Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:25:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2800.39 | 5478.58 | 5478.58 |
Net Site Energy | 2800.39 | 5478.58 | 5478.58 |
Total Source Energy | 4756.26 | 9304.95 | 9304.95 |
Net Source Energy | 4756.26 | 9304.95 | 9304.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1086.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 55.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 120.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.53 | 418.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 48.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 826.03 | 1974.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1086.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 55.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 120.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.53 | 418.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1086.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 55.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 49.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 120.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.53 | 418.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 48.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 147.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 493.54 | 2943.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 975.08 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1616.02 | 3862.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 147.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 493.54 | 2943.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 975.08 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1616.02 | 3862.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 826.034 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 826.034 | 100.00 |
Total On-Site and Utility Electric Sources | 826.034 | 100.00 |
Total Electricity End Uses | 826.034 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 2.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4528.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 7.7280 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.0598 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.7280 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.0598 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.0912 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-11:00 | 06-JAN-07:49 | - | - | - | - | - | - | - | - | - | - | 02-MAR-19:10 |
Heating | 0.00 | 201737.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29753.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22726.43 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7154.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2995.89 | 36281.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1720.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 66480.73 | 251596.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 201737.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 29753.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21698.93 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7154.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2995.89 | 36281.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 449.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1177.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 176.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1423.36 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 382.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.19 | 453.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 155.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2616.05 | 2140.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2304.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 344.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 307.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 747.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.94 | 886.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 303.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5117.94 | 4187.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2304.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 344.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 307.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 747.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.94 | 886.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 303.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5117.94 | 4187.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.55 |
KITCHEN DIRECT AIR | 1.56 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.55 | 3.55 | 3.55 | 3.55 | 3.55 | 3.55 | 1.00 | 1.00 | 3.55 |
PSZ-AC_2:2 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.00 | 1.00 | 1.56 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.55 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.56 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.55 | 6059.79 |
PSZ-AC_2:2_ADDAQ FAN | 1.56 | 1670.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.55 | 3.55 | 3.55 | 2.34 | 88057.35 | 161038.82 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.03 | 38770.11 | 111221.53 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.55 | 1.77 | 2.36 | 88057.35 | 44028.68 | 0.701120 | 0.701120 |
PSZ-AC_2:2 COOLING COIL | 1.56 | 0.780636 | 1.04 | 38770.11 | 19385.06 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 161038.82 |
PSZ-AC_2:2 HEATING COIL | 111221.53 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 7.728 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 72.655 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.060 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1069.700 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2872.862 | 7.728 | 10.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2872.862 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1262.985 | 9.060 | 167.774 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1262.985 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7719 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1345 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2291 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.062 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.356 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.287 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.30075618E-16 | 0.17394661E-15 | 0.12402583E-13 | -0.41376697E-16 |
24 | 3 | -0.12971024E-07 | 0.72198543E-07 | -0.59837000E-04 | 0.16553701E-12 |
25 | 2 | 0.68419174E-04 | 0.15226993E-02 | 1.1866788 | -0.78740824E-04 |
26 | 1 | -0.34646128E-01 | 0.38608229E-01 | -17.391783 | 0.34506386 |
27 | 0 | 0.98978059E-01 | 0.24269337E-01 | 16.269565 | |
28 | 4 | 0.12402583E-13 | 0.17394661E-15 | 0.30075618E-16 | -0.41376697E-16 |
29 | 3 | -0.59837000E-04 | 0.72198543E-07 | -0.12971024E-07 | 0.16553701E-12 |
30 | 2 | 1.1866788 | 0.15226993E-02 | 0.68419174E-04 | -0.78740824E-04 |
31 | 1 | -17.391783 | 0.38608229E-01 | -0.34646128E-01 | 0.34506386 |
32 | 0 | 16.269565 | 0.24269337E-01 | 0.98978059E-01 | |
33 | 7 | -0.30221493E-12 | 0.42806226E-14 | -0.95155442E-13 | 0.15899766E-15 |
34 | 6 | 0.28727294E-07 | 0.21728364E-09 | 0.65803531E-08 | -0.13544055E-12 |
35 | 5 | -0.19039181E-03 | 0.18585303E-05 | -0.97925888E-04 | 0.65048812E-08 |
36 | 4 | 0.29248049 | 0.90406920E-03 | 0.99803377E-01 | -0.33617969E-04 |
37 | 3 | -7.2729408 | 0.27994057E-01 | -2.3408748 | 0.29041410E-01 |
38 | 2 | 40.892958 | 0.99469394E-01 | 15.273156 | -0.33358329 |
39 | 1 | -80.562512 | 0.44862081E-01 | -29.148912 | 1.0789757 |
40 | 0 | 46.824339 | 0.90199676E-03 | 16.291060 | |
41 | 7 | -0.31585163E-08 | -0.22597303E-14 | 0.15834007E-14 | -0.44811583E-16 |
42 | 6 | 0.38926816E-05 | 0.25726622E-08 | 0.31949392E-02 | -0.26801827E-04 |
43 | 5 | -0.27259256E-03 | 0.15209505E-05 | -0.22401268 | 0.19586932E-02 |
44 | 4 | 0.62224649E-02 | 0.69174334E-04 | 4.8343438 | -0.45311104E-01 |
45 | 3 | -0.54492574E-01 | 0.54963890E-03 | -38.048519 | 0.39895333 |
46 | 2 | 0.19328371 | 0.91376166E-03 | 116.53670 | -1.4186449 |
47 | 1 | -0.27884260 | 0.27809541E-03 | -143.93836 | 2.0495503 |
48 | 0 | 0.13591665 | 0.67534627E-05 | 60.838472 | |
49 | 7 | -0.18366387E-08 | -0.45273224E-15 | 0.66973396E-14 | -0.89481334E-16 |
50 | 6 | 0.64176182E-05 | 0.43906086E-08 | 0.31875387E-02 | -0.26739746E-04 |
51 | 5 | -0.46144041E-03 | 0.26013657E-05 | -0.22359208 | 0.19549808E-02 |
52 | 4 | 0.10613927E-01 | 0.11841222E-03 | 4.8273389 | -0.45243768E-01 |
53 | 3 | -0.93204934E-01 | 0.94170345E-03 | -38.008950 | 0.39851596 |
54 | 2 | 0.33095125 | 0.15665766E-02 | 116.45969 | -1.4176148 |
55 | 1 | -0.47767855 | 0.47741295E-03 | -143.89302 | 2.0488052 |
56 | 0 | 0.23289156 | 0.11519323E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.33_SHGC_SOUTH_0.45 | 38 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.33_SHGC_NORTH_0.45 | 39 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.33_SHGC_EAST_0.45 | 40 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.33_SHGC_WEST_0.45 | 41 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.1099E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.1197E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.9964E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8649E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7607E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8089E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3385E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2383E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.5246E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.4304E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1005 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.9407E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.8635E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.8129E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.2686E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.2687E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9377E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.8661E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6245E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6765E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5777E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5767E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2383E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3385E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 38925.98262 | 46711.17914 | 2.95554 | 3.54665 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 11942.55624 | 14331.06749 | 0.53416 | 1.33138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | -32.70000 | 1.83376E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20205.29873 | 24246.35847 | 1.30106 | 1.56127 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 28.98400 | 1.27239E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 2384.68518 | 2861.62221 | 9.64973E-002 | 1.21700 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 55427.58 | 3.54665 | 3.54665 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 112232.36 | 1.33138 | 1.33138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 28238.85 | 1.56127 | 1.56127 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 102590.74 | 1.21700 | 1.21700 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.54665 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56127 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.54665 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.54665 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.54665 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.54665 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.54665 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.54665 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56127 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56127 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56127 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56127 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56127 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56127 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.54665 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.56127 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.54665 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.54665 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6059.79152 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.54665 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.54665 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.54665 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.34079 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.54665 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.77332 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.36443 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 88057.35000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 44028.67500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70112 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70112 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 88057.35000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 161038.82481 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 161038.82481 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56127 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56127 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1670.63511 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56127 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56127 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56127 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03044 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56127 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78064 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04085 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38770.11000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19385.05500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38770.11000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 111221.53292 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 111221.53292 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 85536.5 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 37660.4 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.135 | 0.130 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.229 | 0.217 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1062962472 | 0.5378425970 | Pass | Pass | 0.1997471136 | 0.6021523753 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 5.0892996916E-002 | 0.3061996218 | Pass | Pass | 5.0547409961E-002 | 0.2212228688 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2678165351 | 0.2494265100 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 858.61 | 147.09 | 2631.33 | 8.88 | 693.54 | 4339.45 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.132 | 0.135 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.221 | 0.229 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.33_SHGC_EAST_0.45 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.875 | 0.451 | 0.497 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.33_SHGC_SOUTH_0.45 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 1.875 | 0.451 | 0.497 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.33_SHGC_WEST_0.45 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.875 | 0.451 | 0.497 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 1.875 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.7280 | 371.75 | 2872.86 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.22 | 0.0000 | Y | 32.48 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.0598 | 139.41 | 1262.99 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.59 | 0.0000 | Y | 17.21 |
Interior Lighting Total | 8.0912 | 511.15 | 4135.85 | 49.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 49.55 | 49.55 | 1.97 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.52 | 63.04 | 23.69 | |
Exterior Lighting Total | 2213.72 | 25.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 88057.35 | 61738.77 | 26318.58 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38770.11 | 27180.95 | 11589.16 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 85536.5 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 37660.4 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 161038.82 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 111221.53 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.55 | 6059.79 | 1708.60 | 1.00 | 1.19 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.56 | 1670.64 | 1070.05 | 1.00 | 1.35 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 38925.98 | 46711.18 | 125.65 | 2.956 | 3.547 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.01061 | 29.98 | 0.01273 | 1.331 | 0.00 |
KITCHEN | 20205.30 | 24246.36 | 173.93 | 1.301 | 1.561 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01045 | 28.98 | 0.01272 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 11942.56 | 14331.07 | 38.55 | 0.534 | 1.331 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00778 | -32.70 | 0.00018 | 1.331 | 0.00 |
KITCHEN | 2384.69 | 2861.62 | 20.53 | 0.096 | 1.217 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00676 | -32.70 | 0.00018 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.55 | 3.55 | 1.33 | 1.33 | 3.5466 | 3.5466 | 3.5466 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.56 | 1.56 | 1.22 | 1.22 | 1.5613 | 1.5613 | 1.5613 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 88057.350 | 61738.769 | 3.546650 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 44028.68 | 29885.77 | 2.364433 | 26.28 | 19.03 | 0.01140257 | 11.36 | 11.12 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 56.3085 | 23.98 | 0.01060720 | 54.5876 | 38920.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 161038.825 | 161038.825 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 161038.82 | 161038.82 | 3.546645 | 0.84 | 0.84 | 0.00493037 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 37.5391 | 21.00 | 0.00778332 | 48.2358 | 11941.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38770.110 | 27180.949 | 1.561270 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19385.06 | 12738.43 | 1.040847 | 29.39 | 20.66 | 0.01234117 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 116.9242 | 25.98 | 0.01047657 | 47.8722 | 20205.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 111221.533 | 111221.533 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:40:00 | 111221.53 | 111221.53 | 1.561272 | -21.44 | -21.44 | 0.00164374 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 77.9494 | 19.00 | 0.00680617 | 47.8205 | 1286.20 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 88057.350 | 61738.769 | 3.546650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0368 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.546645 | 4.09256183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 44028.68 | 29885.77 | 1.0000 | 2.72837839 | 2.364433 | 26.28 | 19.03 | 0.01140257 | 55480.1 | 11.36 | 11.12 | 0.00850000 | 32849.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44028.68 | 30.10 | 0.01272586 | 21.13 | 1.33137743 | 56.3085 | 23.98 | 0.01060720 | 23.98 | 0.01060720 | 54.5876 | 38920.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 161038.825 | 161038.825 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.546645 | 4.09256183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 161038.82 | 161038.82 | 1.0000 | 4.09256183 | 3.546645 | 0.84 | 0.84 | 0.00493037 | 13183.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 161038.82 | -32.70 | 0.00018338 | -32.70 | 1.33137743 | 37.5391 | 21.00 | 0.00778332 | 21.00 | 0.00778332 | 48.2358 | 11941.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38770.110 | 27180.949 | 1.561270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.7816 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.561272 | 1.80159086 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19385.06 | 12738.43 | 1.0000 | 1.20105884 | 1.040847 | 29.39 | 20.66 | 0.01234117 | 61069.8 | 11.90 | 11.35 | 0.00850000 | 33401.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19385.06 | 30.10 | 0.01272586 | 21.13 | 1.21700195 | 116.9242 | 25.94 | 0.01047657 | 25.98 | 0.01047657 | 47.8722 | 20205.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 111221.533 | 111221.533 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.561272 | 1.80159086 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:40:00 | Sensible | 111221.53 | 111221.53 | 1.0000 | 1.80159086 | 1.561272 | -21.44 | -21.44 | 0.00164374 | -17495.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 111221.53 | -32.70 | 0.00018338 | -32.70 | 1.21700195 | 77.9494 | 18.38 | 0.00680617 | 19.00 | 0.00680617 | 47.8205 | 1286.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.55 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3921.17 | 5750.17 | 2784.33 |
KITCHEN | 5190.00 | 6262.50 | 4402.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5313.83 | 7005.50 | 4528.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 39.67 | 2.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 78.83 | 0.00 | 2.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 39.67 | 80.83 | 0.00 | 2.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.449 | 0.600 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.351 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.063 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.523 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36533165.20 | 0.00 | 36533165.20 | 4917447.40 | 41450612.59 | 41986318.57 | 1449.77 | 6028.00 | 1282.23 | 256.08 |
KITCHEN | 28921299.19 | 0.00 | 28921299.19 | 157339.58 | 29078638.77 | 38379373.44 | 7671.01 | 1059.03 | 29.96 | 375.40 |
Total Facility | 65454464.38 | 0.00 | 65454464.38 | 5074786.98 | 70529251.36 | 80365692.01 | 7673.81 | 6032.27 | 1304.36 | 493.23 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3830 | 0.0000 | 1.3830 | 0.1865 | 1.5696 | 1.3314 | 0.00 | 5910.22 | 1276.78 |
KITCHEN | 1.0909 | 0.0000 | 1.0909 | 0.0039 | 1.0948 | 1.2170 | 6125.55 | 1035.59 | 25.86 |
Total Facility | 2.4740 | 0.0000 | 2.4740 | 0.1904 | 2.6644 | 2.5484 | 6125.55 | 5914.49 | 1295.97 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48645407.82 | 0.00 | 48645407.82 | 41986318.57 | 1447.55 | 0.15 | 7312.31 | 256.08 |
PSZ-AC_2:2 | 38509987.79 | 0.00 | 38509987.79 | 38379373.44 | 1445.61 | 0.45 | 7313.94 | 375.40 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8416 | 0.0000 | 1.8416 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4526 | 0.0000 | 1.4526 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1260.74 | 158.78 | 6023.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 147.65 | 1660.40 | 5754.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.1832 | 1.9907 | 1.7733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.6516 | 1.5556 | 1.4269 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
Electricity:Building | 506.05 | 2873.83 | 01-JAN-01:20 | 28589.25 | 02-JAN-11:10 |
Electricity:Zone:DINING | 157.59 | 560.03 | 01-JAN-01:20 | 8723.27 | 02-JAN-16:20 |
Electricity:SpaceType:GENERAL | 499.12 | 2737.55 | 01-JAN-01:20 | 26446.15 | 02-JAN-11:10 |
InteriorLights:Electricity | 49.69 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:DINING | 32.48 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-16:20 |
InteriorLights:Electricity:SpaceType:GENERAL | 49.69 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity | 49.69 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 32.48 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 49.69 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:20 |
Electricity:Zone:KITCHEN | 348.47 | 2313.80 | 01-JAN-01:20 | 20370.03 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.33 | 2147.51 | 01-JAN-01:10 | 17341.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 48.98 | 852.61 | 05-JAN-23:30 | 3219.34 | 23-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 118.02 | 1032.98 | 05-JAN-01:10 | 6482.75 | 23-JUL-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 13.49 | 0.00 | 01-JAN-11:10 | 1510.00 | 21-JUL-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 28.56 | 765.08 | 06-JAN-05:40 | 1076.23 | 18-MAY-03:20 |
ElectricityPurchased:Facility | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
ElectricityPurchased:Plant | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
Cogeneration:ElectricityPurchased | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
General:Cogeneration:ElectricityPurchased | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
ElectricityNet:Plant | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
Cogeneration:ElectricityNet | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
General:Cogeneration:ElectricityNet | 826.03 | 4953.76 | 05-JAN-01:40 | 66480.73 | 30-JUN-12:00 |
Electricity:HVAC | 176.30 | 0.00 | 01-JAN-01:10 | 37840.53 | 29-JUN-18:00 |
Fans:Electricity | 120.63 | 0.00 | 01-JAN-01:10 | 7261.19 | 29-JUN-18:00 |
General:Fans:Electricity | 120.63 | 0.00 | 01-JAN-01:10 | 7261.19 | 29-JUN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 55.67 | 0.00 | 01-JAN-00:10 | 30580.91 | 29-JUN-17:50 |
General:Cooling:Electricity | 55.67 | 0.00 | 01-JAN-00:10 | 30580.91 | 29-JUN-17:50 |
ExteriorLights:Electricity | 25.66 | 0.00 | 01-JAN-08:20 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.66 | 0.00 | 01-JAN-08:20 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.09 | 16-FEB-19:10 |
Water Heater:WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.09 | 16-FEB-19:10 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 05-MAR-10:00 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 05-MAR-10:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1974.36 | 2758.01 | 12-APR-00:10 | 251596.60 | 06-JAN-07:50 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 1086.48 | 0.00 | 01-JAN-01:10 | 205015.21 | 06-JAN-07:10 |
Heating:NaturalGas | 1086.48 | 0.00 | 01-JAN-01:10 | 205015.21 | 06-JAN-07:10 |
General:Heating:NaturalGas | 1086.48 | 0.00 | 01-JAN-01:10 | 205015.21 | 06-JAN-07:10 |
NaturalGas:Plant | 418.09 | 947.76 | 01-JAN-00:10 | 37636.66 | 27-FEB-19:50 |
WaterSystems:NaturalGas | 418.09 | 947.76 | 01-JAN-00:10 | 37636.66 | 27-FEB-19:50 |
Water Heater:WaterSystems:NaturalGas | 418.09 | 947.76 | 01-JAN-00:10 | 37636.66 | 27-FEB-19:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 21-APR-07:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 21-APR-07:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2079.71 | 2930.09 | 05-JAN-01:10 | 212073.22 | 06-JAN-05:00 |
EnergyTransfer:Building | 634.44 | 1465.04 | 05-JAN-01:10 | 63745.13 | 06-JAN-05:00 |
EnergyTransfer:Zone:KITCHEN | 399.14 | 1465.04 | 05-JAN-01:10 | 22888.49 | 02-NOV-11:00 |
Refrigeration:EnergyTransfer | 132.79 | 2620.94 | 05-JAN-23:10 | 7834.84 | 26-MAY-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.40 | 1310.47 | 05-JAN-23:10 | 3917.42 | 26-MAY-03:20 |
General:Refrigeration:EnergyTransfer | 66.40 | 1310.47 | 05-JAN-23:10 | 3917.42 | 26-MAY-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.40 | 1310.47 | 05-JAN-23:10 | 3917.42 | 26-MAY-03:20 |
EnergyTransfer:Plant | 367.54 | 1465.04 | 05-JAN-01:10 | 22565.91 | 01-MAR-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 11.95 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 54.45 | 1305.23 | 06-JAN-05:40 | 2238.70 | 18-MAY-03:20 |
EnergyTransfer:Zone:DINING | 235.30 | 0.00 | 01-JAN-01:10 | 60351.98 | 06-JAN-05:00 |
Heating:EnergyTransfer | 19.14 | 0.00 | 01-JAN-00:20 | 32748.46 | 09-JAN-04:20 |
Heating:EnergyTransfer:Zone:DINING | 19.09 | 0.00 | 01-JAN-00:20 | 32748.46 | 09-JAN-04:20 |
General:Heating:EnergyTransfer | 19.14 | 0.00 | 01-JAN-00:20 | 32748.46 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DINING | 19.09 | 0.00 | 01-JAN-00:20 | 32748.46 | 09-JAN-04:20 |
Cooling:EnergyTransfer | 548.90 | 0.00 | 01-JAN-01:10 | 44558.53 | 29-JUN-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 216.22 | 0.00 | 01-JAN-01:10 | 28612.59 | 06-JAN-05:00 |
General:Cooling:EnergyTransfer | 548.90 | 0.00 | 01-JAN-01:10 | 44558.53 | 29-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 216.22 | 0.00 | 01-JAN-01:10 | 28612.59 | 06-JAN-05:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.06 | 0.00 | 01-JAN-00:10 | 2599.89 | 26-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.06 | 0.00 | 01-JAN-00:10 | 2599.89 | 26-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 332.69 | 0.00 | 01-JAN-01:10 | 19553.14 | 02-NOV-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 332.69 | 0.00 | 01-JAN-01:10 | 19553.14 | 02-NOV-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 301.14 | 0.00 | 01-JAN-01:10 | 20590.53 | 24-FEB-19:30 |
PlantLoopHeatingDemand:Plant | 301.14 | 0.00 | 01-JAN-01:10 | 20590.53 | 24-FEB-19:30 |
WaterSystems:PlantLoopHeatingDemand | 301.14 | 0.00 | 01-JAN-01:10 | 20590.53 | 24-FEB-19:30 |
General:WaterSystems:PlantLoopHeatingDemand | 301.14 | 0.00 | 01-JAN-01:10 | 20590.53 | 24-FEB-19:30 |
EnergyTransfer:HVAC | 1077.73 | 0.00 | 01-JAN-01:10 | 164012.16 | 06-JAN-07:10 |
HeatingCoils:EnergyTransfer | 869.19 | 0.00 | 01-JAN-01:10 | 164012.16 | 06-JAN-07:10 |
CoolingCoils:EnergyTransfer | 208.54 | 0.00 | 01-JAN-00:10 | 118398.53 | 29-JUN-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 301.14 | 0.00 | 01-JAN-01:10 | 20590.53 | 24-FEB-19:30 |
WaterUse:WaterSystems:EnergyTransfer | 301.14 | 0.00 | 01-JAN-01:10 | 20590.53 | 24-FEB-19:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 19.087 | -216.213 | 0.000 | 0.000 | 231.833 | 32.476 | 93.832 | 47.559 | 0.000 | 0.915 | 0.003 | 0.000 | -30.149 | 0.000 | -105.031 | -74.309 |
KITCHEN | 0.000 | 0.000 | 0.057 | -332.675 | 0.000 | 0.000 | 6.231 | 17.209 | 286.918 | 0.000 | 0.000 | 0.007 | 26.095 | 0.000 | 0.000 | 0.000 | -3.842 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.570 | 24.962 | 0.000 | 0.000 | 0.000 | -33.532 | -0.001 |
Total Facility | 0.000 | 0.000 | 19.144 | -548.888 | 0.000 | 0.000 | 238.064 | 49.685 | 380.750 | 47.559 | 0.000 | 9.492 | 51.060 | 0.000 | -30.149 | 0.000 | -142.405 | -74.311 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-JAN-00:01 | 0.00 | 0.00 | 0.00 | -74933.26 | 0.00 | 0.00 | 1157.79 | 409.12 | 540.00 | 0.00 | 0.00 | 0.00 | 77476.36 | 0.00 | -3975.65 | 0.00 | -674.37 | 0.00 |
KITCHEN | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | -65476.68 | 0.00 | 0.00 | 26.93 | 30.01 | 6912.73 | 0.00 | 0.00 | 0.00 | 58675.52 | 0.00 | -0.00 | 0.00 | -168.52 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-AUG-03:01 | 0.00 | 0.00 | 0.00 | -110572.34 | 0.00 | 0.00 | 0.00 | 110.04 | 4372.65 | 0.00 | 0.00 | 1449.08 | 106003.26 | 0.00 | -1362.69 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 16-FEB-04:01 | 0.00 | 0.00 | 107737.39 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2512.59 | 0.00 | -1754.52 | -104450.31 |
KITCHEN | 26-JAN-05:02 | 0.00 | 0.00 | 23363.83 | 0.00 | 0.00 | 0.00 | 27.50 | 30.01 | 6912.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14.51 | -30319.56 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-FEB-04:01 | 0.00 | 0.00 | 107737.39 | 0.00 | 0.00 | 0.00 | 0.00 | 110.04 | 4372.65 | 0.00 | 0.00 | 58.99 | 0.00 | 0.00 | -2512.59 | 0.00 | -2905.71 | -106860.77 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.5466 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.5466 | 0.3754 | 1.0000 | Not calculated | 1.3314 | 0.3754 | ||
PSZ-AC_2:2 | 1.5613 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5613 | 0.1169 | 1.0000 | Not calculated | 0.1826 | 0.1169 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.5466 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.5466 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3754 | ||
PSZ-AC_2:2 | 1.5613 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5613 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1169 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5466 | 3.5466 | 3.5466 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5613 | 1.5613 | 1.5613 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.5466 | 3.5466 | 3.5466 | 3.5466 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5613 | 1.5613 | 1.5613 | 1.5613 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5466 | 3.5466 | 3.5466 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5613 | 1.5613 | 1.5613 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.5466 | 3.5466 | 3.5466 | 3.5466 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5613 | 1.5613 | 1.5613 | 1.5613 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 2.50 |
Number of hours not met | 2.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1086.48 | 205015.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 55.67 | 30580.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 49.69 | 3339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.66 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 120.63 | 7261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.53 | 4742.09 | 418.09 | 37636.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.49 | 1510.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.56 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 498.42 | 826.03 |
Natural Gas | 469.79 | 1974.36 |
Additional | 0.00 | 0.00 |
Total | 968.20 | 2800.39 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 97.20 |
Space Heating | 0.00 |
Space Cooling | 108.91 |
Fans (All) | 236.00 |
Service Water Heating | 147.76 |
Receptacle Equipment | 879.26 |
Miscellaneous (All) | 1616.02 |
Subtotal | 1616.02 |
Natural Gas [MJ/m2] | |
Space Heating | 2125.55 |
Service Water Heating | 817.93 |
Miscellaneous (All) | 3862.56 |
Subtotal | 3862.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.77 |
Space Heating | 38.80 |
Space Cooling | 1.99 |
Fans (All) | 4.31 |
Service Water Heating | 17.63 |
Receptacle Equipment | 32.82 |
Miscellaneous | 2.68 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8306.83 | 445.83 | 7.33 | 0.00 | 0.00 |
ATTIC | 7603.50 | 450.17 | 340.17 | 305.33 | 60.83 |
Min | 7603.50 | 6.67 | 0.00 | 0.00 | 0.00 |
Max | 8753.33 | 450.17 | 340.17 | 305.33 | 60.83 |
Average | 8221.22 | 300.89 | 115.83 | 101.78 | 20.28 |
Sum | 24663.67 | 902.67 | 347.50 | 305.33 | 60.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824210.33 | 11.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19216.33 | 16.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824210.33 | 16.67 | 0.00 | 0.00 | 0.00 |
Average | 281142.22 | 9.44 | 0.00 | 0.00 | 0.00 |
Sum | 843426.67 | 28.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8207.83 | 552.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6819.00 | 1940.33 | 0.67 | 0.00 | 0.00 |
ATTIC | 7587.83 | 686.00 | 205.50 | 139.33 | 141.33 |
Min | 6819.00 | 552.17 | 0.00 | 0.00 | 0.00 |
Max | 8207.83 | 1940.33 | 205.50 | 139.33 | 141.33 |
Average | 7538.22 | 1059.50 | 68.72 | 46.44 | 47.11 |
Sum | 22614.67 | 3178.50 | 206.17 | 139.33 | 141.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 772993.67 | 51228.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14783.83 | 4449.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 772993.67 | 51228.33 | 0.00 | 0.00 | 0.00 |
Average | 262592.50 | 18559.17 | 0.00 | 0.00 | 0.00 |
Sum | 787777.50 | 55677.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354732E+10 | 74935.14 | 06-JAN-00:01 | -32.3 | -32.4 | 0.119975E+11 | 10741.00 | 14-JAN-19:10 | -13.4 | -13.8 |
February | 0.615660E+10 | 67190.69 | 14-FEB-00:01 | -27.0 | -27.2 | 0.108635E+11 | 10741.01 | 11-FEB-19:00 | -27.0 | -27.2 |
March | 0.100508E+11 | 59336.65 | 05-MAR-00:01 | -21.5 | -21.7 | 0.121373E+11 | 10741.00 | 04-MAR-19:00 | -21.5 | -21.7 |
April | 0.173628E+11 | 42859.21 | 04-APR-23:01 | -10.1 | -11.5 | 0.121674E+11 | 14049.95 | 22-APR-18:19 | 16.27 | 7.08 |
May | 0.256403E+11 | 59434.73 | 19-MAY-03:01 | 13.93 | 9.28 | 0.141143E+11 | 14050.04 | 06-MAY-18:19 | 13.93 | 9.28 |
June | 0.276011E+11 | 52966.39 | 18-JUN-03:01 | 12.70 | 7.47 | 0.145616E+11 | 14050.88 | 10-JUN-18:00 | 12.70 | 7.47 |
July | 0.315983E+11 | 57286.78 | 24-JUL-03:01 | 18.30 | 16.16 | 0.151232E+11 | 14050.51 | 15-JUL-18:19 | 18.30 | 16.16 |
August | 0.305490E+11 | 58847.48 | 25-AUG-03:01 | 8.90 | 8.90 | 0.151932E+11 | 14051.28 | 26-AUG-18:00 | 22.20 | 17.55 |
September | 0.262635E+11 | 53829.92 | 08-SEP-03:01 | 11.42 | 10.79 | 0.134605E+11 | 14050.63 | 09-SEP-18:19 | 14.63 | 9.58 |
October | 0.210135E+11 | 41350.32 | 30-OCT-07:07 | -9.0 | -9.4 | 0.123989E+11 | 14047.36 | 21-OCT-18:30 | -9.0 | -9.4 |
November | 0.123846E+11 | 49849.99 | 25-NOV-00:01 | -15.0 | -15.4 | 0.116791E+11 | 12934.52 | 01-NOV-11:00 | -15.0 | -15.4 |
December | 0.404794E+10 | 73120.39 | 25-DEC-00:01 | -31.1 | -31.2 | 0.119920E+11 | 10740.98 | 02-DEC-19:10 | -31.1 | -31.2 |
Annual Sum or Average | 0.216216E+12 | 0.155689E+12 | ||||||||
Minimum of Months | 0.354732E+10 | 41350.32 | -32.3 | -32.4 | 0.108635E+11 | 10740.98 | -31.1 | -31.2 | ||
Maximum of Months | 0.315983E+11 | 74935.14 | 18.30 | 16.16 | 0.151932E+11 | 14051.28 | 22.20 | 17.55 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245397E+11 | 65185.90 | 06-JAN-05:01 | -34.9 | -35.0 | 0.103883E+11 | 6815.12 | 13-JAN-11:39 | -23.5 | -23.8 |
February | 0.229208E+11 | 62450.59 | 14-FEB-05:01 | -32.1 | -32.3 | 0.938376E+10 | 6828.01 | 21-FEB-11:00 | 6.10 | 2.99 |
March | 0.261092E+11 | 56804.68 | 05-MAR-05:01 | -28.1 | -28.3 | 0.103924E+11 | 6819.31 | 28-MAR-10:00 | 4.40 | 2.03 |
April | 0.266768E+11 | 44143.12 | 24-APR-03:01 | 6.32 | 4.80 | 0.100966E+11 | 6930.42 | 18-APR-10:00 | 6.32 | 4.80 |
May | 0.287410E+11 | 56445.77 | 17-MAY-03:01 | 10.07 | 7.04 | 0.105395E+11 | 6930.44 | 19-MAY-10:50 | 16.60 | 12.94 |
June | 0.284907E+11 | 55160.97 | 08-JUN-03:01 | 7.88 | 7.58 | 0.102436E+11 | 6945.22 | 30-JUN-10:50 | 30.92 | 23.73 |
July | 0.307569E+11 | 56159.31 | 18-JUL-03:11 | 8.30 | 8.06 | 0.105883E+11 | 6938.63 | 05-JUL-10:00 | 8.30 | 8.06 |
August | 0.308360E+11 | 51824.98 | 25-AUG-03:01 | 8.90 | 8.90 | 0.105905E+11 | 6930.46 | 15-AUG-10:00 | 8.90 | 8.90 |
September | 0.297010E+11 | 55850.17 | 09-SEP-03:01 | 11.38 | 7.20 | 0.101948E+11 | 6930.45 | 19-SEP-10:00 | 16.10 | 15.79 |
October | 0.306741E+11 | 54606.25 | 20-OCT-03:01 | 6.20 | 5.95 | 0.104322E+11 | 6930.19 | 19-OCT-10:00 | 6.20 | 5.95 |
November | 0.277772E+11 | 48899.42 | 29-NOV-05:01 | -19.6 | -19.9 | 0.100626E+11 | 6928.08 | 01-NOV-10:00 | -19.6 | -19.9 |
December | 0.254623E+11 | 56351.26 | 26-DEC-05:01 | -25.9 | -26.2 | 0.103882E+11 | 6815.13 | 19-DEC-11:39 | -25.9 | -26.2 |
Annual Sum or Average | 0.332686E+12 | 0.123301E+12 | ||||||||
Minimum of Months | 0.229208E+11 | 44143.12 | -34.9 | -35.0 | 0.938376E+10 | 6815.12 | -25.9 | -26.2 | ||
Maximum of Months | 0.308360E+11 | 65185.90 | 11.38 | 8.90 | 0.105905E+11 | 6945.22 | 30.92 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 | -3.3 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 | 0.38 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 | -1.4 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 | 13.57 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 | 0.51 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.703624E+10 | 102195.52 | 12-JAN-04:01 | -16.8 |
February | 0.349083E+10 | 107741.45 | 16-FEB-04:01 | -13.4 |
March | 0.199202E+10 | 101394.38 | 06-MAR-04:01 | -17.4 |
April | 0.399794E+09 | 63734.48 | 04-APR-03:01 | -6.3 |
May | 18094195.99 | 21104.50 | 01-MAY-03:02 | -2.1 |
June | 6284084.25 | 4549.43 | 29-JUN-23:02 | 26.20 |
July | 364483.23 | 2383.04 | 10-JUL-04:05 | 8.07 |
August | 2870.39 | 47.84 | 19-AUG-04:04 | 4.40 |
September | 3488326.41 | 9999.64 | 24-SEP-04:03 | 4.50 |
October | 64308499.35 | 61492.61 | 30-OCT-07:08 | -9.0 |
November | 0.671341E+09 | 64979.89 | 26-NOV-04:01 | -10.6 |
December | 0.540402E+10 | 94658.05 | 14-DEC-05:01 | -23.4 |
Annual Sum or Average | 0.190868E+11 | |||
Minimum of Months | 2870.39 | 47.84 | -23.4 | |
Maximum of Months | 0.703624E+10 | 107741.45 | 26.20 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16838157.82 | 23399.03 | 26-JAN-05:02 | -31.0 |
February | 11734848.73 | 21704.38 | 25-FEB-05:02 | -29.0 |
March | 8763598.31 | 21219.92 | 05-MAR-05:02 | -28.1 |
April | 1769191.87 | 8336.35 | 06-APR-04:03 | -7.0 |
May | 69971.45 | 1166.19 | 01-MAY-04:04 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 283759.62 | 2502.91 | 25-OCT-04:04 | -3.3 |
November | 2389305.25 | 11145.42 | 23-NOV-05:03 | -9.0 |
December | 14964000.79 | 20891.68 | 21-DEC-05:02 | -26.9 |
Annual Sum or Average | 56812833.84 | |||
Minimum of Months | 0.00 | 0.00 | -31.0 | |
Maximum of Months | 16838157.82 | 23399.03 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.307766E+10 | 2454.69 | 02-JAN-16:19 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.264987E+10 | 2454.69 | 01-FEB-17:10 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.281603E+10 | 2454.69 | 01-MAR-17:19 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.252374E+10 | 2454.69 | 01-APR-18:10 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.247407E+10 | 2454.69 | 01-MAY-19:30 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.235701E+10 | 2454.69 | 01-JUN-19:49 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.241906E+10 | 2454.69 | 01-JUL-20:19 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.260633E+10 | 2454.69 | 01-AUG-19:40 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.261028E+10 | 2454.69 | 01-SEP-18:49 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.285160E+10 | 2454.69 | 02-OCT-17:19 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.296074E+10 | 2454.69 | 01-NOV-16:40 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.312965E+10 | 2454.69 | 01-DEC-16:19 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.324761E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.235701E+10 | 2454.69 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.312965E+10 | 2454.69 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.145365E+10 | 885.05 | 02-JAN-10:09 | 0.275454E+11 | 17341.88 | 01-JAN-11:09 |
February | 0.131681E+10 | 885.05 | 01-FEB-10:09 | 0.248798E+11 | 17341.88 | 01-FEB-11:09 |
March | 0.147869E+10 | 885.05 | 01-MAR-10:09 | 0.275456E+11 | 17341.88 | 01-MAR-11:09 |
April | 0.141254E+10 | 885.05 | 01-APR-16:10 | 0.266569E+11 | 17341.88 | 01-APR-10:09 |
May | 0.146617E+10 | 885.05 | 01-MAY-09:09 | 0.275455E+11 | 17341.88 | 01-MAY-10:09 |
June | 0.142908E+10 | 885.05 | 01-JUN-09:09 | 0.266570E+11 | 17341.88 | 01-JUN-10:09 |
July | 0.144981E+10 | 885.05 | 01-JUL-16:10 | 0.275454E+11 | 17341.88 | 01-JUL-10:09 |
August | 0.147869E+10 | 885.05 | 01-AUG-09:09 | 0.275456E+11 | 17341.88 | 01-AUG-10:09 |
September | 0.141289E+10 | 885.05 | 01-SEP-09:09 | 0.266569E+11 | 17341.88 | 01-SEP-10:09 |
October | 0.145348E+10 | 885.05 | 02-OCT-09:09 | 0.275454E+11 | 17341.88 | 01-OCT-10:09 |
November | 0.140753E+10 | 885.05 | 01-NOV-09:09 | 0.266568E+11 | 17341.88 | 01-NOV-10:09 |
December | 0.144998E+10 | 885.05 | 01-DEC-10:09 | 0.275454E+11 | 17341.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.172093E+11 | 0.324326E+12 | ||||
Minimum of Months | 0.131681E+10 | 885.05 | 0.248798E+11 | 17341.88 | ||
Maximum of Months | 0.147869E+10 | 885.05 | 0.275456E+11 | 17341.88 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.307766E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197006E+11 |
February | 0.272721E+11 | 0.264987E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146996E+11 |
March | 0.305458E+11 | 0.281603E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131059E+11 |
April | 0.292871E+11 | 0.252374E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5704008.64 | 0.757739E+10 |
May | 0.303219E+11 | 0.247407E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109088E+09 | 0.359627E+10 |
June | 0.295292E+11 | 0.235701E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301729E+09 | 0.199278E+10 |
July | 0.300798E+11 | 0.241906E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364291E+09 | 0.141501E+10 |
August | 0.305458E+11 | 0.260633E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129972E+09 | 0.214954E+10 |
September | 0.292871E+11 | 0.261028E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4142944.09 | 0.423198E+10 |
October | 0.300980E+11 | 0.285160E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726619E+10 |
November | 0.290996E+11 | 0.296074E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107874E+11 |
December | 0.300798E+11 | 0.312965E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185079E+11 |
Annual Sum or Average | 0.356244E+12 | 0.324761E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914926E+09 | 0.105031E+12 |
Minimum of Months | 0.272721E+11 | 0.235701E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141501E+10 |
Maximum of Months | 0.305458E+11 | 0.312965E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364291E+09 | 0.197006E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.145365E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613804E+09 |
February | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528764E+09 |
March | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386399E+09 |
April | 0.786997E+09 | 0.141254E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 21795.61 | 0.329049E+09 |
May | 0.814802E+09 | 0.146617E+10 | 0.225868E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 477602.12 | 0.174714E+09 |
June | 0.793501E+09 | 0.142908E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 3263630.01 | 0.119077E+09 |
July | 0.808298E+09 | 0.144981E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2781195.88 | 81888519.62 |
August | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 787690.60 | 0.122901E+09 |
September | 0.786997E+09 | 0.141289E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1339.34 | 0.185385E+09 |
October | 0.808786E+09 | 0.145348E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236832E+09 |
November | 0.781956E+09 | 0.140753E+10 | 0.218581E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427837E+09 |
December | 0.808298E+09 | 0.144998E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635789E+09 |
Annual Sum or Average | 0.957291E+10 | 0.172093E+11 | 0.265941E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 7333253.57 | 0.384244E+10 |
Minimum of Months | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81888519.62 |
Maximum of Months | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3263630.01 | 0.635789E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904022E+09 | 0.145000E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798845E+09 | 0.190489E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714961E+09 | 0.299868E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665943E+09 | 0.331986E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643595E+09 | 0.454256E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541629E+09 | 0.439039E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750622E+09 | 0.473006E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581414E+09 | 0.373695E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599129E+09 | 0.269667E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842428E+09 | 0.173606E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779110E+09 | 0.931663E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748452E+09 | 0.109412E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857015E+10 | 0.335319E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541629E+09 | 0.931663E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904022E+09 | 0.473006E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2454.69 | 02-JAN-16:19 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 23350.77 | 04-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2454.69 | 01-FEB-17:10 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 20635.22 | 01-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 2454.69 | 01-MAR-17:19 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 17724.37 | 06-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2454.69 | 01-APR-18:10 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 543.69 | 23-APR-16:05 | 12009.74 | 04-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 2454.69 | 01-MAY-19:30 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1952.58 | 25-MAY-18:00 | 5722.07 | 08-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 2454.69 | 01-JUN-19:49 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3648.01 | 29-JUN-17:05 | 4195.42 | 02-JUN-12:00 |
July | 30255.31 | 01-JUL-18:10 | 2454.69 | 01-JUL-20:19 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1836.70 | 29-JUL-17:03 | 4282.47 | 08-JUL-19:00 |
August | 30255.31 | 05-AUG-18:10 | 2454.69 | 01-AUG-19:40 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1945.08 | 08-AUG-17:03 | 4711.97 | 17-AUG-11:55 |
September | 30255.31 | 02-SEP-18:10 | 2454.69 | 01-SEP-18:49 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 444.97 | 01-SEP-16:05 | 6206.09 | 23-SEP-18:52 |
October | 30255.31 | 07-OCT-18:10 | 2454.69 | 02-OCT-17:19 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 9466.26 | 31-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2454.69 | 01-NOV-16:40 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 16874.89 | 25-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 2454.69 | 01-DEC-16:19 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 21852.80 | 19-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4195.42 | |||||
Maximum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3648.01 | 23350.77 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 885.05 | 02-JAN-10:09 | 14079.00 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1545.48 | 04-JAN-03:00 |
February | 813.01 | 04-FEB-19:10 | 885.05 | 01-FEB-10:09 | 14079.00 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1503.00 | 13-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 885.05 | 01-MAR-10:09 | 14079.00 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1113.15 | 17-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 885.05 | 01-APR-16:10 | 14079.00 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 7.22 | 23-APR-15:55 | 891.98 | 02-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 885.05 | 01-MAY-09:09 | 14079.00 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 9.49 | 24-MAY-14:53 | 522.15 | 09-MAY-03:40 |
June | 813.01 | 03-JUN-18:10 | 885.05 | 01-JUN-09:09 | 14079.00 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 50.97 | 29-JUN-15:00 | 450.69 | 20-JUN-03:30 |
July | 813.01 | 01-JUL-18:10 | 885.05 | 01-JUL-16:10 | 14079.00 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 38.37 | 15-JUL-15:00 | 361.49 | 06-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 885.05 | 01-AUG-09:09 | 14079.00 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 30.65 | 08-AUG-16:00 | 431.71 | 17-AUG-02:00 |
September | 813.01 | 02-SEP-18:10 | 885.05 | 01-SEP-09:09 | 14079.00 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.33 | 01-SEP-15:00 | 663.18 | 11-SEP-03:00 |
October | 813.01 | 07-OCT-18:10 | 885.05 | 02-OCT-09:09 | 14079.00 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 722.83 | 31-OCT-03:40 |
November | 813.01 | 04-NOV-18:10 | 885.05 | 01-NOV-09:09 | 14079.00 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1318.39 | 22-NOV-02:00 |
December | 813.01 | 02-DEC-19:10 | 885.05 | 01-DEC-10:09 | 14079.00 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1348.83 | 16-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 361.49 | ||||||
Maximum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 50.97 | 1545.48 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2130.69 | 28-JAN-02:50 | 5317.23 | 27-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.14 | 17-FEB-07:45 | 5083.33 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1865.14 | 03-MAR-01:00 | 8438.25 | 23-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2149.22 | 22-APR-04:00 | 6961.96 | 22-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1928.26 | 02-MAY-04:01 | 8069.67 | 01-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1885.51 | 04-JUN-03:55 | 7365.92 | 14-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.39 | 15-JUL-04:53 | 8272.01 | 13-JUL-12:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2161.65 | 05-AUG-03:55 | 7192.15 | 04-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1863.63 | 06-SEP-05:40 | 5867.61 | 01-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1918.61 | 25-OCT-07:00 | 5767.42 | 09-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1863.70 | 19-NOV-07:30 | 3421.31 | 07-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1372.88 | 03-DEC-01:25 | 4528.00 | 02-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1372.88 | 3421.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.14 | 8438.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 74935.14 | 06-JAN-00:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.37 |
February | 67190.69 | 14-FEB-00:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.42 |
March | 59336.65 | 05-MAR-00:01 | 16808.50 | 5454.99 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.60 |
April | 42859.21 | 04-APR-23:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.13 |
May | 59434.73 | 19-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 |
June | 52966.39 | 18-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.44 |
July | 57286.78 | 24-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.17 |
August | 58847.48 | 25-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53829.92 | 08-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.72 |
October | 41350.32 | 30-OCT-07:07 | 134468.03 | 16364.68 | 43397.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6708.99 |
November | 49849.99 | 25-NOV-00:01 | 16808.50 | 5454.99 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.16 |
December | 73120.39 | 25-DEC-00:01 | 16808.50 | 5454.99 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 971.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41350.32 | 0.00 | 800.29 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74935.14 | 134468.03 | 16364.68 | 43397.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6708.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 65185.90 | 06-JAN-05:01 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 168.52 |
February | 62450.59 | 14-FEB-05:01 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 190.70 |
March | 56804.68 | 05-MAR-05:01 | 0.00 | 270.10 | 57631.93 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44143.12 | 24-APR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 507.28 |
May | 56445.77 | 17-MAY-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 171.70 |
June | 55160.97 | 08-JUN-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 222.93 |
July | 56159.31 | 18-JUL-03:11 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 51824.98 | 25-AUG-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 55850.17 | 09-SEP-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 320.48 |
October | 54606.25 | 20-OCT-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 161.95 |
November | 48899.42 | 29-NOV-05:01 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 72.53 |
December | 56351.26 | 26-DEC-05:01 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 139.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 44143.12 | 0.00 | 270.10 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65185.90 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 507.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.48 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.00 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.10 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.81 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1505.36 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.85 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.45 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.09 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.30 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.61 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.55 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1505.36 | 114.61 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.685686E+11 | 39339.84 | 05-JAN-11:20 | 0.347014E+12 | 251596.60 | 06-JAN-07:49 |
February | 0.607636E+11 | 38713.45 | 13-FEB-11:20 | 0.260404E+12 | 241690.72 | 14-FEB-07:19 |
March | 0.660759E+11 | 38364.58 | 13-MAR-10:09 | 0.233769E+12 | 206771.92 | 06-MAR-04:30 |
April | 0.625152E+11 | 42796.13 | 23-APR-16:19 | 0.134732E+12 | 155661.34 | 05-APR-06:19 |
May | 0.688877E+11 | 52098.90 | 26-MAY-10:00 | 0.857543E+11 | 107097.75 | 01-MAY-06:30 |
June | 0.749986E+11 | 66480.73 | 30-JUN-11:00 | 0.732901E+11 | 63251.30 | 04-JUN-05:19 |
July | 0.832105E+11 | 60344.68 | 21-JUL-11:00 | 0.726248E+11 | 50196.36 | 03-JUL-18:30 |
August | 0.781009E+11 | 60129.69 | 08-AUG-17:19 | 0.722875E+11 | 52290.41 | 19-AUG-05:10 |
September | 0.651027E+11 | 51713.00 | 01-SEP-10:00 | 0.761350E+11 | 63278.45 | 06-SEP-06:00 |
October | 0.652543E+11 | 41152.69 | 19-OCT-17:19 | 0.116305E+12 | 131480.54 | 30-OCT-06:40 |
November | 0.641991E+11 | 38713.95 | 25-NOV-11:09 | 0.181258E+12 | 206771.92 | 25-NOV-04:30 |
December | 0.683573E+11 | 38938.20 | 21-DEC-11:20 | 0.320785E+12 | 223060.79 | 20-DEC-07:19 |
Annual Sum or Average | 0.826034E+12 | 0.197436E+13 | ||||
Minimum of Months | 0.607636E+11 | 38364.58 | 0.722875E+11 | 50196.36 | ||
Maximum of Months | 0.832105E+11 | 66480.73 | 0.347014E+12 | 251596.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.453132E+10 | 0.301973E+10 | 0.381711E+11 | 0.00 | 0.125909E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639916E+10 | 0.00 |
February | 0.396668E+10 | 0.241596E+10 | 0.344772E+11 | 0.00 | 0.106179E+11 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579138E+10 | 0.00 |
March | 0.429472E+10 | 0.225201E+10 | 0.381714E+11 | 0.00 | 0.109917E+11 | 37879553.69 | 0.00 | 102252.92 | 0.00 | 0.00 | 0.00 | 0.646743E+10 | 0.00 |
April | 0.393628E+10 | 0.175412E+10 | 0.369399E+11 | 0.00 | 0.937254E+10 | 36657632.61 | 0.00 | 0.393834E+09 | 0.00 | 0.00 | 0.00 | 0.620809E+10 | 0.00 |
May | 0.394024E+10 | 0.148731E+10 | 0.381712E+11 | 0.00 | 0.903476E+10 | 37879553.69 | 0.00 | 0.542248E+10 | 0.00 | 0.00 | 0.00 | 0.642116E+10 | 0.00 |
June | 0.378609E+10 | 0.128182E+10 | 0.369400E+11 | 0.00 | 0.896507E+10 | 36657632.61 | 0.00 | 0.133240E+11 | 0.00 | 0.00 | 0.00 | 0.623832E+10 | 0.00 |
July | 0.386887E+10 | 0.138134E+10 | 0.381711E+11 | 0.00 | 0.940426E+10 | 37879553.69 | 0.00 | 0.193477E+11 | 0.00 | 0.00 | 0.00 | 0.637259E+10 | 0.00 |
August | 0.408502E+10 | 0.164539E+10 | 0.381714E+11 | 0.00 | 0.917231E+10 | 37879553.69 | 0.00 | 0.139224E+11 | 0.00 | 0.00 | 0.00 | 0.645118E+10 | 0.00 |
September | 0.402318E+10 | 0.199320E+10 | 0.369399E+11 | 0.00 | 0.870716E+10 | 36657632.61 | 0.00 | 0.294193E+10 | 0.00 | 0.00 | 0.00 | 0.620062E+10 | 0.00 |
October | 0.430508E+10 | 0.250039E+10 | 0.381711E+11 | 0.00 | 0.947337E+10 | 37879553.69 | 0.00 | 0.310826E+09 | 0.00 | 0.00 | 0.00 | 0.639327E+10 | 0.00 |
November | 0.436828E+10 | 0.280608E+10 | 0.369398E+11 | 0.00 | 0.100718E+11 | 36657632.61 | 0.00 | 8537288.21 | 0.00 | 0.00 | 0.00 | 0.619147E+10 | 0.00 |
December | 0.457964E+10 | 0.312200E+10 | 0.381711E+11 | 0.00 | 0.122284E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639101E+10 | 0.00 |
Annual Sum or Average | 0.496854E+11 | 0.256594E+11 | 0.449435E+12 | 0.00 | 0.120630E+12 | 0.446001E+09 | 0.00 | 0.556719E+11 | 0.00 | 0.00 | 0.00 | 0.755257E+11 | 0.00 |
Minimum of Months | 0.378609E+10 | 0.128182E+10 | 0.344772E+11 | 0.00 | 0.870716E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579138E+10 | 0.00 |
Maximum of Months | 0.457964E+10 | 0.312200E+10 | 0.381714E+11 | 0.00 | 0.125909E+11 | 37879553.69 | 0.00 | 0.193477E+11 | 0.00 | 0.00 | 0.00 | 0.646743E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.268773E+12 | 0.00 | 0.383416E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.188948E+12 | 0.00 | 0.354175E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.154493E+12 | 0.00 | 0.393765E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.593478E+11 | 0.00 | 0.367720E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.961029E+10 | 0.00 | 0.362443E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.139514E+10 | 0.00 | 0.332823E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.289144E+09 | 0.00 | 0.324360E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.451535E+09 | 0.00 | 0.319363E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.662650E+10 | 0.00 | 0.308959E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.433833E+11 | 0.00 | 0.330215E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.108967E+12 | 0.00 | 0.336778E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.244199E+12 | 0.00 | 0.366862E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.108648E+13 | 0.00 | 0.418088E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.289144E+09 | 0.00 | 0.308959E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.268773E+12 | 0.00 | 0.393765E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3339.74 | 02-JAN-16:19 | 2213.72 | 01-JAN-06:10 | 24333.76 | 01-JAN-11:09 | 0.00 | 6690.09 | 06-JAN-07:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 3339.74 | 01-FEB-17:10 | 2213.72 | 01-FEB-06:10 | 24333.76 | 01-FEB-11:09 | 0.00 | 6562.48 | 14-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 3339.74 | 01-MAR-17:19 | 2213.72 | 01-MAR-06:10 | 24333.76 | 01-MAR-11:09 | 0.00 | 6347.50 | 05-MAR-07:10 | 17.86 | 05-MAR-09:00 | 0.00 | 01-MAR-00:10 |
April | 3339.74 | 01-APR-18:10 | 2213.72 | 01-APR-05:10 | 24333.76 | 01-APR-10:09 | 0.00 | 5456.88 | 05-APR-05:49 | 17.86 | 16-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 3339.74 | 01-MAY-19:30 | 2213.72 | 01-MAY-19:30 | 24333.76 | 01-MAY-10:09 | 0.00 | 4894.57 | 01-MAY-05:00 | 17.86 | 09-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 3339.74 | 01-JUN-19:49 | 2213.72 | 01-JUN-19:00 | 24333.76 | 01-JUN-10:09 | 0.00 | 7261.19 | 29-JUN-17:00 | 17.86 | 12-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 3339.74 | 01-JUL-20:19 | 2213.72 | 01-JUL-20:19 | 24333.76 | 01-JUL-10:09 | 0.00 | 6231.59 | 15-JUL-13:00 | 17.86 | 03-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 3339.74 | 01-AUG-19:40 | 2213.72 | 01-AUG-19:49 | 24333.76 | 01-AUG-10:09 | 0.00 | 6252.49 | 08-AUG-17:19 | 17.86 | 10-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 3339.74 | 01-SEP-18:49 | 2213.72 | 01-SEP-05:10 | 24333.76 | 01-SEP-10:09 | 0.00 | 4450.74 | 06-SEP-04:00 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 3339.74 | 02-OCT-17:19 | 2213.72 | 01-OCT-05:10 | 24333.76 | 01-OCT-10:09 | 0.00 | 5225.24 | 30-OCT-05:10 | 17.86 | 03-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 3339.74 | 01-NOV-16:40 | 2213.72 | 01-NOV-05:10 | 24333.76 | 01-NOV-10:09 | 0.00 | 6059.79 | 25-NOV-04:30 | 17.86 | 20-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 3339.74 | 01-DEC-16:19 | 2213.72 | 01-DEC-06:10 | 24333.76 | 01-DEC-11:09 | 0.00 | 6497.95 | 24-DEC-07:10 | 17.86 | 01-DEC-00:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 4450.74 | 17.86 | 0.00 | ||||||
Maximum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 7261.19 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.56 | 20-JAN-19:49 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4742.09 | 16-FEB-19:10 | 0.00 |
March | 170.42 | 21-MAR-03:49 | 0.00 | 0.00 | 0.00 | 4741.95 | 15-MAR-18:40 | 0.00 |
April | 11392.53 | 23-APR-17:19 | 0.00 | 0.00 | 0.00 | 4741.97 | 12-APR-06:49 | 0.00 |
May | 18790.57 | 25-MAY-17:00 | 0.00 | 0.00 | 0.00 | 4741.84 | 02-MAY-06:19 | 0.00 |
June | 30580.91 | 29-JUN-17:49 | 0.00 | 0.00 | 0.00 | 4740.35 | 02-JUN-06:49 | 0.00 |
July | 26448.08 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 4739.71 | 18-JUL-06:10 | 0.00 |
August | 25578.22 | 08-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4739.64 | 25-AUG-06:10 | 0.00 |
September | 16252.94 | 01-SEP-17:19 | 0.00 | 0.00 | 0.00 | 4740.97 | 28-SEP-06:40 | 0.00 |
October | 6808.64 | 19-OCT-16:10 | 0.00 | 0.00 | 0.00 | 4741.92 | 24-OCT-18:00 | 0.00 |
November | 739.13 | 21-NOV-04:19 | 0.00 | 0.00 | 0.00 | 4741.93 | 29-NOV-07:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4741.42 | 21-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4739.64 | 0.00 | ||
Maximum of Months | 30580.91 | 0.00 | 0.00 | 0.00 | 4742.09 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39339.84 | 05-JAN-11:20 | 2112.39 | 24333.76 | 0.00 | 0.00 | 6227.12 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 38713.45 | 13-FEB-11:20 | 2112.39 | 24333.76 | 0.00 | 0.00 | 5842.65 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 38364.58 | 13-MAR-10:09 | 2112.39 | 24333.76 | 0.00 | 0.00 | 5328.64 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 42796.13 | 23-APR-16:19 | 1408.26 | 21922.77 | 0.00 | 0.00 | 3916.30 | 17.86 | 0.00 | 10813.47 | 0.00 |
May | 52098.90 | 26-MAY-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4303.00 | 17.86 | 0.00 | 15461.20 | 0.00 |
June | 66480.73 | 30-JUN-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7154.80 | 17.86 | 0.00 | 29753.23 | 0.00 |
July | 60344.68 | 21-JUL-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 6007.74 | 17.86 | 0.00 | 24649.24 | 0.00 |
August | 60129.69 | 08-AUG-17:19 | 2112.39 | 20315.44 | 0.00 | 0.00 | 6252.49 | 17.86 | 0.00 | 25567.06 | 0.00 |
September | 51713.00 | 01-SEP-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4235.43 | 17.86 | 0.00 | 15151.36 | 0.00 |
October | 41152.69 | 19-OCT-17:19 | 3339.74 | 20315.44 | 2213.72 | 0.00 | 3916.30 | 17.86 | 0.00 | 5298.92 | 0.00 |
November | 38713.95 | 25-NOV-11:09 | 1877.68 | 24333.76 | 0.00 | 0.00 | 5429.90 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 38938.20 | 21-DEC-11:20 | 2112.39 | 24333.76 | 0.00 | 0.00 | 5849.83 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 38364.58 | 1408.26 | 20315.44 | 0.00 | 0.00 | 3916.30 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66480.73 | 3339.74 | 24333.76 | 2213.72 | 0.00 | 7154.80 | 17.86 | 0.00 | 29753.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 205015.21 | 06-JAN-07:10 | 0.00 | 37291.28 | 31-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 201298.53 | 01-FEB-04:10 | 0.00 | 37636.66 | 27-FEB-19:49 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 201298.53 | 06-MAR-04:30 | 0.00 | 37625.24 | 02-MAR-19:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 114066.75 | 05-APR-04:19 | 0.00 | 36855.16 | 04-APR-06:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 69117.08 | 01-MAY-05:00 | 0.00 | 35368.65 | 01-MAY-06:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 42608.71 | 04-JUN-04:00 | 0.00 | 32914.20 | 01-JUN-18:30 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 13449.13 | 02-JUL-04:00 | 0.00 | 30296.16 | 03-JUL-06:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 25954.87 | 19-AUG-04:00 | 0.00 | 28564.85 | 03-AUG-06:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 35200.40 | 06-SEP-04:00 | 0.00 | 29065.86 | 29-SEP-06:49 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 94801.46 | 30-OCT-05:10 | 0.00 | 31287.89 | 31-OCT-06:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 201298.53 | 25-NOV-04:30 | 0.00 | 33686.27 | 29-NOV-19:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 201298.53 | 10-DEC-04:00 | 0.00 | 35813.39 | 29-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 13449.13 | 0.00 | 28564.85 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 205015.21 | 0.00 | 37636.66 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
February | 8.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 6.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
April | 1.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.91 | 0.00 | 24.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.65 | 0.00 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.64 | 0.00 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.00 | 24.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.67 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
December | 8.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 39.67 | 19.24 | 0.00 | 19.24 | 2.33 | 19.54 | 0.00 | 19.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.50 | 20.32 | 0.00 | 20.32 | 1.50 | 24.91 | 0.00 | 24.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.57 | 0.00 | 26.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.18 | 0.00 | 27.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.96 | 0.00 | 28.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 29.57 | 1.17 | 29.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 30.10 | 1.33 | 29.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 30.20 | 0.00 | 30.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 29.22 | 0.00 | 29.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.24 | 0.00 | 27.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.99 | 0.00 | 26.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 78.83 | 29.57 | 2.50 | 29.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 30.20 | 1.33 | 30.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.73 | 539.00 | 20.72 | 539.00 | 20.71 |
February | 551.00 | 20.73 | 398.00 | 20.69 | 398.00 | 20.67 |
March | 612.00 | 20.74 | 324.67 | 20.66 | 324.67 | 20.62 |
April | 565.17 | 21.03 | 129.67 | 20.87 | 123.17 | 20.73 |
May | 371.00 | 21.53 | 175.83 | 22.14 | 20.33 | 22.04 |
June | 327.50 | 22.86 | 370.00 | 23.43 | 168.83 | 23.52 |
July | 278.83 | 23.37 | 510.50 | 23.75 | 200.67 | 23.80 |
August | 276.50 | 23.10 | 467.50 | 23.62 | 167.33 | 23.68 |
September | 390.33 | 21.56 | 196.83 | 22.26 | 49.67 | 22.29 |
October | 569.17 | 20.91 | 67.50 | 20.82 | 51.00 | 20.68 |
November | 589.67 | 20.79 | 215.33 | 20.67 | 215.33 | 20.60 |
December | 609.00 | 20.73 | 526.33 | 20.71 | 526.33 | 20.71 |
Annual Sum or Average | 5750.17 | 21.26 | 3921.17 | 21.56 | 2784.33 | 21.49 |
Minimum of Months | 276.50 | 20.73 | 67.50 | 20.66 | 20.33 | 20.60 |
Maximum of Months | 612.00 | 23.37 | 539.00 | 23.75 | 539.00 | 23.80 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.00 | 553.17 | 19.00 | 553.17 | 19.00 |
February | 551.00 | 19.01 | 445.50 | 19.01 | 445.50 | 19.00 |
March | 612.00 | 19.04 | 435.00 | 19.02 | 435.00 | 19.02 |
April | 513.83 | 19.58 | 276.50 | 19.98 | 211.17 | 19.84 |
May | 385.33 | 23.11 | 403.17 | 24.14 | 211.50 | 24.42 |
June | 457.50 | 25.49 | 532.50 | 25.55 | 418.00 | 25.67 |
July | 528.17 | 25.87 | 593.67 | 25.77 | 519.83 | 25.83 |
August | 487.67 | 25.82 | 593.33 | 25.68 | 478.00 | 25.75 |
September | 394.17 | 23.47 | 381.00 | 24.26 | 227.17 | 24.62 |
October | 535.83 | 19.86 | 166.83 | 20.37 | 105.33 | 20.42 |
November | 578.00 | 19.18 | 281.33 | 19.23 | 269.67 | 19.20 |
December | 609.00 | 19.00 | 528.00 | 19.00 | 528.00 | 19.00 |
Annual Sum or Average | 6262.50 | 21.26 | 5190.00 | 21.74 | 4402.33 | 21.80 |
Minimum of Months | 385.33 | 19.00 | 166.83 | 19.00 | 105.33 | 19.00 |
Maximum of Months | 612.00 | 25.87 | 593.67 | 25.77 | 553.17 | 25.83 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73193 | 13.60703 | -0.7074 | 16.37413 |
February | 551.00000 | 20.73324 | 15.52393 | -0.6496 | 14.84603 |
March | 612.00000 | 20.73962 | 19.56379 | -0.6012 | 13.56507 |
April | 590.00000 | 21.15064 | 25.07733 | -0.4066 | 10.56383 |
May | 611.00000 | 22.48272 | 37.69791 | -0.9484 | 28.47514 |
June | 592.00000 | 23.32854 | 52.69972 | -0.5308 | 14.25636 |
July | 609.00000 | 23.65472 | 58.40701 | -0.3327 | 9.05378 |
August | 612.00000 | 23.50956 | 57.07695 | -0.4006 | 10.42847 |
September | 590.00000 | 22.34051 | 47.19905 | -0.8976 | 26.13273 |
October | 610.00000 | 21.10560 | 35.13085 | -0.3155 | 8.89464 |
November | 591.00000 | 20.80137 | 23.86026 | -0.5264 | 11.96867 |
December | 609.00000 | 20.73205 | 15.03344 | -0.6845 | 15.69219 |
Annual Sum or Average | 7187.00000 | 21.78347 | 33.51736 | -0.5828 | 15.01475 |
Minimum of Months | 551.00000 | 20.73193 | 13.60703 | -0.9484 | 8.89464 |
Maximum of Months | 612.00000 | 23.65472 | 58.40701 | -0.3155 | 28.47514 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.00169 | 19.89364 | -0.7781 | 18.06510 |
February | 551.00000 | 19.00833 | 22.89308 | -0.7390 | 16.85271 |
March | 612.00000 | 19.03683 | 27.69114 | -0.6926 | 15.51088 |
April | 590.00000 | 20.27330 | 32.74504 | -0.3386 | 12.70842 |
May | 611.00000 | 23.59876 | 40.24352 | -0.2835 | 20.87616 |
June | 592.00000 | 25.15880 | 50.56296 | 0.34484 | 13.68296 |
July | 609.00000 | 25.57939 | 54.82630 | 0.56303 | 14.57483 |
August | 612.00000 | 25.42533 | 53.18353 | 0.49648 | 13.59188 |
September | 590.00000 | 23.49605 | 47.61462 | -0.2104 | 18.31610 |
October | 610.00000 | 20.33973 | 41.38948 | -0.2062 | 10.87220 |
November | 591.00000 | 19.29534 | 30.62991 | -0.5545 | 13.22710 |
December | 609.00000 | 19.00215 | 21.13970 | -0.7488 | 17.10394 |
Annual Sum or Average | 7187.00000 | 21.61864 | 36.98232 | -0.2590 | 15.44708 |
Minimum of Months | 551.00000 | 19.00169 | 19.89364 | -0.7781 | 10.87220 |
Maximum of Months | 612.00000 | 25.57939 | 54.82630 | 0.56303 | 20.87616 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.758519E+09 | 0.239040E+09 | 28.23 | 0.625784E+09 | 0.132735E+09 | 0.00 | 0.65 | 23-APR-17:10 | 0.00 | 01-APR-00:01 | 25342.41 | 23-APR-17:10 | 20066.74 | 23-APR-17:05 | 5553.73 | 23-APR-18:10 | 7510.55 | 23-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.111582E+11 | 0.334160E+10 | 196.13 | 0.869482E+10 | 0.246337E+10 | 0.00 | 1.00 | 19-MAY-03:01 | 0.00 | 01-MAY-00:01 | 86872.72 | 19-MAY-03:01 | 66888.34 | 19-MAY-03:01 | 38668.38 | 27-MAY-03:01 | 23275.68 | 19-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.284574E+11 | 0.804021E+10 | 337.19 | 0.180514E+11 | 0.104060E+11 | 0.00 | 1.00 | 07-JUN-03:01 | 0.00 | 01-JUN-00:01 | 96521.31 | 30-JUN-03:01 | 59448.32 | 07-JUN-03:51 | 57524.82 | 30-JUN-03:02 | 24008.72 | 30-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.426939E+11 | 0.118053E+11 | 439.12 | 0.252146E+11 | 0.174792E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 96521.31 | 04-JUL-03:01 | 55040.31 | 06-JUL-03:01 | 62633.88 | 04-JUL-03:02 | 24008.72 | 04-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.292575E+11 | 0.835320E+10 | 368.31 | 0.176461E+11 | 0.116114E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 90919.91 | 09-AUG-03:01 | 56125.11 | 07-AUG-03:01 | 47998.87 | 30-AUG-03:01 | 23577.66 | 09-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.512595E+10 | 0.160011E+10 | 142.81 | 0.360446E+10 | 0.152150E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 88642.35 | 01-SEP-03:01 | 53942.05 | 02-SEP-03:01 | 48829.59 | 01-SEP-03:01 | 23408.80 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.536814E+09 | 0.177279E+09 | 25.00 | 0.441496E+09 | 95318146.24 | 0.00 | 0.40 | 19-OCT-13:00 | 0.00 | 01-OCT-00:01 | 14835.30 | 19-OCT-13:00 | 11544.81 | 19-OCT-16:05 | 3402.71 | 19-OCT-13:00 | 4683.72 | 19-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 274691.51 | 95233.36 | 0.17 | 187611.11 | 87080.39 | 0.00 | 0.01 | 01-NOV-13:00 | 0.00 | 01-NOV-00:01 | 457.82 | 01-NOV-13:00 | 312.69 | 01-NOV-13:00 | 145.13 | 01-NOV-13:00 | 158.72 | 01-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.117989E+12 | 0.335569E+11 | 1536.96 | 0.742789E+11 | 0.437097E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.426939E+11 | 0.118053E+11 | 439.12 | 0.252146E+11 | 0.174792E+11 | 0.00 | 1.00 | 0.00 | 96521.31 | 66888.34 | 62633.88 | 24008.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 334267.73 | 102252.92 | 0.08 | 220715.46 | 113552.27 | 0.00 | 0.07 | 21-MAR-03:50 | 0.00 | 01-MAR-00:01 | 1114.23 | 21-MAR-03:50 | 735.72 | 21-MAR-03:50 | 378.51 | 21-MAR-03:50 | 340.84 | 21-MAR-03:50 | 0.00 | 01-MAR-00:01 |
April | 0.569404E+09 | 0.154794E+09 | 32.94 | 0.477662E+09 | 91742627.86 | 0.00 | 1.00 | 14-APR-03:01 | 0.00 | 01-APR-00:01 | 25273.31 | 24-APR-03:01 | 16605.81 | 24-APR-03:01 | 8667.50 | 24-APR-03:01 | 6061.67 | 24-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.810331E+10 | 0.208088E+10 | 227.52 | 0.635164E+10 | 0.175167E+10 | 0.00 | 1.00 | 05-MAY-03:01 | 0.00 | 01-MAY-00:01 | 38248.55 | 18-MAY-03:51 | 28402.46 | 22-MAY-03:01 | 19750.22 | 27-MAY-03:01 | 9170.06 | 11-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.217384E+11 | 0.528379E+10 | 387.94 | 0.133853E+11 | 0.835313E+10 | 0.00 | 1.00 | 02-JUN-03:01 | 0.00 | 01-JUN-00:01 | 42496.66 | 29-JUN-10:51 | 30322.06 | 29-JUN-16:55 | 25550.37 | 30-JUN-02:53 | 10261.25 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.317943E+11 | 0.754241E+10 | 484.00 | 0.181371E+11 | 0.136572E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 42496.66 | 15-JUL-13:10 | 23722.21 | 15-JUL-15:40 | 28371.46 | 04-JUL-03:01 | 9698.28 | 15-JUL-13:53 | 0.00 | 01-JUL-00:01 |
August | 0.228322E+11 | 0.556921E+10 | 426.70 | 0.131625E+11 | 0.966975E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 39753.27 | 08-AUG-16:53 | 23979.53 | 08-AUG-15:30 | 23755.95 | 01-AUG-03:02 | 9253.93 | 09-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.501916E+10 | 0.134182E+10 | 188.16 | 0.331372E+10 | 0.170544E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 38248.55 | 08-SEP-03:01 | 31196.89 | 09-SEP-03:41 | 23141.57 | 01-SEP-03:31 | 9170.06 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.467635E+09 | 0.133547E+09 | 31.17 | 0.375561E+09 | 92074012.64 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 38248.55 | 20-OCT-03:41 | 24439.79 | 02-OCT-03:42 | 16769.25 | 20-OCT-03:41 | 9170.06 | 02-OCT-03:42 | 0.00 | 01-OCT-00:01 |
November | 27882737.61 | 8442054.85 | 5.83 | 18267099.05 | 9615638.56 | 0.00 | 0.38 | 21-NOV-04:08 | 0.00 | 01-NOV-00:01 | 6044.73 | 21-NOV-04:08 | 3131.27 | 21-NOV-04:08 | 2913.46 | 21-NOV-04:08 | 1719.51 | 21-NOV-04:08 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.905526E+11 | 0.221150E+11 | 1784.34 | 0.552219E+11 | 0.353307E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.317943E+11 | 0.754241E+10 | 484.00 | 0.181371E+11 | 0.136572E+11 | 0.00 | 1.00 | 0.00 | 42496.66 | 31196.89 | 28371.46 | 10261.25 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.46 | 74.82 | 105.64 | 69.07 | 648.77 | 0.00 | 0.00 | 0.00 |
February | 286.77 | 123.33 | 163.44 | 171.62 | 507.65 | 0.00 | 0.00 | 0.00 |
March | 389.80 | 195.97 | 193.84 | 305.40 | 389.54 | 0.00 | 0.00 | 0.00 |
April | 536.85 | 289.43 | 247.42 | 534.33 | 234.69 | 0.00 | 0.00 | 0.00 |
May | 583.07 | 257.16 | 325.90 | 663.43 | 128.15 | 0.00 | 0.00 | 0.00 |
June | 657.91 | 314.68 | 343.24 | 804.27 | 92.47 | 0.00 | 0.00 | 0.00 |
July | 645.87 | 303.85 | 342.02 | 803.58 | 87.33 | 0.00 | 0.00 | 0.00 |
August | 497.15 | 217.27 | 279.88 | 594.54 | 104.49 | 0.00 | 0.00 | 0.00 |
September | 399.19 | 179.12 | 220.07 | 428.60 | 158.56 | 0.00 | 0.00 | 0.00 |
October | 240.34 | 90.37 | 149.97 | 193.36 | 245.59 | 0.00 | 0.00 | 0.00 |
November | 153.96 | 51.27 | 102.68 | 74.67 | 389.89 | 0.00 | 0.00 | 0.00 |
December | 141.55 | 53.13 | 88.42 | 43.46 | 631.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 393.13 | 179.34 | 213.79 | 391.56 | 300.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.55 | 51.27 | 88.42 | 43.46 | 87.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 657.91 | 314.68 | 343.24 | 804.27 | 648.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 792.66 | 552.43 | 240.23 | 677.68 | 787.92 | 0.00 | 0.00 | 0.00 |
February | 989.61 | 665.84 | 323.77 | 954.76 | 655.90 | 0.00 | 0.00 | 0.00 |
March | 869.87 | 547.52 | 322.35 | 865.14 | 532.39 | 0.00 | 0.00 | 0.00 |
April | 794.51 | 430.76 | 363.75 | 863.97 | 344.01 | 0.00 | 0.00 | 0.00 |
May | 680.09 | 239.94 | 440.15 | 808.29 | 192.15 | 0.00 | 0.00 | 0.00 |
June | 597.58 | 157.43 | 440.14 | 748.91 | 135.02 | 0.00 | 0.00 | 0.00 |
July | 657.51 | 209.23 | 448.28 | 856.05 | 126.91 | 0.00 | 0.00 | 0.00 |
August | 697.68 | 290.04 | 407.63 | 879.32 | 149.08 | 0.00 | 0.00 | 0.00 |
September | 735.85 | 384.99 | 350.86 | 863.79 | 226.36 | 0.00 | 0.00 | 0.00 |
October | 654.30 | 390.06 | 264.24 | 686.52 | 336.86 | 0.00 | 0.00 | 0.00 |
November | 571.51 | 358.37 | 213.15 | 524.23 | 503.08 | 0.00 | 0.00 | 0.00 |
December | 608.83 | 399.47 | 209.36 | 479.65 | 766.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.13 | 383.78 | 335.35 | 766.01 | 395.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 571.51 | 157.43 | 209.36 | 479.65 | 126.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.61 | 665.84 | 448.28 | 954.76 | 787.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.45 | 78.50 | 106.96 | 80.04 | 653.73 | 0.00 | 0.00 | 0.00 |
February | 300.01 | 137.69 | 162.32 | 201.26 | 521.96 | 0.00 | 0.00 | 0.00 |
March | 393.62 | 201.91 | 191.71 | 322.47 | 402.40 | 0.00 | 0.00 | 0.00 |
April | 502.34 | 254.84 | 247.50 | 496.85 | 244.12 | 0.00 | 0.00 | 0.00 |
May | 617.76 | 295.59 | 322.17 | 713.47 | 135.06 | 0.00 | 0.00 | 0.00 |
June | 593.52 | 256.34 | 337.17 | 720.82 | 95.25 | 0.00 | 0.00 | 0.00 |
July | 634.52 | 295.10 | 339.42 | 793.22 | 90.38 | 0.00 | 0.00 | 0.00 |
August | 520.87 | 236.05 | 284.82 | 629.76 | 106.44 | 0.00 | 0.00 | 0.00 |
September | 408.91 | 183.59 | 225.32 | 444.41 | 162.02 | 0.00 | 0.00 | 0.00 |
October | 258.59 | 104.06 | 154.53 | 222.65 | 250.51 | 0.00 | 0.00 | 0.00 |
November | 157.35 | 53.49 | 103.86 | 83.80 | 394.65 | 0.00 | 0.00 | 0.00 |
December | 138.70 | 48.05 | 90.64 | 43.71 | 634.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 393.15 | 179.01 | 214.13 | 397.20 | 306.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.70 | 48.05 | 90.64 | 43.71 | 90.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.52 | 295.59 | 339.42 | 793.22 | 653.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.483344E+09 | 0.200403E+09 | 0.282940E+09 | 0.185000E+09 | 0.173767E+10 |
February | 0.693756E+09 | 0.298366E+09 | 0.395391E+09 | 0.415187E+09 | 0.122811E+10 |
March | 0.104404E+10 | 0.524874E+09 | 0.519169E+09 | 0.817971E+09 | 0.104335E+10 |
April | 0.139152E+10 | 0.750207E+09 | 0.641317E+09 | 0.138498E+10 | 0.608326E+09 |
May | 0.156168E+10 | 0.688779E+09 | 0.872903E+09 | 0.177694E+10 | 0.343247E+09 |
June | 0.170531E+10 | 0.815642E+09 | 0.889668E+09 | 0.208468E+10 | 0.239676E+09 |
July | 0.172990E+10 | 0.813836E+09 | 0.916063E+09 | 0.215231E+10 | 0.233908E+09 |
August | 0.133157E+10 | 0.581927E+09 | 0.749640E+09 | 0.159241E+10 | 0.279862E+09 |
September | 0.103470E+10 | 0.464271E+09 | 0.570433E+09 | 0.111093E+10 | 0.410993E+09 |
October | 0.643729E+09 | 0.242049E+09 | 0.401680E+09 | 0.517890E+09 | 0.657785E+09 |
November | 0.399057E+09 | 0.132902E+09 | 0.266155E+09 | 0.193538E+09 | 0.101059E+10 |
December | 0.379123E+09 | 0.142309E+09 | 0.236814E+09 | 0.116413E+09 | 0.169070E+10 |
Annual Sum or Average | 0.123977E+11 | 0.565557E+10 | 0.674217E+10 | 0.123482E+11 | 0.948421E+10 |
Minimum of Months | 0.379123E+09 | 0.132902E+09 | 0.236814E+09 | 0.116413E+09 | 0.233908E+09 |
Maximum of Months | 0.172990E+10 | 0.815642E+09 | 0.916063E+09 | 0.215231E+10 | 0.173767E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.212307E+10 | 0.147963E+10 | 0.643438E+09 | 0.181509E+10 | 0.211035E+10 |
February | 0.239407E+10 | 0.161081E+10 | 0.783262E+09 | 0.230976E+10 | 0.158675E+10 |
March | 0.232987E+10 | 0.146648E+10 | 0.863395E+09 | 0.231718E+10 | 0.142596E+10 |
April | 0.205938E+10 | 0.111653E+10 | 0.942849E+09 | 0.223941E+10 | 0.891665E+09 |
May | 0.182155E+10 | 0.642654E+09 | 0.117889E+10 | 0.216492E+10 | 0.514649E+09 |
June | 0.154892E+10 | 0.408071E+09 | 0.114085E+10 | 0.194118E+10 | 0.349971E+09 |
July | 0.176107E+10 | 0.560392E+09 | 0.120068E+10 | 0.229284E+10 | 0.339906E+09 |
August | 0.186865E+10 | 0.776855E+09 | 0.109180E+10 | 0.235518E+10 | 0.399290E+09 |
September | 0.190732E+10 | 0.997884E+09 | 0.909440E+09 | 0.223894E+10 | 0.586730E+09 |
October | 0.175248E+10 | 0.104474E+10 | 0.707740E+09 | 0.183879E+10 | 0.902253E+09 |
November | 0.148136E+10 | 0.928885E+09 | 0.552478E+09 | 0.135881E+10 | 0.130399E+10 |
December | 0.163069E+10 | 0.106993E+10 | 0.560757E+09 | 0.128471E+10 | 0.205278E+10 |
Annual Sum or Average | 0.226784E+11 | 0.121029E+11 | 0.105756E+11 | 0.241568E+11 | 0.124643E+11 |
Minimum of Months | 0.148136E+10 | 0.408071E+09 | 0.552478E+09 | 0.128471E+10 | 0.339906E+09 |
Maximum of Months | 0.239407E+10 | 0.161081E+10 | 0.120068E+10 | 0.235518E+10 | 0.211035E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.496712E+09 | 0.210243E+09 | 0.286468E+09 | 0.214387E+09 | 0.175094E+10 |
February | 0.725790E+09 | 0.333093E+09 | 0.392697E+09 | 0.486882E+09 | 0.126274E+10 |
March | 0.105427E+10 | 0.540795E+09 | 0.513479E+09 | 0.863711E+09 | 0.107778E+10 |
April | 0.130207E+10 | 0.660557E+09 | 0.641516E+09 | 0.128783E+10 | 0.632766E+09 |
May | 0.165460E+10 | 0.791697E+09 | 0.862898E+09 | 0.191096E+10 | 0.361742E+09 |
June | 0.153840E+10 | 0.664440E+09 | 0.873956E+09 | 0.186836E+10 | 0.246897E+09 |
July | 0.169950E+10 | 0.790405E+09 | 0.909091E+09 | 0.212456E+10 | 0.242080E+09 |
August | 0.139510E+10 | 0.632231E+09 | 0.762868E+09 | 0.168674E+10 | 0.285097E+09 |
September | 0.105989E+10 | 0.475853E+09 | 0.584036E+09 | 0.115192E+10 | 0.419968E+09 |
October | 0.692613E+09 | 0.278711E+09 | 0.413902E+09 | 0.596357E+09 | 0.670958E+09 |
November | 0.407858E+09 | 0.138649E+09 | 0.269209E+09 | 0.217204E+09 | 0.102295E+10 |
December | 0.371482E+09 | 0.128706E+09 | 0.242776E+09 | 0.117065E+09 | 0.169817E+10 |
Annual Sum or Average | 0.123983E+11 | 0.564538E+10 | 0.675290E+10 | 0.125260E+11 | 0.967208E+10 |
Minimum of Months | 0.371482E+09 | 0.128706E+09 | 0.242776E+09 | 0.117065E+09 | 0.242080E+09 |
Maximum of Months | 0.169950E+10 | 0.791697E+09 | 0.909091E+09 | 0.212456E+10 | 0.175094E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 695.96 | 1959.59 | 1158.57 | 705.75 | 452.82 | 0.00 | 0.00 |
February | 1244.92 | 1602.80 | 1576.40 | 926.86 | 649.53 | 0.00 | 0.00 |
March | 1428.45 | 1259.78 | 1653.30 | 945.39 | 707.90 | 0.00 | 0.00 |
April | 1848.17 | 775.85 | 1833.71 | 975.03 | 858.67 | 0.00 | 0.00 |
May | 2159.91 | 430.08 | 1880.91 | 792.69 | 1088.22 | 0.00 | 0.00 |
June | 2259.33 | 308.06 | 1849.01 | 728.45 | 1120.55 | 0.00 | 0.00 |
July | 2441.40 | 293.18 | 1937.90 | 808.18 | 1129.72 | 0.00 | 0.00 |
August | 2095.48 | 351.87 | 1715.70 | 743.36 | 972.34 | 0.00 | 0.00 |
September | 1721.80 | 531.94 | 1543.95 | 747.69 | 796.26 | 0.00 | 0.00 |
October | 1087.87 | 818.29 | 1153.23 | 584.49 | 568.74 | 0.00 | 0.00 |
November | 642.60 | 1247.52 | 882.82 | 463.13 | 419.69 | 0.00 | 0.00 |
December | 459.99 | 1924.84 | 889.07 | 500.65 | 388.42 | 0.00 | 0.00 |
Annual Sum or Average | 1508.10 | 956.02 | 1505.41 | 742.13 | 763.28 | 0.00 | 0.00 |
Minimum of Months | 459.99 | 293.18 | 882.82 | 463.13 | 388.42 | 0.00 | 0.00 |
Maximum of Months | 2441.40 | 1959.59 | 1937.90 | 975.03 | 1129.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186407E+10 | 0.524856E+10 | 0.310313E+10 | 0.189028E+10 | 0.121285E+10 | 0.00 | 0.00 |
February | 0.301172E+10 | 0.387749E+10 | 0.381362E+10 | 0.224227E+10 | 0.157135E+10 | 0.00 | 0.00 |
March | 0.382596E+10 | 0.337419E+10 | 0.442819E+10 | 0.253214E+10 | 0.189604E+10 | 0.00 | 0.00 |
April | 0.479044E+10 | 0.201099E+10 | 0.475297E+10 | 0.252729E+10 | 0.222568E+10 | 0.00 | 0.00 |
May | 0.578510E+10 | 0.115192E+10 | 0.503782E+10 | 0.212313E+10 | 0.291469E+10 | 0.00 | 0.00 |
June | 0.585617E+10 | 0.798503E+09 | 0.479263E+10 | 0.188815E+10 | 0.290447E+10 | 0.00 | 0.00 |
July | 0.653906E+10 | 0.785252E+09 | 0.519047E+10 | 0.216463E+10 | 0.302584E+10 | 0.00 | 0.00 |
August | 0.561254E+10 | 0.942458E+09 | 0.459532E+10 | 0.199101E+10 | 0.260431E+10 | 0.00 | 0.00 |
September | 0.446289E+10 | 0.137879E+10 | 0.400192E+10 | 0.193801E+10 | 0.206391E+10 | 0.00 | 0.00 |
October | 0.291374E+10 | 0.219170E+10 | 0.308882E+10 | 0.156550E+10 | 0.152332E+10 | 0.00 | 0.00 |
November | 0.166561E+10 | 0.323358E+10 | 0.228828E+10 | 0.120044E+10 | 0.108784E+10 | 0.00 | 0.00 |
December | 0.123203E+10 | 0.515549E+10 | 0.238129E+10 | 0.134095E+10 | 0.104035E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.475593E+11 | 0.301489E+11 | 0.474745E+11 | 0.234038E+11 | 0.240707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123203E+10 | 0.785252E+09 | 0.228828E+10 | 0.120044E+10 | 0.104035E+10 | 0.00 | 0.00 |
Maximum of Months | 0.653906E+10 | 0.524856E+10 | 0.519047E+10 | 0.253214E+10 | 0.302584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639912E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173944489.5 | 81.22 | 0.00 | 0.00 |
February | 0.579129E+10 | -0.563430E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156989439.8 | 81.22 | 0.00 | 0.00 |
March | 0.646735E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173484788.4 | 81.22 | 0.00 | 0.00 |
April | 0.620795E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164479577.5 | 81.22 | 0.00 | 0.00 |
May | 0.642103E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160835110.2 | 81.21 | 0.00 | 0.00 |
June | 0.623815E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151573052.8 | 81.21 | 0.00 | 0.00 |
July | 0.637244E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155349539.8 | 81.21 | 0.00 | 0.00 |
August | 0.645097E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155762289.1 | 81.21 | 0.00 | 0.00 |
September | 0.620049E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155675107.8 | 81.21 | 0.00 | 0.00 |
October | 0.639310E+10 | -0.622382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -169278524.4 | 81.22 | 0.00 | 0.00 |
November | 0.619148E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166864971.0 | 81.22 | 0.00 | 0.00 |
December | 0.639088E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173787969.3 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755242E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.195802E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579129E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173944489.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646735E+10 | -0.563430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151573052.8 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.288258E+11 | -0.278072E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101866E+10 | 58.99 | 0.00 | 0.00 |
February | 0.266652E+11 | -0.257462E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -919007183.7 | 58.99 | 0.00 | 0.00 |
March | 0.296593E+11 | -0.286448E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101449E+10 | 58.99 | 0.00 | 0.00 |
April | 0.276230E+11 | -0.266725E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -950546917.9 | 58.99 | 0.00 | 0.00 |
May | 0.271317E+11 | -0.262331E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -898610193.8 | 58.99 | 0.00 | 0.00 |
June | 0.248167E+11 | -0.239844E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -832317281.2 | 58.99 | 0.00 | 0.00 |
July | 0.240612E+11 | -0.232126E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -848574914.0 | 58.99 | 0.00 | 0.00 |
August | 0.236668E+11 | -0.228144E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -852443155.6 | 59.00 | 0.00 | 0.00 |
September | 0.228958E+11 | -0.220260E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -869856705.8 | 58.99 | 0.00 | 0.00 |
October | 0.245382E+11 | -0.235623E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -975917120.1 | 58.99 | 0.00 | 0.00 |
November | 0.251341E+11 | -0.241618E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -972263249.4 | 58.99 | 0.00 | 0.00 |
December | 0.274926E+11 | -0.264753E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101723E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.312511E+12 | -0.301341E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.111699E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228958E+11 | -0.286448E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.101866E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.296593E+11 | -0.220260E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -832317281.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.50 | 01-JAN-08:39 | 3726.13 | 33.99 | 197.17 | 234.50 | 3947.58 | 35.46 | 217.50 | 233.83 |
February | 265.33 | 0.52 | 0.50 | 01-FEB-08:39 | 2124.69 | 27.57 | 215.83 | 254.67 | 2238.68 | 27.68 | 209.83 | 253.67 |
March | 254.17 | 0.52 | 0.50 | 02-MAR-10:39 | 1793.71 | 23.55 | 189.83 | 317.50 | 1721.87 | 23.72 | 200.50 | 316.83 |
April | 296.33 | 0.52 | 0.50 | 01-APR-07:40 | 1651.10 | 21.29 | 164.33 | 356.67 | 1691.37 | 21.23 | 155.00 | 356.33 |
May | 437.50 | 0.52 | 0.50 | 01-MAY-05:40 | 1469.85 | 21.97 | 241.67 | 420.67 | 1434.46 | 21.35 | 234.67 | 420.67 |
June | 401.83 | 0.52 | 0.50 | 01-JUN-04:00 | 1330.15 | 22.94 | 255.67 | 426.33 | 1440.93 | 21.45 | 206.50 | 414.50 |
July | 409.17 | 0.52 | 0.50 | 01-JUL-04:00 | 1430.81 | 23.13 | 274.33 | 429.00 | 1687.68 | 21.75 | 222.33 | 421.17 |
August | 352.83 | 0.52 | 0.50 | 01-AUG-07:40 | 1490.88 | 22.14 | 210.33 | 378.33 | 1416.46 | 21.93 | 207.17 | 376.83 |
September | 344.17 | 0.52 | 0.50 | 01-SEP-06:30 | 1378.30 | 21.97 | 198.83 | 332.00 | 1439.10 | 22.29 | 215.00 | 331.17 |
October | 299.00 | 0.52 | 0.50 | 01-OCT-06:49 | 1149.37 | 23.89 | 195.50 | 290.67 | 1109.33 | 23.90 | 198.50 | 290.67 |
November | 255.50 | 0.53 | 0.50 | 01-NOV-07:00 | 2757.78 | 32.90 | 215.17 | 233.83 | 2744.50 | 32.91 | 211.67 | 233.83 |
December | 226.33 | 0.52 | 0.50 | 01-DEC-08:20 | 2746.40 | 33.69 | 193.67 | 218.33 | 2777.88 | 33.90 | 199.17 | 213.50 |
Annual Sum or Average | 3785.50 | 0.52 | 1809.24 | 25.02 | 2552.33 | 3892.50 | 1861.64 | 24.78 | 2477.83 | 3863.00 | ||
Minimum of Months | 226.33 | 0.52 | 0.50 | 1149.37 | 21.29 | 164.33 | 218.33 | 1109.33 | 21.23 | 155.00 | 213.50 | |
Maximum of Months | 437.50 | 0.53 | 0.50 | 3726.13 | 33.99 | 274.33 | 429.00 | 3947.58 | 35.46 | 234.67 | 421.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131675E+12 | 161038.82 | 01-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.939984E+11 | 161038.82 | 01-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.791017E+11 | 161038.82 | 05-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331773E+11 | 104115.52 | 04-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635705E+10 | 46980.54 | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102458E+10 | 27593.86 | 04-JUN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.231315E+09 | 19644.04 | 10-JUL-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.349090E+09 | 22951.76 | 19-AUG-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.489077E+10 | 32441.93 | 24-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265828E+11 | 104778.27 | 30-OCT-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.582246E+11 | 161038.82 | 25-NOV-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120283E+12 | 161038.82 | 01-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.231315E+09 | 19644.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131675E+12 | 161038.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.833437E+11 | 92202.61 | 26-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.571601E+11 | 87791.94 | 25-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444925E+11 | 86095.80 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143009E+11 | 48432.03 | 05-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133118E+10 | 30101.45 | 01-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91535027.98 | 19095.37 | 04-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12138698.68 | 6405.46 | 19-AUG-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410426E+09 | 18532.04 | 06-SEP-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.812388E+10 | 42315.92 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.289494E+11 | 55658.92 | 29-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750766E+11 | 84653.12 | 24-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313292E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.833437E+11 | 92202.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.758519E+09 | 0.625784E+09 | 25342.41 | 23-APR-17:10 | 20062.92 | 0.00 |
May | 0.00 | 0.00 | 0.111582E+11 | 0.869482E+10 | 86872.72 | 19-MAY-03:01 | 66888.34 | 0.00 |
June | 0.00 | 0.00 | 0.284574E+11 | 0.180514E+11 | 96521.31 | 30-JUN-03:01 | 39058.22 | 0.00 |
July | 0.00 | 0.00 | 0.426939E+11 | 0.252146E+11 | 96521.31 | 04-JUL-03:01 | 33893.97 | 0.00 |
August | 0.00 | 0.00 | 0.292575E+11 | 0.176461E+11 | 90919.91 | 09-AUG-03:01 | 43578.16 | 0.00 |
September | 0.00 | 0.00 | 0.512595E+10 | 0.360446E+10 | 88642.35 | 01-SEP-03:01 | 39812.76 | 0.00 |
October | 0.00 | 0.00 | 0.536814E+09 | 0.441496E+09 | 14835.30 | 19-OCT-13:00 | 11432.59 | 0.00 |
November | 0.00 | 0.00 | 274691.51 | 187611.11 | 457.82 | 01-NOV-13:00 | 312.69 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117989E+12 | 0.742789E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.426939E+11 | 0.252146E+11 | 96521.31 | 66888.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 334267.73 | 220715.46 | 1114.23 | 21-MAR-03:50 | 735.72 | 0.00 |
April | 0.00 | 0.00 | 0.569404E+09 | 0.477662E+09 | 25273.31 | 24-APR-03:01 | 16605.81 | 0.00 |
May | 0.00 | 0.00 | 0.810331E+10 | 0.635164E+10 | 38248.55 | 18-MAY-03:51 | 25664.83 | 0.00 |
June | 0.00 | 0.00 | 0.217384E+11 | 0.133853E+11 | 42496.66 | 29-JUN-10:51 | 23001.54 | 0.00 |
July | 0.00 | 0.00 | 0.317943E+11 | 0.181371E+11 | 42496.66 | 15-JUL-13:10 | 19876.81 | 0.00 |
August | 0.00 | 0.00 | 0.228322E+11 | 0.131625E+11 | 39753.27 | 08-AUG-16:53 | 22818.57 | 0.00 |
September | 0.00 | 0.00 | 0.501916E+10 | 0.331372E+10 | 38248.55 | 08-SEP-03:01 | 19710.27 | 0.00 |
October | 0.00 | 0.00 | 0.467635E+09 | 0.375561E+09 | 38248.55 | 20-OCT-03:41 | 21479.30 | 0.00 |
November | 0.00 | 0.00 | 27882737.61 | 18267099.05 | 6044.73 | 21-NOV-04:08 | 3131.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.905526E+11 | 0.552219E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.317943E+11 | 0.181371E+11 | 42496.66 | 25664.83 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10838.21 | 20954.78 | 31-JAN-20:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 11097.99 | 21167.27 | 23-FEB-19:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 11150.35 | 21169.64 | 02-MAR-19:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 10746.54 | 20742.17 | 03-APR-18:35 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10251.18 | 19953.20 | 01-MAY-06:46 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9711.70 | 18822.99 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 9126.37 | 17740.88 | 03-JUL-18:46 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8978.20 | 17034.68 | 01-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8957.81 | 17161.05 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 9256.78 | 18040.40 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9780.30 | 19127.47 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10342.02 | 20149.77 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 10013.34 | ||||
Minimum of Months | 0.00 | 0.00 | 8957.81 | 17034.68 | ||
Maximum of Months | 0.00 | 0.00 | 11150.35 | 21169.64 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.28 |
February | 0.166145E+10 | 0.23 | 824.13 | 01-FEB-00:01 | 0.28 |
March | 0.184119E+10 | 0.23 | 824.13 | 01-MAR-00:01 | 0.28 |
April | 0.180522E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.27 |
May | 0.194540E+10 | 0.24 | 824.13 | 01-MAY-04:01 | 0.27 |
June | 0.192711E+10 | 0.25 | 824.13 | 01-JUN-03:02 | 0.27 |
July | 0.204794E+10 | 0.25 | 824.13 | 01-JUL-00:45 | 0.27 |
August | 0.204621E+10 | 0.25 | 824.13 | 01-AUG-00:55 | 0.27 |
September | 0.188650E+10 | 0.24 | 824.13 | 01-SEP-00:20 | 0.27 |
October | 0.189175E+10 | 0.24 | 824.13 | 01-OCT-03:01 | 0.27 |
November | 0.179285E+10 | 0.23 | 824.13 | 01-NOV-04:01 | 0.27 |
December | 0.183946E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.225245E+11 | 0.24 | |||
Minimum of Months | 0.166145E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.204794E+10 | 0.25 | 824.13 | 0.28 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.850873E+10 | 0.99 | 6059.79 | 01-JAN-04:10 | 1.47 |
February | 0.709405E+10 | 0.95 | 6059.79 | 01-FEB-04:03 | 1.47 |
March | 0.725795E+10 | 0.92 | 6059.79 | 05-MAR-04:01 | 1.47 |
April | 0.599268E+10 | 0.82 | 4110.65 | 09-APR-22:58 | 1.21 |
May | 0.555855E+10 | 0.75 | 3432.88 | 02-MAY-04:01 | 1.10 |
June | 0.538883E+10 | 0.75 | 6059.79 | 25-JUN-03:01 | 1.45 |
July | 0.554785E+10 | 0.75 | 6059.79 | 04-JUL-03:01 | 1.44 |
August | 0.547452E+10 | 0.75 | 6059.79 | 09-AUG-03:01 | 1.45 |
September | 0.534991E+10 | 0.75 | 6059.79 | 01-SEP-03:01 | 1.45 |
October | 0.601152E+10 | 0.79 | 4789.56 | 30-OCT-07:08 | 1.32 |
November | 0.657371E+10 | 0.88 | 6059.79 | 25-NOV-04:10 | 1.47 |
December | 0.822080E+10 | 0.98 | 6059.79 | 01-DEC-04:02 | 1.47 |
Annual Sum or Average | 0.769791E+11 | 0.84 | |||
Minimum of Months | 0.534991E+10 | 0.75 | 3432.88 | 1.10 | |
Maximum of Months | 0.850873E+10 | 0.99 | 6059.79 | 1.47 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.224268E+10 | 0.59 | 1499.23 | 26-JAN-05:02 | 0.88 |
February | 0.186235E+10 | 0.57 | 1459.48 | 25-FEB-05:02 | 0.87 |
March | 0.189259E+10 | 0.54 | 1444.19 | 05-MAR-05:02 | 0.86 |
April | 0.157464E+10 | 0.49 | 1104.75 | 05-APR-04:03 | 0.75 |
May | 0.153080E+10 | 0.49 | 1670.64 | 11-MAY-03:01 | 0.92 |
June | 0.164913E+10 | 0.52 | 1670.64 | 05-JUN-03:01 | 0.92 |
July | 0.180847E+10 | 0.55 | 1670.64 | 01-JUL-03:01 | 0.92 |
August | 0.165158E+10 | 0.53 | 1670.64 | 01-AUG-03:01 | 0.91 |
September | 0.147075E+10 | 0.49 | 1670.64 | 01-SEP-03:01 | 0.91 |
October | 0.157010E+10 | 0.49 | 1520.08 | 20-OCT-03:01 | 0.88 |
November | 0.170526E+10 | 0.52 | 1169.88 | 29-NOV-05:03 | 0.78 |
December | 0.216817E+10 | 0.58 | 1431.19 | 24-DEC-05:02 | 0.86 |
Annual Sum or Average | 0.211265E+11 | 0.53 | |||
Minimum of Months | 0.147075E+10 | 0.49 | 1104.75 | 0.75 | |
Maximum of Months | 0.224268E+10 | 0.59 | 1670.64 | 0.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 46.68 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 45.62 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 45.45 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.22 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 50.36 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 50.67 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.37 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 51.72 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 51.91 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.26 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.52 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 46.93 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 45.45 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 51.91 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 46.68 | 59.92 | 10838.21 | 20954.78 | 31-JAN-20:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 45.62 | 59.03 | 11097.99 | 21167.27 | 23-FEB-19:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 45.45 | 59.33 | 11150.35 | 21169.64 | 02-MAR-19:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 47.38 | 47.38 | 10746.54 | 20742.17 | 03-APR-18:35 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 48.06 | 48.06 | 10251.18 | 19953.20 | 01-MAY-06:46 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 48.88 | 48.88 | 9711.70 | 18822.99 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 48.97 | 48.97 | 9126.37 | 17740.88 | 03-JUL-18:46 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 49.34 | 49.34 | 8978.20 | 17034.68 | 01-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.01 | 50.01 | 8957.81 | 17161.05 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 47.22 | 47.22 | 9256.78 | 18040.40 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 48.75 | 48.75 | 9780.30 | 19127.47 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 46.93 | 58.84 | 10342.02 | 20149.77 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 10013.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.45 | 47.22 | 8957.81 | 17034.68 | ||
Maximum of Months | 0.00 | 0.00 | 50.01 | 59.92 | 11150.35 | 21169.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.850873E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.709405E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.725795E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.623172E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.890015E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.134290E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.173532E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.138277E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.695002E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.618880E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.657381E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.822080E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.110536E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.618880E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.173532E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.224268E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.186235E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.189270E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172943E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.361168E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.693292E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.935088E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.722079E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.281257E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.170364E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.171371E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.216817E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.432415E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.170364E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.935088E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.850873E+10 | 0.00 | 0.131675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709405E+10 | 0.00 | 0.939984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725795E+10 | 0.00 | 0.791017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599268E+10 | 0.758519E+09 | 0.331773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555855E+10 | 0.111468E+11 | 0.635705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.538883E+10 | 0.284277E+11 | 0.102458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.554785E+10 | 0.426142E+11 | 0.231315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.547452E+10 | 0.292077E+11 | 0.349090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.534991E+10 | 0.512064E+10 | 0.489077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601152E+10 | 0.536814E+09 | 0.265828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657371E+10 | 274691.51 | 0.582246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822080E+10 | 0.00 | 0.120283E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769791E+11 | 0.117813E+12 | 0.555895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.534991E+10 | 0.00 | 0.231315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.850873E+10 | 0.426142E+11 | 0.131675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.224268E+10 | 0.00 | 0.833437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186235E+10 | 0.00 | 0.571601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189259E+10 | 334267.73 | 0.444925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157464E+10 | 0.569404E+09 | 0.143009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153080E+10 | 0.808528E+10 | 0.133118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164913E+10 | 0.217014E+11 | 91535027.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180847E+10 | 0.317491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165158E+10 | 0.228212E+11 | 12138698.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147075E+10 | 0.501406E+10 | 0.410426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157010E+10 | 0.465359E+09 | 0.812388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170526E+10 | 27882737.61 | 0.289494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216817E+10 | 0.00 | 0.750766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211265E+11 | 0.904340E+11 | 0.313292E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.224268E+10 | 0.317491E+11 | 0.833437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.850873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599268E+10 | 0.00 | 0.00 | 0.00 | 0.239040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555855E+10 | 0.00 | 0.00 | 0.00 | 0.334160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.538883E+10 | 0.00 | 0.00 | 0.00 | 0.804021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.554785E+10 | 0.00 | 0.00 | 0.00 | 0.118053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.547452E+10 | 0.00 | 0.00 | 0.00 | 0.835320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.534991E+10 | 0.00 | 0.00 | 0.00 | 0.160011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601152E+10 | 0.00 | 0.00 | 0.00 | 0.177279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657371E+10 | 0.00 | 0.00 | 0.00 | 95233.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769791E+11 | 0.00 | 0.00 | 0.00 | 0.335569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.534991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.850873E+10 | 0.00 | 0.00 | 0.00 | 0.118053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.224268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189259E+10 | 0.00 | 0.00 | 0.00 | 102252.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157464E+10 | 0.00 | 0.00 | 0.00 | 0.154794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153080E+10 | 0.00 | 0.00 | 0.00 | 0.208088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164913E+10 | 0.00 | 0.00 | 0.00 | 0.528379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180847E+10 | 0.00 | 0.00 | 0.00 | 0.754241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165158E+10 | 0.00 | 0.00 | 0.00 | 0.556921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147075E+10 | 0.00 | 0.00 | 0.00 | 0.134182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157010E+10 | 0.00 | 0.00 | 0.00 | 0.133547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170526E+10 | 0.00 | 0.00 | 0.00 | 8442054.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211265E+11 | 0.00 | 0.00 | 0.00 | 0.221150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.224268E+10 | 0.00 | 0.00 | 0.00 | 0.754241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.390582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107882E+12 | 0.00 | 0.00 | 3.58 |
February | 0.545262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585226E+11 | 0.00 | 0.00 | 3.58 |
March | 0.729299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319054E+11 | 0.00 | 0.00 | 3.57 |
April | 0.560758E+11 | 21800484.24 | 0.00 | 7913812.60 | 0.00 | 0.606515E+10 | 0.376436E+10 | 0.00 | 3.61 |
May | 0.262039E+11 | 0.463587E+09 | 0.00 | 42542555.35 | 0.00 | 0.347066E+09 | 0.129341E+11 | 0.00 | 3.80 |
June | 0.110872E+11 | 0.510893E+10 | 0.00 | 56836823.02 | 21229146.49 | 8358351.62 | 0.136130E+11 | 0.00 | 3.97 |
July | 0.633340E+10 | 0.767950E+10 | 0.00 | 63221378.36 | 12708704.28 | 3192353.44 | 0.114404E+11 | 0.00 | 4.03 |
August | 0.828398E+10 | 0.299426E+10 | 0.00 | 72318528.77 | 0.00 | 0.00 | 0.165956E+11 | 0.00 | 4.03 |
September | 0.276232E+11 | 81784072.97 | 0.00 | 36217432.42 | 0.00 | 20992906.81 | 0.158054E+11 | 0.00 | 3.81 |
October | 0.589315E+11 | 0.00 | 0.00 | 6942960.68 | 0.00 | 0.131363E+10 | 0.356542E+10 | 0.00 | 3.59 |
November | 0.714084E+11 | 0.00 | 0.00 | 496388.47 | 0.00 | 0.145000E+11 | 0.640996E+09 | 0.00 | 3.58 |
December | 0.462536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911130E+11 | 0.00 | 0.00 | 3.57 |
Annual Sum or Average | 0.478715E+12 | 0.163499E+11 | 0.00 | 0.286490E+09 | 33937850.77 | 0.311682E+12 | 0.783592E+11 | 0.00 | 3.73 |
Minimum of Months | 0.633340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
Maximum of Months | 0.729299E+11 | 0.767950E+10 | 0.00 | 72318528.77 | 21229146.49 | 0.107882E+12 | 0.165956E+11 | 0.00 | 4.03 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120650E+12 | 0.00 | 0.00 | 8085.90 | 80617023.06 | 0.112524E+09 | 6575148.59 | 0.00 | 8.34 |
February | 0.929470E+11 | 0.00 | 1049204.47 | 13023.31 | 0.100648E+09 | 76815541.74 | 6252039.11 | 2092.51 | 8.14 |
March | 0.864760E+11 | 0.00 | 0.00 | 22439.52 | 13008814.05 | 58882477.48 | 16169064.99 | 0.00 | 7.92 |
April | 0.513326E+11 | 0.00 | 0.00 | 9492627.08 | 0.00 | 26078990.52 | 0.545443E+10 | 0.00 | 7.56 |
May | 0.181124E+11 | 59651839.12 | 0.00 | 56613800.48 | 0.00 | 2996910.95 | 0.214277E+11 | 0.00 | 7.55 |
June | 0.570059E+10 | 0.301497E+10 | 0.00 | 78493315.30 | 0.00 | 0.00 | 0.204991E+11 | 0.00 | 7.86 |
July | 0.280010E+10 | 0.405888E+10 | 0.00 | 91776078.68 | 0.00 | 0.00 | 0.167799E+11 | 0.00 | 8.08 |
August | 0.265627E+10 | 0.147447E+10 | 0.00 | 97810666.28 | 0.00 | 0.00 | 0.230171E+11 | 0.00 | 7.86 |
September | 0.155248E+11 | 0.00 | 0.00 | 51925513.98 | 0.00 | 0.00 | 0.251108E+11 | 0.00 | 7.56 |
October | 0.462380E+11 | 0.00 | 0.00 | 10460683.26 | 0.00 | 6350884.74 | 0.733378E+10 | 0.00 | 7.46 |
November | 0.698719E+11 | 0.00 | 0.00 | 1362523.59 | 0.00 | 28368454.59 | 0.133627E+10 | 0.00 | 7.77 |
December | 0.113578E+12 | 0.00 | 0.00 | 13066.88 | 42041470.15 | 0.104983E+09 | 7007571.85 | 0.00 | 8.24 |
Annual Sum or Average | 0.625887E+12 | 0.860798E+10 | 1049204.47 | 0.397992E+09 | 0.236316E+09 | 0.417000E+09 | 0.120995E+12 | 2092.51 | 7.86 |
Minimum of Months | 0.265627E+10 | 0.00 | 0.00 | 8085.90 | 0.00 | 0.00 | 6252039.11 | 0.00 | 7.46 |
Maximum of Months | 0.120650E+12 | 0.405888E+10 | 1049204.47 | 97810666.28 | 0.100648E+09 | 0.112524E+09 | 0.251108E+11 | 2092.51 | 8.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.246025E+11 | 0.227099E+11 | 0.412022E+12 | 0.00 | 0.665112E+11 |
February | 0.478154E+11 | 0.180079E+11 | 0.321857E+12 | 0.00 | 0.508935E+11 |
March | 0.715763E+11 | 0.175671E+11 | 0.303957E+12 | 0.00 | 0.466443E+11 |
April | 0.100842E+12 | 0.123458E+11 | 0.207299E+12 | 0.374470E+09 | 0.303901E+11 |
May | 0.118183E+12 | 0.914972E+10 | 0.144767E+12 | 0.147622E+10 | 0.480867E+11 |
June | 0.125216E+12 | 0.587928E+10 | 0.863631E+11 | 0.170719E+10 | 0.877159E+11 |
July | 0.126965E+12 | 0.395907E+10 | 0.626458E+11 | 0.139883E+10 | 0.120543E+12 |
August | 0.104055E+12 | 0.522935E+10 | 0.947135E+11 | 0.195953E+10 | 0.901216E+11 |
September | 0.761344E+11 | 0.780878E+10 | 0.151105E+12 | 0.163322E+10 | 0.334540E+11 |
October | 0.365667E+11 | 0.999468E+10 | 0.201076E+12 | 0.312354E+09 | 0.251646E+11 |
November | 0.135647E+11 | 0.130976E+11 | 0.256314E+12 | 18185644.89 | 0.334574E+11 |
December | 0.130834E+11 | 0.213370E+11 | 0.389208E+12 | 0.00 | 0.605570E+11 |
Annual Sum or Average | 0.858605E+12 | 0.147086E+12 | 0.263133E+13 | 0.887999E+10 | 0.693539E+12 |
Minimum of Months | 0.130834E+11 | 0.395907E+10 | 0.626458E+11 | 0.00 | 0.251646E+11 |
Maximum of Months | 0.126965E+12 | 0.227099E+11 | 0.412022E+12 | 0.195953E+10 | 0.120543E+12 |