Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:27:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1803.38 | 3528.06 | 3528.06 |
Net Site Energy | 1803.38 | 3528.06 | 3528.06 |
Total Source Energy | 4295.59 | 8403.72 | 8403.72 |
Net Source Energy | 4295.59 | 8403.72 | 8403.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 12.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 397.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.39 | 222.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 38.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1123.73 | 679.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 12.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 397.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 394.51 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 143.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.39 | 222.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 12.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 397.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 143.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.39 | 222.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 38.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 109.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1205.23 | 460.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 884.04 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2198.42 | 1329.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 109.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1205.23 | 460.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 884.04 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2198.42 | 1329.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1123.728 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1123.728 | 100.00 |
Total On-Site and Utility Electric Sources | 1123.728 | 100.00 |
Total Electricity End Uses | 1123.728 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1595.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5928.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 5.1620 | 1.33 | 61.4214 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.3591 | 18.52 | 1000.6314 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 5.1620 | 1.33 | 61.4214 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.3591 | 18.52 | 1000.6314 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Conditioned Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 6.0339 | 1.78 | 317.5692 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUN-17:10 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 06-MAR-07:00 |
Heating | 0.00 | 28504.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42963.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18837.19 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9884.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4159.59 | 14764.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1255.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 78795.39 | 56112.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 28504.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 42963.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 18246.39 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9884.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4159.59 | 14764.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 424.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 14.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1257.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1308.43 | 481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 453.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.76 | 240.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 122.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3558.85 | 736.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2460.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 886.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.09 | 471.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 240.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6962.39 | 1441.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2460.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 886.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.09 | 471.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 240.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6962.39 | 1441.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.37 |
KITCHEN DIRECT AIR | 1.54 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.37 | 4.37 | 4.37 | 4.37 | 4.37 | 4.37 | 1.00 | 1.00 | 4.37 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.37 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.54 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.37 | 7408.86 |
PSZ-AC_2:2_ADDAQ FAN | 1.54 | 1651.24 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.37 | 4.37 | 4.37 | 2.88 | 108500.65 | 121001.80 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.02 | 38319.91 | 63761.48 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.37 | 2.18 | 2.91 | 108500.65 | 54250.32 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.54 | 0.771571 | 1.03 | 38319.91 | 19159.96 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 121001.80 |
PSZ-AC_2:2 HEATING COIL | 63761.48 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 5.162 | 61.421 | 0.000 | 0.000 | 0.000 | 0.000 | 66.583 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.359 | 386.416 | 614.215 | 0.000 | 0.000 | 0.000 | 1008.991 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 1918.948 | 5.162 | 6.850 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1918.948 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1165.301 | 8.359 | 154.798 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1165.301 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 22833.282 | 61.421 | 81.506 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6621.652 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 53277.659 | 382.178 | 7077.360 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 15450.521 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 85624.808 | 614.215 | 11374.329 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 24831.194 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.342 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5109 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 6 | 0.21862767E-07 | 0.34448908E-09 | 0.50649605E-08 | -0.99069094E-13 |
34 | 5 | -0.15485004E-03 | 0.31008008E-05 | -0.80011323E-04 | 0.50225397E-08 |
35 | 4 | 0.24987207 | 0.15775750E-02 | 0.84530116E-01 | -0.27712185E-04 |
36 | 3 | -6.4266483 | 0.50820490E-01 | -2.0899201 | 0.24901095E-01 |
37 | 2 | 38.099035 | 0.18692275 | 14.237681 | -0.30248143 |
38 | 1 | -78.418483 | 0.86852168E-01 | -28.218840 | 1.0332909 |
39 | 0 | 46.824353 | 0.17981083E-02 | 16.314603 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 38 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.23 | 39 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 40 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 41 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.884 | 0.3002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 3.373E-002 | 9.073E-005 | 1.994E-004 | 0.107 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 2.124E-002 | 1.523E-004 | 1.958E-004 | 0.180 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.9886E-004 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.8802E-003 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.2819E-004 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.5773E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.5682E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.2352E-003 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.9399E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.3570E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.4331E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.3515E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.5842E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4889E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.6854E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.6432E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.5148E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.5150E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.5651E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.4665E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.0003E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.4163E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.4818E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.0469E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.3570E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.9399E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 48663.25336 | 58395.90403 | 3.64110 | 4.36932 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 4290.42583 | 5148.51100 | 0.18866 | 1.33138 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 6.30000 | 6.07234E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20262.69785 | 24315.23742 | 1.28595 | 1.54314 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 41.12700 | 9.15644E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 6.30000 | 6.07234E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 85924.04 | 4.36932 | 4.36932 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 52920.60 | 1.33138 | 1.33138 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 46054.86 | 1.54314 | 1.54314 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 48374.32 | 1.21700 | 1.21700 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.36932 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54314 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.36932 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.36932 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.36932 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.36932 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.36932 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.36932 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.54314 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54314 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.54314 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54314 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.54314 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.54314 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.36932 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.54314 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.36932 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.36932 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7408.85824 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.36932 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.36932 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.36932 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.88375 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.36932 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.18466 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.91288 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 108500.65000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 54250.32500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 108500.65000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 121001.79717 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 121001.79717 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.54314 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.54314 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1651.23560 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.54314 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.54314 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.54314 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01847 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.54314 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77157 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02876 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38319.91000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19159.95500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38319.91000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 63761.48495 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 63761.48495 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 105395.1 | 11.22 | 11.17 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 37223.1 | 12.34 | 12.29 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | N/A | 2.860 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | N/A | 2.860 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | N/A | 2.860 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.2325743703E-002 | 0.2256658115 | Pass | Pass | 8.0683502782E-002 | 0.3113406693 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1938493207 | 0.5463085292 | Pass | Pass | 4.6237091049E-002 | 0.2213021900 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4166016432 | 0.4150423131 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 971.34 | -25.7 | -235.8 | 37.26 | 2228.43 | 2975.62 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.503_SHGC_EAST_0.23 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.23 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.503_SHGC_WEST_0.23 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.860 | 0.231 | 0.254 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 5.1620 | 371.75 | 1918.95 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.64 | 0.0000 | Y | 21.84 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.3591 | 139.41 | 1165.30 | LightsWired | LTG_SCH_KITCHEN | 79.77 | 168.00 | 76.30 | 0.0000 | Y | 16.69 |
Interior Lighting Total | 6.0339 | 511.15 | 3084.25 | 38.53 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 204.54 | AstronomicalClock | - | 48.75 | 48.75 | 1.87 | |
EXTERIOR_LIGHTS_B | 1305.94 | AstronomicalClock | - | 83.75 | 62.75 | 15.38 | |
Exterior Lighting Total | 1510.48 | 17.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 108500.65 | 76067.64 | 32433.01 | 0.70 | 3.57 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38319.91 | 26865.32 | 11454.59 | 0.70 | 3.99 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 105395.1 | 11.22 | 11.17 | ||||
PSZ-AC_2:2 COOLING COIL | 37223.1 | 12.34 | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 121001.80 | 0.81 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 63761.48 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.37 | 7408.86 | 1695.65 | 1.00 | 1.18 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1651.24 | 1070.05 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.95 | 0.88 | 0.30 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 48663.25 | 58395.90 | 157.08 | 3.641 | 4.369 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 23.99 | 0.00855 | 41.90 | 0.00916 | 1.331 | 0.00 |
KITCHEN | 20262.70 | 24315.24 | 174.42 | 1.286 | 1.543 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 26.00 | 25.99 | 0.00881 | 41.13 | 0.00916 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 4290.43 | 5148.51 | 13.85 | 0.189 | 1.331 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 21.59 | 0.00166 | 6.30 | 0.00607 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.37 | 4.37 | 1.33 | 1.33 | 4.3693 | 4.3693 | 4.3693 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.22 | 1.22 | 1.5431 | 1.5431 | 1.5431 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 108500.650 | 76067.636 | 4.369320 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 54250.32 | 44986.96 | 2.912880 | 29.48 | 18.18 | 0.00873202 | 11.39 | 9.72 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 45.7066 | 23.99 | 0.00854533 | 44.8664 | 48650.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 121001.797 | 121001.797 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 121001.80 | 121001.80 | 4.369321 | 16.52 | 12.30 | 0.00740590 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 30.4710 | 21.00 | 0.00799034 | 50.3524 | 4289.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38319.910 | 26865.323 | 1.543140 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 19159.96 | 16345.02 | 1.028760 | 39.11 | 21.40 | 0.00909484 | 11.91 | 9.95 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 118.2979 | 25.99 | 0.00880738 | 41.0332 | 19477.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 63761.485 | 63761.485 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 63761.48 | 63761.48 | 1.543143 | 4.97 | 4.47 | 0.00514048 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 78.8652 | 21.59 | 0.00166320 | 10.2120 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 108500.650 | 76067.636 | 4.369320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0724 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.369321 | 5.12864553 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | Sensible | 54250.32 | 44986.96 | 1.0000 | 3.41909619 | 2.912880 | 29.48 | 18.18 | 0.00873202 | 51935.2 | 11.39 | 9.72 | 0.00700000 | 29095.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54250.32 | 42.00 | 0.00915790 | 22.26 | 1.33137743 | 45.7066 | 23.99 | 0.00854533 | 23.99 | 0.00854533 | 44.8664 | 48650.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 121001.797 | 121001.797 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.369321 | 5.12864553 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 121001.80 | 121001.80 | 1.0000 | 5.12864553 | 4.369321 | 16.52 | 12.30 | 0.00740590 | 35349.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 121001.80 | 6.30 | 0.00607234 | 6.30 | 1.33137743 | 30.4710 | 21.00 | 0.00799034 | 21.00 | 0.00799034 | 50.3524 | 4289.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38319.910 | 26865.323 | 1.543140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7468 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.543143 | 1.81131842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | Sensible | 19159.96 | 16345.02 | 1.0000 | 1.20754353 | 1.028760 | 39.11 | 21.40 | 0.00909484 | 62707.7 | 11.91 | 9.95 | 0.00700000 | 29626.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19159.96 | 42.00 | 0.00915790 | 22.26 | 1.21700195 | 118.2979 | 25.95 | 0.00880738 | 25.99 | 0.00880738 | 41.0332 | 19477.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 63761.485 | 63761.485 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.543143 | 1.81131842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 63761.48 | 63761.48 | 1.0000 | 1.81131842 | 1.543143 | 4.97 | 4.47 | 0.00514048 | 17896.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63761.48 | 6.30 | 0.00607234 | 6.30 | 1.21700195 | 78.8652 | 0.00 | 0.00166320 | 21.59 | 0.00166320 | 10.2120 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 5719.67 | 3565.50 | 2534.00 |
KITCHEN | 6690.50 | 6323.00 | 5916.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6702.33 | 6930.67 | 5928.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 41.00 | 0.00 | 1.00 |
KITCHEN | 0.00 | 1866.33 | 0.00 | 1595.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1892.83 | 0.00 | 1595.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.365 | 0.875 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.828 | 0.004 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 3.990 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.189 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35526387.16 | 0.00 | 35526387.16 | 6917182.20 | 42443569.36 | 41986318.57 | 1399.00 | 7361.00 | 0.00 | 304.29 |
KITCHEN | 30295313.92 | 0.00 | 30295313.92 | 17525.72 | 30312839.63 | 38379373.44 | 5552.31 | 3135.04 | 72.64 | 830.94 |
Total Facility | 65821701.07 | 0.00 | 65821701.07 | 6934707.92 | 72756409.00 | 80365692.01 | 5595.59 | 7363.23 | 72.64 | 891.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3316 | 0.0000 | 1.3316 | 0.2670 | 1.5986 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1132 | 0.0000 | 1.1132 | 0.0005 | 1.1136 | 1.2170 | 4083.91 | 3103.09 | 0.00 |
Total Facility | 2.4448 | 0.0000 | 2.4448 | 0.2675 | 2.7123 | 2.5484 | 4083.91 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48944586.34 | 0.00 | 48944586.34 | 41986318.57 | 1379.41 | 2.26 | 7378.32 | 304.29 |
PSZ-AC_2:2 | 41738645.72 | 0.00 | 41738645.72 | 38379373.44 | 1347.41 | 2.06 | 7410.53 | 830.94 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8345 | 0.0000 | 1.8345 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.5336 | 0.0000 | 1.5336 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 131.81 | 0.00 | 7359.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 4348.44 | 3669.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.8345 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.6439 | 1.4283 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
Electricity:Building | 458.61 | 2350.73 | 01-JAN-01:20 | 26459.53 | 02-JAN-11:10 |
Electricity:Zone:DINING | 140.20 | 534.11 | 01-JAN-01:20 | 7569.70 | 02-JAN-17:40 |
Electricity:SpaceType:GENERAL | 451.68 | 2214.45 | 01-JAN-01:20 | 24316.43 | 02-JAN-11:10 |
InteriorLights:Electricity | 38.53 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 21.84 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 38.53 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 38.53 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 21.84 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 38.53 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 318.41 | 1816.62 | 01-JAN-01:20 | 19025.40 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 294.79 | 1650.33 | 01-JAN-01:10 | 16024.20 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 276.16 | 1059.53 | 01-JAN-01:10 | 15433.40 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 38.74 | 610.49 | 31-DEC-23:30 | 2780.19 | 17-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 107.64 | 755.32 | 20-DEC-01:10 | 5939.50 | 28-AUG-18:40 |
LowTempRefrigeration:Refrigeration:Electricity | 12.30 | 0.00 | 01-JAN-11:10 | 1028.10 | 16-MAY-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 19.51 | 519.75 | 20-DEC-06:00 | 637.09 | 13-JAN-14:10 |
ElectricityPurchased:Facility | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
ElectricityPurchased:Plant | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
Cogeneration:ElectricityPurchased | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
ElectricityNet:Plant | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
Cogeneration:ElectricityNet | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
General:Cogeneration:ElectricityNet | 1123.73 | 3856.86 | 02-JAN-01:20 | 78795.39 | 22-JUN-17:10 |
Electricity:HVAC | 540.22 | 0.00 | 01-JAN-01:10 | 54208.07 | 10-JUN-18:10 |
Fans:Electricity | 143.06 | 0.00 | 01-JAN-01:10 | 9884.22 | 22-JUN-17:10 |
General:Fans:Electricity | 143.06 | 0.00 | 01-JAN-01:10 | 9884.22 | 22-JUN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 397.16 | 0.00 | 01-JAN-00:10 | 44417.56 | 10-JUN-18:10 |
General:Cooling:Electricity | 397.16 | 0.00 | 01-JAN-00:10 | 44417.56 | 10-JUN-18:10 |
ExteriorLights:Electricity | 17.26 | 0.00 | 01-JAN-07:20 | 1510.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 17.26 | 0.00 | 01-JAN-07:20 | 1510.48 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.39 | 0.00 | 01-JAN-01:10 | 4741.37 | 20-DEC-07:20 |
Water Heater:WaterSystems:Electricity | 75.39 | 0.00 | 01-JAN-01:10 | 4741.37 | 20-DEC-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 30-MAR-14:40 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 30-MAR-14:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 679.65 | 2515.72 | 01-JAN-01:50 | 56112.91 | 03-JAN-07:10 |
NaturalGas:Building | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:HVAC | 12.93 | 0.00 | 01-JAN-01:10 | 30399.02 | 05-JAN-07:00 |
Heating:NaturalGas | 12.93 | 0.00 | 01-JAN-01:10 | 30399.02 | 05-JAN-07:00 |
General:Heating:NaturalGas | 12.93 | 0.00 | 01-JAN-01:10 | 30399.02 | 05-JAN-07:00 |
NaturalGas:Plant | 222.31 | 803.23 | 04-JAN-01:20 | 15803.98 | 17-JAN-19:20 |
WaterSystems:NaturalGas | 222.31 | 803.23 | 04-JAN-01:20 | 15803.98 | 17-JAN-19:20 |
Water Heater:WaterSystems:NaturalGas | 222.31 | 803.23 | 04-JAN-01:20 | 15803.98 | 17-JAN-19:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 28-MAR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 28-MAR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2671.27 | 3122.29 | 21-DEC-01:10 | 215569.81 | 28-AUG-18:20 |
EnergyTransfer:Building | 840.17 | 1561.14 | 21-DEC-01:10 | 57227.00 | 08-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN | 419.92 | 1561.14 | 21-DEC-01:10 | 22498.04 | 26-MAY-10:50 |
Refrigeration:EnergyTransfer | 157.60 | 2838.85 | 31-DEC-23:20 | 7834.84 | 24-FEB-04:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.80 | 1419.43 | 31-DEC-23:20 | 3917.42 | 24-FEB-04:10 |
General:Refrigeration:EnergyTransfer | 78.80 | 1419.43 | 31-DEC-23:20 | 3917.42 | 24-FEB-04:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.80 | 1419.43 | 31-DEC-23:20 | 3917.42 | 24-FEB-04:10 |
EnergyTransfer:Plant | 255.92 | 1561.14 | 21-DEC-01:10 | 16006.16 | 18-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.47 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 66.33 | 1383.30 | 20-DEC-06:00 | 2238.70 | 13-JAN-14:10 |
EnergyTransfer:Zone:DINING | 420.25 | 0.00 | 01-JAN-01:10 | 39125.14 | 07-JUN-17:10 |
Heating:EnergyTransfer | 2.96 | 0.00 | 01-JAN-00:10 | 14899.38 | 03-MAY-23:10 |
Heating:EnergyTransfer:Zone:DINING | 2.96 | 0.00 | 01-JAN-00:10 | 14899.38 | 03-MAY-23:10 |
General:Heating:EnergyTransfer | 2.96 | 0.00 | 01-JAN-00:10 | 14899.38 | 03-MAY-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.96 | 0.00 | 01-JAN-00:10 | 14899.38 | 03-MAY-23:10 |
Cooling:EnergyTransfer | 758.41 | 0.00 | 01-JAN-01:10 | 54614.07 | 08-JUN-17:40 |
Cooling:EnergyTransfer:Zone:DINING | 417.29 | 0.00 | 01-JAN-01:10 | 39125.14 | 07-JUN-17:10 |
General:Cooling:EnergyTransfer | 758.41 | 0.00 | 01-JAN-01:10 | 54614.07 | 08-JUN-17:40 |
General:Cooling:EnergyTransfer:Zone:DINING | 417.29 | 0.00 | 01-JAN-01:10 | 39125.14 | 07-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 341.13 | 0.00 | 01-JAN-01:10 | 18776.71 | 03-MAY-18:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 341.13 | 0.00 | 01-JAN-01:10 | 18776.71 | 03-MAY-18:40 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 177.12 | 0.00 | 01-JAN-01:10 | 13401.00 | 17-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 177.12 | 0.00 | 01-JAN-01:10 | 13401.00 | 17-JAN-07:30 |
WaterSystems:PlantLoopHeatingDemand | 177.12 | 0.00 | 01-JAN-01:10 | 13401.00 | 17-JAN-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 177.12 | 0.00 | 01-JAN-01:10 | 13401.00 | 17-JAN-07:30 |
EnergyTransfer:HVAC | 1575.19 | 0.00 | 01-JAN-01:10 | 157160.42 | 25-AUG-11:10 |
HeatingCoils:EnergyTransfer | 10.46 | 0.00 | 01-JAN-01:10 | 24553.59 | 05-JAN-07:00 |
CoolingCoils:EnergyTransfer | 1564.73 | 0.00 | 01-JAN-00:10 | 157160.42 | 25-AUG-11:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 177.12 | 0.00 | 01-JAN-01:10 | 13401.00 | 17-JAN-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 177.12 | 0.00 | 01-JAN-01:10 | 13401.00 | 17-JAN-07:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.960 | -417.284 | 0.000 | 0.000 | 209.313 | 21.844 | 88.765 | 42.322 | 0.000 | 38.460 | 41.842 | 0.000 | -10.081 | 0.000 | -18.140 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -341.119 | 0.000 | 0.000 | 4.640 | 16.690 | 259.402 | 0.000 | 0.000 | 0.054 | 60.398 | 0.000 | 0.000 | 0.000 | -0.066 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.659 | 31.347 | 0.000 | 0.000 | 0.000 | -48.006 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.960 | -758.403 | 0.000 | 0.000 | 213.953 | 38.535 | 348.168 | 42.322 | 0.000 | 55.173 | 133.587 | 0.000 | -10.081 | 0.000 | -66.213 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 08-APR-03:01 | 0.00 | 0.00 | 0.00 | -87793.19 | 0.00 | 0.00 | 0.00 | 80.03 | 851.41 | 0.00 | 0.00 | 0.00 | 87345.30 | 0.00 | -483.53 | 0.00 | -0.02 | 0.00 |
KITCHEN | 30-DEC-04:01 | 0.00 | 0.00 | 0.00 | -54908.02 | 0.00 | 0.00 | 0.00 | 30.01 | 2903.90 | 0.00 | 0.00 | 0.00 | 52018.03 | 0.00 | -0.00 | 0.00 | -43.92 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-APR-03:01 | 0.00 | 0.00 | 0.00 | -127367.00 | 0.00 | 0.00 | 0.00 | 110.04 | 3755.31 | 0.00 | 0.00 | 1004.98 | 122987.42 | 0.00 | -483.53 | 0.00 | -7.23 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-MAY-23:01 | 0.00 | 0.00 | 19716.16 | 0.00 | 0.00 | 0.00 | 973.89 | 273.28 | 510.84 | 969.73 | 0.00 | 128.32 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22572.23 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-MAY-23:01 | -8677.66 | 8677.66 | 19716.16 | -8677.66 | 0.00 | 0.00 | 996.37 | 416.29 | 2489.51 | 969.73 | 0.00 | 1152.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17063.39 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.3693 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.3693 | 0.3047 | 1.0000 | Not calculated | 1.3314 | 0.3047 | ||
PSZ-AC_2:2 | 1.5431 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5431 | 0.1183 | 1.0000 | Not calculated | 0.1826 | 0.1183 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.3693 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.3693 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3047 | ||
PSZ-AC_2:2 | 1.5431 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5431 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1183 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3693 | 4.3693 | 4.3693 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5431 | 1.5431 | 1.5431 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.3693 | 4.3693 | 4.3693 | 4.3693 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5431 | 1.5431 | 1.5431 | 1.5431 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3693 | 4.3693 | 4.3693 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5431 | 1.5431 | 1.5431 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.3693 | 4.3693 | 4.3693 | 4.3693 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5431 | 1.5431 | 1.5431 | 1.5431 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1595.00 |
Number of hours not met | 1595.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 12.93 | 30399.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 397.16 | 44417.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 38.53 | 2497.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 17.26 | 1510.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 394.51 | 22047.72 | 444.42 | 24831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 143.06 | 9884.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.39 | 4741.37 | 222.31 | 15803.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.30 | 1028.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.51 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 451.88 | 1123.73 |
Natural Gas | 444.42 | 679.65 |
Additional | 0.00 | 0.00 |
Total | 896.30 | 1803.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 75.39 |
Space Heating | 0.00 |
Space Cooling | 776.99 |
Fans (All) | 279.88 |
Service Water Heating | 147.49 |
Receptacle Equipment | 808.26 |
Miscellaneous (All) | 2198.42 |
Subtotal | 2198.42 |
Natural Gas [MJ/m2] | |
Space Heating | 25.29 |
Service Water Heating | 434.91 |
Miscellaneous (All) | 1329.64 |
Subtotal | 1329.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.14 |
Space Heating | 0.72 |
Space Cooling | 22.02 |
Fans (All) | 7.93 |
Service Water Heating | 16.51 |
Receptacle Equipment | 47.55 |
Miscellaneous | 3.13 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 4159. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8088.17 | 552.00 | 119.83 | 0.00 | 0.00 |
KITCHEN | 5867.00 | 2294.00 | 599.00 | 0.00 | 0.00 |
ATTIC | 4212.33 | 1110.33 | 1133.17 | 1132.17 | 1172.00 |
Min | 4212.33 | 552.00 | 119.83 | 0.00 | 0.00 |
Max | 8088.17 | 2294.00 | 1133.17 | 1132.17 | 1172.00 |
Average | 6055.83 | 1318.78 | 617.33 | 377.39 | 390.67 |
Sum | 18167.50 | 3956.33 | 1852.00 | 1132.17 | 1172.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 821979.67 | 1640.33 | 602.00 | 0.00 | 0.00 |
KITCHEN | 13758.17 | 4201.17 | 1273.67 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 821979.67 | 4201.17 | 1273.67 | 0.00 | 0.00 |
Average | 278579.28 | 1947.17 | 625.22 | 0.00 | 0.00 |
Sum | 835737.83 | 5841.50 | 1875.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 5521.00 | 3118.33 | 120.67 | 0.00 | 0.00 |
KITCHEN | 2364.83 | 6208.50 | 186.67 | 0.00 | 0.00 |
ATTIC | 3468.83 | 2269.33 | 909.33 | 502.00 | 1610.50 |
Min | 2364.83 | 2269.33 | 120.67 | 0.00 | 0.00 |
Max | 5521.00 | 6208.50 | 909.33 | 502.00 | 1610.50 |
Average | 3784.89 | 3865.39 | 405.56 | 167.33 | 536.83 |
Sum | 11354.67 | 11596.17 | 1216.67 | 502.00 | 1610.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 554743.00 | 269098.67 | 380.33 | 0.00 | 0.00 |
KITCHEN | 4892.83 | 13869.00 | 471.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 554743.00 | 269098.67 | 471.17 | 0.00 | 0.00 |
Average | 186545.28 | 94322.56 | 283.83 | 0.00 | 0.00 |
Sum | 559635.83 | 282967.67 | 851.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212916E+11 | 25448.16 | 15-JAN-04:01 | 15.53 | 13.64 | 0.139371E+11 | 13978.32 | 14-JAN-19:00 | 15.53 | 13.64 |
February | 0.221748E+11 | 39002.35 | 25-FEB-04:01 | 17.35 | 15.45 | 0.132027E+11 | 13979.12 | 04-FEB-19:30 | 17.35 | 15.45 |
March | 0.305944E+11 | 67614.06 | 14-MAR-03:01 | 20.88 | 16.42 | 0.152773E+11 | 13979.82 | 11-MAR-19:00 | 20.88 | 16.42 |
April | 0.382139E+11 | 87798.09 | 08-APR-03:01 | 24.27 | 14.18 | 0.147670E+11 | 13978.42 | 08-APR-18:00 | 31.00 | 16.17 |
May | 0.448095E+11 | 77845.54 | 06-MAY-03:01 | 30.88 | 18.02 | 0.152955E+11 | 13978.60 | 20-MAY-18:00 | 32.60 | 23.86 |
June | 0.448005E+11 | 65315.83 | 05-JUN-03:01 | 30.82 | 20.05 | 0.148856E+11 | 13978.87 | 24-JUN-18:00 | 27.40 | 25.19 |
July | 0.439627E+11 | 44370.86 | 01-JUL-03:01 | 30.57 | 24.17 | 0.152007E+11 | 15101.59 | 01-JUL-18:49 | 36.20 | 28.67 |
August | 0.427145E+11 | 44471.66 | 03-AUG-03:01 | 29.13 | 23.71 | 0.153886E+11 | 13978.83 | 19-AUG-18:49 | 26.08 | 25.54 |
September | 0.393162E+11 | 52054.59 | 29-SEP-03:01 | 24.60 | 20.85 | 0.147706E+11 | 13979.28 | 09-SEP-18:00 | 24.60 | 20.85 |
October | 0.369581E+11 | 68624.71 | 21-OCT-03:01 | 18.75 | 15.66 | 0.151697E+11 | 13979.84 | 21-OCT-18:00 | 25.60 | 17.80 |
November | 0.289864E+11 | 53086.77 | 02-NOV-03:01 | 16.68 | 13.52 | 0.144513E+11 | 13979.73 | 25-NOV-19:49 | 16.28 | 11.46 |
December | 0.234658E+11 | 23212.08 | 21-DEC-05:01 | 5.03 | 4.11 | 0.141739E+11 | 13979.32 | 16-DEC-19:00 | 5.03 | 4.11 |
Annual Sum or Average | 0.417289E+12 | 0.176520E+12 | ||||||||
Minimum of Months | 0.212916E+11 | 23212.08 | 5.03 | 4.11 | 0.132027E+11 | 13978.32 | 5.03 | 4.11 | ||
Maximum of Months | 0.448095E+11 | 87798.09 | 30.88 | 24.17 | 0.153886E+11 | 15101.59 | 36.20 | 28.67 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263030E+11 | 46843.06 | 27-JAN-04:01 | 12.12 | 10.72 | 0.999107E+10 | 6568.43 | 13-JAN-11:00 | 12.12 | 10.72 |
February | 0.237159E+11 | 49461.85 | 20-FEB-04:01 | 11.80 | 10.02 | 0.905155E+10 | 6568.43 | 13-FEB-11:00 | 11.80 | 10.02 |
March | 0.272031E+11 | 47649.70 | 01-MAR-04:01 | 13.33 | 10.54 | 0.100470E+11 | 6568.43 | 22-MAR-10:39 | 21.83 | 15.27 |
April | 0.283881E+11 | 41737.48 | 10-APR-03:01 | 18.93 | 13.53 | 0.972264E+10 | 6569.07 | 17-APR-10:00 | 34.50 | 22.99 |
May | 0.310413E+11 | 33647.89 | 28-MAY-03:01 | 27.47 | 16.79 | 0.100593E+11 | 6613.24 | 22-MAY-10:50 | 27.47 | 16.79 |
June | 0.301286E+11 | 28642.50 | 02-JUN-03:01 | 28.05 | 20.58 | 0.977281E+10 | 6651.99 | 28-JUN-10:00 | 32.50 | 28.26 |
July | 0.303672E+11 | 21137.94 | 11-JUL-03:01 | 26.53 | 23.31 | 0.101223E+11 | 6659.60 | 17-JUL-10:00 | 34.60 | 27.95 |
August | 0.303391E+11 | 22493.11 | 03-AUG-03:21 | 29.00 | 23.64 | 0.101351E+11 | 6673.88 | 25-AUG-10:50 | 32.72 | 28.77 |
September | 0.298461E+11 | 27956.93 | 29-SEP-03:01 | 24.60 | 20.85 | 0.975474E+10 | 6637.22 | 12-SEP-10:00 | 24.60 | 20.85 |
October | 0.299827E+11 | 42205.65 | 24-OCT-03:11 | 18.53 | 14.37 | 0.100440E+11 | 6570.90 | 04-OCT-10:00 | 18.53 | 14.37 |
November | 0.269404E+11 | 49156.75 | 24-NOV-04:01 | 11.00 | 9.68 | 0.971070E+10 | 6568.43 | 28-NOV-11:39 | 20.30 | 14.63 |
December | 0.268702E+11 | 55002.06 | 30-DEC-04:01 | 11.15 | 7.23 | 0.100029E+11 | 6568.45 | 29-DEC-11:50 | 11.15 | 7.23 |
Annual Sum or Average | 0.341126E+12 | 0.118414E+12 | ||||||||
Minimum of Months | 0.237159E+11 | 21137.94 | 11.00 | 7.23 | 0.905155E+10 | 6568.43 | 11.15 | 7.23 | ||
Maximum of Months | 0.310413E+11 | 55002.06 | 29.00 | 23.64 | 0.101351E+11 | 6673.88 | 34.60 | 28.77 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 | 7.85 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 | 12.96 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 | 16.77 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 30.53 | 18.24 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 | 22.58 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 | 24.65 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 | 21.85 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 | 9.11 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3347267.06 | 8015.96 | 05-JAN-05:03 | 5.75 |
February | 1178866.13 | 5990.57 | 05-FEB-05:04 | 7.50 |
March | 2326513.07 | 2648.89 | 11-MAR-00:03 | 24.75 |
April | 0.269071E+09 | 14623.00 | 27-APR-23:01 | 32.73 |
May | 0.613241E+09 | 19716.18 | 03-MAY-23:01 | 35.95 |
June | 0.721848E+09 | 19429.58 | 13-JUN-23:01 | 35.63 |
July | 0.625037E+09 | 18931.86 | 02-JUL-23:01 | 35.28 |
August | 0.441990E+09 | 13961.65 | 08-AUG-23:01 | 32.07 |
September | 0.253868E+09 | 10854.72 | 17-SEP-23:01 | 30.23 |
October | 26050795.80 | 9532.09 | 22-OCT-23:02 | 29.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 1177442.32 | 6408.60 | 24-DEC-05:03 | 6.52 |
Annual Sum or Average | 0.295914E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.75 | |
Maximum of Months | 0.721848E+09 | 19716.18 | 35.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.194316E+10 | 1639.63 | 02-JAN-17:40 | 0.100519E+11 | 6614.32 | 01-JAN-11:09 |
February | 0.172668E+10 | 1639.63 | 01-FEB-17:00 | 0.907918E+10 | 6614.32 | 01-FEB-11:09 |
March | 0.185605E+10 | 1639.63 | 01-MAR-18:19 | 0.100520E+11 | 6614.32 | 01-MAR-11:09 |
April | 0.172344E+10 | 1639.63 | 01-APR-18:40 | 0.972770E+10 | 6614.32 | 01-APR-10:09 |
May | 0.177222E+10 | 1639.63 | 01-MAY-18:00 | 0.100520E+11 | 6614.32 | 01-MAY-10:09 |
June | 0.172453E+10 | 1639.63 | 01-JUN-19:10 | 0.972773E+10 | 6614.32 | 01-JUN-10:09 |
July | 0.177366E+10 | 1639.63 | 01-JUL-19:19 | 0.100519E+11 | 6614.32 | 01-JUL-10:09 |
August | 0.183868E+10 | 1639.63 | 01-AUG-19:10 | 0.100520E+11 | 6614.32 | 01-AUG-10:09 |
September | 0.178338E+10 | 1639.63 | 01-SEP-18:49 | 0.972770E+10 | 6614.32 | 01-SEP-10:09 |
October | 0.187813E+10 | 1639.63 | 02-OCT-18:10 | 0.100519E+11 | 6614.32 | 01-OCT-10:09 |
November | 0.187373E+10 | 1639.63 | 01-NOV-17:40 | 0.972767E+10 | 6614.32 | 01-NOV-10:09 |
December | 0.195059E+10 | 1639.63 | 01-DEC-17:19 | 0.100519E+11 | 6614.32 | 01-DEC-11:09 |
Annual Sum or Average | 0.218442E+11 | 0.118354E+12 | ||||
Minimum of Months | 0.172344E+10 | 1639.63 | 0.907918E+10 | 6614.32 | ||
Maximum of Months | 0.195059E+10 | 1639.63 | 0.100520E+11 | 6614.32 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140982E+10 | 858.09 | 02-JAN-10:09 | 0.250369E+11 | 16024.20 | 01-JAN-11:09 |
February | 0.127710E+10 | 858.09 | 01-FEB-10:09 | 0.226140E+11 | 16024.20 | 01-FEB-11:09 |
March | 0.143409E+10 | 858.09 | 01-MAR-10:09 | 0.250371E+11 | 16024.20 | 01-MAR-11:09 |
April | 0.136995E+10 | 858.09 | 01-APR-16:10 | 0.242293E+11 | 16024.20 | 01-APR-10:09 |
May | 0.142196E+10 | 858.09 | 01-MAY-09:09 | 0.250370E+11 | 16024.20 | 01-MAY-10:09 |
June | 0.138598E+10 | 858.09 | 01-JUN-09:09 | 0.242294E+11 | 16024.20 | 01-JUN-10:09 |
July | 0.140610E+10 | 858.09 | 01-JUL-16:10 | 0.250369E+11 | 16024.20 | 01-JUL-10:09 |
August | 0.143409E+10 | 858.09 | 01-AUG-09:09 | 0.250371E+11 | 16024.20 | 01-AUG-10:09 |
September | 0.137029E+10 | 858.09 | 01-SEP-09:09 | 0.242293E+11 | 16024.20 | 01-SEP-10:09 |
October | 0.140965E+10 | 858.09 | 02-OCT-09:09 | 0.250369E+11 | 16024.20 | 01-OCT-10:09 |
November | 0.136509E+10 | 858.09 | 01-NOV-09:09 | 0.242292E+11 | 16024.20 | 01-NOV-10:09 |
December | 0.140627E+10 | 858.09 | 01-DEC-10:09 | 0.250369E+11 | 16024.20 | 01-DEC-11:09 |
Annual Sum or Average | 0.166904E+11 | 0.294790E+12 | ||||
Minimum of Months | 0.127710E+10 | 858.09 | 0.226140E+11 | 16024.20 | ||
Maximum of Months | 0.143409E+10 | 858.09 | 0.250371E+11 | 16024.20 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.194316E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581262E+10 |
February | 0.272721E+11 | 0.172668E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84685941.57 | 0.320274E+10 |
March | 0.305458E+11 | 0.185605E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132156E+10 | 0.117680E+10 |
April | 0.292871E+11 | 0.172344E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483969E+10 | 96193464.96 |
May | 0.303219E+11 | 0.177222E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733860E+10 | 1787895.98 |
June | 0.295292E+11 | 0.172453E+10 | 0.972773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729774E+10 | 424679.74 |
July | 0.300798E+11 | 0.177366E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576171E+10 | 188580.46 |
August | 0.305458E+11 | 0.183868E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476860E+10 | 238242.62 |
September | 0.292871E+11 | 0.178338E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392430E+10 | 788179.20 |
October | 0.300980E+11 | 0.187813E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249265E+10 | 0.476048E+09 |
November | 0.290996E+11 | 0.187373E+10 | 0.972767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627610E+09 | 0.220461E+10 |
December | 0.300798E+11 | 0.195059E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2829582.29 | 0.516779E+10 |
Annual Sum or Average | 0.356244E+12 | 0.218442E+11 | 0.118354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384600E+11 | 0.181402E+11 |
Minimum of Months | 0.272721E+11 | 0.172344E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188580.46 |
Maximum of Months | 0.305458E+11 | 0.195059E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733860E+10 | 0.581262E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.140982E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13435670.31 |
February | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 9820.62 | 15216277.90 |
March | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 1437219.81 | 12849117.83 |
April | 0.786997E+09 | 0.136995E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 7793240.93 | 1455873.97 |
May | 0.814802E+09 | 0.142196E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 15076549.54 | 1454906.44 |
June | 0.793501E+09 | 0.138598E+10 | 0.196898E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 10020945.61 | 670967.94 |
July | 0.808298E+09 | 0.140610E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 8950610.67 | 1175922.88 |
August | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 4603766.43 | 1129904.82 |
September | 0.786997E+09 | 0.137029E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 3711394.74 | 1228338.46 |
October | 0.808786E+09 | 0.140965E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 2142828.59 | 1249769.75 |
November | 0.781956E+09 | 0.136509E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 301399.53 | 3657688.44 |
December | 0.808298E+09 | 0.140627E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12510220.45 |
Annual Sum or Average | 0.957291E+10 | 0.166904E+11 | 0.239558E+12 | 0.133326E+12 | 0.00 | 0.00 | 0.00 | 54047776.47 | 66034659.18 |
Minimum of Months | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 670967.94 |
Maximum of Months | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 15076549.54 | 15216277.90 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169482E+10 | 0.298426E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126969E+10 | 0.316791E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132258E+10 | 0.451816E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154706E+10 | 0.513553E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129872E+10 | 0.521307E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126294E+10 | 0.515884E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763068E+09 | 0.400483E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771956E+09 | 0.381596E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115704E+10 | 0.332896E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178278E+10 | 0.416752E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189903E+10 | 0.346096E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188965E+10 | 0.305048E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166593E+11 | 0.480065E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763068E+09 | 0.298426E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189903E+10 | 0.521307E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 1639.63 | 02-JAN-17:40 | 6614.32 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7605.32 | 21-JAN-19:55 |
February | 30255.31 | 04-FEB-19:10 | 1639.63 | 01-FEB-17:00 | 6614.32 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1572.15 | 22-FEB-14:00 | 6423.18 | 04-FEB-19:53 |
March | 30255.31 | 04-MAR-19:10 | 1639.63 | 01-MAR-18:19 | 6614.32 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6037.27 | 28-MAR-17:08 | 3397.91 | 01-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 1639.63 | 01-APR-18:40 | 6614.32 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8396.77 | 28-APR-17:02 | 1803.79 | 11-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 1639.63 | 01-MAY-18:00 | 6614.32 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10311.42 | 03-MAY-17:02 | 360.04 | 13-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 1639.63 | 01-JUN-19:10 | 6614.32 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10876.59 | 07-JUN-17:03 | 79.59 | 27-JUN-11:00 |
July | 30255.31 | 01-JUL-18:10 | 1639.63 | 01-JUL-19:19 | 6614.32 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8575.46 | 03-JUL-17:03 | 16.61 | 19-JUL-03:00 |
August | 30255.31 | 05-AUG-18:10 | 1639.63 | 01-AUG-19:10 | 6614.32 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7052.06 | 07-AUG-17:03 | 15.04 | 16-AUG-00:10 |
September | 30255.31 | 02-SEP-18:10 | 1639.63 | 01-SEP-18:49 | 6614.32 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6779.12 | 17-SEP-20:00 | 98.84 | 27-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 1639.63 | 02-OCT-18:10 | 6614.32 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6634.76 | 02-OCT-12:00 | 2927.84 | 29-OCT-06:20 |
November | 30255.31 | 04-NOV-18:10 | 1639.63 | 01-NOV-17:40 | 6614.32 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3089.56 | 09-NOV-13:00 | 5448.91 | 25-NOV-19:53 |
December | 30255.31 | 02-DEC-19:10 | 1639.63 | 01-DEC-17:19 | 6614.32 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.32 | 28-DEC-14:00 | 7867.06 | 30-DEC-19:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | |||||
Maximum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10876.59 | 7867.06 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 858.09 | 02-JAN-10:09 | 12937.52 | 01-JAN-11:09 | 7449.36 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 54.97 | 15-JAN-03:00 |
February | 813.01 | 04-FEB-19:10 | 858.09 | 01-FEB-10:09 | 12937.52 | 01-FEB-11:09 | 7449.36 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.55 | 22-FEB-15:03 | 71.85 | 26-FEB-01:50 |
March | 813.01 | 04-MAR-19:10 | 858.09 | 01-MAR-10:09 | 12937.52 | 01-MAR-11:09 | 7449.36 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 10.63 | 27-MAR-15:00 | 212.13 | 25-MAR-00:10 |
April | 813.01 | 01-APR-18:10 | 858.09 | 01-APR-16:10 | 12937.52 | 01-APR-10:09 | 7449.36 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 30.34 | 15-APR-14:00 | 23.83 | 05-APR-00:10 |
May | 813.01 | 06-MAY-18:10 | 858.09 | 01-MAY-09:09 | 12937.52 | 01-MAY-10:09 | 7449.36 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 75.15 | 03-MAY-24:00 | 38.99 | 15-MAY-03:10 |
June | 813.01 | 03-JUN-18:10 | 858.09 | 01-JUN-09:09 | 12937.52 | 01-JUN-10:09 | 7449.36 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 35.25 | 30-JUN-23:02 | 38.36 | 18-JUN-01:20 |
July | 813.01 | 01-JUL-18:10 | 858.09 | 01-JUL-16:10 | 12937.52 | 01-JUL-10:09 | 7449.36 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 32.59 | 03-JUL-03:30 | 25.78 | 19-JUL-02:40 |
August | 813.01 | 05-AUG-18:10 | 858.09 | 01-AUG-09:09 | 12937.52 | 01-AUG-10:09 | 7449.36 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 19.79 | 31-AUG-03:10 | 23.71 | 16-AUG-00:40 |
September | 813.01 | 02-SEP-18:10 | 858.09 | 01-SEP-09:09 | 12937.52 | 01-SEP-10:09 | 7449.36 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 11.84 | 28-SEP-14:00 | 18.69 | 09-SEP-00:30 |
October | 813.01 | 07-OCT-18:10 | 858.09 | 02-OCT-09:09 | 12937.52 | 01-OCT-10:09 | 7449.36 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 14.17 | 03-OCT-14:53 | 39.92 | 12-OCT-03:10 |
November | 813.01 | 04-NOV-18:10 | 858.09 | 01-NOV-09:09 | 12937.52 | 01-NOV-10:09 | 7449.36 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 3.26 | 13-NOV-14:00 | 47.25 | 28-NOV-04:40 |
December | 813.01 | 02-DEC-19:10 | 858.09 | 01-DEC-10:09 | 12937.52 | 01-DEC-11:09 | 7449.36 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 93.88 | 29-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | ||||||
Maximum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 75.15 | 212.13 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1903.12 | 19-JAN-07:15 | 5778.77 | 05-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1982.87 | 19-FEB-23:00 | 6649.89 | 20-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.15 | 05-MAR-07:23 | 7549.72 | 31-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1945.60 | 11-APR-06:25 | 8306.88 | 29-APR-14:12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.62 | 22-MAY-14:00 | 7955.20 | 14-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2983.89 | 03-JUN-19:00 | 8213.60 | 08-JUN-13:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1569.90 | 04-JUL-05:40 | 7675.76 | 10-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.71 | 06-AUG-22:00 | 6394.39 | 05-AUG-13:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1751.05 | 30-SEP-06:45 | 6329.16 | 15-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2056.22 | 02-OCT-06:45 | 7113.32 | 09-OCT-13:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1913.90 | 22-NOV-07:13 | 6101.11 | 04-NOV-13:20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2259.13 | 03-DEC-07:23 | 5714.09 | 02-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.71 | 5714.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2983.89 | 8306.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25448.16 | 15-JAN-04:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 |
February | 39002.35 | 25-FEB-04:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
March | 67614.06 | 14-MAR-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 |
April | 87798.09 | 08-APR-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
May | 77845.54 | 06-MAY-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 0.00 |
June | 65315.83 | 05-JUN-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44370.86 | 01-JUL-03:01 | 0.00 | 720.26 | 10216.89 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 | 0.00 |
August | 44471.66 | 03-AUG-03:01 | 0.00 | 720.26 | 10216.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 0.00 |
September | 52054.59 | 29-SEP-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 68624.71 | 21-OCT-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53086.77 | 02-NOV-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
December | 23212.08 | 21-DEC-05:01 | 16808.50 | 800.29 | 27369.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23212.08 | 0.00 | 720.26 | 10216.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87798.09 | 16808.50 | 800.29 | 27369.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 | 49.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 46843.06 | 27-JAN-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 |
February | 49461.85 | 20-FEB-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 |
March | 47649.70 | 01-MAR-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 |
April | 41737.48 | 10-APR-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 |
May | 33647.89 | 28-MAY-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
June | 28642.50 | 02-JUN-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 |
July | 21137.94 | 11-JUL-03:01 | 0.00 | 270.10 | 24388.73 | 11559.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
August | 22493.11 | 03-AUG-03:21 | 0.00 | 210.08 | 18969.01 | 8990.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
September | 27956.93 | 29-SEP-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
October | 42205.65 | 24-OCT-03:11 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
November | 49156.75 | 24-NOV-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55002.06 | 30-DEC-04:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 43.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21137.94 | 0.00 | 210.08 | 18969.01 | 8990.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55002.06 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 43.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1510.81 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1499.34 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1391.21 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1607.97 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.65 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.31 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.03 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.92 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.94 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1543.24 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1444.10 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.65 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.624715E+11 | 41368.54 | 26-JAN-11:00 | 0.677206E+11 | 56112.91 | 03-JAN-07:10 |
February | 0.613998E+11 | 45457.95 | 22-FEB-11:00 | 0.558635E+11 | 45271.11 | 02-FEB-07:10 |
March | 0.787078E+11 | 54141.38 | 10-MAR-18:40 | 0.588054E+11 | 39082.29 | 05-MAR-11:20 |
April | 0.920315E+11 | 64717.67 | 26-APR-17:19 | 0.549823E+11 | 38851.55 | 01-APR-10:50 |
May | 0.113552E+12 | 74541.92 | 17-MAY-17:19 | 0.549580E+11 | 38512.73 | 06-MAY-10:50 |
June | 0.120728E+12 | 78795.39 | 22-JUN-17:10 | 0.518126E+11 | 38289.43 | 04-JUN-10:20 |
July | 0.129180E+12 | 77512.32 | 01-JUL-17:10 | 0.527939E+11 | 38153.65 | 01-JUL-10:30 |
August | 0.127118E+12 | 76549.66 | 25-AUG-11:00 | 0.533697E+11 | 38229.45 | 27-AUG-10:30 |
September | 0.112546E+12 | 74117.37 | 14-SEP-17:19 | 0.528609E+11 | 38502.62 | 30-SEP-10:30 |
October | 0.899241E+11 | 63381.87 | 04-OCT-11:00 | 0.564287E+11 | 38784.51 | 29-OCT-10:09 |
November | 0.718355E+11 | 50761.15 | 09-NOV-11:00 | 0.566756E+11 | 39032.15 | 26-NOV-11:30 |
December | 0.642348E+11 | 42975.16 | 16-DEC-11:00 | 0.633788E+11 | 51700.54 | 23-DEC-06:19 |
Annual Sum or Average | 0.112373E+13 | 0.679650E+12 | ||||
Minimum of Months | 0.613998E+11 | 41368.54 | 0.518126E+11 | 38153.65 | ||
Maximum of Months | 0.129180E+12 | 78795.39 | 0.677206E+11 | 56112.91 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.335298E+10 | 0.173067E+10 | 0.350888E+11 | 0.00 | 0.102189E+11 | 37879553.69 | 0.00 | 0.252010E+10 | 0.00 | 0.00 | 0.00 | 0.638646E+10 | 0.00 |
February | 0.300378E+10 | 0.147680E+10 | 0.316932E+11 | 0.00 | 0.910527E+10 | 34213790.43 | 0.00 | 0.741478E+10 | 0.00 | 0.00 | 0.00 | 0.577707E+10 | 0.00 |
March | 0.329014E+10 | 0.149504E+10 | 0.350891E+11 | 0.00 | 0.102220E+11 | 37879553.69 | 0.00 | 0.188535E+11 | 0.00 | 0.00 | 0.00 | 0.644900E+10 | 0.00 |
April | 0.309339E+10 | 0.130981E+10 | 0.339570E+11 | 0.00 | 0.106811E+11 | 36657632.61 | 0.00 | 0.335820E+11 | 0.00 | 0.00 | 0.00 | 0.619295E+10 | 0.00 |
May | 0.319417E+10 | 0.123312E+10 | 0.350889E+11 | 0.00 | 0.129196E+11 | 37879553.69 | 0.00 | 0.513480E+11 | 0.00 | 0.00 | 0.00 | 0.641401E+10 | 0.00 |
June | 0.311050E+10 | 0.112856E+10 | 0.339571E+11 | 0.00 | 0.142340E+11 | 36657632.61 | 0.00 | 0.587694E+11 | 0.00 | 0.00 | 0.00 | 0.623357E+10 | 0.00 |
July | 0.317976E+10 | 0.120140E+10 | 0.350888E+11 | 0.00 | 0.158940E+11 | 37879553.69 | 0.00 | 0.640171E+11 | 0.00 | 0.00 | 0.00 | 0.636714E+10 | 0.00 |
August | 0.327277E+10 | 0.129837E+10 | 0.350891E+11 | 0.00 | 0.157543E+11 | 37879553.69 | 0.00 | 0.618158E+11 | 0.00 | 0.00 | 0.00 | 0.644496E+10 | 0.00 |
September | 0.315367E+10 | 0.138775E+10 | 0.339570E+11 | 0.00 | 0.133664E+11 | 36657632.61 | 0.00 | 0.511918E+11 | 0.00 | 0.00 | 0.00 | 0.619255E+10 | 0.00 |
October | 0.328778E+10 | 0.157660E+10 | 0.350888E+11 | 0.00 | 0.107720E+11 | 37879553.69 | 0.00 | 0.294658E+11 | 0.00 | 0.00 | 0.00 | 0.637816E+10 | 0.00 |
November | 0.323882E+10 | 0.164423E+10 | 0.339569E+11 | 0.00 | 0.977671E+10 | 36657632.61 | 0.00 | 0.138641E+11 | 0.00 | 0.00 | 0.00 | 0.617575E+10 | 0.00 |
December | 0.335686E+10 | 0.177327E+10 | 0.350888E+11 | 0.00 | 0.101198E+11 | 37879553.69 | 0.00 | 0.431727E+10 | 0.00 | 0.00 | 0.00 | 0.637703E+10 | 0.00 |
Annual Sum or Average | 0.385346E+11 | 0.172556E+11 | 0.413144E+12 | 0.00 | 0.143064E+12 | 0.446001E+09 | 0.00 | 0.397160E+12 | 0.00 | 0.00 | 0.00 | 0.753887E+11 | 0.00 |
Minimum of Months | 0.300378E+10 | 0.112856E+10 | 0.316932E+11 | 0.00 | 0.910527E+10 | 34213790.43 | 0.00 | 0.252010E+10 | 0.00 | 0.00 | 0.00 | 0.577707E+10 | 0.00 |
Maximum of Months | 0.335686E+10 | 0.177327E+10 | 0.350891E+11 | 0.00 | 0.158940E+11 | 37879553.69 | 0.00 | 0.640171E+11 | 0.00 | 0.00 | 0.00 | 0.644900E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.377451E+11 | 0.00 | 0.736410E+10 | 0.00 | 0.226114E+11 | 0.00 | 0.00 |
February | 0.340924E+11 | 0.00 | 0.171613E+10 | 0.00 | 0.200550E+11 | 0.00 | 0.00 |
March | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.210603E+11 | 0.00 | 0.00 |
April | 0.365275E+11 | 0.00 | 0.00 | 0.00 | 0.184547E+11 | 0.00 | 0.00 |
May | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.172129E+11 | 0.00 | 0.00 |
June | 0.365275E+11 | 0.00 | 0.00 | 0.00 | 0.152851E+11 | 0.00 | 0.00 |
July | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.150488E+11 | 0.00 | 0.00 |
August | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.156245E+11 | 0.00 | 0.00 |
September | 0.365275E+11 | 0.00 | 0.00 | 0.00 | 0.163333E+11 | 0.00 | 0.00 |
October | 0.377451E+11 | 0.00 | 0.00 | 0.00 | 0.186835E+11 | 0.00 | 0.00 |
November | 0.365275E+11 | 0.00 | 0.220121E+09 | 0.00 | 0.199279E+11 | 0.00 | 0.00 |
December | 0.377451E+11 | 0.00 | 0.362547E+10 | 0.00 | 0.220082E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.444418E+12 | 0.00 | 0.129258E+11 | 0.00 | 0.222306E+12 | 0.00 | 0.00 |
Minimum of Months | 0.340924E+11 | 0.00 | 0.00 | 0.00 | 0.150488E+11 | 0.00 | 0.00 |
Maximum of Months | 0.377451E+11 | 0.00 | 0.736410E+10 | 0.00 | 0.226114E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2497.72 | 02-JAN-17:40 | 1510.48 | 01-JAN-06:10 | 22638.52 | 01-JAN-11:09 | 0.00 | 5235.63 | 03-JAN-06:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2497.72 | 01-FEB-17:00 | 1510.48 | 01-FEB-06:10 | 22638.52 | 01-FEB-11:09 | 0.00 | 5020.69 | 02-FEB-06:00 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 2497.72 | 01-MAR-18:19 | 1510.48 | 01-MAR-06:10 | 22638.52 | 01-MAR-11:09 | 0.00 | 5144.16 | 28-MAR-17:10 | 17.86 | 30-MAR-14:39 | 0.00 | 01-MAR-00:10 |
April | 2497.72 | 01-APR-18:40 | 1510.48 | 01-APR-05:10 | 22638.52 | 01-APR-10:09 | 0.00 | 7007.41 | 26-APR-17:19 | 17.86 | 22-APR-14:09 | 0.00 | 01-APR-00:10 |
May | 2497.72 | 01-MAY-18:00 | 1510.48 | 01-MAY-05:10 | 22638.52 | 01-MAY-10:09 | 0.00 | 8828.62 | 17-MAY-17:10 | 17.86 | 07-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 2497.72 | 01-JUN-19:10 | 1510.48 | 01-JUN-05:10 | 22638.52 | 01-JUN-10:09 | 0.00 | 9884.22 | 22-JUN-17:10 | 17.86 | 02-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 2497.72 | 01-JUL-19:19 | 1510.48 | 01-JUL-05:10 | 22638.52 | 01-JUL-10:09 | 0.00 | 9884.22 | 01-JUL-17:10 | 17.86 | 01-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 2497.72 | 01-AUG-19:10 | 1510.48 | 01-AUG-05:10 | 22638.52 | 01-AUG-10:09 | 0.00 | 9884.22 | 25-AUG-11:09 | 17.86 | 08-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 2497.72 | 01-SEP-18:49 | 1510.48 | 01-SEP-05:10 | 22638.52 | 01-SEP-10:09 | 0.00 | 9639.04 | 14-SEP-17:10 | 17.86 | 08-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 2497.72 | 02-OCT-18:10 | 1510.48 | 01-OCT-05:10 | 22638.52 | 01-OCT-10:09 | 0.00 | 6969.71 | 04-OCT-11:00 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 2497.72 | 01-NOV-17:40 | 1510.48 | 01-NOV-05:10 | 22638.52 | 01-NOV-10:09 | 0.00 | 4757.95 | 09-NOV-11:00 | 17.86 | 26-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 2497.72 | 01-DEC-17:19 | 1510.48 | 01-DEC-06:10 | 22638.52 | 01-DEC-11:09 | 0.00 | 5219.08 | 23-DEC-06:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 4757.95 | 17.86 | 0.00 | ||||||
Maximum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 9884.22 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 9512.54 | 12-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4741.21 | 03-JAN-07:49 | 0.00 |
February | 13825.40 | 24-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.19 | 02-FEB-07:40 | 0.00 |
March | 22697.56 | 28-MAR-17:10 | 0.00 | 0.00 | 0.00 | 4737.88 | 03-MAR-07:19 | 0.00 |
April | 31566.08 | 26-APR-17:19 | 0.00 | 0.00 | 0.00 | 4736.82 | 03-APR-18:00 | 0.00 |
May | 39751.11 | 17-MAY-17:10 | 0.00 | 0.00 | 0.00 | 4736.72 | 03-MAY-18:10 | 0.00 |
June | 44417.56 | 10-JUN-18:10 | 0.00 | 0.00 | 0.00 | 4736.52 | 01-JUN-18:00 | 0.00 |
July | 41649.70 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.64 | 07-JUL-06:00 | 0.00 |
August | 40075.11 | 28-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.10 | 22-AUG-06:00 | 0.00 |
September | 39250.70 | 17-SEP-19:00 | 0.00 | 0.00 | 0.00 | 4736.61 | 27-SEP-18:30 | 0.00 |
October | 29407.35 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4737.30 | 30-OCT-06:19 | 0.00 |
November | 17861.83 | 09-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4739.30 | 27-NOV-07:19 | 0.00 |
December | 11334.82 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4741.37 | 20-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9512.54 | 0.00 | 0.00 | 0.00 | 4736.10 | 0.00 | ||
Maximum of Months | 44417.56 | 0.00 | 0.00 | 0.00 | 4741.37 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 41368.54 | 26-JAN-11:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 4448.17 | 17.86 | 0.00 | 7370.92 | 0.00 |
February | 45457.95 | 22-FEB-11:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 4448.17 | 17.86 | 0.00 | 11437.66 | 0.00 |
March | 54141.38 | 10-MAR-18:40 | 2497.72 | 18837.19 | 1510.48 | 0.00 | 4992.05 | 17.86 | 0.00 | 20834.41 | 0.00 |
April | 64717.67 | 26-APR-17:19 | 1677.91 | 18837.19 | 0.00 | 0.00 | 7007.41 | 17.86 | 0.00 | 31566.08 | 0.00 |
May | 74541.92 | 17-MAY-17:19 | 1677.91 | 18837.19 | 0.00 | 0.00 | 8818.96 | 17.86 | 0.00 | 39596.22 | 0.00 |
June | 78795.39 | 22-JUN-17:10 | 1677.91 | 18837.19 | 0.00 | 0.00 | 9884.22 | 17.86 | 0.00 | 42963.40 | 0.00 |
July | 77512.32 | 01-JUL-17:10 | 1677.91 | 18837.19 | 0.00 | 0.00 | 9884.22 | 17.86 | 0.00 | 41649.70 | 0.00 |
August | 76549.66 | 25-AUG-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 9884.22 | 17.86 | 0.00 | 39602.87 | 0.00 |
September | 74117.37 | 14-SEP-17:19 | 1677.91 | 18837.19 | 0.00 | 0.00 | 9621.54 | 17.86 | 0.00 | 38404.63 | 0.00 |
October | 63381.87 | 04-OCT-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 6969.71 | 17.86 | 0.00 | 29407.35 | 0.00 |
November | 50761.15 | 09-NOV-11:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 4757.95 | 17.86 | 0.00 | 16437.67 | 0.00 |
December | 42975.16 | 16-DEC-11:00 | 1491.48 | 22638.52 | 0.00 | 0.00 | 4448.17 | 17.86 | 0.00 | 8605.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 41368.54 | 1491.48 | 18837.19 | 0.00 | 0.00 | 4448.17 | 17.86 | 0.00 | 7370.92 | 0.00 | |
Maximum of Months | 78795.39 | 2497.72 | 22638.52 | 1510.48 | 0.00 | 9884.22 | 17.86 | 0.00 | 42963.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 24831.19 | 01-JAN-11:09 | 0.00 | 30399.02 | 05-JAN-06:00 | 0.00 | 15803.98 | 17-JAN-19:19 | 0.00 |
February | 24831.19 | 01-FEB-11:09 | 0.00 | 20576.74 | 02-FEB-06:00 | 0.00 | 15447.10 | 01-FEB-19:19 | 0.00 |
March | 24831.19 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 14893.29 | 01-MAR-07:49 | 0.00 |
April | 24831.19 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 14532.21 | 03-APR-18:00 | 0.00 |
May | 24831.19 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 14181.61 | 01-MAY-18:40 | 0.00 |
June | 24831.19 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 13854.00 | 01-JUN-18:40 | 0.00 |
July | 24831.19 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 13656.05 | 03-JUL-18:30 | 0.00 |
August | 24831.19 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 13807.58 | 31-AUG-18:40 | 0.00 |
September | 24831.19 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 14090.59 | 29-SEP-18:00 | 0.00 |
October | 24831.19 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 14494.11 | 31-OCT-18:19 | 0.00 |
November | 24831.19 | 01-NOV-10:09 | 0.00 | 8620.79 | 27-NOV-06:49 | 0.00 | 14838.51 | 30-NOV-07:00 | 0.00 |
December | 24831.19 | 01-DEC-11:09 | 0.00 | 29435.86 | 23-DEC-06:10 | 0.00 | 15053.25 | 28-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 24831.19 | 0.00 | 0.00 | 0.00 | 13656.05 | 0.00 | |||
Maximum of Months | 24831.19 | 0.00 | 30399.02 | 0.00 | 15803.98 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.69 | 0.00 | 24.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.85 | 0.00 | 24.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.12 | 0.00 | 25.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.22 | 0.00 | 25.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.11 | 1.00 | 25.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 25.11 | 0.00 | 25.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.13 | 0.00 | 25.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.82 | 0.00 | 24.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.56 | 0.00 | 24.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 41.00 | 25.05 | 1.00 | 25.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.22 | 1.00 | 25.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.50 | 0.00 | 27.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.10 | 0.00 | 28.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 29.48 | 0.00 | 29.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 30.21 | 0.00 | 30.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 142.67 | 27.83 | 116.00 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 323.17 | 28.28 | 289.33 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 524.83 | 28.37 | 476.83 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 504.17 | 28.59 | 458.00 | 28.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 287.33 | 27.87 | 254.83 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.39 | 0.00 | 30.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 29.14 | 0.00 | 29.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.71 | 0.00 | 27.71 |
Annual Sum or Average | 0.00 | 0.00 | 1866.33 | 28.35 | 1595.00 | 28.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.50 | 0.00 | 27.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 524.83 | 30.39 | 476.83 | 30.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 362.67 | 21.46 | 98.67 | 21.89 | 10.67 | 21.83 |
February | 204.67 | 21.74 | 270.50 | 23.01 | 4.17 | 23.02 |
March | 64.67 | 22.68 | 507.17 | 23.87 | 6.17 | 23.87 |
April | 25.50 | 25.88 | 580.00 | 24.22 | 25.17 | 24.29 |
May | 221.00 | 24.56 | 611.00 | 24.31 | 221.00 | 24.36 |
June | 401.50 | 24.35 | 592.00 | 24.28 | 401.50 | 24.30 |
July | 594.83 | 24.23 | 609.00 | 24.23 | 594.83 | 24.23 |
August | 612.00 | 24.20 | 612.00 | 24.20 | 612.00 | 24.20 |
September | 535.83 | 24.18 | 590.00 | 24.17 | 535.83 | 24.17 |
October | 119.33 | 24.20 | 600.67 | 24.08 | 116.17 | 24.10 |
November | 109.67 | 22.10 | 436.33 | 23.60 | 0.67 | 23.60 |
December | 313.83 | 21.60 | 212.33 | 22.52 | 5.83 | 22.51 |
Annual Sum or Average | 3565.50 | 23.51 | 5719.67 | 23.88 | 2534.00 | 23.96 |
Minimum of Months | 25.50 | 21.46 | 98.67 | 21.89 | 0.67 | 21.83 |
Maximum of Months | 612.00 | 25.88 | 612.00 | 24.31 | 612.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.83 | 23.12 | 406.33 | 24.19 | 198.33 | 24.53 |
February | 390.17 | 25.05 | 460.00 | 25.26 | 323.33 | 25.45 |
March | 505.00 | 25.99 | 610.33 | 25.87 | 505.00 | 25.91 |
April | 579.00 | 26.00 | 590.00 | 26.00 | 579.00 | 26.00 |
May | 611.00 | 26.26 | 611.00 | 26.26 | 611.00 | 26.26 |
June | 592.00 | 27.03 | 592.00 | 27.03 | 592.00 | 27.03 |
July | 609.00 | 27.79 | 609.00 | 27.79 | 609.00 | 27.79 |
August | 612.00 | 27.87 | 612.00 | 27.87 | 612.00 | 27.87 |
September | 590.00 | 26.72 | 590.00 | 26.72 | 590.00 | 26.72 |
October | 595.50 | 25.99 | 610.00 | 25.98 | 595.50 | 25.98 |
November | 443.33 | 25.83 | 568.50 | 25.67 | 429.50 | 25.76 |
December | 417.17 | 24.15 | 431.33 | 24.75 | 271.83 | 25.04 |
Annual Sum or Average | 6323.00 | 26.18 | 6690.50 | 26.25 | 5916.50 | 26.35 |
Minimum of Months | 378.83 | 23.12 | 406.33 | 24.19 | 198.33 | 24.53 |
Maximum of Months | 612.00 | 27.87 | 612.00 | 27.87 | 612.00 | 27.87 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.45048 | 46.73296 | 0.08802 | 7.33476 |
February | 551.00000 | 23.12430 | 48.61281 | 0.28642 | 8.34231 |
March | 612.00000 | 23.84992 | 48.22374 | 0.49871 | 10.67416 |
April | 590.00000 | 24.14063 | 47.73085 | 0.61225 | 13.17445 |
May | 611.00000 | 24.21405 | 57.19685 | -0.0782 | 6.01596 |
June | 592.00000 | 24.24000 | 64.25469 | -0.0049 | 6.17563 |
July | 609.00000 | 24.22885 | 71.63285 | 0.03861 | 6.16457 |
August | 612.00000 | 24.19685 | 73.19984 | 0.03445 | 5.93619 |
September | 590.00000 | 24.16354 | 70.44226 | -0.0118 | 5.66672 |
October | 610.00000 | 24.03755 | 55.53189 | 0.64819 | 14.00650 |
November | 591.00000 | 23.58481 | 49.01260 | 0.44991 | 10.08058 |
December | 609.00000 | 22.72116 | 45.72803 | 0.17192 | 7.63500 |
Annual Sum or Average | 7187.00000 | 23.74834 | 56.57797 | 0.22692 | 8.43049 |
Minimum of Months | 551.00000 | 22.45048 | 45.72803 | -0.0782 | 5.66672 |
Maximum of Months | 612.00000 | 24.24000 | 73.19984 | 0.64819 | 14.00650 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.56483 | 48.47426 | 0.57383 | 18.72588 |
February | 551.00000 | 24.72394 | 48.66950 | 0.86890 | 24.91145 |
March | 612.00000 | 25.75974 | 48.16950 | 1.15037 | 33.57913 |
April | 590.00000 | 25.99573 | 48.76507 | 1.26073 | 38.48578 |
May | 611.00000 | 26.26415 | 57.56929 | 0.89991 | 23.27085 |
June | 592.00000 | 27.03465 | 63.14651 | 1.22326 | 38.23495 |
July | 609.00000 | 27.78543 | 67.49641 | 1.50954 | 51.69356 |
August | 612.00000 | 27.87445 | 67.33960 | 1.53792 | 52.95640 |
September | 590.00000 | 26.72264 | 65.39758 | 1.11371 | 32.81487 |
October | 610.00000 | 25.96460 | 54.43038 | 1.30433 | 40.66652 |
November | 591.00000 | 25.39438 | 49.16628 | 1.07903 | 31.19423 |
December | 609.00000 | 24.09209 | 46.85199 | 0.71000 | 20.90406 |
Annual Sum or Average | 7187.00000 | 25.93811 | 55.50150 | 1.10394 | 34.01753 |
Minimum of Months | 551.00000 | 23.56483 | 46.85199 | 0.57383 | 18.72588 |
Maximum of Months | 612.00000 | 27.87445 | 67.49641 | 1.53792 | 52.95640 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.518071E+10 | 0.161967E+10 | 192.43 | 0.414962E+10 | 0.103108E+10 | 0.00 | 0.53 | 15-JAN-04:01 | 0.00 | 01-JAN-00:02 | 25075.33 | 15-JAN-04:01 | 19527.31 | 12-JAN-14:00 | 11604.48 | 15-JAN-04:01 | 7289.80 | 15-JAN-04:01 | 0.00 | 01-JAN-00:02 |
February | 0.161222E+11 | 0.483957E+10 | 304.52 | 0.126473E+11 | 0.347489E+10 | 0.00 | 1.00 | 25-FEB-04:01 | 0.00 | 01-FEB-00:03 | 56229.93 | 25-FEB-04:01 | 33036.54 | 25-FEB-04:01 | 23193.39 | 25-FEB-04:01 | 14294.95 | 25-FEB-04:01 | 0.00 | 01-FEB-00:03 |
March | 0.441946E+11 | 0.125658E+11 | 513.98 | 0.348030E+11 | 0.939160E+10 | 0.00 | 1.00 | 07-MAR-04:01 | 0.00 | 01-MAR-00:03 | 113786.09 | 29-MAR-03:01 | 76463.13 | 30-MAR-03:01 | 48150.60 | 29-MAR-03:01 | 27792.51 | 29-MAR-03:01 | 0.00 | 01-MAR-00:03 |
April | 0.773336E+11 | 0.220320E+11 | 583.93 | 0.646492E+11 | 0.126843E+11 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 117369.88 | 27-APR-03:01 | 102846.44 | 08-APR-03:01 | 53968.71 | 26-APR-03:01 | 28053.93 | 27-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.118179E+12 | 0.333986E+11 | 615.26 | 0.865412E+11 | 0.316376E+11 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 118929.62 | 14-MAY-03:01 | 100299.12 | 06-MAY-03:01 | 80726.68 | 23-MAY-03:01 | 29549.74 | 04-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.140890E+12 | 0.387344E+11 | 601.91 | 0.883723E+11 | 0.525176E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 118929.62 | 24-JUN-03:01 | 86244.72 | 05-JUN-03:01 | 82781.14 | 28-JUN-03:01 | 33718.57 | 10-JUN-18:10 | 0.00 | 01-JUN-00:01 |
July | 0.165386E+12 | 0.423583E+11 | 618.52 | 0.824623E+11 | 0.829242E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 118929.62 | 26-JUL-03:01 | 67571.10 | 03-JUL-17:10 | 85010.69 | 19-JUL-03:01 | 31647.95 | 01-JUL-17:03 | 0.00 | 01-JUL-00:01 |
August | 0.163667E+12 | 0.408019E+11 | 614.37 | 0.751427E+11 | 0.885238E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 118929.62 | 04-AUG-03:02 | 60944.27 | 07-AUG-17:10 | 85477.66 | 30-AUG-03:01 | 30451.48 | 28-AUG-17:03 | 0.00 | 01-AUG-00:01 |
September | 0.130784E+12 | 0.326615E+11 | 593.53 | 0.648414E+11 | 0.659431E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 118929.62 | 05-SEP-03:02 | 62077.76 | 29-SEP-03:01 | 82618.73 | 13-SEP-03:01 | 29183.13 | 17-SEP-20:00 | 0.00 | 01-SEP-00:01 |
October | 0.714450E+11 | 0.193639E+11 | 588.19 | 0.501753E+11 | 0.212698E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 118929.62 | 04-OCT-03:01 | 75324.86 | 05-OCT-03:01 | 64351.46 | 13-OCT-03:01 | 28173.87 | 04-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.322165E+11 | 0.927246E+10 | 423.26 | 0.251976E+11 | 0.701895E+10 | 0.00 | 1.00 | 02-NOV-03:01 | 0.00 | 01-NOV-00:01 | 70944.99 | 11-NOV-04:01 | 48370.18 | 02-NOV-03:01 | 26483.28 | 11-NOV-04:01 | 18110.19 | 11-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.885523E+10 | 0.273000E+10 | 244.59 | 0.693053E+10 | 0.192471E+10 | 0.00 | 0.59 | 28-DEC-14:00 | 0.00 | 01-DEC-00:03 | 28110.40 | 28-DEC-14:00 | 23032.66 | 28-DEC-14:00 | 7853.94 | 29-DEC-04:01 | 8052.95 | 28-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.974254E+12 | 0.260378E+12 | 5894.48 | 0.595912E+12 | 0.378342E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.518071E+10 | 0.161967E+10 | 192.43 | 0.414962E+10 | 0.103108E+10 | 0.00 | 0.53 | 0.00 | 25075.33 | 19527.31 | 7853.94 | 7289.80 | 0.00 | |||||||
Maximum of Months | 0.165386E+12 | 0.423583E+11 | 618.52 | 0.883723E+11 | 0.885238E+11 | 0.00 | 1.00 | 0.00 | 118929.62 | 102846.44 | 85477.66 | 33718.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.332617E+10 | 0.900430E+09 | 221.89 | 0.255329E+10 | 0.772880E+09 | 0.00 | 1.00 | 12-JAN-04:01 | 0.00 | 01-JAN-00:02 | 37804.41 | 14-JAN-04:01 | 21413.24 | 14-JAN-04:01 | 20547.97 | 16-JAN-04:01 | 8631.97 | 14-JAN-04:01 | 0.00 | 01-JAN-00:02 |
February | 0.101568E+11 | 0.257521E+10 | 325.66 | 0.791391E+10 | 0.224294E+10 | 0.00 | 1.00 | 07-FEB-04:01 | 0.00 | 01-FEB-00:03 | 37804.41 | 24-FEB-04:01 | 24830.96 | 18-FEB-04:01 | 19040.83 | 26-FEB-04:01 | 8631.97 | 09-FEB-04:01 | 0.00 | 01-FEB-00:03 |
March | 0.263850E+11 | 0.628778E+10 | 546.91 | 0.216501E+11 | 0.473487E+10 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 | 39008.44 | 29-MAR-03:01 | 30385.98 | 28-MAR-16:18 | 20384.59 | 31-MAR-03:01 | 8708.81 | 29-MAR-03:01 | 0.00 | 01-MAR-00:03 |
April | 0.476828E+11 | 0.115500E+11 | 663.06 | 0.425077E+11 | 0.517509E+10 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 41315.97 | 20-APR-03:01 | 37941.39 | 15-APR-15:03 | 20802.55 | 23-APR-03:01 | 10545.13 | 27-APR-16:13 | 0.00 | 01-APR-00:01 |
May | 0.738786E+11 | 0.179494E+11 | 702.61 | 0.581865E+11 | 0.156921E+11 | 0.00 | 1.00 | 01-MAY-03:11 | 0.00 | 01-MAY-00:01 | 42003.19 | 24-MAY-03:01 | 39302.62 | 04-MAY-18:30 | 26916.79 | 22-MAY-22:35 | 11788.79 | 03-MAY-14:55 | 0.00 | 01-MAY-00:01 |
June | 0.838059E+11 | 0.200350E+11 | 683.21 | 0.564902E+11 | 0.273157E+11 | 0.00 | 1.00 | 01-JUN-03:11 | 0.00 | 01-JUN-00:01 | 42003.19 | 24-JUN-15:07 | 39292.97 | 12-JUN-19:35 | 29139.03 | 25-JUN-03:52 | 11635.66 | 07-JUN-14:55 | 0.00 | 01-JUN-00:01 |
July | 0.956661E+11 | 0.216588E+11 | 707.25 | 0.484859E+11 | 0.471803E+11 | 0.00 | 1.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:01 | 42003.19 | 10-JUL-19:50 | 37001.22 | 04-JUL-18:00 | 30031.52 | 19-JUL-03:21 | 10599.86 | 02-JUL-15:55 | 0.00 | 01-JUL-00:01 |
August | 0.953584E+11 | 0.210138E+11 | 707.08 | 0.423025E+11 | 0.530559E+11 | 0.00 | 1.00 | 01-AUG-00:08 | 0.00 | 01-AUG-00:01 | 42003.19 | 12-AUG-03:45 | 28710.13 | 07-AUG-14:00 | 30402.39 | 12-AUG-08:00 | 10033.09 | 07-AUG-14:55 | 0.00 | 01-AUG-00:01 |
September | 0.848097E+11 | 0.185303E+11 | 684.19 | 0.406891E+11 | 0.441207E+11 | 0.00 | 1.00 | 01-SEP-00:09 | 0.00 | 01-SEP-00:01 | 42003.19 | 05-SEP-12:40 | 32512.19 | 26-SEP-15:27 | 29971.49 | 10-SEP-03:13 | 10067.57 | 17-SEP-20:00 | 0.00 | 01-SEP-00:01 |
October | 0.442411E+11 | 0.101019E+11 | 659.59 | 0.320018E+11 | 0.122393E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 42003.19 | 06-OCT-10:53 | 32441.23 | 02-OCT-15:07 | 26078.25 | 12-OCT-03:52 | 9312.17 | 04-OCT-11:02 | 0.00 | 01-OCT-00:01 |
November | 0.191413E+11 | 0.459162E+10 | 435.91 | 0.153483E+11 | 0.379300E+10 | 0.00 | 1.00 | 01-NOV-03:11 | 0.00 | 01-NOV-00:01 | 37804.41 | 03-NOV-03:01 | 22982.69 | 21-NOV-04:01 | 19913.15 | 09-NOV-04:11 | 8631.97 | 01-NOV-03:11 | 0.00 | 01-NOV-00:01 |
December | 0.601939E+10 | 0.158727E+10 | 275.07 | 0.458169E+10 | 0.143770E+10 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:03 | 37804.41 | 01-DEC-04:01 | 27923.54 | 30-DEC-04:01 | 18463.21 | 28-DEC-04:01 | 8631.97 | 01-DEC-04:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.590471E+12 | 0.136782E+12 | 6612.42 | 0.372711E+12 | 0.217760E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.332617E+10 | 0.900430E+09 | 221.89 | 0.255329E+10 | 0.772880E+09 | 0.00 | 1.00 | 0.00 | 37804.41 | 21413.24 | 18463.21 | 8631.97 | 0.00 | |||||||
Maximum of Months | 0.956661E+11 | 0.216588E+11 | 707.25 | 0.581865E+11 | 0.530559E+11 | 0.00 | 1.00 | 0.00 | 42003.19 | 39302.62 | 30402.39 | 11788.79 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.87 | 54.86 | 82.02 | 154.65 | 244.57 | 0.00 | 0.00 | 0.00 |
February | 166.75 | 68.85 | 97.90 | 236.09 | 190.81 | 0.00 | 0.00 | 0.00 |
March | 203.50 | 84.13 | 119.36 | 358.93 | 114.45 | 0.00 | 0.00 | 0.00 |
April | 242.21 | 112.93 | 129.28 | 541.62 | 41.21 | 0.00 | 0.00 | 0.00 |
May | 237.99 | 105.62 | 132.38 | 616.94 | 8.03 | 0.00 | 0.00 | 0.00 |
June | 193.27 | 63.96 | 129.31 | 551.15 | 5.96 | 0.00 | 0.00 | 0.00 |
July | 162.21 | 33.91 | 128.31 | 453.19 | 2.06 | 2.67 | 0.00 | 0.00 |
August | 146.61 | 25.51 | 121.10 | 381.83 | 5.61 | 0.00 | 0.00 | 0.00 |
September | 156.36 | 43.44 | 112.93 | 356.68 | 20.21 | 0.00 | 0.00 | 0.00 |
October | 171.07 | 68.92 | 102.14 | 342.42 | 93.57 | 0.00 | 0.00 | 0.00 |
November | 151.50 | 64.77 | 86.73 | 241.21 | 175.52 | 0.00 | 0.00 | 0.00 |
December | 132.61 | 52.65 | 79.95 | 160.41 | 243.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.03 | 64.86 | 110.17 | 366.71 | 95.05 | 2.67 | 0.00 | 0.00 |
Minimum of Months | 132.61 | 25.51 | 79.95 | 154.65 | 2.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.21 | 112.93 | 132.38 | 616.94 | 244.57 | 2.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 403.96 | 245.89 | 158.07 | 608.27 | 333.31 | 0.00 | 0.00 | 0.00 |
February | 383.25 | 212.88 | 170.37 | 626.06 | 267.06 | 0.00 | 0.00 | 0.00 |
March | 325.65 | 142.80 | 182.85 | 618.86 | 165.16 | 0.00 | 0.00 | 0.00 |
April | 232.17 | 66.96 | 165.22 | 594.61 | 59.20 | 0.00 | 0.00 | 0.00 |
May | 167.37 | 14.10 | 153.27 | 554.70 | 11.40 | 0.00 | 0.00 | 0.00 |
June | 151.38 | 2.63 | 148.75 | 535.71 | 8.35 | 0.00 | 0.00 | 0.00 |
July | 157.24 | 1.54 | 155.70 | 497.43 | 2.85 | 2.67 | 0.00 | 0.00 |
August | 165.79 | 7.27 | 158.52 | 463.53 | 7.84 | 0.00 | 0.00 | 0.00 |
September | 229.41 | 63.17 | 166.25 | 538.26 | 28.37 | 0.00 | 0.00 | 0.00 |
October | 388.39 | 217.84 | 170.56 | 784.52 | 132.32 | 0.00 | 0.00 | 0.00 |
November | 484.60 | 321.04 | 163.56 | 856.95 | 245.74 | 0.00 | 0.00 | 0.00 |
December | 431.08 | 270.35 | 160.74 | 674.26 | 328.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 292.83 | 130.05 | 162.78 | 612.45 | 131.96 | 2.67 | 0.00 | 0.00 |
Minimum of Months | 151.38 | 1.54 | 148.75 | 463.53 | 2.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 484.60 | 321.04 | 182.85 | 856.95 | 333.31 | 2.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.08 | 52.17 | 81.91 | 165.86 | 259.95 | 0.00 | 0.00 | 0.00 |
February | 153.71 | 56.79 | 96.92 | 224.21 | 202.43 | 0.00 | 0.00 | 0.00 |
March | 199.22 | 79.85 | 119.37 | 357.15 | 121.19 | 0.00 | 0.00 | 0.00 |
April | 241.34 | 113.02 | 128.32 | 539.72 | 42.88 | 0.00 | 0.00 | 0.00 |
May | 228.79 | 97.06 | 131.73 | 598.75 | 8.08 | 0.00 | 0.00 | 0.00 |
June | 215.25 | 83.83 | 131.42 | 592.73 | 5.93 | 0.00 | 0.00 | 0.00 |
July | 159.31 | 30.87 | 128.44 | 448.34 | 1.96 | 2.67 | 0.00 | 0.00 |
August | 146.24 | 25.77 | 120.47 | 381.71 | 5.59 | 0.00 | 0.00 | 0.00 |
September | 161.50 | 47.76 | 113.74 | 366.71 | 20.47 | 0.00 | 0.00 | 0.00 |
October | 167.95 | 67.06 | 100.89 | 341.10 | 97.65 | 0.00 | 0.00 | 0.00 |
November | 151.75 | 64.77 | 86.98 | 254.13 | 185.58 | 0.00 | 0.00 | 0.00 |
December | 129.49 | 49.24 | 80.25 | 164.61 | 251.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 174.02 | 63.93 | 110.09 | 370.03 | 99.85 | 2.67 | 0.00 | 0.00 |
Minimum of Months | 129.49 | 25.77 | 80.25 | 164.61 | 1.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 241.34 | 113.02 | 131.73 | 598.75 | 259.95 | 2.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366605E+09 | 0.146928E+09 | 0.219677E+09 | 0.414216E+09 | 0.655043E+09 |
February | 0.403390E+09 | 0.166551E+09 | 0.236839E+09 | 0.571151E+09 | 0.461615E+09 |
March | 0.545041E+09 | 0.225334E+09 | 0.319707E+09 | 0.961355E+09 | 0.306541E+09 |
April | 0.627819E+09 | 0.292718E+09 | 0.335100E+09 | 0.140389E+10 | 0.106812E+09 |
May | 0.637445E+09 | 0.282885E+09 | 0.354561E+09 | 0.165241E+10 | 21503839.10 |
June | 0.500959E+09 | 0.165777E+09 | 0.335181E+09 | 0.142858E+10 | 15435740.49 |
July | 0.434476E+09 | 90823076.91 | 0.343653E+09 | 0.121381E+10 | 5519590.90 |
August | 0.392687E+09 | 68325085.38 | 0.324362E+09 | 0.102268E+10 | 15029529.92 |
September | 0.405297E+09 | 0.112594E+09 | 0.292703E+09 | 0.924518E+09 | 52391646.81 |
October | 0.458187E+09 | 0.184607E+09 | 0.273580E+09 | 0.917133E+09 | 0.250621E+09 |
November | 0.392686E+09 | 0.167890E+09 | 0.224796E+09 | 0.625220E+09 | 0.454959E+09 |
December | 0.355174E+09 | 0.141024E+09 | 0.214150E+09 | 0.429630E+09 | 0.651907E+09 |
Annual Sum or Average | 0.551977E+10 | 0.204546E+10 | 0.347431E+10 | 0.115646E+11 | 0.299738E+10 |
Minimum of Months | 0.355174E+09 | 68325085.38 | 0.214150E+09 | 0.414216E+09 | 5519590.90 |
Maximum of Months | 0.637445E+09 | 0.292718E+09 | 0.354561E+09 | 0.165241E+10 | 0.655043E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108198E+10 | 0.658590E+09 | 0.423385E+09 | 0.162919E+10 | 0.892746E+09 |
February | 0.927163E+09 | 0.515001E+09 | 0.412161E+09 | 0.151457E+10 | 0.646080E+09 |
March | 0.872229E+09 | 0.382483E+09 | 0.489746E+09 | 0.165756E+10 | 0.442364E+09 |
April | 0.601790E+09 | 0.173549E+09 | 0.428242E+09 | 0.154123E+10 | 0.153450E+09 |
May | 0.448290E+09 | 37761891.72 | 0.410528E+09 | 0.148571E+10 | 30532684.45 |
June | 0.392385E+09 | 6823169.61 | 0.385562E+09 | 0.138857E+10 | 21633132.53 |
July | 0.421148E+09 | 4124110.52 | 0.417024E+09 | 0.133233E+10 | 7637239.15 |
August | 0.444054E+09 | 19460899.13 | 0.424593E+09 | 0.124151E+10 | 20987671.62 |
September | 0.594637E+09 | 0.163724E+09 | 0.430913E+09 | 0.139517E+10 | 73525313.23 |
October | 0.104028E+10 | 0.583455E+09 | 0.456820E+09 | 0.210125E+10 | 0.354398E+09 |
November | 0.125608E+10 | 0.832135E+09 | 0.423941E+09 | 0.222121E+10 | 0.636963E+09 |
December | 0.115461E+10 | 0.724097E+09 | 0.430513E+09 | 0.180595E+10 | 0.881070E+09 |
Annual Sum or Average | 0.923463E+10 | 0.410120E+10 | 0.513343E+10 | 0.193142E+11 | 0.416139E+10 |
Minimum of Months | 0.392385E+09 | 4124110.52 | 0.385562E+09 | 0.124151E+10 | 7637239.15 |
Maximum of Months | 0.125608E+10 | 0.832135E+09 | 0.489746E+09 | 0.222121E+10 | 0.892746E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359121E+09 | 0.139737E+09 | 0.219384E+09 | 0.444226E+09 | 0.696240E+09 |
February | 0.371850E+09 | 0.137382E+09 | 0.234468E+09 | 0.542408E+09 | 0.489722E+09 |
March | 0.533578E+09 | 0.213857E+09 | 0.319721E+09 | 0.956597E+09 | 0.324604E+09 |
April | 0.625542E+09 | 0.292941E+09 | 0.332600E+09 | 0.139895E+10 | 0.111152E+09 |
May | 0.612791E+09 | 0.259954E+09 | 0.352837E+09 | 0.160370E+10 | 21629009.21 |
June | 0.557921E+09 | 0.217287E+09 | 0.340633E+09 | 0.153635E+10 | 15360126.08 |
July | 0.426698E+09 | 82685994.21 | 0.344012E+09 | 0.120084E+10 | 5252399.26 |
August | 0.391699E+09 | 69023970.24 | 0.322675E+09 | 0.102236E+10 | 14983148.98 |
September | 0.418596E+09 | 0.123786E+09 | 0.294810E+09 | 0.950519E+09 | 53066348.64 |
October | 0.449829E+09 | 0.179605E+09 | 0.270224E+09 | 0.913594E+09 | 0.261555E+09 |
November | 0.393338E+09 | 0.167889E+09 | 0.225448E+09 | 0.658708E+09 | 0.481017E+09 |
December | 0.346815E+09 | 0.131882E+09 | 0.214933E+09 | 0.440881E+09 | 0.674366E+09 |
Annual Sum or Average | 0.548778E+10 | 0.201603E+10 | 0.347175E+10 | 0.116691E+11 | 0.314895E+10 |
Minimum of Months | 0.346815E+09 | 69023970.24 | 0.214933E+09 | 0.440881E+09 | 5252399.26 |
Maximum of Months | 0.625542E+09 | 0.292941E+09 | 0.352837E+09 | 0.160370E+10 | 0.696240E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 903.23 | 812.28 | 674.92 | 352.92 | 322.00 | 0.00 | 0.00 |
February | 1071.11 | 645.05 | 703.70 | 338.51 | 365.19 | 0.00 | 0.00 |
March | 1324.67 | 390.53 | 728.36 | 306.78 | 421.58 | 0.00 | 0.00 |
April | 1673.08 | 140.42 | 715.72 | 292.90 | 422.82 | 0.00 | 0.00 |
May | 1770.25 | 27.36 | 634.16 | 216.77 | 417.39 | 0.00 | 0.00 |
June | 1679.49 | 20.12 | 559.90 | 150.42 | 409.48 | 0.00 | 0.00 |
July | 1398.96 | 6.87 | 478.76 | 66.32 | 412.44 | 0.00 | 0.00 |
August | 1227.03 | 19.01 | 458.65 | 58.55 | 400.10 | 0.00 | 0.00 |
September | 1261.33 | 68.73 | 547.27 | 154.36 | 392.91 | 0.00 | 0.00 |
October | 1464.93 | 320.44 | 727.41 | 353.82 | 373.59 | 0.00 | 0.00 |
November | 1343.79 | 598.34 | 787.85 | 450.58 | 337.26 | 0.00 | 0.00 |
December | 979.07 | 803.92 | 693.17 | 372.24 | 320.94 | 0.00 | 0.00 |
Annual Sum or Average | 1342.01 | 319.68 | 641.88 | 258.84 | 383.04 | 0.00 | 0.00 |
Minimum of Months | 903.23 | 6.87 | 458.65 | 58.55 | 320.94 | 0.00 | 0.00 |
Maximum of Months | 1770.25 | 812.28 | 787.85 | 450.58 | 422.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241922E+10 | 0.217561E+10 | 0.180770E+10 | 0.945256E+09 | 0.862446E+09 | 0.00 | 0.00 |
February | 0.259122E+10 | 0.156051E+10 | 0.170240E+10 | 0.818934E+09 | 0.883469E+09 | 0.00 | 0.00 |
March | 0.354799E+10 | 0.104599E+10 | 0.195085E+10 | 0.821675E+09 | 0.112917E+10 | 0.00 | 0.00 |
April | 0.433662E+10 | 0.363963E+09 | 0.185515E+10 | 0.759208E+09 | 0.109594E+10 | 0.00 | 0.00 |
May | 0.474144E+10 | 73280686.02 | 0.169853E+10 | 0.580601E+09 | 0.111793E+10 | 0.00 | 0.00 |
June | 0.435323E+10 | 52154415.86 | 0.145126E+10 | 0.389888E+09 | 0.106138E+10 | 0.00 | 0.00 |
July | 0.374697E+10 | 18399946.28 | 0.128232E+10 | 0.177633E+09 | 0.110469E+10 | 0.00 | 0.00 |
August | 0.328649E+10 | 50928622.71 | 0.122844E+10 | 0.156810E+09 | 0.107163E+10 | 0.00 | 0.00 |
September | 0.326937E+10 | 0.178148E+09 | 0.141853E+10 | 0.400104E+09 | 0.101843E+10 | 0.00 | 0.00 |
October | 0.392368E+10 | 0.858274E+09 | 0.194829E+10 | 0.947666E+09 | 0.100062E+10 | 0.00 | 0.00 |
November | 0.348311E+10 | 0.155091E+10 | 0.204210E+10 | 0.116791E+10 | 0.874186E+09 | 0.00 | 0.00 |
December | 0.262233E+10 | 0.215321E+10 | 0.185660E+10 | 0.997003E+09 | 0.859596E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423217E+11 | 0.100814E+11 | 0.202422E+11 | 0.816269E+10 | 0.120795E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241922E+10 | 18399946.28 | 0.122844E+10 | 0.156810E+09 | 0.859596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.474144E+10 | 0.217561E+10 | 0.204210E+10 | 0.116791E+10 | 0.112917E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638641E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161242283.4 | 81.22 | 0.00 | 0.00 |
February | 0.577697E+10 | -0.563427E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -142696661.2 | 81.22 | 0.00 | 0.00 |
March | 0.644884E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154966452.2 | 81.21 | 0.00 | 0.00 |
April | 0.619276E+10 | -0.604350E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149263386.6 | 81.21 | 0.00 | 0.00 |
May | 0.641380E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153597287.6 | 81.21 | 0.00 | 0.00 |
June | 0.623338E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -146805641.0 | 81.21 | 0.00 | 0.00 |
July | 0.636695E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149864019.2 | 81.22 | 0.00 | 0.00 |
August | 0.644485E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149640064.3 | 81.22 | 0.00 | 0.00 |
September | 0.619237E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147545465.5 | 81.21 | 0.00 | 0.00 |
October | 0.637813E+10 | -0.622384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154290534.5 | 81.21 | 0.00 | 0.00 |
November | 0.617555E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150941487.3 | 81.22 | 0.00 | 0.00 |
December | 0.637686E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159769213.9 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.753869E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.182062E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577697E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161242283.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644884E+10 | -0.563427E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -142696661.2 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.194363E+11 | -0.185340E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -902302788.8 | 58.99 | 0.00 | 0.00 |
February | 0.172013E+11 | -0.164133E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -788006498.9 | 58.99 | 0.00 | 0.00 |
March | 0.179597E+11 | -0.171149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -844815437.0 | 58.98 | 0.00 | 0.00 |
April | 0.155531E+11 | -0.147419E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811239720.3 | 58.99 | 0.00 | 0.00 |
May | 0.143022E+11 | -0.134701E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -832126654.3 | 58.98 | 0.00 | 0.00 |
June | 0.125439E+11 | -0.117554E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -788517914.8 | 58.98 | 0.00 | 0.00 |
July | 0.122460E+11 | -0.114481E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -797858559.1 | 58.98 | 0.00 | 0.00 |
August | 0.127963E+11 | -0.120003E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -795941859.8 | 58.98 | 0.00 | 0.00 |
September | 0.135335E+11 | -0.127383E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -795268490.3 | 58.98 | 0.00 | 0.00 |
October | 0.157080E+11 | -0.148693E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838664211.3 | 58.99 | 0.00 | 0.00 |
November | 0.169475E+11 | -0.161210E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -826507957.1 | 58.99 | 0.00 | 0.00 |
December | 0.188625E+11 | -0.179738E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -888769561.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.187090E+12 | -0.177180E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.991002E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.122460E+11 | -0.185340E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -902302788.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.194363E+11 | -0.114481E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -788006498.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.50 | 01-JAN-07:49 | 757.07 | 24.44 | 207.50 | 283.00 | 805.96 | 24.73 | 210.83 | 285.17 |
February | 303.83 | 0.53 | 0.50 | 01-FEB-07:49 | 766.60 | 23.12 | 172.33 | 269.00 | 755.27 | 22.51 | 155.83 | 268.50 |
March | 364.50 | 0.52 | 0.50 | 01-MAR-07:30 | 804.23 | 20.62 | 133.33 | 324.83 | 818.82 | 20.33 | 125.83 | 326.17 |
April | 379.83 | 0.53 | 0.50 | 01-APR-07:10 | 832.59 | 19.49 | 90.33 | 337.00 | 720.81 | 19.48 | 84.17 | 337.17 |
May | 406.00 | 0.54 | 0.50 | 01-MAY-06:40 | 615.18 | 18.99 | 64.83 | 352.83 | 624.27 | 18.95 | 62.50 | 353.33 |
June | 386.67 | 0.54 | 0.50 | 01-JUN-07:10 | 551.13 | 18.84 | 62.17 | 332.17 | 553.46 | 18.63 | 49.33 | 333.17 |
July | 379.83 | 0.53 | 0.50 | 01-JUL-06:40 | 518.98 | 18.74 | 43.00 | 325.00 | 525.83 | 18.76 | 40.67 | 325.67 |
August | 372.50 | 0.54 | 0.50 | 01-AUG-06:49 | 542.41 | 18.71 | 53.67 | 314.00 | 534.20 | 18.71 | 55.67 | 313.17 |
September | 344.33 | 0.53 | 0.50 | 01-SEP-07:10 | 662.42 | 19.58 | 92.17 | 297.67 | 696.11 | 19.57 | 94.50 | 296.50 |
October | 347.33 | 0.54 | 0.50 | 01-OCT-06:00 | 803.26 | 21.19 | 150.83 | 303.00 | 821.75 | 21.38 | 157.00 | 302.67 |
November | 317.83 | 0.53 | 0.50 | 01-NOV-07:10 | 883.20 | 24.18 | 194.17 | 281.17 | 813.40 | 24.23 | 196.67 | 285.17 |
December | 315.50 | 0.52 | 0.50 | 01-DEC-07:19 | 828.07 | 24.15 | 204.17 | 284.17 | 880.78 | 26.11 | 221.83 | 287.17 |
Annual Sum or Average | 4237.50 | 0.53 | 706.82 | 20.82 | 1468.50 | 3703.83 | 704.85 | 20.92 | 1454.83 | 3713.83 | ||
Minimum of Months | 303.83 | 0.52 | 0.50 | 518.98 | 18.71 | 43.00 | 269.00 | 525.83 | 18.63 | 40.67 | 268.50 | |
Maximum of Months | 406.00 | 0.54 | 0.50 | 883.20 | 24.44 | 207.50 | 352.83 | 880.78 | 26.11 | 221.83 | 353.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.539564E+10 | 28062.57 | 05-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136819E+10 | 23493.89 | 05-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178298E+09 | 12403.58 | 27-NOV-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276969E+10 | 26964.38 | 23-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.971183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.539564E+10 | 28062.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.562248E+09 | 11401.40 | 05-JAN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21599765.30 | 9162.69 | 02-FEB-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164879E+09 | 12277.57 | 23-DEC-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.748727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.562248E+09 | 12277.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.518071E+10 | 0.414962E+10 | 25075.33 | 15-JAN-04:01 | 13470.86 | 0.00 |
February | 0.00 | 0.00 | 0.161222E+11 | 0.126473E+11 | 56229.93 | 25-FEB-04:01 | 33036.54 | 0.00 |
March | 0.00 | 0.00 | 0.441946E+11 | 0.348030E+11 | 113786.09 | 29-MAR-03:01 | 65635.49 | 0.00 |
April | 0.00 | 0.00 | 0.773336E+11 | 0.646492E+11 | 117369.88 | 27-APR-03:01 | 67564.66 | 0.00 |
May | 0.00 | 0.00 | 0.118179E+12 | 0.865412E+11 | 118929.62 | 14-MAY-03:01 | 58332.83 | 0.00 |
June | 0.00 | 0.00 | 0.140890E+12 | 0.883723E+11 | 118929.62 | 24-JUN-03:01 | 49832.95 | 0.00 |
July | 0.00 | 0.00 | 0.165386E+12 | 0.824623E+11 | 118929.62 | 26-JUL-03:01 | 47193.40 | 0.00 |
August | 0.00 | 0.00 | 0.163667E+12 | 0.751427E+11 | 118929.62 | 04-AUG-03:02 | 48003.25 | 0.00 |
September | 0.00 | 0.00 | 0.130784E+12 | 0.648414E+11 | 118929.62 | 05-SEP-03:02 | 40741.62 | 0.00 |
October | 0.00 | 0.00 | 0.714450E+11 | 0.501753E+11 | 118929.62 | 04-OCT-03:01 | 57073.69 | 0.00 |
November | 0.00 | 0.00 | 0.322165E+11 | 0.251976E+11 | 70944.99 | 11-NOV-04:01 | 44461.71 | 0.00 |
December | 0.00 | 0.00 | 0.885523E+10 | 0.693053E+10 | 28110.40 | 28-DEC-14:00 | 23032.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.974254E+12 | 0.595912E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.518071E+10 | 0.414962E+10 | 25075.33 | 13470.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.165386E+12 | 0.883723E+11 | 118929.62 | 67564.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.332617E+10 | 0.255329E+10 | 37804.41 | 14-JAN-04:01 | 21413.24 | 0.00 |
February | 0.00 | 0.00 | 0.101568E+11 | 0.791391E+10 | 37804.41 | 24-FEB-04:01 | 21672.64 | 0.00 |
March | 0.00 | 0.00 | 0.263850E+11 | 0.216501E+11 | 39008.44 | 29-MAR-03:01 | 20536.77 | 0.00 |
April | 0.00 | 0.00 | 0.476828E+11 | 0.425077E+11 | 41315.97 | 20-APR-03:01 | 25777.23 | 0.00 |
May | 0.00 | 0.00 | 0.738786E+11 | 0.581865E+11 | 42003.19 | 24-MAY-03:01 | 17282.55 | 0.00 |
June | 0.00 | 0.00 | 0.838059E+11 | 0.564902E+11 | 42003.19 | 24-JUN-15:07 | 14730.33 | 0.00 |
July | 0.00 | 0.00 | 0.956661E+11 | 0.484859E+11 | 42003.19 | 10-JUL-19:50 | 20382.51 | 0.00 |
August | 0.00 | 0.00 | 0.953584E+11 | 0.423025E+11 | 42003.19 | 12-AUG-03:45 | 13579.69 | 0.00 |
September | 0.00 | 0.00 | 0.848097E+11 | 0.406891E+11 | 42003.19 | 05-SEP-12:40 | 17016.26 | 0.00 |
October | 0.00 | 0.00 | 0.442411E+11 | 0.320018E+11 | 42003.19 | 06-OCT-10:53 | 23099.77 | 0.00 |
November | 0.00 | 0.00 | 0.191413E+11 | 0.153483E+11 | 37804.41 | 03-NOV-03:01 | 22729.24 | 0.00 |
December | 0.00 | 0.00 | 0.601939E+10 | 0.458169E+10 | 37804.41 | 01-DEC-04:01 | 22744.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.590471E+12 | 0.372711E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.332617E+10 | 0.255329E+10 | 37804.41 | 13579.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.956661E+11 | 0.581865E+11 | 42003.19 | 25777.23 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7382.56 | 14039.79 | 18-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7248.12 | 13945.84 | 02-FEB-19:12 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 6854.46 | 13371.30 | 01-MAR-07:47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6153.51 | 12189.45 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5497.21 | 10970.54 | 01-MAY-18:23 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5004.99 | 9771.06 | 01-JUN-18:38 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4744.61 | 9047.91 | 03-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4950.42 | 9614.31 | 31-AUG-18:50 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5382.96 | 10648.82 | 29-SEP-18:43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6018.09 | 12055.73 | 31-OCT-18:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6684.00 | 13188.93 | 30-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 7174.11 | 13855.15 | 27-DEC-19:13 |
Annual Sum or Average | 0.00 | 6084.87 | ||||
Minimum of Months | 0.00 | 0.00 | 4744.61 | 9047.91 | ||
Maximum of Months | 0.00 | 0.00 | 7382.56 | 14039.79 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191425E+10 | 0.23 | 824.13 | 01-JAN-00:02 | 0.27 |
February | 0.173414E+10 | 0.23 | 824.13 | 01-FEB-00:03 | 0.27 |
March | 0.199423E+10 | 0.24 | 824.13 | 01-MAR-00:03 | 0.27 |
April | 0.200888E+10 | 0.25 | 824.13 | 01-APR-00:50 | 0.27 |
May | 0.209925E+10 | 0.25 | 824.13 | 01-MAY-00:40 | 0.27 |
June | 0.203489E+10 | 0.25 | 824.13 | 01-JUN-00:40 | 0.27 |
July | 0.210480E+10 | 0.25 | 824.13 | 01-JUL-00:10 | 0.27 |
August | 0.210420E+10 | 0.25 | 824.13 | 01-AUG-00:08 | 0.27 |
September | 0.203868E+10 | 0.25 | 824.13 | 01-SEP-00:09 | 0.27 |
October | 0.207739E+10 | 0.25 | 824.13 | 01-OCT-00:30 | 0.27 |
November | 0.189435E+10 | 0.24 | 824.13 | 01-NOV-01:15 | 0.27 |
December | 0.191610E+10 | 0.23 | 824.13 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.239212E+11 | 0.25 | |||
Minimum of Months | 0.173414E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.210480E+10 | 0.25 | 824.13 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.681303E+10 | 0.73 | 3994.49 | 05-JAN-05:03 | 1.04 |
February | 0.602675E+10 | 0.72 | 3826.65 | 05-FEB-05:04 | 1.01 |
March | 0.663591E+10 | 0.74 | 7408.86 | 11-MAR-04:01 | 1.42 |
April | 0.664314E+10 | 0.76 | 7408.86 | 03-APR-03:01 | 1.41 |
May | 0.788744E+10 | 0.81 | 7408.86 | 01-MAY-03:01 | 1.42 |
June | 0.884946E+10 | 0.87 | 7408.86 | 01-JUN-03:01 | 1.41 |
July | 0.997455E+10 | 0.91 | 7408.86 | 01-JUL-03:01 | 1.41 |
August | 0.988407E+10 | 0.91 | 7408.86 | 01-AUG-03:01 | 1.40 |
September | 0.803278E+10 | 0.83 | 7408.86 | 01-SEP-03:01 | 1.40 |
October | 0.674899E+10 | 0.75 | 7408.86 | 01-OCT-03:01 | 1.41 |
November | 0.642136E+10 | 0.74 | 4414.22 | 11-NOV-04:01 | 1.10 |
December | 0.671654E+10 | 0.72 | 3954.15 | 23-DEC-05:03 | 1.03 |
Annual Sum or Average | 0.906340E+11 | 0.79 | |||
Minimum of Months | 0.602675E+10 | 0.72 | 3826.65 | 1.01 | |
Maximum of Months | 0.997455E+10 | 0.91 | 7408.86 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149163E+10 | 0.47 | 1651.24 | 14-JAN-04:01 | 0.90 |
February | 0.134439E+10 | 0.47 | 1651.24 | 09-FEB-04:01 | 0.90 |
March | 0.159181E+10 | 0.51 | 1651.24 | 01-MAR-04:01 | 0.90 |
April | 0.202905E+10 | 0.61 | 1651.24 | 01-APR-03:01 | 0.89 |
May | 0.293296E+10 | 0.71 | 1651.24 | 01-MAY-03:11 | 0.89 |
June | 0.334963E+10 | 0.77 | 1651.24 | 01-JUN-03:11 | 0.89 |
July | 0.381465E+10 | 0.81 | 1651.24 | 01-JUL-03:01 | 0.89 |
August | 0.376602E+10 | 0.80 | 1651.24 | 01-AUG-03:01 | 0.88 |
September | 0.329493E+10 | 0.77 | 1651.24 | 01-SEP-03:01 | 0.88 |
October | 0.194565E+10 | 0.59 | 1651.24 | 01-OCT-03:01 | 0.89 |
November | 0.146101E+10 | 0.49 | 1651.24 | 01-NOV-03:11 | 0.90 |
December | 0.148714E+10 | 0.47 | 1651.24 | 01-DEC-04:01 | 0.90 |
Annual Sum or Average | 0.285089E+11 | 0.62 | |||
Minimum of Months | 0.134439E+10 | 0.47 | 1651.24 | 0.88 | |
Maximum of Months | 0.381465E+10 | 0.81 | 1651.24 | 0.90 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:02 | 5.36 | 5.36 | 50.86 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 50.96 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 51.36 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 54.20 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 54.18 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 55.42 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 54.69 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.86 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 55.38 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 54.25 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.72 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 51.31 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.86 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.42 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 50.86 | 59.91 | 7382.56 | 14039.79 | 18-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.96 | 58.83 | 7248.12 | 13945.84 | 02-FEB-19:12 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.36 | 59.28 | 6854.46 | 13371.30 | 01-MAR-07:47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.64 | 52.64 | 6153.51 | 12189.45 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.11 | 53.11 | 5497.21 | 10970.54 | 01-MAY-18:23 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 54.21 | 54.21 | 5004.99 | 9771.06 | 01-JUN-18:38 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.80 | 53.80 | 4744.61 | 9047.91 | 03-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.75 | 53.75 | 4950.42 | 9614.31 | 31-AUG-18:50 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 54.31 | 54.31 | 5382.96 | 10648.82 | 29-SEP-18:43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.55 | 51.55 | 6018.09 | 12055.73 | 31-OCT-18:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.10 | 52.10 | 6684.00 | 13188.93 | 30-NOV-07:55 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.31 | 58.66 | 7174.11 | 13855.15 | 27-DEC-19:13 |
Annual Sum or Average | 0.00 | 6084.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.86 | 51.55 | 4744.61 | 9047.91 | ||
Maximum of Months | 0.00 | 0.00 | 54.31 | 59.91 | 7382.56 | 14039.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.843270E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.108663E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192017E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.286751E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.412860E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.475839E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.523328E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.506860E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.406943E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.261129E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.156938E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.944653E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.351012E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.843270E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.523328E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.239206E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.391960E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.787959E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.135791E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.208824E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.233846E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.254735E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.247799E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.218252E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.120476E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.605263E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.307441E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165291E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.239206E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.254735E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.681303E+10 | 0.518071E+10 | 0.539564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602675E+10 | 0.161222E+11 | 0.136819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.663591E+10 | 0.441946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664314E+10 | 0.773336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.788744E+10 | 0.118179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.884946E+10 | 0.140890E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997455E+10 | 0.165386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.988407E+10 | 0.163667E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.803278E+10 | 0.130784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674899E+10 | 0.714450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.642136E+10 | 0.322165E+11 | 0.178298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671654E+10 | 0.885523E+10 | 0.276969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906340E+11 | 0.974254E+12 | 0.971183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.602675E+10 | 0.518071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997455E+10 | 0.165386E+12 | 0.539564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149163E+10 | 0.332617E+10 | 0.562248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134439E+10 | 0.101568E+11 | 21599765.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159181E+10 | 0.263850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202905E+10 | 0.476828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293296E+10 | 0.738786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.334963E+10 | 0.838059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.381465E+10 | 0.956661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.376602E+10 | 0.953584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329493E+10 | 0.848097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194565E+10 | 0.442411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146101E+10 | 0.191413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148714E+10 | 0.601939E+10 | 0.164879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285089E+11 | 0.590471E+12 | 0.748727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134439E+10 | 0.332617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.381465E+10 | 0.956661E+11 | 0.562248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.681303E+10 | 0.00 | 0.00 | 0.00 | 0.161967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602675E+10 | 0.00 | 0.00 | 0.00 | 0.483957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.663591E+10 | 0.00 | 0.00 | 0.00 | 0.125658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664314E+10 | 0.00 | 0.00 | 0.00 | 0.220320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.788744E+10 | 0.00 | 0.00 | 0.00 | 0.333986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.884946E+10 | 0.00 | 0.00 | 0.00 | 0.387344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997455E+10 | 0.00 | 0.00 | 0.00 | 0.423583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.988407E+10 | 0.00 | 0.00 | 0.00 | 0.408019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.803278E+10 | 0.00 | 0.00 | 0.00 | 0.326615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674899E+10 | 0.00 | 0.00 | 0.00 | 0.193639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.642136E+10 | 0.00 | 0.00 | 0.00 | 0.927246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671654E+10 | 0.00 | 0.00 | 0.00 | 0.273000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906340E+11 | 0.00 | 0.00 | 0.00 | 0.260378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.602675E+10 | 0.00 | 0.00 | 0.00 | 0.161967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997455E+10 | 0.00 | 0.00 | 0.00 | 0.423583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149163E+10 | 0.00 | 0.00 | 0.00 | 0.900430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134439E+10 | 0.00 | 0.00 | 0.00 | 0.257521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159181E+10 | 0.00 | 0.00 | 0.00 | 0.628778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202905E+10 | 0.00 | 0.00 | 0.00 | 0.115500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293296E+10 | 0.00 | 0.00 | 0.00 | 0.179494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.334963E+10 | 0.00 | 0.00 | 0.00 | 0.200350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.381465E+10 | 0.00 | 0.00 | 0.00 | 0.216588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.376602E+10 | 0.00 | 0.00 | 0.00 | 0.210138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329493E+10 | 0.00 | 0.00 | 0.00 | 0.185303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194565E+10 | 0.00 | 0.00 | 0.00 | 0.101019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146101E+10 | 0.00 | 0.00 | 0.00 | 0.459162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148714E+10 | 0.00 | 0.00 | 0.00 | 0.158727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285089E+11 | 0.00 | 0.00 | 0.00 | 0.136782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134439E+10 | 0.00 | 0.00 | 0.00 | 0.900430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.381465E+10 | 0.00 | 0.00 | 0.00 | 0.216588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.253069E+11 | 0.00 | 0.00 | 36045493.86 | 0.00 | 22435875.87 | 0.145271E+11 | 0.00 | 3.58 |
February | 0.127020E+11 | 95059919.84 | 0.00 | 60596826.46 | 0.00 | 7496531.96 | 0.122033E+11 | 0.00 | 3.60 |
March | 0.366749E+10 | 0.477096E+10 | 0.00 | 70927068.73 | 4859243.77 | 0.00 | 0.816940E+10 | 0.00 | 3.63 |
April | 0.150547E+09 | 0.197633E+11 | 0.00 | 15653016.97 | 0.210895E+09 | 0.00 | 0.104699E+10 | 0.00 | 3.68 |
May | 7920475.91 | 0.478294E+11 | 0.00 | 2046941.24 | 0.755955E+09 | 0.00 | 4067499.26 | 0.00 | 3.74 |
June | 0.00 | 0.661397E+11 | 0.00 | 850569.32 | 0.136978E+10 | 0.00 | 3446953.30 | 0.00 | 3.80 |
July | 0.00 | 0.851309E+11 | 0.00 | 466584.02 | 0.158257E+10 | 0.00 | 2251398.10 | 0.00 | 3.83 |
August | 2334091.00 | 0.833032E+11 | 0.00 | 1479531.73 | 0.134264E+10 | 0.00 | 1702525.58 | 0.00 | 3.82 |
September | 5077201.89 | 0.600832E+11 | 0.00 | 2604899.41 | 0.860105E+09 | 0.00 | 2247998.83 | 0.00 | 3.78 |
October | 0.853512E+09 | 0.156788E+11 | 0.00 | 25226806.58 | 55907953.84 | 0.00 | 0.316103E+10 | 0.00 | 3.67 |
November | 0.729118E+10 | 0.189631E+10 | 0.00 | 77593606.87 | 0.00 | 0.00 | 0.109923E+11 | 0.00 | 3.61 |
December | 0.208589E+11 | 0.00 | 0.00 | 49875285.40 | 0.00 | 12613004.34 | 0.151503E+11 | 0.00 | 3.57 |
Annual Sum or Average | 0.708459E+11 | 0.384691E+12 | 0.00 | 0.343367E+09 | 0.618271E+10 | 42545412.16 | 0.652641E+11 | 0.00 | 3.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 466584.02 | 0.00 | 0.00 | 1702525.58 | 0.00 | 3.57 |
Maximum of Months | 0.253069E+11 | 0.851309E+11 | 0.00 | 77593606.87 | 0.158257E+10 | 22435875.87 | 0.151503E+11 | 0.00 | 3.83 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167507E+11 | 0.00 | 0.00 | 50520957.73 | 0.00 | 0.00 | 0.232938E+11 | 0.00 | 7.38 |
February | 0.802937E+10 | 0.00 | 0.00 | 71961703.08 | 0.00 | 0.00 | 0.207366E+11 | 0.00 | 7.44 |
March | 0.620103E+09 | 0.721675E+09 | 0.00 | 0.118814E+09 | 0.00 | 0.00 | 0.182189E+11 | 0.00 | 7.69 |
April | 0.00 | 0.788187E+10 | 0.00 | 70744194.95 | 0.00 | 0.00 | 0.472513E+10 | 0.00 | 8.37 |
May | 0.00 | 0.259739E+11 | 0.00 | 5644983.60 | 0.00 | 0.00 | 89531945.08 | 0.00 | 9.07 |
June | 0.00 | 0.368611E+11 | 0.00 | 205528.76 | 0.00 | 0.00 | 941392.70 | 0.00 | 9.56 |
July | 0.00 | 0.486113E+11 | 0.00 | 9219.22 | 0.00 | 0.00 | 46051.56 | 0.00 | 9.84 |
August | 0.00 | 0.485958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 |
September | 0.00 | 0.398801E+11 | 0.00 | 150066.51 | 0.00 | 0.00 | 1250549.31 | 0.00 | 9.47 |
October | 16203288.64 | 0.547568E+10 | 0.00 | 90259286.14 | 0.00 | 0.00 | 0.737099E+10 | 0.00 | 8.24 |
November | 0.272569E+10 | 0.00 | 0.00 | 0.119729E+09 | 0.00 | 0.00 | 0.220503E+11 | 0.00 | 7.51 |
December | 0.135184E+11 | 0.00 | 0.00 | 65897289.46 | 0.00 | 0.00 | 0.243835E+11 | 0.00 | 7.38 |
Annual Sum or Average | 0.416604E+11 | 0.214002E+12 | 0.00 | 0.593936E+09 | 0.00 | 0.00 | 0.120871E+12 | 0.00 | 8.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 |
Maximum of Months | 0.167507E+11 | 0.486113E+11 | 0.00 | 0.119729E+09 | 0.00 | 0.00 | 0.243835E+11 | 0.00 | 9.84 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.535466E+11 | 0.869426E+10 | 0.147775E+12 | 0.101564E+11 | 0.311825E+11 |
February | 0.637912E+11 | 0.629948E+10 | 0.102949E+12 | 0.779919E+10 | 0.521286E+11 |
March | 0.914171E+11 | 0.401888E+10 | 0.615842E+11 | 0.488738E+10 | 0.111623E+12 |
April | 0.111953E+12 | -538486137.1 | -0.151454E+11 | 0.699144E+09 | 0.182456E+12 |
May | 0.121890E+12 | -0.608382E+10 | -0.100548E+12 | -867784284.3 | 0.268519E+12 |
June | 0.108420E+12 | -0.957795E+10 | -0.144201E+12 | -0.223057E+10 | 0.308500E+12 |
July | 0.890035E+11 | -0.134725E+11 | -0.188336E+12 | -0.232654E+10 | 0.347372E+12 |
August | 0.745480E+11 | -0.143045E+11 | -0.186509E+12 | -0.126505E+10 | 0.342503E+12 |
September | 0.780979E+11 | -0.109195E+11 | -0.144010E+12 | -319301015.3 | 0.287429E+12 |
October | 0.720275E+11 | -0.123411E+10 | 0.508798E+10 | 0.342154E+10 | 0.169691E+12 |
November | 0.587891E+11 | 0.364269E+10 | 0.870913E+11 | 0.680183E+10 | 0.874809E+11 |
December | 0.478582E+11 | 0.782410E+10 | 0.138496E+12 | 0.105085E+11 | 0.395387E+11 |
Annual Sum or Average | 0.971342E+12 | -0.256515E+11 | -0.235766E+12 | 0.372648E+11 | 0.222842E+13 |
Minimum of Months | 0.478582E+11 | -0.143045E+11 | -0.188336E+12 | -0.232654E+10 | 0.311825E+11 |
Maximum of Months | 0.121890E+12 | 0.869426E+10 | 0.147775E+12 | 0.105085E+11 | 0.347372E+12 |