Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:24:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3017.71 | 5903.73 | 5903.73 |
Net Site Energy | 3017.71 | 5903.73 | 5903.73 |
Total Source Energy | 5954.18 | 11648.52 | 11648.52 |
Net Source Energy | 5954.18 | 11648.52 | 11648.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 866.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 90.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 352.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.50 | 393.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 65.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1288.04 | 1729.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 866.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 90.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 352.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 77.50 | 393.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 866.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 90.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 352.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 77.50 | 393.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 65.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1020.08 | 2464.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1029.72 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2519.86 | 3383.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1020.08 | 2464.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1029.72 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2519.86 | 3383.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1288.036 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1288.036 | 100.00 |
Total On-Site and Utility Electric Sources | 1288.036 | 100.00 |
Total Electricity End Uses | 1288.036 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5279.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 20.6319 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.3949 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 18.1127 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 18.1127 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 20.6319 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.3949 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 18.1127 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 18.1127 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 18.1127 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-17:19 | 28-JAN-04:10 | - | - | - | - | - | - | - | - | - | - | 11-JAN-07:40 |
Heating | 0.00 | 291770.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35822.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20676.91 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13067.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4499.59 | 14035.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2063.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 84480.94 | 310331.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 291770.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35822.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13067.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4499.59 | 14035.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 513.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1005.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 939.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 286.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 533.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 245.45 | 426.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 207.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4079.21 | 1874.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1837.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 560.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 445.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2186.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 480.18 | 833.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 406.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7980.40 | 3668.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1837.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 560.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 445.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2186.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 480.18 | 833.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 406.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7980.40 | 3668.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.74 |
KITCHEN DIRECT AIR | 1.80 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.74 | 4.74 | 4.74 | 4.74 | 4.74 | 4.74 | 1.00 | 1.00 | 4.74 |
PSZ-AC_2:2 | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 | 1.00 | 1.00 | 1.80 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.74 | 2.64 |
PSZ-AC_2:2_OA_CONTROLLER | 1.80 | 0.187543 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.74 | 8893.87 |
PSZ-AC_2:2_ADDAQ FAN | 1.80 | 1970.66 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.74 | 4.74 | 4.74 | 4.74 | 94734.52 | 231228.25 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.80 | 1.80 | 1.80 | 1.80 | 37488.06 | 50770.22 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.74 | 2.37 | 4.74 | 94734.52 | 47320.89 | 94734.52 | 0.776320 | 0.776320 |
PSZ-AC_2:2 COOLING COIL | 1.80 | 0.900251 | 1.80 | 37488.06 | 17996.70 | 37488.06 | 0.760300 | 0.760300 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 231228.25 |
PSZ-AC_2:2 HEATING COIL | 50770.22 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 20.632 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 85.559 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.395 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.475 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 7669.876 | 20.632 | 27.379 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7669.876 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1588.510 | 11.395 | 211.016 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1588.510 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7390 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27638744E-12 | 0.13692172E-14 | -0.80454349E-13 | 0.78568260E-16 |
34 | 6 | 0.25667740E-07 | 0.27924344E-09 | 0.59050449E-08 | -0.11914668E-12 |
35 | 5 | -0.17473551E-03 | 0.24386372E-05 | -0.90062287E-04 | 0.58456630E-08 |
36 | 4 | 0.27398001 | 0.12082630E-02 | 0.93158629E-01 | -0.31026392E-04 |
37 | 3 | -6.9061245 | 0.38026294E-01 | -2.2320589 | 0.27244997E-01 |
38 | 2 | 39.682701 | 0.13706054 | 14.825764 | -0.32010675 |
39 | 1 | -79.634567 | 0.62587550E-01 | -28.747502 | 1.0592017 |
40 | 0 | 46.824345 | 0.12738124E-02 | 16.300887 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | 38 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
2 | NONRESWINDOW_U_0.5722_SHGC_NORTH_0.39 | 39 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
3 | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | 40 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
4 | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | 41 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.237 | 1.0416 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.744 | 0.2415 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 47340.59836 | 56808.71803 | 3.94757 | 4.73709 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
2 | DINING | Heating | 15489.13117 | 18586.95741 | 0.75907 | 2.64387 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
3 | KITCHEN | Cooling | 21209.90123 | 25451.88147 | 1.50042 | 1.80050 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
4 | KITCHEN | Heating | 2923.44815 | 3508.13777 | 0.12962 | 0.18754 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60000 | 3.41898E-004 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 82396.25 | 4.73709 | 4.73709 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 189137.55 | 2.64387 | 2.64387 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26259.67 | 1.80050 | 1.80050 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 13416.50 | 0.18754 | 0.18754 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.73709 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.80050 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.73709 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.73709 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.73709 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.73709 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.73709 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.73709 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.80050 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.80050 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.80050 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.80050 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.80050 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.80050 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.73709 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.80050 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.73709 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.64387 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.73709 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 8893.87206 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.73709 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.73709 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.73709 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.73709 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.73709 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.36854 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.73709 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 94734.52000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 47320.89103 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 94734.52000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77632 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77632 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 94734.52000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 231228.25086 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 231228.25086 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.80050 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.18754 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.80050 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1970.65975 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.80050 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.80050 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.80050 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.80050 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.80050 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90025 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.80050 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37488.06000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17996.69982 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 37488.06000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76030 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76030 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37488.06000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50770.22423 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 50770.22423 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 91309.9 | 9.68 | 9.56 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 36190.1 | 10.43 | 10.30 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | N/A | 3.253 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | N/A | 3.253 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | N/A | 3.253 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.3830309703E-002 | 0.4306747528 | Pass | Pass | 0.5191844105 | 3.5648650227 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1309354657 | 0.4010805754 | Pass | Pass | 0.2223282493 | 0.7167049296 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2760784510 | 0.2883796314 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 980.10 | 178.45 | 3930.37 | 260.89 | 831.42 | 6181.24 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 3.253 | 0.391 | 0.391 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 3.253 | 0.391 | 0.391 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 20.6319 | 371.75 | 7669.88 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 139.55 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.3949 | 139.41 | 1588.51 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 28.90 |
Interior Lighting Total | 18.1127 | 511.15 | 9258.39 | 168.45 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.57 | 83.57 | 71.82 | |
Exterior Lighting Total | 4578.48 | 71.82 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 94734.52 | 73544.30 | 21190.22 | 0.78 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37488.06 | 28502.17 | 8985.89 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 91309.9 | 9.68 | 9.56 | ||||
PSZ-AC_2:2 COOLING COIL | 36190.1 | 10.43 | 10.30 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 231228.25 | 0.79 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 50770.22 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 2.64 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.74 | 8893.87 | 1877.50 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.80 | 1970.66 | 1094.51 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.04 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.74 | 0.24 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 47340.60 | 56808.72 | 152.82 | 3.948 | 4.737 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.00820 | 33.24 | 0.00631 | 2.644 | 0.00 |
KITCHEN | 21209.90 | 25451.88 | 182.57 | 1.500 | 1.801 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.00879 | 31.96 | 0.00630 | 0.188 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 15489.13 | 18586.96 | 50.00 | 0.759 | 2.644 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00771 | -27.60 | 0.00034 | 2.644 | 0.00 |
KITCHEN | 2923.45 | 3508.14 | 25.17 | 0.130 | 0.188 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00667 | -27.60 | 0.00034 | 0.188 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.74 | 4.74 | 2.64 | 2.64 | 4.7371 | 4.7371 | 4.7371 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.80 | 1.80 | 0.19 | 0.19 | 1.8005 | 1.8005 | 1.8005 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 94734.520 | 73544.303 | 4.737090 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 94734.52 | 93249.75 | 4.737090 | 29.24 | 15.67 | 0.00714254 | 11.05 | 8.66 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 55.8121 | 23.99 | 0.00819904 | 38.6486 | 47321.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 231228.251 | 231228.251 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 231228.25 | 231228.25 | 4.737088 | -6.13 | -6.13 | 0.00359643 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 55.8121 | 21.00 | 0.00770712 | 43.5985 | 15488.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 37488.060 | 28502.172 | 1.800500 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 37488.06 | 31418.21 | 1.800500 | 26.58 | 15.91 | 0.00852774 | 11.78 | 8.98 | 0.00700000 | 31.96 | 0.00630459 | 15.89 | 10.4162 | 25.99 | 0.00878623 | 36.7307 | 21209.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 50770.224 | 50770.224 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 50770.22 | 50770.22 | 1.800502 | 13.35 | 8.64 | 0.00603238 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 10.4162 | 19.00 | 0.00669402 | 42.9339 | 1780.39 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 94734.520 | 73544.303 | 4.737090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1176 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.737088 | 4.98881592 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 94734.52 | 93249.75 | 1.0000 | 4.98881839 | 4.737090 | 29.24 | 15.67 | 0.00714254 | 47635.6 | 11.05 | 8.66 | 0.00700000 | 28752.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94734.52 | 33.40 | 0.00630683 | 16.37 | 2.64386968 | 55.8121 | 23.99 | 0.00819904 | 23.99 | 0.00819904 | 38.6486 | 47321.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 231228.251 | 231228.251 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.737088 | 4.98881592 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 231228.25 | 231228.25 | 1.0000 | 4.98881592 | 4.737088 | -6.13 | -6.13 | 0.00359643 | 2798.6 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 231228.25 | -27.60 | 0.00034190 | -27.60 | 2.64386968 | 55.8121 | 21.00 | 0.00770712 | 21.00 | 0.00770712 | 43.5985 | 15488.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37488.060 | 28502.172 | 1.800500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6926 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.800502 | 1.89618086 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 37488.06 | 31418.21 | 1.0000 | 1.89617835 | 1.800500 | 26.58 | 15.91 | 0.00852774 | 48459.2 | 11.78 | 8.98 | 0.00700000 | 29498.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37488.06 | 31.96 | 0.00630459 | 15.89 | 0.18754328 | 10.4162 | 25.96 | 0.00878623 | 25.99 | 0.00878623 | 36.7307 | 21209.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50770.224 | 50770.224 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.800502 | 1.89618086 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 50770.22 | 50770.22 | 1.0000 | 1.89618086 | 1.800502 | 13.35 | 8.64 | 0.00603238 | 28655.5 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50770.22 | -27.60 | 0.00034190 | -27.60 | 0.18754328 | 10.4162 | 18.12 | 0.00669402 | 19.00 | 0.00669402 | 42.9339 | 1780.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 2.64 | 4.74 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.19 | 1.80 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2732.17 | 5221.67 | 1190.00 |
KITCHEN | 7064.67 | 4377.17 | 4286.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7187.00 | 7132.83 | 5279.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 15.83 | 42.17 | 0.17 | 0.00 |
KITCHEN | 0.00 | 332.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 15.83 | 335.67 | 0.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 8.503 | 0.977 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 4.923 | 0.081 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 8.072 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 1.573 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 2.6439 | 2.644 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1242 | 0.053 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 2.7680 | 2.697 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 70029874.02 | 0.00 | 70029874.02 | 8116251.60 | 78146125.61 | 83377074.30 | 1459.62 | 7126.55 | 173.83 | 384.88 |
KITCHEN | 15757776.92 | 0.00 | 15757776.92 | 392802.82 | 16150579.73 | 5914364.89 | 996.67 | 1821.26 | 5942.06 | 1042.81 |
Total Facility | 85787650.94 | 0.00 | 85787650.94 | 8509054.41 | 94296705.35 | 89291439.19 | 1460.00 | 7176.46 | 5983.81 | 1108.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 2.6522 | 0.0000 | 2.6522 | 0.3044 | 2.9566 | 2.6439 | 0.00 | 7013.71 | 173.29 |
KITCHEN | 0.5650 | 0.0000 | 0.5650 | 0.0093 | 0.5743 | 0.1875 | 0.00 | 1789.64 | 5397.36 |
Total Facility | 3.2172 | 0.0000 | 3.2172 | 0.3137 | 3.5309 | 2.8314 | 0.00 | 7055.46 | 5439.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 77670383.90 | 0.00 | 77670383.90 | 83377074.30 | 1459.53 | 0.00 | 7300.47 | 384.90 |
PSZ-AC_2:2 | 17475316.22 | 0.00 | 17475316.22 | 5914364.89 | 955.92 | 8.37 | 7795.70 | 1042.87 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 2.9415 | 0.0000 | 2.9415 | 2.6439 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 0.6266 | 0.0000 | 0.6266 | 0.1875 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 272.39 | 177.75 | 7121.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 5488.45 | 2741.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 3.2931 | 2.9330 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.7654 | 0.2080 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
Electricity:Building | 646.02 | 4774.49 | 01-JAN-01:10 | 35397.39 | 02-JAN-11:10 |
Electricity:Zone:DINING | 264.83 | 1633.21 | 01-JAN-01:10 | 13902.52 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 629.17 | 4365.45 | 01-JAN-01:10 | 33032.24 | 02-JAN-11:10 |
InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.20 | 3141.27 | 01-JAN-01:10 | 21494.87 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 65.63 | 1123.02 | 10-JAN-23:30 | 3441.39 | 06-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 126.72 | 1134.80 | 11-JAN-01:10 | 6564.99 | 28-JAN-12:00 |
LowTempRefrigeration:Refrigeration:Electricity | 17.31 | 0.00 | 01-JAN-11:10 | 1460.89 | 05-SEP-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 31.47 | 806.36 | 11-JAN-01:10 | 1076.23 | 05-JAN-14:10 |
ElectricityPurchased:Facility | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
ElectricityPurchased:Plant | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
Cogeneration:ElectricityPurchased | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
General:Cogeneration:ElectricityPurchased | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
ElectricityNet:Plant | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
Cogeneration:ElectricityNet | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
General:Cogeneration:ElectricityNet | 1288.04 | 10487.77 | 11-JAN-01:10 | 84480.94 | 17-JUL-17:20 |
Electricity:HVAC | 443.47 | 0.00 | 01-JAN-01:40 | 48890.15 | 17-JUL-17:20 |
Fans:Electricity | 352.96 | 0.00 | 01-JAN-01:40 | 13067.94 | 02-JAN-10:40 |
General:Fans:Electricity | 352.96 | 0.00 | 01-JAN-01:40 | 13067.94 | 02-JAN-10:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 90.51 | 0.00 | 01-JAN-00:10 | 35822.21 | 17-JUL-17:20 |
General:Cooling:Electricity | 90.51 | 0.00 | 01-JAN-00:10 | 35822.21 | 17-JUL-17:20 |
ExteriorLights:Electricity | 71.82 | 0.00 | 01-JAN-08:20 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 71.82 | 0.00 | 01-JAN-08:20 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 77.50 | 0.00 | 01-JAN-01:10 | 4791.42 | 11-JAN-07:20 |
Water Heater:WaterSystems:Electricity | 77.50 | 0.00 | 01-JAN-01:10 | 4791.42 | 11-JAN-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 14-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 14-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1729.68 | 2863.57 | 11-JAN-01:10 | 310331.80 | 28-JAN-04:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 866.65 | 0.00 | 01-JAN-01:10 | 291770.66 | 06-JAN-04:30 |
Heating:NaturalGas | 866.65 | 0.00 | 01-JAN-01:10 | 291770.66 | 06-JAN-04:30 |
General:Heating:NaturalGas | 866.65 | 0.00 | 01-JAN-01:10 | 291770.66 | 06-JAN-04:30 |
NaturalGas:Plant | 393.24 | 1053.32 | 06-JAN-04:10 | 35034.57 | 22-FEB-19:40 |
WaterSystems:NaturalGas | 393.24 | 1053.32 | 06-JAN-04:10 | 35034.57 | 22-FEB-19:40 |
Water Heater:WaterSystems:NaturalGas | 393.24 | 1053.32 | 06-JAN-04:10 | 35034.57 | 22-FEB-19:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 29-NOV-07:50 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 29-NOV-07:50 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2044.96 | 3389.38 | 11-JAN-01:10 | 254568.58 | 29-DEC-04:30 |
EnergyTransfer:Building | 708.63 | 1694.69 | 11-JAN-01:10 | 66667.93 | 26-NOV-12:00 |
EnergyTransfer:Zone:KITCHEN | 400.66 | 1694.69 | 11-JAN-01:10 | 23623.43 | 17-JUL-11:00 |
Refrigeration:EnergyTransfer | 157.45 | 3224.19 | 10-JAN-23:30 | 7834.84 | 06-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.73 | 1612.09 | 10-JAN-23:30 | 3917.42 | 06-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 78.73 | 1612.09 | 10-JAN-23:30 | 3917.42 | 06-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.73 | 1612.09 | 10-JAN-23:30 | 3917.42 | 06-JAN-11:40 |
EnergyTransfer:Plant | 358.34 | 1694.69 | 11-JAN-01:10 | 21901.65 | 09-FEB-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.55 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 63.18 | 1429.07 | 11-JAN-01:10 | 2238.70 | 05-JAN-14:10 |
EnergyTransfer:Zone:DINING | 307.97 | 0.00 | 01-JAN-01:10 | 48545.95 | 26-NOV-12:00 |
Heating:EnergyTransfer | 17.71 | 0.00 | 01-JAN-00:10 | 23325.15 | 26-NOV-12:00 |
Heating:EnergyTransfer:Zone:DINING | 17.70 | 0.00 | 01-JAN-00:10 | 23325.15 | 26-NOV-12:00 |
General:Heating:EnergyTransfer | 17.71 | 0.00 | 01-JAN-00:10 | 23325.15 | 26-NOV-12:00 |
General:Heating:EnergyTransfer:Zone:DINING | 17.70 | 0.00 | 01-JAN-00:10 | 23325.15 | 26-NOV-12:00 |
Cooling:EnergyTransfer | 612.19 | 0.00 | 01-JAN-01:40 | 55889.92 | 17-JUL-17:30 |
Cooling:EnergyTransfer:Zone:DINING | 290.27 | 0.00 | 01-JAN-01:10 | 37293.79 | 17-JUL-17:30 |
General:Cooling:EnergyTransfer | 612.19 | 0.00 | 01-JAN-01:40 | 55889.92 | 17-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:DINING | 290.27 | 0.00 | 01-JAN-01:10 | 37293.79 | 17-JUL-17:30 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 579.20 | 27-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 579.20 | 27-JAN-04:20 |
Cooling:EnergyTransfer:Zone:KITCHEN | 321.93 | 0.00 | 01-JAN-01:40 | 19759.41 | 17-JUL-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 321.93 | 0.00 | 01-JAN-01:40 | 19759.41 | 17-JUL-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 279.61 | 0.00 | 01-JAN-01:10 | 19195.05 | 15-FEB-07:50 |
PlantLoopHeatingDemand:Plant | 279.61 | 0.00 | 01-JAN-01:10 | 19195.05 | 15-FEB-07:50 |
WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19195.05 | 15-FEB-07:50 |
General:WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19195.05 | 15-FEB-07:50 |
EnergyTransfer:HVAC | 977.99 | 0.00 | 01-JAN-01:40 | 232271.78 | 29-DEC-04:30 |
HeatingCoils:EnergyTransfer | 686.82 | 0.00 | 01-JAN-01:10 | 231228.25 | 06-JAN-04:30 |
CoolingCoils:EnergyTransfer | 291.17 | 0.00 | 01-JAN-00:10 | 109633.59 | 17-JUL-17:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19195.05 | 15-FEB-07:50 |
WaterUse:WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19195.05 | 15-FEB-07:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 17.705 | -290.263 | 0.000 | 0.000 | 232.177 | 139.549 | 93.957 | 44.372 | 0.000 | 3.143 | 0.000 | 0.000 | -43.060 | 0.000 | -124.877 | -72.703 |
KITCHEN | 0.000 | 0.000 | 0.000 | -321.920 | 0.000 | 0.000 | 4.778 | 28.902 | 297.857 | 0.000 | 0.000 | 0.039 | 0.000 | 0.000 | 0.000 | 0.000 | -8.324 | -1.332 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.043 | 27.225 | 0.000 | 0.000 | 0.000 | -33.267 | -0.000 |
Total Facility | 0.000 | 0.000 | 17.705 | -612.183 | 0.000 | 0.000 | 236.955 | 168.451 | 391.814 | 44.372 | 0.000 | 9.224 | 27.226 | 0.000 | -43.060 | 0.000 | -166.468 | -74.036 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 11-JAN-00:01 | 0.00 | 0.00 | 0.00 | -121674.73 | 0.00 | 0.00 | 1157.80 | 1150.48 | 543.07 | 0.00 | 0.00 | 0.00 | 127159.66 | 0.00 | -6200.66 | 0.00 | -2135.63 | 0.00 |
KITCHEN | 28-FEB-04:21 | 0.00 | 0.00 | 0.00 | -49453.63 | 0.00 | 0.00 | 0.00 | 238.28 | 3821.48 | 0.00 | 0.00 | 0.00 | 46159.18 | 0.00 | -0.00 | 0.00 | -765.31 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JAN-00:01 | 0.00 | 0.00 | 0.00 | -129863.68 | 0.00 | 0.00 | 1188.41 | 1388.76 | 3382.99 | 0.00 | 0.00 | 660.64 | 133017.76 | 0.00 | -6200.66 | 0.00 | -3574.23 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 30-JAN-04:01 | 0.00 | 0.00 | 127936.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.48 | 905.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4416.24 | 0.00 | -2482.68 | -123093.48 |
KITCHEN | 27-JAN-04:15 | 0.00 | 0.00 | 1158.44 | 0.00 | 0.00 | 0.00 | 0.00 | 238.28 | 3821.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1250.10 | -3968.10 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JAN-04:01 | 0.00 | 0.00 | 127936.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.76 | 4726.60 | 0.00 | 0.00 | 1099.10 | 0.00 | 0.00 | -4416.24 | 0.00 | -4198.15 | -126536.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.7371 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 4.7371 | 0.5581 | 1.0000 | Not calculated | 2.6439 | 0.5581 | ||
PSZ-AC_2:2 | 1.8005 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.8005 | 0.0690 | 1.0000 | Not calculated | 0.1242 | 0.0690 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.7371 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 4.7371 | 1.0000 | 1.0000 | Not calculated | 2.6439 | 0.5581 | ||
PSZ-AC_2:2 | 1.8005 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.8005 | 0.6620 | 1.0000 | Not calculated | 0.1242 | 0.0690 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.007112 | 371.75 | 2.6439 | 1.0000 | 2.6439 | 1.000 | 2.6439 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000381 | 139.41 | 0.1242 | 1.0000 | 0.1242 | 1.000 | 0.1242 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.007112 | 371.7481 | 2.6439 | 2.6439 | 2.6439 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000381 | 139.4052 | 0.1242 | 0.1242 | 0.1242 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7371 | 4.7371 | 4.7371 | No | 2.6439 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8005 | 1.8005 | 1.8005 | No | 0.1242 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.7371 | 4.7371 | 4.7371 | 4.7371 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.8005 | 1.8005 | 1.8005 | 1.8005 | 0.1242 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7371 | 4.7371 | 4.7371 | No | 2.6439 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8005 | 1.8005 | 1.8005 | No | 0.1242 | 0.6620 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.7371 | 4.7371 | 4.7371 | 4.7371 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.8005 | 1.8005 | 1.8005 | 1.8005 | 0.1242 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 866.65 | 291770.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 90.51 | 35822.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 168.45 | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.82 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 352.96 | 13067.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 77.50 | 4791.42 | 393.24 | 35034.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.31 | 1460.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.47 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 526.34 | 1288.04 |
Natural Gas | 469.79 | 1729.68 |
Additional | 0.00 | 0.00 |
Total | 996.13 | 3017.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 329.55 |
Space Heating | 0.00 |
Space Cooling | 177.07 |
Fans (All) | 690.52 |
Service Water Heating | 151.62 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2519.86 |
Subtotal | 2519.86 |
Natural Gas [MJ/m2] | |
Space Heating | 1695.48 |
Service Water Heating | 769.31 |
Miscellaneous (All) | 3383.87 |
Subtotal | 3383.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.58 |
Space Heating | 28.72 |
Space Cooling | 3.00 |
Fans (All) | 11.70 |
Service Water Heating | 15.60 |
Receptacle Equipment | 30.83 |
Miscellaneous | 4.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 6817. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8592.83 | 167.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7484.17 | 472.83 | 391.67 | 403.00 | 8.33 |
Min | 7484.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 472.83 | 391.67 | 403.00 | 8.33 |
Average | 8279.00 | 213.33 | 130.56 | 134.33 | 2.78 |
Sum | 24837.00 | 640.00 | 391.67 | 403.00 | 8.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7016.33 | 1743.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 7664.50 | 607.33 | 204.67 | 168.83 | 114.67 |
Min | 7016.33 | 0.17 | 0.00 | 0.00 | 0.00 |
Max | 8759.83 | 1743.67 | 204.67 | 168.83 | 114.67 |
Average | 7813.56 | 783.72 | 68.22 | 56.28 | 38.22 |
Sum | 23440.67 | 2351.17 | 204.67 | 168.83 | 114.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 824189.33 | 32.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 13565.67 | 5667.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824189.33 | 5667.33 | 0.00 | 0.00 | 0.00 |
Average | 279251.67 | 1900.00 | 0.00 | 0.00 | 0.00 |
Sum | 837755.00 | 5700.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:40
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.826444E+10 | 121677.77 | 11-JAN-00:01 | -31.6 | -31.8 | 0.120016E+11 | 10742.52 | 28-JAN-19:30 | -24.1 | -24.6 |
February | 0.122754E+11 | 95999.66 | 04-FEB-00:01 | -21.0 | -21.3 | 0.109351E+11 | 12936.46 | 27-FEB-12:00 | 17.20 | 6.49 |
March | 0.166991E+11 | 100959.61 | 05-MAR-00:01 | -23.1 | -23.6 | 0.121584E+11 | 11466.75 | 14-MAR-11:00 | 14.40 | 6.37 |
April | 0.216751E+11 | 55882.50 | 28-APR-23:01 | -4.6 | -6.2 | 0.122606E+11 | 14050.28 | 22-APR-18:10 | -4.6 | -6.2 |
May | 0.266569E+11 | 50079.53 | 07-MAY-23:01 | -2.3 | -2.8 | 0.134092E+11 | 14053.37 | 20-MAY-18:40 | 23.33 | 13.71 |
June | 0.335230E+11 | 33840.54 | 25-JUN-04:01 | 7.12 | 4.53 | 0.142221E+11 | 14051.82 | 17-JUN-18:00 | 7.12 | 4.53 |
July | 0.401397E+11 | 37295.46 | 17-JUL-17:37 | 36.10 | 16.77 | 0.150313E+11 | 14052.79 | 22-JUL-18:00 | 22.20 | 12.65 |
August | 0.390570E+11 | 35987.36 | 05-AUG-18:03 | 34.13 | 16.80 | 0.150393E+11 | 14052.93 | 26-AUG-18:00 | 20.60 | 12.09 |
September | 0.329561E+11 | 38064.52 | 18-SEP-23:01 | 2.80 | 2.08 | 0.136553E+11 | 14052.34 | 23-SEP-18:40 | 16.50 | 9.82 |
October | 0.281955E+11 | 47510.77 | 09-OCT-23:01 | -1.1 | -1.4 | 0.128604E+11 | 13102.41 | 28-OCT-18:00 | 13.90 | 7.20 |
November | 0.192718E+11 | 81493.18 | 27-NOV-00:01 | -15.1 | -15.9 | 0.118121E+11 | 13402.37 | 04-NOV-18:30 | -15.1 | -15.9 |
December | 0.115510E+11 | 102325.76 | 29-DEC-00:01 | -23.6 | -23.9 | 0.120008E+11 | 10762.26 | 06-DEC-12:00 | -23.6 | -23.9 |
Annual Sum or Average | 0.290265E+12 | 0.155386E+12 | ||||||||
Minimum of Months | 0.826444E+10 | 33840.54 | -31.6 | -31.8 | 0.109351E+11 | 10742.52 | -24.1 | -24.6 | ||
Maximum of Months | 0.401397E+11 | 121677.77 | 36.10 | 16.80 | 0.150393E+11 | 14053.37 | 23.33 | 13.71 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218733E+11 | 36084.49 | 02-JAN-04:21 | -0.3 | -2.9 | 0.105948E+11 | 6934.82 | 06-JAN-11:09 | -20.2 | -21.1 |
February | 0.208874E+11 | 49445.26 | 28-FEB-04:21 | -2.8 | -3.4 | 0.957609E+10 | 6934.82 | 01-FEB-11:09 | -2.8 | -3.4 |
March | 0.237258E+11 | 49006.97 | 28-MAR-03:21 | -0.6 | -3.4 | 0.106075E+11 | 6934.79 | 27-MAR-10:09 | -0.6 | -3.4 |
April | 0.246423E+11 | 47548.19 | 14-APR-03:21 | 0.30 | 0.18 | 0.102629E+11 | 6934.91 | 07-APR-10:50 | 0.30 | 0.18 |
May | 0.277113E+11 | 48423.97 | 23-MAY-03:21 | -0.6 | -0.8 | 0.106058E+11 | 6934.91 | 02-MAY-10:00 | -0.6 | -0.8 |
June | 0.299383E+11 | 42995.31 | 30-JUN-03:21 | 11.65 | 8.42 | 0.102663E+11 | 6934.91 | 26-JUN-10:00 | 11.65 | 8.42 |
July | 0.329557E+11 | 48358.44 | 12-JUL-03:21 | 8.60 | 4.51 | 0.106028E+11 | 6934.97 | 14-JUL-10:50 | 28.72 | 16.45 |
August | 0.326127E+11 | 45451.43 | 11-AUG-03:21 | 18.30 | 8.29 | 0.106090E+11 | 6934.99 | 11-AUG-10:00 | 28.30 | 12.92 |
September | 0.299468E+11 | 44908.26 | 26-SEP-03:21 | 14.15 | 9.56 | 0.102630E+11 | 6934.95 | 21-SEP-10:00 | 14.15 | 9.56 |
October | 0.287258E+11 | 42949.18 | 20-OCT-03:21 | 5.80 | 2.30 | 0.106027E+11 | 6934.97 | 23-OCT-10:50 | 18.22 | 8.28 |
November | 0.252828E+11 | 49378.01 | 10-NOV-04:21 | -3.3 | -4.3 | 0.102602E+11 | 6934.77 | 06-NOV-11:20 | -3.3 | -4.3 |
December | 0.236267E+11 | 48129.14 | 19-DEC-04:21 | 2.75 | -0.3 | 0.106005E+11 | 6934.82 | 29-DEC-11:09 | -21.4 | -21.9 |
Annual Sum or Average | 0.321929E+12 | 0.124852E+12 | ||||||||
Minimum of Months | 0.208874E+11 | 36084.49 | -3.3 | -4.3 | 0.957609E+10 | 6934.77 | -21.4 | -21.9 | ||
Maximum of Months | 0.329557E+11 | 49445.26 | 18.30 | 9.56 | 0.106090E+11 | 6934.99 | 28.72 | 16.45 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.9 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 | -4.1 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 | 0.55 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 | 13.32 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 | 11.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 | 11.59 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 | 6.94 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 | 1.54 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.00 | 0.00 | -12.4 | -13.9 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.00 | 0.00 | 19.45 | 13.32 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.849086E+10 | 127939.00 | 30-JAN-04:01 | -17.7 |
February | 0.299642E+10 | 120584.22 | 05-FEB-04:01 | -20.0 |
March | 0.167996E+10 | 125646.24 | 06-MAR-04:01 | -18.4 |
April | 0.190221E+09 | 75231.22 | 27-APR-22:52 | -3.3 |
May | 0.106823E+09 | 36558.97 | 08-MAY-03:02 | -2.7 |
June | 1075995.94 | 3128.17 | 20-JUN-04:05 | 7.15 |
July | 116719.77 | 1167.20 | 12-JUL-04:05 | 6.10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 844972.83 | 2341.80 | 29-SEP-04:05 | 8.30 |
October | 18850315.47 | 11874.34 | 10-OCT-03:51 | -5.0 |
November | 0.609106E+09 | 112106.73 | 26-NOV-11:59 | -13.7 |
December | 0.361062E+10 | 106477.64 | 30-DEC-04:01 | -20.1 |
Annual Sum or Average | 0.177049E+11 | |||
Minimum of Months | 0.00 | 0.00 | -20.1 | |
Maximum of Months | 0.849086E+10 | 127939.00 | 18.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 347517.27 | 1158.39 | 27-JAN-04:15 | -27.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 359.70 | 4.20 | 01-JUN-04:03 | 13.12 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 347876.97 | |||
Minimum of Months | 0.00 | 0.00 | -27.4 | |
Maximum of Months | 347517.27 | 1158.39 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117915E+11 | 6902.89 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.106801E+11 | 6902.89 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.119793E+11 | 6902.89 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.114574E+11 | 6902.89 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.118854E+11 | 6902.89 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.115789E+11 | 6902.89 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.117653E+11 | 6902.89 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.119793E+11 | 6902.89 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.114602E+11 | 6902.89 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.117901E+11 | 6902.89 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.114146E+11 | 6902.89 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.117667E+11 | 6902.89 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.139549E+12 | 0.125277E+12 | ||||
Minimum of Months | 0.106801E+11 | 6902.89 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.119793E+11 | 6902.89 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.244214E+10 | 1429.66 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.221197E+10 | 1429.66 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.248103E+10 | 1429.66 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.237295E+10 | 1429.66 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.246159E+10 | 1429.66 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.239811E+10 | 1429.66 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.243671E+10 | 1429.66 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.248103E+10 | 1429.66 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.237352E+10 | 1429.66 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.244186E+10 | 1429.66 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.236408E+10 | 1429.66 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.243700E+10 | 1429.66 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.289020E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.221197E+10 | 1429.66 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.248103E+10 | 1429.66 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.117915E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230579E+11 |
February | 0.272721E+11 | 0.106801E+11 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157965E+11 |
March | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147391E+11 |
April | 0.292871E+11 | 0.114574E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951215E+10 |
May | 0.303219E+11 | 0.118854E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47745029.91 | 0.769845E+10 |
June | 0.295292E+11 | 0.115789E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436105E+09 | 0.374793E+10 |
July | 0.300798E+11 | 0.117653E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130752E+10 | 0.191769E+10 |
August | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984285E+09 | 0.274129E+10 |
September | 0.292871E+11 | 0.114602E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364727E+09 | 0.525463E+10 |
October | 0.300980E+11 | 0.117901E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2295723.03 | 0.886353E+10 |
November | 0.290996E+11 | 0.114146E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127589E+11 |
December | 0.300798E+11 | 0.117667E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187886E+11 |
Annual Sum or Average | 0.356244E+12 | 0.139549E+12 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314268E+10 | 0.124877E+12 |
Minimum of Months | 0.272721E+11 | 0.106801E+11 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191769E+10 |
Maximum of Months | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130752E+10 | 0.230579E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.244214E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128698E+10 |
February | 0.732850E+09 | 0.221197E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100965E+10 |
March | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910581E+09 |
April | 0.786997E+09 | 0.237295E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625792E+09 |
May | 0.814802E+09 | 0.246159E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 596339.70 | 0.620097E+09 |
June | 0.793501E+09 | 0.239811E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 4902195.44 | 0.338481E+09 |
July | 0.808298E+09 | 0.243671E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 14542198.99 | 0.211406E+09 |
August | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 13103915.85 | 0.251022E+09 |
September | 0.786997E+09 | 0.237352E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 5537877.26 | 0.462279E+09 |
October | 0.808786E+09 | 0.244186E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627127E+09 |
November | 0.781956E+09 | 0.236408E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900476E+09 |
December | 0.808298E+09 | 0.243700E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108003E+10 |
Annual Sum or Average | 0.957291E+10 | 0.289020E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 38682527.24 | 0.832393E+10 |
Minimum of Months | 0.732850E+09 | 0.221197E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211406E+09 |
Maximum of Months | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 14542198.99 | 0.128698E+10 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518760E+09 | 0.139125E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427969E+09 | 0.168458E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545809E+09 | 0.270184E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466470E+09 | 0.314947E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351812E+09 | 0.424474E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312923E+09 | 0.475599E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456691E+09 | 0.484351E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528934E+09 | 0.401989E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533115E+09 | 0.255921E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659056E+09 | 0.181731E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612946E+09 | 0.117296E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628052E+09 | 0.926756E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604254E+10 | 0.332675E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312923E+09 | 0.926756E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659056E+09 | 0.484351E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 6902.89 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 34225.99 | 10-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 6902.89 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 28884.24 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 6902.89 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 27762.74 | 04-MAR-19:55 |
April | 30255.31 | 01-APR-18:10 | 6902.89 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 15651.70 | 28-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 6902.89 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1986.89 | 20-MAY-17:10 | 13114.72 | 22-MAY-19:00 |
June | 30255.31 | 03-JUN-18:10 | 6902.89 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3968.98 | 29-JUN-13:00 | 9088.94 | 16-JUN-11:02 |
July | 30255.31 | 01-JUL-18:10 | 6902.89 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6343.63 | 17-JUL-17:03 | 5586.86 | 07-JUL-19:53 |
August | 30255.31 | 05-AUG-18:10 | 6902.89 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5905.51 | 05-AUG-18:03 | 7597.13 | 17-AUG-12:00 |
September | 30255.31 | 02-SEP-18:10 | 6902.89 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4734.81 | 02-SEP-17:03 | 10691.32 | 18-SEP-20:00 |
October | 30255.31 | 07-OCT-18:10 | 6902.89 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.09 | 18-OCT-14:00 | 13223.35 | 31-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 6902.89 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 20009.77 | 26-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 6902.89 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 28099.22 | 29-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 6902.89 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5586.86 | |||||
Maximum of Months | 30255.31 | 6902.89 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 6343.63 | 34225.99 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1429.66 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2176.27 | 31-JAN-01:10 |
February | 813.01 | 04-FEB-19:10 | 1429.66 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2042.55 | 17-FEB-04:20 |
March | 813.01 | 04-MAR-19:10 | 1429.66 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2329.74 | 17-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 1429.66 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1637.47 | 27-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 1429.66 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 40.26 | 20-MAY-15:53 | 3183.13 | 22-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 1429.66 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 95.46 | 29-JUN-15:00 | 1424.19 | 14-JUN-02:00 |
July | 813.01 | 01-JUL-18:10 | 1429.66 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 103.54 | 25-JUL-15:00 | 792.98 | 05-JUL-00:40 |
August | 813.01 | 05-AUG-18:10 | 1429.66 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 95.12 | 11-AUG-14:00 | 1067.61 | 23-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 1429.66 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 96.79 | 02-SEP-13:55 | 1837.40 | 12-SEP-03:20 |
October | 813.01 | 07-OCT-18:10 | 1429.66 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1457.04 | 31-OCT-00:40 |
November | 813.01 | 04-NOV-18:10 | 1429.66 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1936.51 | 28-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 1429.66 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3234.49 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1429.66 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 792.98 | ||||||
Maximum of Months | 813.01 | 1429.66 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 103.54 | 3234.49 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3237.33 | 11-JAN-08:31 | 5759.63 | 29-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2043.66 | 05-FEB-23:53 | 5250.75 | 23-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1785.09 | 01-MAR-07:00 | 6053.22 | 07-MAR-14:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.88 | 11-APR-06:53 | 6994.75 | 22-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1413.77 | 13-MAY-03:51 | 8082.02 | 09-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.68 | 17-JUN-05:43 | 7017.06 | 03-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1489.20 | 03-JUL-14:40 | 7894.95 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.36 | 03-AUG-04:40 | 6884.99 | 03-AUG-12:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1700.87 | 02-SEP-03:51 | 6082.49 | 17-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1434.99 | 27-OCT-06:55 | 4522.91 | 06-OCT-12:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.01 | 21-NOV-08:65 | 4025.84 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.38 | 29-DEC-06:00 | 4280.62 | 29-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.68 | 4025.84 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3237.33 | 8082.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 121677.77 | 11-JAN-00:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2135.63 |
February | 95999.66 | 04-FEB-00:01 | 16808.50 | 15339.75 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.28 |
March | 100959.61 | 05-MAR-00:01 | 16808.50 | 15339.75 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1744.94 |
April | 55882.50 | 28-APR-23:01 | 16808.50 | 15339.75 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 838.86 |
May | 50079.53 | 07-MAY-23:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1782.01 |
June | 33840.54 | 25-JUN-04:01 | 0.00 | 8053.37 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.91 |
July | 37295.46 | 17-JUL-17:37 | 80680.82 | 20708.67 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 6321.54 | 0.00 |
August | 35987.36 | 05-AUG-18:03 | 121021.23 | 27611.56 | 21240.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5905.51 | 0.00 |
September | 38064.52 | 18-SEP-23:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 958.21 |
October | 47510.77 | 09-OCT-23:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.80 |
November | 81493.18 | 27-NOV-00:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.55 |
December | 102325.76 | 29-DEC-00:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 33840.54 | 0.00 | 8053.37 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 121677.77 | 121021.23 | 27611.56 | 21240.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6321.54 | 2135.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36084.49 | 02-JAN-04:21 | 0.00 | 1667.94 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49445.26 | 28-FEB-04:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 765.31 |
March | 49006.97 | 28-MAR-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 652.13 |
April | 47548.19 | 14-APR-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 843.93 |
May | 48423.97 | 23-MAY-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 472.89 |
June | 42995.31 | 30-JUN-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 318.26 |
July | 48358.44 | 12-JUL-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 300.29 |
August | 45451.43 | 11-AUG-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 182.85 |
September | 44908.26 | 26-SEP-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 204.44 |
October | 42949.18 | 20-OCT-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 383.85 |
November | 49378.01 | 10-NOV-04:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 879.82 |
December | 48129.14 | 19-DEC-04:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 875.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36084.49 | 0.00 | 1667.94 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49445.26 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 879.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.46 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.38 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.32 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.42 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.44 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.57 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.16 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.56 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.27 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.07 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.68 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.68 | 671.38 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.103258E+12 | 53603.65 | 28-JAN-17:00 | 0.289562E+12 | 310331.80 | 28-JAN-04:10 |
February | 0.928412E+11 | 54923.69 | 27-FEB-13:00 | 0.197632E+12 | 248755.52 | 01-FEB-04:19 |
March | 0.102151E+12 | 53236.13 | 04-MAR-18:49 | 0.190575E+12 | 195890.18 | 04-MAR-21:40 |
April | 0.989890E+11 | 61653.94 | 07-APR-18:00 | 0.129203E+12 | 124391.59 | 28-APR-06:30 |
May | 0.106231E+12 | 70385.36 | 20-MAY-16:10 | 0.111364E+12 | 118351.86 | 08-MAY-06:30 |
June | 0.112902E+12 | 76062.07 | 20-JUN-17:40 | 0.774393E+11 | 89330.81 | 16-JUN-06:19 |
July | 0.127845E+12 | 84480.94 | 17-JUL-17:19 | 0.718956E+11 | 58608.36 | 08-JUL-05:10 |
August | 0.124031E+12 | 80296.13 | 05-AUG-17:00 | 0.728678E+11 | 58351.52 | 17-AUG-06:40 |
September | 0.111382E+12 | 79487.22 | 02-SEP-17:10 | 0.829324E+11 | 87316.04 | 19-SEP-06:00 |
October | 0.104928E+12 | 66310.79 | 18-OCT-10:00 | 0.111956E+12 | 127432.04 | 10-OCT-06:40 |
November | 0.999210E+11 | 53563.99 | 30-NOV-17:49 | 0.158382E+12 | 164047.65 | 27-NOV-07:30 |
December | 0.103557E+12 | 53588.34 | 29-DEC-17:40 | 0.235868E+12 | 297349.61 | 29-DEC-04:30 |
Annual Sum or Average | 0.128804E+13 | 0.172968E+13 | ||||
Minimum of Months | 0.928412E+11 | 53236.13 | 0.718956E+11 | 58351.52 | ||
Maximum of Months | 0.127845E+12 | 84480.94 | 0.289562E+12 | 310331.80 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.142337E+11 | 0.779074E+10 | 0.391293E+11 | 0.00 | 0.298789E+11 | 37879553.69 | 0.00 | 94801117.66 | 0.00 | 0.00 | 0.00 | 0.656203E+10 | 0.00 |
February | 0.128921E+11 | 0.643643E+10 | 0.353426E+11 | 0.00 | 0.270073E+11 | 34213790.43 | 0.00 | 0.174354E+09 | 0.00 | 0.00 | 0.00 | 0.593664E+10 | 0.00 |
March | 0.144603E+11 | 0.628534E+10 | 0.391293E+11 | 0.00 | 0.298950E+11 | 37879553.69 | 0.00 | 0.153202E+09 | 0.00 | 0.00 | 0.00 | 0.662831E+10 | 0.00 |
April | 0.138304E+11 | 0.523320E+10 | 0.378671E+11 | 0.00 | 0.289797E+11 | 36657632.61 | 0.00 | 0.129284E+10 | 0.00 | 0.00 | 0.00 | 0.636674E+10 | 0.00 |
May | 0.143470E+11 | 0.465357E+10 | 0.391293E+11 | 0.00 | 0.299610E+11 | 37879553.69 | 0.00 | 0.592731E+10 | 0.00 | 0.00 | 0.00 | 0.659391E+10 | 0.00 |
June | 0.139770E+11 | 0.410964E+10 | 0.378671E+11 | 0.00 | 0.290610E+11 | 36657632.61 | 0.00 | 0.160126E+11 | 0.00 | 0.00 | 0.00 | 0.640963E+10 | 0.00 |
July | 0.142020E+11 | 0.442831E+10 | 0.391293E+11 | 0.00 | 0.301273E+11 | 37879553.69 | 0.00 | 0.277607E+11 | 0.00 | 0.00 | 0.00 | 0.655059E+10 | 0.00 |
August | 0.144603E+11 | 0.506838E+10 | 0.391293E+11 | 0.00 | 0.300972E+11 | 37879553.69 | 0.00 | 0.229962E+11 | 0.00 | 0.00 | 0.00 | 0.662897E+10 | 0.00 |
September | 0.138337E+11 | 0.571120E+10 | 0.378671E+11 | 0.00 | 0.290798E+11 | 36657632.61 | 0.00 | 0.130684E+11 | 0.00 | 0.00 | 0.00 | 0.636776E+10 | 0.00 |
October | 0.142320E+11 | 0.677432E+10 | 0.391293E+11 | 0.00 | 0.299592E+11 | 37879553.69 | 0.00 | 0.267312E+10 | 0.00 | 0.00 | 0.00 | 0.655744E+10 | 0.00 |
November | 0.137787E+11 | 0.732374E+10 | 0.378671E+11 | 0.00 | 0.289796E+11 | 36657632.61 | 0.00 | 0.217804E+09 | 0.00 | 0.00 | 0.00 | 0.634784E+10 | 0.00 |
December | 0.142037E+11 | 0.800776E+10 | 0.391293E+11 | 0.00 | 0.299345E+11 | 37879553.69 | 0.00 | 0.139703E+09 | 0.00 | 0.00 | 0.00 | 0.655174E+10 | 0.00 |
Annual Sum or Average | 0.168451E+12 | 0.718226E+11 | 0.460716E+12 | 0.00 | 0.352960E+12 | 0.446001E+09 | 0.00 | 0.905111E+11 | 0.00 | 0.00 | 0.00 | 0.775016E+11 | 0.00 |
Minimum of Months | 0.128921E+11 | 0.410964E+10 | 0.353426E+11 | 0.00 | 0.270073E+11 | 34213790.43 | 0.00 | 94801117.66 | 0.00 | 0.00 | 0.00 | 0.593664E+10 | 0.00 |
Maximum of Months | 0.144603E+11 | 0.800776E+10 | 0.391293E+11 | 0.00 | 0.301273E+11 | 37879553.69 | 0.00 | 0.277607E+11 | 0.00 | 0.00 | 0.00 | 0.662897E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.213354E+12 | 0.00 | 0.363077E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.128231E+12 | 0.00 | 0.333629E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.113791E+12 | 0.00 | 0.368845E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.563087E+11 | 0.00 | 0.342820E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.377219E+11 | 0.00 | 0.337423E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.781917E+10 | 0.00 | 0.310075E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.169670E+10 | 0.00 | 0.302992E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.295205E+10 | 0.00 | 0.300161E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.151244E+11 | 0.00 | 0.291953E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.407527E+11 | 0.00 | 0.313040E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.877770E+11 | 0.00 | 0.319920E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.161124E+12 | 0.00 | 0.348441E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.866652E+12 | 0.00 | 0.393237E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.169670E+10 | 0.00 | 0.291953E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.213354E+12 | 0.00 | 0.368845E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8332.55 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13067.94 | 02-JAN-10:39 | 17.86 | 14-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 8332.55 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13067.94 | 01-FEB-09:20 | 17.86 | 27-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 8332.55 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13067.94 | 01-MAR-08:20 | 17.86 | 01-MAR-00:20 | 0.00 | 01-MAR-00:10 |
April | 8332.55 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13067.94 | 01-APR-12:20 | 17.86 | 13-APR-08:39 | 0.00 | 01-APR-00:10 |
May | 8332.55 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13067.94 | 01-MAY-07:10 | 17.86 | 15-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 8332.55 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13067.94 | 01-JUN-14:20 | 17.86 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 8332.55 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13067.94 | 01-JUL-07:19 | 17.86 | 03-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 8332.55 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13067.94 | 01-AUG-07:40 | 17.86 | 22-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 8332.55 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13067.94 | 01-SEP-04:10 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 8332.55 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13067.94 | 01-OCT-04:10 | 17.86 | 06-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 8332.55 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13067.94 | 02-NOV-09:30 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 8332.55 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13067.94 | 07-DEC-00:20 | 17.86 | 01-DEC-00:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 8332.55 | 4578.48 | 24699.69 | 0.00 | 13067.94 | 17.86 | 0.00 | ||||||
Maximum of Months | 8332.55 | 4578.48 | 24699.69 | 0.00 | 13067.94 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1565.87 | 24-JAN-04:30 | 0.00 | 0.00 | 0.00 | 4791.42 | 11-JAN-07:19 | 0.00 |
February | 7188.03 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 4787.63 | 01-FEB-07:19 | 0.00 |
March | 1352.33 | 28-MAR-03:30 | 0.00 | 0.00 | 0.00 | 4786.56 | 06-MAR-07:19 | 0.00 |
April | 13272.72 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 4784.45 | 11-APR-18:40 | 0.00 |
May | 21557.54 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 4784.28 | 31-MAY-18:40 | 0.00 |
June | 27481.86 | 20-JUN-17:19 | 0.00 | 0.00 | 0.00 | 4784.25 | 29-JUN-18:49 | 0.00 |
July | 35822.21 | 17-JUL-17:19 | 0.00 | 0.00 | 0.00 | 4784.21 | 07-JUL-18:10 | 0.00 |
August | 32357.31 | 05-AUG-18:10 | 0.00 | 0.00 | 0.00 | 4784.31 | 18-AUG-18:40 | 0.00 |
September | 31044.63 | 02-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4784.18 | 07-SEP-18:10 | 0.00 |
October | 17039.27 | 18-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4784.27 | 03-OCT-18:40 | 0.00 |
November | 2021.40 | 17-NOV-04:30 | 0.00 | 0.00 | 0.00 | 4784.12 | 29-NOV-07:49 | 0.00 |
December | 1531.34 | 10-DEC-04:30 | 0.00 | 0.00 | 0.00 | 4786.86 | 29-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1352.33 | 0.00 | 0.00 | 0.00 | 4784.12 | 0.00 | ||
Maximum of Months | 35822.21 | 0.00 | 0.00 | 0.00 | 4791.42 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 53603.65 | 28-JAN-17:00 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 13067.94 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 54923.69 | 27-FEB-13:00 | 8332.55 | 21481.47 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 7095.80 | 0.00 |
March | 53236.13 | 04-MAR-18:49 | 8332.55 | 20676.91 | 4578.48 | 0.00 | 13067.94 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 61653.94 | 07-APR-18:00 | 8332.55 | 19067.80 | 4578.48 | 0.00 | 13067.94 | 17.86 | 0.00 | 10082.98 | 0.00 |
May | 70385.36 | 20-MAY-16:10 | 8332.55 | 22286.02 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 21381.01 | 0.00 |
June | 76062.07 | 20-JUN-17:40 | 8332.55 | 20676.91 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 27402.00 | 0.00 |
July | 84480.94 | 17-JUL-17:19 | 8332.55 | 20676.91 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 35822.21 | 0.00 |
August | 80296.13 | 05-AUG-17:00 | 8332.55 | 20676.91 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 31742.04 | 0.00 |
September | 79487.22 | 02-SEP-17:10 | 8332.55 | 20676.91 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 31044.63 | 0.00 |
October | 66310.79 | 18-OCT-10:00 | 8332.55 | 24699.69 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 13537.06 | 0.00 |
November | 53563.99 | 30-NOV-17:49 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 13067.94 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 53588.34 | 29-DEC-17:40 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 13067.94 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 53236.13 | 8332.55 | 19067.80 | 0.00 | 0.00 | 13067.94 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84480.94 | 8332.55 | 24699.69 | 4578.48 | 0.00 | 13067.94 | 17.86 | 0.00 | 35822.21 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 291770.66 | 06-JAN-04:30 | 0.00 | 34792.94 | 30-JAN-19:49 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 243176.57 | 01-FEB-04:19 | 0.00 | 35034.57 | 22-FEB-19:40 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 158310.75 | 04-MAR-23:00 | 0.00 | 34939.32 | 02-MAR-07:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 95976.96 | 29-APR-05:10 | 0.00 | 33841.70 | 03-APR-18:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 75856.72 | 08-MAY-05:10 | 0.00 | 31926.71 | 02-MAY-18:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 55601.41 | 17-JUN-04:00 | 0.00 | 29295.04 | 01-JUN-06:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 38004.46 | 08-JUL-04:19 | 0.00 | 26443.40 | 03-JUL-18:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 34229.95 | 18-AUG-04:19 | 0.00 | 24712.00 | 01-AUG-06:49 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 58407.83 | 17-SEP-05:00 | 0.00 | 25884.83 | 29-SEP-06:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 87418.46 | 10-OCT-06:10 | 0.00 | 28548.10 | 31-OCT-18:49 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 132535.44 | 26-NOV-07:00 | 0.00 | 31310.52 | 30-NOV-19:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 291770.66 | 29-DEC-04:30 | 0.00 | 33482.69 | 29-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 34229.95 | 0.00 | 24712.00 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 291770.66 | 0.00 | 35034.57 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
February | 2.33 | 19.83 | 0.17 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
March | 1.83 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
April | 0.33 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
May | 0.50 | 20.39 | 0.00 | 20.39 | 0.17 | 21.43 | 0.00 | 21.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.68 | 0.00 | 24.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 24.77 | 0.00 | 24.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 24.77 | 0.00 | 24.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 24.74 | 0.00 | 24.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
December | 2.33 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
Annual Sum or Average | 15.83 | 19.40 | 0.17 | 19.39 | 42.17 | 23.28 | 0.00 | 23.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 20.39 | 0.17 | 20.39 | 14.17 | 24.77 | 0.00 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.30 | 0.00 | 27.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.27 | 0.00 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.39 | 0.00 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.61 | 0.00 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.85 | 0.00 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 28.31 | 0.00 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.57 | 0.00 | 28.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.58 | 0.00 | 28.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 28.37 | 0.00 | 28.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.09 | 0.00 | 28.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 27.68 | 0.00 | 27.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.35 | 0.00 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 332.83 | 27.92 | 0.00 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.27 | 0.00 | 27.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.58 | 0.00 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.74 | 338.00 | 20.66 | 338.00 | 20.62 |
February | 547.50 | 20.78 | 190.00 | 20.64 | 190.00 | 20.56 |
March | 612.00 | 20.75 | 174.00 | 20.60 | 174.00 | 20.50 |
April | 532.83 | 20.93 | 76.50 | 20.76 | 70.50 | 20.59 |
May | 442.17 | 21.06 | 134.33 | 21.42 | 35.17 | 21.26 |
June | 219.00 | 21.36 | 307.83 | 22.81 | 6.17 | 22.75 |
July | 107.33 | 21.63 | 461.00 | 23.54 | 4.50 | 23.54 |
August | 148.33 | 21.45 | 404.50 | 23.29 | 1.33 | 23.28 |
September | 296.83 | 21.26 | 261.50 | 22.40 | 19.00 | 22.33 |
October | 513.50 | 21.03 | 64.00 | 21.02 | 30.83 | 20.85 |
November | 583.17 | 20.89 | 94.17 | 20.71 | 94.17 | 20.57 |
December | 609.00 | 20.74 | 226.33 | 20.63 | 226.33 | 20.56 |
Annual Sum or Average | 5221.67 | 20.93 | 2732.17 | 21.39 | 1190.00 | 21.22 |
Minimum of Months | 107.33 | 20.74 | 64.00 | 20.60 | 1.33 | 20.50 |
Maximum of Months | 612.00 | 21.63 | 461.00 | 23.54 | 338.00 | 23.54 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 272.33 | 25.14 | 543.17 | 25.66 | 215.83 | 25.72 |
February | 208.83 | 25.84 | 529.33 | 25.93 | 198.33 | 25.94 |
March | 277.50 | 25.89 | 599.33 | 25.95 | 267.83 | 25.96 |
April | 299.83 | 25.99 | 590.00 | 25.99 | 299.83 | 25.99 |
May | 399.50 | 25.99 | 611.00 | 25.99 | 399.50 | 25.99 |
June | 467.17 | 26.00 | 592.00 | 26.00 | 467.17 | 26.00 |
July | 537.00 | 26.00 | 609.00 | 26.00 | 537.00 | 26.00 |
August | 497.67 | 26.00 | 612.00 | 26.00 | 497.67 | 26.00 |
September | 461.83 | 26.00 | 590.00 | 26.00 | 461.83 | 26.00 |
October | 398.17 | 25.99 | 610.00 | 25.99 | 398.17 | 25.99 |
November | 310.33 | 25.99 | 589.17 | 25.99 | 310.17 | 25.99 |
December | 247.00 | 25.82 | 589.67 | 25.92 | 233.50 | 25.94 |
Annual Sum or Average | 4377.17 | 25.92 | 7064.67 | 25.96 | 4286.83 | 25.97 |
Minimum of Months | 208.83 | 25.14 | 529.33 | 25.66 | 198.33 | 25.72 |
Maximum of Months | 537.00 | 26.00 | 612.00 | 26.00 | 537.00 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73630 | 13.23694 | -0.6157 | 14.13051 |
February | 551.00000 | 20.80349 | 16.71422 | -0.5161 | 11.93689 |
March | 612.00000 | 20.74813 | 18.28285 | -0.4976 | 11.34440 |
April | 590.00000 | 21.22157 | 23.95257 | -0.3188 | 9.35576 |
May | 611.00000 | 21.85509 | 28.20510 | -1.1604 | 36.99737 |
June | 592.00000 | 22.96135 | 35.63519 | -0.6638 | 18.68834 |
July | 609.00000 | 23.53072 | 37.77936 | -0.4120 | 11.10097 |
August | 612.00000 | 23.33500 | 34.08342 | -0.5079 | 13.76555 |
September | 590.00000 | 22.56902 | 35.47656 | -0.7887 | 23.49371 |
October | 610.00000 | 21.47424 | 26.82628 | -0.1777 | 7.92766 |
November | 591.00000 | 20.92231 | 20.05198 | -0.4087 | 9.86070 |
December | 609.00000 | 20.74380 | 15.67254 | -0.5479 | 12.34418 |
Annual Sum or Average | 7187.00000 | 21.74778 | 25.53106 | -0.5517 | 15.10447 |
Minimum of Months | 551.00000 | 20.73630 | 13.23694 | -1.1604 | 7.92766 |
Maximum of Months | 612.00000 | 23.53072 | 37.77936 | -0.1777 | 36.99737 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.53050 | 38.70774 | 0.78682 | 20.24205 |
February | 551.00000 | 25.86812 | 34.77334 | 0.87421 | 21.83825 |
March | 612.00000 | 25.92344 | 33.56669 | 0.88893 | 22.27491 |
April | 590.00000 | 25.99401 | 33.22697 | 0.94454 | 24.22937 |
May | 611.00000 | 25.99563 | 36.86998 | 0.39947 | 9.27556 |
June | 592.00000 | 25.99751 | 42.35552 | 0.54132 | 12.11362 |
July | 609.00000 | 25.99945 | 46.31614 | 0.63447 | 14.33322 |
August | 612.00000 | 25.99863 | 43.31050 | 0.59650 | 13.45430 |
September | 590.00000 | 25.99650 | 40.57529 | 0.52936 | 11.83668 |
October | 610.00000 | 25.99347 | 33.05806 | 1.02158 | 27.38114 |
November | 591.00000 | 25.98018 | 30.56633 | 0.94099 | 24.00809 |
December | 609.00000 | 25.87996 | 34.14265 | 0.88246 | 22.10129 |
Annual Sum or Average | 7187.00000 | 25.92965 | 37.31676 | 0.75247 | 18.56746 |
Minimum of Months | 551.00000 | 25.53050 | 30.56633 | 0.39947 | 9.27556 |
Maximum of Months | 612.00000 | 25.99945 | 46.31614 | 1.02158 | 27.38114 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 52086001.69 | 18700565.10 | 2.67 | 52086001.69 | -0.0 | 0.00 | 0.10 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 | 7597.85 | 27-FEB-14:00 | 7597.85 | 27-FEB-14:00 | 0.00 | 27-FEB-14:50 | 2710.82 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.115197E+10 | 0.404561E+09 | 29.83 | 0.115087E+10 | 1099011.18 | 0.00 | 0.28 | 07-APR-12:53 | 0.00 | 01-APR-00:01 | 21567.76 | 07-APR-12:53 | 21567.76 | 07-APR-12:53 | 424.97 | 24-APR-13:00 | 7375.39 | 07-APR-12:53 | 0.00 | 01-APR-00:01 |
May | 0.813055E+10 | 0.276460E+10 | 126.08 | 0.781612E+10 | 0.314434E+09 | 0.00 | 0.55 | 20-MAY-17:05 | 0.00 | 01-MAY-00:01 | 45274.96 | 20-MAY-17:05 | 45274.96 | 20-MAY-17:05 | 5929.79 | 21-MAY-03:13 | 14524.17 | 20-MAY-16:00 | 0.00 | 01-MAY-00:01 |
June | 0.277118E+11 | 0.913947E+10 | 310.26 | 0.254668E+11 | 0.224499E+10 | 0.00 | 0.75 | 20-JUN-17:10 | 0.00 | 01-JUN-00:01 | 66924.52 | 20-JUN-17:20 | 61163.23 | 29-JUN-13:00 | 18365.69 | 22-JUN-00:05 | 19868.65 | 20-JUN-17:10 | 0.00 | 01-JUN-00:01 |
July | 0.527421E+11 | 0.173760E+11 | 494.52 | 0.498302E+11 | 0.291194E+10 | 0.00 | 0.92 | 17-JUL-17:27 | 0.00 | 01-JUL-00:01 | 80342.07 | 17-JUL-17:27 | 80342.07 | 17-JUL-17:27 | 18826.70 | 19-JUL-00:04 | 26831.73 | 17-JUL-17:27 | 0.00 | 01-JUL-00:01 |
August | 0.419956E+11 | 0.138965E+11 | 424.36 | 0.408187E+11 | 0.117687E+10 | 0.00 | 0.85 | 05-AUG-18:03 | 0.00 | 01-AUG-00:01 | 73520.84 | 05-AUG-18:03 | 73520.84 | 05-AUG-18:03 | 11335.60 | 01-AUG-00:41 | 23966.52 | 05-AUG-18:03 | 0.00 | 01-AUG-00:01 |
September | 0.223316E+11 | 0.740960E+10 | 257.21 | 0.203994E+11 | 0.193224E+10 | 0.00 | 0.81 | 02-SEP-17:03 | 0.00 | 01-SEP-00:01 | 69998.59 | 02-SEP-17:03 | 69998.59 | 02-SEP-17:03 | 22119.95 | 07-SEP-17:20 | 22984.26 | 02-SEP-17:03 | 0.00 | 01-SEP-00:01 |
October | 0.287553E+10 | 0.996406E+09 | 57.25 | 0.287266E+10 | 2866304.64 | 0.00 | 0.41 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 | 32728.87 | 18-OCT-12:55 | 32728.87 | 18-OCT-12:55 | 1058.42 | 19-OCT-03:14 | 10832.51 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.156991E+12 | 0.520059E+11 | 1702.18 | 0.148407E+12 | 0.858443E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.527421E+11 | 0.173760E+11 | 494.52 | 0.498302E+11 | 0.291194E+10 | 0.00 | 0.92 | 0.00 | 80342.07 | 80342.07 | 22119.95 | 26831.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.289626E+09 | 94801117.66 | 52.19 | 0.244294E+09 | 45332554.88 | 0.00 | 0.56 | 13-JAN-05:03 | 0.00 | 01-JAN-00:01 | 18277.45 | 13-JAN-05:03 | 18277.45 | 13-JAN-05:03 | 4281.94 | 14-JAN-04:22 | 5380.47 | 13-JAN-05:03 | 0.00 | 01-JAN-00:01 |
February | 0.486746E+09 | 0.155654E+09 | 66.64 | 0.412941E+09 | 73805705.40 | 0.00 | 0.67 | 28-FEB-04:21 | 0.00 | 01-FEB-00:01 | 22585.45 | 28-FEB-04:21 | 18699.48 | 21-FEB-04:21 | 5916.02 | 28-FEB-04:21 | 6453.94 | 28-FEB-04:21 | 0.00 | 01-FEB-00:01 |
March | 0.467886E+09 | 0.153202E+09 | 74.77 | 0.387738E+09 | 80147767.35 | 0.00 | 0.67 | 28-MAR-03:21 | 0.00 | 01-MAR-00:01 | 22494.64 | 28-MAR-03:21 | 18934.01 | 28-MAR-03:21 | 3560.63 | 28-MAR-03:21 | 6431.96 | 28-MAR-03:21 | 0.00 | 01-MAR-00:01 |
April | 0.295900E+10 | 0.888283E+09 | 115.47 | 0.236376E+10 | 0.595235E+09 | 0.00 | 0.73 | 07-APR-03:21 | 0.00 | 01-APR-00:01 | 25021.97 | 07-APR-03:21 | 22613.09 | 07-APR-03:21 | 8922.77 | 14-APR-03:21 | 7033.69 | 07-APR-03:21 | 0.00 | 01-APR-00:01 |
May | 0.109772E+11 | 0.316271E+10 | 215.88 | 0.824507E+10 | 0.273210E+10 | 0.00 | 0.92 | 30-MAY-03:21 | 0.00 | 01-MAY-00:01 | 33048.72 | 30-MAY-03:21 | 29097.86 | 30-MAY-04:02 | 11647.69 | 19-MAY-03:21 | 8816.76 | 30-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.241989E+11 | 0.687317E+10 | 365.26 | 0.179055E+11 | 0.629344E+10 | 0.00 | 1.00 | 06-JUN-04:01 | 0.00 | 01-JUN-00:01 | 36983.75 | 13-JUN-03:21 | 36983.75 | 06-JUN-04:01 | 19986.79 | 13-JUN-03:21 | 9626.14 | 06-JUN-04:01 | 0.00 | 01-JUN-00:01 |
July | 0.364526E+11 | 0.103847E+11 | 504.96 | 0.271958E+11 | 0.925677E+10 | 0.00 | 1.00 | 14-JUL-03:21 | 0.00 | 01-JUL-00:01 | 36983.75 | 14-JUL-03:21 | 35316.55 | 28-JUL-04:02 | 16044.62 | 19-JUL-02:61 | 9626.14 | 14-JUL-03:21 | 0.00 | 01-JUL-00:01 |
August | 0.317827E+11 | 0.909964E+10 | 459.14 | 0.241964E+11 | 0.758629E+10 | 0.00 | 1.00 | 08-AUG-03:21 | 0.00 | 01-AUG-00:01 | 36983.75 | 08-AUG-03:21 | 35795.86 | 01-AUG-04:02 | 14074.94 | 01-AUG-03:21 | 9626.14 | 08-AUG-03:21 | 0.00 | 01-AUG-00:01 |
September | 0.197809E+11 | 0.565881E+10 | 311.64 | 0.147978E+11 | 0.498310E+10 | 0.00 | 1.00 | 05-SEP-03:21 | 0.00 | 01-SEP-00:01 | 36983.75 | 05-SEP-03:21 | 36418.60 | 26-SEP-04:02 | 20936.21 | 08-SEP-03:21 | 9626.14 | 05-SEP-03:21 | 0.00 | 01-SEP-00:01 |
October | 0.568512E+10 | 0.167671E+10 | 150.28 | 0.449360E+10 | 0.119152E+10 | 0.00 | 0.93 | 13-OCT-04:02 | 0.00 | 01-OCT-00:01 | 33795.72 | 13-OCT-04:02 | 33795.72 | 13-OCT-04:02 | 8586.85 | 07-OCT-02:61 | 8973.50 | 13-OCT-04:02 | 0.00 | 01-OCT-00:01 |
November | 0.672115E+09 | 0.217804E+09 | 80.19 | 0.555848E+09 | 0.116267E+09 | 0.00 | 0.69 | 04-NOV-03:21 | 0.00 | 01-NOV-00:01 | 23331.42 | 04-NOV-03:21 | 22341.36 | 24-NOV-05:03 | 6677.94 | 04-NOV-03:21 | 6633.46 | 04-NOV-03:21 | 0.00 | 01-NOV-00:01 |
December | 0.426300E+09 | 0.139703E+09 | 74.74 | 0.359079E+09 | 67221242.24 | 0.00 | 0.72 | 19-DEC-04:21 | 0.00 | 01-DEC-00:01 | 24653.17 | 19-DEC-04:21 | 20576.30 | 10-DEC-04:21 | 5289.58 | 19-DEC-04:21 | 6947.15 | 19-DEC-04:21 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.134179E+12 | 0.385052E+11 | 2471.16 | 0.101158E+12 | 0.330212E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.289626E+09 | 94801117.66 | 52.19 | 0.244294E+09 | 45332554.88 | 0.00 | 0.56 | 0.00 | 18277.45 | 18277.45 | 3560.63 | 5380.47 | 0.00 | |||||||
Maximum of Months | 0.364526E+11 | 0.103847E+11 | 504.96 | 0.271958E+11 | 0.925677E+10 | 0.00 | 1.00 | 0.00 | 36983.75 | 36983.75 | 20936.21 | 9626.14 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.18 | 74.86 | 87.32 | 59.89 | 889.16 | 0.00 | 0.00 | 0.00 |
February | 254.06 | 126.99 | 127.06 | 156.50 | 650.24 | 0.00 | 0.00 | 0.00 |
March | 340.43 | 141.65 | 198.78 | 235.10 | 523.04 | 0.00 | 0.00 | 0.00 |
April | 433.27 | 215.24 | 218.02 | 392.61 | 360.06 | 0.00 | 0.00 | 0.00 |
May | 477.63 | 212.84 | 264.79 | 474.61 | 285.97 | 0.00 | 0.00 | 0.00 |
June | 617.32 | 317.61 | 299.71 | 735.99 | 183.88 | 0.00 | 0.00 | 0.00 |
July | 647.99 | 366.32 | 281.67 | 854.81 | 146.70 | 0.00 | 0.00 | 0.00 |
August | 564.84 | 315.10 | 249.74 | 717.78 | 167.79 | 0.00 | 0.00 | 0.00 |
September | 399.18 | 206.11 | 193.06 | 440.31 | 250.49 | 0.00 | 0.00 | 0.00 |
October | 284.98 | 144.06 | 140.92 | 238.99 | 373.53 | 0.00 | 0.00 | 0.00 |
November | 181.54 | 84.82 | 96.72 | 97.99 | 546.58 | 0.00 | 0.00 | 0.00 |
December | 133.90 | 57.70 | 76.20 | 43.58 | 764.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.41 | 188.92 | 186.48 | 371.94 | 427.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.90 | 57.70 | 76.20 | 43.58 | 146.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.99 | 366.32 | 299.71 | 854.81 | 889.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 684.36 | 488.61 | 195.75 | 573.70 | 1104.48 | 0.00 | 0.00 | 0.00 |
February | 859.79 | 615.02 | 244.77 | 820.73 | 816.61 | 0.00 | 0.00 | 0.00 |
March | 769.04 | 427.55 | 341.49 | 737.21 | 717.95 | 0.00 | 0.00 | 0.00 |
April | 632.90 | 306.28 | 326.62 | 647.58 | 527.41 | 0.00 | 0.00 | 0.00 |
May | 561.09 | 189.61 | 371.49 | 583.40 | 422.68 | 0.00 | 0.00 | 0.00 |
June | 549.95 | 158.49 | 391.46 | 670.22 | 285.23 | 0.00 | 0.00 | 0.00 |
July | 594.50 | 218.77 | 375.73 | 836.23 | 221.96 | 0.00 | 0.00 | 0.00 |
August | 698.23 | 347.13 | 351.11 | 951.39 | 252.86 | 0.00 | 0.00 | 0.00 |
September | 784.26 | 480.07 | 304.19 | 972.90 | 359.81 | 0.00 | 0.00 | 0.00 |
October | 827.84 | 574.40 | 253.45 | 919.33 | 505.85 | 0.00 | 0.00 | 0.00 |
November | 747.89 | 541.42 | 206.46 | 731.79 | 678.64 | 0.00 | 0.00 | 0.00 |
December | 650.48 | 469.78 | 180.70 | 561.67 | 941.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.55 | 400.00 | 295.55 | 749.88 | 568.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 549.95 | 158.49 | 180.70 | 561.67 | 221.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 859.79 | 615.02 | 391.46 | 972.90 | 1104.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.49 | 59.32 | 87.17 | 55.60 | 910.14 | 0.00 | 0.00 | 0.00 |
February | 251.10 | 124.43 | 126.67 | 161.35 | 665.63 | 0.00 | 0.00 | 0.00 |
March | 319.92 | 117.92 | 202.00 | 219.06 | 538.21 | 0.00 | 0.00 | 0.00 |
April | 416.50 | 184.23 | 232.27 | 380.70 | 372.17 | 0.00 | 0.00 | 0.00 |
May | 515.11 | 235.39 | 279.72 | 535.20 | 295.41 | 0.00 | 0.00 | 0.00 |
June | 558.83 | 256.32 | 302.51 | 666.11 | 195.95 | 0.00 | 0.00 | 0.00 |
July | 572.68 | 289.16 | 283.52 | 762.63 | 159.00 | 0.00 | 0.00 | 0.00 |
August | 486.86 | 238.70 | 248.15 | 621.85 | 178.48 | 0.00 | 0.00 | 0.00 |
September | 392.22 | 198.31 | 193.92 | 445.02 | 263.16 | 0.00 | 0.00 | 0.00 |
October | 280.46 | 139.49 | 140.97 | 245.96 | 388.46 | 0.00 | 0.00 | 0.00 |
November | 198.51 | 98.64 | 99.86 | 131.65 | 558.50 | 0.00 | 0.00 | 0.00 |
December | 132.66 | 55.80 | 76.86 | 50.45 | 778.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 356.42 | 166.63 | 189.79 | 357.36 | 441.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 132.66 | 55.80 | 76.86 | 50.45 | 159.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 572.68 | 289.16 | 302.51 | 762.63 | 910.14 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434371E+09 | 0.200495E+09 | 0.233876E+09 | 0.160402E+09 | 0.238152E+10 |
February | 0.614610E+09 | 0.307218E+09 | 0.307392E+09 | 0.378597E+09 | 0.157307E+10 |
March | 0.911812E+09 | 0.379397E+09 | 0.532415E+09 | 0.629693E+09 | 0.140090E+10 |
April | 0.112303E+10 | 0.557912E+09 | 0.565117E+09 | 0.101765E+10 | 0.933286E+09 |
May | 0.127929E+10 | 0.570080E+09 | 0.709211E+09 | 0.127120E+10 | 0.765942E+09 |
June | 0.160009E+10 | 0.823239E+09 | 0.776854E+09 | 0.190770E+10 | 0.476612E+09 |
July | 0.173558E+10 | 0.981154E+09 | 0.754426E+09 | 0.228953E+10 | 0.392925E+09 |
August | 0.151287E+10 | 0.843962E+09 | 0.668903E+09 | 0.192251E+10 | 0.449405E+09 |
September | 0.103466E+10 | 0.534246E+09 | 0.500416E+09 | 0.114128E+10 | 0.649280E+09 |
October | 0.763282E+09 | 0.385839E+09 | 0.377443E+09 | 0.640105E+09 | 0.100045E+10 |
November | 0.470547E+09 | 0.219847E+09 | 0.250700E+09 | 0.254001E+09 | 0.141674E+10 |
December | 0.358639E+09 | 0.154544E+09 | 0.204095E+09 | 0.116727E+09 | 0.204734E+10 |
Annual Sum or Average | 0.118388E+11 | 0.595793E+10 | 0.588085E+10 | 0.117294E+11 | 0.134875E+11 |
Minimum of Months | 0.358639E+09 | 0.154544E+09 | 0.204095E+09 | 0.116727E+09 | 0.392925E+09 |
Maximum of Months | 0.173558E+10 | 0.981154E+09 | 0.776854E+09 | 0.228953E+10 | 0.238152E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183300E+10 | 0.130870E+10 | 0.524306E+09 | 0.153660E+10 | 0.295825E+10 |
February | 0.208001E+10 | 0.148785E+10 | 0.592153E+09 | 0.198551E+10 | 0.197554E+10 |
March | 0.205979E+10 | 0.114514E+10 | 0.914648E+09 | 0.197454E+10 | 0.192295E+10 |
April | 0.164049E+10 | 0.793878E+09 | 0.846609E+09 | 0.167852E+10 | 0.136704E+10 |
May | 0.150284E+10 | 0.507851E+09 | 0.994986E+09 | 0.156258E+10 | 0.113211E+10 |
June | 0.142548E+10 | 0.410809E+09 | 0.101467E+10 | 0.173721E+10 | 0.739319E+09 |
July | 0.159231E+10 | 0.585962E+09 | 0.100635E+10 | 0.223975E+10 | 0.594502E+09 |
August | 0.187015E+10 | 0.929747E+09 | 0.940405E+09 | 0.254821E+10 | 0.677273E+09 |
September | 0.203280E+10 | 0.124433E+10 | 0.788466E+09 | 0.252176E+10 | 0.932623E+09 |
October | 0.221730E+10 | 0.153846E+10 | 0.678838E+09 | 0.246233E+10 | 0.135486E+10 |
November | 0.193852E+10 | 0.140337E+10 | 0.535156E+09 | 0.189679E+10 | 0.175905E+10 |
December | 0.174223E+10 | 0.125826E+10 | 0.483976E+09 | 0.150438E+10 | 0.252204E+10 |
Annual Sum or Average | 0.219349E+11 | 0.126144E+11 | 0.932056E+10 | 0.236482E+11 | 0.179356E+11 |
Minimum of Months | 0.142548E+10 | 0.410809E+09 | 0.483976E+09 | 0.150438E+10 | 0.594502E+09 |
Maximum of Months | 0.221730E+10 | 0.153846E+10 | 0.101467E+10 | 0.254821E+10 | 0.295825E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.392356E+09 | 0.158882E+09 | 0.233475E+09 | 0.148932E+09 | 0.243771E+10 |
February | 0.607464E+09 | 0.301021E+09 | 0.306443E+09 | 0.390328E+09 | 0.161030E+10 |
March | 0.856879E+09 | 0.315843E+09 | 0.541035E+09 | 0.586724E+09 | 0.144155E+10 |
April | 0.107958E+10 | 0.477532E+09 | 0.602045E+09 | 0.986783E+09 | 0.964659E+09 |
May | 0.137968E+10 | 0.630478E+09 | 0.749203E+09 | 0.143349E+10 | 0.791235E+09 |
June | 0.144849E+10 | 0.664372E+09 | 0.784113E+09 | 0.172656E+10 | 0.507899E+09 |
July | 0.153386E+10 | 0.774486E+09 | 0.759370E+09 | 0.204262E+10 | 0.425852E+09 |
August | 0.130400E+10 | 0.639344E+09 | 0.664655E+09 | 0.166557E+10 | 0.478028E+09 |
September | 0.101664E+10 | 0.514009E+09 | 0.502634E+09 | 0.115350E+10 | 0.682109E+09 |
October | 0.751188E+09 | 0.373604E+09 | 0.377584E+09 | 0.658791E+09 | 0.104046E+10 |
November | 0.514528E+09 | 0.255678E+09 | 0.258850E+09 | 0.341224E+09 | 0.144762E+10 |
December | 0.355320E+09 | 0.149449E+09 | 0.205872E+09 | 0.135129E+09 | 0.208522E+10 |
Annual Sum or Average | 0.112400E+11 | 0.525470E+10 | 0.598528E+10 | 0.112696E+11 | 0.139126E+11 |
Minimum of Months | 0.355320E+09 | 0.149449E+09 | 0.205872E+09 | 0.135129E+09 | 0.425852E+09 |
Maximum of Months | 0.153386E+10 | 0.774486E+09 | 0.784113E+09 | 0.204262E+10 | 0.243771E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 549.13 | 2763.71 | 993.03 | 622.79 | 370.24 | 0.00 | 0.00 |
February | 1019.33 | 2013.25 | 1364.95 | 866.44 | 498.51 | 0.00 | 0.00 |
March | 1130.90 | 1718.73 | 1429.39 | 687.12 | 742.27 | 0.00 | 0.00 |
April | 1352.09 | 1190.84 | 1482.67 | 705.76 | 776.92 | 0.00 | 0.00 |
May | 1534.26 | 945.11 | 1553.84 | 637.85 | 915.99 | 0.00 | 0.00 |
June | 2025.18 | 617.92 | 1726.10 | 732.42 | 993.69 | 0.00 | 0.00 |
July | 2424.96 | 498.95 | 1815.17 | 874.25 | 940.92 | 0.00 | 0.00 |
August | 2257.71 | 565.81 | 1749.93 | 900.93 | 849.00 | 0.00 | 0.00 |
September | 1823.95 | 839.18 | 1575.66 | 884.49 | 691.17 | 0.00 | 0.00 |
October | 1358.61 | 1222.16 | 1393.28 | 857.94 | 535.34 | 0.00 | 0.00 |
November | 858.84 | 1681.14 | 1127.93 | 724.88 | 403.05 | 0.00 | 0.00 |
December | 525.73 | 2354.56 | 917.04 | 583.28 | 333.76 | 0.00 | 0.00 |
Annual Sum or Average | 1407.02 | 1365.43 | 1427.37 | 755.55 | 671.83 | 0.00 | 0.00 |
Minimum of Months | 525.73 | 498.95 | 917.04 | 583.28 | 333.76 | 0.00 | 0.00 |
Maximum of Months | 2424.96 | 2763.71 | 1815.17 | 900.93 | 993.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147078E+10 | 0.740233E+10 | 0.265973E+10 | 0.166807E+10 | 0.991657E+09 | 0.00 | 0.00 |
February | 0.246597E+10 | 0.487045E+10 | 0.330208E+10 | 0.209609E+10 | 0.120599E+10 | 0.00 | 0.00 |
March | 0.302900E+10 | 0.460344E+10 | 0.382848E+10 | 0.184038E+10 | 0.198810E+10 | 0.00 | 0.00 |
April | 0.350462E+10 | 0.308665E+10 | 0.384309E+10 | 0.182932E+10 | 0.201377E+10 | 0.00 | 0.00 |
May | 0.410935E+10 | 0.253137E+10 | 0.416181E+10 | 0.170841E+10 | 0.245340E+10 | 0.00 | 0.00 |
June | 0.524928E+10 | 0.160164E+10 | 0.447405E+10 | 0.189842E+10 | 0.257563E+10 | 0.00 | 0.00 |
July | 0.649501E+10 | 0.133638E+10 | 0.486175E+10 | 0.234160E+10 | 0.252015E+10 | 0.00 | 0.00 |
August | 0.604706E+10 | 0.151548E+10 | 0.468702E+10 | 0.241305E+10 | 0.227396E+10 | 0.00 | 0.00 |
September | 0.472768E+10 | 0.217516E+10 | 0.408410E+10 | 0.229259E+10 | 0.179152E+10 | 0.00 | 0.00 |
October | 0.363890E+10 | 0.327344E+10 | 0.373177E+10 | 0.229790E+10 | 0.143387E+10 | 0.00 | 0.00 |
November | 0.222612E+10 | 0.435752E+10 | 0.292360E+10 | 0.187889E+10 | 0.104471E+10 | 0.00 | 0.00 |
December | 0.140810E+10 | 0.630646E+10 | 0.245619E+10 | 0.156225E+10 | 0.893943E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.443719E+11 | 0.430603E+11 | 0.450137E+11 | 0.238270E+11 | 0.211867E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140810E+10 | 0.133638E+10 | 0.245619E+10 | 0.156225E+10 | 0.893943E+09 | 0.00 | 0.00 |
Maximum of Months | 0.649501E+10 | 0.740233E+10 | 0.486175E+10 | 0.241305E+10 | 0.257563E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.656205E+10 | -0.622531E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -336739197.1 | 81.22 | 0.00 | 0.00 |
February | 0.593651E+10 | -0.563441E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -302098946.6 | 81.22 | 0.00 | 0.00 |
March | 0.662817E+10 | -0.629399E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -334176750.8 | 81.22 | 0.00 | 0.00 |
April | 0.636647E+10 | -0.604359E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322876864.9 | 81.22 | 0.00 | 0.00 |
May | 0.659387E+10 | -0.626032E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333555949.7 | 81.22 | 0.00 | 0.00 |
June | 0.640936E+10 | -0.608671E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322643959.8 | 81.22 | 0.00 | 0.00 |
July | 0.655052E+10 | -0.621721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333308528.6 | 81.22 | 0.00 | 0.00 |
August | 0.662866E+10 | -0.629534E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333315745.2 | 81.22 | 0.00 | 0.00 |
September | 0.636759E+10 | -0.604496E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322634718.0 | 81.22 | 0.00 | 0.00 |
October | 0.655746E+10 | -0.622396E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333502341.0 | 81.22 | 0.00 | 0.00 |
November | 0.634769E+10 | -0.602475E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322939455.6 | 81.22 | 0.00 | 0.00 |
December | 0.655158E+10 | -0.621721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -334362848.2 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.774999E+11 | -0.735678E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.393216E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.593651E+10 | -0.629534E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -336739197.1 | 81.22 | 0.00 | 0.00 |
Maximum of Months | 0.662866E+10 | -0.563441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -302098946.6 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.269587E+11 | -0.260946E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -864059010.5 | 58.99 | 0.00 | 0.00 |
February | 0.248060E+11 | -0.240343E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -771685813.9 | 58.99 | 0.00 | 0.00 |
March | 0.274217E+11 | -0.265686E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -853130218.5 | 58.99 | 0.00 | 0.00 |
April | 0.253988E+11 | -0.245755E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -823296599.9 | 58.99 | 0.00 | 0.00 |
May | 0.248959E+11 | -0.240454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850537724.6 | 58.99 | 0.00 | 0.00 |
June | 0.227575E+11 | -0.219351E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -822399903.8 | 58.99 | 0.00 | 0.00 |
July | 0.221216E+11 | -0.212722E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -849456914.2 | 58.99 | 0.00 | 0.00 |
August | 0.218886E+11 | -0.210392E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -849381663.7 | 58.99 | 0.00 | 0.00 |
September | 0.213062E+11 | -0.204838E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -822374776.5 | 58.99 | 0.00 | 0.00 |
October | 0.229278E+11 | -0.220777E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850167967.8 | 58.99 | 0.00 | 0.00 |
November | 0.235604E+11 | -0.227367E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -823703837.9 | 58.99 | 0.00 | 0.00 |
December | 0.257771E+11 | -0.249231E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -853999973.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.289820E+12 | -0.279786E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.100342E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213062E+11 | -0.265686E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -864059010.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.274217E+11 | -0.204838E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -771685813.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169082E+12 | 231228.25 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101623E+12 | 231228.25 | 01-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.901790E+11 | 231228.25 | 05-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.446246E+11 | 136852.41 | 27-APR-22:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.298946E+11 | 69785.74 | 08-MAY-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619669E+10 | 46271.67 | 15-JUN-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134463E+10 | 33877.96 | 12-JUL-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.233950E+10 | 29820.48 | 18-AUG-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119861E+11 | 46288.21 | 17-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322965E+11 | 69279.13 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695633E+11 | 203659.23 | 26-NOV-11:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127691E+12 | 231228.25 | 28-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.686821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.134463E+10 | 29820.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169082E+12 | 231228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 922222.34 | 816.29 | 11-JAN-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 922222.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 922222.34 | 816.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 52086001.69 | 52086001.69 | 7597.85 | 27-FEB-14:00 | 7597.85 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.115197E+10 | 0.115087E+10 | 21567.76 | 07-APR-12:53 | 21567.76 | 0.00 |
May | 0.00 | 0.00 | 0.813055E+10 | 0.781612E+10 | 45274.96 | 20-MAY-17:05 | 45274.96 | 0.00 |
June | 0.00 | 0.00 | 0.277118E+11 | 0.254668E+11 | 66924.52 | 20-JUN-17:20 | 52289.17 | 0.00 |
July | 0.00 | 0.00 | 0.527421E+11 | 0.498302E+11 | 80342.07 | 17-JUL-17:27 | 80342.07 | 0.00 |
August | 0.00 | 0.00 | 0.419956E+11 | 0.408187E+11 | 73520.84 | 05-AUG-18:03 | 73520.84 | 0.00 |
September | 0.00 | 0.00 | 0.223316E+11 | 0.203994E+11 | 69998.59 | 02-SEP-17:03 | 69998.59 | 0.00 |
October | 0.00 | 0.00 | 0.287553E+10 | 0.287266E+10 | 32728.87 | 18-OCT-12:55 | 32728.87 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156991E+12 | 0.148407E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.527421E+11 | 0.498302E+11 | 80342.07 | 80342.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.289626E+09 | 0.244294E+09 | 18277.45 | 13-JAN-05:03 | 18277.45 | 0.00 |
February | 0.00 | 0.00 | 0.486746E+09 | 0.412941E+09 | 22585.45 | 28-FEB-04:21 | 16669.43 | 0.00 |
March | 0.00 | 0.00 | 0.467886E+09 | 0.387738E+09 | 22494.64 | 28-MAR-03:21 | 18934.01 | 0.00 |
April | 0.00 | 0.00 | 0.295900E+10 | 0.236376E+10 | 25021.97 | 07-APR-03:21 | 22613.09 | 0.00 |
May | 0.00 | 0.00 | 0.109772E+11 | 0.824507E+10 | 33048.72 | 30-MAY-03:21 | 23824.38 | 0.00 |
June | 0.00 | 0.00 | 0.241989E+11 | 0.179055E+11 | 36983.75 | 13-JUN-03:21 | 16996.96 | 0.00 |
July | 0.00 | 0.00 | 0.364526E+11 | 0.271958E+11 | 36983.75 | 14-JUL-03:21 | 24685.89 | 0.00 |
August | 0.00 | 0.00 | 0.317827E+11 | 0.241964E+11 | 36983.75 | 08-AUG-03:21 | 29114.01 | 0.00 |
September | 0.00 | 0.00 | 0.197809E+11 | 0.147978E+11 | 36983.75 | 05-SEP-03:21 | 27395.16 | 0.00 |
October | 0.00 | 0.00 | 0.568512E+10 | 0.449360E+10 | 33795.72 | 13-OCT-04:02 | 33795.72 | 0.00 |
November | 0.00 | 0.00 | 0.672115E+09 | 0.555848E+09 | 23331.42 | 04-NOV-03:21 | 16653.48 | 0.00 |
December | 0.00 | 0.00 | 0.426300E+09 | 0.359079E+09 | 24653.17 | 19-DEC-04:21 | 19363.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134179E+12 | 0.101158E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.289626E+09 | 0.244294E+09 | 18277.45 | 16653.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.364526E+11 | 0.271958E+11 | 36983.75 | 33795.72 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10200.20 | 19660.78 | 30-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10392.04 | 19774.87 | 17-FEB-19:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 10376.63 | 19744.95 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9939.30 | 19220.12 | 03-APR-18:47 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9436.54 | 18387.46 | 01-MAY-18:12 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8922.63 | 17272.57 | 02-JUN-18:26 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8403.23 | 16301.53 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8316.36 | 15715.62 | 03-AUG-18:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8364.19 | 16090.40 | 29-SEP-18:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8703.54 | 17004.19 | 31-OCT-18:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9231.49 | 18100.52 | 29-NOV-07:48 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9763.81 | 18990.79 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 9331.28 | ||||
Minimum of Months | 0.00 | 0.00 | 8316.36 | 15715.62 | ||
Maximum of Months | 0.00 | 0.00 | 10392.04 | 19774.87 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.537088E+10 | 0.66 | 2203.40 | 01-JAN-00:01 | 0.73 |
February | 0.501844E+10 | 0.68 | 2203.40 | 01-FEB-00:01 | 0.73 |
March | 0.557859E+10 | 0.69 | 2203.40 | 01-MAR-00:01 | 0.73 |
April | 0.546302E+10 | 0.69 | 2203.40 | 01-APR-00:04 | 0.73 |
May | 0.564561E+10 | 0.69 | 2203.40 | 01-MAY-00:04 | 0.73 |
June | 0.546466E+10 | 0.69 | 2203.40 | 01-JUN-00:03 | 0.72 |
July | 0.564844E+10 | 0.69 | 2203.40 | 01-JUL-00:03 | 0.72 |
August | 0.564896E+10 | 0.69 | 2203.40 | 01-AUG-00:03 | 0.73 |
September | 0.546522E+10 | 0.69 | 2203.40 | 01-SEP-00:02 | 0.73 |
October | 0.564636E+10 | 0.69 | 2203.40 | 01-OCT-00:04 | 0.73 |
November | 0.545698E+10 | 0.69 | 2203.40 | 01-NOV-00:03 | 0.73 |
December | 0.557919E+10 | 0.69 | 2203.40 | 01-DEC-00:01 | 0.73 |
Annual Sum or Average | 0.659863E+11 | 0.69 | |||
Minimum of Months | 0.501844E+10 | 0.66 | 2203.40 | 0.72 | |
Maximum of Months | 0.564896E+10 | 0.69 | 2203.40 | 0.73 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.200910E+11 | 1.52 | 8893.87 | 01-JAN-00:07 | 1.76 |
February | 0.179942E+11 | 1.51 | 8893.87 | 01-FEB-00:04 | 1.77 |
March | 0.198886E+11 | 1.51 | 8893.87 | 11-MAR-14:20 | 1.76 |
April | 0.192174E+11 | 1.49 | 8893.87 | 01-APR-04:50 | 1.77 |
May | 0.198595E+11 | 1.49 | 8893.87 | 01-MAY-04:10 | 1.76 |
June | 0.192541E+11 | 1.56 | 8893.87 | 01-JUN-05:40 | 1.75 |
July | 0.199675E+11 | 1.66 | 8893.87 | 01-JUL-07:58 | 1.74 |
August | 0.199455E+11 | 1.62 | 8893.87 | 10-AUG-06:20 | 1.75 |
September | 0.192705E+11 | 1.56 | 8893.87 | 01-SEP-04:02 | 1.75 |
October | 0.198522E+11 | 1.47 | 8893.87 | 01-OCT-04:08 | 1.75 |
November | 0.192244E+11 | 1.49 | 8893.87 | 01-NOV-04:07 | 1.76 |
December | 0.199296E+11 | 1.51 | 8893.87 | 01-DEC-00:06 | 1.77 |
Annual Sum or Average | 0.234495E+12 | 1.53 | |||
Minimum of Months | 0.179942E+11 | 1.47 | 8893.87 | 1.74 | |
Maximum of Months | 0.200910E+11 | 1.66 | 8893.87 | 1.77 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.441695E+10 | 0.94 | 1970.66 | 01-JAN-00:01 | 1.02 |
February | 0.399464E+10 | 0.98 | 1970.66 | 09-FEB-08:00 | 1.02 |
March | 0.442781E+10 | 0.98 | 1970.66 | 21-MAR-04:03 | 1.03 |
April | 0.429923E+10 | 1.00 | 1970.66 | 06-APR-11:43 | 1.02 |
May | 0.445582E+10 | 1.00 | 1970.66 | 02-MAY-12:17 | 1.01 |
June | 0.434224E+10 | 1.00 | 1970.66 | 01-JUN-16:00 | 1.01 |
July | 0.451138E+10 | 1.00 | 1970.66 | 01-JUL-04:08 | 1.02 |
August | 0.450276E+10 | 1.00 | 1970.66 | 01-AUG-04:12 | 1.02 |
September | 0.434411E+10 | 1.00 | 1970.66 | 01-SEP-07:27 | 1.02 |
October | 0.446064E+10 | 1.00 | 1970.66 | 12-OCT-11:00 | 1.02 |
November | 0.429818E+10 | 1.00 | 1970.66 | 01-NOV-04:03 | 1.02 |
December | 0.442566E+10 | 0.98 | 1970.66 | 20-DEC-05:05 | 1.03 |
Annual Sum or Average | 0.524794E+11 | 0.99 | |||
Minimum of Months | 0.399464E+10 | 0.94 | 1970.66 | 1.01 | |
Maximum of Months | 0.451138E+10 | 1.00 | 1970.66 | 1.03 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.65 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 46.47 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.27 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 51.05 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 51.31 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 51.42 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 52.30 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.22 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.66 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.81 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.77 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.26 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 46.27 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.66 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.65 | 59.93 | 10200.20 | 19660.78 | 30-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.47 | 59.66 | 10392.04 | 19774.87 | 17-FEB-19:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.27 | 59.84 | 10376.63 | 19744.95 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 48.22 | 48.22 | 9939.30 | 19220.12 | 03-APR-18:47 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 48.61 | 48.61 | 9436.54 | 18387.46 | 01-MAY-18:12 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 49.41 | 49.41 | 8922.63 | 17272.57 | 02-JUN-18:26 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 49.81 | 49.81 | 8403.23 | 16301.53 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.69 | 50.69 | 8316.36 | 15715.62 | 03-AUG-18:20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.36 | 50.36 | 8364.19 | 16090.40 | 29-SEP-18:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.19 | 48.19 | 8703.54 | 17004.19 | 31-OCT-18:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.81 | 49.81 | 9231.49 | 18100.52 | 29-NOV-07:48 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.26 | 58.06 | 9763.81 | 18990.79 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 9331.28 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.27 | 48.19 | 8316.36 | 15715.62 | ||
Maximum of Months | 0.00 | 0.00 | 50.69 | 59.93 | 10392.04 | 19774.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.200910E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180129E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.198886E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.196220E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.226241E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.283936E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.373435E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.338420E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266801E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.208486E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.192244E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.199296E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.286500E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.180129E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.373435E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.451175E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.415030E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.458101E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.518751E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.761853E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.112154E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.148961E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.136024E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.100029E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.613736E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.451599E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.456536E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.909846E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.415030E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.148961E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.200910E+11 | 0.00 | 0.169082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179942E+11 | 52086001.69 | 0.101623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198886E+11 | 0.00 | 0.901790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192174E+11 | 0.115197E+10 | 0.446246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198595E+11 | 0.813055E+10 | 0.298946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192541E+11 | 0.277118E+11 | 0.619669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199675E+11 | 0.527421E+11 | 0.134463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199455E+11 | 0.419956E+11 | 0.233950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192705E+11 | 0.223316E+11 | 0.119861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198522E+11 | 0.287553E+10 | 0.322965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192244E+11 | 0.00 | 0.695633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199296E+11 | 0.00 | 0.127691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234495E+12 | 0.156991E+12 | 0.686821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179942E+11 | 0.00 | 0.134463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200910E+11 | 0.527421E+11 | 0.169082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.441695E+10 | 0.289626E+09 | 922222.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399464E+10 | 0.486746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.442781E+10 | 0.467886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.429923E+10 | 0.295900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.445582E+10 | 0.109772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.434224E+10 | 0.241989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.451138E+10 | 0.364526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.450276E+10 | 0.317827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434411E+10 | 0.197809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.446064E+10 | 0.568512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.429818E+10 | 0.672115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442566E+10 | 0.426300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524794E+11 | 0.134179E+12 | 922222.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.399464E+10 | 0.289626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451138E+10 | 0.364526E+11 | 922222.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.200910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179942E+11 | 0.00 | 0.00 | 0.00 | 18700565.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192174E+11 | 0.00 | 0.00 | 0.00 | 0.404561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198595E+11 | 0.00 | 0.00 | 0.00 | 0.276460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192541E+11 | 0.00 | 0.00 | 0.00 | 0.913947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199675E+11 | 0.00 | 0.00 | 0.00 | 0.173760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199455E+11 | 0.00 | 0.00 | 0.00 | 0.138965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192705E+11 | 0.00 | 0.00 | 0.00 | 0.740960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198522E+11 | 0.00 | 0.00 | 0.00 | 0.996406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234495E+12 | 0.00 | 0.00 | 0.00 | 0.520059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200910E+11 | 0.00 | 0.00 | 0.00 | 0.173760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.441695E+10 | 0.00 | 0.00 | 0.00 | 94801117.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399464E+10 | 0.00 | 0.00 | 0.00 | 0.155654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.442781E+10 | 0.00 | 0.00 | 0.00 | 0.153202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.429923E+10 | 0.00 | 0.00 | 0.00 | 0.888283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.445582E+10 | 0.00 | 0.00 | 0.00 | 0.316271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.434224E+10 | 0.00 | 0.00 | 0.00 | 0.687317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.451138E+10 | 0.00 | 0.00 | 0.00 | 0.103847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.450276E+10 | 0.00 | 0.00 | 0.00 | 0.909964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434411E+10 | 0.00 | 0.00 | 0.00 | 0.565881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.446064E+10 | 0.00 | 0.00 | 0.00 | 0.167671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.429818E+10 | 0.00 | 0.00 | 0.00 | 0.217804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442566E+10 | 0.00 | 0.00 | 0.00 | 0.139703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524794E+11 | 0.00 | 0.00 | 0.00 | 0.385052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.399464E+10 | 0.00 | 0.00 | 0.00 | 94801117.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451138E+10 | 0.00 | 0.00 | 0.00 | 0.103847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.733697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126169E+12 | 0.00 | 0.00 | 7.07 |
February | 0.763929E+11 | 0.00 | 0.00 | 629531.04 | 0.00 | 0.611025E+11 | 0.101089E+10 | 0.00 | 7.04 |
March | 0.100105E+12 | 0.00 | 0.00 | 49182.97 | 0.00 | 0.355820E+11 | 0.176005E+09 | 0.00 | 7.08 |
April | 0.828239E+11 | 0.00 | 0.00 | 12435889.66 | 0.00 | 0.498722E+10 | 0.728835E+10 | 0.00 | 7.07 |
May | 0.633203E+11 | 0.154737E+09 | 0.00 | 41059305.24 | 0.00 | 0.341753E+10 | 0.135233E+11 | 0.00 | 7.11 |
June | 0.253752E+11 | 0.193103E+10 | 0.00 | 79928253.60 | 0.00 | 18517184.92 | 0.207170E+11 | 0.00 | 7.21 |
July | 0.118344E+11 | 0.594081E+10 | 0.00 | 0.102915E+09 | 0.00 | 0.00 | 0.163017E+11 | 0.00 | 7.24 |
August | 0.160990E+11 | 0.423399E+10 | 0.00 | 97845961.38 | 0.00 | 0.00 | 0.209108E+11 | 0.00 | 7.25 |
September | 0.371811E+11 | 0.215586E+10 | 0.00 | 59388254.56 | 0.00 | 18140075.70 | 0.191546E+11 | 0.00 | 7.20 |
October | 0.758522E+11 | 0.00 | 0.00 | 17186220.88 | 0.00 | 0.675458E+09 | 0.124506E+11 | 0.00 | 7.07 |
November | 0.965011E+11 | 0.00 | 0.00 | 1332504.68 | 0.00 | 0.176747E+11 | 0.377114E+10 | 0.00 | 7.01 |
December | 0.967945E+11 | 0.00 | 0.00 | 7335.87 | 0.00 | 0.692706E+11 | 0.124013E+09 | 0.00 | 7.08 |
Annual Sum or Average | 0.755649E+12 | 0.144164E+11 | 0.00 | 0.412777E+09 | 0.00 | 0.318916E+12 | 0.115428E+12 | 0.00 | 7.12 |
Minimum of Months | 0.118344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
Maximum of Months | 0.100105E+12 | 0.594081E+10 | 0.00 | 0.102915E+09 | 0.00 | 0.126169E+12 | 0.209108E+11 | 0.00 | 7.25 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292155E+10 | 0.00 | 0.00 | 56129549.48 | 0.00 | 0.00 | 0.371875E+11 | 0.00 | 2.74 |
February | 0.717309E+09 | 0.00 | 0.00 | 65930387.88 | 0.00 | 0.00 | 0.372438E+11 | 0.00 | 3.55 |
March | 0.561962E+09 | 0.00 | 0.00 | 87092642.96 | 0.00 | 0.00 | 0.430353E+11 | 0.00 | 3.81 |
April | 0.00 | 0.00 | 0.00 | 0.102561E+09 | 0.00 | 0.00 | 0.420488E+11 | 0.00 | 5.04 |
May | 0.00 | 0.00 | 0.00 | 0.125706E+09 | 0.00 | 0.00 | 0.379957E+11 | 0.00 | 4.99 |
June | 0.00 | 3658869.76 | 0.00 | 0.142438E+09 | 0.00 | 0.00 | 0.260853E+11 | 0.00 | 4.92 |
July | 191424.82 | 9117772.49 | 0.00 | 0.168381E+09 | 0.00 | 0.00 | 0.175900E+11 | 0.00 | 4.06 |
August | 0.00 | 0.00 | 0.00 | 0.153075E+09 | 0.00 | 0.00 | 0.216122E+11 | 0.00 | 4.46 |
September | 0.00 | 7091727.69 | 0.00 | 0.117876E+09 | 0.00 | 0.00 | 0.294954E+11 | 0.00 | 5.11 |
October | 0.00 | 0.00 | 0.00 | 0.101608E+09 | 0.00 | 0.00 | 0.430962E+11 | 0.00 | 5.57 |
November | 44788326.39 | 0.00 | 0.00 | 73336038.48 | 0.00 | 0.00 | 0.432046E+11 | 0.00 | 4.74 |
December | 0.659615E+09 | 0.00 | 0.00 | 63225504.61 | 0.00 | 0.00 | 0.412784E+11 | 0.00 | 3.25 |
Annual Sum or Average | 0.490542E+10 | 19868369.94 | 0.00 | 0.125736E+10 | 0.00 | 0.00 | 0.419873E+12 | 0.00 | 4.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 56129549.48 | 0.00 | 0.00 | 0.175900E+11 | 0.00 | 2.74 |
Maximum of Months | 0.292155E+10 | 9117772.49 | 0.00 | 0.168381E+09 | 0.00 | 0.00 | 0.432046E+11 | 0.00 | 5.57 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:40
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.270906E+11 | 0.272925E+11 | 0.581697E+12 | 0.163764E+11 | 0.622760E+11 |
February | 0.478751E+11 | 0.198428E+11 | 0.435982E+12 | 0.204305E+11 | 0.446841E+11 |
March | 0.882142E+11 | 0.196965E+11 | 0.438704E+12 | 0.256078E+11 | 0.456121E+11 |
April | 0.962037E+11 | 0.145491E+11 | 0.322281E+12 | 0.286853E+11 | 0.400526E+11 |
May | 0.133095E+12 | 0.139923E+11 | 0.283365E+12 | 0.260335E+11 | 0.587120E+11 |
June | 0.146254E+12 | 0.963122E+10 | 0.182305E+12 | 0.181986E+11 | 0.968868E+11 |
July | 0.144385E+12 | 0.673761E+10 | 0.138355E+12 | 0.109757E+11 | 0.147529E+12 |
August | 0.119585E+12 | 0.727710E+10 | 0.164387E+12 | 0.139395E+11 | 0.125181E+12 |
September | 0.895494E+11 | 0.894353E+10 | 0.201472E+12 | 0.208648E+11 | 0.814610E+11 |
October | 0.519656E+11 | 0.124027E+11 | 0.293850E+12 | 0.306281E+11 | 0.411487E+11 |
November | 0.220446E+11 | 0.160019E+11 | 0.375241E+12 | 0.278791E+11 | 0.366428E+11 |
December | 0.138374E+11 | 0.220870E+11 | 0.512733E+12 | 0.212723E+11 | 0.512337E+11 |
Annual Sum or Average | 0.980099E+12 | 0.178454E+12 | 0.393037E+13 | 0.260892E+12 | 0.831420E+12 |
Minimum of Months | 0.138374E+11 | 0.673761E+10 | 0.138355E+12 | 0.109757E+11 | 0.366428E+11 |
Maximum of Months | 0.146254E+12 | 0.272925E+11 | 0.581697E+12 | 0.306281E+11 | 0.147529E+12 |