Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:27:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2026.00 | 3963.58 | 3963.58 |
Net Site Energy | 2026.00 | 3963.58 | 3963.58 |
Total Source Energy | 3710.37 | 7258.82 | 7258.82 |
Net Source Energy | 3710.37 | 7258.82 | 7258.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 534.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 62.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 83.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.50 | 319.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 35.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 726.93 | 1299.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 534.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 62.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 394.51 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 83.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.50 | 319.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 18.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 534.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 62.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 83.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.50 | 319.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 35.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 108.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 434.52 | 1672.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 878.64 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1422.13 | 2541.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 108.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 434.52 | 1672.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 878.64 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1422.13 | 2541.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 726.927 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 726.927 | 100.00 |
Total On-Site and Utility Electric Sources | 726.927 | 100.00 |
Total Electricity End Uses | 726.927 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3917.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 5.1620 | 1.33 | 61.4214 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.3591 | 18.52 | 1000.6314 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 5.1620 | 1.33 | 61.4214 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.3591 | 18.52 | 1000.6314 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Conditioned Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 6.0339 | 1.78 | 317.5692 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-11:00 | 07-FEB-04:30 | - | - | - | - | - | - | - | - | - | - | 08-MAR-07:00 |
Heating | 0.00 | 155196.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23869.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21117.99 | 4281.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4594.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2994.91 | 11806.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1188.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 55461.26 | 171284.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 155196.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23869.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 20527.19 | 4281.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4594.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2994.91 | 11806.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 364.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 629.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 579.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 198.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1308.43 | 481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 264.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.12 | 346.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 113.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2302.18 | 1408.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1134.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 517.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.81 | 678.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 222.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4503.89 | 2754.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1134.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 517.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.81 | 678.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 222.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4503.89 | 2754.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.28 |
KITCHEN DIRECT AIR | 1.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.28 | 3.28 | 3.28 | 3.28 | 3.28 | 3.28 | 1.00 | 1.00 | 3.28 |
PSZ-AC_2:2 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.00 | 1.00 | 1.40 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.28 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.40 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.28 | 3504.91 |
PSZ-AC_2:2_ADDAQ FAN | 1.40 | 1548.59 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.28 | 3.28 | 3.28 | 2.16 | 81337.85 | 131994.73 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.40 | 1.40 | 1.40 | 0.923148 | 34733.28 | 85489.53 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.28 | 1.64 | 2.18 | 81337.85 | 40668.93 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.40 | 0.699355 | 0.932473 | 34733.28 | 17366.64 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 131994.73 |
PSZ-AC_2:2 HEATING COIL | 85489.53 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 5.162 | 61.421 | 0.000 | 0.000 | 0.000 | 0.000 | 66.583 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.359 | 386.416 | 614.215 | 0.000 | 0.000 | 0.000 | 1008.991 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 1918.948 | 5.162 | 6.850 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1918.948 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1165.301 | 8.359 | 154.798 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1165.301 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 22833.282 | 61.421 | 81.506 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6621.652 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 53277.659 | 382.178 | 7077.360 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 15450.521 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 85624.808 | 614.215 | 11374.329 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 24831.194 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.5498 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1372 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2338 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.585 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.210 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.201 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.34553825E-12 | 0.81763784E-15 | -0.11024907E-12 | 0.10773525E-15 |
34 | 6 | 0.31342084E-07 | 0.15855893E-09 | 0.71574906E-08 | -0.14960171E-12 |
35 | 5 | -0.20357449E-03 | 0.13349788E-05 | -0.10451606E-03 | 0.70666961E-08 |
36 | 4 | 0.30776810 | 0.64029868E-03 | 0.10530805 | -0.35789263E-04 |
37 | 3 | -7.5753792 | 0.19580090E-01 | -2.4306415 | 0.30524464E-01 |
38 | 2 | 41.890041 | 0.68805090E-01 | 15.640563 | -0.34469026 |
39 | 1 | -81.326189 | 0.30732018E-01 | -29.478092 | 1.0952505 |
40 | 0 | 46.824334 | 0.61202870E-03 | 16.283337 | |
41 | 7 | -0.30956576E-08 | -0.21303207E-14 | 0.16211864E-14 | -0.47943075E-16 |
42 | 6 | 0.39621431E-05 | 0.26242558E-08 | 0.31947295E-02 | -0.26800069E-04 |
43 | 5 | -0.27788690E-03 | 0.15515089E-05 | -0.22400076 | 0.19585881E-02 |
44 | 4 | 0.63462498E-02 | 0.70567942E-04 | 4.8341454 | -0.45309197E-01 |
45 | 3 | -0.55586032E-01 | 0.56073102E-03 | -38.047399 | 0.39894095 |
46 | 2 | 0.19717555 | 0.93224475E-03 | 116.53452 | -1.4186157 |
47 | 1 | -0.28446589 | 0.28372391E-03 | -143.93707 | 2.0495292 |
48 | 0 | 0.13865977 | 0.68942715E-05 | 60.838472 | |
49 | 7 | -0.17992014E-08 | -0.42643710E-15 | 0.60732754E-14 | -0.80508795E-16 |
50 | 6 | 0.65450224E-05 | 0.44811019E-08 | 0.31871723E-02 | -0.26736672E-04 |
51 | 5 | -0.47085772E-03 | 0.26548585E-05 | -0.22357125 | 0.19547969E-02 |
52 | 4 | 0.10832139E-01 | 0.12085242E-03 | 4.8269919 | -0.45240433E-01 |
53 | 3 | -0.95125865E-01 | 0.96112441E-03 | -38.006990 | 0.39849429 |
54 | 2 | 0.33777835 | 0.15989493E-02 | 116.45587 | -1.4175637 |
55 | 1 | -0.48753632 | 0.48725992E-03 | -143.89078 | 2.0487682 |
56 | 0 | 0.23769862 | 0.11769722E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.379 | 38 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.379 | 39 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.362_SHGC_EAST_0.379 | 40 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.362_SHGC_WEST_0.379 | 41 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.884 | 0.3002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 3.373E-002 | 9.073E-005 | 1.994E-004 | 0.107 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 2.124E-002 | 1.523E-004 | 1.958E-004 | 0.180 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7242E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7229E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6195E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5056E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4657E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4853E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1282E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0430E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.1868E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.0426E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0974E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.9231E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2312E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1764E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0686E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0686E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5565E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5109E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2929E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3459E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2678E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2888E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0430E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1282E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 36571.51366 | 43885.81639 | 2.72956 | 3.27548 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 8194.99334 | 9833.99201 | 0.36030 | 1.33138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | -16.30000 | 9.24091E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 18592.06231 | 22310.47477 | 1.16559 | 1.39871 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.83700 | 1.33520E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 977.36808 | 1172.84170 | 3.88764E-002 | 1.21700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -16.30000 | 9.24091E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 53129.13 | 3.27548 | 3.27548 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 88420.91 | 1.33138 | 1.33138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26707.64 | 1.39871 | 1.39871 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 80824.88 | 1.21700 | 1.21700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.27548 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39871 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.27548 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.27548 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.27548 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.27548 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.27548 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.27548 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39871 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39871 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39871 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39871 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39871 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39871 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.27548 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.39871 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.27548 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.27548 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3504.91339 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.27548 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.27548 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.27548 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.16181 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.27548 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.63774 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.18365 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 81337.85000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 40668.92500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 81337.85000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 131994.72656 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 131994.72656 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39871 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39871 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1548.59290 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39871 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39871 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39871 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92315 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39871 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69935 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93247 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34733.28000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17366.64000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34733.28000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 85489.52796 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 85489.52796 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 79009.7 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 33739.1 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.550 | 0.508 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_EAST_0.379 | N/A | 2.057 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.550 | 0.508 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.379 | N/A | 2.057 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.550 | 0.508 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_WEST_0.379 | N/A | 2.057 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.137 | 0.133 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.550 | 0.508 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.550 | 0.508 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.550 | 0.508 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.234 | 0.221 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.5693570530E-002 | 0.4183940871 | Pass | Pass | 0.2809110503 | 2.1510049148 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 8.2653384912E-002 | 0.4802776189 | Pass | Pass | 2.7491693362E-002 | 8.3912236936E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1288549424 | 0.1202206189 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 971.00 | 114.62 | 2048.41 | 7.81 | 552.94 | 3694.78 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.508 | 0.550 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.508 | 0.550 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.508 | 0.550 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.134 | 0.137 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.508 | 0.550 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.508 | 0.550 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.508 | 0.550 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.225 | 0.234 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.362_SHGC_EAST_0.379 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.057 | 0.380 | 0.418 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.379 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.057 | 0.380 | 0.418 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.362_SHGC_WEST_0.379 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.057 | 0.380 | 0.418 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.057 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.057 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 5.1620 | 371.75 | 1918.95 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.29 | 0.0000 | Y | 21.72 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.3591 | 139.41 | 1165.30 | LightsWired | LTG_SCH_KITCHEN | 79.77 | 168.00 | 76.30 | 0.0000 | Y | 16.69 |
Interior Lighting Total | 6.0339 | 511.15 | 3084.25 | 38.41 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 204.54 | AstronomicalClock | - | 49.04 | 49.04 | 1.88 | |
EXTERIOR_LIGHTS_B | 1305.94 | AstronomicalClock | - | 83.67 | 62.85 | 15.41 | |
Exterior Lighting Total | 1510.48 | 17.29 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 81337.85 | 57024.34 | 24313.51 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34733.28 | 24350.81 | 10382.47 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 79009.7 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 33739.1 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 131994.73 | 0.85 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 85489.53 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 3.28 | 3504.91 | 1070.05 | 1.00 | 1.26 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.40 | 1548.59 | 1107.16 | 1.00 | 1.33 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.95 | 0.88 | 0.30 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 36571.51 | 43885.82 | 118.05 | 2.730 | 3.275 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.99 | 0.01079 | 30.30 | 0.01337 | 1.331 | 0.00 |
KITCHEN | 18592.06 | 22310.47 | 160.04 | 1.166 | 1.399 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 26.00 | 25.99 | 0.01047 | 21.84 | 0.01335 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8194.99 | 9833.99 | 26.45 | 0.360 | 1.331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00780 | -16.30 | 0.00092 | 1.331 | 0.00 |
KITCHEN | 977.37 | 1172.84 | 8.41 | 0.039 | 1.217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00549 | -16.30 | 0.00092 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.28 | 3.28 | 1.33 | 1.33 | 3.2755 | 3.2755 | 3.2755 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.40 | 1.40 | 1.22 | 1.22 | 1.3987 | 1.3987 | 1.3987 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 81337.850 | 57024.340 | 3.275480 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40668.93 | 26342.56 | 2.183653 | 26.55 | 19.63 | 0.01183785 | 11.91 | 11.51 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 60.9702 | 23.99 | 0.01079066 | 56.4677 | 36571.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 131994.727 | 131994.727 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 131994.73 | 131994.73 | 3.275475 | 5.84 | 4.75 | 0.00500388 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 40.6468 | 21.00 | 0.00779784 | 49.1615 | 8192.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 34733.280 | 24350.808 | 1.398710 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 17366.64 | 10636.76 | 0.932473 | 29.01 | 21.20 | 0.01299814 | 11.88 | 11.49 | 0.00850000 | 29.46 | 0.01336548 | 21.59 | 130.5133 | 25.99 | 0.01050945 | 48.8367 | 18389.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 85489.528 | 85489.528 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 85489.53 | 85489.53 | 1.398709 | -11.81 | -11.81 | 0.00153901 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 87.0089 | 19.00 | 0.00565748 | 40.5116 | 516.98 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 81337.850 | 57024.340 | 3.275480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8460 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.275475 | 3.84516335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 40668.93 | 26342.56 | 1.0000 | 2.56344592 | 2.183653 | 26.55 | 19.63 | 0.01183785 | 56868.8 | 11.91 | 11.51 | 0.00850000 | 33416.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40668.93 | 30.30 | 0.01336696 | 21.83 | 1.33137743 | 60.9702 | 23.98 | 0.01079066 | 23.99 | 0.01079066 | 56.4677 | 36571.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 131994.727 | 131994.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.275475 | 3.84516335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 131994.73 | 131994.73 | 1.0000 | 3.84516335 | 3.275475 | 5.84 | 4.75 | 0.00500388 | 18435.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 131994.73 | -16.30 | 0.00092409 | -16.30 | 1.33137743 | 40.6468 | 21.00 | 0.00779784 | 21.00 | 0.00779784 | 49.1615 | 8192.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34733.280 | 24350.808 | 1.398710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.0029 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.398709 | 1.64197991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | Sensible | 17366.64 | 10636.76 | 1.0000 | 1.09465405 | 0.932473 | 29.01 | 21.20 | 0.01299814 | 62359.9 | 11.88 | 11.49 | 0.00850000 | 33386.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17366.64 | 29.46 | 0.01336548 | 21.59 | 1.21700195 | 130.5133 | 25.95 | 0.01050945 | 25.99 | 0.01050945 | 48.8367 | 18389.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 85489.528 | 85489.528 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.398709 | 1.64197991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 85489.53 | 85489.53 | 1.0000 | 1.64197991 | 1.398709 | -11.81 | -11.81 | 0.00153901 | -8055.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85489.53 | -16.30 | 0.00092409 | -16.30 | 1.21700195 | 87.0089 | 18.24 | 0.00565748 | 19.00 | 0.00565748 | 40.5116 | 516.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.28 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.40 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3157.50 | 5560.83 | 1828.50 |
KITCHEN | 4691.67 | 6077.67 | 3749.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4859.00 | 7117.50 | 3917.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 11.00 | 3.67 | 0.00 | 0.00 |
KITCHEN | 0.00 | 75.83 | 0.00 | 0.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 11.00 | 79.50 | 0.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.457 | 0.578 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 8.264 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.046 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 7.586 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.14 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.17 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.32 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36539471.54 | 0.00 | 36539471.54 | 4692703.96 | 41232175.50 | 41986318.57 | 1453.57 | 5901.58 | 1404.86 | 230.87 |
KITCHEN | 25520392.45 | 0.00 | 25520392.45 | 75283.48 | 25595675.92 | 38379373.44 | 8662.86 | 86.42 | 10.72 | 379.35 |
Total Facility | 62059863.99 | 0.00 | 62059863.99 | 4767987.43 | 66827851.42 | 80365692.01 | 8666.25 | 5902.58 | 1412.80 | 469.87 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3846 | 0.0000 | 1.3846 | 0.1796 | 1.5642 | 1.3314 | 0.00 | 5796.01 | 1390.99 |
KITCHEN | 0.9614 | 0.0000 | 0.9614 | 0.0018 | 0.9632 | 1.2170 | 7094.83 | 86.14 | 6.02 |
Total Facility | 2.3459 | 0.0000 | 2.3459 | 0.1814 | 2.5274 | 2.5484 | 7094.83 | 5796.85 | 1395.62 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50354762.59 | 0.00 | 50354762.59 | 41986318.57 | 1450.49 | 0.50 | 7309.00 | 230.87 |
PSZ-AC_2:2 | 35169657.92 | 0.00 | 35169657.92 | 38379373.44 | 1439.12 | 0.74 | 7320.14 | 379.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9081 | 0.0000 | 1.9081 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3248 | 0.0000 | 1.3248 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1343.26 | 178.56 | 5896.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 189.35 | 892.83 | 6484.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.2365 | 2.0522 | 1.8352 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.3442 | 1.3801 | 1.3194 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
Electricity:Building | 458.49 | 2350.73 | 01-JAN-01:20 | 26459.53 | 02-JAN-11:10 |
Electricity:Zone:DINING | 140.07 | 534.11 | 01-JAN-01:20 | 7569.70 | 02-JAN-16:50 |
Electricity:SpaceType:GENERAL | 451.55 | 2214.45 | 01-JAN-01:20 | 24316.43 | 02-JAN-11:10 |
InteriorLights:Electricity | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:DINING | 21.72 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-16:50 |
InteriorLights:Electricity:SpaceType:GENERAL | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 21.72 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 38.41 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:50 |
Electricity:Zone:KITCHEN | 318.41 | 1816.62 | 01-JAN-01:20 | 19025.40 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 294.79 | 1650.33 | 01-JAN-01:10 | 16024.20 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 276.16 | 1059.53 | 01-JAN-01:10 | 15433.40 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 35.98 | 595.55 | 04-JAN-23:30 | 2780.19 | 08-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 105.00 | 741.26 | 29-JAN-01:10 | 5843.65 | 27-JUL-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 10.88 | 0.00 | 01-JAN-11:10 | 1020.98 | 11-AUG-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 18.16 | 509.05 | 06-MAR-06:00 | 637.09 | 12-MAR-13:10 |
ElectricityPurchased:Facility | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
ElectricityPurchased:Plant | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
Cogeneration:ElectricityPurchased | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
General:Cogeneration:ElectricityPurchased | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
ElectricityNet:Plant | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
Cogeneration:ElectricityNet | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
General:Cogeneration:ElectricityNet | 726.93 | 3793.30 | 06-FEB-01:30 | 55461.26 | 20-JUL-12:00 |
Electricity:HVAC | 146.15 | 0.00 | 01-JAN-01:10 | 29541.43 | 27-JUN-13:00 |
Fans:Electricity | 83.45 | 0.00 | 01-JAN-01:10 | 4694.68 | 27-JUN-13:00 |
General:Fans:Electricity | 83.45 | 0.00 | 01-JAN-01:10 | 4694.68 | 27-JUN-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 62.70 | 0.00 | 01-JAN-00:10 | 24846.75 | 27-JUN-13:00 |
General:Cooling:Electricity | 62.70 | 0.00 | 01-JAN-00:10 | 24846.75 | 27-JUN-13:00 |
ExteriorLights:Electricity | 17.29 | 0.00 | 01-JAN-08:00 | 1510.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 17.29 | 0.00 | 01-JAN-08:00 | 1510.48 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.50 | 0.00 | 01-JAN-01:10 | 4742.12 | 21-MAR-18:10 |
Water Heater:WaterSystems:Electricity | 75.50 | 0.00 | 01-JAN-01:10 | 4742.12 | 21-MAR-18:10 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1299.07 | 2515.72 | 01-JAN-01:20 | 171284.00 | 07-FEB-04:30 |
NaturalGas:Building | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:HVAC | 534.93 | 0.00 | 01-JAN-01:10 | 155196.62 | 10-JAN-04:30 |
Heating:NaturalGas | 534.93 | 0.00 | 01-JAN-01:10 | 155196.62 | 10-JAN-04:30 |
General:Heating:NaturalGas | 534.93 | 0.00 | 01-JAN-01:10 | 155196.62 | 10-JAN-04:30 |
NaturalGas:Plant | 319.72 | 803.23 | 23-FEB-00:10 | 28420.48 | 17-FEB-19:30 |
WaterSystems:NaturalGas | 319.72 | 803.23 | 23-FEB-00:10 | 28420.48 | 17-FEB-19:30 |
Water Heater:WaterSystems:NaturalGas | 319.72 | 803.23 | 23-FEB-00:10 | 28420.48 | 17-FEB-19:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 27-MAR-06:30 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 27-MAR-06:30 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1659.79 | 2931.16 | 07-FEB-01:10 | 154269.11 | 20-JUL-19:00 |
EnergyTransfer:Building | 631.05 | 1465.58 | 07-FEB-01:10 | 44662.13 | 05-FEB-21:00 |
EnergyTransfer:Zone:KITCHEN | 384.80 | 1465.58 | 07-FEB-01:10 | 22494.44 | 28-NOV-12:00 |
Refrigeration:EnergyTransfer | 137.19 | 2621.06 | 07-JAN-23:20 | 7834.84 | 02-JUN-03:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.59 | 1310.53 | 07-JAN-23:20 | 3917.42 | 02-JUN-03:10 |
General:Refrigeration:EnergyTransfer | 68.59 | 1310.53 | 07-JAN-23:20 | 3917.42 | 02-JUN-03:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.59 | 1310.53 | 07-JAN-23:20 | 3917.42 | 02-JUN-03:10 |
EnergyTransfer:Plant | 337.08 | 1465.58 | 07-FEB-01:10 | 20777.32 | 15-MAR-18:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.04 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 56.56 | 1305.30 | 06-MAR-06:00 | 2238.70 | 12-MAR-13:10 |
EnergyTransfer:Zone:DINING | 246.25 | 0.00 | 01-JAN-01:10 | 31075.04 | 05-FEB-21:00 |
Heating:EnergyTransfer | 3.35 | 0.00 | 01-JAN-00:10 | 15330.85 | 05-FEB-21:00 |
Heating:EnergyTransfer:Zone:DINING | 3.33 | 0.00 | 01-JAN-00:10 | 15330.85 | 05-FEB-21:00 |
General:Heating:EnergyTransfer | 3.35 | 0.00 | 01-JAN-00:10 | 15330.85 | 05-FEB-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 3.33 | 0.00 | 01-JAN-00:10 | 15330.85 | 05-FEB-21:00 |
Cooling:EnergyTransfer | 559.10 | 0.00 | 01-JAN-01:10 | 40737.91 | 21-JUL-12:00 |
Cooling:EnergyTransfer:Zone:DINING | 242.92 | 0.00 | 01-JAN-01:10 | 25682.52 | 21-JUL-12:00 |
General:Cooling:EnergyTransfer | 559.10 | 0.00 | 01-JAN-01:10 | 40737.91 | 21-JUL-12:00 |
General:Cooling:EnergyTransfer:Zone:DINING | 242.92 | 0.00 | 01-JAN-01:10 | 25682.52 | 21-JUL-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1227.81 | 05-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1227.81 | 05-MAR-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 316.19 | 0.00 | 01-JAN-01:10 | 19195.97 | 28-NOV-12:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 316.19 | 0.00 | 01-JAN-01:10 | 19195.97 | 28-NOV-12:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 268.49 | 0.00 | 01-JAN-01:10 | 18450.26 | 16-FEB-19:20 |
PlantLoopHeatingDemand:Plant | 268.49 | 0.00 | 01-JAN-01:10 | 18450.26 | 16-FEB-19:20 |
WaterSystems:PlantLoopHeatingDemand | 268.49 | 0.00 | 01-JAN-01:10 | 18450.26 | 16-FEB-19:20 |
General:WaterSystems:PlantLoopHeatingDemand | 268.49 | 0.00 | 01-JAN-01:10 | 18450.26 | 16-FEB-19:20 |
EnergyTransfer:HVAC | 691.66 | 0.00 | 01-JAN-01:10 | 131994.73 | 10-JAN-04:30 |
HeatingCoils:EnergyTransfer | 454.96 | 0.00 | 01-JAN-01:10 | 131994.73 | 10-JAN-04:30 |
CoolingCoils:EnergyTransfer | 236.70 | 0.00 | 01-JAN-00:10 | 100905.68 | 27-JUN-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 268.49 | 0.00 | 01-JAN-01:10 | 18450.26 | 16-FEB-19:20 |
WaterUse:WaterSystems:EnergyTransfer | 268.49 | 0.00 | 01-JAN-01:10 | 18450.26 | 16-FEB-19:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 3.335 | -242.917 | 0.000 | 0.000 | 229.946 | 21.719 | 88.765 | 37.374 | 0.000 | 1.054 | 0.000 | 0.000 | -23.924 | 0.000 | -71.833 | -43.519 |
KITCHEN | 0.000 | 0.000 | 0.016 | -316.175 | 0.000 | 0.000 | 6.017 | 16.690 | 259.402 | 0.000 | 0.000 | 0.004 | 35.479 | 0.000 | 0.000 | 0.000 | -1.433 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.002 | 28.119 | 0.000 | 0.000 | 0.000 | -34.122 | -0.000 |
Total Facility | 0.000 | 0.000 | 3.350 | -559.092 | 0.000 | 0.000 | 235.963 | 38.409 | 348.168 | 37.374 | 0.000 | 7.059 | 63.599 | 0.000 | -23.924 | 0.000 | -107.388 | -43.520 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-AUG-03:01 | 0.00 | 0.00 | 0.00 | -64309.43 | 0.00 | 0.00 | 0.00 | 80.03 | 851.41 | 0.00 | 0.00 | 0.00 | 64410.86 | 0.00 | -980.64 | 0.00 | -52.22 | 0.00 |
KITCHEN | 04-JUN-03:01 | 0.00 | 0.00 | 0.00 | -52860.94 | 0.00 | 0.00 | 0.00 | 30.01 | 2903.90 | 0.00 | 0.00 | 0.00 | 49959.51 | 0.00 | -0.00 | 0.00 | -32.48 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-AUG-03:01 | 0.00 | 0.00 | 0.00 | -103376.07 | 0.00 | 0.00 | 0.00 | 110.04 | 3755.31 | 0.00 | 0.00 | 83.28 | 100505.92 | 0.00 | -980.64 | 0.00 | -97.83 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 07-FEB-05:01 | 0.00 | 0.00 | 74428.43 | 0.00 | 0.00 | 0.00 | 1270.21 | 80.03 | 2052.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2991.66 | 0.00 | -171.78 | -74667.95 |
KITCHEN | 05-MAR-05:03 | 0.00 | 0.00 | 12263.05 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 6142.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.85 | -18432.46 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-FEB-05:01 | -40988.74 | 40988.74 | 74428.43 | -40988.74 | 0.00 | 0.00 | 1295.51 | 110.04 | 8210.94 | 0.00 | 0.00 | 147.92 | 0.00 | 0.00 | -2991.66 | 0.00 | -284.41 | -39928.02 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.2755 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.2755 | 0.4065 | 1.0000 | Not calculated | 1.3314 | 0.4065 | ||
PSZ-AC_2:2 | 1.3987 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.3987 | 0.1305 | 1.0000 | Not calculated | 0.1826 | 0.1305 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.2755 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.2755 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.4065 | ||
PSZ-AC_2:2 | 1.3987 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.3987 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1305 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2755 | 3.2755 | 3.2755 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3987 | 1.3987 | 1.3987 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.2755 | 3.2755 | 3.2755 | 3.2755 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.3987 | 1.3987 | 1.3987 | 1.3987 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2755 | 3.2755 | 3.2755 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3987 | 1.3987 | 1.3987 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.2755 | 3.2755 | 3.2755 | 3.2755 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.3987 | 1.3987 | 1.3987 | 1.3987 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 534.93 | 155196.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 62.70 | 24846.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 38.41 | 2497.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 17.29 | 1510.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 394.51 | 22047.72 | 444.42 | 24831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 83.45 | 4694.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.50 | 4742.12 | 319.72 | 28420.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.88 | 1020.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 18.16 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 449.12 | 726.93 |
Natural Gas | 444.42 | 1299.07 |
Additional | 0.00 | 0.00 |
Total | 893.54 | 2026.00 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 75.14 |
Space Heating | 0.00 |
Space Cooling | 122.67 |
Fans (All) | 163.26 |
Service Water Heating | 147.71 |
Receptacle Equipment | 808.26 |
Miscellaneous (All) | 1422.13 |
Subtotal | 1422.13 |
Natural Gas [MJ/m2] | |
Space Heating | 1046.52 |
Service Water Heating | 625.49 |
Miscellaneous (All) | 2541.45 |
Subtotal | 2541.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.90 |
Space Heating | 26.40 |
Space Cooling | 3.09 |
Fans (All) | 4.12 |
Service Water Heating | 19.51 |
Receptacle Equipment | 42.33 |
Miscellaneous | 2.65 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 4159. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8246.17 | 505.33 | 8.50 | 0.00 | 0.00 |
ATTIC | 7381.00 | 515.50 | 472.00 | 371.67 | 19.83 |
Min | 7381.00 | 17.17 | 0.00 | 0.00 | 0.00 |
Max | 8742.83 | 515.50 | 472.00 | 371.67 | 19.83 |
Average | 8123.33 | 346.00 | 160.17 | 123.89 | 6.61 |
Sum | 24370.00 | 1038.00 | 480.50 | 371.67 | 19.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824203.33 | 18.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19232.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824203.33 | 18.67 | 0.00 | 0.00 | 0.00 |
Average | 281145.28 | 6.39 | 0.00 | 0.00 | 0.00 |
Sum | 843435.83 | 19.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7963.50 | 796.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6293.67 | 2466.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 7264.00 | 939.50 | 261.17 | 181.33 | 114.00 |
Min | 6293.67 | 796.50 | 0.00 | 0.00 | 0.00 |
Max | 7963.50 | 2466.33 | 261.17 | 181.33 | 114.00 |
Average | 7173.72 | 1400.78 | 87.06 | 60.44 | 38.00 |
Sum | 21521.17 | 4202.33 | 261.17 | 181.33 | 114.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 751506.00 | 72716.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 13744.50 | 5488.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 751506.00 | 72716.00 | 0.00 | 0.00 | 0.00 |
Average | 255083.50 | 26068.17 | 0.00 | 0.00 | 0.00 |
Sum | 765250.50 | 78204.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.904315E+10 | 46236.51 | 24-JAN-00:01 | -11.1 | -12.0 | 0.118546E+11 | 10669.42 | 28-JAN-19:00 | -8.9 | -10.4 |
February | 0.807336E+10 | 52040.23 | 07-FEB-00:01 | -15.0 | -15.8 | 0.107393E+11 | 10669.42 | 25-FEB-19:00 | -6.7 | -7.8 |
March | 0.155085E+11 | 47422.12 | 07-MAR-00:01 | -11.8 | -12.6 | 0.122563E+11 | 12850.69 | 15-MAR-11:00 | 25.00 | 15.61 |
April | 0.192717E+11 | 34234.33 | 16-APR-23:01 | -2.9 | -4.7 | 0.119836E+11 | 13978.90 | 08-APR-18:00 | -2.9 | -4.7 |
May | 0.235939E+11 | 26189.74 | 08-MAY-04:01 | 3.30 | 0.17 | 0.138369E+11 | 13978.73 | 27-MAY-18:19 | 18.70 | 10.11 |
June | 0.271332E+11 | 56690.19 | 28-JUN-03:01 | 18.72 | 15.78 | 0.144816E+11 | 13979.70 | 10-JUN-18:49 | 18.72 | 15.78 |
July | 0.307844E+11 | 58049.48 | 11-JUL-03:01 | 19.08 | 15.53 | 0.151024E+11 | 13980.11 | 22-JUL-18:00 | 21.70 | 19.38 |
August | 0.308485E+11 | 64333.14 | 20-AUG-03:01 | 15.00 | 12.86 | 0.152154E+11 | 13979.48 | 12-AUG-18:10 | 15.00 | 12.86 |
September | 0.268559E+11 | 57180.61 | 09-SEP-03:01 | 17.70 | 16.01 | 0.141292E+11 | 13979.39 | 09-SEP-18:49 | 16.97 | 12.20 |
October | 0.232478E+11 | 30308.54 | 16-OCT-23:01 | -0.1 | -0.7 | 0.127501E+11 | 13978.11 | 21-OCT-18:19 | 16.13 | 12.19 |
November | 0.181329E+11 | 32667.74 | 24-NOV-00:01 | -1.8 | -2.5 | 0.116815E+11 | 13835.02 | 04-NOV-18:00 | -1.8 | -2.5 |
December | 0.104257E+11 | 53744.55 | 11-DEC-00:01 | -16.1 | -16.3 | 0.118554E+11 | 11208.87 | 01-DEC-12:00 | -16.1 | -16.3 |
Annual Sum or Average | 0.242919E+12 | 0.155886E+12 | ||||||||
Minimum of Months | 0.807336E+10 | 26189.74 | -16.1 | -16.3 | 0.107393E+11 | 10669.42 | -16.1 | -16.3 | ||
Maximum of Months | 0.308485E+11 | 64333.14 | 19.08 | 16.01 | 0.152154E+11 | 13980.11 | 25.00 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257702E+11 | 39402.43 | 10-JAN-05:01 | -13.3 | -14.3 | 0.983970E+10 | 6490.52 | 11-JAN-11:00 | 9.40 | 8.22 |
February | 0.230077E+11 | 41011.85 | 07-FEB-05:01 | -15.7 | -16.1 | 0.888830E+10 | 6467.33 | 22-FEB-11:00 | 6.70 | 2.27 |
March | 0.260004E+11 | 39200.76 | 07-MAR-05:01 | -13.3 | -13.9 | 0.987257E+10 | 6568.43 | 15-MAR-10:39 | 23.33 | 15.40 |
April | 0.255185E+11 | 42579.92 | 09-APR-03:01 | 12.12 | 10.59 | 0.958405E+10 | 6568.40 | 07-APR-10:00 | 12.12 | 10.59 |
May | 0.256514E+11 | 50595.69 | 27-MAY-03:01 | 7.70 | 6.85 | 0.100020E+11 | 6568.47 | 17-MAY-10:00 | 7.70 | 6.85 |
June | 0.261354E+11 | 52926.97 | 04-JUN-03:01 | 8.12 | 5.87 | 0.971492E+10 | 6570.62 | 27-JUN-10:00 | 28.30 | 22.79 |
July | 0.278461E+11 | 43562.16 | 06-JUL-03:01 | 13.12 | 10.73 | 0.100428E+11 | 6570.23 | 20-JUL-10:00 | 29.40 | 22.73 |
August | 0.280979E+11 | 46677.27 | 03-AUG-03:11 | 11.50 | 9.78 | 0.100473E+11 | 6568.52 | 15-AUG-10:50 | 26.70 | 22.40 |
September | 0.267049E+11 | 50212.30 | 03-SEP-03:01 | 7.80 | 7.20 | 0.970547E+10 | 6568.45 | 26-SEP-10:09 | 16.47 | 15.98 |
October | 0.278690E+11 | 47440.06 | 02-OCT-03:01 | 8.80 | 8.48 | 0.994031E+10 | 6568.45 | 12-OCT-10:50 | 17.70 | 14.38 |
November | 0.270482E+11 | 37361.77 | 05-NOV-03:01 | 15.10 | 11.96 | 0.956004E+10 | 6568.41 | 16-NOV-11:00 | 18.30 | 12.18 |
December | 0.265355E+11 | 42286.62 | 11-DEC-05:01 | -17.5 | -18.0 | 0.984019E+10 | 6546.38 | 01-DEC-11:50 | -17.5 | -18.0 |
Annual Sum or Average | 0.316185E+12 | 0.117038E+12 | ||||||||
Minimum of Months | 0.230077E+11 | 37361.77 | -17.5 | -18.0 | 0.888830E+10 | 6467.33 | -17.5 | -18.0 | ||
Maximum of Months | 0.280979E+11 | 52926.97 | 15.10 | 11.96 | 0.100473E+11 | 6570.62 | 29.40 | 22.79 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.953254E+09 | 67785.64 | 04-JAN-09:28 | -10.6 |
February | 0.110424E+10 | 74427.02 | 07-FEB-05:01 | -15.7 |
March | 0.423531E+09 | 64553.55 | 06-MAR-08:18 | -9.0 |
April | 85818065.42 | 30052.40 | 17-APR-03:02 | -2.9 |
May | 4015314.70 | 7582.81 | 20-MAY-04:03 | 7.12 |
June | 1638890.15 | 6012.93 | 04-JUN-04:05 | 7.12 |
July | 8074419.22 | 4401.74 | 19-JUL-23:02 | 26.60 |
August | 229642.41 | 845.17 | 13-AUG-23:03 | 24.32 |
September | 940925.01 | 4776.02 | 30-SEP-04:03 | 7.20 |
October | 10846412.33 | 21409.08 | 14-OCT-04:14 | 6.70 |
November | 45982970.93 | 22586.46 | 25-NOV-05:01 | -1.7 |
December | 0.696115E+09 | 72646.61 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.333469E+10 | |||
Minimum of Months | 229642.41 | 845.17 | -17.5 | |
Maximum of Months | 0.110424E+10 | 74427.02 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4555952.09 | 12037.28 | 30-JAN-05:03 | -9.5 |
February | 4358222.48 | 10509.39 | 07-FEB-05:03 | -15.7 |
March | 3561109.58 | 12278.10 | 05-MAR-05:03 | -10.7 |
April | 111850.00 | 1066.99 | 03-APR-04:04 | -2.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 25856.39 | 430.94 | 25-NOV-05:04 | -1.7 |
December | 3040220.19 | 11226.05 | 10-DEC-05:03 | -13.3 |
Annual Sum or Average | 15653210.72 | |||
Minimum of Months | 0.00 | 0.00 | -15.7 | |
Maximum of Months | 4555952.09 | 12278.10 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202828E+10 | 1639.63 | 02-JAN-16:49 | 0.100519E+11 | 6614.32 | 01-JAN-11:09 |
February | 0.177085E+10 | 1639.63 | 01-FEB-17:30 | 0.907918E+10 | 6614.32 | 01-FEB-11:09 |
March | 0.186454E+10 | 1639.63 | 01-MAR-17:00 | 0.100520E+11 | 6614.32 | 01-MAR-11:09 |
April | 0.169781E+10 | 1639.63 | 01-APR-18:40 | 0.972770E+10 | 6614.32 | 01-APR-10:09 |
May | 0.169862E+10 | 1639.63 | 01-MAY-19:10 | 0.100520E+11 | 6614.32 | 01-MAY-10:09 |
June | 0.161364E+10 | 1639.63 | 01-JUN-19:49 | 0.972773E+10 | 6614.32 | 01-JUN-10:09 |
July | 0.164540E+10 | 1639.63 | 01-JUL-19:00 | 0.100519E+11 | 6614.32 | 01-JUL-10:09 |
August | 0.173235E+10 | 1639.63 | 01-AUG-19:40 | 0.100520E+11 | 6614.32 | 01-AUG-10:09 |
September | 0.175181E+10 | 1639.63 | 01-SEP-18:49 | 0.972770E+10 | 6614.32 | 01-SEP-10:09 |
October | 0.189240E+10 | 1639.63 | 02-OCT-17:00 | 0.100519E+11 | 6614.32 | 01-OCT-10:09 |
November | 0.196567E+10 | 1639.63 | 01-NOV-17:10 | 0.972767E+10 | 6614.32 | 01-NOV-10:09 |
December | 0.205727E+10 | 1639.63 | 01-DEC-16:40 | 0.100519E+11 | 6614.32 | 01-DEC-11:09 |
Annual Sum or Average | 0.217186E+11 | 0.118354E+12 | ||||
Minimum of Months | 0.161364E+10 | 1639.63 | 0.907918E+10 | 6614.32 | ||
Maximum of Months | 0.205727E+10 | 1639.63 | 0.100520E+11 | 6614.32 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140982E+10 | 858.09 | 02-JAN-10:09 | 0.250369E+11 | 16024.20 | 01-JAN-11:09 |
February | 0.127710E+10 | 858.09 | 01-FEB-10:09 | 0.226140E+11 | 16024.20 | 01-FEB-11:09 |
March | 0.143409E+10 | 858.09 | 01-MAR-10:09 | 0.250371E+11 | 16024.20 | 01-MAR-11:09 |
April | 0.136995E+10 | 858.09 | 01-APR-16:10 | 0.242293E+11 | 16024.20 | 01-APR-10:09 |
May | 0.142196E+10 | 858.09 | 01-MAY-09:09 | 0.250370E+11 | 16024.20 | 01-MAY-10:09 |
June | 0.138598E+10 | 858.09 | 01-JUN-09:09 | 0.242294E+11 | 16024.20 | 01-JUN-10:09 |
July | 0.140610E+10 | 858.09 | 01-JUL-16:10 | 0.250369E+11 | 16024.20 | 01-JUL-10:09 |
August | 0.143409E+10 | 858.09 | 01-AUG-09:09 | 0.250371E+11 | 16024.20 | 01-AUG-10:09 |
September | 0.137029E+10 | 858.09 | 01-SEP-09:09 | 0.242293E+11 | 16024.20 | 01-SEP-10:09 |
October | 0.140965E+10 | 858.09 | 02-OCT-09:09 | 0.250369E+11 | 16024.20 | 01-OCT-10:09 |
November | 0.136509E+10 | 858.09 | 01-NOV-09:09 | 0.242292E+11 | 16024.20 | 01-NOV-10:09 |
December | 0.140627E+10 | 858.09 | 01-DEC-10:09 | 0.250369E+11 | 16024.20 | 01-DEC-11:09 |
Annual Sum or Average | 0.166904E+11 | 0.294790E+12 | ||||
Minimum of Months | 0.127710E+10 | 858.09 | 0.226140E+11 | 16024.20 | ||
Maximum of Months | 0.143409E+10 | 858.09 | 0.250371E+11 | 16024.20 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.202828E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120728E+11 |
February | 0.272721E+11 | 0.177085E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112763E+11 |
March | 0.305458E+11 | 0.186454E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7724243.96 | 0.882781E+10 |
April | 0.292871E+11 | 0.169781E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598444E+10 |
May | 0.303219E+11 | 0.169862E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4961791.73 | 0.364674E+10 |
June | 0.295292E+11 | 0.161364E+10 | 0.972773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169609E+09 | 0.184828E+10 |
July | 0.300798E+11 | 0.164540E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472227E+09 | 0.730566E+09 |
August | 0.305458E+11 | 0.173235E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372472E+09 | 0.119643E+10 |
September | 0.292871E+11 | 0.175181E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26762197.40 | 0.257523E+10 |
October | 0.300980E+11 | 0.189240E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534918E+10 |
November | 0.290996E+11 | 0.196567E+10 | 0.972767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688380E+10 |
December | 0.300798E+11 | 0.205727E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114414E+11 |
Annual Sum or Average | 0.356244E+12 | 0.217186E+11 | 0.118354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105376E+10 | 0.718330E+11 |
Minimum of Months | 0.272721E+11 | 0.161364E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730566E+09 |
Maximum of Months | 0.305458E+11 | 0.205727E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472227E+09 | 0.120728E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.140982E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222821E+09 |
February | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236376E+09 |
March | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 151.60 | 0.146252E+09 |
April | 0.786997E+09 | 0.136995E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113334E+09 |
May | 0.814802E+09 | 0.142196E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 914.75 | 73702801.56 |
June | 0.793501E+09 | 0.138598E+10 | 0.196898E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 594361.30 | 54798022.66 |
July | 0.808298E+09 | 0.140610E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 1603900.73 | 33747694.30 |
August | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 1266544.60 | 38369906.11 |
September | 0.786997E+09 | 0.137029E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 46778.91 | 52462049.66 |
October | 0.808786E+09 | 0.140965E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98011810.38 |
November | 0.781956E+09 | 0.136509E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130163E+09 |
December | 0.808298E+09 | 0.140627E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232931E+09 |
Annual Sum or Average | 0.957291E+10 | 0.166904E+11 | 0.239558E+12 | 0.133326E+12 | 0.00 | 0.00 | 0.00 | 3512651.90 | 0.143297E+10 |
Minimum of Months | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33747694.30 |
Maximum of Months | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 1603900.73 | 0.236376E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501746E+09 | 0.123235E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368544E+09 | 0.174140E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612768E+09 | 0.274367E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435883E+09 | 0.361535E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530422E+09 | 0.426368E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432878E+09 | 0.464809E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450506E+09 | 0.472518E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451290E+09 | 0.406789E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672402E+09 | 0.301601E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566377E+09 | 0.195123E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574872E+09 | 0.108298E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404473E+09 | 0.103378E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600216E+10 | 0.341216E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368544E+09 | 0.103378E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672402E+09 | 0.472518E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 1639.63 | 02-JAN-16:49 | 6614.32 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 14608.51 | 30-JAN-19:00 |
February | 30255.31 | 04-FEB-19:10 | 1639.63 | 01-FEB-17:30 | 6614.32 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 15863.80 | 06-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 1639.63 | 01-MAR-17:00 | 6614.32 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 430.12 | 15-MAR-14:00 | 13760.13 | 06-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 1639.63 | 01-APR-18:40 | 6614.32 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 8375.49 | 16-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 1639.63 | 01-MAY-19:10 | 6614.32 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 423.49 | 10-MAY-14:00 | 5007.20 | 06-MAY-18:53 |
June | 30255.31 | 03-JUN-18:10 | 1639.63 | 01-JUN-19:49 | 6614.32 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2222.32 | 27-JUN-12:00 | 4778.48 | 13-JUN-12:00 |
July | 30255.31 | 01-JUL-18:10 | 1639.63 | 01-JUL-19:00 | 6614.32 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2221.75 | 21-JUL-12:00 | 1954.94 | 06-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 1639.63 | 01-AUG-19:40 | 6614.32 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2219.35 | 10-AUG-12:00 | 4065.71 | 30-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 1639.63 | 01-SEP-18:49 | 6614.32 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 797.58 | 16-SEP-13:00 | 4307.77 | 28-SEP-17:20 |
October | 30255.31 | 07-OCT-18:10 | 1639.63 | 02-OCT-17:00 | 6614.32 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 8181.16 | 16-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 1639.63 | 01-NOV-17:10 | 6614.32 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9411.66 | 22-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 1639.63 | 01-DEC-16:40 | 6614.32 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 16109.98 | 11-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1954.94 | |||||
Maximum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2222.32 | 16109.98 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 858.09 | 02-JAN-10:09 | 12937.52 | 01-JAN-11:09 | 7449.36 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 660.68 | 12-JAN-05:00 |
February | 813.01 | 04-FEB-19:10 | 858.09 | 01-FEB-10:09 | 12937.52 | 01-FEB-11:09 | 7449.36 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 653.55 | 13-FEB-04:10 |
March | 813.01 | 04-MAR-19:10 | 858.09 | 01-MAR-10:09 | 12937.52 | 01-MAR-11:09 | 7449.36 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.22 | 15-MAR-14:00 | 418.19 | 02-MAR-05:00 |
April | 813.01 | 01-APR-18:10 | 858.09 | 01-APR-16:10 | 12937.52 | 01-APR-10:09 | 7449.36 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 404.26 | 16-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 858.09 | 01-MAY-09:09 | 12937.52 | 01-MAY-10:09 | 7449.36 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.34 | 14-MAY-15:00 | 150.44 | 30-MAY-02:00 |
June | 813.01 | 03-JUN-18:10 | 858.09 | 01-JUN-09:09 | 12937.52 | 01-JUN-10:09 | 7449.36 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 13.98 | 27-JUN-12:55 | 244.28 | 13-JUN-03:00 |
July | 813.01 | 01-JUL-18:10 | 858.09 | 01-JUL-16:10 | 12937.52 | 01-JUL-10:09 | 7449.36 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 26.19 | 21-JUL-03:20 | 203.31 | 06-JUL-02:00 |
August | 813.01 | 05-AUG-18:10 | 858.09 | 01-AUG-09:09 | 12937.52 | 01-AUG-10:09 | 7449.36 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 14.87 | 13-AUG-13:00 | 114.32 | 27-AUG-02:40 |
September | 813.01 | 02-SEP-18:10 | 858.09 | 01-SEP-09:09 | 12937.52 | 01-SEP-10:09 | 7449.36 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 3.50 | 16-SEP-13:00 | 220.35 | 29-SEP-03:40 |
October | 813.01 | 07-OCT-18:10 | 858.09 | 02-OCT-09:09 | 12937.52 | 01-OCT-10:09 | 7449.36 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 227.99 | 07-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 858.09 | 01-NOV-09:09 | 12937.52 | 01-NOV-10:09 | 7449.36 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 419.50 | 17-NOV-02:00 |
December | 813.01 | 02-DEC-19:10 | 858.09 | 01-DEC-10:09 | 12937.52 | 01-DEC-11:09 | 7449.36 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 531.34 | 26-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 0.00 | 114.32 | ||||||
Maximum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 26.19 | 660.68 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.97 | 06-JAN-03:50 | 4305.35 | 30-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.13 | 27-FEB-23:00 | 5909.53 | 08-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1551.94 | 08-MAR-07:13 | 6236.48 | 07-MAR-13:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1510.47 | 24-APR-05:40 | 7938.89 | 06-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.53 | 27-MAY-04:55 | 8259.29 | 26-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.33 | 04-JUN-05:15 | 8243.50 | 10-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.63 | 13-JUL-02:00 | 7867.82 | 03-JUL-12:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.17 | 12-AUG-03:00 | 7447.74 | 03-AUG-13:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1482.37 | 10-SEP-22:30 | 6425.88 | 03-SEP-12:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.43 | 02-OCT-06:25 | 5568.54 | 17-OCT-13:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.83 | 25-NOV-21:00 | 3944.62 | 24-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.86 | 16-DEC-08:00 | 3885.73 | 11-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.83 | 3885.73 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.13 | 8259.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 46236.51 | 24-JAN-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.03 |
February | 52040.23 | 07-FEB-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.51 |
March | 47422.12 | 07-MAR-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.88 |
April | 34234.33 | 16-APR-23:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.89 |
May | 26189.74 | 08-MAY-04:01 | 16808.50 | 800.29 | 27369.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 |
June | 56690.19 | 28-JUN-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.15 |
July | 58049.48 | 11-JUL-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.04 |
August | 64333.14 | 20-AUG-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 |
September | 57180.61 | 09-SEP-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.43 |
October | 30308.54 | 16-OCT-23:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.57 |
November | 32667.74 | 24-NOV-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.57 |
December | 53744.55 | 11-DEC-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26189.74 | 0.00 | 800.29 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | |
Maximum of Months | 64333.14 | 16808.50 | 2732.77 | 27369.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39402.43 | 10-JAN-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 |
February | 41011.85 | 07-FEB-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 112.62 |
March | 39200.76 | 07-MAR-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 |
April | 42579.92 | 09-APR-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 88.81 |
May | 50595.69 | 27-MAY-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 52926.97 | 04-JUN-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 |
July | 43562.16 | 06-JUL-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 |
August | 46677.27 | 03-AUG-03:11 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 60.10 |
September | 50212.30 | 03-SEP-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 58.20 |
October | 47440.06 | 02-OCT-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 |
November | 37361.77 | 05-NOV-03:01 | 0.00 | 270.10 | 24388.73 | 11559.35 | 0.00 | 0.00 | 0.00 | 0.00 | 113.18 |
December | 42286.62 | 11-DEC-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37361.77 | 0.00 | 270.10 | 24388.73 | 11559.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52926.97 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 113.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.49 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.49 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.04 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.82 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.46 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.82 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.24 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.95 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.45 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.74 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.49 | 15.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.576541E+11 | 34327.24 | 28-JAN-11:20 | 0.192448E+12 | 160281.09 | 10-JAN-04:30 |
February | 0.519439E+11 | 34567.54 | 06-FEB-11:09 | 0.181097E+12 | 171284.00 | 07-FEB-04:30 |
March | 0.572688E+11 | 41081.84 | 15-MAR-10:00 | 0.142773E+12 | 160281.09 | 07-MAR-04:19 |
April | 0.540904E+11 | 35657.31 | 08-APR-10:00 | 0.968398E+11 | 102298.82 | 17-APR-06:19 |
May | 0.575420E+11 | 40464.37 | 10-MAY-10:00 | 0.708233E+11 | 69560.08 | 01-MAY-06:19 |
June | 0.656239E+11 | 55221.66 | 27-JUN-11:00 | 0.624572E+11 | 42004.06 | 14-JUN-06:49 |
July | 0.780212E+11 | 55461.26 | 20-JUL-11:00 | 0.621968E+11 | 39642.55 | 02-JUL-10:09 |
August | 0.733267E+11 | 54827.97 | 10-AUG-11:00 | 0.620904E+11 | 39504.36 | 13-AUG-10:20 |
September | 0.619900E+11 | 50079.54 | 15-SEP-11:00 | 0.617795E+11 | 43067.07 | 30-SEP-05:19 |
October | 0.569057E+11 | 37952.54 | 11-OCT-17:40 | 0.832847E+11 | 89782.26 | 17-OCT-06:30 |
November | 0.549570E+11 | 34898.85 | 05-NOV-10:00 | 0.103455E+12 | 95547.58 | 24-NOV-07:30 |
December | 0.576030E+11 | 34420.33 | 11-DEC-11:09 | 0.179824E+12 | 171283.89 | 11-DEC-04:19 |
Annual Sum or Average | 0.726927E+12 | 0.129907E+13 | ||||
Minimum of Months | 0.519439E+11 | 34327.24 | 0.617795E+11 | 39504.36 | ||
Maximum of Months | 0.780212E+11 | 55461.26 | 0.192448E+12 | 171284.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.343810E+10 | 0.194002E+10 | 0.350888E+11 | 0.00 | 0.790529E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639849E+10 | 0.00 |
February | 0.304795E+10 | 0.158102E+10 | 0.316932E+11 | 0.00 | 0.722743E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579102E+10 | 0.00 |
March | 0.329863E+10 | 0.151407E+10 | 0.350891E+11 | 0.00 | 0.731326E+10 | 37879553.69 | 0.00 | 0.634447E+09 | 0.00 | 0.00 | 0.00 | 0.646472E+10 | 0.00 |
April | 0.306776E+10 | 0.122644E+10 | 0.339570E+11 | 0.00 | 0.660239E+10 | 36657632.61 | 0.00 | 0.112481E+09 | 0.00 | 0.00 | 0.00 | 0.620639E+10 | 0.00 |
May | 0.312057E+10 | 0.107119E+10 | 0.350889E+11 | 0.00 | 0.652286E+10 | 37879553.69 | 0.00 | 0.212293E+10 | 0.00 | 0.00 | 0.00 | 0.642029E+10 | 0.00 |
June | 0.299962E+10 | 0.952793E+09 | 0.339571E+11 | 0.00 | 0.646590E+10 | 36657632.61 | 0.00 | 0.118258E+11 | 0.00 | 0.00 | 0.00 | 0.623766E+10 | 0.00 |
July | 0.305150E+10 | 0.100839E+10 | 0.350888E+11 | 0.00 | 0.705186E+10 | 37879553.69 | 0.00 | 0.221261E+11 | 0.00 | 0.00 | 0.00 | 0.637183E+10 | 0.00 |
August | 0.316644E+10 | 0.117330E+10 | 0.350891E+11 | 0.00 | 0.682682E+10 | 37879553.69 | 0.00 | 0.173015E+11 | 0.00 | 0.00 | 0.00 | 0.645016E+10 | 0.00 |
September | 0.312210E+10 | 0.136238E+10 | 0.339570E+11 | 0.00 | 0.637516E+10 | 36657632.61 | 0.00 | 0.780825E+10 | 0.00 | 0.00 | 0.00 | 0.619674E+10 | 0.00 |
October | 0.330206E+10 | 0.165273E+10 | 0.350888E+11 | 0.00 | 0.668553E+10 | 37879553.69 | 0.00 | 0.691764E+09 | 0.00 | 0.00 | 0.00 | 0.638838E+10 | 0.00 |
November | 0.333076E+10 | 0.181190E+10 | 0.339569E+11 | 0.00 | 0.670501E+10 | 36657632.61 | 0.00 | 79521629.30 | 0.00 | 0.00 | 0.00 | 0.618885E+10 | 0.00 |
December | 0.346354E+10 | 0.199712E+10 | 0.350888E+11 | 0.00 | 0.777041E+10 | 37879553.69 | 0.00 | 59869.66 | 0.00 | 0.00 | 0.00 | 0.639038E+10 | 0.00 |
Annual Sum or Average | 0.384090E+11 | 0.172913E+11 | 0.413144E+12 | 0.00 | 0.834519E+11 | 0.446001E+09 | 0.00 | 0.627029E+11 | 0.00 | 0.00 | 0.00 | 0.755049E+11 | 0.00 |
Minimum of Months | 0.299962E+10 | 0.952793E+09 | 0.316932E+11 | 0.00 | 0.637516E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579102E+10 | 0.00 |
Maximum of Months | 0.346354E+10 | 0.199712E+10 | 0.350891E+11 | 0.00 | 0.790529E+10 | 37879553.69 | 0.00 | 0.221261E+11 | 0.00 | 0.00 | 0.00 | 0.646472E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.377451E+11 | 0.00 | 0.125001E+12 | 0.00 | 0.297026E+11 | 0.00 | 0.00 |
February | 0.340924E+11 | 0.00 | 0.119778E+12 | 0.00 | 0.272270E+11 | 0.00 | 0.00 |
March | 0.377451E+11 | 0.00 | 0.750391E+11 | 0.00 | 0.299887E+11 | 0.00 | 0.00 |
April | 0.365275E+11 | 0.00 | 0.325317E+11 | 0.00 | 0.277805E+11 | 0.00 | 0.00 |
May | 0.377451E+11 | 0.00 | 0.585795E+10 | 0.00 | 0.272203E+11 | 0.00 | 0.00 |
June | 0.365275E+11 | 0.00 | 0.962237E+09 | 0.00 | 0.249674E+11 | 0.00 | 0.00 |
July | 0.377451E+11 | 0.00 | 24501316.41 | 0.00 | 0.244272E+11 | 0.00 | 0.00 |
August | 0.377451E+11 | 0.00 | 64261787.17 | 0.00 | 0.242811E+11 | 0.00 | 0.00 |
September | 0.365275E+11 | 0.00 | 0.152495E+10 | 0.00 | 0.237270E+11 | 0.00 | 0.00 |
October | 0.377451E+11 | 0.00 | 0.199510E+11 | 0.00 | 0.255886E+11 | 0.00 | 0.00 |
November | 0.365275E+11 | 0.00 | 0.406929E+11 | 0.00 | 0.262345E+11 | 0.00 | 0.00 |
December | 0.377451E+11 | 0.00 | 0.113505E+12 | 0.00 | 0.285739E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.444418E+12 | 0.00 | 0.534932E+12 | 0.00 | 0.319719E+12 | 0.00 | 0.00 |
Minimum of Months | 0.340924E+11 | 0.00 | 24501316.41 | 0.00 | 0.237270E+11 | 0.00 | 0.00 |
Maximum of Months | 0.377451E+11 | 0.00 | 0.125001E+12 | 0.00 | 0.299887E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2497.72 | 02-JAN-16:49 | 1510.48 | 01-JAN-06:10 | 22638.52 | 01-JAN-11:09 | 0.00 | 4083.34 | 10-JAN-06:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 2497.72 | 01-FEB-17:30 | 1510.48 | 01-FEB-06:10 | 22638.52 | 01-FEB-11:09 | 0.00 | 4275.05 | 07-FEB-07:10 | 17.86 | 23-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 2497.72 | 01-MAR-17:00 | 1510.48 | 01-MAR-06:10 | 22638.52 | 01-MAR-11:09 | 0.00 | 4093.15 | 07-MAR-06:10 | 17.86 | 17-MAR-23:10 | 0.00 | 01-MAR-00:10 |
April | 2497.72 | 01-APR-18:40 | 1510.48 | 01-APR-05:10 | 22638.52 | 01-APR-10:09 | 0.00 | 3685.61 | 17-APR-05:00 | 17.86 | 10-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 2497.72 | 01-MAY-19:10 | 1510.48 | 01-MAY-05:10 | 22638.52 | 01-MAY-10:09 | 0.00 | 3377.68 | 01-MAY-05:10 | 17.86 | 18-MAY-11:39 | 0.00 | 01-MAY-00:10 |
June | 2497.72 | 01-JUN-19:49 | 1510.48 | 01-JUN-19:49 | 22638.52 | 01-JUN-10:09 | 0.00 | 4694.68 | 27-JUN-12:00 | 17.86 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 2497.72 | 01-JUL-19:00 | 1510.48 | 01-JUL-19:00 | 22638.52 | 01-JUL-10:09 | 0.00 | 4594.80 | 20-JUL-11:00 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 2497.72 | 01-AUG-19:40 | 1510.48 | 01-AUG-19:40 | 22638.52 | 01-AUG-10:09 | 0.00 | 4447.87 | 10-AUG-11:00 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2497.72 | 01-SEP-18:49 | 1510.48 | 01-SEP-05:10 | 22638.52 | 01-SEP-10:09 | 0.00 | 3713.44 | 15-SEP-11:00 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 2497.72 | 02-OCT-17:00 | 1510.48 | 01-OCT-05:10 | 22638.52 | 01-OCT-10:09 | 0.00 | 3575.23 | 17-OCT-05:10 | 17.86 | 08-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 2497.72 | 01-NOV-17:10 | 1510.48 | 01-NOV-05:10 | 22638.52 | 01-NOV-10:09 | 0.00 | 3641.80 | 24-NOV-06:10 | 17.86 | 01-NOV-23:10 | 0.00 | 01-NOV-00:10 |
December | 2497.72 | 01-DEC-16:40 | 1510.48 | 01-DEC-06:10 | 22638.52 | 01-DEC-11:09 | 0.00 | 4351.84 | 11-DEC-06:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 3377.68 | 17.86 | 0.00 | ||||||
Maximum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 4694.68 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.32 | 25-JAN-07:49 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4742.05 | 28-FEB-07:49 | 0.00 |
March | 10916.93 | 15-MAR-17:19 | 0.00 | 0.00 | 0.00 | 4742.12 | 21-MAR-18:10 | 0.00 |
April | 4916.75 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 4741.74 | 24-APR-06:49 | 0.00 |
May | 11419.07 | 10-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4741.87 | 08-MAY-06:49 | 0.00 |
June | 24846.75 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 4740.38 | 14-JUN-06:49 | 0.00 |
July | 24018.87 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4738.23 | 07-JUL-06:19 | 0.00 |
August | 23384.16 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4739.09 | 02-AUG-06:19 | 0.00 |
September | 19361.31 | 15-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4741.07 | 06-SEP-06:19 | 0.00 |
October | 8175.60 | 11-OCT-17:10 | 0.00 | 0.00 | 0.00 | 4740.89 | 30-OCT-06:49 | 0.00 |
November | 2728.46 | 16-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4741.50 | 03-NOV-18:00 | 0.00 |
December | 99.78 | 15-DEC-04:00 | 0.00 | 0.00 | 0.00 | 4741.66 | 11-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4738.23 | 0.00 | ||
Maximum of Months | 24846.75 | 0.00 | 0.00 | 0.00 | 4742.12 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 34327.24 | 28-JAN-11:20 | 1491.48 | 22638.52 | 0.00 | 0.00 | 3589.34 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 34567.54 | 06-FEB-11:09 | 1677.91 | 22638.52 | 0.00 | 0.00 | 4075.76 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 41081.84 | 15-MAR-10:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 2845.53 | 17.86 | 0.00 | 8718.21 | 0.00 |
April | 35657.31 | 08-APR-10:00 | 1491.48 | 22638.52 | 0.00 | 0.00 | 2845.53 | 17.86 | 0.00 | 3059.71 | 0.00 |
May | 40464.37 | 10-MAY-10:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 2845.53 | 17.86 | 0.00 | 8013.81 | 0.00 |
June | 55221.66 | 27-JUN-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 4508.17 | 17.86 | 0.00 | 23715.80 | 0.00 |
July | 55461.26 | 20-JUL-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 4594.80 | 17.86 | 0.00 | 23869.49 | 0.00 |
August | 54827.97 | 10-AUG-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 4447.87 | 17.86 | 0.00 | 23384.16 | 0.00 |
September | 50079.54 | 15-SEP-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 3713.44 | 17.86 | 0.00 | 19361.31 | 0.00 |
October | 37952.54 | 11-OCT-17:40 | 2497.72 | 18837.19 | 1510.48 | 0.00 | 2845.53 | 17.86 | 0.00 | 6851.64 | 0.00 |
November | 34898.85 | 05-NOV-10:00 | 1305.04 | 22638.52 | 0.00 | 0.00 | 2845.53 | 17.86 | 0.00 | 2326.38 | 0.00 |
December | 34420.33 | 11-DEC-11:09 | 1677.91 | 22638.52 | 0.00 | 0.00 | 3897.62 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 34327.24 | 1305.04 | 18837.19 | 0.00 | 0.00 | 2845.53 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55461.26 | 2497.72 | 22638.52 | 1510.48 | 0.00 | 4594.80 | 17.86 | 0.00 | 23869.49 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 24831.19 | 01-JAN-11:09 | 0.00 | 155196.62 | 10-JAN-04:30 | 0.00 | 28268.71 | 30-JAN-19:00 | 0.00 |
February | 24831.19 | 01-FEB-11:09 | 0.00 | 155196.62 | 05-FEB-04:30 | 0.00 | 28420.48 | 17-FEB-19:30 | 0.00 |
March | 24831.19 | 01-MAR-11:09 | 0.00 | 155196.62 | 07-MAR-04:19 | 0.00 | 28311.61 | 01-MAR-07:49 | 0.00 |
April | 24831.19 | 01-APR-10:09 | 0.00 | 69504.27 | 17-APR-05:00 | 0.00 | 27181.36 | 04-APR-06:40 | 0.00 |
May | 24831.19 | 01-MAY-10:09 | 0.00 | 42594.80 | 01-MAY-05:10 | 0.00 | 25493.79 | 01-MAY-06:19 | 0.00 |
June | 24831.19 | 01-JUN-10:09 | 0.00 | 18002.38 | 14-JUN-04:00 | 0.00 | 22914.92 | 01-JUN-06:30 | 0.00 |
July | 24831.19 | 01-JUL-10:09 | 0.00 | 2412.46 | 13-JUL-04:49 | 0.00 | 20407.87 | 03-JUL-18:00 | 0.00 |
August | 24831.19 | 01-AUG-10:09 | 0.00 | 4924.97 | 31-AUG-04:00 | 0.00 | 19037.59 | 29-AUG-06:30 | 0.00 |
September | 24831.19 | 01-SEP-10:09 | 0.00 | 19589.16 | 30-SEP-05:00 | 0.00 | 20459.79 | 29-SEP-18:40 | 0.00 |
October | 24831.19 | 01-OCT-10:09 | 0.00 | 59677.86 | 17-OCT-05:10 | 0.00 | 22995.26 | 31-OCT-06:00 | 0.00 |
November | 24831.19 | 01-NOV-10:09 | 0.00 | 65437.54 | 24-NOV-06:10 | 0.00 | 25388.46 | 30-NOV-07:40 | 0.00 |
December | 24831.19 | 01-DEC-11:09 | 0.00 | 155196.62 | 10-DEC-04:00 | 0.00 | 27174.24 | 29-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 24831.19 | 0.00 | 2412.46 | 0.00 | 19037.59 | 0.00 | |||
Maximum of Months | 24831.19 | 0.00 | 155196.62 | 0.00 | 28420.48 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 4.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
March | 0.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
April | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.00 | 24.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.66 | 0.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.61 | 0.00 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.64 | 0.00 | 24.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
December | 3.17 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Annual Sum or Average | 11.00 | 19.99 | 0.00 | 19.99 | 3.67 | 21.15 | 0.00 | 21.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.41 | 0.00 | 20.41 | 1.67 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 0.00 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.07 | 0.00 | 27.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.73 | 0.00 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 29.22 | 0.00 | 29.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 29.87 | 0.17 | 29.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 29.94 | 0.00 | 29.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 29.43 | 0.00 | 29.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.90 | 0.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.21 | 0.00 | 27.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.58 | 0.00 | 26.58 |
Annual Sum or Average | 0.00 | 0.00 | 75.83 | 29.29 | 0.17 | 29.28 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 29.94 | 0.17 | 29.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.74 | 337.00 | 20.66 | 337.00 | 20.63 |
February | 551.00 | 20.74 | 291.33 | 20.66 | 291.33 | 20.62 |
March | 585.50 | 20.84 | 162.83 | 20.78 | 144.00 | 20.68 |
April | 579.17 | 21.10 | 63.67 | 20.94 | 60.67 | 20.79 |
May | 438.50 | 21.72 | 88.83 | 21.98 | 24.00 | 21.95 |
June | 264.67 | 22.84 | 394.67 | 23.50 | 130.50 | 23.57 |
July | 291.00 | 23.78 | 566.83 | 23.92 | 258.83 | 23.94 |
August | 226.83 | 23.41 | 525.33 | 23.81 | 162.33 | 23.84 |
September | 293.83 | 22.36 | 346.83 | 23.22 | 90.50 | 23.30 |
October | 529.00 | 21.15 | 77.67 | 21.27 | 26.83 | 21.15 |
November | 582.33 | 20.94 | 54.33 | 20.77 | 54.33 | 20.62 |
December | 609.00 | 20.75 | 248.17 | 20.64 | 248.17 | 20.58 |
Annual Sum or Average | 5560.83 | 21.38 | 3157.50 | 21.82 | 1828.50 | 21.77 |
Minimum of Months | 226.83 | 20.74 | 54.33 | 20.64 | 24.00 | 20.58 |
Maximum of Months | 610.00 | 23.78 | 566.83 | 23.92 | 337.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.05 | 383.83 | 19.03 | 383.83 | 19.02 |
February | 551.00 | 19.05 | 329.00 | 19.03 | 329.00 | 19.02 |
March | 561.00 | 19.65 | 290.33 | 19.90 | 252.33 | 19.90 |
April | 458.00 | 20.02 | 198.83 | 20.77 | 93.33 | 20.71 |
May | 340.83 | 23.87 | 447.33 | 24.60 | 209.00 | 24.88 |
June | 476.83 | 25.72 | 554.17 | 25.70 | 453.67 | 25.78 |
July | 568.83 | 25.99 | 609.00 | 25.93 | 568.83 | 25.95 |
August | 536.00 | 25.98 | 611.83 | 25.87 | 536.00 | 25.90 |
September | 437.00 | 25.56 | 535.50 | 25.52 | 402.83 | 25.65 |
October | 411.33 | 21.49 | 278.67 | 22.61 | 123.00 | 22.91 |
November | 521.67 | 19.81 | 153.83 | 20.25 | 101.83 | 20.26 |
December | 605.17 | 19.04 | 299.33 | 19.04 | 296.17 | 19.03 |
Annual Sum or Average | 6077.67 | 21.93 | 4691.67 | 22.63 | 3749.83 | 22.81 |
Minimum of Months | 340.83 | 19.04 | 153.83 | 19.03 | 93.33 | 19.02 |
Maximum of Months | 610.00 | 25.99 | 611.83 | 25.93 | 568.83 | 25.95 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73913 | 21.61864 | -0.5962 | 13.30010 |
February | 551.00000 | 20.74298 | 21.78962 | -0.5941 | 13.26116 |
March | 612.00000 | 20.97629 | 30.94168 | -0.4269 | 10.67789 |
April | 590.00000 | 21.15331 | 36.75715 | -0.3207 | 8.71807 |
May | 611.00000 | 22.33975 | 42.74792 | -0.9955 | 29.06067 |
June | 592.00000 | 23.43931 | 52.33252 | -0.4952 | 12.81465 |
July | 609.00000 | 23.87005 | 60.80746 | -0.2601 | 7.23223 |
August | 612.00000 | 23.73716 | 56.06590 | -0.3350 | 8.56343 |
September | 590.00000 | 23.12475 | 52.94801 | -0.5915 | 15.60419 |
October | 610.00000 | 21.51374 | 42.55112 | -0.1550 | 7.67904 |
November | 591.00000 | 20.98491 | 34.73858 | -0.3750 | 9.16257 |
December | 609.00000 | 20.74907 | 25.44269 | -0.5563 | 12.33240 |
Annual Sum or Average | 7187.00000 | 21.95535 | 40.00014 | -0.4745 | 12.36987 |
Minimum of Months | 551.00000 | 20.73913 | 21.61864 | -0.9955 | 7.23223 |
Maximum of Months | 612.00000 | 23.87005 | 60.80746 | -0.1550 | 29.06067 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.04954 | 29.42351 | -0.6456 | 14.15280 |
February | 551.00000 | 19.04998 | 29.85211 | -0.6497 | 14.25129 |
March | 612.00000 | 19.97921 | 38.26237 | -0.3677 | 13.32167 |
April | 590.00000 | 20.93307 | 43.48188 | -0.1041 | 11.01015 |
May | 611.00000 | 24.03278 | 43.91830 | -0.1425 | 15.09255 |
June | 592.00000 | 25.40218 | 49.67665 | 0.41752 | 12.91512 |
July | 609.00000 | 25.87461 | 55.70773 | 0.65524 | 14.97572 |
August | 612.00000 | 25.77084 | 52.17066 | 0.59727 | 13.88600 |
September | 590.00000 | 25.10679 | 49.94204 | 0.33555 | 12.74615 |
October | 610.00000 | 22.18790 | 45.37811 | 0.25296 | 13.57054 |
November | 591.00000 | 20.31972 | 41.06920 | -0.2294 | 10.78349 |
December | 609.00000 | 19.06872 | 33.23961 | -0.6052 | 13.20607 |
Annual Sum or Average | 7187.00000 | 22.25066 | 42.74748 | -0.0369 | 13.33436 |
Minimum of Months | 551.00000 | 19.04954 | 29.42351 | -0.6497 | 10.78349 |
Maximum of Months | 612.00000 | 25.87461 | 55.70773 | 0.65524 | 15.09255 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.123823E+10 | 0.378713E+09 | 21.38 | 0.928253E+09 | 0.309977E+09 | 0.00 | 0.68 | 15-MAR-17:10 | 0.00 | 01-MAR-00:01 | 25588.59 | 14-MAR-13:00 | 20141.39 | 15-MAR-11:53 | 8200.08 | 14-MAR-11:45 | 7387.15 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.108309E+09 | 36451332.91 | 8.67 | 89841997.65 | 18467256.50 | 0.00 | 0.26 | 08-APR-13:00 | 0.00 | 01-APR-00:01 | 8448.32 | 08-APR-13:00 | 6848.41 | 08-APR-13:00 | 1599.91 | 08-APR-13:00 | 2765.02 | 08-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.324346E+10 | 0.103030E+10 | 106.88 | 0.258046E+10 | 0.663004E+09 | 0.00 | 0.72 | 10-MAY-13:00 | 0.00 | 01-MAY-00:01 | 26906.44 | 10-MAY-13:00 | 19065.29 | 10-MAY-13:00 | 7841.15 | 10-MAY-13:00 | 7741.26 | 10-MAY-13:00 | 0.00 | 01-MAY-00:01 |
June | 0.242729E+11 | 0.694180E+10 | 355.71 | 0.154183E+11 | 0.885458E+10 | 0.00 | 1.00 | 02-JUN-03:01 | 0.00 | 01-JUN-00:01 | 87886.85 | 18-JUN-03:01 | 55688.06 | 03-JUN-03:01 | 48714.52 | 18-JUN-03:02 | 22074.36 | 18-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.489515E+11 | 0.134528E+11 | 511.47 | 0.286008E+11 | 0.203507E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 89155.94 | 21-JUL-03:03 | 50643.85 | 06-JUL-03:01 | 53171.16 | 16-JUL-03:01 | 22176.66 | 20-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.371159E+11 | 0.104875E+11 | 448.60 | 0.243828E+11 | 0.127331E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 89155.94 | 14-AUG-03:01 | 54682.28 | 06-AUG-03:56 | 53760.69 | 14-AUG-03:14 | 22176.66 | 14-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.146545E+11 | 0.431508E+10 | 271.53 | 0.904254E+10 | 0.561198E+10 | 0.00 | 1.00 | 08-SEP-03:01 | 0.00 | 01-SEP-00:01 | 85988.26 | 16-SEP-03:01 | 51636.62 | 08-SEP-03:51 | 48633.97 | 16-SEP-03:01 | 21928.16 | 16-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.832979E+09 | 0.271533E+09 | 46.09 | 0.625457E+09 | 0.207522E+09 | 0.00 | 0.51 | 11-OCT-17:10 | 0.00 | 01-OCT-00:01 | 17867.59 | 11-OCT-17:10 | 14231.76 | 11-OCT-13:00 | 5990.35 | 12-OCT-03:09 | 5487.32 | 11-OCT-17:10 | 0.00 | 01-OCT-00:01 |
November | 24915445.89 | 8488987.13 | 3.67 | 18309941.81 | 6605504.08 | 0.00 | 0.15 | 16-NOV-13:00 | 0.00 | 01-NOV-00:01 | 4844.50 | 16-NOV-13:00 | 3587.69 | 16-NOV-13:00 | 1256.80 | 16-NOV-13:00 | 1626.42 | 16-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.130443E+12 | 0.369227E+11 | 1773.99 | 0.816868E+11 | 0.487559E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.489515E+11 | 0.134528E+11 | 511.47 | 0.286008E+11 | 0.203507E+11 | 0.00 | 1.00 | 0.00 | 89155.94 | 55688.06 | 53760.69 | 22176.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.987634E+09 | 0.255734E+09 | 28.24 | 0.741217E+09 | 0.246418E+09 | 0.00 | 1.00 | 14-MAR-03:42 | 0.00 | 01-MAR-00:01 | 34266.02 | 17-MAR-03:41 | 24513.06 | 16-MAR-03:42 | 16023.58 | 17-MAR-03:41 | 8215.25 | 16-MAR-03:01 | 0.00 | 01-MAR-00:01 |
April | 0.264618E+09 | 76029854.62 | 26.97 | 0.204955E+09 | 59662536.92 | 0.00 | 1.00 | 08-APR-03:01 | 0.00 | 01-APR-00:01 | 34266.02 | 08-APR-03:42 | 22539.81 | 08-APR-03:42 | 14754.73 | 09-APR-03:01 | 8215.25 | 08-APR-03:42 | 0.00 | 01-APR-00:01 |
May | 0.400579E+10 | 0.109263E+10 | 199.81 | 0.303725E+10 | 0.968540E+09 | 0.00 | 1.00 | 05-MAY-03:02 | 0.00 | 01-MAY-00:01 | 34266.02 | 28-MAY-03:01 | 25742.59 | 28-MAY-03:01 | 18385.22 | 29-MAY-03:01 | 8215.25 | 11-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.199806E+11 | 0.488405E+10 | 441.75 | 0.124207E+11 | 0.755984E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 38071.80 | 27-JUN-10:40 | 23853.93 | 15-JUN-03:01 | 21271.66 | 18-JUN-03:22 | 8633.61 | 27-JUN-12:55 | 0.00 | 01-JUN-00:01 |
July | 0.369901E+11 | 0.867332E+10 | 571.79 | 0.209994E+11 | 0.159906E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 38071.80 | 20-JUL-03:11 | 23481.34 | 21-JUL-11:00 | 24462.23 | 20-JUL-21:00 | 8562.27 | 20-JUL-13:55 | 0.00 | 01-JUL-00:01 |
August | 0.283361E+11 | 0.681398E+10 | 524.71 | 0.180798E+11 | 0.102564E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 38071.80 | 14-AUG-03:31 | 22602.55 | 06-AUG-03:50 | 23913.10 | 14-AUG-03:42 | 8473.98 | 14-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.139288E+11 | 0.349317E+10 | 371.31 | 0.837114E+10 | 0.555769E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 36219.28 | 16-SEP-03:01 | 21332.45 | 19-SEP-03:01 | 21044.25 | 16-SEP-03:01 | 8345.53 | 16-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.151368E+10 | 0.420231E+09 | 88.09 | 0.106121E+10 | 0.452471E+09 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 34266.02 | 06-OCT-03:41 | 24672.13 | 22-OCT-03:01 | 17818.56 | 26-OCT-03:42 | 8215.25 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.248284E+09 | 71032642.17 | 23.48 | 0.172563E+09 | 75720505.20 | 0.00 | 1.00 | 05-NOV-03:01 | 0.00 | 01-NOV-00:01 | 34266.02 | 27-NOV-04:42 | 25317.71 | 27-NOV-04:42 | 12441.97 | 05-NOV-03:01 | 8215.25 | 27-NOV-04:42 | 0.00 | 01-NOV-00:01 |
December | 193459.20 | 59869.66 | 0.17 | 123882.94 | 69576.27 | 0.00 | 0.02 | 15-DEC-05:00 | 0.00 | 01-DEC-00:01 | 322.43 | 15-DEC-05:00 | 206.47 | 15-DEC-05:00 | 115.96 | 15-DEC-05:00 | 99.78 | 15-DEC-05:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.106256E+12 | 0.257802E+11 | 2276.31 | 0.650884E+11 | 0.411674E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.369901E+11 | 0.867332E+10 | 571.79 | 0.209994E+11 | 0.159906E+11 | 0.00 | 1.00 | 0.00 | 38071.80 | 25742.59 | 24462.23 | 8633.61 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.30 | 45.51 | 95.79 | 54.93 | 451.16 | 0.00 | 0.00 | 0.00 |
February | 208.61 | 63.19 | 145.42 | 99.64 | 423.99 | 0.00 | 0.00 | 0.00 |
March | 299.34 | 125.88 | 173.46 | 246.12 | 290.21 | 0.00 | 0.00 | 0.00 |
April | 394.03 | 174.05 | 219.98 | 395.85 | 201.90 | 0.00 | 0.00 | 0.00 |
May | 441.47 | 195.32 | 246.15 | 508.03 | 133.89 | 0.00 | 0.00 | 0.00 |
June | 492.63 | 217.51 | 275.12 | 621.67 | 90.68 | 0.00 | 0.00 | 0.00 |
July | 473.12 | 208.04 | 265.08 | 639.03 | 62.74 | 0.00 | 0.00 | 0.00 |
August | 427.32 | 179.00 | 248.33 | 564.18 | 83.66 | 0.00 | 0.00 | 0.00 |
September | 355.97 | 157.91 | 198.06 | 426.36 | 132.55 | 0.00 | 0.00 | 0.00 |
October | 241.42 | 99.73 | 141.69 | 228.23 | 208.40 | 0.00 | 0.00 | 0.00 |
November | 136.86 | 43.82 | 93.04 | 87.86 | 282.41 | 0.00 | 0.00 | 0.00 |
December | 110.25 | 22.84 | 87.41 | 28.15 | 443.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 310.65 | 128.04 | 182.61 | 326.22 | 232.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.25 | 22.84 | 87.41 | 28.15 | 62.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 492.63 | 217.51 | 275.12 | 639.03 | 451.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 460.66 | 269.04 | 191.63 | 384.26 | 577.88 | 0.00 | 0.00 | 0.00 |
February | 521.69 | 249.50 | 272.19 | 430.17 | 561.92 | 0.00 | 0.00 | 0.00 |
March | 641.04 | 360.15 | 280.89 | 659.80 | 395.81 | 0.00 | 0.00 | 0.00 |
April | 530.18 | 211.38 | 318.80 | 577.99 | 298.32 | 0.00 | 0.00 | 0.00 |
May | 467.53 | 137.82 | 329.70 | 553.11 | 197.07 | 0.00 | 0.00 | 0.00 |
June | 450.02 | 94.23 | 355.79 | 582.05 | 134.16 | 0.00 | 0.00 | 0.00 |
July | 457.42 | 108.36 | 349.05 | 651.94 | 92.58 | 0.00 | 0.00 | 0.00 |
August | 512.19 | 162.53 | 349.66 | 713.32 | 121.87 | 0.00 | 0.00 | 0.00 |
September | 599.53 | 290.96 | 308.58 | 772.27 | 190.47 | 0.00 | 0.00 | 0.00 |
October | 576.54 | 329.62 | 246.91 | 654.06 | 286.67 | 0.00 | 0.00 | 0.00 |
November | 413.55 | 233.99 | 179.56 | 411.40 | 376.37 | 0.00 | 0.00 | 0.00 |
December | 385.21 | 199.66 | 185.54 | 304.31 | 566.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 501.16 | 220.51 | 280.65 | 558.63 | 315.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.21 | 94.23 | 179.56 | 304.31 | 92.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 641.04 | 360.15 | 355.79 | 772.27 | 577.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.69 | 28.68 | 93.00 | 34.19 | 461.31 | 0.00 | 0.00 | 0.00 |
February | 197.60 | 51.18 | 146.42 | 87.51 | 432.14 | 0.00 | 0.00 | 0.00 |
March | 309.37 | 132.86 | 176.51 | 261.04 | 294.93 | 0.00 | 0.00 | 0.00 |
April | 377.15 | 154.51 | 222.64 | 378.83 | 208.29 | 0.00 | 0.00 | 0.00 |
May | 445.41 | 201.51 | 243.90 | 514.73 | 137.89 | 0.00 | 0.00 | 0.00 |
June | 536.73 | 252.21 | 284.52 | 685.25 | 94.40 | 0.00 | 0.00 | 0.00 |
July | 479.77 | 210.01 | 269.76 | 651.26 | 66.39 | 0.00 | 0.00 | 0.00 |
August | 433.71 | 183.84 | 249.86 | 575.94 | 87.14 | 0.00 | 0.00 | 0.00 |
September | 340.96 | 147.08 | 193.88 | 407.21 | 136.48 | 0.00 | 0.00 | 0.00 |
October | 222.03 | 78.65 | 143.38 | 205.74 | 213.22 | 0.00 | 0.00 | 0.00 |
November | 130.82 | 37.52 | 93.29 | 81.17 | 285.76 | 0.00 | 0.00 | 0.00 |
December | 113.19 | 24.39 | 88.81 | 32.13 | 445.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 309.54 | 125.56 | 183.98 | 327.53 | 237.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.19 | 24.39 | 88.81 | 32.13 | 66.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 536.73 | 252.21 | 284.52 | 685.25 | 461.31 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378459E+09 | 0.121888E+09 | 0.256571E+09 | 0.147121E+09 | 0.120839E+10 |
February | 0.504678E+09 | 0.152875E+09 | 0.351802E+09 | 0.241049E+09 | 0.102571E+10 |
March | 0.801750E+09 | 0.337163E+09 | 0.464587E+09 | 0.659214E+09 | 0.777298E+09 |
April | 0.102134E+10 | 0.451141E+09 | 0.570195E+09 | 0.102604E+10 | 0.523323E+09 |
May | 0.118244E+10 | 0.523152E+09 | 0.659291E+09 | 0.136071E+10 | 0.358600E+09 |
June | 0.127691E+10 | 0.563796E+09 | 0.713112E+09 | 0.161136E+10 | 0.235041E+09 |
July | 0.126719E+10 | 0.557207E+09 | 0.709985E+09 | 0.171156E+10 | 0.168044E+09 |
August | 0.114454E+10 | 0.479423E+09 | 0.665121E+09 | 0.151111E+10 | 0.224071E+09 |
September | 0.922680E+09 | 0.409304E+09 | 0.513376E+09 | 0.110513E+10 | 0.343568E+09 |
October | 0.646627E+09 | 0.267124E+09 | 0.379503E+09 | 0.611293E+09 | 0.558166E+09 |
November | 0.354750E+09 | 0.113594E+09 | 0.241156E+09 | 0.227725E+09 | 0.732003E+09 |
December | 0.295305E+09 | 61175378.67 | 0.234129E+09 | 75395188.05 | 0.118776E+10 |
Annual Sum or Average | 0.979667E+10 | 0.403784E+10 | 0.575883E+10 | 0.102877E+11 | 0.734197E+10 |
Minimum of Months | 0.295305E+09 | 61175378.67 | 0.234129E+09 | 75395188.05 | 0.168044E+09 |
Maximum of Months | 0.127691E+10 | 0.563796E+09 | 0.713112E+09 | 0.171156E+10 | 0.120839E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123384E+10 | 0.720586E+09 | 0.513253E+09 | 0.102920E+10 | 0.154780E+10 |
February | 0.126207E+10 | 0.603602E+09 | 0.658471E+09 | 0.104066E+10 | 0.135940E+10 |
March | 0.171695E+10 | 0.964616E+09 | 0.752338E+09 | 0.176721E+10 | 0.106015E+10 |
April | 0.137423E+10 | 0.547899E+09 | 0.826331E+09 | 0.149815E+10 | 0.773235E+09 |
May | 0.125223E+10 | 0.369149E+09 | 0.883077E+09 | 0.148146E+10 | 0.527828E+09 |
June | 0.116645E+10 | 0.244246E+09 | 0.922206E+09 | 0.150867E+10 | 0.347730E+09 |
July | 0.122514E+10 | 0.290235E+09 | 0.934907E+09 | 0.174616E+10 | 0.247955E+09 |
August | 0.137185E+10 | 0.435320E+09 | 0.936533E+09 | 0.191055E+10 | 0.326409E+09 |
September | 0.155399E+10 | 0.754167E+09 | 0.799827E+09 | 0.200171E+10 | 0.493707E+09 |
October | 0.154420E+10 | 0.882865E+09 | 0.661332E+09 | 0.175182E+10 | 0.767804E+09 |
November | 0.107191E+10 | 0.606491E+09 | 0.465422E+09 | 0.106636E+10 | 0.975550E+09 |
December | 0.103173E+10 | 0.534778E+09 | 0.496956E+09 | 0.815057E+09 | 0.151816E+10 |
Annual Sum or Average | 0.158046E+11 | 0.695395E+10 | 0.885065E+10 | 0.176170E+11 | 0.994573E+10 |
Minimum of Months | 0.103173E+10 | 0.244246E+09 | 0.465422E+09 | 0.815057E+09 | 0.247955E+09 |
Maximum of Months | 0.171695E+10 | 0.964616E+09 | 0.936533E+09 | 0.200171E+10 | 0.154780E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.325928E+09 | 76825035.59 | 0.249103E+09 | 91567755.59 | 0.123557E+10 |
February | 0.478043E+09 | 0.123816E+09 | 0.354227E+09 | 0.211713E+09 | 0.104544E+10 |
March | 0.828607E+09 | 0.355848E+09 | 0.472759E+09 | 0.699162E+09 | 0.789935E+09 |
April | 0.977570E+09 | 0.400483E+09 | 0.577087E+09 | 0.981918E+09 | 0.539886E+09 |
May | 0.119299E+10 | 0.539724E+09 | 0.653261E+09 | 0.137866E+10 | 0.369337E+09 |
June | 0.139121E+10 | 0.653731E+09 | 0.737482E+09 | 0.177616E+10 | 0.244692E+09 |
July | 0.128501E+10 | 0.562498E+09 | 0.722512E+09 | 0.174434E+10 | 0.177806E+09 |
August | 0.116164E+10 | 0.492402E+09 | 0.669235E+09 | 0.154260E+10 | 0.233397E+09 |
September | 0.883776E+09 | 0.381239E+09 | 0.502537E+09 | 0.105548E+10 | 0.353755E+09 |
October | 0.594675E+09 | 0.210647E+09 | 0.384027E+09 | 0.551057E+09 | 0.571086E+09 |
November | 0.339074E+09 | 97257677.81 | 0.241817E+09 | 0.210398E+09 | 0.740693E+09 |
December | 0.303176E+09 | 65318922.40 | 0.237857E+09 | 86059556.28 | 0.119365E+10 |
Annual Sum or Average | 0.976169E+10 | 0.395979E+10 | 0.580190E+10 | 0.103291E+11 | 0.749525E+10 |
Minimum of Months | 0.303176E+09 | 65318922.40 | 0.237857E+09 | 86059556.28 | 0.177806E+09 |
Maximum of Months | 0.139121E+10 | 0.653731E+09 | 0.737482E+09 | 0.177616E+10 | 0.123557E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 418.39 | 1435.37 | 723.65 | 343.23 | 380.42 | 0.00 | 0.00 |
February | 571.92 | 1372.66 | 927.91 | 363.88 | 564.03 | 0.00 | 0.00 |
March | 1116.65 | 930.64 | 1249.74 | 618.89 | 630.86 | 0.00 | 0.00 |
April | 1317.95 | 673.79 | 1301.36 | 539.94 | 761.42 | 0.00 | 0.00 |
May | 1554.69 | 447.67 | 1354.41 | 534.66 | 819.75 | 0.00 | 0.00 |
June | 1873.26 | 303.54 | 1479.39 | 563.96 | 915.43 | 0.00 | 0.00 |
July | 1933.39 | 212.86 | 1410.30 | 526.41 | 883.89 | 0.00 | 0.00 |
August | 1844.77 | 284.00 | 1373.22 | 525.37 | 847.85 | 0.00 | 0.00 |
September | 1592.30 | 445.97 | 1296.47 | 595.95 | 700.52 | 0.00 | 0.00 |
October | 1073.07 | 693.32 | 1039.99 | 508.00 | 531.98 | 0.00 | 0.00 |
November | 563.32 | 927.42 | 681.23 | 315.33 | 365.89 | 0.00 | 0.00 |
December | 322.11 | 1413.46 | 608.65 | 246.89 | 361.76 | 0.00 | 0.00 |
Annual Sum or Average | 1185.13 | 758.61 | 1121.35 | 474.11 | 647.24 | 0.00 | 0.00 |
Minimum of Months | 322.11 | 212.86 | 608.65 | 246.89 | 361.76 | 0.00 | 0.00 |
Maximum of Months | 1933.39 | 1435.37 | 1479.39 | 618.89 | 915.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112063E+10 | 0.384449E+10 | 0.193823E+10 | 0.919299E+09 | 0.101893E+10 | 0.00 | 0.00 |
February | 0.138360E+10 | 0.332073E+10 | 0.224479E+10 | 0.880293E+09 | 0.136450E+10 | 0.00 | 0.00 |
March | 0.299084E+10 | 0.249263E+10 | 0.334731E+10 | 0.165763E+10 | 0.168968E+10 | 0.00 | 0.00 |
April | 0.341612E+10 | 0.174645E+10 | 0.337314E+10 | 0.139952E+10 | 0.197361E+10 | 0.00 | 0.00 |
May | 0.416409E+10 | 0.119903E+10 | 0.362765E+10 | 0.143203E+10 | 0.219563E+10 | 0.00 | 0.00 |
June | 0.485550E+10 | 0.786772E+09 | 0.383457E+10 | 0.146177E+10 | 0.237280E+10 | 0.00 | 0.00 |
July | 0.517838E+10 | 0.570124E+09 | 0.377734E+10 | 0.140994E+10 | 0.236740E+10 | 0.00 | 0.00 |
August | 0.494103E+10 | 0.760654E+09 | 0.367803E+10 | 0.140715E+10 | 0.227089E+10 | 0.00 | 0.00 |
September | 0.412725E+10 | 0.115594E+10 | 0.336045E+10 | 0.154471E+10 | 0.181574E+10 | 0.00 | 0.00 |
October | 0.287411E+10 | 0.185699E+10 | 0.278550E+10 | 0.136064E+10 | 0.142486E+10 | 0.00 | 0.00 |
November | 0.146012E+10 | 0.240388E+10 | 0.176574E+10 | 0.817342E+09 | 0.948394E+09 | 0.00 | 0.00 |
December | 0.862738E+09 | 0.378581E+10 | 0.163021E+10 | 0.661272E+09 | 0.968943E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373744E+11 | 0.239235E+11 | 0.353630E+11 | 0.149516E+11 | 0.204114E+11 | 0.00 | 0.00 |
Minimum of Months | 0.862738E+09 | 0.570124E+09 | 0.163021E+10 | 0.661272E+09 | 0.948394E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517838E+10 | 0.384449E+10 | 0.383457E+10 | 0.165763E+10 | 0.237280E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639850E+10 | -0.622515E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173352660.2 | 81.22 | 0.00 | 0.00 |
February | 0.579093E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156650850.7 | 81.22 | 0.00 | 0.00 |
March | 0.646467E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -170810829.4 | 81.22 | 0.00 | 0.00 |
April | 0.620625E+10 | -0.604348E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162773806.5 | 81.22 | 0.00 | 0.00 |
May | 0.642007E+10 | -0.626017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159907383.6 | 81.22 | 0.00 | 0.00 |
June | 0.623752E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150936908.2 | 81.21 | 0.00 | 0.00 |
July | 0.637171E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154606974.5 | 81.21 | 0.00 | 0.00 |
August | 0.645008E+10 | -0.629524E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154846756.9 | 81.21 | 0.00 | 0.00 |
September | 0.619646E+10 | -0.604480E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151658777.7 | 81.22 | 0.00 | 0.00 |
October | 0.638839E+10 | -0.622382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164576360.3 | 81.22 | 0.00 | 0.00 |
November | 0.618873E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164124529.1 | 81.22 | 0.00 | 0.00 |
December | 0.639025E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173189300.2 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755036E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193744E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579093E+10 | -0.629524E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173352660.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646467E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150936908.2 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.261731E+11 | -0.251599E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101321E+10 | 58.99 | 0.00 | 0.00 |
February | 0.240181E+11 | -0.231022E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -915840498.4 | 58.99 | 0.00 | 0.00 |
March | 0.264438E+11 | -0.254538E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -990035939.4 | 58.99 | 0.00 | 0.00 |
April | 0.244080E+11 | -0.234731E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -934918922.2 | 58.99 | 0.00 | 0.00 |
May | 0.238129E+11 | -0.229228E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -890069441.2 | 58.99 | 0.00 | 0.00 |
June | 0.217348E+11 | -0.209083E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -826492326.4 | 58.99 | 0.00 | 0.00 |
July | 0.211601E+11 | -0.203184E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -841696874.2 | 58.99 | 0.00 | 0.00 |
August | 0.210186E+11 | -0.201748E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843811965.5 | 58.99 | 0.00 | 0.00 |
September | 0.205600E+11 | -0.197269E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -833087167.4 | 58.99 | 0.00 | 0.00 |
October | 0.222619E+11 | -0.213291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -932801188.1 | 58.99 | 0.00 | 0.00 |
November | 0.229392E+11 | -0.219920E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -947208271.8 | 58.99 | 0.00 | 0.00 |
December | 0.250991E+11 | -0.240874E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101167E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279629E+12 | -0.268649E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.109808E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.205600E+11 | -0.254538E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.101321E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.264438E+11 | -0.197269E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -826492326.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.50 | 01-JAN-08:50 | 1842.60 | 27.75 | 174.17 | 236.67 | 1793.28 | 27.62 | 179.83 | 238.33 |
February | 262.50 | 0.52 | 0.50 | 01-FEB-09:20 | 1180.44 | 24.91 | 210.67 | 249.50 | 1122.03 | 24.32 | 199.17 | 249.83 |
March | 339.33 | 0.51 | 0.50 | 01-MAR-07:19 | 1109.26 | 21.90 | 176.17 | 321.33 | 1173.13 | 22.23 | 186.83 | 321.83 |
April | 371.17 | 0.52 | 0.50 | 01-APR-06:49 | 1141.35 | 20.76 | 163.33 | 347.33 | 1148.16 | 20.75 | 160.00 | 347.00 |
May | 332.17 | 0.52 | 0.50 | 01-MAY-05:00 | 1159.91 | 21.13 | 158.83 | 383.67 | 1302.24 | 20.98 | 158.00 | 384.83 |
June | 430.67 | 0.52 | 0.50 | 01-JUN-05:00 | 1134.47 | 22.12 | 214.33 | 401.83 | 1236.46 | 20.78 | 194.83 | 401.17 |
July | 439.00 | 0.52 | 0.50 | 01-JUL-05:30 | 1071.79 | 21.96 | 215.50 | 403.83 | 1168.06 | 20.73 | 189.50 | 405.83 |
August | 406.00 | 0.52 | 0.50 | 01-AUG-05:00 | 1154.14 | 21.08 | 208.50 | 380.17 | 1114.15 | 21.08 | 203.00 | 376.00 |
September | 289.17 | 0.52 | 0.50 | 01-SEP-07:40 | 1298.77 | 21.95 | 174.83 | 321.83 | 1544.85 | 22.29 | 186.50 | 324.33 |
October | 314.33 | 0.52 | 0.50 | 01-OCT-07:10 | 1050.88 | 23.26 | 198.00 | 294.33 | 1071.39 | 23.32 | 194.33 | 293.50 |
November | 258.33 | 0.52 | 0.50 | 01-NOV-07:40 | 1084.25 | 26.44 | 176.33 | 231.67 | 1083.05 | 26.18 | 173.17 | 231.83 |
December | 230.67 | 0.51 | 0.50 | 01-DEC-07:00 | 2284.10 | 30.87 | 189.83 | 223.67 | 2342.28 | 31.31 | 198.83 | 224.67 |
Annual Sum or Average | 3928.50 | 0.52 | 1248.79 | 23.19 | 2260.50 | 3795.83 | 1300.78 | 22.91 | 2224.00 | 3799.17 | ||
Minimum of Months | 230.67 | 0.51 | 0.50 | 1050.88 | 20.76 | 158.83 | 223.67 | 1071.39 | 20.73 | 158.00 | 224.67 | |
Maximum of Months | 439.00 | 0.52 | 0.50 | 2284.10 | 30.87 | 215.50 | 403.83 | 2342.28 | 31.31 | 203.00 | 405.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.739669E+11 | 131994.73 | 04-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701545E+11 | 131994.73 | 03-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464385E+11 | 131994.73 | 04-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228472E+11 | 91058.61 | 17-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.475928E+10 | 33200.36 | 08-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.817602E+09 | 26156.13 | 04-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20838369.61 | 7879.38 | 13-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 54654649.99 | 9180.51 | 31-AUG-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129663E+10 | 24656.65 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148939E+11 | 47867.05 | 17-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287690E+11 | 60713.02 | 24-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.683239E+11 | 131994.73 | 07-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20838369.61 | 7879.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.739669E+11 | 131994.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.323462E+11 | 55335.76 | 04-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317164E+11 | 59104.16 | 07-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173823E+11 | 53729.33 | 05-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.482102E+10 | 27333.02 | 03-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222901E+09 | 12430.39 | 08-MAY-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 779940.18 | 5909.17 | 14-JUN-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 346130.14 | 2892.21 | 30-SEP-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207437E+10 | 21348.23 | 17-OCT-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.584027E+10 | 25730.02 | 25-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282122E+11 | 56690.86 | 11-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323462E+11 | 59104.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.123823E+10 | 0.928253E+09 | 25588.59 | 14-MAR-13:00 | 17575.31 | 0.00 |
April | 0.00 | 0.00 | 0.108309E+09 | 89841997.65 | 8448.32 | 08-APR-13:00 | 6848.41 | 0.00 |
May | 0.00 | 0.00 | 0.324346E+10 | 0.258046E+10 | 26906.44 | 10-MAY-13:00 | 19065.29 | 0.00 |
June | 0.00 | 0.00 | 0.242729E+11 | 0.154183E+11 | 87886.85 | 18-JUN-03:01 | 39179.56 | 0.00 |
July | 0.00 | 0.00 | 0.489515E+11 | 0.286008E+11 | 89155.94 | 21-JUL-03:03 | 36744.97 | 0.00 |
August | 0.00 | 0.00 | 0.371159E+11 | 0.243828E+11 | 89155.94 | 14-AUG-03:01 | 35507.95 | 0.00 |
September | 0.00 | 0.00 | 0.146545E+11 | 0.904254E+10 | 85988.26 | 16-SEP-03:01 | 37354.29 | 0.00 |
October | 0.00 | 0.00 | 0.832979E+09 | 0.625457E+09 | 17867.59 | 11-OCT-17:10 | 13590.87 | 0.00 |
November | 0.00 | 0.00 | 24915445.89 | 18309941.81 | 4844.50 | 16-NOV-13:00 | 3587.69 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130443E+12 | 0.816868E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.489515E+11 | 0.286008E+11 | 89155.94 | 39179.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.987634E+09 | 0.741217E+09 | 34266.02 | 17-MAR-03:41 | 18242.44 | 0.00 |
April | 0.00 | 0.00 | 0.264618E+09 | 0.204955E+09 | 34266.02 | 08-APR-03:42 | 22539.81 | 0.00 |
May | 0.00 | 0.00 | 0.400579E+10 | 0.303725E+10 | 34266.02 | 28-MAY-03:01 | 25742.59 | 0.00 |
June | 0.00 | 0.00 | 0.199806E+11 | 0.124207E+11 | 38071.80 | 27-JUN-10:40 | 20627.27 | 0.00 |
July | 0.00 | 0.00 | 0.369901E+11 | 0.209994E+11 | 38071.80 | 20-JUL-03:11 | 16545.22 | 0.00 |
August | 0.00 | 0.00 | 0.283361E+11 | 0.180798E+11 | 38071.80 | 14-AUG-03:31 | 14254.73 | 0.00 |
September | 0.00 | 0.00 | 0.139288E+11 | 0.837114E+10 | 36219.28 | 16-SEP-03:01 | 15175.03 | 0.00 |
October | 0.00 | 0.00 | 0.151368E+10 | 0.106121E+10 | 34266.02 | 06-OCT-03:41 | 20114.12 | 0.00 |
November | 0.00 | 0.00 | 0.248284E+09 | 0.172563E+09 | 34266.02 | 27-NOV-04:42 | 25317.71 | 0.00 |
December | 0.00 | 0.00 | 193459.20 | 123882.94 | 322.43 | 15-DEC-05:00 | 206.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.106256E+12 | 0.650884E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.369901E+11 | 0.209994E+11 | 38071.80 | 25742.59 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9852.07 | 18953.49 | 30-JAN-19:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10007.55 | 19023.61 | 10-FEB-19:30 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9961.33 | 18970.60 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9514.74 | 18408.82 | 03-APR-18:10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9018.30 | 17593.84 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8527.32 | 16512.18 | 01-JUN-18:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8048.12 | 15579.12 | 03-JUL-06:44 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 7994.33 | 15082.32 | 02-AUG-18:08 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8072.43 | 15541.26 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8424.66 | 16474.69 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8944.87 | 17480.22 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9452.22 | 18361.94 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8978.83 | ||||
Minimum of Months | 0.00 | 0.00 | 7994.33 | 15082.32 | ||
Maximum of Months | 0.00 | 0.00 | 10007.55 | 19023.61 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183995E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.27 |
February | 0.166145E+10 | 0.23 | 824.13 | 01-FEB-00:01 | 0.27 |
March | 0.185602E+10 | 0.23 | 824.13 | 01-MAR-00:01 | 0.27 |
April | 0.181523E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.27 |
May | 0.191808E+10 | 0.23 | 824.13 | 01-MAY-03:15 | 0.27 |
June | 0.192179E+10 | 0.24 | 824.13 | 01-JUN-03:01 | 0.27 |
July | 0.205159E+10 | 0.25 | 824.13 | 01-JUL-01:25 | 0.27 |
August | 0.204698E+10 | 0.25 | 824.13 | 01-AUG-00:50 | 0.27 |
September | 0.190844E+10 | 0.24 | 824.13 | 01-SEP-03:01 | 0.27 |
October | 0.190312E+10 | 0.23 | 824.13 | 01-OCT-03:01 | 0.27 |
November | 0.181276E+10 | 0.23 | 824.13 | 01-NOV-03:02 | 0.27 |
December | 0.184243E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.225778E+11 | 0.23 | |||
Minimum of Months | 0.166145E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.205159E+10 | 0.25 | 824.13 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.433117E+10 | 0.58 | 3504.91 | 04-JAN-04:02 | 0.91 |
February | 0.397249E+10 | 0.58 | 3504.91 | 03-FEB-04:02 | 0.90 |
March | 0.388281E+10 | 0.53 | 3504.91 | 04-MAR-04:02 | 0.91 |
April | 0.339360E+10 | 0.49 | 2417.92 | 17-APR-03:02 | 0.90 |
May | 0.320550E+10 | 0.46 | 1930.92 | 08-MAY-04:02 | 0.67 |
June | 0.306904E+10 | 0.46 | 3504.91 | 12-JUN-03:01 | 0.89 |
July | 0.322687E+10 | 0.47 | 3504.91 | 02-JUL-03:01 | 0.89 |
August | 0.317802E+10 | 0.46 | 3504.91 | 06-AUG-03:01 | 0.90 |
September | 0.305903E+10 | 0.46 | 3504.91 | 09-SEP-03:01 | 0.90 |
October | 0.336702E+10 | 0.48 | 2164.59 | 17-OCT-04:01 | 0.71 |
November | 0.348729E+10 | 0.50 | 2308.47 | 25-NOV-05:01 | 0.74 |
December | 0.423863E+10 | 0.56 | 3504.91 | 07-DEC-04:02 | 0.90 |
Annual Sum or Average | 0.424115E+11 | 0.50 | |||
Minimum of Months | 0.305903E+10 | 0.46 | 1930.92 | 0.67 | |
Maximum of Months | 0.433117E+10 | 0.58 | 3504.91 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173417E+10 | 0.54 | 1220.86 | 04-JAN-05:03 | 0.84 |
February | 0.159350E+10 | 0.55 | 1261.82 | 07-FEB-05:03 | 0.85 |
March | 0.157443E+10 | 0.51 | 1548.59 | 16-MAR-03:01 | 0.93 |
April | 0.139355E+10 | 0.49 | 1548.59 | 09-APR-03:01 | 0.93 |
May | 0.139928E+10 | 0.49 | 1548.59 | 11-MAY-03:01 | 0.93 |
June | 0.147506E+10 | 0.52 | 1548.59 | 01-JUN-03:01 | 0.93 |
July | 0.177341E+10 | 0.57 | 1548.59 | 01-JUL-03:01 | 0.93 |
August | 0.160182E+10 | 0.55 | 1548.59 | 01-AUG-03:01 | 0.93 |
September | 0.140770E+10 | 0.51 | 1548.59 | 01-SEP-03:01 | 0.93 |
October | 0.141538E+10 | 0.49 | 1548.59 | 01-OCT-03:01 | 0.93 |
November | 0.140496E+10 | 0.49 | 1469.12 | 05-NOV-03:01 | 0.91 |
December | 0.168935E+10 | 0.53 | 1235.59 | 11-DEC-05:03 | 0.84 |
Annual Sum or Average | 0.184626E+11 | 0.52 | |||
Minimum of Months | 0.139355E+10 | 0.49 | 1220.86 | 0.84 | |
Maximum of Months | 0.177341E+10 | 0.57 | 1548.59 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.91 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 47.19 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.75 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.91 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:05 | 5.36 | 5.36 | 51.38 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 51.72 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 52.62 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.40 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.54 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.88 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.68 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.86 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 46.75 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.62 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.91 | 59.93 | 9852.07 | 18953.49 | 30-JAN-19:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 47.19 | 59.38 | 10007.55 | 19023.61 | 10-FEB-19:30 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.75 | 59.66 | 9961.33 | 18970.60 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 48.95 | 48.95 | 9514.74 | 18408.82 | 03-APR-18:10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.49 | 49.49 | 9018.30 | 17593.84 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.09 | 50.09 | 8527.32 | 16512.18 | 01-JUN-18:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.53 | 50.53 | 8048.12 | 15579.12 | 03-JUL-06:44 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.91 | 50.91 | 7994.33 | 15082.32 | 02-AUG-18:08 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.04 | 51.04 | 8072.43 | 15541.26 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.55 | 48.55 | 8424.66 | 16474.69 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.19 | 50.19 | 8944.87 | 17480.22 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.86 | 59.81 | 9452.22 | 18361.94 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8978.83 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.75 | 48.55 | 7994.33 | 15082.32 | ||
Maximum of Months | 0.00 | 0.00 | 51.04 | 59.93 | 10007.55 | 19023.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.433117E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.397249E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.426152E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.343005E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.423580E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.100108E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.166797E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.136655E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.737411E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.363855E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.349578E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.423863E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.793342E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.343005E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166797E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.173417E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159350E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.183016E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146958E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.249191E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.635911E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.104467E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.841580E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.490087E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.183561E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147599E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168941E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.442428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146958E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104467E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.433117E+10 | 0.00 | 0.739669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397249E+10 | 0.00 | 0.701545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388281E+10 | 0.123823E+10 | 0.464385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339360E+10 | 0.108309E+09 | 0.228472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.320550E+10 | 0.324346E+10 | 0.475928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306904E+10 | 0.242234E+11 | 0.817602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322687E+10 | 0.488423E+11 | 20838369.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.317802E+10 | 0.370225E+11 | 54654649.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305903E+10 | 0.146163E+11 | 0.129663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336702E+10 | 0.832979E+09 | 0.148939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348729E+10 | 24915445.89 | 0.287690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.423863E+10 | 0.00 | 0.683239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424115E+11 | 0.130152E+12 | 0.332343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305903E+10 | 0.00 | 20838369.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.433117E+10 | 0.488423E+11 | 0.739669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173417E+10 | 0.00 | 0.323462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159350E+10 | 0.00 | 0.317164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157443E+10 | 0.985237E+09 | 0.173823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139355E+10 | 0.263220E+09 | 0.482102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139928E+10 | 0.399897E+10 | 0.222901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147506E+10 | 0.199283E+11 | 779940.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177341E+10 | 0.368607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160182E+10 | 0.282563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140770E+10 | 0.138939E+11 | 346130.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141538E+10 | 0.151012E+10 | 0.207437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140496E+10 | 0.246886E+09 | 0.584027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168935E+10 | 193459.20 | 0.282122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184626E+11 | 0.105944E+12 | 0.122617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177341E+10 | 0.368607E+11 | 0.323462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.433117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388281E+10 | 0.00 | 0.00 | 0.00 | 0.378713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339360E+10 | 0.00 | 0.00 | 0.00 | 36451332.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.320550E+10 | 0.00 | 0.00 | 0.00 | 0.103030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306904E+10 | 0.00 | 0.00 | 0.00 | 0.694180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322687E+10 | 0.00 | 0.00 | 0.00 | 0.134528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.317802E+10 | 0.00 | 0.00 | 0.00 | 0.104875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305903E+10 | 0.00 | 0.00 | 0.00 | 0.431508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336702E+10 | 0.00 | 0.00 | 0.00 | 0.271533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348729E+10 | 0.00 | 0.00 | 0.00 | 8488987.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.423863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424115E+11 | 0.00 | 0.00 | 0.00 | 0.369227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.433117E+10 | 0.00 | 0.00 | 0.00 | 0.134528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157443E+10 | 0.00 | 0.00 | 0.00 | 0.255734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139355E+10 | 0.00 | 0.00 | 0.00 | 76029854.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139928E+10 | 0.00 | 0.00 | 0.00 | 0.109263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147506E+10 | 0.00 | 0.00 | 0.00 | 0.488405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177341E+10 | 0.00 | 0.00 | 0.00 | 0.867332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160182E+10 | 0.00 | 0.00 | 0.00 | 0.681398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140770E+10 | 0.00 | 0.00 | 0.00 | 0.349317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141538E+10 | 0.00 | 0.00 | 0.00 | 0.420231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140496E+10 | 0.00 | 0.00 | 0.00 | 71032642.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168935E+10 | 0.00 | 0.00 | 0.00 | 59869.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184626E+11 | 0.00 | 0.00 | 0.00 | 0.257802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177341E+10 | 0.00 | 0.00 | 0.00 | 0.867332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.772930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192848E+11 | 0.00 | 0.00 | 3.57 |
February | 0.675093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228181E+11 | 0.00 | 0.00 | 3.58 |
March | 0.652739E+11 | 5108466.15 | 0.00 | 3942573.79 | 0.00 | 0.827554E+10 | 0.122570E+10 | 0.00 | 3.56 |
April | 0.517685E+11 | 0.00 | 0.00 | 2779716.20 | 0.00 | 0.120970E+10 | 0.272369E+10 | 0.00 | 3.59 |
May | 0.267352E+11 | 50100946.65 | 0.00 | 28358250.58 | 0.00 | 29492491.64 | 0.137309E+11 | 0.00 | 3.73 |
June | 0.906746E+10 | 0.288971E+10 | 98364.64 | 58694716.97 | 7045223.57 | 4563872.43 | 0.143418E+11 | 2717.97 | 3.96 |
July | 0.287902E+10 | 0.883135E+10 | 0.00 | 48853479.62 | 52049548.99 | 0.00 | 0.673057E+10 | 0.00 | 4.03 |
August | 0.458551E+10 | 0.457116E+10 | 0.00 | 69972551.79 | 13635960.15 | 0.00 | 0.118598E+11 | 0.00 | 4.00 |
September | 0.131553E+11 | 0.707815E+09 | 0.00 | 54237412.03 | 1432773.95 | 6251922.30 | 0.171900E+11 | 0.00 | 3.96 |
October | 0.443761E+11 | 0.00 | 0.00 | 10236614.30 | 0.00 | 51852320.37 | 0.740263E+10 | 0.00 | 3.63 |
November | 0.574449E+11 | 0.00 | 0.00 | 1232110.70 | 0.00 | 0.102348E+10 | 0.197623E+10 | 0.00 | 3.57 |
December | 0.767161E+11 | 0.00 | 0.00 | 11799.40 | 0.00 | 0.157344E+11 | 51470208.31 | 0.00 | 3.58 |
Annual Sum or Average | 0.496804E+12 | 0.170552E+11 | 98364.64 | 0.278319E+09 | 74163506.66 | 0.684382E+11 | 0.772328E+11 | 2717.97 | 3.73 |
Minimum of Months | 0.287902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
Maximum of Months | 0.772930E+11 | 0.883135E+10 | 98364.64 | 69972551.79 | 52049548.99 | 0.228181E+11 | 0.171900E+11 | 2717.97 | 4.03 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.724813E+11 | 0.00 | 0.00 | 15923.18 | 0.00 | 51664086.75 | 90891768.07 | 0.00 | 7.08 |
February | 0.678454E+11 | 0.00 | 0.00 | 37594.03 | 0.00 | 37025154.57 | 0.195831E+09 | 0.00 | 7.13 |
March | 0.535052E+11 | 0.00 | 0.00 | 6482450.03 | 0.00 | 25604942.70 | 0.383277E+10 | 0.00 | 6.83 |
April | 0.370389E+11 | 0.00 | 0.00 | 8048757.05 | 0.00 | 5351230.11 | 0.796314E+10 | 0.00 | 6.70 |
May | 0.132962E+11 | 0.00 | 0.00 | 49816607.69 | 0.00 | 0.00 | 0.250948E+11 | 0.00 | 6.74 |
June | 0.380895E+10 | 0.135296E+10 | 0.00 | 76526148.78 | 0.00 | 0.00 | 0.192385E+11 | 0.00 | 7.02 |
July | 0.570180E+09 | 0.449978E+10 | 0.00 | 74978270.93 | 0.00 | 0.00 | 0.105041E+11 | 0.00 | 7.49 |
August | 0.687045E+09 | 0.207005E+10 | 0.00 | 92218420.92 | 0.00 | 0.00 | 0.169525E+11 | 0.00 | 7.18 |
September | 0.512301E+10 | 0.158784E+09 | 0.00 | 74752817.55 | 0.00 | 0.00 | 0.231080E+11 | 0.00 | 6.88 |
October | 0.252301E+11 | 0.00 | 0.00 | 21742378.73 | 0.00 | 0.00 | 0.178028E+11 | 0.00 | 6.69 |
November | 0.402619E+11 | 0.00 | 0.00 | 5371340.04 | 0.00 | 2502695.36 | 0.586370E+10 | 0.00 | 6.70 |
December | 0.685022E+11 | 0.00 | 0.00 | 126266.25 | 0.00 | 29056949.76 | 0.246596E+09 | 0.00 | 7.04 |
Annual Sum or Average | 0.388350E+12 | 0.808157E+10 | 0.00 | 0.410117E+09 | 0.00 | 0.151205E+09 | 0.130894E+12 | 0.00 | 6.96 |
Minimum of Months | 0.570180E+09 | 0.00 | 0.00 | 15923.18 | 0.00 | 0.00 | 90891768.07 | 0.00 | 6.69 |
Maximum of Months | 0.724813E+11 | 0.449978E+10 | 0.00 | 92218420.92 | 0.00 | 51664086.75 | 0.250948E+11 | 0.00 | 7.49 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.227053E+11 | 0.147892E+11 | 0.283382E+12 | 0.00 | 0.282524E+11 |
February | 0.478848E+11 | 0.144657E+11 | 0.263468E+12 | 0.00 | 0.271315E+11 |
March | 0.807040E+11 | 0.127814E+11 | 0.228564E+12 | 76787543.68 | 0.266774E+11 |
April | 0.103100E+12 | 0.109430E+11 | 0.183717E+12 | 0.119938E+09 | 0.199258E+11 |
May | 0.134488E+12 | 0.917846E+10 | 0.152329E+12 | 0.115307E+10 | 0.283153E+11 |
June | 0.153431E+12 | 0.656814E+10 | 0.884188E+11 | 0.176697E+10 | 0.747121E+11 |
July | 0.140272E+12 | 0.372648E+10 | 0.308583E+11 | 0.717468E+09 | 0.128358E+12 |
August | 0.116074E+12 | 0.469045E+10 | 0.667710E+11 | 0.134296E+10 | 0.102505E+12 |
September | 0.827514E+11 | 0.577445E+10 | 0.113679E+12 | 0.196362E+10 | 0.543984E+11 |
October | 0.499574E+11 | 0.848667E+10 | 0.175838E+12 | 0.607310E+09 | 0.196894E+11 |
November | 0.200506E+11 | 0.916770E+10 | 0.190583E+12 | 62051380.87 | 0.168590E+11 |
December | 0.195782E+11 | 0.140447E+11 | 0.270804E+12 | 0.00 | 0.261132E+11 |
Annual Sum or Average | 0.970996E+12 | 0.114616E+12 | 0.204841E+13 | 0.781017E+10 | 0.552937E+12 |
Minimum of Months | 0.195782E+11 | 0.372648E+10 | 0.308583E+11 | 0.00 | 0.168590E+11 |
Maximum of Months | 0.153431E+12 | 0.147892E+11 | 0.283382E+12 | 0.196362E+10 | 0.128358E+12 |