Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:26:55
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1762.09 | 3447.28 | 3447.28 |
Net Site Energy | 1762.09 | 3447.28 | 3447.28 |
Total Source Energy | 3950.81 | 7729.21 | 7729.21 |
Net Source Energy | 3950.81 | 7729.21 | 7729.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 27.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 231.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 130.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.42 | 285.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 37.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 979.69 | 782.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 27.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 231.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 130.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.42 | 285.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 11.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 27.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 231.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 43.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 130.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.42 | 285.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 37.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 856.01 | 611.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 926.08 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1916.64 | 1530.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 856.01 | 611.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 926.08 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1916.64 | 1530.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 979.695 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 979.695 | 100.00 |
Total On-Site and Utility Electric Sources | 979.695 | 100.00 |
Total Electricity End Uses | 979.695 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4745.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.3716 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.8021 | 18.52 | 1057.5080 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.3716 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.8021 | 18.52 | 1057.5080 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Conditioned Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.0345 | 1.78 | 335.6309 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-17:10 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 24-FEB-19:10 |
Heating | 0.00 | 50512.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 37114.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1871.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 19878.74 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8283.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4189.57 | 17470.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1152.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 72508.43 | 81560.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 50512.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 37114.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1871.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19287.94 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8283.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4189.57 | 17470.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 362.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 595.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 29.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 136.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1379.75 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 413.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.85 | 309.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 119.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3102.69 | 848.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 57.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1432.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 267.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 808.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.28 | 605.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 233.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6069.99 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 57.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1432.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 267.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 808.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.28 | 605.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 233.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6069.99 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.57 |
KITCHEN DIRECT AIR | 1.68 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | 1.00 | 0.999992 | 4.57 |
PSZ-AC_2:2 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.00 | 1.00 | 1.68 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.57 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.68 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.57 | 7741.71 |
PSZ-AC_2:2_ADDAQ FAN | 1.68 | 1799.90 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.57 | 4.57 | 4.57 | 3.01 | 95541.98 | 125273.65 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.11 | 41769.89 | 73242.24 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.57 | 2.28 | 3.04 | 95541.98 | 47770.99 | 0.758830 | 0.758830 |
PSZ-AC_2:2 COOLING COIL | 1.68 | 0.841037 | 1.12 | 41769.89 | 20884.94 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 125273.65 |
PSZ-AC_2:2 HEATING COIL | 73242.24 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.372 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.299 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.802 | 408.232 | 649.276 | 0.000 | 0.000 | 0.000 | 1066.310 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2368.645 | 6.372 | 8.455 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2368.645 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1227.055 | 8.802 | 163.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1227.055 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7390 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27638744E-12 | 0.13692172E-14 | -0.80454349E-13 | 0.78568260E-16 |
34 | 6 | 0.25667740E-07 | 0.27924344E-09 | 0.59050449E-08 | -0.11914668E-12 |
35 | 5 | -0.17473551E-03 | 0.24386372E-05 | -0.90062287E-04 | 0.58456630E-08 |
36 | 4 | 0.27398001 | 0.12082630E-02 | 0.93158629E-01 | -0.31026392E-04 |
37 | 3 | -6.9061245 | 0.38026294E-01 | -2.2320589 | 0.27244997E-01 |
38 | 2 | 39.682701 | 0.13706054 | 14.825764 | -0.32010675 |
39 | 1 | -79.634567 | 0.62587550E-01 | -28.747502 | 1.0592017 |
40 | 0 | 46.824345 | 0.12738124E-02 | 16.300887 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.453_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.574 | 2.574 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.453_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.574 | 2.574 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.453_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.574 | 2.574 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.453_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.574 | 2.574 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.62916E-002 | 0.16139 | 0.61691 | 0.61691 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12096 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.62916E-002 | 0.16139 | 0.61691 | 0.61691 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12096 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.62916E-002 | 0.16139 | 0.61691 | 0.61691 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12096 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.62916E-002 | 0.16139 | 0.61691 | 0.61691 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12096 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0829E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0746E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0017E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.2591E-003 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.3306E-004 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.1285E-003 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 7.5380E-004 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.9092E-003 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2580E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1916E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.5922E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.5134E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.0158E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.9859E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0806E-003 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.0808E-003 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.8601E-003 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.7470E-004 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.1681E-003 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.6656E-004 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.9391E-003 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.3263E-004 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.9092E-003 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.5380E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 47510.51260 | 57012.61512 | 3.80465 | 4.56558 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 5285.83124 | 6342.99749 | 0.24956 | 1.33138 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 0.50000 | 4.31558E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20625.49159 | 24750.58991 | 1.40173 | 1.68207 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 0.50000 | 4.31558E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 80687.23 | 4.56562 | 4.56562 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 57769.76 | 1.33138 | 1.33138 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 43168.07 | 1.68207 | 1.68207 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 52806.90 | 1.21700 | 1.21700 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.56558 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.68207 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.56558 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.56558 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.56558 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.56558 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.56562 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.56562 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99999 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.68207 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.68207 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.68207 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.68207 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.68207 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.68207 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.56562 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.68207 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.56562 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.56562 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7741.70608 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.56562 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.56562 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.56562 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.01331 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.56562 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.28281 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.04375 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 95541.98000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 47770.99000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75883 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75883 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 95541.98000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 125273.65375 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 125273.65375 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.68207 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.68207 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1799.89808 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.68207 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.68207 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.68207 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11017 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.68207 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.84104 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.12138 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41769.89000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20884.94500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41769.89000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 73242.24137 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 73242.24137 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 92252.0 | 10.49 | 10.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40574.3 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_EAST_0.25 | N/A | 2.574 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_SOUTH_0.25 | N/A | 2.574 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_WEST_0.25 | N/A | 2.574 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.8683139423E-002 | 0.2671107079 | Pass | Pass | 9.3169332279E-002 | 0.4228011424 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1832462755 | 0.6034366962 | Pass | Pass | 2.3345471130E-002 | 8.0013835135E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4476026219 | 0.4076331470 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1094.44 | 61.90 | 802.80 | 31.73 | 1309.51 | 3300.39 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.453_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.574 | 0.251 | 0.276 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.453_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.574 | 0.251 | 0.276 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.453_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.574 | 0.251 | 0.276 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.574 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.574 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.3716 | 371.75 | 2368.64 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 59.63 | 0.0000 | Y | 26.51 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.8021 | 139.41 | 1227.05 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.61 | 0.0000 | Y | 16.72 |
Interior Lighting Total | 7.0345 | 511.15 | 3595.70 | 43.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 48.79 | 48.79 | 1.93 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.79 | 62.79 | 23.60 | |
Exterior Lighting Total | 2213.72 | 25.54 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 95541.98 | 72500.12 | 23041.86 | 0.76 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41769.89 | 29284.03 | 12485.86 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 92252.0 | 10.49 | 10.44 | ||||
PSZ-AC_2:2 COOLING COIL | 40574.3 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 125273.65 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 73242.24 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.57 | 7741.71 | 1695.65 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.68 | 1799.90 | 1070.05 | 1.00 | 1.34 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 47510.51 | 57012.62 | 153.36 | 3.805 | 4.566 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00941 | 40.53 | 0.00563 | 1.331 | 0.00 |
KITCHEN | 20625.49 | 24750.59 | 177.54 | 1.402 | 1.682 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01032 | 39.60 | 0.00563 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 5285.83 | 6343.00 | 17.06 | 0.250 | 1.331 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00784 | 0.50 | 0.00432 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 20.49 | 0.00351 | 0.50 | 0.00432 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.57 | 4.57 | 1.33 | 1.33 | 4.5656 | 4.5656 | 4.5656 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.68 | 1.68 | 1.22 | 1.22 | 1.6821 | 1.6821 | 1.6821 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 95541.980 | 72500.121 | 4.565620 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 47770.99 | 47770.99 | 3.043747 | 28.89 | 16.89 | 0.00830835 | 11.28 | 10.42 | 0.00830835 | 40.80 | 0.00563111 | 18.58 | 43.7414 | 23.99 | 0.00941107 | 45.9448 | 47487.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 125273.654 | 125273.654 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | 125273.65 | 125273.65 | 4.565616 | 15.02 | 10.46 | 0.00680923 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 29.1610 | 21.00 | 0.00783575 | 45.9999 | 5280.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41769.890 | 29284.034 | 1.682070 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 20884.94 | 20884.94 | 1.121380 | 37.14 | 18.33 | 0.00678607 | 11.84 | 9.09 | 0.00678607 | 40.80 | 0.00563111 | 18.58 | 108.5272 | 25.99 | 0.01032475 | 44.6962 | 19782.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 73242.241 | 73242.241 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 73242.24 | 73242.24 | 1.682073 | 0.36 | 0.11 | 0.00409265 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 72.3513 | 20.49 | 0.00350929 | 21.4101 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 95541.980 | 72500.121 | 4.565620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2848 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.565616 | 4.99110467 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 47770.99 | 47770.99 | 1.0000 | 3.32740625 | 3.043747 | 28.89 | 16.89 | 0.00830835 | 50259.4 | 11.28 | 10.42 | 0.00830835 | 32287.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47770.99 | 40.80 | 0.00563111 | 18.58 | 1.33137743 | 43.7414 | 23.99 | 0.00941107 | 23.99 | 0.00941107 | 45.9448 | 47487.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 125273.654 | 125273.654 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.565616 | 4.99110467 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | Sensible | 125273.65 | 125273.65 | 1.0000 | 4.99110467 | 4.565616 | 15.02 | 10.46 | 0.00680923 | 32314.2 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 125273.65 | 0.50 | 0.00431558 | 0.50 | 1.33137743 | 29.1610 | 21.00 | 0.00783575 | 21.00 | 0.00783575 | 45.9999 | 5280.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41769.890 | 29284.034 | 1.682070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.4550 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.682073 | 1.83883294 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 20884.94 | 20884.94 | 1.0000 | 1.22588613 | 1.121380 | 37.14 | 18.33 | 0.00678607 | 54764.4 | 11.84 | 9.09 | 0.00678607 | 29016.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20884.94 | 40.80 | 0.00563111 | 18.58 | 1.21700195 | 108.5272 | 25.94 | 0.01032475 | 25.99 | 0.01032475 | 44.6962 | 19782.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 73242.241 | 73242.241 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.682073 | 1.83883294 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 73242.24 | 73242.24 | 1.0000 | 1.83883294 | 1.682073 | 0.36 | 0.11 | 0.00409265 | 10601.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73242.24 | 0.50 | 0.00431558 | 0.50 | 1.21700195 | 72.3513 | 0.00 | 0.00350929 | 20.49 | 0.00350929 | 21.4101 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.57 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.68 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3429.17 | 2302.17 | 414.50 |
KITCHEN | 6137.17 | 5566.50 | 4720.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6158.83 | 6583.33 | 4745.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 20.67 | 0.00 | 0.00 |
KITCHEN | 0.00 | 165.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 181.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.923 | 0.900 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.881 | 0.027 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.172 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.296 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 40282026.24 | 0.00 | 40282026.24 | 7274736.16 | 47556762.40 | 41986318.57 | 1436.42 | 5501.18 | 1822.40 | 223.02 |
KITCHEN | 30637133.32 | 0.00 | 30637133.32 | 127800.38 | 30764933.70 | 38379373.44 | 7120.37 | 1625.49 | 14.14 | 637.97 |
Total Facility | 70919159.56 | 0.00 | 70919159.56 | 7402536.53 | 78321696.09 | 80365692.01 | 7124.26 | 5503.74 | 1830.84 | 680.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.5213 | 0.0000 | 1.5213 | 0.2782 | 1.7995 | 1.3314 | 0.00 | 5412.49 | 1774.51 |
KITCHEN | 1.1379 | 0.0000 | 1.1379 | 0.0031 | 1.1410 | 1.2170 | 5556.97 | 1623.46 | 6.57 |
Total Facility | 2.6592 | 0.0000 | 2.6592 | 0.2813 | 2.9404 | 2.5484 | 5556.97 | 5414.99 | 1778.65 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48139542.76 | 0.00 | 48139542.76 | 41986318.57 | 1435.19 | 0.18 | 7324.63 | 223.02 |
PSZ-AC_2:2 | 36611787.40 | 0.00 | 36611787.40 | 38379373.44 | 1398.16 | 1.54 | 7360.30 | 637.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8180 | 0.0000 | 1.8180 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3598 | 0.0000 | 1.3598 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1339.63 | 577.80 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 442.30 | 2390.39 | 4992.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.7011 | 2.0880 | 1.5913 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.3420 | 1.4276 | 1.3333 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
Electricity:Building | 485.83 | 2437.13 | 01-JAN-01:20 | 27911.96 | 02-JAN-11:10 |
Electricity:Zone:DINING | 151.62 | 560.03 | 01-JAN-01:20 | 8292.44 | 02-JAN-17:30 |
Electricity:SpaceType:GENERAL | 478.90 | 2300.85 | 01-JAN-01:20 | 25768.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 43.24 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 26.51 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 43.24 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 43.24 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 26.51 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 43.24 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 334.21 | 1877.10 | 01-JAN-01:20 | 19908.15 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 310.55 | 1710.81 | 01-JAN-01:10 | 16905.18 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 37.71 | 595.55 | 05-DEC-23:30 | 2780.19 | 14-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 106.64 | 741.36 | 09-DEC-01:10 | 5841.95 | 09-AUG-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 11.91 | 0.00 | 01-JAN-11:10 | 1036.69 | 14-JUL-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 18.87 | 509.05 | 07-DEC-06:00 | 637.09 | 08-JAN-14:40 |
ElectricityPurchased:Facility | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
ElectricityPurchased:Plant | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
Cogeneration:ElectricityPurchased | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
ElectricityNet:Plant | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
Cogeneration:ElectricityNet | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
General:Cogeneration:ElectricityNet | 979.69 | 4275.79 | 07-DEC-01:30 | 72508.43 | 28-JUN-17:10 |
Electricity:HVAC | 361.69 | 0.00 | 01-JAN-01:10 | 45398.08 | 28-JUN-17:10 |
Fans:Electricity | 130.42 | 0.00 | 01-JAN-01:10 | 8283.10 | 28-JUN-17:10 |
General:Fans:Electricity | 130.42 | 0.00 | 01-JAN-01:10 | 8283.10 | 28-JUN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 231.27 | 0.00 | 01-JAN-00:10 | 37114.98 | 28-JUN-17:10 |
General:Cooling:Electricity | 231.27 | 0.00 | 01-JAN-00:10 | 37114.98 | 28-JUN-17:10 |
ExteriorLights:Electricity | 25.54 | 0.00 | 01-JAN-07:30 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.54 | 0.00 | 01-JAN-07:30 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4741.93 | 04-DEC-08:00 |
Water Heater:WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4741.93 | 04-DEC-08:00 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-15:20 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-15:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 782.40 | 2758.01 | 01-JAN-01:10 | 81560.45 | 06-DEC-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 27.16 | 0.00 | 01-JAN-01:10 | 52981.58 | 07-DEC-06:10 |
Heating:NaturalGas | 27.16 | 0.00 | 01-JAN-01:10 | 52981.58 | 07-DEC-06:10 |
General:Heating:NaturalGas | 27.16 | 0.00 | 01-JAN-01:10 | 52981.58 | 07-DEC-06:10 |
NaturalGas:Plant | 285.44 | 947.76 | 01-JAN-01:10 | 21809.17 | 18-JAN-08:00 |
WaterSystems:NaturalGas | 285.44 | 947.76 | 01-JAN-01:10 | 21809.17 | 18-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 285.44 | 947.76 | 01-JAN-01:10 | 21809.17 | 18-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-MAR-19:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-MAR-19:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1909.24 | 2932.17 | 09-DEC-01:10 | 175548.05 | 28-JUN-17:20 |
EnergyTransfer:Building | 808.18 | 1466.09 | 09-DEC-01:10 | 56213.78 | 26-AUG-18:10 |
EnergyTransfer:Zone:KITCHEN | 420.01 | 1466.09 | 09-DEC-01:10 | 22964.99 | 09-SEP-11:00 |
Refrigeration:EnergyTransfer | 147.91 | 2621.06 | 05-DEC-23:30 | 7834.84 | 13-JUN-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 73.96 | 1310.53 | 05-DEC-23:30 | 3917.42 | 13-JUN-03:20 |
General:Refrigeration:EnergyTransfer | 73.96 | 1310.53 | 05-DEC-23:30 | 3917.42 | 13-JUN-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 73.96 | 1310.53 | 05-DEC-23:30 | 3917.42 | 13-JUN-03:20 |
EnergyTransfer:Plant | 269.40 | 1466.09 | 09-DEC-01:10 | 16732.24 | 23-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.28 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 61.68 | 1305.28 | 07-DEC-06:00 | 2238.70 | 08-JAN-14:40 |
EnergyTransfer:Zone:DINING | 388.17 | 0.00 | 01-JAN-01:10 | 36359.57 | 28-JUN-17:20 |
Heating:EnergyTransfer | 1.31 | 0.00 | 01-JAN-00:10 | 10509.97 | 20-JUL-23:10 |
Heating:EnergyTransfer:Zone:DINING | 1.31 | 0.00 | 01-JAN-00:10 | 10509.97 | 20-JUL-23:10 |
General:Heating:EnergyTransfer | 1.31 | 0.00 | 01-JAN-00:10 | 10509.97 | 20-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 1.31 | 0.00 | 01-JAN-00:10 | 10509.97 | 20-JUL-23:10 |
Cooling:EnergyTransfer | 732.92 | 0.00 | 01-JAN-01:10 | 53727.78 | 28-JUN-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 386.86 | 0.00 | 01-JAN-01:10 | 36359.57 | 28-JUN-17:20 |
General:Cooling:EnergyTransfer | 732.92 | 0.00 | 01-JAN-01:10 | 53727.78 | 28-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 386.86 | 0.00 | 01-JAN-01:10 | 36359.57 | 28-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 198.91 | 07-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 198.91 | 07-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 346.06 | 0.00 | 01-JAN-01:10 | 19127.31 | 22-JUL-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 346.06 | 0.00 | 01-JAN-01:10 | 19127.31 | 22-JUL-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 195.45 | 0.00 | 01-JAN-01:10 | 14212.28 | 25-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 195.45 | 0.00 | 01-JAN-01:10 | 14212.28 | 25-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14212.28 | 25-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14212.28 | 25-JAN-07:10 |
EnergyTransfer:HVAC | 831.65 | 0.00 | 01-JAN-01:10 | 110509.32 | 19-JUL-12:00 |
HeatingCoils:EnergyTransfer | 21.73 | 0.00 | 01-JAN-01:10 | 42385.27 | 07-DEC-06:10 |
CoolingCoils:EnergyTransfer | 809.92 | 0.00 | 01-JAN-00:10 | 110509.32 | 19-JUL-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14212.28 | 25-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14212.28 | 25-JAN-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.307 | -386.856 | 0.000 | 0.000 | 211.215 | 26.512 | 93.832 | 49.670 | 0.000 | 28.520 | 19.128 | 0.000 | -14.352 | 0.000 | -28.977 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -346.048 | 0.000 | 0.000 | 5.012 | 16.725 | 273.146 | 0.000 | 0.000 | 0.226 | 51.899 | 0.000 | 0.000 | 0.000 | -0.959 | -0.003 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.389 | 35.417 | 0.000 | 0.000 | 0.000 | -46.806 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.308 | -732.905 | 0.000 | 0.000 | 216.227 | 43.237 | 366.978 | 49.670 | 0.000 | 40.135 | 106.444 | 0.000 | -14.352 | 0.000 | -76.743 | -0.004 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-JUL-03:01 | 0.00 | 0.00 | 0.00 | -92323.42 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 92157.22 | 0.00 | -774.87 | 0.00 | -38.96 | 0.00 |
KITCHEN | 14-MAY-03:11 | 0.00 | 0.00 | 0.00 | -62293.69 | 0.00 | 0.00 | 0.00 | 30.01 | 3035.94 | 0.00 | 0.00 | 0.00 | 59354.79 | 0.00 | -0.00 | 0.00 | -127.05 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-JUL-03:01 | 0.00 | 0.00 | 0.00 | -142067.15 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 952.22 | 137943.42 | 0.00 | -774.87 | 0.00 | -99.60 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-JUL-03:47 | 0.00 | 0.00 | 23743.25 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.69 | 0.00 | 0.00 | -799.28 | 0.00 | 0.00 | -23924.70 |
KITCHEN | 07-DEC-05:04 | 0.00 | 0.00 | 1986.45 | 0.00 | 0.00 | 0.00 | 22.07 | 30.01 | 6476.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -60.18 | -8454.38 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-JUL-03:47 | 0.00 | 0.00 | 23743.25 | 0.00 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 1199.93 | 0.00 | 0.00 | -799.28 | 0.00 | -26.97 | -28162.92 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.5656 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.5656 | 0.2916 | 1.0000 | Not calculated | 1.3314 | 0.2916 | ||
PSZ-AC_2:2 | 1.6821 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6821 | 0.1085 | 1.0000 | Not calculated | 0.1826 | 0.1085 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.5656 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.5656 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2916 | ||
PSZ-AC_2:2 | 1.6821 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6821 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1085 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5656 | 4.5656 | 4.5656 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6821 | 1.6821 | 1.6821 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.5656 | 4.5656 | 4.5656 | 4.5656 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6821 | 1.6821 | 1.6821 | 1.6821 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5656 | 4.5656 | 4.5656 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6821 | 1.6821 | 1.6821 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.5656 | 4.5656 | 4.5656 | 4.5656 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6821 | 1.6821 | 1.6821 | 1.6821 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 27.16 | 52981.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 231.27 | 37114.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 43.24 | 2883.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.54 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 130.42 | 8283.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.42 | 4741.93 | 285.44 | 21809.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 11.91 | 1036.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 18.87 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 473.37 | 979.69 |
Natural Gas | 469.79 | 782.40 |
Additional | 0.00 | 0.00 |
Total | 943.16 | 1762.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.59 |
Space Heating | 0.00 |
Space Cooling | 452.46 |
Fans (All) | 255.14 |
Service Water Heating | 147.55 |
Receptacle Equipment | 852.31 |
Miscellaneous (All) | 1916.64 |
Subtotal | 1916.64 |
Natural Gas [MJ/m2] | |
Space Heating | 53.14 |
Service Water Heating | 558.43 |
Miscellaneous (All) | 1530.65 |
Subtotal | 1530.65 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.45 |
Space Heating | 1.54 |
Space Cooling | 13.13 |
Fans (All) | 7.40 |
Service Water Heating | 20.48 |
Receptacle Equipment | 51.39 |
Miscellaneous | 3.61 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8532.17 | 227.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7830.67 | 921.67 | 7.67 | 0.00 | 0.00 |
ATTIC | 5260.33 | 1047.83 | 904.50 | 1257.17 | 290.17 |
Min | 5260.33 | 227.83 | 0.00 | 0.00 | 0.00 |
Max | 8532.17 | 1047.83 | 904.50 | 1257.17 | 290.17 |
Average | 7207.72 | 732.44 | 304.06 | 419.06 | 96.72 |
Sum | 21623.17 | 2197.33 | 912.17 | 1257.17 | 290.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 823386.67 | 835.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823386.67 | 835.33 | 0.00 | 0.00 | 0.00 |
Average | 280873.22 | 278.44 | 0.00 | 0.00 | 0.00 |
Sum | 842619.67 | 835.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8355.00 | 405.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6658.83 | 2100.83 | 0.33 | 0.00 | 0.00 |
ATTIC | 5425.83 | 1602.00 | 457.50 | 361.33 | 913.33 |
Min | 5425.83 | 405.00 | 0.00 | 0.00 | 0.00 |
Max | 8355.00 | 2100.83 | 457.50 | 361.33 | 913.33 |
Average | 6813.22 | 1369.28 | 152.61 | 120.44 | 304.44 |
Sum | 20439.67 | 4107.83 | 457.83 | 361.33 | 913.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 808595.67 | 15626.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15181.83 | 4051.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 808595.67 | 15626.33 | 0.00 | 0.00 | 0.00 |
Average | 274592.50 | 6559.17 | 0.00 | 0.00 | 0.00 |
Sum | 823777.50 | 19677.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:55
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251769E+11 | 61869.38 | 08-JAN-04:01 | 17.00 | 11.36 | 0.145650E+11 | 14051.32 | 07-JAN-19:00 | 17.00 | 11.36 |
February | 0.191650E+11 | 22612.10 | 01-FEB-05:01 | 5.00 | 3.59 | 0.126693E+11 | 14048.67 | 25-FEB-19:10 | 14.83 | 9.57 |
March | 0.236050E+11 | 62478.82 | 17-MAR-03:01 | 16.33 | 10.90 | 0.148015E+11 | 14049.92 | 18-MAR-18:49 | 23.67 | 11.80 |
April | 0.328311E+11 | 78478.99 | 25-APR-03:01 | 24.00 | 12.37 | 0.147956E+11 | 14050.31 | 15-APR-18:00 | 24.00 | 12.37 |
May | 0.367087E+11 | 81262.23 | 01-MAY-03:01 | 13.58 | 4.86 | 0.154020E+11 | 14049.91 | 13-MAY-18:00 | 27.00 | 9.96 |
June | 0.423710E+11 | 91292.83 | 25-JUN-03:01 | 22.00 | 11.77 | 0.150136E+11 | 14050.01 | 17-JUN-18:10 | 22.00 | 11.77 |
July | 0.426289E+11 | 92323.16 | 06-JUL-03:01 | 22.00 | 10.77 | 0.153314E+11 | 14050.46 | 08-JUL-18:10 | 27.83 | 18.87 |
August | 0.427939E+11 | 89572.82 | 26-AUG-03:01 | 23.00 | 9.61 | 0.155251E+11 | 14051.26 | 05-AUG-18:30 | 23.00 | 9.61 |
September | 0.394412E+11 | 88815.22 | 17-SEP-03:01 | 22.20 | 12.79 | 0.149035E+11 | 14050.41 | 09-SEP-18:49 | 22.20 | 12.79 |
October | 0.330936E+11 | 81442.45 | 18-OCT-03:01 | 14.00 | 5.24 | 0.150867E+11 | 14051.95 | 07-OCT-18:30 | 14.00 | 5.24 |
November | 0.258771E+11 | 61867.30 | 02-NOV-03:01 | 14.17 | 11.17 | 0.142294E+11 | 14049.91 | 04-NOV-18:19 | 16.33 | 7.56 |
December | 0.231671E+11 | 24962.20 | 14-DEC-05:01 | 2.00 | -0.3 | 0.139835E+11 | 14049.91 | 02-DEC-19:00 | 2.00 | -0.3 |
Annual Sum or Average | 0.386859E+12 | 0.176307E+12 | ||||||||
Minimum of Months | 0.191650E+11 | 22612.10 | 2.00 | -0.3 | 0.126693E+11 | 14048.67 | 2.00 | -0.3 | ||
Maximum of Months | 0.427939E+11 | 92323.16 | 24.00 | 12.79 | 0.155251E+11 | 14051.95 | 27.83 | 18.87 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272652E+11 | 49381.54 | 07-JAN-04:01 | 14.00 | 7.98 | 0.105560E+11 | 6930.40 | 09-JAN-11:00 | 17.00 | 11.36 |
February | 0.244116E+11 | 39660.59 | 17-FEB-04:01 | 11.83 | 11.83 | 0.951353E+10 | 6930.44 | 16-FEB-11:00 | 11.83 | 11.83 |
March | 0.268313E+11 | 53831.45 | 21-MAR-03:01 | 12.75 | 8.43 | 0.105659E+11 | 6930.43 | 01-MAR-11:00 | 12.75 | 8.43 |
April | 0.277007E+11 | 61035.07 | 20-APR-03:11 | 13.67 | 5.59 | 0.102500E+11 | 6930.39 | 07-APR-10:50 | 13.67 | 5.59 |
May | 0.293689E+11 | 62347.18 | 14-MAY-03:11 | 14.00 | 4.29 | 0.105968E+11 | 6930.38 | 18-MAY-10:00 | 32.00 | 13.10 |
June | 0.305369E+11 | 53193.23 | 21-JUN-03:11 | 20.33 | 9.33 | 0.102583E+11 | 6930.39 | 05-JUN-10:00 | 20.33 | 9.33 |
July | 0.320835E+11 | 54462.63 | 02-JUL-03:11 | 19.63 | 7.07 | 0.105944E+11 | 6930.41 | 14-JUL-10:20 | 29.00 | 21.28 |
August | 0.321055E+11 | 53211.01 | 25-AUG-03:11 | 21.33 | 9.42 | 0.106007E+11 | 6930.39 | 03-AUG-10:50 | 21.33 | 9.42 |
September | 0.307604E+11 | 49628.32 | 29-SEP-03:11 | 21.47 | 11.73 | 0.102550E+11 | 6930.39 | 21-SEP-10:20 | 21.47 | 11.73 |
October | 0.295993E+11 | 58327.60 | 12-OCT-03:01 | 8.00 | 3.46 | 0.105827E+11 | 6930.41 | 23-OCT-10:00 | 19.00 | 12.59 |
November | 0.275596E+11 | 55726.54 | 22-NOV-04:01 | 13.50 | 7.58 | 0.102223E+11 | 6930.46 | 03-NOV-10:00 | 13.50 | 7.58 |
December | 0.278358E+11 | 43832.04 | 23-DEC-04:01 | 10.17 | 3.09 | 0.105247E+11 | 6930.40 | 12-DEC-11:00 | 10.17 | 3.09 |
Annual Sum or Average | 0.346059E+12 | 0.124520E+12 | ||||||||
Minimum of Months | 0.244116E+11 | 39660.59 | 8.00 | 3.09 | 0.951353E+10 | 6930.38 | 10.17 | 3.09 | ||
Maximum of Months | 0.321055E+11 | 62347.18 | 21.47 | 11.83 | 0.106007E+11 | 6930.46 | 32.00 | 21.28 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 | 1.81 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 | 4.43 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 | 8.83 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 | 7.34 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 | 7.18 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 | 11.09 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 | 14.60 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 | 18.35 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 | 16.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 | 15.51 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 | 10.27 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 | 2.98 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.00 | 0.00 | 4.27 | 1.81 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.00 | 0.00 | 29.40 | 18.35 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1161247.68 | 2958.23 | 12-JAN-05:04 | 6.00 |
February | 1991315.35 | 6052.42 | 09-FEB-05:03 | 5.00 |
March | 1812585.16 | 9380.76 | 26-MAR-04:02 | 0.50 |
April | 20693660.73 | 20624.55 | 25-APR-03:47 | 24.00 |
May | 57641672.26 | 12082.12 | 21-MAY-03:47 | 19.83 |
June | 0.404120E+09 | 14087.88 | 29-JUN-23:01 | 32.83 |
July | 0.381293E+09 | 23747.63 | 04-JUL-03:47 | 21.00 |
August | 0.293930E+09 | 11489.10 | 13-AUG-23:01 | 31.00 |
September | 0.115522E+09 | 11501.32 | 17-SEP-03:45 | 22.20 |
October | 25861666.15 | 7835.81 | 21-OCT-03:04 | 17.17 |
November | 175153.27 | 1713.88 | 24-NOV-05:03 | 3.83 |
December | 3236207.68 | 6905.37 | 14-DEC-05:03 | 2.00 |
Annual Sum or Average | 0.130744E+10 | |||
Minimum of Months | 175153.27 | 1713.88 | 0.50 | |
Maximum of Months | 0.404120E+09 | 23747.63 | 32.83 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 |
August | 18689.17 | 186.89 | 17-AUG-04:02 | 24.83 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 119345.08 | 1989.08 | 07-DEC-05:04 | -1.1 |
Annual Sum or Average | 138034.24 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 119345.08 | 1989.08 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.238976E+10 | 2023.86 | 02-JAN-17:30 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.215738E+10 | 2023.86 | 01-FEB-17:00 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.227515E+10 | 2023.86 | 01-MAR-18:19 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.209615E+10 | 2023.86 | 01-APR-18:40 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.213678E+10 | 2023.86 | 01-MAY-18:30 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.201287E+10 | 2023.86 | 01-JUN-19:19 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.207348E+10 | 2023.86 | 01-JUL-19:30 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.220536E+10 | 2023.86 | 01-AUG-19:19 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.214764E+10 | 2023.86 | 01-SEP-18:49 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.227473E+10 | 2023.86 | 02-OCT-18:10 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.231241E+10 | 2023.86 | 01-NOV-17:30 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.243067E+10 | 2023.86 | 01-DEC-16:30 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.265124E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.201287E+10 | 2023.86 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.243067E+10 | 2023.86 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141271E+10 | 859.87 | 02-JAN-10:09 | 0.263757E+11 | 16905.18 | 01-JAN-11:09 |
February | 0.127972E+10 | 859.87 | 01-FEB-10:09 | 0.238233E+11 | 16905.18 | 01-FEB-11:09 |
March | 0.143703E+10 | 859.87 | 01-MAR-10:09 | 0.263759E+11 | 16905.18 | 01-MAR-11:09 |
April | 0.137275E+10 | 859.87 | 01-APR-16:10 | 0.255250E+11 | 16905.18 | 01-APR-10:09 |
May | 0.142487E+10 | 859.87 | 01-MAY-09:09 | 0.263758E+11 | 16905.18 | 01-MAY-10:09 |
June | 0.138882E+10 | 859.87 | 01-JUN-09:09 | 0.255251E+11 | 16905.18 | 01-JUN-10:09 |
July | 0.140898E+10 | 859.87 | 01-JUL-16:10 | 0.263757E+11 | 16905.18 | 01-JUL-10:09 |
August | 0.143703E+10 | 859.87 | 01-AUG-09:09 | 0.263759E+11 | 16905.18 | 01-AUG-10:09 |
September | 0.137310E+10 | 859.87 | 01-SEP-09:09 | 0.255250E+11 | 16905.18 | 01-SEP-10:09 |
October | 0.141254E+10 | 859.87 | 02-OCT-09:09 | 0.263757E+11 | 16905.18 | 01-OCT-10:09 |
November | 0.136789E+10 | 859.87 | 01-NOV-09:09 | 0.255249E+11 | 16905.18 | 01-NOV-10:09 |
December | 0.140915E+10 | 859.87 | 01-DEC-10:09 | 0.263757E+11 | 16905.18 | 01-DEC-11:09 |
Annual Sum or Average | 0.167246E+11 | 0.310554E+12 | ||||
Minimum of Months | 0.127972E+10 | 859.87 | 0.238233E+11 | 16905.18 | ||
Maximum of Months | 0.143703E+10 | 859.87 | 0.263759E+11 | 16905.18 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.238976E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64972615.24 | 0.452635E+10 |
February | 0.272721E+11 | 0.215738E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562572E+10 |
March | 0.305458E+11 | 0.227515E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170932E+09 | 0.424368E+10 |
April | 0.292871E+11 | 0.209615E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213627E+10 | 0.914666E+09 |
May | 0.303219E+11 | 0.213678E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367940E+10 | 0.326190E+09 |
June | 0.295292E+11 | 0.201287E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637832E+10 | 46324150.79 |
July | 0.300798E+11 | 0.207348E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553038E+10 | 37935043.31 |
August | 0.305458E+11 | 0.220536E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519932E+10 | 0.118641E+09 |
September | 0.292871E+11 | 0.214764E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380395E+10 | 0.192167E+09 |
October | 0.300980E+11 | 0.227473E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141958E+10 | 0.214680E+10 |
November | 0.290996E+11 | 0.231241E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121377E+09 | 0.445222E+10 |
December | 0.300798E+11 | 0.243067E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15030045.56 | 0.634644E+10 |
Annual Sum or Average | 0.356244E+12 | 0.265124E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285195E+11 | 0.289771E+11 |
Minimum of Months | 0.272721E+11 | 0.201287E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37935043.31 |
Maximum of Months | 0.305458E+11 | 0.243067E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637832E+10 | 0.634644E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.141271E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 117501.78 | 0.143484E+09 |
February | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107554E+09 |
March | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 408680.16 | 0.154823E+09 |
April | 0.786997E+09 | 0.137275E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 13309340.79 | 63298215.67 |
May | 0.814802E+09 | 0.142487E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 28949414.78 | 43957200.50 |
June | 0.793501E+09 | 0.138882E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 59510664.32 | 16174084.31 |
July | 0.808298E+09 | 0.140898E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 51386115.66 | 17368444.56 |
August | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 36364340.25 | 24462123.46 |
September | 0.786997E+09 | 0.137310E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 27112661.80 | 36917382.12 |
October | 0.808786E+09 | 0.141254E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8850676.59 | 87391450.52 |
November | 0.781956E+09 | 0.136789E+10 | 0.207262E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 244603.07 | 0.132486E+09 |
December | 0.808298E+09 | 0.140915E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1.21 | 0.131503E+09 |
Annual Sum or Average | 0.957291E+10 | 0.167246E+11 | 0.252169E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.226254E+09 | 0.959421E+09 |
Minimum of Months | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16174084.31 |
Maximum of Months | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 59510664.32 | 0.154823E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114337E+10 | 0.289244E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691963E+09 | 0.287280E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686873E+09 | 0.365711E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107571E+10 | 0.499930E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114872E+10 | 0.524252E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963199E+09 | 0.528872E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662935E+09 | 0.481621E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862967E+09 | 0.462488E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683041E+09 | 0.361920E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115961E+10 | 0.325616E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957659E+09 | 0.282907E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135309E+10 | 0.270776E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113891E+11 | 0.468062E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662935E+09 | 0.270776E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135309E+10 | 0.528872E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2023.86 | 02-JAN-17:30 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1976.38 | 31-JAN-14:00 | 8401.90 | 01-JAN-08:00 |
February | 30255.31 | 04-FEB-19:10 | 2023.86 | 01-FEB-17:00 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7915.59 | 04-FEB-19:55 |
March | 30255.31 | 04-MAR-19:10 | 2023.86 | 01-MAR-18:19 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.47 | 20-MAR-17:03 | 8244.03 | 26-MAR-06:10 |
April | 30255.31 | 01-APR-18:10 | 2023.86 | 01-APR-18:40 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5810.37 | 14-APR-17:03 | 3968.04 | 06-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 2023.86 | 01-MAY-18:30 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6872.22 | 31-MAY-17:03 | 3238.00 | 13-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 2023.86 | 01-JUN-19:19 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9422.03 | 28-JUN-17:03 | 1526.57 | 21-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 2023.86 | 01-JUL-19:30 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8151.74 | 22-JUL-18:03 | 1983.58 | 01-JUL-06:10 |
August | 30255.31 | 05-AUG-18:10 | 2023.86 | 01-AUG-19:19 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8885.42 | 25-AUG-17:03 | 4336.47 | 05-AUG-18:10 |
September | 30255.31 | 02-SEP-18:10 | 2023.86 | 01-SEP-18:49 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7005.84 | 07-SEP-17:03 | 2261.70 | 22-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 2023.86 | 02-OCT-18:10 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5398.67 | 06-OCT-12:00 | 6239.23 | 25-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 2023.86 | 01-NOV-17:30 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1968.26 | 01-NOV-13:00 | 8528.45 | 23-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 2023.86 | 01-DEC-16:30 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 747.12 | 25-DEC-14:00 | 10121.31 | 05-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2023.86 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1526.57 | |||||
Maximum of Months | 30255.31 | 2023.86 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9422.03 | 10121.31 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 859.87 | 02-JAN-10:09 | 13642.30 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 5.72 | 31-JAN-15:30 | 426.23 | 01-JAN-02:00 |
February | 813.01 | 04-FEB-19:10 | 859.87 | 01-FEB-10:09 | 13642.30 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 384.65 | 05-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 859.87 | 01-MAR-10:09 | 13642.30 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 10.30 | 15-MAR-15:00 | 429.38 | 28-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 859.87 | 01-APR-16:10 | 13642.30 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 56.05 | 30-APR-16:00 | 210.23 | 27-APR-00:10 |
May | 813.01 | 06-MAY-18:10 | 859.87 | 01-MAY-09:09 | 13642.30 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 92.53 | 20-MAY-14:00 | 183.42 | 14-MAY-03:10 |
June | 813.01 | 03-JUN-18:10 | 859.87 | 01-JUN-09:09 | 13642.30 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 123.98 | 19-JUN-13:53 | 129.76 | 13-JUN-03:50 |
July | 813.01 | 01-JUL-18:10 | 859.87 | 01-JUL-16:10 | 13642.30 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 120.27 | 22-JUL-15:53 | 213.36 | 27-JUL-00:30 |
August | 813.01 | 05-AUG-18:10 | 859.87 | 01-AUG-09:09 | 13642.30 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 94.85 | 13-AUG-15:58 | 219.63 | 19-AUG-01:50 |
September | 813.01 | 02-SEP-18:10 | 859.87 | 01-SEP-09:09 | 13642.30 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 100.79 | 17-SEP-24:00 | 200.90 | 26-SEP-03:10 |
October | 813.01 | 07-OCT-18:10 | 859.87 | 02-OCT-09:09 | 13642.30 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 47.74 | 10-OCT-14:57 | 294.35 | 26-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 859.87 | 01-NOV-09:09 | 13642.30 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 8.95 | 01-NOV-15:53 | 494.51 | 29-NOV-04:00 |
December | 813.01 | 02-DEC-19:10 | 859.87 | 01-DEC-10:09 | 13642.30 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25-DEC-15:53 | 345.79 | 17-DEC-04:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 129.76 | ||||||
Maximum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 123.98 | 494.51 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1661.28 | 18-JAN-07:25 | 5747.37 | 09-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1522.64 | 02-FEB-05:45 | 7615.60 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.75 | 19-MAR-07:42 | 8138.77 | 26-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1594.85 | 30-APR-06:00 | 8216.02 | 27-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1672.41 | 24-MAY-06:23 | 7852.23 | 27-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.95 | 20-JUN-05:53 | 7673.02 | 25-JUN-12:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1583.39 | 04-JUL-02:00 | 7619.27 | 27-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1731.62 | 25-AUG-06:33 | 7482.90 | 07-AUG-13:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1856.03 | 17-SEP-04:53 | 7112.17 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1650.85 | 26-OCT-07:13 | 6269.58 | 04-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1573.04 | 19-NOV-03:00 | 6305.06 | 14-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.02 | 21-DEC-07:25 | 5370.79 | 14-DEC-12:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.75 | 5370.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.02 | 8216.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 61869.38 | 08-JAN-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.02 |
February | 22612.10 | 01-FEB-05:01 | 16808.50 | 800.29 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 |
March | 62478.82 | 17-MAR-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.28 |
April | 78478.99 | 25-APR-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
May | 81262.23 | 01-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.69 |
June | 91292.83 | 25-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.58 |
July | 92323.16 | 06-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.96 |
August | 89572.82 | 26-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 |
September | 88815.22 | 17-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
October | 81442.45 | 18-OCT-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.31 |
November | 61867.30 | 02-NOV-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.06 |
December | 24962.20 | 14-DEC-05:01 | 16808.50 | 800.29 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22612.10 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | |
Maximum of Months | 92323.16 | 16808.50 | 800.29 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49381.54 | 07-JAN-04:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 161.88 |
February | 39660.59 | 17-FEB-04:01 | 0.00 | 270.10 | 25477.38 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 |
March | 53831.45 | 21-MAR-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 178.30 |
April | 61035.07 | 20-APR-03:11 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 65.02 |
May | 62347.18 | 14-MAY-03:11 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 127.05 |
June | 53193.23 | 21-JUN-03:11 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 |
July | 54462.63 | 02-JUL-03:11 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 89.35 |
August | 53211.01 | 25-AUG-03:11 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 82.01 |
September | 49628.32 | 29-SEP-03:11 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 106.03 |
October | 58327.60 | 12-OCT-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 |
November | 55726.54 | 22-NOV-04:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 103.77 |
December | 43832.04 | 23-DEC-04:01 | 0.00 | 270.10 | 25477.38 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 149.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39660.59 | 0.00 | 270.10 | 25477.38 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 | |
Maximum of Months | 62347.18 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.43 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.62 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.78 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1033.53 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 933.21 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.74 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.20 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.13 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.20 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.55 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1364.72 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1364.72 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.684470E+11 | 46025.98 | 31-JAN-18:19 | 0.720393E+11 | 74769.15 | 01-JAN-07:49 |
February | 0.578272E+11 | 40152.00 | 18-FEB-11:00 | 0.658075E+11 | 53391.47 | 28-FEB-07:10 |
March | 0.684030E+11 | 47185.90 | 17-MAR-10:00 | 0.711888E+11 | 74815.78 | 26-MAR-05:10 |
April | 0.798052E+11 | 55962.07 | 14-APR-17:10 | 0.626955E+11 | 43125.46 | 01-APR-10:00 |
May | 0.887322E+11 | 59759.88 | 31-MAY-17:19 | 0.627531E+11 | 42756.49 | 06-MAY-10:39 |
June | 0.100009E+12 | 72508.43 | 28-JUN-17:10 | 0.592328E+11 | 42501.19 | 03-JUN-10:09 |
July | 0.104570E+12 | 69261.40 | 19-JUL-11:00 | 0.601976E+11 | 42342.10 | 01-JUL-10:20 |
August | 0.104039E+12 | 69722.82 | 25-AUG-17:10 | 0.606525E+11 | 42383.96 | 26-AUG-10:09 |
September | 0.952562E+11 | 65903.37 | 01-SEP-11:00 | 0.597430E+11 | 42627.00 | 30-SEP-10:09 |
October | 0.797340E+11 | 59315.54 | 03-OCT-11:00 | 0.641048E+11 | 43988.43 | 25-OCT-06:10 |
November | 0.670029E+11 | 49234.14 | 01-NOV-10:00 | 0.660721E+11 | 64613.09 | 23-NOV-06:00 |
December | 0.658684E+11 | 44670.64 | 22-DEC-11:00 | 0.779082E+11 | 81560.45 | 06-DEC-07:10 |
Annual Sum or Average | 0.979695E+12 | 0.782395E+12 | ||||
Minimum of Months | 0.578272E+11 | 40152.00 | 0.592328E+11 | 42342.10 | ||
Maximum of Months | 0.104570E+12 | 72508.43 | 0.779082E+11 | 81560.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.380247E+10 | 0.262126E+10 | 0.370015E+11 | 0.00 | 0.105566E+11 | 37879553.69 | 0.00 | 0.490728E+10 | 0.00 | 0.00 | 0.00 | 0.638534E+10 | 0.00 |
February | 0.343710E+10 | 0.221274E+10 | 0.334207E+11 | 0.00 | 0.956396E+10 | 34213790.43 | 0.00 | 0.560727E+09 | 0.00 | 0.00 | 0.00 | 0.578045E+10 | 0.00 |
March | 0.371218E+10 | 0.221881E+10 | 0.370017E+11 | 0.00 | 0.105700E+11 | 37879553.69 | 0.00 | 0.525232E+10 | 0.00 | 0.00 | 0.00 | 0.645341E+10 | 0.00 |
April | 0.346890E+10 | 0.191085E+10 | 0.358080E+11 | 0.00 | 0.103545E+11 | 36657632.61 | 0.00 | 0.189105E+11 | 0.00 | 0.00 | 0.00 | 0.619379E+10 | 0.00 |
May | 0.356165E+10 | 0.177119E+10 | 0.370016E+11 | 0.00 | 0.109375E+11 | 37879553.69 | 0.00 | 0.257672E+11 | 0.00 | 0.00 | 0.00 | 0.641495E+10 | 0.00 |
June | 0.340169E+10 | 0.162926E+10 | 0.358081E+11 | 0.00 | 0.116348E+11 | 36657632.61 | 0.00 | 0.381154E+11 | 0.00 | 0.00 | 0.00 | 0.623622E+10 | 0.00 |
July | 0.348246E+10 | 0.171541E+10 | 0.370015E+11 | 0.00 | 0.120093E+11 | 37879553.69 | 0.00 | 0.406809E+11 | 0.00 | 0.00 | 0.00 | 0.637175E+10 | 0.00 |
August | 0.364239E+10 | 0.188276E+10 | 0.370017E+11 | 0.00 | 0.119952E+11 | 37879553.69 | 0.00 | 0.397473E+11 | 0.00 | 0.00 | 0.00 | 0.644982E+10 | 0.00 |
September | 0.352074E+10 | 0.204234E+10 | 0.358080E+11 | 0.00 | 0.111088E+11 | 36657632.61 | 0.00 | 0.333691E+11 | 0.00 | 0.00 | 0.00 | 0.619438E+10 | 0.00 |
October | 0.368727E+10 | 0.235694E+10 | 0.370015E+11 | 0.00 | 0.107554E+11 | 37879553.69 | 0.00 | 0.162941E+11 | 0.00 | 0.00 | 0.00 | 0.637991E+10 | 0.00 |
November | 0.368029E+10 | 0.248730E+10 | 0.358078E+11 | 0.00 | 0.102203E+11 | 36657632.61 | 0.00 | 0.552778E+10 | 0.00 | 0.00 | 0.00 | 0.617848E+10 | 0.00 |
December | 0.383982E+10 | 0.268634E+10 | 0.370015E+11 | 0.00 | 0.107090E+11 | 37879553.69 | 0.00 | 0.214182E+10 | 0.00 | 0.00 | 0.00 | 0.637971E+10 | 0.00 |
Annual Sum or Average | 0.432369E+11 | 0.255352E+11 | 0.435663E+12 | 0.00 | 0.130415E+12 | 0.446001E+09 | 0.00 | 0.231274E+12 | 0.00 | 0.00 | 0.00 | 0.754182E+11 | 0.00 |
Minimum of Months | 0.340169E+10 | 0.162926E+10 | 0.334207E+11 | 0.00 | 0.956396E+10 | 34213790.43 | 0.00 | 0.560727E+09 | 0.00 | 0.00 | 0.00 | 0.578045E+10 | 0.00 |
Maximum of Months | 0.383982E+10 | 0.268634E+10 | 0.370017E+11 | 0.00 | 0.120093E+11 | 37879553.69 | 0.00 | 0.406809E+11 | 0.00 | 0.00 | 0.00 | 0.645341E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.409637E+10 | 0.00 | 0.280433E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.460062E+10 | 0.00 | 0.251684E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.442455E+10 | 0.00 | 0.268646E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 78665304.52 | 0.00 | 0.240042E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 7968297.82 | 0.00 | 0.228454E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 9656726.13 | 0.00 | 0.206105E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 8017202.89 | 0.00 | 0.202899E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 2883032.67 | 0.00 | 0.207499E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 1942716.03 | 0.00 | 0.211284E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.562441E+09 | 0.00 | 0.236426E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.262949E+10 | 0.00 | 0.248300E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.107416E+11 | 0.00 | 0.272669E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.271642E+11 | 0.00 | 0.285444E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 1942716.03 | 0.00 | 0.202899E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.107416E+11 | 0.00 | 0.280433E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2883.74 | 02-JAN-17:30 | 2213.72 | 01-JAN-06:10 | 23897.06 | 01-JAN-11:09 | 0.00 | 5793.42 | 01-JAN-06:10 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2883.74 | 01-FEB-17:00 | 2213.72 | 01-FEB-06:10 | 23897.06 | 01-FEB-11:09 | 0.00 | 5316.31 | 08-FEB-06:10 | 17.86 | 23-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 2883.74 | 01-MAR-18:19 | 2213.72 | 01-MAR-06:10 | 23897.06 | 01-MAR-11:09 | 0.00 | 5778.08 | 26-MAR-05:00 | 17.86 | 07-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 2883.74 | 01-APR-18:40 | 2213.72 | 01-APR-05:10 | 23897.06 | 01-APR-10:09 | 0.00 | 5647.98 | 14-APR-17:10 | 17.86 | 22-APR-08:30 | 0.00 | 01-APR-00:10 |
May | 2883.74 | 01-MAY-18:30 | 2213.72 | 01-MAY-05:10 | 23897.06 | 01-MAY-10:09 | 0.00 | 6259.02 | 31-MAY-17:10 | 17.86 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 2883.74 | 01-JUN-19:19 | 2213.72 | 01-JUN-05:10 | 23897.06 | 01-JUN-10:09 | 0.00 | 8283.10 | 28-JUN-17:10 | 17.86 | 29-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 2883.74 | 01-JUL-19:30 | 2213.72 | 01-JUL-05:10 | 23897.06 | 01-JUL-10:09 | 0.00 | 7931.49 | 19-JUL-11:00 | 17.86 | 07-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 2883.74 | 01-AUG-19:19 | 2213.72 | 01-AUG-05:10 | 23897.06 | 01-AUG-10:09 | 0.00 | 7956.68 | 25-AUG-17:10 | 17.86 | 02-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 2883.74 | 01-SEP-18:49 | 2213.72 | 01-SEP-05:10 | 23897.06 | 01-SEP-10:09 | 0.00 | 7590.61 | 01-SEP-11:00 | 17.86 | 13-SEP-11:39 | 0.00 | 01-SEP-00:10 |
October | 2883.74 | 02-OCT-18:10 | 2213.72 | 01-OCT-05:10 | 23897.06 | 01-OCT-10:09 | 0.00 | 6347.18 | 03-OCT-11:00 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 2883.74 | 01-NOV-17:30 | 2213.72 | 01-NOV-05:10 | 23897.06 | 01-NOV-10:09 | 0.00 | 5640.01 | 23-NOV-06:00 | 17.86 | 07-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 2883.74 | 01-DEC-16:30 | 2213.72 | 01-DEC-06:10 | 23897.06 | 01-DEC-11:09 | 0.00 | 5868.13 | 06-DEC-06:00 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2883.74 | 2213.72 | 23897.06 | 0.00 | 5316.31 | 17.86 | 0.00 | ||||||
Maximum of Months | 2883.74 | 2213.72 | 23897.06 | 0.00 | 8283.10 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12729.74 | 31-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4741.20 | 30-JAN-07:10 | 0.00 |
February | 7064.60 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.83 | 28-FEB-07:40 | 0.00 |
March | 13868.21 | 20-MAR-17:10 | 0.00 | 0.00 | 0.00 | 4740.98 | 29-MAR-06:49 | 0.00 |
April | 23198.33 | 14-APR-17:10 | 0.00 | 0.00 | 0.00 | 4739.76 | 21-APR-06:00 | 0.00 |
May | 26237.02 | 31-MAY-17:10 | 0.00 | 0.00 | 0.00 | 4737.70 | 22-MAY-06:19 | 0.00 |
June | 37114.98 | 28-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.89 | 05-JUN-06:19 | 0.00 |
July | 34039.25 | 19-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4736.67 | 03-JUL-18:00 | 0.00 |
August | 34942.47 | 25-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.80 | 21-AUG-06:49 | 0.00 |
September | 29953.05 | 01-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.93 | 22-SEP-06:19 | 0.00 |
October | 24609.28 | 03-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4739.79 | 13-OCT-06:30 | 0.00 |
November | 15752.16 | 01-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4741.14 | 27-NOV-07:10 | 0.00 |
December | 10632.13 | 22-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4741.93 | 04-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7064.60 | 0.00 | 0.00 | 0.00 | 4736.67 | 0.00 | ||
Maximum of Months | 37114.98 | 0.00 | 0.00 | 0.00 | 4741.93 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 46025.98 | 31-JAN-18:19 | 2883.74 | 19878.74 | 2213.72 | 0.00 | 4640.77 | 17.86 | 0.00 | 10806.40 | 0.00 |
February | 40152.00 | 18-FEB-11:00 | 1663.82 | 23897.06 | 0.00 | 0.00 | 4640.77 | 17.86 | 0.00 | 4535.08 | 0.00 |
March | 47185.90 | 17-MAR-10:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4640.77 | 17.86 | 0.00 | 11477.93 | 0.00 |
April | 55962.07 | 14-APR-17:10 | 1871.80 | 19878.74 | 0.00 | 0.00 | 5647.98 | 17.86 | 0.00 | 23198.33 | 0.00 |
May | 59759.88 | 31-MAY-17:19 | 1871.80 | 19878.74 | 0.00 | 0.00 | 6245.54 | 17.86 | 0.00 | 26162.73 | 0.00 |
June | 72508.43 | 28-JUN-17:10 | 1871.80 | 19878.74 | 0.00 | 0.00 | 8283.10 | 17.86 | 0.00 | 37114.98 | 0.00 |
July | 69261.40 | 19-JUL-11:00 | 1871.80 | 22289.73 | 0.00 | 0.00 | 7931.49 | 17.86 | 0.00 | 32968.62 | 0.00 |
August | 69722.82 | 25-AUG-17:10 | 1871.80 | 19878.74 | 0.00 | 0.00 | 7956.68 | 17.86 | 0.00 | 34942.47 | 0.00 |
September | 65903.37 | 01-SEP-11:00 | 1871.80 | 22289.73 | 0.00 | 0.00 | 7590.61 | 17.86 | 0.00 | 29953.05 | 0.00 |
October | 59315.54 | 03-OCT-11:00 | 1871.80 | 22289.73 | 0.00 | 0.00 | 6347.18 | 17.86 | 0.00 | 24609.28 | 0.00 |
November | 49234.14 | 01-NOV-10:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4658.59 | 17.86 | 0.00 | 13525.88 | 0.00 |
December | 44670.64 | 22-DEC-11:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4640.77 | 17.86 | 0.00 | 8917.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 40152.00 | 1663.82 | 19878.74 | 0.00 | 0.00 | 4640.77 | 17.86 | 0.00 | 4535.08 | 0.00 | |
Maximum of Months | 72508.43 | 2883.74 | 23897.06 | 2213.72 | 0.00 | 8283.10 | 17.86 | 0.00 | 37114.98 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 48973.34 | 01-JAN-06:10 | 0.00 | 21809.17 | 18-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 26688.16 | 09-FEB-06:10 | 0.00 | 21806.18 | 01-FEB-07:40 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 48242.60 | 26-MAR-05:10 | 0.00 | 19891.51 | 03-MAR-19:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 7735.91 | 21-APR-05:10 | 0.00 | 17586.24 | 03-APR-18:49 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 4958.35 | 21-MAY-03:49 | 0.00 | 17208.25 | 01-MAY-18:49 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 3146.96 | 04-JUN-03:49 | 0.00 | 16825.50 | 01-JUN-06:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 9294.15 | 04-JUL-03:49 | 0.00 | 16581.11 | 03-JUL-18:19 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 3025.11 | 26-AUG-03:49 | 0.00 | 16679.07 | 31-AUG-18:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 3237.86 | 17-SEP-03:49 | 0.00 | 16969.17 | 29-SEP-18:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 15597.97 | 25-OCT-05:00 | 0.00 | 17391.88 | 31-OCT-06:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 41970.05 | 23-NOV-06:00 | 0.00 | 17780.69 | 30-NOV-07:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 52981.58 | 07-DEC-06:10 | 0.00 | 20972.57 | 29-DEC-19:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 3025.11 | 0.00 | 16581.11 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 52981.58 | 0.00 | 21809.17 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.67 | 0.00 | 24.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.67 | 0.00 | 24.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.97 | 0.00 | 24.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.14 | 0.00 | 25.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.13 | 0.00 | 25.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.98 | 0.00 | 24.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.76 | 0.00 | 24.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.00 | 24.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.67 | 24.96 | 0.00 | 24.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.14 | 0.00 | 25.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.78 | 0.00 | 27.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.55 | 0.00 | 27.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.81 | 0.00 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 29.50 | 0.00 | 29.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 29.79 | 0.00 | 29.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 30.37 | 0.00 | 30.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 30.52 | 0.00 | 30.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 30.51 | 0.00 | 30.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 30.61 | 0.00 | 30.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 30.03 | 0.00 | 30.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.64 | 0.00 | 28.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.46 | 0.00 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 165.17 | 29.89 | 0.00 | 29.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.46 | 0.00 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 30.61 | 0.00 | 30.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.67 | 21.85 | 60.67 | 22.14 | 10.00 | 22.13 |
February | 378.83 | 21.69 | 66.67 | 21.96 | 17.00 | 21.97 |
March | 312.00 | 22.01 | 101.67 | 22.43 | 7.17 | 22.39 |
April | 102.83 | 22.95 | 206.00 | 23.69 | 0.00 | 23.69 |
May | 52.33 | 23.48 | 248.83 | 24.03 | 0.00 | 24.03 |
June | 8.83 | 27.32 | 471.50 | 24.29 | 6.00 | 24.35 |
July | 97.83 | 24.81 | 568.00 | 24.28 | 94.83 | 24.35 |
August | 87.83 | 24.80 | 591.17 | 24.25 | 87.83 | 24.31 |
September | 98.83 | 24.33 | 576.50 | 24.16 | 98.83 | 24.18 |
October | 129.67 | 22.39 | 314.50 | 23.56 | 9.67 | 23.59 |
November | 278.83 | 22.20 | 193.50 | 22.88 | 55.33 | 22.95 |
December | 441.67 | 21.81 | 30.17 | 21.68 | 27.83 | 21.55 |
Annual Sum or Average | 2302.17 | 22.36 | 3429.17 | 23.38 | 414.50 | 23.42 |
Minimum of Months | 8.83 | 21.69 | 30.17 | 21.68 | 0.00 | 21.55 |
Maximum of Months | 441.67 | 27.32 | 591.17 | 24.29 | 98.83 | 24.35 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.50 | 23.74 | 409.00 | 24.62 | 249.83 | 24.91 |
February | 304.50 | 22.68 | 352.83 | 23.85 | 136.83 | 24.15 |
March | 406.00 | 24.07 | 444.67 | 24.81 | 268.83 | 25.08 |
April | 420.00 | 25.91 | 563.33 | 25.87 | 411.50 | 25.91 |
May | 455.50 | 26.00 | 607.67 | 25.96 | 455.50 | 25.97 |
June | 518.17 | 26.00 | 592.00 | 26.00 | 518.17 | 26.00 |
July | 586.50 | 26.00 | 609.00 | 26.00 | 586.50 | 26.00 |
August | 598.33 | 26.00 | 612.00 | 26.00 | 598.33 | 26.00 |
September | 586.50 | 26.00 | 590.00 | 26.00 | 586.50 | 26.00 |
October | 474.50 | 25.56 | 553.83 | 25.66 | 433.67 | 25.76 |
November | 429.50 | 24.50 | 451.00 | 25.01 | 321.17 | 25.23 |
December | 370.50 | 22.12 | 351.83 | 23.46 | 153.50 | 23.70 |
Annual Sum or Average | 5566.50 | 25.09 | 6137.17 | 25.42 | 4720.33 | 25.56 |
Minimum of Months | 304.50 | 22.12 | 351.83 | 23.46 | 136.83 | 23.70 |
Maximum of Months | 598.33 | 26.00 | 612.00 | 26.00 | 598.33 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.87884 | 28.08973 | 0.10536 | 7.20722 |
February | 551.00000 | 22.37499 | 43.19542 | 0.04730 | 6.76965 |
March | 612.00000 | 22.96655 | 32.59041 | 0.13090 | 7.26717 |
April | 590.00000 | 23.85029 | 22.57172 | 0.34534 | 8.11847 |
May | 611.00000 | 24.03761 | 21.02894 | -0.4497 | 9.72047 |
June | 592.00000 | 24.18694 | 28.29231 | -0.3001 | 7.56776 |
July | 609.00000 | 24.17911 | 46.02039 | -0.1729 | 6.39571 |
August | 612.00000 | 24.16261 | 48.16022 | -0.1580 | 6.11779 |
September | 590.00000 | 24.12449 | 48.36837 | -0.1755 | 6.10682 |
October | 610.00000 | 23.66342 | 31.36598 | 0.37224 | 9.23619 |
November | 591.00000 | 23.12243 | 33.07311 | 0.22026 | 8.17056 |
December | 609.00000 | 22.40843 | 21.40460 | -0.0573 | 7.46854 |
Annual Sum or Average | 7187.00000 | 23.50221 | 33.60908 | -0.0085 | 7.51865 |
Minimum of Months | 551.00000 | 22.37499 | 21.02894 | -0.4497 | 6.10682 |
Maximum of Months | 612.00000 | 24.18694 | 48.36837 | 0.37224 | 9.72047 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 24.01306 | 32.73665 | 0.59872 | 18.62574 |
February | 551.00000 | 23.32098 | 45.38636 | 0.50566 | 15.97227 |
March | 612.00000 | 24.22047 | 36.12231 | 0.66395 | 20.05234 |
April | 590.00000 | 25.68088 | 26.67323 | 0.99593 | 27.20726 |
May | 611.00000 | 25.92169 | 24.71584 | 0.47727 | 10.72274 |
June | 592.00000 | 25.99659 | 30.42982 | 0.60112 | 13.20490 |
July | 609.00000 | 25.99924 | 45.44467 | 0.73140 | 16.89136 |
August | 612.00000 | 25.99964 | 47.19565 | 0.74235 | 17.19373 |
September | 590.00000 | 25.99825 | 46.63423 | 0.73286 | 16.83561 |
October | 610.00000 | 25.34992 | 33.78854 | 0.98705 | 28.33700 |
November | 591.00000 | 24.44210 | 35.52802 | 0.75400 | 22.66226 |
December | 609.00000 | 23.09043 | 27.22939 | 0.35170 | 15.16009 |
Annual Sum or Average | 7187.00000 | 25.01123 | 35.92621 | 0.67890 | 18.57653 |
Minimum of Months | 551.00000 | 23.09043 | 24.71584 | 0.35170 | 10.72274 |
Maximum of Months | 612.00000 | 25.99964 | 47.19565 | 0.99593 | 28.33700 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.926427E+10 | 0.293746E+10 | 228.76 | 0.920533E+10 | 58942272.46 | 0.00 | 1.00 | 08-JAN-04:01 | 0.00 | 01-JAN-00:01 | 94256.67 | 08-JAN-04:01 | 75911.27 | 08-JAN-04:01 | 18345.39 | 08-JAN-04:01 | 25254.05 | 08-JAN-04:01 | 0.00 | 01-JAN-00:01 |
February | 0.570729E+09 | 0.190993E+09 | 38.08 | 0.493845E+09 | 76883923.33 | 0.00 | 0.33 | 18-FEB-13:53 | 0.00 | 01-FEB-00:03 | 12755.69 | 18-FEB-13:53 | 10942.22 | 22-FEB-14:00 | 2586.26 | 18-FEB-13:53 | 4105.72 | 18-FEB-13:53 | 0.00 | 01-FEB-00:03 |
March | 0.986096E+10 | 0.308593E+10 | 225.08 | 0.959698E+10 | 0.263988E+09 | 0.00 | 1.00 | 17-MAR-03:01 | 0.00 | 01-MAR-00:03 | 94256.67 | 17-MAR-03:01 | 75093.95 | 17-MAR-03:01 | 19162.71 | 17-MAR-03:01 | 25254.05 | 17-MAR-03:01 | 0.00 | 01-MAR-00:03 |
April | 0.404147E+11 | 0.121225E+11 | 455.74 | 0.403293E+11 | 85397500.92 | 0.00 | 1.00 | 02-APR-03:01 | 0.00 | 01-APR-00:01 | 94256.67 | 10-APR-03:01 | 94256.67 | 13-APR-03:01 | 12375.92 | 16-APR-03:01 | 25254.05 | 02-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.544002E+11 | 0.163586E+11 | 524.53 | 0.543894E+11 | 10849886.99 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 94256.67 | 02-MAY-03:41 | 94256.67 | 08-MAY-03:30 | 8741.44 | 11-MAY-03:14 | 25254.05 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.757269E+11 | 0.237552E+11 | 571.02 | 0.753651E+11 | 0.361874E+09 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 94256.67 | 02-JUN-03:28 | 94256.67 | 02-JUN-03:01 | 9930.85 | 17-JUN-17:10 | 25254.05 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.859889E+11 | 0.254404E+11 | 601.30 | 0.733696E+11 | 0.126193E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 104541.48 | 14-JUL-03:01 | 94256.67 | 03-JUL-03:56 | 59597.10 | 14-JUL-03:02 | 26034.27 | 14-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.839898E+11 | 0.249383E+11 | 602.30 | 0.714295E+11 | 0.125603E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 101299.21 | 01-AUG-03:01 | 94256.67 | 24-AUG-03:13 | 45648.40 | 07-AUG-03:13 | 25779.80 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.723109E+11 | 0.209334E+11 | 566.74 | 0.600491E+11 | 0.122618E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 103411.32 | 04-SEP-03:01 | 94256.67 | 18-SEP-03:01 | 60631.82 | 04-SEP-03:12 | 25943.20 | 04-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.342982E+11 | 0.102302E+11 | 409.81 | 0.317832E+11 | 0.251499E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 101078.29 | 03-OCT-03:01 | 94256.67 | 15-OCT-03:01 | 49962.53 | 03-OCT-03:09 | 25763.08 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.100624E+11 | 0.312126E+10 | 214.78 | 0.930465E+10 | 0.757728E+09 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 95978.24 | 13-NOV-04:01 | 74924.89 | 01-NOV-03:01 | 56004.19 | 13-NOV-04:01 | 25383.68 | 13-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.377570E+10 | 0.121310E+10 | 121.67 | 0.376971E+10 | 5991645.55 | 0.00 | 0.59 | 22-DEC-14:00 | 0.00 | 01-DEC-00:05 | 24576.16 | 22-DEC-14:00 | 24576.16 | 22-DEC-14:00 | 906.95 | 12-DEC-13:00 | 7399.64 | 22-DEC-14:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.480664E+12 | 0.144327E+12 | 4559.81 | 0.439086E+12 | 0.415781E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.570729E+09 | 0.190993E+09 | 38.08 | 0.493845E+09 | 5991645.55 | 0.00 | 0.33 | 0.00 | 12755.69 | 10942.22 | 906.95 | 4105.72 | 0.00 | |||||||
Maximum of Months | 0.859889E+11 | 0.254404E+11 | 602.30 | 0.753651E+11 | 0.126193E+11 | 0.00 | 1.00 | 0.00 | 104541.48 | 94256.67 | 60631.82 | 26034.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.699568E+10 | 0.196982E+10 | 288.87 | 0.668522E+10 | 0.310459E+09 | 0.00 | 1.00 | 06-JAN-04:01 | 0.00 | 01-JAN-00:01 | 41207.98 | 06-JAN-04:01 | 39438.81 | 27-JAN-04:41 | 18651.11 | 09-JAN-04:01 | 10055.85 | 06-JAN-04:01 | 0.00 | 01-JAN-00:01 |
February | 0.126074E+10 | 0.369734E+09 | 99.92 | 0.957440E+09 | 0.303301E+09 | 0.00 | 1.00 | 01-FEB-04:01 | 0.00 | 01-FEB-00:03 | 41207.98 | 10-FEB-04:41 | 34275.10 | 10-FEB-04:01 | 22523.66 | 12-FEB-04:01 | 10055.85 | 10-FEB-04:01 | 0.00 | 01-FEB-00:03 |
March | 0.784979E+10 | 0.216639E+10 | 292.77 | 0.730314E+10 | 0.546656E+09 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 | 41207.98 | 06-MAR-04:01 | 33361.03 | 23-MAR-03:01 | 21351.52 | 06-MAR-04:01 | 10055.85 | 06-MAR-04:01 | 0.00 | 01-MAR-00:03 |
April | 0.260204E+11 | 0.678805E+10 | 497.40 | 0.258553E+11 | 0.165105E+09 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 41207.98 | 06-APR-03:01 | 41207.98 | 03-APR-03:31 | 11920.12 | 17-APR-03:11 | 10055.85 | 02-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.357523E+11 | 0.940858E+10 | 581.48 | 0.356931E+11 | 59264642.01 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 41207.98 | 04-MAY-03:21 | 41207.98 | 05-MAY-03:01 | 9589.77 | 26-MAY-03:01 | 10055.85 | 02-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.514480E+11 | 0.143601E+11 | 624.85 | 0.512382E+11 | 0.209830E+09 | 0.00 | 1.00 | 01-JUN-01:13 | 0.00 | 01-JUN-00:01 | 41207.98 | 03-JUN-03:22 | 41207.98 | 02-JUN-01:43 | 5956.18 | 01-JUN-03:11 | 12856.02 | 28-JUN-17:00 | 0.00 | 01-JUN-00:01 |
July | 0.587430E+11 | 0.152405E+11 | 653.62 | 0.503341E+11 | 0.840889E+10 | 0.00 | 1.00 | 01-JUL-00:53 | 0.00 | 01-JUL-00:01 | 45603.06 | 14-JUL-03:11 | 41207.98 | 02-JUL-03:23 | 27535.85 | 14-JUL-03:11 | 10912.90 | 19-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.568828E+11 | 0.148090E+11 | 655.41 | 0.484803E+11 | 0.840249E+10 | 0.00 | 1.00 | 01-AUG-00:22 | 0.00 | 01-AUG-00:01 | 44996.11 | 01-AUG-02:53 | 41207.98 | 25-AUG-03:56 | 22327.21 | 01-AUG-03:53 | 12429.50 | 25-AUG-17:00 | 0.00 | 01-AUG-00:01 |
September | 0.490100E+11 | 0.124356E+11 | 623.02 | 0.402269E+11 | 0.878305E+10 | 0.00 | 1.00 | 01-SEP-01:03 | 0.00 | 01-SEP-00:01 | 44970.81 | 04-SEP-03:11 | 41207.98 | 18-SEP-02:13 | 28507.29 | 03-SEP-03:52 | 10313.09 | 04-SEP-03:11 | 0.00 | 01-SEP-00:01 |
October | 0.232396E+11 | 0.606384E+10 | 465.07 | 0.211862E+11 | 0.205342E+10 | 0.00 | 1.00 | 01-OCT-01:03 | 0.00 | 01-OCT-00:01 | 44094.13 | 03-OCT-03:01 | 41207.98 | 14-OCT-03:42 | 24095.59 | 03-OCT-03:01 | 10251.93 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.881503E+10 | 0.240652E+10 | 302.15 | 0.729858E+10 | 0.151644E+10 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 41207.98 | 03-NOV-03:01 | 37438.55 | 28-NOV-04:41 | 25978.09 | 12-NOV-04:01 | 10055.85 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.323997E+10 | 0.928723E+09 | 175.75 | 0.318074E+10 | 59238396.56 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:05 | 41207.98 | 12-DEC-04:41 | 40405.61 | 12-DEC-04:41 | 17958.30 | 13-DEC-04:01 | 10055.85 | 01-DEC-04:41 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.329257E+12 | 0.869469E+11 | 5260.29 | 0.298439E+12 | 0.308181E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.126074E+10 | 0.369734E+09 | 99.92 | 0.957440E+09 | 59238396.56 | 0.00 | 1.00 | 0.00 | 41207.98 | 33361.03 | 5956.18 | 10055.85 | 0.00 | |||||||
Maximum of Months | 0.587430E+11 | 0.152405E+11 | 655.41 | 0.512382E+11 | 0.878305E+10 | 0.00 | 1.00 | 0.00 | 45603.06 | 41207.98 | 28507.29 | 12856.02 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 196.32 | 123.22 | 73.10 | 265.09 | 233.48 | 0.00 | 0.00 | 0.00 |
February | 195.15 | 112.28 | 82.87 | 239.10 | 225.10 | 0.00 | 0.00 | 0.00 |
March | 242.32 | 124.67 | 117.65 | 334.35 | 197.42 | 0.00 | 0.00 | 0.00 |
April | 345.32 | 205.75 | 139.57 | 592.80 | 110.38 | 0.00 | 0.00 | 0.00 |
May | 358.48 | 212.71 | 145.77 | 657.12 | 76.95 | 0.00 | 0.00 | 0.00 |
June | 372.98 | 231.72 | 141.26 | 783.01 | 33.29 | 0.00 | 0.00 | 0.00 |
July | 315.49 | 178.01 | 137.47 | 669.00 | 25.08 | 0.00 | 0.00 | 0.00 |
August | 299.68 | 171.22 | 128.46 | 625.74 | 34.24 | 0.00 | 0.00 | 0.00 |
September | 245.58 | 118.44 | 127.13 | 494.50 | 48.53 | 0.00 | 0.00 | 0.00 |
October | 246.44 | 149.91 | 96.54 | 399.82 | 149.23 | 0.00 | 0.00 | 0.00 |
November | 189.64 | 113.81 | 75.84 | 250.58 | 219.90 | 0.00 | 0.00 | 0.00 |
December | 173.23 | 104.77 | 68.46 | 208.27 | 281.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.37 | 154.07 | 111.30 | 460.99 | 135.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.23 | 104.77 | 68.46 | 208.27 | 25.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 372.98 | 231.72 | 145.77 | 783.01 | 281.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 693.33 | 553.89 | 139.44 | 1092.43 | 320.70 | 0.00 | 0.00 | 0.00 |
February | 432.62 | 290.03 | 142.59 | 621.06 | 308.28 | 0.00 | 0.00 | 0.00 |
March | 358.14 | 181.48 | 176.66 | 548.03 | 285.16 | 0.00 | 0.00 | 0.00 |
April | 314.33 | 129.48 | 184.85 | 606.54 | 167.62 | 0.00 | 0.00 | 0.00 |
May | 210.03 | 36.54 | 173.49 | 446.92 | 118.87 | 0.00 | 0.00 | 0.00 |
June | 177.78 | 13.56 | 164.21 | 501.01 | 51.06 | 0.00 | 0.00 | 0.00 |
July | 180.15 | 17.13 | 163.02 | 488.79 | 37.57 | 0.00 | 0.00 | 0.00 |
August | 222.76 | 62.74 | 160.02 | 567.57 | 49.70 | 0.00 | 0.00 | 0.00 |
September | 316.42 | 133.74 | 182.69 | 683.34 | 70.14 | 0.00 | 0.00 | 0.00 |
October | 507.91 | 351.61 | 156.30 | 873.37 | 208.13 | 0.00 | 0.00 | 0.00 |
November | 597.03 | 458.55 | 138.49 | 926.72 | 299.77 | 0.00 | 0.00 | 0.00 |
December | 645.68 | 511.55 | 134.13 | 976.90 | 382.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 388.05 | 228.34 | 159.71 | 695.16 | 191.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 177.78 | 13.56 | 134.13 | 446.92 | 37.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 693.33 | 553.89 | 184.85 | 1092.43 | 382.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 206.14 | 128.43 | 77.71 | 302.15 | 253.11 | 0.00 | 0.00 | 0.00 |
February | 166.97 | 81.04 | 85.94 | 201.65 | 237.87 | 0.00 | 0.00 | 0.00 |
March | 220.95 | 105.68 | 115.28 | 308.34 | 209.41 | 0.00 | 0.00 | 0.00 |
April | 338.38 | 193.13 | 145.25 | 588.28 | 120.66 | 0.00 | 0.00 | 0.00 |
May | 339.60 | 190.31 | 149.29 | 629.57 | 85.65 | 0.00 | 0.00 | 0.00 |
June | 360.00 | 211.69 | 148.31 | 756.70 | 36.48 | 0.00 | 0.00 | 0.00 |
July | 261.87 | 122.03 | 139.84 | 571.91 | 26.85 | 0.00 | 0.00 | 0.00 |
August | 250.68 | 126.05 | 124.62 | 539.57 | 35.28 | 0.00 | 0.00 | 0.00 |
September | 218.15 | 91.72 | 126.42 | 448.58 | 50.65 | 0.00 | 0.00 | 0.00 |
October | 224.12 | 128.52 | 95.59 | 370.46 | 159.40 | 0.00 | 0.00 | 0.00 |
November | 205.15 | 123.78 | 81.37 | 294.23 | 234.75 | 0.00 | 0.00 | 0.00 |
December | 164.60 | 93.32 | 71.28 | 215.83 | 303.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.66 | 133.16 | 113.50 | 436.58 | 145.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.60 | 81.04 | 71.28 | 201.65 | 26.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.00 | 211.69 | 149.29 | 756.70 | 303.76 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.525815E+09 | 0.330026E+09 | 0.195789E+09 | 0.710017E+09 | 0.625354E+09 |
February | 0.472106E+09 | 0.271630E+09 | 0.200476E+09 | 0.578439E+09 | 0.544562E+09 |
March | 0.649042E+09 | 0.333919E+09 | 0.315123E+09 | 0.895533E+09 | 0.528757E+09 |
April | 0.895072E+09 | 0.533304E+09 | 0.361769E+09 | 0.153652E+10 | 0.286106E+09 |
May | 0.960147E+09 | 0.569718E+09 | 0.390429E+09 | 0.176003E+10 | 0.206099E+09 |
June | 0.966769E+09 | 0.600618E+09 | 0.366150E+09 | 0.202955E+10 | 86277414.09 |
July | 0.844997E+09 | 0.476785E+09 | 0.368211E+09 | 0.179186E+10 | 67177197.52 |
August | 0.802674E+09 | 0.458597E+09 | 0.344077E+09 | 0.167599E+10 | 91709835.76 |
September | 0.636531E+09 | 0.307003E+09 | 0.329528E+09 | 0.128175E+10 | 0.125791E+09 |
October | 0.660072E+09 | 0.401512E+09 | 0.258560E+09 | 0.107086E+10 | 0.399694E+09 |
November | 0.491558E+09 | 0.294985E+09 | 0.196573E+09 | 0.649503E+09 | 0.569978E+09 |
December | 0.463977E+09 | 0.280606E+09 | 0.183371E+09 | 0.557834E+09 | 0.752978E+09 |
Annual Sum or Average | 0.836876E+10 | 0.485870E+10 | 0.351006E+10 | 0.145379E+11 | 0.428448E+10 |
Minimum of Months | 0.463977E+09 | 0.271630E+09 | 0.183371E+09 | 0.557834E+09 | 67177197.52 |
Maximum of Months | 0.966769E+09 | 0.600618E+09 | 0.390429E+09 | 0.202955E+10 | 0.752978E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185703E+10 | 0.148355E+10 | 0.373477E+09 | 0.292596E+10 | 0.858958E+09 |
February | 0.104660E+10 | 0.701644E+09 | 0.344960E+09 | 0.150247E+10 | 0.745786E+09 |
March | 0.959244E+09 | 0.486075E+09 | 0.473169E+09 | 0.146786E+10 | 0.763769E+09 |
April | 0.814736E+09 | 0.335612E+09 | 0.479125E+09 | 0.157215E+10 | 0.434464E+09 |
May | 0.562539E+09 | 97856651.04 | 0.464683E+09 | 0.119703E+10 | 0.318369E+09 |
June | 0.460802E+09 | 35156463.06 | 0.425645E+09 | 0.129862E+10 | 0.132338E+09 |
July | 0.482508E+09 | 45876740.08 | 0.436631E+09 | 0.130919E+10 | 0.100628E+09 |
August | 0.596644E+09 | 0.168037E+09 | 0.428607E+09 | 0.152017E+10 | 0.133123E+09 |
September | 0.820170E+09 | 0.346646E+09 | 0.473524E+09 | 0.177122E+10 | 0.181791E+09 |
October | 0.136040E+10 | 0.941760E+09 | 0.418636E+09 | 0.233924E+10 | 0.557457E+09 |
November | 0.154750E+10 | 0.118855E+10 | 0.358955E+09 | 0.240205E+10 | 0.777015E+09 |
December | 0.172940E+10 | 0.137015E+10 | 0.359253E+09 | 0.261653E+10 | 0.102373E+10 |
Annual Sum or Average | 0.122376E+11 | 0.720091E+10 | 0.503666E+10 | 0.219225E+11 | 0.602743E+10 |
Minimum of Months | 0.460802E+09 | 35156463.06 | 0.344960E+09 | 0.119703E+10 | 0.100628E+09 |
Maximum of Months | 0.185703E+10 | 0.148355E+10 | 0.479125E+09 | 0.292596E+10 | 0.102373E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.552136E+09 | 0.343997E+09 | 0.208139E+09 | 0.809282E+09 | 0.677940E+09 |
February | 0.403944E+09 | 0.196042E+09 | 0.207902E+09 | 0.487821E+09 | 0.575455E+09 |
March | 0.591796E+09 | 0.283041E+09 | 0.308756E+09 | 0.825862E+09 | 0.560892E+09 |
April | 0.877069E+09 | 0.500583E+09 | 0.376486E+09 | 0.152483E+10 | 0.312738E+09 |
May | 0.909581E+09 | 0.509722E+09 | 0.399860E+09 | 0.168624E+10 | 0.229396E+09 |
June | 0.933119E+09 | 0.548695E+09 | 0.384424E+09 | 0.196137E+10 | 94562094.79 |
July | 0.701403E+09 | 0.326845E+09 | 0.374558E+09 | 0.153180E+10 | 71905899.97 |
August | 0.671420E+09 | 0.337626E+09 | 0.333794E+09 | 0.144518E+10 | 94488611.71 |
September | 0.565440E+09 | 0.237748E+09 | 0.327692E+09 | 0.116273E+10 | 0.131277E+09 |
October | 0.600274E+09 | 0.344236E+09 | 0.256038E+09 | 0.992242E+09 | 0.426933E+09 |
November | 0.531752E+09 | 0.320848E+09 | 0.210903E+09 | 0.762639E+09 | 0.608467E+09 |
December | 0.440872E+09 | 0.249960E+09 | 0.190912E+09 | 0.578075E+09 | 0.813601E+09 |
Annual Sum or Average | 0.777881E+10 | 0.419934E+10 | 0.357946E+10 | 0.137681E+11 | 0.459766E+10 |
Minimum of Months | 0.403944E+09 | 0.196042E+09 | 0.190912E+09 | 0.487821E+09 | 71905899.97 |
Maximum of Months | 0.933119E+09 | 0.548695E+09 | 0.399860E+09 | 0.196137E+10 | 0.813601E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1635.57 | 783.19 | 1095.80 | 805.55 | 290.25 | 0.00 | 0.00 |
February | 1037.04 | 746.47 | 794.75 | 483.35 | 311.40 | 0.00 | 0.00 |
March | 1160.06 | 661.31 | 821.42 | 411.83 | 409.59 | 0.00 | 0.00 |
April | 1762.98 | 374.01 | 998.02 | 528.36 | 469.67 | 0.00 | 0.00 |
May | 1716.26 | 264.12 | 908.10 | 439.55 | 468.55 | 0.00 | 0.00 |
June | 2033.17 | 113.27 | 910.76 | 456.97 | 453.79 | 0.00 | 0.00 |
July | 1726.11 | 85.91 | 757.51 | 317.17 | 440.34 | 0.00 | 0.00 |
August | 1729.25 | 115.60 | 773.13 | 360.01 | 413.11 | 0.00 | 0.00 |
September | 1621.92 | 164.81 | 780.15 | 343.90 | 436.24 | 0.00 | 0.00 |
October | 1626.76 | 499.87 | 978.47 | 630.04 | 348.43 | 0.00 | 0.00 |
November | 1448.34 | 731.23 | 991.83 | 696.14 | 295.69 | 0.00 | 0.00 |
December | 1369.24 | 935.35 | 983.52 | 709.65 | 273.87 | 0.00 | 0.00 |
Annual Sum or Average | 1575.04 | 455.09 | 900.09 | 515.57 | 384.52 | 0.00 | 0.00 |
Minimum of Months | 1037.04 | 85.91 | 757.51 | 317.17 | 273.87 | 0.00 | 0.00 |
Maximum of Months | 2033.17 | 935.35 | 1095.80 | 805.55 | 469.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438070E+10 | 0.209769E+10 | 0.293498E+10 | 0.215757E+10 | 0.777404E+09 | 0.00 | 0.00 |
February | 0.250880E+10 | 0.180587E+10 | 0.192265E+10 | 0.116932E+10 | 0.753338E+09 | 0.00 | 0.00 |
March | 0.310709E+10 | 0.177126E+10 | 0.220008E+10 | 0.110303E+10 | 0.109705E+10 | 0.00 | 0.00 |
April | 0.456963E+10 | 0.969440E+09 | 0.258688E+10 | 0.136950E+10 | 0.121738E+10 | 0.00 | 0.00 |
May | 0.459683E+10 | 0.707409E+09 | 0.243227E+10 | 0.117730E+10 | 0.125497E+10 | 0.00 | 0.00 |
June | 0.526997E+10 | 0.293601E+09 | 0.236069E+10 | 0.118447E+10 | 0.117622E+10 | 0.00 | 0.00 |
July | 0.462323E+10 | 0.230092E+09 | 0.202891E+10 | 0.849507E+09 | 0.117940E+10 | 0.00 | 0.00 |
August | 0.463164E+10 | 0.309620E+09 | 0.207074E+10 | 0.964259E+09 | 0.110648E+10 | 0.00 | 0.00 |
September | 0.420402E+10 | 0.427183E+09 | 0.202214E+10 | 0.891397E+09 | 0.113074E+10 | 0.00 | 0.00 |
October | 0.435711E+10 | 0.133884E+10 | 0.262074E+10 | 0.168751E+10 | 0.933234E+09 | 0.00 | 0.00 |
November | 0.375409E+10 | 0.189536E+10 | 0.257081E+10 | 0.180438E+10 | 0.766431E+09 | 0.00 | 0.00 |
December | 0.366737E+10 | 0.250523E+10 | 0.263425E+10 | 0.190071E+10 | 0.733535E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.496705E+11 | 0.143516E+11 | 0.283851E+11 | 0.162590E+11 | 0.121262E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250880E+10 | 0.230092E+09 | 0.192265E+10 | 0.849507E+09 | 0.733535E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526997E+10 | 0.250523E+10 | 0.293498E+10 | 0.215757E+10 | 0.125497E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638520E+10 | -0.622516E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160033949.0 | 81.22 | 0.00 | 0.00 |
February | 0.578043E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146133130.9 | 81.22 | 0.00 | 0.00 |
March | 0.645322E+10 | -0.629385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159375166.9 | 81.22 | 0.00 | 0.00 |
April | 0.619366E+10 | -0.604346E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150197130.1 | 81.21 | 0.00 | 0.00 |
May | 0.641475E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154547686.5 | 81.21 | 0.00 | 0.00 |
June | 0.623609E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149509672.6 | 81.21 | 0.00 | 0.00 |
July | 0.637154E+10 | -0.621713E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154409897.5 | 81.21 | 0.00 | 0.00 |
August | 0.644962E+10 | -0.629524E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154379272.3 | 81.21 | 0.00 | 0.00 |
September | 0.619421E+10 | -0.604485E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149360315.0 | 81.21 | 0.00 | 0.00 |
October | 0.637989E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156060855.7 | 81.21 | 0.00 | 0.00 |
November | 0.617818E+10 | -0.602460E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153572346.2 | 81.22 | 0.00 | 0.00 |
December | 0.637961E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162531180.6 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754164E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.185011E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578043E+10 | -0.629524E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162531180.6 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645322E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146133130.9 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.205312E+11 | -0.196401E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -891184647.1 | 58.99 | 0.00 | 0.00 |
February | 0.184141E+11 | -0.175945E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -819512897.3 | 58.99 | 0.00 | 0.00 |
March | 0.195863E+11 | -0.187012E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -885104361.9 | 58.98 | 0.00 | 0.00 |
April | 0.173429E+11 | -0.165231E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -819737096.0 | 58.99 | 0.00 | 0.00 |
May | 0.163466E+11 | -0.155055E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -841074018.5 | 58.99 | 0.00 | 0.00 |
June | 0.146102E+11 | -0.137968E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -813408640.3 | 58.98 | 0.00 | 0.00 |
July | 0.142906E+11 | -0.134509E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839685977.2 | 58.98 | 0.00 | 0.00 |
August | 0.146582E+11 | -0.138187E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839548334.5 | 58.99 | 0.00 | 0.00 |
September | 0.150314E+11 | -0.142192E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -812227853.6 | 58.99 | 0.00 | 0.00 |
October | 0.169847E+11 | -0.161297E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -854958483.8 | 58.99 | 0.00 | 0.00 |
November | 0.180114E+11 | -0.171610E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -850467992.0 | 58.98 | 0.00 | 0.00 |
December | 0.199033E+11 | -0.189892E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -914062937.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.205711E+12 | -0.195530E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.101810E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.142906E+11 | -0.196401E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -914062937.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.205312E+11 | -0.134509E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -812227853.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.52 | 0.50 | 01-JAN-07:49 | 993.80 | 25.07 | 126.17 | 292.50 | 1168.57 | 25.56 | 148.17 | 291.50 |
February | 241.00 | 0.52 | 0.50 | 01-FEB-07:40 | 859.78 | 22.99 | 104.00 | 254.83 | 1104.06 | 23.96 | 130.83 | 255.83 |
March | 344.33 | 0.52 | 0.50 | 01-MAR-07:19 | 873.25 | 20.10 | 99.50 | 327.83 | 892.82 | 19.81 | 95.00 | 329.17 |
April | 380.33 | 0.52 | 0.50 | 01-APR-06:00 | 1155.17 | 19.76 | 62.50 | 347.50 | 917.27 | 19.78 | 99.83 | 350.50 |
May | 403.17 | 0.51 | 0.50 | 01-MAY-06:19 | 720.15 | 19.66 | 29.50 | 380.17 | 887.57 | 19.59 | 53.17 | 383.17 |
June | 418.17 | 0.52 | 0.50 | 01-JUN-06:10 | 751.80 | 18.96 | 5.17 | 385.17 | 904.30 | 19.02 | 17.50 | 393.00 |
July | 399.50 | 0.52 | 0.50 | 01-JUL-06:19 | 662.92 | 19.21 | 23.50 | 378.17 | 760.19 | 19.17 | 38.00 | 376.17 |
August | 361.83 | 0.52 | 0.50 | 01-AUG-06:19 | 795.92 | 19.57 | 48.00 | 348.50 | 719.05 | 19.29 | 54.33 | 351.00 |
September | 350.17 | 0.53 | 0.50 | 01-SEP-06:49 | 784.07 | 19.96 | 94.33 | 324.33 | 1002.27 | 19.84 | 89.50 | 325.33 |
October | 348.00 | 0.52 | 0.50 | 01-OCT-07:10 | 915.00 | 21.41 | 120.67 | 321.83 | 1010.82 | 22.58 | 137.50 | 316.00 |
November | 288.50 | 0.51 | 0.50 | 01-NOV-07:30 | 1108.95 | 24.65 | 127.33 | 279.17 | 1009.14 | 25.09 | 140.33 | 281.50 |
December | 290.67 | 0.51 | 0.50 | 01-DEC-07:30 | 1107.95 | 24.77 | 112.50 | 278.00 | 1015.10 | 25.52 | 139.83 | 278.00 |
Annual Sum or Average | 4135.50 | 0.52 | 882.03 | 21.06 | 953.17 | 3918.00 | 936.58 | 21.28 | 1144.00 | 3931.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.50 | 662.92 | 18.96 | 5.17 | 254.83 | 719.05 | 19.02 | 17.50 | 255.83 | |
Maximum of Months | 418.17 | 0.53 | 0.50 | 1155.17 | 25.07 | 127.33 | 385.17 | 1168.57 | 25.56 | 148.17 | 393.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.286741E+10 | 25743.69 | 01-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334961E+10 | 25528.38 | 09-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298899E+10 | 35002.07 | 26-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62932243.62 | 17413.29 | 25-APR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6374638.26 | 11919.42 | 09-MAY-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7725380.91 | 7959.80 | 23-JUN-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6413762.31 | 22305.96 | 04-JUL-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2306426.13 | 9680.34 | 26-AUG-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1554172.82 | 10361.15 | 17-SEP-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.447790E+09 | 13215.64 | 26-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181023E+10 | 25055.04 | 23-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.654918E+10 | 31524.61 | 17-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1554172.82 | 7959.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.654918E+10 | 35002.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.409684E+09 | 18557.82 | 01-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330891E+09 | 10767.87 | 02-FEB-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.550654E+09 | 21258.70 | 26-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2163365.77 | 4435.81 | 26-OCT-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293358E+09 | 14921.51 | 23-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204411E+10 | 27788.22 | 07-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204411E+10 | 27788.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.926427E+10 | 0.920533E+10 | 94256.67 | 08-JAN-04:01 | 75911.27 | 0.00 |
February | 0.00 | 0.00 | 0.570729E+09 | 0.493845E+09 | 12755.69 | 18-FEB-13:53 | 10169.43 | 0.00 |
March | 0.00 | 0.00 | 0.986096E+10 | 0.959698E+10 | 94256.67 | 17-MAR-03:01 | 75093.95 | 0.00 |
April | 0.00 | 0.00 | 0.404147E+11 | 0.403293E+11 | 94256.67 | 10-APR-03:01 | 92942.99 | 0.00 |
May | 0.00 | 0.00 | 0.544002E+11 | 0.543894E+11 | 94256.67 | 02-MAY-03:41 | 94256.67 | 0.00 |
June | 0.00 | 0.00 | 0.757269E+11 | 0.753651E+11 | 94256.67 | 02-JUN-03:28 | 94256.67 | 0.00 |
July | 0.00 | 0.00 | 0.859889E+11 | 0.733696E+11 | 104541.48 | 14-JUL-03:01 | 45120.70 | 0.00 |
August | 0.00 | 0.00 | 0.839898E+11 | 0.714295E+11 | 101299.21 | 01-AUG-03:01 | 62981.85 | 0.00 |
September | 0.00 | 0.00 | 0.723109E+11 | 0.600491E+11 | 103411.32 | 04-SEP-03:01 | 42806.43 | 0.00 |
October | 0.00 | 0.00 | 0.342982E+11 | 0.317832E+11 | 101078.29 | 03-OCT-03:01 | 51679.25 | 0.00 |
November | 0.00 | 0.00 | 0.100624E+11 | 0.930465E+10 | 95978.24 | 13-NOV-04:01 | 39974.05 | 0.00 |
December | 0.00 | 0.00 | 0.377570E+10 | 0.376971E+10 | 24576.16 | 22-DEC-14:00 | 24576.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.480664E+12 | 0.439086E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.570729E+09 | 0.493845E+09 | 12755.69 | 10169.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.859889E+11 | 0.753651E+11 | 104541.48 | 94256.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.699568E+10 | 0.668522E+10 | 41207.98 | 06-JAN-04:01 | 32883.68 | 0.00 |
February | 0.00 | 0.00 | 0.126074E+10 | 0.957440E+09 | 41207.98 | 10-FEB-04:41 | 33890.86 | 0.00 |
March | 0.00 | 0.00 | 0.784979E+10 | 0.730314E+10 | 41207.98 | 06-MAR-04:01 | 19856.46 | 0.00 |
April | 0.00 | 0.00 | 0.260204E+11 | 0.258553E+11 | 41207.98 | 06-APR-03:01 | 39967.36 | 0.00 |
May | 0.00 | 0.00 | 0.357523E+11 | 0.356931E+11 | 41207.98 | 04-MAY-03:21 | 41207.98 | 0.00 |
June | 0.00 | 0.00 | 0.514480E+11 | 0.512382E+11 | 41207.98 | 03-JUN-03:22 | 37834.66 | 0.00 |
July | 0.00 | 0.00 | 0.587430E+11 | 0.503341E+11 | 45603.06 | 14-JUL-03:11 | 18067.21 | 0.00 |
August | 0.00 | 0.00 | 0.568828E+11 | 0.484803E+11 | 44996.11 | 01-AUG-02:53 | 23629.94 | 0.00 |
September | 0.00 | 0.00 | 0.490100E+11 | 0.402269E+11 | 44970.81 | 04-SEP-03:11 | 16920.09 | 0.00 |
October | 0.00 | 0.00 | 0.232396E+11 | 0.211862E+11 | 44094.13 | 03-OCT-03:01 | 19998.54 | 0.00 |
November | 0.00 | 0.00 | 0.881503E+10 | 0.729858E+10 | 41207.98 | 03-NOV-03:01 | 24020.30 | 0.00 |
December | 0.00 | 0.00 | 0.323997E+10 | 0.318074E+10 | 41207.98 | 12-DEC-04:41 | 40405.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.329257E+12 | 0.298439E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.126074E+10 | 0.957440E+09 | 41207.98 | 16920.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.587430E+11 | 0.512382E+11 | 45603.06 | 41207.98 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7794.95 | 14846.73 | 19-JAN-07:13 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7735.34 | 14791.52 | 01-FEB-19:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7444.75 | 14406.32 | 01-MAR-07:13 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6838.83 | 13425.03 | 03-APR-18:42 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6254.53 | 12360.88 | 01-MAY-18:43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5789.90 | 11249.48 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5490.13 | 10499.13 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5626.59 | 10816.78 | 31-AUG-18:22 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5952.95 | 11665.36 | 29-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6487.77 | 12881.56 | 31-OCT-18:06 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7084.37 | 13931.26 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 7552.46 | 14626.72 | 29-DEC-20:00 |
Annual Sum or Average | 0.00 | 6665.09 | ||||
Minimum of Months | 0.00 | 0.00 | 5490.13 | 10499.13 | ||
Maximum of Months | 0.00 | 0.00 | 7794.95 | 14846.73 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191165E+10 | 0.25 | 824.13 | 01-JAN-00:01 | 0.29 |
February | 0.173006E+10 | 0.25 | 824.13 | 01-FEB-00:03 | 0.29 |
March | 0.191709E+10 | 0.25 | 824.13 | 01-MAR-00:03 | 0.29 |
April | 0.195986E+10 | 0.27 | 824.13 | 01-APR-03:01 | 0.29 |
May | 0.206494E+10 | 0.27 | 824.13 | 01-MAY-00:55 | 0.29 |
June | 0.202667E+10 | 0.28 | 824.13 | 01-JUN-00:40 | 0.29 |
July | 0.209787E+10 | 0.27 | 824.13 | 01-JUL-00:20 | 0.29 |
August | 0.209560E+10 | 0.27 | 824.13 | 01-AUG-00:20 | 0.29 |
September | 0.202688E+10 | 0.27 | 824.13 | 01-SEP-00:30 | 0.29 |
October | 0.200888E+10 | 0.26 | 824.13 | 01-OCT-00:30 | 0.29 |
November | 0.187655E+10 | 0.26 | 824.13 | 01-NOV-02:65 | 0.29 |
December | 0.190832E+10 | 0.25 | 824.13 | 01-DEC-00:05 | 0.29 |
Annual Sum or Average | 0.236244E+11 | 0.26 | |||
Minimum of Months | 0.173006E+10 | 0.25 | 824.13 | 0.29 | |
Maximum of Months | 0.209787E+10 | 0.28 | 824.13 | 0.29 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.701877E+10 | 0.78 | 4051.23 | 01-JAN-06:10 | 1.10 |
February | 0.636711E+10 | 0.78 | 4043.25 | 09-FEB-05:03 | 1.09 |
March | 0.702349E+10 | 0.78 | 4394.52 | 26-MAR-04:02 | 1.15 |
April | 0.672743E+10 | 0.79 | 7026.00 | 25-APR-03:01 | 1.46 |
May | 0.699048E+10 | 0.80 | 5589.71 | 26-MAY-03:01 | 1.31 |
June | 0.727300E+10 | 0.83 | 7741.71 | 02-JUN-03:01 | 1.53 |
July | 0.749969E+10 | 0.83 | 7741.71 | 05-JUL-03:01 | 1.53 |
August | 0.753681E+10 | 0.83 | 7741.71 | 01-AUG-03:01 | 1.51 |
September | 0.698298E+10 | 0.80 | 7741.71 | 01-SEP-03:01 | 1.52 |
October | 0.699765E+10 | 0.79 | 7741.71 | 01-OCT-03:01 | 1.52 |
November | 0.676451E+10 | 0.78 | 4470.75 | 03-NOV-03:01 | 1.16 |
December | 0.715463E+10 | 0.79 | 4265.58 | 17-DEC-05:02 | 1.14 |
Annual Sum or Average | 0.843366E+11 | 0.80 | |||
Minimum of Months | 0.636711E+10 | 0.78 | 4043.25 | 1.09 | |
Maximum of Months | 0.753681E+10 | 0.83 | 7741.71 | 1.53 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162622E+10 | 0.51 | 1799.90 | 08-JAN-04:01 | 0.97 |
February | 0.146679E+10 | 0.51 | 1553.83 | 18-FEB-04:01 | 0.90 |
March | 0.162941E+10 | 0.51 | 1799.90 | 06-MAR-04:01 | 0.97 |
April | 0.166716E+10 | 0.55 | 1799.90 | 02-APR-03:01 | 0.97 |
May | 0.188207E+10 | 0.58 | 1799.90 | 02-MAY-03:01 | 0.97 |
June | 0.233514E+10 | 0.65 | 1799.90 | 01-JUN-03:11 | 0.96 |
July | 0.241178E+10 | 0.65 | 1799.90 | 02-JUL-03:11 | 0.97 |
August | 0.236276E+10 | 0.64 | 1799.90 | 01-AUG-03:01 | 0.96 |
September | 0.209890E+10 | 0.62 | 1799.90 | 01-SEP-03:01 | 0.96 |
October | 0.174885E+10 | 0.54 | 1799.90 | 01-OCT-03:01 | 0.96 |
November | 0.157924E+10 | 0.51 | 1799.90 | 01-NOV-03:01 | 0.96 |
December | 0.164608E+10 | 0.51 | 1531.12 | 13-DEC-04:01 | 0.90 |
Annual Sum or Average | 0.224544E+11 | 0.57 | |||
Minimum of Months | 0.146679E+10 | 0.51 | 1531.12 | 0.90 | |
Maximum of Months | 0.241178E+10 | 0.65 | 1799.90 | 0.97 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 50.07 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 50.58 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 50.76 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 52.86 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.82 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 54.14 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 55.05 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.42 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.67 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.65 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.96 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 51.04 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.07 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.05 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 50.07 | 59.92 | 7794.95 | 14846.73 | 19-JAN-07:13 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.58 | 59.58 | 7735.34 | 14791.52 | 01-FEB-19:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.76 | 59.71 | 7444.75 | 14406.32 | 01-MAR-07:13 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.60 | 51.60 | 6838.83 | 13425.03 | 03-APR-18:42 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 52.56 | 52.56 | 6254.53 | 12360.88 | 01-MAY-18:43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.04 | 53.04 | 5789.90 | 11249.48 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.83 | 53.83 | 5490.13 | 10499.13 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.99 | 52.99 | 5626.59 | 10816.78 | 31-AUG-18:22 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.54 | 53.54 | 5952.95 | 11665.36 | 29-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.17 | 51.17 | 6487.77 | 12881.56 | 31-OCT-18:06 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.07 | 52.07 | 7084.37 | 13931.26 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.04 | 58.80 | 7552.46 | 14626.72 | 29-DEC-20:00 |
Annual Sum or Average | 0.00 | 6665.09 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.07 | 51.17 | 5490.13 | 10499.13 | ||
Maximum of Months | 0.00 | 0.00 | 53.83 | 59.92 | 7794.95 | 14846.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.995623E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.655811E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101094E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.188499E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.233491E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.310282E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.329401E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.324752E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.279164E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.172279E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.988576E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.836773E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.228664E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.655811E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.329401E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.359604E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.183653E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.379580E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.845521E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.112906E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.166953E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.176523E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.171718E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.145345E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.781270E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.398576E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.257481E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.109401E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183653E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.176523E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.701877E+10 | 0.926235E+10 | 0.286741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.636711E+10 | 0.570729E+09 | 0.334961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.702349E+10 | 0.985904E+10 | 0.298899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672743E+10 | 0.403389E+11 | 62932243.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699048E+10 | 0.542616E+11 | 6374638.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.727300E+10 | 0.753958E+11 | 7725380.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.749969E+10 | 0.858032E+11 | 6413762.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.753681E+10 | 0.837693E+11 | 2306426.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.698298E+10 | 0.719787E+11 | 1554172.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.699765E+10 | 0.341917E+11 | 0.447790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676451E+10 | 0.100527E+11 | 0.181023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715463E+10 | 0.377570E+10 | 0.654918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.843366E+11 | 0.479260E+12 | 0.181005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.636711E+10 | 0.570729E+09 | 1554172.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.753681E+10 | 0.858032E+11 | 0.654918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162622E+10 | 0.698359E+10 | 0.409684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146679E+10 | 0.125651E+10 | 0.330891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162941E+10 | 0.784547E+10 | 0.550654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166716E+10 | 0.259776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188207E+10 | 0.356615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233514E+10 | 0.510890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.241178E+10 | 0.583078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.236276E+10 | 0.564532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.209890E+10 | 0.486316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174885E+10 | 0.231391E+11 | 2163365.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157924E+10 | 0.880492E+10 | 0.293358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164608E+10 | 0.323477E+10 | 0.204411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224544E+11 | 0.327385E+12 | 0.363086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146679E+10 | 0.125651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.241178E+10 | 0.583078E+11 | 0.204411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.701877E+10 | 0.00 | 0.00 | 0.00 | 0.293746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.636711E+10 | 0.00 | 0.00 | 0.00 | 0.190993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.702349E+10 | 0.00 | 0.00 | 0.00 | 0.308593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672743E+10 | 0.00 | 0.00 | 0.00 | 0.121225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699048E+10 | 0.00 | 0.00 | 0.00 | 0.163586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.727300E+10 | 0.00 | 0.00 | 0.00 | 0.237552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.749969E+10 | 0.00 | 0.00 | 0.00 | 0.254404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.753681E+10 | 0.00 | 0.00 | 0.00 | 0.249383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.698298E+10 | 0.00 | 0.00 | 0.00 | 0.209334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.699765E+10 | 0.00 | 0.00 | 0.00 | 0.102302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676451E+10 | 0.00 | 0.00 | 0.00 | 0.312126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715463E+10 | 0.00 | 0.00 | 0.00 | 0.121310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.843366E+11 | 0.00 | 0.00 | 0.00 | 0.144327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.636711E+10 | 0.00 | 0.00 | 0.00 | 0.190993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.753681E+10 | 0.00 | 0.00 | 0.00 | 0.254404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162622E+10 | 0.00 | 0.00 | 0.00 | 0.196982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146679E+10 | 0.00 | 0.00 | 0.00 | 0.369734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162941E+10 | 0.00 | 0.00 | 0.00 | 0.216639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166716E+10 | 0.00 | 0.00 | 0.00 | 0.678805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188207E+10 | 0.00 | 0.00 | 0.00 | 0.940858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233514E+10 | 0.00 | 0.00 | 0.00 | 0.143601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.241178E+10 | 0.00 | 0.00 | 0.00 | 0.152405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.236276E+10 | 0.00 | 0.00 | 0.00 | 0.148090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.209890E+10 | 0.00 | 0.00 | 0.00 | 0.124356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174885E+10 | 0.00 | 0.00 | 0.00 | 0.606384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157924E+10 | 0.00 | 0.00 | 0.00 | 0.240652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164608E+10 | 0.00 | 0.00 | 0.00 | 0.928723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224544E+11 | 0.00 | 0.00 | 0.00 | 0.869469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146679E+10 | 0.00 | 0.00 | 0.00 | 0.369734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.241178E+10 | 0.00 | 0.00 | 0.00 | 0.152405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179477E+11 | 16568339.16 | 0.00 | 74372860.90 | 0.00 | 0.119669E+09 | 0.200102E+11 | 0.00 | 4.43 |
February | 0.228094E+11 | 0.00 | 0.00 | 28131471.30 | 0.00 | 15571346.48 | 0.158657E+11 | 0.00 | 3.90 |
March | 0.168257E+11 | 52020365.56 | 0.00 | 70278775.33 | 0.00 | 12817846.35 | 0.193685E+11 | 0.00 | 4.38 |
April | 0.392068E+10 | 0.253083E+10 | 412658.25 | 0.105380E+09 | 2205778.17 | 454655.62 | 0.990390E+10 | 25337.84 | 4.16 |
May | 0.134600E+10 | 0.564603E+10 | 0.00 | 77042538.34 | 3358281.27 | 683935.18 | 0.607628E+10 | 0.00 | 3.97 |
June | 0.144243E+09 | 0.158437E+11 | 327324.37 | 21490701.69 | 93240056.72 | 421733.78 | 0.171434E+10 | 24300.36 | 3.86 |
July | 96486064.95 | 0.223434E+11 | 4533.62 | 8732998.73 | 0.229821E+09 | 523812.49 | 0.744850E+09 | 2188.34 | 3.80 |
August | 0.156034E+09 | 0.203611E+11 | 71383.39 | 11848828.10 | 0.179858E+09 | 31039.52 | 0.115778E+10 | 10883.24 | 3.94 |
September | 0.321602E+09 | 0.143011E+11 | 68252.65 | 19577511.93 | 69775991.51 | 0.00 | 0.233213E+10 | 11426.69 | 4.10 |
October | 0.651074E+10 | 0.332996E+10 | 127956.03 | 84997079.00 | 16123932.61 | 243365.63 | 0.160455E+11 | 2623.31 | 4.47 |
November | 0.141669E+11 | 56848127.06 | 0.00 | 73879417.00 | 0.00 | 3203065.72 | 0.222992E+11 | 0.00 | 4.45 |
December | 0.281276E+11 | 0.00 | 0.00 | 45927804.14 | 0.00 | 23234625.62 | 0.164893E+11 | 0.00 | 4.12 |
Annual Sum or Average | 0.112373E+12 | 0.844815E+11 | 1012108.32 | 0.621660E+09 | 0.594383E+09 | 0.176854E+09 | 0.132008E+12 | 76759.78 | 4.13 |
Minimum of Months | 96486064.95 | 0.00 | 0.00 | 8732998.73 | 0.00 | 0.00 | 0.744850E+09 | 0.00 | 3.80 |
Maximum of Months | 0.281276E+11 | 0.223434E+11 | 412658.25 | 0.105380E+09 | 0.229821E+09 | 0.119669E+09 | 0.222992E+11 | 25337.84 | 4.47 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146075E+11 | 0.00 | 0.00 | 76141381.46 | 24560711.00 | 0.00 | 0.255668E+11 | 0.00 | 8.03 |
February | 0.153439E+11 | 0.00 | 0.00 | 40106245.47 | 0.00 | 0.00 | 0.236684E+11 | 0.00 | 8.09 |
March | 0.132378E+11 | 0.00 | 0.00 | 76317236.90 | 0.00 | 0.00 | 0.254819E+11 | 0.00 | 8.10 |
April | 0.185361E+10 | 0.705192E+09 | 0.00 | 0.136979E+09 | 0.00 | 0.00 | 0.207071E+11 | 0.00 | 8.32 |
May | 0.212791E+09 | 0.177439E+10 | 0.00 | 0.136092E+09 | 0.00 | 0.00 | 0.156738E+11 | 0.00 | 8.50 |
June | 9154099.84 | 0.627189E+10 | 0.00 | 81700435.26 | 0.00 | 0.00 | 0.575565E+10 | 0.00 | 8.85 |
July | 925963.41 | 0.103956E+11 | 0.00 | 39283032.78 | 0.00 | 0.00 | 0.229689E+10 | 0.00 | 9.00 |
August | 0.00 | 0.877446E+10 | 0.00 | 42434893.50 | 744720.84 | 0.00 | 0.260643E+10 | 0.00 | 8.96 |
September | 113582.95 | 0.609456E+10 | 0.00 | 62056359.00 | 427602.85 | 0.00 | 0.474428E+10 | 0.00 | 8.88 |
October | 0.437165E+10 | 0.100195E+10 | 0.00 | 0.102850E+09 | 325104.58 | 0.00 | 0.222336E+11 | 0.00 | 8.34 |
November | 0.105963E+11 | 0.00 | 0.00 | 79589931.33 | 0.00 | 0.00 | 0.265971E+11 | 0.00 | 8.12 |
December | 0.227379E+11 | 0.00 | 0.00 | 52564052.57 | 31318219.70 | 2679568.62 | 0.234013E+11 | 0.00 | 8.05 |
Annual Sum or Average | 0.829716E+11 | 0.350180E+11 | 0.00 | 0.926114E+09 | 57376358.97 | 2679568.62 | 0.198733E+12 | 0.00 | 8.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 39283032.78 | 0.00 | 0.00 | 0.229689E+10 | 0.00 | 8.03 |
Maximum of Months | 0.227379E+11 | 0.103956E+11 | 0.00 | 0.136979E+09 | 31318219.70 | 2679568.62 | 0.265971E+11 | 0.00 | 9.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:55
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.559837E+11 | 0.872940E+10 | 0.131798E+12 | 0.545204E+10 | 0.420274E+11 |
February | 0.634095E+11 | 0.998365E+10 | 0.132540E+12 | 0.223629E+10 | 0.197302E+11 |
March | 0.902750E+11 | 0.975915E+10 | 0.127298E+12 | 0.499255E+10 | 0.442003E+11 |
April | 0.124375E+12 | 0.554862E+10 | 0.716323E+11 | 0.255711E+10 | 0.108968E+12 |
May | 0.132201E+12 | 0.380387E+10 | 0.472354E+11 | 0.135227E+10 | 0.140514E+12 |
June | 0.138095E+12 | 0.881924E+09 | -0.627426E+10 | 0.555361E+09 | 0.190168E+12 |
July | 0.123091E+12 | -573046267.8 | -0.321979E+11 | 0.103547E+09 | 0.210583E+12 |
August | 0.104193E+12 | -468070962.1 | -0.252424E+11 | 0.311432E+09 | 0.206511E+12 |
September | 0.858447E+11 | 0.169134E+09 | -0.593399E+10 | 0.539445E+09 | 0.177213E+12 |
October | 0.757502E+11 | 0.512678E+10 | 0.833663E+11 | 0.449482E+10 | 0.953212E+11 |
November | 0.586470E+11 | 0.852325E+10 | 0.124151E+12 | 0.554469E+10 | 0.436280E+11 |
December | 0.425750E+11 | 0.104200E+11 | 0.154429E+12 | 0.359428E+10 | 0.306400E+11 |
Annual Sum or Average | 0.109444E+13 | 0.619046E+11 | 0.802802E+12 | 0.317338E+11 | 0.130951E+13 |
Minimum of Months | 0.425750E+11 | -573046267.8 | -0.321979E+11 | 0.103547E+09 | 0.197302E+11 |
Maximum of Months | 0.138095E+12 | 0.104200E+11 | 0.154429E+12 | 0.554469E+10 | 0.210583E+12 |