.67 | 389.17 | 1716.87 | 20.99 | 120.17 | 381.33 |
June | 412.83 | 0.51 | 0.50 | 01-JUN-05:49 | 947.40 | 20.99 | 101.67 | 388.33 | 1693.11 | 20.07 | 91.00 | 398.50 |
July | 395.33 | 0.52 | 0.50 | 01-JUL-06:40 | 973.08 | 20.75 | 128.83 | 385.67 | 1535.01 | 20.68 | 139.83 | 386.33 |
August | 408.83 | 0.52 | 0.50 | 01-AUG-05:00 | 1360.63 | 21.20 | 182.67 | 384.00 | 1372.13 | 21.20 | 187.67 | 383.00 |
September | 359.33 | 0.52 | 0.50 | 01-SEP-06:30 | 1336.30 | 21.49 | 163.67 | 337.83 | 1198.13 | 20.96 | 137.33 | 339.50 |
October | 329.00 | 0.52 | 0.50 | 01-OCT-06:49 | 1596.22 | 23.56 | 170.33 | 318.67 | 1861.49 | 23.25 | 173.50 | 321.00 |
November | 284.17 | 0.51 | 0.50 | 01-NOV-06:49 | 1603.84 | 26.50 | 179.33 | 283.67 | 1671.64 | 26.24 | 182.50 | 282.33 |
December | 265.67 | 0.52 | 0.50 | 01-DEC-07:49 | 2110.74 | 27.98 | 157.83 | 270.00 | 2200.75 | 28.68 | 163.50 | 271.67 |
Annual Sum or Average | 4149.83 | 0.52 | 1420.62 | 22.69 | 1938.50 | 4016.17 | 1588.58 | 22.61 | 1908.00 | 4019.83 | ||
Minimum of Months | 265.67 | 0.51 | 0.50 | 947.40 | 20.75 | 101.67 | 270.00 | 1198.13 | 20.07 | 91.00 | 271.67 | |
Maximum of Months | 412.83 | 0.52 | 0.50 | 2110.74 | 27.98 | 196.17 | 389.17 | 2200.75 | 28.68 | 187.67 | 398.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247266E+11 | 121516.75 | 20-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179866E+11 | 121516.75 | 04-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.871761E+10 | 62151.88 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.248012E+10 | 25355.80 | 06-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.520334E+09 | 18774.15 | 06-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28536985.01 | 10982.68 | 09-JUN-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6369495.35 | 9606.31 | 20-JUL-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4094355.77 | 9910.37 | 02-AUG-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 522042.43 | 3480.28 | 03-SEP-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322029E+10 | 33819.40 | 25-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.968949E+10 | 38466.95 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251879E+11 | 121516.75 | 15-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.925684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 522042.43 | 3480.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251879E+11 | 121516.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135771E+11 | 28173.07 | 22-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.958258E+10 | 35180.67 | 04-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367610E+10 | 22148.69 | 30-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.663541E+09 | 14340.79 | 20-APR-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49176199.70 | 8354.87 | 06-MAY-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113913E+10 | 21622.36 | 25-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.443638E+10 | 22230.16 | 16-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136128E+11 | 31489.38 | 15-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136128E+11 | 35180.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.361246E+09 | 0.361246E+09 | 13021.48 | 14-FEB-14:00 | 13021.48 | 0.00 |
March | 0.00 | 0.00 | 0.129844E+10 | 0.129779E+10 | 18614.62 | 08-MAR-14:00 | 18614.62 | 0.00 |
April | 0.00 | 0.00 | 0.957253E+10 | 0.956568E+10 | 80128.70 | 27-APR-03:01 | 80128.70 | 0.00 |
May | 0.00 | 0.00 | 0.205006E+11 | 0.199632E+11 | 80128.70 | 19-MAY-03:41 | 75218.07 | 0.00 |
June | 0.00 | 0.00 | 0.416454E+11 | 0.400311E+11 | 80128.70 | 12-JUN-03:02 | 69934.85 | 0.00 |
July | 0.00 | 0.00 | 0.592813E+11 | 0.506690E+11 | 80813.24 | 16-JUL-03:01 | 40934.48 | 0.00 |
August | 0.00 | 0.00 | 0.529385E+11 | 0.452048E+11 | 80653.25 | 14-AUG-03:01 | 45152.22 | 0.00 |
September | 0.00 | 0.00 | 0.338709E+11 | 0.298470E+11 | 80128.70 | 01-SEP-03:12 | 58945.76 | 0.00 |
October | 0.00 | 0.00 | 0.127470E+11 | 0.117499E+11 | 80128.70 | 11-OCT-03:02 | 53809.21 | 0.00 |
November | 0.00 | 0.00 | 76371504.81 | 69917645.38 | 8570.04 | 09-NOV-14:00 | 8241.91 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232292E+12 | 0.208760E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.592813E+11 | 0.506690E+11 | 80813.24 | 80128.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6312208.87 | 4955426.83 | 4653.36 | 06-JAN-04:06 | 3736.43 | 0.00 |
February | 0.00 | 0.00 | 0.210099E+09 | 0.207332E+09 | 20115.26 | 15-FEB-04:01 | 16375.78 | 0.00 |
March | 0.00 | 0.00 | 0.843419E+09 | 0.837912E+09 | 20115.26 | 14-MAR-03:41 | 17219.67 | 0.00 |
April | 0.00 | 0.00 | 0.636193E+10 | 0.633532E+10 | 40276.72 | 13-APR-03:51 | 40276.72 | 0.00 |
May | 0.00 | 0.00 | 0.145576E+11 | 0.138514E+11 | 40276.72 | 18-MAY-03:01 | 30015.73 | 0.00 |
June | 0.00 | 0.00 | 0.296486E+11 | 0.281192E+11 | 40276.72 | 22-JUN-01:32 | 32745.07 | 0.00 |
July | 0.00 | 0.00 | 0.422734E+11 | 0.358091E+11 | 40848.77 | 01-JUL-03:01 | 16632.33 | 0.00 |
August | 0.00 | 0.00 | 0.368648E+11 | 0.309587E+11 | 40276.72 | 20-AUG-01:22 | 32184.54 | 0.00 |
September | 0.00 | 0.00 | 0.232717E+11 | 0.197824E+11 | 40276.72 | 03-SEP-03:38 | 30236.61 | 0.00 |
October | 0.00 | 0.00 | 0.847572E+10 | 0.754846E+10 | 40276.72 | 03-OCT-03:01 | 23441.63 | 0.00 |
November | 0.00 | 0.00 | 0.133477E+09 | 0.109660E+09 | 40276.72 | 01-NOV-03:11 | 25949.58 | 0.00 |
December | 0.00 | 0.00 | 6373067.33 | 5300180.02 | 3843.00 | 19-DEC-04:08 | 3347.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162653E+12 | 0.143570E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6312208.87 | 4955426.83 | 3843.00 | 3347.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.422734E+11 | 0.358091E+11 | 40848.77 | 40276.72 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9133.65 | 17547.14 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 9218.15 | 17548.07 | 14-FEB-07:58 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9078.66 | 17401.85 | 01-MAR-07:54 |
April | 0.00 | 0.00 | 01-APR-00:01 | 8558.08 | 16638.13 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8006.60 | 15678.87 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 7501.03 | 14523.43 | 01-JUN-18:15 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 7069.45 | 13642.97 | 03-JUL-18:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 7076.68 | 13418.31 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 7250.44 | 14024.54 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7685.46 | 15083.49 | 31-OCT-18:50 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8256.53 | 16180.38 | 30-NOV-19:55 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 8773.29 | 17049.13 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8127.75 | ||||
Minimum of Months | 0.00 | 0.00 | 7069.45 | 13418.31 | ||
Maximum of Months | 0.00 | 0.00 | 9218.15 | 17548.07 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.186557E+10 | 0.27 | 824.13 | 01-JAN-00:01 | 0.32 |
February | 0.169636E+10 | 0.27 | 824.13 | 01-FEB-00:01 | 0.32 |
March | 0.190725E+10 | 0.28 | 824.13 | 01-MAR-00:01 | 0.32 |
April | 0.188841E+10 | 0.28 | 824.13 | 01-APR-03:02 | 0.32 |
May | 0.202266E+10 | 0.29 | 824.13 | 01-MAY-01:45 | 0.32 |
June | 0.201574E+10 | 0.30 | 824.13 | 01-JUN-00:40 | 0.32 |
July | 0.210883E+10 | 0.30 | 824.13 | 01-JUL-00:12 | 0.32 |
August | 0.210515E+10 | 0.30 | 824.13 | 01-AUG-00:12 | 0.32 |
September | 0.202390E+10 | 0.30 | 824.13 | 01-SEP-00:12 | 0.32 |
October | 0.198412E+10 | 0.29 | 824.13 | 01-OCT-00:30 | 0.32 |
November | 0.184742E+10 | 0.28 | 824.13 | 01-NOV-01:55 | 0.32 |
December | 0.186572E+10 | 0.27 | 824.13 | 01-DEC-00:02 | 0.32 |
Annual Sum or Average | 0.233311E+11 | 0.29 | |||
Minimum of Months | 0.169636E+10 | 0.27 | 824.13 | 0.32 | |
Maximum of Months | 0.210883E+10 | 0.30 | 824.13 | 0.32 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.758445E+10 | 0.94 | 7463.26 | 20-JAN-04:02 | 1.69 |
February | 0.669196E+10 | 0.92 | 7463.26 | 04-FEB-04:03 | 1.70 |
March | 0.698537E+10 | 0.88 | 5275.64 | 04-MAR-05:02 | 1.44 |
April | 0.654495E+10 | 0.87 | 3919.68 | 06-APR-04:03 | 1.22 |
May | 0.669952E+10 | 0.87 | 4969.12 | 22-MAY-03:01 | 1.38 |
June | 0.657895E+10 | 0.88 | 7463.26 | 24-JUN-03:01 | 1.68 |
July | 0.690572E+10 | 0.88 | 7463.26 | 01-JUL-03:01 | 1.67 |
August | 0.680725E+10 | 0.87 | 7463.26 | 06-AUG-03:01 | 1.68 |
September | 0.650099E+10 | 0.87 | 7463.26 | 07-SEP-03:01 | 1.68 |
October | 0.680174E+10 | 0.87 | 6879.77 | 02-OCT-03:01 | 1.62 |
November | 0.680591E+10 | 0.88 | 4402.83 | 27-NOV-05:01 | 1.30 |
December | 0.760247E+10 | 0.94 | 7463.26 | 15-DEC-04:02 | 1.70 |
Annual Sum or Average | 0.825093E+11 | 0.89 | |||
Minimum of Months | 0.650099E+10 | 0.87 | 3919.68 | 1.22 | |
Maximum of Months | 0.760247E+10 | 0.94 | 7463.26 | 1.70 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201175E+10 | 0.58 | 1216.77 | 22-JAN-05:03 | 0.83 |
February | 0.177992E+10 | 0.58 | 1317.10 | 04-FEB-05:03 | 0.87 |
March | 0.187668E+10 | 0.57 | 1130.52 | 30-MAR-04:04 | 0.79 |
April | 0.178683E+10 | 0.57 | 2033.55 | 14-APR-03:11 | 1.07 |
May | 0.185605E+10 | 0.59 | 2033.55 | 01-MAY-03:11 | 1.07 |
June | 0.202925E+10 | 0.63 | 2033.55 | 01-JUN-03:11 | 1.06 |
July | 0.227680E+10 | 0.66 | 2033.55 | 01-JUL-03:01 | 1.06 |
August | 0.212139E+10 | 0.64 | 2033.55 | 04-AUG-03:31 | 1.06 |
September | 0.184529E+10 | 0.61 | 2033.55 | 01-SEP-03:31 | 1.06 |
October | 0.186373E+10 | 0.58 | 2033.55 | 01-OCT-03:01 | 1.06 |
November | 0.182863E+10 | 0.57 | 2033.55 | 01-NOV-03:11 | 1.07 |
December | 0.201227E+10 | 0.58 | 1264.25 | 15-DEC-05:03 | 0.85 |
Annual Sum or Average | 0.232886E+11 | 0.60 | |||
Minimum of Months | 0.177992E+10 | 0.57 | 1130.52 | 0.79 | |
Maximum of Months | 0.227680E+10 | 0.66 | 2033.55 | 1.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 48.95 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 47.93 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 48.26 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 51.57 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 52.71 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 52.86 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 53.36 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 53.03 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 53.44 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.23 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.46 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:02 | 5.36 | 5.36 | 48.91 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 47.93 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 53.44 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 48.95 | 59.91 | 9133.65 | 17547.14 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 47.93 | 59.13 | 9218.15 | 17548.07 | 14-FEB-07:58 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 48.26 | 59.16 | 9078.66 | 17401.85 | 01-MAR-07:54 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.04 | 50.04 | 8558.08 | 16638.13 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 50.30 | 50.30 | 8006.60 | 15678.87 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.36 | 51.36 | 7501.03 | 14523.43 | 01-JUN-18:15 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.91 | 51.91 | 7069.45 | 13642.97 | 03-JUL-18:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.77 | 51.77 | 7076.68 | 13418.31 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.05 | 52.05 | 7250.44 | 14024.54 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 49.37 | 49.37 | 7685.46 | 15083.49 | 31-OCT-18:50 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.49 | 50.49 | 8256.53 | 16180.38 | 30-NOV-19:55 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 48.91 | 58.18 | 8773.29 | 17049.13 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8127.75 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.93 | 49.37 | 7069.45 | 13418.31 | ||
Maximum of Months | 0.00 | 0.00 | 52.05 | 59.91 | 9218.15 | 17548.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.758445E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.680995E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.741452E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.952483E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.128897E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.188929E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.240393E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.219972E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.164145E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106572E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.683151E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.760247E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.150659E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.680995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.240393E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201367E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.184193E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.212783E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.355078E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.572065E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.979727E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131143E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114942E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.781951E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.412989E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.186758E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.201424E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.654919E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.184193E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.131143E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.758445E+10 | 0.00 | 0.247266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669196E+10 | 0.361246E+09 | 0.179866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.698537E+10 | 0.129844E+10 | 0.871761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654495E+10 | 0.956763E+10 | 0.248012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.669952E+10 | 0.204704E+11 | 0.520334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.657895E+10 | 0.415486E+11 | 28536985.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690572E+10 | 0.590112E+11 | 6369495.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.680725E+10 | 0.526968E+11 | 4094355.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650099E+10 | 0.337971E+11 | 522042.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.680174E+10 | 0.127264E+11 | 0.322029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.680591E+10 | 76371504.81 | 0.968949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.760247E+10 | 0.00 | 0.251879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825093E+11 | 0.231554E+12 | 0.925684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.650099E+10 | 0.00 | 522042.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.760247E+10 | 0.590112E+11 | 0.251879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.201175E+10 | 6312208.87 | 0.135771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177992E+10 | 0.210099E+09 | 0.958258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187668E+10 | 0.843419E+09 | 0.367610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178683E+10 | 0.635006E+10 | 0.663541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185605E+10 | 0.145427E+11 | 49176199.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202925E+10 | 0.295426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.227680E+10 | 0.420245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212139E+10 | 0.366769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184529E+10 | 0.232302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186373E+10 | 0.847079E+10 | 0.113913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182863E+10 | 0.131743E+09 | 0.443638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201227E+10 | 6373067.33 | 0.136128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232886E+11 | 0.162036E+12 | 0.467368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177992E+10 | 6312208.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227680E+10 | 0.420245E+11 | 0.136128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.758445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669196E+10 | 0.00 | 0.00 | 0.00 | 0.117987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.698537E+10 | 0.00 | 0.00 | 0.00 | 0.429148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654495E+10 | 0.00 | 0.00 | 0.00 | 0.297988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.669952E+10 | 0.00 | 0.00 | 0.00 | 0.619013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.657895E+10 | 0.00 | 0.00 | 0.00 | 0.123140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690572E+10 | 0.00 | 0.00 | 0.00 | 0.171336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.680725E+10 | 0.00 | 0.00 | 0.00 | 0.151900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650099E+10 | 0.00 | 0.00 | 0.00 | 0.991351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.680174E+10 | 0.00 | 0.00 | 0.00 | 0.385549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.680591E+10 | 0.00 | 0.00 | 0.00 | 25596747.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.760247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825093E+11 | 0.00 | 0.00 | 0.00 | 0.681493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.650099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.760247E+10 | 0.00 | 0.00 | 0.00 | 0.171336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 1926143.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177992E+10 | 0.00 | 0.00 | 0.00 | 62016789.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187668E+10 | 0.00 | 0.00 | 0.00 | 0.251146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178683E+10 | 0.00 | 0.00 | 0.00 | 0.176395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185605E+10 | 0.00 | 0.00 | 0.00 | 0.386461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202925E+10 | 0.00 | 0.00 | 0.00 | 0.776802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.227680E+10 | 0.00 | 0.00 | 0.00 | 0.108375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212139E+10 | 0.00 | 0.00 | 0.00 | 0.937281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184529E+10 | 0.00 | 0.00 | 0.00 | 0.597422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186373E+10 | 0.00 | 0.00 | 0.00 | 0.226617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182863E+10 | 0.00 | 0.00 | 0.00 | 38952122.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201227E+10 | 0.00 | 0.00 | 0.00 | 1968734.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232886E+11 | 0.00 | 0.00 | 0.00 | 0.422033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177992E+10 | 0.00 | 0.00 | 0.00 | 1926143.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227680E+10 | 0.00 | 0.00 | 0.00 | 0.108375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.575679E+11 | 0.00 | 0.00 | 2941916.92 | 0.00 | 0.272063E+10 | 0.348539E+10 | 0.00 | 3.54 |
February | 0.470697E+11 | 0.00 | 0.00 | 9061921.02 | 0.00 | 0.182108E+10 | 0.507281E+10 | 0.00 | 3.63 |
March | 0.344530E+11 | 0.00 | 0.00 | 35044390.95 | 0.00 | 0.383883E+09 | 0.154657E+11 | 0.00 | 3.88 |
April | 0.172772E+11 | 0.00 | 0.00 | 79230383.35 | 0.00 | 13613008.35 | 0.212546E+11 | 0.00 | 4.25 |
May | 0.856103E+10 | 58503493.17 | 0.00 | 0.116991E+09 | 0.00 | 1306439.14 | 0.212194E+11 | 0.00 | 4.34 |
June | 0.258962E+10 | 0.261374E+10 | 71372.37 | 0.109828E+09 | 1926975.33 | 24587.60 | 0.122830E+11 | 11360.43 | 4.19 |
July | 0.513755E+09 | 0.569816E+10 | 331677.56 | 63492512.81 | 18167770.86 | 111652.47 | 0.486580E+10 | 15103.33 | 4.20 |
August | 0.670887E+09 | 0.317929E+10 | 228857.05 | 96877724.88 | 6016371.59 | 18862.73 | 0.864017E+10 | 13299.48 | 4.32 |
September | 0.230401E+10 | 0.475154E+09 | 0.00 | 0.145717E+09 | 0.00 | 52361.34 | 0.182411E+11 | 0.00 | 4.50 |
October | 0.180585E+11 | 23241769.38 | 0.00 | 91511039.09 | 0.00 | 7229627.87 | 0.226867E+11 | 0.00 | 4.30 |
November | 0.392495E+11 | 0.00 | 0.00 | 14700869.80 | 0.00 | 37235370.74 | 0.130053E+11 | 0.00 | 3.61 |
December | 0.619335E+11 | 0.00 | 0.00 | 266800.02 | 0.00 | 0.199318E+10 | 0.102223E+10 | 0.00 | 3.53 |
Annual Sum or Average | 0.290249E+12 | 0.120481E+11 | 631906.98 | 0.765663E+09 | 26111117.78 | 0.697837E+10 | 0.147242E+12 | 39763.24 | 4.03 |
Minimum of Months | 0.513755E+09 | 0.00 | 0.00 | 266800.02 | 0.00 | 18862.73 | 0.102223E+10 | 0.00 | 3.53 |
Maximum of Months | 0.619335E+11 | 0.569816E+10 | 331677.56 | 0.145717E+09 | 18167770.86 | 0.272063E+10 | 0.226867E+11 | 15103.33 | 4.50 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.554509E+11 | 0.00 | 0.00 | 1900411.39 | 0.00 | 0.00 | 0.366907E+10 | 0.00 | 8.58 |
February | 0.445985E+11 | 0.00 | 0.00 | 7922178.95 | 0.00 | 5415660.57 | 0.555810E+10 | 0.00 | 8.63 |
March | 0.309637E+11 | 0.00 | 0.00 | 31380036.32 | 0.00 | 0.00 | 0.173707E+11 | 0.00 | 8.75 |
April | 0.157575E+11 | 0.00 | 0.00 | 73343226.42 | 0.00 | 0.00 | 0.236061E+11 | 0.00 | 8.93 |
May | 0.578264E+10 | 38884.96 | 0.00 | 0.117559E+09 | 0.00 | 0.00 | 0.263580E+11 | 0.00 | 9.07 |
June | 0.949053E+09 | 0.372555E+09 | 0.00 | 0.149534E+09 | 0.00 | 0.00 | 0.179273E+11 | 0.00 | 9.21 |
July | 0.00 | 0.773962E+09 | 0.00 | 0.157495E+09 | 0.00 | 0.00 | 0.894325E+10 | 0.00 | 9.38 |
August | 424553.85 | 0.214566E+09 | 0.00 | 0.167676E+09 | 0.00 | 0.00 | 0.131324E+11 | 0.00 | 9.36 |
September | 0.395806E+09 | 3264468.51 | 0.00 | 0.150803E+09 | 0.00 | 0.00 | 0.225701E+11 | 0.00 | 9.24 |
October | 0.148294E+11 | 0.00 | 0.00 | 85176465.97 | 0.00 | 0.00 | 0.248385E+11 | 0.00 | 8.98 |
November | 0.360117E+11 | 0.00 | 0.00 | 12195440.74 | 0.00 | 0.00 | 0.129169E+11 | 0.00 | 8.64 |
December | 0.581757E+11 | 0.00 | 0.00 | 659670.56 | 0.00 | 0.00 | 0.123128E+10 | 0.00 | 8.57 |
Annual Sum or Average | 0.262915E+12 | 0.136439E+10 | 0.00 | 0.955643E+09 | 0.00 | 5415660.57 | 0.178122E+12 | 0.00 | 8.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 659670.56 | 0.00 | 0.00 | 0.123128E+10 | 0.00 | 8.57 |
Maximum of Months | 0.581757E+11 | 0.773962E+09 | 0.00 | 0.167676E+09 | 0.00 | 5415660.57 | 0.263580E+11 | 0.00 | 9.38 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:00
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.538034E+11 | 0.108864E+11 | 0.196918E+12 | 91525069.11 | 0.281133E+11 |
February | 0.714171E+11 | 0.100057E+11 | 0.168525E+12 | 0.603616E+09 | 0.251425E+11 |
March | 0.101540E+12 | 0.988144E+10 | 0.162919E+12 | 0.286497E+10 | 0.280950E+11 |
April | 0.135303E+12 | 0.871985E+10 | 0.131935E+12 | 0.502073E+10 | 0.456924E+11 |
May | 0.147501E+12 | 0.771477E+10 | 0.111349E+12 | 0.520083E+10 | 0.719859E+11 |
June | 0.139417E+12 | 0.548060E+10 | 0.642383E+11 | 0.310113E+10 | 0.119558E+12 |
July | 0.140809E+12 | 0.426302E+10 | 0.275679E+11 | 0.149747E+10 | 0.159592E+12 |
August | 0.134221E+12 | 0.507113E+10 | 0.449675E+11 | 0.247531E+10 | 0.143819E+12 |
September | 0.104416E+12 | 0.541699E+10 | 0.826966E+11 | 0.486968E+10 | 0.999856E+11 |
October | 0.795182E+11 | 0.751352E+10 | 0.136238E+12 | 0.557062E+10 | 0.522174E+11 |
November | 0.599148E+11 | 0.927955E+10 | 0.167374E+12 | 0.862537E+09 | 0.220346E+11 |
December | 0.490706E+11 | 0.108213E+11 | 0.198519E+12 | 0.00 | 0.265842E+11 |
Annual Sum or Average | 0.121693E+13 | 0.950543E+11 | 0.149325E+13 | 0.321584E+11 | 0.822820E+12 |
Minimum of Months | 0.490706E+11 | 0.426302E+10 | 0.275679E+11 | 0.00 | 0.220346E+11 |
Maximum of Months | 0.147501E+12 | 0.108864E+11 | 0.198519E+12 | 0.557062E+10 | 0.159592E+12 |