Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:26:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2505.27 | 4901.21 | 4901.21 |
Net Site Energy | 2505.27 | 4901.21 | 4901.21 |
Total Source Energy | 4331.68 | 8474.32 | 8474.32 |
Net Source Energy | 4331.68 | 8474.32 | 8474.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 863.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 70.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.52 | 395.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 35.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 775.79 | 1729.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 863.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 70.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 89.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.52 | 395.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 863.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 70.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 43.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 435.66 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 89.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.52 | 395.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 35.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 135.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 460.45 | 2464.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 922.11 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1517.72 | 3383.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 135.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 460.45 | 2464.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 922.11 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1517.72 | 3383.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 775.788 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 775.788 | 100.00 |
Total On-Site and Utility Electric Sources | 775.788 | 100.00 |
Total Electricity End Uses | 775.788 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 21.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4475.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.3716 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.8021 | 18.52 | 1057.5080 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.0345 | 1.78 | 335.6309 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.3716 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.8021 | 18.52 | 1057.5080 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Conditioned Total | 511.15 | 7.0345 | 0.89 | 335.6309 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.0345 | 1.78 | 335.6309 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-11:00 | 02-FEB-07:49 | - | - | - | - | - | - | - | - | - | - | 22-MAR-18:40 |
Heating | 0.00 | 213577.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 31523.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1871.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22289.73 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5787.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2994.72 | 35750.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1222.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 65707.69 | 262904.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 213577.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 31523.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1871.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21698.93 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5787.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2994.72 | 35750.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 391.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 936.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 221.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 137.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1379.75 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 282.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.17 | 429.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 112.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2456.92 | 1874.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1831.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 433.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.89 | 839.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 221.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4806.62 | 3667.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1831.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 433.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2699.28 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.89 | 839.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 221.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4806.62 | 3667.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.50 |
KITCHEN DIRECT AIR | 1.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.50 | 3.50 | 3.50 | 3.50 | 3.50 | 3.50 | 1.00 | 0.999976 | 3.50 |
PSZ-AC_2:2 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.00 | 1.000000 | 1.50 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.50 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.50 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.50 | 3748.33 |
PSZ-AC_2:2_ADDAQ FAN | 1.50 | 1600.43 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.50 | 3.50 | 3.50 | 2.31 | 86986.75 | 149343.72 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.50 | 1.50 | 1.50 | 0.987140 | 37140.96 | 99887.30 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.50 | 1.75 | 2.34 | 86986.75 | 43493.38 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.50 | 0.747833 | 0.997113 | 37140.96 | 18570.48 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 149343.72 |
PSZ-AC_2:2 HEATING COIL | 99887.30 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.372 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.299 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.802 | 408.232 | 649.276 | 0.000 | 0.000 | 0.000 | 1066.310 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2368.645 | 6.372 | 8.455 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2368.645 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1227.055 | 8.802 | 163.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1227.055 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 277.500 | 1.991 | 36.863 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 313.300 | 2.247 | 41.619 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7719 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1345 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2291 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.062 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.356 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.287 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.30221493E-12 | 0.42806226E-14 | -0.95155442E-13 | 0.15899766E-15 |
34 | 6 | 0.28727294E-07 | 0.21728364E-09 | 0.65803531E-08 | -0.13544055E-12 |
35 | 5 | -0.19039181E-03 | 0.18585303E-05 | -0.97925888E-04 | 0.65048812E-08 |
36 | 4 | 0.29248049 | 0.90406920E-03 | 0.99803377E-01 | -0.33617969E-04 |
37 | 3 | -7.2729408 | 0.27994057E-01 | -2.3408748 | 0.29041410E-01 |
38 | 2 | 40.892958 | 0.99469394E-01 | 15.273156 | -0.33358329 |
39 | 1 | -80.562512 | 0.44862081E-01 | -29.148912 | 1.0789757 |
40 | 0 | 46.824339 | 0.90199676E-03 | 16.291060 | |
41 | 7 | -0.31585163E-08 | -0.22597303E-14 | 0.15834007E-14 | -0.44811583E-16 |
42 | 6 | 0.38926816E-05 | 0.25726622E-08 | 0.31949392E-02 | -0.26801827E-04 |
43 | 5 | -0.27259256E-03 | 0.15209505E-05 | -0.22401268 | 0.19586932E-02 |
44 | 4 | 0.62224649E-02 | 0.69174334E-04 | 4.8343438 | -0.45311104E-01 |
45 | 3 | -0.54492574E-01 | 0.54963890E-03 | -38.048519 | 0.39895333 |
46 | 2 | 0.19328371 | 0.91376166E-03 | 116.53670 | -1.4186449 |
47 | 1 | -0.27884260 | 0.27809541E-03 | -143.93836 | 2.0495503 |
48 | 0 | 0.13591665 | 0.67534627E-05 | 60.838472 | |
49 | 7 | -0.18366387E-08 | -0.45273224E-15 | 0.66973396E-14 | -0.89481334E-16 |
50 | 6 | 0.64176182E-05 | 0.43906086E-08 | 0.31875387E-02 | -0.26739746E-04 |
51 | 5 | -0.46144041E-03 | 0.26013657E-05 | -0.22359208 | 0.19549808E-02 |
52 | 4 | 0.10613927E-01 | 0.11841222E-03 | 4.8273389 | -0.45243768E-01 |
53 | 3 | -0.93204934E-01 | 0.94170345E-03 | -38.008950 | 0.39851596 |
54 | 2 | 0.33095125 | 0.15665766E-02 | 116.45969 | -1.4176148 |
55 | 1 | -0.47767855 | 0.47741295E-03 | -143.89302 | 2.0488052 |
56 | 0 | 0.23289156 | 0.11519323E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 39 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 40 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 41 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7059E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7094E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5954E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4869E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4521E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4708E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1282E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0430E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.3406E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.2348E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.3041E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.1773E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2428E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.2000E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0686E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0686E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5757E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5329E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3153E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3728E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2958E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3101E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0430E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1282E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 38257.50865 | 45909.01038 | 2.91906 | 3.50287 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 12264.27703 | 14717.13243 | 0.55109 | 1.33138 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 19265.30566 | 23118.36679 | 1.24639 | 1.49567 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30.24600 | 1.53633E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 3270.82386 | 3924.98863 | 0.13297 | 1.21700 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 56291.40 | 3.50296 | 3.50296 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 101722.32 | 1.33138 | 1.33138 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 28869.69 | 1.49567 | 1.49567 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 92983.59 | 1.21700 | 1.21700 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.50287 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49567 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.50287 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.50287 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.50287 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.50287 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.50296 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.50296 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99998 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49567 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49567 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49567 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49567 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49567 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49567 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.50296 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.49567 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.50296 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.50296 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3748.32875 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.50296 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.50296 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.50296 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.31195 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.50296 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.75148 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.33531 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 86986.75000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 43493.37500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 86986.75000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 149343.72286 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 149343.72286 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49567 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49567 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1600.43376 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49567 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49567 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49567 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98714 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49567 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74783 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99711 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37140.96000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18570.48000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37140.96000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 99887.30120 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 99887.30120 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 84497.0 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 36077.9 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.135 | 0.130 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.229 | 0.217 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.2419353848E-002 | 0.4455542933 | Pass | Pass | 0.2630241672 | 1.1637043379 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 7.2500782921E-002 | 0.4321190138 | Pass | Pass | 4.2924537304E-002 | 0.1864320336 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1413363152 | 0.1718494150 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 980.60 | 135.94 | 2240.59 | 8.11 | 685.20 | 4050.45 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.132 | 0.135 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.221 | 0.229 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.943 | 0.380 | 0.418 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.3716 | 371.75 | 2368.64 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.17 | 0.0000 | Y | 26.75 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.8021 | 139.41 | 1227.05 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.61 | 0.0000 | Y | 16.72 |
Interior Lighting Total | 7.0345 | 511.15 | 3595.70 | 43.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 2368.64 | 592.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 49.24 | 49.24 | 1.95 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.63 | 62.93 | 23.66 | |
Exterior Lighting Total | 2213.72 | 25.61 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 86986.75 | 60984.67 | 26002.08 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37140.96 | 26038.78 | 11102.18 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 84497.0 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 36077.9 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 149343.72 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 99887.30 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 3.50 | 3748.33 | 1070.05 | 1.00 | 1.25 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.50 | 1600.43 | 1070.05 | 1.00 | 1.36 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 38257.51 | 45909.01 | 123.49 | 2.919 | 3.503 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.01096 | 31.09 | 0.01536 | 1.331 | 0.00 |
KITCHEN | 19265.31 | 23118.37 | 165.84 | 1.246 | 1.496 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01059 | 30.25 | 0.01536 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 12264.28 | 14717.13 | 39.59 | 0.551 | 1.331 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00754 | -26.20 | 0.00036 | 1.331 | 0.00 |
KITCHEN | 3270.82 | 3924.99 | 28.16 | 0.133 | 1.217 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00659 | -26.20 | 0.00036 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.50 | 3.50 | 1.33 | 1.33 | 3.5030 | 3.5029 | 3.5030 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.50 | 1.50 | 1.22 | 1.22 | 1.4957 | 1.4957 | 1.4957 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 86986.750 | 60984.671 | 3.502960 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 43493.38 | 26323.62 | 2.335307 | 26.72 | 20.02 | 0.01263373 | 11.89 | 11.30 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 57.0108 | 23.98 | 0.01095916 | 56.1136 | 38254.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 149343.723 | 149343.723 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 149343.72 | 149343.72 | 3.502956 | 3.06 | 2.89 | 0.00481239 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 38.0073 | 21.00 | 0.00754129 | 46.5385 | 12263.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 37140.960 | 26038.784 | 1.495670 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 18570.48 | 10356.03 | 0.997113 | 30.46 | 22.50 | 0.01469579 | 11.90 | 11.31 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 122.0525 | 25.98 | 0.01061293 | 48.2606 | 19265.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 99887.301 | 99887.301 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | 99887.30 | 99887.30 | 1.495666 | -17.87 | -17.87 | 0.00152493 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 81.3685 | 19.00 | 0.00660665 | 46.2205 | 2298.83 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 86986.750 | 60984.671 | 3.502960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.3255 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.502956 | 4.02334079 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 43493.38 | 26323.62 | 1.0000 | 2.68223008 | 2.335307 | 26.72 | 20.02 | 0.01263373 | 59076.7 | 11.89 | 11.30 | 0.00850000 | 33397.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43493.38 | 31.20 | 0.01536508 | 23.13 | 1.33137743 | 57.0108 | 23.98 | 0.01095916 | 23.98 | 0.01095916 | 56.1136 | 38254.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 149343.723 | 149343.723 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.502956 | 4.02334079 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 149343.72 | 149343.72 | 1.0000 | 4.02334079 | 3.502956 | 3.06 | 2.89 | 0.00481239 | 15137.4 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 149343.72 | -26.20 | 0.00036134 | -26.20 | 1.33137743 | 38.0073 | 21.00 | 0.00754129 | 21.00 | 0.00754129 | 46.5385 | 12263.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37140.960 | 26038.784 | 1.495670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1032.1587 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.495666 | 1.71785638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 18570.48 | 10356.03 | 1.0000 | 1.14524033 | 0.997113 | 30.46 | 22.50 | 0.01469579 | 68191.9 | 11.90 | 11.31 | 0.00850000 | 33400.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18570.48 | 31.20 | 0.01536508 | 23.13 | 1.21700195 | 122.0525 | 25.94 | 0.01061293 | 25.98 | 0.01061293 | 48.2606 | 19265.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99887.301 | 99887.301 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.495666 | 1.71785638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | Sensible | 99887.30 | 99887.30 | 1.0000 | 1.71785638 | 1.495666 | -17.87 | -17.87 | 0.00152493 | -14188.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99887.30 | -26.20 | 0.00036134 | -26.20 | 1.21700195 | 81.3685 | 18.53 | 0.00660665 | 19.00 | 0.00660665 | 46.2205 | 2298.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.50 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.50 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3906.33 | 5828.50 | 2742.83 |
KITCHEN | 5110.83 | 6255.33 | 4329.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5255.50 | 7086.67 | 4475.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 32.33 | 3.67 | 0.00 | 0.00 |
KITCHEN | 0.00 | 80.50 | 0.00 | 21.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 32.33 | 84.17 | 0.00 | 21.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.490 | 0.603 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.985 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.085 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.185 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36824924.43 | 0.00 | 36824924.43 | 4992110.83 | 41817035.26 | 41986318.57 | 1448.24 | 6112.75 | 1199.01 | 258.94 |
KITCHEN | 27705740.15 | 0.00 | 27705740.15 | 239388.33 | 27945128.47 | 38379373.44 | 8217.06 | 516.67 | 26.27 | 335.49 |
Total Facility | 64530664.57 | 0.00 | 64530664.57 | 5231499.16 | 69762163.73 | 80365692.01 | 8219.65 | 6117.36 | 1217.93 | 454.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3938 | 0.0000 | 1.3938 | 0.1872 | 1.5810 | 1.3314 | 0.00 | 5992.72 | 1194.28 |
KITCHEN | 1.0457 | 0.0000 | 1.0457 | 0.0056 | 1.0513 | 1.2170 | 6656.77 | 507.75 | 22.48 |
Total Facility | 2.4395 | 0.0000 | 2.4395 | 0.1928 | 2.6323 | 2.5484 | 6656.77 | 5997.05 | 1210.76 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48578455.13 | 0.00 | 48578455.13 | 41986318.57 | 1446.31 | 0.08 | 7313.61 | 258.94 |
PSZ-AC_2:2 | 36548695.39 | 0.00 | 36548695.39 | 38379373.44 | 1444.65 | 0.26 | 7315.09 | 335.49 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8387 | 0.0000 | 1.8387 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3794 | 0.0000 | 1.3794 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1166.16 | 171.28 | 6108.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 165.88 | 1208.13 | 6148.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.2882 | 2.0198 | 1.7567 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.4888 | 1.4788 | 1.3630 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
Electricity:Building | 486.07 | 2437.13 | 01-JAN-01:20 | 27911.96 | 02-JAN-11:10 |
Electricity:Zone:DINING | 151.86 | 560.03 | 01-JAN-01:20 | 8292.44 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 479.14 | 2300.85 | 01-JAN-01:20 | 25768.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 43.48 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 26.75 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 43.48 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 43.48 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 26.75 | 80.03 | 01-JAN-01:20 | 2023.86 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 43.48 | 110.04 | 01-JAN-01:20 | 2883.74 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 334.21 | 1877.10 | 01-JAN-01:20 | 19908.15 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.72 | 30.01 | 01-JAN-01:20 | 859.87 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 435.66 | 2190.81 | 01-JAN-01:10 | 23897.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 310.55 | 1710.81 | 01-JAN-01:10 | 16905.18 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 35.68 | 595.54 | 02-FEB-23:30 | 2780.19 | 18-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 104.71 | 735.78 | 09-DEC-02:10 | 5865.51 | 26-JUL-18:50 |
LowTempRefrigeration:Refrigeration:Electricity | 10.72 | 0.00 | 01-JAN-11:10 | 1029.63 | 04-AUG-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 18.02 | 507.06 | 09-DEC-02:10 | 637.09 | 14-APR-12:10 |
ElectricityPurchased:Facility | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
ElectricityPurchased:Plant | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
Cogeneration:ElectricityPurchased | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
General:Cogeneration:ElectricityPurchased | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
ElectricityNet:Plant | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
Cogeneration:ElectricityNet | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
General:Cogeneration:ElectricityNet | 775.79 | 4175.05 | 02-FEB-04:00 | 65707.69 | 04-AUG-12:00 |
Electricity:HVAC | 159.40 | 0.00 | 01-JAN-01:10 | 37771.39 | 04-AUG-13:00 |
Fans:Electricity | 89.35 | 0.00 | 01-JAN-01:10 | 5820.11 | 04-AUG-13:00 |
General:Fans:Electricity | 89.35 | 0.00 | 01-JAN-01:10 | 5820.11 | 04-AUG-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 70.05 | 0.00 | 01-JAN-00:10 | 31951.28 | 04-AUG-13:00 |
General:Cooling:Electricity | 70.05 | 0.00 | 01-JAN-00:10 | 31951.28 | 04-AUG-13:00 |
ExteriorLights:Electricity | 25.61 | 0.00 | 01-JAN-08:00 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.61 | 0.00 | 01-JAN-08:00 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.29 | 31-OCT-18:30 |
Water Heater:WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.29 | 31-OCT-18:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 18-MAR-23:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 18-MAR-23:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1729.48 | 2758.01 | 20-MAR-00:10 | 262904.71 | 02-FEB-07:50 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 863.76 | 0.00 | 01-JAN-01:10 | 217160.98 | 02-FEB-07:10 |
Heating:NaturalGas | 863.76 | 0.00 | 01-JAN-01:10 | 217160.98 | 02-FEB-07:10 |
General:Heating:NaturalGas | 863.76 | 0.00 | 01-JAN-01:10 | 217160.98 | 02-FEB-07:10 |
NaturalGas:Plant | 395.93 | 947.76 | 01-JAN-00:10 | 35942.85 | 22-FEB-07:20 |
WaterSystems:NaturalGas | 395.93 | 947.76 | 01-JAN-00:10 | 35942.85 | 22-FEB-07:20 |
Water Heater:WaterSystems:NaturalGas | 395.93 | 947.76 | 01-JAN-00:10 | 35942.85 | 22-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 26-APR-07:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 26-APR-07:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1931.80 | 2892.61 | 09-DEC-02:10 | 217645.26 | 31-JAN-04:20 |
EnergyTransfer:Building | 622.14 | 1446.31 | 09-DEC-02:10 | 65118.58 | 31-JAN-04:20 |
EnergyTransfer:Zone:KITCHEN | 378.97 | 1446.31 | 09-DEC-02:10 | 21617.67 | 27-JUL-11:00 |
Refrigeration:EnergyTransfer | 135.01 | 2620.87 | 02-FEB-23:10 | 7834.84 | 12-MAY-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 67.50 | 1310.44 | 02-FEB-23:10 | 3917.42 | 12-MAY-10:40 |
General:Refrigeration:EnergyTransfer | 67.50 | 1310.44 | 02-FEB-23:10 | 3917.42 | 12-MAY-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 67.50 | 1310.44 | 02-FEB-23:10 | 3917.42 | 12-MAY-10:40 |
EnergyTransfer:Plant | 350.90 | 1446.31 | 09-DEC-02:10 | 21700.31 | 23-MAR-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.00 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.51 | 1290.76 | 09-DEC-02:10 | 2238.70 | 14-APR-12:10 |
EnergyTransfer:Zone:DINING | 243.17 | 0.00 | 01-JAN-01:10 | 61942.48 | 04-FEB-04:20 |
Heating:EnergyTransfer | 14.78 | 0.00 | 01-JAN-00:20 | 36181.02 | 04-FEB-04:30 |
Heating:EnergyTransfer:Zone:DINING | 14.75 | 0.00 | 01-JAN-00:20 | 36181.02 | 04-FEB-04:30 |
General:Heating:EnergyTransfer | 14.78 | 0.00 | 01-JAN-00:20 | 36181.02 | 04-FEB-04:30 |
General:Heating:EnergyTransfer:Zone:DINING | 14.75 | 0.00 | 01-JAN-00:20 | 36181.02 | 04-FEB-04:30 |
Cooling:EnergyTransfer | 539.85 | 0.00 | 01-JAN-01:10 | 42652.78 | 07-SEP-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 228.42 | 0.00 | 01-JAN-01:10 | 26989.97 | 04-AUG-12:00 |
General:Cooling:EnergyTransfer | 539.85 | 0.00 | 01-JAN-01:10 | 42652.78 | 07-SEP-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 228.42 | 0.00 | 01-JAN-01:10 | 26989.97 | 04-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 2773.16 | 09-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 2773.16 | 09-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 311.43 | 0.00 | 01-JAN-01:10 | 18649.46 | 31-OCT-17:20 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 311.43 | 0.00 | 01-JAN-01:10 | 18649.46 | 31-OCT-17:20 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 283.40 | 0.00 | 01-JAN-01:10 | 19651.92 | 21-FEB-19:20 |
PlantLoopHeatingDemand:Plant | 283.40 | 0.00 | 01-JAN-01:10 | 19651.92 | 21-FEB-19:20 |
WaterSystems:PlantLoopHeatingDemand | 283.40 | 0.00 | 01-JAN-01:10 | 19651.92 | 21-FEB-19:20 |
General:WaterSystems:PlantLoopHeatingDemand | 283.40 | 0.00 | 01-JAN-01:10 | 19651.92 | 21-FEB-19:20 |
EnergyTransfer:HVAC | 958.76 | 0.00 | 01-JAN-01:10 | 173728.78 | 02-FEB-07:10 |
HeatingCoils:EnergyTransfer | 691.01 | 0.00 | 01-JAN-01:10 | 173728.78 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 267.76 | 0.00 | 01-JAN-00:10 | 126614.23 | 04-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 283.40 | 0.00 | 01-JAN-01:10 | 19651.92 | 21-FEB-19:20 |
WaterUse:WaterSystems:EnergyTransfer | 283.40 | 0.00 | 01-JAN-01:10 | 19651.92 | 21-FEB-19:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 14.747 | -228.422 | 0.000 | 0.000 | 230.767 | 26.754 | 93.832 | 41.165 | 0.000 | 1.568 | 0.004 | 0.000 | -27.612 | 0.000 | -90.995 | -61.805 |
KITCHEN | 0.000 | 0.000 | 0.037 | -311.417 | 0.000 | 0.000 | 6.123 | 16.725 | 273.146 | 0.000 | 0.000 | 0.017 | 20.520 | 0.000 | 0.000 | 0.000 | -5.149 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.545 | 27.536 | 0.000 | 0.000 | 0.000 | -33.081 | -0.001 |
Total Facility | 0.000 | 0.000 | 14.783 | -539.839 | 0.000 | 0.000 | 236.890 | 43.479 | 366.978 | 41.165 | 0.000 | 7.130 | 48.059 | 0.000 | -27.612 | 0.000 | -129.225 | -61.807 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-FEB-00:01 | 0.00 | 0.00 | 0.00 | -76355.39 | 0.00 | 0.00 | 1157.79 | 337.32 | 540.00 | 0.00 | 0.00 | 0.00 | 80827.54 | 0.00 | -4299.17 | 0.00 | -2208.09 | 0.00 |
KITCHEN | 01-JUN-03:01 | 0.00 | 0.00 | 0.00 | -52727.85 | 0.00 | 0.00 | 0.00 | 30.01 | 3035.94 | 0.00 | 0.00 | 0.00 | 49854.71 | 0.00 | -0.00 | 0.00 | -192.81 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-SEP-03:01 | 0.00 | 0.00 | 0.00 | -103765.51 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 359.79 | 100721.30 | 0.00 | -1032.13 | 0.00 | -329.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 01-MAR-04:01 | 0.00 | 0.00 | 107429.66 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1901.62 | 0.00 | -1422.26 | -105085.82 |
KITCHEN | 09-FEB-05:04 | 0.00 | 0.00 | 27704.41 | 0.00 | 0.00 | 0.00 | 26.20 | 30.01 | 6476.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -82.20 | -34154.46 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-MAR-04:01 | 0.00 | 0.00 | 107429.66 | 0.00 | 0.00 | 0.00 | 0.00 | 110.04 | 3935.95 | 0.00 | 0.00 | 542.57 | 0.00 | 0.00 | -1901.62 | 0.00 | -2339.19 | -107777.41 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.5029 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.5030 | 0.3801 | 1.0000 | Not calculated | 1.3314 | 0.3801 | ||
PSZ-AC_2:2 | 1.4957 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.4957 | 0.1221 | 1.0000 | Not calculated | 0.1826 | 0.1221 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.5029 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.5029 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3801 | ||
PSZ-AC_2:2 | 1.4957 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.4957 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1221 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5029 | 3.5029 | 3.5029 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4957 | 1.4957 | 1.4957 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.5029 | 3.5030 | 3.5029 | 3.5029 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.4957 | 1.4957 | 1.4957 | 1.4957 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5029 | 3.5029 | 3.5029 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4957 | 1.4957 | 1.4957 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.5029 | 3.5029 | 3.5029 | 3.5029 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.4957 | 1.4957 | 1.4957 | 1.4957 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 21.83 |
Number of hours not met | 21.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 863.76 | 217160.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 70.05 | 31951.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 43.48 | 2883.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.61 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 89.35 | 5820.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.52 | 4742.29 | 395.93 | 35942.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.72 | 1029.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 18.02 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 471.34 | 775.79 |
Natural Gas | 469.79 | 1729.48 |
Additional | 0.00 | 0.00 |
Total | 941.13 | 2505.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 85.06 |
Space Heating | 0.00 |
Space Cooling | 137.03 |
Fans (All) | 174.80 |
Service Water Heating | 147.74 |
Receptacle Equipment | 852.31 |
Miscellaneous (All) | 1517.72 |
Subtotal | 1517.72 |
Natural Gas [MJ/m2] | |
Space Heating | 1689.82 |
Service Water Heating | 774.59 |
Miscellaneous (All) | 3383.49 |
Subtotal | 3383.49 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.74 |
Space Heating | 34.48 |
Space Cooling | 2.80 |
Fans (All) | 3.57 |
Service Water Heating | 18.82 |
Receptacle Equipment | 36.14 |
Miscellaneous | 2.46 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8274.83 | 471.67 | 13.50 | 0.00 | 0.00 |
ATTIC | 7434.67 | 430.83 | 398.83 | 403.17 | 92.50 |
Min | 7434.67 | 7.50 | 0.00 | 0.00 | 0.00 |
Max | 8752.50 | 471.67 | 398.83 | 403.17 | 92.50 |
Average | 8154.00 | 303.33 | 137.44 | 134.39 | 30.83 |
Sum | 24462.00 | 910.00 | 412.33 | 403.17 | 92.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19133.67 | 99.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 99.33 | 0.00 | 0.00 | 0.00 |
Average | 281118.56 | 33.11 | 0.00 | 0.00 | 0.00 |
Sum | 843355.67 | 99.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7887.50 | 872.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6219.00 | 2540.50 | 0.50 | 0.00 | 0.00 |
ATTIC | 7324.17 | 775.33 | 244.00 | 203.17 | 213.33 |
Min | 6219.00 | 775.33 | 0.00 | 0.00 | 0.00 |
Max | 7887.50 | 2540.50 | 244.00 | 203.17 | 213.33 |
Average | 7143.56 | 1396.11 | 81.50 | 67.72 | 71.11 |
Sum | 21430.67 | 4188.33 | 244.50 | 203.17 | 213.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 743957.67 | 80264.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 13288.00 | 5945.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 743957.67 | 80264.33 | 0.00 | 0.00 | 0.00 |
Average | 252415.22 | 28736.44 | 0.00 | 0.00 | 0.00 |
Sum | 757245.67 | 86209.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451971E+10 | 70780.39 | 31-JAN-00:01 | -29.1 | -29.3 | 0.119975E+11 | 10741.01 | 14-JAN-19:40 | -29.1 | -29.3 |
February | 0.746883E+10 | 76357.37 | 02-FEB-00:01 | -33.0 | -33.1 | 0.108638E+11 | 10740.96 | 25-FEB-19:10 | 1.60 | -0.2 |
March | 0.128617E+11 | 52353.71 | 06-MAR-00:01 | -16.3 | -16.8 | 0.122824E+11 | 13359.78 | 25-MAR-18:19 | 14.63 | 10.09 |
April | 0.177336E+11 | 38232.05 | 16-APR-03:01 | 19.32 | 16.48 | 0.123613E+11 | 14051.43 | 15-APR-18:10 | 19.32 | 16.48 |
May | 0.240480E+11 | 41814.14 | 31-MAY-03:01 | 16.70 | 15.32 | 0.141526E+11 | 14050.55 | 06-MAY-18:19 | 16.70 | 15.32 |
June | 0.284332E+11 | 59222.12 | 28-JUN-03:01 | 18.22 | 16.15 | 0.144428E+11 | 14051.47 | 17-JUN-18:00 | 18.22 | 16.15 |
July | 0.311973E+11 | 59475.00 | 01-JUL-03:01 | 15.83 | 14.40 | 0.152239E+11 | 14051.42 | 15-JUL-18:00 | 21.70 | 18.33 |
August | 0.313613E+11 | 55187.97 | 22-AUG-03:01 | 16.70 | 16.39 | 0.153396E+11 | 14051.52 | 05-AUG-18:00 | 16.70 | 16.39 |
September | 0.279949E+11 | 65291.60 | 09-SEP-03:01 | 14.90 | 13.95 | 0.137759E+11 | 14051.34 | 16-SEP-18:10 | 25.13 | 17.26 |
October | 0.220850E+11 | 30371.11 | 18-OCT-23:01 | -0.8 | -2.1 | 0.125632E+11 | 13759.39 | 21-OCT-18:00 | 13.90 | 10.64 |
November | 0.136351E+11 | 64105.29 | 26-NOV-00:01 | -24.4 | -24.8 | 0.117593E+11 | 12795.99 | 03-NOV-11:00 | -24.4 | -24.8 |
December | 0.708562E+10 | 61573.68 | 09-DEC-00:01 | -22.8 | -23.0 | 0.119922E+11 | 10740.93 | 02-DEC-19:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.228424E+12 | 0.156755E+12 | ||||||||
Minimum of Months | 0.451971E+10 | 30371.11 | -33.0 | -33.1 | 0.108638E+11 | 10740.93 | -29.1 | -29.3 | ||
Maximum of Months | 0.313613E+11 | 76357.37 | 19.32 | 16.48 | 0.153396E+11 | 14051.52 | 25.13 | 18.33 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230173E+11 | 52412.71 | 06-JAN-05:01 | -26.7 | -26.9 | 0.103883E+11 | 6815.12 | 05-JAN-11:00 | -26.7 | -26.9 |
February | 0.215290E+11 | 41738.76 | 16-FEB-05:01 | -17.3 | -17.7 | 0.938377E+10 | 6827.37 | 24-FEB-11:00 | 6.10 | 3.16 |
March | 0.250862E+11 | 40314.11 | 08-MAR-05:01 | -14.7 | -15.0 | 0.104103E+11 | 6874.66 | 28-MAR-10:00 | 12.80 | 7.63 |
April | 0.248997E+11 | 42669.75 | 17-APR-03:01 | 13.22 | 11.90 | 0.101145E+11 | 6930.39 | 17-APR-10:00 | 15.60 | 11.49 |
May | 0.262746E+11 | 44536.37 | 06-MAY-03:01 | 8.90 | 6.83 | 0.105500E+11 | 6930.46 | 16-MAY-10:00 | 18.30 | 16.16 |
June | 0.270136E+11 | 52811.82 | 01-JUN-03:01 | 7.60 | 7.55 | 0.102396E+11 | 6933.89 | 30-JUN-10:00 | 28.30 | 23.10 |
July | 0.285613E+11 | 48664.14 | 24-JUL-03:01 | 10.00 | 9.40 | 0.105927E+11 | 6934.78 | 03-JUL-10:00 | 10.00 | 9.40 |
August | 0.288123E+11 | 47169.87 | 08-AUG-03:01 | 12.02 | 9.91 | 0.105969E+11 | 6972.41 | 04-AUG-10:00 | 12.02 | 9.91 |
September | 0.277818E+11 | 51480.99 | 05-SEP-03:01 | 7.80 | 7.19 | 0.102093E+11 | 6930.46 | 12-SEP-10:00 | 16.10 | 15.06 |
October | 0.280967E+11 | 46284.54 | 22-OCT-03:01 | 10.98 | 7.68 | 0.104545E+11 | 6930.39 | 20-OCT-10:00 | 10.98 | 7.68 |
November | 0.257009E+11 | 48017.22 | 28-NOV-05:01 | -21.1 | -21.4 | 0.100812E+11 | 6922.40 | 08-NOV-11:50 | -21.1 | -21.4 |
December | 0.246539E+11 | 45436.20 | 12-DEC-05:01 | -20.0 | -20.3 | 0.103883E+11 | 6815.12 | 28-DEC-11:50 | -7.6 | -8.3 |
Annual Sum or Average | 0.311427E+12 | 0.123409E+12 | ||||||||
Minimum of Months | 0.215290E+11 | 40314.11 | -26.7 | -26.9 | 0.938377E+10 | 6815.12 | -26.7 | -26.9 | ||
Maximum of Months | 0.288123E+11 | 52811.82 | 13.22 | 11.90 | 0.105969E+11 | 6972.41 | 28.30 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -12.0 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -12.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 | -2.2 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 | 5.15 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 | 10.69 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 | 15.94 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 | 1.39 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 | -0.5 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.563414E+10 | 97365.61 | 08-JAN-04:01 | -12.2 |
February | 0.377058E+10 | 100894.46 | 13-FEB-04:01 | -5.5 |
March | 0.981089E+09 | 107428.59 | 01-MAR-04:01 | -4.4 |
April | 0.375607E+09 | 104988.08 | 03-APR-03:01 | -6.2 |
May | 11455334.81 | 18069.30 | 02-MAY-03:02 | 2.80 |
June | 869100.48 | 7254.87 | 04-JUN-04:03 | 7.70 |
July | 989255.62 | 1934.20 | 25-JUL-23:03 | 25.00 |
August | 254379.96 | 1025.35 | 02-AUG-23:03 | 24.40 |
September | 9238240.20 | 19875.15 | 30-SEP-04:01 | -0.5 |
October | 42994677.32 | 23035.24 | 08-OCT-04:01 | -0.6 |
November | 0.109432E+10 | 99165.53 | 27-NOV-04:01 | -10.4 |
December | 0.282534E+10 | 98253.00 | 13-DEC-04:01 | -11.6 |
Annual Sum or Average | 0.147469E+11 | |||
Minimum of Months | 254379.96 | 1025.35 | -12.2 | |
Maximum of Months | 0.563414E+10 | 107428.59 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13537078.27 | 18170.71 | 06-JAN-05:02 | -26.7 |
February | 6965889.54 | 27731.65 | 09-FEB-05:04 | -3.9 |
March | 2923972.81 | 10606.76 | 15-MAR-04:03 | -6.2 |
April | 553009.59 | 6846.67 | 06-APR-04:03 | -5.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 195229.95 | 2644.52 | 28-OCT-04:04 | -1.7 |
November | 4671736.45 | 11289.92 | 12-NOV-05:03 | -9.3 |
December | 7724743.45 | 10494.87 | 23-DEC-05:03 | -6.7 |
Annual Sum or Average | 36571660.06 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 13537078.27 | 27731.65 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250844E+10 | 2023.86 | 02-JAN-16:40 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.218204E+10 | 2023.86 | 01-FEB-17:19 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.229628E+10 | 2023.86 | 01-MAR-17:00 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.209907E+10 | 2023.86 | 01-APR-18:40 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.207173E+10 | 2023.86 | 01-MAY-19:10 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.199164E+10 | 2023.86 | 01-JUN-19:40 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.202863E+10 | 2023.86 | 01-JUL-19:00 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.212855E+10 | 2023.86 | 01-AUG-19:40 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.214755E+10 | 2023.86 | 01-SEP-18:49 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.231758E+10 | 2023.86 | 02-OCT-17:49 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.241051E+10 | 2023.86 | 01-NOV-16:00 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.257228E+10 | 2023.86 | 01-DEC-16:30 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.267543E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.199164E+10 | 2023.86 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.257228E+10 | 2023.86 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141271E+10 | 859.87 | 02-JAN-10:09 | 0.263757E+11 | 16905.18 | 01-JAN-11:09 |
February | 0.127972E+10 | 859.87 | 01-FEB-10:09 | 0.238233E+11 | 16905.18 | 01-FEB-11:09 |
March | 0.143703E+10 | 859.87 | 01-MAR-10:09 | 0.263759E+11 | 16905.18 | 01-MAR-11:09 |
April | 0.137275E+10 | 859.87 | 01-APR-16:10 | 0.255250E+11 | 16905.18 | 01-APR-10:09 |
May | 0.142487E+10 | 859.87 | 01-MAY-09:09 | 0.263758E+11 | 16905.18 | 01-MAY-10:09 |
June | 0.138882E+10 | 859.87 | 01-JUN-09:09 | 0.255251E+11 | 16905.18 | 01-JUN-10:09 |
July | 0.140898E+10 | 859.87 | 01-JUL-16:10 | 0.263757E+11 | 16905.18 | 01-JUL-10:09 |
August | 0.143703E+10 | 859.87 | 01-AUG-09:09 | 0.263759E+11 | 16905.18 | 01-AUG-10:09 |
September | 0.137310E+10 | 859.87 | 01-SEP-09:09 | 0.255250E+11 | 16905.18 | 01-SEP-10:09 |
October | 0.141254E+10 | 859.87 | 02-OCT-09:09 | 0.263757E+11 | 16905.18 | 01-OCT-10:09 |
November | 0.136789E+10 | 859.87 | 01-NOV-09:09 | 0.255249E+11 | 16905.18 | 01-NOV-10:09 |
December | 0.140915E+10 | 859.87 | 01-DEC-10:09 | 0.263757E+11 | 16905.18 | 01-DEC-11:09 |
Annual Sum or Average | 0.167246E+11 | 0.310554E+12 | ||||
Minimum of Months | 0.127972E+10 | 859.87 | 0.238233E+11 | 16905.18 | ||
Maximum of Months | 0.143703E+10 | 859.87 | 0.263759E+11 | 16905.18 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.250844E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177926E+11 |
February | 0.272721E+11 | 0.218204E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134842E+11 |
March | 0.305458E+11 | 0.229628E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103284E+11 |
April | 0.292871E+11 | 0.209907E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69108246.88 | 0.670148E+10 |
May | 0.303219E+11 | 0.207173E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69480449.96 | 0.357609E+10 |
June | 0.295292E+11 | 0.199164E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467226E+09 | 0.180580E+10 |
July | 0.300798E+11 | 0.202863E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348612E+09 | 0.110040E+10 |
August | 0.305458E+11 | 0.212855E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360993E+09 | 0.144328E+10 |
September | 0.292871E+11 | 0.214755E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252281E+09 | 0.316666E+10 |
October | 0.300980E+11 | 0.231758E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647138E+10 |
November | 0.290996E+11 | 0.241051E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102999E+11 |
December | 0.300798E+11 | 0.257228E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148245E+11 |
Annual Sum or Average | 0.356244E+12 | 0.267543E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156770E+10 | 0.909947E+11 |
Minimum of Months | 0.272721E+11 | 0.199164E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110040E+10 |
Maximum of Months | 0.305458E+11 | 0.257228E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467226E+09 | 0.177926E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.141271E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884483E+09 |
February | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677924E+09 |
March | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593080E+09 |
April | 0.786997E+09 | 0.137275E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1636340.71 | 0.380254E+09 |
May | 0.814802E+09 | 0.142487E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 594578.69 | 0.239149E+09 |
June | 0.793501E+09 | 0.138882E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 6807803.27 | 0.154772E+09 |
July | 0.808298E+09 | 0.140898E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2172259.42 | 0.118231E+09 |
August | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2900578.06 | 0.156358E+09 |
September | 0.786997E+09 | 0.137310E+10 | 0.207263E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2611357.81 | 0.216067E+09 |
October | 0.808786E+09 | 0.141254E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358211E+09 |
November | 0.781956E+09 | 0.136789E+10 | 0.207262E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594635E+09 |
December | 0.808298E+09 | 0.140915E+10 | 0.214171E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775996E+09 |
Annual Sum or Average | 0.957291E+10 | 0.167246E+11 | 0.252169E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 16722917.97 | 0.514916E+10 |
Minimum of Months | 0.732850E+09 | 0.127972E+10 | 0.193445E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118231E+09 |
Maximum of Months | 0.820818E+09 | 0.143703E+10 | 0.214172E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 6807803.27 | 0.884483E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405979E+09 | 0.160425E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424221E+09 | 0.176006E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406267E+09 | 0.237550E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370938E+09 | 0.328111E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373197E+09 | 0.410658E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418228E+09 | 0.441010E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571269E+09 | 0.478242E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423037E+09 | 0.385730E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633610E+09 | 0.273454E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601793E+09 | 0.193898E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470550E+09 | 0.125686E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446259E+09 | 0.973597E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554535E+10 | 0.330813E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370938E+09 | 0.973597E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633610E+09 | 0.478242E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2023.86 | 02-JAN-16:40 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 22259.34 | 30-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2023.86 | 01-FEB-17:19 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 24942.79 | 02-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 2023.86 | 01-MAR-17:00 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 13933.55 | 05-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2023.86 | 01-APR-18:40 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.62 | 15-APR-17:03 | 10567.34 | 03-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 2023.86 | 01-MAY-19:10 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1969.25 | 31-MAY-12:00 | 7005.83 | 01-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 2023.86 | 01-JUN-19:40 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2539.12 | 26-JUN-17:03 | 5391.55 | 01-JUN-17:52 |
July | 30255.31 | 01-JUL-18:10 | 2023.86 | 01-JUL-19:00 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1969.82 | 26-JUL-17:53 | 3249.79 | 10-JUL-12:00 |
August | 30255.31 | 05-AUG-18:10 | 2023.86 | 01-AUG-19:40 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2585.68 | 04-AUG-11:53 | 3629.26 | 06-AUG-19:53 |
September | 30255.31 | 02-SEP-18:10 | 2023.86 | 01-SEP-18:49 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2450.60 | 07-SEP-13:00 | 7132.34 | 29-SEP-19:55 |
October | 30255.31 | 07-OCT-18:10 | 2023.86 | 02-OCT-17:49 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 8839.06 | 31-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2023.86 | 01-NOV-16:00 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 21285.05 | 25-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 2023.86 | 01-DEC-16:30 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 20449.47 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2023.86 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3249.79 | |||||
Maximum of Months | 30255.31 | 2023.86 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2585.68 | 24942.79 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 859.87 | 02-JAN-10:09 | 13642.30 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2457.02 | 19-JAN-00:01 |
February | 813.01 | 04-FEB-19:10 | 859.87 | 01-FEB-10:09 | 13642.30 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1592.31 | 05-FEB-00:10 |
March | 813.01 | 04-MAR-19:10 | 859.87 | 01-MAR-10:09 | 13642.30 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1483.69 | 21-MAR-03:10 |
April | 813.01 | 01-APR-18:10 | 859.87 | 01-APR-16:10 | 13642.30 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 50.45 | 15-APR-15:00 | 1181.58 | 03-APR-00:10 |
May | 813.01 | 06-MAY-18:10 | 859.87 | 01-MAY-09:09 | 13642.30 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 22.65 | 31-MAY-12:55 | 832.24 | 02-MAY-03:10 |
June | 813.01 | 03-JUN-18:10 | 859.87 | 01-JUN-09:09 | 13642.30 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 66.18 | 18-JUN-16:00 | 577.61 | 19-JUN-01:00 |
July | 813.01 | 01-JUL-18:10 | 859.87 | 01-JUL-16:10 | 13642.30 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.78 | 25-JUL-15:55 | 412.80 | 25-JUL-03:10 |
August | 813.01 | 05-AUG-18:10 | 859.87 | 01-AUG-09:09 | 13642.30 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 28.55 | 03-AUG-16:00 | 414.24 | 19-AUG-02:00 |
September | 813.01 | 02-SEP-18:10 | 859.87 | 01-SEP-09:09 | 13642.30 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 35.15 | 06-SEP-14:00 | 514.48 | 19-SEP-02:00 |
October | 813.01 | 07-OCT-18:10 | 859.87 | 02-OCT-09:09 | 13642.30 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 928.87 | 24-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 859.87 | 01-NOV-09:09 | 13642.30 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1748.83 | 21-NOV-01:10 |
December | 813.01 | 02-DEC-19:10 | 859.87 | 01-DEC-10:09 | 13642.30 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3049.35 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 412.80 | ||||||
Maximum of Months | 813.01 | 859.87 | 13642.30 | 7874.59 | 0.00 | 0.00 | 0.00 | 66.18 | 3049.35 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1060.13 | 25-JAN-04:55 | 5201.64 | 30-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.84 | 21-FEB-05:50 | 4977.65 | 03-FEB-14:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.50 | 22-MAR-01:00 | 5288.82 | 13-MAR-11:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.08 | 05-APR-23:10 | 8514.66 | 26-APR-13:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.31 | 03-MAY-02:00 | 8418.28 | 21-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.78 | 07-JUN-23:00 | 8201.94 | 09-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.40 | 23-JUL-23:00 | 8055.42 | 05-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.71 | 05-AUG-05:00 | 6766.94 | 16-AUG-13:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1834.54 | 08-SEP-03:51 | 6637.37 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.59 | 31-OCT-07:05 | 5507.00 | 23-OCT-13:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1325.87 | 28-NOV-06:00 | 4362.12 | 12-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.76 | 04-DEC-07:55 | 3446.66 | 07-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.76 | 3446.66 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1834.54 | 8514.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 70780.39 | 31-JAN-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.13 |
February | 76357.37 | 02-FEB-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2208.09 |
March | 52353.71 | 06-MAR-00:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.98 |
April | 38232.05 | 16-APR-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.65 |
May | 41814.14 | 31-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.78 |
June | 59222.12 | 28-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.70 |
July | 59475.00 | 01-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.15 |
August | 55187.97 | 22-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.44 |
September | 65291.60 | 09-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.40 |
October | 30371.11 | 18-OCT-23:01 | 16808.50 | 3373.19 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.28 |
November | 64105.29 | 26-NOV-00:01 | 16808.50 | 4497.58 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.07 |
December | 61573.68 | 09-DEC-00:01 | 16808.50 | 4497.58 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3994.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 30371.11 | 0.00 | 800.29 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.70 | |
Maximum of Months | 76357.37 | 16808.50 | 4497.58 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3994.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 52412.71 | 06-JAN-05:01 | 406.51 | 270.10 | 53922.80 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 185.90 |
February | 41738.76 | 16-FEB-05:01 | 361.34 | 240.09 | 47931.38 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 161.32 |
March | 40314.11 | 08-MAR-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 |
April | 42669.75 | 17-APR-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 310.95 |
May | 44536.37 | 06-MAY-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 311.49 |
June | 52811.82 | 01-JUN-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 192.81 |
July | 48664.14 | 24-JUL-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 208.81 |
August | 47169.87 | 08-AUG-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 244.67 |
September | 51480.99 | 05-SEP-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 228.44 |
October | 46284.54 | 22-OCT-03:01 | 0.00 | 300.11 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 348.89 |
November | 48017.22 | 28-NOV-05:01 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 |
December | 45436.20 | 12-DEC-05:01 | 406.51 | 270.10 | 53922.80 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 226.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 40314.11 | 0.00 | 240.09 | 28308.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | |
Maximum of Months | 52811.82 | 451.67 | 300.11 | 59914.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 348.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.65 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.02 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.58 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.59 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.16 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.29 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.53 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.60 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.53 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.65 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.65 | 157.02 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.621576E+11 | 36746.01 | 30-JAN-11:09 | 0.308031E+12 | 232931.52 | 31-JAN-07:10 |
February | 0.553214E+11 | 36939.15 | 02-FEB-11:09 | 0.231478E+12 | 262904.71 | 02-FEB-07:49 |
March | 0.600662E+11 | 35868.58 | 04-MAR-11:09 | 0.176951E+12 | 192153.04 | 06-MAR-04:19 |
April | 0.592524E+11 | 51187.17 | 18-APR-10:50 | 0.122243E+12 | 129000.18 | 03-APR-06:19 |
May | 0.627691E+11 | 51050.72 | 31-MAY-10:00 | 0.808168E+11 | 85126.53 | 02-MAY-06:19 |
June | 0.723386E+11 | 57490.34 | 30-JUN-11:09 | 0.714755E+11 | 56052.44 | 02-JUN-06:49 |
July | 0.796648E+11 | 62240.56 | 26-JUL-17:00 | 0.701213E+11 | 46553.67 | 03-JUL-18:30 |
August | 0.782193E+11 | 65707.69 | 04-AUG-11:00 | 0.698454E+11 | 44606.36 | 01-AUG-18:00 |
September | 0.656445E+11 | 53219.93 | 11-SEP-10:00 | 0.747621E+11 | 84111.03 | 29-SEP-06:40 |
October | 0.598345E+11 | 37347.51 | 20-OCT-17:19 | 0.103367E+12 | 94246.35 | 23-OCT-06:49 |
November | 0.588148E+11 | 36260.85 | 26-NOV-11:09 | 0.170043E+12 | 207192.07 | 26-NOV-07:10 |
December | 0.617043E+11 | 36561.70 | 09-DEC-11:20 | 0.250347E+12 | 204998.75 | 12-DEC-04:19 |
Annual Sum or Average | 0.775788E+12 | 0.172948E+13 | ||||
Minimum of Months | 0.553214E+11 | 35868.58 | 0.698454E+11 | 44606.36 | ||
Maximum of Months | 0.796648E+11 | 65707.69 | 0.308031E+12 | 262904.71 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.392115E+10 | 0.288292E+10 | 0.370015E+11 | 0.00 | 0.909759E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639943E+10 | 0.00 |
February | 0.346176E+10 | 0.234690E+10 | 0.334207E+11 | 0.00 | 0.771096E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579163E+10 | 0.00 |
March | 0.373331E+10 | 0.224271E+10 | 0.370017E+11 | 0.00 | 0.770004E+10 | 37879553.69 | 0.00 | 4241797.32 | 0.00 | 0.00 | 0.00 | 0.646625E+10 | 0.00 |
April | 0.347183E+10 | 0.180592E+10 | 0.358080E+11 | 0.00 | 0.697680E+10 | 36657632.61 | 0.00 | 0.207302E+10 | 0.00 | 0.00 | 0.00 | 0.620658E+10 | 0.00 |
May | 0.349660E+10 | 0.158151E+10 | 0.370016E+11 | 0.00 | 0.679664E+10 | 37879553.69 | 0.00 | 0.427240E+10 | 0.00 | 0.00 | 0.00 | 0.642053E+10 | 0.00 |
June | 0.338046E+10 | 0.140386E+10 | 0.358081E+11 | 0.00 | 0.689274E+10 | 36657632.61 | 0.00 | 0.154376E+11 | 0.00 | 0.00 | 0.00 | 0.623848E+10 | 0.00 |
July | 0.343760E+10 | 0.149110E+10 | 0.370015E+11 | 0.00 | 0.726657E+10 | 37879553.69 | 0.00 | 0.207758E+11 | 0.00 | 0.00 | 0.00 | 0.637201E+10 | 0.00 |
August | 0.356558E+10 | 0.172603E+10 | 0.370017E+11 | 0.00 | 0.721097E+10 | 37879553.69 | 0.00 | 0.189476E+11 | 0.00 | 0.00 | 0.00 | 0.645054E+10 | 0.00 |
September | 0.352065E+10 | 0.200781E+10 | 0.358080E+11 | 0.00 | 0.669577E+10 | 36657632.61 | 0.00 | 0.830580E+10 | 0.00 | 0.00 | 0.00 | 0.619923E+10 | 0.00 |
October | 0.373012E+10 | 0.245125E+10 | 0.370015E+11 | 0.00 | 0.701419E+10 | 37879553.69 | 0.00 | 0.225957E+09 | 0.00 | 0.00 | 0.00 | 0.639171E+10 | 0.00 |
November | 0.377840E+10 | 0.269716E+10 | 0.358078E+11 | 0.00 | 0.749543E+10 | 36657632.61 | 0.00 | 3098535.86 | 0.00 | 0.00 | 0.00 | 0.619040E+10 | 0.00 |
December | 0.398143E+10 | 0.297191E+10 | 0.370015E+11 | 0.00 | 0.849358E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639120E+10 | 0.00 |
Annual Sum or Average | 0.434789E+11 | 0.256091E+11 | 0.435663E+12 | 0.00 | 0.893513E+11 | 0.446001E+09 | 0.00 | 0.700455E+11 | 0.00 | 0.00 | 0.00 | 0.755180E+11 | 0.00 |
Minimum of Months | 0.338046E+10 | 0.140386E+10 | 0.334207E+11 | 0.00 | 0.669577E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579163E+10 | 0.00 |
Maximum of Months | 0.398143E+10 | 0.297191E+10 | 0.370017E+11 | 0.00 | 0.909759E+10 | 37879553.69 | 0.00 | 0.207758E+11 | 0.00 | 0.00 | 0.00 | 0.646625E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.231242E+12 | 0.00 | 0.368896E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.161446E+12 | 0.00 | 0.339944E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.994785E+11 | 0.00 | 0.375725E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.488204E+11 | 0.00 | 0.348097E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.689331E+10 | 0.00 | 0.340237E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.182032E+10 | 0.00 | 0.310425E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 77744878.51 | 0.00 | 0.301438E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.189572E+09 | 0.00 | 0.297561E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.715935E+10 | 0.00 | 0.289902E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.321838E+11 | 0.00 | 0.312833E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.992518E+11 | 0.00 | 0.321782E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.175196E+12 | 0.00 | 0.352504E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.863759E+12 | 0.00 | 0.395934E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 77744878.51 | 0.00 | 0.289902E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.231242E+12 | 0.00 | 0.375725E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2883.74 | 02-JAN-16:40 | 2213.72 | 01-JAN-06:10 | 23897.06 | 01-JAN-11:09 | 0.00 | 4904.06 | 31-JAN-07:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 2883.74 | 01-FEB-17:19 | 2213.72 | 01-FEB-06:10 | 23897.06 | 01-FEB-11:09 | 0.00 | 5186.09 | 02-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 2883.74 | 01-MAR-17:00 | 2213.72 | 01-MAR-06:10 | 23897.06 | 01-MAR-11:09 | 0.00 | 4265.99 | 05-MAR-23:30 | 17.86 | 18-MAR-23:10 | 0.00 | 01-MAR-00:10 |
April | 2883.74 | 01-APR-18:40 | 2213.72 | 01-APR-05:10 | 23897.06 | 01-APR-10:09 | 0.00 | 3927.80 | 03-APR-04:19 | 17.86 | 06-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 2883.74 | 01-MAY-19:10 | 2213.72 | 01-MAY-19:10 | 23897.06 | 01-MAY-10:09 | 0.00 | 3503.15 | 03-MAY-04:00 | 17.86 | 02-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 2883.74 | 01-JUN-19:40 | 2213.72 | 01-JUN-19:40 | 23897.06 | 01-JUN-10:09 | 0.00 | 4559.15 | 30-JUN-11:09 | 17.86 | 09-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 2883.74 | 01-JUL-19:00 | 2213.72 | 01-JUL-19:00 | 23897.06 | 01-JUL-10:09 | 0.00 | 5493.62 | 26-JUL-17:00 | 17.86 | 04-JUL-13:39 | 0.00 | 01-JUL-00:10 |
August | 2883.74 | 01-AUG-19:40 | 2213.72 | 01-AUG-19:40 | 23897.06 | 01-AUG-10:09 | 0.00 | 5820.11 | 04-AUG-12:00 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2883.74 | 01-SEP-18:49 | 2213.72 | 01-SEP-05:10 | 23897.06 | 01-SEP-10:09 | 0.00 | 3814.35 | 11-SEP-11:00 | 17.86 | 12-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 2883.74 | 02-OCT-17:49 | 2213.72 | 01-OCT-05:10 | 23897.06 | 01-OCT-10:09 | 0.00 | 3643.59 | 23-OCT-05:00 | 17.86 | 12-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 2883.74 | 01-NOV-16:00 | 2213.72 | 01-NOV-05:10 | 23897.06 | 01-NOV-10:09 | 0.00 | 4793.58 | 26-NOV-07:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2883.74 | 01-DEC-16:30 | 2213.72 | 01-DEC-06:10 | 23897.06 | 01-DEC-11:09 | 0.00 | 4592.67 | 09-DEC-05:10 | 17.86 | 01-DEC-00:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2883.74 | 2213.72 | 23897.06 | 0.00 | 3503.15 | 17.86 | 0.00 | ||||||
Maximum of Months | 2883.74 | 2213.72 | 23897.06 | 0.00 | 5820.11 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.38 | 23-JAN-19:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4741.91 | 24-FEB-07:49 | 0.00 |
March | 691.95 | 19-MAR-16:19 | 0.00 | 0.00 | 0.00 | 4741.91 | 20-MAR-18:00 | 0.00 |
April | 18460.44 | 18-APR-11:00 | 0.00 | 0.00 | 0.00 | 4741.86 | 26-APR-06:49 | 0.00 |
May | 18503.72 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4741.67 | 03-MAY-06:49 | 0.00 |
June | 24663.12 | 11-JUN-15:09 | 0.00 | 0.00 | 0.00 | 4740.48 | 01-JUN-06:10 | 0.00 |
July | 29324.75 | 26-JUL-17:00 | 0.00 | 0.00 | 0.00 | 4737.66 | 12-JUL-06:40 | 0.00 |
August | 31951.28 | 04-AUG-12:00 | 0.00 | 0.00 | 0.00 | 4739.32 | 07-AUG-06:00 | 0.00 |
September | 20373.18 | 11-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4741.39 | 20-SEP-06:40 | 0.00 |
October | 6279.72 | 20-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4742.29 | 31-OCT-18:30 | 0.00 |
November | 1814.06 | 09-NOV-04:49 | 0.00 | 0.00 | 0.00 | 4741.66 | 27-NOV-19:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4741.41 | 19-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4737.66 | 0.00 | ||
Maximum of Months | 31951.28 | 0.00 | 0.00 | 0.00 | 4742.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 36746.01 | 30-JAN-11:09 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4604.12 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 36939.15 | 02-FEB-11:09 | 1871.80 | 23897.06 | 0.00 | 0.00 | 4846.06 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 35868.58 | 04-MAR-11:09 | 1663.82 | 23897.06 | 0.00 | 0.00 | 3652.11 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 51187.17 | 18-APR-10:50 | 1871.80 | 23897.06 | 0.00 | 0.00 | 3428.81 | 17.86 | 0.00 | 16601.05 | 0.00 |
May | 51050.72 | 31-MAY-10:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 3392.32 | 17.86 | 0.00 | 16509.63 | 0.00 |
June | 57490.34 | 30-JUN-11:09 | 1871.80 | 22289.73 | 0.00 | 0.00 | 4559.15 | 17.86 | 0.00 | 24239.79 | 0.00 |
July | 62240.56 | 26-JUL-17:00 | 1871.80 | 19878.74 | 0.00 | 0.00 | 5493.62 | 17.86 | 0.00 | 29324.75 | 0.00 |
August | 65707.69 | 04-AUG-11:00 | 1871.80 | 22289.73 | 0.00 | 0.00 | 5787.49 | 17.86 | 0.00 | 31523.54 | 0.00 |
September | 53219.93 | 11-SEP-10:00 | 1871.80 | 23897.06 | 0.00 | 0.00 | 3597.51 | 17.86 | 0.00 | 18478.84 | 0.00 |
October | 37347.51 | 20-OCT-17:19 | 2883.74 | 19878.74 | 2213.72 | 0.00 | 2963.64 | 17.86 | 0.00 | 3803.03 | 0.00 |
November | 36260.85 | 26-NOV-11:09 | 1455.85 | 23897.06 | 0.00 | 0.00 | 4200.25 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 36561.70 | 09-DEC-11:20 | 1663.82 | 23897.06 | 0.00 | 0.00 | 4417.17 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 35868.58 | 1455.85 | 19878.74 | 0.00 | 0.00 | 2963.64 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65707.69 | 2883.74 | 23897.06 | 2213.72 | 0.00 | 5787.49 | 17.86 | 0.00 | 31523.54 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 189532.90 | 31-JAN-07:10 | 0.00 | 35691.23 | 31-JAN-19:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 217160.98 | 02-FEB-07:10 | 0.00 | 35942.85 | 22-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 186679.65 | 06-MAR-04:19 | 0.00 | 35885.84 | 01-MAR-19:19 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 93799.48 | 03-APR-04:19 | 0.00 | 34734.75 | 04-APR-06:30 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 50404.79 | 03-MAY-04:00 | 0.00 | 32852.43 | 01-MAY-06:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 28256.96 | 03-JUN-04:00 | 0.00 | 29894.98 | 01-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 6352.75 | 24-JUL-04:00 | 0.00 | 26640.93 | 03-JUL-18:30 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 11841.32 | 07-AUG-05:00 | 0.00 | 24723.61 | 01-AUG-06:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 54892.93 | 30-SEP-04:49 | 0.00 | 26065.69 | 29-SEP-06:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 64016.89 | 23-OCT-05:00 | 0.00 | 28940.51 | 31-OCT-18:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 186679.65 | 25-NOV-04:30 | 0.00 | 31885.48 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 186679.65 | 10-DEC-04:10 | 0.00 | 34180.56 | 29-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 6352.75 | 0.00 | 24723.61 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 217160.98 | 0.00 | 35942.85 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 7.33 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
March | 3.33 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
April | 0.83 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.65 | 0.00 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.66 | 0.00 | 24.66 |
October | 0.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
November | 2.17 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
December | 6.17 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
Annual Sum or Average | 32.33 | 19.69 | 0.00 | 19.69 | 3.67 | 20.19 | 0.00 | 20.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.17 | 20.41 | 0.00 | 20.41 | 1.33 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.69 | 0.00 | 26.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.77 | 0.00 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.70 | 0.00 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 29.23 | 0.00 | 29.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 28.86 | 8.17 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 28.55 | 13.67 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 29.20 | 0.00 | 29.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.27 | 0.00 | 27.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 0.00 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 80.50 | 28.67 | 21.83 | 28.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 29.23 | 13.67 | 29.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.73 | 519.83 | 20.71 | 519.83 | 20.70 |
February | 551.00 | 20.74 | 338.17 | 20.67 | 338.17 | 20.65 |
March | 611.83 | 20.87 | 232.67 | 20.73 | 232.67 | 20.66 |
April | 533.00 | 21.10 | 174.50 | 21.21 | 126.67 | 21.12 |
May | 431.33 | 21.92 | 220.33 | 22.47 | 98.83 | 22.56 |
June | 341.67 | 22.82 | 418.83 | 23.44 | 181.00 | 23.53 |
July | 363.00 | 23.75 | 561.33 | 23.87 | 327.33 | 23.90 |
August | 339.50 | 23.48 | 523.00 | 23.76 | 268.00 | 23.80 |
September | 290.17 | 21.49 | 283.33 | 22.60 | 30.67 | 22.56 |
October | 559.33 | 20.99 | 61.67 | 20.90 | 47.00 | 20.75 |
November | 588.67 | 20.88 | 185.83 | 20.75 | 185.83 | 20.67 |
December | 609.00 | 20.73 | 386.83 | 20.68 | 386.83 | 20.65 |
Annual Sum or Average | 5828.50 | 21.42 | 3906.33 | 21.77 | 2742.83 | 21.73 |
Minimum of Months | 290.17 | 20.73 | 61.67 | 20.67 | 30.67 | 20.65 |
Maximum of Months | 611.83 | 23.75 | 561.33 | 23.87 | 519.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.00 | 527.00 | 19.00 | 527.00 | 19.00 |
February | 551.00 | 19.01 | 391.83 | 19.01 | 391.83 | 19.00 |
March | 576.00 | 19.30 | 328.33 | 19.38 | 300.00 | 19.29 |
April | 496.67 | 20.36 | 281.33 | 20.98 | 207.83 | 21.04 |
May | 415.00 | 23.91 | 451.00 | 24.53 | 276.83 | 24.79 |
June | 471.00 | 25.45 | 538.17 | 25.50 | 427.67 | 25.64 |
July | 566.17 | 25.96 | 605.50 | 25.89 | 565.33 | 25.92 |
August | 533.83 | 25.92 | 602.33 | 25.81 | 529.17 | 25.86 |
September | 438.17 | 24.26 | 433.50 | 24.80 | 316.50 | 25.06 |
October | 486.67 | 20.36 | 201.17 | 21.06 | 108.67 | 21.13 |
November | 501.83 | 19.27 | 296.50 | 19.62 | 224.00 | 19.49 |
December | 609.00 | 19.00 | 454.17 | 19.00 | 454.17 | 19.00 |
Annual Sum or Average | 6255.33 | 21.66 | 5110.83 | 22.17 | 4329.00 | 22.27 |
Minimum of Months | 415.00 | 19.00 | 201.17 | 19.00 | 108.67 | 19.00 |
Maximum of Months | 610.00 | 25.96 | 605.50 | 25.89 | 565.33 | 25.92 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73382 | 16.35223 | -0.6885 | 15.83480 |
February | 551.00000 | 20.73666 | 20.96799 | -0.6247 | 14.20681 |
March | 612.00000 | 20.86698 | 27.47280 | -0.5106 | 11.84807 |
April | 590.00000 | 21.37139 | 36.10689 | -0.2919 | 10.12941 |
May | 611.00000 | 22.49263 | 50.73433 | -0.8912 | 25.82705 |
June | 592.00000 | 23.29349 | 57.63252 | -0.5011 | 14.21069 |
July | 609.00000 | 23.81567 | 62.06100 | -0.2624 | 7.39210 |
August | 612.00000 | 23.66657 | 60.41249 | -0.3223 | 8.80982 |
September | 590.00000 | 22.71500 | 45.52807 | -0.7672 | 22.73944 |
October | 610.00000 | 21.22437 | 35.90726 | -0.2758 | 8.43128 |
November | 591.00000 | 20.89027 | 29.56392 | -0.4660 | 11.02905 |
December | 609.00000 | 20.73466 | 19.20384 | -0.6339 | 14.32469 |
Annual Sum or Average | 7187.00000 | 21.88618 | 38.60606 | -0.5189 | 13.71953 |
Minimum of Months | 551.00000 | 20.73382 | 16.35223 | -0.8912 | 7.39210 |
Maximum of Months | 612.00000 | 23.81567 | 62.06100 | -0.2624 | 25.82705 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.00129 | 23.08556 | -0.7570 | 17.40505 |
February | 551.00000 | 19.00950 | 28.54668 | -0.7084 | 16.00862 |
March | 612.00000 | 19.59117 | 34.86450 | -0.5057 | 13.31823 |
April | 590.00000 | 20.93377 | 41.93792 | -0.1234 | 14.46957 |
May | 611.00000 | 23.96373 | 50.04619 | -0.1093 | 17.21916 |
June | 592.00000 | 25.12258 | 54.78466 | 0.37941 | 15.02175 |
July | 609.00000 | 25.81243 | 57.02154 | 0.65794 | 15.65975 |
August | 612.00000 | 25.65131 | 55.51172 | 0.59766 | 15.24621 |
September | 590.00000 | 24.13286 | 46.25858 | 0.00317 | 18.34416 |
October | 610.00000 | 21.05147 | 41.26619 | -0.0490 | 11.05397 |
November | 591.00000 | 19.92141 | 35.57404 | -0.3854 | 12.84798 |
December | 609.00000 | 19.00351 | 26.27308 | -0.7011 | 15.62630 |
Annual Sum or Average | 7187.00000 | 21.95144 | 41.33733 | -0.1381 | 15.17774 |
Minimum of Months | 551.00000 | 19.00129 | 23.08556 | -0.7570 | 11.05397 |
Maximum of Months | 612.00000 | 25.81243 | 57.02154 | 0.65794 | 18.34416 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.445961E+10 | 0.126988E+10 | 61.85 | 0.290034E+10 | 0.155927E+10 | 0.00 | 1.00 | 16-APR-03:01 | 0.00 | 01-APR-00:01 | 85816.53 | 16-APR-03:01 | 47658.36 | 16-APR-03:01 | 38158.16 | 16-APR-03:01 | 22992.70 | 16-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.794203E+10 | 0.234919E+10 | 142.40 | 0.516638E+10 | 0.277565E+10 | 0.00 | 1.00 | 31-MAY-03:01 | 0.00 | 01-MAY-00:01 | 85816.53 | 31-MAY-03:01 | 44421.91 | 31-MAY-03:01 | 41394.61 | 31-MAY-03:01 | 22992.70 | 31-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.339319E+11 | 0.938628E+10 | 353.87 | 0.206819E+11 | 0.132501E+11 | 0.00 | 1.00 | 09-JUN-03:01 | 0.00 | 01-JUN-00:01 | 93479.22 | 26-JUN-03:01 | 53372.67 | 24-JUN-03:01 | 54135.49 | 26-JUN-03:01 | 23567.36 | 26-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.457141E+11 | 0.125455E+11 | 456.76 | 0.254379E+11 | 0.202762E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 92360.61 | 07-JUL-03:01 | 51248.38 | 25-JUL-03:02 | 56552.28 | 27-JUL-03:13 | 23481.40 | 07-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.412391E+11 | 0.114144E+11 | 425.88 | 0.233533E+11 | 0.178858E+11 | 0.00 | 1.00 | 01-AUG-03:02 | 0.00 | 01-AUG-00:01 | 95347.81 | 04-AUG-03:16 | 51056.41 | 19-AUG-03:01 | 63545.01 | 04-AUG-03:03 | 23716.83 | 03-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.175823E+11 | 0.510982E+10 | 240.67 | 0.129545E+11 | 0.462785E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 89325.74 | 12-SEP-03:01 | 54803.11 | 06-SEP-03:01 | 50790.12 | 12-SEP-03:01 | 23254.83 | 12-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.279201E+09 | 91573713.41 | 12.17 | 0.235246E+09 | 43954401.95 | 0.00 | 0.38 | 20-OCT-13:00 | 0.00 | 01-OCT-00:01 | 13923.73 | 20-OCT-13:00 | 12160.99 | 20-OCT-13:00 | 1778.83 | 20-OCT-11:55 | 4416.24 | 20-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.151148E+12 | 0.421666E+11 | 1693.60 | 0.907295E+11 | 0.604188E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.457141E+11 | 0.125455E+11 | 456.76 | 0.254379E+11 | 0.202762E+11 | 0.00 | 1.00 | 0.00 | 95347.81 | 54803.11 | 63545.01 | 23716.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 13993690.56 | 4241797.32 | 3.33 | 9168176.56 | 4825514.00 | 0.00 | 0.16 | 19-MAR-16:13 | 0.00 | 01-MAR-00:01 | 2310.99 | 19-MAR-16:13 | 1515.69 | 19-MAR-16:13 | 795.29 | 19-MAR-16:13 | 693.18 | 19-MAR-16:13 | 0.00 | 01-MAR-00:01 |
April | 0.331985E+10 | 0.803143E+09 | 68.95 | 0.218699E+10 | 0.113286E+10 | 0.00 | 1.00 | 14-APR-03:42 | 0.00 | 01-APR-00:01 | 36641.30 | 16-APR-03:01 | 21782.89 | 15-APR-03:01 | 17496.20 | 16-APR-03:01 | 8784.72 | 15-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.757906E+10 | 0.192321E+10 | 225.78 | 0.477020E+10 | 0.280887E+10 | 0.00 | 1.00 | 05-MAY-03:01 | 0.00 | 01-MAY-00:01 | 36641.30 | 13-MAY-03:01 | 24005.84 | 05-MAY-03:01 | 21898.14 | 12-MAY-03:01 | 8784.72 | 05-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.254604E+11 | 0.605131E+10 | 399.86 | 0.153768E+11 | 0.100836E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 40710.90 | 30-JUN-10:45 | 25744.53 | 11-JUN-16:00 | 24218.42 | 26-JUN-03:47 | 9577.72 | 11-JUN-14:53 | 0.00 | 01-JUN-00:01 |
July | 0.349983E+11 | 0.823026E+10 | 529.55 | 0.187739E+11 | 0.162244E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 40710.90 | 26-JUL-16:57 | 22168.55 | 02-JUL-10:57 | 27310.57 | 26-JUL-18:53 | 9164.99 | 03-JUL-14:55 | 0.00 | 01-JUL-00:01 |
August | 0.318938E+11 | 0.753322E+10 | 484.81 | 0.173659E+11 | 0.145279E+11 | 0.00 | 1.00 | 01-AUG-03:11 | 0.00 | 01-AUG-00:01 | 40710.90 | 03-AUG-09:55 | 24793.18 | 04-AUG-15:00 | 27796.14 | 04-AUG-03:52 | 9663.84 | 04-AUG-15:00 | 0.00 | 01-AUG-00:01 |
September | 0.128588E+11 | 0.319598E+10 | 282.40 | 0.958395E+10 | 0.327481E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 37684.99 | 12-SEP-03:01 | 24322.49 | 06-SEP-15:10 | 23328.36 | 12-SEP-03:01 | 8854.74 | 12-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.470548E+09 | 0.134383E+09 | 36.50 | 0.356871E+09 | 0.113678E+09 | 0.00 | 1.00 | 02-OCT-03:01 | 0.00 | 01-OCT-00:01 | 36641.30 | 03-OCT-03:01 | 23588.73 | 21-OCT-03:01 | 15662.71 | 03-OCT-03:01 | 8784.72 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 12318540.35 | 3098535.86 | 0.47 | 6582698.77 | 5735841.58 | 0.00 | 1.00 | 03-NOV-03:42 | 0.00 | 01-NOV-00:01 | 36641.30 | 09-NOV-04:42 | 19537.22 | 09-NOV-04:42 | 17104.08 | 09-NOV-04:42 | 8784.72 | 09-NOV-04:42 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.116607E+12 | 0.278788E+11 | 2031.65 | 0.684304E+11 | 0.481766E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.349983E+11 | 0.823026E+10 | 529.55 | 0.187739E+11 | 0.162244E+11 | 0.00 | 1.00 | 0.00 | 40710.90 | 25744.53 | 27796.14 | 9663.84 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.73 | 67.92 | 97.81 | 71.22 | 607.41 | 0.00 | 0.00 | 0.00 |
February | 220.68 | 97.13 | 123.55 | 127.75 | 480.85 | 0.00 | 0.00 | 0.00 |
March | 299.72 | 118.92 | 180.80 | 238.51 | 307.47 | 0.00 | 0.00 | 0.00 |
April | 365.81 | 159.43 | 206.38 | 369.51 | 211.81 | 0.00 | 0.00 | 0.00 |
May | 462.21 | 202.16 | 260.05 | 548.44 | 121.28 | 0.00 | 0.00 | 0.00 |
June | 507.95 | 221.28 | 286.67 | 659.52 | 86.16 | 0.00 | 0.00 | 0.00 |
July | 513.53 | 237.05 | 276.48 | 677.45 | 77.39 | 0.00 | 0.00 | 0.00 |
August | 432.94 | 186.58 | 246.36 | 570.09 | 91.48 | 0.00 | 0.00 | 0.00 |
September | 387.88 | 183.96 | 203.91 | 474.27 | 152.27 | 0.00 | 0.00 | 0.00 |
October | 245.63 | 102.24 | 143.39 | 226.76 | 233.20 | 0.00 | 0.00 | 0.00 |
November | 145.29 | 47.15 | 98.14 | 78.42 | 374.89 | 0.00 | 0.00 | 0.00 |
December | 112.13 | 48.01 | 64.12 | 48.73 | 550.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 322.12 | 139.52 | 182.61 | 342.04 | 273.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.13 | 47.15 | 64.12 | 48.73 | 77.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 513.53 | 237.05 | 286.67 | 677.45 | 607.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 669.90 | 458.98 | 210.92 | 607.08 | 756.17 | 0.00 | 0.00 | 0.00 |
February | 722.15 | 489.94 | 232.21 | 685.55 | 602.75 | 0.00 | 0.00 | 0.00 |
March | 618.60 | 323.82 | 294.78 | 621.31 | 424.12 | 0.00 | 0.00 | 0.00 |
April | 551.49 | 252.74 | 298.74 | 622.29 | 305.39 | 0.00 | 0.00 | 0.00 |
May | 470.34 | 131.57 | 338.77 | 571.57 | 181.23 | 0.00 | 0.00 | 0.00 |
June | 449.00 | 89.67 | 359.33 | 598.46 | 126.06 | 0.00 | 0.00 | 0.00 |
July | 476.48 | 119.17 | 357.32 | 658.37 | 112.36 | 0.00 | 0.00 | 0.00 |
August | 528.01 | 182.85 | 345.16 | 737.05 | 133.39 | 0.00 | 0.00 | 0.00 |
September | 637.51 | 328.96 | 308.54 | 833.51 | 216.16 | 0.00 | 0.00 | 0.00 |
October | 687.01 | 433.13 | 253.88 | 792.31 | 319.11 | 0.00 | 0.00 | 0.00 |
November | 514.20 | 321.93 | 192.26 | 499.14 | 485.36 | 0.00 | 0.00 | 0.00 |
December | 547.51 | 414.65 | 132.87 | 532.49 | 703.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.83 | 294.54 | 277.30 | 646.36 | 362.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 449.00 | 89.67 | 132.87 | 499.14 | 112.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 722.15 | 489.94 | 359.33 | 833.51 | 756.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.60 | 67.34 | 98.26 | 75.63 | 614.55 | 0.00 | 0.00 | 0.00 |
February | 241.69 | 118.99 | 122.70 | 160.43 | 485.83 | 0.00 | 0.00 | 0.00 |
March | 288.43 | 107.28 | 181.15 | 228.23 | 314.46 | 0.00 | 0.00 | 0.00 |
April | 421.80 | 208.73 | 213.07 | 451.31 | 215.03 | 0.00 | 0.00 | 0.00 |
May | 422.65 | 169.22 | 253.43 | 498.26 | 127.01 | 0.00 | 0.00 | 0.00 |
June | 494.43 | 213.79 | 280.64 | 642.28 | 89.56 | 0.00 | 0.00 | 0.00 |
July | 531.06 | 251.95 | 279.11 | 707.12 | 80.35 | 0.00 | 0.00 | 0.00 |
August | 463.68 | 212.17 | 251.50 | 617.21 | 95.33 | 0.00 | 0.00 | 0.00 |
September | 376.24 | 178.28 | 197.96 | 459.69 | 154.63 | 0.00 | 0.00 | 0.00 |
October | 263.74 | 117.83 | 145.92 | 257.33 | 238.91 | 0.00 | 0.00 | 0.00 |
November | 157.36 | 58.43 | 98.93 | 100.03 | 381.18 | 0.00 | 0.00 | 0.00 |
December | 121.13 | 57.32 | 63.81 | 66.72 | 557.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 329.33 | 146.81 | 182.53 | 356.32 | 278.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 121.13 | 57.32 | 63.81 | 66.72 | 80.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 531.06 | 251.95 | 280.64 | 707.12 | 614.55 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443889E+09 | 0.181908E+09 | 0.261981E+09 | 0.190753E+09 | 0.162688E+10 |
February | 0.533864E+09 | 0.234972E+09 | 0.298892E+09 | 0.309060E+09 | 0.116328E+10 |
March | 0.802767E+09 | 0.318502E+09 | 0.484264E+09 | 0.638821E+09 | 0.823535E+09 |
April | 0.948177E+09 | 0.413250E+09 | 0.534927E+09 | 0.957764E+09 | 0.549024E+09 |
May | 0.123798E+10 | 0.541458E+09 | 0.696521E+09 | 0.146894E+10 | 0.324840E+09 |
June | 0.131661E+10 | 0.573557E+09 | 0.743051E+09 | 0.170948E+10 | 0.223316E+09 |
July | 0.137544E+10 | 0.634921E+09 | 0.740519E+09 | 0.181449E+10 | 0.207291E+09 |
August | 0.115960E+10 | 0.499743E+09 | 0.659854E+09 | 0.152693E+10 | 0.245026E+09 |
September | 0.100538E+10 | 0.476832E+09 | 0.528547E+09 | 0.122930E+10 | 0.394686E+09 |
October | 0.657890E+09 | 0.273837E+09 | 0.384053E+09 | 0.607347E+09 | 0.624597E+09 |
November | 0.376595E+09 | 0.122224E+09 | 0.254370E+09 | 0.203266E+09 | 0.971702E+09 |
December | 0.300316E+09 | 0.128583E+09 | 0.171733E+09 | 0.130517E+09 | 0.147572E+10 |
Annual Sum or Average | 0.101585E+11 | 0.439979E+10 | 0.575871E+10 | 0.107867E+11 | 0.862989E+10 |
Minimum of Months | 0.300316E+09 | 0.122224E+09 | 0.171733E+09 | 0.130517E+09 | 0.207291E+09 |
Maximum of Months | 0.137544E+10 | 0.634921E+09 | 0.743051E+09 | 0.181449E+10 | 0.162688E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179426E+10 | 0.122933E+10 | 0.564932E+09 | 0.162600E+10 | 0.202531E+10 |
February | 0.174703E+10 | 0.118527E+10 | 0.561760E+09 | 0.165848E+10 | 0.145817E+10 |
March | 0.165685E+10 | 0.867320E+09 | 0.789531E+09 | 0.166413E+10 | 0.113597E+10 |
April | 0.142946E+10 | 0.655112E+09 | 0.774347E+09 | 0.161298E+10 | 0.791578E+09 |
May | 0.125977E+10 | 0.352405E+09 | 0.907364E+09 | 0.153089E+10 | 0.485404E+09 |
June | 0.116380E+10 | 0.232415E+09 | 0.931387E+09 | 0.155122E+10 | 0.326759E+09 |
July | 0.127621E+10 | 0.319175E+09 | 0.957038E+09 | 0.176338E+10 | 0.300951E+09 |
August | 0.141422E+10 | 0.489748E+09 | 0.924473E+09 | 0.197410E+10 | 0.357273E+09 |
September | 0.165241E+10 | 0.852667E+09 | 0.799747E+09 | 0.216047E+10 | 0.560296E+09 |
October | 0.184008E+10 | 0.116009E+10 | 0.679988E+09 | 0.212212E+10 | 0.854697E+09 |
November | 0.133280E+10 | 0.834452E+09 | 0.498345E+09 | 0.129378E+10 | 0.125806E+10 |
December | 0.146646E+10 | 0.111059E+10 | 0.355867E+09 | 0.142622E+10 | 0.188345E+10 |
Annual Sum or Average | 0.180334E+11 | 0.928858E+10 | 0.874478E+10 | 0.203838E+11 | 0.114379E+11 |
Minimum of Months | 0.116380E+10 | 0.232415E+09 | 0.355867E+09 | 0.129378E+10 | 0.300951E+09 |
Maximum of Months | 0.184008E+10 | 0.122933E+10 | 0.957038E+09 | 0.216047E+10 | 0.202531E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443532E+09 | 0.180360E+09 | 0.263172E+09 | 0.202561E+09 | 0.164600E+10 |
February | 0.584690E+09 | 0.287859E+09 | 0.296832E+09 | 0.388103E+09 | 0.117533E+10 |
March | 0.772535E+09 | 0.287330E+09 | 0.485205E+09 | 0.611296E+09 | 0.842247E+09 |
April | 0.109330E+10 | 0.541028E+09 | 0.552270E+09 | 0.116980E+10 | 0.557362E+09 |
May | 0.113202E+10 | 0.453240E+09 | 0.678777E+09 | 0.133455E+10 | 0.340194E+09 |
June | 0.128157E+10 | 0.554148E+09 | 0.727419E+09 | 0.166478E+10 | 0.232152E+09 |
July | 0.142238E+10 | 0.674816E+09 | 0.747568E+09 | 0.189394E+10 | 0.215204E+09 |
August | 0.124191E+10 | 0.568288E+09 | 0.673621E+09 | 0.165314E+10 | 0.255324E+09 |
September | 0.975218E+09 | 0.462110E+09 | 0.513108E+09 | 0.119151E+10 | 0.400794E+09 |
October | 0.706405E+09 | 0.315586E+09 | 0.390820E+09 | 0.689228E+09 | 0.639892E+09 |
November | 0.407874E+09 | 0.151446E+09 | 0.256429E+09 | 0.259268E+09 | 0.988028E+09 |
December | 0.324422E+09 | 0.153519E+09 | 0.170903E+09 | 0.178715E+09 | 0.149339E+10 |
Annual Sum or Average | 0.103859E+11 | 0.462973E+10 | 0.575612E+10 | 0.112369E+11 | 0.878592E+10 |
Minimum of Months | 0.324422E+09 | 0.151446E+09 | 0.170903E+09 | 0.178715E+09 | 0.215204E+09 |
Maximum of Months | 0.142238E+10 | 0.674816E+09 | 0.747568E+09 | 0.189394E+10 | 0.164600E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 644.00 | 1868.20 | 1001.23 | 594.23 | 406.99 | 0.00 | 0.00 |
February | 875.29 | 1471.00 | 1184.52 | 706.06 | 478.46 | 0.00 | 0.00 |
March | 1047.42 | 1005.42 | 1206.75 | 550.01 | 656.74 | 0.00 | 0.00 |
April | 1414.64 | 703.77 | 1339.09 | 620.91 | 718.19 | 0.00 | 0.00 |
May | 1598.51 | 409.75 | 1355.20 | 502.95 | 852.25 | 0.00 | 0.00 |
June | 1889.23 | 290.75 | 1451.38 | 524.74 | 926.64 | 0.00 | 0.00 |
July | 2035.19 | 262.36 | 1521.07 | 608.17 | 912.91 | 0.00 | 0.00 |
August | 1914.24 | 310.09 | 1424.63 | 581.61 | 843.02 | 0.00 | 0.00 |
September | 1752.93 | 508.52 | 1401.62 | 691.21 | 710.42 | 0.00 | 0.00 |
October | 1255.93 | 770.75 | 1196.38 | 653.19 | 543.18 | 0.00 | 0.00 |
November | 634.86 | 1198.70 | 816.85 | 427.52 | 389.33 | 0.00 | 0.00 |
December | 575.45 | 1739.25 | 780.76 | 519.97 | 260.79 | 0.00 | 0.00 |
Annual Sum or Average | 1305.34 | 875.56 | 1223.29 | 580.86 | 642.43 | 0.00 | 0.00 |
Minimum of Months | 575.45 | 262.36 | 780.76 | 427.52 | 260.79 | 0.00 | 0.00 |
Maximum of Months | 2035.19 | 1868.20 | 1521.07 | 706.06 | 926.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172489E+10 | 0.500378E+10 | 0.268168E+10 | 0.159160E+10 | 0.109008E+10 | 0.00 | 0.00 |
February | 0.211751E+10 | 0.355864E+10 | 0.286559E+10 | 0.170810E+10 | 0.115748E+10 | 0.00 | 0.00 |
March | 0.280541E+10 | 0.269291E+10 | 0.323215E+10 | 0.147315E+10 | 0.175900E+10 | 0.00 | 0.00 |
April | 0.366675E+10 | 0.182417E+10 | 0.347093E+10 | 0.160939E+10 | 0.186154E+10 | 0.00 | 0.00 |
May | 0.428144E+10 | 0.109749E+10 | 0.362976E+10 | 0.134710E+10 | 0.228266E+10 | 0.00 | 0.00 |
June | 0.489689E+10 | 0.753634E+09 | 0.376198E+10 | 0.136012E+10 | 0.240186E+10 | 0.00 | 0.00 |
July | 0.545106E+10 | 0.702698E+09 | 0.407404E+10 | 0.162891E+10 | 0.244513E+10 | 0.00 | 0.00 |
August | 0.512709E+10 | 0.830543E+09 | 0.381573E+10 | 0.155778E+10 | 0.225795E+10 | 0.00 | 0.00 |
September | 0.454359E+10 | 0.131808E+10 | 0.363301E+10 | 0.179161E+10 | 0.184140E+10 | 0.00 | 0.00 |
October | 0.336389E+10 | 0.206438E+10 | 0.320438E+10 | 0.174951E+10 | 0.145486E+10 | 0.00 | 0.00 |
November | 0.164556E+10 | 0.310704E+10 | 0.211727E+10 | 0.110812E+10 | 0.100914E+10 | 0.00 | 0.00 |
December | 0.154130E+10 | 0.465840E+10 | 0.209120E+10 | 0.139270E+10 | 0.698503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.411654E+11 | 0.276118E+11 | 0.385777E+11 | 0.183181E+11 | 0.202596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154130E+10 | 0.702698E+09 | 0.209120E+10 | 0.110812E+10 | 0.698503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.545106E+10 | 0.500378E+10 | 0.407404E+10 | 0.179161E+10 | 0.244513E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639948E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174291443.8 | 81.22 | 0.00 | 0.00 |
February | 0.579154E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157248989.7 | 81.22 | 0.00 | 0.00 |
March | 0.646612E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172258326.6 | 81.22 | 0.00 | 0.00 |
April | 0.620648E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -163010149.6 | 81.22 | 0.00 | 0.00 |
May | 0.642036E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160176743.0 | 81.21 | 0.00 | 0.00 |
June | 0.623827E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151685160.0 | 81.21 | 0.00 | 0.00 |
July | 0.637191E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154821068.2 | 81.21 | 0.00 | 0.00 |
August | 0.645043E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155218989.4 | 81.21 | 0.00 | 0.00 |
September | 0.619903E+10 | -0.604480E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154232483.8 | 81.22 | 0.00 | 0.00 |
October | 0.639167E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167840654.9 | 81.22 | 0.00 | 0.00 |
November | 0.619029E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -165675788.9 | 81.22 | 0.00 | 0.00 |
December | 0.639109E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173988739.5 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755167E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.195045E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.579154E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174291443.8 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646612E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151685160.0 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.276583E+11 | -0.266365E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102183E+10 | 58.99 | 0.00 | 0.00 |
February | 0.255182E+11 | -0.245969E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -921356348.3 | 58.99 | 0.00 | 0.00 |
March | 0.282029E+11 | -0.271997E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100321E+10 | 58.99 | 0.00 | 0.00 |
April | 0.260444E+11 | -0.251074E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -937059624.7 | 58.99 | 0.00 | 0.00 |
May | 0.253506E+11 | -0.244580E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -892563378.5 | 58.99 | 0.00 | 0.00 |
June | 0.230108E+11 | -0.221773E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -833512011.4 | 58.99 | 0.00 | 0.00 |
July | 0.222209E+11 | -0.213773E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843575605.9 | 58.99 | 0.00 | 0.00 |
August | 0.219074E+11 | -0.210602E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -847247566.9 | 58.99 | 0.00 | 0.00 |
September | 0.213584E+11 | -0.205018E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -856534988.9 | 58.98 | 0.00 | 0.00 |
October | 0.231380E+11 | -0.221753E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -962667284.6 | 58.99 | 0.00 | 0.00 |
November | 0.239273E+11 | -0.229658E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -961450031.0 | 58.99 | 0.00 | 0.00 |
December | 0.263398E+11 | -0.253208E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101905E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294677E+12 | -0.283577E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.111001E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213584E+11 | -0.271997E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102183E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.282029E+11 | -0.205018E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -833512011.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.50 | 01-JAN-09:39 | 3204.71 | 31.49 | 154.67 | 234.67 | 3496.39 | 33.59 | 172.67 | 236.17 |
February | 226.83 | 0.52 | 0.50 | 01-FEB-07:49 | 1437.36 | 26.33 | 171.33 | 249.83 | 1473.04 | 25.69 | 161.33 | 248.67 |
March | 334.33 | 0.51 | 0.50 | 01-MAR-07:40 | 1123.65 | 21.78 | 184.83 | 322.33 | 1155.99 | 22.00 | 187.33 | 323.00 |
April | 285.17 | 0.51 | 0.50 | 01-APR-06:00 | 1451.37 | 21.23 | 134.67 | 346.50 | 1303.81 | 21.48 | 139.33 | 344.00 |
May | 428.67 | 0.52 | 0.50 | 01-MAY-05:00 | 1028.12 | 20.85 | 177.33 | 400.50 | 1191.73 | 20.67 | 164.33 | 398.33 |
June | 400.67 | 0.52 | 0.50 | 01-JUN-05:10 | 1156.25 | 22.54 | 217.83 | 400.83 | 1121.63 | 21.10 | 193.17 | 401.33 |
July | 414.00 | 0.51 | 0.50 | 01-JUL-05:40 | 1204.72 | 22.23 | 226.33 | 408.83 | 1371.87 | 21.40 | 204.00 | 409.83 |
August | 410.83 | 0.52 | 0.50 | 01-AUG-05:49 | 1325.84 | 21.08 | 199.83 | 384.83 | 1159.55 | 21.11 | 211.33 | 382.50 |
September | 326.50 | 0.51 | 0.50 | 01-SEP-06:10 | 1352.91 | 22.16 | 186.83 | 333.67 | 1386.84 | 22.34 | 190.83 | 331.17 |
October | 325.17 | 0.51 | 0.50 | 01-OCT-06:49 | 1138.94 | 23.80 | 208.50 | 301.33 | 1110.13 | 23.69 | 221.00 | 302.33 |
November | 254.83 | 0.52 | 0.50 | 01-NOV-07:40 | 1350.73 | 26.79 | 174.83 | 240.83 | 1362.77 | 27.06 | 177.17 | 241.17 |
December | 186.17 | 0.52 | 0.50 | 01-DEC-07:00 | 4388.79 | 35.58 | 149.33 | 204.50 | 4503.73 | 36.31 | 153.17 | 204.83 |
Annual Sum or Average | 3807.33 | 0.52 | 1503.08 | 23.72 | 2186.33 | 3828.67 | 1535.28 | 23.64 | 2175.67 | 3823.33 | ||
Minimum of Months | 186.17 | 0.51 | 0.50 | 1028.12 | 20.85 | 134.67 | 204.50 | 1110.13 | 20.67 | 139.33 | 204.83 | |
Maximum of Months | 428.67 | 0.52 | 0.50 | 4388.79 | 35.58 | 226.33 | 408.83 | 4503.73 | 36.31 | 221.00 | 409.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116400E+12 | 149343.72 | 03-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.831861E+11 | 149343.72 | 01-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.545573E+11 | 149343.72 | 01-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286782E+11 | 149343.72 | 03-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482832E+10 | 44132.21 | 03-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142848E+10 | 25994.86 | 04-JUN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 62195902.81 | 13260.46 | 24-JUL-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151657E+09 | 13514.21 | 07-AUG-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.489753E+10 | 51556.61 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206441E+11 | 54964.23 | 08-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538534E+11 | 149343.72 | 24-NOV-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.908717E+11 | 149343.72 | 09-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 62195902.81 | 13260.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116400E+12 | 149343.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.685932E+11 | 80842.80 | 06-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.459703E+11 | 79093.32 | 03-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250255E+11 | 52888.91 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103781E+11 | 39840.33 | 06-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.686331E+09 | 17263.20 | 03-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27770553.72 | 11862.72 | 03-JUN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.829947E+09 | 18999.11 | 30-SEP-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.510294E+10 | 28951.58 | 28-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.255480E+11 | 63891.49 | 26-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492855E+11 | 62408.99 | 11-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.685932E+11 | 80842.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.445961E+10 | 0.290034E+10 | 85816.53 | 16-APR-03:01 | 47658.36 | 0.00 |
May | 0.00 | 0.00 | 0.794203E+10 | 0.516638E+10 | 85816.53 | 31-MAY-03:01 | 44421.91 | 0.00 |
June | 0.00 | 0.00 | 0.339319E+11 | 0.206819E+11 | 93479.22 | 26-JUN-03:01 | 39343.72 | 0.00 |
July | 0.00 | 0.00 | 0.457141E+11 | 0.254379E+11 | 92360.61 | 07-JUL-03:01 | 38437.16 | 0.00 |
August | 0.00 | 0.00 | 0.412391E+11 | 0.233533E+11 | 95347.81 | 04-AUG-03:16 | 32839.25 | 0.00 |
September | 0.00 | 0.00 | 0.175823E+11 | 0.129545E+11 | 89325.74 | 12-SEP-03:01 | 38535.62 | 0.00 |
October | 0.00 | 0.00 | 0.279201E+09 | 0.235246E+09 | 13923.73 | 20-OCT-13:00 | 12160.99 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151148E+12 | 0.907295E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.457141E+11 | 0.254379E+11 | 95347.81 | 47658.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13993690.56 | 9168176.56 | 2310.99 | 19-MAR-16:13 | 1515.69 | 0.00 |
April | 0.00 | 0.00 | 0.331985E+10 | 0.218699E+10 | 36641.30 | 16-APR-03:01 | 19145.10 | 0.00 |
May | 0.00 | 0.00 | 0.757906E+10 | 0.477020E+10 | 36641.30 | 13-MAY-03:01 | 17843.17 | 0.00 |
June | 0.00 | 0.00 | 0.254604E+11 | 0.153768E+11 | 40710.90 | 30-JUN-10:45 | 21333.50 | 0.00 |
July | 0.00 | 0.00 | 0.349983E+11 | 0.187739E+11 | 40710.90 | 26-JUL-16:57 | 17355.76 | 0.00 |
August | 0.00 | 0.00 | 0.318938E+11 | 0.173659E+11 | 40710.90 | 03-AUG-09:55 | 19079.45 | 0.00 |
September | 0.00 | 0.00 | 0.128588E+11 | 0.958395E+10 | 37684.99 | 12-SEP-03:01 | 14356.63 | 0.00 |
October | 0.00 | 0.00 | 0.470548E+09 | 0.356871E+09 | 36641.30 | 03-OCT-03:01 | 20978.59 | 0.00 |
November | 0.00 | 0.00 | 12318540.35 | 6582698.77 | 36641.30 | 09-NOV-04:42 | 19537.22 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116607E+12 | 0.684304E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.349983E+11 | 0.187739E+11 | 40710.90 | 21333.50 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10402.03 | 20081.40 | 31-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10623.90 | 20227.72 | 17-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 10611.86 | 20182.97 | 03-MAR-20:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 10144.01 | 19642.21 | 03-APR-18:23 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9589.72 | 18722.59 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9015.97 | 17536.58 | 01-JUN-18:08 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8442.24 | 16393.93 | 03-JUL-18:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8324.48 | 15757.70 | 04-AUG-18:09 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8370.69 | 16093.09 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8739.97 | 17126.57 | 31-OCT-18:10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9319.63 | 18278.66 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9911.86 | 19325.20 | 29-DEC-19:50 |
Annual Sum or Average | 0.00 | 9451.14 | ||||
Minimum of Months | 0.00 | 0.00 | 8324.48 | 15757.70 | ||
Maximum of Months | 0.00 | 0.00 | 10623.90 | 20227.72 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.28 |
February | 0.166145E+10 | 0.23 | 824.13 | 01-FEB-00:01 | 0.28 |
March | 0.184589E+10 | 0.23 | 824.13 | 01-MAR-00:01 | 0.28 |
April | 0.179792E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.28 |
May | 0.191091E+10 | 0.24 | 824.13 | 01-MAY-03:55 | 0.28 |
June | 0.191610E+10 | 0.25 | 824.13 | 01-JUN-03:01 | 0.27 |
July | 0.202662E+10 | 0.25 | 824.13 | 01-JUL-00:50 | 0.27 |
August | 0.200552E+10 | 0.25 | 824.13 | 01-AUG-01:15 | 0.27 |
September | 0.190045E+10 | 0.25 | 824.13 | 01-SEP-01:25 | 0.27 |
October | 0.187432E+10 | 0.23 | 824.13 | 01-OCT-04:01 | 0.28 |
November | 0.179644E+10 | 0.23 | 824.13 | 01-NOV-04:01 | 0.28 |
December | 0.183946E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.224145E+11 | 0.24 | |||
Minimum of Months | 0.166145E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.202662E+10 | 0.25 | 824.13 | 0.28 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.516985E+10 | 0.62 | 3748.33 | 03-JAN-04:03 | 0.93 |
February | 0.431699E+10 | 0.59 | 3748.33 | 01-FEB-04:01 | 0.93 |
March | 0.418422E+10 | 0.55 | 3748.33 | 01-MAR-04:01 | 0.92 |
April | 0.367530E+10 | 0.51 | 3748.33 | 03-APR-03:01 | 0.92 |
May | 0.342013E+10 | 0.47 | 2163.93 | 03-MAY-04:01 | 0.70 |
June | 0.332379E+10 | 0.47 | 3748.33 | 14-JUN-03:01 | 0.91 |
July | 0.345125E+10 | 0.48 | 3748.33 | 02-JUL-03:01 | 0.91 |
August | 0.345978E+10 | 0.48 | 3748.33 | 03-AUG-03:01 | 0.91 |
September | 0.332912E+10 | 0.47 | 3748.33 | 11-SEP-03:01 | 0.91 |
October | 0.365801E+10 | 0.49 | 2327.05 | 08-OCT-04:01 | 0.73 |
November | 0.406848E+10 | 0.55 | 3748.33 | 24-NOV-04:10 | 0.93 |
December | 0.475145E+10 | 0.60 | 3748.33 | 09-DEC-04:10 | 0.93 |
Annual Sum or Average | 0.468084E+11 | 0.52 | |||
Minimum of Months | 0.332379E+10 | 0.47 | 2163.93 | 0.70 | |
Maximum of Months | 0.516985E+10 | 0.62 | 3748.33 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208828E+10 | 0.59 | 1417.35 | 06-JAN-05:02 | 0.88 |
February | 0.173252E+10 | 0.56 | 1400.53 | 03-FEB-05:03 | 0.87 |
March | 0.166994E+10 | 0.51 | 1148.62 | 06-MAR-05:03 | 0.79 |
April | 0.150358E+10 | 0.49 | 1600.43 | 16-APR-03:01 | 0.91 |
May | 0.146560E+10 | 0.48 | 1600.43 | 05-MAY-03:01 | 0.92 |
June | 0.165285E+10 | 0.53 | 1600.43 | 01-JUN-03:01 | 0.92 |
July | 0.178870E+10 | 0.55 | 1600.43 | 01-JUL-03:01 | 0.92 |
August | 0.174567E+10 | 0.54 | 1600.43 | 01-AUG-03:11 | 0.92 |
September | 0.146621E+10 | 0.50 | 1600.43 | 01-SEP-03:01 | 0.92 |
October | 0.148185E+10 | 0.48 | 1383.83 | 22-OCT-03:01 | 0.86 |
November | 0.163051E+10 | 0.52 | 1254.39 | 26-NOV-05:04 | 0.83 |
December | 0.190267E+10 | 0.56 | 1240.14 | 11-DEC-05:03 | 0.82 |
Annual Sum or Average | 0.201284E+11 | 0.53 | |||
Minimum of Months | 0.146560E+10 | 0.48 | 1148.62 | 0.79 | |
Maximum of Months | 0.208828E+10 | 0.59 | 1600.43 | 0.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.47 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 45.98 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.06 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.82 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 51.22 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 51.54 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.70 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 51.93 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.45 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.89 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.99 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.24 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 45.98 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.45 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.47 | 59.93 | 10402.03 | 20081.40 | 31-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 45.98 | 59.17 | 10623.90 | 20227.72 | 17-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.06 | 59.52 | 10611.86 | 20182.97 | 03-MAR-20:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 47.85 | 47.85 | 10144.01 | 19642.21 | 03-APR-18:23 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 48.38 | 48.38 | 9589.72 | 18722.59 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 48.86 | 48.86 | 9015.97 | 17536.58 | 01-JUN-18:08 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 49.86 | 49.86 | 8442.24 | 16393.93 | 03-JUL-18:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.40 | 50.40 | 8324.48 | 15757.70 | 04-AUG-18:09 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.74 | 50.74 | 8370.69 | 16093.09 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.00 | 48.00 | 8739.97 | 17126.57 | 31-OCT-18:10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.34 | 49.34 | 9319.63 | 18278.66 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.24 | 59.85 | 9911.86 | 19325.20 | 29-DEC-19:50 |
Annual Sum or Average | 0.00 | 9451.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.98 | 47.85 | 8324.48 | 15757.70 | ||
Maximum of Months | 0.00 | 0.00 | 50.74 | 59.93 | 10623.90 | 20227.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.516985E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.431699E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.418422E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.494518E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.576932E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127101E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.159968E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.148741E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.843893E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.374959E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.406848E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.475145E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.889750E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.374959E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.159968E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.208828E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.173252E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167418E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.230673E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.338881E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.770416E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.100190E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.927889E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.466219E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.161624E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163361E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.190267E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.480072E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.161624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.100190E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.516985E+10 | 0.00 | 0.116400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431699E+10 | 0.00 | 0.831861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418422E+10 | 0.00 | 0.545573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.367530E+10 | 0.445786E+10 | 0.286782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342013E+10 | 0.794028E+10 | 0.482832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332379E+10 | 0.338801E+11 | 0.142848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.345125E+10 | 0.456355E+11 | 62195902.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345978E+10 | 0.411567E+11 | 0.151657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.332912E+10 | 0.175493E+11 | 0.489753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.365801E+10 | 0.279201E+09 | 0.206441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406848E+10 | 0.00 | 0.538534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.475145E+10 | 0.00 | 0.908717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468084E+11 | 0.150899E+12 | 0.459559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.332379E+10 | 0.00 | 62195902.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.516985E+10 | 0.456355E+11 | 0.116400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.208828E+10 | 0.00 | 0.685932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173252E+10 | 0.00 | 0.459703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166994E+10 | 13993690.56 | 0.250255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150358E+10 | 0.331547E+10 | 0.103781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146560E+10 | 0.757688E+10 | 0.686331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165285E+10 | 0.254193E+11 | 27770553.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178870E+10 | 0.349458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174567E+10 | 0.318292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146621E+10 | 0.128432E+11 | 0.829947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148185E+10 | 0.468680E+09 | 0.510294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163051E+10 | 10823575.26 | 0.255480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190267E+10 | 0.00 | 0.492855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201284E+11 | 0.116424E+12 | 0.231448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208828E+10 | 0.349458E+11 | 0.685932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.516985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.367530E+10 | 0.00 | 0.00 | 0.00 | 0.126988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342013E+10 | 0.00 | 0.00 | 0.00 | 0.234919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332379E+10 | 0.00 | 0.00 | 0.00 | 0.938628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.345125E+10 | 0.00 | 0.00 | 0.00 | 0.125455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345978E+10 | 0.00 | 0.00 | 0.00 | 0.114144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.332912E+10 | 0.00 | 0.00 | 0.00 | 0.510982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.365801E+10 | 0.00 | 0.00 | 0.00 | 91573713.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.475145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468084E+11 | 0.00 | 0.00 | 0.00 | 0.421666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.332379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.516985E+10 | 0.00 | 0.00 | 0.00 | 0.125455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.208828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166994E+10 | 0.00 | 0.00 | 0.00 | 4241797.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150358E+10 | 0.00 | 0.00 | 0.00 | 0.803143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146560E+10 | 0.00 | 0.00 | 0.00 | 0.192321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165285E+10 | 0.00 | 0.00 | 0.00 | 0.605131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178870E+10 | 0.00 | 0.00 | 0.00 | 0.823026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174567E+10 | 0.00 | 0.00 | 0.00 | 0.753322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146621E+10 | 0.00 | 0.00 | 0.00 | 0.319598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148185E+10 | 0.00 | 0.00 | 0.00 | 0.134383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163051E+10 | 0.00 | 0.00 | 0.00 | 3098535.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201284E+11 | 0.00 | 0.00 | 0.00 | 0.278788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208828E+10 | 0.00 | 0.00 | 0.00 | 0.823026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.431524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875283E+11 | 0.00 | 0.00 | 3.59 |
February | 0.542148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462678E+11 | 0.00 | 0.00 | 3.59 |
March | 0.654886E+11 | 0.00 | 0.00 | 574814.83 | 0.00 | 0.146620E+11 | 0.987890E+09 | 0.00 | 3.59 |
April | 0.489895E+11 | 0.794316E+09 | 0.00 | 8976155.48 | 0.00 | 0.475185E+10 | 0.318957E+10 | 0.00 | 3.64 |
May | 0.231894E+11 | 0.623361E+09 | 0.00 | 32357531.52 | 0.00 | 33213467.68 | 0.144224E+11 | 0.00 | 3.82 |
June | 0.110776E+11 | 0.724940E+10 | 0.00 | 44873549.09 | 10482717.91 | 4621912.02 | 0.965920E+10 | 0.00 | 3.99 |
July | 0.351323E+10 | 0.896220E+10 | 0.00 | 58133540.11 | 10955342.52 | 0.00 | 0.103214E+11 | 0.00 | 4.15 |
August | 0.566287E+10 | 0.802670E+10 | 0.00 | 59179825.59 | 19962025.06 | 0.00 | 0.117996E+11 | 0.00 | 4.13 |
September | 0.209982E+11 | 0.188324E+10 | 0.00 | 46655172.09 | 310633.65 | 0.180134E+09 | 0.119875E+11 | 0.00 | 3.89 |
October | 0.516154E+11 | 0.00 | 0.00 | 6131940.22 | 0.00 | 0.504126E+09 | 0.485100E+10 | 0.00 | 3.59 |
November | 0.606108E+11 | 0.00 | 0.00 | 437778.97 | 0.00 | 0.186369E+11 | 0.128934E+10 | 0.00 | 3.57 |
December | 0.664895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436132E+11 | 0.00 | 0.00 | 3.57 |
Annual Sum or Average | 0.455002E+12 | 0.275392E+11 | 0.00 | 0.257320E+09 | 41710719.14 | 0.216182E+12 | 0.685079E+11 | 0.00 | 3.76 |
Minimum of Months | 0.351323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
Maximum of Months | 0.664895E+11 | 0.896220E+10 | 0.00 | 59179825.59 | 19962025.06 | 0.875283E+11 | 0.144224E+11 | 0.00 | 4.15 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105201E+12 | 0.00 | 0.00 | 0.00 | 73828311.85 | 0.109337E+09 | 0.00 | 0.00 | 8.02 |
February | 0.808863E+11 | 0.00 | 0.00 | 0.00 | 21088169.87 | 85519134.44 | 0.00 | 0.00 | 7.74 |
March | 0.630254E+11 | 0.00 | 0.00 | 1732511.38 | 0.00 | 40288183.39 | 0.238690E+10 | 0.00 | 7.43 |
April | 0.414557E+11 | 0.192786E+09 | 0.00 | 13640489.56 | 0.00 | 6438732.35 | 0.597892E+10 | 0.00 | 7.26 |
May | 0.138080E+11 | 63334400.74 | 0.00 | 52737498.94 | 0.00 | 0.00 | 0.218311E+11 | 0.00 | 7.24 |
June | 0.525192E+10 | 0.394616E+10 | 0.00 | 62502421.72 | 0.00 | 0.00 | 0.155524E+11 | 0.00 | 7.66 |
July | 0.111436E+10 | 0.477272E+10 | 0.00 | 83857126.93 | 0.00 | 0.00 | 0.131530E+11 | 0.00 | 7.84 |
August | 0.158546E+10 | 0.465070E+10 | 0.00 | 78926411.08 | 0.00 | 0.00 | 0.158362E+11 | 0.00 | 7.75 |
September | 0.122336E+11 | 0.453478E+09 | 0.00 | 66947219.98 | 0.00 | 0.00 | 0.199219E+11 | 0.00 | 7.35 |
October | 0.372149E+11 | 0.00 | 0.00 | 11201280.48 | 0.00 | 5062386.25 | 0.108594E+11 | 0.00 | 7.14 |
November | 0.601112E+11 | 0.00 | 1623424.66 | 3169308.89 | 0.00 | 38864666.23 | 0.540580E+10 | 7631.37 | 7.44 |
December | 0.885724E+11 | 0.00 | 0.00 | 0.00 | 4030647.30 | 67925352.81 | 0.00 | 0.00 | 7.72 |
Annual Sum or Average | 0.510460E+12 | 0.140792E+11 | 1623424.66 | 0.374714E+09 | 98947129.03 | 0.353435E+09 | 0.110926E+12 | 7631.37 | 7.55 |
Minimum of Months | 0.111436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 |
Maximum of Months | 0.105201E+12 | 0.477272E+10 | 1623424.66 | 83857126.93 | 73828311.85 | 0.109337E+09 | 0.218311E+11 | 7631.37 | 8.02 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.383832E+11 | 0.218197E+11 | 0.368852E+12 | 0.00 | 0.565275E+11 |
February | 0.492073E+11 | 0.172280E+11 | 0.288727E+12 | 0.00 | 0.419486E+11 |
March | 0.894099E+11 | 0.148452E+11 | 0.243806E+12 | 183518.16 | 0.316557E+11 |
April | 0.109873E+12 | 0.115524E+11 | 0.178092E+12 | 0.418252E+09 | 0.335324E+11 |
May | 0.129947E+12 | 0.896313E+10 | 0.133807E+12 | 0.139471E+10 | 0.387997E+11 |
June | 0.135920E+12 | 0.551672E+10 | 0.669520E+11 | 0.145478E+10 | 0.946434E+11 |
July | 0.133084E+12 | 0.391047E+10 | 0.417672E+11 | 0.134783E+10 | 0.123015E+12 |
August | 0.119244E+12 | 0.402818E+10 | 0.533817E+11 | 0.161450E+10 | 0.111703E+12 |
September | 0.776119E+11 | 0.644765E+10 | 0.120679E+12 | 0.162575E+10 | 0.577970E+11 |
October | 0.544830E+11 | 0.100602E+11 | 0.184418E+12 | 0.255039E+09 | 0.205163E+11 |
November | 0.279743E+11 | 0.135290E+11 | 0.241885E+12 | 0.00 | 0.304680E+11 |
December | 0.154642E+11 | 0.180421E+11 | 0.318220E+12 | 0.00 | 0.445934E+11 |
Annual Sum or Average | 0.980602E+12 | 0.135943E+12 | 0.224059E+13 | 0.811104E+10 | 0.685200E+12 |
Minimum of Months | 0.154642E+11 | 0.391047E+10 | 0.417672E+11 | 0.00 | 0.205163E+11 |
Maximum of Months | 0.135920E+12 | 0.218197E+11 | 0.368852E+12 | 0.162575E+10 | 0.123015E+12 |