Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:24:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2361.48 | 4619.91 | 4619.91 |
Net Site Energy | 2361.48 | 4619.91 | 4619.91 |
Total Source Energy | 4450.23 | 8706.26 | 8706.26 |
Net Source Energy | 4450.23 | 8706.26 | 8706.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 605.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 70.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.51 | 378.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 62.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 907.53 | 1453.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 605.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 70.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.19 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 122.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.51 | 378.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 605.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 70.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 71.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 122.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.51 | 378.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 62.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 526.43 | 1925.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1021.92 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1775.46 | 2844.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 526.43 | 1925.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1021.92 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1775.46 | 2844.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 907.532 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 907.532 | 100.00 |
Total On-Site and Utility Electric Sources | 907.532 | 100.00 |
Total Electricity End Uses | 907.532 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4093.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 9.5182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.3127 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.5182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.3127 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 9.4622 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-10:00 | 11-DEC-04:30 | - | - | - | - | - | - | - | - | - | - | 08-MAR-07:00 |
Heating | 0.00 | 171080.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23006.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24680.63 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5469.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3395.45 | 13975.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2931.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 62709.27 | 189582.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 171080.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23006.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 23313.05 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5469.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3395.45 | 13975.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1310.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 656.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 224.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 225.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 142.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1457.82 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 387.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.14 | 410.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2874.15 | 1576.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1283.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 438.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 757.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.84 | 803.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 384.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5622.88 | 3083.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1283.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 438.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 757.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.84 | 803.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 384.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5622.88 | 3083.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.49 |
KITCHEN DIRECT AIR | 1.58 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.49 | 3.49 | 3.49 | 3.49 | 3.49 | 3.49 | 1.00 | 1.00 | 3.49 |
PSZ-AC_2:2 | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.00 | 1.00 | 1.58 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.49 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.58 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.49 | 3737.32 |
PSZ-AC_2:2_ADDAQ FAN | 1.58 | 1686.39 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.49 | 3.49 | 3.49 | 2.31 | 86731.28 | 136864.36 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.58 | 1.58 | 1.58 | 1.04 | 39135.75 | 90026.01 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.49 | 1.75 | 2.33 | 86731.28 | 43365.64 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.58 | 0.787998 | 1.05 | 39135.75 | 19567.88 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 136864.36 |
PSZ-AC_2:2 HEATING COIL | 90026.01 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 9.518 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 74.446 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.313 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.393 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3538.380 | 9.518 | 12.631 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3538.380 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1298.236 | 9.313 | 172.457 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1298.236 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.8794 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9031 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.28842413E-12 | 0.14163715E-14 | -0.83625437E-13 | 0.83302026E-16 |
34 | 6 | 0.27446597E-07 | 0.24415596E-09 | 0.62976823E-08 | -0.12863247E-12 |
35 | 5 | -0.18387070E-03 | 0.21059431E-05 | -0.94655602E-04 | 0.62291981E-08 |
36 | 4 | 0.28482235 | 0.10320537E-02 | 0.97050522E-01 | -0.32540306E-04 |
37 | 3 | -7.1212123 | 0.32167701E-01 | -2.2958568 | 0.28298028E-01 |
38 | 2 | 40.392481 | 0.11496341 | 15.088345 | -0.32800964 |
39 | 1 | -80.178917 | 0.52112252E-01 | -28.983173 | 1.0708012 |
40 | 0 | 46.824341 | 0.10529732E-02 | 16.295060 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.4731_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6349E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.1228E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5375E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8463E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3939E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.0466E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0758E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5500E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.6451E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.3515E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1004 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.6679E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.8301E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.7500E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.6281E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.6443E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9961E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4324E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6561E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2773E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8326E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2265E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6313E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0762E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 38999.82042 | 46799.78451 | 2.91056 | 3.49267 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 11478.56637 | 13774.27964 | 0.50465 | 1.33138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | -16.30000 | 9.24091E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20748.56974 | 24898.28368 | 1.31333 | 1.57600 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 29.46300 | 1.33655E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 1361.25597 | 1633.50716 | 5.41438E-002 | 1.21700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -16.30000 | 9.24091E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 55989.88 | 3.49267 | 3.49267 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 88420.91 | 1.33138 | 1.33138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 29492.10 | 1.57600 | 1.57600 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 80824.88 | 1.21700 | 1.21700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.49267 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.57600 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.49267 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.49267 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.49267 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.49267 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.49267 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.49267 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.57600 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57600 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.57600 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.57600 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.57600 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.57600 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.49267 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.57600 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.49267 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.49267 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3737.32047 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.49267 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.49267 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.49267 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.30516 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.49267 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.74633 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.32845 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 86731.28000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 43365.64000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 86731.28000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 136864.36210 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 136864.36210 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.57600 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.57600 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1686.39103 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.57600 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.57600 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.57600 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04016 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.57600 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78800 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05067 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39135.75000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19567.87500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39135.75000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 90026.01442 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 90026.01442 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 84248.8 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 38015.6 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | N/A | 2.689 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | N/A | 2.689 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | N/A | 2.689 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.8802012431E-002 | 0.4312820211 | Pass | Pass | 0.1737048389 | 0.5423521891 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 9.4944161226E-002 | 0.5499439897 | Pass | Pass | 2.7001377054E-002 | 8.7095815723E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1269637094 | 0.1199913021 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 992.00 | 122.64 | 2077.45 | 8.39 | 688.09 | 3888.58 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.689 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.689 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.5182 | 371.75 | 3538.38 | LightsWired | LTG_SCH_DINING | 93.86 | 168.00 | 77.66 | 0.0000 | Y | 51.58 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.3127 | 139.41 | 1298.24 | LightsWired | LTG_SCH_KITCHEN | 80.88 | 168.00 | 80.41 | 0.0000 | Y | 19.60 |
Interior Lighting Total | 9.4622 | 511.15 | 4836.62 | 71.18 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.52 | AstronomicalClock | - | 49.04 | 49.04 | 1.93 | |
EXTERIOR_LIGHTS_B | 3124.83 | AstronomicalClock | - | 83.67 | 73.28 | 42.98 | |
Exterior Lighting Total | 3334.35 | 44.91 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 86731.28 | 60805.57 | 25925.71 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39135.75 | 27437.29 | 11698.46 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 84248.8 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 38015.6 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 136864.36 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 90026.01 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.55 | 1983.06 | 778.12 | 1.00 | 0.59 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 3.49 | 3737.32 | 1070.05 | 1.00 | 1.25 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.58 | 1686.39 | 1070.05 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 38999.82 | 46799.78 | 125.89 | 2.911 | 3.493 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.01069 | 30.21 | 0.01337 | 1.331 | 0.00 |
KITCHEN | 20748.57 | 24898.28 | 178.60 | 1.313 | 1.576 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01041 | 29.46 | 0.01337 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 11478.57 | 13774.28 | 37.05 | 0.505 | 1.331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00760 | -16.30 | 0.00092 | 1.331 | 0.00 |
KITCHEN | 1361.26 | 1633.51 | 11.72 | 0.054 | 1.217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00517 | -16.30 | 0.00092 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.49 | 3.49 | 1.33 | 1.33 | 3.4927 | 3.4927 | 3.4927 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.58 | 1.58 | 1.22 | 1.22 | 1.5760 | 1.5760 | 1.5760 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 86731.280 | 60805.566 | 3.492670 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 43365.64 | 28373.03 | 2.328447 | 26.39 | 19.49 | 0.01170973 | 11.91 | 11.51 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 57.1788 | 23.99 | 0.01068871 | 55.9437 | 38992.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 136864.362 | 136864.362 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 136864.36 | 136864.36 | 3.492669 | 6.78 | 5.30 | 0.00505502 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 38.1192 | 21.00 | 0.00759971 | 47.9297 | 11476.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 39135.750 | 27437.292 | 1.576000 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19567.88 | 12221.46 | 1.050667 | 28.66 | 20.89 | 0.01269122 | 11.91 | 11.51 | 0.00850000 | 29.46 | 0.01336548 | 21.59 | 115.8314 | 25.99 | 0.01040548 | 48.3639 | 20748.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 90026.014 | 90026.014 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 90026.01 | 90026.01 | 1.575997 | -8.42 | -8.57 | 0.00180850 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 77.2211 | 19.00 | 0.00480665 | 34.4678 | 1024.68 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 86731.280 | 60805.566 | 3.492670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6078 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.492669 | 4.10013204 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 43365.64 | 28373.03 | 1.0000 | 2.73342248 | 2.328447 | 26.39 | 19.49 | 0.01170973 | 56378.3 | 11.91 | 11.51 | 0.00850000 | 33416.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43365.64 | 30.30 | 0.01336696 | 21.83 | 1.33137743 | 57.1788 | 23.98 | 0.01068871 | 23.99 | 0.01068871 | 55.9437 | 38992.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 136864.362 | 136864.362 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.492669 | 4.10013204 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 136864.36 | 136864.36 | 1.0000 | 4.10013204 | 3.492669 | 6.78 | 5.30 | 0.00505502 | 19519.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 136864.36 | -16.30 | 0.00092409 | -16.30 | 1.33137743 | 38.1192 | 21.00 | 0.00759971 | 21.00 | 0.00759971 | 47.9297 | 11476.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39135.750 | 27437.292 | 1.576000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4323 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.575997 | 1.85010248 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19567.88 | 12221.46 | 1.0000 | 1.23340420 | 1.050667 | 28.66 | 20.89 | 0.01269122 | 61218.7 | 11.91 | 11.51 | 0.00850000 | 33417.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19567.88 | 29.46 | 0.01336548 | 21.59 | 1.21700195 | 115.8314 | 25.95 | 0.01040548 | 25.99 | 0.01040548 | 48.3639 | 20748.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90026.014 | 90026.014 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.575997 | 1.85010248 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | Sensible | 90026.01 | 90026.01 | 1.0000 | 1.85010248 | 1.575997 | -8.42 | -8.57 | 0.00180850 | -3970.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90026.01 | -16.30 | 0.00092409 | -16.30 | 1.21700195 | 77.2211 | 18.27 | 0.00480665 | 19.00 | 0.00480665 | 34.4678 | 1024.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.49 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.58 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3457.67 | 5491.00 | 2040.33 |
KITCHEN | 4881.17 | 6079.83 | 3940.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5033.50 | 7088.33 | 4093.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 19.17 | 7.83 | 0.00 | 0.00 |
KITCHEN | 0.00 | 189.00 | 0.00 | 0.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 19.17 | 190.83 | 0.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.462 | 0.596 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.310 | 0.044 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.046 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.537 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36718574.36 | 0.00 | 36718574.36 | 4914758.77 | 41633333.13 | 41986318.57 | 1443.32 | 5835.36 | 1481.32 | 343.21 |
KITCHEN | 29240607.53 | 0.00 | 29240607.53 | 215095.64 | 29455703.17 | 38379373.44 | 8169.99 | 517.79 | 72.22 | 639.97 |
Total Facility | 65959181.89 | 0.00 | 65959181.89 | 5129854.41 | 71089036.30 | 80365692.01 | 8173.18 | 5849.20 | 1520.60 | 749.27 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3860 | 0.0000 | 1.3860 | 0.1850 | 1.5710 | 1.3314 | 0.00 | 5726.39 | 1460.61 |
KITCHEN | 1.0835 | 0.0000 | 1.0835 | 0.0052 | 1.0886 | 1.2170 | 6612.81 | 508.42 | 65.77 |
Total Facility | 2.4695 | 0.0000 | 2.4695 | 0.1901 | 2.6596 | 2.5484 | 6612.81 | 5739.51 | 1496.60 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50601532.15 | 0.00 | 50601532.15 | 41986318.57 | 1441.36 | 0.12 | 7318.52 | 343.19 |
PSZ-AC_2:2 | 40296610.78 | 0.00 | 40296610.78 | 38379373.44 | 1393.71 | 1.78 | 7364.51 | 639.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9101 | 0.0000 | 1.9101 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4931 | 0.0000 | 1.4931 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1538.50 | 162.90 | 5828.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 287.60 | 1378.31 | 6161.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.2252 | 2.0359 | 1.8350 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.6385 | 1.5749 | 1.4784 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
Electricity:Building | 548.35 | 4052.25 | 01-JAN-01:10 | 30253.07 | 02-JAN-11:10 |
Electricity:Zone:DINING | 176.74 | 991.88 | 01-JAN-01:10 | 9336.09 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 531.49 | 3643.21 | 01-JAN-01:10 | 27887.91 | 02-JAN-11:10 |
InteriorLights:Electricity | 71.18 | 557.53 | 11-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 51.58 | 395.98 | 11-JUN-05:00 | 3065.69 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 71.18 | 557.53 | 11-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 71.18 | 557.53 | 11-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 51.58 | 395.98 | 11-JUN-05:00 | 3065.69 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 71.18 | 557.53 | 11-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 371.61 | 3060.37 | 01-JAN-01:10 | 21021.20 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.16 | 2489.78 | 01-JAN-01:10 | 17686.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.03 | 1122.20 | 01-JAN-01:10 | 16319.14 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.04 | 1038.01 | 11-DEC-23:30 | 3441.39 | 14-MAR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 121.14 | 1103.42 | 29-JAN-01:10 | 6497.01 | 16-JUL-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.73 | 0.00 | 01-JAN-11:10 | 1458.21 | 21-JUL-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 29.46 | 777.32 | 13-FEB-01:10 | 1076.23 | 12-MAR-13:10 |
ElectricityPurchased:Facility | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
ElectricityPurchased:Plant | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
Cogeneration:ElectricityPurchased | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
General:Cogeneration:ElectricityPurchased | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
ElectricityNet:Plant | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
Cogeneration:ElectricityNet | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
General:Cogeneration:ElectricityNet | 907.53 | 7343.05 | 29-JAN-01:10 | 62709.27 | 20-JUL-11:00 |
Electricity:HVAC | 193.13 | 0.00 | 01-JAN-01:10 | 32209.58 | 27-JUN-13:00 |
Fans:Electricity | 122.29 | 0.00 | 01-JAN-01:10 | 5992.53 | 27-JUN-13:00 |
General:Fans:Electricity | 122.29 | 0.00 | 01-JAN-01:10 | 5992.53 | 27-JUN-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 70.84 | 0.00 | 01-JAN-00:10 | 26217.06 | 27-JUN-13:00 |
General:Cooling:Electricity | 70.84 | 0.00 | 01-JAN-00:10 | 26217.06 | 27-JUN-13:00 |
ExteriorLights:Electricity | 44.91 | 0.00 | 01-JAN-08:00 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.91 | 0.00 | 01-JAN-08:00 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.51 | 0.00 | 01-JAN-01:10 | 4742.28 | 21-MAR-18:40 |
Water Heater:WaterSystems:Electricity | 75.51 | 0.00 | 01-JAN-01:10 | 4742.28 | 21-MAR-18:40 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 17-MAR-23:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 17-MAR-23:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1453.95 | 2803.57 | 01-JAN-01:20 | 189582.01 | 11-DEC-04:30 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 605.43 | 0.00 | 01-JAN-01:10 | 171080.45 | 04-JAN-04:30 |
Heating:NaturalGas | 605.43 | 0.00 | 01-JAN-01:10 | 171080.45 | 04-JAN-04:30 |
General:Heating:NaturalGas | 605.43 | 0.00 | 01-JAN-01:10 | 171080.45 | 04-JAN-04:30 |
NaturalGas:Plant | 378.73 | 993.32 | 01-JAN-00:10 | 33581.36 | 17-FEB-07:40 |
WaterSystems:NaturalGas | 378.73 | 993.32 | 01-JAN-00:10 | 33581.36 | 17-FEB-07:40 |
Water Heater:WaterSystems:NaturalGas | 378.73 | 993.32 | 01-JAN-00:10 | 33581.36 | 17-FEB-07:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1779.29 | 3206.96 | 07-FEB-01:10 | 163549.95 | 20-JUL-11:10 |
EnergyTransfer:Building | 686.42 | 1603.48 | 07-FEB-01:10 | 47614.38 | 21-JUL-11:10 |
EnergyTransfer:Zone:KITCHEN | 432.50 | 1603.48 | 07-FEB-01:10 | 24790.34 | 12-SEP-04:10 |
Refrigeration:EnergyTransfer | 144.98 | 2714.14 | 11-DEC-23:20 | 7834.84 | 14-MAR-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.49 | 1357.07 | 11-DEC-23:20 | 3917.42 | 14-MAR-10:40 |
General:Refrigeration:EnergyTransfer | 72.49 | 1357.07 | 11-DEC-23:20 | 3917.42 | 14-MAR-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.49 | 1357.07 | 11-DEC-23:20 | 3917.42 | 14-MAR-10:40 |
EnergyTransfer:Plant | 340.98 | 1603.48 | 07-FEB-01:10 | 20915.20 | 15-MAR-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.33 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 57.16 | 1341.96 | 13-FEB-01:10 | 2238.70 | 12-MAR-13:10 |
EnergyTransfer:Zone:DINING | 253.92 | 0.00 | 01-JAN-01:10 | 30033.02 | 26-DEC-21:30 |
Heating:EnergyTransfer | 6.37 | 0.00 | 01-JAN-00:10 | 17547.13 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:DINING | 6.35 | 0.00 | 01-JAN-00:10 | 17547.13 | 13-FEB-04:10 |
General:Heating:EnergyTransfer | 6.37 | 0.00 | 01-JAN-00:10 | 17547.13 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:DINING | 6.35 | 0.00 | 01-JAN-00:10 | 17547.13 | 13-FEB-04:10 |
Cooling:EnergyTransfer | 607.56 | 0.00 | 01-JAN-01:10 | 44224.06 | 21-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 247.57 | 0.00 | 01-JAN-01:10 | 26845.96 | 21-JUL-12:00 |
General:Cooling:EnergyTransfer | 607.56 | 0.00 | 01-JAN-01:10 | 44224.06 | 21-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 247.57 | 0.00 | 01-JAN-01:10 | 26845.96 | 21-JUL-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1175.22 | 07-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1175.22 | 07-MAR-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 359.99 | 0.00 | 01-JAN-01:10 | 20947.51 | 12-SEP-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 359.99 | 0.00 | 01-JAN-01:10 | 20947.51 | 12-SEP-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 268.49 | 0.00 | 01-JAN-01:10 | 18450.75 | 14-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 268.49 | 0.00 | 01-JAN-01:10 | 18450.75 | 14-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 268.49 | 0.00 | 01-JAN-01:10 | 18450.75 | 14-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 268.49 | 0.00 | 01-JAN-01:10 | 18450.75 | 14-FEB-07:20 |
EnergyTransfer:HVAC | 751.89 | 0.00 | 01-JAN-01:10 | 136864.36 | 06-FEB-04:30 |
HeatingCoils:EnergyTransfer | 484.34 | 0.00 | 01-JAN-01:10 | 136864.36 | 06-FEB-04:30 |
CoolingCoils:EnergyTransfer | 267.55 | 0.00 | 01-JAN-00:10 | 106501.62 | 27-JUN-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 268.49 | 0.00 | 01-JAN-01:10 | 18450.75 | 14-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 268.49 | 0.00 | 01-JAN-01:10 | 18450.75 | 14-FEB-07:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 6.351 | -247.570 | 0.000 | 0.000 | 229.699 | 51.581 | 93.867 | 37.486 | 0.000 | 1.085 | 0.000 | 0.000 | -30.436 | 0.000 | -75.655 | -66.408 |
KITCHEN | 0.000 | 0.000 | 0.018 | -359.982 | 0.000 | 0.000 | 6.019 | 19.596 | 297.703 | 0.000 | 0.000 | 0.011 | 40.671 | 0.000 | 0.000 | 0.000 | -4.035 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.363 | 29.043 | 0.000 | 0.000 | 0.000 | -34.406 | -0.001 |
Total Facility | 0.000 | 0.000 | 6.368 | -607.552 | 0.000 | 0.000 | 235.718 | 71.177 | 391.570 | 37.486 | 0.000 | 6.458 | 69.714 | 0.000 | -30.436 | 0.000 | -114.095 | -66.409 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 11-DEC-00:01 | 0.00 | 0.00 | 0.00 | -53360.99 | 0.00 | 0.00 | 1157.80 | 510.94 | 541.06 | 0.00 | 0.00 | 0.00 | 55661.21 | 0.00 | -3826.30 | 0.00 | -683.71 | 0.00 |
KITCHEN | 12-SEP-04:01 | 0.00 | 0.00 | 0.00 | -52754.78 | 0.00 | 0.00 | 11.93 | 215.40 | 7253.89 | 0.00 | 0.00 | 0.00 | 45317.15 | 0.00 | -0.00 | 0.00 | -43.61 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-MAY-00:41 | 0.00 | 0.00 | 0.00 | -81325.33 | 0.00 | 0.00 | 0.00 | 672.49 | 2707.55 | 0.00 | 0.00 | 252.96 | 78037.30 | 0.00 | -241.13 | 0.00 | -103.84 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 22-FEB-04:01 | 0.00 | 0.00 | 94105.43 | 0.00 | 0.00 | 0.00 | 0.00 | 510.94 | 901.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2659.24 | 0.00 | -1493.63 | -91365.26 |
KITCHEN | 07-MAR-05:03 | 0.00 | 0.00 | 11739.77 | 0.00 | 0.00 | 0.00 | 23.78 | 215.40 | 7253.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -91.52 | -19141.33 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-FEB-04:01 | 0.00 | 0.00 | 94105.43 | 0.00 | 0.00 | 0.00 | 0.00 | 672.49 | 4717.49 | 0.00 | 0.00 | 479.86 | 0.00 | 0.00 | -2659.24 | 0.00 | -2528.32 | -94787.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.4927 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.4927 | 0.3812 | 1.0000 | Not calculated | 1.3314 | 0.3812 | ||
PSZ-AC_2:2 | 1.5760 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5760 | 0.1159 | 1.0000 | Not calculated | 0.1826 | 0.1159 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.4927 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.4927 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3812 | ||
PSZ-AC_2:2 | 1.5760 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5760 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1159 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4927 | 3.4927 | 3.4927 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5760 | 1.5760 | 1.5760 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.4927 | 3.4927 | 3.4927 | 3.4927 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5760 | 1.5760 | 1.5760 | 1.5760 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4927 | 3.4927 | 3.4927 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5760 | 1.5760 | 1.5760 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.4927 | 3.4927 | 3.4927 | 3.4927 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5760 | 1.5760 | 1.5760 | 1.5760 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 605.43 | 171080.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 70.84 | 26217.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 71.18 | 4035.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.91 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.19 | 23313.05 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 122.29 | 5992.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.51 | 4742.28 | 378.73 | 33581.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.73 | 1458.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.46 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 522.36 | 907.53 |
Natural Gas | 469.79 | 1453.95 |
Additional | 0.00 | 0.00 |
Total | 992.14 | 2361.48 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 139.25 |
Space Heating | 0.00 |
Space Cooling | 138.60 |
Fans (All) | 239.24 |
Service Water Heating | 147.72 |
Receptacle Equipment | 900.54 |
Miscellaneous (All) | 1775.46 |
Subtotal | 1775.46 |
Natural Gas [MJ/m2] | |
Space Heating | 1184.44 |
Service Water Heating | 740.94 |
Miscellaneous (All) | 2844.45 |
Subtotal | 2844.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.01 |
Space Heating | 25.64 |
Space Cooling | 3.00 |
Fans (All) | 5.18 |
Service Water Heating | 19.24 |
Receptacle Equipment | 39.39 |
Miscellaneous | 4.55 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4894. | 8760. |
LTG_SCH_KITCHEN | 4218. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8605.00 | 155.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7381.67 | 520.00 | 472.33 | 367.67 | 18.33 |
Min | 7381.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 520.00 | 472.33 | 367.67 | 18.33 |
Average | 8248.89 | 225.00 | 157.44 | 122.56 | 6.11 |
Sum | 24746.67 | 675.00 | 472.33 | 367.67 | 18.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19232.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.50 | 0.00 | 0.00 | 0.00 |
Average | 281151.50 | 0.17 | 0.00 | 0.00 | 0.00 |
Sum | 843454.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8145.00 | 615.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6688.50 | 2071.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7264.50 | 945.67 | 259.67 | 181.17 | 109.00 |
Min | 6688.50 | 615.00 | 0.00 | 0.00 | 0.00 |
Max | 8145.00 | 2071.50 | 259.67 | 181.17 | 109.00 |
Average | 7366.00 | 1210.72 | 86.56 | 60.39 | 36.33 |
Sum | 22098.00 | 3632.17 | 259.67 | 181.17 | 109.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 755514.67 | 68707.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14104.83 | 5128.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 755514.67 | 68707.33 | 0.00 | 0.00 | 0.00 |
Average | 256539.83 | 24611.83 | 0.00 | 0.00 | 0.00 |
Sum | 769619.50 | 73835.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803821E+10 | 45846.08 | 24-JAN-00:01 | -11.1 | -12.0 | 0.119990E+11 | 10741.41 | 28-JAN-19:40 | -8.2 | -9.7 |
February | 0.710064E+10 | 51605.40 | 07-FEB-00:01 | -15.0 | -15.8 | 0.108699E+11 | 10741.41 | 25-FEB-19:00 | -6.7 | -7.8 |
March | 0.148709E+11 | 47056.63 | 07-MAR-00:01 | -11.8 | -12.6 | 0.124082E+11 | 12938.01 | 14-MAR-11:00 | 23.90 | 17.56 |
April | 0.190508E+11 | 33929.40 | 16-APR-23:01 | -2.9 | -4.7 | 0.121651E+11 | 14051.31 | 08-APR-18:49 | -2.9 | -4.7 |
May | 0.238834E+11 | 46619.29 | 24-MAY-01:51 | 19.40 | 14.18 | 0.140383E+11 | 14050.84 | 20-MAY-18:40 | 19.40 | 14.18 |
June | 0.284444E+11 | 40141.54 | 17-JUN-01:51 | 18.90 | 15.79 | 0.146334E+11 | 14051.79 | 10-JUN-18:49 | 18.90 | 15.79 |
July | 0.328047E+11 | 42632.09 | 08-JUL-00:42 | 19.40 | 14.70 | 0.152436E+11 | 14052.46 | 22-JUL-18:00 | 21.70 | 19.38 |
August | 0.329478E+11 | 41522.96 | 06-AUG-03:22 | 20.60 | 15.63 | 0.153628E+11 | 14051.75 | 26-AUG-18:10 | 22.70 | 20.68 |
September | 0.283508E+11 | 45533.29 | 08-SEP-01:51 | 17.80 | 14.06 | 0.143061E+11 | 14051.45 | 16-SEP-18:10 | 24.82 | 19.37 |
October | 0.240576E+11 | 41181.65 | 23-OCT-03:11 | 15.17 | 12.48 | 0.129644E+11 | 14050.53 | 21-OCT-18:19 | 15.17 | 12.48 |
November | 0.183691E+11 | 32416.75 | 24-NOV-00:01 | -1.8 | -2.5 | 0.118429E+11 | 14045.72 | 04-NOV-18:49 | -1.8 | -2.5 |
December | 0.965356E+10 | 53362.28 | 11-DEC-00:01 | -16.1 | -16.3 | 0.120006E+11 | 11410.96 | 01-DEC-12:00 | -16.1 | -16.3 |
Annual Sum or Average | 0.247572E+12 | 0.157834E+12 | ||||||||
Minimum of Months | 0.710064E+10 | 32416.75 | -16.1 | -16.3 | 0.108699E+11 | 10741.41 | -16.1 | -16.3 | ||
Maximum of Months | 0.329478E+11 | 53362.28 | 20.60 | 15.79 | 0.153628E+11 | 14052.46 | 24.82 | 20.68 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282668E+11 | 44548.99 | 10-JAN-05:01 | -13.3 | -14.3 | 0.103921E+11 | 6853.64 | 11-JAN-11:00 | 9.40 | 8.22 |
February | 0.250940E+11 | 45466.28 | 07-FEB-05:01 | -15.7 | -16.1 | 0.938730E+10 | 6827.78 | 22-FEB-11:00 | 6.70 | 2.27 |
March | 0.288690E+11 | 44166.94 | 07-MAR-05:01 | -13.3 | -13.9 | 0.104245E+11 | 6931.61 | 15-MAR-10:39 | 23.33 | 15.40 |
April | 0.286939E+11 | 33204.48 | 09-APR-04:01 | 11.70 | 10.38 | 0.101188E+11 | 6931.57 | 07-APR-10:00 | 11.70 | 10.38 |
May | 0.296019E+11 | 47941.46 | 30-MAY-04:01 | 12.20 | 11.62 | 0.105536E+11 | 6931.66 | 17-MAY-10:00 | 12.20 | 11.62 |
June | 0.305709E+11 | 52746.54 | 16-JUN-04:01 | 12.62 | 9.73 | 0.102491E+11 | 6931.66 | 01-JUN-10:39 | 12.62 | 9.73 |
July | 0.326976E+11 | 49156.38 | 07-JUL-04:01 | 12.20 | 11.56 | 0.105953E+11 | 6931.62 | 13-JUL-10:39 | 21.83 | 16.26 |
August | 0.329933E+11 | 51316.00 | 04-AUG-04:01 | 12.20 | 10.63 | 0.105996E+11 | 6931.65 | 30-AUG-10:20 | 17.97 | 17.50 |
September | 0.312676E+11 | 52778.68 | 12-SEP-04:01 | 8.48 | 7.88 | 0.102395E+11 | 6931.63 | 26-SEP-10:09 | 16.47 | 15.98 |
October | 0.320528E+11 | 52191.89 | 06-OCT-04:01 | 10.60 | 9.10 | 0.104928E+11 | 6931.63 | 12-OCT-10:00 | 17.80 | 14.41 |
November | 0.305907E+11 | 33144.05 | 24-NOV-05:01 | -3.0 | -3.7 | 0.100947E+11 | 6931.60 | 16-NOV-11:00 | -3.0 | -3.7 |
December | 0.292934E+11 | 47765.85 | 11-DEC-05:01 | -17.5 | -18.0 | 0.103927E+11 | 6914.48 | 01-DEC-11:50 | -17.5 | -18.0 |
Annual Sum or Average | 0.359992E+12 | 0.123540E+12 | ||||||||
Minimum of Months | 0.250940E+11 | 33144.05 | -17.5 | -18.0 | 0.938730E+10 | 6827.78 | -17.5 | -18.0 | ||
Maximum of Months | 0.329933E+11 | 52778.68 | 12.62 | 11.62 | 0.105996E+11 | 6931.66 | 23.33 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175034E+10 | 90202.68 | 26-JAN-04:01 | -7.2 |
February | 0.203006E+10 | 94107.75 | 22-FEB-04:01 | -5.4 |
March | 0.840760E+09 | 83640.91 | 06-MAR-04:01 | -11.1 |
April | 0.216462E+09 | 62238.02 | 17-APR-03:01 | -2.9 |
May | 4840806.91 | 8150.08 | 04-MAY-04:02 | 5.82 |
June | 794853.23 | 5975.40 | 14-JUN-04:03 | 6.70 |
July | 372810.54 | 2570.74 | 21-JUL-04:03 | 26.52 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 767504.48 | 9631.17 | 30-SEP-04:03 | 7.20 |
October | 36358502.13 | 50591.53 | 17-OCT-05:58 | -2.8 |
November | 0.123841E+09 | 40689.75 | 18-NOV-05:05 | 1.60 |
December | 0.134614E+10 | 83289.40 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.635074E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.203006E+10 | 94107.75 | 26.52 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6372419.31 | 11693.84 | 25-JAN-05:03 | -9.1 |
February | 4814761.18 | 11682.93 | 11-FEB-05:03 | -9.4 |
March | 3562800.08 | 11752.17 | 07-MAR-05:03 | -13.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 2785607.31 | 10915.42 | 26-DEC-05:03 | -12.2 |
Annual Sum or Average | 17535587.88 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 6372419.31 | 11752.17 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.455233E+10 | 3065.69 | 02-JAN-16:30 | 0.106297E+11 | 6993.92 | 01-JAN-11:09 |
February | 0.405852E+10 | 3065.69 | 01-FEB-17:10 | 0.960102E+10 | 6993.92 | 01-FEB-11:09 |
March | 0.442470E+10 | 3065.69 | 01-MAR-17:49 | 0.106297E+11 | 6993.92 | 01-MAR-11:09 |
April | 0.414958E+10 | 3065.69 | 01-APR-18:30 | 0.102868E+11 | 6993.92 | 01-APR-10:09 |
May | 0.423907E+10 | 3065.69 | 01-MAY-19:10 | 0.106297E+11 | 6993.92 | 01-MAY-10:09 |
June | 0.408872E+10 | 3065.69 | 01-JUN-19:40 | 0.102868E+11 | 6993.92 | 01-JUN-10:09 |
July | 0.416504E+10 | 3065.69 | 01-JUL-19:40 | 0.106297E+11 | 6993.92 | 01-JUL-10:09 |
August | 0.429234E+10 | 3065.69 | 01-AUG-19:30 | 0.106297E+11 | 6993.92 | 01-AUG-10:09 |
September | 0.420486E+10 | 3065.69 | 01-SEP-18:40 | 0.102868E+11 | 6993.92 | 01-SEP-10:09 |
October | 0.441649E+10 | 3065.69 | 02-OCT-17:30 | 0.106297E+11 | 6993.92 | 01-OCT-10:09 |
November | 0.441110E+10 | 3065.69 | 01-NOV-16:00 | 0.102868E+11 | 6993.92 | 01-NOV-10:09 |
December | 0.457847E+10 | 3065.69 | 01-DEC-16:19 | 0.106297E+11 | 6993.92 | 01-DEC-11:09 |
Annual Sum or Average | 0.515812E+11 | 0.125156E+12 | ||||
Minimum of Months | 0.405852E+10 | 3065.69 | 0.960102E+10 | 6993.92 | ||
Maximum of Months | 0.457847E+10 | 3065.69 | 0.106297E+11 | 6993.92 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165581E+10 | 969.33 | 02-JAN-10:09 | 0.284656E+11 | 17686.72 | 01-JAN-11:09 |
February | 0.149975E+10 | 969.33 | 01-FEB-10:09 | 0.257108E+11 | 17686.72 | 01-FEB-11:09 |
March | 0.168217E+10 | 969.33 | 01-MAR-10:09 | 0.284657E+11 | 17686.72 | 01-MAR-11:09 |
April | 0.160889E+10 | 969.33 | 01-APR-16:10 | 0.275474E+11 | 17686.72 | 01-APR-10:09 |
May | 0.166899E+10 | 969.33 | 01-MAY-09:09 | 0.284656E+11 | 17686.72 | 01-MAY-10:09 |
June | 0.162595E+10 | 969.33 | 01-JUN-09:09 | 0.275474E+11 | 17686.72 | 01-JUN-10:09 |
July | 0.165212E+10 | 969.33 | 01-JUL-16:10 | 0.284656E+11 | 17686.72 | 01-JUL-10:09 |
August | 0.168217E+10 | 969.33 | 01-AUG-09:09 | 0.284657E+11 | 17686.72 | 01-AUG-10:09 |
September | 0.160928E+10 | 969.33 | 01-SEP-09:09 | 0.275474E+11 | 17686.72 | 01-SEP-10:09 |
October | 0.165561E+10 | 969.33 | 02-OCT-09:09 | 0.284656E+11 | 17686.72 | 01-OCT-10:09 |
November | 0.160288E+10 | 969.33 | 01-NOV-09:09 | 0.275473E+11 | 17686.72 | 01-NOV-10:09 |
December | 0.165232E+10 | 969.33 | 01-DEC-10:09 | 0.284656E+11 | 17686.72 | 01-DEC-11:09 |
Annual Sum or Average | 0.195960E+11 | 0.335159E+12 | ||||
Minimum of Months | 0.149975E+10 | 969.33 | 0.257108E+11 | 17686.72 | ||
Maximum of Months | 0.168217E+10 | 969.33 | 0.284657E+11 | 17686.72 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.455233E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126991E+11 |
February | 0.272721E+11 | 0.405852E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119428E+11 |
March | 0.305458E+11 | 0.442470E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7928932.54 | 0.923658E+10 |
April | 0.292871E+11 | 0.414958E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630059E+10 |
May | 0.303219E+11 | 0.423907E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5185582.20 | 0.383275E+10 |
June | 0.295292E+11 | 0.408872E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175491E+09 | 0.195767E+10 |
July | 0.300798E+11 | 0.416504E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487098E+09 | 0.776753E+09 |
August | 0.305458E+11 | 0.429234E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381514E+09 | 0.125845E+10 |
September | 0.292871E+11 | 0.420486E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27785029.17 | 0.269652E+10 |
October | 0.300980E+11 | 0.441649E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561873E+10 |
November | 0.290996E+11 | 0.441110E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723906E+10 |
December | 0.300798E+11 | 0.457847E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120958E+11 |
Annual Sum or Average | 0.356244E+12 | 0.515812E+11 | 0.125156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108500E+10 | 0.756547E+11 |
Minimum of Months | 0.272721E+11 | 0.405852E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776753E+09 |
Maximum of Months | 0.305458E+11 | 0.457847E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487098E+09 | 0.126991E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.165581E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639854E+09 |
February | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676918E+09 |
March | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 432.98 | 0.419499E+09 |
April | 0.786997E+09 | 0.160889E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325330E+09 |
May | 0.814802E+09 | 0.166899E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8259.74 | 0.202521E+09 |
June | 0.793501E+09 | 0.162595E+10 | 0.227469E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1699853.01 | 0.140423E+09 |
July | 0.808298E+09 | 0.165212E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 5220211.24 | 79615378.07 |
August | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3618740.66 | 93689886.93 |
September | 0.786997E+09 | 0.160928E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 134351.98 | 0.137816E+09 |
October | 0.808786E+09 | 0.165561E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275159E+09 |
November | 0.781956E+09 | 0.160288E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374210E+09 |
December | 0.808298E+09 | 0.165232E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670068E+09 |
Annual Sum or Average | 0.957291E+10 | 0.195960E+11 | 0.276753E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 10681849.62 | 0.403510E+10 |
Minimum of Months | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79615378.07 |
Maximum of Months | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 5220211.24 | 0.676918E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404672E+09 | 0.130217E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297517E+09 | 0.181670E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542670E+09 | 0.278586E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390116E+09 | 0.363723E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492362E+09 | 0.426424E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408081E+09 | 0.463206E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432763E+09 | 0.470065E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424691E+09 | 0.405185E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632652E+09 | 0.301494E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511622E+09 | 0.197940E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510645E+09 | 0.111908E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314737E+09 | 0.110134E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536253E+10 | 0.344055E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297517E+09 | 0.110134E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632652E+09 | 0.470065E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3065.69 | 02-JAN-16:30 | 6993.92 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 14689.31 | 30-JAN-19:00 |
February | 30255.31 | 04-FEB-19:10 | 3065.69 | 01-FEB-17:10 | 6993.92 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 16198.87 | 06-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 3065.69 | 01-MAR-17:49 | 6993.92 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 443.92 | 15-MAR-14:00 | 13836.23 | 06-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 3065.69 | 01-APR-18:30 | 6993.92 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 8464.57 | 16-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 3065.69 | 01-MAY-19:10 | 6993.92 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 434.08 | 10-MAY-14:00 | 5137.18 | 06-MAY-18:53 |
June | 30255.31 | 03-JUN-18:10 | 3065.69 | 01-JUN-19:40 | 6993.92 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2269.90 | 27-JUN-12:00 | 4916.33 | 13-JUN-12:00 |
July | 30255.31 | 01-JUL-18:10 | 3065.69 | 01-JUL-19:40 | 6993.92 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2257.82 | 21-JUL-12:00 | 1970.99 | 06-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 3065.69 | 01-AUG-19:30 | 6993.92 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.61 | 10-AUG-12:00 | 4168.73 | 30-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 3065.69 | 01-SEP-18:40 | 6993.92 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 825.09 | 16-SEP-13:00 | 4416.86 | 28-SEP-17:30 |
October | 30255.31 | 07-OCT-18:10 | 3065.69 | 02-OCT-17:30 | 6993.92 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 8247.88 | 16-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 3065.69 | 01-NOV-16:00 | 6993.92 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9476.08 | 22-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 3065.69 | 01-DEC-16:19 | 6993.92 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 16241.34 | 11-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1970.99 | |||||
Maximum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2269.90 | 16241.34 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 969.33 | 02-JAN-10:09 | 14422.89 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1861.94 | 12-JAN-05:00 |
February | 813.01 | 04-FEB-19:10 | 969.33 | 01-FEB-10:09 | 14422.89 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1836.81 | 13-FEB-04:10 |
March | 813.01 | 04-MAR-19:10 | 969.33 | 01-MAR-10:09 | 14422.89 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.63 | 15-MAR-14:00 | 1197.33 | 02-MAR-05:00 |
April | 813.01 | 01-APR-18:10 | 969.33 | 01-APR-16:10 | 14422.89 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1163.20 | 16-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 969.33 | 01-MAY-09:09 | 14422.89 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 16.99 | 24-MAY-00:15 | 457.42 | 30-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 969.33 | 01-JUN-09:09 | 14422.89 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 40.02 | 27-JUN-12:55 | 706.49 | 13-JUN-03:20 |
July | 813.01 | 01-JUL-18:10 | 969.33 | 01-JUL-16:10 | 14422.89 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 101.70 | 21-JUL-03:00 | 531.60 | 06-JUL-02:00 |
August | 813.01 | 05-AUG-18:10 | 969.33 | 01-AUG-09:09 | 14422.89 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 42.47 | 13-AUG-13:00 | 310.72 | 27-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 969.33 | 01-SEP-09:09 | 14422.89 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 10.02 | 16-SEP-13:00 | 636.34 | 29-SEP-03:30 |
October | 813.01 | 07-OCT-18:10 | 969.33 | 02-OCT-09:09 | 14422.89 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 639.10 | 07-OCT-02:10 |
November | 813.01 | 04-NOV-18:10 | 969.33 | 01-NOV-09:09 | 14422.89 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1229.44 | 17-NOV-02:00 |
December | 813.01 | 02-DEC-19:10 | 969.33 | 01-DEC-10:09 | 14422.89 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1509.36 | 26-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 310.72 | ||||||
Maximum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 101.70 | 1861.94 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1325.87 | 06-JAN-03:50 | 4351.48 | 30-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.63 | 27-FEB-23:00 | 5962.98 | 08-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1451.98 | 08-MAR-07:13 | 6242.94 | 07-MAR-13:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.76 | 24-APR-05:40 | 7897.58 | 06-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 27-MAY-04:55 | 8203.48 | 26-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.50 | 04-JUN-05:15 | 8189.20 | 10-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.69 | 13-JUL-02:00 | 7809.32 | 03-JUL-12:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.79 | 12-AUG-03:00 | 7388.53 | 03-AUG-13:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1432.94 | 10-SEP-22:30 | 6392.26 | 03-SEP-12:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1281.96 | 02-OCT-06:15 | 5559.72 | 17-OCT-13:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.15 | 25-NOV-21:00 | 3942.55 | 24-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1280.53 | 16-DEC-08:00 | 3940.31 | 11-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.15 | 3940.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.69 | 8203.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 45846.08 | 24-JAN-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1563.89 |
February | 51605.40 | 07-FEB-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.60 |
March | 47056.63 | 07-MAR-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.60 |
April | 33929.40 | 16-APR-23:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.29 |
May | 46619.29 | 24-MAY-01:51 | 0.00 | 4087.54 | 5771.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.88 |
June | 40141.54 | 17-JUN-01:51 | 0.00 | 3576.59 | 5049.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.22 |
July | 42632.09 | 08-JUL-00:42 | 0.00 | 3065.65 | 2885.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 |
August | 41522.96 | 06-AUG-03:22 | 0.00 | 3065.65 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 |
September | 45533.29 | 08-SEP-01:51 | 0.00 | 3576.59 | 5049.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.61 |
October | 41181.65 | 23-OCT-03:11 | 0.00 | 4087.54 | 9618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.29 |
November | 32416.75 | 24-NOV-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.75 |
December | 53362.28 | 11-DEC-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32416.75 | 0.00 | 3065.65 | 2885.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | |
Maximum of Months | 53362.28 | 16808.50 | 5109.42 | 9618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 44548.99 | 10-JAN-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 135.63 |
February | 45466.28 | 07-FEB-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 316.89 |
March | 44166.94 | 07-MAR-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 |
April | 33204.48 | 09-APR-04:01 | 0.00 | 1615.53 | 67541.24 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 52.82 |
May | 47941.46 | 30-MAY-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 92.49 |
June | 52746.54 | 16-JUN-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 |
July | 49156.38 | 07-JUL-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 |
August | 51316.00 | 04-AUG-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 |
September | 52778.68 | 12-SEP-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 43.61 |
October | 52191.89 | 06-OCT-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 100.22 |
November | 33144.05 | 24-NOV-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 72.29 |
December | 47765.85 | 11-DEC-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 70.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 33144.05 | 0.00 | 1615.53 | 67541.24 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | |
Maximum of Months | 52778.68 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 316.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.50 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.44 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.95 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.76 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.57 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.80 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.26 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.33 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.44 | 31.22 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.725199E+11 | 39850.68 | 31-JAN-11:09 | 0.218110E+12 | 187244.62 | 31-JAN-04:49 |
February | 0.651723E+11 | 40073.38 | 06-FEB-11:09 | 0.205373E+12 | 189580.53 | 07-FEB-04:00 |
March | 0.718284E+11 | 48177.06 | 15-MAR-10:00 | 0.160791E+12 | 176599.40 | 06-MAR-04:30 |
April | 0.679150E+11 | 41934.95 | 08-APR-10:00 | 0.107819E+12 | 114814.81 | 17-APR-06:19 |
May | 0.723289E+11 | 47576.20 | 10-MAY-10:00 | 0.786153E+11 | 78871.47 | 01-MAY-06:19 |
June | 0.809869E+11 | 62327.34 | 27-JUN-11:00 | 0.692759E+11 | 49606.35 | 06-JUN-06:19 |
July | 0.949699E+11 | 62709.27 | 20-JUL-10:00 | 0.688981E+11 | 44039.64 | 03-JUL-18:49 |
August | 0.900807E+11 | 61951.55 | 10-AUG-11:00 | 0.687669E+11 | 43611.42 | 12-AUG-10:30 |
September | 0.776483E+11 | 57255.15 | 15-SEP-11:00 | 0.683296E+11 | 47561.27 | 06-SEP-06:00 |
October | 0.720935E+11 | 46492.00 | 11-OCT-17:40 | 0.913426E+11 | 97971.84 | 17-OCT-06:10 |
November | 0.694578E+11 | 41318.77 | 16-NOV-17:00 | 0.113951E+12 | 107934.62 | 24-NOV-07:30 |
December | 0.725304E+11 | 39962.26 | 11-DEC-11:09 | 0.202676E+12 | 189582.01 | 11-DEC-04:30 |
Annual Sum or Average | 0.907532E+12 | 0.145395E+13 | ||||
Minimum of Months | 0.651723E+11 | 39850.68 | 0.683296E+11 | 43611.42 | ||
Maximum of Months | 0.949699E+11 | 62709.27 | 0.218110E+12 | 189582.01 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.620814E+10 | 0.485967E+10 | 0.390952E+11 | 0.00 | 0.109985E+11 | 37879553.69 | 0.00 | 327209.83 | 0.00 | 0.00 | 0.00 | 0.639832E+10 | 0.00 |
February | 0.555826E+10 | 0.401133E+10 | 0.353119E+11 | 0.00 | 0.100233E+11 | 34213790.43 | 0.00 | 96842.40 | 0.00 | 0.00 | 0.00 | 0.579092E+10 | 0.00 |
March | 0.610687E+10 | 0.391938E+10 | 0.390954E+11 | 0.00 | 0.104385E+11 | 37879553.69 | 0.00 | 0.717172E+09 | 0.00 | 0.00 | 0.00 | 0.646463E+10 | 0.00 |
April | 0.575847E+10 | 0.326582E+10 | 0.378342E+11 | 0.00 | 0.967489E+10 | 36657632.61 | 0.00 | 0.150389E+09 | 0.00 | 0.00 | 0.00 | 0.620626E+10 | 0.00 |
May | 0.590806E+10 | 0.292965E+10 | 0.390953E+11 | 0.00 | 0.100037E+11 | 37879553.69 | 0.00 | 0.250071E+10 | 0.00 | 0.00 | 0.00 | 0.642092E+10 | 0.00 |
June | 0.571468E+10 | 0.263491E+10 | 0.378342E+11 | 0.00 | 0.985472E+10 | 36657632.61 | 0.00 | 0.132686E+11 | 0.00 | 0.00 | 0.00 | 0.623876E+10 | 0.00 |
July | 0.581717E+10 | 0.278968E+10 | 0.390952E+11 | 0.00 | 0.105534E+11 | 37879553.69 | 0.00 | 0.246638E+11 | 0.00 | 0.00 | 0.00 | 0.637294E+10 | 0.00 |
August | 0.597452E+10 | 0.316715E+10 | 0.390954E+11 | 0.00 | 0.103089E+11 | 37879553.69 | 0.00 | 0.194139E+11 | 0.00 | 0.00 | 0.00 | 0.645155E+10 | 0.00 |
September | 0.581414E+10 | 0.356591E+10 | 0.378342E+11 | 0.00 | 0.976457E+10 | 36657632.61 | 0.00 | 0.905798E+10 | 0.00 | 0.00 | 0.00 | 0.619764E+10 | 0.00 |
October | 0.607210E+10 | 0.422547E+10 | 0.390952E+11 | 0.00 | 0.100518E+11 | 37879553.69 | 0.00 | 0.941946E+09 | 0.00 | 0.00 | 0.00 | 0.638868E+10 | 0.00 |
November | 0.601398E+10 | 0.455822E+10 | 0.378341E+11 | 0.00 | 0.976639E+10 | 36657632.61 | 0.00 | 0.128753E+09 | 0.00 | 0.00 | 0.00 | 0.618866E+10 | 0.00 |
December | 0.623078E+10 | 0.498571E+10 | 0.390952E+11 | 0.00 | 0.108471E+11 | 37879553.69 | 0.00 | 1262695.90 | 0.00 | 0.00 | 0.00 | 0.639018E+10 | 0.00 |
Annual Sum or Average | 0.711772E+11 | 0.449129E+11 | 0.460316E+12 | 0.00 | 0.122286E+12 | 0.446001E+09 | 0.00 | 0.708449E+11 | 0.00 | 0.00 | 0.00 | 0.755094E+11 | 0.00 |
Minimum of Months | 0.555826E+10 | 0.263491E+10 | 0.353119E+11 | 0.00 | 0.967489E+10 | 34213790.43 | 0.00 | 96842.40 | 0.00 | 0.00 | 0.00 | 0.579092E+10 | 0.00 |
Maximum of Months | 0.623078E+10 | 0.498571E+10 | 0.390954E+11 | 0.00 | 0.109985E+11 | 37879553.69 | 0.00 | 0.246638E+11 | 0.00 | 0.00 | 0.00 | 0.646463E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.143045E+12 | 0.00 | 0.351649E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.137102E+12 | 0.00 | 0.322330E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.853798E+11 | 0.00 | 0.355119E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.363122E+11 | 0.00 | 0.328945E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.646792E+10 | 0.00 | 0.322477E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.107238E+10 | 0.00 | 0.295909E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 38895479.67 | 0.00 | 0.289595E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 81448414.36 | 0.00 | 0.287857E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.159298E+10 | 0.00 | 0.281240E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.211205E+11 | 0.00 | 0.303224E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.442702E+11 | 0.00 | 0.310679E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.128947E+12 | 0.00 | 0.338298E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.605430E+12 | 0.00 | 0.378732E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 38895479.67 | 0.00 | 0.281240E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.143045E+12 | 0.00 | 0.355119E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4035.02 | 02-JAN-16:30 | 3334.35 | 01-JAN-00:10 | 24680.63 | 01-JAN-11:09 | 0.00 | 5495.44 | 10-JAN-06:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 4035.02 | 01-FEB-17:10 | 3334.35 | 01-FEB-00:10 | 24680.63 | 01-FEB-11:09 | 0.00 | 5690.17 | 07-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 4035.02 | 01-MAR-17:49 | 3334.35 | 01-MAR-00:10 | 24680.63 | 01-MAR-11:09 | 0.00 | 5504.43 | 07-MAR-06:10 | 17.86 | 17-MAR-23:10 | 0.00 | 01-MAR-00:10 |
April | 4035.02 | 01-APR-18:30 | 3334.35 | 01-APR-05:10 | 24680.63 | 01-APR-10:09 | 0.00 | 5068.24 | 17-APR-05:00 | 17.86 | 11-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 4035.02 | 01-MAY-19:10 | 3334.35 | 01-MAY-05:10 | 24680.63 | 01-MAY-10:09 | 0.00 | 4724.73 | 01-MAY-05:10 | 17.86 | 18-MAY-11:39 | 0.00 | 01-MAY-00:10 |
June | 4035.02 | 01-JUN-19:40 | 3334.35 | 01-JUN-19:49 | 24680.63 | 01-JUN-10:09 | 0.00 | 5992.53 | 27-JUN-12:00 | 17.86 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 4035.02 | 01-JUL-19:40 | 3334.35 | 01-JUL-19:00 | 24680.63 | 01-JUL-10:09 | 0.00 | 5873.83 | 20-JUL-11:00 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 4035.02 | 01-AUG-19:30 | 3334.35 | 01-AUG-19:40 | 24680.63 | 01-AUG-10:09 | 0.00 | 5757.51 | 10-AUG-11:00 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 4035.02 | 01-SEP-18:40 | 3334.35 | 01-SEP-05:10 | 24680.63 | 01-SEP-10:09 | 0.00 | 5022.49 | 15-SEP-11:00 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 4035.02 | 02-OCT-17:30 | 3334.35 | 01-OCT-05:10 | 24680.63 | 01-OCT-10:09 | 0.00 | 4933.38 | 17-OCT-05:10 | 17.86 | 08-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 4035.02 | 01-NOV-16:00 | 3334.35 | 01-NOV-05:10 | 24680.63 | 01-NOV-10:09 | 0.00 | 5008.45 | 24-NOV-06:10 | 17.86 | 01-NOV-23:10 | 0.00 | 01-NOV-00:10 |
December | 4035.02 | 01-DEC-16:19 | 3334.35 | 01-DEC-00:10 | 24680.63 | 01-DEC-11:09 | 0.00 | 5749.69 | 11-DEC-06:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 4724.73 | 17.86 | 0.00 | ||||||
Maximum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 5992.53 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 196.98 | 17-JAN-04:10 | 0.00 | 0.00 | 0.00 | 4741.25 | 26-JAN-07:49 | 0.00 |
February | 161.40 | 17-FEB-04:49 | 0.00 | 0.00 | 0.00 | 4741.89 | 28-FEB-07:49 | 0.00 |
March | 11893.49 | 15-MAR-17:19 | 0.00 | 0.00 | 0.00 | 4742.28 | 21-MAR-18:40 | 0.00 |
April | 5608.69 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 4741.82 | 24-APR-06:49 | 0.00 |
May | 12478.13 | 10-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4741.88 | 08-MAY-06:49 | 0.00 |
June | 26217.06 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 4740.25 | 06-JUN-06:49 | 0.00 |
July | 25315.40 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4738.11 | 03-JUL-06:10 | 0.00 |
August | 24778.69 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4738.41 | 01-AUG-06:40 | 0.00 |
September | 20688.11 | 15-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4740.24 | 05-SEP-06:19 | 0.00 |
October | 9378.53 | 11-OCT-17:10 | 0.00 | 0.00 | 0.00 | 4740.70 | 30-OCT-06:49 | 0.00 |
November | 3537.95 | 16-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4741.41 | 14-NOV-19:00 | 0.00 |
December | 569.56 | 01-DEC-04:19 | 0.00 | 0.00 | 0.00 | 4741.58 | 11-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 161.40 | 0.00 | 0.00 | 0.00 | 4738.11 | 0.00 | ||
Maximum of Months | 26217.06 | 0.00 | 0.00 | 0.00 | 4742.28 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39850.68 | 31-JAN-11:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5248.58 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 40073.38 | 06-FEB-11:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5494.12 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 48177.06 | 15-MAR-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 4152.55 | 17.86 | 0.00 | 9552.27 | 0.00 |
April | 41934.95 | 08-APR-10:00 | 2850.91 | 24680.63 | 0.00 | 0.00 | 4152.55 | 17.86 | 0.00 | 3700.31 | 0.00 |
May | 47576.20 | 10-MAY-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 4152.55 | 17.86 | 0.00 | 8954.39 | 0.00 |
June | 62327.34 | 27-JUN-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 5789.01 | 17.86 | 0.00 | 24970.81 | 0.00 |
July | 62709.27 | 20-JUL-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5469.49 | 17.86 | 0.00 | 23006.66 | 0.00 |
August | 61951.55 | 10-AUG-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 5757.51 | 17.86 | 0.00 | 24778.69 | 0.00 |
September | 57255.15 | 15-SEP-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 5022.49 | 17.86 | 0.00 | 20688.11 | 0.00 |
October | 46492.00 | 11-OCT-17:40 | 4035.02 | 20661.14 | 3334.35 | 0.00 | 4152.55 | 17.86 | 0.00 | 8020.09 | 0.00 |
November | 41318.77 | 16-NOV-17:00 | 4035.02 | 22268.94 | 3334.35 | 0.00 | 4152.55 | 17.86 | 0.00 | 2328.33 | 0.00 |
December | 39962.26 | 11-DEC-11:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5296.10 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 39850.68 | 2850.91 | 20661.14 | 0.00 | 0.00 | 4152.55 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62709.27 | 4035.02 | 24680.63 | 3334.35 | 0.00 | 5789.01 | 17.86 | 0.00 | 24970.81 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 171080.45 | 04-JAN-04:30 | 0.00 | 33444.00 | 31-JAN-19:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 171080.45 | 05-FEB-04:19 | 0.00 | 33581.36 | 17-FEB-07:40 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 171080.45 | 06-MAR-04:30 | 0.00 | 33455.08 | 01-MAR-19:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 78866.46 | 17-APR-05:00 | 0.00 | 32169.93 | 03-APR-06:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 47726.30 | 01-MAY-05:10 | 0.00 | 30130.81 | 01-MAY-06:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 21101.71 | 14-JUN-04:49 | 0.00 | 27098.61 | 01-JUN-06:30 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 3017.55 | 03-JUL-04:49 | 0.00 | 24126.89 | 03-JUL-18:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 5532.70 | 31-AUG-04:00 | 0.00 | 22376.77 | 24-AUG-06:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 20957.59 | 30-SEP-05:00 | 0.00 | 24252.99 | 29-SEP-06:49 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 66478.39 | 17-OCT-05:10 | 0.00 | 27195.78 | 31-OCT-06:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 73185.31 | 24-NOV-06:10 | 0.00 | 30010.89 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 171080.45 | 10-DEC-04:30 | 0.00 | 32120.40 | 29-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 3017.55 | 0.00 | 22376.77 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 171080.45 | 0.00 | 33581.36 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
February | 6.17 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
March | 2.83 | 20.06 | 0.00 | 20.06 | 0.00 | 20.06 | 0.00 | 20.06 |
April | 0.33 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.00 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.66 | 0.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.61 | 0.00 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.58 | 0.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.50 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
Annual Sum or Average | 19.17 | 19.91 | 0.00 | 19.91 | 7.83 | 21.28 | 0.00 | 21.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 20.28 | 0.00 | 20.28 | 3.83 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.74 | 0.00 | 26.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.45 | 0.00 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.16 | 0.00 | 27.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.53 | 0.00 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 28.16 | 0.00 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 28.42 | 0.17 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.45 | 0.00 | 28.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 28.22 | 0.00 | 28.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.51 | 0.00 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.16 | 0.00 | 27.16 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.91 | 0.00 | 26.91 |
Annual Sum or Average | 0.00 | 0.00 | 189.00 | 27.99 | 0.17 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 28.45 | 0.17 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.74 | 396.67 | 20.68 | 396.67 | 20.66 |
February | 551.00 | 20.74 | 352.50 | 20.68 | 352.50 | 20.66 |
March | 584.00 | 20.84 | 198.50 | 20.80 | 177.33 | 20.70 |
April | 573.67 | 21.10 | 78.67 | 20.94 | 75.33 | 20.80 |
May | 431.17 | 21.74 | 109.00 | 22.05 | 27.33 | 22.02 |
June | 261.00 | 22.82 | 407.33 | 23.51 | 127.50 | 23.57 |
July | 281.67 | 23.73 | 566.00 | 23.89 | 248.67 | 23.91 |
August | 221.17 | 23.37 | 527.33 | 23.79 | 155.83 | 23.82 |
September | 278.67 | 22.35 | 362.00 | 23.25 | 85.33 | 23.32 |
October | 512.00 | 21.14 | 95.00 | 21.32 | 30.50 | 21.20 |
November | 577.67 | 20.94 | 63.50 | 20.77 | 62.17 | 20.63 |
December | 609.00 | 20.75 | 301.17 | 20.66 | 301.17 | 20.62 |
Annual Sum or Average | 5491.00 | 21.37 | 3457.67 | 21.80 | 2040.33 | 21.74 |
Minimum of Months | 221.17 | 20.74 | 63.50 | 20.66 | 27.33 | 20.62 |
Maximum of Months | 610.00 | 23.73 | 566.00 | 23.89 | 396.67 | 23.91 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.05 | 448.17 | 19.03 | 448.17 | 19.02 |
February | 551.00 | 19.05 | 382.67 | 19.03 | 382.67 | 19.02 |
March | 562.17 | 19.63 | 323.67 | 19.86 | 286.33 | 19.83 |
April | 459.33 | 19.99 | 214.83 | 20.74 | 108.00 | 20.65 |
May | 345.17 | 23.70 | 434.67 | 24.53 | 201.17 | 24.82 |
June | 475.67 | 25.66 | 550.00 | 25.67 | 446.67 | 25.76 |
July | 566.50 | 25.99 | 607.83 | 25.93 | 566.50 | 25.95 |
August | 530.67 | 25.99 | 608.50 | 25.88 | 530.67 | 25.91 |
September | 439.83 | 25.46 | 528.50 | 25.49 | 396.50 | 25.63 |
October | 411.17 | 21.48 | 284.83 | 22.59 | 130.33 | 22.88 |
November | 523.33 | 19.83 | 163.00 | 20.27 | 112.83 | 20.28 |
December | 605.00 | 19.04 | 334.50 | 19.04 | 331.00 | 19.03 |
Annual Sum or Average | 6079.83 | 21.90 | 4881.17 | 22.54 | 3940.83 | 22.69 |
Minimum of Months | 345.17 | 19.04 | 163.00 | 19.03 | 108.00 | 19.02 |
Maximum of Months | 610.00 | 25.99 | 608.50 | 25.93 | 566.50 | 25.95 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73817 | 21.66915 | -0.6203 | 13.96010 |
February | 551.00000 | 20.74197 | 21.84403 | -0.6215 | 14.01213 |
March | 612.00000 | 20.97960 | 30.97288 | -0.4425 | 11.13227 |
April | 590.00000 | 21.18165 | 36.76711 | -0.3219 | 8.95695 |
May | 611.00000 | 22.37880 | 42.68295 | -0.9835 | 28.78683 |
June | 592.00000 | 23.44660 | 52.10679 | -0.4816 | 12.66703 |
July | 609.00000 | 23.84829 | 60.49145 | -0.2526 | 7.21410 |
August | 612.00000 | 23.73000 | 55.75156 | -0.3215 | 8.47322 |
September | 590.00000 | 23.15984 | 52.62525 | -0.5645 | 15.05633 |
October | 610.00000 | 21.56852 | 42.42551 | -0.1356 | 7.79712 |
November | 591.00000 | 21.00256 | 34.74132 | -0.3710 | 9.24463 |
December | 609.00000 | 20.74750 | 25.49537 | -0.5741 | 12.81218 |
Annual Sum or Average | 7187.00000 | 21.96812 | 39.90194 | -0.4735 | 12.50956 |
Minimum of Months | 551.00000 | 20.73817 | 21.66915 | -0.9835 | 7.21410 |
Maximum of Months | 612.00000 | 23.84829 | 60.49145 | -0.1356 | 28.78683 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.04781 | 28.28963 | -0.6698 | 14.87411 |
February | 551.00000 | 19.04897 | 28.71098 | -0.6772 | 15.07682 |
March | 612.00000 | 19.96263 | 37.15777 | -0.3916 | 13.83954 |
April | 590.00000 | 20.93204 | 42.39418 | -0.1171 | 11.37925 |
May | 611.00000 | 23.98087 | 43.08257 | -0.1784 | 15.96524 |
June | 592.00000 | 25.37231 | 48.87634 | 0.39509 | 13.10273 |
July | 609.00000 | 25.86905 | 54.88789 | 0.64625 | 14.93567 |
August | 612.00000 | 25.75862 | 51.34899 | 0.58684 | 13.90983 |
September | 590.00000 | 25.07490 | 49.14935 | 0.31815 | 13.11336 |
October | 610.00000 | 22.18146 | 44.43680 | 0.24905 | 13.79116 |
November | 591.00000 | 20.32257 | 40.02180 | -0.2318 | 11.04284 |
December | 609.00000 | 19.07021 | 32.18135 | -0.6219 | 13.71457 |
Annual Sum or Average | 7187.00000 | 22.23775 | 41.78322 | -0.0541 | 13.73484 |
Minimum of Months | 551.00000 | 19.04781 | 28.28963 | -0.6772 | 11.04284 |
Maximum of Months | 612.00000 | 25.86905 | 54.88789 | 0.64625 | 15.96524 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.134589E+10 | 0.411450E+09 | 21.72 | 0.100693E+10 | 0.338961E+09 | 0.00 | 0.68 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 | 27210.17 | 14-MAR-13:00 | 21265.63 | 15-MAR-17:10 | 8772.37 | 14-MAR-11:43 | 7860.42 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.139832E+09 | 46935614.21 | 9.47 | 0.115425E+09 | 24407383.12 | 0.00 | 0.27 | 08-APR-13:00 | 0.00 | 01-APR-00:01 | 9509.15 | 08-APR-13:00 | 7705.67 | 08-APR-13:00 | 1803.48 | 08-APR-13:00 | 3102.05 | 08-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.376959E+10 | 0.119658E+10 | 118.41 | 0.299786E+10 | 0.771727E+09 | 0.00 | 1.00 | 24-MAY-00:21 | 0.00 | 01-MAY-00:01 | 85564.50 | 24-MAY-01:51 | 71272.43 | 24-MAY-00:21 | 32598.67 | 24-MAY-03:51 | 22925.17 | 24-MAY-00:21 | 0.00 | 01-MAY-00:01 |
June | 0.264128E+11 | 0.758268E+10 | 374.67 | 0.168590E+11 | 0.955382E+10 | 0.00 | 1.00 | 02-JUN-00:42 | 0.00 | 01-JUN-00:01 | 92890.76 | 18-JUN-00:21 | 57162.63 | 12-JUN-01:35 | 49564.61 | 18-JUN-00:21 | 23473.81 | 18-JUN-00:21 | 0.00 | 01-JUN-00:01 |
July | 0.527417E+11 | 0.145469E+11 | 535.44 | 0.309068E+11 | 0.218349E+11 | 0.00 | 1.00 | 02-JUL-00:42 | 0.00 | 01-JUL-00:01 | 94204.34 | 16-JUL-00:42 | 59296.71 | 08-JUL-01:22 | 52953.83 | 22-JUL-00:10 | 23577.01 | 16-JUL-00:42 | 0.00 | 01-JUL-00:01 |
August | 0.404573E+11 | 0.114544E+11 | 470.70 | 0.265512E+11 | 0.139061E+11 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 94470.06 | 14-AUG-00:12 | 60064.79 | 06-AUG-03:22 | 54525.59 | 14-AUG-00:12 | 23598.38 | 14-AUG-00:12 | 0.00 | 01-AUG-00:01 |
September | 0.167581E+11 | 0.494708E+10 | 301.68 | 0.104612E+11 | 0.629685E+10 | 0.00 | 1.00 | 08-SEP-00:42 | 0.00 | 01-SEP-00:01 | 92159.40 | 16-SEP-00:09 | 58011.50 | 17-SEP-02:62 | 54274.12 | 16-SEP-00:09 | 23417.76 | 16-SEP-00:09 | 0.00 | 01-SEP-00:01 |
October | 0.119858E+10 | 0.390350E+09 | 57.58 | 0.889320E+09 | 0.309258E+09 | 0.00 | 1.00 | 23-OCT-01:11 | 0.00 | 01-OCT-00:01 | 42733.18 | 23-OCT-01:11 | 28161.76 | 23-OCT-01:11 | 14929.91 | 23-OCT-03:11 | 11458.36 | 23-OCT-01:11 | 0.00 | 01-OCT-00:01 |
November | 44603300.68 | 15154747.39 | 5.67 | 32634952.82 | 11968347.86 | 0.00 | 0.18 | 16-NOV-13:00 | 0.00 | 01-NOV-00:01 | 6090.75 | 16-NOV-13:00 | 4517.97 | 16-NOV-13:00 | 1572.78 | 16-NOV-13:00 | 2032.20 | 16-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.142868E+12 | 0.405915E+11 | 1895.35 | 0.898204E+11 | 0.530480E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.527417E+11 | 0.145469E+11 | 535.44 | 0.309068E+11 | 0.218349E+11 | 0.00 | 1.00 | 0.00 | 94470.06 | 71272.43 | 54525.59 | 23598.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1079517.38 | 327209.83 | 0.31 | 902993.02 | 176524.36 | 0.00 | 0.21 | 17-JAN-04:10 | 0.00 | 01-JAN-00:01 | 3327.07 | 17-JAN-04:10 | 2881.37 | 17-JAN-04:10 | 445.69 | 17-JAN-04:10 | 984.91 | 17-JAN-04:10 | 0.00 | 01-JAN-00:01 |
February | 316242.12 | 96842.40 | 0.08 | 252724.49 | 63517.63 | 0.00 | 0.07 | 17-FEB-04:50 | 0.00 | 01-FEB-00:01 | 1054.14 | 17-FEB-04:50 | 842.41 | 17-FEB-04:50 | 211.73 | 17-FEB-04:50 | 322.81 | 17-FEB-04:50 | 0.00 | 01-FEB-00:01 |
March | 0.118657E+10 | 0.305721E+09 | 29.97 | 0.885185E+09 | 0.301383E+09 | 0.00 | 1.00 | 14-MAR-03:32 | 0.00 | 01-MAR-00:01 | 38609.26 | 16-MAR-01:22 | 27247.73 | 16-MAR-03:22 | 12625.16 | 16-MAR-01:22 | 9256.54 | 16-MAR-01:22 | 0.00 | 01-MAR-00:01 |
April | 0.360835E+09 | 0.103454E+09 | 35.53 | 0.281279E+09 | 79555665.79 | 0.00 | 1.00 | 08-APR-00:53 | 0.00 | 01-APR-00:01 | 38609.26 | 08-APR-03:32 | 25453.30 | 08-APR-03:32 | 13155.95 | 08-APR-03:32 | 9256.54 | 08-APR-03:32 | 0.00 | 01-APR-00:01 |
May | 0.480148E+10 | 0.130413E+10 | 211.13 | 0.363634E+10 | 0.116515E+10 | 0.00 | 1.00 | 02-MAY-03:32 | 0.00 | 01-MAY-00:01 | 38609.26 | 29-MAY-01:22 | 32075.81 | 24-MAY-00:07 | 20255.29 | 29-MAY-03:22 | 9256.54 | 14-MAY-03:22 | 0.00 | 01-MAY-00:01 |
June | 0.232641E+11 | 0.568591E+10 | 447.64 | 0.144320E+11 | 0.883205E+10 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:01 | 42408.10 | 27-JUN-11:00 | 27255.82 | 05-JUN-01:22 | 24032.05 | 08-JUN-00:42 | 9500.70 | 18-JUN-00:03 | 0.00 | 01-JUN-00:01 |
July | 0.431325E+11 | 0.101169E+11 | 584.37 | 0.243472E+11 | 0.187853E+11 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 42897.42 | 16-JUL-02:11 | 25715.00 | 21-JUL-10:57 | 27562.84 | 20-JUL-21:00 | 9590.42 | 20-JUL-10:55 | 0.00 | 01-JUL-00:01 |
August | 0.331169E+11 | 0.795953E+10 | 533.01 | 0.209842E+11 | 0.121328E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:01 | 42897.42 | 14-AUG-03:35 | 26742.13 | 20-AUG-00:42 | 26997.48 | 14-AUG-04:02 | 9548.06 | 14-AUG-00:03 | 0.00 | 01-AUG-00:01 |
September | 0.164119E+11 | 0.411090E+10 | 383.27 | 0.984601E+10 | 0.656586E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 41468.38 | 16-SEP-00:03 | 24742.94 | 17-SEP-01:42 | 25726.91 | 16-SEP-00:03 | 9447.51 | 16-SEP-00:03 | 0.00 | 01-SEP-00:01 |
October | 0.199854E+10 | 0.551596E+09 | 97.80 | 0.139130E+10 | 0.607242E+09 | 0.00 | 1.00 | 01-OCT-01:22 | 0.00 | 01-OCT-00:01 | 38609.26 | 01-OCT-03:22 | 28135.80 | 22-OCT-03:22 | 20418.46 | 26-OCT-02:52 | 9256.54 | 01-OCT-03:22 | 0.00 | 01-OCT-00:01 |
November | 0.398846E+09 | 0.113598E+09 | 33.03 | 0.276638E+09 | 0.122208E+09 | 0.00 | 1.00 | 05-NOV-01:22 | 0.00 | 01-NOV-00:01 | 38609.26 | 05-NOV-02:62 | 29533.38 | 27-NOV-03:02 | 14403.50 | 05-NOV-02:42 | 9256.54 | 05-NOV-02:62 | 0.00 | 01-NOV-00:01 |
December | 4182797.59 | 1262695.90 | 0.82 | 2731729.61 | 1451067.98 | 0.00 | 0.26 | 01-DEC-04:08 | 0.00 | 01-DEC-00:01 | 4127.35 | 01-DEC-04:08 | 2482.59 | 01-DEC-04:08 | 1644.76 | 01-DEC-04:08 | 1207.66 | 01-DEC-04:08 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.124677E+12 | 0.302534E+11 | 2356.98 | 0.760840E+11 | 0.485932E+11 | 0.00 | ||||||||||||||
Minimum of Months | 316242.12 | 96842.40 | 0.08 | 252724.49 | 63517.63 | 0.00 | 0.07 | 0.00 | 1054.14 | 842.41 | 211.73 | 322.81 | 0.00 | |||||||
Maximum of Months | 0.431325E+11 | 0.101169E+11 | 584.37 | 0.243472E+11 | 0.187853E+11 | 0.00 | 1.00 | 0.00 | 42897.42 | 32075.81 | 27562.84 | 9590.42 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.75 | 48.87 | 102.88 | 47.76 | 580.55 | 0.00 | 0.00 | 0.00 |
February | 224.04 | 67.87 | 156.18 | 87.14 | 547.84 | 0.00 | 0.00 | 0.00 |
March | 321.48 | 135.19 | 186.28 | 238.29 | 372.27 | 0.00 | 0.00 | 0.00 |
April | 423.17 | 186.92 | 236.25 | 393.56 | 257.05 | 0.00 | 0.00 | 0.00 |
May | 474.12 | 209.77 | 264.35 | 516.92 | 169.97 | 0.00 | 0.00 | 0.00 |
June | 529.07 | 233.60 | 295.47 | 642.69 | 113.32 | 0.00 | 0.00 | 0.00 |
July | 508.10 | 223.42 | 284.68 | 669.48 | 76.19 | 0.00 | 0.00 | 0.00 |
August | 458.93 | 192.23 | 266.69 | 588.55 | 103.03 | 0.00 | 0.00 | 0.00 |
September | 382.30 | 169.59 | 212.71 | 436.17 | 168.29 | 0.00 | 0.00 | 0.00 |
October | 259.28 | 107.11 | 152.17 | 222.29 | 266.91 | 0.00 | 0.00 | 0.00 |
November | 146.98 | 47.07 | 99.92 | 81.45 | 365.11 | 0.00 | 0.00 | 0.00 |
December | 118.41 | 24.53 | 93.88 | 22.97 | 573.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.62 | 137.51 | 196.12 | 330.27 | 298.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.41 | 24.53 | 93.88 | 22.97 | 76.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 529.07 | 233.60 | 295.47 | 669.48 | 580.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.73 | 288.93 | 205.80 | 373.89 | 735.46 | 0.00 | 0.00 | 0.00 |
February | 560.27 | 267.96 | 292.31 | 412.08 | 715.47 | 0.00 | 0.00 | 0.00 |
March | 688.44 | 386.78 | 301.66 | 657.85 | 500.20 | 0.00 | 0.00 | 0.00 |
April | 569.39 | 227.01 | 342.38 | 579.28 | 380.05 | 0.00 | 0.00 | 0.00 |
May | 502.10 | 148.02 | 354.09 | 558.38 | 251.70 | 0.00 | 0.00 | 0.00 |
June | 483.30 | 101.20 | 382.10 | 595.75 | 169.02 | 0.00 | 0.00 | 0.00 |
July | 491.24 | 116.37 | 374.87 | 680.55 | 113.33 | 0.00 | 0.00 | 0.00 |
August | 550.07 | 174.55 | 375.52 | 744.23 | 151.21 | 0.00 | 0.00 | 0.00 |
September | 643.87 | 312.48 | 331.40 | 798.59 | 242.48 | 0.00 | 0.00 | 0.00 |
October | 619.17 | 354.00 | 265.17 | 664.25 | 365.67 | 0.00 | 0.00 | 0.00 |
November | 444.13 | 251.29 | 192.84 | 411.80 | 482.38 | 0.00 | 0.00 | 0.00 |
December | 413.69 | 214.43 | 199.26 | 293.45 | 725.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 538.22 | 236.82 | 301.41 | 565.07 | 401.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 413.69 | 101.20 | 192.84 | 293.45 | 113.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 688.44 | 386.78 | 382.10 | 798.59 | 735.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.69 | 30.80 | 99.88 | 29.23 | 595.92 | 0.00 | 0.00 | 0.00 |
February | 212.22 | 54.97 | 157.25 | 75.11 | 559.53 | 0.00 | 0.00 | 0.00 |
March | 332.25 | 142.68 | 189.56 | 252.35 | 376.81 | 0.00 | 0.00 | 0.00 |
April | 405.04 | 165.93 | 239.11 | 376.32 | 265.32 | 0.00 | 0.00 | 0.00 |
May | 478.35 | 216.41 | 261.94 | 523.91 | 174.70 | 0.00 | 0.00 | 0.00 |
June | 576.43 | 270.86 | 305.56 | 710.91 | 118.05 | 0.00 | 0.00 | 0.00 |
July | 515.25 | 225.54 | 289.70 | 683.53 | 80.89 | 0.00 | 0.00 | 0.00 |
August | 465.78 | 197.44 | 268.34 | 602.00 | 107.78 | 0.00 | 0.00 | 0.00 |
September | 366.18 | 157.96 | 208.22 | 416.79 | 173.72 | 0.00 | 0.00 | 0.00 |
October | 238.45 | 84.46 | 153.98 | 199.70 | 273.57 | 0.00 | 0.00 | 0.00 |
November | 140.49 | 40.30 | 100.19 | 74.79 | 370.12 | 0.00 | 0.00 | 0.00 |
December | 121.56 | 26.19 | 95.37 | 26.94 | 576.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 332.43 | 134.85 | 197.58 | 332.37 | 304.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 121.56 | 26.19 | 95.37 | 26.94 | 80.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 576.43 | 270.86 | 305.56 | 710.91 | 595.92 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406448E+09 | 0.130903E+09 | 0.275545E+09 | 0.127914E+09 | 0.155495E+10 |
February | 0.542000E+09 | 0.164181E+09 | 0.377819E+09 | 0.210806E+09 | 0.132534E+10 |
March | 0.861042E+09 | 0.362098E+09 | 0.498945E+09 | 0.638246E+09 | 0.997097E+09 |
April | 0.109687E+10 | 0.484504E+09 | 0.612362E+09 | 0.102011E+10 | 0.666275E+09 |
May | 0.126989E+10 | 0.561840E+09 | 0.708048E+09 | 0.138451E+10 | 0.455239E+09 |
June | 0.137134E+10 | 0.605490E+09 | 0.765849E+09 | 0.166585E+10 | 0.293733E+09 |
July | 0.136090E+10 | 0.598414E+09 | 0.762490E+09 | 0.179313E+10 | 0.204057E+09 |
August | 0.122919E+10 | 0.514878E+09 | 0.714309E+09 | 0.157637E+10 | 0.275952E+09 |
September | 0.990916E+09 | 0.439574E+09 | 0.551342E+09 | 0.113056E+10 | 0.436205E+09 |
October | 0.694447E+09 | 0.286879E+09 | 0.407568E+09 | 0.595374E+09 | 0.714902E+09 |
November | 0.380985E+09 | 0.121994E+09 | 0.258990E+09 | 0.211116E+09 | 0.946363E+09 |
December | 0.317144E+09 | 65699498.71 | 0.251444E+09 | 61515299.72 | 0.153694E+10 |
Annual Sum or Average | 0.105212E+11 | 0.433645E+10 | 0.618471E+10 | 0.104155E+11 | 0.940704E+10 |
Minimum of Months | 0.317144E+09 | 65699498.71 | 0.251444E+09 | 61515299.72 | 0.204057E+09 |
Maximum of Months | 0.137134E+10 | 0.605490E+09 | 0.765849E+09 | 0.179313E+10 | 0.155495E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132508E+10 | 0.773875E+09 | 0.551209E+09 | 0.100142E+10 | 0.196986E+10 |
February | 0.135541E+10 | 0.648240E+09 | 0.707167E+09 | 0.996898E+09 | 0.173087E+10 |
March | 0.184393E+10 | 0.103595E+10 | 0.807976E+09 | 0.176200E+10 | 0.133974E+10 |
April | 0.147586E+10 | 0.588418E+09 | 0.887441E+09 | 0.150148E+10 | 0.985080E+09 |
May | 0.134483E+10 | 0.396449E+09 | 0.948384E+09 | 0.149557E+10 | 0.674152E+09 |
June | 0.125272E+10 | 0.262309E+09 | 0.990406E+09 | 0.154418E+10 | 0.438112E+09 |
July | 0.131575E+10 | 0.311699E+09 | 0.100405E+10 | 0.182280E+10 | 0.303543E+09 |
August | 0.147331E+10 | 0.467514E+09 | 0.100579E+10 | 0.199336E+10 | 0.405007E+09 |
September | 0.166892E+10 | 0.809941E+09 | 0.858977E+09 | 0.206994E+10 | 0.628510E+09 |
October | 0.165839E+10 | 0.948155E+09 | 0.710239E+09 | 0.177913E+10 | 0.979418E+09 |
November | 0.115118E+10 | 0.651343E+09 | 0.499841E+09 | 0.106739E+10 | 0.125032E+10 |
December | 0.110803E+10 | 0.574327E+09 | 0.533708E+09 | 0.785988E+09 | 0.194266E+10 |
Annual Sum or Average | 0.169734E+11 | 0.746822E+10 | 0.950519E+10 | 0.178201E+11 | 0.126473E+11 |
Minimum of Months | 0.110803E+10 | 0.262309E+09 | 0.499841E+09 | 0.785988E+09 | 0.303543E+09 |
Maximum of Months | 0.184393E+10 | 0.103595E+10 | 0.100579E+10 | 0.206994E+10 | 0.196986E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350031E+09 | 82506499.13 | 0.267525E+09 | 78293906.50 | 0.159612E+10 |
February | 0.513396E+09 | 0.132973E+09 | 0.380424E+09 | 0.181695E+09 | 0.135362E+10 |
March | 0.889885E+09 | 0.382164E+09 | 0.507721E+09 | 0.675904E+09 | 0.100926E+10 |
April | 0.104986E+10 | 0.430100E+09 | 0.619765E+09 | 0.975416E+09 | 0.687716E+09 |
May | 0.128121E+10 | 0.579639E+09 | 0.701572E+09 | 0.140325E+10 | 0.467906E+09 |
June | 0.149410E+10 | 0.702076E+09 | 0.792021E+09 | 0.184268E+10 | 0.305976E+09 |
July | 0.138004E+10 | 0.604096E+09 | 0.775944E+09 | 0.183077E+10 | 0.216650E+09 |
August | 0.124754E+10 | 0.528816E+09 | 0.718727E+09 | 0.161241E+10 | 0.288672E+09 |
September | 0.949134E+09 | 0.409433E+09 | 0.539701E+09 | 0.108032E+10 | 0.450293E+09 |
October | 0.638653E+09 | 0.226225E+09 | 0.412427E+09 | 0.534872E+09 | 0.732718E+09 |
November | 0.364150E+09 | 0.104450E+09 | 0.259700E+09 | 0.193856E+09 | 0.959339E+09 |
December | 0.325597E+09 | 70149471.10 | 0.255447E+09 | 72152553.14 | 0.154500E+10 |
Annual Sum or Average | 0.104836E+11 | 0.425263E+10 | 0.623097E+10 | 0.104816E+11 | 0.961327E+10 |
Minimum of Months | 0.325597E+09 | 70149471.10 | 0.255447E+09 | 72152553.14 | 0.216650E+09 |
Maximum of Months | 0.149410E+10 | 0.702076E+09 | 0.792021E+09 | 0.184268E+10 | 0.159612E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 375.82 | 1836.88 | 777.17 | 368.61 | 408.56 | 0.00 | 0.00 |
February | 506.01 | 1754.54 | 996.53 | 390.79 | 605.74 | 0.00 | 0.00 |
March | 1073.99 | 1174.77 | 1342.17 | 664.66 | 677.51 | 0.00 | 0.00 |
April | 1300.36 | 853.62 | 1397.60 | 579.87 | 817.73 | 0.00 | 0.00 |
May | 1568.66 | 565.81 | 1454.57 | 574.20 | 880.38 | 0.00 | 0.00 |
June | 1927.32 | 378.36 | 1588.79 | 605.66 | 983.13 | 0.00 | 0.00 |
July | 2021.43 | 258.26 | 1514.59 | 565.34 | 949.25 | 0.00 | 0.00 |
August | 1922.29 | 349.52 | 1474.78 | 564.22 | 910.55 | 0.00 | 0.00 |
September | 1632.15 | 565.09 | 1392.35 | 640.03 | 752.32 | 0.00 | 0.00 |
October | 1064.51 | 884.42 | 1116.90 | 545.57 | 571.32 | 0.00 | 0.00 |
November | 542.25 | 1191.82 | 731.60 | 338.65 | 392.95 | 0.00 | 0.00 |
December | 284.19 | 1816.80 | 653.66 | 265.15 | 388.52 | 0.00 | 0.00 |
Annual Sum or Average | 1188.68 | 965.13 | 1204.28 | 509.17 | 695.11 | 0.00 | 0.00 |
Minimum of Months | 284.19 | 258.26 | 653.66 | 265.15 | 388.52 | 0.00 | 0.00 |
Maximum of Months | 2021.43 | 1836.88 | 1588.79 | 664.66 | 983.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100660E+10 | 0.491990E+10 | 0.208156E+10 | 0.987284E+09 | 0.109428E+10 | 0.00 | 0.00 |
February | 0.122415E+10 | 0.424457E+10 | 0.241080E+10 | 0.945393E+09 | 0.146541E+10 | 0.00 | 0.00 |
March | 0.287657E+10 | 0.314651E+10 | 0.359486E+10 | 0.178021E+10 | 0.181464E+10 | 0.00 | 0.00 |
April | 0.337052E+10 | 0.221258E+10 | 0.362259E+10 | 0.150302E+10 | 0.211957E+10 | 0.00 | 0.00 |
May | 0.420150E+10 | 0.151548E+10 | 0.389593E+10 | 0.153793E+10 | 0.235800E+10 | 0.00 | 0.00 |
June | 0.499561E+10 | 0.980717E+09 | 0.411815E+10 | 0.156988E+10 | 0.254828E+10 | 0.00 | 0.00 |
July | 0.541418E+10 | 0.691735E+09 | 0.405669E+10 | 0.151421E+10 | 0.254248E+10 | 0.00 | 0.00 |
August | 0.514865E+10 | 0.936147E+09 | 0.395004E+10 | 0.151121E+10 | 0.243883E+10 | 0.00 | 0.00 |
September | 0.423053E+10 | 0.146472E+10 | 0.360897E+10 | 0.165895E+10 | 0.195002E+10 | 0.00 | 0.00 |
October | 0.285117E+10 | 0.236883E+10 | 0.299149E+10 | 0.146126E+10 | 0.153024E+10 | 0.00 | 0.00 |
November | 0.140552E+10 | 0.308919E+10 | 0.189632E+10 | 0.877787E+09 | 0.101853E+10 | 0.00 | 0.00 |
December | 0.761163E+09 | 0.486611E+10 | 0.175077E+10 | 0.710175E+09 | 0.104060E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.374862E+11 | 0.304365E+11 | 0.379782E+11 | 0.160573E+11 | 0.219209E+11 | 0.00 | 0.00 |
Minimum of Months | 0.761163E+09 | 0.691735E+09 | 0.175077E+10 | 0.710175E+09 | 0.101853E+10 | 0.00 | 0.00 |
Maximum of Months | 0.541418E+10 | 0.491990E+10 | 0.411815E+10 | 0.178021E+10 | 0.254828E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639833E+10 | -0.622515E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173178708.5 | 81.22 | 0.00 | 0.00 |
February | 0.579082E+10 | -0.563427E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156546390.1 | 81.22 | 0.00 | 0.00 |
March | 0.646458E+10 | -0.629384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -170740645.4 | 81.22 | 0.00 | 0.00 |
April | 0.620612E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162653564.5 | 81.22 | 0.00 | 0.00 |
May | 0.642069E+10 | -0.626017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160515976.3 | 81.22 | 0.00 | 0.00 |
June | 0.623862E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152039432.4 | 81.21 | 0.00 | 0.00 |
July | 0.637289E+10 | -0.621705E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155841558.3 | 81.22 | 0.00 | 0.00 |
August | 0.645131E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156096358.5 | 81.22 | 0.00 | 0.00 |
September | 0.619753E+10 | -0.604483E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152701808.2 | 81.21 | 0.00 | 0.00 |
October | 0.638864E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164825391.0 | 81.22 | 0.00 | 0.00 |
November | 0.618854E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -163936203.1 | 81.22 | 0.00 | 0.00 |
December | 0.639005E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172972043.9 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755081E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.194205E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579082E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173178708.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646458E+10 | -0.563427E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152039432.4 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.261714E+11 | -0.251598E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101159E+10 | 58.99 | 0.00 | 0.00 |
February | 0.240172E+11 | -0.231023E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -914864664.6 | 58.99 | 0.00 | 0.00 |
March | 0.264429E+11 | -0.254537E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -989232906.6 | 58.99 | 0.00 | 0.00 |
April | 0.244068E+11 | -0.234730E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -933785709.3 | 58.99 | 0.00 | 0.00 |
May | 0.238184E+11 | -0.229227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -895727026.8 | 58.99 | 0.00 | 0.00 |
June | 0.217450E+11 | -0.209084E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -836594541.0 | 58.99 | 0.00 | 0.00 |
July | 0.211714E+11 | -0.203185E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -852820392.9 | 58.99 | 0.00 | 0.00 |
August | 0.210300E+11 | -0.201749E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -855125491.7 | 58.99 | 0.00 | 0.00 |
September | 0.205695E+11 | -0.197269E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -842611840.8 | 58.99 | 0.00 | 0.00 |
October | 0.222641E+11 | -0.213290E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -935069107.7 | 58.99 | 0.00 | 0.00 |
November | 0.229377E+11 | -0.219922E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -945514494.5 | 58.99 | 0.00 | 0.00 |
December | 0.250972E+11 | -0.240875E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100969E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279671E+12 | -0.268649E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.110226E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.205695E+11 | -0.254537E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.101159E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.264429E+11 | -0.197269E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -836594541.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.74 | 0.73 | 01-JAN-08:50 | 3031.97 | 30.35 | 194.33 | 250.67 | 2797.75 | 29.73 | 189.83 | 250.83 |
February | 262.50 | 0.74 | 0.73 | 01-FEB-09:09 | 2078.83 | 25.78 | 143.50 | 258.33 | 1914.54 | 25.37 | 137.17 | 258.33 |
March | 339.33 | 0.74 | 0.73 | 01-MAR-07:19 | 1743.19 | 21.49 | 100.00 | 332.33 | 1612.23 | 21.17 | 99.17 | 332.67 |
April | 371.17 | 0.74 | 0.73 | 01-APR-06:49 | 1579.56 | 19.30 | 67.00 | 359.00 | 1711.90 | 18.97 | 66.83 | 357.67 |
May | 332.17 | 0.74 | 0.73 | 01-MAY-05:00 | 1788.33 | 19.13 | 55.00 | 399.50 | 1689.45 | 19.18 | 45.83 | 399.67 |
June | 430.67 | 0.74 | 0.73 | 01-JUN-05:49 | 1901.01 | 19.63 | 60.17 | 410.50 | 1490.34 | 19.00 | 59.00 | 409.67 |
July | 439.00 | 0.74 | 0.73 | 01-JUL-05:30 | 1738.29 | 19.27 | 66.33 | 415.50 | 1469.73 | 18.95 | 61.00 | 416.67 |
August | 406.00 | 0.74 | 0.73 | 01-AUG-05:00 | 1681.08 | 19.26 | 71.00 | 390.83 | 1820.42 | 19.31 | 84.17 | 388.67 |
September | 289.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2009.12 | 21.48 | 125.33 | 332.00 | 1891.46 | 20.52 | 93.00 | 333.50 |
October | 314.33 | 0.74 | 0.73 | 01-OCT-06:00 | 1576.31 | 22.66 | 113.17 | 304.50 | 1638.25 | 23.02 | 122.17 | 303.50 |
November | 258.33 | 0.74 | 0.73 | 01-NOV-07:40 | 2525.34 | 30.26 | 202.00 | 244.17 | 2596.07 | 31.18 | 216.00 | 243.83 |
December | 230.67 | 0.74 | 0.73 | 01-DEC-08:09 | 2497.68 | 29.67 | 183.50 | 239.00 | 2536.97 | 30.03 | 187.83 | 238.33 |
Annual Sum or Average | 3928.50 | 0.74 | 1949.98 | 22.41 | 1381.33 | 3936.33 | 1859.24 | 22.23 | 1362.00 | 3933.33 | ||
Minimum of Months | 230.67 | 0.74 | 0.73 | 1576.31 | 19.13 | 55.00 | 239.00 | 1469.73 | 18.95 | 45.83 | 238.33 | |
Maximum of Months | 439.00 | 0.74 | 0.73 | 3031.97 | 30.35 | 202.00 | 415.50 | 2797.75 | 31.18 | 216.00 | 416.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.766955E+11 | 136864.36 | 04-JAN-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.727953E+11 | 136864.36 | 05-FEB-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.478897E+11 | 136864.36 | 06-MAR-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232138E+11 | 99709.53 | 17-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.486416E+10 | 32903.87 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.853358E+09 | 26551.73 | 14-JUN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31116383.73 | 7664.29 | 03-JUL-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 65158731.49 | 7484.83 | 31-AUG-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127316E+10 | 29494.20 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144275E+11 | 86605.63 | 17-OCT-05:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285538E+11 | 69702.41 | 18-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704264E+11 | 136864.36 | 10-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31116383.73 | 7484.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.766955E+11 | 136864.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.377406E+11 | 54571.61 | 04-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368864E+11 | 54175.01 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204142E+11 | 56834.23 | 07-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.583591E+10 | 27952.39 | 17-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310170E+09 | 11432.04 | 07-MAY-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4543834.25 | 8146.64 | 14-JUN-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1220591.93 | 6485.22 | 30-SEP-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246896E+10 | 22211.17 | 17-OCT-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.686239E+10 | 26213.50 | 24-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327311E+11 | 54799.53 | 11-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377406E+11 | 56834.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.134589E+10 | 0.100693E+10 | 27210.17 | 14-MAR-13:00 | 18672.17 | 0.00 |
April | 0.00 | 0.00 | 0.139832E+09 | 0.115425E+09 | 9509.15 | 08-APR-13:00 | 7705.67 | 0.00 |
May | 0.00 | 0.00 | 0.376959E+10 | 0.299786E+10 | 85564.50 | 24-MAY-01:51 | 63762.75 | 0.00 |
June | 0.00 | 0.00 | 0.264128E+11 | 0.168590E+11 | 92890.76 | 18-JUN-00:21 | 43326.15 | 0.00 |
July | 0.00 | 0.00 | 0.527417E+11 | 0.309068E+11 | 94204.34 | 16-JUL-00:42 | 42776.95 | 0.00 |
August | 0.00 | 0.00 | 0.404573E+11 | 0.265512E+11 | 94470.06 | 14-AUG-00:12 | 39944.47 | 0.00 |
September | 0.00 | 0.00 | 0.167581E+11 | 0.104612E+11 | 92159.40 | 16-SEP-00:09 | 37885.28 | 0.00 |
October | 0.00 | 0.00 | 0.119858E+10 | 0.889320E+09 | 42733.18 | 23-OCT-01:11 | 28161.76 | 0.00 |
November | 0.00 | 0.00 | 44603300.68 | 32634952.82 | 6090.75 | 16-NOV-13:00 | 4517.97 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142868E+12 | 0.898204E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.527417E+11 | 0.309068E+11 | 94470.06 | 63762.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1079517.38 | 902993.02 | 3327.07 | 17-JAN-04:10 | 2881.37 | 0.00 |
February | 0.00 | 0.00 | 316242.12 | 252724.49 | 1054.14 | 17-FEB-04:50 | 842.41 | 0.00 |
March | 0.00 | 0.00 | 0.118657E+10 | 0.885185E+09 | 38609.26 | 16-MAR-01:22 | 25984.10 | 0.00 |
April | 0.00 | 0.00 | 0.360835E+09 | 0.281279E+09 | 38609.26 | 08-APR-03:32 | 25453.30 | 0.00 |
May | 0.00 | 0.00 | 0.480148E+10 | 0.363634E+10 | 38609.26 | 29-MAY-01:22 | 20429.39 | 0.00 |
June | 0.00 | 0.00 | 0.232641E+11 | 0.144320E+11 | 42408.10 | 27-JUN-11:00 | 23558.94 | 0.00 |
July | 0.00 | 0.00 | 0.431325E+11 | 0.243472E+11 | 42897.42 | 16-JUL-02:11 | 16549.18 | 0.00 |
August | 0.00 | 0.00 | 0.331169E+11 | 0.209842E+11 | 42897.42 | 14-AUG-03:35 | 16061.53 | 0.00 |
September | 0.00 | 0.00 | 0.164119E+11 | 0.984601E+10 | 41468.38 | 16-SEP-00:03 | 15741.47 | 0.00 |
October | 0.00 | 0.00 | 0.199854E+10 | 0.139130E+10 | 38609.26 | 01-OCT-03:22 | 19138.75 | 0.00 |
November | 0.00 | 0.00 | 0.398846E+09 | 0.276638E+09 | 38609.26 | 05-NOV-02:62 | 25011.56 | 0.00 |
December | 0.00 | 0.00 | 4182797.59 | 2731729.61 | 4127.35 | 01-DEC-04:08 | 2482.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124677E+12 | 0.760840E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 316242.12 | 252724.49 | 1054.14 | 842.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.431325E+11 | 0.243472E+11 | 42897.42 | 25984.10 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9852.02 | 18948.59 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10007.78 | 19023.57 | 10-FEB-19:55 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9961.31 | 18967.48 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9514.84 | 18398.30 | 03-APR-18:20 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9018.41 | 17590.89 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8527.44 | 16513.14 | 01-JUN-18:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8047.86 | 15572.95 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 7994.35 | 15078.02 | 01-AUG-18:17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8072.36 | 15519.25 | 29-SEP-18:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8424.63 | 16460.78 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8944.77 | 17478.97 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9452.13 | 18362.13 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8978.83 | ||||
Minimum of Months | 0.00 | 0.00 | 7994.35 | 15078.02 | ||
Maximum of Months | 0.00 | 0.00 | 10007.78 | 19023.57 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.443556E+10 | 0.55 | 1983.06 | 01-JAN-00:01 | 0.66 |
February | 0.399964E+10 | 0.55 | 1983.06 | 01-FEB-00:01 | 0.66 |
March | 0.455113E+10 | 0.56 | 1983.06 | 01-MAR-00:01 | 0.66 |
April | 0.453015E+10 | 0.57 | 1983.06 | 01-APR-03:35 | 0.65 |
May | 0.503345E+10 | 0.62 | 1983.06 | 01-MAY-01:15 | 0.65 |
June | 0.491029E+10 | 0.62 | 1983.06 | 01-JUN-00:05 | 0.65 |
July | 0.508085E+10 | 0.62 | 1983.06 | 01-JUL-00:04 | 0.65 |
August | 0.507906E+10 | 0.62 | 1983.06 | 01-AUG-00:03 | 0.65 |
September | 0.490982E+10 | 0.62 | 1983.06 | 01-SEP-00:07 | 0.65 |
October | 0.491176E+10 | 0.60 | 1983.06 | 01-OCT-00:07 | 0.65 |
November | 0.452250E+10 | 0.57 | 1983.06 | 01-NOV-00:55 | 0.65 |
December | 0.444851E+10 | 0.55 | 1983.06 | 01-DEC-00:01 | 0.65 |
Annual Sum or Average | 0.564127E+11 | 0.59 | |||
Minimum of Months | 0.399964E+10 | 0.55 | 1983.06 | 0.65 | |
Maximum of Months | 0.508085E+10 | 0.62 | 1983.06 | 0.66 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.463295E+10 | 0.58 | 3737.32 | 04-JAN-04:15 | 0.91 |
February | 0.424915E+10 | 0.58 | 3737.32 | 05-FEB-04:10 | 0.91 |
March | 0.414314E+10 | 0.53 | 3737.32 | 06-MAR-04:09 | 0.91 |
April | 0.361276E+10 | 0.50 | 2722.74 | 17-APR-03:01 | 0.90 |
May | 0.341698E+10 | 0.46 | 2034.03 | 01-MAY-04:01 | 0.66 |
June | 0.328490E+10 | 0.47 | 2387.25 | 27-JUN-13:00 | 0.71 |
July | 0.347148E+10 | 0.49 | 3582.30 | 21-JUL-00:05 | 0.87 |
August | 0.341865E+10 | 0.49 | 2847.92 | 11-AUG-00:05 | 0.78 |
September | 0.327204E+10 | 0.47 | 2053.89 | 17-SEP-00:05 | 0.66 |
October | 0.357387E+10 | 0.47 | 2913.88 | 17-OCT-05:58 | 0.80 |
November | 0.369895E+10 | 0.50 | 2636.94 | 18-NOV-05:05 | 0.76 |
December | 0.452447E+10 | 0.57 | 3737.32 | 10-DEC-04:10 | 0.91 |
Annual Sum or Average | 0.452993E+11 | 0.51 | |||
Minimum of Months | 0.327204E+10 | 0.46 | 2034.03 | 0.66 | |
Maximum of Months | 0.463295E+10 | 0.58 | 3737.32 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193001E+10 | 0.53 | 1287.91 | 04-JAN-05:03 | 0.80 |
February | 0.177451E+10 | 0.54 | 1283.45 | 21-FEB-05:03 | 0.80 |
March | 0.174425E+10 | 0.51 | 1313.34 | 07-MAR-05:03 | 0.81 |
April | 0.153198E+10 | 0.49 | 988.72 | 17-APR-04:04 | 0.69 |
May | 0.155329E+10 | 0.51 | 1686.39 | 17-MAY-04:01 | 0.90 |
June | 0.165954E+10 | 0.53 | 1686.39 | 09-JUN-04:01 | 0.90 |
July | 0.200107E+10 | 0.57 | 1686.39 | 01-JUL-04:01 | 0.90 |
August | 0.181116E+10 | 0.54 | 1686.39 | 01-AUG-03:21 | 0.90 |
September | 0.158271E+10 | 0.52 | 1686.39 | 01-SEP-03:21 | 0.90 |
October | 0.156621E+10 | 0.50 | 1686.39 | 01-OCT-04:01 | 0.90 |
November | 0.154494E+10 | 0.49 | 969.18 | 24-NOV-05:04 | 0.68 |
December | 0.187410E+10 | 0.52 | 1290.47 | 11-DEC-05:03 | 0.80 |
Annual Sum or Average | 0.205738E+11 | 0.52 | |||
Minimum of Months | 0.153198E+10 | 0.49 | 969.18 | 0.68 | |
Maximum of Months | 0.200107E+10 | 0.57 | 1686.39 | 0.90 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.83 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 46.56 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.68 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.91 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:05 | 5.36 | 5.36 | 51.39 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 51.79 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 52.64 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.66 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.69 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.93 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.17 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.85 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 46.56 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.69 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.83 | 59.93 | 9852.02 | 18948.59 | 31-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.56 | 59.38 | 10007.78 | 19023.57 | 10-FEB-19:55 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.68 | 58.22 | 9961.31 | 18967.48 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.06 | 49.06 | 9514.84 | 18398.30 | 03-APR-18:20 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.47 | 49.47 | 9018.41 | 17590.89 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.20 | 50.20 | 8527.44 | 16513.14 | 01-JUN-18:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.39 | 50.39 | 8047.86 | 15572.95 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.09 | 51.09 | 7994.35 | 15078.02 | 01-AUG-18:17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.05 | 51.05 | 8072.36 | 15519.25 | 29-SEP-18:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.36 | 48.36 | 8424.63 | 16460.78 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.65 | 49.65 | 8944.77 | 17478.97 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.85 | 59.86 | 9452.13 | 18362.13 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8978.83 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.56 | 48.36 | 7994.35 | 15078.02 | ||
Maximum of Months | 0.00 | 0.00 | 51.09 | 59.93 | 10007.78 | 19023.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.463295E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.424915E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.455459E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.365969E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.461355E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.108676E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.180183E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.148730E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.821912E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396422E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.371410E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.452447E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.858908E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.365969E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.180183E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.193034E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.177461E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204997E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.163543E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.285743E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.734544E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.121180E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.977069E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.569361E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.211781E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.165854E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187536E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.508272E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.163543E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.121180E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.463295E+10 | 0.00 | 0.766955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424915E+10 | 0.00 | 0.727953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414314E+10 | 0.134589E+10 | 0.478897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.361276E+10 | 0.139832E+09 | 0.232138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341698E+10 | 0.375911E+10 | 0.486416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.328490E+10 | 0.262837E+11 | 0.853358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.347148E+10 | 0.523956E+11 | 31116383.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.341865E+10 | 0.401816E+11 | 65158731.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327204E+10 | 0.166556E+11 | 0.127316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357387E+10 | 0.119858E+10 | 0.144275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.369895E+10 | 44603300.68 | 0.285538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452447E+10 | 0.00 | 0.704264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.452993E+11 | 0.142005E+12 | 0.341089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327204E+10 | 0.00 | 31116383.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463295E+10 | 0.523956E+11 | 0.766955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193001E+10 | 1079517.38 | 0.377406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177451E+10 | 316242.12 | 0.368864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174425E+10 | 0.118079E+10 | 0.204142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153198E+10 | 0.359522E+09 | 0.583591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155329E+10 | 0.477372E+10 | 0.310170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165954E+10 | 0.230589E+11 | 4543834.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.200107E+10 | 0.427265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181116E+10 | 0.328087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158271E+10 | 0.162960E+11 | 1220591.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156621E+10 | 0.198665E+10 | 0.246896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154494E+10 | 0.391232E+09 | 0.686239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187410E+10 | 4182797.59 | 0.327311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205738E+11 | 0.123588E+12 | 0.143255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153198E+10 | 316242.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200107E+10 | 0.427265E+11 | 0.377406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.463295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414314E+10 | 0.00 | 0.00 | 0.00 | 0.411450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.361276E+10 | 0.00 | 0.00 | 0.00 | 46935614.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341698E+10 | 0.00 | 0.00 | 0.00 | 0.119658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.328490E+10 | 0.00 | 0.00 | 0.00 | 0.758268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.347148E+10 | 0.00 | 0.00 | 0.00 | 0.145469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.341865E+10 | 0.00 | 0.00 | 0.00 | 0.114544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327204E+10 | 0.00 | 0.00 | 0.00 | 0.494708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357387E+10 | 0.00 | 0.00 | 0.00 | 0.390350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.369895E+10 | 0.00 | 0.00 | 0.00 | 15154747.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.452993E+11 | 0.00 | 0.00 | 0.00 | 0.405915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463295E+10 | 0.00 | 0.00 | 0.00 | 0.145469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193001E+10 | 0.00 | 0.00 | 0.00 | 327209.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177451E+10 | 0.00 | 0.00 | 0.00 | 96842.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174425E+10 | 0.00 | 0.00 | 0.00 | 0.305721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153198E+10 | 0.00 | 0.00 | 0.00 | 0.103454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155329E+10 | 0.00 | 0.00 | 0.00 | 0.130413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165954E+10 | 0.00 | 0.00 | 0.00 | 0.568591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.200107E+10 | 0.00 | 0.00 | 0.00 | 0.101169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181116E+10 | 0.00 | 0.00 | 0.00 | 0.795953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158271E+10 | 0.00 | 0.00 | 0.00 | 0.411090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156621E+10 | 0.00 | 0.00 | 0.00 | 0.551596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154494E+10 | 0.00 | 0.00 | 0.00 | 0.113598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187410E+10 | 0.00 | 0.00 | 0.00 | 1262695.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205738E+11 | 0.00 | 0.00 | 0.00 | 0.302534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153198E+10 | 0.00 | 0.00 | 0.00 | 96842.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200107E+10 | 0.00 | 0.00 | 0.00 | 0.101169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.704526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274310E+11 | 0.00 | 0.00 | 3.57 |
February | 0.617318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296808E+11 | 0.00 | 0.00 | 3.58 |
March | 0.613758E+11 | 6353406.99 | 0.00 | 4315404.76 | 0.00 | 0.126599E+11 | 0.138147E+10 | 0.00 | 3.57 |
April | 0.501891E+11 | 0.00 | 0.00 | 3536885.30 | 0.00 | 0.254480E+10 | 0.328832E+10 | 0.00 | 3.59 |
May | 0.259455E+11 | 56755818.81 | 0.00 | 31361045.54 | 1495112.42 | 29414907.90 | 0.147688E+11 | 0.00 | 3.74 |
June | 0.861285E+10 | 0.308885E+10 | 0.00 | 61904198.92 | 2783091.56 | 5712167.20 | 0.147073E+11 | 0.00 | 3.99 |
July | 0.231479E+10 | 0.980597E+10 | 0.00 | 49167602.28 | 6100884.90 | 0.00 | 0.713573E+10 | 0.00 | 4.09 |
August | 0.402270E+10 | 0.501487E+10 | 0.00 | 72453286.38 | 2550183.38 | 0.00 | 0.122401E+11 | 0.00 | 4.05 |
September | 0.126630E+11 | 0.867249E+09 | 0.00 | 59006305.97 | 0.00 | 4460124.54 | 0.176842E+11 | 0.00 | 3.98 |
October | 0.433476E+11 | 0.00 | 0.00 | 12150677.22 | 0.00 | 0.310980E+09 | 0.848101E+10 | 0.00 | 3.64 |
November | 0.567727E+11 | 0.00 | 0.00 | 1608852.97 | 0.00 | 0.160715E+10 | 0.228017E+10 | 0.00 | 3.58 |
December | 0.715634E+11 | 0.00 | 0.00 | 14336.10 | 0.00 | 0.219225E+11 | 52047759.14 | 0.00 | 3.58 |
Annual Sum or Average | 0.468992E+12 | 0.188401E+11 | 0.00 | 0.295519E+09 | 12929272.25 | 0.961968E+11 | 0.820192E+11 | 0.00 | 3.75 |
Minimum of Months | 0.231479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
Maximum of Months | 0.715634E+11 | 0.980597E+10 | 0.00 | 72453286.38 | 6100884.90 | 0.296808E+11 | 0.176842E+11 | 0.00 | 4.09 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.790941E+11 | 0.00 | 0.00 | 86578.01 | 0.204178E+09 | 53878671.81 | 0.246430E+09 | 0.00 | 8.03 |
February | 0.743292E+11 | 0.00 | 0.00 | 94559.32 | 79295138.14 | 39985727.45 | 0.253517E+09 | 0.00 | 8.08 |
March | 0.585157E+11 | 0.00 | 0.00 | 8483762.85 | 30452902.93 | 25085924.29 | 0.479999E+10 | 0.00 | 7.75 |
April | 0.389103E+11 | 0.00 | 0.00 | 12331718.17 | 0.00 | 0.00 | 0.108504E+11 | 0.00 | 7.60 |
May | 0.132890E+11 | 0.00 | 0.00 | 61582889.37 | 0.00 | 0.00 | 0.291149E+11 | 0.00 | 7.73 |
June | 0.382159E+10 | 0.205183E+10 | 0.00 | 89534772.12 | 0.00 | 0.00 | 0.215570E+11 | 0.00 | 8.16 |
July | 0.626533E+09 | 0.678345E+10 | 0.00 | 82965354.32 | 0.00 | 0.00 | 0.113050E+11 | 0.00 | 8.69 |
August | 0.717847E+09 | 0.288494E+10 | 0.00 | 0.104746E+09 | 0.00 | 0.00 | 0.184987E+11 | 0.00 | 8.37 |
September | 0.511886E+10 | 0.792676E+09 | 0.00 | 87391969.15 | 0.00 | 0.00 | 0.261077E+11 | 0.00 | 8.00 |
October | 0.254554E+11 | 0.00 | 0.00 | 29545538.01 | 0.00 | 0.00 | 0.223896E+11 | 0.00 | 7.65 |
November | 0.429796E+11 | 0.00 | 0.00 | 7866068.62 | 0.00 | 0.00 | 0.818425E+10 | 0.00 | 7.60 |
December | 0.753952E+11 | 0.00 | 0.00 | 336704.32 | 69564614.59 | 21732382.83 | 0.384817E+09 | 0.00 | 7.97 |
Annual Sum or Average | 0.418253E+12 | 0.125129E+11 | 0.00 | 0.484966E+09 | 0.383491E+09 | 0.140683E+09 | 0.153692E+12 | 0.00 | 7.97 |
Minimum of Months | 0.626533E+09 | 0.00 | 0.00 | 86578.01 | 0.00 | 0.00 | 0.246430E+09 | 0.00 | 7.60 |
Maximum of Months | 0.790941E+11 | 0.678345E+10 | 0.00 | 0.104746E+09 | 0.204178E+09 | 53878671.81 | 0.291149E+11 | 0.00 | 8.69 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.262378E+11 | 0.161480E+11 | 0.283872E+12 | 0.00 | 0.409539E+11 |
February | 0.511795E+11 | 0.158697E+11 | 0.263507E+12 | 0.00 | 0.393572E+11 |
March | 0.831076E+11 | 0.137058E+11 | 0.230817E+12 | 80042450.53 | 0.365786E+11 |
April | 0.104746E+12 | 0.116709E+11 | 0.189638E+12 | 0.148923E+09 | 0.266631E+11 |
May | 0.135530E+12 | 0.961645E+10 | 0.161668E+12 | 0.125257E+10 | 0.359037E+11 |
June | 0.153860E+12 | 0.672822E+10 | 0.895330E+11 | 0.182573E+10 | 0.880096E+11 |
July | 0.140323E+12 | 0.362938E+10 | 0.247961E+11 | 0.736409E+09 | 0.147670E+12 |
August | 0.116345E+12 | 0.470880E+10 | 0.624793E+11 | 0.136326E+10 | 0.119393E+12 |
September | 0.836310E+11 | 0.600234E+10 | 0.117015E+12 | 0.222190E+10 | 0.663041E+11 |
October | 0.516639E+11 | 0.911741E+10 | 0.185198E+12 | 0.685619E+09 | 0.265111E+11 |
November | 0.222784E+11 | 0.999497E+10 | 0.196853E+12 | 76679483.18 | 0.230325E+11 |
December | 0.231024E+11 | 0.154525E+11 | 0.272069E+12 | 0.00 | 0.377117E+11 |
Annual Sum or Average | 0.992004E+12 | 0.122644E+12 | 0.207745E+13 | 0.839113E+10 | 0.688089E+12 |
Minimum of Months | 0.222784E+11 | 0.362938E+10 | 0.247961E+11 | 0.00 | 0.230325E+11 |
Maximum of Months | 0.153860E+12 | 0.161480E+11 | 0.283872E+12 | 0.222190E+10 | 0.147670E+12 |