Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:27:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2080.57 | 4070.34 | 4070.34 |
Net Site Energy | 2080.57 | 4070.34 | 4070.34 |
Total Source Energy | 3806.48 | 7446.84 | 7446.84 |
Net Source Energy | 3806.48 | 7446.84 | 7446.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 559.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 119.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.52 | 331.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 35.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 744.67 | 1335.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 559.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 394.51 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 119.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.52 | 331.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 559.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 45.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 413.14 | 444.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 119.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.52 | 331.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 35.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 108.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 470.29 | 1744.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 877.78 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1456.84 | 2613.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 108.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 470.29 | 1744.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 877.78 | 869.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1456.84 | 2613.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 744.667 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 744.667 | 100.00 |
Total On-Site and Utility Electric Sources | 744.667 | 100.00 |
Total Electricity End Uses | 744.667 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3454.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 5.1620 | 1.33 | 61.4214 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.3591 | 18.52 | 1000.6314 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 6.0339 | 1.78 | 317.5692 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 5.1620 | 1.33 | 61.4214 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.3591 | 18.52 | 1000.6314 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Conditioned Total | 511.15 | 6.0339 | 0.89 | 317.5692 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 6.0339 | 1.78 | 317.5692 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-17:00 | 10-JAN-21:49 | - | - | - | - | - | - | - | - | - | - | 11-JAN-07:40 |
Heating | 0.00 | 159996.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23853.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18837.19 | 15412.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4443.71 | 25930.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 56437.81 | 201339.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 159996.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23853.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 18246.39 | 15412.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4443.71 | 25930.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 362.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 593.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 606.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 142.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1308.43 | 481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 378.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.16 | 359.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2358.36 | 1448.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1187.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 279.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 739.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.89 | 703.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 220.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4613.80 | 2833.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1187.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 279.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2559.75 | 942.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 739.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.89 | 703.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 220.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4613.80 | 2833.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.82 |
KITCHEN DIRECT AIR | 1.54 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.82 | 3.82 | 3.82 | 3.82 | 3.82 | 3.82 | 1.00 | 1.00 | 3.82 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.54 | 1.54 | 1.55 | 1.55 | 1.00 | 0.995712 | 1.55 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.82 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.55 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.82 | 6522.33 |
PSZ-AC_2:2_ADDAQ FAN | 1.55 | 1659.12 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.82 | 3.82 | 3.82 | 2.52 | 75241.94 | 145230.20 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.55 | 1.55 | 1.55 | 1.02 | 34859.15 | 94549.85 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.82 | 1.91 | 2.54 | 75241.94 | 37620.97 | 0.781770 | 0.781770 |
PSZ-AC_2:2 COOLING COIL | 1.55 | 0.775256 | 1.03 | 34859.15 | 17429.58 | 0.732700 | 0.732700 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 145230.20 |
PSZ-AC_2:2 HEATING COIL | 94549.85 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 5.162 | 61.421 | 0.000 | 0.000 | 0.000 | 0.000 | 66.583 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.359 | 386.416 | 614.215 | 0.000 | 0.000 | 0.000 | 1008.991 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 1918.948 | 5.162 | 6.850 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1918.948 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1165.301 | 8.359 | 154.798 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1165.301 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 22833.282 | 61.421 | 81.506 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6621.652 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 53277.659 | 382.178 | 7077.360 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 15450.521 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 85624.808 | 614.215 | 11374.329 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 24831.194 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.5101 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1345 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2291 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.726 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.356 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.287 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.34199593E-12 | 0.79080657E-15 | -0.11283654E-12 | 0.10742775E-15 |
34 | 6 | 0.31804408E-07 | 0.14767105E-09 | 0.72595440E-08 | -0.15210669E-12 |
35 | 5 | -0.20588816E-03 | 0.12400370E-05 | -0.10566992E-03 | 0.71658914E-08 |
36 | 4 | 0.31042582 | 0.59335955E-03 | 0.10626624 | -0.36169390E-04 |
37 | 3 | -7.6278987 | 0.18106703E-01 | -2.4462343 | 0.30782168E-01 |
38 | 2 | 42.063121 | 0.63508807E-01 | 15.704238 | -0.34661865 |
39 | 1 | -81.458683 | 0.28319827E-01 | -29.535100 | 1.0980742 |
40 | 0 | 46.824333 | 0.56308001E-03 | 16.282029 | |
41 | 7 | -0.31585163E-08 | -0.22597303E-14 | 0.15834007E-14 | -0.44811583E-16 |
42 | 6 | 0.38926816E-05 | 0.25726622E-08 | 0.31949392E-02 | -0.26801827E-04 |
43 | 5 | -0.27259256E-03 | 0.15209505E-05 | -0.22401268 | 0.19586932E-02 |
44 | 4 | 0.62224649E-02 | 0.69174334E-04 | 4.8343438 | -0.45311104E-01 |
45 | 3 | -0.54492574E-01 | 0.54963890E-03 | -38.048519 | 0.39895333 |
46 | 2 | 0.19328371 | 0.91376166E-03 | 116.53670 | -1.4186449 |
47 | 1 | -0.27884260 | 0.27809541E-03 | -143.93836 | 2.0495503 |
48 | 0 | 0.13591665 | 0.67534627E-05 | 60.838472 | |
49 | 7 | -0.18366387E-08 | -0.45273224E-15 | 0.66973396E-14 | -0.89481334E-16 |
50 | 6 | 0.64176182E-05 | 0.43906086E-08 | 0.31875387E-02 | -0.26739746E-04 |
51 | 5 | -0.46144041E-03 | 0.26013657E-05 | -0.22359208 | 0.19549808E-02 |
52 | 4 | 0.10613927E-01 | 0.11841222E-03 | 4.8273389 | -0.45243768E-01 |
53 | 3 | -0.93204934E-01 | 0.94170345E-03 | -38.008950 | 0.39851596 |
54 | 2 | 0.33095125 | 0.15665766E-02 | 116.45969 | -1.4176148 |
55 | 1 | -0.47767855 | 0.47741295E-03 | -143.89302 | 2.0488052 |
56 | 0 | 0.23289156 | 0.11519323E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 39 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 40 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 41 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.884 | 0.3002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 3.373E-002 | 9.073E-005 | 1.994E-004 | 0.107 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 2.124E-002 | 1.523E-004 | 1.958E-004 | 0.180 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.8398E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8346E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7625E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6346E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5229E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5709E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1282E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0430E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0722E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.7665E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.3122E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.9275E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2565E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1756E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0686E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0686E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6020E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5330E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3289E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3611E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2792E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2902E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0430E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1282E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 38143.46190 | 45772.15428 | 3.18113 | 3.81736 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 9611.71723 | 11534.06068 | 0.47106 | 1.33138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -27.60000 | 3.41898E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 18355.35009 | 22026.42011 | 1.28655 | 1.54386 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 1495.97265 | 1795.16718 | 6.63304E-002 | 1.21700 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60000 | 3.41898E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 58439.45 | 3.81736 | 3.81736 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 95244.28 | 1.33138 | 1.33138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 30122.28 | 1.55051 | 1.55051 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 87062.07 | 1.21700 | 1.21700 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.81736 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54386 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.81736 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.81736 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.81736 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.81736 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.81736 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.81736 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.54386 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54386 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.54386 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54386 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.55051 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.55051 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.99571 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.81736 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.55051 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.81736 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.81736 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6522.32796 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.81736 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.81736 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.81736 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.51945 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.81736 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.90868 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.54491 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 75241.94000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 37620.97000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78177 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78177 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 75241.94000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 145230.19640 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 145230.19640 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.55051 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.55051 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1659.12160 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.55051 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.55051 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.55051 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02334 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.55051 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77526 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03367 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34859.15000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17429.57500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73270 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73270 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34859.15000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 94549.85063 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 94549.85063 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 72479.5 | 10.39 | 10.34 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 33747.9 | 11.66 | 11.60 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.510 | 0.474 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.510 | 0.474 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.510 | 0.474 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.135 | 0.130 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.510 | 0.474 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.510 | 0.474 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.510 | 0.474 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.229 | 0.217 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.2602978850E-002 | 0.3639126321 | Pass | Pass | 7.9810359580E-002 | 0.1819769278 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1146404607 | 0.5049486668 | Pass | Pass | 2.5716039057E-002 | 8.1568722033E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2789463252 | 0.2905784576 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 933.60 | 118.64 | 2162.93 | 17.07 | 475.49 | 3707.73 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.474 | 0.510 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.474 | 0.510 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.474 | 0.510 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.132 | 0.135 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.474 | 0.510 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.474 | 0.510 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.474 | 0.510 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.221 | 0.229 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 5.1620 | 371.75 | 1918.95 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.01 | 0.0000 | Y | 21.61 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.3591 | 139.41 | 1165.30 | LightsWired | LTG_SCH_KITCHEN | 79.77 | 168.00 | 76.30 | 0.0000 | Y | 16.69 |
Interior Lighting Total | 6.0339 | 511.15 | 3084.25 | 38.31 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 1918.95 | 479.74 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 204.54 | AstronomicalClock | - | 49.11 | 49.11 | 1.89 | |
EXTERIOR_LIGHTS_B | 1305.94 | AstronomicalClock | - | 83.57 | 62.84 | 15.40 | |
Exterior Lighting Total | 1510.48 | 17.29 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 75241.94 | 58821.89 | 16420.05 | 0.78 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34859.15 | 25541.30 | 9317.85 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 72479.5 | 10.39 | 10.34 | ||||
PSZ-AC_2:2 COOLING COIL | 33747.9 | 11.66 | 11.60 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 145230.20 | 0.85 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 94549.85 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.82 | 6522.33 | 1708.60 | 1.00 | 1.18 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.55 | 1659.12 | 1070.05 | 1.00 | 1.36 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.95 | 0.88 | 0.30 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 38143.46 | 45772.15 | 123.13 | 3.181 | 3.817 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.00858 | 33.24 | 0.00631 | 1.331 | 0.00 |
KITCHEN | 18355.35 | 22026.42 | 158.00 | 1.287 | 1.544 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 26.00 | 25.99 | 0.00898 | 18.84 | 0.00628 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9611.72 | 11534.06 | 31.03 | 0.471 | 1.331 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00791 | -27.60 | 0.00034 | 1.331 | 0.00 |
KITCHEN | 1495.97 | 1795.17 | 12.88 | 0.066 | 1.217 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00676 | -27.60 | 0.00034 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.82 | 3.82 | 1.33 | 1.33 | 3.8174 | 3.8174 | 3.8174 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.55 | 1.55 | 1.22 | 1.22 | 1.5505 | 1.5439 | 1.5505 | 0.9957 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 75241.940 | 58821.891 | 3.817360 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37620.97 | 34321.10 | 2.544907 | 27.27 | 15.54 | 0.00778632 | 11.21 | 8.73 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 52.3154 | 23.99 | 0.00857897 | 40.4193 | 38132.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 145230.196 | 145230.196 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 145230.20 | 145230.20 | 3.817356 | 4.05 | 3.41 | 0.00526769 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 34.8770 | 21.00 | 0.00790572 | 44.7053 | 9610.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 34859.150 | 25541.299 | 1.550510 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 17429.58 | 17429.57 | 1.033673 | 32.09 | 16.32 | 0.00678164 | 11.80 | 8.76 | 0.00678164 | 33.40 | 0.00630683 | 16.37 | 117.7356 | 25.98 | 0.00901853 | 37.7025 | 17368.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 94549.851 | 94549.851 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | 94549.85 | 94549.85 | 1.550512 | -17.72 | -17.72 | 0.00169264 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 78.4903 | 19.00 | 0.00662161 | 42.4716 | 1260.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 75241.940 | 58821.891 | 3.817360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3144 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.817356 | 4.02020990 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 37620.97 | 34321.10 | 1.0000 | 2.68014270 | 2.544907 | 27.27 | 15.54 | 0.00778632 | 47269.6 | 11.21 | 8.73 | 0.00700000 | 28915.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37620.97 | 33.40 | 0.00630683 | 16.37 | 1.33137743 | 52.3154 | 23.99 | 0.00857897 | 23.99 | 0.00857897 | 40.4193 | 38132.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 145230.196 | 145230.196 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.817356 | 4.02020990 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 145230.20 | 145230.20 | 1.0000 | 4.02020990 | 3.817356 | 4.05 | 3.41 | 0.00526769 | 17283.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 145230.20 | -27.60 | 0.00034190 | -27.60 | 1.33137743 | 34.8770 | 21.00 | 0.00790572 | 21.00 | 0.00790572 | 44.7053 | 9610.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34859.150 | 25541.299 | 1.550510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.4467 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.550512 | 1.63290648 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 17429.58 | 17429.57 | 1.0000 | 1.08860261 | 1.033673 | 32.09 | 16.32 | 0.00678164 | 49613.8 | 11.80 | 8.76 | 0.00678164 | 28967.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17429.58 | 33.40 | 0.00630683 | 16.37 | 1.21700195 | 117.7356 | 25.94 | 0.00901853 | 25.98 | 0.00901853 | 37.7025 | 17368.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94549.851 | 94549.851 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.550512 | 1.63290648 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | Sensible | 94549.85 | 94549.85 | 1.0000 | 1.63290648 | 1.550512 | -17.72 | -17.72 | 0.00169264 | -13623.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94549.85 | -27.60 | 0.00034190 | -27.60 | 1.21700195 | 78.4903 | 18.35 | 0.00662161 | 19.00 | 0.00662161 | 42.4716 | 1260.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.82 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2687.17 | 5203.00 | 1355.17 |
KITCHEN | 4369.33 | 5914.50 | 3346.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4476.00 | 6871.50 | 3454.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 18.00 | 5.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 56.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 18.00 | 61.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.09 | 280.14 | 1133.39 | 4.542 | 0.582 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 9.077 | 0.016 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.09 | 280.14 | 1133.39 | 4.066 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 8.496 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.09 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.17 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.26 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 37273114.34 | 0.00 | 37273114.34 | 4733309.30 | 42006423.64 | 41986318.57 | 1453.72 | 6079.95 | 1226.32 | 217.75 |
KITCHEN | 28042314.91 | 0.00 | 28042314.91 | 76378.33 | 28118693.23 | 38379373.44 | 8269.18 | 487.95 | 2.87 | 332.56 |
Total Facility | 65315429.25 | 0.00 | 65315429.25 | 4809687.62 | 70125116.87 | 80365692.01 | 8270.67 | 6079.97 | 1228.08 | 415.13 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.4143 | 0.0000 | 1.4143 | 0.1811 | 1.5954 | 1.3314 | 0.00 | 5964.52 | 1222.48 |
KITCHEN | 1.0595 | 0.0000 | 1.0595 | 0.0018 | 1.0613 | 1.2170 | 6708.87 | 477.91 | 0.22 |
Total Facility | 2.4738 | 0.0000 | 2.4738 | 0.1830 | 2.6568 | 2.5484 | 6708.87 | 5964.52 | 1222.70 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 41339788.23 | 0.00 | 41339788.23 | 41986318.57 | 1453.38 | 0.06 | 7306.56 | 217.75 |
PSZ-AC_2:2 | 31101736.57 | 0.00 | 31101736.57 | 38379373.44 | 7163.39 | 379.68 | 1216.92 | 332.56 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.5686 | 0.0000 | 1.5686 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1751 | 0.0000 | 1.1751 | 1.2170 | 5627.09 | 371.57 | 1188.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1034.18 | 296.35 | 6074.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 103.00 | 1229.48 | 6187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.0966 | 1.7608 | 1.4770 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.1478 | 1.2564 | 1.1627 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
Electricity:Building | 458.38 | 2350.73 | 01-JAN-01:20 | 26459.53 | 02-JAN-11:10 |
Electricity:Zone:DINING | 139.97 | 534.11 | 01-JAN-01:20 | 7569.70 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 451.45 | 2214.45 | 01-JAN-01:20 | 24316.43 | 02-JAN-11:10 |
InteriorLights:Electricity | 38.31 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 21.62 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 38.31 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 38.31 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 21.62 | 80.03 | 01-JAN-01:20 | 1639.63 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 38.31 | 110.04 | 01-JAN-01:20 | 2497.72 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 318.41 | 1816.62 | 01-JAN-01:20 | 19025.40 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.69 | 30.01 | 01-JAN-01:20 | 858.09 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 413.14 | 2104.41 | 01-JAN-01:10 | 22638.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 118.35 | 454.08 | 01-JAN-01:10 | 6614.32 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 394.51 | 1513.61 | 01-JAN-01:10 | 22047.72 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 294.79 | 1650.33 | 01-JAN-01:10 | 16024.20 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 276.16 | 1059.53 | 01-JAN-01:10 | 15433.40 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 35.54 | 595.54 | 10-JAN-23:30 | 2771.45 | 07-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 104.57 | 741.01 | 28-JAN-01:10 | 5837.44 | 06-SEP-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 10.72 | 0.00 | 01-JAN-11:10 | 1023.21 | 05-SEP-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 17.88 | 509.04 | 27-JAN-05:40 | 637.09 | 02-MAY-13:10 |
ElectricityPurchased:Facility | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
ElectricityPurchased:Plant | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
Cogeneration:ElectricityPurchased | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
General:Cogeneration:ElectricityPurchased | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
ElectricityNet:Plant | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
Cogeneration:ElectricityNet | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
General:Cogeneration:ElectricityNet | 744.67 | 3783.97 | 11-JAN-01:40 | 56437.81 | 17-JUL-18:00 |
Electricity:HVAC | 164.43 | 0.00 | 01-JAN-01:10 | 30339.47 | 17-JUL-17:40 |
Fans:Electricity | 119.39 | 0.00 | 01-JAN-01:10 | 6888.42 | 10-JAN-23:10 |
General:Fans:Electricity | 119.39 | 0.00 | 01-JAN-01:10 | 6888.42 | 10-JAN-23:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 45.04 | 0.00 | 01-JAN-00:10 | 23877.04 | 17-JUL-17:30 |
General:Cooling:Electricity | 45.04 | 0.00 | 01-JAN-00:10 | 23877.04 | 17-JUL-17:30 |
ExteriorLights:Electricity | 17.29 | 0.00 | 01-JAN-08:20 | 1510.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 17.29 | 0.00 | 01-JAN-08:20 | 1510.48 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.24 | 18-APR-18:30 |
Water Heater:WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.24 | 18-APR-18:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 03-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 03-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1335.90 | 2515.72 | 01-JAN-01:20 | 201339.79 | 10-JAN-21:50 |
NaturalGas:Building | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 444.42 | 1712.50 | 01-JAN-01:10 | 24831.19 | 01-JAN-11:10 |
NaturalGas:HVAC | 559.92 | 0.00 | 01-JAN-01:10 | 170758.61 | 07-JAN-04:10 |
Heating:NaturalGas | 559.92 | 0.00 | 01-JAN-01:10 | 170758.61 | 07-JAN-04:10 |
General:Heating:NaturalGas | 559.92 | 0.00 | 01-JAN-01:10 | 170758.61 | 07-JAN-04:10 |
NaturalGas:Plant | 331.56 | 803.23 | 08-JAN-05:10 | 29718.07 | 15-FEB-07:20 |
WaterSystems:NaturalGas | 331.56 | 803.23 | 08-JAN-05:10 | 29718.07 | 15-FEB-07:20 |
Water Heater:WaterSystems:NaturalGas | 331.56 | 803.23 | 08-JAN-05:10 | 29718.07 | 15-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1616.81 | 2930.01 | 11-JAN-01:10 | 177043.42 | 10-JAN-22:00 |
EnergyTransfer:Building | 634.22 | 1465.01 | 11-JAN-01:10 | 46604.50 | 17-JUL-17:40 |
EnergyTransfer:Zone:KITCHEN | 380.74 | 1465.01 | 11-JAN-01:10 | 22301.25 | 25-NOV-12:00 |
Refrigeration:EnergyTransfer | 132.90 | 2620.82 | 10-JAN-23:10 | 7834.84 | 30-JUN-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.45 | 1310.41 | 10-JAN-23:10 | 3917.42 | 30-JUN-03:20 |
General:Refrigeration:EnergyTransfer | 66.45 | 1310.41 | 10-JAN-23:10 | 3917.42 | 30-JUN-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.45 | 1310.41 | 10-JAN-23:10 | 3917.42 | 30-JUN-03:20 |
EnergyTransfer:Plant | 346.06 | 1465.01 | 11-JAN-01:10 | 21361.18 | 27-FEB-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 11.96 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 54.49 | 1305.24 | 27-JAN-05:40 | 2238.70 | 02-MAY-13:10 |
EnergyTransfer:Zone:DINING | 253.48 | 0.00 | 01-JAN-01:10 | 38456.48 | 29-JAN-04:20 |
Heating:EnergyTransfer | 6.87 | 0.00 | 01-JAN-00:10 | 25494.73 | 08-JAN-04:10 |
Heating:EnergyTransfer:Zone:DINING | 6.85 | 0.00 | 01-JAN-00:10 | 25494.73 | 08-JAN-04:10 |
General:Heating:EnergyTransfer | 6.87 | 0.00 | 01-JAN-00:10 | 25494.73 | 08-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:DINING | 6.85 | 0.00 | 01-JAN-00:10 | 25494.73 | 08-JAN-04:10 |
Cooling:EnergyTransfer | 560.90 | 0.00 | 01-JAN-01:10 | 44366.22 | 17-JUL-17:40 |
Cooling:EnergyTransfer:Zone:DINING | 246.63 | 0.00 | 01-JAN-01:10 | 28896.75 | 17-JUL-17:40 |
General:Cooling:EnergyTransfer | 560.90 | 0.00 | 01-JAN-01:10 | 44366.22 | 17-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:DINING | 246.63 | 0.00 | 01-JAN-01:10 | 28896.75 | 17-JUL-17:40 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 2073.62 | 08-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 2073.62 | 08-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 314.28 | 0.00 | 01-JAN-01:10 | 19064.61 | 25-NOV-12:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 314.28 | 0.00 | 01-JAN-01:10 | 19064.61 | 25-NOV-12:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 279.61 | 0.00 | 01-JAN-01:10 | 19196.11 | 17-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 279.61 | 0.00 | 01-JAN-01:10 | 19196.11 | 17-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19196.11 | 17-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19196.11 | 17-FEB-07:20 |
EnergyTransfer:HVAC | 636.53 | 0.00 | 01-JAN-01:10 | 145230.20 | 28-DEC-04:50 |
HeatingCoils:EnergyTransfer | 476.21 | 0.00 | 01-JAN-01:10 | 145230.20 | 28-DEC-04:50 |
CoolingCoils:EnergyTransfer | 160.32 | 0.00 | 01-JAN-00:10 | 80155.12 | 17-JUL-17:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19196.11 | 17-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19196.11 | 17-FEB-07:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 6.855 | -246.623 | 0.000 | 0.000 | 230.302 | 21.615 | 88.765 | 47.998 | 0.000 | 1.896 | 0.000 | 0.000 | -26.862 | 0.000 | -73.315 | -50.632 |
KITCHEN | 0.000 | 0.000 | 0.017 | -314.262 | 0.000 | 0.000 | 6.126 | 16.690 | 259.402 | 0.000 | 0.000 | 0.008 | 33.396 | 0.000 | 0.000 | 0.000 | -1.376 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.985 | 25.779 | 0.000 | 0.000 | 0.000 | -32.764 | -0.000 |
Total Facility | 0.000 | 0.000 | 6.872 | -560.885 | 0.000 | 0.000 | 236.428 | 38.306 | 348.168 | 47.998 | 0.000 | 8.889 | 59.175 | 0.000 | -26.862 | 0.000 | -107.455 | -50.632 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 26-JUL-03:01 | 0.00 | 0.00 | 0.00 | -72925.91 | 0.00 | 0.00 | 0.00 | 80.03 | 851.41 | 0.00 | 0.00 | 0.00 | 72682.81 | 0.00 | -654.42 | 0.00 | -33.92 | 0.00 |
KITCHEN | 28-SEP-03:01 | 0.00 | 0.00 | 0.00 | -55664.39 | 0.00 | 0.00 | 0.00 | 30.01 | 2903.90 | 0.00 | 0.00 | 0.00 | 52878.05 | 0.00 | -0.00 | 0.00 | -147.57 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-AUG-03:01 | 0.00 | 0.00 | 0.00 | -116704.77 | 0.00 | 0.00 | 0.00 | 110.04 | 3755.31 | 0.00 | 0.00 | 264.03 | 113704.31 | 0.00 | -1058.08 | 0.00 | -70.84 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 05-FEB-05:01 | 0.00 | 0.00 | 89408.93 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 2043.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2937.16 | 0.00 | -59.49 | -88535.68 |
KITCHEN | 08-JAN-05:02 | 0.00 | 0.00 | 18635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 6142.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -61.27 | -24746.69 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-FEB-05:01 | -43697.22 | 43697.22 | 89408.93 | -43697.22 | 0.00 | 0.00 | 0.00 | 110.04 | 8185.62 | 0.00 | 0.00 | 359.11 | 0.00 | 0.00 | -2937.16 | 0.00 | -97.37 | -51331.94 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.8174 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.8174 | 0.3488 | 1.0000 | Not calculated | 1.3314 | 0.3488 | ||
PSZ-AC_2:2 | 1.5439 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5505 | 0.1178 | 1.0000 | Not calculated | 0.1826 | 0.1178 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.8174 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.8174 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3488 | ||
PSZ-AC_2:2 | 1.5439 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5439 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1183 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8174 | 3.8174 | 3.8174 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5439 | 1.5439 | 1.5439 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.8174 | 3.8174 | 3.8174 | 3.8174 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5439 | 1.5505 | 1.5439 | 1.5439 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8174 | 3.8174 | 3.8174 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5439 | 1.5439 | 1.5439 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.8174 | 3.8174 | 3.8174 | 3.8174 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5439 | 1.5439 | 1.5439 | 1.5439 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 559.92 | 170758.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 45.04 | 23877.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 38.31 | 2497.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 17.29 | 1510.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 394.51 | 22047.72 | 444.42 | 24831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 119.39 | 6888.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.52 | 4742.24 | 331.56 | 29718.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.72 | 1023.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.88 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 448.68 | 744.67 |
Natural Gas | 444.42 | 1335.90 |
Additional | 0.00 | 0.00 |
Total | 893.10 | 2080.57 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 74.94 |
Space Heating | 0.00 |
Space Cooling | 88.12 |
Fans (All) | 233.56 |
Service Water Heating | 147.74 |
Receptacle Equipment | 808.26 |
Miscellaneous (All) | 1456.84 |
Subtotal | 1456.84 |
Natural Gas [MJ/m2] | |
Space Heating | 1095.41 |
Service Water Heating | 648.66 |
Miscellaneous (All) | 2613.51 |
Subtotal | 2613.51 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.84 |
Space Heating | 26.91 |
Space Cooling | 2.16 |
Fans (All) | 5.74 |
Service Water Heating | 19.57 |
Receptacle Equipment | 41.22 |
Miscellaneous | 2.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 4159. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8351.50 | 408.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7486.83 | 467.83 | 388.67 | 407.83 | 8.83 |
Min | 7486.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 467.83 | 388.67 | 407.83 | 8.83 |
Average | 8199.44 | 292.11 | 129.56 | 135.94 | 2.94 |
Sum | 24598.33 | 876.33 | 388.67 | 407.83 | 8.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8101.83 | 658.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7665.67 | 603.17 | 203.67 | 168.00 | 119.50 |
Min | 7665.67 | 11.83 | 0.00 | 0.00 | 0.00 |
Max | 8748.17 | 658.17 | 203.67 | 168.00 | 119.50 |
Average | 8171.89 | 424.39 | 67.89 | 56.00 | 39.83 |
Sum | 24515.67 | 1273.17 | 203.67 | 168.00 | 119.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 823557.00 | 665.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 18259.17 | 973.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823557.00 | 973.83 | 0.00 | 0.00 | 0.00 |
Average | 280605.39 | 546.28 | 0.00 | 0.00 | 0.00 |
Sum | 841816.17 | 1638.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:36
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.919965E+10 | 66679.80 | 11-JAN-00:01 | -31.6 | -31.8 | 0.118571E+11 | 11115.77 | 14-JAN-19:00 | 9.40 | 3.77 |
February | 0.121049E+11 | 52929.21 | 04-FEB-00:01 | -21.0 | -21.3 | 0.108476E+11 | 12849.63 | 27-FEB-12:00 | 17.20 | 6.49 |
March | 0.158340E+11 | 55645.07 | 05-MAR-00:01 | -23.1 | -23.6 | 0.120641E+11 | 12370.77 | 14-MAR-11:00 | 14.40 | 6.37 |
April | 0.188242E+11 | 31451.58 | 28-APR-23:01 | -4.6 | -6.2 | 0.123370E+11 | 13976.61 | 22-APR-18:10 | -4.6 | -6.2 |
May | 0.221186E+11 | 52457.58 | 20-MAY-03:01 | 14.22 | 9.93 | 0.135041E+11 | 13979.26 | 20-MAY-18:00 | 22.80 | 13.54 |
June | 0.267374E+11 | 62360.18 | 21-JUN-03:01 | 19.22 | 13.03 | 0.143106E+11 | 13979.73 | 03-JUN-18:00 | 19.22 | 13.03 |
July | 0.315075E+11 | 72934.82 | 26-JUL-03:01 | 19.68 | 11.10 | 0.149988E+11 | 13979.53 | 01-JUL-18:10 | 19.68 | 11.10 |
August | 0.307781E+11 | 71132.98 | 08-AUG-03:01 | 18.22 | 11.44 | 0.150372E+11 | 13979.02 | 26-AUG-18:00 | 20.60 | 12.09 |
September | 0.265554E+11 | 69281.72 | 04-SEP-03:01 | 21.10 | 12.40 | 0.137698E+11 | 13978.86 | 23-SEP-18:40 | 16.50 | 9.82 |
October | 0.235164E+11 | 28734.38 | 21-OCT-04:01 | -1.0 | -1.9 | 0.130742E+11 | 13974.66 | 28-OCT-18:30 | 13.60 | 6.97 |
November | 0.174494E+11 | 45170.58 | 27-NOV-00:01 | -15.1 | -15.9 | 0.118530E+11 | 13974.92 | 04-NOV-18:10 | -15.1 | -15.9 |
December | 0.119998E+11 | 56239.67 | 29-DEC-00:01 | -23.6 | -23.9 | 0.118773E+11 | 11704.30 | 06-DEC-12:00 | -23.6 | -23.9 |
Annual Sum or Average | 0.246625E+12 | 0.155531E+12 | ||||||||
Minimum of Months | 0.919965E+10 | 28734.38 | -31.6 | -31.8 | 0.108476E+11 | 11115.77 | -23.6 | -23.9 | ||
Maximum of Months | 0.315075E+11 | 72934.82 | 21.10 | 13.03 | 0.150372E+11 | 13979.73 | 22.80 | 13.54 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249420E+11 | 52519.23 | 27-JAN-05:01 | -27.8 | -28.2 | 0.984141E+10 | 6482.50 | 14-JAN-11:00 | -27.8 | -28.2 |
February | 0.230829E+11 | 49271.66 | 01-FEB-05:01 | -25.0 | -25.2 | 0.890098E+10 | 6564.99 | 27-FEB-11:00 | 16.10 | 6.08 |
March | 0.259990E+11 | 43497.57 | 05-MAR-05:01 | -20.3 | -21.0 | 0.985580E+10 | 6517.98 | 14-MAR-10:00 | 12.80 | 5.58 |
April | 0.251199E+11 | 37084.00 | 08-APR-03:01 | 8.30 | 3.71 | 0.958890E+10 | 6568.39 | 07-APR-10:09 | 8.30 | 3.71 |
May | 0.262356E+11 | 49688.49 | 31-MAY-03:01 | 8.72 | 5.88 | 0.995219E+10 | 6568.43 | 19-MAY-10:20 | 8.72 | 5.88 |
June | 0.261073E+11 | 54523.72 | 20-JUN-03:01 | 7.62 | 4.76 | 0.970009E+10 | 6568.46 | 06-JUN-10:09 | 7.62 | 4.76 |
July | 0.276983E+11 | 53481.01 | 12-JUL-03:01 | 10.27 | 5.20 | 0.100367E+11 | 6568.47 | 07-JUL-10:00 | 10.27 | 5.20 |
August | 0.277145E+11 | 52915.85 | 28-AUG-03:01 | 9.90 | 5.61 | 0.100368E+11 | 6568.43 | 23-AUG-10:50 | 9.90 | 5.61 |
September | 0.269214E+11 | 55748.37 | 28-SEP-03:01 | 5.65 | 2.71 | 0.967305E+10 | 6568.43 | 07-SEP-10:30 | 5.65 | 2.71 |
October | 0.279582E+11 | 51703.76 | 19-OCT-03:01 | 12.80 | 5.83 | 0.993478E+10 | 6568.41 | 16-OCT-10:09 | 12.80 | 5.83 |
November | 0.263526E+11 | 39852.53 | 27-NOV-05:01 | -15.4 | -16.5 | 0.956208E+10 | 6560.43 | 17-NOV-11:00 | -15.4 | -16.5 |
December | 0.261437E+11 | 50165.06 | 29-DEC-05:01 | -25.0 | -25.3 | 0.984600E+10 | 6524.76 | 06-DEC-11:00 | -25.0 | -25.3 |
Annual Sum or Average | 0.314275E+12 | 0.116929E+12 | ||||||||
Minimum of Months | 0.230829E+11 | 37084.00 | -27.8 | -28.2 | 0.890098E+10 | 6482.50 | -27.8 | -28.2 | ||
Maximum of Months | 0.279582E+11 | 55748.37 | 12.80 | 5.88 | 0.100368E+11 | 6568.47 | 16.10 | 6.08 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.9 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 | -4.1 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 | 0.55 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 | 13.32 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 | 11.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 | 11.59 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 | 6.94 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 | 1.54 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.00 | 0.00 | -12.4 | -13.9 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.00 | 0.00 | 19.45 | 13.32 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354886E+10 | 83260.31 | 28-JAN-04:51 | -27.8 |
February | 0.101973E+10 | 89407.97 | 05-FEB-05:01 | -20.0 |
March | 0.578666E+09 | 88372.25 | 05-MAR-05:01 | -20.3 |
April | 0.100795E+09 | 27555.00 | 29-APR-03:02 | -6.9 |
May | 48819124.50 | 25368.29 | 01-MAY-03:02 | -0.7 |
June | 3827856.00 | 8239.49 | 15-JUN-04:03 | 0.97 |
July | 1770916.66 | 7871.27 | 26-JUL-03:45 | 20.82 |
August | 2379347.36 | 5877.06 | 12-AUG-03:47 | 15.00 |
September | 2115881.94 | 9105.44 | 17-SEP-04:03 | 1.02 |
October | 9120173.46 | 17629.22 | 10-OCT-04:01 | -5.2 |
November | 0.177747E+09 | 52774.43 | 11-NOV-05:06 | -7.9 |
December | 0.136106E+10 | 88593.04 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.685490E+10 | |||
Minimum of Months | 1770916.66 | 5877.06 | -27.8 | |
Maximum of Months | 0.354886E+10 | 89407.97 | 20.82 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7684701.71 | 18662.60 | 08-JAN-05:02 | -26.7 |
February | 1933319.34 | 9689.33 | 23-FEB-05:03 | -9.9 |
March | 1482589.50 | 8675.97 | 05-MAR-05:02 | -20.3 |
April | 672237.30 | 8302.85 | 29-APR-04:03 | -7.8 |
May | 3885.97 | 64.77 | 15-MAY-04:05 | 3.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 27772.25 | 462.87 | 05-OCT-04:04 | -1.7 |
November | 1181991.92 | 10859.95 | 12-NOV-05:03 | -10.6 |
December | 3632755.11 | 10736.61 | 16-DEC-05:03 | -9.4 |
Annual Sum or Average | 16619253.10 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 7684701.71 | 18662.60 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.206780E+10 | 1639.63 | 02-JAN-16:40 | 0.100519E+11 | 6614.32 | 01-JAN-11:09 |
February | 0.176408E+10 | 1639.63 | 01-FEB-17:19 | 0.907918E+10 | 6614.32 | 01-FEB-11:09 |
March | 0.187090E+10 | 1639.63 | 01-MAR-18:10 | 0.100520E+11 | 6614.32 | 01-MAR-11:09 |
April | 0.169213E+10 | 1639.63 | 01-APR-18:49 | 0.972770E+10 | 6614.32 | 01-APR-10:09 |
May | 0.167163E+10 | 1639.63 | 01-MAY-19:30 | 0.100520E+11 | 6614.32 | 01-MAY-10:09 |
June | 0.155876E+10 | 1639.63 | 01-JUN-20:10 | 0.972773E+10 | 6614.32 | 01-JUN-10:09 |
July | 0.164438E+10 | 1639.63 | 01-JUL-20:30 | 0.100519E+11 | 6614.32 | 01-JUL-10:09 |
August | 0.170372E+10 | 1639.63 | 01-AUG-19:00 | 0.100520E+11 | 6614.32 | 01-AUG-10:09 |
September | 0.173145E+10 | 1639.63 | 01-SEP-19:10 | 0.972770E+10 | 6614.32 | 01-SEP-10:09 |
October | 0.188614E+10 | 1639.63 | 02-OCT-17:00 | 0.100519E+11 | 6614.32 | 01-OCT-10:09 |
November | 0.194920E+10 | 1639.63 | 01-NOV-17:10 | 0.972767E+10 | 6614.32 | 01-NOV-10:09 |
December | 0.207504E+10 | 1639.63 | 01-DEC-16:40 | 0.100519E+11 | 6614.32 | 01-DEC-11:09 |
Annual Sum or Average | 0.216152E+11 | 0.118354E+12 | ||||
Minimum of Months | 0.155876E+10 | 1639.63 | 0.907918E+10 | 6614.32 | ||
Maximum of Months | 0.207504E+10 | 1639.63 | 0.100520E+11 | 6614.32 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140982E+10 | 858.09 | 02-JAN-10:09 | 0.250369E+11 | 16024.20 | 01-JAN-11:09 |
February | 0.127710E+10 | 858.09 | 01-FEB-10:09 | 0.226140E+11 | 16024.20 | 01-FEB-11:09 |
March | 0.143409E+10 | 858.09 | 01-MAR-10:09 | 0.250371E+11 | 16024.20 | 01-MAR-11:09 |
April | 0.136995E+10 | 858.09 | 01-APR-16:10 | 0.242293E+11 | 16024.20 | 01-APR-10:09 |
May | 0.142196E+10 | 858.09 | 01-MAY-09:09 | 0.250370E+11 | 16024.20 | 01-MAY-10:09 |
June | 0.138598E+10 | 858.09 | 01-JUN-09:09 | 0.242294E+11 | 16024.20 | 01-JUN-10:09 |
July | 0.140610E+10 | 858.09 | 01-JUL-16:10 | 0.250369E+11 | 16024.20 | 01-JUL-10:09 |
August | 0.143409E+10 | 858.09 | 01-AUG-09:09 | 0.250371E+11 | 16024.20 | 01-AUG-10:09 |
September | 0.137029E+10 | 858.09 | 01-SEP-09:09 | 0.242293E+11 | 16024.20 | 01-SEP-10:09 |
October | 0.140965E+10 | 858.09 | 02-OCT-09:09 | 0.250369E+11 | 16024.20 | 01-OCT-10:09 |
November | 0.136509E+10 | 858.09 | 01-NOV-09:09 | 0.242292E+11 | 16024.20 | 01-NOV-10:09 |
December | 0.140627E+10 | 858.09 | 01-DEC-10:09 | 0.250369E+11 | 16024.20 | 01-DEC-11:09 |
Annual Sum or Average | 0.166904E+11 | 0.294790E+12 | ||||
Minimum of Months | 0.127710E+10 | 858.09 | 0.226140E+11 | 16024.20 | ||
Maximum of Months | 0.143409E+10 | 858.09 | 0.250371E+11 | 16024.20 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.206780E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134957E+11 |
February | 0.272721E+11 | 0.176408E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922550E+10 |
March | 0.305458E+11 | 0.187090E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862294E+10 |
April | 0.292871E+11 | 0.169213E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562719E+10 |
May | 0.303219E+11 | 0.167163E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27988459.67 | 0.451963E+10 |
June | 0.295292E+11 | 0.155876E+10 | 0.972773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263199E+09 | 0.222403E+10 |
July | 0.300798E+11 | 0.164438E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791642E+09 | 0.111868E+10 |
August | 0.305458E+11 | 0.170372E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594621E+09 | 0.161808E+10 |
September | 0.292871E+11 | 0.173145E+10 | 0.972770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217674E+09 | 0.310627E+10 |
October | 0.300980E+11 | 0.188614E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1319508.51 | 0.528296E+10 |
November | 0.290996E+11 | 0.194920E+10 | 0.972767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746586E+10 |
December | 0.300798E+11 | 0.207504E+10 | 0.100519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110086E+11 |
Annual Sum or Average | 0.356244E+12 | 0.216152E+11 | 0.118354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189644E+10 | 0.733154E+11 |
Minimum of Months | 0.272721E+11 | 0.155876E+10 | 0.907918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111868E+10 |
Maximum of Months | 0.305458E+11 | 0.207504E+10 | 0.100520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791642E+09 | 0.134957E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.140982E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210590E+09 |
February | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159585E+09 |
March | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142278E+09 |
April | 0.786997E+09 | 0.136995E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99377235.46 |
May | 0.814802E+09 | 0.142196E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 115944.50 | 0.103926E+09 |
June | 0.793501E+09 | 0.138598E+10 | 0.196898E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 953228.45 | 63767623.30 |
July | 0.808298E+09 | 0.140610E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 2828132.37 | 43626084.62 |
August | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 2548646.84 | 49435827.90 |
September | 0.786997E+09 | 0.137029E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 1076977.80 | 81305295.06 |
October | 0.808786E+09 | 0.140965E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105164E+09 |
November | 0.781956E+09 | 0.136509E+10 | 0.196897E+11 | 0.109583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145107E+09 |
December | 0.808298E+09 | 0.140627E+10 | 0.203460E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171839E+09 |
Annual Sum or Average | 0.957291E+10 | 0.166904E+11 | 0.239558E+12 | 0.133326E+12 | 0.00 | 0.00 | 0.00 | 7522929.95 | 0.137600E+10 |
Minimum of Months | 0.732850E+09 | 0.127710E+10 | 0.183771E+11 | 0.102277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43626084.62 |
Maximum of Months | 0.820818E+09 | 0.143409E+10 | 0.203461E+11 | 0.113235E+11 | 0.00 | 0.00 | 0.00 | 2828132.37 | 0.210590E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674856E+09 | 0.128921E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528619E+09 | 0.160390E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646548E+09 | 0.262828E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530922E+09 | 0.310235E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398785E+09 | 0.421023E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344537E+09 | 0.475763E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486492E+09 | 0.486160E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565281E+09 | 0.402819E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576760E+09 | 0.254062E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732169E+09 | 0.177609E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718290E+09 | 0.111741E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781471E+09 | 0.848080E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698473E+10 | 0.327636E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344537E+09 | 0.848080E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781471E+09 | 0.486160E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 1639.63 | 02-JAN-16:40 | 6614.32 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21361.79 | 10-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 1639.63 | 01-FEB-17:19 | 6614.32 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 18032.29 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 1639.63 | 01-MAR-18:10 | 6614.32 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 17460.57 | 04-MAR-19:55 |
April | 30255.31 | 01-APR-18:10 | 1639.63 | 01-APR-18:49 | 6614.32 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 9738.34 | 28-APR-19:53 |
May | 30255.31 | 06-MAY-18:10 | 1639.63 | 01-MAY-19:30 | 6614.32 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.00 | 20-MAY-17:10 | 8018.57 | 22-MAY-19:00 |
June | 30255.31 | 03-JUN-18:10 | 1639.63 | 01-JUN-20:10 | 6614.32 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2405.75 | 29-JUN-13:00 | 5672.79 | 16-JUN-11:10 |
July | 30255.31 | 01-JUL-18:10 | 1639.63 | 01-JUL-20:30 | 6614.32 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3944.03 | 17-JUL-17:03 | 3532.02 | 07-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 1639.63 | 01-AUG-19:00 | 6614.32 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3678.25 | 05-AUG-18:03 | 4808.28 | 17-AUG-12:00 |
September | 30255.31 | 02-SEP-18:10 | 1639.63 | 01-SEP-19:10 | 6614.32 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.53 | 02-SEP-17:03 | 6631.40 | 18-SEP-20:00 |
October | 30255.31 | 07-OCT-18:10 | 1639.63 | 02-OCT-17:00 | 6614.32 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.70 | 18-OCT-14:00 | 8149.07 | 31-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 1639.63 | 01-NOV-17:10 | 6614.32 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 12276.69 | 26-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 1639.63 | 01-DEC-16:40 | 6614.32 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 17537.79 | 29-DEC-18:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3532.02 | |||||
Maximum of Months | 30255.31 | 1639.63 | 6614.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3944.03 | 21361.79 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 858.09 | 02-JAN-10:09 | 12937.52 | 01-JAN-11:09 | 7449.36 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 382.56 | 06-JAN-04:00 |
February | 813.01 | 04-FEB-19:10 | 858.09 | 01-FEB-10:09 | 12937.52 | 01-FEB-11:09 | 7449.36 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 358.27 | 17-FEB-04:10 |
March | 813.01 | 04-MAR-19:10 | 858.09 | 01-MAR-10:09 | 12937.52 | 01-MAR-11:09 | 7449.36 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 409.26 | 17-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 858.09 | 01-APR-16:10 | 12937.52 | 01-APR-10:09 | 7449.36 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 296.05 | 27-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 858.09 | 01-MAY-09:09 | 12937.52 | 01-MAY-10:09 | 7449.36 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 7.83 | 20-MAY-15:53 | 602.47 | 22-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 858.09 | 01-JUN-09:09 | 12937.52 | 01-JUN-10:09 | 7449.36 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 18.58 | 29-JUN-15:00 | 282.00 | 14-JUN-02:00 |
July | 813.01 | 01-JUL-18:10 | 858.09 | 01-JUL-16:10 | 12937.52 | 01-JUL-10:09 | 7449.36 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 20.14 | 25-JUL-14:55 | 155.54 | 05-JUL-01:00 |
August | 813.01 | 05-AUG-18:10 | 858.09 | 01-AUG-09:09 | 12937.52 | 01-AUG-10:09 | 7449.36 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 18.51 | 11-AUG-14:00 | 227.52 | 23-AUG-03:00 |
September | 813.01 | 02-SEP-18:10 | 858.09 | 01-SEP-09:09 | 12937.52 | 01-SEP-10:09 | 7449.36 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 18.83 | 02-SEP-13:55 | 356.45 | 12-SEP-03:00 |
October | 813.01 | 07-OCT-18:10 | 858.09 | 02-OCT-09:09 | 12937.52 | 01-OCT-10:09 | 7449.36 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 243.76 | 31-OCT-00:10 |
November | 813.01 | 04-NOV-18:10 | 858.09 | 01-NOV-09:09 | 12937.52 | 01-NOV-10:09 | 7449.36 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 345.17 | 28-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 858.09 | 01-DEC-10:09 | 12937.52 | 01-DEC-11:09 | 7449.36 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 579.64 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 0.00 | 155.54 | ||||||
Maximum of Months | 813.01 | 858.09 | 12937.52 | 7449.36 | 0.00 | 0.00 | 0.00 | 20.14 | 602.47 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3391.80 | 11-JAN-08:31 | 5670.90 | 29-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.12 | 05-FEB-23:53 | 5209.32 | 23-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1896.46 | 01-MAR-07:00 | 6027.67 | 07-MAR-14:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1414.56 | 11-APR-06:53 | 7021.67 | 22-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1436.39 | 13-MAY-03:42 | 8060.97 | 09-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.70 | 17-JUN-05:53 | 7063.60 | 03-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1508.13 | 03-JUL-14:40 | 7932.79 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.79 | 03-AUG-04:40 | 6918.52 | 03-AUG-12:30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1735.66 | 02-SEP-03:55 | 6092.88 | 17-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1505.64 | 27-OCT-06:55 | 4506.41 | 06-OCT-12:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.14 | 21-NOV-08:15 | 3973.97 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.31 | 29-DEC-06:00 | 4167.72 | 29-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.70 | 3973.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3391.80 | 8060.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 66679.80 | 11-JAN-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.86 |
February | 52929.21 | 04-FEB-00:01 | 16808.50 | 3643.70 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.79 |
March | 55645.07 | 05-MAR-00:01 | 16808.50 | 3643.70 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.42 |
April | 31451.58 | 28-APR-23:01 | 16808.50 | 3643.70 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.23 |
May | 52457.58 | 20-MAY-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 |
June | 62360.18 | 21-JUN-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.43 |
July | 72934.82 | 26-JUL-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 |
August | 71132.98 | 08-AUG-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.70 |
September | 69281.72 | 04-SEP-03:01 | 0.00 | 800.29 | 11352.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 |
October | 28734.38 | 21-OCT-04:01 | 0.00 | 800.29 | 27369.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.86 |
November | 45170.58 | 27-NOV-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.17 |
December | 56239.67 | 29-DEC-00:01 | 16808.50 | 2732.77 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28734.38 | 0.00 | 800.29 | 6811.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 | |
Maximum of Months | 72934.82 | 16808.50 | 3643.70 | 27369.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 52519.23 | 27-JAN-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 56.70 |
February | 49271.66 | 01-FEB-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 20.64 |
March | 43497.57 | 05-MAR-05:01 | 0.00 | 270.10 | 51088.87 | 27742.44 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
April | 37084.00 | 08-APR-03:01 | 0.00 | 270.10 | 24388.73 | 11559.35 | 0.00 | 0.00 | 0.00 | 0.00 | 49.81 |
May | 49688.49 | 31-MAY-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 76.62 |
June | 54523.72 | 20-JUN-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 55.09 |
July | 53481.01 | 12-JUL-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 |
August | 52915.85 | 28-AUG-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 75.58 |
September | 55748.37 | 28-SEP-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 147.57 |
October | 51703.76 | 19-OCT-03:01 | 0.00 | 300.11 | 27098.59 | 12843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 102.58 |
November | 39852.53 | 27-NOV-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 72.56 |
December | 50165.06 | 29-DEC-05:01 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37084.00 | 0.00 | 270.10 | 24388.73 | 11559.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55748.37 | 451.67 | 300.11 | 56997.89 | 30824.93 | 0.00 | 0.00 | 0.00 | 0.00 | 147.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.33 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.50 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.91 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.49 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.64 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.00 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.15 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.11 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.73 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.31 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.93 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.93 | 571.50 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.617933E+11 | 37041.74 | 09-JAN-11:20 | 0.222206E+12 | 201339.79 | 10-JAN-21:49 |
February | 0.547101E+11 | 36666.09 | 04-FEB-11:09 | 0.151566E+12 | 175843.08 | 03-FEB-04:19 |
March | 0.598240E+11 | 36744.07 | 04-MAR-11:09 | 0.142597E+12 | 175843.08 | 04-MAR-04:10 |
April | 0.571236E+11 | 36151.36 | 07-APR-11:00 | 0.959807E+11 | 98496.82 | 29-APR-05:19 |
May | 0.607205E+11 | 41944.95 | 20-MAY-16:10 | 0.856795E+11 | 90103.09 | 08-MAY-06:10 |
June | 0.641527E+11 | 48015.34 | 20-JUN-17:30 | 0.650420E+11 | 59727.62 | 17-JUN-05:10 |
July | 0.731958E+11 | 56437.81 | 17-JUL-17:00 | 0.634847E+11 | 41169.02 | 03-JUL-18:49 |
August | 0.705456E+11 | 51579.50 | 05-AUG-17:00 | 0.635168E+11 | 40444.53 | 17-AUG-09:00 |
September | 0.633842E+11 | 50636.36 | 02-SEP-17:19 | 0.667288E+11 | 63231.92 | 19-SEP-06:49 |
October | 0.599813E+11 | 39846.96 | 18-OCT-10:00 | 0.831021E+11 | 94840.88 | 10-OCT-06:00 |
November | 0.581097E+11 | 36143.96 | 26-NOV-11:20 | 0.117406E+12 | 175843.08 | 27-NOV-04:10 |
December | 0.611258E+11 | 36796.30 | 31-DEC-11:20 | 0.178592E+12 | 183521.30 | 29-DEC-07:49 |
Annual Sum or Average | 0.744667E+12 | 0.133590E+13 | ||||
Minimum of Months | 0.547101E+11 | 36143.96 | 0.634847E+11 | 40444.53 | ||
Maximum of Months | 0.731958E+11 | 56437.81 | 0.222206E+12 | 201339.79 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.347762E+10 | 0.201887E+10 | 0.350888E+11 | 0.00 | 0.119337E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639853E+10 | 0.00 |
February | 0.304118E+10 | 0.162543E+10 | 0.316932E+11 | 0.00 | 0.992522E+10 | 34213790.43 | 0.00 | 9179132.05 | 0.00 | 0.00 | 0.00 | 0.578987E+10 | 0.00 |
March | 0.330499E+10 | 0.152222E+10 | 0.350891E+11 | 0.00 | 0.105313E+11 | 37879553.69 | 0.00 | 198201.86 | 0.00 | 0.00 | 0.00 | 0.646611E+10 | 0.00 |
April | 0.306208E+10 | 0.119290E+10 | 0.339570E+11 | 0.00 | 0.947472E+10 | 36657632.61 | 0.00 | 0.323127E+09 | 0.00 | 0.00 | 0.00 | 0.620616E+10 | 0.00 |
May | 0.309359E+10 | 0.100087E+10 | 0.350889E+11 | 0.00 | 0.958375E+10 | 37879553.69 | 0.00 | 0.243833E+10 | 0.00 | 0.00 | 0.00 | 0.642454E+10 | 0.00 |
June | 0.294474E+10 | 0.868536E+09 | 0.339571E+11 | 0.00 | 0.906259E+10 | 36657632.61 | 0.00 | 0.795328E+10 | 0.00 | 0.00 | 0.00 | 0.623963E+10 | 0.00 |
July | 0.305048E+10 | 0.932727E+09 | 0.350888E+11 | 0.00 | 0.955711E+10 | 37879553.69 | 0.00 | 0.149198E+11 | 0.00 | 0.00 | 0.00 | 0.637304E+10 | 0.00 |
August | 0.313781E+10 | 0.112074E+10 | 0.350891E+11 | 0.00 | 0.947992E+10 | 37879553.69 | 0.00 | 0.120022E+11 | 0.00 | 0.00 | 0.00 | 0.645151E+10 | 0.00 |
September | 0.310174E+10 | 0.135060E+10 | 0.339570E+11 | 0.00 | 0.916627E+10 | 36657632.61 | 0.00 | 0.652178E+10 | 0.00 | 0.00 | 0.00 | 0.619954E+10 | 0.00 |
October | 0.329579E+10 | 0.168354E+10 | 0.350888E+11 | 0.00 | 0.959392E+10 | 37879553.69 | 0.00 | 0.864921E+09 | 0.00 | 0.00 | 0.00 | 0.638915E+10 | 0.00 |
November | 0.331429E+10 | 0.188259E+10 | 0.339569E+11 | 0.00 | 0.989370E+10 | 36657632.61 | 0.00 | 9819549.64 | 0.00 | 0.00 | 0.00 | 0.618900E+10 | 0.00 |
December | 0.348131E+10 | 0.209047E+10 | 0.350888E+11 | 0.00 | 0.111841E+11 | 37879553.69 | 0.00 | 404553.26 | 0.00 | 0.00 | 0.00 | 0.638986E+10 | 0.00 |
Annual Sum or Average | 0.383056E+11 | 0.172895E+11 | 0.413144E+12 | 0.00 | 0.119386E+12 | 0.446001E+09 | 0.00 | 0.450431E+11 | 0.00 | 0.00 | 0.00 | 0.755169E+11 | 0.00 |
Minimum of Months | 0.294474E+10 | 0.868536E+09 | 0.316932E+11 | 0.00 | 0.906259E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578987E+10 | 0.00 |
Maximum of Months | 0.348131E+10 | 0.209047E+10 | 0.350891E+11 | 0.00 | 0.119337E+11 | 37879553.69 | 0.00 | 0.149198E+11 | 0.00 | 0.00 | 0.00 | 0.646611E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.377451E+11 | 0.00 | 0.153772E+12 | 0.00 | 0.306885E+11 | 0.00 | 0.00 |
February | 0.340924E+11 | 0.00 | 0.892776E+11 | 0.00 | 0.281960E+11 | 0.00 | 0.00 |
March | 0.377451E+11 | 0.00 | 0.736746E+11 | 0.00 | 0.311776E+11 | 0.00 | 0.00 |
April | 0.365275E+11 | 0.00 | 0.305181E+11 | 0.00 | 0.289350E+11 | 0.00 | 0.00 |
May | 0.377451E+11 | 0.00 | 0.194841E+11 | 0.00 | 0.284502E+11 | 0.00 | 0.00 |
June | 0.365275E+11 | 0.00 | 0.245445E+10 | 0.00 | 0.260600E+11 | 0.00 | 0.00 |
July | 0.377451E+11 | 0.00 | 0.293807E+09 | 0.00 | 0.254458E+11 | 0.00 | 0.00 |
August | 0.377451E+11 | 0.00 | 0.564507E+09 | 0.00 | 0.252072E+11 | 0.00 | 0.00 |
September | 0.365275E+11 | 0.00 | 0.564838E+10 | 0.00 | 0.245529E+11 | 0.00 | 0.00 |
October | 0.377451E+11 | 0.00 | 0.189739E+11 | 0.00 | 0.263831E+11 | 0.00 | 0.00 |
November | 0.365275E+11 | 0.00 | 0.538643E+11 | 0.00 | 0.270144E+11 | 0.00 | 0.00 |
December | 0.377451E+11 | 0.00 | 0.111395E+12 | 0.00 | 0.294518E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.444418E+12 | 0.00 | 0.559921E+12 | 0.00 | 0.331562E+12 | 0.00 | 0.00 |
Minimum of Months | 0.340924E+11 | 0.00 | 0.293807E+09 | 0.00 | 0.245529E+11 | 0.00 | 0.00 |
Maximum of Months | 0.377451E+11 | 0.00 | 0.153772E+12 | 0.00 | 0.311776E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2497.72 | 02-JAN-16:40 | 1510.48 | 01-JAN-06:10 | 22638.52 | 01-JAN-11:09 | 0.00 | 6888.42 | 10-JAN-23:10 | 17.86 | 03-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2497.72 | 01-FEB-17:19 | 1510.48 | 01-FEB-06:10 | 22638.52 | 01-FEB-11:09 | 0.00 | 6522.33 | 04-FEB-04:00 | 17.86 | 28-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 2497.72 | 01-MAR-18:10 | 1510.48 | 01-MAR-06:10 | 22638.52 | 01-MAR-11:09 | 0.00 | 6522.33 | 04-MAR-04:10 | 17.86 | 02-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 2497.72 | 01-APR-18:49 | 1510.48 | 01-APR-05:10 | 22638.52 | 01-APR-10:09 | 0.00 | 5427.90 | 29-APR-05:10 | 17.86 | 10-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 2497.72 | 01-MAY-19:30 | 1510.48 | 01-MAY-05:10 | 22638.52 | 01-MAY-10:09 | 0.00 | 5117.32 | 08-MAY-05:10 | 17.86 | 03-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 2497.72 | 01-JUN-20:10 | 1510.48 | 01-JUN-20:10 | 22638.52 | 01-JUN-10:09 | 0.00 | 5007.37 | 20-JUN-17:19 | 17.86 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 2497.72 | 01-JUL-20:30 | 1510.48 | 01-JUL-20:30 | 22638.52 | 01-JUL-10:09 | 0.00 | 6462.46 | 17-JUL-17:40 | 17.86 | 03-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 2497.72 | 01-AUG-19:00 | 1510.48 | 01-AUG-19:00 | 22638.52 | 01-AUG-10:09 | 0.00 | 5763.52 | 05-AUG-18:10 | 17.86 | 22-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 2497.72 | 01-SEP-19:10 | 1510.48 | 01-SEP-05:10 | 22638.52 | 01-SEP-10:09 | 0.00 | 5353.69 | 02-SEP-17:10 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 2497.72 | 02-OCT-17:00 | 1510.48 | 01-OCT-05:10 | 22638.52 | 01-OCT-10:09 | 0.00 | 5243.28 | 10-OCT-05:10 | 17.86 | 03-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 2497.72 | 01-NOV-17:10 | 1510.48 | 01-NOV-05:10 | 22638.52 | 01-NOV-10:09 | 0.00 | 6522.33 | 27-NOV-04:10 | 17.86 | 15-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 2497.72 | 01-DEC-16:40 | 1510.48 | 01-DEC-06:10 | 22638.52 | 01-DEC-11:09 | 0.00 | 6643.76 | 31-DEC-07:10 | 17.86 | 02-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 5007.37 | 17.86 | 0.00 | ||||||
Maximum of Months | 2497.72 | 1510.48 | 22638.52 | 0.00 | 6888.42 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.87 | 11-JAN-07:49 | 0.00 |
February | 1612.85 | 27-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.82 | 24-FEB-07:49 | 0.00 |
March | 172.52 | 21-MAR-03:39 | 0.00 | 0.00 | 0.00 | 4741.94 | 08-MAR-07:49 | 0.00 |
April | 6261.57 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 4742.24 | 18-APR-18:30 | 0.00 |
May | 11796.66 | 20-MAY-17:10 | 0.00 | 0.00 | 0.00 | 4741.99 | 08-MAY-18:40 | 0.00 |
June | 17100.37 | 20-JUN-17:30 | 0.00 | 0.00 | 0.00 | 4741.78 | 15-JUN-06:10 | 0.00 |
July | 23877.04 | 17-JUL-17:30 | 0.00 | 0.00 | 0.00 | 4739.39 | 05-JUL-06:10 | 0.00 |
August | 20809.96 | 05-AUG-18:10 | 0.00 | 0.00 | 0.00 | 4739.86 | 03-AUG-06:40 | 0.00 |
September | 19561.99 | 02-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4741.20 | 20-SEP-06:49 | 0.00 |
October | 9128.00 | 18-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4741.92 | 31-OCT-18:30 | 0.00 |
November | 1538.71 | 24-NOV-04:49 | 0.00 | 0.00 | 0.00 | 4741.69 | 14-NOV-07:49 | 0.00 |
December | 189.85 | 05-DEC-04:40 | 0.00 | 0.00 | 0.00 | 4741.64 | 21-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4739.39 | 0.00 | ||
Maximum of Months | 23877.04 | 0.00 | 0.00 | 0.00 | 4742.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 37041.74 | 09-JAN-11:20 | 1677.91 | 22638.52 | 0.00 | 0.00 | 6386.46 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 36666.09 | 04-FEB-11:09 | 1491.48 | 22638.52 | 0.00 | 0.00 | 5851.07 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 36744.07 | 04-MAR-11:09 | 1491.48 | 22638.52 | 0.00 | 0.00 | 5847.82 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 36151.36 | 07-APR-11:00 | 1677.91 | 21117.99 | 0.00 | 0.00 | 4096.71 | 17.86 | 0.00 | 5002.86 | 0.00 |
May | 41944.95 | 20-MAY-16:10 | 1677.91 | 20357.72 | 0.00 | 0.00 | 4157.21 | 17.86 | 0.00 | 11586.17 | 0.00 |
June | 48015.34 | 20-JUN-17:30 | 1677.91 | 18837.19 | 0.00 | 0.00 | 5006.21 | 17.86 | 0.00 | 17100.37 | 0.00 |
July | 56437.81 | 17-JUL-17:00 | 1677.91 | 18837.19 | 0.00 | 0.00 | 6457.48 | 17.86 | 0.00 | 23853.82 | 0.00 |
August | 51579.50 | 05-AUG-17:00 | 1677.91 | 18837.19 | 0.00 | 0.00 | 5429.14 | 17.86 | 0.00 | 20020.59 | 0.00 |
September | 50636.36 | 02-SEP-17:19 | 1677.91 | 18837.19 | 0.00 | 0.00 | 5278.10 | 17.86 | 0.00 | 19230.52 | 0.00 |
October | 39846.96 | 18-OCT-10:00 | 1677.91 | 22638.52 | 0.00 | 0.00 | 4096.71 | 17.86 | 0.00 | 6112.74 | 0.00 |
November | 36143.96 | 26-NOV-11:20 | 1305.04 | 22638.52 | 0.00 | 0.00 | 5550.24 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 36796.30 | 31-DEC-11:20 | 1305.04 | 22638.52 | 0.00 | 0.00 | 6146.59 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 36143.96 | 1305.04 | 18837.19 | 0.00 | 0.00 | 4096.71 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56437.81 | 1677.91 | 22638.52 | 0.00 | 0.00 | 6457.48 | 17.86 | 0.00 | 23853.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 24831.19 | 01-JAN-11:09 | 0.00 | 170758.61 | 07-JAN-04:10 | 0.00 | 29546.98 | 31-JAN-07:30 | 0.00 |
February | 24831.19 | 01-FEB-11:09 | 0.00 | 170758.61 | 03-FEB-04:19 | 0.00 | 29718.07 | 15-FEB-07:19 | 0.00 |
March | 24831.19 | 01-MAR-11:09 | 0.00 | 170758.61 | 04-MAR-04:10 | 0.00 | 29651.50 | 01-MAR-19:30 | 0.00 |
April | 24831.19 | 01-APR-10:09 | 0.00 | 76097.56 | 29-APR-05:10 | 0.00 | 28688.74 | 04-APR-06:40 | 0.00 |
May | 24831.19 | 01-MAY-10:09 | 0.00 | 57098.30 | 08-MAY-05:10 | 0.00 | 27039.37 | 03-MAY-06:30 | 0.00 |
June | 24831.19 | 01-JUN-10:09 | 0.00 | 37982.93 | 17-JUN-04:00 | 0.00 | 24797.05 | 01-JUN-06:40 | 0.00 |
July | 24831.19 | 01-JUL-10:09 | 0.00 | 13124.67 | 08-JUL-04:00 | 0.00 | 22331.57 | 03-JUL-18:49 | 0.00 |
August | 24831.19 | 01-AUG-10:09 | 0.00 | 14676.07 | 18-AUG-04:00 | 0.00 | 20868.79 | 01-AUG-18:30 | 0.00 |
September | 24831.19 | 01-SEP-10:09 | 0.00 | 35725.24 | 17-SEP-05:00 | 0.00 | 21898.35 | 28-SEP-06:49 | 0.00 |
October | 24831.19 | 01-OCT-10:09 | 0.00 | 64265.14 | 10-OCT-05:10 | 0.00 | 24269.90 | 31-OCT-06:40 | 0.00 |
November | 24831.19 | 01-NOV-10:09 | 0.00 | 170758.61 | 27-NOV-04:10 | 0.00 | 26576.85 | 30-NOV-19:40 | 0.00 |
December | 24831.19 | 01-DEC-11:09 | 0.00 | 170758.61 | 30-DEC-04:10 | 0.00 | 28379.83 | 29-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 24831.19 | 0.00 | 13124.67 | 0.00 | 20868.79 | 0.00 | |||
Maximum of Months | 24831.19 | 0.00 | 170758.61 | 0.00 | 29718.07 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
February | 5.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
March | 3.50 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
April | 0.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.58 | 0.00 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.70 | 0.00 | 24.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.71 | 0.00 | 24.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.67 | 0.00 | 24.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
December | 2.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 18.00 | 19.32 | 0.00 | 19.32 | 5.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 20.41 | 0.00 | 20.41 | 1.83 | 24.71 | 0.00 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.59 | 0.00 | 26.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.88 | 0.00 | 26.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.57 | 0.00 | 26.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.19 | 0.00 | 27.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.74 | 0.00 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.89 | 0.00 | 28.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 29.66 | 0.00 | 29.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 29.55 | 0.00 | 29.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 29.34 | 0.00 | 29.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.60 | 0.00 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.20 | 0.00 | 27.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 56.17 | 29.01 | 0.00 | 29.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 29.66 | 0.00 | 29.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.75 | 375.17 | 20.69 | 375.17 | 20.66 |
February | 551.00 | 20.87 | 216.00 | 20.73 | 216.00 | 20.66 |
March | 612.00 | 20.80 | 195.50 | 20.67 | 195.50 | 20.59 |
April | 557.83 | 21.27 | 74.00 | 21.08 | 74.00 | 20.93 |
May | 446.00 | 21.36 | 86.17 | 21.46 | 38.50 | 21.32 |
June | 206.00 | 21.75 | 272.50 | 22.99 | 9.50 | 22.97 |
July | 100.50 | 22.20 | 451.17 | 23.68 | 11.33 | 23.69 |
August | 133.67 | 21.85 | 373.67 | 23.44 | 0.83 | 23.43 |
September | 288.00 | 21.66 | 233.83 | 22.62 | 27.67 | 22.61 |
October | 502.83 | 21.32 | 31.00 | 21.19 | 28.50 | 21.06 |
November | 586.17 | 21.05 | 114.50 | 20.89 | 114.50 | 20.77 |
December | 609.00 | 20.77 | 263.67 | 20.67 | 263.67 | 20.62 |
Annual Sum or Average | 5203.00 | 21.11 | 2687.17 | 21.48 | 1355.17 | 21.32 |
Minimum of Months | 100.50 | 20.75 | 31.00 | 20.67 | 0.83 | 20.59 |
Maximum of Months | 612.00 | 22.20 | 451.17 | 23.68 | 375.17 | 23.69 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.10 | 420.00 | 19.06 | 420.00 | 19.04 |
February | 520.67 | 19.27 | 297.67 | 19.28 | 283.33 | 19.21 |
March | 605.00 | 19.40 | 265.50 | 19.29 | 264.17 | 19.22 |
April | 444.83 | 19.90 | 218.50 | 20.72 | 109.83 | 20.58 |
May | 445.33 | 21.69 | 319.33 | 22.79 | 182.50 | 23.03 |
June | 427.33 | 24.86 | 485.33 | 25.22 | 340.67 | 25.42 |
July | 488.33 | 25.84 | 584.00 | 25.76 | 474.17 | 25.83 |
August | 448.50 | 25.68 | 560.50 | 25.64 | 420.33 | 25.75 |
September | 426.33 | 23.93 | 422.67 | 24.64 | 284.67 | 24.95 |
October | 397.17 | 20.79 | 253.17 | 22.15 | 92.67 | 22.33 |
November | 494.67 | 19.59 | 226.50 | 19.95 | 158.33 | 19.80 |
December | 606.33 | 19.23 | 316.17 | 19.15 | 316.17 | 19.11 |
Annual Sum or Average | 5914.50 | 21.39 | 4369.33 | 22.10 | 3346.83 | 22.22 |
Minimum of Months | 397.17 | 19.10 | 218.50 | 19.06 | 92.67 | 19.04 |
Maximum of Months | 610.00 | 25.84 | 584.00 | 25.76 | 474.17 | 25.83 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.75128 | 16.73308 | -0.6345 | 14.39423 |
February | 551.00000 | 20.86756 | 20.17624 | -0.5395 | 12.30935 |
March | 612.00000 | 20.80369 | 21.78129 | -0.5278 | 11.82345 |
April | 590.00000 | 21.41546 | 27.15159 | -0.3247 | 9.23757 |
May | 611.00000 | 22.06895 | 31.00659 | -1.1803 | 37.54889 |
June | 592.00000 | 23.19051 | 37.97197 | -0.6827 | 18.12306 |
July | 609.00000 | 23.68698 | 40.19750 | -0.4550 | 10.92193 |
August | 612.00000 | 23.51967 | 36.45327 | -0.5432 | 13.45724 |
September | 590.00000 | 22.82683 | 37.93109 | -0.7981 | 22.94415 |
October | 610.00000 | 21.77761 | 29.75632 | -0.1653 | 7.72159 |
November | 591.00000 | 21.07594 | 23.41805 | -0.4216 | 10.11498 |
December | 609.00000 | 20.77233 | 19.16330 | -0.5784 | 12.92324 |
Annual Sum or Average | 7187.00000 | 21.90260 | 28.51387 | -0.5714 | 15.15278 |
Minimum of Months | 551.00000 | 20.75128 | 16.73308 | -1.1803 | 7.72159 |
Maximum of Months | 612.00000 | 23.68698 | 40.19750 | -0.1653 | 37.54889 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.09950 | 23.28790 | -0.6850 | 15.45868 |
February | 551.00000 | 19.53932 | 27.16620 | -0.5453 | 13.42168 |
March | 612.00000 | 19.44868 | 29.49394 | -0.5442 | 12.52718 |
April | 590.00000 | 21.02952 | 33.88753 | -0.1455 | 11.64269 |
May | 611.00000 | 22.41173 | 36.32718 | -0.7258 | 31.53336 |
June | 592.00000 | 24.69087 | 39.93041 | 0.09892 | 13.97144 |
July | 609.00000 | 25.51773 | 41.02922 | 0.41694 | 11.81868 |
August | 612.00000 | 25.27765 | 37.83046 | 0.31004 | 11.61169 |
September | 590.00000 | 23.95877 | 39.80044 | -0.1257 | 19.11201 |
October | 610.00000 | 21.97310 | 34.54186 | 0.13271 | 12.51542 |
November | 591.00000 | 20.32323 | 29.17777 | -0.3091 | 11.44171 |
December | 609.00000 | 19.24393 | 25.66797 | -0.6095 | 13.72570 |
Annual Sum or Average | 7187.00000 | 21.88917 | 33.20169 | -0.2262 | 14.92060 |
Minimum of Months | 551.00000 | 19.09950 | 23.28790 | -0.7258 | 11.44171 |
Maximum of Months | 612.00000 | 25.51773 | 41.02922 | 0.41694 | 31.53336 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 12709610.36 | 4346560.35 | 2.50 | 12709610.36 | 0.00 | 0.00 | 0.12 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 | 3634.99 | 27-FEB-14:00 | 3634.99 | 27-FEB-14:00 | 0.00 | 27-FEB-13:30 | 1228.40 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.555377E+09 | 0.182541E+09 | 30.92 | 0.554026E+09 | 1351833.66 | 0.00 | 0.43 | 07-APR-12:53 | 0.00 | 01-APR-00:01 | 13620.88 | 07-APR-12:53 | 13620.88 | 07-APR-12:53 | 280.06 | 24-APR-13:00 | 4270.97 | 07-APR-12:53 | 0.00 | 01-APR-00:01 |
May | 0.464952E+10 | 0.144592E+10 | 124.77 | 0.442081E+10 | 0.228717E+09 | 0.00 | 1.00 | 20-MAY-03:01 | 0.00 | 01-MAY-00:01 | 74229.72 | 20-MAY-03:01 | 56668.37 | 20-MAY-03:01 | 17561.35 | 20-MAY-03:01 | 19888.26 | 20-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.166045E+11 | 0.491480E+10 | 291.27 | 0.150716E+11 | 0.153290E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 74229.72 | 01-JUN-03:01 | 55359.59 | 21-JUN-03:01 | 32212.83 | 13-JUN-03:01 | 19888.26 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.319431E+11 | 0.940193E+10 | 429.14 | 0.298373E+11 | 0.210582E+10 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 74249.58 | 19-JUL-03:01 | 73255.68 | 26-JUL-03:58 | 28458.55 | 01-JUL-03:01 | 19889.77 | 19-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.253069E+11 | 0.749625E+10 | 377.52 | 0.244106E+11 | 0.896306E+09 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 74229.72 | 07-AUG-03:41 | 74229.72 | 11-AUG-03:42 | 25137.22 | 16-AUG-03:01 | 19888.26 | 04-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.133541E+11 | 0.397240E+10 | 236.72 | 0.120208E+11 | 0.133326E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 74229.72 | 04-SEP-03:27 | 69485.48 | 04-SEP-03:53 | 32343.10 | 08-SEP-03:01 | 19888.26 | 02-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.153467E+10 | 0.492566E+09 | 58.66 | 0.152937E+10 | 5304921.65 | 0.00 | 0.64 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 | 21388.69 | 18-OCT-12:55 | 21388.69 | 18-OCT-12:55 | 348.56 | 12-OCT-12:00 | 6350.32 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.939608E+11 | 0.279107E+11 | 1551.50 | 0.878571E+11 | 0.610367E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.319431E+11 | 0.940193E+10 | 429.14 | 0.298373E+11 | 0.210582E+10 | 0.00 | 1.00 | 0.00 | 74249.58 | 74229.72 | 32343.10 | 19889.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 15899665.08 | 4832571.69 | 3.97 | 15376761.18 | 522903.90 | 0.00 | 0.21 | 28-FEB-04:08 | 0.00 | 01-FEB-00:01 | 2954.91 | 28-FEB-04:08 | 2117.14 | 28-FEB-04:08 | 837.77 | 28-FEB-04:08 | 874.86 | 28-FEB-04:08 | 0.00 | 01-FEB-00:01 |
March | 648827.79 | 198201.86 | 0.17 | 528669.58 | 120158.21 | 0.00 | 0.08 | 21-MAR-03:40 | 0.00 | 01-MAR-00:01 | 1130.41 | 21-MAR-03:40 | 893.96 | 21-MAR-03:40 | 236.44 | 21-MAR-03:40 | 345.04 | 21-MAR-03:40 | 0.00 | 01-MAR-00:01 |
April | 0.486919E+09 | 0.140586E+09 | 49.55 | 0.473116E+09 | 13802731.82 | 0.00 | 1.00 | 07-APR-03:01 | 0.00 | 01-APR-00:01 | 34390.20 | 07-APR-03:01 | 30720.19 | 07-APR-03:01 | 7073.81 | 08-APR-03:01 | 8245.02 | 07-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.368966E+10 | 0.992411E+09 | 157.53 | 0.337545E+10 | 0.314210E+09 | 0.00 | 1.00 | 14-MAY-03:01 | 0.00 | 01-MAY-00:01 | 34390.20 | 21-MAY-03:01 | 30051.81 | 29-MAY-03:42 | 13756.12 | 21-MAY-03:01 | 8245.02 | 20-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.118435E+11 | 0.303848E+10 | 336.92 | 0.104144E+11 | 0.142913E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 34390.20 | 01-JUN-03:01 | 26016.90 | 06-JUN-03:01 | 18169.81 | 13-JUN-03:01 | 8245.02 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.216338E+11 | 0.551788E+10 | 477.83 | 0.198308E+11 | 0.180306E+10 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 34390.20 | 19-JUL-03:47 | 31231.50 | 26-JUL-03:45 | 18472.87 | 01-JUL-03:01 | 8646.67 | 17-JUL-15:55 | 0.00 | 01-JUL-00:01 |
August | 0.174439E+11 | 0.450598E+10 | 437.80 | 0.163821E+11 | 0.106184E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 34390.20 | 01-AUG-03:01 | 33827.71 | 11-AUG-03:01 | 14791.46 | 14-AUG-03:01 | 8245.02 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.988140E+10 | 0.254938E+10 | 275.55 | 0.852871E+10 | 0.135269E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 34390.20 | 03-SEP-03:11 | 29899.27 | 04-SEP-03:43 | 19436.16 | 08-SEP-03:21 | 8245.02 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.132734E+10 | 0.372355E+09 | 83.92 | 0.127784E+10 | 49507509.42 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 34390.20 | 03-OCT-03:41 | 30605.09 | 18-OCT-03:01 | 14959.07 | 01-OCT-03:01 | 8245.02 | 03-OCT-03:41 | 0.00 | 01-OCT-00:01 |
November | 34598573.48 | 9819549.64 | 9.78 | 29722063.16 | 4876510.32 | 0.00 | 1.00 | 05-NOV-03:01 | 0.00 | 01-NOV-00:01 | 34390.20 | 05-NOV-03:01 | 31951.77 | 24-NOV-04:42 | 6259.94 | 05-NOV-03:01 | 8245.02 | 05-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 1323328.46 | 404553.26 | 0.42 | 1084076.68 | 239251.77 | 0.00 | 0.09 | 05-DEC-04:40 | 0.00 | 01-DEC-00:01 | 1246.40 | 05-DEC-04:40 | 1101.52 | 05-DEC-04:40 | 327.38 | 06-DEC-04:20 | 379.70 | 05-DEC-04:40 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.663590E+11 | 0.171323E+11 | 1833.44 | 0.603291E+11 | 0.603000E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.216338E+11 | 0.551788E+10 | 477.83 | 0.198308E+11 | 0.180306E+10 | 0.00 | 1.00 | 0.00 | 34390.20 | 33827.71 | 19436.16 | 8646.67 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.13 | 72.07 | 84.07 | 84.53 | 548.58 | 0.00 | 0.00 | 0.00 |
February | 244.59 | 122.26 | 122.33 | 192.12 | 395.53 | 0.00 | 0.00 | 0.00 |
March | 327.75 | 136.37 | 191.37 | 285.27 | 317.85 | 0.00 | 0.00 | 0.00 |
April | 417.12 | 207.22 | 209.90 | 432.69 | 219.72 | 0.00 | 0.00 | 0.00 |
May | 459.83 | 204.91 | 254.92 | 509.77 | 174.22 | 0.00 | 0.00 | 0.00 |
June | 594.32 | 305.77 | 288.54 | 746.45 | 114.85 | 0.00 | 0.00 | 0.00 |
July | 623.85 | 352.67 | 271.17 | 840.49 | 94.88 | 0.00 | 0.00 | 0.00 |
August | 543.79 | 303.36 | 240.43 | 713.42 | 107.09 | 0.00 | 0.00 | 0.00 |
September | 384.30 | 198.43 | 185.87 | 459.09 | 157.75 | 0.00 | 0.00 | 0.00 |
October | 274.36 | 138.69 | 135.67 | 274.08 | 233.82 | 0.00 | 0.00 | 0.00 |
November | 174.77 | 81.66 | 93.12 | 127.58 | 333.73 | 0.00 | 0.00 | 0.00 |
December | 128.91 | 55.55 | 73.36 | 66.21 | 469.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 361.42 | 181.88 | 179.53 | 395.46 | 263.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 128.91 | 55.55 | 73.36 | 66.21 | 94.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.85 | 352.67 | 288.54 | 840.49 | 548.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 658.86 | 470.40 | 188.46 | 644.32 | 694.05 | 0.00 | 0.00 | 0.00 |
February | 827.75 | 592.10 | 235.65 | 891.92 | 509.88 | 0.00 | 0.00 | 0.00 |
March | 740.38 | 411.62 | 328.77 | 802.28 | 443.54 | 0.00 | 0.00 | 0.00 |
April | 609.32 | 294.87 | 314.45 | 690.82 | 321.82 | 0.00 | 0.00 | 0.00 |
May | 540.19 | 182.54 | 357.64 | 625.23 | 255.13 | 0.00 | 0.00 | 0.00 |
June | 529.46 | 152.59 | 376.87 | 688.28 | 174.87 | 0.00 | 0.00 | 0.00 |
July | 572.35 | 210.62 | 361.73 | 824.73 | 140.94 | 0.00 | 0.00 | 0.00 |
August | 672.22 | 334.19 | 338.02 | 937.59 | 158.98 | 0.00 | 0.00 | 0.00 |
September | 755.03 | 462.18 | 292.86 | 978.33 | 225.80 | 0.00 | 0.00 | 0.00 |
October | 797.00 | 552.99 | 244.00 | 951.76 | 320.44 | 0.00 | 0.00 | 0.00 |
November | 720.02 | 521.25 | 198.77 | 788.16 | 426.50 | 0.00 | 0.00 | 0.00 |
December | 626.24 | 452.27 | 173.96 | 628.67 | 591.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 669.63 | 385.09 | 284.54 | 786.83 | 354.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 529.46 | 152.59 | 173.96 | 625.23 | 140.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 827.75 | 592.10 | 376.87 | 978.33 | 694.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.03 | 57.11 | 83.92 | 74.97 | 561.50 | 0.00 | 0.00 | 0.00 |
February | 241.74 | 119.79 | 121.95 | 194.76 | 404.46 | 0.00 | 0.00 | 0.00 |
March | 308.00 | 113.53 | 194.47 | 265.36 | 325.93 | 0.00 | 0.00 | 0.00 |
April | 400.98 | 177.37 | 223.62 | 418.63 | 227.97 | 0.00 | 0.00 | 0.00 |
May | 495.92 | 226.62 | 269.30 | 564.62 | 179.33 | 0.00 | 0.00 | 0.00 |
June | 538.01 | 246.77 | 291.24 | 675.37 | 122.22 | 0.00 | 0.00 | 0.00 |
July | 551.34 | 278.38 | 272.95 | 746.69 | 101.50 | 0.00 | 0.00 | 0.00 |
August | 468.72 | 229.81 | 238.91 | 616.82 | 113.14 | 0.00 | 0.00 | 0.00 |
September | 377.61 | 190.92 | 186.69 | 457.44 | 163.82 | 0.00 | 0.00 | 0.00 |
October | 270.01 | 134.29 | 135.72 | 275.32 | 241.84 | 0.00 | 0.00 | 0.00 |
November | 191.11 | 94.97 | 96.14 | 158.42 | 341.68 | 0.00 | 0.00 | 0.00 |
December | 127.72 | 53.72 | 74.00 | 71.47 | 478.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 343.14 | 160.42 | 182.72 | 377.59 | 271.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.72 | 53.72 | 74.00 | 71.47 | 101.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.34 | 278.38 | 291.24 | 746.69 | 561.50 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418185E+09 | 0.193024E+09 | 0.225161E+09 | 0.226417E+09 | 0.146933E+10 |
February | 0.591708E+09 | 0.295770E+09 | 0.295938E+09 | 0.464789E+09 | 0.956857E+09 |
March | 0.877835E+09 | 0.365259E+09 | 0.512576E+09 | 0.764069E+09 | 0.851324E+09 |
April | 0.108118E+10 | 0.537123E+09 | 0.544059E+09 | 0.112154E+10 | 0.569518E+09 |
May | 0.123162E+10 | 0.548837E+09 | 0.682783E+09 | 0.136538E+10 | 0.466631E+09 |
June | 0.154047E+10 | 0.792563E+09 | 0.747906E+09 | 0.193481E+10 | 0.297691E+09 |
July | 0.167091E+10 | 0.944594E+09 | 0.726314E+09 | 0.225117E+10 | 0.254116E+09 |
August | 0.145649E+10 | 0.812513E+09 | 0.643978E+09 | 0.191083E+10 | 0.286839E+09 |
September | 0.996108E+09 | 0.514339E+09 | 0.481769E+09 | 0.118996E+10 | 0.408890E+09 |
October | 0.734840E+09 | 0.371461E+09 | 0.363379E+09 | 0.734097E+09 | 0.626274E+09 |
November | 0.453013E+09 | 0.211655E+09 | 0.241358E+09 | 0.330680E+09 | 0.865030E+09 |
December | 0.345275E+09 | 0.148785E+09 | 0.196490E+09 | 0.177345E+09 | 0.125705E+10 |
Annual Sum or Average | 0.113976E+11 | 0.573592E+10 | 0.566171E+10 | 0.124711E+11 | 0.830955E+10 |
Minimum of Months | 0.345275E+09 | 0.148785E+09 | 0.196490E+09 | 0.177345E+09 | 0.254116E+09 |
Maximum of Months | 0.167091E+10 | 0.944594E+09 | 0.747906E+09 | 0.225117E+10 | 0.146933E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176470E+10 | 0.125993E+10 | 0.504769E+09 | 0.172574E+10 | 0.185893E+10 |
February | 0.200250E+10 | 0.143241E+10 | 0.570088E+09 | 0.215772E+10 | 0.123350E+10 |
March | 0.198304E+10 | 0.110247E+10 | 0.880566E+09 | 0.214882E+10 | 0.118798E+10 |
April | 0.157936E+10 | 0.764296E+09 | 0.815062E+09 | 0.179060E+10 | 0.834158E+09 |
May | 0.144684E+10 | 0.488927E+09 | 0.957910E+09 | 0.167461E+10 | 0.683344E+09 |
June | 0.137236E+10 | 0.395501E+09 | 0.976856E+09 | 0.178402E+10 | 0.453272E+09 |
July | 0.153298E+10 | 0.564127E+09 | 0.968853E+09 | 0.220896E+10 | 0.377488E+09 |
August | 0.180046E+10 | 0.895102E+09 | 0.905362E+09 | 0.251123E+10 | 0.425803E+09 |
September | 0.195705E+10 | 0.119797E+10 | 0.759085E+09 | 0.253583E+10 | 0.585270E+09 |
October | 0.213468E+10 | 0.148113E+10 | 0.653543E+09 | 0.254921E+10 | 0.858267E+09 |
November | 0.186629E+10 | 0.135107E+10 | 0.515214E+09 | 0.204290E+10 | 0.110549E+10 |
December | 0.167731E+10 | 0.121137E+10 | 0.465942E+09 | 0.168384E+10 | 0.158415E+10 |
Annual Sum or Average | 0.211176E+11 | 0.121443E+11 | 0.897325E+10 | 0.248135E+11 | 0.111877E+11 |
Minimum of Months | 0.137236E+10 | 0.395501E+09 | 0.465942E+09 | 0.167461E+10 | 0.377488E+09 |
Maximum of Months | 0.213468E+10 | 0.148113E+10 | 0.976856E+09 | 0.254921E+10 | 0.185893E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377736E+09 | 0.152961E+09 | 0.224775E+09 | 0.200791E+09 | 0.150391E+10 |
February | 0.584828E+09 | 0.289804E+09 | 0.295024E+09 | 0.471168E+09 | 0.978458E+09 |
March | 0.824949E+09 | 0.304074E+09 | 0.520875E+09 | 0.710748E+09 | 0.872973E+09 |
April | 0.103935E+10 | 0.459738E+09 | 0.579611E+09 | 0.108510E+10 | 0.590888E+09 |
May | 0.132827E+10 | 0.606984E+09 | 0.721286E+09 | 0.151229E+10 | 0.480304E+09 |
June | 0.139451E+10 | 0.639616E+09 | 0.754894E+09 | 0.175055E+10 | 0.316791E+09 |
July | 0.147670E+10 | 0.745626E+09 | 0.731074E+09 | 0.199993E+10 | 0.271866E+09 |
August | 0.125541E+10 | 0.615520E+09 | 0.639888E+09 | 0.165208E+10 | 0.303046E+09 |
September | 0.978760E+09 | 0.494856E+09 | 0.483905E+09 | 0.118569E+10 | 0.424614E+09 |
October | 0.723197E+09 | 0.359682E+09 | 0.363514E+09 | 0.737410E+09 | 0.647748E+09 |
November | 0.495355E+09 | 0.246151E+09 | 0.249204E+09 | 0.410626E+09 | 0.885642E+09 |
December | 0.342080E+09 | 0.143880E+09 | 0.198200E+09 | 0.191435E+09 | 0.128239E+10 |
Annual Sum or Average | 0.108211E+11 | 0.505889E+10 | 0.576225E+10 | 0.119078E+11 | 0.855863E+10 |
Minimum of Months | 0.342080E+09 | 0.143880E+09 | 0.198200E+09 | 0.191435E+09 | 0.271866E+09 |
Maximum of Months | 0.147670E+10 | 0.745626E+09 | 0.754894E+09 | 0.199993E+10 | 0.150391E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 720.96 | 1721.27 | 956.03 | 599.58 | 356.45 | 0.00 | 0.00 |
February | 1218.04 | 1249.10 | 1314.09 | 834.15 | 479.93 | 0.00 | 0.00 |
March | 1324.89 | 1059.30 | 1376.13 | 661.52 | 714.61 | 0.00 | 0.00 |
April | 1506.68 | 734.04 | 1427.43 | 679.46 | 747.97 | 0.00 | 0.00 |
May | 1670.93 | 579.98 | 1495.94 | 614.08 | 881.86 | 0.00 | 0.00 |
June | 2084.34 | 386.19 | 1661.78 | 705.12 | 956.66 | 0.00 | 0.00 |
July | 2396.43 | 321.84 | 1747.53 | 841.68 | 905.85 | 0.00 | 0.00 |
August | 2251.11 | 362.50 | 1684.72 | 867.36 | 817.36 | 0.00 | 0.00 |
September | 1877.32 | 529.82 | 1516.94 | 851.53 | 665.42 | 0.00 | 0.00 |
October | 1479.99 | 774.93 | 1341.37 | 825.97 | 515.40 | 0.00 | 0.00 |
November | 1022.20 | 1049.96 | 1085.90 | 697.87 | 388.03 | 0.00 | 0.00 |
December | 694.90 | 1468.12 | 882.87 | 561.54 | 321.32 | 0.00 | 0.00 |
Annual Sum or Average | 1522.02 | 851.78 | 1374.19 | 727.39 | 646.79 | 0.00 | 0.00 |
Minimum of Months | 694.90 | 321.84 | 882.87 | 561.54 | 321.32 | 0.00 | 0.00 |
Maximum of Months | 2396.43 | 1721.27 | 1747.53 | 867.36 | 956.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193103E+10 | 0.461026E+10 | 0.256062E+10 | 0.160591E+10 | 0.954705E+09 | 0.00 | 0.00 |
February | 0.294669E+10 | 0.302183E+10 | 0.317903E+10 | 0.201798E+10 | 0.116105E+10 | 0.00 | 0.00 |
March | 0.354859E+10 | 0.283724E+10 | 0.368582E+10 | 0.177181E+10 | 0.191402E+10 | 0.00 | 0.00 |
April | 0.390532E+10 | 0.190264E+10 | 0.369989E+10 | 0.176116E+10 | 0.193873E+10 | 0.00 | 0.00 |
May | 0.447541E+10 | 0.155342E+10 | 0.400673E+10 | 0.164475E+10 | 0.236198E+10 | 0.00 | 0.00 |
June | 0.540261E+10 | 0.100100E+10 | 0.430734E+10 | 0.182768E+10 | 0.247966E+10 | 0.00 | 0.00 |
July | 0.641859E+10 | 0.862006E+09 | 0.468059E+10 | 0.225435E+10 | 0.242624E+10 | 0.00 | 0.00 |
August | 0.602936E+10 | 0.970913E+09 | 0.451236E+10 | 0.232314E+10 | 0.218923E+10 | 0.00 | 0.00 |
September | 0.486600E+10 | 0.137330E+10 | 0.393192E+10 | 0.220716E+10 | 0.172476E+10 | 0.00 | 0.00 |
October | 0.396400E+10 | 0.207558E+10 | 0.359271E+10 | 0.221228E+10 | 0.138044E+10 | 0.00 | 0.00 |
November | 0.264953E+10 | 0.272149E+10 | 0.281465E+10 | 0.180888E+10 | 0.100578E+10 | 0.00 | 0.00 |
December | 0.186123E+10 | 0.393221E+10 | 0.236467E+10 | 0.150404E+10 | 0.860632E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.479984E+11 | 0.268619E+11 | 0.433363E+11 | 0.229391E+11 | 0.203972E+11 | 0.00 | 0.00 |
Minimum of Months | 0.186123E+10 | 0.862006E+09 | 0.236467E+10 | 0.150404E+10 | 0.860632E+09 | 0.00 | 0.00 |
Maximum of Months | 0.641859E+10 | 0.461026E+10 | 0.468059E+10 | 0.232314E+10 | 0.247966E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639853E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173361188.0 | 81.22 | 0.00 | 0.00 |
February | 0.578972E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155437780.7 | 81.22 | 0.00 | 0.00 |
March | 0.646608E+10 | -0.629385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172231695.6 | 81.22 | 0.00 | 0.00 |
April | 0.620602E+10 | -0.604346E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162559575.9 | 81.22 | 0.00 | 0.00 |
May | 0.642440E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164216111.6 | 81.22 | 0.00 | 0.00 |
June | 0.623944E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152870523.1 | 81.21 | 0.00 | 0.00 |
July | 0.637275E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155653482.9 | 81.21 | 0.00 | 0.00 |
August | 0.645143E+10 | -0.629522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156209594.9 | 81.21 | 0.00 | 0.00 |
September | 0.619949E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154661614.0 | 81.21 | 0.00 | 0.00 |
October | 0.638901E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165202567.9 | 81.22 | 0.00 | 0.00 |
November | 0.618884E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164225627.8 | 81.22 | 0.00 | 0.00 |
December | 0.638981E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172731736.0 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755155E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.194936E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.578972E+10 | -0.629522E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173361188.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646608E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152870523.1 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.271081E+11 | -0.260948E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101330E+10 | 58.99 | 0.00 | 0.00 |
February | 0.249392E+11 | -0.240344E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -904769385.2 | 58.99 | 0.00 | 0.00 |
March | 0.275715E+11 | -0.265686E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100298E+10 | 58.99 | 0.00 | 0.00 |
April | 0.255084E+11 | -0.245755E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -932911980.6 | 58.99 | 0.00 | 0.00 |
May | 0.249750E+11 | -0.240454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -929583785.9 | 58.99 | 0.00 | 0.00 |
June | 0.227794E+11 | -0.219351E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -844274503.4 | 58.99 | 0.00 | 0.00 |
July | 0.221234E+11 | -0.212720E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -851368045.1 | 59.00 | 0.00 | 0.00 |
August | 0.218957E+11 | -0.210393E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -856400514.1 | 58.99 | 0.00 | 0.00 |
September | 0.213446E+11 | -0.204839E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -860678758.1 | 58.99 | 0.00 | 0.00 |
October | 0.230164E+11 | -0.220778E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -938561905.5 | 58.99 | 0.00 | 0.00 |
November | 0.236850E+11 | -0.227369E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -948077679.7 | 58.99 | 0.00 | 0.00 |
December | 0.259306E+11 | -0.249231E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100749E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.290877E+12 | -0.279787E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.110904E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213446E+11 | -0.265686E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.101330E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275715E+11 | -0.204839E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -844274503.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.50 | 01-JAN-08:50 | 3913.59 | 36.45 | 202.83 | 223.83 | 3630.99 | 34.42 | 184.50 | 221.00 |
February | 275.00 | 0.52 | 0.50 | 01-FEB-08:20 | 1433.23 | 26.48 | 190.50 | 254.50 | 1575.67 | 27.40 | 195.33 | 254.17 |
March | 304.00 | 0.51 | 0.50 | 01-MAR-07:40 | 1294.08 | 22.76 | 209.50 | 315.50 | 1483.43 | 22.93 | 208.50 | 314.67 |
April | 325.17 | 0.51 | 0.50 | 01-APR-08:39 | 1465.21 | 21.18 | 148.17 | 345.67 | 1400.02 | 21.19 | 154.33 | 348.67 |
May | 385.83 | 0.51 | 0.50 | 01-MAY-05:00 | 1265.36 | 22.19 | 191.67 | 395.83 | 1228.58 | 21.09 | 181.17 | 398.67 |
June | 434.17 | 0.52 | 0.50 | 01-JUN-13:39 | 1245.47 | 22.26 | 231.17 | 425.33 | 1397.89 | 20.75 | 181.67 | 419.67 |
July | 417.33 | 0.51 | 0.50 | 01-JUL-06:40 | 1390.38 | 21.96 | 201.33 | 409.33 | 1444.72 | 21.12 | 182.00 | 415.00 |
August | 421.33 | 0.52 | 0.50 | 01-AUG-05:00 | 1199.63 | 20.74 | 167.50 | 392.17 | 1343.55 | 20.66 | 164.00 | 392.67 |
September | 352.17 | 0.52 | 0.50 | 01-SEP-06:19 | 1244.33 | 21.30 | 167.33 | 329.50 | 1314.95 | 21.29 | 163.33 | 329.50 |
October | 317.67 | 0.52 | 0.50 | 01-OCT-07:49 | 1282.24 | 24.44 | 202.67 | 299.00 | 1117.04 | 24.31 | 202.83 | 298.67 |
November | 269.50 | 0.52 | 0.50 | 01-NOV-07:49 | 2887.29 | 34.13 | 233.83 | 247.67 | 2983.34 | 33.28 | 213.67 | 247.17 |
December | 236.83 | 0.53 | 0.50 | 01-DEC-08:39 | 3179.05 | 35.39 | 198.17 | 223.83 | 3306.61 | 35.80 | 205.00 | 219.83 |
Annual Sum or Average | 3965.83 | 0.52 | 1675.04 | 24.79 | 2344.67 | 3862.17 | 1719.22 | 24.34 | 2236.33 | 3859.67 | ||
Minimum of Months | 226.83 | 0.51 | 0.50 | 1199.63 | 20.74 | 148.17 | 223.83 | 1117.04 | 20.66 | 154.33 | 219.83 | |
Maximum of Months | 434.17 | 0.53 | 0.50 | 3913.59 | 36.45 | 233.83 | 425.33 | 3630.99 | 35.80 | 213.67 | 419.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.818623E+11 | 145230.20 | 06-JAN-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.494053E+11 | 145230.20 | 01-FEB-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422276E+11 | 145230.20 | 04-MAR-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191467E+11 | 101211.60 | 29-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124014E+11 | 65197.02 | 08-MAY-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186917E+10 | 32938.80 | 15-JUN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249323E+09 | 21112.03 | 08-JUL-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.472758E+09 | 19567.30 | 18-AUG-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410447E+10 | 33839.08 | 17-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124937E+11 | 51492.42 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313697E+11 | 145230.20 | 27-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.611032E+11 | 145230.20 | 16-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316706E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.249323E+09 | 19567.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.818623E+11 | 145230.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.489210E+11 | 77304.17 | 29-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265253E+11 | 54858.21 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204326E+11 | 58036.19 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.680897E+10 | 41804.72 | 29-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416988E+10 | 22128.46 | 08-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218338E+09 | 15908.30 | 15-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 559834.94 | 3315.10 | 08-JUL-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7355299.88 | 2595.17 | 17-AUG-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.699480E+09 | 15576.05 | 17-SEP-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364359E+10 | 28836.86 | 10-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144419E+11 | 47862.02 | 12-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336381E+11 | 57870.60 | 31-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 559834.94 | 2595.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489210E+11 | 77304.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 12709610.36 | 12709610.36 | 3634.99 | 27-FEB-14:00 | 3634.99 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.555377E+09 | 0.554026E+09 | 13620.88 | 07-APR-12:53 | 13620.88 | 0.00 |
May | 0.00 | 0.00 | 0.464952E+10 | 0.442081E+10 | 74229.72 | 20-MAY-03:01 | 56668.37 | 0.00 |
June | 0.00 | 0.00 | 0.166045E+11 | 0.150716E+11 | 74229.72 | 01-JUN-03:01 | 52596.39 | 0.00 |
July | 0.00 | 0.00 | 0.319431E+11 | 0.298373E+11 | 74249.58 | 19-JUL-03:01 | 47768.21 | 0.00 |
August | 0.00 | 0.00 | 0.253069E+11 | 0.244106E+11 | 74229.72 | 07-AUG-03:41 | 73566.00 | 0.00 |
September | 0.00 | 0.00 | 0.133541E+11 | 0.120208E+11 | 74229.72 | 04-SEP-03:27 | 68639.40 | 0.00 |
October | 0.00 | 0.00 | 0.153467E+10 | 0.152937E+10 | 21388.69 | 18-OCT-12:55 | 21388.69 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.939608E+11 | 0.878571E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.319431E+11 | 0.298373E+11 | 74249.58 | 73566.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 15899665.08 | 15376761.18 | 2954.91 | 28-FEB-04:08 | 2117.14 | 0.00 |
March | 0.00 | 0.00 | 648827.79 | 528669.58 | 1130.41 | 21-MAR-03:40 | 893.96 | 0.00 |
April | 0.00 | 0.00 | 0.486919E+09 | 0.473116E+09 | 34390.20 | 07-APR-03:01 | 30720.19 | 0.00 |
May | 0.00 | 0.00 | 0.368966E+10 | 0.337545E+10 | 34390.20 | 21-MAY-03:01 | 20634.08 | 0.00 |
June | 0.00 | 0.00 | 0.118435E+11 | 0.104144E+11 | 34390.20 | 01-JUN-03:01 | 21156.39 | 0.00 |
July | 0.00 | 0.00 | 0.216338E+11 | 0.198308E+11 | 34390.20 | 19-JUL-03:47 | 19548.31 | 0.00 |
August | 0.00 | 0.00 | 0.174439E+11 | 0.163821E+11 | 34390.20 | 01-AUG-03:01 | 20654.70 | 0.00 |
September | 0.00 | 0.00 | 0.988140E+10 | 0.852871E+10 | 34390.20 | 03-SEP-03:11 | 27161.80 | 0.00 |
October | 0.00 | 0.00 | 0.132734E+10 | 0.127784E+10 | 34390.20 | 03-OCT-03:41 | 21667.94 | 0.00 |
November | 0.00 | 0.00 | 34598573.48 | 29722063.16 | 34390.20 | 05-NOV-03:01 | 28130.27 | 0.00 |
December | 0.00 | 0.00 | 1323328.46 | 1084076.68 | 1246.40 | 05-DEC-04:40 | 1101.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.663590E+11 | 0.603291E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216338E+11 | 0.198308E+11 | 34390.20 | 30720.19 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10200.17 | 19656.57 | 31-JAN-19:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10391.78 | 19775.56 | 21-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 10376.36 | 19745.62 | 01-MAR-19:38 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9939.25 | 19220.36 | 03-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9436.24 | 18385.81 | 01-MAY-18:27 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8922.50 | 17272.49 | 02-JUN-18:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8403.36 | 16305.41 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8316.65 | 15713.87 | 03-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8364.15 | 16105.57 | 29-SEP-18:28 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8703.43 | 17004.35 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9231.45 | 18052.81 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9763.62 | 18991.63 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 9331.19 | ||||
Minimum of Months | 0.00 | 0.00 | 8316.65 | 15713.87 | ||
Maximum of Months | 0.00 | 0.00 | 10391.78 | 19775.56 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184243E+10 | 0.25 | 824.13 | 01-JAN-00:01 | 0.30 |
February | 0.166738E+10 | 0.25 | 824.13 | 01-FEB-00:01 | 0.30 |
March | 0.184292E+10 | 0.25 | 824.13 | 01-MAR-00:01 | 0.30 |
April | 0.181251E+10 | 0.26 | 824.13 | 01-APR-04:01 | 0.30 |
May | 0.189064E+10 | 0.26 | 824.13 | 01-MAY-04:01 | 0.30 |
June | 0.188446E+10 | 0.27 | 824.13 | 01-JUN-03:01 | 0.30 |
July | 0.200733E+10 | 0.27 | 824.13 | 01-JUL-00:55 | 0.30 |
August | 0.199596E+10 | 0.27 | 824.13 | 01-AUG-00:50 | 0.30 |
September | 0.189632E+10 | 0.27 | 824.13 | 01-SEP-00:55 | 0.30 |
October | 0.190485E+10 | 0.26 | 824.13 | 01-OCT-03:01 | 0.30 |
November | 0.181214E+10 | 0.26 | 824.13 | 01-NOV-04:01 | 0.30 |
December | 0.184564E+10 | 0.25 | 824.13 | 01-DEC-00:01 | 0.30 |
Annual Sum or Average | 0.224026E+11 | 0.26 | |||
Minimum of Months | 0.166738E+10 | 0.25 | 824.13 | 0.30 | |
Maximum of Months | 0.200733E+10 | 0.27 | 824.13 | 0.30 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.809483E+10 | 1.01 | 6522.33 | 06-JAN-04:07 | 1.61 |
February | 0.664028E+10 | 0.96 | 6522.33 | 01-FEB-04:07 | 1.61 |
March | 0.699183E+10 | 0.93 | 6522.33 | 04-MAR-04:05 | 1.61 |
April | 0.615381E+10 | 0.86 | 4545.44 | 29-APR-03:02 | 1.61 |
May | 0.615921E+10 | 0.84 | 3714.23 | 07-MAY-04:01 | 1.21 |
June | 0.569860E+10 | 0.82 | 5905.46 | 21-JUN-03:01 | 1.53 |
July | 0.592152E+10 | 0.83 | 6522.33 | 17-JUL-03:01 | 1.60 |
August | 0.588384E+10 | 0.82 | 6117.83 | 08-AUG-03:01 | 1.55 |
September | 0.576488E+10 | 0.83 | 6419.48 | 04-SEP-03:01 | 1.58 |
October | 0.616018E+10 | 0.84 | 3996.45 | 10-OCT-04:01 | 1.26 |
November | 0.649281E+10 | 0.90 | 6522.33 | 27-NOV-04:03 | 1.61 |
December | 0.750270E+10 | 0.97 | 6522.33 | 16-DEC-04:02 | 1.61 |
Annual Sum or Average | 0.774645E+11 | 0.88 | |||
Minimum of Months | 0.569860E+10 | 0.82 | 3714.23 | 1.21 | |
Maximum of Months | 0.809483E+10 | 1.01 | 6522.33 | 1.61 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199649E+10 | 0.61 | 1477.55 | 29-JAN-05:02 | 0.96 |
February | 0.161755E+10 | 0.57 | 1241.23 | 01-FEB-05:02 | 0.88 |
March | 0.169652E+10 | 0.55 | 1274.69 | 05-MAR-05:02 | 0.89 |
April | 0.150840E+10 | 0.53 | 1103.79 | 29-APR-04:03 | 0.83 |
May | 0.153390E+10 | 0.53 | 1659.12 | 20-MAY-03:01 | 1.00 |
June | 0.147953E+10 | 0.54 | 1659.12 | 01-JUN-03:01 | 1.00 |
July | 0.162825E+10 | 0.57 | 1659.12 | 01-JUL-03:01 | 1.00 |
August | 0.160012E+10 | 0.56 | 1659.12 | 01-AUG-03:01 | 1.00 |
September | 0.150507E+10 | 0.54 | 1659.12 | 01-SEP-03:01 | 1.00 |
October | 0.152888E+10 | 0.53 | 1659.12 | 19-OCT-03:01 | 1.01 |
November | 0.158875E+10 | 0.55 | 1167.57 | 12-NOV-05:03 | 0.85 |
December | 0.183574E+10 | 0.58 | 1272.94 | 31-DEC-05:02 | 0.89 |
Annual Sum or Average | 0.195192E+11 | 0.56 | |||
Minimum of Months | 0.147953E+10 | 0.53 | 1103.79 | 0.83 | |
Maximum of Months | 0.199649E+10 | 0.61 | 1659.12 | 1.01 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.71 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 46.44 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.62 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.44 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 51.25 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 51.93 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.94 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.27 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.67 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 52.01 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.72 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.61 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 46.44 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.67 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.71 | 59.93 | 10200.17 | 19656.57 | 31-JAN-19:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.44 | 59.69 | 10391.78 | 19775.56 | 21-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.62 | 58.99 | 10376.36 | 19745.62 | 01-MAR-19:38 |
April | 0.00 | 0.00 | 01-APR-00:01 | 48.63 | 48.63 | 9939.25 | 19220.36 | 03-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 48.75 | 48.75 | 9436.24 | 18385.81 | 01-MAY-18:27 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 49.41 | 49.41 | 8922.50 | 17272.49 | 02-JUN-18:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 49.79 | 49.79 | 8403.36 | 16305.41 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.03 | 50.03 | 8316.65 | 15713.87 | 03-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.44 | 50.44 | 8364.15 | 16105.57 | 29-SEP-18:28 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 47.71 | 47.71 | 8703.43 | 17004.35 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.00 | 50.00 | 9231.45 | 18052.81 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.61 | 58.56 | 9763.62 | 18991.63 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 9331.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.44 | 47.71 | 8316.65 | 15713.87 | ||
Maximum of Months | 0.00 | 0.00 | 50.44 | 59.93 | 10391.78 | 19775.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.809483E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.664463E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.699183E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.633635E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.760513E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.106134E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.153234E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.133801E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.973727E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.665275E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.649281E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.750270E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.105375E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.633635E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153234E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.199649E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.162238E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.169672E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.164898E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.252632E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.451801E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.714614E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.610609E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.405445E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.190124E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159857E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.183614E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.366515E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159857E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.714614E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.809483E+10 | 0.00 | 0.818623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.664028E+10 | 12709610.36 | 0.494053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699183E+10 | 0.00 | 0.422276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615381E+10 | 0.555377E+09 | 0.191467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.615921E+10 | 0.464801E+10 | 0.124014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569860E+10 | 0.165969E+11 | 0.186917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.592152E+10 | 0.318869E+11 | 0.249323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.588384E+10 | 0.252707E+11 | 0.472758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576488E+10 | 0.133376E+11 | 0.410447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616018E+10 | 0.153467E+10 | 0.124937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649281E+10 | 0.00 | 0.313697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750270E+10 | 0.00 | 0.611032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774645E+11 | 0.938429E+11 | 0.316706E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.569860E+10 | 0.00 | 0.249323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.809483E+10 | 0.318869E+11 | 0.818623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199649E+10 | 0.00 | 0.489210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161755E+10 | 15899665.08 | 0.265253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169652E+10 | 648827.79 | 0.204326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150840E+10 | 0.484135E+09 | 0.680897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153390E+10 | 0.368732E+10 | 0.416988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147953E+10 | 0.118365E+11 | 0.218338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162825E+10 | 0.215977E+11 | 559834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160012E+10 | 0.174263E+11 | 7355299.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150507E+10 | 0.986587E+10 | 0.699480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152888E+10 | 0.132141E+10 | 0.364359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158875E+10 | 32649795.25 | 0.144419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183574E+10 | 1323328.46 | 0.336381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195192E+11 | 0.662698E+11 | 0.159507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147953E+10 | 0.00 | 559834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199649E+10 | 0.215977E+11 | 0.489210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.809483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.664028E+10 | 0.00 | 0.00 | 0.00 | 4346560.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615381E+10 | 0.00 | 0.00 | 0.00 | 0.182541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.615921E+10 | 0.00 | 0.00 | 0.00 | 0.144592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569860E+10 | 0.00 | 0.00 | 0.00 | 0.491480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.592152E+10 | 0.00 | 0.00 | 0.00 | 0.940193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.588384E+10 | 0.00 | 0.00 | 0.00 | 0.749625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576488E+10 | 0.00 | 0.00 | 0.00 | 0.397240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616018E+10 | 0.00 | 0.00 | 0.00 | 0.492566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774645E+11 | 0.00 | 0.00 | 0.00 | 0.279107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.569860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.809483E+10 | 0.00 | 0.00 | 0.00 | 0.940193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.199649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161755E+10 | 0.00 | 0.00 | 0.00 | 4832571.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169652E+10 | 0.00 | 0.00 | 0.00 | 198201.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150840E+10 | 0.00 | 0.00 | 0.00 | 0.140586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153390E+10 | 0.00 | 0.00 | 0.00 | 0.992411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147953E+10 | 0.00 | 0.00 | 0.00 | 0.303848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162825E+10 | 0.00 | 0.00 | 0.00 | 0.551788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160012E+10 | 0.00 | 0.00 | 0.00 | 0.450598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150507E+10 | 0.00 | 0.00 | 0.00 | 0.254938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152888E+10 | 0.00 | 0.00 | 0.00 | 0.372355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158875E+10 | 0.00 | 0.00 | 0.00 | 9819549.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183574E+10 | 0.00 | 0.00 | 0.00 | 404553.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195192E+11 | 0.00 | 0.00 | 0.00 | 0.171323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199649E+10 | 0.00 | 0.00 | 0.00 | 0.551788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.528605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529583E+11 | 0.00 | 0.00 | 3.57 |
February | 0.534449E+11 | 0.00 | 0.00 | 652636.82 | 0.00 | 0.221817E+11 | 0.858348E+09 | 0.00 | 3.57 |
March | 0.626939E+11 | 0.00 | 0.00 | 135131.16 | 0.00 | 0.120176E+11 | 0.206058E+09 | 0.00 | 3.57 |
April | 0.465030E+11 | 0.00 | 0.00 | 12065754.75 | 0.00 | 0.160194E+10 | 0.611917E+10 | 0.00 | 3.67 |
May | 0.351358E+11 | 21295595.90 | 0.00 | 36646811.18 | 0.00 | 0.928044E+09 | 0.117694E+11 | 0.00 | 3.86 |
June | 0.133776E+11 | 0.452901E+09 | 0.00 | 80404756.95 | 0.00 | 8597002.13 | 0.175555E+11 | 0.00 | 4.12 |
July | 0.622085E+10 | 0.166251E+10 | 0.00 | 0.105155E+09 | 0.00 | 2958546.49 | 0.145454E+11 | 0.00 | 4.12 |
August | 0.840648E+10 | 0.110408E+10 | 0.00 | 99686114.59 | 0.00 | 1707337.50 | 0.178473E+11 | 0.00 | 4.18 |
September | 0.193873E+11 | 0.656724E+09 | 0.00 | 56855836.18 | 0.00 | 11571733.08 | 0.165850E+11 | 0.00 | 4.02 |
October | 0.410459E+11 | 0.00 | 0.00 | 18283970.61 | 0.00 | 50963948.93 | 0.109782E+11 | 0.00 | 3.73 |
November | 0.570992E+11 | 0.00 | 0.00 | 1931374.62 | 0.00 | 0.460497E+10 | 0.368073E+10 | 0.00 | 3.54 |
December | 0.636530E+11 | 0.00 | 0.00 | 58240.19 | 0.00 | 0.255156E+11 | 0.330526E+09 | 0.00 | 3.58 |
Annual Sum or Average | 0.459828E+12 | 0.389750E+10 | 0.00 | 0.411875E+09 | 0.00 | 0.119884E+12 | 0.100476E+12 | 0.00 | 3.80 |
Minimum of Months | 0.622085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1707337.50 | 0.00 | 0.00 | 3.54 |
Maximum of Months | 0.636530E+11 | 0.166251E+10 | 0.00 | 0.105155E+09 | 0.00 | 0.529583E+11 | 0.178473E+11 | 0.00 | 4.18 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.879357E+11 | 0.00 | 0.00 | 50419.01 | 14588058.06 | 58573538.04 | 0.225061E+09 | 0.00 | 7.96 |
February | 0.607833E+11 | 0.00 | 0.00 | 1126405.31 | 58205905.57 | 23708307.94 | 0.161244E+10 | 0.00 | 7.72 |
March | 0.615157E+11 | 0.00 | 0.00 | 161517.39 | 3937306.95 | 16371146.06 | 0.664900E+09 | 0.00 | 7.62 |
April | 0.391940E+11 | 0.00 | 0.00 | 12389129.70 | 0.00 | 7953414.10 | 0.847676E+10 | 0.00 | 7.42 |
May | 0.291043E+11 | 0.00 | 0.00 | 39275901.86 | 0.00 | 0.00 | 0.151038E+11 | 0.00 | 7.44 |
June | 0.945949E+10 | 19550745.28 | 0.00 | 86254493.64 | 0.00 | 0.00 | 0.226315E+11 | 0.00 | 7.55 |
July | 0.334308E+10 | 0.981118E+09 | 0.00 | 0.115873E+09 | 0.00 | 0.00 | 0.216755E+11 | 0.00 | 7.71 |
August | 0.387905E+10 | 0.634661E+09 | 0.00 | 0.103455E+09 | 0.00 | 0.00 | 0.249448E+11 | 0.00 | 7.68 |
September | 0.132835E+11 | 0.381801E+09 | 0.00 | 62354301.73 | 0.00 | 0.00 | 0.207350E+11 | 0.00 | 7.58 |
October | 0.293488E+11 | 0.00 | 0.00 | 22963928.52 | 0.00 | 2615575.32 | 0.169958E+11 | 0.00 | 7.41 |
November | 0.475177E+11 | 0.00 | 0.00 | 4699705.70 | 8073344.30 | 15193359.75 | 0.777893E+10 | 0.00 | 7.51 |
December | 0.732961E+11 | 0.00 | 0.00 | 221298.88 | 0.00 | 36209543.52 | 0.114821E+10 | 0.00 | 7.82 |
Annual Sum or Average | 0.458661E+12 | 0.201713E+10 | 0.00 | 0.448826E+09 | 84804614.87 | 0.160625E+09 | 0.141993E+12 | 0.00 | 7.62 |
Minimum of Months | 0.334308E+10 | 0.00 | 0.00 | 50419.01 | 0.00 | 0.00 | 0.225061E+09 | 0.00 | 7.41 |
Maximum of Months | 0.879357E+11 | 0.981118E+09 | 0.00 | 0.115873E+09 | 58205905.57 | 58573538.04 | 0.249448E+11 | 0.00 | 7.96 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:36
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.192579E+11 | 0.161002E+11 | 0.306094E+12 | 0.00 | 0.342907E+11 |
February | 0.421977E+11 | 0.120338E+11 | 0.224423E+12 | 80726447.27 | 0.241803E+11 |
March | 0.828080E+11 | 0.124957E+11 | 0.224478E+12 | 0.00 | 0.241975E+11 |
April | 0.925201E+11 | 0.996544E+10 | 0.175430E+12 | 0.894636E+09 | 0.211408E+11 |
May | 0.130080E+12 | 0.101358E+11 | 0.160674E+12 | 0.209514E+10 | 0.316695E+11 |
June | 0.144776E+12 | 0.797664E+10 | 0.115255E+12 | 0.332170E+10 | 0.572372E+11 |
July | 0.143721E+12 | 0.631280E+10 | 0.888684E+11 | 0.287830E+10 | 0.917666E+11 |
August | 0.118566E+12 | 0.624172E+10 | 0.103307E+12 | 0.365091E+10 | 0.761079E+11 |
September | 0.873279E+11 | 0.647909E+10 | 0.125396E+12 | 0.279254E+10 | 0.475432E+11 |
October | 0.483149E+11 | 0.817939E+10 | 0.172382E+12 | 0.128415E+10 | 0.209697E+11 |
November | 0.169776E+11 | 0.973824E+10 | 0.202818E+12 | 67848520.09 | 0.191149E+11 |
December | 0.705293E+10 | 0.129794E+11 | 0.263804E+12 | 0.00 | 0.272719E+11 |
Annual Sum or Average | 0.933601E+12 | 0.118638E+12 | 0.216293E+13 | 0.170659E+11 | 0.475490E+12 |
Minimum of Months | 0.705293E+10 | 0.624172E+10 | 0.888684E+11 | 0.00 | 0.191149E+11 |
Maximum of Months | 0.144776E+12 | 0.161002E+11 | 0.306094E+12 | 0.365091E+10 | 0.917666E+11 |