Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:25:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1959.71 | 3833.90 | 3833.90 |
Net Site Energy | 1959.71 | 3833.90 | 3833.90 |
Total Source Energy | 4673.01 | 9142.09 | 9142.09 |
Net Source Energy | 4673.01 | 9142.09 | 9142.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 435.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 132.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.38 | 264.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 55.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1223.56 | 736.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 435.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 132.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.38 | 264.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 435.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 49.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 132.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.38 | 264.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 55.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1259.06 | 521.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 987.44 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2393.73 | 1440.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1259.06 | 521.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 987.44 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2393.73 | 1440.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1223.563 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1223.563 | 100.00 |
Total On-Site and Utility Electric Sources | 1223.563 | 100.00 |
Total Electricity End Uses | 1223.563 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 806.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6806.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 7.7280 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.0598 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.7280 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.0598 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.0912 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-JUL-11:09 | 04-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 01-MAR-19:10 |
Heating | 0.00 | 24447.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 34835.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22726.43 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8478.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2993.68 | 14621.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2097.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 73261.57 | 52645.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 24447.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 34835.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21698.93 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8478.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2993.68 | 14621.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 827.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1379.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1423.36 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 418.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.74 | 287.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 175.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3875.02 | 797.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2699.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 307.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 817.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.06 | 561.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 342.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7580.94 | 1561.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2699.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 307.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 817.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.06 | 561.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 342.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7580.94 | 1561.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.71 |
KITCHEN DIRECT AIR | 1.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.71 | 3.71 | 3.71 | 3.71 | 3.71 | 3.71 | 1.00 | 0.999990 | 3.71 |
PSZ-AC_2:2 | 1.60 | 1.60 | 1.60 | 1.60 | 1.60 | 1.60 | 1.00 | 1.00 | 1.60 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.71 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.60 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.71 | 6339.06 |
PSZ-AC_2:2_ADDAQ FAN | 1.60 | 1709.51 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.71 | 3.71 | 3.71 | 2.45 | 92130.42 | 104986.27 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.60 | 1.60 | 1.60 | 1.05 | 39672.33 | 64437.12 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.71 | 1.86 | 2.47 | 92130.42 | 46065.21 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.60 | 0.798802 | 1.07 | 39672.33 | 19836.17 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 104986.27 |
PSZ-AC_2:2 HEATING COIL | 64437.12 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 7.728 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 72.655 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.060 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1069.700 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2872.862 | 7.728 | 10.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2872.862 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1262.985 | 9.060 | 167.774 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1262.985 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.342 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5109 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 6 | 0.21862767E-07 | 0.34448908E-09 | 0.50649605E-08 | -0.99069094E-13 |
34 | 5 | -0.15485004E-03 | 0.31008008E-05 | -0.80011323E-04 | 0.50225397E-08 |
35 | 4 | 0.24987207 | 0.15775750E-02 | 0.84530116E-01 | -0.27712185E-04 |
36 | 3 | -6.4266483 | 0.50820490E-01 | -2.0899201 | 0.24901095E-01 |
37 | 2 | 38.099035 | 0.18692275 | 14.237681 | -0.30248143 |
38 | 1 | -78.418483 | 0.86852168E-01 | -28.218840 | 1.0332909 |
39 | 0 | 46.824353 | 0.17981083E-02 | 16.314603 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.569_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.569_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.569_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0712E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0605E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.9289E-004 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.1899E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.1505E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.7002E-003 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 7.5380E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.9092E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.4368E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.3549E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.5490E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4540E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.7451E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.7002E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0806E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.0808E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.1708E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.0777E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.4873E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.9398E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.7924E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.4751E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.9092E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.5380E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 42438.48823 | 50926.18588 | 3.09171 | 3.71006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 32.99900 | 1.71668E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 3431.79002 | 4118.14802 | 0.14727 | 1.33138 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 8.70000 | 6.99286E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 21551.66670 | 25862.00004 | 1.33134 | 1.59760 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.59700 | 1.71661E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 8.70000 | 6.99286E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 64918.88 | 3.71009 | 3.71009 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 50364.19 | 1.33138 | 1.33138 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 35168.92 | 1.59760 | 1.59760 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 46037.52 | 1.21700 | 1.21700 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.71006 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.59760 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.71006 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.71006 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.71006 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.71006 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.71009 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.71009 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99999 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.59760 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.59760 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.59760 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.59760 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.59760 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.59760 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.71009 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.59760 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.71009 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.71009 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6339.05675 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.71009 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.71009 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.71009 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.44866 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.71009 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.85505 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.47339 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 92130.42000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 46065.21000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 92130.42000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 104986.27377 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 104986.27377 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.59760 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.59760 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1709.51259 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.59760 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.59760 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.59760 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05442 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.59760 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.79880 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06507 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39672.33000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19836.16500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39672.33000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64437.11659 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 64437.11659 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 89493.4 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 38536.8 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_EAST_0.25 | N/A | 3.235 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_SOUTH_0.25 | N/A | 3.235 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | N/A | 3.235 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 4.1909756965E-002 | 0.1626244451 | Pass | Pass | 6.8587922473E-002 | 0.2389413458 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1566508833 | 0.5977156829 | Pass | Pass | 0.1555002337 | 0.4775467666 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4082217260 | 0.4054683581 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1228.98 | -30.9 | -554.0 | 25.96 | 2460.57 | 3130.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.569_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.235 | 0.251 | 0.276 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.569_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 3.235 | 0.251 | 0.276 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.569_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.235 | 0.251 | 0.276 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 3.235 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 3.235 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.7280 | 371.75 | 2872.86 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.27 | 0.0000 | Y | 32.50 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.0598 | 139.41 | 1262.99 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.59 | 0.0000 | Y | 17.21 |
Interior Lighting Total | 8.0912 | 511.15 | 4135.85 | 49.71 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 48.82 | 48.82 | 1.94 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.82 | 62.82 | 23.61 | |
Exterior Lighting Total | 2213.72 | 25.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 92130.42 | 64590.79 | 27539.63 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39672.33 | 27813.48 | 11858.85 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 89493.4 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 38536.8 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 104986.27 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 64437.12 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.71 | 6339.06 | 1708.60 | 1.00 | 1.18 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.60 | 1709.51 | 1070.05 | 1.00 | 1.35 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 42438.49 | 50926.19 | 136.99 | 3.092 | 3.710 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 23.98 | 0.01130 | 33.00 | 0.01717 | 1.331 | 0.00 |
KITCHEN | 21551.67 | 25862.00 | 185.52 | 1.331 | 1.598 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01037 | 32.60 | 0.01717 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 3431.79 | 4118.15 | 11.08 | 0.147 | 1.331 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 25.15 | 0.00572 | 8.70 | 0.00699 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.71 | 3.71 | 1.33 | 1.33 | 3.7101 | 3.7101 | 3.7101 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.60 | 1.60 | 1.22 | 1.22 | 1.5976 | 1.5976 | 1.5976 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 92130.420 | 64590.795 | 3.710090 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 46065.21 | 25861.26 | 2.473393 | 27.29 | 21.27 | 0.01340901 | 11.42 | 11.42 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 53.8280 | 23.98 | 0.01130284 | 60.5656 | 42388.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 104986.274 | 104986.274 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 104986.27 | 104986.27 | 3.710092 | 16.59 | 12.70 | 0.00755998 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 35.8853 | 21.00 | 0.00787740 | 50.8747 | 3415.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 39672.330 | 27813.477 | 1.597600 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19836.17 | 10390.67 | 1.065067 | 31.01 | 23.75 | 0.01554711 | 11.94 | 11.73 | 0.00850000 | 32.60 | 0.01716606 | 25.17 | 114.2653 | 25.99 | 0.01037039 | 49.3864 | 21551.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 64437.117 | 64437.117 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 64437.12 | 64437.12 | 1.597605 | 6.63 | 6.63 | 0.00669034 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 76.1767 | 25.15 | 0.00572302 | 28.8445 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 92130.420 | 64590.795 | 3.710090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.7667 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.710092 | 4.46227208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 46065.21 | 25861.26 | 1.0000 | 2.97484646 | 2.473393 | 27.29 | 21.27 | 0.01340901 | 61637.3 | 11.42 | 11.42 | 0.00850000 | 32914.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46065.21 | 33.20 | 0.01716721 | 25.32 | 1.33137743 | 53.8280 | 23.98 | 0.01130284 | 23.98 | 0.01130284 | 60.5656 | 42388.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 104986.274 | 104986.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.710092 | 4.46227208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 104986.27 | 104986.27 | 1.0000 | 4.46227208 | 3.710092 | 16.59 | 12.70 | 0.00755998 | 35806.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 104986.27 | 8.70 | 0.00699286 | 8.70 | 1.33137743 | 35.8853 | 21.00 | 0.00787740 | 21.00 | 0.00787740 | 50.8747 | 3415.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39672.330 | 27813.477 | 1.597600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.7413 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.597605 | 1.92150142 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19836.17 | 10390.67 | 1.0000 | 1.28099715 | 1.065067 | 31.01 | 23.75 | 0.01554711 | 70943.2 | 11.94 | 11.73 | 0.00850000 | 33443.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19836.17 | 32.60 | 0.01716606 | 25.17 | 1.21700195 | 114.2653 | 25.95 | 0.01037039 | 25.99 | 0.01037039 | 49.3864 | 21551.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64437.117 | 64437.117 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.597605 | 1.92150142 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 64437.12 | 64437.12 | 1.0000 | 1.92150142 | 1.597605 | 6.63 | 6.63 | 0.00669034 | 23474.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64437.12 | 8.70 | 0.00699286 | 8.70 | 1.21700195 | 76.1767 | 0.00 | 0.00572302 | 25.15 | 0.00572302 | 28.8445 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6711.00 | 4878.17 | 4551.67 |
KITCHEN | 7087.17 | 6860.33 | 6805.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7087.67 | 7120.67 | 6806.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 48.67 | 0.00 | 0.00 |
KITCHEN | 0.00 | 1114.33 | 0.00 | 806.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1154.17 | 0.00 | 806.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.331 | 0.895 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.081 | 0.034 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.169 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.785 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35510964.99 | 0.00 | 35510964.99 | 7206954.47 | 42717919.46 | 41986318.57 | 1432.45 | 7327.55 | 0.00 | 360.53 |
KITCHEN | 31607127.51 | 0.00 | 31607127.51 | 153239.30 | 31760366.81 | 38379373.44 | 4716.94 | 3980.53 | 62.54 | 1042.08 |
Total Facility | 67118092.51 | 0.00 | 67118092.51 | 7360193.77 | 74478286.27 | 80365692.01 | 4764.05 | 7332.91 | 62.54 | 1100.42 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3315 | 0.0000 | 1.3315 | 0.2753 | 1.6068 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1537 | 0.0000 | 1.1537 | 0.0039 | 1.1575 | 1.2170 | 3230.85 | 3956.15 | 0.00 |
Total Facility | 2.4852 | 0.0000 | 2.4852 | 0.2791 | 2.7643 | 2.5484 | 3230.85 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 51368841.86 | 0.00 | 51368841.86 | 41986318.57 | 1391.72 | 3.49 | 7364.79 | 360.53 |
PSZ-AC_2:2 | 45721758.39 | 0.00 | 45721758.39 | 38379373.44 | 1310.54 | 5.01 | 7444.45 | 1042.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9261 | 0.0000 | 1.9261 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6689 | 0.0000 | 1.6689 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 220.80 | 0.00 | 7326.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 5440.70 | 2788.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9261 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.7353 | 1.5646 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
Electricity:Building | 506.08 | 2873.83 | 01-JAN-01:20 | 28589.25 | 02-JAN-11:10 |
Electricity:Zone:DINING | 157.61 | 560.03 | 01-JAN-01:20 | 8723.27 | 02-JAN-17:30 |
Electricity:SpaceType:GENERAL | 499.14 | 2737.55 | 01-JAN-01:20 | 26446.15 | 02-JAN-11:10 |
InteriorLights:Electricity | 49.71 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 32.50 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 49.71 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 49.71 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 32.50 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 49.71 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 348.47 | 2313.80 | 01-JAN-01:20 | 20370.03 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.33 | 2147.51 | 01-JAN-01:10 | 17341.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 55.30 | 910.03 | 03-FEB-23:30 | 3219.34 | 02-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 124.19 | 1101.57 | 16-MAR-00:10 | 6531.68 | 29-JUL-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.57 | 0.00 | 01-JAN-11:10 | 1510.93 | 03-JAN-04:20 |
MedTempRefrigeration:Refrigeration:Electricity | 32.79 | 778.76 | 04-FEB-06:00 | 1076.23 | 01-JAN-01:20 |
ElectricityPurchased:Facility | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
ElectricityPurchased:Plant | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
Cogeneration:ElectricityPurchased | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
General:Cogeneration:ElectricityPurchased | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
ElectricityNet:Plant | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
Cogeneration:ElectricityNet | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
General:Cogeneration:ElectricityNet | 1223.56 | 5150.13 | 04-FEB-01:20 | 73261.57 | 14-JUL-11:10 |
Electricity:HVAC | 567.74 | 0.00 | 01-JAN-01:10 | 43432.21 | 14-JUL-11:30 |
Fans:Electricity | 132.02 | 0.00 | 01-JAN-01:10 | 8493.29 | 14-JUL-11:20 |
General:Fans:Electricity | 132.02 | 0.00 | 01-JAN-01:10 | 8493.29 | 14-JUL-11:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 435.72 | 0.00 | 01-JAN-00:50 | 35010.25 | 22-AUG-13:00 |
General:Cooling:Electricity | 435.72 | 0.00 | 01-JAN-00:50 | 35010.25 | 22-AUG-13:00 |
ExteriorLights:Electricity | 25.55 | 0.00 | 01-JAN-07:20 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.55 | 0.00 | 01-JAN-07:20 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.38 | 0.00 | 01-JAN-01:10 | 4740.23 | 15-DEC-07:30 |
Water Heater:WaterSystems:Electricity | 75.38 | 0.00 | 01-JAN-01:10 | 4740.23 | 15-DEC-07:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 24-FEB-09:20 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 24-FEB-09:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 736.15 | 2758.01 | 01-JAN-01:10 | 52645.81 | 04-FEB-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 1.57 | 0.00 | 01-JAN-00:10 | 29310.15 | 04-FEB-07:00 |
Heating:NaturalGas | 1.57 | 0.00 | 01-JAN-00:10 | 29310.15 | 04-FEB-07:00 |
General:Heating:NaturalGas | 1.57 | 0.00 | 01-JAN-00:10 | 29310.15 | 04-FEB-07:00 |
NaturalGas:Plant | 264.79 | 947.76 | 01-JAN-01:10 | 17327.12 | 09-JAN-08:00 |
WaterSystems:NaturalGas | 264.79 | 947.76 | 01-JAN-01:10 | 17327.12 | 09-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 264.79 | 947.76 | 01-JAN-01:10 | 17327.12 | 09-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 09-JUN-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 09-JUN-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2882.16 | 3085.51 | 04-FEB-01:10 | 196960.70 | 27-JUL-18:10 |
EnergyTransfer:Building | 876.34 | 1542.75 | 04-FEB-01:10 | 53530.50 | 29-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN | 461.99 | 1542.75 | 04-FEB-01:10 | 24149.18 | 11-AUG-11:00 |
Refrigeration:EnergyTransfer | 159.28 | 2965.53 | 03-FEB-23:30 | 7834.84 | 02-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.64 | 1482.76 | 03-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 79.64 | 1482.76 | 03-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.64 | 1482.76 | 03-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
EnergyTransfer:Plant | 258.81 | 1542.75 | 04-FEB-01:10 | 14668.72 | 23-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.49 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.15 | 1346.28 | 04-FEB-06:00 | 2238.70 | 01-JAN-01:20 |
EnergyTransfer:Zone:DINING | 414.35 | 0.00 | 01-JAN-01:10 | 32746.77 | 29-JUL-18:10 |
Heating:EnergyTransfer | 1.07 | 0.00 | 01-JAN-00:10 | 6930.58 | 10-SEP-23:10 |
Heating:EnergyTransfer:Zone:DINING | 1.07 | 0.00 | 01-JAN-00:10 | 6930.58 | 10-SEP-23:10 |
General:Heating:EnergyTransfer | 1.07 | 0.00 | 01-JAN-00:10 | 6930.58 | 10-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 1.07 | 0.00 | 01-JAN-00:10 | 6930.58 | 10-SEP-23:10 |
Cooling:EnergyTransfer | 795.63 | 0.00 | 01-JAN-01:10 | 50666.61 | 29-JUL-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 413.28 | 0.00 | 01-JAN-01:10 | 32746.77 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer | 795.63 | 0.00 | 01-JAN-01:10 | 50666.61 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 413.28 | 0.00 | 01-JAN-01:10 | 32746.77 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 382.35 | 0.00 | 01-JAN-01:10 | 20231.76 | 11-AUG-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 382.35 | 0.00 | 01-JAN-01:10 | 20231.76 | 11-AUG-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 179.16 | 0.00 | 01-JAN-01:10 | 12056.25 | 17-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 179.16 | 0.00 | 01-JAN-01:10 | 12056.25 | 17-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 179.16 | 0.00 | 01-JAN-01:10 | 12056.25 | 17-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 179.16 | 0.00 | 01-JAN-01:10 | 12056.25 | 17-JAN-07:10 |
EnergyTransfer:HVAC | 1747.01 | 0.00 | 01-JAN-00:50 | 138676.66 | 21-AUG-12:00 |
HeatingCoils:EnergyTransfer | 1.26 | 0.00 | 01-JAN-00:10 | 23448.12 | 04-FEB-07:00 |
CoolingCoils:EnergyTransfer | 1745.75 | 0.00 | 01-JAN-00:50 | 138676.66 | 21-AUG-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 179.16 | 0.00 | 01-JAN-01:10 | 12056.25 | 17-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 179.16 | 0.00 | 01-JAN-01:10 | 12056.25 | 17-JAN-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.073 | -413.277 | 0.000 | 0.000 | 207.121 | 32.500 | 93.832 | 40.642 | 0.000 | 21.593 | 34.750 | 0.000 | -8.025 | 0.000 | -10.210 | 0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -382.346 | 0.000 | 0.000 | 4.716 | 17.209 | 286.918 | 0.000 | 0.000 | 0.122 | 74.103 | 0.000 | 0.000 | 0.000 | -0.722 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.045 | 35.080 | 0.000 | 0.000 | 0.000 | -44.124 | -0.001 |
Total Facility | 0.000 | 0.000 | 1.073 | -795.624 | 0.000 | 0.000 | 211.837 | 49.710 | 380.750 | 40.642 | 0.000 | 30.760 | 143.932 | 0.000 | -8.025 | 0.000 | -55.056 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-APR-03:01 | 0.00 | 0.00 | 0.00 | -64213.27 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 64668.16 | 0.00 | -1320.38 | 0.00 | -114.55 | 0.00 |
KITCHEN | 03-FEB-04:01 | 0.00 | 0.00 | 0.00 | -58233.02 | 0.00 | 0.00 | 0.00 | 30.01 | 3472.64 | 0.00 | 0.00 | 0.00 | 55177.32 | 0.00 | -0.00 | 0.00 | -446.95 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-APR-03:01 | 0.00 | 0.00 | 0.00 | -111013.56 | 0.00 | 0.00 | 0.00 | 110.04 | 4372.65 | 0.00 | 0.00 | 827.47 | 107250.72 | 0.00 | -1320.38 | 0.00 | -226.95 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 10-SEP-23:01 | 0.00 | 0.00 | 9793.17 | 0.00 | 0.00 | 0.00 | 973.97 | 409.12 | 540.00 | 311.31 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12027.58 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-SEP-23:01 | -9194.60 | 9194.60 | 9793.17 | -9194.60 | 0.00 | 0.00 | 996.45 | 556.63 | 3034.59 | 311.31 | 0.00 | 361.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5858.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.7101 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.7101 | 0.3589 | 1.0000 | Not calculated | 1.3314 | 0.3589 | ||
PSZ-AC_2:2 | 1.5976 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5976 | 0.1143 | 1.0000 | Not calculated | 0.1826 | 0.1143 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.7101 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.7101 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3589 | ||
PSZ-AC_2:2 | 1.5976 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5976 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1143 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7101 | 3.7101 | 3.7101 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5976 | 1.5976 | 1.5976 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.7101 | 3.7101 | 3.7101 | 3.7101 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5976 | 1.5976 | 1.5976 | 1.5976 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7101 | 3.7101 | 3.7101 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5976 | 1.5976 | 1.5976 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.7101 | 3.7101 | 3.7101 | 3.7101 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5976 | 1.5976 | 1.5976 | 1.5976 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 806.67 |
Number of hours not met | 806.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.57 | 29310.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 435.72 | 35010.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 49.71 | 3339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.55 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 132.02 | 8493.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.38 | 4740.23 | 264.79 | 17327.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.57 | 1510.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.79 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 504.73 | 1223.56 |
Natural Gas | 469.79 | 736.15 |
Additional | 0.00 | 0.00 |
Total | 974.52 | 1959.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 97.25 |
Space Heating | 0.00 |
Space Cooling | 852.43 |
Fans (All) | 258.28 |
Service Water Heating | 147.48 |
Receptacle Equipment | 879.26 |
Miscellaneous (All) | 2393.73 |
Subtotal | 2393.73 |
Natural Gas [MJ/m2] | |
Space Heating | 3.08 |
Service Water Heating | 518.02 |
Miscellaneous (All) | 1440.17 |
Subtotal | 1440.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.54 |
Space Heating | 0.08 |
Space Cooling | 22.23 |
Fans (All) | 6.74 |
Service Water Heating | 17.36 |
Receptacle Equipment | 46.91 |
Miscellaneous | 4.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8005.67 | 753.00 | 1.33 | 0.00 | 0.00 |
KITCHEN | 6552.33 | 2030.83 | 176.83 | 0.00 | 0.00 |
ATTIC | 4699.50 | 1035.17 | 983.67 | 1186.50 | 855.17 |
Min | 4699.50 | 753.00 | 1.33 | 0.00 | 0.00 |
Max | 8005.67 | 2030.83 | 983.67 | 1186.50 | 855.17 |
Average | 6419.17 | 1273.00 | 387.28 | 395.50 | 285.06 |
Sum | 19257.50 | 3819.00 | 1161.83 | 1186.50 | 855.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822306.33 | 1897.00 | 18.67 | 0.00 | 0.00 |
KITCHEN | 15776.33 | 3456.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822306.33 | 3456.67 | 18.67 | 0.00 | 0.00 |
Average | 279360.89 | 1784.56 | 6.22 | 0.00 | 0.00 |
Sum | 838082.67 | 5353.67 | 18.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 2612.17 | 6147.50 | 0.33 | 0.00 | 0.00 |
KITCHEN | 809.50 | 7944.83 | 5.67 | 0.00 | 0.00 |
ATTIC | 2466.00 | 3651.67 | 755.50 | 645.17 | 1241.67 |
Min | 809.50 | 3651.67 | 0.33 | 0.00 | 0.00 |
Max | 2612.17 | 7944.83 | 755.50 | 645.17 | 1241.67 |
Average | 1962.56 | 5914.67 | 253.83 | 215.06 | 413.89 |
Sum | 5887.67 | 17744.00 | 761.50 | 645.17 | 1241.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 267638.00 | 556579.33 | 4.67 | 0.00 | 0.00 |
KITCHEN | 1732.00 | 17501.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 267638.00 | 556579.33 | 4.67 | 0.00 | 0.00 |
Average | 89790.00 | 191360.11 | 1.56 | 0.00 | 0.00 |
Sum | 269370.00 | 574080.33 | 4.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287268E+11 | 49951.18 | 06-JAN-04:01 | 22.20 | 19.56 | 0.150692E+11 | 14051.96 | 28-JAN-19:49 | 21.78 | 19.82 |
February | 0.273153E+11 | 52743.37 | 12-FEB-04:01 | 18.30 | 16.83 | 0.137046E+11 | 14052.65 | 18-FEB-19:10 | 23.30 | 21.31 |
March | 0.308891E+11 | 62153.49 | 12-MAR-03:01 | 21.10 | 15.45 | 0.153499E+11 | 14050.44 | 25-MAR-18:10 | 24.32 | 20.61 |
April | 0.327566E+11 | 64226.82 | 02-APR-03:01 | 17.02 | 12.71 | 0.148874E+11 | 14050.48 | 22-APR-18:10 | 24.90 | 20.79 |
May | 0.366857E+11 | 53178.14 | 08-MAY-03:01 | 23.30 | 18.59 | 0.154235E+11 | 14050.21 | 06-MAY-18:19 | 23.30 | 18.59 |
June | 0.374546E+11 | 43494.88 | 17-JUN-03:01 | 26.52 | 21.99 | 0.150099E+11 | 14050.59 | 24-JUN-18:00 | 26.70 | 24.69 |
July | 0.401900E+11 | 46833.48 | 02-JUL-03:01 | 24.90 | 21.02 | 0.153264E+11 | 14050.24 | 08-JUL-18:00 | 29.40 | 24.96 |
August | 0.398863E+11 | 36467.51 | 31-AUG-03:01 | 25.68 | 23.23 | 0.155236E+11 | 14050.43 | 12-AUG-18:49 | 25.68 | 23.23 |
September | 0.386731E+11 | 39384.81 | 05-SEP-03:01 | 23.30 | 21.69 | 0.149064E+11 | 14050.42 | 02-SEP-18:10 | 23.30 | 21.69 |
October | 0.380093E+11 | 55591.32 | 18-OCT-03:01 | 24.32 | 18.76 | 0.153300E+11 | 14050.43 | 21-OCT-18:10 | 25.40 | 19.40 |
November | 0.329718E+11 | 57079.43 | 11-NOV-04:01 | 17.20 | 14.49 | 0.147646E+11 | 14050.65 | 04-NOV-18:00 | 17.20 | 14.49 |
December | 0.297202E+11 | 56977.98 | 04-DEC-04:01 | 17.12 | 15.42 | 0.151047E+11 | 14051.97 | 02-DEC-19:49 | 17.12 | 15.42 |
Annual Sum or Average | 0.413279E+12 | 0.180400E+12 | ||||||||
Minimum of Months | 0.273153E+11 | 36467.51 | 17.02 | 12.71 | 0.137046E+11 | 14050.21 | 17.12 | 14.49 | ||
Maximum of Months | 0.401900E+11 | 64226.82 | 26.52 | 23.23 | 0.155236E+11 | 14052.65 | 29.40 | 24.96 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306348E+11 | 55925.24 | 27-JAN-04:01 | 14.32 | 8.34 | 0.105868E+11 | 6930.45 | 18-JAN-11:09 | 14.32 | 8.34 |
February | 0.278444E+11 | 58286.36 | 03-FEB-04:01 | 12.12 | 7.31 | 0.956438E+10 | 6930.43 | 06-FEB-11:20 | 22.60 | 16.88 |
March | 0.310992E+11 | 54465.79 | 15-MAR-03:01 | 12.20 | 8.80 | 0.105952E+11 | 6937.89 | 14-MAR-10:50 | 12.20 | 8.80 |
April | 0.309724E+11 | 47615.09 | 19-APR-03:01 | 15.00 | 11.82 | 0.102548E+11 | 6939.44 | 13-APR-10:00 | 15.00 | 11.82 |
May | 0.331563E+11 | 34176.01 | 08-MAY-03:01 | 23.30 | 18.59 | 0.105994E+11 | 6953.46 | 31-MAY-10:00 | 32.80 | 24.33 |
June | 0.326124E+11 | 25811.91 | 17-JUN-03:01 | 26.52 | 21.99 | 0.102711E+11 | 6973.07 | 06-JUN-10:00 | 26.52 | 21.99 |
July | 0.339501E+11 | 29148.78 | 04-JUL-03:21 | 23.05 | 20.94 | 0.106170E+11 | 6987.18 | 14-JUL-10:00 | 31.70 | 26.37 |
August | 0.337387E+11 | 25037.55 | 14-AUG-03:01 | 22.80 | 22.32 | 0.106206E+11 | 6980.17 | 04-AUG-10:00 | 22.80 | 22.32 |
September | 0.328439E+11 | 26344.56 | 05-SEP-03:01 | 23.30 | 21.69 | 0.102675E+11 | 6973.30 | 06-SEP-10:00 | 30.60 | 26.05 |
October | 0.332631E+11 | 32145.33 | 18-OCT-03:01 | 24.32 | 18.76 | 0.105998E+11 | 6977.03 | 04-OCT-10:00 | 24.32 | 18.76 |
November | 0.311287E+11 | 56268.93 | 13-NOV-04:01 | 12.80 | 8.34 | 0.102522E+11 | 6958.11 | 30-NOV-11:00 | 27.20 | 25.17 |
December | 0.311071E+11 | 57710.17 | 15-DEC-04:01 | 8.22 | 5.67 | 0.105875E+11 | 6930.43 | 21-DEC-11:00 | 20.00 | 16.20 |
Annual Sum or Average | 0.382351E+12 | 0.124816E+12 | ||||||||
Minimum of Months | 0.278444E+11 | 25037.55 | 8.22 | 5.67 | 0.956438E+10 | 6930.43 | 12.20 | 8.34 | ||
Maximum of Months | 0.339501E+11 | 58286.36 | 26.52 | 22.32 | 0.106206E+11 | 6987.18 | 32.80 | 26.37 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 16.65 | 13.10 | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 | 13.44 | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 | 18.63 | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 | 20.01 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 26.68 | 24.42 | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 26.83 | 23.72 | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 28.60 | 25.82 | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 27.05 | 24.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 27.93 | 23.96 | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 | 21.03 | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 | 21.22 | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.00 | 0.00 | 16.65 | 13.10 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.00 | 0.00 | 28.60 | 25.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 884950.79 | 1831.28 | 07-JAN-00:03 | 24.32 |
February | 435149.43 | 987.63 | 11-FEB-00:03 | 23.90 |
March | 1068771.62 | 1785.20 | 13-MAR-23:03 | 24.32 |
April | 6846189.45 | 3570.24 | 12-APR-23:03 | 25.60 |
May | 80416404.79 | 5655.58 | 31-MAY-23:02 | 26.87 |
June | 0.255386E+09 | 9659.06 | 10-JUN-23:01 | 29.32 |
July | 0.194151E+09 | 8520.06 | 31-JUL-23:02 | 28.68 |
August | 0.238906E+09 | 9015.59 | 02-AUG-23:01 | 28.90 |
September | 0.178546E+09 | 9788.80 | 10-SEP-23:01 | 29.40 |
October | 79880448.31 | 6178.88 | 03-OCT-23:02 | 27.12 |
November | 34244036.53 | 5361.95 | 03-NOV-23:02 | 26.70 |
December | 1840084.48 | 2558.94 | 09-DEC-00:03 | 24.90 |
Annual Sum or Average | 0.107260E+10 | |||
Minimum of Months | 435149.43 | 987.63 | 23.90 | |
Maximum of Months | 0.255386E+09 | 9788.80 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.289945E+10 | 2454.69 | 02-JAN-17:30 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.256330E+10 | 2454.69 | 01-FEB-17:49 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.276193E+10 | 2454.69 | 01-MAR-18:19 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.258178E+10 | 2454.69 | 01-APR-18:30 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.265546E+10 | 2454.69 | 01-MAY-18:40 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.259358E+10 | 2454.69 | 01-JUN-18:30 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.259413E+10 | 2454.69 | 01-JUL-18:00 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.270018E+10 | 2454.69 | 01-AUG-18:00 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.264942E+10 | 2454.69 | 01-SEP-18:30 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.277635E+10 | 2454.69 | 02-OCT-18:10 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.278843E+10 | 2454.69 | 01-NOV-17:30 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.293637E+10 | 2454.69 | 01-DEC-17:19 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.325004E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.256330E+10 | 2454.69 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.293637E+10 | 2454.69 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.145365E+10 | 885.05 | 02-JAN-10:09 | 0.275454E+11 | 17341.88 | 01-JAN-11:09 |
February | 0.131681E+10 | 885.05 | 01-FEB-10:09 | 0.248798E+11 | 17341.88 | 01-FEB-11:09 |
March | 0.147869E+10 | 885.05 | 01-MAR-10:09 | 0.275456E+11 | 17341.88 | 01-MAR-11:09 |
April | 0.141254E+10 | 885.05 | 01-APR-16:10 | 0.266569E+11 | 17341.88 | 01-APR-10:09 |
May | 0.146617E+10 | 885.05 | 01-MAY-09:09 | 0.275455E+11 | 17341.88 | 01-MAY-10:09 |
June | 0.142908E+10 | 885.05 | 01-JUN-09:09 | 0.266570E+11 | 17341.88 | 01-JUN-10:09 |
July | 0.144981E+10 | 885.05 | 01-JUL-16:10 | 0.275454E+11 | 17341.88 | 01-JUL-10:09 |
August | 0.147869E+10 | 885.05 | 01-AUG-09:09 | 0.275456E+11 | 17341.88 | 01-AUG-10:09 |
September | 0.141289E+10 | 885.05 | 01-SEP-09:09 | 0.266569E+11 | 17341.88 | 01-SEP-10:09 |
October | 0.145348E+10 | 885.05 | 02-OCT-09:09 | 0.275454E+11 | 17341.88 | 01-OCT-10:09 |
November | 0.140753E+10 | 885.05 | 01-NOV-09:09 | 0.266568E+11 | 17341.88 | 01-NOV-10:09 |
December | 0.144998E+10 | 885.05 | 01-DEC-10:09 | 0.275454E+11 | 17341.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.172093E+11 | 0.324326E+12 | ||||
Minimum of Months | 0.131681E+10 | 885.05 | 0.248798E+11 | 17341.88 | ||
Maximum of Months | 0.147869E+10 | 885.05 | 0.275456E+11 | 17341.88 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.289945E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214012E+09 | 0.288883E+10 |
February | 0.272721E+11 | 0.256330E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344125E+09 | 0.172904E+10 |
March | 0.305458E+11 | 0.276193E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408530E+09 | 0.165458E+10 |
April | 0.292871E+11 | 0.258178E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110187E+10 | 0.459569E+09 |
May | 0.303219E+11 | 0.265546E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244564E+10 | 60534399.40 |
June | 0.295292E+11 | 0.259358E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309633E+10 | 8455659.36 |
July | 0.300798E+11 | 0.259413E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371656E+10 | 25158620.02 |
August | 0.305458E+11 | 0.270018E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343562E+10 | 28458302.98 |
September | 0.292871E+11 | 0.264942E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307229E+10 | 16826885.85 |
October | 0.300980E+11 | 0.277635E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230296E+10 | 54516531.57 |
November | 0.290996E+11 | 0.278843E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114323E+10 | 0.797684E+09 |
December | 0.300798E+11 | 0.293637E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312022E+09 | 0.248636E+10 |
Annual Sum or Average | 0.356244E+12 | 0.325004E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215932E+11 | 0.102100E+11 |
Minimum of Months | 0.272721E+11 | 0.256330E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214012E+09 | 8455659.36 |
Maximum of Months | 0.305458E+11 | 0.293637E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371656E+10 | 0.288883E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.145365E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 451881.80 | 95183965.75 |
February | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 1041104.58 | 0.131001E+09 |
March | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1439491.29 | 0.133091E+09 |
April | 0.786997E+09 | 0.141254E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 5004844.43 | 65883246.23 |
May | 0.814802E+09 | 0.146617E+10 | 0.225868E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 17409211.34 | 39845699.94 |
June | 0.793501E+09 | 0.142908E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 20632663.39 | 15731926.07 |
July | 0.808298E+09 | 0.144981E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 18537212.41 | 13779279.68 |
August | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 21396119.13 | 12729853.63 |
September | 0.786997E+09 | 0.141289E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 20024416.39 | 15800409.60 |
October | 0.808786E+09 | 0.145348E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 11937021.84 | 25054761.43 |
November | 0.781956E+09 | 0.140753E+10 | 0.218581E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 3758398.40 | 74270791.34 |
December | 0.808298E+09 | 0.144998E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 805598.41 | 99478737.40 |
Annual Sum or Average | 0.957291E+10 | 0.172093E+11 | 0.265941E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.122438E+09 | 0.721850E+09 |
Minimum of Months | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 451881.80 | 12729853.63 |
Maximum of Months | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 21396119.13 | 0.133091E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102738E+10 | 0.282977E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616282E+09 | 0.267766E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577144E+09 | 0.373250E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672350E+09 | 0.444227E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579899E+09 | 0.438231E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655909E+09 | 0.441284E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833815E+09 | 0.525747E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850760E+09 | 0.405411E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739473E+09 | 0.394048E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947004E+09 | 0.321752E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767584E+09 | 0.254569E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777135E+09 | 0.263187E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904474E+10 | 0.441245E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577144E+09 | 0.254569E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102738E+10 | 0.525747E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2454.69 | 02-JAN-17:30 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2653.74 | 02-JAN-14:00 | 6905.54 | 24-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2454.69 | 01-FEB-17:49 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2376.78 | 02-FEB-14:00 | 7240.43 | 03-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 2454.69 | 01-MAR-18:19 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2940.89 | 13-MAR-17:03 | 6348.77 | 15-MAR-11:10 |
April | 30255.31 | 01-APR-18:10 | 2454.69 | 01-APR-18:30 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4226.18 | 17-APR-17:03 | 3355.57 | 02-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 2454.69 | 01-MAY-18:40 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5592.86 | 22-MAY-12:00 | 1276.47 | 07-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 2454.69 | 01-JUN-18:30 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4291.92 | 09-JUN-12:00 | 292.21 | 13-JUN-16:51 |
July | 30255.31 | 01-JUL-18:10 | 2454.69 | 01-JUL-18:00 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6022.94 | 29-JUL-18:06 | 744.96 | 14-JUL-17:55 |
August | 30255.31 | 05-AUG-18:10 | 2454.69 | 01-AUG-18:00 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593.87 | 23-AUG-12:00 | 1122.61 | 28-AUG-12:00 |
September | 30255.31 | 02-SEP-18:10 | 2454.69 | 01-SEP-18:30 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4650.15 | 13-SEP-12:00 | 559.70 | 05-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 2454.69 | 02-OCT-18:10 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4662.76 | 03-OCT-12:00 | 963.85 | 28-OCT-06:10 |
November | 30255.31 | 04-NOV-18:10 | 2454.69 | 01-NOV-17:30 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2983.03 | 17-NOV-13:00 | 5008.87 | 12-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 2454.69 | 01-DEC-17:19 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.79 | 08-DEC-14:00 | 7204.79 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.79 | 292.21 | |||||
Maximum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6022.94 | 7240.43 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 885.05 | 02-JAN-10:09 | 14079.00 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 17.19 | 07-JAN-13:00 | 448.60 | 24-JAN-02:30 |
February | 813.01 | 04-FEB-19:10 | 885.05 | 01-FEB-10:09 | 14079.00 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 20.74 | 02-FEB-14:00 | 618.74 | 04-FEB-04:40 |
March | 813.01 | 04-MAR-19:10 | 885.05 | 01-MAR-10:09 | 14079.00 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 25.97 | 13-MAR-16:53 | 625.01 | 16-MAR-02:00 |
April | 813.01 | 01-APR-18:10 | 885.05 | 01-APR-16:10 | 14079.00 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 36.44 | 15-APR-16:53 | 278.85 | 23-APR-02:10 |
May | 813.01 | 06-MAY-18:10 | 885.05 | 01-MAY-09:09 | 14079.00 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 59.39 | 22-MAY-14:41 | 226.17 | 08-MAY-01:00 |
June | 813.01 | 03-JUN-18:10 | 885.05 | 01-JUN-09:09 | 14079.00 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 83.32 | 16-JUN-23:12 | 210.75 | 18-JUN-02:50 |
July | 813.01 | 01-JUL-18:10 | 885.05 | 01-JUL-16:10 | 14079.00 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 40.43 | 27-JUL-14:00 | 151.15 | 04-JUL-02:55 |
August | 813.01 | 05-AUG-18:10 | 885.05 | 01-AUG-09:09 | 14079.00 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 60.21 | 26-AUG-23:40 | 248.58 | 14-AUG-02:50 |
September | 813.01 | 02-SEP-18:10 | 885.05 | 01-SEP-09:09 | 14079.00 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 58.52 | 23-SEP-24:00 | 141.70 | 27-SEP-02:50 |
October | 813.01 | 07-OCT-18:10 | 885.05 | 02-OCT-09:09 | 14079.00 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 35.89 | 03-OCT-12:55 | 212.53 | 17-OCT-02:10 |
November | 813.01 | 04-NOV-18:10 | 885.05 | 01-NOV-09:09 | 14079.00 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 18.40 | 03-NOV-13:00 | 490.02 | 12-NOV-04:00 |
December | 813.01 | 02-DEC-19:10 | 885.05 | 01-DEC-10:09 | 14079.00 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 22.90 | 10-DEC-15:00 | 597.66 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 17.19 | 141.70 | ||||||
Maximum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 83.32 | 625.01 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2018.49 | 27-JAN-03:40 | 6703.73 | 17-JAN-13:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1923.62 | 28-FEB-07:05 | 6625.68 | 22-FEB-14:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.55 | 02-MAR-04:00 | 7644.31 | 21-MAR-12:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.49 | 09-APR-06:53 | 7723.06 | 10-APR-12:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1279.70 | 02-MAY-05:50 | 7760.43 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1379.63 | 10-JUN-03:10 | 7819.65 | 09-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.23 | 15-JUL-03:45 | 7965.90 | 07-JUL-12:45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.38 | 31-AUG-04:00 | 7417.75 | 30-AUG-12:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1431.31 | 12-SEP-02:40 | 7383.19 | 30-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.65 | 22-OCT-04:00 | 7654.95 | 06-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.24 | 07-NOV-06:40 | 6003.13 | 10-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1972.35 | 13-DEC-06:00 | 5767.79 | 04-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1279.70 | 5767.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2018.49 | 7965.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49951.18 | 06-JAN-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 |
February | 52743.37 | 12-FEB-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.46 |
March | 62153.49 | 12-MAR-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.71 |
April | 64226.82 | 02-APR-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.55 |
May | 53178.14 | 08-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.22 |
June | 43494.88 | 17-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 0.00 |
July | 46833.48 | 02-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 36467.51 | 31-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39384.81 | 05-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
October | 55591.32 | 18-OCT-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.77 |
November | 57079.43 | 11-NOV-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.62 |
December | 56977.98 | 04-DEC-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 36467.51 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64226.82 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 323.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 55925.24 | 27-JAN-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58286.36 | 03-FEB-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 446.95 |
March | 54465.79 | 15-MAR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 482.70 |
April | 47615.09 | 19-APR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 170.84 |
May | 34176.01 | 08-MAY-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 149.73 |
June | 25811.91 | 17-JUN-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 43.85 |
July | 29148.78 | 04-JUL-03:21 | 0.00 | 210.08 | 22872.64 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 95.50 |
August | 25037.55 | 14-AUG-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 175.01 |
September | 26344.56 | 05-SEP-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 |
October | 32145.33 | 18-OCT-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 |
November | 56268.93 | 13-NOV-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 355.31 |
December | 57710.17 | 15-DEC-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 495.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25037.55 | 0.00 | 210.08 | 22872.64 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58286.36 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 495.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.78 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.31 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.13 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.65 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.14 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.66 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 982.25 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.75 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.39 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.52 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.51 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.31 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.825657E+11 | 63256.08 | 02-JAN-13:00 | 0.644636E+11 | 42907.12 | 21-JAN-11:50 |
February | 0.781848E+11 | 62714.47 | 11-FEB-11:50 | 0.583484E+11 | 52645.81 | 04-FEB-07:10 |
March | 0.895015E+11 | 62195.15 | 14-MAR-10:39 | 0.639308E+11 | 46839.29 | 16-MAR-07:10 |
April | 0.936086E+11 | 66112.22 | 13-APR-11:00 | 0.604875E+11 | 42702.49 | 01-APR-10:20 |
May | 0.109081E+12 | 68646.40 | 31-MAY-11:09 | 0.615923E+11 | 42536.87 | 06-MAY-10:20 |
June | 0.115055E+12 | 70162.07 | 06-JUN-11:09 | 0.589583E+11 | 42414.38 | 04-JUN-10:39 |
July | 0.121655E+12 | 73261.57 | 14-JUL-11:09 | 0.604132E+11 | 42345.39 | 01-JUL-10:09 |
August | 0.121887E+12 | 71948.27 | 23-AUG-11:09 | 0.608374E+11 | 42386.97 | 26-AUG-10:30 |
September | 0.115665E+12 | 71615.85 | 22-SEP-11:50 | 0.593810E+11 | 42514.75 | 30-SEP-10:20 |
October | 0.111903E+12 | 70716.75 | 03-OCT-11:30 | 0.622257E+11 | 42663.74 | 28-OCT-10:39 |
November | 0.971822E+11 | 67440.99 | 30-NOV-18:40 | 0.612211E+11 | 42778.28 | 25-NOV-11:20 |
December | 0.872753E+11 | 60953.68 | 08-DEC-11:00 | 0.642902E+11 | 42886.13 | 25-DEC-11:09 |
Annual Sum or Average | 0.122356E+13 | 0.736149E+12 | ||||
Minimum of Months | 0.781848E+11 | 60953.68 | 0.583484E+11 | 42345.39 | ||
Maximum of Months | 0.121887E+12 | 73261.57 | 0.644636E+11 | 52645.81 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.435311E+10 | 0.253493E+10 | 0.381711E+11 | 0.00 | 0.949626E+10 | 37879553.69 | 0.00 | 0.169695E+11 | 0.00 | 0.00 | 0.00 | 0.638060E+10 | 0.00 |
February | 0.388011E+10 | 0.215563E+10 | 0.344772E+11 | 0.00 | 0.864902E+10 | 34213790.43 | 0.00 | 0.190331E+11 | 0.00 | 0.00 | 0.00 | 0.577458E+10 | 0.00 |
March | 0.424062E+10 | 0.220552E+10 | 0.381714E+11 | 0.00 | 0.972807E+10 | 37879553.69 | 0.00 | 0.240232E+11 | 0.00 | 0.00 | 0.00 | 0.644898E+10 | 0.00 |
April | 0.399432E+10 | 0.195734E+10 | 0.369399E+11 | 0.00 | 0.976990E+10 | 36657632.61 | 0.00 | 0.301891E+11 | 0.00 | 0.00 | 0.00 | 0.619291E+10 | 0.00 |
May | 0.412163E+10 | 0.186284E+10 | 0.381712E+11 | 0.00 | 0.112867E+11 | 37879553.69 | 0.00 | 0.424748E+11 | 0.00 | 0.00 | 0.00 | 0.641450E+10 | 0.00 |
June | 0.402265E+10 | 0.173021E+10 | 0.369400E+11 | 0.00 | 0.123638E+11 | 36657632.61 | 0.00 | 0.491291E+11 | 0.00 | 0.00 | 0.00 | 0.623532E+10 | 0.00 |
July | 0.404394E+10 | 0.181104E+10 | 0.381711E+11 | 0.00 | 0.132905E+11 | 37879553.69 | 0.00 | 0.531709E+11 | 0.00 | 0.00 | 0.00 | 0.637016E+10 | 0.00 |
August | 0.417887E+10 | 0.195183E+10 | 0.381714E+11 | 0.00 | 0.132640E+11 | 37879553.69 | 0.00 | 0.530670E+11 | 0.00 | 0.00 | 0.00 | 0.644848E+10 | 0.00 |
September | 0.406232E+10 | 0.205961E+10 | 0.369399E+11 | 0.00 | 0.124479E+11 | 36657632.61 | 0.00 | 0.493303E+11 | 0.00 | 0.00 | 0.00 | 0.619356E+10 | 0.00 |
October | 0.422983E+10 | 0.231178E+10 | 0.381711E+11 | 0.00 | 0.116772E+11 | 37879553.69 | 0.00 | 0.443780E+11 | 0.00 | 0.00 | 0.00 | 0.637784E+10 | 0.00 |
November | 0.419596E+10 | 0.240097E+10 | 0.369398E+11 | 0.00 | 0.103073E+11 | 36657632.61 | 0.00 | 0.325980E+11 | 0.00 | 0.00 | 0.00 | 0.617419E+10 | 0.00 |
December | 0.438636E+10 | 0.256946E+10 | 0.381711E+11 | 0.00 | 0.973833E+10 | 37879553.69 | 0.00 | 0.213595E+11 | 0.00 | 0.00 | 0.00 | 0.637244E+10 | 0.00 |
Annual Sum or Average | 0.497097E+11 | 0.255512E+11 | 0.449435E+12 | 0.00 | 0.132019E+12 | 0.446001E+09 | 0.00 | 0.435722E+12 | 0.00 | 0.00 | 0.00 | 0.753835E+11 | 0.00 |
Minimum of Months | 0.388011E+10 | 0.173021E+10 | 0.344772E+11 | 0.00 | 0.864902E+10 | 34213790.43 | 0.00 | 0.169695E+11 | 0.00 | 0.00 | 0.00 | 0.577458E+10 | 0.00 |
Maximum of Months | 0.438636E+10 | 0.256946E+10 | 0.381714E+11 | 0.00 | 0.132905E+11 | 37879553.69 | 0.00 | 0.531709E+11 | 0.00 | 0.00 | 0.00 | 0.644898E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.256230E+09 | 0.00 | 0.243076E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.497580E+09 | 0.00 | 0.218123E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.344157E+09 | 0.00 | 0.236870E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.218749E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.216926E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.203457E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.205135E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.209376E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.207684E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.223260E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 68051103.85 | 0.00 | 0.225404E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.407458E+09 | 0.00 | 0.239830E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.157348E+10 | 0.00 | 0.264789E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.203457E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.497580E+09 | 0.00 | 0.243076E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3339.74 | 02-JAN-17:30 | 2213.72 | 01-JAN-06:10 | 24333.76 | 01-JAN-11:09 | 0.00 | 6937.02 | 02-JAN-13:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3339.74 | 01-FEB-17:49 | 2213.72 | 01-FEB-06:10 | 24333.76 | 01-FEB-11:09 | 0.00 | 6255.67 | 11-FEB-13:00 | 17.86 | 24-FEB-09:20 | 0.00 | 01-FEB-00:10 |
March | 3339.74 | 01-MAR-18:19 | 2213.72 | 01-MAR-06:10 | 24333.76 | 01-MAR-11:09 | 0.00 | 6252.09 | 13-MAR-11:00 | 17.86 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 3339.74 | 01-APR-18:30 | 2213.72 | 01-APR-05:10 | 24333.76 | 01-APR-10:09 | 0.00 | 7108.71 | 13-APR-11:00 | 17.86 | 25-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 3339.74 | 01-MAY-18:40 | 2213.72 | 01-MAY-05:10 | 24333.76 | 01-MAY-10:09 | 0.00 | 7831.72 | 31-MAY-12:00 | 17.86 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 3339.74 | 01-JUN-18:30 | 2213.72 | 01-JUN-05:10 | 24333.76 | 01-JUN-10:09 | 0.00 | 8085.11 | 28-JUN-11:00 | 17.86 | 13-JUN-16:49 | 0.00 | 01-JUN-00:10 |
July | 3339.74 | 01-JUL-18:00 | 2213.72 | 01-JUL-05:10 | 24333.76 | 01-JUL-10:09 | 0.00 | 8493.29 | 14-JUL-11:20 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 3339.74 | 01-AUG-18:00 | 2213.72 | 01-AUG-05:10 | 24333.76 | 01-AUG-10:09 | 0.00 | 8436.70 | 21-AUG-11:00 | 17.86 | 01-AUG-10:30 | 0.00 | 01-AUG-00:10 |
September | 3339.74 | 01-SEP-18:30 | 2213.72 | 01-SEP-05:10 | 24333.76 | 01-SEP-10:09 | 0.00 | 8298.98 | 18-SEP-17:00 | 17.86 | 02-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 3339.74 | 02-OCT-18:10 | 2213.72 | 01-OCT-05:10 | 24333.76 | 01-OCT-10:09 | 0.00 | 8038.92 | 02-OCT-11:00 | 17.86 | 09-OCT-11:39 | 0.00 | 01-OCT-00:10 |
November | 3339.74 | 01-NOV-17:30 | 2213.72 | 01-NOV-05:10 | 24333.76 | 01-NOV-10:09 | 0.00 | 7245.19 | 30-NOV-12:20 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 3339.74 | 01-DEC-17:19 | 2213.72 | 01-DEC-06:10 | 24333.76 | 01-DEC-11:09 | 0.00 | 6023.22 | 08-DEC-12:00 | 17.86 | 02-DEC-09:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 6023.22 | 17.86 | 0.00 | ||||||
Maximum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 8493.29 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 28568.50 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4739.65 | 26-JAN-07:19 | 0.00 |
February | 26421.86 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4737.81 | 27-FEB-07:19 | 0.00 |
March | 26081.16 | 13-MAR-12:00 | 0.00 | 0.00 | 0.00 | 4739.79 | 16-MAR-06:10 | 0.00 |
April | 29434.11 | 13-APR-11:00 | 0.00 | 0.00 | 0.00 | 4736.85 | 19-APR-06:49 | 0.00 |
May | 32586.60 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4736.65 | 19-MAY-18:30 | 0.00 |
June | 32748.10 | 08-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.67 | 15-JUN-18:30 | 0.00 |
July | 34944.41 | 14-JUL-11:30 | 0.00 | 0.00 | 0.00 | 4736.72 | 27-JUL-06:30 | 0.00 |
August | 35010.25 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 4736.61 | 30-AUG-18:30 | 0.00 |
September | 33764.31 | 22-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.58 | 25-SEP-18:00 | 0.00 |
October | 33133.60 | 03-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4736.31 | 23-OCT-18:00 | 0.00 |
November | 29594.61 | 30-NOV-12:20 | 0.00 | 0.00 | 0.00 | 4738.35 | 27-NOV-07:40 | 0.00 |
December | 25023.54 | 08-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4740.23 | 15-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 25023.54 | 0.00 | 0.00 | 0.00 | 4736.31 | 0.00 | ||
Maximum of Months | 35010.25 | 0.00 | 0.00 | 0.00 | 4740.23 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 63256.08 | 02-JAN-13:00 | 2112.39 | 21119.10 | 0.00 | 0.00 | 6937.02 | 17.86 | 0.00 | 28568.50 | 0.00 |
February | 62714.47 | 11-FEB-11:50 | 1877.68 | 24333.76 | 0.00 | 0.00 | 5663.21 | 17.86 | 0.00 | 24360.25 | 0.00 |
March | 62195.15 | 14-MAR-10:39 | 2112.39 | 24333.76 | 0.00 | 0.00 | 5536.22 | 17.86 | 0.00 | 23947.82 | 0.00 |
April | 66112.22 | 13-APR-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7108.71 | 17.86 | 0.00 | 29434.11 | 0.00 |
May | 68646.40 | 31-MAY-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7373.86 | 17.86 | 0.00 | 31241.88 | 0.00 |
June | 70162.07 | 06-JUN-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7864.23 | 17.86 | 0.00 | 32235.55 | 0.00 |
July | 73261.57 | 14-JUL-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 8478.89 | 17.86 | 0.00 | 34835.01 | 0.00 |
August | 71948.27 | 23-AUG-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 8091.54 | 17.86 | 0.00 | 33788.66 | 0.00 |
September | 71615.85 | 22-SEP-11:50 | 2112.39 | 22726.43 | 0.00 | 0.00 | 8232.45 | 17.86 | 0.00 | 33651.47 | 0.00 |
October | 70716.75 | 03-OCT-11:30 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7991.06 | 17.86 | 0.00 | 32998.71 | 0.00 |
November | 67440.99 | 30-NOV-18:40 | 3339.74 | 20315.44 | 2213.72 | 0.00 | 6923.01 | 17.86 | 0.00 | 28530.31 | 0.00 |
December | 60953.68 | 08-DEC-11:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 5294.66 | 17.86 | 0.00 | 22949.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 60953.68 | 1877.68 | 20315.44 | 0.00 | 0.00 | 5294.66 | 17.86 | 0.00 | 22949.63 | 0.00 | |
Maximum of Months | 73261.57 | 3339.74 | 24333.76 | 2213.72 | 0.00 | 8478.89 | 17.86 | 0.00 | 34835.01 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 11289.61 | 25-JAN-06:00 | 0.00 | 17327.12 | 09-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 29310.15 | 04-FEB-06:00 | 0.00 | 17302.83 | 02-FEB-07:49 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 17795.56 | 16-MAR-05:00 | 0.00 | 17236.42 | 01-MAR-07:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 17054.20 | 03-APR-18:30 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 16878.49 | 01-MAY-18:40 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16701.08 | 01-JUN-18:19 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16600.64 | 03-JUL-18:19 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16677.45 | 31-AUG-18:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 16812.41 | 29-SEP-18:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 17012.97 | 31-OCT-18:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 7663.53 | 27-NOV-06:49 | 0.00 | 17191.35 | 27-NOV-07:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 13725.45 | 15-DEC-06:00 | 0.00 | 17301.90 | 27-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16600.64 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 29310.15 | 0.00 | 17327.12 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.68 | 0.00 | 24.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.72 | 0.00 | 24.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.71 | 0.00 | 24.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.75 | 0.00 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.87 | 0.00 | 24.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.99 | 0.00 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.00 | 0.00 | 25.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.05 | 0.00 | 25.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.04 | 0.00 | 25.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.97 | 0.00 | 24.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.85 | 0.00 | 24.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.74 | 0.00 | 24.74 |
Annual Sum or Average | 0.00 | 0.00 | 48.67 | 24.90 | 0.00 | 24.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.68 | 0.00 | 24.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.05 | 0.00 | 25.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 30.30 | 0.00 | 30.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 30.27 | 0.17 | 30.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 30.38 | 0.00 | 30.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 30.67 | 0.00 | 30.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 29.18 | 19.00 | 28.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 157.50 | 27.67 | 128.67 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 282.83 | 27.52 | 249.50 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 246.50 | 27.57 | 213.00 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 155.67 | 27.72 | 125.67 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 28.28 | 54.83 | 27.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 29.15 | 15.50 | 28.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 30.39 | 0.33 | 30.33 |
Annual Sum or Average | 0.00 | 0.00 | 1114.33 | 28.04 | 806.67 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.52 | 0.00 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 282.83 | 30.67 | 249.50 | 30.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 266.17 | 23.23 | 465.83 | 23.72 | 165.17 | 23.78 |
February | 223.00 | 23.45 | 454.33 | 23.83 | 159.83 | 23.87 |
March | 263.67 | 23.56 | 514.17 | 23.88 | 201.67 | 23.93 |
April | 218.67 | 24.09 | 581.83 | 24.07 | 213.33 | 24.09 |
May | 430.83 | 24.15 | 611.00 | 24.13 | 430.83 | 24.13 |
June | 572.67 | 24.16 | 592.00 | 24.16 | 572.67 | 24.16 |
July | 590.00 | 24.15 | 609.00 | 24.15 | 590.00 | 24.15 |
August | 602.00 | 24.15 | 612.00 | 24.15 | 602.00 | 24.15 |
September | 569.17 | 24.15 | 590.00 | 24.14 | 569.17 | 24.15 |
October | 447.50 | 24.15 | 610.00 | 24.13 | 447.50 | 24.14 |
November | 371.17 | 23.97 | 556.17 | 24.03 | 347.50 | 24.05 |
December | 323.33 | 23.52 | 514.67 | 23.82 | 252.00 | 23.87 |
Annual Sum or Average | 4878.17 | 23.98 | 6711.00 | 24.04 | 4551.67 | 24.07 |
Minimum of Months | 218.67 | 23.23 | 454.33 | 23.72 | 159.83 | 23.78 |
Maximum of Months | 602.00 | 24.16 | 612.00 | 24.16 | 602.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 504.50 | 25.88 | 589.67 | 25.78 | 493.50 | 25.84 |
February | 486.50 | 25.85 | 528.17 | 25.84 | 473.50 | 25.89 |
March | 548.83 | 25.91 | 589.67 | 25.88 | 539.33 | 25.92 |
April | 580.83 | 26.00 | 590.00 | 25.99 | 580.83 | 26.00 |
May | 611.00 | 26.04 | 611.00 | 26.04 | 611.00 | 26.04 |
June | 592.00 | 26.27 | 592.00 | 26.27 | 592.00 | 26.27 |
July | 609.00 | 26.50 | 609.00 | 26.50 | 609.00 | 26.50 |
August | 612.00 | 26.44 | 612.00 | 26.44 | 612.00 | 26.44 |
September | 590.00 | 26.27 | 590.00 | 26.27 | 590.00 | 26.27 |
October | 610.00 | 26.11 | 610.00 | 26.11 | 610.00 | 26.11 |
November | 569.17 | 26.00 | 583.33 | 25.99 | 565.00 | 26.00 |
December | 546.50 | 25.81 | 582.33 | 25.81 | 529.17 | 25.86 |
Annual Sum or Average | 6860.33 | 26.10 | 7087.17 | 26.09 | 6805.33 | 26.10 |
Minimum of Months | 486.50 | 25.81 | 528.17 | 25.78 | 473.50 | 25.84 |
Maximum of Months | 612.00 | 26.50 | 612.00 | 26.50 | 612.00 | 26.50 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.62535 | 55.99304 | 0.50416 | 11.63433 |
February | 551.00000 | 23.75436 | 55.94212 | 0.54096 | 12.30664 |
March | 612.00000 | 23.80070 | 57.85222 | 0.56982 | 13.01249 |
April | 590.00000 | 24.04963 | 61.15200 | 0.66826 | 14.61180 |
May | 611.00000 | 24.11159 | 67.24950 | -0.0868 | 5.45949 |
June | 592.00000 | 24.15375 | 70.49162 | -0.0359 | 5.53747 |
July | 609.00000 | 24.14485 | 70.31982 | -0.0210 | 5.47806 |
August | 612.00000 | 24.15170 | 70.88947 | -0.0201 | 5.52037 |
September | 590.00000 | 24.14218 | 69.91569 | -0.0214 | 5.52535 |
October | 610.00000 | 24.11602 | 67.44186 | 0.75780 | 17.28722 |
November | 591.00000 | 23.97685 | 63.92342 | 0.67555 | 15.29625 |
December | 609.00000 | 23.71705 | 60.23742 | 0.56229 | 12.88973 |
Annual Sum or Average | 7187.00000 | 23.97946 | 64.33113 | 0.33957 | 10.36401 |
Minimum of Months | 551.00000 | 23.62535 | 55.94212 | -0.0868 | 5.45949 |
Maximum of Months | 612.00000 | 24.15375 | 70.88947 | 0.75780 | 17.28722 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.55704 | 51.88740 | 1.15098 | 34.47847 |
February | 551.00000 | 25.65786 | 51.88928 | 1.18097 | 35.95401 |
March | 612.00000 | 25.70074 | 53.38924 | 1.20804 | 37.08547 |
April | 590.00000 | 25.98263 | 56.54588 | 1.31860 | 41.42684 |
May | 611.00000 | 26.04095 | 61.53065 | 0.83842 | 20.31892 |
June | 592.00000 | 26.26932 | 64.48692 | 0.95699 | 25.26457 |
July | 609.00000 | 26.50141 | 64.79825 | 1.05525 | 29.82149 |
August | 612.00000 | 26.43552 | 64.99873 | 1.02165 | 28.25999 |
September | 590.00000 | 26.27200 | 64.17761 | 0.96466 | 25.60025 |
October | 610.00000 | 26.11170 | 61.80585 | 1.41629 | 46.46960 |
November | 591.00000 | 25.92297 | 58.09394 | 1.31939 | 41.88148 |
December | 609.00000 | 25.61986 | 54.92027 | 1.19827 | 36.74957 |
Annual Sum or Average | 7187.00000 | 26.00777 | 59.08415 | 1.13530 | 33.58726 |
Minimum of Months | 551.00000 | 25.55704 | 51.88740 | 0.83842 | 20.31892 |
Maximum of Months | 612.00000 | 26.50141 | 64.99873 | 1.41629 | 46.46960 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.359744E+11 | 0.101933E+11 | 454.66 | 0.208911E+11 | 0.150833E+11 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:10 | 100985.90 | 07-JAN-04:01 | 55387.22 | 06-JAN-04:01 | 59699.29 | 07-JAN-04:01 | 25119.24 | 07-JAN-04:01 | 0.00 | 01-JAN-00:10 |
February | 0.412208E+11 | 0.115961E+11 | 454.41 | 0.250998E+11 | 0.161210E+11 | 0.00 | 1.00 | 02-FEB-04:02 | 0.00 | 01-FEB-00:05 | 100985.90 | 11-FEB-04:01 | 58918.75 | 16-FEB-04:01 | 56887.36 | 11-FEB-04:01 | 25119.24 | 11-FEB-04:01 | 0.00 | 01-FEB-00:05 |
March | 0.527619E+11 | 0.145559E+11 | 530.22 | 0.300844E+11 | 0.226775E+11 | 0.00 | 1.00 | 03-MAR-04:01 | 0.00 | 01-MAR-00:03 | 100985.90 | 14-MAR-03:01 | 67453.90 | 12-MAR-03:01 | 59541.47 | 27-MAR-03:01 | 25119.24 | 05-MAR-04:01 | 0.00 | 01-MAR-00:03 |
April | 0.678698E+11 | 0.184528E+11 | 580.93 | 0.400175E+11 | 0.278522E+11 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 100985.90 | 12-APR-03:01 | 64406.35 | 18-APR-03:01 | 58796.66 | 13-APR-03:02 | 25119.24 | 12-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.987413E+11 | 0.256388E+11 | 613.03 | 0.528833E+11 | 0.458580E+11 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 100985.90 | 14-MAY-03:02 | 61953.07 | 09-MAY-03:01 | 68200.99 | 29-MAY-03:01 | 25119.24 | 10-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.116770E+12 | 0.297275E+11 | 593.84 | 0.579090E+11 | 0.588614E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 100985.90 | 09-JUN-03:11 | 53444.00 | 17-JUN-03:01 | 66869.09 | 07-JUN-03:01 | 25119.24 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.126918E+12 | 0.326231E+11 | 613.31 | 0.642476E+11 | 0.626709E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 100985.90 | 10-JUL-03:01 | 54830.72 | 02-JUL-03:01 | 64327.70 | 26-JUL-03:01 | 25119.24 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.127058E+12 | 0.324414E+11 | 613.58 | 0.627791E+11 | 0.642793E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 100985.90 | 19-AUG-03:01 | 51995.24 | 23-AUG-11:55 | 65432.27 | 28-AUG-03:01 | 25119.24 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.117588E+12 | 0.300491E+11 | 593.59 | 0.590035E+11 | 0.585849E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 100985.90 | 13-SEP-03:02 | 48567.27 | 11-SEP-12:00 | 64422.47 | 06-SEP-03:02 | 25119.24 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.104515E+12 | 0.269501E+11 | 613.39 | 0.541423E+11 | 0.503726E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 100985.90 | 02-OCT-03:01 | 63823.70 | 18-OCT-03:01 | 68034.96 | 04-OCT-03:01 | 25119.24 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.749293E+11 | 0.196937E+11 | 553.18 | 0.389256E+11 | 0.360037E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 100985.90 | 03-NOV-03:01 | 55115.77 | 11-NOV-04:01 | 63667.12 | 05-NOV-03:02 | 25119.24 | 03-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.462507E+11 | 0.127193E+11 | 494.08 | 0.247690E+11 | 0.214817E+11 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:03 | 100985.90 | 23-DEC-04:01 | 55579.03 | 01-DEC-04:01 | 63089.51 | 26-DEC-04:01 | 25119.24 | 07-DEC-04:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.101060E+13 | 0.264641E+12 | 6708.23 | 0.530752E+12 | 0.479846E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.359744E+11 | 0.101933E+11 | 454.41 | 0.208911E+11 | 0.150833E+11 | 0.00 | 1.00 | 0.00 | 100985.90 | 48567.27 | 56887.36 | 25119.24 | 0.00 | |||||||
Maximum of Months | 0.127058E+12 | 0.326231E+11 | 613.58 | 0.642476E+11 | 0.642793E+11 | 0.00 | 1.00 | 0.00 | 100985.90 | 67453.90 | 68200.99 | 25119.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.276792E+11 | 0.677621E+10 | 537.48 | 0.152354E+11 | 0.124439E+11 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:50 | 43485.60 | 02-JAN-14:10 | 32837.26 | 27-JAN-04:01 | 28407.75 | 07-JAN-04:01 | 9851.67 | 02-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.306835E+11 | 0.743707E+10 | 523.85 | 0.178100E+11 | 0.128734E+11 | 0.00 | 1.00 | 01-FEB-04:01 | 0.00 | 01-FEB-00:05 | 43485.60 | 11-FEB-04:32 | 32363.34 | 03-FEB-05:01 | 26322.26 | 11-FEB-04:32 | 9878.50 | 11-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.395796E+11 | 0.946732E+10 | 613.22 | 0.214218E+11 | 0.181578E+11 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 | 43485.60 | 05-MAR-11:42 | 30086.02 | 17-MAR-03:01 | 28602.93 | 06-MAR-04:01 | 9851.67 | 05-MAR-04:01 | 0.00 | 01-MAR-00:03 |
April | 0.495119E+11 | 0.117363E+11 | 668.02 | 0.283430E+11 | 0.211689E+11 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 43485.60 | 01-APR-15:27 | 28759.14 | 20-APR-03:11 | 28215.62 | 01-APR-03:01 | 10037.25 | 14-APR-13:52 | 0.00 | 01-APR-00:01 |
May | 0.731391E+11 | 0.168360E+11 | 703.75 | 0.380322E+11 | 0.351069E+11 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 43485.60 | 28-MAY-13:00 | 31263.49 | 22-MAY-13:00 | 30268.12 | 29-MAY-03:01 | 10413.03 | 29-MAY-12:53 | 0.00 | 01-MAY-00:01 |
June | 0.847700E+11 | 0.194016E+11 | 684.30 | 0.408645E+11 | 0.439055E+11 | 0.00 | 1.00 | 01-JUN-00:53 | 0.00 | 01-JUN-00:01 | 43485.60 | 05-JUN-20:10 | 28221.88 | 11-JUN-12:55 | 29768.54 | 25-JUN-03:32 | 10250.76 | 11-JUN-12:55 | 0.00 | 01-JUN-00:01 |
July | 0.888317E+11 | 0.205478E+11 | 706.44 | 0.439213E+11 | 0.449104E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 43485.60 | 10-JUL-15:47 | 31811.08 | 07-JUL-11:53 | 29663.19 | 03-JUL-03:01 | 10790.75 | 29-JUL-15:53 | 0.00 | 01-JUL-00:01 |
August | 0.897082E+11 | 0.206256E+11 | 707.76 | 0.429932E+11 | 0.467150E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:01 | 43485.60 | 08-AUG-14:36 | 29542.21 | 23-AUG-12:00 | 29889.98 | 10-AUG-03:01 | 10506.66 | 23-AUG-13:00 | 0.00 | 01-AUG-00:01 |
September | 0.839492E+11 | 0.192812E+11 | 683.55 | 0.407441E+11 | 0.432051E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 43485.60 | 01-SEP-03:21 | 28550.41 | 08-SEP-16:00 | 29881.15 | 06-SEP-03:01 | 10250.76 | 13-SEP-12:55 | 0.00 | 01-SEP-00:01 |
October | 0.758153E+11 | 0.174279E+11 | 705.37 | 0.376837E+11 | 0.381316E+11 | 0.00 | 1.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:01 | 43485.60 | 01-OCT-12:50 | 28095.93 | 23-OCT-11:00 | 30893.93 | 04-OCT-03:45 | 10250.76 | 09-OCT-10:53 | 0.00 | 01-OCT-00:01 |
November | 0.554445E+11 | 0.129042E+11 | 641.17 | 0.273985E+11 | 0.280460E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 43485.60 | 29-NOV-20:30 | 32960.05 | 12-NOV-04:01 | 29434.05 | 04-NOV-03:01 | 9895.37 | 03-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.360384E+11 | 0.864019E+10 | 569.75 | 0.180280E+11 | 0.180104E+11 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-01:01 | 43485.60 | 10-DEC-11:46 | 25504.06 | 15-DEC-04:01 | 29669.38 | 24-DEC-04:01 | 9851.67 | 09-DEC-04:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.735151E+12 | 0.171081E+12 | 7744.67 | 0.372476E+12 | 0.362675E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.276792E+11 | 0.677621E+10 | 523.85 | 0.152354E+11 | 0.124439E+11 | 0.00 | 1.00 | 0.00 | 43485.60 | 25504.06 | 26322.26 | 9851.67 | 0.00 | |||||||
Maximum of Months | 0.897082E+11 | 0.206256E+11 | 707.76 | 0.439213E+11 | 0.467150E+11 | 0.00 | 1.00 | 0.00 | 43485.60 | 32960.05 | 30893.93 | 10790.75 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.24 | 81.58 | 88.66 | 237.67 | 170.07 | 0.00 | 0.00 | 0.00 |
February | 197.46 | 91.74 | 105.73 | 298.01 | 139.57 | 0.00 | 0.00 | 0.00 |
March | 240.53 | 113.72 | 126.81 | 366.98 | 112.95 | 0.00 | 0.00 | 0.00 |
April | 261.36 | 116.68 | 144.68 | 451.51 | 77.53 | 0.00 | 0.00 | 0.00 |
May | 247.28 | 98.86 | 148.41 | 470.28 | 37.83 | 0.00 | 0.00 | 0.00 |
June | 243.03 | 93.27 | 149.76 | 488.01 | 18.65 | 0.00 | 0.00 | 0.00 |
July | 250.05 | 90.23 | 159.81 | 520.86 | 26.19 | 0.00 | 0.00 | 0.00 |
August | 228.55 | 76.52 | 152.03 | 457.24 | 20.28 | 0.00 | 0.00 | 0.00 |
September | 220.19 | 79.51 | 140.68 | 449.50 | 30.13 | 0.00 | 0.00 | 0.00 |
October | 202.43 | 86.88 | 115.56 | 380.83 | 47.88 | 0.00 | 0.00 | 0.00 |
November | 164.84 | 65.64 | 99.19 | 272.94 | 87.43 | 0.00 | 0.00 | 0.00 |
December | 133.32 | 47.24 | 86.08 | 188.43 | 149.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.30 | 86.76 | 126.54 | 382.18 | 76.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.32 | 47.24 | 86.08 | 188.43 | 18.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 261.36 | 116.68 | 159.81 | 520.86 | 170.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 460.89 | 299.69 | 161.20 | 722.75 | 229.96 | 0.00 | 0.00 | 0.00 |
February | 406.87 | 231.40 | 175.47 | 668.16 | 193.57 | 0.00 | 0.00 | 0.00 |
March | 314.44 | 130.00 | 184.43 | 519.11 | 161.43 | 0.00 | 0.00 | 0.00 |
April | 225.46 | 46.18 | 179.27 | 414.13 | 110.46 | 0.00 | 0.00 | 0.00 |
May | 176.03 | 5.59 | 170.44 | 358.63 | 53.93 | 0.00 | 0.00 | 0.00 |
June | 166.04 | 0.35 | 165.70 | 364.14 | 26.56 | 0.00 | 0.00 | 0.00 |
July | 177.67 | 1.49 | 176.18 | 411.18 | 36.79 | 0.00 | 0.00 | 0.00 |
August | 199.74 | 14.94 | 184.80 | 434.79 | 28.15 | 0.00 | 0.00 | 0.00 |
September | 259.01 | 63.99 | 195.02 | 565.47 | 42.42 | 0.00 | 0.00 | 0.00 |
October | 359.47 | 170.92 | 188.55 | 691.51 | 66.67 | 0.00 | 0.00 | 0.00 |
November | 407.23 | 228.55 | 178.68 | 700.99 | 121.34 | 0.00 | 0.00 | 0.00 |
December | 444.35 | 280.57 | 163.78 | 712.49 | 201.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.27 | 122.33 | 176.94 | 546.34 | 105.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.04 | 0.35 | 161.20 | 358.63 | 26.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 460.89 | 299.69 | 195.02 | 722.75 | 229.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 153.38 | 66.32 | 87.06 | 213.47 | 175.91 | 0.00 | 0.00 | 0.00 |
February | 192.50 | 87.67 | 104.83 | 296.69 | 146.38 | 0.00 | 0.00 | 0.00 |
March | 238.45 | 109.00 | 129.45 | 372.25 | 119.29 | 0.00 | 0.00 | 0.00 |
April | 261.73 | 121.02 | 140.71 | 450.79 | 78.35 | 0.00 | 0.00 | 0.00 |
May | 239.37 | 92.42 | 146.96 | 455.98 | 38.76 | 0.00 | 0.00 | 0.00 |
June | 202.67 | 56.87 | 145.80 | 414.46 | 18.97 | 0.00 | 0.00 | 0.00 |
July | 226.15 | 69.89 | 156.26 | 475.89 | 26.50 | 0.00 | 0.00 | 0.00 |
August | 225.62 | 73.34 | 152.29 | 450.27 | 19.98 | 0.00 | 0.00 | 0.00 |
September | 192.53 | 56.74 | 135.79 | 398.57 | 30.71 | 0.00 | 0.00 | 0.00 |
October | 191.88 | 74.95 | 116.94 | 361.01 | 48.89 | 0.00 | 0.00 | 0.00 |
November | 157.85 | 57.82 | 100.03 | 265.94 | 92.01 | 0.00 | 0.00 | 0.00 |
December | 158.26 | 70.73 | 87.53 | 234.68 | 150.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 203.45 | 78.04 | 125.41 | 366.22 | 78.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.38 | 56.74 | 87.06 | 213.47 | 18.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 261.73 | 121.02 | 156.26 | 475.89 | 175.91 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455969E+09 | 0.218512E+09 | 0.237457E+09 | 0.636571E+09 | 0.455510E+09 |
February | 0.477698E+09 | 0.221926E+09 | 0.255772E+09 | 0.720944E+09 | 0.337654E+09 |
March | 0.644236E+09 | 0.304591E+09 | 0.339645E+09 | 0.982923E+09 | 0.302526E+09 |
April | 0.677444E+09 | 0.302425E+09 | 0.375019E+09 | 0.117031E+10 | 0.200959E+09 |
May | 0.662305E+09 | 0.264791E+09 | 0.397514E+09 | 0.125960E+10 | 0.101311E+09 |
June | 0.629926E+09 | 0.241761E+09 | 0.388165E+09 | 0.126493E+10 | 48348243.18 |
July | 0.669722E+09 | 0.241676E+09 | 0.428046E+09 | 0.139506E+10 | 70137083.12 |
August | 0.612147E+09 | 0.204954E+09 | 0.407194E+09 | 0.122467E+10 | 54317916.74 |
September | 0.570721E+09 | 0.206083E+09 | 0.364638E+09 | 0.116511E+10 | 78089335.81 |
October | 0.542201E+09 | 0.232694E+09 | 0.309507E+09 | 0.102001E+10 | 0.128235E+09 |
November | 0.427256E+09 | 0.170148E+09 | 0.257109E+09 | 0.707463E+09 | 0.226608E+09 |
December | 0.357075E+09 | 0.126515E+09 | 0.230559E+09 | 0.504681E+09 | 0.399417E+09 |
Annual Sum or Average | 0.672670E+10 | 0.273607E+10 | 0.399063E+10 | 0.120523E+11 | 0.240311E+10 |
Minimum of Months | 0.357075E+09 | 0.126515E+09 | 0.230559E+09 | 0.504681E+09 | 48348243.18 |
Maximum of Months | 0.677444E+09 | 0.304591E+09 | 0.428046E+09 | 0.139506E+10 | 0.455510E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123445E+10 | 0.802683E+09 | 0.431768E+09 | 0.193582E+10 | 0.615926E+09 |
February | 0.984290E+09 | 0.559803E+09 | 0.424488E+09 | 0.161641E+10 | 0.468293E+09 |
March | 0.842183E+09 | 0.348193E+09 | 0.493989E+09 | 0.139037E+10 | 0.432385E+09 |
April | 0.584381E+09 | 0.119709E+09 | 0.464672E+09 | 0.107344E+10 | 0.286324E+09 |
May | 0.471481E+09 | 14966438.46 | 0.456515E+09 | 0.960557E+09 | 0.144433E+09 |
June | 0.430386E+09 | 895899.24 | 0.429490E+09 | 0.943862E+09 | 68845596.32 |
July | 0.475874E+09 | 3995887.91 | 0.471878E+09 | 0.110131E+10 | 98537319.38 |
August | 0.534976E+09 | 40006713.83 | 0.494969E+09 | 0.116453E+10 | 75392518.73 |
September | 0.671363E+09 | 0.165858E+09 | 0.505505E+09 | 0.146571E+10 | 0.109961E+09 |
October | 0.962806E+09 | 0.457804E+09 | 0.505003E+09 | 0.185214E+10 | 0.178569E+09 |
November | 0.105554E+10 | 0.592402E+09 | 0.463137E+09 | 0.181698E+10 | 0.314510E+09 |
December | 0.119015E+10 | 0.751475E+09 | 0.438677E+09 | 0.190835E+10 | 0.540946E+09 |
Annual Sum or Average | 0.943788E+10 | 0.385779E+10 | 0.558009E+10 | 0.172295E+11 | 0.333412E+10 |
Minimum of Months | 0.430386E+09 | 895899.24 | 0.424488E+09 | 0.943862E+09 | 68845596.32 |
Maximum of Months | 0.123445E+10 | 0.802683E+09 | 0.505505E+09 | 0.193582E+10 | 0.615926E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.410811E+09 | 0.177640E+09 | 0.233171E+09 | 0.571762E+09 | 0.471164E+09 |
February | 0.465698E+09 | 0.212101E+09 | 0.253597E+09 | 0.717759E+09 | 0.354115E+09 |
March | 0.638670E+09 | 0.291954E+09 | 0.346715E+09 | 0.997027E+09 | 0.319511E+09 |
April | 0.678401E+09 | 0.313692E+09 | 0.364709E+09 | 0.116845E+10 | 0.203085E+09 |
May | 0.641140E+09 | 0.247532E+09 | 0.393608E+09 | 0.122131E+10 | 0.103814E+09 |
June | 0.525324E+09 | 0.147405E+09 | 0.377918E+09 | 0.107427E+10 | 49170719.72 |
July | 0.605721E+09 | 0.187194E+09 | 0.418527E+09 | 0.127463E+10 | 70971221.12 |
August | 0.604309E+09 | 0.196425E+09 | 0.407884E+09 | 0.120601E+10 | 53501779.37 |
September | 0.499048E+09 | 0.147069E+09 | 0.351978E+09 | 0.103310E+10 | 79596055.07 |
October | 0.513939E+09 | 0.200738E+09 | 0.313201E+09 | 0.966925E+09 | 0.130955E+09 |
November | 0.409143E+09 | 0.149859E+09 | 0.259284E+09 | 0.689323E+09 | 0.238489E+09 |
December | 0.423884E+09 | 0.189443E+09 | 0.234440E+09 | 0.628567E+09 | 0.402066E+09 |
Annual Sum or Average | 0.641609E+10 | 0.246105E+10 | 0.395503E+10 | 0.115491E+11 | 0.247644E+10 |
Minimum of Months | 0.409143E+09 | 0.147069E+09 | 0.233171E+09 | 0.571762E+09 | 49170719.72 |
Maximum of Months | 0.678401E+09 | 0.313692E+09 | 0.418527E+09 | 0.127463E+10 | 0.471164E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1158.34 | 560.38 | 784.51 | 447.59 | 336.92 | 0.00 | 0.00 |
February | 1251.15 | 467.81 | 796.83 | 410.81 | 386.02 | 0.00 | 0.00 |
March | 1240.77 | 376.11 | 793.42 | 352.73 | 440.69 | 0.00 | 0.00 |
April | 1309.75 | 259.67 | 748.54 | 283.88 | 464.66 | 0.00 | 0.00 |
May | 1282.57 | 128.19 | 662.68 | 196.87 | 465.81 | 0.00 | 0.00 |
June | 1265.20 | 62.76 | 611.74 | 150.49 | 461.26 | 0.00 | 0.00 |
July | 1407.16 | 88.70 | 653.87 | 161.61 | 492.25 | 0.00 | 0.00 |
August | 1342.00 | 68.10 | 653.91 | 164.79 | 489.12 | 0.00 | 0.00 |
September | 1412.51 | 102.22 | 671.73 | 200.24 | 471.50 | 0.00 | 0.00 |
October | 1432.00 | 162.09 | 753.79 | 332.75 | 421.04 | 0.00 | 0.00 |
November | 1234.52 | 295.42 | 729.91 | 352.01 | 377.91 | 0.00 | 0.00 |
December | 1127.59 | 493.20 | 735.93 | 398.53 | 337.39 | 0.00 | 0.00 |
Annual Sum or Average | 1288.75 | 254.47 | 716.03 | 287.13 | 428.90 | 0.00 | 0.00 |
Minimum of Months | 1127.59 | 62.76 | 611.74 | 150.49 | 336.92 | 0.00 | 0.00 |
Maximum of Months | 1432.00 | 560.38 | 796.83 | 447.59 | 492.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310249E+10 | 0.150093E+10 | 0.210123E+10 | 0.119884E+10 | 0.902396E+09 | 0.00 | 0.00 |
February | 0.302678E+10 | 0.113173E+10 | 0.192769E+10 | 0.993830E+09 | 0.933856E+09 | 0.00 | 0.00 |
March | 0.332327E+10 | 0.100737E+10 | 0.212509E+10 | 0.944739E+09 | 0.118035E+10 | 0.00 | 0.00 |
April | 0.339488E+10 | 0.673055E+09 | 0.194023E+10 | 0.735826E+09 | 0.120440E+10 | 0.00 | 0.00 |
May | 0.343524E+10 | 0.343334E+09 | 0.177493E+10 | 0.527289E+09 | 0.124764E+10 | 0.00 | 0.00 |
June | 0.327939E+10 | 0.162684E+09 | 0.158564E+10 | 0.390062E+09 | 0.119557E+10 | 0.00 | 0.00 |
July | 0.376893E+10 | 0.237576E+09 | 0.175132E+10 | 0.432865E+09 | 0.131845E+10 | 0.00 | 0.00 |
August | 0.359441E+10 | 0.182405E+09 | 0.175143E+10 | 0.441386E+09 | 0.131005E+10 | 0.00 | 0.00 |
September | 0.366122E+10 | 0.264952E+09 | 0.174113E+10 | 0.519011E+09 | 0.122212E+10 | 0.00 | 0.00 |
October | 0.383547E+10 | 0.434155E+09 | 0.201895E+10 | 0.891235E+09 | 0.112771E+10 | 0.00 | 0.00 |
November | 0.319988E+10 | 0.765720E+09 | 0.189194E+10 | 0.912409E+09 | 0.979530E+09 | 0.00 | 0.00 |
December | 0.302014E+10 | 0.132098E+10 | 0.197111E+10 | 0.106743E+10 | 0.903677E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.406421E+11 | 0.802488E+10 | 0.225807E+11 | 0.905492E+10 | 0.135258E+11 | 0.00 | 0.00 |
Minimum of Months | 0.302014E+10 | 0.162684E+09 | 0.158564E+10 | 0.390062E+09 | 0.902396E+09 | 0.00 | 0.00 |
Maximum of Months | 0.383547E+10 | 0.150093E+10 | 0.212509E+10 | 0.119884E+10 | 0.131845E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638054E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155356256.4 | 81.21 | 0.00 | 0.00 |
February | 0.577446E+10 | -0.563430E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -140161761.8 | 81.21 | 0.00 | 0.00 |
March | 0.644885E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154979148.4 | 81.21 | 0.00 | 0.00 |
April | 0.619279E+10 | -0.604349E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149298755.3 | 81.21 | 0.00 | 0.00 |
May | 0.641432E+10 | -0.626022E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154101874.2 | 81.21 | 0.00 | 0.00 |
June | 0.623515E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148561409.8 | 81.21 | 0.00 | 0.00 |
July | 0.637004E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152942405.2 | 81.21 | 0.00 | 0.00 |
August | 0.644831E+10 | -0.629522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153088614.3 | 81.21 | 0.00 | 0.00 |
September | 0.619336E+10 | -0.604483E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148535314.7 | 81.21 | 0.00 | 0.00 |
October | 0.637776E+10 | -0.622385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153912798.3 | 81.21 | 0.00 | 0.00 |
November | 0.617406E+10 | -0.602463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149433489.9 | 81.21 | 0.00 | 0.00 |
December | 0.637231E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155214267.0 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753819E+11 | -0.735664E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181559E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577446E+10 | -0.629522E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155356256.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644885E+10 | -0.563430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -140161761.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.175257E+11 | -0.166776E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -848131624.4 | 58.97 | 0.00 | 0.00 |
February | 0.157123E+11 | -0.149474E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -764949879.6 | 58.99 | 0.00 | 0.00 |
March | 0.170275E+11 | -0.161827E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -844867666.5 | 58.98 | 0.00 | 0.00 |
April | 0.156303E+11 | -0.148189E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811477712.5 | 58.99 | 0.00 | 0.00 |
May | 0.154168E+11 | -0.145800E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -836802652.0 | 58.98 | 0.00 | 0.00 |
June | 0.144020E+11 | -0.135975E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -804485777.2 | 58.98 | 0.00 | 0.00 |
July | 0.144685E+11 | -0.136422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -826316450.7 | 58.99 | 0.00 | 0.00 |
August | 0.148072E+11 | -0.139796E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -827624754.2 | 58.99 | 0.00 | 0.00 |
September | 0.147407E+11 | -0.139363E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -804410759.3 | 58.98 | 0.00 | 0.00 |
October | 0.159299E+11 | -0.150949E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -834963359.0 | 58.98 | 0.00 | 0.00 |
November | 0.161637E+11 | -0.153511E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -812603589.8 | 58.98 | 0.00 | 0.00 |
December | 0.172657E+11 | -0.164185E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -847152756.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.189090E+12 | -0.179227E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.986379E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.144020E+11 | -0.166776E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -848131624.4 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.175257E+11 | -0.135975E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -764949879.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.50 | 01-JAN-07:40 | 846.24 | 24.82 | 174.50 | 291.83 | 846.45 | 24.60 | 175.00 | 290.50 |
February | 304.33 | 0.53 | 0.50 | 01-FEB-07:00 | 821.06 | 22.33 | 145.33 | 277.33 | 791.41 | 22.14 | 139.83 | 277.33 |
March | 362.67 | 0.53 | 0.50 | 01-MAR-07:40 | 871.29 | 20.35 | 105.83 | 332.00 | 928.03 | 20.34 | 116.33 | 333.83 |
April | 357.50 | 0.52 | 0.50 | 01-APR-07:10 | 964.01 | 20.09 | 102.00 | 338.67 | 818.91 | 20.26 | 83.33 | 334.00 |
May | 389.00 | 0.53 | 0.50 | 01-MAY-06:49 | 675.06 | 19.58 | 74.83 | 354.00 | 692.87 | 19.60 | 60.50 | 355.67 |
June | 388.17 | 0.55 | 0.50 | 01-JUN-06:49 | 566.01 | 20.29 | 86.17 | 334.67 | 669.56 | 18.95 | 51.67 | 336.00 |
July | 403.83 | 0.53 | 0.50 | 01-JUL-06:49 | 637.75 | 19.80 | 91.67 | 362.33 | 684.49 | 19.75 | 79.50 | 359.17 |
August | 348.33 | 0.53 | 0.50 | 01-AUG-07:10 | 751.62 | 20.02 | 101.83 | 345.17 | 714.45 | 20.09 | 99.67 | 345.17 |
September | 349.67 | 0.53 | 0.50 | 01-SEP-06:00 | 755.01 | 20.34 | 137.00 | 317.00 | 841.62 | 20.18 | 109.17 | 314.67 |
October | 323.50 | 0.53 | 0.50 | 02-OCT-07:30 | 864.68 | 21.57 | 164.83 | 316.83 | 1032.28 | 22.51 | 188.67 | 315.00 |
November | 314.83 | 0.53 | 0.50 | 01-NOV-06:00 | 905.19 | 24.29 | 206.50 | 288.17 | 876.98 | 24.13 | 204.67 | 288.50 |
December | 282.67 | 0.52 | 0.50 | 01-DEC-08:39 | 991.21 | 24.53 | 170.83 | 274.00 | 850.12 | 24.54 | 177.00 | 275.67 |
Annual Sum or Average | 4111.50 | 0.53 | 793.85 | 21.31 | 1561.33 | 3832.00 | 805.66 | 21.22 | 1485.33 | 3825.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.50 | 566.01 | 19.58 | 74.83 | 274.00 | 669.56 | 18.95 | 51.67 | 275.67 | |
Maximum of Months | 403.83 | 0.55 | 0.50 | 991.21 | 24.82 | 206.50 | 362.33 | 1032.28 | 24.60 | 204.67 | 359.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204984E+09 | 12852.60 | 25-JAN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371200E+09 | 21182.36 | 04-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274881E+09 | 18949.92 | 16-MAR-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54440883.08 | 9295.61 | 27-NOV-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.325967E+09 | 13156.35 | 21-DEC-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371200E+09 | 21182.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26864022.81 | 8947.08 | 04-FEB-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 444323.78 | 354.85 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27308346.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26864022.81 | 8947.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.359744E+11 | 0.208911E+11 | 100985.90 | 07-JAN-04:01 | 41286.61 | 0.00 |
February | 0.00 | 0.00 | 0.412208E+11 | 0.250998E+11 | 100985.90 | 11-FEB-04:01 | 44098.54 | 0.00 |
March | 0.00 | 0.00 | 0.527619E+11 | 0.300844E+11 | 100985.90 | 14-MAR-03:01 | 41578.15 | 0.00 |
April | 0.00 | 0.00 | 0.678698E+11 | 0.400175E+11 | 100985.90 | 12-APR-03:01 | 45964.64 | 0.00 |
May | 0.00 | 0.00 | 0.987413E+11 | 0.528833E+11 | 100985.90 | 14-MAY-03:02 | 40610.55 | 0.00 |
June | 0.00 | 0.00 | 0.116770E+12 | 0.579090E+11 | 100985.90 | 09-JUN-03:11 | 40966.26 | 0.00 |
July | 0.00 | 0.00 | 0.126918E+12 | 0.642476E+11 | 100985.90 | 10-JUL-03:01 | 42948.02 | 0.00 |
August | 0.00 | 0.00 | 0.127058E+12 | 0.627791E+11 | 100985.90 | 19-AUG-03:01 | 44480.72 | 0.00 |
September | 0.00 | 0.00 | 0.117588E+12 | 0.590035E+11 | 100985.90 | 13-SEP-03:02 | 38162.58 | 0.00 |
October | 0.00 | 0.00 | 0.104515E+12 | 0.541423E+11 | 100985.90 | 02-OCT-03:01 | 37640.39 | 0.00 |
November | 0.00 | 0.00 | 0.749293E+11 | 0.389256E+11 | 100985.90 | 03-NOV-03:01 | 47924.08 | 0.00 |
December | 0.00 | 0.00 | 0.462507E+11 | 0.247690E+11 | 100985.90 | 23-DEC-04:01 | 43266.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101060E+13 | 0.530752E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.359744E+11 | 0.208911E+11 | 100985.90 | 37640.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127058E+12 | 0.642476E+11 | 100985.90 | 47924.08 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.276792E+11 | 0.152354E+11 | 43485.60 | 02-JAN-14:10 | 21824.48 | 0.00 |
February | 0.00 | 0.00 | 0.306835E+11 | 0.178100E+11 | 43485.60 | 11-FEB-04:32 | 17163.34 | 0.00 |
March | 0.00 | 0.00 | 0.395796E+11 | 0.214218E+11 | 43485.60 | 05-MAR-11:42 | 22764.63 | 0.00 |
April | 0.00 | 0.00 | 0.495119E+11 | 0.283430E+11 | 43485.60 | 01-APR-15:27 | 20187.55 | 0.00 |
May | 0.00 | 0.00 | 0.731391E+11 | 0.380322E+11 | 43485.60 | 28-MAY-13:00 | 17172.19 | 0.00 |
June | 0.00 | 0.00 | 0.847700E+11 | 0.408645E+11 | 43485.60 | 05-JUN-20:10 | 19686.02 | 0.00 |
July | 0.00 | 0.00 | 0.888317E+11 | 0.439213E+11 | 43485.60 | 10-JUL-15:47 | 21149.53 | 0.00 |
August | 0.00 | 0.00 | 0.897082E+11 | 0.429932E+11 | 43485.60 | 08-AUG-14:36 | 20196.90 | 0.00 |
September | 0.00 | 0.00 | 0.839492E+11 | 0.407441E+11 | 43485.60 | 01-SEP-03:21 | 20060.86 | 0.00 |
October | 0.00 | 0.00 | 0.758153E+11 | 0.376837E+11 | 43485.60 | 01-OCT-12:50 | 19199.50 | 0.00 |
November | 0.00 | 0.00 | 0.554445E+11 | 0.273985E+11 | 43485.60 | 29-NOV-20:30 | 18279.73 | 0.00 |
December | 0.00 | 0.00 | 0.360384E+11 | 0.180280E+11 | 43485.60 | 10-DEC-11:46 | 22329.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.735151E+12 | 0.372476E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.276792E+11 | 0.152354E+11 | 43485.60 | 17163.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.897082E+11 | 0.439213E+11 | 43485.60 | 22764.63 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6691.47 | 12686.73 | 17-JAN-19:43 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6643.88 | 12655.35 | 02-FEB-19:17 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 6507.38 | 12431.62 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6183.55 | 11915.91 | 03-APR-18:33 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5910.48 | 11402.43 | 01-MAY-19:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5713.03 | 10884.47 | 01-JUN-18:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5561.50 | 10559.05 | 03-JUL-18:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5687.00 | 10809.89 | 31-AUG-18:16 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5843.70 | 11212.08 | 28-SEP-18:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6102.10 | 11806.14 | 30-OCT-18:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6388.25 | 12292.71 | 27-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 6595.32 | 12621.54 | 28-DEC-07:25 |
Annual Sum or Average | 0.00 | 6149.58 | ||||
Minimum of Months | 0.00 | 0.00 | 5561.50 | 10559.05 | ||
Maximum of Months | 0.00 | 0.00 | 6691.47 | 12686.73 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204889E+10 | 0.24 | 824.13 | 01-JAN-00:10 | 0.26 |
February | 0.185844E+10 | 0.24 | 824.13 | 01-FEB-00:05 | 0.26 |
March | 0.206364E+10 | 0.25 | 824.13 | 01-MAR-00:03 | 0.26 |
April | 0.202977E+10 | 0.25 | 824.13 | 01-APR-00:30 | 0.26 |
May | 0.210506E+10 | 0.25 | 824.13 | 01-MAY-00:30 | 0.26 |
June | 0.204211E+10 | 0.25 | 824.13 | 01-JUN-00:12 | 0.26 |
July | 0.210616E+10 | 0.25 | 824.13 | 01-JUL-00:10 | 0.26 |
August | 0.210754E+10 | 0.25 | 824.13 | 01-AUG-00:10 | 0.26 |
September | 0.203948E+10 | 0.25 | 824.13 | 01-SEP-00:10 | 0.26 |
October | 0.210860E+10 | 0.25 | 824.13 | 01-OCT-00:10 | 0.26 |
November | 0.201987E+10 | 0.25 | 824.13 | 01-NOV-00:20 | 0.26 |
December | 0.205606E+10 | 0.24 | 824.13 | 01-DEC-00:03 | 0.26 |
Annual Sum or Average | 0.245856E+11 | 0.25 | |||
Minimum of Months | 0.185844E+10 | 0.24 | 824.13 | 0.26 | |
Maximum of Months | 0.210860E+10 | 0.25 | 824.13 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.570932E+10 | 0.72 | 6339.06 | 01-JAN-04:01 | 1.39 |
February | 0.518261E+10 | 0.72 | 6339.06 | 10-FEB-04:01 | 1.39 |
March | 0.576410E+10 | 0.73 | 6339.06 | 04-MAR-04:01 | 1.39 |
April | 0.571383E+10 | 0.74 | 6339.06 | 01-APR-03:01 | 1.39 |
May | 0.641600E+10 | 0.78 | 6339.06 | 01-MAY-03:01 | 1.39 |
June | 0.708306E+10 | 0.83 | 6339.06 | 01-JUN-03:01 | 1.38 |
July | 0.775394E+10 | 0.86 | 6339.06 | 01-JUL-03:01 | 1.38 |
August | 0.770628E+10 | 0.85 | 6339.06 | 01-AUG-03:01 | 1.38 |
September | 0.719427E+10 | 0.84 | 6339.06 | 01-SEP-03:01 | 1.38 |
October | 0.668368E+10 | 0.79 | 6339.06 | 01-OCT-03:01 | 1.38 |
November | 0.596814E+10 | 0.76 | 6339.06 | 01-NOV-03:01 | 1.39 |
December | 0.577440E+10 | 0.73 | 6339.06 | 01-DEC-04:01 | 1.39 |
Annual Sum or Average | 0.769496E+11 | 0.78 | |||
Minimum of Months | 0.518261E+10 | 0.72 | 6339.06 | 1.38 | |
Maximum of Months | 0.775394E+10 | 0.86 | 6339.06 | 1.39 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173805E+10 | 0.52 | 1709.51 | 01-JAN-04:01 | 0.87 |
February | 0.160797E+10 | 0.53 | 1709.51 | 01-FEB-04:01 | 0.87 |
March | 0.190033E+10 | 0.55 | 1709.51 | 01-MAR-04:01 | 0.88 |
April | 0.202630E+10 | 0.58 | 1709.51 | 01-APR-03:01 | 0.87 |
May | 0.276563E+10 | 0.67 | 1709.51 | 01-MAY-03:01 | 0.87 |
June | 0.323866E+10 | 0.73 | 1709.51 | 01-JUN-03:01 | 0.87 |
July | 0.343039E+10 | 0.74 | 1709.51 | 01-JUL-03:01 | 0.87 |
August | 0.345014E+10 | 0.74 | 1709.51 | 01-AUG-03:01 | 0.86 |
September | 0.321411E+10 | 0.73 | 1709.51 | 01-SEP-03:01 | 0.87 |
October | 0.288496E+10 | 0.68 | 1709.51 | 01-OCT-03:01 | 0.86 |
November | 0.231924E+10 | 0.62 | 1709.51 | 01-NOV-03:01 | 0.87 |
December | 0.190787E+10 | 0.55 | 1709.51 | 01-DEC-04:01 | 0.87 |
Annual Sum or Average | 0.304836E+11 | 0.64 | |||
Minimum of Months | 0.160797E+10 | 0.52 | 1709.51 | 0.86 | |
Maximum of Months | 0.345014E+10 | 0.74 | 1709.51 | 0.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 50.99 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 51.94 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 51.97 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 53.51 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.88 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 54.45 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 54.28 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.07 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.19 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 54.24 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.81 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 51.88 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.99 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.45 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.99 | 59.48 | 6691.47 | 12686.73 | 17-JAN-19:43 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51.94 | 59.13 | 6643.88 | 12655.35 | 02-FEB-19:17 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.97 | 59.35 | 6507.38 | 12431.62 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.38 | 52.38 | 6183.55 | 11915.91 | 03-APR-18:33 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 52.80 | 52.80 | 5910.48 | 11402.43 | 01-MAY-19:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.35 | 53.35 | 5713.03 | 10884.47 | 01-JUN-18:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.88 | 52.88 | 5561.50 | 10559.05 | 03-JUL-18:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.02 | 53.02 | 5687.00 | 10809.89 | 31-AUG-18:16 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.75 | 52.75 | 5843.70 | 11212.08 | 28-SEP-18:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.73 | 51.73 | 6102.10 | 11806.14 | 30-OCT-18:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.18 | 52.18 | 6388.25 | 12292.71 | 27-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.88 | 59.41 | 6595.32 | 12621.54 | 28-DEC-07:25 |
Annual Sum or Average | 0.00 | 6149.58 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.99 | 51.73 | 5561.50 | 10559.05 | ||
Maximum of Months | 0.00 | 0.00 | 53.35 | 59.48 | 6691.47 | 12686.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.159026E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.167787E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.203200E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.241666E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.320548E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.368105E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.403770E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.401476E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.372434E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.336338E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.256619E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184937E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.341591E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159026E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.403770E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.851426E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.904505E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.113676E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137626E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.196016E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226402E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.239782E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.240757E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.224953E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.203129E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152235E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105481E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.201565E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.851426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.240757E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.570932E+10 | 0.359744E+11 | 0.204984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518261E+10 | 0.412208E+11 | 0.371200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.576410E+10 | 0.527619E+11 | 0.274881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571383E+10 | 0.678698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.641600E+10 | 0.987413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.708306E+10 | 0.116770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.775394E+10 | 0.126918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.770628E+10 | 0.127058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.719427E+10 | 0.117588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.668368E+10 | 0.104515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596814E+10 | 0.749293E+11 | 54440883.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577440E+10 | 0.462507E+11 | 0.325967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769496E+11 | 0.101060E+13 | 0.123147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.518261E+10 | 0.359744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.775394E+10 | 0.127058E+12 | 0.371200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173805E+10 | 0.276792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160797E+10 | 0.306835E+11 | 26864022.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190033E+10 | 0.395796E+11 | 444323.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202630E+10 | 0.495119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276563E+10 | 0.731391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323866E+10 | 0.847700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343039E+10 | 0.888317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345014E+10 | 0.897082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321411E+10 | 0.839492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288496E+10 | 0.758153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231924E+10 | 0.554445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190787E+10 | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304836E+11 | 0.735151E+12 | 27308346.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160797E+10 | 0.276792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345014E+10 | 0.897082E+11 | 26864022.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.570932E+10 | 0.00 | 0.00 | 0.00 | 0.101933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518261E+10 | 0.00 | 0.00 | 0.00 | 0.115961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.576410E+10 | 0.00 | 0.00 | 0.00 | 0.145559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571383E+10 | 0.00 | 0.00 | 0.00 | 0.184528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.641600E+10 | 0.00 | 0.00 | 0.00 | 0.256388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.708306E+10 | 0.00 | 0.00 | 0.00 | 0.297275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.775394E+10 | 0.00 | 0.00 | 0.00 | 0.326231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.770628E+10 | 0.00 | 0.00 | 0.00 | 0.324414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.719427E+10 | 0.00 | 0.00 | 0.00 | 0.300491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.668368E+10 | 0.00 | 0.00 | 0.00 | 0.269501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596814E+10 | 0.00 | 0.00 | 0.00 | 0.196937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577440E+10 | 0.00 | 0.00 | 0.00 | 0.127193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769496E+11 | 0.00 | 0.00 | 0.00 | 0.264641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.518261E+10 | 0.00 | 0.00 | 0.00 | 0.101933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.775394E+10 | 0.00 | 0.00 | 0.00 | 0.326231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173805E+10 | 0.00 | 0.00 | 0.00 | 0.677621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160797E+10 | 0.00 | 0.00 | 0.00 | 0.743707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190033E+10 | 0.00 | 0.00 | 0.00 | 0.946732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202630E+10 | 0.00 | 0.00 | 0.00 | 0.117363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276563E+10 | 0.00 | 0.00 | 0.00 | 0.168360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323866E+10 | 0.00 | 0.00 | 0.00 | 0.194016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343039E+10 | 0.00 | 0.00 | 0.00 | 0.205478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345014E+10 | 0.00 | 0.00 | 0.00 | 0.206256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321411E+10 | 0.00 | 0.00 | 0.00 | 0.192812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288496E+10 | 0.00 | 0.00 | 0.00 | 0.174279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231924E+10 | 0.00 | 0.00 | 0.00 | 0.129042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190787E+10 | 0.00 | 0.00 | 0.00 | 0.864019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304836E+11 | 0.00 | 0.00 | 0.00 | 0.171081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160797E+10 | 0.00 | 0.00 | 0.00 | 0.677621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345014E+10 | 0.00 | 0.00 | 0.00 | 0.206256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.654928E+10 | 0.494215E+10 | 0.00 | 50576436.73 | 15946139.34 | 0.00 | 0.119213E+11 | 0.00 | 3.61 |
February | 0.444477E+10 | 0.567439E+10 | 0.00 | 43795517.12 | 13572017.05 | 0.00 | 0.679139E+10 | 0.00 | 3.61 |
March | 0.420917E+10 | 0.982217E+10 | 0.00 | 39175377.87 | 44381711.89 | 1410833.09 | 0.618270E+10 | 0.00 | 3.62 |
April | 0.590728E+09 | 0.150487E+11 | 0.00 | 21006423.47 | 69680543.86 | 0.00 | 0.195221E+10 | 0.00 | 3.63 |
May | 88484160.26 | 0.352284E+11 | 0.00 | 3580783.58 | 0.343088E+09 | 0.00 | 69704867.80 | 0.00 | 3.67 |
June | 16282752.69 | 0.496132E+11 | 0.00 | 1793446.99 | 0.713947E+09 | 0.00 | 3037069.03 | 0.00 | 3.71 |
July | 31257941.15 | 0.556783E+11 | 0.00 | 1742309.48 | 0.652786E+09 | 0.00 | 5055666.41 | 0.00 | 3.71 |
August | 11487674.98 | 0.555430E+11 | 0.00 | 1802378.98 | 0.770502E+09 | 0.00 | 2854016.59 | 0.00 | 3.72 |
September | 26769172.52 | 0.493617E+11 | 0.00 | 2420487.76 | 0.608616E+09 | 0.00 | 4713536.40 | 0.00 | 3.71 |
October | 79462992.66 | 0.387151E+11 | 0.00 | 3560427.21 | 0.410016E+09 | 0.00 | 11900055.45 | 0.00 | 3.69 |
November | 0.171732E+10 | 0.225521E+11 | 0.00 | 20212833.01 | 0.181271E+09 | 0.00 | 0.330538E+10 | 0.00 | 3.65 |
December | 0.514379E+10 | 0.940646E+10 | 0.00 | 36923007.58 | 51875691.63 | 0.00 | 0.979712E+10 | 0.00 | 3.62 |
Annual Sum or Average | 0.229088E+11 | 0.351586E+12 | 0.00 | 0.226589E+09 | 0.387568E+10 | 1410833.09 | 0.400474E+11 | 0.00 | 3.66 |
Minimum of Months | 11487674.98 | 0.494215E+10 | 0.00 | 1742309.48 | 13572017.05 | 0.00 | 2854016.59 | 0.00 | 3.61 |
Maximum of Months | 0.654928E+10 | 0.556783E+11 | 0.00 | 50576436.73 | 0.770502E+09 | 1410833.09 | 0.119213E+11 | 0.00 | 3.72 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201809E+10 | 0.346863E+10 | 0.00 | 76474085.98 | 0.00 | 0.00 | 0.196916E+11 | 0.00 | 8.03 |
February | 0.180301E+10 | 0.374438E+10 | 0.00 | 69024666.41 | 0.00 | 0.00 | 0.128668E+11 | 0.00 | 8.08 |
March | 0.192610E+10 | 0.687457E+10 | 0.00 | 63775224.51 | 0.00 | 0.00 | 0.115115E+11 | 0.00 | 8.24 |
April | 14208075.75 | 0.870486E+10 | 0.00 | 56979373.98 | 0.00 | 0.00 | 0.465269E+10 | 0.00 | 8.49 |
May | 0.00 | 0.250864E+11 | 0.00 | 3971642.26 | 0.00 | 0.00 | 0.211155E+09 | 0.00 | 9.01 |
June | 0.00 | 0.371013E+11 | 0.00 | 73890.74 | 0.00 | 0.00 | 556044.53 | 0.00 | 9.33 |
July | 0.00 | 0.383844E+11 | 0.00 | 477620.98 | 0.00 | 0.00 | 5192785.66 | 0.00 | 9.31 |
August | 0.00 | 0.398290E+11 | 0.00 | 135698.22 | 0.00 | 0.00 | 827862.24 | 0.00 | 9.37 |
September | 0.00 | 0.354529E+11 | 0.00 | 181509.09 | 0.00 | 0.00 | 2370693.37 | 0.00 | 9.28 |
October | 0.00 | 0.275479E+11 | 0.00 | 7240658.78 | 0.00 | 0.00 | 0.239582E+09 | 0.00 | 9.09 |
November | 0.626452E+09 | 0.164224E+11 | 0.00 | 30499487.40 | 0.00 | 0.00 | 0.594340E+10 | 0.00 | 8.66 |
December | 0.236154E+10 | 0.681837E+10 | 0.00 | 64079207.37 | 0.00 | 0.00 | 0.146752E+11 | 0.00 | 8.19 |
Annual Sum or Average | 0.874940E+10 | 0.249435E+12 | 0.00 | 0.372913E+09 | 0.00 | 0.00 | 0.698008E+11 | 0.00 | 8.76 |
Minimum of Months | 0.00 | 0.346863E+10 | 0.00 | 73890.74 | 0.00 | 0.00 | 556044.53 | 0.00 | 8.03 |
Maximum of Months | 0.236154E+10 | 0.398290E+11 | 0.00 | 76474085.98 | 0.00 | 0.00 | 0.196916E+11 | 0.00 | 9.37 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.697906E+11 | 0.432546E+10 | 0.706602E+11 | 0.592142E+10 | 0.102361E+12 |
February | 0.840690E+11 | 0.317185E+10 | 0.434890E+11 | 0.442167E+10 | 0.110355E+12 |
March | 0.118480E+12 | 0.321980E+10 | 0.284166E+11 | 0.400503E+10 | 0.138206E+12 |
April | 0.130062E+12 | 0.748649E+09 | -0.108822E+11 | 0.227696E+10 | 0.171199E+12 |
May | 0.131379E+12 | -0.414998E+10 | -0.832869E+11 | 0.111527E+10 | 0.238190E+12 |
June | 0.115300E+12 | -0.724878E+10 | -0.125693E+12 | -297333026.5 | 0.275000E+12 |
July | 0.122145E+12 | -0.774414E+10 | -0.134774E+12 | -107061847.9 | 0.296730E+12 |
August | 0.129626E+12 | -0.886115E+10 | -0.137928E+12 | -399756538.7 | 0.296433E+12 |
September | 0.987426E+11 | -0.795580E+10 | -0.122824E+12 | 0.128860E+09 | 0.275572E+12 |
October | 0.917367E+11 | -0.640855E+10 | -0.924770E+11 | 0.799204E+09 | 0.248942E+12 |
November | 0.683571E+11 | -0.279034E+10 | -0.298878E+11 | 0.312662E+10 | 0.182974E+12 |
December | 0.692888E+11 | 0.277090E+10 | 0.411590E+11 | 0.496792E+10 | 0.124609E+12 |
Annual Sum or Average | 0.122898E+13 | -0.309221E+11 | -0.554027E+12 | 0.259588E+11 | 0.246057E+13 |
Minimum of Months | 0.683571E+11 | -0.886115E+10 | -0.137928E+12 | -399756538.7 | 0.102361E+12 |
Maximum of Months | 0.131379E+12 | 0.432546E+10 | 0.706602E+11 | 0.592142E+10 | 0.296730E+12 |