Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:27:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1878.01 | 3674.07 | 3674.07 |
Net Site Energy | 1878.01 | 3674.07 | 3674.07 |
Total Source Energy | 4595.96 | 8991.35 | 8991.35 |
Net Source Energy | 4595.96 | 8991.35 | 8991.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 492.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.37 | 204.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 39.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1229.09 | 648.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 492.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 17.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 394.51 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 152.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.37 | 204.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 492.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 17.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 152.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.37 | 204.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 39.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 108.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1410.49 | 400.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 885.10 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2404.54 | 1269.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 108.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1410.49 | 400.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 885.10 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2404.54 | 1269.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1229.088 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1229.088 | 100.00 |
Total On-Site and Utility Electric Sources | 1229.088 | 100.00 |
Total Electricity End Uses | 1229.088 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1932.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6784.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 5.1620 | 1.33 | 61.4214 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.3591 | 18.52 | 1000.6314 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 5.1620 | 1.33 | 61.4214 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.3591 | 18.52 | 1000.6314 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Conditioned Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 6.0339 | 1.78 | 317.5692 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-11:00 | 16-JAN-11:20 | - | - | - | - | - | - | - | - | - | - | 15-FEB-07:19 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47452.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21117.99 | 24831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9519.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3130.88 | 14107.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1248.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 84166.19 | 38938.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 47452.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 20527.19 | 24831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9519.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3130.88 | 14107.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 417.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1561.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1308.43 | 481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 482.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.68 | 221.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 124.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3892.52 | 703.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3054.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 943.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.95 | 433.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 243.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7615.18 | 1376.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3054.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 943.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.95 | 433.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 243.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7615.18 | 1376.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.45 |
KITCHEN DIRECT AIR | 1.54 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.45 | 4.45 | 4.45 | 4.45 | 4.45 | 4.45 | 1.00 | 1.00 | 4.45 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.45 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.54 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.45 | 7552.43 |
PSZ-AC_2:2_ADDAQ FAN | 1.54 | 1644.17 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.45 | 4.45 | 4.45 | 2.94 | 110603.21 | 115714.89 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.01 | 38155.88 | 55641.10 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.45 | 2.23 | 2.97 | 110603.21 | 55301.61 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.54 | 0.768269 | 1.02 | 38155.88 | 19077.94 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 115714.89 |
PSZ-AC_2:2 HEATING COIL | 55641.10 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 5.162 | 61.421 | 0.000 | 0.000 | 0.000 | 0.000 | 66.583 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.359 | 386.416 | 614.215 | 0.000 | 0.000 | 0.000 | 1008.991 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 1918.948 | 5.162 | 6.850 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1918.948 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1165.301 | 8.359 | 154.798 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1165.301 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 22833.282 | 61.421 | 81.506 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6621.652 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 53277.659 | 382.178 | 7077.360 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 15450.521 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 85624.808 | 614.215 | 11374.329 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 24831.194 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.342 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5109 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 6 | 0.21862767E-07 | 0.34448908E-09 | 0.50649605E-08 | -0.99069094E-13 |
34 | 5 | -0.15485004E-03 | 0.31008008E-05 | -0.80011323E-04 | 0.50225397E-08 |
35 | 4 | 0.24987207 | 0.15775750E-02 | 0.84530116E-01 | -0.27712185E-04 |
36 | 3 | -6.4266483 | 0.50820490E-01 | -2.0899201 | 0.24901095E-01 |
37 | 2 | 38.099035 | 0.18692275 | 14.237681 | -0.30248143 |
38 | 1 | -78.418483 | 0.86852168E-01 | -28.218840 | 1.0332909 |
39 | 0 | 46.824353 | 0.17981083E-02 | 16.314603 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.22 | 38 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.22 | 39 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.22 | 40 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.22 | 41 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.884 | 0.3002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 3.373E-002 | 9.073E-005 | 1.994E-004 | 0.107 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 2.124E-002 | 1.523E-004 | 1.958E-004 | 0.180 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.3338E-004 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.2351E-003 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.6257E-004 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 7.9781E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 7.9612E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 7.5263E-003 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.6407E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.0808E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.1060E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.0408E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.1954E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.1199E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.5180E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.4818E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.2319E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.2321E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.0737E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.0114E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.6031E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.0192E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 5.9793E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.5965E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.0808E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.6407E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 50858.20162 | 61029.84194 | 3.71166 | 4.45399 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 1877.04769 | 2252.45723 | 8.04942E-002 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 12.70000 | 9.15345E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20688.52569 | 24826.23083 | 1.28045 | 1.53654 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 41.92700 | 1.07803E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 12.70000 | 9.15345E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 90542.39 | 4.45399 | 4.45399 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 43959.14 | 1.33138 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 48345.61 | 1.53654 | 1.53654 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 40182.71 | 1.21700 | 1.21700 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.45399 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53654 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.45399 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.45399 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.45399 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.45399 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.45399 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.45399 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53654 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53654 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53654 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53654 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53654 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53654 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.45399 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.53654 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.45399 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.45399 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7552.42942 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.45399 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.45399 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.45399 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.93963 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.45399 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.22700 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.96933 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 110603.21000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 55301.60500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 110603.21000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 115714.88804 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 115714.88804 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53654 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53654 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1644.16744 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53654 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53654 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53654 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01411 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53654 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76827 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02436 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38155.88000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19077.94000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38155.88000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55641.09535 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 55641.09535 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 107437.5 | 11.22 | 11.17 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 37063.8 | 12.34 | 12.29 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_EAST_0.22 | N/A | 2.860 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.22 | N/A | 2.860 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_WEST_0.22 | N/A | 2.860 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.4375706049E-002 | 0.1932092947 | Pass | Pass | 3.6580577655E-002 | 8.1261202461E-002 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1821512046 | 0.5267585257 | Pass | Pass | 8.5795360240E-002 | 0.4817004125 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3222757452 | 0.2542506898 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 977.19 | -63.8 | -676.2 | 16.99 | 2653.58 | 2907.75 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.503_SHGC_EAST_0.22 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.860 | 0.221 | 0.243 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.22 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.860 | 0.221 | 0.243 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.503_SHGC_WEST_0.22 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.860 | 0.221 | 0.243 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.860 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.860 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 5.1620 | 371.75 | 1918.95 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.29 | 0.0000 | Y | 21.72 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.3591 | 139.41 | 1165.30 | LightsWired | LTG_SCH_KITCHEN | 79.77 | 168.00 | 76.30 | 0.0000 | Y | 16.69 |
Interior Lighting Total | 6.0339 | 511.15 | 3084.25 | 38.41 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 204.54 | AstronomicalClock | - | 48.85 | 48.85 | 1.88 | |
EXTERIOR_LIGHTS_B | 1305.94 | AstronomicalClock | - | 83.85 | 62.85 | 15.41 | |
Exterior Lighting Total | 1510.48 | 17.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 110603.21 | 77541.70 | 33061.51 | 0.70 | 3.57 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38155.88 | 26750.32 | 11405.56 | 0.70 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 107437.5 | 11.22 | 11.17 | ||||
PSZ-AC_2:2 COOLING COIL | 37063.8 | 12.34 | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 115714.89 | 0.81 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 55641.10 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.45 | 7552.43 | 1695.65 | 1.00 | 1.18 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1644.17 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.95 | 0.88 | 0.30 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 50858.20 | 61029.84 | 164.17 | 3.712 | 4.454 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 23.99 | 0.00871 | 42.70 | 0.01078 | 1.331 | 0.00 |
KITCHEN | 20688.53 | 24826.23 | 178.09 | 1.280 | 1.537 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.00878 | 41.93 | 0.01078 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 1877.05 | 2252.46 | 6.06 | 0.080 | 1.331 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00805 | 12.70 | 0.00915 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 24.99 | 0.00480 | 12.70 | 0.00915 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.45 | 4.45 | 1.33 | 1.33 | 4.4540 | 4.4540 | 4.4540 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.22 | 1.22 | 1.5365 | 1.5365 | 1.5365 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 110603.210 | 77541.698 | 4.453990 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 55301.61 | 43215.21 | 2.969327 | 29.61 | 18.96 | 0.00932584 | 11.42 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 44.8377 | 23.99 | 0.00870505 | 46.8578 | 50852.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 115714.888 | 115714.888 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | 115714.89 | 115714.89 | 4.453991 | 18.52 | 14.25 | 0.00838045 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 29.8918 | 21.00 | 0.00805087 | 52.0172 | 1870.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38155.880 | 26750.324 | 1.536540 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 19077.94 | 14918.96 | 1.024360 | 39.80 | 22.81 | 0.01042443 | 11.93 | 10.17 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 118.8061 | 25.99 | 0.00877340 | 41.9148 | 19924.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 55641.095 | 55641.095 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 55641.10 | 55641.10 | 1.536537 | 10.06 | 10.06 | 0.00824720 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 79.2042 | 24.99 | 0.00479562 | 24.4641 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 110603.210 | 77541.698 | 4.453990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1763 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.453991 | 5.36080138 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 55301.61 | 43215.21 | 1.0000 | 3.57386667 | 2.969327 | 29.61 | 18.96 | 0.00932584 | 53588.4 | 11.42 | 9.95 | 0.00700000 | 29132.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55301.61 | 42.80 | 0.01078182 | 23.86 | 1.33137743 | 44.8377 | 23.98 | 0.00870505 | 23.99 | 0.00870505 | 46.8578 | 50852.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 115714.888 | 115714.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.453991 | 5.36080138 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | Sensible | 115714.89 | 115714.89 | 1.0000 | 5.36080138 | 4.453991 | 18.52 | 14.25 | 0.00838045 | 39856.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 115714.89 | 12.70 | 0.00915345 | 12.70 | 1.33137743 | 29.8918 | 21.00 | 0.00805087 | 21.00 | 0.00805087 | 52.0172 | 1870.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38155.880 | 26750.324 | 1.536540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2185 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.536537 | 1.84936847 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 19077.94 | 14918.96 | 1.0000 | 1.23291456 | 1.024360 | 39.80 | 22.81 | 0.01042443 | 66835.8 | 11.93 | 10.17 | 0.00700000 | 29651.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19077.94 | 42.80 | 0.01078182 | 23.86 | 1.21700195 | 118.8061 | 25.95 | 0.00877340 | 25.99 | 0.00877340 | 41.9148 | 19924.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55641.095 | 55641.095 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.536537 | 1.84936847 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 55641.10 | 55641.10 | 1.0000 | 1.84936847 | 1.536537 | 10.06 | 10.06 | 0.00824720 | 30887.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55641.10 | 12.70 | 0.00915345 | 12.70 | 1.21700195 | 79.2042 | 0.00 | 0.00479562 | 24.99 | 0.00479562 | 24.4641 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6761.17 | 3125.33 | 2897.33 |
KITCHEN | 7171.17 | 6784.83 | 6784.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7171.17 | 7011.00 | 6784.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 105.00 | 0.00 | 50.17 |
KITCHEN | 0.00 | 2272.17 | 0.00 | 1932.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2302.50 | 0.00 | 1932.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.370 | 0.870 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.994 | 0.010 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.231 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.647 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35637567.10 | 0.00 | 35637567.10 | 6885138.11 | 42522705.21 | 41986318.57 | 1383.32 | 7376.68 | 0.00 | 364.32 |
KITCHEN | 31065308.34 | 0.00 | 31065308.34 | 41411.73 | 31106720.07 | 38379373.44 | 4999.06 | 3665.64 | 95.30 | 980.09 |
Total Facility | 66702875.44 | 0.00 | 66702875.44 | 6926549.85 | 73629425.28 | 80365692.01 | 5058.10 | 7379.89 | 95.30 | 1061.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3316 | 0.0000 | 1.3316 | 0.2653 | 1.5969 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1292 | 0.0000 | 1.1292 | 0.0011 | 1.1303 | 1.2170 | 3554.78 | 3632.22 | 0.00 |
Total Facility | 2.4608 | 0.0000 | 2.4608 | 0.2664 | 2.7272 | 2.5484 | 3554.78 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 51622555.43 | 0.00 | 51622555.43 | 41986318.57 | 1359.43 | 1.67 | 7398.90 | 364.32 |
PSZ-AC_2:2 | 45001436.25 | 0.00 | 45001436.25 | 38379373.44 | 1288.18 | 4.18 | 7467.64 | 980.09 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9289 | 0.0000 | 1.9289 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6357 | 0.0000 | 1.6357 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 175.53 | 0.00 | 7375.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 4972.62 | 3194.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.7343 | 1.5131 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
Electricity:Building | 458.48 | 2350.73 | 01-JAN-01:20 | 26459.53 | 02-JAN-11:10 |
Electricity:Zone:DINING | 140.07 | 534.11 | 01-JAN-01:20 | 7569.70 | 02-JAN-17:40 |
Electricity:SpaceType:GENERAL | 451.55 | 2214.45 | 01-JAN-01:20 | 24316.43 | 02-JAN-11:10 |
InteriorLights:Electricity | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 21.72 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 21.72 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 318.41 | 1816.62 | 01-JAN-01:20 | 19025.40 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 294.79 | 1650.33 | 01-JAN-01:10 | 16024.20 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 276.16 | 1059.53 | 01-JAN-01:10 | 15433.40 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 39.28 | 656.62 | 02-JAN-23:30 | 2780.19 | 09-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 108.16 | 837.89 | 13-FEB-01:10 | 5955.98 | 30-AUG-18:50 |
LowTempRefrigeration:Refrigeration:Electricity | 12.58 | 0.00 | 01-JAN-11:10 | 1039.82 | 18-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 19.77 | 551.63 | 01-JAN-06:00 | 637.09 | 05-JAN-04:20 |
ElectricityPurchased:Facility | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
ElectricityPurchased:Plant | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
Cogeneration:ElectricityPurchased | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
General:Cogeneration:ElectricityPurchased | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
ElectricityNet:Plant | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
Cogeneration:ElectricityNet | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
General:Cogeneration:ElectricityNet | 1229.09 | 3935.68 | 20-JAN-01:20 | 84166.19 | 16-AUG-12:00 |
Electricity:HVAC | 645.16 | 0.00 | 01-JAN-01:10 | 56973.87 | 10-AUG-13:00 |
Fans:Electricity | 152.22 | 0.00 | 01-JAN-01:10 | 10020.73 | 23-JUN-11:50 |
General:Fans:Electricity | 152.22 | 0.00 | 01-JAN-01:10 | 10020.73 | 23-JUN-11:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 492.94 | 0.00 | 01-JAN-00:10 | 47452.93 | 16-AUG-12:00 |
General:Cooling:Electricity | 492.94 | 0.00 | 01-JAN-00:10 | 47452.93 | 16-AUG-12:00 |
ExteriorLights:Electricity | 17.28 | 0.00 | 01-JAN-07:10 | 1510.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 17.28 | 0.00 | 01-JAN-07:10 | 1510.48 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.37 | 0.00 | 01-JAN-01:10 | 4738.75 | 10-JAN-07:20 |
Water Heater:WaterSystems:Electricity | 75.37 | 0.00 | 01-JAN-01:10 | 4738.75 | 10-JAN-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 648.92 | 2515.72 | 01-JAN-01:10 | 38938.38 | 16-JAN-11:20 |
NaturalGas:Building | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:HVAC | 0.06 | 0.00 | 01-JAN-00:10 | 2824.21 | 16-JAN-06:10 |
Heating:NaturalGas | 0.06 | 0.00 | 01-JAN-00:10 | 2824.21 | 16-JAN-06:10 |
General:Heating:NaturalGas | 0.06 | 0.00 | 01-JAN-00:10 | 2824.21 | 16-JAN-06:10 |
NaturalGas:Plant | 204.45 | 803.23 | 01-JAN-01:10 | 14668.37 | 09-JAN-07:20 |
WaterSystems:NaturalGas | 204.45 | 803.23 | 01-JAN-01:10 | 14668.37 | 09-JAN-07:20 |
Water Heater:WaterSystems:NaturalGas | 204.45 | 803.23 | 01-JAN-01:10 | 14668.37 | 09-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3041.31 | 3629.01 | 20-JAN-01:10 | 219269.13 | 09-SEP-19:00 |
EnergyTransfer:Building | 891.08 | 1814.51 | 20-JAN-01:10 | 58279.12 | 20-JUL-19:00 |
EnergyTransfer:Zone:KITCHEN | 430.03 | 1814.51 | 20-JAN-01:10 | 24304.91 | 09-OCT-10:50 |
Refrigeration:EnergyTransfer | 161.62 | 3511.49 | 02-JAN-23:30 | 7834.84 | 06-JAN-04:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.81 | 1755.75 | 02-JAN-23:30 | 3917.42 | 06-JAN-04:20 |
General:Refrigeration:EnergyTransfer | 80.81 | 1755.75 | 02-JAN-23:30 | 3917.42 | 06-JAN-04:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.81 | 1755.75 | 02-JAN-23:30 | 3917.42 | 06-JAN-04:20 |
EnergyTransfer:Plant | 241.20 | 1814.51 | 20-JAN-01:10 | 14625.85 | 09-JAN-20:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.55 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.26 | 1615.65 | 01-JAN-06:00 | 2238.70 | 05-JAN-04:20 |
EnergyTransfer:Zone:DINING | 461.05 | 0.00 | 01-JAN-01:10 | 40701.67 | 21-JUL-12:00 |
Heating:EnergyTransfer | 4.12 | 0.00 | 01-JAN-00:10 | 15852.88 | 13-JUL-23:10 |
Heating:EnergyTransfer:Zone:DINING | 4.12 | 0.00 | 01-JAN-00:10 | 15852.88 | 13-JUL-23:10 |
General:Heating:EnergyTransfer | 4.12 | 0.00 | 01-JAN-00:10 | 15852.88 | 13-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 4.12 | 0.00 | 01-JAN-00:10 | 15852.88 | 13-JUL-23:10 |
Cooling:EnergyTransfer | 806.15 | 0.00 | 01-JAN-01:10 | 55417.57 | 20-JUL-19:00 |
Cooling:EnergyTransfer:Zone:DINING | 456.93 | 0.00 | 01-JAN-01:10 | 40701.67 | 21-JUL-12:00 |
General:Cooling:EnergyTransfer | 806.15 | 0.00 | 01-JAN-01:10 | 55417.57 | 20-JUL-19:00 |
General:Cooling:EnergyTransfer:Zone:DINING | 456.93 | 0.00 | 01-JAN-01:10 | 40701.67 | 21-JUL-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 168.41 | 04-JUL-04:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 168.41 | 04-JUL-04:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 349.22 | 0.00 | 01-JAN-01:10 | 20865.22 | 20-JUL-19:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 349.22 | 0.00 | 01-JAN-01:10 | 20865.22 | 20-JUL-19:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 160.39 | 0.00 | 01-JAN-01:10 | 12007.06 | 09-JAN-20:00 |
PlantLoopHeatingDemand:Plant | 160.39 | 0.00 | 01-JAN-01:10 | 12007.06 | 09-JAN-20:00 |
WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12007.06 | 09-JAN-20:00 |
General:WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12007.06 | 09-JAN-20:00 |
EnergyTransfer:HVAC | 1909.04 | 0.00 | 01-JAN-00:10 | 161359.88 | 09-AUG-03:10 |
HeatingCoils:EnergyTransfer | 0.05 | 0.00 | 01-JAN-00:10 | 2287.61 | 16-JAN-06:10 |
CoolingCoils:EnergyTransfer | 1908.99 | 0.00 | 01-JAN-00:10 | 161359.88 | 09-AUG-03:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12007.06 | 09-JAN-20:00 |
WaterUse:WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12007.06 | 09-JAN-20:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 4.122 | -456.924 | 0.000 | 0.000 | 206.428 | 21.716 | 88.765 | 42.078 | 0.000 | 50.101 | 57.158 | 0.000 | -6.142 | 0.000 | -7.303 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -349.215 | 0.000 | 0.000 | 4.403 | 16.690 | 259.402 | 0.000 | 0.000 | 0.151 | 68.697 | 0.000 | 0.000 | 0.000 | -0.128 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.551 | 26.201 | 0.000 | 0.000 | 0.000 | -39.753 | -0.000 |
Total Facility | 0.000 | 0.000 | 4.122 | -806.139 | 0.000 | 0.000 | 210.831 | 38.406 | 348.168 | 42.078 | 0.000 | 63.803 | 152.056 | 0.000 | -6.142 | 0.000 | -47.184 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 10-MAY-03:01 | 0.00 | 0.00 | 0.00 | -78412.26 | 0.00 | 0.00 | 0.00 | 80.03 | 851.41 | 0.00 | 0.00 | 26.46 | 77470.79 | 0.00 | -16.42 | 0.00 | 0.00 | 0.00 |
KITCHEN | 01-JAN-04:01 | 0.00 | 0.00 | 0.00 | -51424.77 | 0.00 | 0.00 | 0.00 | 30.01 | 2903.90 | 0.00 | 0.00 | 0.00 | 48518.60 | 0.00 | -0.00 | 0.00 | -27.74 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-MAR-03:01 | 0.00 | 0.00 | 0.00 | -118885.40 | 0.00 | 0.00 | 0.00 | 110.04 | 3755.31 | 0.00 | 0.00 | 1133.93 | 114596.36 | 0.00 | -695.28 | 0.00 | -14.96 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-JUL-23:01 | 0.00 | 0.00 | 22649.01 | 0.00 | 0.00 | 0.00 | 973.97 | 273.28 | 510.84 | 1010.57 | 0.00 | 75.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25492.82 |
KITCHEN | 04-JUL-04:03 | 0.00 | 0.00 | 1010.45 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 6142.24 | 0.00 | 0.00 | 0.24 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7182.94 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-23:01 | -11566.03 | 11566.03 | 22649.01 | -11566.03 | 0.00 | 0.00 | 996.46 | 416.29 | 2489.51 | 1010.57 | 0.00 | 1026.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17021.99 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.4540 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.4540 | 0.2989 | 1.0000 | Not calculated | 1.3314 | 0.2989 | ||
PSZ-AC_2:2 | 1.5365 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5365 | 0.1188 | 1.0000 | Not calculated | 0.1826 | 0.1188 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.4540 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.4540 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2989 | ||
PSZ-AC_2:2 | 1.5365 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5365 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1188 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4540 | 4.4540 | 4.4540 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5365 | 1.5365 | 1.5365 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.4540 | 4.4540 | 4.4540 | 4.4540 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5365 | 1.5365 | 1.5365 | 1.5365 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4540 | 4.4540 | 4.4540 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5365 | 1.5365 | 1.5365 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.4540 | 4.4540 | 4.4540 | 4.4540 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5365 | 1.5365 | 1.5365 | 1.5365 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1932.67 |
Number of hours not met | 1932.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.06 | 2824.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 492.94 | 47452.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 38.41 | 2497.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 17.28 | 1510.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 394.51 | 22047.72 | 444.42 | 24831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 152.22 | 10020.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.37 | 4738.75 | 204.45 | 14668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.58 | 1039.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.77 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 452.42 | 1229.09 |
Natural Gas | 444.42 | 648.92 |
Additional | 0.00 | 0.00 |
Total | 896.84 | 1878.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 75.14 |
Space Heating | 0.00 |
Space Cooling | 964.37 |
Fans (All) | 297.80 |
Service Water Heating | 147.44 |
Receptacle Equipment | 808.26 |
Miscellaneous (All) | 2404.54 |
Subtotal | 2404.54 |
Natural Gas [MJ/m2] | |
Space Heating | 0.11 |
Service Water Heating | 399.98 |
Miscellaneous (All) | 1269.53 |
Subtotal | 1269.53 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.05 |
Space Heating | 0.00 |
Space Cooling | 26.25 |
Fans (All) | 8.11 |
Service Water Heating | 14.90 |
Receptacle Equipment | 45.66 |
Miscellaneous | 3.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 4159. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7964.17 | 512.33 | 280.33 | 3.17 | 0.00 |
KITCHEN | 5449.17 | 2183.33 | 1062.50 | 65.00 | 0.00 |
ATTIC | 3610.33 | 1039.67 | 1497.50 | 1442.33 | 1170.17 |
Min | 3610.33 | 512.33 | 280.33 | 3.17 | 0.00 |
Max | 7964.17 | 2183.33 | 1497.50 | 1442.33 | 1170.17 |
Average | 5674.56 | 1245.11 | 946.78 | 503.50 | 390.06 |
Sum | 17023.67 | 3735.33 | 2840.33 | 1510.50 | 1170.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 821543.33 | 1596.00 | 1040.67 | 42.00 | 0.00 |
KITCHEN | 13136.33 | 3464.17 | 2415.50 | 217.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 821543.33 | 3464.17 | 2415.50 | 217.00 | 0.00 |
Average | 278226.56 | 1686.72 | 1152.06 | 86.33 | 0.00 |
Sum | 834679.67 | 5060.17 | 3456.17 | 259.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 4585.33 | 3921.17 | 248.67 | 4.83 | 0.00 |
KITCHEN | 1140.33 | 6907.17 | 669.50 | 43.00 | 0.00 |
ATTIC | 2797.33 | 2317.00 | 1245.50 | 758.83 | 1641.33 |
Min | 1140.33 | 2317.00 | 248.67 | 4.83 | 0.00 |
Max | 4585.33 | 6907.17 | 1245.50 | 758.83 | 1641.33 |
Average | 2841.00 | 4381.78 | 721.22 | 268.89 | 547.11 |
Sum | 8523.00 | 13145.33 | 2163.67 | 806.67 | 1641.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 479497.67 | 343952.00 | 725.67 | 46.67 | 0.00 |
KITCHEN | 2268.17 | 15139.67 | 1674.00 | 151.17 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 479497.67 | 343952.00 | 1674.00 | 151.17 | 0.00 |
Average | 160588.61 | 119697.22 | 799.89 | 65.94 | 0.00 |
Sum | 481765.83 | 359091.67 | 2399.67 | 197.83 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267371E+11 | 61616.84 | 25-JAN-04:01 | 19.65 | 14.53 | 0.149468E+11 | 13978.32 | 28-JAN-19:49 | 22.08 | 16.97 |
February | 0.255127E+11 | 61720.94 | 10-FEB-04:01 | 20.25 | 13.47 | 0.136353E+11 | 13978.34 | 11-FEB-19:10 | 19.33 | 13.92 |
March | 0.307852E+11 | 76529.92 | 23-MAR-03:01 | 22.67 | 13.25 | 0.153101E+11 | 13979.51 | 25-MAR-18:10 | 27.38 | 20.47 |
April | 0.339681E+11 | 75676.97 | 29-APR-03:01 | 26.83 | 16.73 | 0.147586E+11 | 13979.64 | 15-APR-18:19 | 26.83 | 16.73 |
May | 0.426483E+11 | 78435.00 | 10-MAY-03:01 | 30.03 | 16.53 | 0.152929E+11 | 13978.66 | 13-MAY-18:49 | 31.58 | 23.75 |
June | 0.442661E+11 | 58371.44 | 02-JUN-03:01 | 28.93 | 19.10 | 0.148834E+11 | 13978.80 | 03-JUN-18:10 | 35.28 | 25.40 |
July | 0.490323E+11 | 67059.66 | 04-JUL-03:01 | 30.08 | 16.17 | 0.152852E+11 | 14148.12 | 01-JUL-18:19 | 30.08 | 16.17 |
August | 0.508994E+11 | 52114.45 | 06-AUG-03:01 | 35.97 | 22.54 | 0.155309E+11 | 14712.68 | 22-AUG-17:30 | 36.00 | 30.49 |
September | 0.455552E+11 | 52761.24 | 02-SEP-03:01 | 30.92 | 22.67 | 0.147990E+11 | 14094.91 | 09-SEP-18:30 | 34.80 | 28.08 |
October | 0.425983E+11 | 73311.71 | 21-OCT-03:01 | 22.85 | 15.66 | 0.151955E+11 | 13978.80 | 14-OCT-18:40 | 22.85 | 15.66 |
November | 0.354002E+11 | 71876.08 | 05-NOV-03:01 | 21.98 | 15.88 | 0.146800E+11 | 13980.41 | 18-NOV-19:00 | 25.00 | 16.38 |
December | 0.295221E+11 | 68882.98 | 01-DEC-04:01 | 17.42 | 12.43 | 0.150864E+11 | 13978.33 | 23-DEC-19:00 | 22.00 | 19.30 |
Annual Sum or Average | 0.456925E+12 | 0.179404E+12 | ||||||||
Minimum of Months | 0.255127E+11 | 52114.45 | 17.42 | 12.43 | 0.136353E+11 | 13978.32 | 19.33 | 13.92 | ||
Maximum of Months | 0.508994E+11 | 78435.00 | 35.97 | 22.67 | 0.155309E+11 | 14712.68 | 36.00 | 30.49 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273162E+11 | 51493.40 | 01-JAN-04:01 | 13.75 | 9.25 | 0.100359E+11 | 6568.44 | 25-JAN-11:09 | 21.33 | 15.53 |
February | 0.248474E+11 | 47739.98 | 13-FEB-04:01 | 13.50 | 11.03 | 0.906944E+10 | 6568.43 | 10-FEB-11:09 | 13.50 | 11.03 |
March | 0.279215E+11 | 47042.32 | 08-MAR-04:01 | 15.67 | 11.64 | 0.100484E+11 | 6568.44 | 06-MAR-11:09 | 15.67 | 11.64 |
April | 0.279677E+11 | 46081.27 | 26-APR-03:11 | 23.10 | 12.28 | 0.972303E+10 | 6581.81 | 28-APR-10:00 | 40.00 | 18.54 |
May | 0.308749E+11 | 38224.14 | 05-MAY-03:11 | 26.57 | 16.72 | 0.100569E+11 | 6627.97 | 30-MAY-10:00 | 36.00 | 26.94 |
June | 0.300233E+11 | 30114.93 | 02-JUN-03:01 | 28.93 | 19.10 | 0.977684E+10 | 6646.50 | 09-JUN-10:50 | 38.63 | 27.06 |
July | 0.304578E+11 | 32957.50 | 04-JUL-03:21 | 30.25 | 16.36 | 0.101491E+11 | 6683.69 | 25-JUL-10:00 | 36.00 | 29.02 |
August | 0.306990E+11 | 22982.81 | 06-AUG-03:01 | 35.97 | 22.54 | 0.101747E+11 | 6686.36 | 08-AUG-10:00 | 35.80 | 29.24 |
September | 0.300433E+11 | 27625.03 | 26-SEP-04:01 | 26.97 | 19.72 | 0.979558E+10 | 6687.39 | 11-SEP-10:00 | 26.97 | 19.72 |
October | 0.315138E+11 | 39600.27 | 21-OCT-03:11 | 22.70 | 15.54 | 0.100599E+11 | 6640.13 | 07-OCT-10:50 | 22.70 | 15.54 |
November | 0.292964E+11 | 39137.76 | 26-NOV-04:01 | 17.58 | 14.78 | 0.972127E+10 | 6607.32 | 01-NOV-10:00 | 17.58 | 14.78 |
December | 0.282593E+11 | 47399.88 | 31-DEC-04:01 | 14.83 | 11.18 | 0.100409E+11 | 6568.47 | 15-DEC-11:39 | 14.83 | 11.18 |
Annual Sum or Average | 0.349221E+12 | 0.118652E+12 | ||||||||
Minimum of Months | 0.248474E+11 | 22982.81 | 13.50 | 9.25 | 0.906944E+10 | 6568.43 | 13.50 | 11.03 | ||
Maximum of Months | 0.315138E+11 | 51493.40 | 35.97 | 22.54 | 0.101747E+11 | 6687.39 | 40.00 | 29.24 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17.20 | 14.59 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 22.85 | 18.46 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 | 23.56 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 | 23.24 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 | 27.02 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 | 25.04 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 | 21.17 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 | 15.63 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.00 | 0.00 | 15.70 | 12.84 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 328528.43 | 1284.05 | 06-FEB-00:03 | 23.92 |
March | 24965034.25 | 7445.90 | 27-MAR-23:02 | 27.83 |
April | 99496440.31 | 8834.80 | 28-APR-23:02 | 28.83 |
May | 0.517088E+09 | 15685.62 | 31-MAY-23:01 | 33.03 |
June | 0.704964E+09 | 18690.48 | 08-JUN-23:01 | 34.83 |
July | 0.884652E+09 | 22645.32 | 20-JUL-23:01 | 37.67 |
August | 0.844372E+09 | 21831.08 | 05-AUG-23:01 | 37.00 |
September | 0.646480E+09 | 16052.92 | 04-SEP-23:01 | 33.22 |
October | 0.340346E+09 | 11964.73 | 05-OCT-23:01 | 30.67 |
November | 57195839.73 | 10059.61 | 01-NOV-23:01 | 29.50 |
December | 240077.19 | 1147.51 | 12-DEC-00:03 | 23.90 |
Annual Sum or Average | 0.412013E+10 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.884652E+09 | 22645.32 | 37.67 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 101045.31 | 1010.45 | 04-JUL-04:03 | 30.42 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 101045.31 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 101045.31 | 1010.45 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.193469E+10 | 1639.63 | 02-JAN-17:40 | 0.100519E+11 | 6614.32 | 01-JAN-11:09 |
February | 0.172504E+10 | 1639.63 | 01-FEB-17:00 | 0.907918E+10 | 6614.32 | 01-FEB-11:09 |
March | 0.187255E+10 | 1639.63 | 01-MAR-18:19 | 0.100520E+11 | 6614.32 | 01-MAR-11:09 |
April | 0.173569E+10 | 1639.63 | 01-APR-18:40 | 0.972770E+10 | 6614.32 | 01-APR-10:09 |
May | 0.177179E+10 | 1639.63 | 01-MAY-18:49 | 0.100520E+11 | 6614.32 | 01-MAY-10:09 |
June | 0.170622E+10 | 1639.63 | 01-JUN-18:00 | 0.972773E+10 | 6614.32 | 01-JUN-10:09 |
July | 0.175478E+10 | 1639.63 | 01-JUL-19:10 | 0.100519E+11 | 6614.32 | 01-JUL-10:09 |
August | 0.180113E+10 | 1639.63 | 01-AUG-19:10 | 0.100520E+11 | 6614.32 | 01-AUG-10:09 |
September | 0.175415E+10 | 1639.63 | 01-SEP-18:40 | 0.972770E+10 | 6614.32 | 01-SEP-10:09 |
October | 0.185738E+10 | 1639.63 | 02-OCT-17:00 | 0.100519E+11 | 6614.32 | 01-OCT-10:09 |
November | 0.185557E+10 | 1639.63 | 01-NOV-17:40 | 0.972767E+10 | 6614.32 | 01-NOV-10:09 |
December | 0.194701E+10 | 1639.63 | 01-DEC-17:30 | 0.100519E+11 | 6614.32 | 01-DEC-11:09 |
Annual Sum or Average | 0.217160E+11 | 0.118354E+12 | ||||
Minimum of Months | 0.170622E+10 | 1639.63 | 0.907918E+10 | 6614.32 | ||
Maximum of Months | 0.194701E+10 | 1639.63 | 0.100520E+11 | 6614.32 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140982E+10 | 858.09 | 02-JAN-10:09 | 0.250369E+11 | 16024.20 | 01-JAN-11:09 |
February | 0.127710E+10 | 858.09 | 01-FEB-10:09 | 0.226140E+11 | 16024.20 | 01-FEB-11:09 |
March | 0.143409E+10 | 858.09 | 01-MAR-10:09 | 0.250371E+11 | 16024.20 | 01-MAR-11:09 |
April | 0.136995E+10 | 858.09 | 01-APR-16:10 | 0.242293E+11 | 16024.20 | 01-APR-10:09 |
May | 0.142196E+10 | 858.09 | 01-MAY-09:09 | 0.250370E+11 | 16024.20 | 01-MAY-10:09 |
June | 0.138598E+10 | 858.09 | 01-JUN-09:09 | 0.242294E+11 | 16024.20 | 01-JUN-10:09 |
July | 0.140610E+10 | 858.09 | 01-JUL-16:10 | 0.250369E+11 | 16024.20 | 01-JUL-10:09 |
August | 0.143409E+10 | 858.09 | 01-AUG-09:09 | 0.250371E+11 | 16024.20 | 01-AUG-10:09 |
September | 0.137029E+10 | 858.09 | 01-SEP-09:09 | 0.242293E+11 | 16024.20 | 01-SEP-10:09 |
October | 0.140965E+10 | 858.09 | 02-OCT-09:09 | 0.250369E+11 | 16024.20 | 01-OCT-10:09 |
November | 0.136509E+10 | 858.09 | 01-NOV-09:09 | 0.242292E+11 | 16024.20 | 01-NOV-10:09 |
December | 0.140627E+10 | 858.09 | 01-DEC-10:09 | 0.250369E+11 | 16024.20 | 01-DEC-11:09 |
Annual Sum or Average | 0.166904E+11 | 0.294790E+12 | ||||
Minimum of Months | 0.127710E+10 | 858.09 | 0.226140E+11 | 16024.20 | ||
Maximum of Months | 0.143409E+10 | 858.09 | 0.250371E+11 | 16024.20 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.193469E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60066428.74 | 0.252557E+10 |
February | 0.272721E+11 | 0.172504E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399066E+09 | 0.171542E+10 |
March | 0.305458E+11 | 0.187255E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124267E+10 | 0.975205E+09 |
April | 0.292871E+11 | 0.173569E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303077E+10 | 0.236865E+09 |
May | 0.303219E+11 | 0.177179E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643846E+10 | 16692965.80 |
June | 0.295292E+11 | 0.170622E+10 | 0.972773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716773E+10 | 1370565.20 |
July | 0.300798E+11 | 0.175478E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854374E+10 | 0.00 |
August | 0.305458E+11 | 0.180113E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878187E+10 | 0.00 |
September | 0.292871E+11 | 0.175415E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673659E+10 | 917158.14 |
October | 0.300980E+11 | 0.185738E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498538E+10 | 23746764.72 |
November | 0.290996E+11 | 0.185557E+10 | 0.972767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233190E+10 | 0.251346E+09 |
December | 0.300798E+11 | 0.194701E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382691E+09 | 0.155582E+10 |
Annual Sum or Average | 0.356244E+12 | 0.217160E+11 | 0.118354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501009E+11 | 0.730294E+10 |
Minimum of Months | 0.272721E+11 | 0.170622E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60066428.74 | 0.00 |
Maximum of Months | 0.305458E+11 | 0.194701E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878187E+10 | 0.252557E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.140982E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 35760.44 | 28395927.52 |
February | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 872978.72 | 28536267.01 |
March | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 3291952.91 | 18324966.28 |
April | 0.786997E+09 | 0.136995E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 8039712.33 | 10280726.20 |
May | 0.814802E+09 | 0.142196E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 20502668.02 | 2470914.87 |
June | 0.793501E+09 | 0.138598E+10 | 0.196898E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 24109561.66 | 1324986.92 |
July | 0.808298E+09 | 0.140610E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 28586903.80 | 148670.73 |
August | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 28325626.06 | 135195.85 |
September | 0.786997E+09 | 0.137029E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 19112924.03 | 1357926.39 |
October | 0.808786E+09 | 0.140965E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 12909616.99 | 4042255.34 |
November | 0.781956E+09 | 0.136509E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 4635623.07 | 10557409.63 |
December | 0.808298E+09 | 0.140627E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 350021.26 | 22610902.57 |
Annual Sum or Average | 0.957291E+10 | 0.166904E+11 | 0.239558E+12 | 0.133326E+12 | 0.00 | 0.00 | 0.00 | 0.150773E+09 | 0.128186E+09 |
Minimum of Months | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 35760.44 | 135195.85 |
Maximum of Months | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 28586903.80 | 28536267.01 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116955E+10 | 0.259096E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849827E+09 | 0.270086E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115783E+10 | 0.343460E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113888E+10 | 0.371829E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113725E+10 | 0.414926E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103046E+10 | 0.392573E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100549E+10 | 0.407019E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105769E+10 | 0.376612E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113976E+10 | 0.340044E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133414E+10 | 0.312451E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133408E+10 | 0.251033E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119634E+10 | 0.236128E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135513E+11 | 0.397526E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849827E+09 | 0.236128E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133414E+10 | 0.414926E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 1639.63 | 02-JAN-17:40 | 6614.32 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2154.55 | 23-JAN-14:00 | 3918.75 | 01-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 1639.63 | 01-FEB-17:00 | 6614.32 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4260.15 | 06-FEB-14:00 | 3937.93 | 20-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 1639.63 | 01-MAR-18:19 | 6614.32 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8098.73 | 27-MAR-11:10 | 3884.14 | 05-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 1639.63 | 01-APR-18:40 | 6614.32 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10313.95 | 28-APR-11:55 | 2828.45 | 01-APR-06:30 |
May | 30255.31 | 06-MAY-18:10 | 1639.63 | 01-MAY-18:49 | 6614.32 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10323.82 | 31-MAY-19:00 | 1201.53 | 01-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 1639.63 | 01-JUN-18:00 | 6614.32 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10762.14 | 12-JUN-12:00 | 1016.50 | 22-JUN-08:00 |
July | 30255.31 | 01-JUL-18:10 | 1639.63 | 01-JUL-19:10 | 6614.32 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12280.97 | 21-JUL-12:00 | 0.00 | 01-JUL-00:01 |
August | 30255.31 | 05-AUG-18:10 | 1639.63 | 01-AUG-19:10 | 6614.32 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12384.32 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 30255.31 | 02-SEP-18:10 | 1639.63 | 01-SEP-18:40 | 6614.32 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9778.92 | 26-SEP-12:00 | 260.69 | 25-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 1639.63 | 02-OCT-17:00 | 6614.32 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8125.78 | 04-OCT-12:00 | 1415.00 | 29-OCT-07:00 |
November | 30255.31 | 04-NOV-18:10 | 1639.63 | 01-NOV-17:40 | 6614.32 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5064.90 | 01-NOV-11:55 | 2662.76 | 26-NOV-07:10 |
December | 30255.31 | 02-DEC-19:10 | 1639.63 | 01-DEC-17:30 | 6614.32 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2540.27 | 01-DEC-13:00 | 3758.49 | 15-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2154.55 | 0.00 | |||||
Maximum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 12384.32 | 3937.93 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 858.09 | 02-JAN-10:09 | 12937.52 | 01-JAN-11:09 | 7449.36 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 3.13 | 23-JAN-13:50 | 153.39 | 18-JAN-04:10 |
February | 813.01 | 04-FEB-19:10 | 858.09 | 01-FEB-10:09 | 12937.52 | 01-FEB-11:09 | 7449.36 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 14.41 | 05-FEB-14:55 | 107.41 | 10-FEB-05:00 |
March | 813.01 | 04-MAR-19:10 | 858.09 | 01-MAR-10:09 | 12937.52 | 01-MAR-11:09 | 7449.36 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 39.86 | 02-MAR-04:13 | 77.13 | 15-MAR-02:00 |
April | 813.01 | 01-APR-18:10 | 858.09 | 01-APR-16:10 | 12937.52 | 01-APR-10:09 | 7449.36 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 37.84 | 28-APR-12:53 | 72.24 | 05-APR-00:50 |
May | 813.01 | 06-MAY-18:10 | 858.09 | 01-MAY-09:09 | 12937.52 | 01-MAY-10:09 | 7449.36 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 106.30 | 21-MAY-12:52 | 36.54 | 02-MAY-03:10 |
June | 813.01 | 03-JUN-18:10 | 858.09 | 01-JUN-09:09 | 12937.52 | 01-JUN-10:09 | 7449.36 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 64.67 | 09-JUN-03:10 | 32.30 | 06-JUN-03:30 |
July | 813.01 | 01-JUL-18:10 | 858.09 | 01-JUL-16:10 | 12937.52 | 01-JUL-10:09 | 7449.36 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 73.25 | 13-JUL-23:25 | 19.52 | 18-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 858.09 | 01-AUG-09:09 | 12937.52 | 01-AUG-10:09 | 7449.36 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 78.92 | 01-AUG-24:00 | 21.00 | 08-AUG-04:00 |
September | 813.01 | 02-SEP-18:10 | 858.09 | 01-SEP-09:09 | 12937.52 | 01-SEP-10:09 | 7449.36 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 41.65 | 13-SEP-03:51 | 25.24 | 28-SEP-03:20 |
October | 813.01 | 07-OCT-18:10 | 858.09 | 02-OCT-09:09 | 12937.52 | 01-OCT-10:09 | 7449.36 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 33.93 | 19-OCT-14:55 | 44.91 | 31-OCT-03:10 |
November | 813.01 | 04-NOV-18:10 | 858.09 | 01-NOV-09:09 | 12937.52 | 01-NOV-10:09 | 7449.36 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 20.55 | 01-NOV-23:01 | 57.02 | 21-NOV-04:10 |
December | 813.01 | 02-DEC-19:10 | 858.09 | 01-DEC-10:09 | 12937.52 | 01-DEC-11:09 | 7449.36 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 5.63 | 10-DEC-13:00 | 94.09 | 15-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 3.13 | 19.52 | ||||||
Maximum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 106.30 | 153.39 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.82 | 03-JAN-07:10 | 5412.51 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2454.84 | 15-FEB-07:42 | 5861.53 | 22-FEB-13:45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.83 | 27-MAR-06:43 | 6803.53 | 30-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.81 | 26-APR-06:00 | 6728.94 | 30-APR-12:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2514.13 | 04-MAY-07:51 | 6497.91 | 30-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.07 | 16-JUN-05:50 | 6269.59 | 08-JUN-12:25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1764.82 | 04-JUL-04:40 | 6414.07 | 04-JUL-12:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.76 | 05-AUG-01:52 | 6366.87 | 30-AUG-11:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2481.64 | 30-SEP-07:41 | 5845.12 | 17-SEP-13:43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2449.20 | 29-OCT-04:55 | 5665.24 | 04-OCT-12:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.63 | 05-NOV-07:23 | 4965.07 | 07-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.40 | 19-DEC-05:00 | 5322.90 | 25-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.76 | 4965.07 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2514.13 | 6803.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 61616.84 | 25-JAN-04:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 |
February | 61720.94 | 10-FEB-04:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.61 |
March | 76529.92 | 23-MAR-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
April | 75676.97 | 29-APR-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 | 0.00 |
May | 78435.00 | 10-MAY-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 | 0.00 |
June | 58371.44 | 02-JUN-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
July | 67059.66 | 04-JUL-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
August | 52114.45 | 06-AUG-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 | 0.00 |
September | 52761.24 | 02-SEP-03:01 | 0.00 | 720.26 | 10216.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 | 0.00 |
October | 73311.71 | 21-OCT-03:01 | 0.00 | 640.23 | 9081.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 |
November | 71876.08 | 05-NOV-03:01 | 0.00 | 640.23 | 9081.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 |
December | 68882.98 | 01-DEC-04:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 52114.45 | 0.00 | 640.23 | 9081.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78435.00 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 | 58.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51493.40 | 01-JAN-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 |
February | 47739.98 | 13-FEB-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 76.27 |
March | 47042.32 | 08-MAR-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 |
April | 46081.27 | 26-APR-03:11 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
May | 38224.14 | 05-MAY-03:11 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
June | 30114.93 | 02-JUN-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
July | 32957.50 | 04-JUL-03:21 | 0.00 | 210.08 | 18969.01 | 8990.60 | 0.00 | 0.00 | 0.00 | 1.01 | 0.00 |
August | 22982.81 | 06-AUG-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 17.63 | 0.00 |
September | 27625.03 | 26-SEP-04:01 | 316.17 | 210.08 | 39898.52 | 21577.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 39600.27 | 21-OCT-03:11 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 |
November | 39137.76 | 26-NOV-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 |
December | 47399.88 | 31-DEC-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22982.81 | 0.00 | 210.08 | 18969.01 | 8990.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51493.40 | 316.17 | 300.11 | 39898.52 | 21577.45 | 0.00 | 0.00 | 0.00 | 17.63 | 76.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.89 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.91 | 0.00 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.99 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.69 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.88 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.86 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1060.29 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.48 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.09 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.35 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.86 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.91 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.728737E+11 | 49607.40 | 24-JAN-11:00 | 0.583180E+11 | 38938.38 | 16-JAN-11:20 |
February | 0.692877E+11 | 53380.43 | 07-FEB-12:00 | 0.522010E+11 | 38905.84 | 04-FEB-11:20 |
March | 0.816439E+11 | 60509.69 | 27-MAR-10:00 | 0.567481E+11 | 38763.06 | 04-MAR-11:09 |
April | 0.889718E+11 | 69243.51 | 28-APR-11:00 | 0.532293E+11 | 38562.62 | 01-APR-10:20 |
May | 0.109412E+12 | 77874.37 | 31-MAY-11:00 | 0.534479E+11 | 38282.49 | 06-MAY-10:39 |
June | 0.121206E+12 | 81106.28 | 09-JUN-11:00 | 0.506578E+11 | 38107.81 | 03-JUN-10:20 |
July | 0.138588E+12 | 81047.64 | 19-JUL-11:39 | 0.518254E+11 | 38022.96 | 30-JUL-10:09 |
August | 0.142831E+12 | 84166.19 | 16-AUG-11:00 | 0.524654E+11 | 38117.05 | 26-AUG-10:09 |
September | 0.125256E+12 | 80702.70 | 07-SEP-11:00 | 0.519145E+11 | 38349.85 | 30-SEP-10:00 |
October | 0.109990E+12 | 75870.32 | 07-OCT-18:00 | 0.552362E+11 | 38588.38 | 29-OCT-10:00 |
November | 0.899161E+11 | 68644.84 | 01-NOV-11:00 | 0.549825E+11 | 38785.07 | 26-NOV-11:39 |
December | 0.791122E+11 | 54239.46 | 05-DEC-12:00 | 0.578982E+11 | 38927.65 | 30-DEC-11:30 |
Annual Sum or Average | 0.122909E+13 | 0.648924E+12 | ||||
Minimum of Months | 0.692877E+11 | 49607.40 | 0.506578E+11 | 38022.96 | ||
Maximum of Months | 0.142831E+12 | 84166.19 | 0.583180E+11 | 38938.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.334451E+10 | 0.170076E+10 | 0.350888E+11 | 0.00 | 0.102391E+11 | 37879553.69 | 0.00 | 0.128259E+11 | 0.00 | 0.00 | 0.00 | 0.638088E+10 | 0.00 |
February | 0.300214E+10 | 0.145595E+10 | 0.316932E+11 | 0.00 | 0.932691E+10 | 34213790.43 | 0.00 | 0.150449E+11 | 0.00 | 0.00 | 0.00 | 0.577444E+10 | 0.00 |
March | 0.330664E+10 | 0.149504E+10 | 0.350891E+11 | 0.00 | 0.104873E+11 | 37879553.69 | 0.00 | 0.214979E+11 | 0.00 | 0.00 | 0.00 | 0.644863E+10 | 0.00 |
April | 0.310564E+10 | 0.132250E+10 | 0.339570E+11 | 0.00 | 0.106207E+11 | 36657632.61 | 0.00 | 0.305496E+11 | 0.00 | 0.00 | 0.00 | 0.619287E+10 | 0.00 |
May | 0.319375E+10 | 0.126665E+10 | 0.350889E+11 | 0.00 | 0.125906E+11 | 37879553.69 | 0.00 | 0.475063E+11 | 0.00 | 0.00 | 0.00 | 0.641414E+10 | 0.00 |
June | 0.309220E+10 | 0.117931E+10 | 0.339571E+11 | 0.00 | 0.145246E+11 | 36657632.61 | 0.00 | 0.589146E+11 | 0.00 | 0.00 | 0.00 | 0.623314E+10 | 0.00 |
July | 0.316088E+10 | 0.123584E+10 | 0.350888E+11 | 0.00 | 0.171845E+11 | 37879553.69 | 0.00 | 0.720999E+11 | 0.00 | 0.00 | 0.00 | 0.636544E+10 | 0.00 |
August | 0.323522E+10 | 0.132194E+10 | 0.350891E+11 | 0.00 | 0.179017E+11 | 37879553.69 | 0.00 | 0.753681E+11 | 0.00 | 0.00 | 0.00 | 0.644248E+10 | 0.00 |
September | 0.312444E+10 | 0.139229E+10 | 0.339570E+11 | 0.00 | 0.153593E+11 | 36657632.61 | 0.00 | 0.619081E+11 | 0.00 | 0.00 | 0.00 | 0.619032E+10 | 0.00 |
October | 0.326703E+10 | 0.156210E+10 | 0.350888E+11 | 0.00 | 0.128290E+11 | 37879553.69 | 0.00 | 0.474724E+11 | 0.00 | 0.00 | 0.00 | 0.637725E+10 | 0.00 |
November | 0.322066E+10 | 0.161795E+10 | 0.339569E+11 | 0.00 | 0.107314E+11 | 36657632.61 | 0.00 | 0.309432E+11 | 0.00 | 0.00 | 0.00 | 0.617395E+10 | 0.00 |
December | 0.335328E+10 | 0.173248E+10 | 0.350888E+11 | 0.00 | 0.104270E+11 | 37879553.69 | 0.00 | 0.188109E+11 | 0.00 | 0.00 | 0.00 | 0.637200E+10 | 0.00 |
Annual Sum or Average | 0.384064E+11 | 0.172828E+11 | 0.413144E+12 | 0.00 | 0.152222E+12 | 0.446001E+09 | 0.00 | 0.492942E+12 | 0.00 | 0.00 | 0.00 | 0.753655E+11 | 0.00 |
Minimum of Months | 0.300214E+10 | 0.117931E+10 | 0.316932E+11 | 0.00 | 0.932691E+10 | 34213790.43 | 0.00 | 0.128259E+11 | 0.00 | 0.00 | 0.00 | 0.577444E+10 | 0.00 |
Maximum of Months | 0.335328E+10 | 0.173248E+10 | 0.350891E+11 | 0.00 | 0.179017E+11 | 37879553.69 | 0.00 | 0.753681E+11 | 0.00 | 0.00 | 0.00 | 0.644863E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.377451E+11 | 0.00 | 56193751.45 | 0.00 | 0.205167E+11 | 0.00 | 0.00 |
February | 0.340924E+11 | 0.00 | 233225.49 | 0.00 | 0.181084E+11 | 0.00 | 0.00 |
March | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.190029E+11 | 0.00 | 0.00 |
April | 0.365275E+11 | 0.00 | 0.00 | 0.00 | 0.167018E+11 | 0.00 | 0.00 |
May | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.157028E+11 | 0.00 | 0.00 |
June | 0.365275E+11 | 0.00 | 0.00 | 0.00 | 0.141303E+11 | 0.00 | 0.00 |
July | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.140803E+11 | 0.00 | 0.00 |
August | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.147202E+11 | 0.00 | 0.00 |
September | 0.365275E+11 | 0.00 | 0.00 | 0.00 | 0.153870E+11 | 0.00 | 0.00 |
October | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.174910E+11 | 0.00 | 0.00 |
November | 0.365275E+11 | 0.00 | 0.00 | 0.00 | 0.184550E+11 | 0.00 | 0.00 |
December | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.201531E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.444418E+12 | 0.00 | 56426976.94 | 0.00 | 0.204449E+12 | 0.00 | 0.00 |
Minimum of Months | 0.340924E+11 | 0.00 | 0.00 | 0.00 | 0.140803E+11 | 0.00 | 0.00 |
Maximum of Months | 0.377451E+11 | 0.00 | 56193751.45 | 0.00 | 0.205167E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2497.72 | 02-JAN-17:40 | 1510.48 | 01-JAN-06:10 | 22638.52 | 01-JAN-11:09 | 0.00 | 4864.32 | 24-JAN-11:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2497.72 | 01-FEB-17:00 | 1510.48 | 01-FEB-06:10 | 22638.52 | 01-FEB-11:09 | 0.00 | 5187.36 | 07-FEB-15:00 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 2497.72 | 01-MAR-18:19 | 1510.48 | 01-MAR-06:10 | 22638.52 | 01-MAR-11:09 | 0.00 | 5784.25 | 27-MAR-11:09 | 17.86 | 25-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 2497.72 | 01-APR-18:40 | 1510.48 | 01-APR-05:10 | 22638.52 | 01-APR-10:09 | 0.00 | 7172.84 | 28-APR-11:00 | 17.86 | 01-APR-09:50 | 0.00 | 01-APR-00:10 |
May | 2497.72 | 01-MAY-18:49 | 1510.48 | 01-MAY-05:10 | 22638.52 | 01-MAY-10:09 | 0.00 | 9596.72 | 30-MAY-17:00 | 17.86 | 04-MAY-07:00 | 0.00 | 01-MAY-00:10 |
June | 2497.72 | 01-JUN-18:00 | 1510.48 | 01-JUN-05:10 | 22638.52 | 01-JUN-10:09 | 0.00 | 10020.73 | 23-JUN-11:50 | 17.86 | 09-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 2497.72 | 01-JUL-19:10 | 1510.48 | 01-JUL-05:10 | 22638.52 | 01-JUL-10:09 | 0.00 | 10020.73 | 01-JUL-03:00 | 17.86 | 01-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 2497.72 | 01-AUG-19:10 | 1510.48 | 01-AUG-05:10 | 22638.52 | 01-AUG-10:09 | 0.00 | 10020.73 | 03-AUG-11:50 | 17.86 | 03-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 2497.72 | 01-SEP-18:40 | 1510.48 | 01-SEP-05:10 | 22638.52 | 01-SEP-10:09 | 0.00 | 10020.73 | 07-SEP-11:30 | 17.86 | 01-SEP-23:10 | 0.00 | 01-SEP-00:10 |
October | 2497.72 | 02-OCT-17:00 | 1510.48 | 01-OCT-05:10 | 22638.52 | 01-OCT-10:09 | 0.00 | 10008.18 | 07-OCT-18:00 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 2497.72 | 01-NOV-17:40 | 1510.48 | 01-NOV-05:10 | 22638.52 | 01-NOV-10:09 | 0.00 | 8241.03 | 01-NOV-11:00 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2497.72 | 01-DEC-17:30 | 1510.48 | 01-DEC-06:10 | 22638.52 | 01-DEC-11:09 | 0.00 | 5260.62 | 05-DEC-12:00 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 4864.32 | 17.86 | 0.00 | ||||||
Maximum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 10020.73 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 16989.42 | 24-JAN-12:00 | 0.00 | 0.00 | 0.00 | 4738.75 | 10-JAN-07:19 | 0.00 |
February | 21344.40 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 4737.27 | 13-FEB-07:40 | 0.00 |
March | 27077.13 | 27-MAR-11:09 | 0.00 | 0.00 | 0.00 | 4737.37 | 13-MAR-06:19 | 0.00 |
April | 35068.57 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 4736.59 | 07-APR-18:30 | 0.00 |
May | 41577.93 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4736.60 | 10-MAY-18:30 | 0.00 |
June | 44031.57 | 09-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4736.85 | 13-JUN-06:00 | 0.00 |
July | 44815.91 | 21-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4736.37 | 03-JUL-18:00 | 0.00 |
August | 47452.93 | 16-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4736.80 | 15-AUG-18:40 | 0.00 |
September | 43629.40 | 07-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.13 | 15-SEP-06:19 | 0.00 |
October | 38906.30 | 07-OCT-18:00 | 0.00 | 0.00 | 0.00 | 4736.19 | 23-OCT-18:00 | 0.00 |
November | 33377.28 | 01-NOV-11:00 | 0.00 | 0.00 | 0.00 | 4736.80 | 08-NOV-07:19 | 0.00 |
December | 21973.97 | 05-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4737.95 | 29-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16989.42 | 0.00 | 0.00 | 0.00 | 4736.13 | 0.00 | ||
Maximum of Months | 47452.93 | 0.00 | 0.00 | 0.00 | 4738.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49607.40 | 24-JAN-11:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 4864.32 | 17.86 | 0.00 | 15299.73 | 0.00 |
February | 53380.43 | 07-FEB-12:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 5040.64 | 17.86 | 0.00 | 21344.40 | 0.00 |
March | 60509.69 | 27-MAR-10:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 5425.04 | 17.86 | 0.00 | 25567.55 | 0.00 |
April | 69243.51 | 28-APR-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 7172.84 | 17.86 | 0.00 | 35068.57 | 0.00 |
May | 77874.37 | 31-MAY-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 9262.89 | 17.86 | 0.00 | 41577.93 | 0.00 |
June | 81106.28 | 09-JUN-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 9959.50 | 17.86 | 0.00 | 44031.57 | 0.00 |
July | 81047.64 | 19-JUL-11:39 | 1677.91 | 21117.99 | 0.00 | 0.00 | 10020.73 | 17.86 | 0.00 | 43889.97 | 0.00 |
August | 84166.19 | 16-AUG-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 9519.74 | 17.86 | 0.00 | 47452.93 | 0.00 |
September | 80702.70 | 07-SEP-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 10020.73 | 17.86 | 0.00 | 43629.40 | 0.00 |
October | 75870.32 | 07-OCT-18:00 | 2497.72 | 17316.66 | 1510.48 | 0.00 | 10008.18 | 17.86 | 0.00 | 38906.30 | 0.00 |
November | 68644.84 | 01-NOV-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 8241.03 | 17.86 | 0.00 | 33377.28 | 0.00 |
December | 54239.46 | 05-DEC-12:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 5260.62 | 17.86 | 0.00 | 21973.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 49607.40 | 1677.91 | 17316.66 | 0.00 | 0.00 | 4864.32 | 17.86 | 0.00 | 15299.73 | 0.00 | |
Maximum of Months | 84166.19 | 2497.72 | 22638.52 | 1510.48 | 0.00 | 10020.73 | 17.86 | 0.00 | 47452.93 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 24831.19 | 01-JAN-11:09 | 0.00 | 2824.21 | 16-JAN-06:10 | 0.00 | 14668.37 | 09-JAN-07:19 | 0.00 |
February | 24831.19 | 01-FEB-11:09 | 0.00 | 185.55 | 13-FEB-06:49 | 0.00 | 14628.12 | 01-FEB-07:19 | 0.00 |
March | 24831.19 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 14452.92 | 01-MAR-19:40 | 0.00 |
April | 24831.19 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 14146.30 | 03-APR-18:00 | 0.00 |
May | 24831.19 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 13862.87 | 01-MAY-18:30 | 0.00 |
June | 24831.19 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 13614.78 | 01-JUN-18:49 | 0.00 |
July | 24831.19 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 13488.59 | 31-JUL-18:40 | 0.00 |
August | 24831.19 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 13638.72 | 31-AUG-06:00 | 0.00 |
September | 24831.19 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 13885.67 | 29-SEP-18:19 | 0.00 |
October | 24831.19 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 14218.76 | 31-OCT-18:30 | 0.00 |
November | 24831.19 | 01-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 14488.39 | 30-NOV-19:19 | 0.00 |
December | 24831.19 | 01-DEC-11:09 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 14645.30 | 29-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 24831.19 | 0.00 | 0.00 | 0.00 | 13488.59 | 0.00 | |||
Maximum of Months | 24831.19 | 0.00 | 2824.21 | 0.00 | 14668.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.71 | 0.00 | 24.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.71 | 0.00 | 24.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.75 | 0.00 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.03 | 0.00 | 25.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.14 | 0.00 | 25.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 25.00 | 20.67 | 24.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 25.10 | 26.00 | 25.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.06 | 3.50 | 25.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 25.09 | 0.00 | 25.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.86 | 0.00 | 24.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.66 | 0.00 | 24.66 |
Annual Sum or Average | 0.00 | 0.00 | 105.00 | 25.02 | 50.17 | 25.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 25.14 | 26.00 | 25.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 29.37 | 0.00 | 29.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 29.49 | 0.00 | 29.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 29.78 | 0.00 | 29.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 29.46 | 5.83 | 29.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 98.83 | 28.32 | 71.33 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 359.17 | 28.31 | 322.67 | 28.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 549.50 | 29.10 | 500.00 | 29.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 581.00 | 29.35 | 530.17 | 29.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 431.67 | 28.62 | 390.00 | 28.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 135.50 | 28.51 | 103.67 | 28.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 29.62 | 9.00 | 29.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 29.90 | 0.00 | 29.90 |
Annual Sum or Average | 0.00 | 0.00 | 2272.17 | 28.91 | 1932.67 | 28.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.31 | 0.00 | 27.97 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 581.00 | 29.90 | 530.17 | 29.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.33 | 22.32 | 449.50 | 23.65 | 10.33 | 23.65 |
February | 104.17 | 23.13 | 464.50 | 23.84 | 52.17 | 23.86 |
March | 99.00 | 23.66 | 529.33 | 23.99 | 68.17 | 24.00 |
April | 128.83 | 24.26 | 565.50 | 24.13 | 128.83 | 24.15 |
May | 196.50 | 24.59 | 610.33 | 24.29 | 196.50 | 24.35 |
June | 426.33 | 24.33 | 592.00 | 24.27 | 426.33 | 24.29 |
July | 486.00 | 24.39 | 609.00 | 24.34 | 486.00 | 24.36 |
August | 525.17 | 24.38 | 612.00 | 24.35 | 525.17 | 24.36 |
September | 451.67 | 24.32 | 590.00 | 24.28 | 451.67 | 24.29 |
October | 298.33 | 24.33 | 610.00 | 24.23 | 298.33 | 24.26 |
November | 140.50 | 24.21 | 588.17 | 24.11 | 140.50 | 24.13 |
December | 151.50 | 23.62 | 540.83 | 23.92 | 113.33 | 23.93 |
Annual Sum or Average | 3125.33 | 24.18 | 6761.17 | 24.16 | 2897.33 | 24.20 |
Minimum of Months | 99.00 | 22.32 | 449.50 | 23.65 | 10.33 | 23.65 |
Maximum of Months | 525.17 | 24.59 | 612.00 | 24.35 | 525.17 | 24.36 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 460.67 | 25.98 | 595.83 | 25.76 | 460.17 | 25.83 |
February | 459.50 | 25.98 | 549.33 | 25.84 | 459.50 | 25.88 |
March | 537.33 | 26.00 | 612.00 | 25.93 | 537.33 | 25.95 |
April | 579.33 | 26.01 | 590.00 | 26.00 | 579.33 | 26.01 |
May | 611.00 | 26.20 | 611.00 | 26.20 | 611.00 | 26.20 |
June | 592.00 | 27.18 | 592.00 | 27.18 | 592.00 | 27.18 |
July | 609.00 | 28.48 | 609.00 | 28.48 | 609.00 | 28.48 |
August | 612.00 | 28.84 | 612.00 | 28.84 | 612.00 | 28.84 |
September | 590.00 | 27.66 | 590.00 | 27.66 | 590.00 | 27.66 |
October | 610.00 | 26.36 | 610.00 | 26.36 | 610.00 | 26.36 |
November | 588.00 | 26.02 | 591.00 | 26.02 | 588.00 | 26.02 |
December | 536.00 | 25.97 | 609.00 | 25.87 | 536.00 | 25.90 |
Annual Sum or Average | 6784.83 | 26.77 | 7171.17 | 26.71 | 6784.33 | 26.73 |
Minimum of Months | 459.50 | 25.97 | 549.33 | 25.76 | 459.50 | 25.83 |
Maximum of Months | 612.00 | 28.84 | 612.00 | 28.84 | 612.00 | 28.84 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.64023 | 51.41044 | 0.45348 | 10.11291 |
February | 551.00000 | 23.80003 | 54.80142 | 0.52413 | 11.27355 |
March | 612.00000 | 23.95066 | 51.79870 | 0.54950 | 11.69219 |
April | 590.00000 | 24.09503 | 55.38274 | 0.63019 | 13.59753 |
May | 611.00000 | 24.19797 | 57.96022 | -0.0963 | 6.12093 |
June | 592.00000 | 24.23639 | 65.85119 | -0.0003 | 6.26487 |
July | 609.00000 | 24.30763 | 68.20608 | 0.07379 | 6.79913 |
August | 612.00000 | 24.32954 | 69.59623 | 0.11134 | 6.88142 |
September | 590.00000 | 24.24310 | 68.45594 | 0.04815 | 6.36039 |
October | 610.00000 | 24.17730 | 62.08959 | 0.75505 | 17.42045 |
November | 591.00000 | 24.08613 | 58.10997 | 0.67262 | 14.70115 |
December | 609.00000 | 23.87256 | 56.08040 | 0.56284 | 12.04315 |
Annual Sum or Average | 7187.00000 | 24.07945 | 60.00002 | 0.35576 | 10.26316 |
Minimum of Months | 551.00000 | 23.64023 | 51.41044 | -0.0963 | 6.12093 |
Maximum of Months | 612.00000 | 24.32954 | 69.59623 | 0.75505 | 17.42045 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.51723 | 49.10734 | 1.09770 | 31.66603 |
February | 551.00000 | 25.70860 | 51.95793 | 1.17214 | 34.65111 |
March | 612.00000 | 25.87183 | 49.85585 | 1.20514 | 35.94141 |
April | 590.00000 | 26.00072 | 53.58751 | 1.28834 | 39.87812 |
May | 611.00000 | 26.19680 | 57.80805 | 0.87376 | 22.33876 |
June | 592.00000 | 27.18422 | 64.37322 | 1.28273 | 41.06140 |
July | 609.00000 | 28.47787 | 66.54213 | 1.76256 | 61.76250 |
August | 612.00000 | 28.84446 | 67.80009 | 1.91297 | 68.18977 |
September | 590.00000 | 27.66368 | 66.38015 | 1.47630 | 49.36733 |
October | 610.00000 | 26.35969 | 60.02213 | 1.47876 | 49.47893 |
November | 591.00000 | 26.01978 | 55.36731 | 1.32729 | 41.81152 |
December | 609.00000 | 25.79376 | 52.61847 | 1.21218 | 36.37351 |
Annual Sum or Average | 7187.00000 | 26.64354 | 57.98034 | 1.34217 | 42.77265 |
Minimum of Months | 551.00000 | 25.51723 | 49.10734 | 0.87376 | 22.33876 |
Maximum of Months | 612.00000 | 28.84446 | 67.80009 | 1.91297 | 68.18977 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.281646E+11 | 0.828868E+10 | 456.64 | 0.196030E+11 | 0.856166E+10 | 0.00 | 1.00 | 11-JAN-04:01 | 0.00 | 01-JAN-00:10 | 116580.85 | 30-JAN-04:01 | 65166.14 | 23-JAN-04:01 | 52381.36 | 30-JAN-04:01 | 28373.19 | 30-JAN-04:01 | 0.00 | 01-JAN-00:10 |
February | 0.342045E+11 | 0.978767E+10 | 455.96 | 0.233625E+11 | 0.108420E+11 | 0.00 | 1.00 | 04-FEB-04:01 | 0.00 | 01-FEB-00:05 | 119461.25 | 09-FEB-04:01 | 68244.65 | 08-FEB-04:01 | 58502.77 | 09-FEB-04:01 | 28583.79 | 09-FEB-04:01 | 0.00 | 01-FEB-00:05 |
March | 0.498834E+11 | 0.140579E+11 | 546.98 | 0.363697E+11 | 0.135136E+11 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:05 | 119556.15 | 29-MAR-03:01 | 86651.73 | 02-MAR-04:01 | 60808.76 | 29-MAR-03:01 | 28590.92 | 29-MAR-03:01 | 0.00 | 01-MAR-00:05 |
April | 0.731102E+11 | 0.198383E+11 | 576.68 | 0.514339E+11 | 0.216763E+11 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 121234.27 | 30-APR-03:01 | 92812.52 | 29-APR-03:01 | 78089.83 | 30-APR-03:01 | 28719.84 | 30-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.112981E+12 | 0.307893E+11 | 612.71 | 0.790470E+11 | 0.339340E+11 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 121234.27 | 27-MAY-03:01 | 100771.74 | 10-MAY-03:01 | 84803.10 | 30-MAY-03:01 | 31243.23 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.144773E+12 | 0.390155E+11 | 595.93 | 0.869018E+11 | 0.578711E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 121234.27 | 14-JUN-03:01 | 75777.44 | 02-JUN-03:01 | 86545.92 | 27-JUN-03:01 | 33623.19 | 09-JUN-12:00 | 0.00 | 01-JUN-00:01 |
July | 0.179115E+12 | 0.494033E+11 | 628.35 | 0.102829E+12 | 0.762863E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 121013.41 | 06-JUL-03:50 | 86777.83 | 04-JUL-03:01 | 87604.28 | 18-JUL-03:01 | 34284.61 | 21-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.189499E+12 | 0.522917E+11 | 630.16 | 0.106162E+12 | 0.833369E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 121234.27 | 31-AUG-03:01 | 83815.06 | 16-AUG-12:00 | 89373.67 | 09-AUG-03:02 | 35877.79 | 10-AUG-12:55 | 0.00 | 01-AUG-00:01 |
September | 0.157447E+12 | 0.415767E+11 | 597.73 | 0.870537E+11 | 0.703933E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 121234.27 | 03-SEP-03:08 | 72517.30 | 02-SEP-03:01 | 87567.09 | 11-SEP-03:01 | 33338.05 | 07-SEP-11:53 | 0.00 | 01-SEP-00:01 |
October | 0.118044E+12 | 0.306876E+11 | 612.46 | 0.721756E+11 | 0.458687E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 121234.27 | 02-OCT-03:01 | 86011.64 | 21-OCT-03:01 | 87679.68 | 07-OCT-03:01 | 29757.07 | 07-OCT-19:00 | 0.00 | 01-OCT-00:01 |
November | 0.759730E+11 | 0.201071E+11 | 581.48 | 0.493625E+11 | 0.266105E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 121234.27 | 03-NOV-03:02 | 83041.63 | 05-NOV-03:01 | 67226.67 | 08-NOV-04:01 | 28719.84 | 02-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.435039E+11 | 0.122037E+11 | 518.65 | 0.282485E+11 | 0.152554E+11 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:05 | 118800.24 | 06-DEC-04:01 | 74575.63 | 10-DEC-04:01 | 62346.03 | 06-DEC-04:01 | 28534.53 | 06-DEC-04:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.120670E+13 | 0.328047E+12 | 6813.72 | 0.742549E+12 | 0.464150E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.281646E+11 | 0.828868E+10 | 455.96 | 0.196030E+11 | 0.856166E+10 | 0.00 | 1.00 | 0.00 | 116580.85 | 65166.14 | 52381.36 | 28373.19 | 0.00 | |||||||
Maximum of Months | 0.189499E+12 | 0.522917E+11 | 630.16 | 0.106162E+12 | 0.833369E+11 | 0.00 | 1.00 | 0.00 | 121234.27 | 100771.74 | 89373.67 | 35877.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.185855E+11 | 0.453721E+10 | 484.73 | 0.126088E+11 | 0.597668E+10 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:10 | 38547.22 | 30-JAN-04:01 | 29800.44 | 18-JAN-04:11 | 19896.74 | 10-JAN-04:01 | 8652.93 | 30-JAN-04:01 | 0.00 | 01-JAN-00:10 |
February | 0.221805E+11 | 0.525723E+10 | 485.21 | 0.148622E+11 | 0.731832E+10 | 0.00 | 1.00 | 01-FEB-04:01 | 0.00 | 01-FEB-00:05 | 39901.77 | 09-FEB-04:01 | 30307.81 | 10-FEB-04:21 | 20958.63 | 03-FEB-04:01 | 8738.53 | 09-FEB-04:01 | 0.00 | 01-FEB-00:05 |
March | 0.317275E+11 | 0.744006E+10 | 608.94 | 0.232898E+11 | 0.843768E+10 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-01:01 | 40516.81 | 01-MAR-04:01 | 37642.57 | 22-MAR-03:01 | 23445.36 | 24-MAR-03:21 | 9903.53 | 27-MAR-10:55 | 0.00 | 01-MAR-00:05 |
April | 0.468640E+11 | 0.107113E+11 | 652.08 | 0.338543E+11 | 0.130097E+11 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 41823.37 | 29-APR-19:23 | 38716.75 | 28-APR-12:23 | 26836.59 | 30-APR-03:52 | 11206.62 | 28-APR-12:00 | 0.00 | 01-APR-00:01 |
May | 0.711677E+11 | 0.167170E+11 | 703.00 | 0.531847E+11 | 0.179830E+11 | 0.00 | 1.00 | 01-MAY-03:11 | 0.00 | 01-MAY-00:01 | 41823.37 | 18-MAY-03:01 | 38948.81 | 31-MAY-17:55 | 27846.69 | 01-MAY-03:52 | 11121.10 | 31-MAY-19:00 | 0.00 | 01-MAY-00:01 |
June | 0.843388E+11 | 0.198991E+11 | 684.22 | 0.544905E+11 | 0.298483E+11 | 0.00 | 1.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:01 | 41823.37 | 22-JUN-03:01 | 39229.44 | 27-JUN-10:52 | 29384.49 | 08-JUN-03:32 | 11080.22 | 21-JUN-11:55 | 0.00 | 01-JUN-00:01 |
July | 0.932124E+11 | 0.226966E+11 | 708.86 | 0.593891E+11 | 0.338233E+11 | 0.00 | 1.00 | 01-JUL-00:20 | 0.00 | 01-JUL-00:01 | 41823.37 | 06-JUL-05:50 | 39269.56 | 20-JUL-18:53 | 28595.81 | 27-JUL-03:45 | 11789.52 | 21-JUL-11:53 | 0.00 | 01-JUL-00:01 |
August | 0.947203E+11 | 0.230764E+11 | 709.41 | 0.592421E+11 | 0.354782E+11 | 0.00 | 1.00 | 01-AUG-00:06 | 0.00 | 01-AUG-00:01 | 41823.37 | 27-AUG-06:00 | 39250.46 | 15-AUG-18:13 | 29490.88 | 08-AUG-03:45 | 11719.88 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 0.876714E+11 | 0.203313E+11 | 684.46 | 0.513973E+11 | 0.362740E+11 | 0.00 | 1.00 | 01-SEP-00:08 | 0.00 | 01-SEP-00:01 | 41823.37 | 28-SEP-07:00 | 39192.59 | 13-SEP-12:10 | 29393.30 | 03-SEP-03:01 | 10816.67 | 26-SEP-12:00 | 0.00 | 01-SEP-00:01 |
October | 0.747079E+11 | 0.167848E+11 | 705.38 | 0.468109E+11 | 0.278970E+11 | 0.00 | 1.00 | 01-OCT-00:09 | 0.00 | 01-OCT-00:01 | 41823.37 | 01-OCT-04:13 | 37111.58 | 09-OCT-11:53 | 30764.90 | 07-OCT-03:01 | 9850.57 | 09-OCT-11:53 | 0.00 | 01-OCT-00:01 |
November | 0.485726E+11 | 0.108361E+11 | 661.32 | 0.319024E+11 | 0.166702E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 41823.37 | 07-NOV-18:20 | 28721.68 | 05-NOV-12:00 | 25322.55 | 08-NOV-04:52 | 9329.98 | 01-NOV-13:55 | 0.00 | 01-NOV-00:01 |
December | 0.285459E+11 | 0.660717E+10 | 561.45 | 0.179887E+11 | 0.105572E+11 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-01:01 | 39630.19 | 11-DEC-04:01 | 27173.80 | 01-DEC-04:01 | 22830.13 | 06-DEC-04:01 | 8721.32 | 11-DEC-04:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.702294E+12 | 0.164894E+12 | 7649.07 | 0.459021E+12 | 0.243274E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.185855E+11 | 0.453721E+10 | 484.73 | 0.126088E+11 | 0.597668E+10 | 0.00 | 1.00 | 0.00 | 38547.22 | 27173.80 | 19896.74 | 8652.93 | 0.00 | |||||||
Maximum of Months | 0.947203E+11 | 0.230764E+11 | 709.41 | 0.593891E+11 | 0.362740E+11 | 0.00 | 1.00 | 0.00 | 41823.37 | 39269.56 | 30764.90 | 11789.52 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.63 | 36.99 | 85.65 | 170.91 | 154.27 | 0.00 | 0.00 | 0.00 |
February | 133.91 | 36.29 | 97.62 | 208.26 | 128.44 | 0.00 | 0.00 | 0.00 |
March | 148.05 | 36.52 | 111.53 | 266.71 | 96.34 | 0.00 | 0.00 | 0.00 |
April | 180.23 | 52.45 | 127.78 | 387.63 | 59.35 | 0.00 | 0.00 | 0.00 |
May | 201.09 | 64.04 | 137.05 | 527.86 | 15.88 | 0.50 | 0.00 | 0.00 |
June | 196.98 | 60.22 | 136.76 | 553.87 | 4.08 | 0.17 | 0.00 | 0.00 |
July | 183.88 | 52.98 | 130.89 | 595.52 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 188.34 | 57.82 | 130.52 | 605.15 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 176.96 | 54.66 | 122.29 | 497.63 | 7.49 | 2.50 | 0.00 | 0.00 |
October | 160.54 | 52.37 | 108.17 | 391.83 | 28.15 | 1.50 | 0.00 | 0.00 |
November | 134.48 | 42.47 | 92.01 | 268.86 | 71.85 | 0.00 | 0.00 | 0.00 |
December | 109.03 | 29.98 | 79.05 | 166.72 | 129.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.45 | 48.11 | 113.33 | 387.77 | 57.61 | 4.67 | 0.00 | 0.00 |
Minimum of Months | 109.03 | 29.98 | 79.05 | 166.72 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.09 | 64.04 | 137.05 | 605.15 | 154.27 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.29 | 144.18 | 161.12 | 497.80 | 210.98 | 0.00 | 0.00 | 0.00 |
February | 285.40 | 116.73 | 168.67 | 493.13 | 179.95 | 0.00 | 0.00 | 0.00 |
March | 232.42 | 61.34 | 171.09 | 447.97 | 139.64 | 0.00 | 0.00 | 0.00 |
April | 185.61 | 20.50 | 165.11 | 429.16 | 87.39 | 0.00 | 0.00 | 0.00 |
May | 157.04 | 2.96 | 154.08 | 492.15 | 23.41 | 0.50 | 0.00 | 0.00 |
June | 147.28 | 0.18 | 147.10 | 514.11 | 6.07 | 0.17 | 0.00 | 0.00 |
July | 147.08 | 0.97 | 146.11 | 607.67 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 170.14 | 11.32 | 158.83 | 669.52 | 0.15 | 0.00 | 0.00 | 0.00 |
September | 225.53 | 51.86 | 173.67 | 674.89 | 10.50 | 2.50 | 0.00 | 0.00 |
October | 295.40 | 117.74 | 177.66 | 703.64 | 39.28 | 1.50 | 0.00 | 0.00 |
November | 326.94 | 158.39 | 168.54 | 651.40 | 100.27 | 0.00 | 0.00 | 0.00 |
December | 302.54 | 149.72 | 152.83 | 522.81 | 178.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 231.40 | 69.40 | 161.99 | 559.13 | 80.84 | 4.67 | 0.00 | 0.00 |
Minimum of Months | 147.08 | 0.18 | 146.11 | 429.16 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 326.94 | 158.39 | 177.66 | 703.64 | 210.98 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.83 | 34.75 | 86.07 | 174.96 | 162.39 | 0.00 | 0.00 | 0.00 |
February | 137.90 | 39.45 | 98.45 | 221.17 | 134.54 | 0.00 | 0.00 | 0.00 |
March | 162.89 | 48.23 | 114.67 | 299.40 | 101.48 | 0.00 | 0.00 | 0.00 |
April | 178.12 | 50.04 | 128.08 | 382.53 | 62.77 | 0.00 | 0.00 | 0.00 |
May | 193.77 | 57.99 | 135.78 | 510.74 | 16.55 | 0.50 | 0.00 | 0.00 |
June | 200.17 | 63.07 | 137.10 | 556.57 | 4.25 | 0.17 | 0.00 | 0.00 |
July | 183.59 | 52.43 | 131.16 | 591.58 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 188.37 | 57.16 | 131.20 | 603.06 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 179.49 | 56.47 | 123.03 | 499.80 | 7.35 | 2.33 | 0.00 | 0.00 |
October | 159.66 | 51.76 | 107.90 | 387.65 | 28.67 | 1.50 | 0.00 | 0.00 |
November | 137.27 | 45.04 | 92.23 | 276.94 | 76.71 | 0.00 | 0.00 | 0.00 |
December | 114.47 | 34.46 | 80.01 | 183.88 | 136.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.13 | 49.27 | 113.86 | 391.66 | 60.60 | 4.50 | 0.00 | 0.00 |
Minimum of Months | 114.47 | 34.46 | 80.01 | 174.96 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.17 | 63.07 | 137.10 | 603.06 | 162.39 | 2.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328462E+09 | 99068081.85 | 0.229394E+09 | 0.457763E+09 | 0.413210E+09 |
February | 0.323959E+09 | 87800574.75 | 0.236158E+09 | 0.503817E+09 | 0.310729E+09 |
March | 0.396527E+09 | 97810156.13 | 0.298716E+09 | 0.714347E+09 | 0.258046E+09 |
April | 0.467145E+09 | 0.135937E+09 | 0.331207E+09 | 0.100475E+10 | 0.153844E+09 |
May | 0.538593E+09 | 0.171519E+09 | 0.367074E+09 | 0.141381E+10 | 42531327.98 |
June | 0.510569E+09 | 0.156081E+09 | 0.354488E+09 | 0.143564E+10 | 10587198.06 |
July | 0.492492E+09 | 0.141908E+09 | 0.350584E+09 | 0.159504E+10 | 134505.94 |
August | 0.504450E+09 | 0.154878E+09 | 0.349572E+09 | 0.162084E+10 | 304224.31 |
September | 0.458674E+09 | 0.141691E+09 | 0.316983E+09 | 0.128985E+10 | 19415067.41 |
October | 0.429978E+09 | 0.140266E+09 | 0.289712E+09 | 0.104948E+10 | 75404553.11 |
November | 0.348568E+09 | 0.110087E+09 | 0.238482E+09 | 0.696886E+09 | 0.186229E+09 |
December | 0.292026E+09 | 80294997.85 | 0.211731E+09 | 0.446548E+09 | 0.346381E+09 |
Annual Sum or Average | 0.509144E+10 | 0.151734E+10 | 0.357410E+10 | 0.122288E+11 | 0.181682E+10 |
Minimum of Months | 0.292026E+09 | 80294997.85 | 0.211731E+09 | 0.446548E+09 | 134505.94 |
Maximum of Months | 0.538593E+09 | 0.171519E+09 | 0.367074E+09 | 0.162084E+10 | 0.413210E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.817694E+09 | 0.386163E+09 | 0.431531E+09 | 0.133330E+10 | 0.565079E+09 |
February | 0.690428E+09 | 0.282384E+09 | 0.408044E+09 | 0.119298E+10 | 0.435340E+09 |
March | 0.622525E+09 | 0.164288E+09 | 0.458237E+09 | 0.119985E+10 | 0.374020E+09 |
April | 0.481114E+09 | 53137829.44 | 0.427976E+09 | 0.111238E+10 | 0.226511E+09 |
May | 0.420614E+09 | 7936575.76 | 0.412677E+09 | 0.131817E+10 | 62704358.20 |
June | 0.381758E+09 | 472126.58 | 0.381286E+09 | 0.133258E+10 | 15741463.43 |
July | 0.393934E+09 | 2606591.54 | 0.391328E+09 | 0.162758E+10 | 215282.45 |
August | 0.455711E+09 | 30312996.76 | 0.425398E+09 | 0.179325E+10 | 413032.09 |
September | 0.584572E+09 | 0.134420E+09 | 0.450152E+09 | 0.174931E+10 | 27224834.91 |
October | 0.791204E+09 | 0.315352E+09 | 0.475852E+09 | 0.188463E+10 | 0.105209E+09 |
November | 0.847416E+09 | 0.410558E+09 | 0.436858E+09 | 0.168842E+10 | 0.259889E+09 |
December | 0.810334E+09 | 0.401007E+09 | 0.409327E+09 | 0.140028E+10 | 0.477159E+09 |
Annual Sum or Average | 0.729730E+10 | 0.218864E+10 | 0.510867E+10 | 0.176327E+11 | 0.254951E+10 |
Minimum of Months | 0.381758E+09 | 472126.58 | 0.381286E+09 | 0.111238E+10 | 215282.45 |
Maximum of Months | 0.847416E+09 | 0.410558E+09 | 0.475852E+09 | 0.188463E+10 | 0.565079E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323619E+09 | 93087218.84 | 0.230531E+09 | 0.468622E+09 | 0.434947E+09 |
February | 0.333604E+09 | 95440198.15 | 0.238163E+09 | 0.535059E+09 | 0.325484E+09 |
March | 0.436295E+09 | 0.129174E+09 | 0.307121E+09 | 0.801925E+09 | 0.271798E+09 |
April | 0.461676E+09 | 0.129701E+09 | 0.331975E+09 | 0.991521E+09 | 0.162709E+09 |
May | 0.518993E+09 | 0.155330E+09 | 0.363663E+09 | 0.136797E+10 | 44338811.76 |
June | 0.518841E+09 | 0.163476E+09 | 0.355365E+09 | 0.144262E+10 | 11007614.97 |
July | 0.491736E+09 | 0.140429E+09 | 0.351307E+09 | 0.158449E+10 | 140489.43 |
August | 0.504521E+09 | 0.153108E+09 | 0.351413E+09 | 0.161524E+10 | 244367.70 |
September | 0.465250E+09 | 0.146364E+09 | 0.318886E+09 | 0.129549E+10 | 19056312.92 |
October | 0.427623E+09 | 0.138631E+09 | 0.288993E+09 | 0.103827E+10 | 76793972.81 |
November | 0.355805E+09 | 0.116741E+09 | 0.239064E+09 | 0.717831E+09 | 0.198828E+09 |
December | 0.306596E+09 | 92307052.40 | 0.214289E+09 | 0.492499E+09 | 0.365591E+09 |
Annual Sum or Average | 0.514456E+10 | 0.155379E+10 | 0.359077E+10 | 0.123515E+11 | 0.191094E+10 |
Minimum of Months | 0.306596E+09 | 92307052.40 | 0.214289E+09 | 0.468622E+09 | 140489.43 |
Maximum of Months | 0.518993E+09 | 0.163476E+09 | 0.363663E+09 | 0.161524E+10 | 0.434947E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 830.75 | 514.72 | 548.75 | 215.92 | 332.83 | 0.00 | 0.00 |
February | 912.65 | 433.03 | 557.21 | 192.47 | 364.73 | 0.00 | 0.00 |
March | 1007.24 | 330.63 | 543.36 | 146.08 | 397.28 | 0.00 | 0.00 |
April | 1194.93 | 205.12 | 543.96 | 122.98 | 420.97 | 0.00 | 0.00 |
May | 1528.80 | 53.90 | 551.90 | 124.99 | 426.90 | 0.00 | 0.00 |
June | 1624.33 | 14.18 | 544.43 | 123.47 | 420.96 | 0.00 | 0.00 |
July | 1794.77 | 0.18 | 514.55 | 106.39 | 408.16 | 0.00 | 0.00 |
August | 1877.74 | 0.36 | 546.85 | 126.31 | 420.54 | 0.00 | 0.00 |
September | 1671.87 | 24.90 | 581.98 | 162.99 | 418.99 | 0.00 | 0.00 |
October | 1481.54 | 94.52 | 615.59 | 221.87 | 393.73 | 0.00 | 0.00 |
November | 1192.23 | 243.86 | 598.68 | 245.91 | 352.78 | 0.00 | 0.00 |
December | 864.83 | 435.40 | 526.04 | 214.16 | 311.88 | 0.00 | 0.00 |
Annual Sum or Average | 1334.28 | 194.76 | 555.98 | 166.79 | 389.19 | 0.00 | 0.00 |
Minimum of Months | 830.75 | 0.18 | 514.55 | 106.39 | 311.88 | 0.00 | 0.00 |
Maximum of Months | 1877.74 | 514.72 | 615.59 | 245.91 | 426.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.222507E+10 | 0.137862E+10 | 0.146977E+10 | 0.578318E+09 | 0.891456E+09 | 0.00 | 0.00 |
February | 0.220788E+10 | 0.104757E+10 | 0.134799E+10 | 0.465625E+09 | 0.882366E+09 | 0.00 | 0.00 |
March | 0.269780E+10 | 0.885546E+09 | 0.145535E+10 | 0.391272E+09 | 0.106407E+10 | 0.00 | 0.00 |
April | 0.309725E+10 | 0.531660E+09 | 0.140993E+10 | 0.318776E+09 | 0.109116E+10 | 0.00 | 0.00 |
May | 0.409475E+10 | 0.144379E+09 | 0.147820E+10 | 0.334785E+09 | 0.114341E+10 | 0.00 | 0.00 |
June | 0.421026E+10 | 36765247.21 | 0.141117E+10 | 0.320029E+09 | 0.109114E+10 | 0.00 | 0.00 |
July | 0.480711E+10 | 485855.40 | 0.137816E+10 | 0.284944E+09 | 0.109322E+10 | 0.00 | 0.00 |
August | 0.502933E+10 | 959208.79 | 0.146468E+10 | 0.338299E+09 | 0.112638E+10 | 0.00 | 0.00 |
September | 0.433349E+10 | 64535453.31 | 0.150849E+10 | 0.422475E+09 | 0.108602E+10 | 0.00 | 0.00 |
October | 0.396815E+10 | 0.253173E+09 | 0.164881E+10 | 0.594249E+09 | 0.105456E+10 | 0.00 | 0.00 |
November | 0.309027E+10 | 0.632077E+09 | 0.155179E+10 | 0.637386E+09 | 0.914404E+09 | 0.00 | 0.00 |
December | 0.231637E+10 | 0.116617E+10 | 0.140896E+10 | 0.573609E+09 | 0.835348E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.420777E+11 | 0.614195E+10 | 0.175333E+11 | 0.525977E+10 | 0.122735E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220788E+10 | 485855.40 | 0.134799E+10 | 0.284944E+09 | 0.835348E+09 | 0.00 | 0.00 |
Maximum of Months | 0.502933E+10 | 0.137862E+10 | 0.164881E+10 | 0.637386E+09 | 0.114341E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638079E+10 | -0.622519E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155596037.8 | 81.21 | 0.00 | 0.00 |
February | 0.577435E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -140062060.3 | 81.21 | 0.00 | 0.00 |
March | 0.644850E+10 | -0.629388E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154625619.9 | 81.21 | 0.00 | 0.00 |
April | 0.619277E+10 | -0.604350E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149272370.1 | 81.21 | 0.00 | 0.00 |
May | 0.641393E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153727436.7 | 81.21 | 0.00 | 0.00 |
June | 0.623302E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -146451284.8 | 81.21 | 0.00 | 0.00 |
July | 0.636523E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148144491.3 | 81.22 | 0.00 | 0.00 |
August | 0.644240E+10 | -0.629520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147205394.3 | 81.22 | 0.00 | 0.00 |
September | 0.619011E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -145290712.3 | 81.22 | 0.00 | 0.00 |
October | 0.637716E+10 | -0.622384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153312082.2 | 81.21 | 0.00 | 0.00 |
November | 0.617381E+10 | -0.602463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149173192.1 | 81.21 | 0.00 | 0.00 |
December | 0.637193E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154811880.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753640E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179767E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577435E+10 | -0.629520E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155596037.8 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644850E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -140062060.3 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.174460E+11 | -0.165953E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850769282.5 | 58.99 | 0.00 | 0.00 |
February | 0.153560E+11 | -0.145921E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -763946579.3 | 58.99 | 0.00 | 0.00 |
March | 0.160020E+11 | -0.151601E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -841803869.7 | 58.99 | 0.00 | 0.00 |
April | 0.138856E+11 | -0.130746E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811019596.9 | 58.98 | 0.00 | 0.00 |
May | 0.128741E+11 | -0.120408E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -833253780.0 | 58.98 | 0.00 | 0.00 |
June | 0.114434E+11 | -0.106581E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -785286029.5 | 58.98 | 0.00 | 0.00 |
July | 0.113274E+11 | -0.105452E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -782229164.1 | 58.98 | 0.00 | 0.00 |
August | 0.119402E+11 | -0.111668E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -773402069.0 | 58.97 | 0.00 | 0.00 |
September | 0.126323E+11 | -0.118577E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -774661911.1 | 58.98 | 0.00 | 0.00 |
October | 0.145718E+11 | -0.137422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -829674908.2 | 58.98 | 0.00 | 0.00 |
November | 0.155522E+11 | -0.147418E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -810369192.4 | 58.99 | 0.00 | 0.00 |
December | 0.170988E+11 | -0.162554E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843495066.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.170130E+12 | -0.160430E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.969991E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.113274E+11 | -0.165953E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -850769282.5 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.174460E+11 | -0.105452E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -763946579.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.50 | 01-JAN-07:00 | 747.28 | 24.40 | 210.50 | 291.67 | 717.57 | 24.12 | 212.00 | 291.50 |
February | 308.33 | 0.53 | 0.50 | 01-FEB-07:00 | 697.34 | 21.73 | 146.67 | 267.67 | 687.73 | 21.78 | 152.83 | 267.50 |
March | 357.50 | 0.53 | 0.50 | 01-MAR-08:09 | 700.22 | 19.77 | 91.67 | 311.33 | 683.34 | 19.87 | 106.50 | 311.50 |
April | 375.00 | 0.53 | 0.50 | 01-APR-07:19 | 677.30 | 19.18 | 73.50 | 328.00 | 592.61 | 19.23 | 77.67 | 325.00 |
May | 405.33 | 0.53 | 0.50 | 01-MAY-06:30 | 602.64 | 19.09 | 61.67 | 355.83 | 605.75 | 19.07 | 65.00 | 354.83 |
June | 403.50 | 0.54 | 0.50 | 01-JUN-06:40 | 568.97 | 20.61 | 92.50 | 347.83 | 593.40 | 19.05 | 60.67 | 347.17 |
July | 405.00 | 0.54 | 0.50 | 01-JUL-06:00 | 563.00 | 19.38 | 68.83 | 346.50 | 573.75 | 18.91 | 68.83 | 344.00 |
August | 395.83 | 0.54 | 0.50 | 01-AUG-06:49 | 670.77 | 19.36 | 92.17 | 345.00 | 618.25 | 19.37 | 97.00 | 343.00 |
September | 358.83 | 0.53 | 0.50 | 01-SEP-06:00 | 724.00 | 20.09 | 116.50 | 321.50 | 678.98 | 20.06 | 119.83 | 318.67 |
October | 351.17 | 0.53 | 0.50 | 01-OCT-06:00 | 765.75 | 21.28 | 167.17 | 316.00 | 839.34 | 22.06 | 193.33 | 316.00 |
November | 318.83 | 0.51 | 0.50 | 01-NOV-06:00 | 831.18 | 24.33 | 230.33 | 294.33 | 806.21 | 24.50 | 233.17 | 297.33 |
December | 319.00 | 0.53 | 0.50 | 01-DEC-07:19 | 755.19 | 24.25 | 210.00 | 284.33 | 708.63 | 24.15 | 209.83 | 285.67 |
Annual Sum or Average | 4323.33 | 0.53 | 685.63 | 20.96 | 1561.50 | 3810.00 | 669.70 | 20.83 | 1596.67 | 3802.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.50 | 563.00 | 19.09 | 61.67 | 267.67 | 573.75 | 18.91 | 60.67 | 267.50 | |
Maximum of Months | 405.33 | 0.54 | 0.50 | 831.18 | 24.40 | 230.33 | 355.83 | 839.34 | 24.50 | 233.17 | 354.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 45516938.68 | 3196.17 | 01-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 188912.64 | 150.29 | 13-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45705851.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45516938.68 | 3196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.281646E+11 | 0.196030E+11 | 116580.85 | 30-JAN-04:01 | 64199.48 | 0.00 |
February | 0.00 | 0.00 | 0.342045E+11 | 0.233625E+11 | 119461.25 | 09-FEB-04:01 | 60958.49 | 0.00 |
March | 0.00 | 0.00 | 0.498834E+11 | 0.363697E+11 | 119556.15 | 29-MAR-03:01 | 58747.39 | 0.00 |
April | 0.00 | 0.00 | 0.731102E+11 | 0.514339E+11 | 121234.27 | 30-APR-03:01 | 43144.44 | 0.00 |
May | 0.00 | 0.00 | 0.112981E+12 | 0.790470E+11 | 121234.27 | 27-MAY-03:01 | 47360.81 | 0.00 |
June | 0.00 | 0.00 | 0.144773E+12 | 0.869018E+11 | 121234.27 | 14-JUN-03:01 | 37918.51 | 0.00 |
July | 0.00 | 0.00 | 0.179115E+12 | 0.102829E+12 | 121013.41 | 06-JUL-03:50 | 40520.09 | 0.00 |
August | 0.00 | 0.00 | 0.189499E+12 | 0.106162E+12 | 121234.27 | 31-AUG-03:01 | 36874.90 | 0.00 |
September | 0.00 | 0.00 | 0.157447E+12 | 0.870537E+11 | 121234.27 | 03-SEP-03:08 | 37032.73 | 0.00 |
October | 0.00 | 0.00 | 0.118044E+12 | 0.721756E+11 | 121234.27 | 02-OCT-03:01 | 39099.07 | 0.00 |
November | 0.00 | 0.00 | 0.759730E+11 | 0.493625E+11 | 121234.27 | 03-NOV-03:02 | 55916.80 | 0.00 |
December | 0.00 | 0.00 | 0.435039E+11 | 0.282485E+11 | 118800.24 | 06-DEC-04:01 | 56454.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120670E+13 | 0.742549E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.281646E+11 | 0.196030E+11 | 116580.85 | 36874.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.189499E+12 | 0.106162E+12 | 121234.27 | 64199.48 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185855E+11 | 0.126088E+11 | 38547.22 | 30-JAN-04:01 | 19871.58 | 0.00 |
February | 0.00 | 0.00 | 0.221805E+11 | 0.148622E+11 | 39901.77 | 09-FEB-04:01 | 20110.92 | 0.00 |
March | 0.00 | 0.00 | 0.317275E+11 | 0.232898E+11 | 40516.81 | 01-MAR-04:01 | 26030.06 | 0.00 |
April | 0.00 | 0.00 | 0.468640E+11 | 0.338543E+11 | 41823.37 | 29-APR-19:23 | 19165.29 | 0.00 |
May | 0.00 | 0.00 | 0.711677E+11 | 0.531847E+11 | 41823.37 | 18-MAY-03:01 | 20232.43 | 0.00 |
June | 0.00 | 0.00 | 0.843388E+11 | 0.544905E+11 | 41823.37 | 22-JUN-03:01 | 17913.47 | 0.00 |
July | 0.00 | 0.00 | 0.932124E+11 | 0.593891E+11 | 41823.37 | 06-JUL-05:50 | 14495.06 | 0.00 |
August | 0.00 | 0.00 | 0.947203E+11 | 0.592421E+11 | 41823.37 | 27-AUG-06:00 | 13047.65 | 0.00 |
September | 0.00 | 0.00 | 0.876714E+11 | 0.513973E+11 | 41823.37 | 28-SEP-07:00 | 14754.23 | 0.00 |
October | 0.00 | 0.00 | 0.747079E+11 | 0.468109E+11 | 41823.37 | 01-OCT-04:13 | 13883.24 | 0.00 |
November | 0.00 | 0.00 | 0.485726E+11 | 0.319024E+11 | 41823.37 | 07-NOV-18:20 | 21641.73 | 0.00 |
December | 0.00 | 0.00 | 0.285459E+11 | 0.179887E+11 | 39630.19 | 11-DEC-04:01 | 20622.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.702294E+12 | 0.459021E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.185855E+11 | 0.126088E+11 | 38547.22 | 13047.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.947203E+11 | 0.593891E+11 | 41823.37 | 26030.06 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6660.90 | 12651.41 | 13-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6497.06 | 12510.11 | 02-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 6126.56 | 11922.41 | 01-MAR-19:45 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5511.42 | 10852.18 | 03-APR-18:43 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4964.82 | 9831.87 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4583.15 | 8865.90 | 01-JUN-18:15 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4408.33 | 8389.74 | 31-JUL-18:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4639.36 | 9004.62 | 31-AUG-18:43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5044.01 | 9952.99 | 29-SEP-18:17 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5598.47 | 11111.81 | 31-OCT-18:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6153.63 | 12046.89 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 6534.35 | 12558.33 | 29-DEC-19:25 |
Annual Sum or Average | 0.00 | 5555.07 | ||||
Minimum of Months | 0.00 | 0.00 | 4408.33 | 8389.74 | ||
Maximum of Months | 0.00 | 0.00 | 6660.90 | 12651.41 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.198137E+10 | 0.24 | 824.13 | 01-JAN-00:10 | 0.26 |
February | 0.181671E+10 | 0.24 | 824.13 | 01-FEB-00:05 | 0.26 |
March | 0.204739E+10 | 0.24 | 824.13 | 01-MAR-00:05 | 0.26 |
April | 0.200418E+10 | 0.25 | 824.13 | 01-APR-00:50 | 0.26 |
May | 0.209595E+10 | 0.25 | 824.13 | 01-MAY-00:40 | 0.26 |
June | 0.203767E+10 | 0.25 | 824.13 | 01-JUN-00:10 | 0.26 |
July | 0.210711E+10 | 0.25 | 824.13 | 01-JUL-00:20 | 0.26 |
August | 0.210733E+10 | 0.25 | 824.13 | 01-AUG-00:06 | 0.26 |
September | 0.203636E+10 | 0.25 | 824.13 | 01-SEP-00:08 | 0.26 |
October | 0.210104E+10 | 0.25 | 824.13 | 01-OCT-00:09 | 0.26 |
November | 0.201450E+10 | 0.25 | 824.13 | 01-NOV-00:30 | 0.26 |
December | 0.204022E+10 | 0.24 | 824.13 | 01-DEC-00:05 | 0.26 |
Annual Sum or Average | 0.243898E+11 | 0.25 | |||
Minimum of Months | 0.181671E+10 | 0.24 | 824.13 | 0.26 | |
Maximum of Months | 0.210733E+10 | 0.25 | 824.13 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.675830E+10 | 0.71 | 7552.43 | 30-JAN-04:01 | 1.38 |
February | 0.610919E+10 | 0.72 | 7552.43 | 06-FEB-04:01 | 1.38 |
March | 0.677721E+10 | 0.72 | 7552.43 | 01-MAR-04:01 | 1.38 |
April | 0.663516E+10 | 0.73 | 7552.43 | 01-APR-03:01 | 1.38 |
May | 0.767131E+10 | 0.77 | 7552.43 | 01-MAY-03:01 | 1.37 |
June | 0.911447E+10 | 0.86 | 7552.43 | 01-JUN-03:01 | 1.37 |
July | 0.112907E+11 | 0.94 | 7552.43 | 01-JUL-03:01 | 1.36 |
August | 0.119447E+11 | 0.97 | 7552.43 | 01-AUG-03:01 | 1.36 |
September | 0.983003E+10 | 0.89 | 7552.43 | 01-SEP-03:01 | 1.37 |
October | 0.781471E+10 | 0.78 | 7552.43 | 01-OCT-03:01 | 1.36 |
November | 0.671269E+10 | 0.73 | 7552.43 | 01-NOV-03:01 | 1.38 |
December | 0.677307E+10 | 0.72 | 7552.43 | 03-DEC-04:01 | 1.38 |
Annual Sum or Average | 0.974315E+11 | 0.79 | |||
Minimum of Months | 0.610919E+10 | 0.71 | 7552.43 | 1.36 | |
Maximum of Months | 0.119447E+11 | 0.97 | 7552.43 | 1.38 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149939E+10 | 0.48 | 1644.17 | 01-JAN-04:01 | 0.88 |
February | 0.140101E+10 | 0.49 | 1644.17 | 01-FEB-04:01 | 0.88 |
March | 0.166275E+10 | 0.52 | 1644.17 | 01-MAR-04:01 | 0.87 |
April | 0.198140E+10 | 0.58 | 1644.17 | 01-APR-03:01 | 0.87 |
May | 0.282337E+10 | 0.68 | 1644.17 | 01-MAY-03:11 | 0.87 |
June | 0.337244E+10 | 0.75 | 1644.17 | 01-JUN-03:01 | 0.87 |
July | 0.378662E+10 | 0.78 | 1644.17 | 01-JUL-03:01 | 0.86 |
August | 0.384971E+10 | 0.79 | 1644.17 | 01-AUG-00:06 | 0.86 |
September | 0.349295E+10 | 0.77 | 1644.17 | 01-SEP-03:01 | 0.86 |
October | 0.291327E+10 | 0.69 | 1644.17 | 01-OCT-03:01 | 0.86 |
November | 0.200425E+10 | 0.59 | 1644.17 | 01-NOV-03:01 | 0.87 |
December | 0.161372E+10 | 0.51 | 1644.17 | 01-DEC-04:01 | 0.88 |
Annual Sum or Average | 0.304009E+11 | 0.64 | |||
Minimum of Months | 0.140101E+10 | 0.48 | 1644.17 | 0.86 | |
Maximum of Months | 0.384971E+10 | 0.79 | 1644.17 | 0.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 51.03 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 52.01 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:05 | 5.36 | 5.36 | 51.97 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 54.64 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 55.08 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 55.23 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 55.36 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 55.94 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.84 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 55.15 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 54.35 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 51.87 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 51.03 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.94 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 51.03 | 59.48 | 6660.90 | 12651.41 | 13-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 52.01 | 59.05 | 6497.06 | 12510.11 | 02-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.97 | 58.42 | 6126.56 | 11922.41 | 01-MAR-19:45 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.94 | 52.94 | 5511.42 | 10852.18 | 03-APR-18:43 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.60 | 53.60 | 4964.82 | 9831.87 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 54.26 | 54.26 | 4583.15 | 8865.90 | 01-JUN-18:15 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.51 | 54.51 | 4408.33 | 8389.74 | 31-JUL-18:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 54.96 | 54.96 | 4639.36 | 9004.62 | 31-AUG-18:43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.97 | 53.97 | 5044.01 | 9952.99 | 29-SEP-18:17 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 52.30 | 52.30 | 5598.47 | 11111.81 | 31-OCT-18:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.22 | 53.22 | 6153.63 | 12046.89 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.87 | 58.39 | 6534.35 | 12558.33 | 29-DEC-19:25 |
Annual Sum or Average | 0.00 | 5555.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.03 | 52.30 | 4408.33 | 8389.74 | ||
Maximum of Months | 0.00 | 0.00 | 54.96 | 59.48 | 6660.90 | 12651.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150470E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158969E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.208351E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.264734E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.384606E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.481300E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.606940E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.642364E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.514068E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.385023E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.268198E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.189768E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.425479E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150470E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.642364E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.603660E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.665824E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.910280E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126927E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.195404E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.232715E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.264832E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.269261E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.238243E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.196981E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.128404E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.822090E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195295E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.603660E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.269261E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.675830E+10 | 0.281646E+11 | 45516938.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.610919E+10 | 0.342045E+11 | 188912.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677721E+10 | 0.498834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.663516E+10 | 0.731102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.767131E+10 | 0.112981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.911447E+10 | 0.144773E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112907E+11 | 0.179115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119447E+11 | 0.189499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.983003E+10 | 0.157447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781471E+10 | 0.118044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.671269E+10 | 0.759730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677307E+10 | 0.435039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974315E+11 | 0.120670E+13 | 45705851.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.610919E+10 | 0.281646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119447E+11 | 0.189499E+12 | 45516938.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149939E+10 | 0.185855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140101E+10 | 0.221805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166275E+10 | 0.317275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198140E+10 | 0.468640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282337E+10 | 0.711677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.337244E+10 | 0.843388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.378662E+10 | 0.932124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384971E+10 | 0.947203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.349295E+10 | 0.876714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291327E+10 | 0.747079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200425E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161372E+10 | 0.285459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304009E+11 | 0.702294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140101E+10 | 0.185855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384971E+10 | 0.947203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.675830E+10 | 0.00 | 0.00 | 0.00 | 0.828868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.610919E+10 | 0.00 | 0.00 | 0.00 | 0.978767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677721E+10 | 0.00 | 0.00 | 0.00 | 0.140579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.663516E+10 | 0.00 | 0.00 | 0.00 | 0.198383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.767131E+10 | 0.00 | 0.00 | 0.00 | 0.307893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.911447E+10 | 0.00 | 0.00 | 0.00 | 0.390155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112907E+11 | 0.00 | 0.00 | 0.00 | 0.494033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119447E+11 | 0.00 | 0.00 | 0.00 | 0.522917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.983003E+10 | 0.00 | 0.00 | 0.00 | 0.415767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781471E+10 | 0.00 | 0.00 | 0.00 | 0.306876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.671269E+10 | 0.00 | 0.00 | 0.00 | 0.201071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677307E+10 | 0.00 | 0.00 | 0.00 | 0.122037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974315E+11 | 0.00 | 0.00 | 0.00 | 0.328047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.610919E+10 | 0.00 | 0.00 | 0.00 | 0.828868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119447E+11 | 0.00 | 0.00 | 0.00 | 0.522917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149939E+10 | 0.00 | 0.00 | 0.00 | 0.453721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140101E+10 | 0.00 | 0.00 | 0.00 | 0.525723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166275E+10 | 0.00 | 0.00 | 0.00 | 0.744006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198140E+10 | 0.00 | 0.00 | 0.00 | 0.107113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282337E+10 | 0.00 | 0.00 | 0.00 | 0.167170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.337244E+10 | 0.00 | 0.00 | 0.00 | 0.198991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.378662E+10 | 0.00 | 0.00 | 0.00 | 0.226966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384971E+10 | 0.00 | 0.00 | 0.00 | 0.230764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.349295E+10 | 0.00 | 0.00 | 0.00 | 0.203313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291327E+10 | 0.00 | 0.00 | 0.00 | 0.167848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200425E+10 | 0.00 | 0.00 | 0.00 | 0.108361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161372E+10 | 0.00 | 0.00 | 0.00 | 0.660717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304009E+11 | 0.00 | 0.00 | 0.00 | 0.164894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140101E+10 | 0.00 | 0.00 | 0.00 | 0.453721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384971E+10 | 0.00 | 0.00 | 0.00 | 0.230764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.719988E+10 | 0.583763E+09 | 0.00 | 67234790.88 | 0.00 | 0.00 | 0.124224E+11 | 0.00 | 3.60 |
February | 0.407044E+10 | 0.255961E+10 | 0.00 | 56021701.23 | 4693223.63 | 0.00 | 0.889088E+10 | 0.00 | 3.62 |
March | 0.222324E+10 | 0.643789E+10 | 0.00 | 52992531.49 | 21505546.76 | 0.00 | 0.667881E+10 | 0.00 | 3.65 |
April | 0.330366E+09 | 0.191889E+11 | 0.00 | 16176413.52 | 0.125162E+09 | 0.00 | 0.220123E+10 | 0.00 | 3.66 |
May | 13712396.14 | 0.445314E+11 | 0.00 | 5403857.47 | 0.788047E+09 | 0.00 | 0.109759E+09 | 0.00 | 3.72 |
June | 0.00 | 0.695070E+11 | 0.00 | 3157512.03 | 0.142068E+10 | 0.00 | 15728779.79 | 0.00 | 3.80 |
July | 0.00 | 0.933461E+11 | 0.00 | 2092402.57 | 0.241489E+10 | 0.00 | 29375491.06 | 0.00 | 3.83 |
August | 0.00 | 0.997629E+11 | 0.00 | 1148700.10 | 0.216394E+10 | 0.00 | 1660275.44 | 0.00 | 3.83 |
September | 261131.35 | 0.778886E+11 | 0.00 | 2562116.90 | 0.149859E+10 | 0.00 | 7883913.46 | 0.00 | 3.79 |
October | 28469007.60 | 0.478617E+11 | 0.00 | 5467110.31 | 0.710092E+09 | 0.00 | 0.163166E+09 | 0.00 | 3.72 |
November | 0.332049E+09 | 0.194637E+11 | 0.00 | 16435187.27 | 0.114358E+09 | 0.00 | 0.181015E+10 | 0.00 | 3.66 |
December | 0.343501E+10 | 0.443192E+10 | 0.00 | 53113546.76 | 6290011.45 | 0.00 | 0.873957E+10 | 0.00 | 3.62 |
Annual Sum or Average | 0.176334E+11 | 0.485563E+12 | 0.00 | 0.281806E+09 | 0.926823E+10 | 0.00 | 0.410706E+11 | 0.00 | 3.71 |
Minimum of Months | 0.00 | 0.583763E+09 | 0.00 | 1148700.10 | 0.00 | 0.00 | 1660275.44 | 0.00 | 3.60 |
Maximum of Months | 0.719988E+10 | 0.997629E+11 | 0.00 | 67234790.88 | 0.241489E+10 | 0.00 | 0.124224E+11 | 0.00 | 3.83 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262934E+10 | 58110279.42 | 0.00 | 86227195.82 | 0.00 | 0.00 | 0.219242E+11 | 0.00 | 7.45 |
February | 0.706568E+09 | 0.713793E+09 | 0.00 | 81450393.04 | 0.00 | 0.00 | 0.166985E+11 | 0.00 | 7.58 |
March | 0.147756E+09 | 0.253931E+10 | 0.00 | 91908763.15 | 0.00 | 0.00 | 0.140636E+11 | 0.00 | 7.80 |
April | 7434274.55 | 0.978771E+10 | 0.00 | 54473272.61 | 0.00 | 0.00 | 0.478150E+10 | 0.00 | 8.32 |
May | 0.00 | 0.250003E+11 | 0.00 | 16749762.15 | 0.00 | 0.00 | 0.647300E+09 | 0.00 | 8.97 |
June | 0.00 | 0.383856E+11 | 0.00 | 1410409.06 | 0.00 | 0.00 | 29931319.59 | 0.00 | 9.57 |
July | 0.00 | 0.456326E+11 | 0.00 | 1036937.61 | 233382.84 | 0.00 | 33662561.74 | 0.00 | 10.04 |
August | 0.00 | 0.467541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 |
September | 0.00 | 0.417319E+11 | 0.00 | 727095.69 | 0.00 | 0.00 | 11007158.73 | 0.00 | 9.67 |
October | 0.00 | 0.284384E+11 | 0.00 | 11681552.80 | 0.00 | 0.00 | 0.624893E+09 | 0.00 | 9.07 |
November | 11204324.66 | 0.101482E+11 | 0.00 | 47559489.44 | 0.00 | 0.00 | 0.416998E+10 | 0.00 | 8.30 |
December | 0.403661E+09 | 0.161054E+10 | 0.00 | 79699013.96 | 0.00 | 0.00 | 0.159954E+11 | 0.00 | 7.69 |
Annual Sum or Average | 0.390596E+10 | 0.250800E+12 | 0.00 | 0.472924E+09 | 233382.84 | 0.00 | 0.789800E+11 | 0.00 | 8.72 |
Minimum of Months | 0.00 | 58110279.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
Maximum of Months | 0.262934E+10 | 0.467541E+11 | 0.00 | 91908763.15 | 233382.84 | 0.00 | 0.219242E+11 | 0.00 | 10.12 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.527178E+11 | 0.489957E+10 | 0.906619E+11 | 0.680754E+10 | 0.775277E+11 |
February | 0.616204E+11 | 0.349102E+10 | 0.618128E+11 | 0.484189E+10 | 0.881952E+11 |
March | 0.846382E+11 | 0.221658E+10 | 0.447154E+11 | 0.418898E+10 | 0.122948E+12 |
April | 0.972713E+11 | -0.160958E+10 | -0.134460E+11 | 0.315856E+10 | 0.171317E+12 |
May | 0.108988E+12 | -0.645706E+10 | -0.922555E+11 | 0.646813E+09 | 0.254056E+12 |
June | 0.109163E+12 | -0.112544E+11 | -0.150250E+12 | -959040918.0 | 0.310627E+12 |
July | 0.107887E+12 | -0.149714E+11 | -0.188816E+12 | -0.359865E+10 | 0.368852E+12 |
August | 0.105495E+12 | -0.168342E+11 | -0.197860E+12 | -0.438909E+10 | 0.383923E+12 |
September | 0.863233E+11 | -0.138154E+11 | -0.165802E+12 | -0.124780E+10 | 0.330258E+12 |
October | 0.670516E+11 | -0.834907E+10 | -0.103749E+12 | -138702655.4 | 0.261993E+12 |
November | 0.498039E+11 | -0.316004E+10 | -0.183446E+11 | 0.261400E+10 | 0.174807E+12 |
December | 0.462283E+11 | 0.200700E+10 | 0.571550E+11 | 0.506382E+10 | 0.109074E+12 |
Annual Sum or Average | 0.977188E+12 | -0.638371E+11 | -0.676177E+12 | 0.169883E+11 | 0.265358E+13 |
Minimum of Months | 0.462283E+11 | -0.168342E+11 | -0.197860E+12 | -0.438909E+10 | 0.775277E+11 |
Maximum of Months | 0.109163E+12 | 0.489957E+10 | 0.906619E+11 | 0.680754E+10 | 0.383923E+12 |