Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:26:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3204.37 | 6268.90 | 6268.90 |
Net Site Energy | 3204.37 | 6268.90 | 6268.90 |
Total Source Energy | 4978.69 | 9740.11 | 9740.11 |
Net Source Energy | 4978.69 | 9740.11 | 9740.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1563.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 26.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.55 | 448.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 34.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 722.59 | 2481.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1563.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 44.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 26.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 89.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.55 | 448.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1563.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 16.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 44.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 26.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 89.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.55 | 448.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 34.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 138.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 354.89 | 3936.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 920.46 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1413.65 | 4855.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 138.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 354.89 | 3936.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 920.46 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1413.65 | 4855.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 722.591 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 722.591 | 100.00 |
Total On-Site and Utility Electric Sources | 722.591 | 100.00 |
Total Electricity End Uses | 722.591 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4709.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.3716 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.8021 | 18.52 | 1057.5080 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.3716 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.8021 | 18.52 | 1057.5080 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Conditioned Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.0345 | 1.78 | 335.6309 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-10:00 | 12-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 22-MAY-06:00 |
Heating | 0.00 | 226976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10568.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1663.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 23897.06 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3809.51 | 33899.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1689.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 44774.72 | 274452.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 226976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10568.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1663.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 23306.26 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3809.51 | 33899.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 184.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 882.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 622.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1695.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 141.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 82.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1379.75 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 282.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.26 | 485.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 110.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2288.45 | 2690.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3316.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 100.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 276.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 468.09 | 950.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 215.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4477.02 | 5263.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3316.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 100.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 276.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 468.09 | 950.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 215.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4477.02 | 5263.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.32 |
KITCHEN DIRECT AIR | 1.45 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.32 | 3.32 | 3.32 | 3.32 | 3.32 | 3.32 | 1.00 | 1.00 | 3.32 |
PSZ-AC_2:2 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.00 | 1.00 | 1.45 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.32 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.45 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.32 | 3549.17 |
PSZ-AC_2:2_ADDAQ FAN | 1.45 | 1549.99 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.32 | 3.32 | 3.32 | 2.19 | 65994.03 | 174824.81 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.45 | 1.45 | 1.45 | 0.956024 | 28531.88 | 124671.96 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.32 | 1.66 | 2.21 | 65994.03 | 32997.01 | 0.777880 | 0.777880 |
PSZ-AC_2:2 COOLING COIL | 1.45 | 0.724261 | 0.965680 | 28531.88 | 14265.94 | 0.781980 | 0.781980 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 174824.81 |
PSZ-AC_2:2 HEATING COIL | 124671.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.372 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.299 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.802 | 408.232 | 649.276 | 0.000 | 0.000 | 0.000 | 1066.310 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2368.645 | 6.372 | 8.455 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2368.645 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1227.055 | 8.802 | 163.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1227.055 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6880 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1141 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1940 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.219 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.685 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.079 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.30075618E-16 | 0.17394661E-15 | 0.12402583E-13 | -0.41376697E-16 |
24 | 3 | -0.12971024E-07 | 0.72198543E-07 | -0.59837000E-04 | 0.16553701E-12 |
25 | 2 | 0.68419174E-04 | 0.15226993E-02 | 1.1866788 | -0.78740824E-04 |
26 | 1 | -0.34646128E-01 | 0.38608229E-01 | -17.391783 | 0.34506386 |
27 | 0 | 0.98978059E-01 | 0.24269337E-01 | 16.269565 | |
28 | 4 | 0.12402583E-13 | 0.17394661E-15 | 0.30075618E-16 | -0.41376697E-16 |
29 | 3 | -0.59837000E-04 | 0.72198543E-07 | -0.12971024E-07 | 0.16553701E-12 |
30 | 2 | 1.1866788 | 0.15226993E-02 | 0.68419174E-04 | -0.78740824E-04 |
31 | 1 | -17.391783 | 0.38608229E-01 | -0.34646128E-01 | 0.34506386 |
32 | 0 | 16.269565 | 0.24269337E-01 | 0.98978059E-01 | |
33 | 7 | -0.33088179E-12 | 0.10631229E-14 | -0.10378878E-12 | 0.10075143E-15 |
34 | 6 | 0.29719541E-07 | 0.19558652E-09 | 0.67993556E-08 | -0.14083615E-12 |
35 | 5 | -0.19541429E-03 | 0.16626448E-05 | -0.10043991E-03 | 0.67182350E-08 |
36 | 4 | 0.29833466 | 0.80433903E-03 | 0.10190988 | -0.34446327E-04 |
37 | 3 | -7.3888246 | 0.24784659E-01 | -2.3752651 | 0.29609467E-01 |
38 | 2 | 41.275084 | 0.87686042E-01 | 15.414083 | -0.33783954 |
39 | 1 | -80.855271 | 0.39398643E-01 | -29.275225 | 1.0852145 |
40 | 0 | 46.824337 | 0.78921727E-03 | 16.288062 | |
41 | 7 | -0.37309081E-08 | -0.37068867E-14 | 0.85049737E-15 | -0.35906658E-16 |
42 | 6 | 0.33748536E-05 | 0.21839903E-08 | 0.31965250E-02 | -0.26815130E-04 |
43 | 5 | -0.23274106E-03 | 0.12898622E-05 | -0.22410278 | 0.19594886E-02 |
44 | 4 | 0.52882249E-02 | 0.58640541E-04 | 4.8358442 | -0.45325527E-01 |
45 | 3 | -0.46231823E-01 | 0.46575588E-03 | -38.056992 | 0.39904699 |
46 | 2 | 0.16387024 | 0.77406680E-03 | 116.55318 | -1.4188654 |
47 | 1 | -0.23633551 | 0.23544142E-03 | -143.94806 | 2.0497098 |
48 | 0 | 0.11517916 | 0.57296983E-05 | 60.838472 | |
49 | 7 | -0.21775440E-08 | -0.74942673E-15 | 0.50575888E-14 | -0.69571699E-16 |
50 | 6 | 0.54627457E-05 | 0.37131184E-08 | 0.31903002E-02 | -0.26762911E-04 |
51 | 5 | -0.39062423E-03 | 0.21979559E-05 | -0.22374903 | 0.19563662E-02 |
52 | 4 | 0.89713145E-02 | 0.10003318E-03 | 4.8299532 | -0.45268898E-01 |
53 | 3 | -0.78738827E-01 | 0.79531588E-03 | -38.023719 | 0.39867920 |
54 | 2 | 0.27952853 | 0.13229159E-02 | 116.48843 | -1.4179993 |
55 | 1 | -0.40342200 | 0.40291091E-03 | -143.90995 | 2.0490833 |
56 | 0 | 0.19667931 | 0.97812645E-05 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.261_SHGC_SOUTH_0.399 | 38 | 1 | VerySmooth | 1.482 | 1.482 | 1.000 | 0.400 | ||
2 | NONRESWINDOW_U_0.261_SHGC_NORTH_0.399 | 39 | 1 | VerySmooth | 1.482 | 1.482 | 1.000 | 0.400 | ||
3 | NONRESWINDOW_U_0.261_SHGC_EAST_0.399 | 40 | 1 | VerySmooth | 1.482 | 1.482 | 1.000 | 0.400 | ||
4 | NONRESWINDOW_U_0.261_SHGC_WEST_0.399 | 41 | 1 | VerySmooth | 1.482 | 1.482 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.48453E-002 | 0.31332 | 0.49262 | 0.49262 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 8.97828E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.48453E-002 | 0.31332 | 0.49262 | 0.49262 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 8.97828E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.48453E-002 | 0.31332 | 0.49262 | 0.49262 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 8.97828E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.48453E-002 | 0.31332 | 0.49262 | 0.49262 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 8.97828E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.3162E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3540E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.3667E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.2498E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6213E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7171E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1804E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0955E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.6315E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.1580E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.3649E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.7427E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.7378E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.6561E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.1220E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.1221E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9827E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7871E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6869E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6039E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3501E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3461E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0955E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1804E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 37306.72662 | 44768.07195 | 2.76403 | 3.31684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 27.19600 | 7.00683E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 11768.42103 | 14122.10524 | 0.51240 | 1.33138 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 19387.30959 | 23264.77151 | 1.20710 | 1.44852 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.11800 | 6.99333E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 3061.91422 | 3674.29706 | 0.12061 | 1.21700 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -41.90000 | 6.45023E-005 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 49566.05 | 3.31684 | 3.31684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 129888.10 | 1.33138 | 1.33138 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 23181.16 | 1.44852 | 1.44852 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 118729.72 | 1.21700 | 1.21700 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.31684 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44852 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.31684 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.31684 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.31684 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.31684 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.31684 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.31684 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44852 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44852 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44852 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44852 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44852 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.44852 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.31684 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.44852 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.31684 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.31684 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3549.17383 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.31684 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.31684 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.31684 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.18911 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.31684 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.65842 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.21123 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 65994.03000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32997.01500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77788 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77788 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 65994.03000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 174824.80826 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 174824.80826 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44852 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44852 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1549.98680 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44852 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44852 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44852 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95602 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44852 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72426 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96568 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28531.88000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14265.94000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78198 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78198 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28531.88000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 124671.95897 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 124671.95897 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 63595.3 | 11.25 | 11.20 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27483.6 | 11.40 | 11.34 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.688 | 0.624 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.261_SHGC_EAST_0.399 | N/A | 1.482 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.688 | 0.624 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.261_SHGC_SOUTH_0.399 | N/A | 1.482 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.688 | 0.624 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.261_SHGC_WEST_0.399 | N/A | 1.482 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.114 | 0.111 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.688 | 0.624 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.688 | 0.624 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.688 | 0.624 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.194 | 0.185 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.7580171944E-002 | 0.5112615425 | Pass | Pass | 8.0505771783E-002 | 0.2226158302 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 5.7429620686E-002 | 0.3544676726 | Pass | Pass | 4.9626097961E-002 | 0.2261017938 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 6.0046811790E-002 | 4.8986304312E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 531.62 | 169.55 | 3326.92 | 8.22 | 539.57 | 4575.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.688 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.688 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.688 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.112 | 0.114 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.688 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.688 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.688 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.261_SHGC_EAST_0.399 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.482 | 0.400 | 0.440 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.261_SHGC_SOUTH_0.399 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 1.482 | 0.400 | 0.440 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.261_SHGC_WEST_0.399 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.482 | 0.400 | 0.440 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 1.482 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 1.482 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.3716 | 371.75 | 2368.64 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 62.69 | 0.0000 | Y | 27.88 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.8021 | 139.41 | 1227.05 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.61 | 0.0000 | Y | 16.72 |
Interior Lighting Total | 7.0345 | 511.15 | 3595.70 | 44.60 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 51.74 | 51.74 | 2.05 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.06 | 63.95 | 24.04 | |
Exterior Lighting Total | 2213.72 | 26.09 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 65994.03 | 51335.44 | 14658.59 | 0.78 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28531.88 | 22311.36 | 6220.52 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 63595.3 | 11.25 | 11.20 | ||||
PSZ-AC_2:2 COOLING COIL | 27483.6 | 11.40 | 11.34 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 174824.81 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 124671.96 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 3.32 | 3549.17 | 1070.05 | 1.00 | 1.25 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.45 | 1549.99 | 1070.05 | 1.00 | 1.37 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 37306.73 | 44768.07 | 120.43 | 2.764 | 3.317 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00867 | 27.20 | 0.00701 | 1.331 | 0.00 |
KITCHEN | 19387.31 | 23264.77 | 166.89 | 1.207 | 1.449 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 26.00 | 25.99 | 0.00896 | 18.12 | 0.00699 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 11768.42 | 14122.11 | 37.99 | 0.512 | 1.331 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 1.331 | 0.00 |
KITCHEN | 3061.91 | 3674.30 | 26.36 | 0.121 | 1.217 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00746 | -41.90 | 0.00006 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.32 | 3.32 | 1.33 | 1.33 | 3.3168 | 3.3168 | 3.3168 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.45 | 1.45 | 1.22 | 1.22 | 1.4485 | 1.4485 | 1.4485 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 65994.030 | 51335.436 | 3.316840 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 32997.01 | 28729.02 | 2.211227 | 25.36 | 16.28 | 0.00800035 | 11.91 | 10.04 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 60.2099 | 23.99 | 0.00866748 | 45.9582 | 37268.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 174824.808 | 174824.808 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 174824.81 | 174824.81 | 3.316838 | -4.25 | -4.25 | 0.00479641 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 40.1400 | 21.00 | 0.00796946 | 50.7214 | 11767.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28531.880 | 22311.360 | 1.448520 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 14265.94 | 13888.01 | 0.965680 | 27.26 | 16.27 | 0.00720364 | 11.91 | 10.04 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 126.0254 | 25.98 | 0.00906069 | 42.6336 | 18857.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 124671.959 | 124671.959 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | 124671.96 | 124671.96 | 1.448522 | -32.25 | -32.25 | 0.00124949 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 84.0168 | 19.00 | 0.00747845 | 53.9188 | 2093.83 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 65994.030 | 51335.436 | 3.316840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7122 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.316838 | 3.93191051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 32997.01 | 28729.02 | 1.0000 | 2.62127498 | 2.211227 | 25.36 | 16.28 | 0.00800035 | 45866.1 | 11.91 | 10.04 | 0.00700000 | 29634.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32997.01 | 27.40 | 0.00700714 | 16.15 | 1.33137743 | 60.2099 | 23.99 | 0.00866748 | 23.99 | 0.00866748 | 45.9582 | 37268.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 174824.808 | 174824.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.316838 | 3.93191051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 174824.81 | 174824.81 | 1.0000 | 3.93191051 | 3.316838 | -4.25 | -4.25 | 0.00479641 | 7689.0 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 174824.81 | -41.90 | 0.00006450 | -41.90 | 1.33137743 | 40.1400 | 21.00 | 0.00796946 | 21.00 | 0.00796946 | 50.7214 | 11767.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28531.880 | 22311.360 | 1.448520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2312 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.448522 | 1.71713467 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | Sensible | 14265.94 | 13888.01 | 1.0000 | 1.14475502 | 0.965680 | 27.26 | 16.27 | 0.00720364 | 45773.2 | 11.91 | 10.04 | 0.00700000 | 29632.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14265.94 | 27.40 | 0.00700714 | 16.15 | 1.21700195 | 126.0254 | 25.94 | 0.00906069 | 25.98 | 0.00906069 | 42.6336 | 18857.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 124671.959 | 124671.959 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.448522 | 1.71713467 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | Sensible | 124671.96 | 124671.96 | 1.0000 | 1.71713467 | 1.448522 | -32.25 | -32.25 | 0.00124949 | -29359.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 124671.96 | -41.90 | 0.00006450 | -41.90 | 1.21700195 | 84.0168 | 18.45 | 0.00747845 | 19.00 | 0.00747845 | 53.9188 | 2093.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.32 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.45 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4050.50 | 6020.50 | 3246.83 |
KITCHEN | 5499.67 | 6108.67 | 4607.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5602.17 | 7068.83 | 4709.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 55.50 | 0.33 | 0.17 | 0.00 |
KITCHEN | 0.00 | 29.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 55.50 | 30.17 | 0.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.404 | 0.604 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.784 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.092 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 7.965 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36072112.43 | 0.00 | 36072112.43 | 4905875.71 | 40977988.14 | 41986318.57 | 1454.98 | 6456.21 | 848.81 | 263.31 |
KITCHEN | 26970123.84 | 0.00 | 26970123.84 | 105934.74 | 27076058.57 | 38379373.44 | 8695.89 | 62.35 | 1.76 | 245.77 |
Total Facility | 63042236.27 | 0.00 | 63042236.27 | 5011810.45 | 68054046.72 | 80365692.01 | 8697.01 | 6456.21 | 850.04 | 381.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3651 | 0.0000 | 1.3651 | 0.1870 | 1.5522 | 1.3314 | 0.00 | 6339.12 | 847.88 |
KITCHEN | 1.0221 | 0.0000 | 1.0221 | 0.0025 | 1.0246 | 1.2170 | 7125.22 | 61.71 | 0.08 |
Total Facility | 2.3872 | 0.0000 | 2.3872 | 0.1895 | 2.5768 | 2.5484 | 7125.22 | 6339.12 | 847.96 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50691197.29 | 0.00 | 50691197.29 | 41986318.57 | 1449.98 | 0.83 | 7309.18 | 263.31 |
PSZ-AC_2:2 | 37900191.72 | 0.00 | 37900191.72 | 38379373.44 | 1455.86 | 0.09 | 7304.05 | 245.77 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9184 | 0.0000 | 1.9184 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4363 | 0.0000 | 1.4363 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 856.30 | 142.51 | 6451.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 24.78 | 870.49 | 6537.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.3074 | 2.0886 | 1.8713 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.4779 | 1.4323 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
Electricity:Building | 487.20 | 2437.13 | 01-JAN-01:20 | 28923.90 | 02-JAN-11:10 |
Electricity:Zone:DINING | 152.98 | 560.03 | 01-JAN-01:20 | 9015.74 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 480.26 | 2300.85 | 01-JAN-01:20 | 26780.79 | 02-JAN-11:10 |
InteriorLights:Electricity | 44.60 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 27.88 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 44.60 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 44.60 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 27.88 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 44.60 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 334.21 | 1877.10 | 01-JAN-01:20 | 19908.15 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 310.55 | 1710.81 | 01-JAN-01:10 | 16905.18 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 34.83 | 595.55 | 11-JAN-23:30 | 2772.60 | 26-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 103.90 | 741.00 | 12-JAN-01:10 | 5839.27 | 17-JUL-18:50 |
LowTempRefrigeration:Refrigeration:Electricity | 10.33 | 0.00 | 01-JAN-11:10 | 1004.37 | 30-JUN-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 17.57 | 509.05 | 12-JAN-06:00 | 637.09 | 20-JUN-13:10 |
ElectricityPurchased:Facility | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
ElectricityPurchased:Plant | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
Cogeneration:ElectricityPurchased | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
General:Cogeneration:ElectricityPurchased | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
ElectricityNet:Plant | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
Cogeneration:ElectricityNet | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
General:Cogeneration:ElectricityNet | 722.59 | 3341.07 | 30-MAY-03:00 | 44774.72 | 22-JUL-11:00 |
Electricity:HVAC | 105.41 | 0.00 | 01-JAN-01:10 | 17199.29 | 29-JUL-18:20 |
Fans:Electricity | 89.26 | 0.00 | 01-JAN-01:10 | 4742.42 | 12-JAN-07:10 |
General:Fans:Electricity | 89.26 | 0.00 | 01-JAN-01:10 | 4742.42 | 12-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 16.15 | 0.00 | 01-JAN-00:10 | 13713.07 | 29-JUL-18:20 |
General:Cooling:Electricity | 16.15 | 0.00 | 01-JAN-00:10 | 13713.07 | 29-JUL-18:20 |
ExteriorLights:Electricity | 26.09 | 0.00 | 01-JAN-11:20 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 26.09 | 0.00 | 01-JAN-11:20 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.55 | 0.00 | 01-JAN-01:10 | 4742.13 | 26-MAY-06:40 |
Water Heater:WaterSystems:Electricity | 75.55 | 0.00 | 01-JAN-01:10 | 4742.13 | 26-MAY-06:40 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 17-APR-23:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 17-APR-23:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2481.78 | 2758.01 | 18-APR-00:10 | 274452.69 | 12-JAN-07:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 1563.95 | 0.00 | 01-JAN-01:10 | 229890.73 | 12-JAN-07:10 |
Heating:NaturalGas | 1563.95 | 0.00 | 01-JAN-01:10 | 229890.73 | 12-JAN-07:10 |
General:Heating:NaturalGas | 1563.95 | 0.00 | 01-JAN-01:10 | 229890.73 | 12-JAN-07:10 |
NaturalGas:Plant | 448.04 | 947.76 | 01-JAN-00:10 | 37895.83 | 09-JAN-19:50 |
WaterSystems:NaturalGas | 448.04 | 947.76 | 01-JAN-00:10 | 37895.83 | 09-JAN-19:50 |
Water Heater:WaterSystems:NaturalGas | 448.04 | 947.76 | 01-JAN-00:10 | 37895.83 | 09-JAN-19:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAY-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2278.62 | 2929.99 | 12-JAN-01:10 | 229492.16 | 12-JAN-07:10 |
EnergyTransfer:Building | 578.39 | 1464.99 | 12-JAN-01:10 | 50946.85 | 09-NOV-15:10 |
EnergyTransfer:Zone:KITCHEN | 364.58 | 1464.99 | 12-JAN-01:10 | 20918.19 | 07-OCT-10:50 |
Refrigeration:EnergyTransfer | 128.09 | 2621.03 | 12-JAN-23:10 | 7834.84 | 30-JUN-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 64.05 | 1310.51 | 12-JAN-23:10 | 3917.42 | 30-JUN-03:20 |
General:Refrigeration:EnergyTransfer | 64.05 | 1310.51 | 12-JAN-23:10 | 3917.42 | 30-JUN-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 64.05 | 1310.51 | 12-JAN-23:10 | 3917.42 | 30-JUN-03:20 |
EnergyTransfer:Plant | 389.07 | 1464.99 | 12-JAN-01:10 | 23244.13 | 10-MAY-18:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 11.85 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 52.20 | 1305.27 | 12-JAN-06:00 | 2238.70 | 20-JUN-13:10 |
EnergyTransfer:Zone:DINING | 213.81 | 0.00 | 01-JAN-01:10 | 43515.59 | 12-JAN-04:20 |
Heating:EnergyTransfer | 36.20 | 0.00 | 01-JAN-00:30 | 31040.49 | 12-JAN-04:10 |
Heating:EnergyTransfer:Zone:DINING | 36.12 | 0.00 | 01-JAN-00:30 | 31040.49 | 12-JAN-04:10 |
General:Heating:EnergyTransfer | 36.20 | 0.00 | 01-JAN-00:30 | 31040.49 | 12-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:DINING | 36.12 | 0.00 | 01-JAN-00:30 | 31040.49 | 12-JAN-04:10 |
Cooling:EnergyTransfer | 478.14 | 0.00 | 01-JAN-01:10 | 39487.12 | 29-JUL-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 177.69 | 0.00 | 01-JAN-01:10 | 24496.65 | 13-APR-23:20 |
General:Cooling:EnergyTransfer | 478.14 | 0.00 | 01-JAN-01:10 | 39487.12 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 177.69 | 0.00 | 01-JAN-01:10 | 24496.65 | 13-APR-23:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.08 | 0.00 | 01-JAN-00:10 | 2353.12 | 13-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.08 | 0.00 | 01-JAN-00:10 | 2353.12 | 13-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 300.45 | 0.00 | 01-JAN-01:10 | 17582.60 | 07-OCT-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 300.45 | 0.00 | 01-JAN-01:10 | 17582.60 | 07-OCT-10:50 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 325.02 | 0.00 | 01-JAN-01:10 | 20743.00 | 18-JAN-19:10 |
PlantLoopHeatingDemand:Plant | 325.02 | 0.00 | 01-JAN-01:10 | 20743.00 | 18-JAN-19:10 |
WaterSystems:PlantLoopHeatingDemand | 325.02 | 0.00 | 01-JAN-01:10 | 20743.00 | 18-JAN-19:10 |
General:WaterSystems:PlantLoopHeatingDemand | 325.02 | 0.00 | 01-JAN-01:10 | 20743.00 | 18-JAN-19:10 |
EnergyTransfer:HVAC | 1311.17 | 0.00 | 01-JAN-01:10 | 183912.59 | 12-JAN-07:10 |
HeatingCoils:EnergyTransfer | 1251.16 | 0.00 | 01-JAN-01:10 | 183912.59 | 12-JAN-07:10 |
CoolingCoils:EnergyTransfer | 60.01 | 0.00 | 01-JAN-00:10 | 57647.47 | 29-JUL-18:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 325.02 | 0.00 | 01-JAN-01:10 | 20743.00 | 18-JAN-19:10 |
WaterUse:WaterSystems:EnergyTransfer | 325.02 | 0.00 | 01-JAN-01:10 | 20743.00 | 18-JAN-19:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 36.121 | -177.690 | 0.000 | 0.000 | 235.911 | 27.875 | 93.832 | 38.167 | 0.000 | 0.139 | 0.002 | 0.000 | -32.084 | 0.000 | -133.450 | -88.822 |
KITCHEN | 0.000 | 0.000 | 0.081 | -300.440 | 0.000 | 0.000 | 6.444 | 16.725 | 273.146 | 0.000 | 0.000 | 0.000 | 6.744 | 0.000 | 0.000 | 0.000 | -2.700 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.667 | 13.523 | 0.000 | 0.000 | 0.000 | -27.191 | -0.001 |
Total Facility | 0.000 | 0.000 | 36.203 | -478.129 | 0.000 | 0.000 | 242.355 | 44.600 | 366.978 | 38.167 | 0.000 | 13.807 | 20.269 | 0.000 | -32.084 | 0.000 | -163.342 | -88.824 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-JAN-00:01 | 0.00 | 0.00 | 0.00 | -83891.23 | 0.00 | 0.00 | 1157.79 | 337.32 | 540.00 | 0.00 | 0.00 | 0.00 | 85975.85 | 0.00 | -3439.98 | 0.00 | -679.76 | 0.00 |
KITCHEN | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | -60790.61 | 0.00 | 0.00 | 26.93 | 30.01 | 6476.03 | 0.00 | 0.00 | 0.00 | 54257.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JUL-03:01 | 0.00 | 0.00 | 0.00 | -102918.03 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 563.24 | 98594.67 | 0.00 | -285.87 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-FEB-04:01 | 0.00 | 0.00 | 119828.71 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1918.17 | 0.00 | -685.46 | -118205.12 |
KITCHEN | 29-NOV-05:02 | 0.00 | 0.00 | 23235.36 | 0.00 | 0.00 | 0.00 | 28.75 | 30.01 | 6476.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29770.15 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-04:01 | 0.00 | 0.00 | 119828.71 | 0.00 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 1270.13 | 0.00 | 0.00 | -1918.17 | 0.00 | -1132.30 | -122094.36 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.3168 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.3168 | 0.4014 | 1.0000 | Not calculated | 1.3314 | 0.4014 | ||
PSZ-AC_2:2 | 1.4485 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.4485 | 0.1261 | 1.0000 | Not calculated | 0.1826 | 0.1261 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.3168 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.3168 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.4014 | ||
PSZ-AC_2:2 | 1.4485 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.4485 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1261 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3168 | 3.3168 | 3.3168 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4485 | 1.4485 | 1.4485 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.3168 | 3.3168 | 3.3168 | 3.3168 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.4485 | 1.4485 | 1.4485 | 1.4485 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3168 | 3.3168 | 3.3168 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4485 | 1.4485 | 1.4485 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.3168 | 3.3168 | 3.3168 | 3.3168 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.4485 | 1.4485 | 1.4485 | 1.4485 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1563.95 | 229890.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 16.15 | 13713.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 44.60 | 2883.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 26.09 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 89.26 | 4742.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.55 | 4742.13 | 448.04 | 37895.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.33 | 1004.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.57 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 470.50 | 722.59 |
Natural Gas | 469.79 | 2481.78 |
Additional | 0.00 | 0.00 |
Total | 940.28 | 3204.37 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 87.25 |
Space Heating | 0.00 |
Space Cooling | 31.59 |
Fans (All) | 174.63 |
Service Water Heating | 147.80 |
Receptacle Equipment | 852.31 |
Miscellaneous (All) | 1413.65 |
Subtotal | 1413.65 |
Natural Gas [MJ/m2] | |
Space Heating | 3059.64 |
Service Water Heating | 876.54 |
Miscellaneous (All) | 4855.25 |
Subtotal | 4855.25 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.39 |
Space Heating | 48.81 |
Space Cooling | 0.50 |
Fans (All) | 2.79 |
Service Water Heating | 16.34 |
Receptacle Equipment | 28.26 |
Miscellaneous | 1.92 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8463.17 | 296.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 7985.33 | 448.83 | 270.33 | 55.50 | 0.00 |
Min | 7985.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 448.83 | 270.33 | 55.50 | 0.00 |
Average | 8402.83 | 248.56 | 90.11 | 18.50 | 0.00 |
Sum | 25208.50 | 745.67 | 270.33 | 55.50 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7980.17 | 779.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 8123.17 | 537.83 | 78.00 | 20.17 | 0.83 |
Min | 7980.17 | 11.67 | 0.00 | 0.00 | 0.00 |
Max | 8748.33 | 779.83 | 78.00 | 20.17 | 0.83 |
Average | 8283.89 | 443.11 | 26.00 | 6.72 | 0.28 |
Sum | 24851.67 | 1329.33 | 78.00 | 20.17 | 0.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 822341.33 | 1880.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 17622.83 | 1610.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822341.33 | 1880.67 | 0.00 | 0.00 | 0.00 |
Average | 279988.06 | 1163.61 | 0.00 | 0.00 | 0.00 |
Sum | 839964.17 | 3490.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205592E+10 | 83893.26 | 12-JAN-00:01 | -36.1 | -36.2 | 0.119977E+11 | 10740.97 | 21-JAN-19:49 | -2.1 | -3.3 |
February | 0.302792E+10 | 75203.27 | 27-FEB-00:01 | -30.3 | -30.4 | 0.108637E+11 | 10740.98 | 18-FEB-19:10 | -30.3 | -30.4 |
March | 0.681443E+10 | 73239.21 | 01-MAR-00:01 | -28.9 | -29.2 | 0.121369E+11 | 10741.00 | 04-MAR-19:00 | -13.3 | -14.5 |
April | 0.171673E+11 | 53640.29 | 02-APR-23:01 | -15.8 | -17.1 | 0.118062E+11 | 13051.63 | 22-APR-18:19 | 12.43 | 5.32 |
May | 0.247586E+11 | 28759.56 | 21-MAY-04:01 | 1.97 | 0.40 | 0.135426E+11 | 14049.91 | 13-MAY-18:10 | 1.97 | 0.40 |
June | 0.275082E+11 | 55236.21 | 23-JUN-03:01 | 13.40 | 8.88 | 0.143248E+11 | 14050.85 | 17-JUN-18:00 | 13.40 | 8.88 |
July | 0.295513E+11 | 58802.06 | 22-JUL-03:01 | 15.22 | 12.39 | 0.147349E+11 | 14052.56 | 08-JUL-18:10 | 15.22 | 12.39 |
August | 0.287120E+11 | 50733.75 | 11-AUG-03:01 | 11.10 | 6.92 | 0.144386E+11 | 14051.46 | 12-AUG-18:49 | 17.48 | 15.07 |
September | 0.217327E+11 | 32164.36 | 28-SEP-23:01 | -1.2 | -2.4 | 0.121688E+11 | 14050.00 | 02-SEP-18:19 | -1.2 | -2.4 |
October | 0.121434E+11 | 55063.33 | 26-OCT-23:01 | -16.7 | -17.3 | 0.120027E+11 | 10741.33 | 07-OCT-18:00 | -16.7 | -17.3 |
November | 0.218619E+10 | 73041.44 | 29-NOV-00:01 | -28.8 | -29.0 | 0.116018E+11 | 10741.00 | 04-NOV-18:10 | -28.8 | -29.0 |
December | 0.203332E+10 | 74993.75 | 15-DEC-00:01 | -30.1 | -30.2 | 0.119917E+11 | 10740.98 | 16-DEC-19:00 | -16.7 | -17.0 |
Annual Sum or Average | 0.177691E+12 | 0.151611E+12 | ||||||||
Minimum of Months | 0.203332E+10 | 28759.56 | -36.1 | -36.2 | 0.108637E+11 | 10740.97 | -30.3 | -30.4 | ||
Maximum of Months | 0.295513E+11 | 83893.26 | 15.22 | 12.39 | 0.147349E+11 | 14052.56 | 17.48 | 15.07 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222846E+11 | 54694.10 | 13-JAN-05:01 | -32.9 | -33.0 | 0.103883E+11 | 6815.12 | 30-JAN-11:50 | -24.5 | -24.9 |
February | 0.200005E+11 | 52610.88 | 28-FEB-05:01 | -26.1 | -26.3 | 0.938360E+10 | 6815.12 | 28-FEB-11:09 | -25.3 | -25.6 |
March | 0.235692E+11 | 51531.57 | 03-MAR-05:01 | -25.6 | -26.1 | 0.103914E+11 | 6816.15 | 20-MAR-10:00 | 5.00 | 1.39 |
April | 0.249939E+11 | 43023.81 | 03-APR-04:01 | -21.1 | -21.6 | 0.100771E+11 | 6868.97 | 22-APR-10:00 | 12.80 | 6.00 |
May | 0.265409E+11 | 46633.74 | 14-MAY-03:01 | 7.80 | 4.03 | 0.105150E+11 | 6930.38 | 31-MAY-10:20 | 17.77 | 10.12 |
June | 0.264513E+11 | 51212.44 | 07-JUN-03:01 | 6.52 | 5.05 | 0.102381E+11 | 6930.41 | 20-JUN-10:00 | 18.90 | 12.97 |
July | 0.280966E+11 | 49373.13 | 31-JUL-03:01 | 7.20 | 6.67 | 0.105768E+11 | 6930.42 | 24-JUL-10:20 | 7.20 | 6.67 |
August | 0.284423E+11 | 49468.90 | 11-AUG-03:01 | 11.10 | 6.92 | 0.105624E+11 | 6930.42 | 08-AUG-10:00 | 11.10 | 6.92 |
September | 0.276428E+11 | 35988.62 | 08-SEP-03:42 | 2.38 | 1.37 | 0.101176E+11 | 6891.14 | 19-SEP-10:00 | 11.70 | 6.96 |
October | 0.269045E+11 | 45114.51 | 31-OCT-04:01 | -17.9 | -18.4 | 0.103970E+11 | 6865.63 | 04-OCT-10:00 | -17.9 | -18.4 |
November | 0.229500E+11 | 55258.22 | 28-NOV-05:01 | -27.7 | -27.9 | 0.100531E+11 | 6815.12 | 01-NOV-10:09 | -27.7 | -27.9 |
December | 0.225731E+11 | 60514.84 | 15-DEC-05:01 | -33.2 | -33.3 | 0.103882E+11 | 6815.12 | 01-DEC-11:09 | -33.2 | -33.3 |
Annual Sum or Average | 0.300450E+12 | 0.123088E+12 | ||||||||
Minimum of Months | 0.200005E+11 | 35988.62 | -33.2 | -33.3 | 0.938360E+10 | 6815.12 | -33.2 | -33.3 | ||
Maximum of Months | 0.284423E+11 | 60514.84 | 11.10 | 6.92 | 0.105768E+11 | 6930.42 | 18.90 | 12.97 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 | -29.2 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 |
April | 0.00 | 0.00 | 01-APR-00:02 | -11.7 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 | 2.18 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 | 8.14 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 | 11.83 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 | 0.12 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 |
November | 0.00 | 0.00 | 01-NOV-00:02 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908951E+10 | 114504.39 | 02-JAN-04:01 | -15.1 |
February | 0.649510E+10 | 119831.13 | 06-FEB-04:01 | -12.3 |
March | 0.277698E+10 | 100186.79 | 06-MAR-04:01 | -20.0 |
April | 0.548120E+09 | 65225.06 | 04-APR-03:01 | -10.5 |
May | 19930134.48 | 20402.91 | 27-MAY-04:01 | 0.00 |
June | 1314687.97 | 7641.41 | 02-JUN-04:04 | 3.68 |
July | 658053.07 | 6624.24 | 06-JUL-04:03 | 7.88 |
August | 2072333.02 | 10848.24 | 20-AUG-04:03 | 5.40 |
September | 24477954.86 | 20596.05 | 28-SEP-04:01 | -1.8 |
October | 0.740910E+09 | 67282.58 | 30-OCT-03:01 | -13.5 |
November | 0.640732E+10 | 96868.36 | 29-NOV-05:01 | -28.9 |
December | 0.100148E+11 | 111924.85 | 29-DEC-04:01 | -15.7 |
Annual Sum or Average | 0.361212E+11 | |||
Minimum of Months | 658053.07 | 6624.24 | -28.9 | |
Maximum of Months | 0.100148E+11 | 119831.13 | 7.88 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16131394.26 | 21178.06 | 13-JAN-05:02 | -32.9 |
February | 13708805.57 | 16870.33 | 20-FEB-05:02 | -23.6 |
March | 12366722.14 | 17087.63 | 27-MAR-04:02 | -21.7 |
April | 4140590.69 | 15845.78 | 03-APR-04:02 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 91528.60 | 1525.48 | 28-SEP-04:04 | -1.8 |
October | 4490988.34 | 13383.23 | 25-OCT-04:03 | -11.1 |
November | 14108713.25 | 23267.63 | 29-NOV-05:02 | -28.9 |
December | 16503809.50 | 20473.86 | 28-DEC-05:02 | -28.2 |
Annual Sum or Average | 81542552.35 | |||
Minimum of Months | 0.00 | 0.00 | -32.9 | |
Maximum of Months | 16503809.50 | 23267.63 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:02 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:02 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.303178E+10 | 2023.86 | 02-JAN-10:09 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.238987E+10 | 2023.86 | 01-FEB-16:19 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.235294E+10 | 2023.86 | 01-MAR-17:30 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.193820E+10 | 2023.86 | 01-APR-19:40 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.190176E+10 | 2023.86 | 04-MAY-20:30 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.178067E+10 | 1908.93 | 02-JUN-20:00 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.184026E+10 | 1936.85 | 26-JUL-20:00 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.201830E+10 | 2023.86 | 08-AUG-20:30 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.215619E+10 | 2023.86 | 01-SEP-19:30 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.250717E+10 | 2023.86 | 02-OCT-18:19 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.275125E+10 | 2023.86 | 01-NOV-16:30 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.320691E+10 | 2023.86 | 01-DEC-10:09 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.278753E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.178067E+10 | 1908.93 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.320691E+10 | 2023.86 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141271E+10 | 859.87 | 02-JAN-10:09 | 0.263757E+11 | 16905.18 | 01-JAN-11:09 |
February | 0.127972E+10 | 859.87 | 01-FEB-10:09 | 0.238233E+11 | 16905.18 | 01-FEB-11:09 |
March | 0.143703E+10 | 859.87 | 01-MAR-10:09 | 0.263759E+11 | 16905.18 | 01-MAR-11:09 |
April | 0.137275E+10 | 859.87 | 01-APR-16:10 | 0.255250E+11 | 16905.18 | 01-APR-10:09 |
May | 0.142487E+10 | 859.87 | 01-MAY-09:09 | 0.263758E+11 | 16905.18 | 01-MAY-10:09 |
June | 0.138882E+10 | 859.87 | 01-JUN-09:09 | 0.255251E+11 | 16905.18 | 01-JUN-10:09 |
July | 0.140898E+10 | 859.87 | 01-JUL-16:10 | 0.263757E+11 | 16905.18 | 01-JUL-10:09 |
August | 0.143703E+10 | 859.87 | 01-AUG-09:09 | 0.263759E+11 | 16905.18 | 01-AUG-10:09 |
September | 0.137310E+10 | 859.87 | 01-SEP-09:09 | 0.255250E+11 | 16905.18 | 01-SEP-10:09 |
October | 0.141254E+10 | 859.87 | 02-OCT-09:09 | 0.263757E+11 | 16905.18 | 01-OCT-10:09 |
November | 0.136789E+10 | 859.87 | 01-NOV-09:09 | 0.255249E+11 | 16905.18 | 01-NOV-10:09 |
December | 0.140915E+10 | 859.87 | 01-DEC-10:09 | 0.263757E+11 | 16905.18 | 01-DEC-11:09 |
Annual Sum or Average | 0.167246E+11 | 0.310554E+12 | ||||
Minimum of Months | 0.127972E+10 | 859.87 | 0.238233E+11 | 16905.18 | ||
Maximum of Months | 0.143703E+10 | 859.87 | 0.263759E+11 | 16905.18 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.303178E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202258E+11 |
February | 0.272721E+11 | 0.238987E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167437E+11 |
March | 0.305458E+11 | 0.235294E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156028E+11 |
April | 0.292871E+11 | 0.193820E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900967E+10 |
May | 0.303219E+11 | 0.190176E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477332E+10 |
June | 0.295292E+11 | 0.178067E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40515066.87 | 0.271629E+10 |
July | 0.300798E+11 | 0.184026E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87735091.90 | 0.232224E+10 |
August | 0.305458E+11 | 0.201830E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11231165.46 | 0.350917E+10 |
September | 0.292871E+11 | 0.215619E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636647E+10 |
October | 0.300980E+11 | 0.250717E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119745E+11 |
November | 0.290996E+11 | 0.275125E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191578E+11 |
December | 0.300798E+11 | 0.320691E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210487E+11 |
Annual Sum or Average | 0.356244E+12 | 0.278753E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139481E+09 | 0.133450E+12 |
Minimum of Months | 0.272721E+11 | 0.178067E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232224E+10 |
Maximum of Months | 0.305458E+11 | 0.320691E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87735091.90 | 0.210487E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.141271E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287559E+09 |
February | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238024E+09 |
March | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371225E+09 |
April | 0.786997E+09 | 0.137275E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365575E+09 |
May | 0.814802E+09 | 0.142487E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242452E+09 |
June | 0.793501E+09 | 0.138882E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 71742.10 | 0.150070E+09 |
July | 0.808298E+09 | 0.140898E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 378881.56 | 0.113341E+09 |
August | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145226E+09 |
September | 0.786997E+09 | 0.137310E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143929E+09 |
October | 0.808786E+09 | 0.141254E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311705E+09 |
November | 0.781956E+09 | 0.136789E+10 | 0.207262E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112529E+09 |
December | 0.808298E+09 | 0.140915E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218710E+09 |
Annual Sum or Average | 0.957291E+10 | 0.167246E+11 | 0.252169E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 450623.67 | 0.270034E+10 |
Minimum of Months | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112529E+09 |
Maximum of Months | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 378881.56 | 0.371225E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231128E+10 | 30333208.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160949E+10 | 0.559497E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101140E+10 | 0.248566E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561556E+09 | 0.380968E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362999E+09 | 0.437130E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200303E+09 | 0.482095E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252727E+09 | 0.464420E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444649E+09 | 0.352919E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786066E+09 | 0.202592E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874916E+09 | 0.805588E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261955E+10 | 0.104924E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263249E+10 | 3471451.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136674E+11 | 0.271907E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200303E+09 | 3471451.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263249E+10 | 0.482095E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2023.86 | 02-JAN-10:09 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 27668.11 | 12-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2023.86 | 01-FEB-16:19 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 23881.58 | 27-FEB-12:05 |
March | 30255.31 | 04-MAR-19:10 | 2023.86 | 01-MAR-17:30 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 19645.15 | 01-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2023.86 | 01-APR-19:40 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 13372.74 | 01-APR-18:53 |
May | 30255.31 | 06-MAY-18:10 | 2023.86 | 04-MAY-20:30 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 6990.51 | 26-MAY-20:00 |
June | 30255.31 | 03-JUN-18:10 | 1908.93 | 02-JUN-20:00 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.48 | 20-JUN-17:53 | 4856.84 | 24-JUN-19:00 |
July | 30255.31 | 01-JUL-18:10 | 1936.85 | 26-JUL-20:00 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1847.51 | 29-JUL-17:10 | 4402.81 | 01-JUL-19:00 |
August | 30255.31 | 05-AUG-18:10 | 2023.86 | 08-AUG-20:30 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 611.00 | 11-AUG-17:05 | 5906.48 | 30-AUG-19:53 |
September | 30255.31 | 02-SEP-18:10 | 2023.86 | 01-SEP-19:30 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 10013.21 | 30-SEP-18:55 |
October | 30255.31 | 07-OCT-18:10 | 2023.86 | 02-OCT-18:19 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 17192.21 | 30-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2023.86 | 01-NOV-16:30 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 22641.95 | 30-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 2023.86 | 01-DEC-10:09 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 25522.95 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 1908.93 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.81 | |||||
Maximum of Months | 30255.31 | 2023.86 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1847.51 | 27668.11 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 859.87 | 02-JAN-10:09 | 13642.30 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1937.79 | 29-JAN-00:01 |
February | 813.01 | 04-FEB-19:10 | 859.87 | 01-FEB-10:09 | 13642.30 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1166.17 | 25-FEB-01:00 |
March | 813.01 | 04-MAR-19:10 | 859.87 | 01-MAR-10:09 | 13642.30 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 870.60 | 25-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 859.87 | 01-APR-16:10 | 13642.30 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 947.06 | 07-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 859.87 | 01-MAY-09:09 | 13642.30 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 665.09 | 26-MAY-02:00 |
June | 813.01 | 03-JUN-18:10 | 859.87 | 01-JUN-09:09 | 13642.30 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 13.48 | 30-JUN-15:00 | 684.91 | 25-JUN-01:30 |
July | 813.01 | 01-JUL-18:10 | 859.87 | 01-JUL-16:10 | 13642.30 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 39.33 | 21-JUL-16:00 | 421.77 | 30-JUL-01:00 |
August | 813.01 | 05-AUG-18:10 | 859.87 | 01-AUG-09:09 | 13642.30 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 509.15 | 30-AUG-01:00 |
September | 813.01 | 02-SEP-18:10 | 859.87 | 01-SEP-09:09 | 13642.30 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 350.69 | 30-SEP-02:00 |
October | 813.01 | 07-OCT-18:10 | 859.87 | 02-OCT-09:09 | 13642.30 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 849.25 | 21-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 859.87 | 01-NOV-09:09 | 13642.30 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 684.81 | 10-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 859.87 | 01-DEC-10:09 | 13642.30 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 700.18 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 350.69 | ||||||
Maximum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 39.33 | 1937.79 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.57 | 13-JAN-01:00 | 994.05 | 30-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2131.02 | 17-FEB-05:00 | 3062.17 | 27-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.59 | 16-MAR-06:55 | 6360.51 | 26-MAR-13:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.69 | 13-APR-01:50 | 6445.05 | 27-APR-13:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.97 | 22-MAY-03:30 | 6200.45 | 31-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.16 | 09-JUN-02:50 | 6481.52 | 08-JUN-12:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.98 | 11-JUL-24:00 | 6487.61 | 06-JUL-12:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.25 | 22-AUG-05:10 | 6194.12 | 09-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.64 | 19-SEP-01:35 | 4508.71 | 07-SEP-12:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1620.01 | 31-OCT-07:55 | 2627.61 | 12-OCT-13:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2352.23 | 18-NOV-03:53 | 1402.52 | 06-NOV-14:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.49 | 28-DEC-10:00 | 345.89 | 24-DEC-12:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.98 | 345.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.49 | 6487.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 83893.26 | 12-JAN-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.76 |
February | 75203.27 | 27-FEB-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73239.21 | 01-MAR-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.68 |
April | 53640.29 | 02-APR-23:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.09 |
May | 28759.56 | 21-MAY-04:01 | 0.00 | 800.29 | 28800.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.86 |
June | 55236.21 | 23-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.98 |
July | 58802.06 | 22-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.21 |
August | 50733.75 | 11-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.78 |
September | 32164.36 | 28-SEP-23:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.24 |
October | 55063.33 | 26-OCT-23:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.06 |
November | 73041.44 | 29-NOV-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74993.75 | 15-DEC-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28759.56 | 0.00 | 800.29 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83893.26 | 16808.50 | 3373.19 | 28800.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54694.10 | 13-JAN-05:01 | 406.51 | 270.10 | 53922.80 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52610.88 | 28-FEB-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51531.57 | 03-MAR-05:01 | 406.51 | 270.10 | 53922.80 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 105.60 |
April | 43023.81 | 03-APR-04:01 | 361.34 | 240.09 | 47931.38 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 118.95 |
May | 46633.74 | 14-MAY-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 |
June | 51212.44 | 07-JUN-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 |
July | 49373.13 | 31-JUL-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 203.91 |
August | 49468.90 | 11-AUG-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 299.67 |
September | 35988.62 | 08-SEP-03:42 | 0.00 | 180.07 | 16984.92 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 154.68 |
October | 45114.51 | 31-OCT-04:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 161.95 |
November | 55258.22 | 28-NOV-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 60514.84 | 15-DEC-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35988.62 | 0.00 | 180.07 | 16984.92 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60514.84 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 299.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.26 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.17 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1928.15 | 0.00 |
April | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.43 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.59 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.94 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.42 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.94 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.21 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.71 | 0.00 |
November | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.47 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2277.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2277.88 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.635009E+11 | 39149.78 | 03-JAN-11:09 | 0.365092E+12 | 274452.69 | 12-JAN-07:19 |
February | 0.561114E+11 | 36284.64 | 27-FEB-11:20 | 0.307515E+12 | 260929.36 | 27-FEB-07:40 |
March | 0.605701E+11 | 35918.86 | 01-MAR-11:20 | 0.280450E+12 | 231461.79 | 01-MAR-07:40 |
April | 0.565042E+11 | 35647.15 | 03-APR-10:09 | 0.160606E+12 | 196379.29 | 03-APR-06:19 |
May | 0.578950E+11 | 37150.60 | 31-MAY-10:00 | 0.941764E+11 | 91737.82 | 27-MAY-08:20 |
June | 0.596384E+11 | 44472.35 | 30-JUN-11:00 | 0.770512E+11 | 60274.18 | 25-JUN-09:00 |
July | 0.641078E+11 | 44774.72 | 22-JUL-10:00 | 0.776686E+11 | 61678.53 | 05-JUL-06:30 |
August | 0.617499E+11 | 40590.19 | 11-AUG-17:49 | 0.810970E+11 | 91839.11 | 31-AUG-06:30 |
September | 0.569370E+11 | 35475.77 | 30-SEP-10:20 | 0.109137E+12 | 113933.90 | 29-SEP-06:40 |
October | 0.605008E+11 | 35735.55 | 28-OCT-10:09 | 0.202836E+12 | 182569.25 | 31-OCT-06:00 |
November | 0.609211E+11 | 36466.02 | 13-NOV-11:09 | 0.345549E+12 | 231971.38 | 29-NOV-07:00 |
December | 0.641542E+11 | 39461.15 | 15-DEC-11:09 | 0.380600E+12 | 254912.02 | 15-DEC-07:10 |
Annual Sum or Average | 0.722591E+12 | 0.248178E+13 | ||||
Minimum of Months | 0.561114E+11 | 35475.77 | 0.770512E+11 | 60274.18 | ||
Maximum of Months | 0.641542E+11 | 44774.72 | 0.380600E+12 | 274452.69 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.444449E+10 | 0.397473E+10 | 0.370015E+11 | 0.00 | 0.882798E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639927E+10 | 0.00 |
February | 0.366959E+10 | 0.285162E+10 | 0.334207E+11 | 0.00 | 0.779851E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579176E+10 | 0.00 |
March | 0.378997E+10 | 0.232108E+10 | 0.370017E+11 | 0.00 | 0.812551E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646817E+10 | 0.00 |
April | 0.331095E+10 | 0.143696E+10 | 0.358080E+11 | 0.00 | 0.691776E+10 | 36657632.61 | 0.00 | 395299.93 | 0.00 | 0.00 | 0.00 | 0.620996E+10 | 0.00 |
May | 0.332663E+10 | 0.829162E+09 | 0.370016E+11 | 0.00 | 0.659724E+10 | 37879553.69 | 0.00 | 0.619890E+09 | 0.00 | 0.00 | 0.00 | 0.642401E+10 | 0.00 |
June | 0.316948E+10 | 0.385401E+09 | 0.358081E+11 | 0.00 | 0.632307E+10 | 36657632.61 | 0.00 | 0.456884E+10 | 0.00 | 0.00 | 0.00 | 0.623893E+10 | 0.00 |
July | 0.324923E+10 | 0.577790E+09 | 0.370015E+11 | 0.00 | 0.657555E+10 | 37879553.69 | 0.00 | 0.706742E+10 | 0.00 | 0.00 | 0.00 | 0.637398E+10 | 0.00 |
August | 0.345533E+10 | 0.117321E+10 | 0.370017E+11 | 0.00 | 0.656276E+10 | 37879553.69 | 0.00 | 0.388026E+10 | 0.00 | 0.00 | 0.00 | 0.645419E+10 | 0.00 |
September | 0.352929E+10 | 0.189491E+10 | 0.358080E+11 | 0.00 | 0.656764E+10 | 36657632.61 | 0.00 | 8232648.97 | 0.00 | 0.00 | 0.00 | 0.620758E+10 | 0.00 |
October | 0.391971E+10 | 0.279659E+10 | 0.370015E+11 | 0.00 | 0.748664E+10 | 37879553.69 | 0.00 | 369290.02 | 0.00 | 0.00 | 0.00 | 0.639675E+10 | 0.00 |
November | 0.411914E+10 | 0.353661E+10 | 0.358078E+11 | 0.00 | 0.850111E+10 | 36657632.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619288E+10 | 0.00 |
December | 0.461606E+10 | 0.431210E+10 | 0.370015E+11 | 0.00 | 0.898080E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639140E+10 | 0.00 |
Annual Sum or Average | 0.445999E+11 | 0.260902E+11 | 0.435663E+12 | 0.00 | 0.892645E+11 | 0.446001E+09 | 0.00 | 0.161454E+11 | 0.00 | 0.00 | 0.00 | 0.755489E+11 | 0.00 |
Minimum of Months | 0.316948E+10 | 0.385401E+09 | 0.334207E+11 | 0.00 | 0.632307E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579176E+10 | 0.00 |
Maximum of Months | 0.461606E+10 | 0.431210E+10 | 0.370017E+11 | 0.00 | 0.898080E+10 | 37879553.69 | 0.00 | 0.706742E+10 | 0.00 | 0.00 | 0.00 | 0.646817E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.285704E+12 | 0.00 | 0.394882E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.235739E+12 | 0.00 | 0.357376E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.200669E+12 | 0.00 | 0.398812E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.836860E+11 | 0.00 | 0.383076E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.149644E+11 | 0.00 | 0.393123E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.160189E+10 | 0.00 | 0.368367E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.137843E+10 | 0.00 | 0.363905E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.519694E+10 | 0.00 | 0.360003E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.359230E+11 | 0.00 | 0.346012E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.126621E+12 | 0.00 | 0.363147E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.270637E+12 | 0.00 | 0.362999E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.301826E+12 | 0.00 | 0.388743E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.156395E+13 | 0.00 | 0.448044E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.137843E+10 | 0.00 | 0.346012E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.301826E+12 | 0.00 | 0.398812E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2883.74 | 02-JAN-10:09 | 2213.72 | 01-JAN-06:10 | 23897.06 | 01-JAN-11:09 | 0.00 | 4742.42 | 12-JAN-07:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 2883.74 | 01-FEB-16:19 | 2213.72 | 01-FEB-06:10 | 23897.06 | 01-FEB-11:09 | 0.00 | 4624.23 | 27-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 2883.74 | 01-MAR-17:30 | 2213.72 | 01-MAR-06:10 | 23897.06 | 01-MAR-11:09 | 0.00 | 4433.24 | 01-MAR-05:10 | 17.86 | 01-MAR-00:20 | 0.00 | 01-MAR-00:10 |
April | 2883.74 | 01-APR-19:40 | 2213.72 | 01-APR-05:10 | 23897.06 | 01-APR-10:09 | 0.00 | 4091.81 | 03-APR-06:10 | 17.86 | 17-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 2883.74 | 04-MAY-20:30 | 2213.72 | 01-MAY-21:10 | 23897.06 | 01-MAY-10:09 | 0.00 | 3351.57 | 27-MAY-05:10 | 17.86 | 01-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 2768.81 | 02-JUN-20:00 | 2213.72 | 01-JUN-22:49 | 23897.06 | 01-JUN-10:09 | 0.00 | 3252.48 | 30-JUN-11:00 | 17.86 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 2796.72 | 26-JUL-20:00 | 2213.72 | 11-JUL-22:00 | 23897.06 | 01-JUL-10:09 | 0.00 | 3486.72 | 29-JUL-18:10 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 2883.74 | 08-AUG-20:30 | 2213.72 | 01-AUG-21:00 | 23897.06 | 01-AUG-10:09 | 0.00 | 3347.38 | 31-AUG-05:00 | 17.86 | 30-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 2883.74 | 01-SEP-19:30 | 2213.72 | 01-SEP-05:10 | 23897.06 | 01-SEP-10:09 | 0.00 | 3506.42 | 30-SEP-05:00 | 17.86 | 21-SEP-23:10 | 0.00 | 01-SEP-00:10 |
October | 2883.74 | 02-OCT-18:19 | 2213.72 | 01-OCT-05:10 | 23897.06 | 01-OCT-10:09 | 0.00 | 4047.67 | 22-OCT-06:10 | 17.86 | 05-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 2883.74 | 01-NOV-16:30 | 2213.72 | 01-NOV-05:10 | 23897.06 | 01-NOV-10:09 | 0.00 | 4424.07 | 29-NOV-05:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2883.74 | 01-DEC-10:09 | 2213.72 | 01-DEC-06:10 | 23897.06 | 01-DEC-11:09 | 0.00 | 4555.25 | 15-DEC-07:10 | 17.86 | 01-DEC-00:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2768.81 | 2213.72 | 23897.06 | 0.00 | 3252.48 | 17.86 | 0.00 | ||||||
Maximum of Months | 2883.74 | 2213.72 | 23897.06 | 0.00 | 4742.42 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.32 | 26-JAN-19:40 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4742.05 | 22-FEB-19:10 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 4742.02 | 01-MAR-19:40 | 0.00 |
April | 233.80 | 28-APR-03:20 | 0.00 | 0.00 | 0.00 | 4742.08 | 13-APR-06:49 | 0.00 |
May | 6704.51 | 31-MAY-17:19 | 0.00 | 0.00 | 0.00 | 4742.13 | 26-MAY-06:40 | 0.00 |
June | 12851.65 | 30-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4741.26 | 02-JUN-06:19 | 0.00 |
July | 13713.07 | 29-JUL-18:19 | 0.00 | 0.00 | 0.00 | 4739.85 | 05-JUL-06:19 | 0.00 |
August | 10559.77 | 11-AUG-17:00 | 0.00 | 0.00 | 0.00 | 4741.69 | 28-AUG-06:10 | 0.00 |
September | 891.02 | 02-SEP-18:10 | 0.00 | 0.00 | 0.00 | 4741.69 | 28-SEP-18:49 | 0.00 |
October | 243.66 | 06-OCT-03:09 | 0.00 | 0.00 | 0.00 | 4741.31 | 13-OCT-18:19 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 4740.97 | 14-NOV-07:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4741.61 | 19-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4739.85 | 0.00 | ||
Maximum of Months | 13713.07 | 0.00 | 0.00 | 0.00 | 4742.13 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39149.78 | 03-JAN-11:09 | 2883.74 | 23897.06 | 2213.72 | 0.00 | 4215.02 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 36284.64 | 27-FEB-11:20 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4451.06 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 35918.86 | 01-MAR-11:20 | 1871.80 | 23897.06 | 0.00 | 0.00 | 3850.42 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 35647.15 | 03-APR-10:09 | 1871.80 | 23897.06 | 0.00 | 0.00 | 3656.69 | 17.86 | 0.00 | 0.00 | 0.00 |
May | 37150.60 | 31-MAY-10:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 2863.79 | 17.86 | 0.00 | 3142.24 | 0.00 |
June | 44472.35 | 30-JUN-11:00 | 1871.80 | 22289.73 | 0.00 | 0.00 | 3252.48 | 17.86 | 0.00 | 12851.65 | 0.00 |
July | 44774.72 | 22-JUL-10:00 | 1663.82 | 23897.06 | 0.00 | 0.00 | 3128.80 | 17.86 | 0.00 | 10568.32 | 0.00 |
August | 40590.19 | 11-AUG-17:49 | 1871.80 | 19878.74 | 0.00 | 0.00 | 2911.02 | 17.86 | 0.00 | 10547.77 | 0.00 |
September | 35475.77 | 30-SEP-10:20 | 1663.82 | 23897.06 | 0.00 | 0.00 | 3281.06 | 17.86 | 0.00 | 0.00 | 0.00 |
October | 35735.55 | 28-OCT-10:09 | 1663.82 | 23897.06 | 0.00 | 0.00 | 3515.97 | 17.86 | 0.00 | 0.00 | 0.00 |
November | 36466.02 | 13-NOV-11:09 | 2417.08 | 23897.06 | 0.00 | 0.00 | 3781.00 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 39461.15 | 15-DEC-11:09 | 2883.74 | 23897.06 | 2213.72 | 0.00 | 4491.25 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 35475.77 | 1663.82 | 19878.74 | 0.00 | 0.00 | 2863.79 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44774.72 | 2883.74 | 23897.06 | 2213.72 | 0.00 | 4491.25 | 17.86 | 0.00 | 12851.65 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 229890.73 | 12-JAN-07:10 | 0.00 | 37895.83 | 09-JAN-19:49 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 218531.01 | 01-FEB-04:30 | 0.00 | 37895.26 | 14-FEB-07:49 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 218531.01 | 01-MAR-04:10 | 0.00 | 37894.84 | 31-MAR-06:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 160399.88 | 03-APR-03:30 | 0.00 | 37895.35 | 07-APR-06:49 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 56906.24 | 27-MAY-04:00 | 0.00 | 37887.34 | 04-MAY-06:00 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 22071.46 | 02-JUN-04:10 | 0.00 | 36634.01 | 07-JUN-06:30 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 18633.23 | 06-JUL-04:10 | 0.00 | 35313.04 | 03-JUL-06:30 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 56299.61 | 31-AUG-05:00 | 0.00 | 34125.02 | 01-AUG-06:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 75840.67 | 30-SEP-05:00 | 0.00 | 33920.96 | 29-SEP-18:00 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 143216.19 | 22-OCT-06:10 | 0.00 | 35085.46 | 31-OCT-06:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 218531.01 | 28-NOV-04:30 | 0.00 | 36554.89 | 30-NOV-19:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 218531.01 | 01-DEC-04:19 | 0.00 | 37887.86 | 29-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 18633.23 | 0.00 | 33920.96 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 229890.73 | 0.00 | 37895.83 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 9.83 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
March | 9.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
April | 1.17 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.00 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.00 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
October | 2.50 | 20.25 | 0.17 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
November | 10.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 12.83 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 55.50 | 19.22 | 0.17 | 19.22 | 0.33 | 19.25 | 0.00 | 19.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.83 | 20.43 | 0.17 | 20.43 | 0.17 | 24.57 | 0.00 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.64 | 0.00 | 26.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.27 | 0.00 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.75 | 0.00 | 28.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.99 | 0.00 | 28.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.74 | 0.00 | 28.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.22 | 0.00 | 27.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.77 | 0.00 | 26.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.83 | 28.38 | 0.00 | 28.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.99 | 0.00 | 28.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.73 | 607.00 | 20.73 | 607.00 | 20.73 |
February | 551.00 | 20.73 | 526.83 | 20.73 | 526.83 | 20.72 |
March | 612.00 | 20.73 | 429.67 | 20.69 | 429.67 | 20.67 |
April | 590.00 | 20.85 | 173.67 | 20.70 | 173.67 | 20.60 |
May | 510.33 | 21.47 | 30.83 | 21.33 | 28.33 | 21.19 |
June | 241.33 | 21.73 | 207.33 | 22.77 | 0.50 | 22.77 |
July | 202.50 | 21.75 | 370.50 | 23.17 | 11.83 | 23.17 |
August | 311.67 | 21.49 | 240.33 | 22.52 | 4.67 | 22.49 |
September | 581.67 | 21.13 | 43.50 | 20.97 | 43.50 | 20.83 |
October | 610.00 | 20.75 | 233.83 | 20.64 | 233.83 | 20.58 |
November | 591.00 | 20.73 | 583.33 | 20.73 | 583.33 | 20.73 |
December | 609.00 | 20.73 | 603.67 | 20.73 | 603.67 | 20.73 |
Annual Sum or Average | 6020.50 | 20.96 | 4050.50 | 21.09 | 3246.83 | 20.97 |
Minimum of Months | 202.50 | 20.73 | 30.83 | 20.64 | 0.50 | 20.58 |
Maximum of Months | 612.00 | 21.75 | 607.00 | 23.17 | 607.00 | 23.17 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.00 | 609.17 | 19.00 | 609.17 | 19.00 |
February | 551.00 | 19.00 | 525.67 | 19.00 | 525.67 | 19.00 |
March | 612.00 | 19.00 | 535.50 | 19.00 | 535.50 | 19.00 |
April | 559.00 | 19.45 | 282.67 | 19.39 | 268.00 | 19.30 |
May | 336.17 | 21.18 | 301.00 | 22.81 | 79.17 | 22.96 |
June | 392.83 | 25.38 | 520.33 | 25.38 | 345.67 | 25.54 |
July | 428.67 | 25.63 | 564.33 | 25.49 | 400.00 | 25.63 |
August | 402.83 | 24.59 | 481.17 | 24.91 | 306.33 | 25.16 |
September | 409.17 | 19.62 | 197.33 | 20.67 | 55.17 | 20.57 |
October | 607.00 | 19.25 | 300.00 | 19.17 | 300.00 | 19.13 |
November | 591.00 | 19.00 | 589.50 | 19.00 | 589.50 | 19.00 |
December | 609.00 | 19.00 | 593.00 | 19.00 | 593.00 | 19.00 |
Annual Sum or Average | 6108.67 | 20.47 | 5499.67 | 20.85 | 4607.17 | 20.80 |
Minimum of Months | 336.17 | 19.00 | 197.33 | 19.00 | 55.17 | 19.00 |
Maximum of Months | 612.00 | 25.63 | 609.17 | 25.49 | 609.17 | 25.63 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73144 | 12.92463 | -0.7652 | 18.04065 |
February | 551.00000 | 20.73207 | 14.21901 | -0.7359 | 17.20755 |
March | 612.00000 | 20.73406 | 15.52172 | -0.6512 | 14.83719 |
April | 590.00000 | 20.84986 | 20.67625 | -0.4909 | 11.34322 |
May | 611.00000 | 21.88052 | 29.24835 | -1.2058 | 37.81465 |
June | 592.00000 | 23.03307 | 42.06598 | -0.6902 | 17.73652 |
July | 609.00000 | 23.17666 | 49.89420 | -0.5756 | 14.82539 |
August | 612.00000 | 22.66222 | 46.08464 | -0.7793 | 21.55167 |
September | 590.00000 | 21.16742 | 36.27992 | -1.4228 | 47.11448 |
October | 610.00000 | 20.75159 | 23.55849 | -0.5395 | 12.00928 |
November | 591.00000 | 20.73117 | 12.09235 | -0.7323 | 17.01446 |
December | 609.00000 | 20.73064 | 11.96889 | -0.7711 | 18.21956 |
Annual Sum or Average | 7187.00000 | 21.43773 | 26.29631 | -0.7798 | 20.64234 |
Minimum of Months | 551.00000 | 20.73064 | 11.96889 | -1.4228 | 11.34322 |
Maximum of Months | 612.00000 | 23.17666 | 49.89420 | -0.4909 | 47.11448 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.00117 | 19.00692 | -0.8048 | 18.88459 |
February | 551.00000 | 19.00141 | 21.50354 | -0.7947 | 18.62366 |
March | 612.00000 | 19.00180 | 24.11777 | -0.7438 | 16.99483 |
April | 590.00000 | 19.67495 | 29.95531 | -0.4961 | 12.62702 |
May | 611.00000 | 22.64455 | 34.63318 | -0.6569 | 25.62017 |
June | 592.00000 | 24.90823 | 42.66592 | 0.19820 | 11.13151 |
July | 609.00000 | 25.07378 | 48.77418 | 0.32476 | 12.30166 |
August | 612.00000 | 24.27759 | 46.27205 | 0.03973 | 14.63354 |
September | 590.00000 | 20.90474 | 42.34192 | -1.1411 | 39.87831 |
October | 610.00000 | 19.26845 | 31.20093 | -0.5651 | 12.82866 |
November | 591.00000 | 19.00150 | 18.46835 | -0.7751 | 17.86728 |
December | 609.00000 | 19.00088 | 17.77381 | -0.8058 | 18.90742 |
Annual Sum or Average | 7187.00000 | 20.99570 | 31.45552 | -0.5156 | 18.33186 |
Minimum of Months | 551.00000 | 19.00088 | 17.77381 | -1.1411 | 11.13151 |
Maximum of Months | 612.00000 | 25.07378 | 48.77418 | 0.32476 | 39.87831 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 01-APR-00:02 | 0.00 | 01-APR-00:02 | 0.00 | 01-APR-00:02 | 0.00 | 01-APR-00:02 | 0.00 | 01-APR-00:02 | 0.00 | 01-APR-00:02 |
May | 0.107924E+10 | 0.321106E+09 | 62.89 | 0.107719E+10 | 2052553.18 | 0.00 | 0.55 | 31-MAY-17:13 | 0.00 | 01-MAY-00:01 | 15720.41 | 31-MAY-17:13 | 15720.41 | 31-MAY-17:13 | 308.04 | 31-MAY-19:30 | 4354.23 | 31-MAY-17:13 | 0.00 | 01-MAY-00:01 |
June | 0.922647E+10 | 0.257172E+10 | 254.94 | 0.858170E+10 | 0.644773E+09 | 0.00 | 1.00 | 04-JUN-03:01 | 0.00 | 01-JUN-00:01 | 65106.22 | 23-JUN-03:01 | 55690.43 | 23-JUN-03:01 | 24042.42 | 30-JUN-03:02 | 15887.66 | 11-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.148726E+11 | 0.403673E+10 | 299.74 | 0.129266E+11 | 0.194607E+10 | 0.00 | 1.00 | 08-JUL-03:01 | 0.00 | 01-JUL-00:01 | 65106.22 | 11-JUL-03:01 | 43297.38 | 29-JUL-03:01 | 28215.55 | 15-JUL-03:01 | 15887.66 | 08-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.757179E+10 | 0.211745E+10 | 195.37 | 0.651639E+10 | 0.105540E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 65106.22 | 01-AUG-03:01 | 54483.25 | 12-AUG-03:02 | 28279.25 | 04-AUG-03:01 | 15887.66 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 1673199.15 | 525321.33 | 0.58 | 1459964.47 | 213234.68 | 0.00 | 0.05 | 02-SEP-18:07 | 0.00 | 01-SEP-00:01 | 1278.92 | 02-SEP-18:07 | 1113.84 | 02-SEP-18:07 | 165.88 | 02-SEP-18:10 | 400.42 | 02-SEP-18:07 | 0.00 | 01-SEP-00:01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.327518E+11 | 0.904754E+10 | 813.52 | 0.291033E+11 | 0.364851E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.148726E+11 | 0.403673E+10 | 299.74 | 0.129266E+11 | 0.194607E+10 | 0.00 | 1.00 | 0.00 | 65106.22 | 55690.43 | 28279.25 | 15887.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 1304364.72 | 395299.93 | 0.51 | 983060.50 | 321304.22 | 0.00 | 0.21 | 21-APR-03:10 | 0.00 | 01-APR-00:02 | 2403.35 | 21-APR-03:10 | 1771.39 | 21-APR-03:10 | 631.97 | 21-APR-03:10 | 711.78 | 21-APR-03:10 | 0.00 | 01-APR-00:02 |
May | 0.104923E+10 | 0.298784E+09 | 94.46 | 0.104203E+10 | 7201791.82 | 0.00 | 1.00 | 11-MAY-03:01 | 0.00 | 01-MAY-00:01 | 23401.56 | 14-MAY-03:01 | 19077.25 | 14-MAY-03:01 | 4324.31 | 14-MAY-03:01 | 5611.39 | 14-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.756805E+10 | 0.199712E+10 | 328.77 | 0.694189E+10 | 0.626166E+09 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 28148.05 | 11-JUN-03:01 | 22613.27 | 14-JUN-03:01 | 13769.76 | 28-JUN-03:01 | 6748.47 | 03-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.119027E+11 | 0.303069E+10 | 377.73 | 0.999947E+10 | 0.190325E+10 | 0.00 | 1.00 | 01-JUL-03:11 | 0.00 | 01-JUL-00:01 | 28148.05 | 09-JUL-03:11 | 22428.27 | 13-JUL-03:01 | 15657.98 | 16-JUL-03:01 | 6748.47 | 01-JUL-03:11 | 0.00 | 01-JUL-00:01 |
August | 0.670847E+10 | 0.176281E+10 | 265.88 | 0.554516E+10 | 0.116331E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 28148.05 | 01-AUG-04:01 | 22549.89 | 11-AUG-03:01 | 14912.69 | 13-AUG-03:01 | 6748.47 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 26769065.20 | 7707327.64 | 5.91 | 20273012.89 | 6496052.31 | 0.00 | 1.00 | 01-SEP-03:42 | 0.00 | 01-SEP-00:01 | 14057.88 | 01-SEP-03:42 | 11050.19 | 19-SEP-03:42 | 6114.11 | 01-SEP-03:42 | 3372.99 | 01-SEP-03:42 | 0.00 | 01-SEP-00:01 |
October | 1228560.79 | 369290.02 | 0.49 | 933636.38 | 294924.41 | 0.00 | 0.29 | 06-OCT-03:10 | 0.00 | 01-OCT-00:01 | 3353.81 | 06-OCT-03:10 | 2864.34 | 06-OCT-03:10 | 489.46 | 06-OCT-03:10 | 974.64 | 06-OCT-03:10 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.272578E+11 | 0.709787E+10 | 1073.76 | 0.235507E+11 | 0.370704E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.119027E+11 | 0.303069E+10 | 377.73 | 0.999947E+10 | 0.190325E+10 | 0.00 | 1.00 | 0.00 | 28148.05 | 22613.27 | 15657.98 | 6748.47 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.28 | 9.37 | 15.91 | 3.77 | 632.62 | 0.00 | 0.00 | 0.00 |
February | 131.11 | 62.87 | 68.24 | 73.40 | 519.86 | 0.00 | 0.00 | 0.00 |
March | 367.65 | 186.15 | 181.50 | 332.17 | 378.53 | 0.00 | 0.00 | 0.00 |
April | 489.09 | 247.73 | 241.37 | 488.86 | 200.97 | 0.00 | 0.00 | 0.00 |
May | 712.27 | 402.04 | 310.23 | 837.98 | 96.77 | 0.00 | 0.00 | 0.00 |
June | 652.33 | 304.65 | 347.68 | 787.59 | 49.27 | 0.00 | 0.00 | 0.00 |
July | 621.30 | 302.11 | 319.19 | 767.67 | 56.64 | 0.00 | 0.00 | 0.00 |
August | 499.18 | 244.60 | 254.58 | 592.51 | 90.18 | 0.00 | 0.00 | 0.00 |
September | 312.45 | 141.32 | 171.13 | 319.38 | 169.35 | 0.00 | 0.00 | 0.00 |
October | 169.25 | 68.58 | 100.67 | 132.46 | 330.71 | 0.00 | 0.00 | 0.00 |
November | 35.08 | 12.74 | 22.34 | 3.01 | 618.40 | 0.00 | 0.00 | 0.00 |
December | 4.99 | 1.18 | 3.81 | 0.00 | 683.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.27 | 165.99 | 170.27 | 363.52 | 317.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.99 | 1.18 | 3.81 | 0.00 | 49.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 712.27 | 402.04 | 347.68 | 837.98 | 683.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.46 | 98.15 | 49.31 | 90.28 | 814.50 | 0.00 | 0.00 | 0.00 |
February | 492.75 | 342.11 | 150.64 | 436.77 | 646.84 | 0.00 | 0.00 | 0.00 |
March | 834.37 | 564.49 | 269.88 | 864.63 | 491.93 | 0.00 | 0.00 | 0.00 |
April | 1022.59 | 636.46 | 386.13 | 1188.53 | 305.89 | 0.00 | 0.00 | 0.00 |
May | 844.33 | 438.35 | 405.97 | 1014.90 | 154.39 | 0.00 | 0.00 | 0.00 |
June | 767.10 | 313.14 | 453.96 | 944.68 | 84.86 | 0.00 | 0.00 | 0.00 |
July | 737.96 | 319.57 | 418.38 | 928.67 | 90.68 | 0.00 | 0.00 | 0.00 |
August | 768.84 | 424.28 | 344.56 | 950.37 | 135.48 | 0.00 | 0.00 | 0.00 |
September | 613.69 | 366.86 | 246.83 | 694.74 | 237.54 | 0.00 | 0.00 | 0.00 |
October | 454.36 | 288.21 | 166.15 | 437.20 | 422.72 | 0.00 | 0.00 | 0.00 |
November | 246.34 | 173.59 | 72.75 | 168.80 | 761.86 | 0.00 | 0.00 | 0.00 |
December | 43.56 | 30.70 | 12.86 | 8.47 | 907.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 580.95 | 332.48 | 248.46 | 644.55 | 420.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.56 | 30.70 | 12.86 | 8.47 | 84.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1022.59 | 636.46 | 453.96 | 1188.53 | 907.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.74 | 2.00 | 9.75 | 0.00 | 648.46 | 0.00 | 0.00 | 0.00 |
February | 70.00 | 24.39 | 45.61 | 14.80 | 546.94 | 0.00 | 0.00 | 0.00 |
March | 210.59 | 90.96 | 119.64 | 129.35 | 390.67 | 0.00 | 0.00 | 0.00 |
April | 498.95 | 259.03 | 239.92 | 514.62 | 215.17 | 0.00 | 0.00 | 0.00 |
May | 484.05 | 220.84 | 263.21 | 532.07 | 103.06 | 0.00 | 0.00 | 0.00 |
June | 530.22 | 226.38 | 303.84 | 626.03 | 56.53 | 0.00 | 0.00 | 0.00 |
July | 442.89 | 167.35 | 275.55 | 527.77 | 62.09 | 0.00 | 0.00 | 0.00 |
August | 365.42 | 155.37 | 210.05 | 413.63 | 94.50 | 0.00 | 0.00 | 0.00 |
September | 219.88 | 91.67 | 128.21 | 197.83 | 174.60 | 0.00 | 0.00 | 0.00 |
October | 86.21 | 25.82 | 60.39 | 34.39 | 347.17 | 0.00 | 0.00 | 0.00 |
November | 34.85 | 12.78 | 22.07 | 3.62 | 620.18 | 0.00 | 0.00 | 0.00 |
December | 3.09 | 0.31 | 2.78 | 0.00 | 686.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 247.12 | 106.63 | 140.49 | 250.50 | 327.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.09 | 0.31 | 2.78 | 0.00 | 56.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 530.22 | 259.03 | 303.84 | 626.03 | 686.16 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67703244.47 | 25083622.98 | 42619621.49 | 10092159.07 | 0.169440E+10 |
February | 0.317175E+09 | 0.152086E+09 | 0.165089E+09 | 0.177558E+09 | 0.125763E+10 |
March | 0.984717E+09 | 0.498581E+09 | 0.486136E+09 | 0.889684E+09 | 0.101385E+10 |
April | 0.126773E+10 | 0.642107E+09 | 0.625618E+09 | 0.126712E+10 | 0.520909E+09 |
May | 0.190774E+10 | 0.107681E+10 | 0.830922E+09 | 0.224444E+10 | 0.259200E+09 |
June | 0.169084E+10 | 0.789655E+09 | 0.901182E+09 | 0.204144E+10 | 0.127709E+09 |
July | 0.166408E+10 | 0.809159E+09 | 0.854922E+09 | 0.205613E+10 | 0.151703E+09 |
August | 0.133699E+10 | 0.655128E+09 | 0.681864E+09 | 0.158697E+10 | 0.241543E+09 |
September | 0.809874E+09 | 0.366307E+09 | 0.443567E+09 | 0.827845E+09 | 0.438946E+09 |
October | 0.453310E+09 | 0.183673E+09 | 0.269638E+09 | 0.354778E+09 | 0.885786E+09 |
November | 90935465.96 | 33031431.12 | 57904034.84 | 7803512.54 | 0.160290E+10 |
December | 13376757.11 | 3168147.34 | 10208609.77 | 0.00 | 0.182937E+10 |
Annual Sum or Average | 0.106045E+11 | 0.523479E+10 | 0.536967E+10 | 0.114639E+11 | 0.100240E+11 |
Minimum of Months | 13376757.11 | 3168147.34 | 10208609.77 | 0.00 | 0.127709E+09 |
Maximum of Months | 0.190774E+10 | 0.107681E+10 | 0.901182E+09 | 0.224444E+10 | 0.182937E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394962E+09 | 0.262894E+09 | 0.132068E+09 | 0.241814E+09 | 0.218156E+10 |
February | 0.119206E+10 | 0.827626E+09 | 0.364432E+09 | 0.105665E+10 | 0.156485E+10 |
March | 0.223479E+10 | 0.151193E+10 | 0.722859E+09 | 0.231581E+10 | 0.131759E+10 |
April | 0.265055E+10 | 0.164970E+10 | 0.100085E+10 | 0.308066E+10 | 0.792861E+09 |
May | 0.226144E+10 | 0.117408E+10 | 0.108736E+10 | 0.271830E+10 | 0.413522E+09 |
June | 0.198833E+10 | 0.811670E+09 | 0.117666E+10 | 0.244862E+10 | 0.219963E+09 |
July | 0.197655E+10 | 0.855949E+09 | 0.112060E+10 | 0.248735E+10 | 0.242880E+09 |
August | 0.205927E+10 | 0.113640E+10 | 0.922873E+09 | 0.254546E+10 | 0.362879E+09 |
September | 0.159069E+10 | 0.950902E+09 | 0.639786E+09 | 0.180075E+10 | 0.615710E+09 |
October | 0.121695E+10 | 0.771938E+09 | 0.445008E+09 | 0.117100E+10 | 0.113220E+10 |
November | 0.638505E+09 | 0.449939E+09 | 0.188566E+09 | 0.437542E+09 | 0.197473E+10 |
December | 0.116669E+09 | 82219795.17 | 34449056.56 | 22687498.93 | 0.243059E+10 |
Annual Sum or Average | 0.183208E+11 | 0.104852E+11 | 0.783551E+10 | 0.203266E+11 | 0.132493E+11 |
Minimum of Months | 0.116669E+09 | 82219795.17 | 34449056.56 | 22687498.93 | 0.219963E+09 |
Maximum of Months | 0.265055E+10 | 0.164970E+10 | 0.117666E+10 | 0.308066E+10 | 0.243059E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31455278.48 | 5349828.02 | 26105450.46 | 0.00 | 0.173682E+10 |
February | 0.169339E+09 | 58996307.23 | 0.110343E+09 | 35811615.49 | 0.132316E+10 |
March | 0.564046E+09 | 0.243614E+09 | 0.320431E+09 | 0.346438E+09 | 0.104636E+10 |
April | 0.129329E+10 | 0.671415E+09 | 0.621872E+09 | 0.133389E+10 | 0.557725E+09 |
May | 0.129648E+10 | 0.591508E+09 | 0.704974E+09 | 0.142509E+10 | 0.276039E+09 |
June | 0.137432E+10 | 0.586771E+09 | 0.787548E+09 | 0.162266E+10 | 0.146527E+09 |
July | 0.118625E+10 | 0.448222E+09 | 0.738024E+09 | 0.141359E+10 | 0.166292E+09 |
August | 0.978739E+09 | 0.416136E+09 | 0.562603E+09 | 0.110788E+10 | 0.253100E+09 |
September | 0.569929E+09 | 0.237617E+09 | 0.332312E+09 | 0.512764E+09 | 0.452567E+09 |
October | 0.230897E+09 | 69147288.57 | 0.161749E+09 | 92100697.24 | 0.929868E+09 |
November | 90319532.01 | 33116032.21 | 57203499.80 | 9395972.50 | 0.160752E+10 |
December | 8270673.02 | 838073.51 | 7432599.51 | 0.00 | 0.183781E+10 |
Annual Sum or Average | 0.779333E+10 | 0.336273E+10 | 0.443060E+10 | 0.789963E+10 | 0.103338E+11 |
Minimum of Months | 8270673.02 | 838073.51 | 7432599.51 | 0.00 | 0.146527E+09 |
Maximum of Months | 0.137432E+10 | 0.671415E+09 | 0.787548E+09 | 0.162266E+10 | 0.183781E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.58 | 2048.11 | 184.48 | 109.52 | 74.97 | 0.00 | 0.00 |
February | 417.12 | 1605.79 | 693.85 | 429.36 | 264.49 | 0.00 | 0.00 |
March | 1235.71 | 1170.70 | 1412.62 | 841.59 | 571.02 | 0.00 | 0.00 |
April | 2127.46 | 657.48 | 2010.63 | 1143.22 | 867.42 | 0.00 | 0.00 |
May | 2346.64 | 315.93 | 2040.64 | 1061.23 | 979.41 | 0.00 | 0.00 |
June | 2333.36 | 165.72 | 1949.65 | 844.17 | 1105.48 | 0.00 | 0.00 |
July | 2206.17 | 191.46 | 1802.15 | 789.03 | 1013.12 | 0.00 | 0.00 |
August | 1934.16 | 297.81 | 1633.44 | 824.25 | 809.19 | 0.00 | 0.00 |
September | 1182.76 | 552.30 | 1146.02 | 599.86 | 546.17 | 0.00 | 0.00 |
October | 547.47 | 1044.02 | 709.81 | 382.60 | 327.21 | 0.00 | 0.00 |
November | 98.12 | 1923.13 | 316.27 | 199.11 | 117.16 | 0.00 | 0.00 |
December | 0.12 | 2268.29 | 51.64 | 32.19 | 19.45 | 0.00 | 0.00 |
Annual Sum or Average | 1210.28 | 1017.39 | 1164.34 | 605.11 | 559.23 | 0.00 | 0.00 |
Minimum of Months | 0.12 | 165.72 | 51.64 | 32.19 | 19.45 | 0.00 | 0.00 |
Maximum of Months | 2346.64 | 2268.29 | 2040.64 | 1143.22 | 1105.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124762E+09 | 0.548564E+10 | 0.494121E+09 | 0.293327E+09 | 0.200794E+09 | 0.00 | 0.00 |
February | 0.100909E+10 | 0.388472E+10 | 0.167857E+10 | 0.103871E+10 | 0.639864E+09 | 0.00 | 0.00 |
March | 0.330973E+10 | 0.313560E+10 | 0.378355E+10 | 0.225412E+10 | 0.152943E+10 | 0.00 | 0.00 |
April | 0.551437E+10 | 0.170419E+10 | 0.521156E+10 | 0.296322E+10 | 0.224834E+10 | 0.00 | 0.00 |
May | 0.628524E+10 | 0.846174E+09 | 0.546566E+10 | 0.284241E+10 | 0.262325E+10 | 0.00 | 0.00 |
June | 0.604806E+10 | 0.429536E+09 | 0.505349E+10 | 0.218810E+10 | 0.286539E+10 | 0.00 | 0.00 |
July | 0.590901E+10 | 0.512808E+09 | 0.482687E+10 | 0.211333E+10 | 0.271354E+10 | 0.00 | 0.00 |
August | 0.518045E+10 | 0.797662E+09 | 0.437500E+10 | 0.220766E+10 | 0.216734E+10 | 0.00 | 0.00 |
September | 0.306570E+10 | 0.143157E+10 | 0.297049E+10 | 0.155483E+10 | 0.141567E+10 | 0.00 | 0.00 |
October | 0.146634E+10 | 0.279631E+10 | 0.190115E+10 | 0.102476E+10 | 0.876395E+09 | 0.00 | 0.00 |
November | 0.254333E+09 | 0.498475E+10 | 0.819760E+09 | 0.516087E+09 | 0.303674E+09 | 0.00 | 0.00 |
December | 313750.02 | 0.607539E+10 | 0.138316E+09 | 86226016.02 | 52090265.85 | 0.00 | 0.00 |
Annual Sum or Average | 0.381674E+11 | 0.320843E+11 | 0.367186E+11 | 0.190828E+11 | 0.176358E+11 | 0.00 | 0.00 |
Minimum of Months | 313750.02 | 0.429536E+09 | 0.138316E+09 | 86226016.02 | 52090265.85 | 0.00 | 0.00 |
Maximum of Months | 0.628524E+10 | 0.607539E+10 | 0.546566E+10 | 0.296322E+10 | 0.286539E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639935E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174171141.3 | 81.22 | 0.00 | 0.00 |
February | 0.579165E+10 | -0.563430E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157348204.6 | 81.22 | 0.00 | 0.00 |
March | 0.646793E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174067334.7 | 81.22 | 0.00 | 0.00 |
April | 0.620982E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166349521.4 | 81.22 | 0.00 | 0.00 |
May | 0.642400E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163813641.2 | 81.22 | 0.00 | 0.00 |
June | 0.623882E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152251260.3 | 81.21 | 0.00 | 0.00 |
July | 0.637388E+10 | -0.621706E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156817626.4 | 81.22 | 0.00 | 0.00 |
August | 0.645406E+10 | -0.629519E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158865151.2 | 81.22 | 0.00 | 0.00 |
September | 0.620747E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162653945.7 | 81.22 | 0.00 | 0.00 |
October | 0.639656E+10 | -0.622382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172742948.7 | 81.22 | 0.00 | 0.00 |
November | 0.619293E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168310793.4 | 81.22 | 0.00 | 0.00 |
December | 0.639123E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174138741.5 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755477E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.198153E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579165E+10 | -0.629519E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174171141.3 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646793E+10 | -0.563430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152251260.3 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.297492E+11 | -0.287284E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102080E+10 | 58.99 | 0.00 | 0.00 |
February | 0.269241E+11 | -0.260017E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -922333314.6 | 58.99 | 0.00 | 0.00 |
March | 0.300656E+11 | -0.290458E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101984E+10 | 58.99 | 0.00 | 0.00 |
April | 0.288580E+11 | -0.278903E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -967647750.9 | 58.99 | 0.00 | 0.00 |
May | 0.296025E+11 | -0.286766E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925956172.3 | 58.99 | 0.00 | 0.00 |
June | 0.276786E+11 | -0.268400E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -838581023.8 | 58.99 | 0.00 | 0.00 |
July | 0.272460E+11 | -0.263842E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -861854795.2 | 58.99 | 0.00 | 0.00 |
August | 0.269372E+11 | -0.260567E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -880558956.7 | 58.99 | 0.00 | 0.00 |
September | 0.258754E+11 | -0.249417E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -933670935.7 | 58.99 | 0.00 | 0.00 |
October | 0.271925E+11 | -0.261849E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100764E+10 | 58.99 | 0.00 | 0.00 |
November | 0.272476E+11 | -0.262620E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985570231.3 | 58.99 | 0.00 | 0.00 |
December | 0.292525E+11 | -0.282320E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102049E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.336629E+12 | -0.325244E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.113850E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.258754E+11 | -0.290458E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102080E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.300656E+11 | -0.249417E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838581023.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.64 | 0.50 | 08-JAN-11:30 | 286.74 | 16.15 | 10.50 | 48.67 | 289.29 | 16.12 | 10.50 | 50.33 |
February | 205.83 | 0.55 | 0.50 | 01-FEB-11:20 | 1712.04 | 33.58 | 168.17 | 166.17 | 1702.58 | 33.76 | 164.33 | 171.50 |
March | 329.50 | 0.53 | 0.50 | 01-MAR-08:30 | 2544.67 | 28.87 | 253.33 | 301.67 | 2574.25 | 28.72 | 249.33 | 301.00 |
April | 421.83 | 0.53 | 0.50 | 01-APR-06:00 | 1539.96 | 22.18 | 258.00 | 388.83 | 1511.40 | 21.68 | 245.33 | 389.83 |
May | 545.00 | 0.54 | 0.50 | 01-MAY-04:00 | 1173.41 | 21.60 | 284.33 | 479.50 | 1545.58 | 19.73 | 212.50 | 465.67 |
June | 583.50 | 0.54 | 0.50 | 01-JUN-04:19 | 1038.39 | 21.96 | 311.33 | 501.50 | 1271.10 | 19.50 | 231.00 | 487.50 |
July | 562.83 | 0.54 | 0.50 | 01-JUL-03:00 | 1014.74 | 21.68 | 294.83 | 491.33 | 1285.17 | 19.56 | 212.33 | 474.83 |
August | 467.17 | 0.53 | 0.50 | 01-AUG-04:00 | 1178.85 | 21.19 | 241.83 | 421.17 | 1303.59 | 20.30 | 198.00 | 408.67 |
September | 356.33 | 0.54 | 0.50 | 01-SEP-05:00 | 1289.43 | 23.60 | 216.33 | 315.83 | 1510.58 | 23.68 | 208.67 | 313.33 |
October | 265.50 | 0.54 | 0.50 | 01-OCT-07:40 | 1693.59 | 31.07 | 207.67 | 222.83 | 1715.88 | 32.22 | 220.67 | 230.67 |
November | 135.83 | 0.57 | 0.50 | 01-NOV-09:39 | 496.44 | 24.26 | 56.83 | 101.33 | 495.48 | 24.11 | 55.67 | 101.50 |
December | 71.17 | 0.81 | 0.50 | 04-DEC-11:20 | 80.35 | 9.04 | 0.00 | 2.83 | 80.56 | 9.03 | 0.00 | 2.83 |
Annual Sum or Average | 4053.17 | 0.55 | 1288.17 | 23.39 | 2303.17 | 3441.67 | 1443.53 | 22.41 | 2008.33 | 3397.67 | ||
Minimum of Months | 71.17 | 0.53 | 0.50 | 80.35 | 9.04 | 0.00 | 2.83 | 80.56 | 9.03 | 0.00 | 2.83 | |
Maximum of Months | 583.50 | 0.81 | 0.50 | 2544.67 | 33.58 | 311.33 | 501.50 | 2574.25 | 33.76 | 249.33 | 487.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143932E+12 | 174824.81 | 04-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119751E+12 | 174824.81 | 01-FEB-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104263E+12 | 174824.81 | 01-MAR-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464150E+11 | 151215.77 | 03-APR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102493E+11 | 52516.97 | 27-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127966E+10 | 33428.05 | 02-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110135E+10 | 25813.95 | 06-JUL-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.369217E+10 | 41363.14 | 31-AUG-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231160E+11 | 57433.72 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690839E+11 | 174824.81 | 22-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136974E+12 | 174824.81 | 08-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152159E+12 | 174824.81 | 01-DEC-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.812017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.110135E+10 | 25813.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152159E+12 | 174824.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.846308E+11 | 94911.91 | 13-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688405E+11 | 85010.80 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.562716E+11 | 81866.89 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205337E+11 | 72799.73 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172224E+10 | 22697.94 | 27-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1853618.75 | 9052.46 | 02-JUN-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1390277.17 | 5951.80 | 06-JUL-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465387E+09 | 19271.15 | 31-AUG-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562233E+10 | 27151.80 | 28-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322131E+11 | 58288.11 | 31-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.795348E+11 | 91228.24 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.893015E+11 | 87530.79 | 28-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1390277.17 | 5951.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.893015E+11 | 94911.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.107924E+10 | 0.107719E+10 | 15720.41 | 31-MAY-17:13 | 15720.41 | 0.00 |
June | 0.00 | 0.00 | 0.922647E+10 | 0.858170E+10 | 65106.22 | 23-JUN-03:01 | 55690.43 | 0.00 |
July | 0.00 | 0.00 | 0.148726E+11 | 0.129266E+11 | 65106.22 | 11-JUL-03:01 | 40127.96 | 0.00 |
August | 0.00 | 0.00 | 0.757179E+10 | 0.651639E+10 | 65106.22 | 01-AUG-03:01 | 40175.39 | 0.00 |
September | 0.00 | 0.00 | 1673199.15 | 1459964.47 | 1278.92 | 02-SEP-18:07 | 1113.84 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.327518E+11 | 0.291033E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148726E+11 | 0.129266E+11 | 65106.22 | 55690.43 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1304364.72 | 983060.50 | 2403.35 | 21-APR-03:10 | 1771.39 | 0.00 |
May | 0.00 | 0.00 | 0.104923E+10 | 0.104203E+10 | 23401.56 | 14-MAY-03:01 | 19077.25 | 0.00 |
June | 0.00 | 0.00 | 0.756805E+10 | 0.694189E+10 | 28148.05 | 11-JUN-03:01 | 20872.48 | 0.00 |
July | 0.00 | 0.00 | 0.119027E+11 | 0.999947E+10 | 28148.05 | 09-JUL-03:11 | 13503.26 | 0.00 |
August | 0.00 | 0.00 | 0.670847E+10 | 0.554516E+10 | 28148.05 | 01-AUG-04:01 | 15441.17 | 0.00 |
September | 0.00 | 0.00 | 26769065.20 | 20273012.89 | 14057.88 | 01-SEP-03:42 | 7943.77 | 0.00 |
October | 0.00 | 0.00 | 1228560.79 | 933636.38 | 3353.81 | 06-OCT-03:10 | 2864.34 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.272578E+11 | 0.235507E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119027E+11 | 0.999947E+10 | 28148.05 | 20872.48 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 11181.75 | 21318.17 | 23-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 11203.73 | 21315.74 | 06-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 11299.78 | 21317.46 | 28-MAR-18:40 |
April | 0.00 | 0.00 | 01-APR-00:02 | 11215.34 | 21317.84 | 14-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 11161.89 | 21315.63 | 11-MAY-18:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 10811.09 | 20794.17 | 01-JUN-06:38 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 10307.76 | 19937.02 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 10186.06 | 19349.69 | 01-AUG-06:35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 10080.51 | 19219.52 | 29-SEP-18:10 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10233.71 | 19766.19 | 31-OCT-18:50 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 10588.81 | 20538.85 | 30-NOV-19:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10996.65 | 21296.17 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 10769.79 | ||||
Minimum of Months | 0.00 | 0.00 | 10080.51 | 19219.52 | ||
Maximum of Months | 0.00 | 0.00 | 11299.78 | 21318.17 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.27 |
February | 0.166145E+10 | 0.22 | 824.13 | 01-FEB-00:01 | 0.27 |
March | 0.183946E+10 | 0.22 | 824.13 | 01-MAR-00:01 | 0.27 |
April | 0.178692E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.27 |
May | 0.190090E+10 | 0.23 | 824.13 | 01-MAY-04:01 | 0.27 |
June | 0.187481E+10 | 0.23 | 824.13 | 01-JUN-03:01 | 0.27 |
July | 0.196234E+10 | 0.24 | 824.13 | 01-JUL-01:45 | 0.27 |
August | 0.193786E+10 | 0.23 | 824.13 | 01-AUG-01:55 | 0.27 |
September | 0.183365E+10 | 0.23 | 824.13 | 01-SEP-03:05 | 0.27 |
October | 0.184552E+10 | 0.23 | 824.13 | 01-OCT-04:01 | 0.27 |
November | 0.178012E+10 | 0.23 | 824.13 | 01-NOV-04:01 | 0.27 |
December | 0.183946E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.221019E+11 | 0.23 | |||
Minimum of Months | 0.166145E+10 | 0.22 | 824.13 | 0.27 | |
Maximum of Months | 0.196234E+10 | 0.24 | 824.13 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.497339E+10 | 0.61 | 3549.17 | 04-JAN-04:01 | 0.90 |
February | 0.437363E+10 | 0.60 | 3549.17 | 01-FEB-04:09 | 0.90 |
March | 0.448247E+10 | 0.58 | 3549.17 | 01-MAR-04:05 | 0.90 |
April | 0.363820E+10 | 0.52 | 3069.88 | 03-APR-03:10 | 0.90 |
May | 0.329370E+10 | 0.46 | 2059.37 | 27-MAY-04:01 | 0.68 |
June | 0.308568E+10 | 0.45 | 1997.40 | 24-JUN-03:01 | 0.66 |
July | 0.319074E+10 | 0.46 | 2990.27 | 22-JUL-03:01 | 0.82 |
August | 0.321848E+10 | 0.46 | 2560.69 | 13-AUG-03:01 | 0.76 |
September | 0.334820E+10 | 0.48 | 2119.26 | 30-SEP-04:01 | 0.69 |
October | 0.401665E+10 | 0.54 | 3549.17 | 22-OCT-03:02 | 0.90 |
November | 0.478851E+10 | 0.61 | 3549.17 | 08-NOV-04:03 | 0.90 |
December | 0.509136E+10 | 0.62 | 3549.17 | 01-DEC-04:09 | 0.90 |
Annual Sum or Average | 0.475010E+11 | 0.53 | |||
Minimum of Months | 0.308568E+10 | 0.45 | 1997.40 | 0.66 | |
Maximum of Months | 0.509136E+10 | 0.62 | 3549.17 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201513E+10 | 0.57 | 1327.99 | 13-JAN-05:02 | 0.84 |
February | 0.176343E+10 | 0.56 | 1254.13 | 27-FEB-05:03 | 0.81 |
March | 0.180359E+10 | 0.53 | 1230.68 | 01-MAR-05:02 | 0.81 |
April | 0.149264E+10 | 0.49 | 1163.05 | 03-APR-04:02 | 0.78 |
May | 0.140265E+10 | 0.47 | 1236.70 | 14-MAY-03:01 | 0.81 |
June | 0.136258E+10 | 0.47 | 1549.99 | 03-JUN-03:01 | 0.89 |
July | 0.142247E+10 | 0.48 | 1549.99 | 01-JUL-03:11 | 0.89 |
August | 0.140641E+10 | 0.47 | 1549.99 | 01-AUG-03:01 | 0.89 |
September | 0.138579E+10 | 0.47 | 822.53 | 28-SEP-04:04 | 0.65 |
October | 0.162448E+10 | 0.50 | 1054.80 | 31-OCT-04:03 | 0.75 |
November | 0.193248E+10 | 0.57 | 1300.51 | 29-NOV-05:02 | 0.83 |
December | 0.204997E+10 | 0.57 | 1272.93 | 28-DEC-05:02 | 0.82 |
Annual Sum or Average | 0.196616E+11 | 0.51 | |||
Minimum of Months | 0.136258E+10 | 0.47 | 822.53 | 0.65 | |
Maximum of Months | 0.204997E+10 | 0.57 | 1549.99 | 0.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 45.97 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 45.35 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 45.34 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.02 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:05 | 5.36 | 5.36 | 49.43 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:05 | 5.36 | 5.36 | 49.82 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:05 | 5.36 | 5.36 | 49.81 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 50.99 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 50.91 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 50.78 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 50.62 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 45.88 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 45.34 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 50.99 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 45.97 | 59.92 | 11181.75 | 21318.17 | 23-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 45.35 | 59.33 | 11203.73 | 21315.74 | 06-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 45.34 | 59.44 | 11299.78 | 21317.46 | 28-MAR-18:40 |
April | 0.00 | 0.00 | 01-APR-00:02 | 47.16 | 47.16 | 11215.34 | 21317.84 | 14-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 47.43 | 47.43 | 11161.89 | 21315.63 | 11-MAY-18:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 47.68 | 47.68 | 10811.09 | 20794.17 | 01-JUN-06:38 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 47.50 | 47.50 | 10307.76 | 19937.02 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 48.21 | 48.21 | 10186.06 | 19349.69 | 01-AUG-06:35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 48.45 | 48.45 | 10080.51 | 19219.52 | 29-SEP-18:10 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 45.54 | 45.54 | 10233.71 | 19766.19 | 31-OCT-18:50 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 47.95 | 47.95 | 10588.81 | 20538.85 | 30-NOV-19:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 45.88 | 59.19 | 10996.65 | 21296.17 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 10769.79 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.34 | 45.54 | 10080.51 | 19219.52 | ||
Maximum of Months | 0.00 | 0.00 | 48.45 | 59.92 | 11299.78 | 21318.17 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.497339E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.437363E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.448247E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.363820E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.361480E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.565740E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.722748E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.533593E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.334872E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.401665E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.478851E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.509136E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.565485E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.334872E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.722748E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201513E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176343E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180359E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.149303E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170143E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.335969E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.445315E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.316922E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.139350E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.162485E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.193248E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.204997E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.267595E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.139350E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.445315E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.497339E+10 | 0.00 | 0.143932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437363E+10 | 0.00 | 0.119751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.448247E+10 | 0.00 | 0.104263E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363820E+10 | 0.00 | 0.464150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329370E+10 | 0.107924E+10 | 0.102493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.308568E+10 | 0.921584E+10 | 0.127966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.319074E+10 | 0.148633E+11 | 0.110135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.321848E+10 | 0.755984E+10 | 0.369217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334820E+10 | 1673199.15 | 0.231160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401665E+10 | 0.00 | 0.690839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478851E+10 | 0.00 | 0.136974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509136E+10 | 0.00 | 0.152159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475010E+11 | 0.327199E+11 | 0.812017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308568E+10 | 0.00 | 0.110135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.509136E+10 | 0.148633E+11 | 0.152159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.201513E+10 | 0.00 | 0.846308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176343E+10 | 0.00 | 0.688405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180359E+10 | 0.00 | 0.562716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149264E+10 | 1304364.72 | 0.205337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140265E+10 | 0.104923E+10 | 0.172224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136258E+10 | 0.756354E+10 | 1853618.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142247E+10 | 0.119012E+11 | 1390277.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140641E+10 | 0.670434E+10 | 0.465387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138579E+10 | 26769065.20 | 0.562233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162448E+10 | 1228560.79 | 0.322131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193248E+10 | 0.00 | 0.795348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204997E+10 | 0.00 | 0.893015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196616E+11 | 0.272476E+11 | 0.439139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136258E+10 | 0.00 | 1390277.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204997E+10 | 0.119012E+11 | 0.893015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.497339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.448247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329370E+10 | 0.00 | 0.00 | 0.00 | 0.321106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.308568E+10 | 0.00 | 0.00 | 0.00 | 0.257172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.319074E+10 | 0.00 | 0.00 | 0.00 | 0.403673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.321848E+10 | 0.00 | 0.00 | 0.00 | 0.211745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334820E+10 | 0.00 | 0.00 | 0.00 | 525321.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475010E+11 | 0.00 | 0.00 | 0.00 | 0.904754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.509136E+10 | 0.00 | 0.00 | 0.00 | 0.403673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.201513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149264E+10 | 0.00 | 0.00 | 0.00 | 395299.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140265E+10 | 0.00 | 0.00 | 0.00 | 0.298784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136258E+10 | 0.00 | 0.00 | 0.00 | 0.199712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142247E+10 | 0.00 | 0.00 | 0.00 | 0.303069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140641E+10 | 0.00 | 0.00 | 0.00 | 0.176281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138579E+10 | 0.00 | 0.00 | 0.00 | 7707327.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162448E+10 | 0.00 | 0.00 | 0.00 | 369290.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196616E+11 | 0.00 | 0.00 | 0.00 | 0.709787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204997E+10 | 0.00 | 0.00 | 0.00 | 0.303069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130350E+12 | 0.00 | 0.00 | 3.64 |
February | 0.340018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959608E+11 | 0.00 | 0.00 | 3.59 |
March | 0.734817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497256E+11 | 0.00 | 0.00 | 3.59 |
April | 0.668079E+11 | 0.00 | 0.00 | 307461.76 | 0.00 | 0.951817E+10 | 0.531265E+09 | 0.00 | 3.59 |
May | 0.362434E+11 | 0.00 | 0.00 | 20699740.17 | 0.00 | 0.119159E+09 | 0.125930E+11 | 0.00 | 3.69 |
June | 0.149987E+11 | 11902400.52 | 0.00 | 56942347.98 | 0.00 | 10308715.12 | 0.202190E+11 | 0.00 | 3.94 |
July | 0.133286E+11 | 85842062.52 | 0.00 | 70162418.04 | 0.00 | 5670363.62 | 0.188684E+11 | 0.00 | 3.98 |
August | 0.223377E+11 | 0.00 | 0.00 | 47301549.87 | 0.00 | 9573669.52 | 0.184897E+11 | 0.00 | 3.85 |
September | 0.546444E+11 | 0.00 | 0.00 | 2786048.02 | 0.00 | 0.361447E+09 | 0.374212E+10 | 0.00 | 3.58 |
October | 0.783519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165141E+11 | 0.00 | 0.00 | 3.59 |
November | 0.288777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118600E+12 | 0.00 | 0.00 | 3.61 |
December | 0.168661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142624E+12 | 0.00 | 0.00 | 3.62 |
Annual Sum or Average | 0.461723E+12 | 97744463.04 | 0.00 | 0.198200E+09 | 0.00 | 0.563799E+12 | 0.744435E+11 | 0.00 | 3.69 |
Minimum of Months | 0.133286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5670363.62 | 0.00 | 0.00 | 3.58 |
Maximum of Months | 0.783519E+11 | 85842062.52 | 0.00 | 70162418.04 | 0.00 | 0.142624E+12 | 0.202190E+11 | 0.00 | 3.98 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130928E+09 | 0.00 | 0.00 | 7.91 |
February | 0.103013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124840E+09 | 0.00 | 0.00 | 7.72 |
March | 0.963292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86462341.27 | 0.00 | 0.00 | 7.48 |
April | 0.603859E+11 | 0.00 | 0.00 | 662281.65 | 0.00 | 33753054.93 | 0.151158E+10 | 0.00 | 7.10 |
May | 0.248699E+11 | 0.00 | 0.00 | 26529346.14 | 0.00 | 0.00 | 0.196064E+11 | 0.00 | 6.94 |
June | 0.745745E+10 | 0.00 | 0.00 | 65446361.62 | 0.00 | 0.00 | 0.276544E+11 | 0.00 | 7.04 |
July | 0.667661E+10 | 0.00 | 0.00 | 78056221.28 | 0.00 | 0.00 | 0.258719E+11 | 0.00 | 7.11 |
August | 0.123077E+11 | 0.00 | 0.00 | 57556969.73 | 0.00 | 0.00 | 0.259921E+11 | 0.00 | 6.98 |
September | 0.365677E+11 | 0.00 | 0.00 | 8907846.21 | 0.00 | 2556020.32 | 0.114372E+11 | 0.00 | 6.95 |
October | 0.729324E+11 | 0.00 | 0.00 | 176917.94 | 0.00 | 49764973.76 | 0.935452E+09 | 0.00 | 7.22 |
November | 0.117351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108830E+09 | 0.00 | 0.00 | 7.83 |
December | 0.126618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124271E+09 | 0.00 | 0.00 | 7.94 |
Annual Sum or Average | 0.785656E+12 | 0.00 | 0.00 | 0.237336E+09 | 0.00 | 0.661404E+09 | 0.113009E+12 | 0.00 | 7.35 |
Minimum of Months | 0.667661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
Maximum of Months | 0.126618E+12 | 0.00 | 0.00 | 78056221.28 | 0.00 | 0.130928E+09 | 0.276544E+11 | 0.00 | 7.94 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.179215E+11 | 0.198420E+11 | 0.433431E+12 | 0.00 | 0.655407E+11 |
February | -0.124650E+10 | 0.174135E+11 | 0.369386E+12 | 0.00 | 0.564397E+11 |
March | 0.400478E+11 | 0.192856E+11 | 0.356047E+12 | 0.00 | 0.523194E+11 |
April | 0.836705E+11 | 0.143911E+11 | 0.239391E+12 | 0.00 | 0.308000E+11 |
May | 0.114625E+12 | 0.109661E+11 | 0.174343E+12 | 0.997549E+09 | 0.218649E+11 |
June | 0.120685E+12 | 0.920338E+10 | 0.134199E+12 | 0.263261E+10 | 0.384887E+11 |
July | 0.107824E+12 | 0.822575E+10 | 0.127204E+12 | 0.243494E+10 | 0.521611E+11 |
August | 0.782196E+11 | 0.835506E+10 | 0.149321E+12 | 0.212100E+10 | 0.359507E+11 |
September | 0.310573E+11 | 0.930736E+10 | 0.192564E+12 | 30551349.91 | 0.199956E+11 |
October | 0.502058E+10 | 0.138966E+11 | 0.283785E+12 | 0.00 | 0.349218E+11 |
November | -0.100082E+11 | 0.183400E+11 | 0.419255E+12 | 0.00 | 0.627140E+11 |
December | -0.203485E+11 | 0.203249E+11 | 0.447992E+12 | 0.00 | 0.683767E+11 |
Annual Sum or Average | 0.531625E+12 | 0.169551E+12 | 0.332692E+13 | 0.821665E+10 | 0.539573E+12 |
Minimum of Months | -0.203485E+11 | 0.822575E+10 | 0.127204E+12 | 0.00 | 0.199956E+11 |
Maximum of Months | 0.120685E+12 | 0.203249E+11 | 0.447992E+12 | 0.263261E+10 | 0.683767E+11 |