Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:26:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2745.26 | 5370.71 | 5370.71 |
Net Site Energy | 2745.26 | 5370.71 | 5370.71 |
Total Source Energy | 4548.25 | 8898.01 | 8898.01 |
Net Source Energy | 4548.25 | 8898.01 | 8898.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1102.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.53 | 418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 35.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 754.87 | 1990.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1102.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 89.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.53 | 418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1102.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 49.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 43.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 89.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.53 | 418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 35.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 135.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 420.17 | 2974.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 921.48 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1476.79 | 3893.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 135.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 420.17 | 2974.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 921.48 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1476.79 | 3893.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 754.866 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 754.866 | 100.00 |
Total On-Site and Utility Electric Sources | 754.866 | 100.00 |
Total Electricity End Uses | 754.866 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 4.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4571.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.3716 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.8021 | 18.52 | 1057.5080 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.3716 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.8021 | 18.52 | 1057.5080 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Conditioned Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.0345 | 1.78 | 335.6309 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-11:00 | 06-JAN-07:49 | - | - | - | - | - | - | - | - | - | - | 02-MAR-19:10 |
Heating | 0.00 | 205232.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28115.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1871.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22289.73 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5136.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2995.83 | 36278.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1201.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 61627.69 | 255087.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 205232.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28115.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1871.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21698.93 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5136.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2995.83 | 36278.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 370.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1195.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 156.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 137.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1379.75 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 282.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.20 | 453.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 111.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2390.66 | 2157.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2338.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 306.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.97 | 886.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 219.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4676.99 | 4221.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2338.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 306.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.97 | 886.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 219.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4676.99 | 4221.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.45 |
KITCHEN DIRECT AIR | 1.47 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.45 | 3.45 | 3.45 | 3.45 | 3.45 | 3.45 | 1.00 | 1.00 | 3.45 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.00 | 1.47 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.45 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.47 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.45 | 3691.30 |
PSZ-AC_2:2_ADDAQ FAN | 1.47 | 1571.14 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.45 | 3.45 | 3.45 | 2.28 | 85663.20 | 158902.00 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.969073 | 36461.19 | 108867.61 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.45 | 1.72 | 2.30 | 85663.20 | 42831.60 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.47 | 0.734146 | 0.978860 | 36461.19 | 18230.60 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 158902.00 |
PSZ-AC_2:2 HEATING COIL | 108867.61 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.372 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.299 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.802 | 408.232 | 649.276 | 0.000 | 0.000 | 0.000 | 1066.310 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2368.645 | 6.372 | 8.455 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2368.645 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1227.055 | 8.802 | 163.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1227.055 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7719 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1345 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2291 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.062 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.356 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.287 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.30075618E-16 | 0.17394661E-15 | 0.12402583E-13 | -0.41376697E-16 |
24 | 3 | -0.12971024E-07 | 0.72198543E-07 | -0.59837000E-04 | 0.16553701E-12 |
25 | 2 | 0.68419174E-04 | 0.15226993E-02 | 1.1866788 | -0.78740824E-04 |
26 | 1 | -0.34646128E-01 | 0.38608229E-01 | -17.391783 | 0.34506386 |
27 | 0 | 0.98978059E-01 | 0.24269337E-01 | 16.269565 | |
28 | 4 | 0.12402583E-13 | 0.17394661E-15 | 0.30075618E-16 | -0.41376697E-16 |
29 | 3 | -0.59837000E-04 | 0.72198543E-07 | -0.12971024E-07 | 0.16553701E-12 |
30 | 2 | 1.1866788 | 0.15226993E-02 | 0.68419174E-04 | -0.78740824E-04 |
31 | 1 | -17.391783 | 0.38608229E-01 | -0.34646128E-01 | 0.34506386 |
32 | 0 | 16.269565 | 0.24269337E-01 | 0.98978059E-01 | |
33 | 7 | -0.30221493E-12 | 0.42806226E-14 | -0.95155442E-13 | 0.15899766E-15 |
34 | 6 | 0.28727294E-07 | 0.21728364E-09 | 0.65803531E-08 | -0.13544055E-12 |
35 | 5 | -0.19039181E-03 | 0.18585303E-05 | -0.97925888E-04 | 0.65048812E-08 |
36 | 4 | 0.29248049 | 0.90406920E-03 | 0.99803377E-01 | -0.33617969E-04 |
37 | 3 | -7.2729408 | 0.27994057E-01 | -2.3408748 | 0.29041410E-01 |
38 | 2 | 40.892958 | 0.99469394E-01 | 15.273156 | -0.33358329 |
39 | 1 | -80.562512 | 0.44862081E-01 | -29.148912 | 1.0789757 |
40 | 0 | 46.824339 | 0.90199676E-03 | 16.291060 | |
41 | 7 | -0.31585163E-08 | -0.22597303E-14 | 0.15834007E-14 | -0.44811583E-16 |
42 | 6 | 0.38926816E-05 | 0.25726622E-08 | 0.31949392E-02 | -0.26801827E-04 |
43 | 5 | -0.27259256E-03 | 0.15209505E-05 | -0.22401268 | 0.19586932E-02 |
44 | 4 | 0.62224649E-02 | 0.69174334E-04 | 4.8343438 | -0.45311104E-01 |
45 | 3 | -0.54492574E-01 | 0.54963890E-03 | -38.048519 | 0.39895333 |
46 | 2 | 0.19328371 | 0.91376166E-03 | 116.53670 | -1.4186449 |
47 | 1 | -0.27884260 | 0.27809541E-03 | -143.93836 | 2.0495503 |
48 | 0 | 0.13591665 | 0.67534627E-05 | 60.838472 | |
49 | 7 | -0.18366387E-08 | -0.45273224E-15 | 0.66973396E-14 | -0.89481334E-16 |
50 | 6 | 0.64176182E-05 | 0.43906086E-08 | 0.31875387E-02 | -0.26739746E-04 |
51 | 5 | -0.46144041E-03 | 0.26013657E-05 | -0.22359208 | 0.19549808E-02 |
52 | 4 | 0.10613927E-01 | 0.11841222E-03 | 4.8273389 | -0.45243768E-01 |
53 | 3 | -0.93204934E-01 | 0.94170345E-03 | -38.008950 | 0.39851596 |
54 | 2 | 0.33095125 | 0.15665766E-02 | 116.45969 | -1.4176148 |
55 | 1 | -0.47767855 | 0.47741295E-03 | -143.89302 | 2.0488052 |
56 | 0 | 0.23289156 | 0.11519323E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.292_SHGC_SOUTH_0.399 | 38 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
2 | NONRESWINDOW_U_0.292_SHGC_NORTH_0.399 | 39 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
3 | NONRESWINDOW_U_0.292_SHGC_EAST_0.399 | 40 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
4 | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | 41 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.8693E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8786E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7685E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6528E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5603E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6033E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1860E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0975E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.5557E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.4722E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.9054E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.8109E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.4243E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.3795E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.1243E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.1244E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7173E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6535E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.4397E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4853E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3984E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3972E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0975E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1860E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 37861.36307 | 45433.63569 | 2.87471 | 3.44966 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 11580.80414 | 13896.96497 | 0.51798 | 1.33138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 19001.99814 | 22802.39776 | 1.22358 | 1.46829 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 28.98400 | 1.27239E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 3075.78123 | 3690.93747 | 0.12446 | 1.21700 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 54171.77 | 3.44966 | 3.44966 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 112232.36 | 1.33138 | 1.33138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 27056.55 | 1.46829 | 1.46829 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 102590.74 | 1.21700 | 1.21700 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.44966 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46829 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.44966 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.44966 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.44966 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.44966 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.44966 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.44966 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46829 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46829 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46829 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46829 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46829 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46829 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.44966 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.46829 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.44966 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.44966 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3691.29604 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.44966 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.44966 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.44966 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.27677 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.44966 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.72483 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.29977 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 85663.20000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 42831.60000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 85663.20000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 158902.00102 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 158902.00102 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46829 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46829 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1571.14210 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46829 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46829 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46829 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96907 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46829 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73415 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97886 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36461.19000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18230.59500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36461.19000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 108867.61095 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 108867.61095 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 83211.3 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 35417.6 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.135 | 0.130 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.229 | 0.217 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1069107271 | 0.5407462765 | Pass | Pass | 0.2200175762 | 0.7285448718 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 3.7755803052E-002 | 0.2144683710 | Pass | Pass | 4.7408061271E-002 | 0.1802004687 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2678212071 | 0.2494248457 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 855.41 | 147.30 | 2636.16 | 9.37 | 632.50 | 4280.75 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.132 | 0.135 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.221 | 0.229 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.292_SHGC_EAST_0.399 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.658 | 0.400 | 0.440 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.292_SHGC_SOUTH_0.399 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 1.658 | 0.400 | 0.440 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.658 | 0.400 | 0.440 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 1.658 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.3716 | 371.75 | 2368.64 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.03 | 0.0000 | Y | 26.69 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.8021 | 139.41 | 1227.05 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.61 | 0.0000 | Y | 16.72 |
Interior Lighting Total | 7.0345 | 511.15 | 3595.70 | 43.42 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 49.55 | 49.55 | 1.97 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.52 | 63.04 | 23.69 | |
Exterior Lighting Total | 2213.72 | 25.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 85663.20 | 60056.76 | 25606.44 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36461.19 | 25562.21 | 10898.98 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 83211.3 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 35417.6 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 158902.00 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 108867.61 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 3.45 | 3691.30 | 1070.05 | 1.00 | 1.25 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1571.14 | 1070.05 | 1.00 | 1.37 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 02:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 37861.36 | 45433.64 | 122.22 | 2.875 | 3.450 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.01066 | 29.98 | 0.01273 | 1.331 | 0.00 |
KITCHEN | 19002.00 | 22802.40 | 163.57 | 1.224 | 1.468 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01056 | 28.98 | 0.01272 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 11580.80 | 13896.96 | 37.38 | 0.518 | 1.331 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -32.70 | 0.00018 | 1.331 | 0.00 |
KITCHEN | 3075.78 | 3690.94 | 26.48 | 0.124 | 1.217 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00705 | -32.70 | 0.00018 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.45 | 3.45 | 1.33 | 1.33 | 3.4497 | 3.4497 | 3.4497 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.22 | 1.22 | 1.4683 | 1.4683 | 1.4683 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 85663.200 | 60056.756 | 3.449660 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 42831.60 | 28938.37 | 2.299773 | 26.34 | 19.09 | 0.01145692 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 57.8917 | 23.98 | 0.01065935 | 54.8515 | 37857.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 158902.001 | 158902.001 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 158902.00 | 158902.00 | 3.449657 | 0.27 | 0.27 | 0.00484612 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 38.5945 | 21.00 | 0.00777673 | 48.1955 | 11579.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 36461.190 | 25562.211 | 1.468290 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 18230.60 | 11897.77 | 0.978860 | 29.58 | 20.79 | 0.01245868 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 124.3285 | 25.98 | 0.01058480 | 48.3584 | 19002.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 108867.611 | 108867.611 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 02:40:00 | 108867.61 | 108867.61 | 1.468292 | -23.94 | -23.94 | 0.00136114 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 82.8855 | 19.00 | 0.00706508 | 49.6194 | 2105.48 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 85663.200 | 60056.756 | 3.449660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1378 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.449657 | 3.98064493 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 42831.60 | 28938.37 | 1.0000 | 2.65376561 | 2.299773 | 26.34 | 19.09 | 0.01145692 | 55684.8 | 11.90 | 11.35 | 0.00850000 | 33399.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42831.60 | 30.10 | 0.01272586 | 21.13 | 1.33137743 | 57.8917 | 23.98 | 0.01065935 | 23.98 | 0.01065935 | 54.8515 | 37857.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 158902.001 | 158902.001 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.449657 | 3.98064493 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 158902.00 | 158902.00 | 1.0000 | 3.98064493 | 3.449657 | 0.27 | 0.27 | 0.00484612 | 12398.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 158902.00 | -32.70 | 0.00018338 | -32.70 | 1.33137743 | 38.5945 | 21.00 | 0.00777673 | 21.00 | 0.00777673 | 48.1955 | 11579.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36461.190 | 25562.211 | 1.468290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.0001 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.468292 | 1.69429891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 18230.60 | 11897.77 | 1.0000 | 1.12953089 | 0.978860 | 29.58 | 20.79 | 0.01245868 | 61567.5 | 11.90 | 11.35 | 0.00850000 | 33401.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18230.60 | 30.10 | 0.01272586 | 21.13 | 1.21700195 | 124.3285 | 25.94 | 0.01058480 | 25.98 | 0.01058480 | 48.3584 | 19002.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 108867.611 | 108867.611 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.468292 | 1.69429891 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 02:40:00 | Sensible | 108867.61 | 108867.61 | 1.0000 | 1.69429891 | 1.468292 | -23.94 | -23.94 | 0.00136114 | -20716.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 108867.61 | -32.70 | 0.00018338 | -32.70 | 1.21700195 | 82.8855 | 18.46 | 0.00706508 | 19.00 | 0.00706508 | 49.6194 | 2105.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.45 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.47 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3912.50 | 5944.33 | 2955.67 |
KITCHEN | 5241.33 | 6245.83 | 4442.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5369.50 | 7058.50 | 4571.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 42.00 | 1.67 | 0.00 | 0.00 |
KITCHEN | 0.00 | 46.17 | 0.00 | 4.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 42.00 | 47.50 | 0.00 | 4.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.464 | 0.600 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 8.828 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.062 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 8.049 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.14 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.17 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.32 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36665087.67 | 0.00 | 36665087.67 | 4917447.40 | 41582535.07 | 41986318.57 | 1449.76 | 6138.70 | 1171.55 | 252.72 |
KITCHEN | 27240692.75 | 0.00 | 27240692.75 | 157339.58 | 27398032.34 | 38379373.44 | 8385.59 | 364.42 | 9.99 | 289.74 |
Total Facility | 63905780.43 | 0.00 | 63905780.43 | 5074786.98 | 68980567.41 | 80365692.01 | 8387.52 | 6139.57 | 1179.69 | 409.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3881 | 0.0000 | 1.3881 | 0.1865 | 1.5746 | 1.3314 | 0.00 | 6018.65 | 1168.35 |
KITCHEN | 1.0299 | 0.0000 | 1.0299 | 0.0039 | 1.0337 | 1.2170 | 6828.35 | 351.66 | 6.99 |
Total Facility | 2.4179 | 0.0000 | 2.4179 | 0.1904 | 2.6083 | 2.5484 | 6828.35 | 6019.48 | 1174.51 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48821245.96 | 0.00 | 48821245.96 | 41986318.57 | 1447.39 | 0.65 | 7311.95 | 252.72 |
PSZ-AC_2:2 | 36272083.01 | 0.00 | 36272083.01 | 38379373.44 | 1450.33 | 0.43 | 7309.24 | 289.74 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8483 | 0.0000 | 1.8483 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3713 | 0.0000 | 1.3713 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1125.02 | 179.45 | 6135.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 83.68 | 1071.22 | 6321.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.2749 | 2.0191 | 1.7731 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.4639 | 1.4570 | 1.3598 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
Electricity:Building | 486.01 | 2437.13 | 01-JAN-01:20 | 27911.96 | 02-JAN-11:10 |
Electricity:Zone:DINING | 151.80 | 560.03 | 01-JAN-01:20 | 8292.44 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 479.08 | 2300.85 | 01-JAN-01:20 | 25768.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 43.42 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 26.69 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 43.42 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 43.42 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 26.69 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 43.42 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 334.21 | 1877.10 | 01-JAN-01:20 | 19908.15 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 310.55 | 1710.81 | 01-JAN-01:10 | 16905.18 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 35.36 | 595.54 | 05-JAN-23:30 | 2780.19 | 19-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 104.40 | 741.01 | 05-JAN-01:10 | 5844.79 | 03-JUL-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 10.57 | 0.00 | 01-JAN-11:10 | 1019.15 | 30-JUN-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 17.85 | 509.04 | 06-JAN-05:40 | 637.09 | 23-APR-13:10 |
ElectricityPurchased:Facility | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
ElectricityPurchased:Plant | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
Cogeneration:ElectricityPurchased | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
General:Cogeneration:ElectricityPurchased | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
ElectricityNet:Plant | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
Cogeneration:ElectricityNet | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
General:Cogeneration:ElectricityNet | 754.87 | 4195.51 | 04-JAN-03:40 | 61627.69 | 30-JUN-12:00 |
Electricity:HVAC | 138.79 | 0.00 | 01-JAN-01:10 | 34096.33 | 29-JUN-18:00 |
Fans:Electricity | 89.33 | 0.00 | 01-JAN-01:10 | 5199.42 | 29-JUN-18:00 |
General:Fans:Electricity | 89.33 | 0.00 | 01-JAN-01:10 | 5199.42 | 29-JUN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 49.47 | 0.00 | 01-JAN-00:10 | 28898.26 | 29-JUN-17:50 |
General:Cooling:Electricity | 49.47 | 0.00 | 01-JAN-00:10 | 28898.26 | 29-JUN-17:50 |
ExteriorLights:Electricity | 25.66 | 0.00 | 01-JAN-08:20 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.66 | 0.00 | 01-JAN-08:20 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.16 | 22-FEB-07:50 |
Water Heater:WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.16 | 22-FEB-07:50 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 05-MAR-10:00 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 05-MAR-10:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1990.39 | 2758.01 | 12-APR-00:10 | 255087.23 | 06-JAN-07:50 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 1102.47 | 0.00 | 01-JAN-01:10 | 208590.19 | 06-JAN-07:10 |
Heating:NaturalGas | 1102.47 | 0.00 | 01-JAN-01:10 | 208590.19 | 06-JAN-07:10 |
General:Heating:NaturalGas | 1102.47 | 0.00 | 01-JAN-01:10 | 208590.19 | 06-JAN-07:10 |
NaturalGas:Plant | 418.14 | 947.76 | 01-JAN-00:10 | 37636.70 | 28-FEB-07:30 |
WaterSystems:NaturalGas | 418.14 | 947.76 | 01-JAN-00:10 | 37636.70 | 28-FEB-07:30 |
Water Heater:WaterSystems:NaturalGas | 418.14 | 947.76 | 01-JAN-00:10 | 37636.70 | 28-FEB-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 21-APR-07:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 21-APR-07:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2037.00 | 2930.08 | 05-JAN-01:10 | 209689.33 | 06-JAN-05:00 |
EnergyTransfer:Building | 602.00 | 1465.04 | 05-JAN-01:10 | 63362.40 | 06-JAN-05:00 |
EnergyTransfer:Zone:KITCHEN | 372.34 | 1465.04 | 05-JAN-01:10 | 21661.06 | 02-NOV-11:00 |
Refrigeration:EnergyTransfer | 132.41 | 2620.99 | 05-JAN-23:10 | 7834.84 | 26-MAY-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.20 | 1310.49 | 05-JAN-23:10 | 3917.42 | 26-MAY-03:20 |
General:Refrigeration:EnergyTransfer | 66.20 | 1310.49 | 05-JAN-23:10 | 3917.42 | 26-MAY-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.20 | 1310.49 | 05-JAN-23:10 | 3917.42 | 26-MAY-03:20 |
EnergyTransfer:Plant | 367.35 | 1465.04 | 05-JAN-01:10 | 22566.26 | 01-MAR-19:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 11.94 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 54.26 | 1305.24 | 06-JAN-05:40 | 2238.70 | 23-APR-13:10 |
EnergyTransfer:Zone:DINING | 229.66 | 0.00 | 01-JAN-01:10 | 60047.28 | 06-JAN-05:00 |
Heating:EnergyTransfer | 19.46 | 0.00 | 01-JAN-00:20 | 37810.55 | 06-JAN-05:00 |
Heating:EnergyTransfer:Zone:DINING | 19.40 | 0.00 | 01-JAN-00:20 | 37810.55 | 06-JAN-05:00 |
General:Heating:EnergyTransfer | 19.46 | 0.00 | 01-JAN-00:20 | 37810.55 | 06-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:DINING | 19.40 | 0.00 | 01-JAN-00:20 | 37810.55 | 06-JAN-05:00 |
Cooling:EnergyTransfer | 516.33 | 0.00 | 01-JAN-01:10 | 42694.18 | 29-JUN-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 210.26 | 0.00 | 01-JAN-01:10 | 27319.87 | 29-JUN-17:20 |
General:Cooling:EnergyTransfer | 516.33 | 0.00 | 01-JAN-01:10 | 42694.18 | 29-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 210.26 | 0.00 | 01-JAN-01:10 | 27319.87 | 29-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.06 | 0.00 | 01-JAN-00:10 | 2265.84 | 14-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.06 | 0.00 | 01-JAN-00:10 | 2265.84 | 14-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 306.07 | 0.00 | 01-JAN-01:10 | 18324.81 | 02-NOV-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 306.07 | 0.00 | 01-JAN-01:10 | 18324.81 | 02-NOV-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 301.14 | 0.00 | 01-JAN-01:10 | 20589.33 | 01-MAR-19:20 |
PlantLoopHeatingDemand:Plant | 301.14 | 0.00 | 01-JAN-01:10 | 20589.33 | 01-MAR-19:20 |
WaterSystems:PlantLoopHeatingDemand | 301.14 | 0.00 | 01-JAN-01:10 | 20589.33 | 01-MAR-19:20 |
General:WaterSystems:PlantLoopHeatingDemand | 301.14 | 0.00 | 01-JAN-01:10 | 20589.33 | 01-MAR-19:20 |
EnergyTransfer:HVAC | 1067.66 | 0.00 | 01-JAN-01:10 | 166872.15 | 06-JAN-07:10 |
HeatingCoils:EnergyTransfer | 881.97 | 0.00 | 01-JAN-01:10 | 166872.15 | 06-JAN-07:10 |
CoolingCoils:EnergyTransfer | 185.68 | 0.00 | 01-JAN-00:10 | 112047.72 | 29-JUN-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 301.14 | 0.00 | 01-JAN-01:10 | 20589.33 | 01-MAR-19:20 |
WaterUse:WaterSystems:EnergyTransfer | 301.14 | 0.00 | 01-JAN-01:10 | 20589.33 | 01-MAR-19:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 19.398 | -210.257 | 0.000 | 0.000 | 232.422 | 26.693 | 93.832 | 42.295 | 0.000 | 0.915 | 0.004 | 0.000 | -26.962 | 0.000 | -104.774 | -73.562 |
KITCHEN | 0.000 | 0.000 | 0.060 | -306.064 | 0.000 | 0.000 | 6.240 | 16.725 | 273.146 | 0.000 | 0.000 | 0.007 | 13.680 | 0.000 | 0.000 | 0.000 | -3.794 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.588 | 24.926 | 0.000 | 0.000 | 0.000 | -33.513 | -0.001 |
Total Facility | 0.000 | 0.000 | 19.458 | -516.321 | 0.000 | 0.000 | 238.662 | 43.417 | 366.978 | 42.295 | 0.000 | 9.510 | 38.609 | 0.000 | -26.962 | 0.000 | -142.081 | -73.564 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-JAN-00:01 | 0.00 | 0.00 | 0.00 | -75960.72 | 0.00 | 0.00 | 1157.79 | 337.32 | 540.00 | 0.00 | 0.00 | 0.00 | 78180.47 | 0.00 | -3580.79 | 0.00 | -674.08 | 0.00 |
KITCHEN | 13-JAN-05:01 | 0.00 | 0.00 | 0.00 | -56672.90 | 0.00 | 0.00 | 27.00 | 30.01 | 6476.03 | 0.00 | 0.00 | 0.00 | 50139.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-MAY-03:01 | 0.00 | 0.00 | 0.00 | -108193.28 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 958.60 | 104273.13 | 0.00 | -926.06 | 0.00 | -158.38 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 16-FEB-04:01 | 0.00 | 0.00 | 103961.69 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2252.42 | 0.00 | -1748.47 | -100940.84 |
KITCHEN | 14-FEB-05:02 | 0.00 | 0.00 | 20365.34 | 0.00 | 0.00 | 0.00 | 28.34 | 30.01 | 6476.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -185.99 | -26713.74 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-FEB-04:01 | 0.00 | 0.00 | 103961.69 | 0.00 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 60.11 | 0.00 | 0.00 | -2252.42 | 0.00 | -2867.23 | -102948.13 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.4497 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.4497 | 0.3859 | 1.0000 | Not calculated | 1.3314 | 0.3859 | ||
PSZ-AC_2:2 | 1.4683 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.4683 | 0.1244 | 1.0000 | Not calculated | 0.1826 | 0.1244 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.4497 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.4497 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3859 | ||
PSZ-AC_2:2 | 1.4683 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.4683 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1244 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4497 | 3.4497 | 3.4497 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4683 | 1.4683 | 1.4683 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.4497 | 3.4497 | 3.4497 | 3.4497 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.4683 | 1.4683 | 1.4683 | 1.4683 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4497 | 3.4497 | 3.4497 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4683 | 1.4683 | 1.4683 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.4497 | 3.4497 | 3.4497 | 3.4497 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.4683 | 1.4683 | 1.4683 | 1.4683 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 4.17 |
Number of hours not met | 4.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1102.47 | 208590.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 49.47 | 28898.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 43.42 | 2883.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.66 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 89.33 | 5199.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.53 | 4742.16 | 418.14 | 37636.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.57 | 1019.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.85 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 471.02 | 754.87 |
Natural Gas | 469.79 | 1990.39 |
Additional | 0.00 | 0.00 |
Total | 940.81 | 2745.26 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.94 |
Space Heating | 0.00 |
Space Cooling | 96.78 |
Fans (All) | 174.75 |
Service Water Heating | 147.76 |
Receptacle Equipment | 852.31 |
Miscellaneous (All) | 1476.79 |
Subtotal | 1476.79 |
Natural Gas [MJ/m2] | |
Space Heating | 2156.83 |
Service Water Heating | 818.03 |
Miscellaneous (All) | 3893.92 |
Subtotal | 3893.92 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.58 |
Space Heating | 40.16 |
Space Cooling | 1.80 |
Fans (All) | 3.25 |
Service Water Heating | 17.98 |
Receptacle Equipment | 32.98 |
Miscellaneous | 2.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8358.67 | 394.00 | 7.33 | 0.00 | 0.00 |
ATTIC | 7603.67 | 450.83 | 339.67 | 305.17 | 60.67 |
Min | 7603.67 | 4.50 | 0.00 | 0.00 | 0.00 |
Max | 8755.50 | 450.83 | 339.67 | 305.17 | 60.67 |
Average | 8239.28 | 283.11 | 115.67 | 101.72 | 20.22 |
Sum | 24717.83 | 849.33 | 347.00 | 305.17 | 60.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824210.33 | 11.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19200.17 | 32.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824210.33 | 32.83 | 0.00 | 0.00 | 0.00 |
Average | 281136.83 | 14.83 | 0.00 | 0.00 | 0.00 |
Sum | 843410.50 | 44.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8155.67 | 604.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6789.67 | 1970.00 | 0.33 | 0.00 | 0.00 |
ATTIC | 7588.67 | 685.33 | 205.33 | 139.50 | 141.17 |
Min | 6789.67 | 604.33 | 0.00 | 0.00 | 0.00 |
Max | 8155.67 | 1970.00 | 205.33 | 139.50 | 141.17 |
Average | 7511.33 | 1086.56 | 68.56 | 46.50 | 47.06 |
Sum | 22534.00 | 3259.67 | 205.67 | 139.50 | 141.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 764437.33 | 59784.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14565.50 | 4667.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 764437.33 | 59784.67 | 0.00 | 0.00 | 0.00 |
Average | 259667.61 | 21484.06 | 0.00 | 0.00 | 0.00 |
Sum | 779002.83 | 64452.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344132E+10 | 75962.62 | 06-JAN-00:01 | -32.3 | -32.4 | 0.119975E+11 | 10741.00 | 14-JAN-19:10 | -13.4 | -13.8 |
February | 0.583351E+10 | 68206.17 | 14-FEB-00:01 | -27.0 | -27.2 | 0.108635E+11 | 10741.01 | 11-FEB-19:00 | -27.0 | -27.2 |
March | 0.956689E+10 | 60337.65 | 05-MAR-00:01 | -21.5 | -21.7 | 0.121373E+11 | 10741.00 | 04-MAR-19:00 | -21.5 | -21.7 |
April | 0.167667E+11 | 43812.26 | 04-APR-23:01 | -10.1 | -11.5 | 0.121121E+11 | 14049.92 | 22-APR-18:19 | 16.27 | 7.08 |
May | 0.249891E+11 | 59424.41 | 19-MAY-03:01 | 13.93 | 9.28 | 0.139980E+11 | 14049.92 | 06-MAY-18:19 | 13.93 | 9.28 |
June | 0.268862E+11 | 49829.09 | 25-JUN-03:01 | 19.08 | 18.24 | 0.144698E+11 | 14051.63 | 10-JUN-18:30 | 19.08 | 18.24 |
July | 0.306939E+11 | 58240.75 | 24-JUL-03:01 | 18.30 | 16.16 | 0.150759E+11 | 14050.32 | 15-JUL-18:10 | 18.30 | 16.16 |
August | 0.298082E+11 | 59793.37 | 10-AUG-03:01 | 16.02 | 15.69 | 0.151142E+11 | 14051.48 | 26-AUG-18:00 | 22.20 | 17.55 |
September | 0.257856E+11 | 55471.94 | 01-SEP-03:01 | 16.93 | 16.67 | 0.133224E+11 | 14051.11 | 02-SEP-18:49 | 15.55 | 13.65 |
October | 0.205069E+11 | 40032.36 | 29-OCT-23:01 | -7.4 | -8.2 | 0.123503E+11 | 14047.43 | 21-OCT-18:19 | -7.4 | -8.2 |
November | 0.120487E+11 | 50835.63 | 25-NOV-00:01 | -15.0 | -15.4 | 0.116672E+11 | 12927.21 | 01-NOV-11:00 | -15.0 | -15.4 |
December | 0.393192E+10 | 74146.96 | 25-DEC-00:01 | -31.1 | -31.2 | 0.119920E+11 | 10740.97 | 02-DEC-19:10 | -31.1 | -31.2 |
Annual Sum or Average | 0.210259E+12 | 0.155100E+12 | ||||||||
Minimum of Months | 0.344132E+10 | 40032.36 | -32.3 | -32.4 | 0.108635E+11 | 10740.97 | -31.1 | -31.2 | ||
Maximum of Months | 0.306939E+11 | 75962.62 | 19.08 | 18.24 | 0.151142E+11 | 14051.63 | 22.20 | 18.24 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224506E+11 | 56420.83 | 13-JAN-05:01 | -30.2 | -30.3 | 0.103883E+11 | 6815.12 | 31-JAN-11:00 | -16.7 | -17.2 |
February | 0.210331E+11 | 56337.03 | 17-FEB-05:01 | -30.3 | -30.5 | 0.938372E+10 | 6827.05 | 21-FEB-11:00 | 6.10 | 2.99 |
March | 0.239859E+11 | 49430.91 | 12-MAR-04:01 | -24.2 | -24.4 | 0.103924E+11 | 6818.00 | 28-MAR-10:00 | 4.40 | 2.03 |
April | 0.245682E+11 | 36688.53 | 05-APR-04:01 | -12.4 | -13.3 | 0.100955E+11 | 6930.41 | 18-APR-10:00 | 17.20 | 11.08 |
May | 0.263954E+11 | 49414.14 | 18-MAY-03:01 | 11.88 | 8.65 | 0.105377E+11 | 6930.44 | 19-MAY-10:50 | 16.60 | 12.94 |
June | 0.261097E+11 | 50940.35 | 18-JUN-03:01 | 12.70 | 7.47 | 0.102424E+11 | 6945.47 | 30-JUN-10:50 | 30.92 | 23.73 |
July | 0.282325E+11 | 50301.85 | 02-JUL-03:01 | 8.22 | 8.02 | 0.105876E+11 | 6936.75 | 05-JUL-10:00 | 24.40 | 23.25 |
August | 0.283282E+11 | 49561.34 | 25-AUG-03:01 | 8.90 | 8.90 | 0.105896E+11 | 6930.46 | 15-AUG-10:00 | 8.90 | 8.90 |
September | 0.274190E+11 | 49194.12 | 09-SEP-03:01 | 11.38 | 7.20 | 0.101931E+11 | 6930.46 | 19-SEP-10:00 | 16.10 | 15.79 |
October | 0.284698E+11 | 36348.36 | 30-OCT-04:01 | -10.0 | -10.7 | 0.104314E+11 | 6929.64 | 19-OCT-10:00 | -10.0 | -10.7 |
November | 0.257167E+11 | 45060.42 | 29-NOV-05:01 | -19.6 | -19.9 | 0.100623E+11 | 6922.91 | 01-NOV-10:00 | -19.6 | -19.9 |
December | 0.233654E+11 | 51905.38 | 26-DEC-05:01 | -25.9 | -26.2 | 0.103882E+11 | 6815.12 | 01-DEC-11:39 | -25.9 | -26.2 |
Annual Sum or Average | 0.306075E+12 | 0.123292E+12 | ||||||||
Minimum of Months | 0.210331E+11 | 36348.36 | -30.3 | -30.5 | 0.938372E+10 | 6815.12 | -25.9 | -26.2 | ||
Maximum of Months | 0.284698E+11 | 56420.83 | 12.70 | 8.90 | 0.105896E+11 | 6945.47 | 30.92 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 | -3.3 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 | 0.38 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 | -1.4 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 | 13.57 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 | 0.51 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.714812E+10 | 98444.50 | 12-JAN-04:01 | -16.8 |
February | 0.353199E+10 | 103965.64 | 16-FEB-04:01 | -13.4 |
March | 0.203803E+10 | 97659.81 | 06-MAR-04:01 | -17.4 |
April | 0.432078E+09 | 64746.53 | 04-APR-03:01 | -6.3 |
May | 25714929.19 | 27168.95 | 01-MAY-03:02 | -2.1 |
June | 6359739.16 | 9385.47 | 04-JUN-04:02 | 2.52 |
July | 28982.06 | 144.91 | 03-JUL-23:03 | 23.80 |
August | 518202.62 | 8636.71 | 19-AUG-04:03 | 4.40 |
September | 4073927.84 | 8335.95 | 13-SEP-04:03 | 3.40 |
October | 70659111.08 | 48587.69 | 09-OCT-04:32 | -2.2 |
November | 0.686824E+09 | 65111.68 | 26-NOV-04:01 | -10.6 |
December | 0.545370E+10 | 93489.04 | 12-DEC-04:01 | -12.7 |
Annual Sum or Average | 0.193981E+11 | |||
Minimum of Months | 28982.06 | 144.91 | -17.4 | |
Maximum of Months | 0.714812E+10 | 103965.64 | 23.80 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13518238.03 | 15256.28 | 15-JAN-05:02 | -18.9 |
February | 14417748.96 | 20392.60 | 14-FEB-05:02 | -32.1 |
March | 9264893.53 | 12207.17 | 12-MAR-04:02 | -24.2 |
April | 1961890.50 | 8269.98 | 03-APR-04:03 | -5.4 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 927214.93 | 10287.20 | 30-OCT-04:03 | -10.0 |
November | 3716097.03 | 11410.20 | 13-NOV-05:03 | -7.9 |
December | 16345450.94 | 19852.35 | 13-DEC-05:02 | -24.7 |
Annual Sum or Average | 60151533.92 | |||
Minimum of Months | 0.00 | 0.00 | -32.1 | |
Maximum of Months | 16345450.94 | 20392.60 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253320E+10 | 2023.86 | 02-JAN-16:30 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.218273E+10 | 2023.86 | 01-FEB-17:10 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.231361E+10 | 2023.86 | 01-MAR-17:00 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.207170E+10 | 2023.86 | 01-APR-18:40 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.203426E+10 | 2023.86 | 01-MAY-19:30 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.193429E+10 | 2023.86 | 01-JUN-19:00 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.198548E+10 | 2023.86 | 01-JUL-20:19 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.213952E+10 | 2023.86 | 01-AUG-19:49 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.214609E+10 | 2023.86 | 01-SEP-18:00 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.234367E+10 | 2023.86 | 02-OCT-17:49 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.243460E+10 | 2023.86 | 01-NOV-16:00 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.257354E+10 | 2023.86 | 01-DEC-16:19 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.266927E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.193429E+10 | 2023.86 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.257354E+10 | 2023.86 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141271E+10 | 859.87 | 02-JAN-10:09 | 0.263757E+11 | 16905.18 | 01-JAN-11:09 |
February | 0.127972E+10 | 859.87 | 01-FEB-10:09 | 0.238233E+11 | 16905.18 | 01-FEB-11:09 |
March | 0.143703E+10 | 859.87 | 01-MAR-10:09 | 0.263759E+11 | 16905.18 | 01-MAR-11:09 |
April | 0.137275E+10 | 859.87 | 01-APR-16:10 | 0.255250E+11 | 16905.18 | 01-APR-10:09 |
May | 0.142487E+10 | 859.87 | 01-MAY-09:09 | 0.263758E+11 | 16905.18 | 01-MAY-10:09 |
June | 0.138882E+10 | 859.87 | 01-JUN-09:09 | 0.255251E+11 | 16905.18 | 01-JUN-10:09 |
July | 0.140898E+10 | 859.87 | 01-JUL-16:10 | 0.263757E+11 | 16905.18 | 01-JUL-10:09 |
August | 0.143703E+10 | 859.87 | 01-AUG-09:09 | 0.263759E+11 | 16905.18 | 01-AUG-10:09 |
September | 0.137310E+10 | 859.87 | 01-SEP-09:09 | 0.255250E+11 | 16905.18 | 01-SEP-10:09 |
October | 0.141254E+10 | 859.87 | 02-OCT-09:09 | 0.263757E+11 | 16905.18 | 01-OCT-10:09 |
November | 0.136789E+10 | 859.87 | 01-NOV-09:09 | 0.255249E+11 | 16905.18 | 01-NOV-10:09 |
December | 0.140915E+10 | 859.87 | 01-DEC-10:09 | 0.263757E+11 | 16905.18 | 01-DEC-11:09 |
Annual Sum or Average | 0.167246E+11 | 0.310554E+12 | ||||
Minimum of Months | 0.127972E+10 | 859.87 | 0.238233E+11 | 16905.18 | ||
Maximum of Months | 0.143703E+10 | 859.87 | 0.263759E+11 | 16905.18 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.253320E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197005E+11 |
February | 0.272721E+11 | 0.218273E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146996E+11 |
March | 0.305458E+11 | 0.231361E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131055E+11 |
April | 0.292871E+11 | 0.207170E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5704004.41 | 0.755293E+10 |
May | 0.303219E+11 | 0.203426E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109088E+09 | 0.354543E+10 |
June | 0.295292E+11 | 0.193429E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301770E+09 | 0.195312E+10 |
July | 0.300798E+11 | 0.198548E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364287E+09 | 0.139474E+10 |
August | 0.305458E+11 | 0.213952E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129972E+09 | 0.211535E+10 |
September | 0.292871E+11 | 0.214609E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4142691.95 | 0.417195E+10 |
October | 0.300980E+11 | 0.234367E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724481E+10 |
November | 0.290996E+11 | 0.243460E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107821E+11 |
December | 0.300798E+11 | 0.257354E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185079E+11 |
Annual Sum or Average | 0.356244E+12 | 0.266927E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914963E+09 | 0.104774E+12 |
Minimum of Months | 0.272721E+11 | 0.193429E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139474E+10 |
Maximum of Months | 0.305458E+11 | 0.257354E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364287E+09 | 0.197005E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.141271E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608419E+09 |
February | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523789E+09 |
March | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382281E+09 |
April | 0.786997E+09 | 0.137275E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 21793.91 | 0.323857E+09 |
May | 0.814802E+09 | 0.142487E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 477592.39 | 0.170869E+09 |
June | 0.793501E+09 | 0.138882E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 3232516.32 | 0.116664E+09 |
July | 0.808298E+09 | 0.140898E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2773368.21 | 80554386.58 |
August | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 787729.34 | 0.121290E+09 |
September | 0.786997E+09 | 0.137310E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1339.55 | 0.181658E+09 |
October | 0.808786E+09 | 0.141254E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232950E+09 |
November | 0.781956E+09 | 0.136789E+10 | 0.207262E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421988E+09 |
December | 0.808298E+09 | 0.140915E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629625E+09 |
Annual Sum or Average | 0.957291E+10 | 0.167246E+11 | 0.252169E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 7294339.72 | 0.379394E+10 |
Minimum of Months | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80554386.58 |
Maximum of Months | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3232516.32 | 0.629625E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905160E+09 | 0.144894E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800253E+09 | 0.190388E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716172E+09 | 0.299709E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667284E+09 | 0.331838E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644959E+09 | 0.454075E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541783E+09 | 0.438833E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753622E+09 | 0.472824E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583661E+09 | 0.373526E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600708E+09 | 0.269387E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843884E+09 | 0.173475E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780203E+09 | 0.931036E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749960E+09 | 0.109264E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858765E+10 | 0.335132E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541783E+09 | 0.931036E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905160E+09 | 0.472824E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2023.86 | 02-JAN-16:30 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 23350.77 | 04-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2023.86 | 01-FEB-17:10 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 20635.15 | 01-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 2023.86 | 01-MAR-17:00 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 17724.37 | 06-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2023.86 | 01-APR-18:40 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 543.69 | 23-APR-16:05 | 12009.74 | 04-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 2023.86 | 01-MAY-19:30 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1952.51 | 25-MAY-18:00 | 5722.09 | 08-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 2023.86 | 01-JUN-19:00 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3648.00 | 29-JUN-17:05 | 4064.57 | 02-JUN-12:00 |
July | 30255.31 | 01-JUL-18:10 | 2023.86 | 01-JUL-20:19 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1836.69 | 29-JUL-17:03 | 4147.23 | 08-JUL-19:00 |
August | 30255.31 | 05-AUG-18:10 | 2023.86 | 01-AUG-19:49 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1945.16 | 08-AUG-17:03 | 4589.34 | 17-AUG-11:55 |
September | 30255.31 | 02-SEP-18:10 | 2023.86 | 01-SEP-18:00 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 444.94 | 01-SEP-16:05 | 6054.55 | 23-SEP-18:52 |
October | 30255.31 | 07-OCT-18:10 | 2023.86 | 02-OCT-17:49 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 9466.26 | 31-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2023.86 | 01-NOV-16:00 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 16874.89 | 25-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 2023.86 | 01-DEC-16:19 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 21852.70 | 19-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2023.86 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4064.57 | |||||
Maximum of Months | 30255.31 | 2023.86 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3648.00 | 23350.77 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 859.87 | 02-JAN-10:09 | 13642.30 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1516.86 | 04-JAN-03:00 |
February | 813.01 | 04-FEB-19:10 | 859.87 | 01-FEB-10:09 | 13642.30 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1469.08 | 13-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 859.87 | 01-MAR-10:09 | 13642.30 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1071.67 | 17-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 859.87 | 01-APR-16:10 | 13642.30 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 7.22 | 23-APR-15:55 | 863.21 | 02-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 859.87 | 01-MAY-09:09 | 13642.30 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 9.49 | 24-MAY-15:00 | 499.32 | 09-MAY-03:35 |
June | 813.01 | 03-JUN-18:10 | 859.87 | 01-JUN-09:09 | 13642.30 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 50.78 | 29-JUN-15:00 | 433.05 | 20-JUN-03:40 |
July | 813.01 | 01-JUL-18:10 | 859.87 | 01-JUL-16:10 | 13642.30 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 37.64 | 15-JUL-15:00 | 329.99 | 06-JUL-02:50 |
August | 813.01 | 05-AUG-18:10 | 859.87 | 01-AUG-09:09 | 13642.30 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 30.66 | 08-AUG-16:00 | 412.62 | 17-AUG-02:00 |
September | 813.01 | 02-SEP-18:10 | 859.87 | 01-SEP-09:09 | 13642.30 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.33 | 01-SEP-15:00 | 624.02 | 11-SEP-03:00 |
October | 813.01 | 07-OCT-18:10 | 859.87 | 02-OCT-09:09 | 13642.30 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 709.46 | 31-OCT-03:50 |
November | 813.01 | 04-NOV-18:10 | 859.87 | 01-NOV-09:09 | 13642.30 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1278.76 | 22-NOV-02:00 |
December | 813.01 | 02-DEC-19:10 | 859.87 | 01-DEC-10:09 | 13642.30 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1312.45 | 16-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 329.99 | ||||||
Maximum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 50.78 | 1516.86 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2131.90 | 28-JAN-02:50 | 5315.82 | 27-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2219.40 | 17-FEB-07:45 | 5082.01 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1865.86 | 03-MAR-01:00 | 8437.02 | 23-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2152.21 | 22-APR-04:00 | 6978.22 | 21-APR-13:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1939.04 | 02-MAY-04:01 | 8068.46 | 01-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1884.57 | 04-JUN-04:00 | 7364.25 | 14-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.92 | 15-JUL-04:53 | 8270.85 | 13-JUL-12:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2181.32 | 05-AUG-03:55 | 7190.91 | 04-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.10 | 06-SEP-05:40 | 5866.56 | 01-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1919.55 | 25-OCT-07:00 | 5766.36 | 09-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.27 | 19-NOV-07:30 | 3420.28 | 07-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.00 | 03-DEC-01:25 | 4526.80 | 02-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.00 | 3420.28 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2219.40 | 8437.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 75962.62 | 06-JAN-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.08 |
February | 68206.17 | 14-FEB-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.94 |
March | 60337.65 | 05-MAR-00:01 | 16808.50 | 4497.58 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.13 |
April | 43812.26 | 04-APR-23:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.36 |
May | 59424.41 | 19-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.44 |
June | 49829.09 | 25-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.82 |
July | 58240.75 | 24-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.44 |
August | 59793.37 | 10-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.81 |
September | 55471.94 | 01-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.51 |
October | 40032.36 | 29-OCT-23:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50835.63 | 25-NOV-00:01 | 16808.50 | 4497.58 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.28 |
December | 74146.96 | 25-DEC-00:01 | 16808.50 | 4497.58 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 971.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 40032.36 | 0.00 | 800.29 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75962.62 | 16808.50 | 4497.58 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56420.83 | 13-JAN-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56337.03 | 17-FEB-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 73.14 |
March | 49430.91 | 12-MAR-04:01 | 0.00 | 270.10 | 53701.63 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 75.12 |
April | 36688.53 | 05-APR-04:01 | 406.51 | 270.10 | 53922.80 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 76.41 |
May | 49414.14 | 18-MAY-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50940.35 | 18-JUN-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 192.18 |
July | 50301.85 | 02-JUL-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 |
August | 49561.34 | 25-AUG-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49194.12 | 09-SEP-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 306.66 |
October | 36348.36 | 30-OCT-04:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 |
November | 45060.42 | 29-NOV-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 |
December | 51905.38 | 26-DEC-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 136.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36348.36 | 0.00 | 270.10 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56420.83 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 306.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.21 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.70 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.82 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.73 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1506.30 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.59 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.27 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.34 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.24 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.46 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.81 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1506.30 | 113.46 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.624191E+11 | 36618.32 | 04-JAN-11:20 | 0.348583E+12 | 255087.23 | 06-JAN-07:49 |
February | 0.554607E+11 | 36404.52 | 13-FEB-11:09 | 0.261657E+12 | 241884.24 | 14-FEB-07:30 |
March | 0.604394E+11 | 36167.56 | 15-MAR-10:20 | 0.235508E+12 | 217084.83 | 16-MAR-03:49 |
April | 0.573481E+11 | 39887.14 | 23-APR-16:19 | 0.137277E+12 | 153782.74 | 05-APR-06:30 |
May | 0.630206E+11 | 48766.42 | 26-MAY-10:00 | 0.871682E+11 | 106764.97 | 01-MAY-06:10 |
June | 0.684790E+11 | 61627.69 | 30-JUN-11:00 | 0.737208E+11 | 65538.37 | 04-JUN-05:19 |
July | 0.760131E+11 | 56067.51 | 21-JUL-11:00 | 0.727707E+11 | 49967.42 | 06-JUL-18:40 |
August | 0.711839E+11 | 55942.80 | 08-AUG-17:10 | 0.724678E+11 | 54617.47 | 19-AUG-05:10 |
September | 0.594600E+11 | 48405.93 | 01-SEP-10:00 | 0.775205E+11 | 65976.75 | 06-SEP-06:49 |
October | 0.598925E+11 | 37742.52 | 19-OCT-17:19 | 0.119036E+12 | 132506.92 | 30-OCT-06:49 |
November | 0.588505E+11 | 36106.65 | 25-NOV-11:09 | 0.182982E+12 | 204100.89 | 25-NOV-04:30 |
December | 0.622989E+11 | 36456.13 | 24-DEC-11:20 | 0.321701E+12 | 227236.04 | 20-DEC-07:10 |
Annual Sum or Average | 0.754866E+12 | 0.199039E+13 | ||||
Minimum of Months | 0.554607E+11 | 36106.65 | 0.724678E+11 | 49967.42 | ||
Maximum of Months | 0.760131E+11 | 61627.69 | 0.348583E+12 | 255087.23 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.394591E+10 | 0.301973E+10 | 0.370015E+11 | 0.00 | 0.920125E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639948E+10 | 0.00 |
February | 0.346245E+10 | 0.241596E+10 | 0.334207E+11 | 0.00 | 0.778859E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579175E+10 | 0.00 |
March | 0.375064E+10 | 0.225201E+10 | 0.370017E+11 | 0.00 | 0.809319E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646802E+10 | 0.00 |
April | 0.344445E+10 | 0.175412E+10 | 0.358080E+11 | 0.00 | 0.696493E+10 | 36657632.61 | 0.00 | 0.311346E+09 | 0.00 | 0.00 | 0.00 | 0.620835E+10 | 0.00 |
May | 0.345913E+10 | 0.148731E+10 | 0.370016E+11 | 0.00 | 0.674702E+10 | 37879553.69 | 0.00 | 0.474292E+10 | 0.00 | 0.00 | 0.00 | 0.642164E+10 | 0.00 |
June | 0.332310E+10 | 0.128182E+10 | 0.358081E+11 | 0.00 | 0.670224E+10 | 36657632.61 | 0.00 | 0.119579E+11 | 0.00 | 0.00 | 0.00 | 0.623864E+10 | 0.00 |
July | 0.339445E+10 | 0.138134E+10 | 0.370015E+11 | 0.00 | 0.704886E+10 | 37879553.69 | 0.00 | 0.175131E+11 | 0.00 | 0.00 | 0.00 | 0.637284E+10 | 0.00 |
August | 0.357655E+10 | 0.164539E+10 | 0.370017E+11 | 0.00 | 0.684254E+10 | 37879553.69 | 0.00 | 0.123692E+11 | 0.00 | 0.00 | 0.00 | 0.645135E+10 | 0.00 |
September | 0.351919E+10 | 0.199320E+10 | 0.358080E+11 | 0.00 | 0.651252E+10 | 36657632.61 | 0.00 | 0.235470E+10 | 0.00 | 0.00 | 0.00 | 0.620113E+10 | 0.00 |
October | 0.375621E+10 | 0.250039E+10 | 0.370015E+11 | 0.00 | 0.704301E+10 | 37879553.69 | 0.00 | 0.215493E+09 | 0.00 | 0.00 | 0.00 | 0.639348E+10 | 0.00 |
November | 0.380249E+10 | 0.280608E+10 | 0.358078E+11 | 0.00 | 0.743583E+10 | 36657632.61 | 0.00 | 3812029.12 | 0.00 | 0.00 | 0.00 | 0.619204E+10 | 0.00 |
December | 0.398269E+10 | 0.312200E+10 | 0.370015E+11 | 0.00 | 0.894571E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639132E+10 | 0.00 |
Annual Sum or Average | 0.434173E+11 | 0.256594E+11 | 0.435663E+12 | 0.00 | 0.893257E+11 | 0.446001E+09 | 0.00 | 0.494684E+11 | 0.00 | 0.00 | 0.00 | 0.755300E+11 | 0.00 |
Minimum of Months | 0.332310E+10 | 0.128182E+10 | 0.334207E+11 | 0.00 | 0.651252E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579175E+10 | 0.00 |
Maximum of Months | 0.398269E+10 | 0.312200E+10 | 0.370017E+11 | 0.00 | 0.920125E+10 | 37879553.69 | 0.00 | 0.175131E+11 | 0.00 | 0.00 | 0.00 | 0.646802E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.270338E+12 | 0.00 | 0.383459E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.190201E+12 | 0.00 | 0.354174E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.156220E+12 | 0.00 | 0.393887E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.618865E+11 | 0.00 | 0.367781E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.110262E+11 | 0.00 | 0.362422E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.181265E+10 | 0.00 | 0.332955E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.438514E+09 | 0.00 | 0.324324E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.629931E+09 | 0.00 | 0.319381E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.800798E+10 | 0.00 | 0.308999E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.461093E+11 | 0.00 | 0.330271E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.110683E+12 | 0.00 | 0.336863E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.245116E+12 | 0.00 | 0.366854E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.110247E+13 | 0.00 | 0.418137E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.438514E+09 | 0.00 | 0.308999E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.270338E+12 | 0.00 | 0.393887E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2883.74 | 02-JAN-16:30 | 2213.72 | 01-JAN-06:10 | 23897.06 | 01-JAN-11:09 | 0.00 | 4887.85 | 06-JAN-07:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 2883.74 | 01-FEB-17:10 | 2213.72 | 01-FEB-06:10 | 23897.06 | 01-FEB-11:09 | 0.00 | 4798.72 | 14-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 2883.74 | 01-MAR-17:00 | 2213.72 | 01-MAR-06:10 | 23897.06 | 01-MAR-11:09 | 0.00 | 4644.46 | 05-MAR-07:10 | 17.86 | 05-MAR-09:00 | 0.00 | 01-MAR-00:10 |
April | 2883.74 | 01-APR-18:40 | 2213.72 | 01-APR-05:10 | 23897.06 | 01-APR-10:09 | 0.00 | 4001.43 | 05-APR-05:00 | 17.86 | 11-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 2883.74 | 01-MAY-19:30 | 2213.72 | 01-MAY-19:30 | 23897.06 | 01-MAY-10:09 | 0.00 | 3607.41 | 01-MAY-05:00 | 17.86 | 08-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 2883.74 | 01-JUN-19:00 | 2213.72 | 01-JUN-19:00 | 23897.06 | 01-JUN-10:09 | 0.00 | 5199.42 | 29-JUN-17:00 | 17.86 | 12-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 2883.74 | 01-JUL-20:19 | 2213.72 | 01-JUL-20:19 | 23897.06 | 01-JUL-10:09 | 0.00 | 4574.16 | 15-JUL-13:00 | 17.86 | 03-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 2883.74 | 01-AUG-19:49 | 2213.72 | 01-AUG-19:49 | 23897.06 | 01-AUG-10:09 | 0.00 | 4569.52 | 08-AUG-17:19 | 17.86 | 10-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2883.74 | 01-SEP-18:00 | 2213.72 | 01-SEP-05:10 | 23897.06 | 01-SEP-10:09 | 0.00 | 3303.98 | 06-SEP-04:00 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 2883.74 | 02-OCT-17:49 | 2213.72 | 01-OCT-05:10 | 23897.06 | 01-OCT-10:09 | 0.00 | 3836.18 | 30-OCT-05:10 | 17.86 | 06-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 2883.74 | 01-NOV-16:00 | 2213.72 | 01-NOV-05:10 | 23897.06 | 01-NOV-10:09 | 0.00 | 4250.35 | 29-NOV-06:10 | 17.86 | 20-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 2883.74 | 01-DEC-16:19 | 2213.72 | 01-DEC-06:10 | 23897.06 | 01-DEC-11:09 | 0.00 | 4747.31 | 24-DEC-07:10 | 17.86 | 01-DEC-00:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2883.74 | 2213.72 | 23897.06 | 0.00 | 3303.98 | 17.86 | 0.00 | ||||||
Maximum of Months | 2883.74 | 2213.72 | 23897.06 | 0.00 | 5199.42 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.46 | 11-JAN-19:40 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4742.16 | 22-FEB-07:49 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 4742.00 | 08-MAR-07:40 | 0.00 |
April | 10552.07 | 23-APR-17:19 | 0.00 | 0.00 | 0.00 | 4742.07 | 28-APR-06:19 | 0.00 |
May | 17711.49 | 25-MAY-17:00 | 0.00 | 0.00 | 0.00 | 4741.87 | 04-MAY-06:40 | 0.00 |
June | 28898.26 | 29-JUN-17:49 | 0.00 | 0.00 | 0.00 | 4740.45 | 02-JUN-06:19 | 0.00 |
July | 24888.42 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 4739.85 | 10-JUL-06:10 | 0.00 |
August | 24229.60 | 08-AUG-17:19 | 0.00 | 0.00 | 0.00 | 4739.12 | 03-AUG-06:00 | 0.00 |
September | 15382.53 | 01-SEP-17:19 | 0.00 | 0.00 | 0.00 | 4741.41 | 07-SEP-06:10 | 0.00 |
October | 5865.91 | 19-OCT-16:10 | 0.00 | 0.00 | 0.00 | 4741.52 | 06-OCT-06:49 | 0.00 |
November | 474.61 | 01-NOV-16:19 | 0.00 | 0.00 | 0.00 | 4741.86 | 29-NOV-07:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4741.47 | 12-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4739.12 | 0.00 | ||
Maximum of Months | 28898.26 | 0.00 | 0.00 | 0.00 | 4742.16 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 36618.32 | 04-JAN-11:20 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4539.95 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 36404.52 | 13-FEB-11:09 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4292.20 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 36167.56 | 15-MAR-10:20 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4020.40 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 39887.14 | 23-APR-16:19 | 1247.87 | 21486.07 | 0.00 | 0.00 | 2929.11 | 17.86 | 0.00 | 9947.72 | 0.00 |
May | 48766.42 | 26-MAY-10:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 3269.89 | 17.86 | 0.00 | 14342.35 | 0.00 |
June | 61627.69 | 30-JUN-11:00 | 1871.80 | 22289.73 | 0.00 | 0.00 | 5136.13 | 17.86 | 0.00 | 28115.01 | 0.00 |
July | 56067.51 | 21-JUL-11:00 | 1871.80 | 22289.73 | 0.00 | 0.00 | 4388.70 | 17.86 | 0.00 | 23315.19 | 0.00 |
August | 55942.80 | 08-AUG-17:10 | 1871.80 | 19878.74 | 0.00 | 0.00 | 4556.39 | 17.86 | 0.00 | 24227.38 | 0.00 |
September | 48405.93 | 01-SEP-10:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 3210.27 | 17.86 | 0.00 | 14040.62 | 0.00 |
October | 37742.52 | 19-OCT-17:19 | 2883.74 | 19878.74 | 2213.72 | 0.00 | 2929.11 | 17.86 | 0.00 | 4220.46 | 0.00 |
November | 36106.65 | 25-NOV-11:09 | 1663.82 | 23897.06 | 0.00 | 0.00 | 3971.37 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 36456.13 | 24-DEC-11:20 | 1455.85 | 23897.06 | 0.00 | 0.00 | 4476.65 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 36106.65 | 1247.87 | 19878.74 | 0.00 | 0.00 | 2929.11 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61627.69 | 2883.74 | 23897.06 | 2213.72 | 0.00 | 5136.13 | 17.86 | 0.00 | 28115.01 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 208590.19 | 06-JAN-07:10 | 0.00 | 37286.21 | 31-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 199173.64 | 14-FEB-07:10 | 0.00 | 37636.70 | 28-FEB-07:30 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 198627.50 | 06-MAR-04:30 | 0.00 | 37580.00 | 06-MAR-19:19 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 113297.77 | 05-APR-04:19 | 0.00 | 36892.26 | 03-APR-06:19 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 69913.88 | 01-MAY-05:00 | 0.00 | 34969.91 | 05-MAY-18:40 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 44799.31 | 04-JUN-04:00 | 0.00 | 32909.77 | 02-JUN-06:30 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 15216.16 | 02-JUL-04:00 | 0.00 | 30283.27 | 03-JUL-06:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 28327.81 | 19-AUG-04:00 | 0.00 | 28567.80 | 03-AUG-06:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 37077.18 | 06-SEP-04:00 | 0.00 | 29093.82 | 29-SEP-06:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 94813.33 | 30-OCT-05:10 | 0.00 | 31318.46 | 31-OCT-06:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 198627.50 | 25-NOV-04:30 | 0.00 | 33768.76 | 30-NOV-19:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 198627.50 | 11-DEC-04:30 | 0.00 | 35693.66 | 27-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 15216.16 | 0.00 | 28567.80 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 208590.19 | 0.00 | 37636.70 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.83 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 8.83 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
March | 6.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
April | 1.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.84 | 0.00 | 24.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.61 | 0.00 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.60 | 0.00 | 24.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
November | 3.33 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
December | 8.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Annual Sum or Average | 42.00 | 19.29 | 0.00 | 19.29 | 1.67 | 19.49 | 0.00 | 19.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.83 | 20.42 | 0.00 | 20.42 | 1.00 | 24.84 | 0.00 | 24.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.10 | 0.00 | 27.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.89 | 0.00 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.23 | 2.83 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 29.15 | 1.33 | 28.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 29.38 | 0.00 | 29.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.06 | 0.00 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.26 | 0.00 | 27.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.78 | 0.00 | 26.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.17 | 28.60 | 4.17 | 28.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 29.38 | 2.83 | 29.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.73 | 551.83 | 20.72 | 551.83 | 20.71 |
February | 551.00 | 20.73 | 415.00 | 20.70 | 415.00 | 20.68 |
March | 612.00 | 20.74 | 351.67 | 20.67 | 351.67 | 20.63 |
April | 574.17 | 21.02 | 143.00 | 20.86 | 138.17 | 20.73 |
May | 394.67 | 21.49 | 164.17 | 22.02 | 24.83 | 21.90 |
June | 355.17 | 22.76 | 350.33 | 23.33 | 175.17 | 23.43 |
July | 315.17 | 23.30 | 496.67 | 23.70 | 223.17 | 23.75 |
August | 338.33 | 23.05 | 448.17 | 23.54 | 204.67 | 23.61 |
September | 417.00 | 21.52 | 164.67 | 22.06 | 56.00 | 22.10 |
October | 576.83 | 20.90 | 66.00 | 20.78 | 54.17 | 20.63 |
November | 591.00 | 20.79 | 224.00 | 20.67 | 224.00 | 20.60 |
December | 609.00 | 20.73 | 537.00 | 20.71 | 537.00 | 20.71 |
Annual Sum or Average | 5944.33 | 21.28 | 3912.50 | 21.53 | 2955.67 | 21.47 |
Minimum of Months | 315.17 | 20.73 | 66.00 | 20.67 | 24.83 | 20.60 |
Maximum of Months | 612.00 | 23.30 | 551.83 | 23.70 | 551.83 | 23.75 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.00 | 559.17 | 19.00 | 559.17 | 19.00 |
February | 551.00 | 19.01 | 459.50 | 19.00 | 459.50 | 19.00 |
March | 612.00 | 19.03 | 451.67 | 19.02 | 451.67 | 19.01 |
April | 514.00 | 19.55 | 287.50 | 19.92 | 222.00 | 19.77 |
May | 380.33 | 23.00 | 398.00 | 24.07 | 203.00 | 24.35 |
June | 454.83 | 25.41 | 526.33 | 25.50 | 407.50 | 25.63 |
July | 526.83 | 25.84 | 590.17 | 25.75 | 516.33 | 25.81 |
August | 485.17 | 25.79 | 590.83 | 25.65 | 474.33 | 25.73 |
September | 389.67 | 23.36 | 373.00 | 24.20 | 218.17 | 24.56 |
October | 534.67 | 19.80 | 174.17 | 20.29 | 110.33 | 20.31 |
November | 578.33 | 19.17 | 295.33 | 19.22 | 284.33 | 19.19 |
December | 609.00 | 19.00 | 535.67 | 19.00 | 535.67 | 19.00 |
Annual Sum or Average | 6245.83 | 21.22 | 5241.33 | 21.69 | 4442.00 | 21.74 |
Minimum of Months | 380.33 | 19.00 | 174.17 | 19.00 | 110.33 | 19.00 |
Maximum of Months | 612.00 | 25.84 | 590.83 | 25.75 | 559.17 | 25.81 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73174 | 13.60667 | -0.7136 | 16.54483 |
February | 551.00000 | 20.73295 | 15.52473 | -0.6583 | 15.06533 |
March | 612.00000 | 20.73848 | 19.56438 | -0.6114 | 13.80960 |
April | 590.00000 | 21.10234 | 25.15599 | -0.4285 | 10.80945 |
May | 611.00000 | 22.36826 | 38.05736 | -0.9997 | 30.41253 |
June | 592.00000 | 23.22080 | 53.48406 | -0.5775 | 15.66073 |
July | 609.00000 | 23.58140 | 59.39396 | -0.3662 | 9.79823 |
August | 612.00000 | 23.40518 | 58.04327 | -0.4436 | 11.49580 |
September | 590.00000 | 22.20706 | 47.72043 | -0.9513 | 28.03829 |
October | 610.00000 | 21.06152 | 35.23380 | -0.3330 | 9.01937 |
November | 591.00000 | 20.79106 | 23.88754 | -0.5347 | 12.11075 |
December | 609.00000 | 20.73180 | 15.03506 | -0.6897 | 15.83275 |
Annual Sum or Average | 7187.00000 | 21.73009 | 33.83891 | -0.6084 | 15.71200 |
Minimum of Months | 551.00000 | 20.73174 | 13.60667 | -0.9997 | 9.01937 |
Maximum of Months | 612.00000 | 23.58140 | 59.39396 | -0.3330 | 30.41253 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.00120 | 20.49834 | -0.7885 | 18.42499 |
February | 551.00000 | 19.00680 | 23.63667 | -0.7488 | 17.17953 |
March | 612.00000 | 19.03449 | 28.50873 | -0.7024 | 15.81318 |
April | 590.00000 | 20.23969 | 33.63874 | -0.3540 | 12.80371 |
May | 611.00000 | 23.53061 | 41.15177 | -0.3161 | 21.36664 |
June | 592.00000 | 25.10228 | 51.49542 | 0.31770 | 13.73381 |
July | 609.00000 | 25.54156 | 55.73067 | 0.54336 | 14.38025 |
August | 612.00000 | 25.37879 | 54.05768 | 0.47433 | 13.38218 |
September | 590.00000 | 23.43167 | 48.51151 | -0.2413 | 18.71773 |
October | 610.00000 | 20.31166 | 42.24819 | -0.2191 | 10.88482 |
November | 591.00000 | 19.28444 | 31.45391 | -0.5647 | 13.41914 |
December | 609.00000 | 19.00140 | 21.77386 | -0.7587 | 17.43448 |
Annual Sum or Average | 7187.00000 | 21.58928 | 37.80674 | -0.2766 | 15.62563 |
Minimum of Months | 551.00000 | 19.00120 | 20.49834 | -0.7885 | 10.88482 |
Maximum of Months | 612.00000 | 25.54156 | 55.73067 | 0.54336 | 21.36664 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.579287E+09 | 0.182035E+09 | 19.00 | 0.467674E+09 | 0.111613E+09 | 0.00 | 0.62 | 23-APR-17:10 | 0.00 | 01-APR-00:01 | 23324.94 | 23-APR-17:10 | 18452.76 | 23-APR-17:05 | 5133.12 | 23-APR-18:10 | 6968.15 | 23-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.957304E+10 | 0.287177E+10 | 176.79 | 0.744775E+10 | 0.212529E+10 | 0.00 | 1.00 | 19-MAY-03:01 | 0.00 | 01-MAY-00:01 | 84510.78 | 25-MAY-03:01 | 64428.11 | 19-MAY-03:01 | 38781.62 | 27-MAY-03:01 | 22642.85 | 19-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.252314E+11 | 0.712562E+10 | 315.53 | 0.158990E+11 | 0.933240E+10 | 0.00 | 1.00 | 07-JUN-03:01 | 0.00 | 01-JUN-00:01 | 93897.04 | 30-JUN-03:01 | 53795.20 | 07-JUN-03:01 | 56005.20 | 30-JUN-03:01 | 23355.96 | 30-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.382435E+11 | 0.105867E+11 | 415.24 | 0.224459E+11 | 0.157976E+11 | 0.00 | 1.00 | 01-JUL-03:02 | 0.00 | 01-JUL-00:01 | 93897.04 | 04-JUL-03:01 | 52713.33 | 06-JUL-03:01 | 61508.75 | 04-JUL-03:02 | 23355.96 | 04-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.254144E+11 | 0.727028E+10 | 336.31 | 0.152385E+11 | 0.101760E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 88255.37 | 09-AUG-03:01 | 53684.33 | 07-AUG-03:01 | 46832.74 | 09-AUG-03:01 | 22922.36 | 09-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.373610E+10 | 0.116522E+10 | 119.65 | 0.262135E+10 | 0.111475E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 85817.40 | 01-SEP-03:01 | 51642.42 | 02-SEP-03:01 | 48046.12 | 01-SEP-03:01 | 22741.37 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.318466E+09 | 0.106021E+09 | 21.26 | 0.261363E+09 | 57102302.46 | 0.00 | 0.35 | 19-OCT-13:00 | 0.00 | 01-OCT-00:01 | 12226.73 | 19-OCT-13:00 | 9542.94 | 19-OCT-16:05 | 2813.37 | 19-OCT-13:00 | 3915.31 | 19-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.103096E+12 | 0.293076E+11 | 1403.78 | 0.643815E+11 | 0.387147E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.382435E+11 | 0.105867E+11 | 415.24 | 0.224459E+11 | 0.157976E+11 | 0.00 | 1.00 | 0.00 | 93897.04 | 64428.11 | 61508.75 | 23355.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.475832E+09 | 0.129311E+09 | 29.72 | 0.398070E+09 | 77762401.66 | 0.00 | 1.00 | 14-APR-03:42 | 0.00 | 01-APR-00:01 | 17964.72 | 14-APR-03:42 | 12266.04 | 14-APR-03:42 | 5698.67 | 14-APR-03:42 | 4310.38 | 14-APR-03:42 | 0.00 | 01-APR-00:01 |
May | 0.727813E+10 | 0.187114E+10 | 215.92 | 0.571136E+10 | 0.156677E+10 | 0.00 | 1.00 | 05-MAY-03:41 | 0.00 | 01-MAY-00:01 | 35970.69 | 26-MAY-03:11 | 29592.21 | 05-MAY-03:41 | 18574.01 | 27-MAY-03:01 | 8623.94 | 05-MAY-03:41 | 0.00 | 01-MAY-00:01 |
June | 0.198851E+11 | 0.483227E+10 | 377.35 | 0.122720E+11 | 0.761311E+10 | 0.00 | 1.00 | 02-JUN-03:01 | 0.00 | 01-JUN-00:01 | 39965.81 | 29-JUN-10:56 | 29109.95 | 29-JUN-17:00 | 23848.60 | 30-JUN-02:33 | 9650.15 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.292101E+11 | 0.692645E+10 | 473.41 | 0.167121E+11 | 0.124980E+11 | 0.00 | 1.00 | 01-JUL-03:11 | 0.00 | 01-JUL-00:01 | 39965.81 | 05-JUL-10:41 | 22557.95 | 29-JUL-16:20 | 26681.82 | 04-JUL-03:01 | 9120.71 | 15-JUL-13:53 | 0.00 | 01-JUL-00:01 |
August | 0.209051E+11 | 0.509889E+10 | 413.38 | 0.120779E+11 | 0.882714E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 37967.87 | 08-AUG-16:53 | 22881.86 | 08-AUG-15:40 | 22341.19 | 01-AUG-03:01 | 8702.82 | 09-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.444024E+10 | 0.118948E+10 | 180.89 | 0.293255E+10 | 0.150770E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 35970.69 | 01-SEP-03:01 | 29338.99 | 09-SEP-03:42 | 21733.90 | 01-SEP-03:21 | 8623.94 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.380026E+09 | 0.109472E+09 | 28.41 | 0.307865E+09 | 72160748.45 | 0.00 | 1.00 | 02-OCT-03:01 | 0.00 | 01-OCT-00:01 | 17964.72 | 02-OCT-03:01 | 11183.89 | 02-OCT-03:01 | 8208.65 | 20-OCT-03:41 | 4310.38 | 02-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 12488843.49 | 3812029.12 | 3.67 | 8047108.02 | 4441735.47 | 0.00 | 0.11 | 01-NOV-16:20 | 0.00 | 01-NOV-00:01 | 1564.55 | 01-NOV-16:20 | 1013.89 | 01-NOV-16:20 | 676.88 | 21-NOV-04:20 | 474.61 | 01-NOV-16:20 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.825870E+11 | 0.201608E+11 | 1722.74 | 0.504199E+11 | 0.321671E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.292101E+11 | 0.692645E+10 | 473.41 | 0.167121E+11 | 0.124980E+11 | 0.00 | 1.00 | 0.00 | 39965.81 | 29592.21 | 26681.82 | 9650.15 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 154.14 | 63.88 | 90.26 | 60.54 | 582.38 | 0.00 | 0.00 | 0.00 |
February | 244.99 | 105.35 | 139.65 | 151.57 | 455.31 | 0.00 | 0.00 | 0.00 |
March | 333.11 | 167.49 | 165.62 | 270.41 | 349.16 | 0.00 | 0.00 | 0.00 |
April | 458.80 | 247.40 | 211.41 | 474.95 | 209.24 | 0.00 | 0.00 | 0.00 |
May | 498.29 | 219.82 | 278.47 | 591.19 | 113.47 | 0.00 | 0.00 | 0.00 |
June | 562.29 | 269.02 | 293.27 | 716.82 | 81.24 | 0.00 | 0.00 | 0.00 |
July | 551.99 | 259.76 | 292.23 | 715.89 | 77.23 | 0.00 | 0.00 | 0.00 |
August | 424.86 | 185.72 | 239.14 | 530.28 | 92.03 | 0.00 | 0.00 | 0.00 |
September | 341.14 | 153.10 | 188.04 | 382.34 | 140.11 | 0.00 | 0.00 | 0.00 |
October | 205.36 | 77.22 | 128.14 | 171.94 | 219.18 | 0.00 | 0.00 | 0.00 |
November | 131.52 | 43.78 | 87.74 | 66.12 | 349.10 | 0.00 | 0.00 | 0.00 |
December | 120.90 | 45.36 | 75.55 | 38.07 | 566.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 335.95 | 153.27 | 182.67 | 348.43 | 268.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.90 | 43.78 | 75.55 | 38.07 | 77.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 562.29 | 269.02 | 293.27 | 716.82 | 582.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 677.82 | 472.55 | 205.26 | 599.46 | 707.36 | 0.00 | 0.00 | 0.00 |
February | 846.18 | 569.54 | 276.64 | 846.34 | 588.36 | 0.00 | 0.00 | 0.00 |
March | 743.43 | 468.00 | 275.43 | 767.16 | 477.27 | 0.00 | 0.00 | 0.00 |
April | 678.45 | 367.65 | 310.80 | 767.82 | 306.90 | 0.00 | 0.00 | 0.00 |
May | 580.45 | 204.37 | 376.08 | 720.16 | 170.29 | 0.00 | 0.00 | 0.00 |
June | 509.93 | 133.86 | 376.07 | 668.16 | 118.79 | 0.00 | 0.00 | 0.00 |
July | 561.06 | 178.03 | 383.03 | 762.66 | 112.38 | 0.00 | 0.00 | 0.00 |
August | 595.61 | 247.32 | 348.30 | 783.36 | 131.33 | 0.00 | 0.00 | 0.00 |
September | 628.64 | 328.85 | 299.79 | 769.22 | 200.11 | 0.00 | 0.00 | 0.00 |
October | 559.37 | 333.60 | 225.78 | 610.07 | 300.76 | 0.00 | 0.00 | 0.00 |
November | 488.68 | 306.56 | 182.12 | 465.03 | 450.58 | 0.00 | 0.00 | 0.00 |
December | 520.59 | 341.70 | 178.89 | 424.03 | 687.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 614.39 | 327.85 | 286.54 | 680.76 | 353.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.68 | 133.86 | 178.89 | 424.03 | 112.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 846.18 | 569.54 | 383.03 | 846.34 | 707.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.42 | 67.03 | 91.39 | 70.48 | 587.05 | 0.00 | 0.00 | 0.00 |
February | 256.33 | 117.63 | 138.70 | 178.24 | 468.33 | 0.00 | 0.00 | 0.00 |
March | 336.38 | 172.57 | 163.81 | 285.91 | 360.89 | 0.00 | 0.00 | 0.00 |
April | 429.30 | 217.83 | 211.47 | 442.03 | 217.99 | 0.00 | 0.00 | 0.00 |
May | 527.96 | 252.69 | 275.27 | 635.77 | 119.82 | 0.00 | 0.00 | 0.00 |
June | 507.25 | 219.16 | 288.09 | 642.84 | 83.92 | 0.00 | 0.00 | 0.00 |
July | 542.27 | 252.26 | 290.01 | 706.62 | 80.09 | 0.00 | 0.00 | 0.00 |
August | 445.12 | 201.75 | 243.36 | 561.41 | 93.80 | 0.00 | 0.00 | 0.00 |
September | 349.44 | 156.92 | 192.52 | 396.41 | 143.34 | 0.00 | 0.00 | 0.00 |
October | 220.96 | 88.92 | 132.04 | 198.05 | 223.70 | 0.00 | 0.00 | 0.00 |
November | 134.42 | 45.68 | 88.74 | 74.36 | 353.48 | 0.00 | 0.00 | 0.00 |
December | 118.47 | 41.02 | 77.45 | 38.39 | 569.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 335.96 | 153.00 | 182.96 | 353.58 | 274.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.47 | 41.02 | 77.45 | 38.39 | 80.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 542.27 | 252.69 | 290.01 | 706.62 | 587.05 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.412842E+09 | 0.171087E+09 | 0.241755E+09 | 0.162141E+09 | 0.155986E+10 |
February | 0.592689E+09 | 0.254853E+09 | 0.337836E+09 | 0.366676E+09 | 0.110149E+10 |
March | 0.892203E+09 | 0.448606E+09 | 0.443598E+09 | 0.724263E+09 | 0.935193E+09 |
April | 0.118922E+10 | 0.641252E+09 | 0.547965E+09 | 0.123108E+10 | 0.542343E+09 |
May | 0.133461E+10 | 0.588767E+09 | 0.745841E+09 | 0.158343E+10 | 0.303912E+09 |
June | 0.145746E+10 | 0.697292E+09 | 0.760166E+09 | 0.185800E+10 | 0.210578E+09 |
July | 0.147845E+10 | 0.695733E+09 | 0.782719E+09 | 0.191745E+10 | 0.206865E+09 |
August | 0.113794E+10 | 0.497423E+09 | 0.640520E+09 | 0.142029E+10 | 0.246488E+09 |
September | 0.884228E+09 | 0.396829E+09 | 0.487399E+09 | 0.991028E+09 | 0.363171E+09 |
October | 0.550038E+09 | 0.206828E+09 | 0.343211E+09 | 0.460519E+09 | 0.587043E+09 |
November | 0.340889E+09 | 0.113476E+09 | 0.227412E+09 | 0.171382E+09 | 0.904877E+09 |
December | 0.323828E+09 | 0.121485E+09 | 0.202343E+09 | 0.101971E+09 | 0.151721E+10 |
Annual Sum or Average | 0.105944E+11 | 0.483363E+10 | 0.576076E+10 | 0.109882E+11 | 0.847903E+10 |
Minimum of Months | 0.323828E+09 | 0.113476E+09 | 0.202343E+09 | 0.101971E+09 | 0.206865E+09 |
Maximum of Months | 0.147845E+10 | 0.697292E+09 | 0.782719E+09 | 0.191745E+10 | 0.155986E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181546E+10 | 0.126569E+10 | 0.549777E+09 | 0.160560E+10 | 0.189459E+10 |
February | 0.204707E+10 | 0.137782E+10 | 0.669248E+09 | 0.204748E+10 | 0.142337E+10 |
March | 0.199120E+10 | 0.125348E+10 | 0.737717E+09 | 0.205476E+10 | 0.127832E+10 |
April | 0.175855E+10 | 0.952941E+09 | 0.805605E+09 | 0.199019E+10 | 0.795480E+09 |
May | 0.155468E+10 | 0.547387E+09 | 0.100729E+10 | 0.192887E+10 | 0.456112E+09 |
June | 0.132174E+10 | 0.346955E+09 | 0.974784E+09 | 0.173187E+10 | 0.307908E+09 |
July | 0.150274E+10 | 0.476838E+09 | 0.102591E+10 | 0.204270E+10 | 0.301005E+09 |
August | 0.159528E+10 | 0.662409E+09 | 0.932875E+09 | 0.209815E+10 | 0.351758E+09 |
September | 0.162943E+10 | 0.852367E+09 | 0.777060E+09 | 0.199381E+10 | 0.518687E+09 |
October | 0.149822E+10 | 0.893504E+09 | 0.604720E+09 | 0.163400E+10 | 0.805558E+09 |
November | 0.126665E+10 | 0.794593E+09 | 0.472058E+09 | 0.120535E+10 | 0.116790E+10 |
December | 0.139435E+10 | 0.915220E+09 | 0.479132E+09 | 0.113573E+10 | 0.184242E+10 |
Annual Sum or Average | 0.193754E+11 | 0.103392E+11 | 0.903617E+10 | 0.214685E+11 | 0.111431E+11 |
Minimum of Months | 0.126665E+10 | 0.346955E+09 | 0.472058E+09 | 0.113573E+10 | 0.301005E+09 |
Maximum of Months | 0.204707E+10 | 0.137782E+10 | 0.102591E+10 | 0.209815E+10 | 0.189459E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.424311E+09 | 0.179542E+09 | 0.244769E+09 | 0.188783E+09 | 0.157236E+10 |
February | 0.620116E+09 | 0.284581E+09 | 0.335535E+09 | 0.431192E+09 | 0.113299E+10 |
March | 0.900956E+09 | 0.462220E+09 | 0.438736E+09 | 0.765787E+09 | 0.966618E+09 |
April | 0.111275E+10 | 0.564613E+09 | 0.548135E+09 | 0.114575E+10 | 0.565018E+09 |
May | 0.141409E+10 | 0.676799E+09 | 0.737292E+09 | 0.170284E+10 | 0.320916E+09 |
June | 0.131479E+10 | 0.568051E+09 | 0.746741E+09 | 0.166623E+10 | 0.217511E+09 |
July | 0.145241E+10 | 0.675648E+09 | 0.776761E+09 | 0.189262E+10 | 0.214509E+09 |
August | 0.119220E+10 | 0.540378E+09 | 0.651823E+09 | 0.150367E+10 | 0.251226E+09 |
September | 0.905750E+09 | 0.406727E+09 | 0.499023E+09 | 0.102750E+10 | 0.371541E+09 |
October | 0.591813E+09 | 0.238160E+09 | 0.353653E+09 | 0.530470E+09 | 0.599162E+09 |
November | 0.348415E+09 | 0.118393E+09 | 0.230022E+09 | 0.192746E+09 | 0.916225E+09 |
December | 0.317297E+09 | 0.109861E+09 | 0.207436E+09 | 0.102817E+09 | 0.152439E+10 |
Annual Sum or Average | 0.105949E+11 | 0.482497E+10 | 0.576993E+10 | 0.111504E+11 | 0.865246E+10 |
Minimum of Months | 0.317297E+09 | 0.109861E+09 | 0.207436E+09 | 0.102817E+09 | 0.214509E+09 |
Maximum of Months | 0.145241E+10 | 0.676799E+09 | 0.776761E+09 | 0.189262E+10 | 0.157236E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 613.24 | 1759.55 | 990.37 | 603.46 | 386.91 | 0.00 | 0.00 |
February | 1101.93 | 1437.78 | 1347.50 | 792.52 | 554.98 | 0.00 | 0.00 |
March | 1265.68 | 1129.53 | 1412.92 | 808.06 | 604.86 | 0.00 | 0.00 |
April | 1643.22 | 692.54 | 1566.56 | 832.87 | 733.68 | 0.00 | 0.00 |
May | 1924.84 | 381.30 | 1606.70 | 676.88 | 929.82 | 0.00 | 0.00 |
June | 2014.97 | 271.10 | 1579.47 | 622.03 | 957.44 | 0.00 | 0.00 |
July | 2175.09 | 259.63 | 1655.32 | 690.05 | 965.27 | 0.00 | 0.00 |
August | 1867.93 | 310.04 | 1465.59 | 634.79 | 830.80 | 0.00 | 0.00 |
September | 1534.90 | 470.50 | 1319.21 | 638.86 | 680.36 | 0.00 | 0.00 |
October | 967.04 | 730.62 | 985.69 | 499.74 | 485.96 | 0.00 | 0.00 |
November | 569.80 | 1117.45 | 754.61 | 396.01 | 358.60 | 0.00 | 0.00 |
December | 404.90 | 1727.89 | 759.96 | 428.08 | 331.88 | 0.00 | 0.00 |
Annual Sum or Average | 1341.15 | 854.96 | 1286.30 | 634.13 | 652.17 | 0.00 | 0.00 |
Minimum of Months | 404.90 | 259.63 | 754.61 | 396.01 | 331.88 | 0.00 | 0.00 |
Maximum of Months | 2175.09 | 1759.55 | 1655.32 | 832.87 | 965.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164251E+10 | 0.471279E+10 | 0.265262E+10 | 0.161632E+10 | 0.103630E+10 | 0.00 | 0.00 |
February | 0.266578E+10 | 0.347828E+10 | 0.325988E+10 | 0.191726E+10 | 0.134262E+10 | 0.00 | 0.00 |
March | 0.339001E+10 | 0.302533E+10 | 0.378435E+10 | 0.216430E+10 | 0.162005E+10 | 0.00 | 0.00 |
April | 0.425923E+10 | 0.179505E+10 | 0.406051E+10 | 0.215881E+10 | 0.190171E+10 | 0.00 | 0.00 |
May | 0.515549E+10 | 0.102128E+10 | 0.430337E+10 | 0.181295E+10 | 0.249042E+10 | 0.00 | 0.00 |
June | 0.522280E+10 | 0.702688E+09 | 0.409399E+10 | 0.161230E+10 | 0.248169E+10 | 0.00 | 0.00 |
July | 0.582577E+10 | 0.695389E+09 | 0.443361E+10 | 0.184822E+10 | 0.258539E+10 | 0.00 | 0.00 |
August | 0.500305E+10 | 0.830420E+09 | 0.392543E+10 | 0.170021E+10 | 0.222522E+10 | 0.00 | 0.00 |
September | 0.397847E+10 | 0.121954E+10 | 0.341940E+10 | 0.165592E+10 | 0.176348E+10 | 0.00 | 0.00 |
October | 0.259013E+10 | 0.195690E+10 | 0.264007E+10 | 0.133849E+10 | 0.130158E+10 | 0.00 | 0.00 |
November | 0.147692E+10 | 0.289644E+10 | 0.195595E+10 | 0.102646E+10 | 0.929493E+09 | 0.00 | 0.00 |
December | 0.108449E+10 | 0.462799E+10 | 0.203548E+10 | 0.114657E+10 | 0.888911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.422946E+11 | 0.269621E+11 | 0.405647E+11 | 0.199978E+11 | 0.205669E+11 | 0.00 | 0.00 |
Minimum of Months | 0.108449E+10 | 0.695389E+09 | 0.195595E+10 | 0.102646E+10 | 0.888911E+09 | 0.00 | 0.00 |
Maximum of Months | 0.582577E+10 | 0.471279E+10 | 0.443361E+10 | 0.216430E+10 | 0.258539E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639951E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174332928.5 | 81.22 | 0.00 | 0.00 |
February | 0.579164E+10 | -0.563430E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157341006.0 | 81.22 | 0.00 | 0.00 |
March | 0.646774E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173871641.6 | 81.22 | 0.00 | 0.00 |
April | 0.620838E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164905671.2 | 81.22 | 0.00 | 0.00 |
May | 0.642147E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161289967.3 | 81.22 | 0.00 | 0.00 |
June | 0.623849E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151913517.5 | 81.21 | 0.00 | 0.00 |
July | 0.637269E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155590812.0 | 81.21 | 0.00 | 0.00 |
August | 0.645120E+10 | -0.629520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155998878.2 | 81.21 | 0.00 | 0.00 |
September | 0.620092E+10 | -0.604481E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156103486.8 | 81.22 | 0.00 | 0.00 |
October | 0.639350E+10 | -0.622382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -169678522.8 | 81.22 | 0.00 | 0.00 |
November | 0.619187E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167250704.1 | 81.22 | 0.00 | 0.00 |
December | 0.639126E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174181647.0 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755287E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.196246E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579164E+10 | -0.629520E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174332928.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646774E+10 | -0.563430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151913517.5 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.288294E+11 | -0.278072E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102224E+10 | 58.99 | 0.00 | 0.00 |
February | 0.266684E+11 | -0.257462E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -922194029.7 | 58.99 | 0.00 | 0.00 |
March | 0.296629E+11 | -0.286449E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101806E+10 | 58.99 | 0.00 | 0.00 |
April | 0.276268E+11 | -0.266724E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -954407299.7 | 58.99 | 0.00 | 0.00 |
May | 0.271357E+11 | -0.262330E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -902678590.2 | 58.99 | 0.00 | 0.00 |
June | 0.248200E+11 | -0.239845E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -835517949.5 | 58.99 | 0.00 | 0.00 |
July | 0.240635E+11 | -0.232127E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850793443.9 | 58.99 | 0.00 | 0.00 |
August | 0.236690E+11 | -0.228144E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -854597430.3 | 59.00 | 0.00 | 0.00 |
September | 0.228998E+11 | -0.220260E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -873771601.6 | 58.99 | 0.00 | 0.00 |
October | 0.245420E+11 | -0.235624E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -979574764.8 | 58.99 | 0.00 | 0.00 |
November | 0.251376E+11 | -0.241617E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -975861679.4 | 58.99 | 0.00 | 0.00 |
December | 0.274961E+11 | -0.264752E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102083E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.312551E+12 | -0.301341E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.112105E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228998E+11 | -0.286449E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102224E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.296629E+11 | -0.220260E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -835517949.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.50 | 01-JAN-08:39 | 3302.90 | 33.63 | 196.00 | 231.33 | 3499.28 | 35.11 | 214.83 | 230.83 |
February | 265.33 | 0.51 | 0.50 | 01-FEB-08:39 | 1883.31 | 27.21 | 207.67 | 251.17 | 1984.26 | 27.32 | 202.00 | 251.17 |
March | 254.17 | 0.52 | 0.50 | 02-MAR-10:39 | 1589.97 | 23.18 | 167.67 | 312.50 | 1526.22 | 23.35 | 176.83 | 312.00 |
April | 296.33 | 0.52 | 0.50 | 01-APR-07:40 | 1463.25 | 20.90 | 135.33 | 352.67 | 1499.00 | 20.84 | 127.00 | 351.17 |
May | 437.50 | 0.51 | 0.50 | 01-MAY-05:40 | 1302.63 | 21.57 | 209.17 | 415.67 | 1271.26 | 20.94 | 204.17 | 415.67 |
June | 401.83 | 0.52 | 0.50 | 01-JUN-04:00 | 1178.84 | 22.56 | 231.67 | 421.33 | 1277.03 | 21.04 | 176.50 | 409.17 |
July | 409.17 | 0.51 | 0.50 | 01-JUL-04:00 | 1268.02 | 22.76 | 248.67 | 423.83 | 1495.69 | 21.35 | 195.67 | 416.67 |
August | 352.83 | 0.51 | 0.50 | 01-AUG-07:40 | 1321.27 | 21.75 | 185.33 | 371.33 | 1255.29 | 21.54 | 183.83 | 372.33 |
September | 344.17 | 0.51 | 0.50 | 01-SEP-06:30 | 1221.59 | 21.56 | 179.00 | 327.00 | 1275.51 | 21.89 | 197.17 | 327.50 |
October | 299.00 | 0.51 | 0.50 | 01-OCT-06:49 | 1018.63 | 23.50 | 174.33 | 286.17 | 983.10 | 23.51 | 174.17 | 286.00 |
November | 255.50 | 0.52 | 0.50 | 01-NOV-07:00 | 2444.75 | 32.54 | 210.00 | 228.50 | 2432.97 | 32.55 | 208.00 | 228.83 |
December | 226.33 | 0.51 | 0.50 | 01-DEC-08:09 | 2434.36 | 33.34 | 192.50 | 213.50 | 2462.29 | 33.54 | 198.33 | 210.67 |
Annual Sum or Average | 3785.50 | 0.51 | 1603.58 | 24.64 | 2337.33 | 3835.00 | 1650.03 | 24.39 | 2258.50 | 3812.00 | ||
Minimum of Months | 226.33 | 0.51 | 0.50 | 1018.63 | 20.90 | 135.33 | 213.50 | 983.10 | 20.84 | 127.00 | 210.67 | |
Maximum of Months | 437.50 | 0.52 | 0.50 | 3302.90 | 33.63 | 248.67 | 423.83 | 3499.28 | 35.11 | 214.83 | 416.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135054E+12 | 158902.00 | 01-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.970957E+11 | 158902.00 | 01-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.823779E+11 | 158902.00 | 05-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.357349E+11 | 113383.08 | 05-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.748509E+10 | 61271.42 | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135573E+10 | 36012.29 | 04-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350812E+09 | 17852.25 | 02-JUL-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.489856E+09 | 32360.81 | 19-AUG-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.597933E+10 | 34520.80 | 10-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290820E+11 | 83966.04 | 30-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610441E+11 | 158902.00 | 25-NOV-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123468E+12 | 158902.00 | 01-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579518E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.350812E+09 | 17852.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135054E+12 | 158902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.812158E+11 | 89146.24 | 06-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.550653E+11 | 90958.41 | 14-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425982E+11 | 76343.98 | 05-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137743E+11 | 41827.89 | 06-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133590E+10 | 25090.84 | 01-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94385408.24 | 13844.02 | 04-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14088606.10 | 7226.79 | 19-AUG-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.427051E+09 | 19390.77 | 06-SEP-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.780548E+10 | 49465.19 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275020E+11 | 60457.70 | 25-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.726246E+11 | 80068.37 | 13-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.812158E+11 | 90958.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.579287E+09 | 0.467674E+09 | 23324.94 | 23-APR-17:10 | 18449.09 | 0.00 |
May | 0.00 | 0.00 | 0.957304E+10 | 0.744775E+10 | 84510.78 | 25-MAY-03:01 | 58112.82 | 0.00 |
June | 0.00 | 0.00 | 0.252314E+11 | 0.158990E+11 | 93897.04 | 30-JUN-03:01 | 37891.84 | 0.00 |
July | 0.00 | 0.00 | 0.382435E+11 | 0.224459E+11 | 93897.04 | 04-JUL-03:01 | 32402.82 | 0.00 |
August | 0.00 | 0.00 | 0.254144E+11 | 0.152385E+11 | 88255.37 | 09-AUG-03:01 | 41422.64 | 0.00 |
September | 0.00 | 0.00 | 0.373610E+10 | 0.262135E+10 | 85817.40 | 01-SEP-03:01 | 37771.28 | 0.00 |
October | 0.00 | 0.00 | 0.318466E+09 | 0.261363E+09 | 12226.73 | 19-OCT-13:00 | 9413.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103096E+12 | 0.643815E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.382435E+11 | 0.224459E+11 | 93897.04 | 58112.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.475832E+09 | 0.398070E+09 | 17964.72 | 14-APR-03:42 | 12266.04 | 0.00 |
May | 0.00 | 0.00 | 0.727813E+10 | 0.571136E+10 | 35970.69 | 26-MAY-03:11 | 20645.80 | 0.00 |
June | 0.00 | 0.00 | 0.198851E+11 | 0.122720E+11 | 39965.81 | 29-JUN-10:56 | 21540.54 | 0.00 |
July | 0.00 | 0.00 | 0.292101E+11 | 0.167121E+11 | 39965.81 | 05-JUL-10:41 | 13867.23 | 0.00 |
August | 0.00 | 0.00 | 0.209051E+11 | 0.120779E+11 | 37967.87 | 08-AUG-16:53 | 21773.05 | 0.00 |
September | 0.00 | 0.00 | 0.444024E+10 | 0.293255E+10 | 35970.69 | 01-SEP-03:01 | 14300.29 | 0.00 |
October | 0.00 | 0.00 | 0.380026E+09 | 0.307865E+09 | 17964.72 | 02-OCT-03:01 | 11183.89 | 0.00 |
November | 0.00 | 0.00 | 12488843.49 | 8047108.02 | 1564.55 | 01-NOV-16:20 | 1013.89 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.825870E+11 | 0.504199E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292101E+11 | 0.167121E+11 | 39965.81 | 21773.05 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10838.38 | 20954.28 | 31-JAN-20:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 11098.37 | 21167.51 | 27-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 11150.38 | 21179.56 | 02-MAR-19:08 |
April | 0.00 | 0.00 | 01-APR-00:01 | 10746.72 | 20742.50 | 03-APR-18:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10251.30 | 19964.61 | 01-MAY-06:58 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9711.55 | 18829.01 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 9126.32 | 17742.09 | 03-JUL-18:46 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8978.18 | 17036.89 | 01-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8957.66 | 17166.22 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 9256.59 | 18050.80 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9780.06 | 19130.10 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10342.13 | 20147.24 | 29-DEC-19:30 |
Annual Sum or Average | 0.00 | 10013.36 | ||||
Minimum of Months | 0.00 | 0.00 | 8957.66 | 17036.89 | ||
Maximum of Months | 0.00 | 0.00 | 11150.38 | 21179.56 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.28 |
February | 0.166145E+10 | 0.23 | 824.13 | 01-FEB-00:01 | 0.28 |
March | 0.183946E+10 | 0.23 | 824.13 | 01-MAR-00:01 | 0.28 |
April | 0.179459E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.27 |
May | 0.191042E+10 | 0.24 | 824.13 | 01-MAY-04:01 | 0.27 |
June | 0.188619E+10 | 0.24 | 824.13 | 01-JUN-03:15 | 0.27 |
July | 0.199992E+10 | 0.25 | 824.13 | 01-JUL-01:13 | 0.27 |
August | 0.197371E+10 | 0.24 | 824.13 | 01-AUG-01:35 | 0.27 |
September | 0.185961E+10 | 0.24 | 824.13 | 01-SEP-00:50 | 0.27 |
October | 0.186826E+10 | 0.23 | 824.13 | 01-OCT-03:01 | 0.27 |
November | 0.178507E+10 | 0.23 | 824.13 | 01-NOV-04:01 | 0.27 |
December | 0.183946E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.222576E+11 | 0.24 | |||
Minimum of Months | 0.166145E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.199992E+10 | 0.25 | 824.13 | 0.28 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.525583E+10 | 0.63 | 3691.30 | 01-JAN-04:10 | 0.92 |
February | 0.438336E+10 | 0.60 | 3691.30 | 01-FEB-04:03 | 0.92 |
March | 0.448215E+10 | 0.58 | 3691.30 | 05-MAR-04:01 | 0.92 |
April | 0.369248E+10 | 0.52 | 2633.89 | 05-APR-03:01 | 0.92 |
May | 0.340225E+10 | 0.47 | 2109.15 | 02-MAY-04:01 | 0.69 |
June | 0.327639E+10 | 0.47 | 3691.30 | 25-JUN-03:01 | 0.91 |
July | 0.336168E+10 | 0.47 | 3691.30 | 04-JUL-03:01 | 0.90 |
August | 0.332850E+10 | 0.47 | 3691.30 | 09-AUG-03:01 | 0.91 |
September | 0.327452E+10 | 0.47 | 3691.30 | 01-SEP-03:01 | 0.91 |
October | 0.370172E+10 | 0.50 | 2634.88 | 09-OCT-04:38 | 0.78 |
November | 0.405483E+10 | 0.55 | 3691.30 | 25-NOV-04:10 | 0.92 |
December | 0.507467E+10 | 0.62 | 3691.30 | 01-DEC-04:02 | 0.92 |
Annual Sum or Average | 0.472884E+11 | 0.53 | |||
Minimum of Months | 0.327452E+10 | 0.47 | 2109.15 | 0.69 | |
Maximum of Months | 0.525583E+10 | 0.63 | 3691.30 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210596E+10 | 0.59 | 1400.37 | 06-JAN-05:02 | 0.88 |
February | 0.174378E+10 | 0.56 | 1416.07 | 14-FEB-05:02 | 0.88 |
March | 0.177157E+10 | 0.54 | 1289.52 | 05-MAR-05:03 | 0.84 |
April | 0.147787E+10 | 0.49 | 990.64 | 06-APR-04:03 | 0.73 |
May | 0.143435E+10 | 0.48 | 1571.14 | 18-MAY-03:01 | 0.92 |
June | 0.153966E+10 | 0.51 | 1571.14 | 07-JUN-03:01 | 0.91 |
July | 0.168726E+10 | 0.54 | 1571.14 | 01-JUL-03:11 | 0.92 |
August | 0.154032E+10 | 0.51 | 1571.14 | 01-AUG-03:01 | 0.91 |
September | 0.137839E+10 | 0.48 | 1571.14 | 01-SEP-03:01 | 0.91 |
October | 0.147302E+10 | 0.48 | 1056.78 | 30-OCT-04:03 | 0.76 |
November | 0.159593E+10 | 0.51 | 1151.96 | 25-NOV-05:02 | 0.80 |
December | 0.203157E+10 | 0.58 | 1321.77 | 13-DEC-05:02 | 0.85 |
Annual Sum or Average | 0.197797E+11 | 0.52 | |||
Minimum of Months | 0.137839E+10 | 0.48 | 990.64 | 0.73 | |
Maximum of Months | 0.210596E+10 | 0.59 | 1571.14 | 0.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 46.64 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 45.62 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 45.29 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 49.79 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 50.72 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 50.90 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.44 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 51.75 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 51.86 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.55 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.01 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 46.66 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 45.29 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 51.86 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 46.64 | 59.92 | 10838.38 | 20954.28 | 31-JAN-20:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 45.62 | 59.00 | 11098.37 | 21167.51 | 27-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 45.29 | 58.82 | 11150.38 | 21179.56 | 02-MAR-19:08 |
April | 0.00 | 0.00 | 01-APR-00:01 | 47.64 | 47.64 | 10746.72 | 20742.50 | 03-APR-18:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 47.69 | 47.69 | 10251.30 | 19964.61 | 01-MAY-06:58 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 48.54 | 48.54 | 9711.55 | 18829.01 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 48.92 | 48.92 | 9126.32 | 17742.09 | 03-JUL-18:46 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 49.36 | 49.36 | 8978.18 | 17036.89 | 01-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.06 | 50.06 | 8957.66 | 17166.22 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 47.01 | 47.01 | 9256.59 | 18050.80 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.25 | 49.25 | 9780.06 | 19130.10 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 46.66 | 59.84 | 10342.13 | 20147.24 | 29-DEC-19:30 |
Annual Sum or Average | 0.00 | 10013.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.29 | 47.01 | 8957.66 | 17036.89 | ||
Maximum of Months | 0.00 | 0.00 | 50.06 | 59.92 | 11150.38 | 21179.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.525583E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.438336E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.448215E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.387451E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.627403E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.104020E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.139483E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.105988E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.443974E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.380774E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.405483E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.507467E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.765960E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.380774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.139483E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.210596E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.174378E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177157E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160718E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.330550E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.637192E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.861371E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.663922E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.256786E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158249E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159974E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.203157E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.399405E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.158249E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.861371E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.525583E+10 | 0.00 | 0.135054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438336E+10 | 0.00 | 0.970957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.448215E+10 | 0.00 | 0.823779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.369248E+10 | 0.579287E+09 | 0.357349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340225E+10 | 0.956269E+10 | 0.748509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.327639E+10 | 0.252051E+11 | 0.135573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.336168E+10 | 0.382012E+11 | 0.350812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.332850E+10 | 0.253846E+11 | 0.489856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327452E+10 | 0.373265E+10 | 0.597933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370172E+10 | 0.318466E+09 | 0.290820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405483E+10 | 0.00 | 0.610441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507467E+10 | 0.00 | 0.123468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472884E+11 | 0.102984E+12 | 0.579518E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327452E+10 | 0.00 | 0.350812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.525583E+10 | 0.382012E+11 | 0.135054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.210596E+10 | 0.00 | 0.812158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174378E+10 | 0.00 | 0.550653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177157E+10 | 0.00 | 0.425982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147787E+10 | 0.475832E+09 | 0.137743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143435E+10 | 0.727139E+10 | 0.133590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153966E+10 | 0.198439E+11 | 94385408.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168726E+10 | 0.291779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154032E+10 | 0.208950E+11 | 14088606.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137839E+10 | 0.443511E+10 | 0.427051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147302E+10 | 0.380026E+09 | 0.780548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159593E+10 | 12488843.49 | 0.275020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203157E+10 | 0.00 | 0.726246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197797E+11 | 0.824916E+11 | 0.302457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210596E+10 | 0.291779E+11 | 0.812158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.525583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.448215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.369248E+10 | 0.00 | 0.00 | 0.00 | 0.182035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340225E+10 | 0.00 | 0.00 | 0.00 | 0.287177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.327639E+10 | 0.00 | 0.00 | 0.00 | 0.712562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.336168E+10 | 0.00 | 0.00 | 0.00 | 0.105867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.332850E+10 | 0.00 | 0.00 | 0.00 | 0.727028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327452E+10 | 0.00 | 0.00 | 0.00 | 0.116522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370172E+10 | 0.00 | 0.00 | 0.00 | 0.106021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472884E+11 | 0.00 | 0.00 | 0.00 | 0.293076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.525583E+10 | 0.00 | 0.00 | 0.00 | 0.105867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.210596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147787E+10 | 0.00 | 0.00 | 0.00 | 0.129311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143435E+10 | 0.00 | 0.00 | 0.00 | 0.187114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153966E+10 | 0.00 | 0.00 | 0.00 | 0.483227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168726E+10 | 0.00 | 0.00 | 0.00 | 0.692645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154032E+10 | 0.00 | 0.00 | 0.00 | 0.509889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137839E+10 | 0.00 | 0.00 | 0.00 | 0.118948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147302E+10 | 0.00 | 0.00 | 0.00 | 0.109472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159593E+10 | 0.00 | 0.00 | 0.00 | 3812029.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197797E+11 | 0.00 | 0.00 | 0.00 | 0.201608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210596E+10 | 0.00 | 0.00 | 0.00 | 0.692645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.379246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108921E+12 | 0.00 | 0.00 | 3.59 |
February | 0.525060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605672E+11 | 0.00 | 0.00 | 3.58 |
March | 0.716862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331161E+11 | 0.00 | 0.00 | 3.57 |
April | 0.560330E+11 | 17771048.67 | 0.00 | 6521596.60 | 0.00 | 0.656815E+10 | 0.305707E+10 | 0.00 | 3.60 |
May | 0.274829E+11 | 0.411617E+09 | 0.00 | 38502949.53 | 0.00 | 0.355410E+09 | 0.113732E+11 | 0.00 | 3.81 |
June | 0.121117E+11 | 0.474661E+10 | 0.00 | 52136344.34 | 22022438.87 | 11536479.53 | 0.127809E+11 | 0.00 | 4.01 |
July | 0.730041E+10 | 0.704431E+10 | 0.00 | 60208438.36 | 10108519.26 | 0.00 | 0.110515E+11 | 0.00 | 4.07 |
August | 0.929438E+10 | 0.268651E+10 | 0.00 | 67577026.94 | 0.00 | 2003180.50 | 0.161455E+11 | 0.00 | 4.08 |
September | 0.288929E+11 | 66368078.37 | 0.00 | 31475778.93 | 0.00 | 22291540.09 | 0.142816E+11 | 0.00 | 3.81 |
October | 0.592091E+11 | 0.00 | 0.00 | 5767175.20 | 0.00 | 0.140012E+10 | 0.304665E+10 | 0.00 | 3.59 |
November | 0.710242E+11 | 0.00 | 0.00 | 344252.31 | 0.00 | 0.148916E+11 | 0.570651E+09 | 0.00 | 3.58 |
December | 0.449265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923144E+11 | 0.00 | 0.00 | 3.57 |
Annual Sum or Average | 0.478392E+12 | 0.149732E+11 | 0.00 | 0.262534E+09 | 32130958.13 | 0.318169E+12 | 0.723071E+11 | 0.00 | 3.74 |
Minimum of Months | 0.730041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
Maximum of Months | 0.716862E+11 | 0.704431E+10 | 0.00 | 67577026.94 | 22022438.87 | 0.108921E+12 | 0.161455E+11 | 0.00 | 4.08 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117541E+12 | 0.00 | 0.00 | 0.00 | 4061338.54 | 0.157403E+09 | 0.00 | 0.00 | 7.98 |
February | 0.900707E+11 | 0.00 | 0.00 | 0.00 | 14291821.66 | 0.109022E+09 | 0.00 | 0.00 | 7.70 |
March | 0.827470E+11 | 0.00 | 1436602.84 | 0.00 | 4889364.77 | 79504168.37 | 0.00 | 8217.45 | 7.45 |
April | 0.494246E+11 | 0.00 | 0.00 | 7537971.31 | 0.00 | 19501928.05 | 0.463799E+10 | 0.00 | 7.10 |
May | 0.181810E+11 | 27750748.88 | 0.00 | 49052308.36 | 0.00 | 0.00 | 0.196182E+11 | 0.00 | 7.08 |
June | 0.598706E+10 | 0.255398E+10 | 0.00 | 70021744.71 | 0.00 | 0.00 | 0.192097E+11 | 0.00 | 7.38 |
July | 0.309375E+10 | 0.341560E+10 | 0.00 | 84795262.52 | 0.00 | 0.00 | 0.158908E+11 | 0.00 | 7.60 |
August | 0.327014E+10 | 0.114293E+10 | 0.00 | 88750003.97 | 0.00 | 0.00 | 0.214514E+11 | 0.00 | 7.35 |
September | 0.161295E+11 | 0.00 | 0.00 | 44719679.08 | 0.00 | 0.00 | 0.226519E+11 | 0.00 | 7.08 |
October | 0.452083E+11 | 0.00 | 0.00 | 8196573.78 | 0.00 | 8940083.52 | 0.577193E+10 | 0.00 | 7.00 |
November | 0.666236E+11 | 0.00 | 0.00 | 937105.88 | 0.00 | 29504668.67 | 0.105591E+10 | 0.00 | 7.30 |
December | 0.110319E+12 | 0.00 | 0.00 | 0.00 | 8664602.73 | 0.142719E+09 | 0.00 | 0.00 | 7.84 |
Annual Sum or Average | 0.608596E+12 | 0.714026E+10 | 1436602.84 | 0.354011E+09 | 31907127.71 | 0.546595E+09 | 0.110288E+12 | 8217.45 | 7.40 |
Minimum of Months | 0.309375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 |
Maximum of Months | 0.117541E+12 | 0.341560E+10 | 1436602.84 | 88750003.97 | 14291821.66 | 0.157403E+09 | 0.226519E+11 | 8217.45 | 7.98 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.241466E+11 | 0.227055E+11 | 0.413424E+12 | 0.00 | 0.647850E+11 |
February | 0.474381E+11 | 0.180039E+11 | 0.323427E+12 | 0.00 | 0.490235E+11 |
March | 0.712314E+11 | 0.175630E+11 | 0.305617E+12 | 0.00 | 0.445408E+11 |
April | 0.100571E+12 | 0.123180E+11 | 0.207780E+12 | 0.280617E+09 | 0.278594E+11 |
May | 0.117993E+12 | 0.912133E+10 | 0.144003E+12 | 0.147716E+10 | 0.416636E+11 |
June | 0.125055E+12 | 0.595295E+10 | 0.868556E+11 | 0.182648E+10 | 0.773509E+11 |
July | 0.126831E+12 | 0.411121E+10 | 0.635417E+11 | 0.161785E+10 | 0.107083E+12 |
August | 0.103900E+12 | 0.535879E+10 | 0.928709E+11 | 0.215817E+10 | 0.787043E+11 |
September | 0.759465E+11 | 0.777606E+10 | 0.150832E+12 | 0.168183E+10 | 0.279540E+11 |
October | 0.363567E+11 | 0.996733E+10 | 0.200093E+12 | 0.324381E+09 | 0.228092E+11 |
November | 0.132856E+11 | 0.130884E+11 | 0.257055E+12 | 5740548.50 | 0.319117E+11 |
December | 0.126567E+11 | 0.213304E+11 | 0.390664E+12 | 0.00 | 0.588132E+11 |
Annual Sum or Average | 0.855412E+12 | 0.147297E+12 | 0.263616E+13 | 0.937222E+10 | 0.632499E+12 |
Minimum of Months | 0.126567E+11 | 0.411121E+10 | 0.635417E+11 | 0.00 | 0.228092E+11 |
Maximum of Months | 0.126831E+12 | 0.227055E+11 | 0.413424E+12 | 0.215817E+10 | 0.107083E+12 |