Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:24:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2073.17 | 4055.87 | 4055.87 |
Net Site Energy | 2073.17 | 4055.87 | 4055.87 |
Total Source Energy | 4052.05 | 7927.27 | 7927.27 |
Net Source Energy | 4052.05 | 7927.27 | 7927.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 359.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.53 | 377.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 61.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 866.41 | 1206.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 359.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.19 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 141.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.53 | 377.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 359.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 10.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 71.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 141.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.53 | 377.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 61.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 446.41 | 1441.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1020.91 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1695.01 | 2360.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 446.41 | 1441.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1020.91 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1695.01 | 2360.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 866.410 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 866.410 | 100.00 |
Total On-Site and Utility Electric Sources | 866.410 | 100.00 |
Total Electricity End Uses | 866.410 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1990.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 9.5182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.3127 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.5182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.3127 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 9.4622 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-10:00 | 10-JAN-07:40 | - | - | - | - | - | - | - | - | - | - | 06-APR-18:30 |
Heating | 0.00 | 78251.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11795.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2850.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24680.63 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5040.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3974.19 | 30393.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2887.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 51247.23 | 122221.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 78251.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 11795.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2850.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 23313.05 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5040.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3974.19 | 30393.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 526.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1310.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1050.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 390.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 34.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 226.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 142.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1457.82 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 447.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.21 | 408.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2743.92 | 1308.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 763.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 442.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 875.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.97 | 799.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 381.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5368.10 | 2559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 763.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 442.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 875.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.97 | 799.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 381.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5368.10 | 2559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.32 |
KITCHEN DIRECT AIR | 1.53 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.32 | 3.32 | 3.32 | 3.32 | 3.32 | 3.32 | 1.00 | 1.00 | 3.32 |
PSZ-AC_2:2 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.00 | 1.00 | 1.53 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.32 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.53 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.32 | 3552.90 |
PSZ-AC_2:2_ADDAQ FAN | 1.53 | 1635.93 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.32 | 3.32 | 3.32 | 2.19 | 63701.29 | 115849.61 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.53 | 1.53 | 1.53 | 1.53 | 27860.33 | 79475.48 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.32 | 1.66 | 2.21 | 63701.29 | 31850.65 | 0.793220 | 0.793220 |
PSZ-AC_2:2 COOLING COIL | 1.53 | 0.764419 | 1.02 | 27860.33 | 13930.17 | 0.800970 | 0.800970 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 115849.61 |
PSZ-AC_2:2 HEATING COIL | 79475.48 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 9.518 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 74.446 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.313 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.393 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3538.380 | 9.518 | 12.631 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3538.380 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1298.236 | 9.313 | 172.457 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1298.236 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.8794 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9031 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.28842413E-12 | 0.14163715E-14 | -0.83625437E-13 | 0.83302026E-16 |
34 | 6 | 0.27446597E-07 | 0.24415596E-09 | 0.62976823E-08 | -0.12863247E-12 |
35 | 5 | -0.18387070E-03 | 0.21059431E-05 | -0.94655602E-04 | 0.62291981E-08 |
36 | 4 | 0.28482235 | 0.10320537E-02 | 0.97050522E-01 | -0.32540306E-04 |
37 | 3 | -7.1212123 | 0.32167701E-01 | -2.2958568 | 0.28298028E-01 |
38 | 2 | 40.392481 | 0.11496341 | 15.088345 | -0.32800964 |
39 | 1 | -80.178917 | 0.52112252E-01 | -28.983173 | 1.0708012 |
40 | 0 | 46.824341 | 0.10529732E-02 | 16.295060 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.4731_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6835E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.1850E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5945E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9091E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4112E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.0962E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0758E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5500E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.2622E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.9798E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1093 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 0.1056 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.7603E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.6958E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.6281E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.6443E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0793E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4855E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7367E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3347E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9124E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2611E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6313E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0762E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 37644.64599 | 45173.57519 | 2.76694 | 3.32032 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 7187.23791 | 8624.68549 | 0.31137 | 1.33138 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | -4.30000 | 2.65759E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20428.42658 | 24514.11189 | 1.27403 | 1.52884 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 25.58100 | 8.40579E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -4.30000 | 2.65759E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 48305.35 | 3.32032 | 3.32032 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 70608.54 | 1.33138 | 1.33138 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 23532.10 | 1.52884 | 1.52884 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 64542.73 | 1.21700 | 1.21700 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.32032 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.52884 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.32032 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.32032 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.32032 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.32032 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.32032 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.32032 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.52884 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.52884 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.52884 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.52884 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.52884 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.52884 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.32032 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.52884 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.32032 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.32032 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3552.90439 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.32032 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.32032 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.32032 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.19141 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.32032 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.66016 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.21355 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 63701.29000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31850.64500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79322 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79322 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63701.29000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 115849.61014 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 115849.61014 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.52884 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.52884 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1635.92985 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.52884 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.52884 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.52884 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.52884 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.52884 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76442 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01923 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27860.33000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13930.16500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80097 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80097 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27860.33000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79475.48347 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 79475.48347 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 61294.1 | 11.18 | 11.12 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 26748.2 | 11.23 | 11.18 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | N/A | 2.689 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | N/A | 2.689 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | N/A | 2.689 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.3355823872E-002 | 0.3807318481 | Pass | Pass | 8.0567566367E-002 | 0.1823394896 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1046258198 | 0.5401300878 | Pass | Pass | 2.6506851805E-002 | 9.0753268484E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1912726664 | 0.1642052368 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 796.31 | 115.87 | 2113.11 | 17.52 | 360.56 | 3403.38 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.689 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.689 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.5182 | 371.75 | 3538.38 | LightsWired | LTG_SCH_DINING | 93.86 | 168.00 | 78.03 | 0.0000 | Y | 51.83 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.3127 | 139.41 | 1298.24 | LightsWired | LTG_SCH_KITCHEN | 80.88 | 168.00 | 80.41 | 0.0000 | Y | 19.60 |
Interior Lighting Total | 9.4622 | 511.15 | 4836.62 | 71.42 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.52 | AstronomicalClock | - | 49.50 | 49.50 | 1.95 | |
EXTERIOR_LIGHTS_B | 3124.83 | AstronomicalClock | - | 83.54 | 73.33 | 43.01 | |
Exterior Lighting Total | 3334.35 | 44.96 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63701.29 | 50529.14 | 13172.15 | 0.79 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27860.33 | 22315.29 | 5545.04 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 61294.1 | 11.18 | 11.12 | ||||
PSZ-AC_2:2 COOLING COIL | 26748.2 | 11.23 | 11.18 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 115849.61 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 79475.48 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.55 | 1983.06 | 778.12 | 1.00 | 0.59 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 3.32 | 3552.90 | 1070.05 | 1.00 | 1.25 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.53 | 1635.93 | 1070.05 | 1.00 | 1.36 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 37644.65 | 45173.58 | 121.52 | 2.767 | 3.320 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 23.99 | 0.01015 | 26.31 | 0.00841 | 1.331 | 0.00 |
KITCHEN | 20428.43 | 24514.11 | 175.85 | 1.274 | 1.529 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.01038 | 25.58 | 0.00841 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7187.24 | 8624.69 | 23.20 | 0.311 | 1.331 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00789 | -4.30 | 0.00266 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 21.78 | 0.00174 | -4.30 | 0.00266 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.32 | 3.32 | 1.33 | 1.33 | 3.3203 | 3.3203 | 3.3203 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.53 | 1.53 | 1.22 | 1.22 | 1.5288 | 1.5288 | 1.5288 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 63701.290 | 50529.137 | 3.320320 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 31850.65 | 27099.67 | 2.213547 | 24.96 | 17.41 | 0.00944958 | 11.92 | 11.64 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 60.1468 | 23.99 | 0.01014770 | 53.9344 | 37632.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 115849.610 | 115849.610 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | 115849.61 | 115849.61 | 3.320325 | 10.86 | 8.26 | 0.00578944 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 40.0978 | 21.00 | 0.00788586 | 50.4476 | 7179.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27860.330 | 22315.289 | 1.528840 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 13930.17 | 13213.64 | 1.019227 | 25.66 | 17.12 | 0.00880880 | 11.92 | 11.64 | 0.00850000 | 25.58 | 0.00840579 | 16.75 | 119.4044 | 25.99 | 0.01038163 | 48.9707 | 20428.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 79475.483 | 79475.483 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 79475.48 | 79475.48 | 1.528839 | -3.42 | -4.08 | 0.00247362 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 79.6030 | 22.16 | 0.00175565 | 10.5620 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63701.290 | 50529.137 | 3.320320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4063 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.320325 | 3.95574192 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 31850.65 | 27099.67 | 1.0000 | 2.63715754 | 2.213547 | 24.96 | 17.41 | 0.00944958 | 49147.4 | 11.92 | 11.64 | 0.00850000 | 33425.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31850.65 | 26.40 | 0.00840708 | 17.04 | 1.33137743 | 60.1468 | 23.99 | 0.01014770 | 23.99 | 0.01014770 | 53.9344 | 37632.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 115849.610 | 115849.610 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.320325 | 3.95574192 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | Sensible | 115849.61 | 115849.61 | 1.0000 | 3.95574192 | 3.320325 | 10.86 | 8.26 | 0.00578944 | 25503.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 115849.61 | -4.30 | 0.00265759 | -4.30 | 1.33137743 | 40.0978 | 21.00 | 0.00788586 | 21.00 | 0.00788586 | 50.4476 | 7179.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27860.330 | 22315.289 | 1.528840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2151 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.528839 | 1.82141582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 13930.17 | 13213.64 | 1.0000 | 1.21427812 | 1.019227 | 25.66 | 17.12 | 0.00880880 | 48231.8 | 11.92 | 11.64 | 0.00850000 | 33424.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13930.17 | 25.58 | 0.00840579 | 16.75 | 1.21700195 | 119.4044 | 25.95 | 0.01038163 | 25.99 | 0.01038163 | 48.9707 | 20428.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79475.483 | 79475.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.528839 | 1.82141582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 79475.48 | 79475.48 | 1.0000 | 1.82141582 | 1.528839 | -3.42 | -4.08 | 0.00247362 | 2731.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79475.48 | -4.30 | 0.00265759 | -4.30 | 1.21700195 | 79.6030 | 0.00 | 0.00175565 | 22.16 | 0.00175565 | 10.5620 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.32 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.53 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 1571.33 | 5873.17 | 533.00 |
KITCHEN | 3004.33 | 5737.00 | 1877.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3117.17 | 6948.67 | 1990.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.33 | 0.17 | 0.00 | 0.00 |
KITCHEN | 0.00 | 176.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.33 | 176.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.346 | 0.579 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.694 | 0.019 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.054 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.963 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35629259.11 | 0.00 | 35629259.11 | 4721555.00 | 40350814.11 | 41986318.57 | 1459.67 | 6435.70 | 864.64 | 173.77 |
KITCHEN | 33219456.20 | 0.00 | 33219456.20 | 94951.61 | 33314407.82 | 38379373.44 | 1456.54 | 6413.23 | 890.22 | 652.92 |
Total Facility | 68848715.31 | 0.00 | 68848715.31 | 4816506.62 | 73665221.93 | 80365692.01 | 1459.94 | 6504.08 | 958.46 | 691.95 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3543 | 0.0000 | 1.3543 | 0.1802 | 1.5346 | 1.3314 | 0.00 | 6322.53 | 864.47 |
KITCHEN | 1.2491 | 0.0000 | 1.2491 | 0.0022 | 1.2514 | 1.2170 | 0.00 | 6300.34 | 886.66 |
Total Facility | 2.6035 | 0.0000 | 2.6035 | 0.1825 | 2.7859 | 2.5484 | 0.00 | 6390.72 | 954.84 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50570302.35 | 0.00 | 50570302.35 | 41986318.57 | 1459.40 | 0.00 | 7300.60 | 173.77 |
PSZ-AC_2:2 | 47150608.83 | 0.00 | 47150608.83 | 38379373.44 | 1447.02 | 0.58 | 7312.39 | 652.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9223 | 0.0000 | 1.9223 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.7730 | 0.0000 | 1.7730 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 813.60 | 117.80 | 6429.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 969.20 | 6870.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.1773 | 2.0418 | 1.8900 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 2.0921 | 1.7276 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
Electricity:Building | 548.59 | 4052.25 | 01-JAN-01:10 | 30253.07 | 02-JAN-11:10 |
Electricity:Zone:DINING | 176.99 | 991.88 | 01-JAN-01:10 | 9336.09 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 531.74 | 3643.21 | 01-JAN-01:10 | 27887.91 | 02-JAN-11:10 |
InteriorLights:Electricity | 71.43 | 557.53 | 20-MAY-05:00 | 4035.02 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 51.83 | 395.98 | 20-MAY-05:00 | 3065.69 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 71.43 | 557.53 | 20-MAY-05:00 | 4035.02 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 71.43 | 557.53 | 20-MAY-05:00 | 4035.02 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 51.83 | 395.98 | 20-MAY-05:00 | 3065.69 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 71.43 | 557.53 | 20-MAY-05:00 | 4035.02 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 371.61 | 3060.37 | 01-JAN-01:10 | 21021.20 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.16 | 2489.78 | 01-JAN-01:10 | 17686.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.03 | 1122.20 | 01-JAN-01:10 | 16319.14 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.53 | 1038.02 | 10-JAN-23:30 | 3441.39 | 17-AUG-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 120.65 | 1111.63 | 09-JAN-01:10 | 6469.51 | 17-JUL-18:50 |
LowTempRefrigeration:Refrigeration:Electricity | 15.43 | 0.00 | 01-JAN-11:10 | 1447.41 | 15-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 29.24 | 777.33 | 10-JAN-00:10 | 1076.23 | 22-MAY-13:10 |
ElectricityPurchased:Facility | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
ElectricityPurchased:Plant | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
Cogeneration:ElectricityPurchased | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
General:Cogeneration:ElectricityPurchased | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
ElectricityNet:Plant | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
Cogeneration:ElectricityNet | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
General:Cogeneration:ElectricityNet | 866.41 | 7351.26 | 09-JAN-01:10 | 51247.23 | 22-JUL-11:00 |
Electricity:HVAC | 152.21 | 0.00 | 01-JAN-01:10 | 21147.21 | 22-JUL-18:10 |
Fans:Electricity | 141.28 | 0.00 | 01-JAN-01:10 | 5804.82 | 11-JAN-24:00 |
General:Fans:Electricity | 141.28 | 0.00 | 01-JAN-01:10 | 5804.82 | 11-JAN-24:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 10.93 | 0.00 | 01-JAN-00:10 | 15573.95 | 22-JUL-18:10 |
General:Cooling:Electricity | 10.93 | 0.00 | 01-JAN-00:10 | 15573.95 | 22-JUL-18:10 |
ExteriorLights:Electricity | 44.96 | 0.00 | 01-JAN-08:20 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.96 | 0.00 | 01-JAN-08:20 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.08 | 01-MAY-06:30 |
Water Heater:WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.08 | 01-MAY-06:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 14-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 14-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1206.76 | 2803.57 | 01-JAN-01:10 | 122221.67 | 10-JAN-07:40 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 359.89 | 0.00 | 01-JAN-01:10 | 84014.12 | 11-JAN-24:00 |
Heating:NaturalGas | 359.89 | 0.00 | 01-JAN-01:10 | 84014.12 | 11-JAN-24:00 |
General:Heating:NaturalGas | 359.89 | 0.00 | 01-JAN-01:10 | 84014.12 | 11-JAN-24:00 |
NaturalGas:Plant | 377.09 | 993.32 | 01-JAN-00:10 | 30795.03 | 17-FEB-07:20 |
WaterSystems:NaturalGas | 377.09 | 993.32 | 01-JAN-00:10 | 30795.03 | 17-FEB-07:20 |
Water Heater:WaterSystems:NaturalGas | 377.09 | 993.32 | 01-JAN-00:10 | 30795.03 | 17-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-APR-18:40 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-APR-18:40 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1373.49 | 3208.26 | 11-JAN-01:10 | 127702.08 | 22-JUL-18:10 |
EnergyTransfer:Building | 706.95 | 1604.13 | 11-JAN-01:10 | 47524.96 | 22-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN | 442.43 | 1604.13 | 11-JAN-01:10 | 25675.98 | 02-JUN-04:10 |
Refrigeration:EnergyTransfer | 143.65 | 2714.19 | 10-JAN-23:10 | 7834.84 | 17-AUG-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 71.83 | 1357.09 | 10-JAN-23:10 | 3917.42 | 17-AUG-10:40 |
General:Refrigeration:EnergyTransfer | 71.83 | 1357.09 | 10-JAN-23:10 | 3917.42 | 17-AUG-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 71.83 | 1357.09 | 10-JAN-23:10 | 3917.42 | 17-AUG-10:40 |
EnergyTransfer:Plant | 338.79 | 1604.13 | 11-JAN-01:10 | 19501.08 | 25-JAN-20:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.31 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 56.51 | 1342.00 | 10-JAN-00:10 | 2238.70 | 22-MAY-13:10 |
EnergyTransfer:Zone:DINING | 264.53 | 0.00 | 01-JAN-01:10 | 27779.93 | 22-JUL-18:10 |
Heating:EnergyTransfer | 1.16 | 0.00 | 01-JAN-00:10 | 9390.97 | 15-DEC-05:30 |
Heating:EnergyTransfer:Zone:DINING | 1.16 | 0.00 | 01-JAN-00:10 | 9390.97 | 15-DEC-05:30 |
General:Heating:EnergyTransfer | 1.16 | 0.00 | 01-JAN-00:10 | 9390.97 | 15-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:DINING | 1.16 | 0.00 | 01-JAN-00:10 | 9390.97 | 15-DEC-05:30 |
Cooling:EnergyTransfer | 633.97 | 0.00 | 01-JAN-01:10 | 44822.76 | 22-JUL-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 263.37 | 0.00 | 01-JAN-01:10 | 27779.93 | 22-JUL-18:10 |
General:Cooling:EnergyTransfer | 633.97 | 0.00 | 01-JAN-01:10 | 44822.76 | 22-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 263.37 | 0.00 | 01-JAN-01:10 | 27779.93 | 22-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 36.07 | 27-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 36.07 | 27-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 370.60 | 0.00 | 01-JAN-01:10 | 21831.02 | 02-JUN-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 370.60 | 0.00 | 01-JAN-01:10 | 21831.02 | 02-JUN-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 266.96 | 0.00 | 01-JAN-01:10 | 17232.09 | 15-FEB-07:40 |
PlantLoopHeatingDemand:Plant | 266.96 | 0.00 | 01-JAN-01:10 | 17232.09 | 15-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 266.96 | 0.00 | 01-JAN-01:10 | 17232.09 | 15-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 266.96 | 0.00 | 01-JAN-01:10 | 17232.09 | 15-FEB-07:40 |
EnergyTransfer:HVAC | 327.75 | 0.00 | 01-JAN-01:10 | 67211.30 | 11-JAN-24:00 |
HeatingCoils:EnergyTransfer | 287.91 | 0.00 | 01-JAN-01:10 | 67211.30 | 11-JAN-24:00 |
CoolingCoils:EnergyTransfer | 39.84 | 0.00 | 01-JAN-00:10 | 63317.21 | 22-JUL-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 266.96 | 0.00 | 01-JAN-01:10 | 17232.09 | 15-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 266.96 | 0.00 | 01-JAN-01:10 | 17232.09 | 15-FEB-07:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.158 | -263.365 | 0.000 | 0.000 | 234.713 | 51.829 | 93.867 | 38.897 | 0.000 | 0.074 | 0.002 | 0.000 | -27.928 | 0.000 | -67.254 | -61.989 |
KITCHEN | 0.000 | 0.000 | 0.000 | -370.590 | 0.000 | 0.000 | 6.281 | 19.596 | 297.703 | 0.000 | 0.000 | 0.000 | 48.584 | 0.000 | 0.000 | 0.000 | -1.574 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.623 | 30.700 | 0.000 | 0.000 | 0.000 | -40.324 | -0.001 |
Total Facility | 0.000 | 0.000 | 1.158 | -633.955 | 0.000 | 0.000 | 240.993 | 71.425 | 391.570 | 38.897 | 0.000 | 9.698 | 79.286 | 0.000 | -27.928 | 0.000 | -109.152 | -61.991 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 15-AUG-03:11 | 0.00 | 0.00 | 0.00 | -40787.81 | 0.00 | 0.00 | 0.00 | 510.94 | 901.76 | 0.00 | 0.00 | 0.00 | 40667.44 | 0.00 | -1292.34 | 0.00 | 0.00 | 0.00 |
KITCHEN | 26-SEP-04:01 | 0.00 | 0.00 | 0.00 | -48463.12 | 0.00 | 0.00 | 11.62 | 215.40 | 7253.89 | 0.00 | 0.00 | 0.00 | 40982.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-SEP-04:01 | 0.00 | 0.00 | 0.00 | -70278.50 | 0.00 | 0.00 | 973.70 | 896.65 | 9424.42 | 0.00 | 0.00 | 480.77 | 60133.06 | 0.00 | -1630.09 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 09-APR-04:07 | 0.00 | 0.00 | 43283.53 | 0.00 | 0.00 | 0.00 | 0.00 | 510.94 | 2164.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2065.41 | 0.00 | 0.00 | -43893.30 |
KITCHEN | 27-DEC-05:04 | 0.00 | 0.00 | 360.27 | 0.00 | 0.00 | 0.00 | 21.60 | 215.40 | 7253.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -26.82 | -7824.35 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-APR-04:07 | -11313.77 | 11313.77 | 43283.53 | -11313.77 | 0.00 | 0.00 | 0.00 | 672.49 | 9407.36 | 0.00 | 0.00 | 1354.80 | 0.00 | 0.00 | -2065.41 | 0.00 | 0.00 | -41339.01 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.3203 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.3203 | 0.4010 | 1.0000 | Not calculated | 1.3314 | 0.4010 | ||
PSZ-AC_2:2 | 1.5288 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5288 | 0.1194 | 1.0000 | Not calculated | 0.1826 | 0.1194 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.3203 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.3203 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.4010 | ||
PSZ-AC_2:2 | 1.5288 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5288 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1194 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3203 | 3.3203 | 3.3203 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5288 | 1.5288 | 1.5288 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.3203 | 3.3203 | 3.3203 | 3.3203 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5288 | 1.5288 | 1.5288 | 1.5288 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3203 | 3.3203 | 3.3203 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5288 | 1.5288 | 1.5288 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.3203 | 3.3203 | 3.3203 | 3.3203 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5288 | 1.5288 | 1.5288 | 1.5288 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 359.89 | 84014.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 10.93 | 15573.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 71.43 | 4035.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.96 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.19 | 23313.05 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 141.28 | 5804.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.53 | 4742.08 | 377.09 | 30795.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.43 | 1447.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.24 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 521.84 | 866.41 |
Natural Gas | 469.79 | 1206.76 |
Additional | 0.00 | 0.00 |
Total | 991.63 | 2073.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 139.73 |
Space Heating | 0.00 |
Space Cooling | 21.38 |
Fans (All) | 276.39 |
Service Water Heating | 147.77 |
Receptacle Equipment | 900.54 |
Miscellaneous (All) | 1695.01 |
Subtotal | 1695.01 |
Natural Gas [MJ/m2] | |
Space Heating | 704.07 |
Service Water Heating | 737.72 |
Miscellaneous (All) | 2360.86 |
Subtotal | 2360.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.45 |
Space Heating | 17.36 |
Space Cooling | 0.53 |
Fans (All) | 6.81 |
Service Water Heating | 21.83 |
Receptacle Equipment | 44.86 |
Miscellaneous | 5.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4894. | 8760. |
LTG_SCH_KITCHEN | 4218. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8628.50 | 131.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7595.83 | 510.33 | 402.83 | 251.00 | 0.00 |
Min | 7595.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 510.33 | 402.83 | 251.00 | 0.00 |
Average | 8328.11 | 213.94 | 134.28 | 83.67 | 0.00 |
Sum | 24984.33 | 641.83 | 402.83 | 251.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7725.33 | 1034.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 7679.83 | 713.00 | 236.00 | 111.67 | 19.50 |
Min | 7679.83 | 6.83 | 0.00 | 0.00 | 0.00 |
Max | 8753.17 | 1034.67 | 236.00 | 111.67 | 19.50 |
Average | 8052.78 | 584.83 | 78.67 | 37.22 | 6.50 |
Sum | 24158.33 | 1754.50 | 236.00 | 111.67 | 19.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 822985.33 | 1236.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16310.50 | 2922.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822985.33 | 2922.50 | 0.00 | 0.00 | 0.00 |
Average | 279765.28 | 1386.39 | 0.00 | 0.00 | 0.00 |
Sum | 839295.83 | 4159.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158111E+11 | 39087.69 | 12-JAN-00:01 | -5.8 | -7.4 | 0.120086E+11 | 10756.20 | 18-JAN-12:00 | 13.00 | 11.30 |
February | 0.150527E+11 | 33199.79 | 20-FEB-00:01 | -1.8 | -1.9 | 0.108657E+11 | 10741.44 | 18-FEB-19:00 | -1.8 | -1.9 |
March | 0.176088E+11 | 28990.27 | 14-MAR-23:01 | 1.02 | 0.28 | 0.121449E+11 | 10910.43 | 25-MAR-18:30 | 10.30 | 9.58 |
April | 0.233226E+11 | 28952.00 | 09-APR-04:06 | 1.00 | 0.52 | 0.122974E+11 | 14050.68 | 29-APR-18:19 | 19.33 | 12.05 |
May | 0.250959E+11 | 26864.00 | 01-MAY-04:01 | 4.83 | 4.00 | 0.128294E+11 | 12970.89 | 27-MAY-18:00 | 13.00 | 10.30 |
June | 0.264116E+11 | 24444.92 | 13-JUN-17:05 | 26.48 | 17.38 | 0.135236E+11 | 14050.53 | 24-JUN-18:49 | 15.17 | 11.59 |
July | 0.282665E+11 | 37935.80 | 18-JUL-03:11 | 16.00 | 14.13 | 0.144518E+11 | 14050.90 | 15-JUL-18:19 | 16.00 | 14.13 |
August | 0.285527E+11 | 40794.06 | 15-AUG-03:11 | 13.67 | 10.29 | 0.149697E+11 | 14051.48 | 26-AUG-18:19 | 16.67 | 14.40 |
September | 0.268445E+11 | 25210.38 | 20-SEP-04:01 | 5.17 | 5.17 | 0.136987E+11 | 14050.89 | 09-SEP-18:19 | 5.17 | 5.17 |
October | 0.230930E+11 | 28692.81 | 07-OCT-04:01 | 2.33 | 2.26 | 0.123968E+11 | 12936.07 | 11-OCT-11:30 | 16.50 | 10.26 |
November | 0.182094E+11 | 32000.56 | 29-NOV-00:01 | -1.0 | -1.4 | 0.116394E+11 | 11691.95 | 24-NOV-12:20 | -1.0 | -1.4 |
December | 0.150993E+11 | 34617.27 | 30-DEC-00:01 | -2.8 | -4.3 | 0.119943E+11 | 10741.42 | 30-DEC-19:00 | 0.00 | -0.9 |
Annual Sum or Average | 0.263368E+12 | 0.152820E+12 | ||||||||
Minimum of Months | 0.150527E+11 | 24444.92 | -5.8 | -7.4 | 0.108657E+11 | 10741.42 | -1.8 | -1.9 | ||
Maximum of Months | 0.285527E+11 | 40794.06 | 26.48 | 17.38 | 0.149697E+11 | 14051.48 | 19.33 | 14.40 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307411E+11 | 38653.46 | 10-JAN-05:01 | -4.0 | -4.8 | 0.104000E+11 | 6870.11 | 17-JAN-11:00 | 12.00 | 10.92 |
February | 0.278938E+11 | 36816.85 | 18-FEB-05:01 | -2.7 | -2.7 | 0.938923E+10 | 6855.06 | 22-FEB-11:00 | 10.00 | 8.45 |
March | 0.309711E+11 | 33594.33 | 08-MAR-05:01 | 0.25 | -1.1 | 0.104091E+11 | 6872.41 | 28-MAR-10:00 | 12.00 | 5.80 |
April | 0.302870E+11 | 38445.12 | 21-APR-04:01 | 8.83 | 7.77 | 0.101251E+11 | 6931.45 | 28-APR-10:09 | 17.67 | 11.40 |
May | 0.317331E+11 | 45329.25 | 26-MAY-03:51 | 8.00 | 8.00 | 0.104753E+11 | 6931.57 | 22-MAY-10:00 | 8.00 | 8.00 |
June | 0.307934E+11 | 46662.73 | 02-JUN-04:01 | 8.00 | 7.45 | 0.102010E+11 | 6931.58 | 26-JUN-10:00 | 19.00 | 14.77 |
July | 0.319057E+11 | 45507.25 | 21-JUL-04:01 | 11.00 | 9.86 | 0.105646E+11 | 6931.59 | 18-JUL-10:50 | 11.00 | 9.86 |
August | 0.317897E+11 | 46551.01 | 25-AUG-04:01 | 12.17 | 9.87 | 0.105817E+11 | 6931.59 | 18-AUG-10:50 | 12.17 | 9.87 |
September | 0.309025E+11 | 48465.41 | 26-SEP-04:01 | 9.00 | 7.43 | 0.102055E+11 | 6931.59 | 19-SEP-10:00 | 9.00 | 7.43 |
October | 0.318697E+11 | 31831.28 | 15-OCT-04:01 | 2.17 | 2.17 | 0.104573E+11 | 6931.39 | 11-OCT-10:00 | 2.17 | 2.17 |
November | 0.307804E+11 | 33755.11 | 29-NOV-05:01 | -0.2 | -1.0 | 0.100757E+11 | 6916.63 | 24-NOV-11:00 | -0.2 | -1.0 |
December | 0.309316E+11 | 35456.20 | 27-DEC-05:01 | -1.2 | -1.2 | 0.103942E+11 | 6859.27 | 04-DEC-11:00 | -1.2 | -1.2 |
Annual Sum or Average | 0.370599E+12 | 0.123279E+12 | ||||||||
Minimum of Months | 0.278938E+11 | 31831.28 | -4.0 | -4.8 | 0.938923E+10 | 6855.06 | -1.2 | -1.2 | ||
Maximum of Months | 0.319057E+11 | 48465.41 | 12.17 | 9.87 | 0.105817E+11 | 6931.59 | 19.00 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.92 | 1.45 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 | 5.79 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 | 3.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.23 | 1.84 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.84 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.47 | 8.15 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9.27 | 7.39 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.39 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 | 9.95 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 11.43 | 9.82 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 12.43 | 10.95 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.57 | 5.83 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.83 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 | 4.29 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.29 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258958E+09 | 38693.53 | 05-JAN-05:38 | 3.00 |
February | 0.277867E+09 | 33724.28 | 17-FEB-04:02 | -2.0 |
March | 0.191982E+09 | 39982.66 | 13-MAR-04:02 | 2.18 |
April | 24985617.57 | 43286.59 | 09-APR-04:07 | 1.00 |
May | 9211019.33 | 19193.90 | 05-MAY-04:01 | 5.17 |
June | 2388022.84 | 6293.80 | 12-JUN-04:04 | 8.17 |
July | 750182.62 | 5994.61 | 06-JUL-04:04 | 7.33 |
August | 1169707.12 | 18368.02 | 28-AUG-04:06 | 9.00 |
September | 1856782.38 | 4482.46 | 05-SEP-04:04 | 6.83 |
October | 6202183.65 | 9070.17 | 23-OCT-04:01 | 3.00 |
November | 62751848.67 | 19686.07 | 29-NOV-04:03 | -0.8 |
December | 0.319675E+09 | 43258.19 | 15-DEC-05:22 | 1.00 |
Annual Sum or Average | 0.115780E+10 | |||
Minimum of Months | 750182.62 | 4482.46 | -2.0 | |
Maximum of Months | 0.319675E+09 | 43286.59 | 9.00 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 21640.54 | 360.68 | 27-DEC-05:04 | -1.2 |
Annual Sum or Average | 21640.54 | |||
Minimum of Months | 0.00 | 0.00 | -1.2 | |
Maximum of Months | 21640.54 | 360.68 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.461855E+10 | 3065.69 | 02-JAN-16:30 | 0.106297E+11 | 6993.92 | 01-JAN-11:09 |
February | 0.408155E+10 | 3065.69 | 01-FEB-17:10 | 0.960102E+10 | 6993.92 | 01-FEB-11:09 |
March | 0.445590E+10 | 3065.69 | 01-MAR-17:40 | 0.106297E+11 | 6993.92 | 01-MAR-11:09 |
April | 0.414335E+10 | 3065.69 | 01-APR-18:30 | 0.102868E+11 | 6993.92 | 01-APR-10:09 |
May | 0.420130E+10 | 3065.69 | 01-MAY-19:19 | 0.106297E+11 | 6993.92 | 01-MAY-10:09 |
June | 0.404865E+10 | 3065.69 | 01-JUN-19:30 | 0.102868E+11 | 6993.92 | 01-JUN-10:09 |
July | 0.413038E+10 | 3065.69 | 01-JUL-20:10 | 0.106297E+11 | 6993.92 | 01-JUL-10:09 |
August | 0.429461E+10 | 3065.69 | 01-AUG-19:40 | 0.106297E+11 | 6993.92 | 01-AUG-10:09 |
September | 0.420764E+10 | 3065.69 | 01-SEP-18:40 | 0.102868E+11 | 6993.92 | 01-SEP-10:09 |
October | 0.446742E+10 | 3065.69 | 02-OCT-17:40 | 0.106297E+11 | 6993.92 | 01-OCT-10:09 |
November | 0.446809E+10 | 3065.69 | 01-NOV-16:10 | 0.102868E+11 | 6993.92 | 01-NOV-10:09 |
December | 0.471180E+10 | 3065.69 | 01-DEC-15:20 | 0.106297E+11 | 6993.92 | 01-DEC-11:09 |
Annual Sum or Average | 0.518293E+11 | 0.125156E+12 | ||||
Minimum of Months | 0.404865E+10 | 3065.69 | 0.960102E+10 | 6993.92 | ||
Maximum of Months | 0.471180E+10 | 3065.69 | 0.106297E+11 | 6993.92 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165581E+10 | 969.33 | 02-JAN-10:09 | 0.284656E+11 | 17686.72 | 01-JAN-11:09 |
February | 0.149975E+10 | 969.33 | 01-FEB-10:09 | 0.257108E+11 | 17686.72 | 01-FEB-11:09 |
March | 0.168217E+10 | 969.33 | 01-MAR-10:09 | 0.284657E+11 | 17686.72 | 01-MAR-11:09 |
April | 0.160889E+10 | 969.33 | 01-APR-16:10 | 0.275474E+11 | 17686.72 | 01-APR-10:09 |
May | 0.166899E+10 | 969.33 | 01-MAY-09:09 | 0.284656E+11 | 17686.72 | 01-MAY-10:09 |
June | 0.162595E+10 | 969.33 | 01-JUN-09:09 | 0.275474E+11 | 17686.72 | 01-JUN-10:09 |
July | 0.165212E+10 | 969.33 | 01-JUL-16:10 | 0.284656E+11 | 17686.72 | 01-JUL-10:09 |
August | 0.168217E+10 | 969.33 | 01-AUG-09:09 | 0.284657E+11 | 17686.72 | 01-AUG-10:09 |
September | 0.160928E+10 | 969.33 | 01-SEP-09:09 | 0.275474E+11 | 17686.72 | 01-SEP-10:09 |
October | 0.165561E+10 | 969.33 | 02-OCT-09:09 | 0.284656E+11 | 17686.72 | 01-OCT-10:09 |
November | 0.160288E+10 | 969.33 | 01-NOV-09:09 | 0.275473E+11 | 17686.72 | 01-NOV-10:09 |
December | 0.165232E+10 | 969.33 | 01-DEC-10:09 | 0.284656E+11 | 17686.72 | 01-DEC-11:09 |
Annual Sum or Average | 0.195960E+11 | 0.335159E+12 | ||||
Minimum of Months | 0.149975E+10 | 969.33 | 0.257108E+11 | 17686.72 | ||
Maximum of Months | 0.168217E+10 | 969.33 | 0.284657E+11 | 17686.72 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.461855E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800326E+10 |
February | 0.272721E+11 | 0.408155E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712893E+10 |
March | 0.305458E+11 | 0.445590E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698664E+10 |
April | 0.292871E+11 | 0.414335E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 0.521382E+10 |
May | 0.303219E+11 | 0.420130E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525937E+10 |
June | 0.295292E+11 | 0.404865E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10968783.85 | 0.395365E+10 |
July | 0.300798E+11 | 0.413038E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53631772.56 | 0.344086E+10 |
August | 0.305458E+11 | 0.429461E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9296343.55 | 0.319560E+10 |
September | 0.292871E+11 | 0.420764E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385248E+10 |
October | 0.300980E+11 | 0.446742E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544161E+10 |
November | 0.290996E+11 | 0.446809E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663911E+10 |
December | 0.300798E+11 | 0.471180E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813916E+10 |
Annual Sum or Average | 0.356244E+12 | 0.518293E+11 | 0.125156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 73896919.95 | 0.672545E+11 |
Minimum of Months | 0.272721E+11 | 0.404865E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319560E+10 |
Maximum of Months | 0.305458E+11 | 0.471180E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53631772.56 | 0.813916E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.165581E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74210696.25 |
February | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111742E+09 |
March | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66184469.98 |
April | 0.786997E+09 | 0.160889E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75577480.70 |
May | 0.814802E+09 | 0.166899E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202066E+09 |
June | 0.793501E+09 | 0.162595E+10 | 0.227469E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 14758.14 | 0.166006E+09 |
July | 0.808298E+09 | 0.165212E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 224631.17 | 0.156004E+09 |
August | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 15522.22 | 0.125731E+09 |
September | 0.786997E+09 | 0.160928E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125040E+09 |
October | 0.808786E+09 | 0.165561E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121634E+09 |
November | 0.781956E+09 | 0.160288E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148959E+09 |
December | 0.808298E+09 | 0.165232E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200681E+09 |
Annual Sum or Average | 0.957291E+10 | 0.195960E+11 | 0.276753E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 254911.54 | 0.157384E+10 |
Minimum of Months | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66184469.98 |
Maximum of Months | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 224631.17 | 0.202066E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114661E+10 | 0.131288E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810680E+09 | 0.182479E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853443E+09 | 0.234284E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853289E+09 | 0.520684E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511744E+09 | 0.557856E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447461E+09 | 0.572028E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523282E+09 | 0.590978E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839347E+09 | 0.499082E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972635E+09 | 0.363908E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101910E+10 | 0.202705E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799939E+09 | 0.107893E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845853E+09 | 0.692017E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962339E+10 | 0.403239E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447461E+09 | 0.692017E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114661E+10 | 0.590978E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3065.69 | 02-JAN-16:30 | 6993.92 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 10938.65 | 10-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 3065.69 | 01-FEB-17:10 | 6993.92 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 10289.20 | 18-FEB-19:53 |
March | 30255.31 | 04-MAR-19:10 | 3065.69 | 01-MAR-17:40 | 6993.92 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 8362.14 | 02-MAR-20:55 |
April | 30255.31 | 01-APR-18:10 | 3065.69 | 01-APR-18:30 | 6993.92 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 30-APR-17:12 | 6504.44 | 07-APR-19:53 |
May | 30255.31 | 06-MAY-18:10 | 3065.69 | 01-MAY-19:19 | 6993.92 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 6202.18 | 05-MAY-19:53 |
June | 30255.31 | 03-JUN-18:10 | 3065.69 | 01-JUN-19:30 | 6993.92 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.34 | 13-JUN-17:05 | 5082.50 | 06-JUN-19:53 |
July | 30255.31 | 01-JUL-18:10 | 3065.69 | 01-JUL-20:10 | 6993.92 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.49 | 22-JUL-18:10 | 4714.02 | 01-JUL-18:53 |
August | 30255.31 | 05-AUG-18:10 | 3065.69 | 01-AUG-19:40 | 6993.92 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.93 | 14-AUG-17:13 | 4495.21 | 29-AUG-19:55 |
September | 30255.31 | 02-SEP-18:10 | 3065.69 | 01-SEP-18:40 | 6993.92 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 6454.39 | 30-SEP-18:52 |
October | 30255.31 | 07-OCT-18:10 | 3065.69 | 02-OCT-17:40 | 6993.92 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 6763.68 | 14-OCT-18:53 |
November | 30255.31 | 04-NOV-18:10 | 3065.69 | 01-NOV-16:10 | 6993.92 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9264.18 | 28-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 3065.69 | 01-DEC-15:20 | 6993.92 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 10166.42 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4495.21 | |||||
Maximum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.49 | 10938.65 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 969.33 | 02-JAN-10:09 | 14422.89 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 399.49 | 04-JAN-04:00 |
February | 813.01 | 04-FEB-19:10 | 969.33 | 01-FEB-10:09 | 14422.89 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 401.72 | 15-FEB-03:00 |
March | 813.01 | 04-MAR-19:10 | 969.33 | 01-MAR-10:09 | 14422.89 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 317.62 | 07-MAR-04:40 |
April | 813.01 | 01-APR-18:10 | 969.33 | 01-APR-16:10 | 14422.89 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 338.62 | 23-APR-03:40 |
May | 813.01 | 06-MAY-18:10 | 969.33 | 01-MAY-09:09 | 14422.89 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 547.46 | 05-MAY-03:40 |
June | 813.01 | 03-JUN-18:10 | 969.33 | 01-JUN-09:09 | 14422.89 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 2.97 | 13-JUN-17:00 | 454.92 | 08-JUN-01:50 |
July | 813.01 | 01-JUL-18:10 | 969.33 | 01-JUL-16:10 | 14422.89 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 8.86 | 22-JUL-15:00 | 517.32 | 11-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 969.33 | 01-AUG-09:09 | 14422.89 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 2.50 | 14-AUG-17:42 | 377.27 | 18-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 969.33 | 01-SEP-09:09 | 14422.89 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 498.57 | 06-SEP-03:30 |
October | 813.01 | 07-OCT-18:10 | 969.33 | 02-OCT-09:09 | 14422.89 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 463.76 | 21-OCT-01:00 |
November | 813.01 | 04-NOV-18:10 | 969.33 | 01-NOV-09:09 | 14422.89 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 648.97 | 25-NOV-04:50 |
December | 813.01 | 02-DEC-19:10 | 969.33 | 01-DEC-10:09 | 14422.89 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 650.56 | 06-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 317.62 | ||||||
Maximum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 8.86 | 650.56 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1770.22 | 21-JAN-00:12 | 4370.48 | 15-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.31 | 17-FEB-23:10 | 5654.27 | 27-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.67 | 25-MAR-07:32 | 5774.71 | 25-MAR-12:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1988.35 | 20-APR-06:22 | 8717.43 | 26-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1766.02 | 03-MAY-05:55 | 8839.54 | 20-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1524.40 | 12-JUN-05:13 | 8752.98 | 09-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1936.63 | 21-JUL-05:53 | 8044.77 | 12-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1918.81 | 20-AUG-06:32 | 7465.39 | 02-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2112.07 | 23-SEP-05:55 | 6708.88 | 09-SEP-12:50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2038.98 | 07-OCT-07:32 | 5691.11 | 04-OCT-12:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1892.22 | 11-NOV-00:55 | 3981.78 | 05-NOV-13:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.71 | 04-DEC-08:43 | 3236.26 | 18-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1524.40 | 3236.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2112.07 | 8839.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39087.69 | 12-JAN-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.75 |
February | 33199.79 | 20-FEB-00:01 | 16808.50 | 6812.44 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.76 |
March | 28990.27 | 14-MAR-23:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28952.00 | 09-APR-04:06 | 0.00 | 5109.42 | 28856.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26864.00 | 01-MAY-04:01 | 16808.50 | 6812.44 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.04 |
June | 24444.92 | 13-JUN-17:05 | 53787.21 | 4475.90 | 11576.14 | 0.00 | 0.00 | 0.00 | 0.00 | 945.34 | 0.00 |
July | 37935.80 | 18-JUL-03:11 | 0.00 | 5109.42 | 12023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 |
August | 40794.06 | 15-AUG-03:11 | 0.00 | 5109.42 | 12023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25210.38 | 20-SEP-04:01 | 16808.50 | 6812.44 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 |
October | 28692.81 | 07-OCT-04:01 | 0.00 | 5109.42 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
November | 32000.56 | 29-NOV-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.41 |
December | 34617.27 | 30-DEC-00:01 | 16808.50 | 6812.44 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24444.92 | 0.00 | 4475.90 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40794.06 | 53787.21 | 6812.44 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 945.34 | 509.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38653.46 | 10-JAN-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 52.31 |
February | 36816.85 | 18-FEB-05:01 | 0.00 | 1615.53 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 |
March | 33594.33 | 08-MAR-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 |
April | 38445.12 | 21-APR-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45329.25 | 26-MAY-03:51 | 0.00 | 1292.42 | 28895.80 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 208.69 |
June | 46662.73 | 02-JUN-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 69.89 |
July | 45507.25 | 21-JUL-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 |
August | 46551.01 | 25-AUG-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48465.41 | 26-SEP-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31831.28 | 15-OCT-04:01 | 0.00 | 1615.53 | 67541.24 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33755.11 | 29-NOV-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 78.48 |
December | 35456.20 | 27-DEC-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31831.28 | 0.00 | 1292.42 | 28895.80 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48465.41 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 208.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.99 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.29 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.59 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.64 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 805.23 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.61 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.27 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.00 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.12 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.53 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.97 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.740020E+11 | 40328.22 | 10-JAN-11:09 | 0.141492E+12 | 122221.67 | 10-JAN-07:40 |
February | 0.662408E+11 | 40205.16 | 13-FEB-11:09 | 0.124573E+12 | 115772.62 | 17-FEB-07:19 |
March | 0.726865E+11 | 40196.30 | 15-MAR-10:09 | 0.123541E+12 | 93852.34 | 08-MAR-07:40 |
April | 0.699225E+11 | 42131.46 | 30-APR-16:40 | 0.935477E+11 | 86294.12 | 08-APR-05:49 |
May | 0.717458E+11 | 44953.96 | 23-MAY-10:00 | 0.887930E+11 | 76285.98 | 06-MAY-05:19 |
June | 0.707634E+11 | 48142.27 | 13-JUN-17:19 | 0.732903E+11 | 55968.11 | 08-JUN-05:19 |
July | 0.745873E+11 | 51247.23 | 22-JUL-10:00 | 0.723541E+11 | 50109.05 | 05-JUL-06:19 |
August | 0.757154E+11 | 47584.23 | 14-AUG-10:50 | 0.716000E+11 | 45659.41 | 03-AUG-18:19 |
September | 0.720050E+11 | 45566.06 | 13-SEP-10:00 | 0.723846E+11 | 58956.03 | 21-SEP-06:30 |
October | 0.731540E+11 | 40045.82 | 17-OCT-10:09 | 0.922235E+11 | 76848.68 | 23-OCT-06:30 |
November | 0.713757E+11 | 40126.10 | 29-NOV-11:09 | 0.111544E+12 | 101379.71 | 29-NOV-07:19 |
December | 0.742117E+11 | 40315.92 | 16-DEC-11:20 | 0.141419E+12 | 103977.79 | 27-DEC-07:40 |
Annual Sum or Average | 0.866410E+12 | 0.120676E+13 | ||||
Minimum of Months | 0.662408E+11 | 40045.82 | 0.716000E+11 | 45659.41 | ||
Maximum of Months | 0.757154E+11 | 51247.23 | 0.141492E+12 | 122221.67 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.627435E+10 | 0.507573E+10 | 0.390952E+11 | 0.00 | 0.120956E+11 | 37879553.69 | 0.00 | 2609868.37 | 0.00 | 0.00 | 0.00 | 0.639715E+10 | 0.00 |
February | 0.558130E+10 | 0.412536E+10 | 0.353119E+11 | 0.00 | 0.108687E+11 | 34213790.43 | 0.00 | 1133664.67 | 0.00 | 0.00 | 0.00 | 0.579017E+10 | 0.00 |
March | 0.613807E+10 | 0.393739E+10 | 0.390954E+11 | 0.00 | 0.119593E+11 | 37879553.69 | 0.00 | 2437739.07 | 0.00 | 0.00 | 0.00 | 0.646536E+10 | 0.00 |
April | 0.575224E+10 | 0.317379E+10 | 0.378342E+11 | 0.00 | 0.115108E+11 | 36657632.61 | 0.00 | 0.395023E+09 | 0.00 | 0.00 | 0.00 | 0.620570E+10 | 0.00 |
May | 0.587029E+10 | 0.277125E+10 | 0.390953E+11 | 0.00 | 0.119020E+11 | 37879553.69 | 0.00 | 0.402263E+09 | 0.00 | 0.00 | 0.00 | 0.642686E+10 | 0.00 |
June | 0.567460E+10 | 0.242638E+10 | 0.378342E+11 | 0.00 | 0.116121E+11 | 36657632.61 | 0.00 | 0.167957E+10 | 0.00 | 0.00 | 0.00 | 0.624318E+10 | 0.00 |
July | 0.578251E+10 | 0.260621E+10 | 0.390952E+11 | 0.00 | 0.120152E+11 | 37879553.69 | 0.00 | 0.318028E+10 | 0.00 | 0.00 | 0.00 | 0.637652E+10 | 0.00 |
August | 0.597678E+10 | 0.303455E+10 | 0.390954E+11 | 0.00 | 0.120106E+11 | 37879553.69 | 0.00 | 0.356845E+10 | 0.00 | 0.00 | 0.00 | 0.645372E+10 | 0.00 |
September | 0.581692E+10 | 0.353390E+10 | 0.378342E+11 | 0.00 | 0.116358E+11 | 36657632.61 | 0.00 | 0.168514E+10 | 0.00 | 0.00 | 0.00 | 0.620094E+10 | 0.00 |
October | 0.612304E+10 | 0.430550E+10 | 0.390952E+11 | 0.00 | 0.119820E+11 | 37879553.69 | 0.00 | 8553286.25 | 0.00 | 0.00 | 0.00 | 0.639131E+10 | 0.00 |
November | 0.607098E+10 | 0.473827E+10 | 0.378341E+11 | 0.00 | 0.115934E+11 | 36657632.61 | 0.00 | 2942119.97 | 0.00 | 0.00 | 0.00 | 0.619025E+10 | 0.00 |
December | 0.636412E+10 | 0.522978E+10 | 0.390952E+11 | 0.00 | 0.120901E+11 | 37879553.69 | 0.00 | 2040595.37 | 0.00 | 0.00 | 0.00 | 0.638968E+10 | 0.00 |
Annual Sum or Average | 0.714252E+11 | 0.449581E+11 | 0.460316E+12 | 0.00 | 0.141276E+12 | 0.446001E+09 | 0.00 | 0.109305E+11 | 0.00 | 0.00 | 0.00 | 0.755309E+11 | 0.00 |
Minimum of Months | 0.558130E+10 | 0.242638E+10 | 0.353119E+11 | 0.00 | 0.108687E+11 | 34213790.43 | 0.00 | 1133664.67 | 0.00 | 0.00 | 0.00 | 0.579017E+10 | 0.00 |
Maximum of Months | 0.636412E+10 | 0.522978E+10 | 0.390954E+11 | 0.00 | 0.120956E+11 | 37879553.69 | 0.00 | 0.356845E+10 | 0.00 | 0.00 | 0.00 | 0.646536E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.682607E+11 | 0.00 | 0.333312E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.581843E+11 | 0.00 | 0.303501E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.499866E+11 | 0.00 | 0.336550E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.231777E+11 | 0.00 | 0.317574E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.167915E+11 | 0.00 | 0.321018E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.430586E+10 | 0.00 | 0.303718E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.197710E+10 | 0.00 | 0.304773E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.112179E+10 | 0.00 | 0.305785E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.414961E+10 | 0.00 | 0.296223E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.211634E+11 | 0.00 | 0.311604E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.419854E+11 | 0.00 | 0.309458E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.687852E+11 | 0.00 | 0.327341E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.359889E+12 | 0.00 | 0.377086E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.112179E+10 | 0.00 | 0.296223E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.687852E+11 | 0.00 | 0.336550E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4035.02 | 02-JAN-16:30 | 3334.35 | 01-JAN-00:10 | 24680.63 | 01-JAN-11:09 | 0.00 | 5804.82 | 11-JAN-23:00 | 17.86 | 14-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4035.02 | 01-FEB-17:10 | 3334.35 | 01-FEB-00:10 | 24680.63 | 01-FEB-11:09 | 0.00 | 5764.20 | 17-FEB-06:00 | 17.86 | 03-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 4035.02 | 01-MAR-17:40 | 3334.35 | 01-MAR-00:10 | 24680.63 | 01-MAR-11:09 | 0.00 | 5654.92 | 08-MAR-06:00 | 17.86 | 02-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 4035.02 | 01-APR-18:30 | 3334.35 | 01-APR-05:10 | 24680.63 | 01-APR-10:09 | 0.00 | 5628.47 | 08-APR-05:10 | 17.86 | 16-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 4035.02 | 01-MAY-19:19 | 3334.35 | 01-MAY-19:19 | 24680.63 | 01-MAY-10:09 | 0.00 | 5559.99 | 06-MAY-04:00 | 17.86 | 04-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 4035.02 | 01-JUN-19:30 | 3334.35 | 01-JUN-19:00 | 24680.63 | 01-JUN-10:09 | 0.00 | 5402.17 | 08-JUN-04:19 | 17.86 | 07-JUN-12:39 | 0.00 | 01-JUN-00:10 |
July | 4035.02 | 01-JUL-20:10 | 3334.35 | 01-JUL-20:19 | 24680.63 | 01-JUL-10:09 | 0.00 | 5573.26 | 22-JUL-18:10 | 17.86 | 13-JUL-12:20 | 0.00 | 01-JUL-00:10 |
August | 4035.02 | 01-AUG-19:40 | 3334.35 | 01-AUG-19:49 | 24680.63 | 01-AUG-10:09 | 0.00 | 5251.75 | 24-AUG-05:00 | 17.86 | 15-AUG-09:50 | 0.00 | 01-AUG-00:10 |
September | 4035.02 | 01-SEP-18:40 | 3334.35 | 01-SEP-05:10 | 24680.63 | 01-SEP-10:09 | 0.00 | 5392.71 | 21-SEP-05:00 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 4035.02 | 02-OCT-17:40 | 3334.35 | 01-OCT-05:10 | 24680.63 | 01-OCT-10:09 | 0.00 | 5527.72 | 23-OCT-04:10 | 17.86 | 22-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 4035.02 | 01-NOV-16:10 | 3334.35 | 01-NOV-05:10 | 24680.63 | 01-NOV-10:09 | 0.00 | 5657.25 | 29-NOV-06:10 | 17.86 | 03-NOV-23:10 | 0.00 | 01-NOV-00:10 |
December | 4035.02 | 01-DEC-15:20 | 3334.35 | 01-DEC-00:10 | 24680.63 | 01-DEC-11:09 | 0.00 | 5711.94 | 29-DEC-23:00 | 17.86 | 02-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 5251.75 | 17.86 | 0.00 | ||||||
Maximum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 5804.82 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 346.21 | 17-JAN-04:19 | 0.00 | 0.00 | 0.00 | 4741.00 | 11-JAN-19:19 | 0.00 |
February | 310.07 | 07-FEB-04:19 | 0.00 | 0.00 | 0.00 | 4741.95 | 24-FEB-19:19 | 0.00 |
March | 310.29 | 17-MAR-03:20 | 0.00 | 0.00 | 0.00 | 4741.63 | 27-MAR-06:49 | 0.00 |
April | 8430.15 | 30-APR-18:10 | 0.00 | 0.00 | 0.00 | 4741.93 | 19-APR-06:49 | 0.00 |
May | 7284.48 | 22-MAY-15:09 | 0.00 | 0.00 | 0.00 | 4742.08 | 01-MAY-06:30 | 0.00 |
June | 12763.18 | 13-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4741.54 | 01-JUN-06:10 | 0.00 |
July | 15573.95 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 | 4740.25 | 05-JUL-06:49 | 0.00 |
August | 11954.58 | 14-AUG-17:19 | 0.00 | 0.00 | 0.00 | 4739.77 | 24-AUG-06:49 | 0.00 |
September | 9506.22 | 11-SEP-17:19 | 0.00 | 0.00 | 0.00 | 4741.60 | 08-SEP-06:10 | 0.00 |
October | 876.97 | 07-OCT-15:09 | 0.00 | 0.00 | 0.00 | 4741.24 | 23-OCT-06:49 | 0.00 |
November | 264.61 | 21-NOV-04:19 | 0.00 | 0.00 | 0.00 | 4741.69 | 10-NOV-19:30 | 0.00 |
December | 307.99 | 22-DEC-04:19 | 0.00 | 0.00 | 0.00 | 4741.88 | 18-DEC-19:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 264.61 | 0.00 | 0.00 | 0.00 | 4739.77 | 0.00 | ||
Maximum of Months | 15573.95 | 0.00 | 0.00 | 0.00 | 4742.08 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 40328.22 | 10-JAN-11:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5568.92 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 40205.16 | 13-FEB-11:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5366.19 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 40196.30 | 15-MAR-10:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5458.03 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 42131.46 | 30-APR-16:40 | 2138.17 | 22268.94 | 0.00 | 0.00 | 5040.16 | 17.86 | 0.00 | 7579.06 | 0.00 |
May | 44953.96 | 23-MAY-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5040.16 | 17.86 | 0.00 | 5467.02 | 0.00 |
June | 48142.27 | 13-JUN-17:19 | 3207.28 | 20661.14 | 0.00 | 0.00 | 5177.78 | 17.86 | 0.00 | 12641.89 | 0.00 |
July | 51247.23 | 22-JUL-10:00 | 2850.91 | 24680.63 | 0.00 | 0.00 | 5040.16 | 17.86 | 0.00 | 11795.52 | 0.00 |
August | 47584.23 | 14-AUG-10:50 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5040.16 | 17.86 | 0.00 | 8099.88 | 0.00 |
September | 45566.06 | 13-SEP-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5040.16 | 17.86 | 0.00 | 6065.24 | 0.00 |
October | 40045.82 | 17-OCT-10:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5154.71 | 17.86 | 0.00 | 0.00 | 0.00 |
November | 40126.10 | 29-NOV-11:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5417.22 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 40315.92 | 16-DEC-11:20 | 3096.17 | 24680.63 | 0.00 | 0.00 | 5248.49 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 40045.82 | 2138.17 | 20661.14 | 0.00 | 0.00 | 5040.16 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51247.23 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5568.92 | 17.86 | 0.00 | 12641.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 84014.12 | 11-JAN-23:00 | 0.00 | 30719.08 | 31-JAN-07:19 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 76424.88 | 17-FEB-06:00 | 0.00 | 30795.03 | 17-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 63967.54 | 08-MAR-06:00 | 0.00 | 30717.89 | 01-MAR-19:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 59946.46 | 08-APR-05:10 | 0.00 | 30061.98 | 04-APR-06:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 51760.71 | 06-MAY-04:00 | 0.00 | 29093.71 | 01-MAY-06:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 31823.86 | 08-JUN-04:00 | 0.00 | 27687.91 | 01-JUN-06:30 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 25625.02 | 05-JUL-04:00 | 0.00 | 26485.91 | 05-JUL-06:19 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 14373.57 | 24-AUG-05:00 | 0.00 | 25821.34 | 30-AUG-06:40 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 30915.29 | 21-SEP-05:00 | 0.00 | 26532.40 | 28-SEP-06:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 46428.25 | 23-OCT-04:00 | 0.00 | 27817.64 | 31-OCT-06:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 65211.30 | 28-NOV-23:30 | 0.00 | 29062.19 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 74489.71 | 29-DEC-23:30 | 0.00 | 30090.81 | 29-DEC-19:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 14373.57 | 0.00 | 25821.34 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 84014.12 | 0.00 | 30795.03 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.00 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 0.33 | 20.42 | 0.00 | 20.42 | 0.17 | 21.80 | 0.00 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.43 | 0.00 | 20.43 | 0.17 | 24.57 | 0.00 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.85 | 0.00 | 26.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.83 | 0.00 | 26.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.84 | 0.00 | 26.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.08 | 0.00 | 27.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.17 | 0.00 | 27.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.58 | 0.00 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 27.86 | 0.00 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 28.01 | 0.00 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 27.67 | 0.00 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.04 | 0.00 | 27.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.96 | 0.00 | 26.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.82 | 0.00 | 26.82 |
Annual Sum or Average | 0.00 | 0.00 | 176.50 | 27.51 | 0.00 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.82 | 0.00 | 26.82 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 28.01 | 0.00 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.77 | 109.50 | 20.61 | 109.50 | 20.49 |
February | 551.00 | 20.76 | 73.67 | 20.57 | 73.67 | 20.43 |
March | 612.00 | 20.78 | 89.17 | 20.61 | 89.17 | 20.48 |
April | 539.00 | 21.05 | 65.17 | 21.04 | 33.83 | 20.89 |
May | 539.00 | 21.06 | 72.00 | 21.15 | 23.83 | 21.03 |
June | 393.00 | 21.49 | 153.33 | 22.12 | 6.83 | 22.09 |
July | 281.67 | 21.61 | 280.50 | 22.75 | 2.00 | 22.74 |
August | 216.33 | 21.72 | 351.17 | 23.10 | 3.50 | 23.11 |
September | 334.67 | 21.51 | 189.50 | 22.35 | 3.33 | 22.33 |
October | 596.50 | 21.06 | 26.67 | 20.92 | 26.67 | 20.78 |
November | 591.00 | 20.82 | 52.33 | 20.66 | 52.33 | 20.52 |
December | 609.00 | 20.76 | 108.33 | 20.59 | 108.33 | 20.47 |
Annual Sum or Average | 5873.17 | 21.02 | 1571.33 | 21.30 | 533.00 | 21.16 |
Minimum of Months | 216.33 | 20.76 | 26.67 | 20.57 | 2.00 | 20.43 |
Maximum of Months | 612.00 | 21.72 | 351.17 | 23.10 | 109.50 | 23.11 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 609.17 | 19.30 | 166.50 | 19.24 | 166.50 | 19.20 |
February | 551.00 | 19.13 | 148.00 | 19.10 | 148.00 | 19.08 |
March | 604.67 | 19.45 | 146.00 | 19.37 | 145.50 | 19.31 |
April | 467.50 | 20.52 | 146.67 | 21.13 | 78.17 | 21.25 |
May | 446.50 | 20.81 | 152.17 | 21.69 | 56.50 | 21.95 |
June | 311.00 | 23.24 | 399.83 | 24.08 | 154.67 | 24.39 |
July | 379.50 | 24.88 | 506.50 | 25.02 | 303.00 | 25.24 |
August | 417.17 | 25.34 | 526.50 | 25.33 | 364.67 | 25.50 |
September | 350.50 | 23.57 | 410.50 | 24.34 | 199.83 | 24.66 |
October | 422.00 | 20.10 | 144.33 | 20.95 | 7.50 | 20.94 |
November | 569.00 | 19.55 | 84.17 | 19.50 | 80.33 | 19.45 |
December | 609.00 | 19.12 | 173.17 | 19.09 | 173.17 | 19.08 |
Annual Sum or Average | 5737.00 | 20.86 | 3004.33 | 21.74 | 1877.83 | 21.97 |
Minimum of Months | 311.00 | 19.12 | 84.17 | 19.09 | 7.50 | 19.08 |
Maximum of Months | 609.17 | 25.34 | 526.50 | 25.33 | 364.67 | 25.50 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.77120 | 37.45076 | -0.4525 | 10.13886 |
February | 551.00000 | 20.75880 | 38.62942 | -0.4389 | 9.87581 |
March | 612.00000 | 20.77632 | 38.62352 | -0.4352 | 9.74526 |
April | 590.00000 | 21.29488 | 38.95697 | -0.2302 | 8.09299 |
May | 611.00000 | 21.37803 | 45.58917 | -1.2726 | 40.81505 |
June | 592.00000 | 22.24354 | 52.96860 | -0.8996 | 25.64252 |
July | 609.00000 | 22.81452 | 53.22066 | -0.6861 | 18.60513 |
August | 612.00000 | 23.11220 | 52.51544 | -0.5858 | 15.24940 |
September | 590.00000 | 22.48679 | 50.60723 | -0.8192 | 22.89771 |
October | 610.00000 | 21.12135 | 47.98900 | -0.2327 | 7.20476 |
November | 591.00000 | 20.82203 | 42.88051 | -0.3784 | 8.68112 |
December | 609.00000 | 20.75865 | 36.69494 | -0.4703 | 10.40029 |
Annual Sum or Average | 7187.00000 | 21.53271 | 44.71078 | -0.5763 | 15.65544 |
Minimum of Months | 551.00000 | 20.75865 | 36.69494 | -1.2726 | 7.20476 |
Maximum of Months | 612.00000 | 23.11220 | 53.22066 | -0.2302 | 40.81505 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.30780 | 43.77495 | -0.4799 | 10.75613 |
February | 551.00000 | 19.12666 | 45.95917 | -0.5095 | 10.86146 |
March | 612.00000 | 19.48726 | 44.76933 | -0.4262 | 9.95796 |
April | 590.00000 | 21.12818 | 43.24361 | -0.0295 | 10.24709 |
May | 611.00000 | 21.49807 | 48.56996 | -0.9132 | 31.33244 |
June | 592.00000 | 23.50772 | 51.67292 | -0.2120 | 15.32597 |
July | 609.00000 | 24.45046 | 50.75174 | 0.10816 | 13.09123 |
August | 612.00000 | 24.80328 | 49.76611 | 0.21543 | 12.29049 |
September | 590.00000 | 23.73119 | 49.40056 | -0.1495 | 15.53460 |
October | 610.00000 | 21.08908 | 50.65048 | 0.01224 | 8.59003 |
November | 591.00000 | 19.65467 | 48.51463 | -0.3485 | 8.95653 |
December | 609.00000 | 19.11809 | 43.34460 | -0.5236 | 11.11201 |
Annual Sum or Average | 7187.00000 | 21.42129 | 47.54170 | -0.2704 | 13.19928 |
Minimum of Months | 551.00000 | 19.11809 | 43.24361 | -0.9132 | 8.59003 |
Maximum of Months | 612.00000 | 24.80328 | 51.67292 | 0.21543 | 31.33244 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.948519E+09 | 0.271998E+09 | 33.10 | 0.892914E+09 | 55604441.33 | 0.00 | 0.70 | 30-APR-18:03 | 0.00 | 01-APR-00:01 | 20034.40 | 30-APR-18:03 | 20034.40 | 30-APR-18:03 | 1589.16 | 30-APR-19:40 | 5334.57 | 30-APR-18:03 | 0.00 | 01-APR-00:01 |
May | 0.992708E+09 | 0.283559E+09 | 35.02 | 0.779235E+09 | 0.213474E+09 | 0.00 | 0.64 | 22-MAY-12:53 | 0.00 | 01-MAY-00:01 | 18038.97 | 22-MAY-12:53 | 15313.24 | 22-MAY-12:57 | 4945.61 | 23-MAY-12:00 | 4880.72 | 22-MAY-12:53 | 0.00 | 01-MAY-00:01 |
June | 0.411545E+10 | 0.111529E+10 | 96.37 | 0.316510E+10 | 0.950356E+09 | 0.00 | 1.00 | 12-JUN-17:27 | 0.00 | 01-JUN-00:01 | 34334.65 | 13-JUN-17:10 | 29989.54 | 13-JUN-17:05 | 14294.05 | 25-JUN-18:00 | 8318.37 | 13-JUN-17:10 | 0.00 | 01-JUN-00:01 |
July | 0.779587E+10 | 0.215760E+10 | 211.39 | 0.613458E+10 | 0.166128E+10 | 0.00 | 1.00 | 18-JUL-01:51 | 0.00 | 01-JUL-00:01 | 62844.34 | 18-JUL-03:11 | 39091.16 | 22-JUL-18:05 | 24053.31 | 18-JUL-03:11 | 15335.70 | 18-JUL-03:11 | 0.00 | 01-JUL-00:01 |
August | 0.886260E+10 | 0.252001E+10 | 282.81 | 0.665339E+10 | 0.220921E+10 | 0.00 | 1.00 | 15-AUG-03:11 | 0.00 | 01-AUG-00:01 | 31386.13 | 15-AUG-03:11 | 30100.51 | 14-AUG-17:07 | 7827.04 | 18-AUG-12:00 | 7665.02 | 15-AUG-03:11 | 0.00 | 01-AUG-00:01 |
September | 0.417031E+10 | 0.118136E+10 | 129.02 | 0.322574E+10 | 0.944573E+09 | 0.00 | 0.85 | 11-SEP-17:10 | 0.00 | 01-SEP-00:01 | 25607.87 | 11-SEP-17:10 | 20457.67 | 11-SEP-17:03 | 6804.37 | 12-SEP-13:00 | 6529.14 | 11-SEP-17:10 | 0.00 | 01-SEP-00:01 |
October | 9631997.49 | 2999121.48 | 1.97 | 9580281.13 | 51716.36 | 0.00 | 0.10 | 07-OCT-15:10 | 0.00 | 01-OCT-00:01 | 2494.86 | 07-OCT-15:10 | 2494.86 | 07-OCT-15:10 | 138.84 | 11-OCT-11:10 | 772.03 | 07-OCT-15:10 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.268951E+11 | 0.753282E+10 | 789.69 | 0.208605E+11 | 0.603455E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.886260E+10 | 0.252001E+10 | 282.81 | 0.665339E+10 | 0.220921E+10 | 0.00 | 1.00 | 0.00 | 62844.34 | 39091.16 | 24053.31 | 15335.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 8683475.07 | 2609868.37 | 2.99 | 5336793.19 | 3346681.87 | 0.00 | 0.25 | 27-JAN-04:08 | 0.00 | 01-JAN-00:01 | 2799.23 | 27-JAN-04:08 | 1745.45 | 27-JAN-04:08 | 1231.97 | 17-JAN-04:08 | 816.30 | 27-JAN-04:08 | 0.00 | 01-JAN-00:01 |
February | 3810907.67 | 1133664.67 | 1.11 | 2208558.84 | 1602348.83 | 0.00 | 0.24 | 21-FEB-04:10 | 0.00 | 01-FEB-00:01 | 2716.25 | 21-FEB-04:10 | 1706.81 | 21-FEB-04:10 | 1106.16 | 07-FEB-04:08 | 793.43 | 21-FEB-04:10 | 0.00 | 01-FEB-00:01 |
March | 8123112.25 | 2437739.07 | 3.29 | 5222132.52 | 2900979.72 | 0.00 | 0.26 | 24-MAR-03:08 | 0.00 | 01-MAR-00:01 | 2978.80 | 24-MAR-03:08 | 1917.09 | 24-MAR-03:08 | 1061.71 | 24-MAR-03:08 | 865.53 | 24-MAR-03:08 | 0.00 | 01-MAR-00:01 |
April | 0.464723E+09 | 0.123025E+09 | 31.75 | 0.456898E+09 | 7825027.32 | 0.00 | 1.00 | 21-APR-04:01 | 0.00 | 01-APR-00:01 | 20169.64 | 21-APR-04:01 | 13437.22 | 21-APR-04:01 | 6732.42 | 21-APR-04:01 | 4824.92 | 21-APR-04:01 | 0.00 | 01-APR-00:01 |
May | 0.434989E+09 | 0.118703E+09 | 32.84 | 0.365968E+09 | 69021158.96 | 0.00 | 1.00 | 12-MAY-04:01 | 0.00 | 01-MAY-00:01 | 27485.53 | 23-MAY-03:21 | 16000.27 | 23-MAY-04:01 | 13373.53 | 23-MAY-03:21 | 6589.63 | 23-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.223634E+10 | 0.564283E+09 | 81.01 | 0.187248E+10 | 0.363859E+09 | 0.00 | 1.00 | 02-JUN-04:01 | 0.00 | 01-JUN-00:01 | 27485.53 | 02-JUN-04:01 | 19756.76 | 13-JUN-03:21 | 15924.44 | 27-JUN-03:21 | 6589.63 | 02-JUN-04:01 | 0.00 | 01-JUN-00:01 |
July | 0.396865E+10 | 0.102268E+10 | 166.82 | 0.340062E+10 | 0.568030E+09 | 0.00 | 1.00 | 07-JUL-03:21 | 0.00 | 01-JUL-00:01 | 27485.53 | 18-JUL-03:21 | 24279.90 | 22-JUL-18:00 | 15536.10 | 24-JUL-04:01 | 6589.63 | 07-JUL-03:21 | 0.00 | 01-JUL-00:01 |
August | 0.390619E+10 | 0.104845E+10 | 230.55 | 0.314230E+10 | 0.763887E+09 | 0.00 | 1.00 | 01-AUG-03:31 | 0.00 | 01-AUG-00:01 | 27485.53 | 15-AUG-04:01 | 19136.93 | 22-AUG-04:01 | 14791.63 | 17-AUG-04:01 | 6589.63 | 01-AUG-03:31 | 0.00 | 01-AUG-00:01 |
September | 0.187376E+10 | 0.503779E+09 | 102.33 | 0.156077E+10 | 0.312994E+09 | 0.00 | 1.00 | 01-SEP-03:21 | 0.00 | 01-SEP-00:01 | 27485.53 | 12-SEP-04:01 | 19361.05 | 26-SEP-04:01 | 15353.84 | 16-SEP-04:01 | 6589.63 | 01-SEP-03:21 | 0.00 | 01-SEP-00:01 |
October | 18485627.78 | 5554164.77 | 9.27 | 10701660.28 | 7783967.50 | 0.00 | 0.71 | 27-OCT-04:01 | 0.00 | 01-OCT-00:01 | 9040.28 | 27-OCT-04:01 | 5674.99 | 27-OCT-04:01 | 3365.29 | 27-OCT-04:01 | 2341.19 | 27-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 9737117.67 | 2942119.97 | 4.74 | 5895308.80 | 3841808.88 | 0.00 | 0.20 | 03-NOV-03:05 | 0.00 | 01-NOV-00:01 | 2292.63 | 03-NOV-03:05 | 1511.07 | 03-NOV-03:05 | 1079.86 | 24-NOV-04:28 | 675.48 | 03-NOV-03:05 | 0.00 | 01-NOV-00:01 |
December | 6798245.88 | 2040595.37 | 2.04 | 4333946.70 | 2464299.18 | 0.00 | 0.30 | 05-DEC-04:08 | 0.00 | 01-DEC-00:01 | 3409.94 | 05-DEC-04:08 | 1974.09 | 05-DEC-04:08 | 1435.85 | 05-DEC-04:08 | 982.28 | 05-DEC-04:08 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.129403E+11 | 0.339763E+10 | 668.74 | 0.108327E+11 | 0.210756E+10 | 0.00 | ||||||||||||||
Minimum of Months | 3810907.67 | 1133664.67 | 1.11 | 2208558.84 | 1602348.83 | 0.00 | 0.20 | 0.00 | 2292.63 | 1511.07 | 1061.71 | 675.48 | 0.00 | |||||||
Maximum of Months | 0.396865E+10 | 0.104845E+10 | 230.55 | 0.340062E+10 | 0.763887E+09 | 0.00 | 1.00 | 0.00 | 27485.53 | 24279.90 | 15924.44 | 6589.63 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.27 | 47.90 | 72.37 | 65.42 | 388.52 | 0.00 | 0.00 | 0.00 |
February | 181.63 | 67.68 | 113.95 | 113.48 | 363.62 | 0.00 | 0.00 | 0.00 |
March | 188.71 | 37.22 | 151.49 | 111.22 | 292.77 | 0.00 | 0.00 | 0.00 |
April | 505.54 | 237.03 | 268.51 | 536.12 | 228.26 | 0.00 | 0.00 | 0.00 |
May | 532.28 | 232.17 | 300.11 | 548.01 | 200.02 | 0.00 | 0.00 | 0.00 |
June | 526.71 | 210.41 | 316.30 | 573.39 | 160.01 | 0.00 | 0.00 | 0.00 |
July | 537.57 | 228.35 | 309.22 | 607.50 | 152.05 | 0.00 | 0.00 | 0.00 |
August | 510.66 | 244.47 | 266.19 | 589.03 | 168.56 | 0.00 | 0.00 | 0.00 |
September | 458.47 | 243.61 | 214.86 | 513.99 | 212.34 | 0.00 | 0.00 | 0.00 |
October | 222.99 | 93.25 | 129.74 | 195.51 | 278.95 | 0.00 | 0.00 | 0.00 |
November | 115.41 | 39.27 | 76.14 | 62.03 | 349.20 | 0.00 | 0.00 | 0.00 |
December | 85.84 | 32.12 | 53.72 | 39.13 | 433.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 332.65 | 142.97 | 189.68 | 330.34 | 268.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.84 | 32.12 | 53.72 | 39.13 | 152.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 537.57 | 244.47 | 316.30 | 607.50 | 433.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 467.59 | 302.80 | 164.80 | 461.16 | 503.66 | 0.00 | 0.00 | 0.00 |
February | 567.40 | 345.82 | 221.58 | 575.95 | 486.41 | 0.00 | 0.00 | 0.00 |
March | 350.20 | 101.23 | 248.97 | 282.48 | 407.22 | 0.00 | 0.00 | 0.00 |
April | 717.90 | 318.10 | 399.80 | 823.98 | 338.67 | 0.00 | 0.00 | 0.00 |
May | 601.83 | 194.96 | 406.87 | 634.25 | 298.70 | 0.00 | 0.00 | 0.00 |
June | 555.55 | 134.36 | 421.19 | 604.02 | 234.83 | 0.00 | 0.00 | 0.00 |
July | 598.82 | 185.26 | 413.57 | 698.01 | 223.59 | 0.00 | 0.00 | 0.00 |
August | 703.33 | 315.12 | 388.20 | 867.58 | 247.66 | 0.00 | 0.00 | 0.00 |
September | 842.86 | 497.46 | 345.40 | 1039.29 | 304.72 | 0.00 | 0.00 | 0.00 |
October | 562.40 | 324.24 | 238.16 | 621.59 | 383.29 | 0.00 | 0.00 | 0.00 |
November | 406.13 | 246.98 | 159.16 | 403.49 | 467.09 | 0.00 | 0.00 | 0.00 |
December | 322.29 | 206.66 | 115.63 | 306.77 | 578.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 557.15 | 263.36 | 293.79 | 608.98 | 372.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 322.29 | 101.23 | 115.63 | 282.48 | 223.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 842.86 | 497.46 | 421.19 | 1039.29 | 578.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.58 | 38.86 | 79.71 | 67.31 | 393.82 | 0.00 | 0.00 | 0.00 |
February | 209.75 | 89.29 | 120.47 | 160.01 | 369.66 | 0.00 | 0.00 | 0.00 |
March | 188.69 | 36.28 | 152.41 | 112.88 | 294.66 | 0.00 | 0.00 | 0.00 |
April | 444.40 | 176.19 | 268.20 | 462.70 | 238.21 | 0.00 | 0.00 | 0.00 |
May | 521.48 | 212.07 | 309.41 | 538.39 | 203.88 | 0.00 | 0.00 | 0.00 |
June | 563.01 | 231.78 | 331.23 | 626.25 | 161.07 | 0.00 | 0.00 | 0.00 |
July | 573.04 | 252.42 | 320.62 | 660.55 | 153.48 | 0.00 | 0.00 | 0.00 |
August | 482.23 | 208.91 | 273.32 | 555.06 | 173.23 | 0.00 | 0.00 | 0.00 |
September | 389.68 | 176.14 | 213.54 | 426.80 | 218.89 | 0.00 | 0.00 | 0.00 |
October | 207.72 | 75.44 | 132.28 | 178.27 | 283.02 | 0.00 | 0.00 | 0.00 |
November | 112.07 | 33.07 | 79.00 | 64.86 | 355.78 | 0.00 | 0.00 | 0.00 |
December | 62.48 | 12.70 | 49.78 | 19.52 | 446.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.09 | 128.64 | 194.45 | 323.26 | 273.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.48 | 12.70 | 49.78 | 19.52 | 153.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 573.04 | 252.42 | 331.23 | 660.55 | 446.14 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322142E+09 | 0.128301E+09 | 0.193841E+09 | 0.175218E+09 | 0.104062E+10 |
February | 0.439395E+09 | 0.163726E+09 | 0.275669E+09 | 0.274524E+09 | 0.879670E+09 |
March | 0.505430E+09 | 99688165.85 | 0.405742E+09 | 0.297887E+09 | 0.784154E+09 |
April | 0.131036E+10 | 0.614377E+09 | 0.695978E+09 | 0.138962E+10 | 0.591662E+09 |
May | 0.142566E+10 | 0.621836E+09 | 0.803821E+09 | 0.146778E+10 | 0.535730E+09 |
June | 0.136524E+10 | 0.545388E+09 | 0.819851E+09 | 0.148623E+10 | 0.414750E+09 |
July | 0.143983E+10 | 0.611599E+09 | 0.828227E+09 | 0.162714E+10 | 0.407240E+09 |
August | 0.136776E+10 | 0.654797E+09 | 0.712966E+09 | 0.157767E+10 | 0.451467E+09 |
September | 0.118836E+10 | 0.631447E+09 | 0.556910E+09 | 0.133225E+10 | 0.550389E+09 |
October | 0.597263E+09 | 0.249766E+09 | 0.347498E+09 | 0.523662E+09 | 0.747153E+09 |
November | 0.299132E+09 | 0.101784E+09 | 0.197348E+09 | 0.160788E+09 | 0.905127E+09 |
December | 0.229916E+09 | 86034699.48 | 0.143881E+09 | 0.104816E+09 | 0.116067E+10 |
Annual Sum or Average | 0.104905E+11 | 0.450874E+10 | 0.598173E+10 | 0.104176E+11 | 0.846863E+10 |
Minimum of Months | 0.229916E+09 | 86034699.48 | 0.143881E+09 | 0.104816E+09 | 0.407240E+09 |
Maximum of Months | 0.143983E+10 | 0.654797E+09 | 0.828227E+09 | 0.162714E+10 | 0.116067E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125240E+10 | 0.811007E+09 | 0.441395E+09 | 0.123517E+10 | 0.134899E+10 |
February | 0.137266E+10 | 0.836603E+09 | 0.536055E+09 | 0.139334E+10 | 0.117673E+10 |
March | 0.937984E+09 | 0.271140E+09 | 0.666844E+09 | 0.756592E+09 | 0.109069E+10 |
April | 0.186079E+10 | 0.824514E+09 | 0.103627E+10 | 0.213576E+10 | 0.877842E+09 |
May | 0.161195E+10 | 0.522179E+09 | 0.108977E+10 | 0.169877E+10 | 0.800050E+09 |
June | 0.143999E+10 | 0.348260E+09 | 0.109173E+10 | 0.156562E+10 | 0.608689E+09 |
July | 0.160389E+10 | 0.496199E+09 | 0.110769E+10 | 0.186955E+10 | 0.598872E+09 |
August | 0.188379E+10 | 0.844027E+09 | 0.103976E+10 | 0.232374E+10 | 0.663341E+09 |
September | 0.218468E+10 | 0.128941E+10 | 0.895267E+09 | 0.269383E+10 | 0.789829E+09 |
October | 0.150634E+10 | 0.868448E+09 | 0.637894E+09 | 0.166487E+10 | 0.102660E+10 |
November | 0.105270E+10 | 0.640167E+09 | 0.412531E+09 | 0.104585E+10 | 0.121069E+10 |
December | 0.863212E+09 | 0.553516E+09 | 0.309696E+09 | 0.821653E+09 | 0.155054E+10 |
Annual Sum or Average | 0.175704E+11 | 0.830548E+10 | 0.926491E+10 | 0.192047E+11 | 0.117429E+11 |
Minimum of Months | 0.863212E+09 | 0.271140E+09 | 0.309696E+09 | 0.756592E+09 | 0.598872E+09 |
Maximum of Months | 0.218468E+10 | 0.128941E+10 | 0.110769E+10 | 0.269383E+10 | 0.155054E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.317595E+09 | 0.104094E+09 | 0.213501E+09 | 0.180294E+09 | 0.105482E+10 |
February | 0.507434E+09 | 0.216004E+09 | 0.291430E+09 | 0.387085E+09 | 0.894271E+09 |
March | 0.505389E+09 | 97182254.63 | 0.408207E+09 | 0.302336E+09 | 0.789213E+09 |
April | 0.115188E+10 | 0.456695E+09 | 0.695181E+09 | 0.119932E+10 | 0.617448E+09 |
May | 0.139674E+10 | 0.568010E+09 | 0.828732E+09 | 0.144202E+10 | 0.546072E+09 |
June | 0.145933E+10 | 0.600786E+09 | 0.858540E+09 | 0.162325E+10 | 0.417506E+09 |
July | 0.153484E+10 | 0.676088E+09 | 0.858753E+09 | 0.176922E+10 | 0.411083E+09 |
August | 0.129160E+10 | 0.559534E+09 | 0.732062E+09 | 0.148668E+10 | 0.463971E+09 |
September | 0.101005E+10 | 0.456560E+09 | 0.553489E+09 | 0.110627E+10 | 0.567357E+09 |
October | 0.556356E+09 | 0.202060E+09 | 0.354296E+09 | 0.477484E+09 | 0.758047E+09 |
November | 0.290482E+09 | 85707905.99 | 0.204775E+09 | 0.168122E+09 | 0.922187E+09 |
December | 0.167340E+09 | 34015942.45 | 0.133324E+09 | 52282485.44 | 0.119495E+10 |
Annual Sum or Average | 0.101890E+11 | 0.405674E+10 | 0.613229E+10 | 0.101943E+11 | 0.863692E+10 |
Minimum of Months | 0.167340E+09 | 34015942.45 | 0.133324E+09 | 52282485.44 | 0.411083E+09 |
Maximum of Months | 0.153484E+10 | 0.676088E+09 | 0.858753E+09 | 0.176922E+10 | 0.119495E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 551.04 | 1243.16 | 706.44 | 389.56 | 316.88 | 0.00 | 0.00 |
February | 818.56 | 1188.82 | 958.78 | 502.78 | 456.00 | 0.00 | 0.00 |
March | 490.53 | 978.60 | 727.60 | 174.74 | 552.86 | 0.00 | 0.00 |
April | 1781.86 | 764.22 | 1667.83 | 731.32 | 936.51 | 0.00 | 0.00 |
May | 1677.30 | 659.26 | 1655.60 | 639.20 | 1016.40 | 0.00 | 0.00 |
June | 1779.14 | 531.40 | 1645.28 | 576.56 | 1068.72 | 0.00 | 0.00 |
July | 1940.63 | 503.68 | 1709.44 | 666.03 | 1043.41 | 0.00 | 0.00 |
August | 1987.36 | 565.13 | 1696.22 | 768.50 | 927.71 | 0.00 | 0.00 |
September | 1949.88 | 705.75 | 1691.01 | 917.21 | 773.79 | 0.00 | 0.00 |
October | 978.45 | 928.34 | 993.12 | 492.93 | 500.18 | 0.00 | 0.00 |
November | 506.68 | 1148.36 | 633.61 | 319.31 | 314.30 | 0.00 | 0.00 |
December | 334.28 | 1427.25 | 470.60 | 251.48 | 219.12 | 0.00 | 0.00 |
Annual Sum or Average | 1233.41 | 885.61 | 1212.90 | 534.97 | 677.92 | 0.00 | 0.00 |
Minimum of Months | 334.28 | 503.68 | 470.60 | 174.74 | 219.12 | 0.00 | 0.00 |
Maximum of Months | 1987.36 | 1427.25 | 1709.44 | 917.21 | 1068.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147592E+10 | 0.332967E+10 | 0.189214E+10 | 0.104340E+10 | 0.848737E+09 | 0.00 | 0.00 |
February | 0.198026E+10 | 0.287599E+10 | 0.231949E+10 | 0.121633E+10 | 0.110315E+10 | 0.00 | 0.00 |
March | 0.131385E+10 | 0.262109E+10 | 0.194880E+10 | 0.468011E+09 | 0.148079E+10 | 0.00 | 0.00 |
April | 0.461859E+10 | 0.198085E+10 | 0.432302E+10 | 0.189559E+10 | 0.242743E+10 | 0.00 | 0.00 |
May | 0.449248E+10 | 0.176576E+10 | 0.443435E+10 | 0.171202E+10 | 0.272232E+10 | 0.00 | 0.00 |
June | 0.461153E+10 | 0.137738E+10 | 0.426456E+10 | 0.149443E+10 | 0.277013E+10 | 0.00 | 0.00 |
July | 0.519777E+10 | 0.134906E+10 | 0.457856E+10 | 0.178389E+10 | 0.279467E+10 | 0.00 | 0.00 |
August | 0.532293E+10 | 0.151363E+10 | 0.454315E+10 | 0.205836E+10 | 0.248479E+10 | 0.00 | 0.00 |
September | 0.505409E+10 | 0.182930E+10 | 0.438309E+10 | 0.237742E+10 | 0.200566E+10 | 0.00 | 0.00 |
October | 0.262067E+10 | 0.248646E+10 | 0.265996E+10 | 0.132027E+10 | 0.133969E+10 | 0.00 | 0.00 |
November | 0.131332E+10 | 0.297656E+10 | 0.164231E+10 | 0.827660E+09 | 0.814654E+09 | 0.00 | 0.00 |
December | 0.895334E+09 | 0.382273E+10 | 0.126047E+10 | 0.673566E+09 | 0.586901E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388968E+11 | 0.279285E+11 | 0.382499E+11 | 0.168710E+11 | 0.213789E+11 | 0.00 | 0.00 |
Minimum of Months | 0.895334E+09 | 0.134906E+10 | 0.126047E+10 | 0.468011E+09 | 0.586901E+09 | 0.00 | 0.00 |
Maximum of Months | 0.532293E+10 | 0.382273E+10 | 0.457856E+10 | 0.237742E+10 | 0.279467E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639713E+10 | -0.622516E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171970805.1 | 81.22 | 0.00 | 0.00 |
February | 0.579006E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155785194.7 | 81.22 | 0.00 | 0.00 |
March | 0.646533E+10 | -0.629384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171497392.4 | 81.22 | 0.00 | 0.00 |
April | 0.620550E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162028808.5 | 81.22 | 0.00 | 0.00 |
May | 0.642669E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166499609.1 | 81.22 | 0.00 | 0.00 |
June | 0.624295E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156381003.5 | 81.22 | 0.00 | 0.00 |
July | 0.637644E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159357130.1 | 81.21 | 0.00 | 0.00 |
August | 0.645365E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158442237.9 | 81.22 | 0.00 | 0.00 |
September | 0.620070E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155875841.0 | 81.22 | 0.00 | 0.00 |
October | 0.639126E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167435083.2 | 81.22 | 0.00 | 0.00 |
November | 0.619009E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -165470323.2 | 81.22 | 0.00 | 0.00 |
December | 0.638954E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172457630.7 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755293E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.196320E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579006E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172457630.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646533E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155785194.7 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.246957E+11 | -0.236952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100051E+10 | 58.99 | 0.00 | 0.00 |
February | 0.224974E+11 | -0.215895E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -907877476.7 | 58.99 | 0.00 | 0.00 |
March | 0.249500E+11 | -0.239538E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -996153110.9 | 58.99 | 0.00 | 0.00 |
April | 0.234921E+11 | -0.225640E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -928040509.1 | 58.99 | 0.00 | 0.00 |
May | 0.236990E+11 | -0.227485E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -950423453.3 | 58.99 | 0.00 | 0.00 |
June | 0.223782E+11 | -0.215019E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -876301552.8 | 58.99 | 0.00 | 0.00 |
July | 0.223871E+11 | -0.215021E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -885036068.2 | 58.99 | 0.00 | 0.00 |
August | 0.224757E+11 | -0.215989E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -876745598.6 | 58.99 | 0.00 | 0.00 |
September | 0.217752E+11 | -0.209034E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -871727278.1 | 58.99 | 0.00 | 0.00 |
October | 0.229408E+11 | -0.219818E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -959013368.1 | 58.99 | 0.00 | 0.00 |
November | 0.228414E+11 | -0.218819E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -959476052.8 | 58.99 | 0.00 | 0.00 |
December | 0.242080E+11 | -0.232030E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100497E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.278340E+12 | -0.267124E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.112163E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.217752E+11 | -0.239538E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.100497E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.249500E+11 | -0.209034E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -871727278.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.75 | 0.73 | 01-JAN-08:50 | 2691.70 | 32.92 | 155.00 | 223.50 | 2603.72 | 32.10 | 149.17 | 221.00 |
February | 217.00 | 0.74 | 0.73 | 01-FEB-11:39 | 3512.02 | 31.45 | 159.17 | 248.17 | 3583.78 | 30.52 | 148.17 | 246.50 |
March | 215.50 | 0.74 | 0.73 | 01-MAR-11:39 | 1382.35 | 21.74 | 83.17 | 314.67 | 1352.20 | 21.83 | 80.50 | 313.83 |
April | 359.67 | 0.74 | 0.73 | 01-APR-06:49 | 2020.43 | 20.89 | 144.00 | 366.67 | 2122.27 | 19.67 | 99.50 | 368.50 |
May | 417.17 | 0.74 | 0.73 | 01-MAY-06:40 | 1757.07 | 19.58 | 84.67 | 422.33 | 1738.54 | 19.40 | 82.00 | 426.50 |
June | 410.67 | 0.74 | 0.73 | 01-JUN-05:10 | 2052.01 | 20.78 | 102.67 | 423.17 | 1673.90 | 19.65 | 82.17 | 424.33 |
July | 429.00 | 0.74 | 0.73 | 01-JUL-05:10 | 2008.56 | 20.27 | 101.67 | 434.17 | 1649.87 | 19.44 | 88.83 | 434.50 |
August | 396.33 | 0.74 | 0.73 | 01-AUG-05:40 | 1886.55 | 19.83 | 94.33 | 392.83 | 1988.65 | 19.46 | 104.83 | 395.33 |
September | 337.67 | 0.74 | 0.73 | 01-SEP-07:40 | 1935.79 | 21.71 | 154.17 | 338.67 | 1952.24 | 20.57 | 113.00 | 340.67 |
October | 234.00 | 0.74 | 0.73 | 01-OCT-06:49 | 2196.73 | 26.29 | 137.50 | 283.83 | 2277.62 | 26.95 | 149.50 | 283.00 |
November | 171.33 | 0.74 | 0.73 | 01-NOV-11:39 | 3123.55 | 33.22 | 139.33 | 217.17 | 3159.53 | 33.15 | 139.67 | 215.33 |
December | 131.67 | 0.75 | 0.73 | 02-DEC-08:39 | 2672.63 | 35.99 | 117.00 | 180.33 | 2651.98 | 34.64 | 111.67 | 179.17 |
Annual Sum or Average | 3515.67 | 0.74 | 2148.43 | 23.50 | 1472.67 | 3845.50 | 2085.85 | 22.87 | 1349.00 | 3848.67 | ||
Minimum of Months | 131.67 | 0.74 | 0.73 | 1382.35 | 19.58 | 83.17 | 180.33 | 1352.20 | 19.40 | 80.50 | 179.17 | |
Maximum of Months | 429.00 | 0.75 | 0.73 | 3512.02 | 35.99 | 159.17 | 434.17 | 3583.78 | 34.64 | 149.50 | 434.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397408E+11 | 73326.83 | 10-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344827E+11 | 109102.89 | 13-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310466E+11 | 68497.21 | 13-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148050E+11 | 73670.46 | 09-APR-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115126E+11 | 43113.12 | 05-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.329324E+10 | 25891.03 | 08-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155957E+10 | 26061.82 | 06-JUL-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.897405E+09 | 36121.01 | 28-AUG-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318722E+10 | 27385.51 | 20-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144870E+11 | 36244.41 | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269152E+11 | 69711.01 | 29-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407419E+11 | 80409.21 | 31-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.897405E+09 | 25891.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.407419E+11 | 109102.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148678E+11 | 27832.32 | 12-JAN-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120647E+11 | 26765.23 | 26-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894274E+10 | 22121.67 | 08-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373711E+10 | 20791.17 | 08-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192060E+10 | 17443.69 | 06-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151446E+09 | 10339.88 | 01-JUN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22110394.76 | 8380.75 | 02-JUL-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23858.00 | 397.63 | 28-AUG-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132469E+09 | 10713.83 | 21-SEP-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244370E+10 | 16767.90 | 06-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.667308E+10 | 26229.17 | 29-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142863E+11 | 28290.41 | 27-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.652421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 23858.00 | 397.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148678E+11 | 28290.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.948519E+09 | 0.892914E+09 | 20034.40 | 30-APR-18:03 | 20034.40 | 0.00 |
May | 0.00 | 0.00 | 0.992708E+09 | 0.779235E+09 | 18038.97 | 22-MAY-12:53 | 15312.55 | 0.00 |
June | 0.00 | 0.00 | 0.411545E+10 | 0.316510E+10 | 34334.65 | 13-JUN-17:10 | 29984.48 | 0.00 |
July | 0.00 | 0.00 | 0.779587E+10 | 0.613458E+10 | 62844.34 | 18-JUL-03:11 | 38791.03 | 0.00 |
August | 0.00 | 0.00 | 0.886260E+10 | 0.665339E+10 | 31386.13 | 15-AUG-03:11 | 24456.77 | 0.00 |
September | 0.00 | 0.00 | 0.417031E+10 | 0.322574E+10 | 25607.87 | 11-SEP-17:10 | 20453.07 | 0.00 |
October | 0.00 | 0.00 | 9631997.49 | 9580281.13 | 2494.86 | 07-OCT-15:10 | 2494.86 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268951E+11 | 0.208605E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.886260E+10 | 0.665339E+10 | 62844.34 | 38791.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8683475.07 | 5336793.19 | 2799.23 | 27-JAN-04:08 | 1745.45 | 0.00 |
February | 0.00 | 0.00 | 3810907.67 | 2208558.84 | 2716.25 | 21-FEB-04:10 | 1706.81 | 0.00 |
March | 0.00 | 0.00 | 8123112.25 | 5222132.52 | 2978.80 | 24-MAR-03:08 | 1917.09 | 0.00 |
April | 0.00 | 0.00 | 0.464723E+09 | 0.456898E+09 | 20169.64 | 21-APR-04:01 | 13437.22 | 0.00 |
May | 0.00 | 0.00 | 0.434989E+09 | 0.365968E+09 | 27485.53 | 23-MAY-03:21 | 14112.00 | 0.00 |
June | 0.00 | 0.00 | 0.223634E+10 | 0.187248E+10 | 27485.53 | 02-JUN-04:01 | 17842.79 | 0.00 |
July | 0.00 | 0.00 | 0.396865E+10 | 0.340062E+10 | 27485.53 | 18-JUL-03:21 | 14851.22 | 0.00 |
August | 0.00 | 0.00 | 0.390619E+10 | 0.314230E+10 | 27485.53 | 15-AUG-04:01 | 18237.51 | 0.00 |
September | 0.00 | 0.00 | 0.187376E+10 | 0.156077E+10 | 27485.53 | 12-SEP-04:01 | 16172.93 | 0.00 |
October | 0.00 | 0.00 | 18485627.78 | 10701660.28 | 9040.28 | 27-OCT-04:01 | 5674.99 | 0.00 |
November | 0.00 | 0.00 | 9737117.67 | 5895308.80 | 2292.63 | 03-NOV-03:05 | 1511.07 | 0.00 |
December | 0.00 | 0.00 | 6798245.88 | 4333946.70 | 3409.94 | 05-DEC-04:08 | 1974.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129403E+11 | 0.108327E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 3810907.67 | 2208558.84 | 2292.63 | 1511.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.396865E+10 | 0.340062E+10 | 27485.53 | 18237.51 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9306.09 | 17785.15 | 30-JAN-19:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 9383.48 | 17829.93 | 17-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9402.42 | 17789.32 | 01-MAR-19:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9164.70 | 17546.02 | 03-APR-18:50 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8953.16 | 17155.15 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8755.69 | 16721.04 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8488.63 | 16269.83 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8524.88 | 16072.80 | 31-AUG-18:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8525.48 | 16264.35 | 28-SEP-18:10 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8667.93 | 16672.54 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8902.27 | 17119.62 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9122.67 | 17513.03 | 29-DEC-19:30 |
Annual Sum or Average | 0.00 | 8930.47 | ||||
Minimum of Months | 0.00 | 0.00 | 8488.63 | 16072.80 | ||
Maximum of Months | 0.00 | 0.00 | 9402.42 | 17829.93 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.452972E+10 | 0.55 | 1983.06 | 01-JAN-00:01 | 0.64 |
February | 0.406151E+10 | 0.54 | 1983.06 | 01-FEB-00:01 | 0.64 |
March | 0.455411E+10 | 0.55 | 1983.06 | 01-MAR-00:01 | 0.64 |
April | 0.461604E+10 | 0.58 | 1983.06 | 01-APR-03:25 | 0.64 |
May | 0.483872E+10 | 0.58 | 1983.06 | 01-MAY-00:12 | 0.64 |
June | 0.487971E+10 | 0.61 | 1983.06 | 01-JUN-00:19 | 0.64 |
July | 0.506050E+10 | 0.61 | 1983.06 | 01-JUL-00:25 | 0.64 |
August | 0.506669E+10 | 0.61 | 1983.06 | 01-AUG-00:12 | 0.64 |
September | 0.490166E+10 | 0.61 | 1983.06 | 01-SEP-00:10 | 0.64 |
October | 0.486511E+10 | 0.59 | 1983.06 | 01-OCT-01:00 | 0.64 |
November | 0.448272E+10 | 0.56 | 1983.06 | 01-NOV-02:65 | 0.64 |
December | 0.450651E+10 | 0.55 | 1983.06 | 01-DEC-00:01 | 0.64 |
Annual Sum or Average | 0.563630E+11 | 0.58 | |||
Minimum of Months | 0.406151E+10 | 0.54 | 1983.06 | 0.64 | |
Maximum of Months | 0.506669E+10 | 0.61 | 1983.06 | 0.64 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.390934E+10 | 0.52 | 2633.84 | 05-JAN-05:38 | 0.77 |
February | 0.350609E+10 | 0.52 | 3345.99 | 13-FEB-04:02 | 0.89 |
March | 0.374770E+10 | 0.51 | 2681.58 | 13-MAR-04:02 | 0.78 |
April | 0.334235E+10 | 0.47 | 2776.77 | 09-APR-04:07 | 0.79 |
May | 0.338392E+10 | 0.46 | 2214.48 | 05-MAY-04:01 | 0.70 |
June | 0.313098E+10 | 0.45 | 1897.58 | 08-JUN-04:02 | 0.64 |
July | 0.320819E+10 | 0.45 | 1954.47 | 22-JUL-18:05 | 0.65 |
August | 0.318914E+10 | 0.45 | 2085.82 | 28-AUG-04:06 | 0.68 |
September | 0.312864E+10 | 0.45 | 1925.08 | 20-SEP-04:03 | 0.65 |
October | 0.343861E+10 | 0.47 | 2088.09 | 23-OCT-04:01 | 0.68 |
November | 0.356658E+10 | 0.50 | 2255.68 | 30-NOV-05:01 | 0.71 |
December | 0.392840E+10 | 0.53 | 2775.86 | 15-DEC-05:28 | 0.79 |
Annual Sum or Average | 0.414800E+11 | 0.48 | |||
Minimum of Months | 0.312864E+10 | 0.45 | 1897.58 | 0.64 | |
Maximum of Months | 0.392840E+10 | 0.53 | 3345.99 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.365655E+10 | 0.75 | 1635.93 | 01-JAN-18:00 | 0.89 |
February | 0.330109E+10 | 0.75 | 1635.93 | 01-FEB-08:00 | 0.88 |
March | 0.365744E+10 | 0.76 | 1635.93 | 01-MAR-08:20 | 0.89 |
April | 0.355244E+10 | 0.79 | 1635.93 | 02-APR-07:47 | 0.89 |
May | 0.367939E+10 | 0.80 | 1635.93 | 02-MAY-05:05 | 0.89 |
June | 0.360145E+10 | 0.83 | 1635.93 | 01-JUN-04:18 | 0.89 |
July | 0.374652E+10 | 0.83 | 1635.93 | 12-JUL-17:45 | 0.88 |
August | 0.375480E+10 | 0.83 | 1635.93 | 01-AUG-17:23 | 0.88 |
September | 0.360553E+10 | 0.83 | 1635.93 | 11-SEP-10:30 | 0.88 |
October | 0.367826E+10 | 0.80 | 1635.93 | 02-OCT-23:03 | 0.88 |
November | 0.354408E+10 | 0.77 | 1635.93 | 01-NOV-23:02 | 0.88 |
December | 0.365518E+10 | 0.75 | 1635.93 | 01-DEC-10:00 | 0.89 |
Annual Sum or Average | 0.434327E+11 | 0.79 | |||
Minimum of Months | 0.330109E+10 | 0.75 | 1635.93 | 0.88 | |
Maximum of Months | 0.375480E+10 | 0.83 | 1635.93 | 0.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 48.58 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 47.84 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 47.83 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 51.34 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 51.43 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:05 | 5.36 | 5.36 | 51.78 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.92 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.32 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.03 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.93 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.10 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.97 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 47.83 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.32 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 48.58 | 59.93 | 9306.09 | 17785.15 | 30-JAN-19:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 47.84 | 58.41 | 9383.48 | 17829.93 | 17-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 47.83 | 58.62 | 9402.42 | 17789.32 | 01-MAR-19:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.60 | 49.60 | 9164.70 | 17546.02 | 03-APR-18:50 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.84 | 49.84 | 8953.16 | 17155.15 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.13 | 50.13 | 8755.69 | 16721.04 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 49.99 | 49.99 | 8488.63 | 16269.83 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 49.89 | 49.89 | 8524.88 | 16072.80 | 31-AUG-18:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.51 | 50.51 | 8525.48 | 16264.35 | 28-SEP-18:10 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 47.71 | 47.71 | 8667.93 | 16672.54 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.52 | 49.52 | 8902.27 | 17119.62 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.97 | 58.20 | 9122.67 | 17513.03 | 29-DEC-19:30 |
Annual Sum or Average | 0.00 | 8930.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.71 | 47.71 | 8488.63 | 16072.80 | ||
Maximum of Months | 0.00 | 0.00 | 50.51 | 59.93 | 9402.42 | 17829.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.390934E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.350609E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.374770E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.361435E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.366748E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.424628E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.536579E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.570915E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.431000E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.344161E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.356658E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.392840E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.490128E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.344161E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.570915E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.365916E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.330222E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.365988E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.367547E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.379810E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.416573E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.476920E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.480324E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.410931E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.368382E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.354702E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.365722E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.468304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.330222E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.480324E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.390934E+10 | 0.00 | 0.397408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350609E+10 | 0.00 | 0.344827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374770E+10 | 0.00 | 0.310466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334235E+10 | 0.948519E+09 | 0.148050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.338392E+10 | 0.992708E+09 | 0.115126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.313098E+10 | 0.411545E+10 | 0.329324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.320819E+10 | 0.779458E+10 | 0.155957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.318914E+10 | 0.886260E+10 | 0.897405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312864E+10 | 0.417031E+10 | 0.318722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343861E+10 | 9631997.49 | 0.144870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.356658E+10 | 0.00 | 0.269152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.392840E+10 | 0.00 | 0.407419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414800E+11 | 0.268938E+11 | 0.222669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312864E+10 | 0.00 | 0.897405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.392840E+10 | 0.886260E+10 | 0.407419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.365655E+10 | 8683475.07 | 0.148678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330109E+10 | 3810907.67 | 0.120647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365744E+10 | 8123112.25 | 0.894274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355244E+10 | 0.464723E+09 | 0.373711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367939E+10 | 0.434989E+09 | 0.192060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.360145E+10 | 0.223634E+10 | 0.151446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.374652E+10 | 0.396865E+10 | 22110394.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.375480E+10 | 0.390619E+10 | 23858.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360553E+10 | 0.187376E+10 | 0.132469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367826E+10 | 18485627.78 | 0.244370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354408E+10 | 9737117.67 | 0.667308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365518E+10 | 6798245.88 | 0.142863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.434327E+11 | 0.129403E+11 | 0.652421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.330109E+10 | 3810907.67 | 23858.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.375480E+10 | 0.396865E+10 | 0.148678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.390934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334235E+10 | 0.00 | 0.00 | 0.00 | 0.271998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.338392E+10 | 0.00 | 0.00 | 0.00 | 0.283559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.313098E+10 | 0.00 | 0.00 | 0.00 | 0.111529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.320819E+10 | 0.00 | 0.00 | 0.00 | 0.215760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.318914E+10 | 0.00 | 0.00 | 0.00 | 0.252001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312864E+10 | 0.00 | 0.00 | 0.00 | 0.118136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343861E+10 | 0.00 | 0.00 | 0.00 | 2999121.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.356658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.392840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414800E+11 | 0.00 | 0.00 | 0.00 | 0.753282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.392840E+10 | 0.00 | 0.00 | 0.00 | 0.252001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.365655E+10 | 0.00 | 0.00 | 0.00 | 2609868.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330109E+10 | 0.00 | 0.00 | 0.00 | 1133664.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365744E+10 | 0.00 | 0.00 | 0.00 | 2437739.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355244E+10 | 0.00 | 0.00 | 0.00 | 0.123025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367939E+10 | 0.00 | 0.00 | 0.00 | 0.118703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.360145E+10 | 0.00 | 0.00 | 0.00 | 0.564283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.374652E+10 | 0.00 | 0.00 | 0.00 | 0.102268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.375480E+10 | 0.00 | 0.00 | 0.00 | 0.104845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360553E+10 | 0.00 | 0.00 | 0.00 | 0.503779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367826E+10 | 0.00 | 0.00 | 0.00 | 5554164.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354408E+10 | 0.00 | 0.00 | 0.00 | 2942119.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365518E+10 | 0.00 | 0.00 | 0.00 | 2040595.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.434327E+11 | 0.00 | 0.00 | 0.00 | 0.339763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.330109E+10 | 0.00 | 0.00 | 0.00 | 1133664.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.375480E+10 | 0.00 | 0.00 | 0.00 | 0.104845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.645327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507344E+10 | 0.00 | 0.00 | 3.55 |
February | 0.584707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368874E+10 | 0.00 | 0.00 | 3.57 |
March | 0.604618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230849E+10 | 0.00 | 0.00 | 3.55 |
April | 0.464104E+11 | 0.00 | 0.00 | 11772312.59 | 0.00 | 0.668000E+09 | 0.411084E+10 | 0.00 | 3.59 |
May | 0.446512E+11 | 0.00 | 0.00 | 14842323.40 | 0.00 | 48584965.04 | 0.543077E+10 | 0.00 | 3.58 |
June | 0.273709E+11 | 21925296.50 | 0.00 | 34987704.88 | 0.00 | 23540603.45 | 0.131758E+11 | 0.00 | 3.66 |
July | 0.187742E+11 | 41841807.79 | 0.00 | 66624449.88 | 0.00 | 8097965.76 | 0.192979E+11 | 0.00 | 3.76 |
August | 0.140205E+11 | 0.00 | 0.00 | 79584807.04 | 0.00 | 4319321.65 | 0.230732E+11 | 0.00 | 3.84 |
September | 0.231220E+11 | 0.00 | 0.00 | 43622454.63 | 0.00 | 22092723.45 | 0.178776E+11 | 0.00 | 3.70 |
October | 0.490129E+11 | 0.00 | 0.00 | 2178315.31 | 0.00 | 42074472.42 | 0.271065E+10 | 0.00 | 3.57 |
November | 0.580654E+11 | 0.00 | 0.00 | 4127.05 | 0.00 | 0.546917E+09 | 89438819.42 | 0.00 | 3.54 |
December | 0.657621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405642E+10 | 0.00 | 0.00 | 3.58 |
Annual Sum or Average | 0.530655E+12 | 63767104.29 | 0.00 | 0.253616E+09 | 0.00 | 0.164907E+11 | 0.857662E+11 | 0.00 | 3.63 |
Minimum of Months | 0.140205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4319321.65 | 0.00 | 0.00 | 3.54 |
Maximum of Months | 0.657621E+11 | 41841807.79 | 0.00 | 79584807.04 | 0.00 | 0.507344E+10 | 0.230732E+11 | 0.00 | 3.84 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.607443E+11 | 0.00 | 0.00 | 647709.24 | 0.00 | 0.00 | 0.116958E+10 | 0.00 | 8.61 |
February | 0.547166E+11 | 0.00 | 0.00 | 389444.23 | 0.00 | 0.00 | 0.286196E+09 | 0.00 | 8.64 |
March | 0.548557E+11 | 0.00 | 0.00 | 824778.25 | 0.00 | 0.00 | 0.170068E+10 | 0.00 | 8.62 |
April | 0.408650E+11 | 0.00 | 0.00 | 15524426.38 | 0.00 | 0.00 | 0.107932E+11 | 0.00 | 8.84 |
May | 0.371617E+11 | 0.00 | 0.00 | 19957671.54 | 0.00 | 0.00 | 0.140497E+11 | 0.00 | 8.85 |
June | 0.176678E+11 | 0.00 | 0.00 | 54151246.82 | 0.00 | 0.00 | 0.288177E+11 | 0.00 | 9.30 |
July | 0.109471E+11 | 0.00 | 0.00 | 87322075.23 | 0.00 | 0.00 | 0.357751E+11 | 0.00 | 9.74 |
August | 0.911609E+10 | 0.00 | 0.00 | 0.100483E+09 | 0.00 | 0.00 | 0.378059E+11 | 0.00 | 10.12 |
September | 0.152316E+11 | 0.00 | 0.00 | 63286410.22 | 0.00 | 0.00 | 0.318331E+11 | 0.00 | 9.43 |
October | 0.370417E+11 | 0.00 | 0.00 | 8457208.82 | 0.00 | 0.00 | 0.140368E+11 | 0.00 | 8.77 |
November | 0.495005E+11 | 0.00 | 0.00 | 1519727.44 | 0.00 | 0.00 | 0.344251E+10 | 0.00 | 8.62 |
December | 0.608377E+11 | 0.00 | 0.00 | 475907.78 | 0.00 | 0.00 | 0.425522E+09 | 0.00 | 8.65 |
Annual Sum or Average | 0.448686E+12 | 0.00 | 0.00 | 0.353039E+09 | 0.00 | 0.00 | 0.180136E+12 | 0.00 | 9.02 |
Minimum of Months | 0.911609E+10 | 0.00 | 0.00 | 389444.23 | 0.00 | 0.00 | 0.286196E+09 | 0.00 | 8.61 |
Maximum of Months | 0.608377E+11 | 0.00 | 0.00 | 0.100483E+09 | 0.00 | 0.00 | 0.378059E+11 | 0.00 | 10.12 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.165700E+11 | 0.953232E+10 | 0.210896E+12 | 12010.01 | 0.281200E+11 |
February | 0.274777E+11 | 0.927851E+10 | 0.186690E+12 | 126333.93 | 0.265109E+11 |
March | 0.367326E+11 | 0.100000E+11 | 0.193863E+12 | 0.00 | 0.258732E+11 |
April | 0.102278E+12 | 0.111411E+11 | 0.176429E+12 | 0.740754E+09 | 0.283971E+11 |
May | 0.128039E+12 | 0.121082E+11 | 0.175259E+12 | 0.790867E+09 | 0.276331E+11 |
June | 0.131854E+12 | 0.109179E+11 | 0.154378E+12 | 0.195583E+10 | 0.331776E+11 |
July | 0.133287E+12 | 0.104701E+11 | 0.147135E+12 | 0.452211E+10 | 0.416911E+11 |
August | 0.106283E+12 | 0.877504E+10 | 0.141738E+12 | 0.665820E+10 | 0.435783E+11 |
September | 0.757866E+11 | 0.787884E+10 | 0.155383E+12 | 0.278570E+10 | 0.324481E+11 |
October | 0.312581E+11 | 0.767094E+10 | 0.179117E+12 | 68125803.66 | 0.228283E+11 |
November | 0.857217E+10 | 0.843578E+10 | 0.183122E+12 | 281855.82 | 0.228678E+11 |
December | -0.182989E+10 | 0.965996E+10 | 0.209099E+12 | 0.00 | 0.274339E+11 |
Annual Sum or Average | 0.796307E+12 | 0.115869E+12 | 0.211311E+13 | 0.175220E+11 | 0.360560E+12 |
Minimum of Months | -0.182989E+10 | 0.767094E+10 | 0.141738E+12 | 0.00 | 0.228283E+11 |
Maximum of Months | 0.133287E+12 | 0.121082E+11 | 0.210896E+12 | 0.665820E+10 | 0.435783E+11 |