Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:24:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2526.33 | 4942.41 | 4942.41 |
Net Site Energy | 2526.33 | 4942.41 | 4942.41 |
Total Source Energy | 5245.47 | 10262.04 | 10262.04 |
Net Source Energy | 5245.47 | 10262.04 | 10262.04 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 489.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 314.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.50 | 363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 66.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1203.52 | 1322.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 489.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 44.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 314.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 77.50 | 363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 489.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 44.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 314.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 77.50 | 363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 66.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 854.01 | 1668.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1030.49 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2354.52 | 2587.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 854.01 | 1668.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1030.49 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2354.52 | 2587.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1203.520 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1203.520 | 100.00 |
Total On-Site and Utility Electric Sources | 1203.520 | 100.00 |
Total Electricity End Uses | 1203.520 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5189.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 20.6319 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.3949 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 18.1127 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 18.1127 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 20.6319 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.3949 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 18.1127 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 18.1127 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 18.1127 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-17:19 | 06-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 19-APR-18:10 |
Heating | 0.00 | 87452.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28720.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20676.91 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11581.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4413.07 | 29110.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2067.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 75809.39 | 130140.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 87452.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28720.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11581.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4413.07 | 29110.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 514.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1007.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 530.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 139.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 533.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 995.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 245.43 | 393.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 209.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3811.55 | 1433.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1038.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 273.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 444.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1948.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 480.15 | 770.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 409.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7456.76 | 2805.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1038.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 273.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 444.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1948.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 480.15 | 770.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 409.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7456.76 | 2805.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.07 |
KITCHEN DIRECT AIR | 1.59 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.07 | 4.07 | 4.07 | 4.07 | 4.07 | 4.07 | 1.00 | 1.00 | 4.07 |
PSZ-AC_2:2 | 1.59 | 1.59 | 1.59 | 1.59 | 1.59 | 1.59 | 1.00 | 1.00 | 1.59 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.07 | 2.64 |
PSZ-AC_2:2_OA_CONTROLLER | 1.59 | 0.187543 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.07 | 7634.05 |
PSZ-AC_2:2_ADDAQ FAN | 1.59 | 1743.90 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.07 | 4.07 | 4.07 | 4.07 | 85200.08 | 171616.84 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.59 | 1.59 | 1.59 | 1.59 | 35134.15 | 46595.17 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.07 | 2.03 | 4.07 | 85200.08 | 42562.01 | 85200.08 | 0.758450 | 0.758450 |
PSZ-AC_2:2 COOLING COIL | 1.59 | 0.796661 | 1.59 | 35134.15 | 16936.06 | 35134.15 | 0.740000 | 0.740000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 171616.84 |
PSZ-AC_2:2 HEATING COIL | 46595.17 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 20.632 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 85.559 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.395 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.475 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 7669.876 | 20.632 | 27.379 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7669.876 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1588.510 | 11.395 | 211.016 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1588.510 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.342 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5109 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.20636098E-16 | 0.18100998E-15 | 0.17288268E-13 | -0.34766289E-16 |
24 | 3 | -0.71341822E-08 | 0.14427768E-06 | -0.58767875E-04 | 0.16137435E-12 |
25 | 2 | 0.62866063E-04 | 0.30866150E-02 | 1.1745480 | -0.77421164E-04 |
26 | 1 | -0.70719755E-01 | 0.78899699E-01 | -17.315014 | 0.34200793 |
27 | 0 | 0.20250090 | 0.49857543E-01 | 16.272369 | |
28 | 4 | 0.17288268E-13 | 0.18100998E-15 | 0.20636098E-16 | -0.34766289E-16 |
29 | 3 | -0.58767875E-04 | 0.14427768E-06 | -0.71341822E-08 | 0.16137435E-12 |
30 | 2 | 1.1745480 | 0.30866150E-02 | 0.62866063E-04 | -0.77421164E-04 |
31 | 1 | -17.315014 | 0.78899699E-01 | -0.70719755E-01 | 0.34200793 |
32 | 0 | 16.272369 | 0.49857543E-01 | 0.20250090 | |
33 | 6 | 0.21862767E-07 | 0.34448908E-09 | 0.50649605E-08 | -0.99069094E-13 |
34 | 5 | -0.15485004E-03 | 0.31008008E-05 | -0.80011323E-04 | 0.50225397E-08 |
35 | 4 | 0.24987207 | 0.15775750E-02 | 0.84530116E-01 | -0.27712185E-04 |
36 | 3 | -6.4266483 | 0.50820490E-01 | -2.0899201 | 0.24901095E-01 |
37 | 2 | 38.099035 | 0.18692275 | 14.237681 | -0.30248143 |
38 | 1 | -78.418483 | 0.86852168E-01 | -28.218840 | 1.0332909 |
39 | 0 | 46.824353 | 0.17981083E-02 | 16.314603 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | 38 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
2 | NONRESWINDOW_U_0.5722_SHGC_NORTH_0.39 | 39 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
3 | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | 40 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 | ||
4 | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | 41 | 1 | VerySmooth | 3.253 | 3.253 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46595 | 0.46595 | 0.39000 | 0.13867 | 0.18233 | 0.00000 | 0.84000 | 0.84000 | 1.44974E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.237 | 1.0416 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.744 | 0.2415 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 45929.13195 | 55114.95834 | 3.38840 | 4.06608 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
2 | DINING | Heating | 9903.61571 | 11884.33885 | 0.43062 | 2.64387 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | -4.20000 | 2.69032E-003 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
3 | KITCHEN | Cooling | 21211.24063 | 25453.48875 | 1.32777 | 1.59332 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
4 | KITCHEN | Heating | 742.89376 | 891.47251 | 2.92240E-002 | 0.18754 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 71317.52 | 4.06608 | 4.06608 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 139384.54 | 2.64387 | 2.64387 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 25562.48 | 1.59332 | 1.59332 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 9887.26 | 0.18754 | 0.18754 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.06608 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.59332 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.06608 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.06608 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.06608 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.06608 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.06608 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.06608 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.59332 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.59332 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.59332 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.59332 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.59332 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.59332 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.06608 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.59332 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.06608 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.64387 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.06608 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7634.04824 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.06608 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.06608 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.06608 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.06608 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.06608 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.03304 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.06608 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 85200.08000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 42562.00914 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 85200.08000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75845 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75845 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 85200.08000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 171616.83706 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 171616.83706 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.59332 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.18754 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.59332 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1743.90060 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.59332 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.59332 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.59332 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.59332 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.59332 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.79666 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.59332 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35134.15000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 16936.06160 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 35134.15000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74000 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35134.15000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46595.16619 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 46595.16619 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 82270.3 | 9.74 | 9.62 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 33990.5 | 10.51 | 10.38 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | N/A | 3.253 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | N/A | 3.253 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | N/A | 3.253 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.8144860444E-002 | 0.4111851875 | Pass | Pass | 0.2300552645 | 1.1347400160 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1220825866 | 0.3811164681 | Pass | Pass | 0.2140642303 | 0.6506301656 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 9.7768626570E-002 | 8.7973245603E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 824.55 | 145.35 | 3207.67 | 363.59 | 536.80 | 5077.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5722_SHGC_EAST_0.39 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5722_SHGC_SOUTH_0.39 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5722_SHGC_WEST_0.39 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.253 | 0.391 | 0.391 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 3.253 | 0.391 | 0.391 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 3.253 | 0.391 | 0.391 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 20.6319 | 371.75 | 7669.88 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 139.55 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.3949 | 139.41 | 1588.51 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 28.90 |
Interior Lighting Total | 18.1127 | 511.15 | 9258.39 | 168.45 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.55 | 83.55 | 71.80 | |
Exterior Lighting Total | 4578.48 | 71.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 85200.08 | 64620.00 | 20580.08 | 0.76 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35134.15 | 25999.27 | 9134.88 | 0.74 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 82270.3 | 9.74 | 9.62 | ||||
PSZ-AC_2:2 COOLING COIL | 33990.5 | 10.51 | 10.38 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 171616.84 | 0.79 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 46595.17 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 2.64 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.07 | 7634.05 | 1877.50 | 1.00 | 1.15 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.59 | 1743.90 | 1094.51 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.04 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.74 | 0.24 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 45929.13 | 55114.96 | 148.26 | 3.388 | 4.066 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 23.99 | 0.00986 | 29.30 | 0.00882 | 2.644 | 0.00 |
KITCHEN | 21211.24 | 25453.49 | 182.59 | 1.328 | 1.593 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.01029 | 28.46 | 0.00882 | 0.188 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9903.62 | 11884.34 | 31.97 | 0.431 | 2.644 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:50:00 | 21.00 | 21.00 | 0.00751 | -4.20 | 0.00269 | 2.644 | 0.00 |
KITCHEN | 742.89 | 891.47 | 6.39 | 0.029 | 0.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 19.00 | 0.00394 | -4.20 | 0.00269 | 0.188 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.07 | 4.07 | 2.64 | 2.64 | 4.0661 | 4.0661 | 4.0661 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.59 | 1.59 | 0.19 | 0.19 | 1.5933 | 1.5933 | 1.5933 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 85200.080 | 64620.001 | 4.066080 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 85200.08 | 77029.41 | 4.066080 | 27.51 | 18.01 | 0.00918408 | 11.25 | 11.25 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 65.0226 | 23.99 | 0.00985845 | 52.2285 | 45918.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 171616.837 | 171616.837 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 171616.84 | 171616.84 | 4.066076 | 4.61 | 3.37 | 0.00437631 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 65.0226 | 21.00 | 0.00751056 | 47.9016 | 9901.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 35134.150 | 25999.271 | 1.593320 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 35134.15 | 27617.26 | 1.593320 | 26.25 | 18.34 | 0.01012004 | 11.90 | 11.60 | 0.00850000 | 28.46 | 0.00882000 | 18.03 | 11.7706 | 25.99 | 0.01029347 | 48.3825 | 21211.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 46595.166 | 46595.166 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | 46595.17 | 46595.17 | 1.593323 | 15.48 | 8.40 | 0.00405124 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 11.7706 | 19.00 | 0.00423279 | 30.7166 | 414.38 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 85200.080 | 64620.001 | 4.066080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9128 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.066076 | 4.82639419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 85200.08 | 77029.41 | 1.0000 | 4.82639948 | 4.066080 | 27.51 | 18.01 | 0.00918408 | 51079.2 | 11.25 | 11.25 | 0.00850000 | 32742.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85200.08 | 29.40 | 0.00882150 | 18.34 | 2.64386968 | 65.0226 | 23.99 | 0.00985845 | 23.99 | 0.00985845 | 52.2285 | 45918.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 171616.837 | 171616.837 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.066076 | 4.82639419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 171616.84 | 171616.84 | 1.0000 | 4.82639419 | 4.066076 | 4.61 | 3.37 | 0.00437631 | 15618.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 171616.84 | -4.20 | 0.00269032 | -4.20 | 2.64386968 | 65.0226 | 21.00 | 0.00751056 | 21.00 | 0.00751056 | 47.9016 | 9901.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35134.150 | 25999.271 | 1.593320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6526 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.593323 | 1.89125952 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 35134.15 | 27617.26 | 1.0000 | 1.89125615 | 1.593320 | 26.25 | 18.34 | 0.01012004 | 52181.3 | 11.90 | 11.60 | 0.00850000 | 33402.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35134.15 | 28.46 | 0.00882000 | 18.03 | 0.18754328 | 11.7706 | 25.96 | 0.01029347 | 25.99 | 0.01029347 | 48.3825 | 21211.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46595.166 | 46595.166 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.593323 | 1.89125952 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | Sensible | 46595.17 | 46595.17 | 1.0000 | 1.89125952 | 1.593323 | 15.48 | 8.40 | 0.00405124 | 25805.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46595.17 | -4.20 | 0.00269032 | -4.20 | 0.18754328 | 11.7706 | 18.11 | 0.00423279 | 19.00 | 0.00423279 | 30.7166 | 414.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 2.64 | 4.07 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.19 | 1.59 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 1781.00 | 5431.83 | 325.50 |
KITCHEN | 7187.00 | 4865.67 | 4865.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7187.00 | 7178.50 | 5189.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.17 | 15.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 365.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 367.33 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 8.593 | 0.949 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 7.489 | 0.058 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 8.140 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 1.595 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.14 | 280.14 | 1133.39 | 371.75 | 2.6439 | 2.644 |
KITCHEN | PSZ-AC_2:2 | 3.17 | 7.53 | 425.02 | 139.41 | 0.1242 | 0.053 |
Total Facility | 121.32 | 287.67 | 1558.40 | 511.15 | 2.7680 | 2.697 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 70356425.41 | 0.00 | 70356425.41 | 7801430.56 | 78157855.97 | 83377074.30 | 1458.50 | 6285.50 | 1016.00 | 260.57 |
KITCHEN | 23440083.78 | 0.00 | 23440083.78 | 281102.43 | 23721186.21 | 5914364.89 | 897.04 | 144.34 | 7718.62 | 1092.03 |
Total Facility | 93796509.20 | 0.00 | 93796509.20 | 8082532.99 | 0.10E+09 | 89291439.19 | 1458.54 | 6297.09 | 7718.65 | 1131.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 2.6719 | 0.0000 | 2.6719 | 0.2948 | 2.9667 | 2.6439 | 0.00 | 6172.50 | 1014.50 |
KITCHEN | 0.8584 | 0.0000 | 0.8584 | 0.0066 | 0.8650 | 0.1875 | 0.00 | 130.77 | 7056.23 |
Total Facility | 3.5303 | 0.0000 | 3.5303 | 0.3014 | 3.8318 | 2.8314 | 0.00 | 6172.50 | 7056.23 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 99128482.94 | 0.00 | 99128482.94 | 83377074.30 | 1458.50 | 0.00 | 7301.50 | 260.57 |
PSZ-AC_2:2 | 33025838.53 | 0.00 | 33025838.53 | 5914364.89 | 744.67 | 6.16 | 8009.17 | 1092.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 3.7646 | 0.0000 | 3.7646 | 2.6439 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.2094 | 0.0000 | 1.2094 | 0.1875 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1098.93 | 72.24 | 6276.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 7342.13 | 936.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 4.0117 | 3.8860 | 3.7257 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.2268 | 0.2651 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
Electricity:Building | 646.02 | 4774.49 | 01-JAN-01:10 | 35397.39 | 02-JAN-11:10 |
Electricity:Zone:DINING | 264.83 | 1633.21 | 01-JAN-01:10 | 13902.52 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 629.17 | 4365.45 | 01-JAN-01:10 | 33032.24 | 02-JAN-11:10 |
InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.20 | 3141.27 | 01-JAN-01:10 | 21494.87 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 66.02 | 1192.44 | 01-APR-22:30 | 3441.39 | 03-MAY-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 127.11 | 1301.13 | 14-AUG-01:00 | 6539.72 | 29-MAY-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 17.36 | 0.00 | 01-JAN-11:10 | 1455.44 | 15-SEP-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 31.80 | 911.97 | 14-AUG-01:00 | 1076.23 | 02-JAN-14:10 |
ElectricityPurchased:Facility | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
ElectricityPurchased:Plant | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
Cogeneration:ElectricityPurchased | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
General:Cogeneration:ElectricityPurchased | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
ElectricityNet:Plant | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
Cogeneration:ElectricityNet | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
General:Cogeneration:ElectricityNet | 1203.52 | 10703.21 | 25-MAR-02:40 | 75809.39 | 10-AUG-17:20 |
Electricity:HVAC | 358.59 | 0.00 | 01-JAN-01:40 | 40388.64 | 10-AUG-17:50 |
Fans:Electricity | 314.49 | 0.00 | 01-JAN-01:40 | 11581.35 | 01-JAN-00:20 |
General:Fans:Electricity | 314.49 | 0.00 | 01-JAN-01:40 | 11581.35 | 01-JAN-00:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 44.10 | 0.00 | 01-JAN-00:10 | 28807.28 | 10-AUG-17:50 |
General:Cooling:Electricity | 44.10 | 0.00 | 01-JAN-00:10 | 28807.28 | 10-AUG-17:50 |
ExteriorLights:Electricity | 71.80 | 0.00 | 01-JAN-08:10 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 71.80 | 0.00 | 01-JAN-08:10 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 77.50 | 0.00 | 01-JAN-01:10 | 4784.49 | 02-AUG-18:10 |
Water Heater:WaterSystems:Electricity | 77.50 | 0.00 | 01-JAN-01:10 | 4784.49 | 02-AUG-18:10 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 12-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 12-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1322.81 | 2863.57 | 30-APR-00:10 | 130140.03 | 06-JAN-08:00 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 489.74 | 0.00 | 01-JAN-01:10 | 101707.32 | 19-FEB-06:10 |
Heating:NaturalGas | 489.74 | 0.00 | 01-JAN-01:10 | 101707.32 | 19-FEB-06:10 |
General:Heating:NaturalGas | 489.74 | 0.00 | 01-JAN-01:10 | 101707.32 | 19-FEB-06:10 |
NaturalGas:Plant | 363.28 | 1053.32 | 12-JAN-00:10 | 29703.33 | 08-FEB-07:50 |
WaterSystems:NaturalGas | 363.28 | 1053.32 | 12-JAN-00:10 | 29703.33 | 08-FEB-07:50 |
Water Heater:WaterSystems:NaturalGas | 363.28 | 1053.32 | 12-JAN-00:10 | 29703.33 | 08-FEB-07:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAY-18:20 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAY-18:20 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1599.87 | 4156.25 | 25-MAR-02:40 | 171830.00 | 10-AUG-18:10 |
EnergyTransfer:Building | 737.31 | 2078.12 | 25-MAR-02:40 | 55918.67 | 10-AUG-17:20 |
EnergyTransfer:Zone:KITCHEN | 412.36 | 2078.12 | 25-MAR-02:40 | 23385.85 | 10-AUG-11:00 |
Refrigeration:EnergyTransfer | 159.54 | 3640.76 | 01-APR-22:30 | 7834.84 | 11-JUL-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.77 | 1820.38 | 01-APR-22:30 | 3917.42 | 11-JUL-10:40 |
General:Refrigeration:EnergyTransfer | 79.77 | 1820.38 | 01-APR-22:30 | 3917.42 | 11-JUL-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.77 | 1820.38 | 01-APR-22:30 | 3917.42 | 11-JUL-10:40 |
EnergyTransfer:Plant | 335.32 | 2018.63 | 14-AUG-01:00 | 19544.10 | 15-FEB-19:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.58 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 64.19 | 1745.91 | 14-AUG-01:00 | 2238.70 | 02-JAN-14:10 |
EnergyTransfer:Zone:DINING | 324.94 | 0.00 | 01-JAN-01:10 | 35390.00 | 18-FEB-08:30 |
Heating:EnergyTransfer | 0.70 | 0.00 | 01-JAN-00:10 | 17061.24 | 18-FEB-08:30 |
Heating:EnergyTransfer:Zone:DINING | 0.70 | 0.00 | 01-JAN-00:10 | 17061.24 | 18-FEB-08:30 |
General:Heating:EnergyTransfer | 0.70 | 0.00 | 01-JAN-00:10 | 17061.24 | 18-FEB-08:30 |
General:Heating:EnergyTransfer:Zone:DINING | 0.70 | 0.00 | 01-JAN-00:10 | 17061.24 | 18-FEB-08:30 |
Cooling:EnergyTransfer | 656.84 | 0.00 | 01-JAN-01:40 | 53461.33 | 10-AUG-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 324.25 | 0.00 | 01-JAN-01:10 | 35060.04 | 10-AUG-17:10 |
General:Cooling:EnergyTransfer | 656.84 | 0.00 | 01-JAN-01:40 | 53461.33 | 10-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 324.25 | 0.00 | 01-JAN-01:10 | 35060.04 | 10-AUG-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 145.72 | 19-JUL-04:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 145.72 | 19-JUL-04:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 332.59 | 0.00 | 01-JAN-01:40 | 19538.92 | 10-AUG-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 332.59 | 0.00 | 01-JAN-01:40 | 19538.92 | 10-AUG-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 255.55 | 0.00 | 01-JAN-01:10 | 16837.12 | 13-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 255.55 | 0.00 | 01-JAN-01:10 | 16837.12 | 13-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 255.55 | 0.00 | 01-JAN-01:10 | 16837.12 | 13-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 255.55 | 0.00 | 01-JAN-01:10 | 16837.12 | 13-FEB-07:10 |
EnergyTransfer:HVAC | 527.25 | 0.00 | 01-JAN-01:20 | 100487.59 | 10-AUG-18:00 |
HeatingCoils:EnergyTransfer | 388.12 | 0.00 | 01-JAN-01:10 | 80603.05 | 19-FEB-06:10 |
CoolingCoils:EnergyTransfer | 139.13 | 0.00 | 01-JAN-00:10 | 100487.59 | 10-AUG-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 255.55 | 0.00 | 01-JAN-01:10 | 16837.12 | 13-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 255.55 | 0.00 | 01-JAN-01:10 | 16837.12 | 13-FEB-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.696 | -324.245 | 0.000 | 0.000 | 233.390 | 139.549 | 93.957 | 35.417 | 0.000 | 0.720 | 0.001 | 0.000 | -30.394 | 0.000 | -93.619 | -55.470 |
KITCHEN | 0.000 | 0.000 | 0.000 | -332.589 | 0.000 | 0.000 | 4.765 | 28.902 | 297.857 | 0.000 | 0.000 | 0.005 | 6.357 | 0.000 | 0.000 | 0.000 | -5.297 | -0.002 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.436 | 30.118 | 0.000 | 0.000 | 0.000 | -35.553 | -0.001 |
Total Facility | 0.000 | 0.000 | 0.696 | -656.834 | 0.000 | 0.000 | 238.155 | 168.451 | 391.814 | 35.417 | 0.000 | 6.161 | 36.475 | 0.000 | -30.394 | 0.000 | -134.470 | -55.473 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 15-AUG-00:42 | 0.00 | 0.00 | 0.00 | -74030.78 | 0.00 | 0.00 | 0.00 | 1150.48 | 362.05 | 0.00 | 0.00 | 0.00 | 73914.05 | 0.00 | -1211.81 | 0.00 | -183.99 | 0.00 |
KITCHEN | 13-JAN-04:21 | 0.00 | 0.00 | 0.00 | -62366.38 | 0.00 | 0.00 | 0.00 | 238.28 | 3821.48 | 0.00 | 0.00 | 0.00 | 59170.53 | 0.00 | -0.00 | 0.00 | -863.90 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-AUG-02:61 | 0.00 | 0.00 | 0.00 | -112915.68 | 0.00 | 0.00 | 0.00 | 1388.76 | 2711.19 | 0.00 | 0.00 | 705.70 | 109766.64 | 0.00 | -1348.59 | 0.00 | -308.02 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 18-FEB-08:29 | 0.00 | 0.00 | 81909.95 | 0.00 | 0.00 | 0.00 | 11577.97 | 4601.93 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1755.96 | 0.00 | -9737.53 | -89854.81 |
KITCHEN | 19-JUL-04:02 | 0.00 | 0.00 | 1165.51 | 0.00 | 0.00 | 0.00 | 13.83 | 317.70 | 7256.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -38.35 | -8715.63 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-FEB-08:29 | -7437.93 | 7437.93 | 81909.95 | -7437.93 | 0.00 | 0.00 | 11802.81 | 5555.03 | 13460.05 | 0.00 | 0.00 | 432.67 | 0.00 | 0.00 | -1755.96 | 0.00 | -9841.90 | -94124.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.0661 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 4.0661 | 0.6502 | 1.0000 | Not calculated | 2.6439 | 0.6502 | ||
PSZ-AC_2:2 | 1.5933 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.5933 | 0.0779 | 1.0000 | Not calculated | 0.1242 | 0.0779 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.0661 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 4.0661 | 1.0000 | 1.0000 | Not calculated | 2.6439 | 0.6502 | ||
PSZ-AC_2:2 | 1.5933 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.5933 | 0.6620 | 1.0000 | Not calculated | 0.1242 | 0.0779 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.007112 | 371.75 | 2.6439 | 1.0000 | 2.6439 | 1.000 | 2.6439 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000381 | 139.41 | 0.1242 | 1.0000 | 0.1242 | 1.000 | 0.1242 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.007112 | 371.7481 | 2.6439 | 2.6439 | 2.6439 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000381 | 139.4052 | 0.1242 | 0.1242 | 0.1242 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.0661 | 4.0661 | 4.0661 | No | 2.6439 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5933 | 1.5933 | 1.5933 | No | 0.1242 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.0661 | 4.0661 | 4.0661 | 4.0661 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.5933 | 1.5933 | 1.5933 | 1.5933 | 0.1242 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.0661 | 4.0661 | 4.0661 | No | 2.6439 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5933 | 1.5933 | 1.5933 | No | 0.1242 | 0.6620 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.0661 | 4.0661 | 4.0661 | 4.0661 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.5933 | 1.5933 | 1.5933 | 1.5933 | 0.1242 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 489.74 | 101707.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 44.10 | 28807.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 168.45 | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.80 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 314.49 | 11581.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 77.50 | 4784.49 | 363.28 | 29703.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.36 | 1455.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.80 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 526.74 | 1203.52 |
Natural Gas | 469.79 | 1322.81 |
Additional | 0.00 | 0.00 |
Total | 996.52 | 2526.33 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 329.55 |
Space Heating | 0.00 |
Space Cooling | 86.27 |
Fans (All) | 615.25 |
Service Water Heating | 151.61 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2354.52 |
Subtotal | 2354.52 |
Natural Gas [MJ/m2] | |
Space Heating | 958.11 |
Service Water Heating | 710.71 |
Miscellaneous (All) | 2587.90 |
Subtotal | 2587.90 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.67 |
Space Heating | 19.39 |
Space Cooling | 1.75 |
Fans (All) | 12.45 |
Service Water Heating | 17.45 |
Receptacle Equipment | 36.83 |
Miscellaneous | 5.47 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 6817. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8479.67 | 280.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 7504.83 | 531.33 | 393.83 | 327.50 | 2.50 |
Min | 7504.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 531.33 | 393.83 | 327.50 | 2.50 |
Average | 8248.17 | 270.56 | 131.28 | 109.17 | 0.83 |
Sum | 24744.50 | 811.67 | 393.83 | 327.50 | 2.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6265.50 | 2494.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7579.00 | 740.33 | 233.33 | 158.00 | 49.33 |
Min | 6265.50 | 1.17 | 0.00 | 0.00 | 0.00 |
Max | 8758.83 | 2494.50 | 233.33 | 158.00 | 49.33 |
Average | 7534.44 | 1078.67 | 77.78 | 52.67 | 16.44 |
Sum | 22603.33 | 3236.00 | 233.33 | 158.00 | 49.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 824100.67 | 121.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 12742.67 | 6490.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824100.67 | 6490.33 | 0.00 | 0.00 | 0.00 |
Average | 278947.78 | 2203.89 | 0.00 | 0.00 | 0.00 |
Sum | 836843.33 | 6611.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2004
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160056E+11 | 56757.81 | 07-JAN-00:01 | -1.2 | -1.2 | 0.120031E+11 | 10742.47 | 07-JAN-19:10 | 1.83 | -0.2 |
February | 0.174409E+11 | 60134.99 | 19-FEB-00:01 | -2.5 | -3.6 | 0.109337E+11 | 12933.98 | 27-FEB-12:00 | 17.80 | 11.29 |
March | 0.242984E+11 | 42513.88 | 05-MAR-00:01 | 3.80 | 2.84 | 0.122977E+11 | 14051.39 | 18-MAR-18:40 | 17.23 | 8.53 |
April | 0.273801E+11 | 42129.33 | 18-APR-23:01 | 3.98 | 3.16 | 0.123031E+11 | 14052.45 | 29-APR-18:30 | 17.75 | 13.28 |
May | 0.311046E+11 | 36212.61 | 17-MAY-23:01 | 6.10 | 5.06 | 0.133535E+11 | 14051.91 | 13-MAY-18:40 | 6.10 | 5.06 |
June | 0.325576E+11 | 34251.82 | 01-JUN-04:02 | 8.90 | 8.00 | 0.138350E+11 | 14053.29 | 03-JUN-18:19 | 19.03 | 12.76 |
July | 0.361890E+11 | 66041.05 | 24-JUL-01:22 | 17.75 | 13.73 | 0.146727E+11 | 14052.55 | 22-JUL-18:10 | 17.75 | 13.73 |
August | 0.377643E+11 | 74054.33 | 15-AUG-00:42 | 17.50 | 12.09 | 0.149884E+11 | 14052.72 | 19-AUG-18:00 | 17.60 | 13.66 |
September | 0.327354E+11 | 29955.43 | 06-SEP-04:02 | 9.90 | 9.03 | 0.134876E+11 | 14052.28 | 09-SEP-18:00 | 17.20 | 12.69 |
October | 0.290623E+11 | 34237.84 | 05-OCT-04:02 | 9.22 | 5.88 | 0.125882E+11 | 12939.58 | 04-OCT-11:30 | 9.22 | 5.88 |
November | 0.217682E+11 | 47228.20 | 12-NOV-00:01 | 2.20 | 1.74 | 0.117141E+11 | 13153.26 | 04-NOV-18:19 | 2.20 | 1.74 |
December | 0.179413E+11 | 55138.90 | 26-DEC-00:01 | -0.7 | -0.7 | 0.119965E+11 | 10742.47 | 02-DEC-19:10 | -0.7 | -0.7 |
Annual Sum or Average | 0.324248E+12 | 0.154173E+12 | ||||||||
Minimum of Months | 0.160056E+11 | 29955.43 | -2.5 | -3.6 | 0.109337E+11 | 10742.47 | -0.7 | -0.7 | ||
Maximum of Months | 0.377643E+11 | 74054.33 | 17.75 | 13.73 | 0.149884E+11 | 14053.29 | 19.03 | 13.73 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245054E+11 | 62372.58 | 13-JAN-04:21 | 3.60 | 2.54 | 0.106027E+11 | 6934.79 | 30-JAN-11:30 | 8.05 | 6.32 |
February | 0.225880E+11 | 47051.65 | 28-FEB-04:21 | 10.55 | 9.51 | 0.957778E+10 | 6934.78 | 28-FEB-11:20 | 11.30 | 10.30 |
March | 0.260714E+11 | 47404.01 | 09-MAR-01:42 | 10.10 | 8.58 | 0.106088E+11 | 6934.89 | 09-MAR-11:00 | 17.20 | 12.45 |
April | 0.266007E+11 | 58430.84 | 11-APR-03:21 | 5.00 | 4.22 | 0.102629E+11 | 6934.93 | 27-APR-10:50 | 20.73 | 13.65 |
May | 0.291533E+11 | 50912.13 | 12-MAY-03:21 | 8.05 | 7.62 | 0.106058E+11 | 6934.98 | 05-MAY-10:50 | 8.05 | 7.62 |
June | 0.297654E+11 | 49248.65 | 02-JUN-03:21 | 10.30 | 8.43 | 0.102663E+11 | 6934.96 | 20-JUN-10:50 | 21.42 | 14.62 |
July | 0.320586E+11 | 48201.82 | 18-JUL-03:21 | 12.20 | 9.08 | 0.106027E+11 | 6934.98 | 14-JUL-10:00 | 12.20 | 9.08 |
August | 0.325329E+11 | 44809.98 | 22-AUG-03:21 | 11.90 | 10.68 | 0.106091E+11 | 6934.96 | 08-AUG-10:00 | 11.90 | 10.68 |
September | 0.298582E+11 | 48727.60 | 29-SEP-03:21 | 10.30 | 8.83 | 0.102630E+11 | 6934.95 | 08-SEP-10:00 | 10.30 | 8.83 |
October | 0.283672E+11 | 51319.00 | 03-OCT-03:21 | 10.00 | 7.39 | 0.106027E+11 | 6934.92 | 04-OCT-10:50 | 18.62 | 11.03 |
November | 0.259030E+11 | 47231.82 | 03-NOV-03:21 | 10.60 | 9.38 | 0.102603E+11 | 6934.78 | 24-NOV-11:09 | 6.20 | 4.42 |
December | 0.251896E+11 | 42895.47 | 26-DEC-04:21 | -0.9 | -0.9 | 0.106024E+11 | 6934.80 | 12-DEC-11:09 | -0.9 | -0.9 |
Annual Sum or Average | 0.332594E+12 | 0.124864E+12 | ||||||||
Minimum of Months | 0.225880E+11 | 42895.47 | -0.9 | -0.9 | 0.957778E+10 | 6934.78 | -0.9 | -0.9 | ||
Maximum of Months | 0.325329E+11 | 62372.58 | 12.20 | 10.68 | 0.106091E+11 | 6934.98 | 21.42 | 14.62 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.83 | 10.29 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 | 12.22 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.17 | 13.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 | 12.42 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 | 8.04 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.00 | 0.00 | 17.17 | 13.75 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305456E+09 | 30559.95 | 16-JAN-04:02 | -2.2 |
February | 0.241392E+09 | 81909.26 | 18-FEB-08:29 | -1.1 |
March | 28970352.11 | 12908.94 | 30-MAR-04:01 | 4.40 |
April | 6858711.63 | 15851.20 | 11-APR-03:57 | 5.00 |
May | 5209905.65 | 4710.38 | 08-MAY-04:05 | 8.98 |
June | 1304008.66 | 4162.35 | 01-JUN-04:05 | 8.90 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 352150.61 | 2261.22 | 03-AUG-04:06 | 11.72 |
September | 841159.39 | 1893.79 | 05-SEP-04:06 | 11.52 |
October | 3241681.19 | 4113.35 | 05-OCT-04:05 | 9.22 |
November | 4888011.24 | 3856.42 | 24-NOV-05:03 | 2.70 |
December | 97514981.27 | 63265.69 | 23-DEC-05:24 | 3.60 |
Annual Sum or Average | 0.696030E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.2 | |
Maximum of Months | 0.305456E+09 | 81909.26 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.93 |
May | 6029.18 | 80.39 | 05-MAY-04:02 | 13.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.83 |
July | 87433.56 | 1165.78 | 19-JUL-04:02 | 13.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.40 |
Annual Sum or Average | 93462.74 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 87433.56 | 1165.78 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117915E+11 | 6902.89 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.106801E+11 | 6902.89 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.119793E+11 | 6902.89 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.114574E+11 | 6902.89 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.118854E+11 | 6902.89 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.115789E+11 | 6902.89 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.117653E+11 | 6902.89 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.119793E+11 | 6902.89 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.114602E+11 | 6902.89 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.117901E+11 | 6902.89 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.114146E+11 | 6902.89 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.117667E+11 | 6902.89 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.139549E+12 | 0.125277E+12 | ||||
Minimum of Months | 0.106801E+11 | 6902.89 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.119793E+11 | 6902.89 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.244214E+10 | 1429.66 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.221197E+10 | 1429.66 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.248103E+10 | 1429.66 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.237295E+10 | 1429.66 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.246159E+10 | 1429.66 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.239811E+10 | 1429.66 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.243671E+10 | 1429.66 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.248103E+10 | 1429.66 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.237352E+10 | 1429.66 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.244186E+10 | 1429.66 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.236408E+10 | 1429.66 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.243700E+10 | 1429.66 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.289020E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.221197E+10 | 1429.66 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.248103E+10 | 1429.66 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.117915E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131618E+11 |
February | 0.272721E+11 | 0.106801E+11 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107410E+11 |
March | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973565E+10 |
April | 0.292871E+11 | 0.114574E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34084416.27 | 0.757961E+10 |
May | 0.303219E+11 | 0.118854E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1920651.64 | 0.634306E+10 |
June | 0.295292E+11 | 0.115789E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20886609.34 | 0.471597E+10 |
July | 0.300798E+11 | 0.117653E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197207E+09 | 0.356561E+10 |
August | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462807E+09 | 0.304998E+10 |
September | 0.292871E+11 | 0.114602E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2988009.86 | 0.495294E+10 |
October | 0.300980E+11 | 0.117901E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751981E+10 |
November | 0.290996E+11 | 0.114146E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999332E+10 |
December | 0.300798E+11 | 0.117667E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122600E+11 |
Annual Sum or Average | 0.356244E+12 | 0.139549E+12 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719893E+09 | 0.936188E+11 |
Minimum of Months | 0.272721E+11 | 0.106801E+11 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304998E+10 |
Maximum of Months | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462807E+09 | 0.131618E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.244214E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657346E+09 |
February | 0.732850E+09 | 0.221197E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557281E+09 |
March | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565423E+09 |
April | 0.786997E+09 | 0.237295E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 141481.30 | 0.512878E+09 |
May | 0.814802E+09 | 0.246159E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411721E+09 |
June | 0.793501E+09 | 0.239811E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 16694.41 | 0.340641E+09 |
July | 0.808298E+09 | 0.243671E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1432692.54 | 0.267723E+09 |
August | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3535770.52 | 0.240474E+09 |
September | 0.786997E+09 | 0.237352E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191898E+09 |
October | 0.808786E+09 | 0.244186E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454398E+09 |
November | 0.781956E+09 | 0.236408E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542362E+09 |
December | 0.808298E+09 | 0.243700E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555216E+09 |
Annual Sum or Average | 0.957291E+10 | 0.289020E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 5126638.77 | 0.529736E+10 |
Minimum of Months | 0.732850E+09 | 0.221197E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191898E+09 |
Maximum of Months | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3535770.52 | 0.657346E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441973E+09 | 0.961104E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433302E+09 | 0.151261E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418840E+09 | 0.253595E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327667E+09 | 0.369462E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351176E+09 | 0.496122E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327790E+09 | 0.500854E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350197E+09 | 0.536695E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428844E+09 | 0.413159E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727711E+09 | 0.348789E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522348E+09 | 0.192455E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449614E+09 | 0.112618E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656293E+09 | 0.842200E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543575E+10 | 0.355534E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327667E+09 | 0.842200E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727711E+09 | 0.536695E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 6902.89 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 15527.88 | 07-JAN-20:00 |
February | 30255.31 | 04-FEB-19:10 | 6902.89 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 16779.80 | 18-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 6902.89 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 11486.89 | 04-MAR-20:00 |
April | 30255.31 | 01-APR-18:10 | 6902.89 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1382.43 | 01-APR-17:03 | 10009.54 | 17-APR-19:00 |
May | 30255.31 | 06-MAY-18:10 | 6902.89 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 269.64 | 05-MAY-16:00 | 9082.04 | 17-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 6902.89 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1524.95 | 28-JUN-17:03 | 6692.37 | 06-JUN-17:53 |
July | 30255.31 | 01-JUL-18:10 | 6902.89 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2953.70 | 24-JUL-18:00 | 5460.17 | 01-JUL-18:55 |
August | 30255.31 | 05-AUG-18:10 | 6902.89 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4488.39 | 10-AUG-17:03 | 5583.43 | 02-AUG-17:52 |
September | 30255.31 | 02-SEP-18:10 | 6902.89 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 412.76 | 14-SEP-17:00 | 6623.83 | 27-SEP-20:00 |
October | 30255.31 | 07-OCT-18:10 | 6902.89 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 9086.44 | 31-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 6902.89 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 11971.60 | 13-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 6902.89 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 13889.14 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 6902.89 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5460.17 | |||||
Maximum of Months | 30255.31 | 6902.89 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4488.39 | 16779.80 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1429.66 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1742.69 | 28-JAN-04:20 |
February | 813.01 | 04-FEB-19:10 | 1429.66 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1493.22 | 16-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 1429.66 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1363.24 | 29-MAR-00:03 |
April | 813.01 | 01-APR-18:10 | 1429.66 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 14.83 | 01-APR-15:55 | 1485.89 | 08-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 1429.66 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 982.97 | 17-MAY-24:00 |
June | 813.01 | 03-JUN-18:10 | 1429.66 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 3.75 | 28-JUN-16:53 | 1439.29 | 13-JUN-03:20 |
July | 813.01 | 01-JUL-18:10 | 1429.66 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 26.70 | 24-JUL-14:10 | 838.68 | 02-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 1429.66 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 43.57 | 08-AUG-16:53 | 1168.80 | 11-AUG-04:00 |
September | 813.01 | 02-SEP-18:10 | 1429.66 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 704.15 | 19-SEP-00:40 |
October | 813.01 | 07-OCT-18:10 | 1429.66 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1201.11 | 28-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 1429.66 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1391.15 | 30-NOV-00:25 |
December | 813.01 | 02-DEC-19:10 | 1429.66 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1296.37 | 17-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1429.66 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 704.15 | ||||||
Maximum of Months | 813.01 | 1429.66 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 43.57 | 1742.69 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172.91 | 09-JAN-03:10 | 3979.04 | 20-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.39 | 27-FEB-03:55 | 4420.99 | 08-FEB-13:40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1322.63 | 01-MAR-21:00 | 6487.77 | 14-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1316.37 | 27-APR-01:51 | 7193.84 | 18-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1204.62 | 15-MAY-03:00 | 8324.28 | 31-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.76 | 09-JUN-04:40 | 7632.90 | 09-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.15 | 08-JUL-02:53 | 7648.96 | 13-JUL-13:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1351.95 | 09-AUG-05:35 | 7276.98 | 06-AUG-12:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.98 | 10-SEP-05:00 | 6559.01 | 02-SEP-12:50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.04 | 12-OCT-03:00 | 5036.23 | 11-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.30 | 04-NOV-20:00 | 4133.36 | 04-NOV-13:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1813.71 | 06-DEC-04:00 | 3336.31 | 06-DEC-12:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172.91 | 3336.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1813.71 | 8324.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56757.81 | 07-JAN-00:01 | 16808.50 | 15339.75 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.56 |
February | 60134.99 | 19-FEB-00:01 | 16808.50 | 15339.75 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.16 |
March | 42513.88 | 05-MAR-00:01 | 16808.50 | 15339.75 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.36 |
April | 42129.33 | 18-APR-23:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 981.10 |
May | 36212.61 | 17-MAY-23:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.11 |
June | 34251.82 | 01-JUN-04:02 | 10085.10 | 9203.85 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.22 |
July | 66041.05 | 24-JUL-01:22 | 0.00 | 6902.89 | 4344.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 |
August | 74054.33 | 15-AUG-00:42 | 0.00 | 6902.89 | 2896.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.99 |
September | 29955.43 | 06-SEP-04:02 | 8404.25 | 7669.88 | 14482.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 |
October | 34237.84 | 05-OCT-04:02 | 10085.10 | 9203.85 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 |
November | 47228.20 | 12-NOV-00:01 | 16808.50 | 15339.75 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55138.90 | 26-DEC-00:01 | 16808.50 | 11504.81 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 29955.43 | 0.00 | 6902.89 | 2896.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74054.33 | 16808.50 | 15339.75 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 62372.58 | 13-JAN-04:21 | 0.00 | 1667.94 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 863.90 |
February | 47051.65 | 28-FEB-04:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 313.28 |
March | 47404.01 | 09-MAR-01:42 | 0.00 | 1429.66 | 13612.11 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 158.96 |
April | 58430.84 | 11-APR-03:21 | 0.00 | 1667.94 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.08 |
May | 50912.13 | 12-MAY-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 190.33 |
June | 49248.65 | 02-JUN-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 398.83 |
July | 48201.82 | 18-JUL-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 229.21 |
August | 44809.98 | 22-AUG-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 293.04 |
September | 48727.60 | 29-SEP-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51319.00 | 03-OCT-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 484.33 |
November | 47231.82 | 03-NOV-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 421.67 |
December | 42895.47 | 26-DEC-04:21 | 0.00 | 1667.94 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 323.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 42895.47 | 0.00 | 1429.66 | 13612.11 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62372.58 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.05 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.10 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 |
May | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.35 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.29 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.58 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.84 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.52 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.49 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.69 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.49 | 14.77 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.100017E+12 | 52092.42 | 05-JAN-17:49 | 0.175131E+12 | 130140.03 | 06-JAN-07:00 |
February | 0.898114E+11 | 52136.90 | 27-FEB-17:49 | 0.143712E+12 | 127848.75 | 19-FEB-07:40 |
March | 0.988582E+11 | 52089.61 | 02-MAR-17:49 | 0.129555E+12 | 113329.06 | 01-MAR-07:10 |
April | 0.961778E+11 | 68400.00 | 27-APR-17:19 | 0.103842E+12 | 98998.37 | 18-APR-06:30 |
May | 0.100127E+12 | 64800.72 | 05-MAY-17:00 | 0.902813E+11 | 82229.98 | 11-MAY-06:19 |
June | 0.992771E+11 | 69235.44 | 28-JUN-17:19 | 0.736484E+11 | 61569.25 | 07-JUN-06:19 |
July | 0.108908E+12 | 73597.33 | 31-JUL-10:00 | 0.707349E+11 | 46204.49 | 04-JUL-05:19 |
August | 0.114088E+12 | 75809.39 | 10-AUG-17:19 | 0.704005E+11 | 45030.68 | 03-AUG-09:20 |
September | 0.100010E+12 | 66253.85 | 14-SEP-16:49 | 0.740579E+11 | 69197.27 | 28-SEP-06:19 |
October | 0.993273E+11 | 56597.57 | 04-OCT-11:00 | 0.977673E+11 | 82302.87 | 16-OCT-06:49 |
November | 0.967407E+11 | 55665.67 | 04-NOV-16:49 | 0.130526E+12 | 107984.90 | 13-NOV-08:09 |
December | 0.100177E+12 | 52092.89 | 30-DEC-17:40 | 0.163155E+12 | 124343.81 | 26-DEC-07:30 |
Annual Sum or Average | 0.120352E+13 | 0.132281E+13 | ||||
Minimum of Months | 0.898114E+11 | 52089.61 | 0.704005E+11 | 45030.68 | ||
Maximum of Months | 0.114088E+12 | 75809.39 | 0.175131E+12 | 130140.03 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.142337E+11 | 0.780722E+10 | 0.391293E+11 | 0.00 | 0.266393E+11 | 37879553.69 | 0.00 | 21508987.08 | 0.00 | 0.00 | 0.00 | 0.655896E+10 | 0.00 |
February | 0.128921E+11 | 0.643643E+10 | 0.353426E+11 | 0.00 | 0.240661E+11 | 34213790.43 | 0.00 | 52974192.88 | 0.00 | 0.00 | 0.00 | 0.593590E+10 | 0.00 |
March | 0.144603E+11 | 0.628259E+10 | 0.391293E+11 | 0.00 | 0.266419E+11 | 37879553.69 | 0.00 | 82376378.10 | 0.00 | 0.00 | 0.00 | 0.662777E+10 | 0.00 |
April | 0.138304E+11 | 0.523320E+10 | 0.378671E+11 | 0.00 | 0.257946E+11 | 36657632.61 | 0.00 | 0.163360E+10 | 0.00 | 0.00 | 0.00 | 0.636663E+10 | 0.00 |
May | 0.143470E+11 | 0.464807E+10 | 0.391293E+11 | 0.00 | 0.266803E+11 | 37879553.69 | 0.00 | 0.307997E+10 | 0.00 | 0.00 | 0.00 | 0.659393E+10 | 0.00 |
June | 0.139770E+11 | 0.409041E+10 | 0.378671E+11 | 0.00 | 0.258644E+11 | 36657632.61 | 0.00 | 0.559483E+10 | 0.00 | 0.00 | 0.00 | 0.640956E+10 | 0.00 |
July | 0.142020E+11 | 0.441457E+10 | 0.391293E+11 | 0.00 | 0.268310E+11 | 37879553.69 | 0.00 | 0.121289E+11 | 0.00 | 0.00 | 0.00 | 0.655096E+10 | 0.00 |
August | 0.144603E+11 | 0.506838E+10 | 0.391293E+11 | 0.00 | 0.269659E+11 | 37879553.69 | 0.00 | 0.161564E+11 | 0.00 | 0.00 | 0.00 | 0.662883E+10 | 0.00 |
September | 0.138337E+11 | 0.571120E+10 | 0.378671E+11 | 0.00 | 0.259041E+11 | 36657632.61 | 0.00 | 0.483914E+10 | 0.00 | 0.00 | 0.00 | 0.636788E+10 | 0.00 |
October | 0.142320E+11 | 0.677707E+10 | 0.391293E+11 | 0.00 | 0.266716E+11 | 37879553.69 | 0.00 | 0.316858E+09 | 0.00 | 0.00 | 0.00 | 0.655745E+10 | 0.00 |
November | 0.137787E+11 | 0.732648E+10 | 0.378671E+11 | 0.00 | 0.257928E+11 | 36657632.61 | 0.00 | 0.171795E+09 | 0.00 | 0.00 | 0.00 | 0.634773E+10 | 0.00 |
December | 0.142037E+11 | 0.800776E+10 | 0.391293E+11 | 0.00 | 0.266362E+11 | 37879553.69 | 0.00 | 20197202.53 | 0.00 | 0.00 | 0.00 | 0.655109E+10 | 0.00 |
Annual Sum or Average | 0.168451E+12 | 0.718034E+11 | 0.460716E+12 | 0.00 | 0.314488E+12 | 0.446001E+09 | 0.00 | 0.440985E+11 | 0.00 | 0.00 | 0.00 | 0.774967E+11 | 0.00 |
Minimum of Months | 0.128921E+11 | 0.409041E+10 | 0.353426E+11 | 0.00 | 0.240661E+11 | 34213790.43 | 0.00 | 20197202.53 | 0.00 | 0.00 | 0.00 | 0.593590E+10 | 0.00 |
Maximum of Months | 0.144603E+11 | 0.800776E+10 | 0.391293E+11 | 0.00 | 0.269659E+11 | 37879553.69 | 0.00 | 0.161564E+11 | 0.00 | 0.00 | 0.00 | 0.662883E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.102616E+12 | 0.00 | 0.326149E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.779804E+11 | 0.00 | 0.296930E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.568511E+11 | 0.00 | 0.328045E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.344658E+11 | 0.00 | 0.307636E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.195726E+11 | 0.00 | 0.308090E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.609357E+10 | 0.00 | 0.289422E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.195196E+10 | 0.00 | 0.288832E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.151960E+10 | 0.00 | 0.289812E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.725415E+10 | 0.00 | 0.281912E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.280299E+11 | 0.00 | 0.298377E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.620157E+11 | 0.00 | 0.298979E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.913903E+11 | 0.00 | 0.318648E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.489741E+12 | 0.00 | 0.363283E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.151960E+10 | 0.00 | 0.281912E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.102616E+12 | 0.00 | 0.328045E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8332.55 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 11581.35 | 01-JAN-00:20 | 17.86 | 12-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 8332.55 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 11581.35 | 01-FEB-05:30 | 17.86 | 03-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 8332.55 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 11581.35 | 01-MAR-00:49 | 17.86 | 30-MAR-23:10 | 0.00 | 01-MAR-00:10 |
April | 8332.55 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 11581.35 | 01-APR-06:10 | 17.86 | 03-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 8332.55 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 11581.35 | 01-MAY-05:30 | 17.86 | 18-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 8332.55 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 11581.35 | 01-JUN-05:00 | 17.86 | 11-JUN-09:30 | 0.00 | 01-JUN-00:10 |
July | 8332.55 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 11581.35 | 01-JUL-04:40 | 17.86 | 01-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 8332.55 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 11581.35 | 01-AUG-04:30 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 8332.55 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 11581.35 | 01-SEP-04:10 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 8332.55 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 11581.35 | 01-OCT-04:10 | 17.86 | 15-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 8332.55 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 11581.35 | 01-NOV-05:30 | 17.86 | 09-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 8332.55 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 11581.35 | 01-DEC-00:20 | 17.86 | 03-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 8332.55 | 4578.48 | 24699.69 | 0.00 | 11581.35 | 17.86 | 0.00 | ||||||
Maximum of Months | 8332.55 | 4578.48 | 24699.69 | 0.00 | 11581.35 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1539.89 | 13-JAN-04:30 | 0.00 | 0.00 | 0.00 | 4783.58 | 26-JAN-19:10 | 0.00 |
February | 4066.54 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 4784.13 | 23-FEB-07:00 | 0.00 |
March | 4657.17 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 4784.12 | 23-MAR-18:10 | 0.00 |
April | 21345.67 | 27-APR-17:19 | 0.00 | 0.00 | 0.00 | 4784.25 | 25-APR-06:30 | 0.00 |
May | 17684.08 | 05-MAY-17:00 | 0.00 | 0.00 | 0.00 | 4784.25 | 05-MAY-18:30 | 0.00 |
June | 22163.64 | 28-JUN-17:19 | 0.00 | 0.00 | 0.00 | 4784.31 | 01-JUN-18:10 | 0.00 |
July | 25545.50 | 31-JUL-17:19 | 0.00 | 0.00 | 0.00 | 4784.31 | 19-JUL-18:10 | 0.00 |
August | 28807.28 | 10-AUG-17:49 | 0.00 | 0.00 | 0.00 | 4784.49 | 02-AUG-18:10 | 0.00 |
September | 19441.04 | 14-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4784.30 | 19-SEP-18:40 | 0.00 |
October | 8469.38 | 04-OCT-16:10 | 0.00 | 0.00 | 0.00 | 4784.12 | 03-OCT-18:40 | 0.00 |
November | 8836.52 | 04-NOV-15:09 | 0.00 | 0.00 | 0.00 | 4783.97 | 21-NOV-19:40 | 0.00 |
December | 629.96 | 29-DEC-01:10 | 0.00 | 0.00 | 0.00 | 4783.64 | 06-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 629.96 | 0.00 | 0.00 | 0.00 | 4783.58 | 0.00 | ||
Maximum of Months | 28807.28 | 0.00 | 0.00 | 0.00 | 4784.49 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52092.42 | 05-JAN-17:49 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 11581.35 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 52136.90 | 27-FEB-17:49 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 11581.35 | 17.86 | 0.00 | 158.75 | 0.00 |
March | 52089.61 | 02-MAR-17:49 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 11581.35 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 68400.00 | 27-APR-17:19 | 8332.55 | 20676.91 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 21345.67 | 0.00 |
May | 64800.72 | 05-MAY-17:00 | 8332.55 | 20676.91 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 17684.08 | 0.00 |
June | 69235.44 | 28-JUN-17:19 | 8332.55 | 20676.91 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 22163.64 | 0.00 |
July | 73597.33 | 31-JUL-10:00 | 8332.55 | 24699.69 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 22728.54 | 0.00 |
August | 75809.39 | 10-AUG-17:19 | 8332.55 | 20676.91 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 28720.62 | 0.00 |
September | 66253.85 | 14-SEP-16:49 | 8332.55 | 22286.02 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 18743.16 | 0.00 |
October | 56597.57 | 04-OCT-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 8252.07 | 0.00 |
November | 55665.67 | 04-NOV-16:49 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 11581.35 | 17.86 | 0.00 | 3774.48 | 0.00 |
December | 52092.89 | 30-DEC-17:40 | 8332.55 | 22286.02 | 4578.48 | 0.00 | 11581.35 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 52089.61 | 8332.55 | 20676.91 | 0.00 | 0.00 | 11581.35 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75809.39 | 8332.55 | 24699.69 | 4578.48 | 0.00 | 11581.35 | 17.86 | 0.00 | 28720.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 93728.74 | 15-JAN-07:00 | 0.00 | 29656.50 | 31-JAN-07:49 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 101707.32 | 19-FEB-06:10 | 0.00 | 29703.33 | 08-FEB-07:49 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 75633.50 | 01-MAR-06:00 | 0.00 | 29572.04 | 01-MAR-19:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 67145.32 | 19-APR-05:10 | 0.00 | 28543.94 | 03-APR-18:30 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 53045.72 | 11-MAY-04:19 | 0.00 | 27023.36 | 02-MAY-06:40 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 37014.29 | 15-JUN-04:19 | 0.00 | 25085.85 | 02-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 20261.30 | 04-JUL-04:00 | 0.00 | 23391.10 | 03-JUL-18:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 18653.05 | 21-AUG-04:00 | 0.00 | 22555.86 | 25-AUG-18:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 42471.30 | 27-SEP-04:19 | 0.00 | 23689.79 | 28-SEP-06:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 47460.93 | 13-OCT-04:19 | 0.00 | 25618.99 | 31-OCT-06:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 75150.50 | 11-NOV-06:00 | 0.00 | 27442.87 | 30-NOV-07:49 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 83190.16 | 26-DEC-07:10 | 0.00 | 28836.17 | 29-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 18653.05 | 0.00 | 22555.86 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 101707.32 | 0.00 | 29703.33 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.61 | 0.00 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.60 | 0.00 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.32 | 0.00 | 20.32 | 15.33 | 24.60 | 0.00 | 24.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.32 | 0.00 | 20.32 | 11.17 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.43 | 0.00 | 27.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.49 | 0.00 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.61 | 0.00 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.75 | 0.00 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.97 | 0.00 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 28.19 | 0.00 | 28.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.34 | 0.00 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.42 | 0.00 | 28.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 28.34 | 0.00 | 28.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.99 | 0.00 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.76 | 0.00 | 27.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.56 | 0.00 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 365.00 | 27.91 | 0.00 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.43 | 0.00 | 27.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.42 | 0.00 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.75 | 75.17 | 20.55 | 75.17 | 20.39 |
February | 543.83 | 20.77 | 63.67 | 20.59 | 63.17 | 20.44 |
March | 601.67 | 20.83 | 40.00 | 20.64 | 40.00 | 20.46 |
April | 517.50 | 20.96 | 66.83 | 21.02 | 24.00 | 20.87 |
May | 453.33 | 21.14 | 131.67 | 21.60 | 15.50 | 21.49 |
June | 295.33 | 21.28 | 248.00 | 22.46 | 2.50 | 22.44 |
July | 200.17 | 21.51 | 364.67 | 23.08 | 0.00 | 23.08 |
August | 160.50 | 21.51 | 419.83 | 23.27 | 2.17 | 23.27 |
September | 325.17 | 21.23 | 223.33 | 22.28 | 1.83 | 22.27 |
October | 535.67 | 20.98 | 55.17 | 21.05 | 18.33 | 20.93 |
November | 579.67 | 20.82 | 40.33 | 20.70 | 30.50 | 20.54 |
December | 609.00 | 20.75 | 52.33 | 20.53 | 52.33 | 20.35 |
Annual Sum or Average | 5431.83 | 20.95 | 1781.00 | 21.43 | 325.50 | 21.29 |
Minimum of Months | 160.50 | 20.75 | 40.00 | 20.53 | 0.00 | 20.35 |
Maximum of Months | 610.00 | 21.51 | 419.83 | 23.27 | 75.17 | 23.27 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 279.50 | 25.99 | 610.00 | 25.99 | 279.50 | 25.99 |
February | 270.33 | 25.99 | 551.00 | 25.99 | 270.33 | 25.99 |
March | 346.00 | 25.99 | 612.00 | 25.99 | 346.00 | 25.99 |
April | 384.83 | 25.99 | 590.00 | 25.99 | 384.83 | 25.99 |
May | 436.83 | 25.99 | 611.00 | 25.99 | 436.83 | 25.99 |
June | 465.33 | 26.00 | 592.00 | 26.00 | 465.33 | 26.00 |
July | 524.00 | 26.00 | 609.00 | 26.00 | 524.00 | 26.00 |
August | 558.50 | 26.00 | 612.00 | 26.00 | 558.50 | 26.00 |
September | 483.67 | 26.00 | 590.00 | 26.00 | 483.67 | 26.00 |
October | 419.00 | 25.99 | 610.00 | 25.99 | 419.00 | 25.99 |
November | 374.00 | 25.99 | 591.00 | 25.99 | 374.00 | 25.99 |
December | 323.67 | 25.99 | 609.00 | 25.99 | 323.67 | 25.99 |
Annual Sum or Average | 4865.67 | 25.99 | 7187.00 | 25.99 | 4865.67 | 25.99 |
Minimum of Months | 270.33 | 25.99 | 551.00 | 25.99 | 270.33 | 25.99 |
Maximum of Months | 558.50 | 26.00 | 612.00 | 26.00 | 558.50 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.74760 | 32.26208 | -0.4263 | 9.70323 |
February | 551.00000 | 20.81242 | 34.14143 | -0.3726 | 9.10090 |
March | 612.00000 | 20.88149 | 35.56767 | -0.3132 | 8.19539 |
April | 590.00000 | 21.31061 | 39.89284 | -0.1530 | 7.61208 |
May | 611.00000 | 21.81536 | 44.21913 | -1.0195 | 30.67977 |
June | 592.00000 | 22.54313 | 45.68323 | -0.7368 | 20.49252 |
July | 609.00000 | 23.07826 | 48.33414 | -0.5139 | 14.18139 |
August | 612.00000 | 23.24661 | 51.62569 | -0.4308 | 12.08640 |
September | 590.00000 | 22.34713 | 51.67562 | -0.7615 | 21.69094 |
October | 610.00000 | 21.29184 | 44.44265 | -0.1222 | 6.82556 |
November | 591.00000 | 20.87785 | 41.24053 | -0.2920 | 7.93314 |
December | 609.00000 | 20.74672 | 34.42454 | -0.3990 | 9.21766 |
Annual Sum or Average | 7187.00000 | 21.64730 | 41.99598 | -0.4623 | 13.16458 |
Minimum of Months | 551.00000 | 20.74672 | 32.26208 | -1.0195 | 6.82556 |
Maximum of Months | 612.00000 | 23.24661 | 51.67562 | -0.1222 | 30.67977 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.99298 | 39.81696 | 0.96588 | 24.97257 |
February | 551.00000 | 25.99143 | 40.23565 | 0.98169 | 25.68091 |
March | 612.00000 | 25.99401 | 39.21206 | 1.00036 | 26.41812 |
April | 590.00000 | 25.99463 | 40.93547 | 1.05015 | 28.59899 |
May | 611.00000 | 25.99551 | 42.89729 | 0.48562 | 10.56846 |
June | 592.00000 | 25.99706 | 43.14116 | 0.53871 | 11.62063 |
July | 609.00000 | 25.99839 | 45.89225 | 0.60034 | 13.20865 |
August | 612.00000 | 25.99920 | 48.37085 | 0.62583 | 13.81707 |
September | 590.00000 | 25.99595 | 47.33939 | 0.56496 | 12.25565 |
October | 610.00000 | 25.99322 | 42.24955 | 1.07759 | 29.71314 |
November | 591.00000 | 25.99319 | 42.47808 | 1.04043 | 28.13097 |
December | 609.00000 | 25.99311 | 40.22313 | 0.98401 | 25.71260 |
Annual Sum or Average | 7187.00000 | 25.99492 | 42.74550 | 0.82524 | 20.85736 |
Minimum of Months | 551.00000 | 25.99143 | 39.21206 | 0.48562 | 10.56846 |
Maximum of Months | 612.00000 | 25.99920 | 48.37085 | 1.07759 | 29.71314 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 40128905.60 | 14469272.26 | 4.33 | 36644806.86 | 3484098.74 | 0.00 | 0.11 | 27-FEB-15:00 | 0.00 | 01-FEB-00:01 | 7266.86 | 27-FEB-15:00 | 6816.57 | 27-FEB-15:00 | 450.28 | 27-FEB-15:00 | 2588.85 | 27-FEB-15:00 | 0.00 | 01-FEB-00:01 |
March | 87589118.95 | 31397352.52 | 5.00 | 87576680.52 | 12438.43 | 0.00 | 0.12 | 18-MAR-16:00 | 0.00 | 01-MAR-00:01 | 7842.19 | 18-MAR-16:00 | 7842.19 | 18-MAR-16:00 | 20.73 | 18-MAR-13:40 | 2788.29 | 18-MAR-16:00 | 0.00 | 01-MAR-00:01 |
April | 0.318399E+10 | 0.106061E+10 | 46.22 | 0.297295E+10 | 0.211034E+09 | 0.00 | 0.61 | 27-APR-17:10 | 0.00 | 01-APR-00:01 | 46014.47 | 27-APR-17:10 | 41458.34 | 27-APR-17:13 | 5292.84 | 27-APR-19:00 | 14462.27 | 27-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.595875E+10 | 0.201717E+10 | 93.81 | 0.497647E+10 | 0.982281E+09 | 0.00 | 0.52 | 05-MAY-18:00 | 0.00 | 01-MAY-00:02 | 38643.75 | 05-MAY-18:00 | 32873.39 | 15-MAY-17:02 | 10675.32 | 05-MAY-18:00 | 12335.87 | 05-MAY-18:00 | 0.00 | 01-MAY-00:02 |
June | 0.108735E+11 | 0.367660E+10 | 191.91 | 0.949497E+10 | 0.137849E+10 | 0.00 | 0.64 | 28-JUN-17:10 | 0.00 | 01-JUN-00:01 | 48586.49 | 28-JUN-17:10 | 44601.82 | 28-JUN-17:03 | 8644.50 | 29-JUN-00:40 | 15152.20 | 28-JUN-17:10 | 0.00 | 01-JUN-00:01 |
July | 0.248838E+11 | 0.814548E+10 | 301.20 | 0.202042E+11 | 0.467964E+10 | 0.00 | 1.00 | 24-JUL-00:42 | 0.00 | 01-JUL-00:01 | 84053.89 | 31-JUL-00:42 | 63302.39 | 24-JUL-00:42 | 28296.73 | 31-JUL-03:21 | 23680.14 | 24-JUL-00:42 | 0.00 | 01-JUL-00:01 |
August | 0.343171E+11 | 0.110054E+11 | 363.15 | 0.280185E+11 | 0.629854E+10 | 0.00 | 1.00 | 08-AUG-00:09 | 0.00 | 01-AUG-00:01 | 84053.89 | 25-AUG-00:09 | 70463.96 | 15-AUG-00:42 | 35250.24 | 26-AUG-00:42 | 23680.14 | 08-AUG-00:09 | 0.00 | 01-AUG-00:01 |
September | 0.965198E+10 | 0.323170E+10 | 147.67 | 0.731815E+10 | 0.233382E+10 | 0.00 | 0.59 | 14-SEP-17:10 | 0.00 | 01-SEP-00:01 | 44210.90 | 14-SEP-17:10 | 36652.56 | 14-SEP-17:03 | 13323.22 | 14-SEP-13:00 | 13972.01 | 14-SEP-17:10 | 0.00 | 01-SEP-00:01 |
October | 0.496663E+09 | 0.173928E+09 | 18.62 | 0.484119E+09 | 12544210.89 | 0.00 | 0.25 | 04-OCT-16:03 | 0.00 | 01-OCT-00:01 | 17356.82 | 04-OCT-16:03 | 17356.82 | 04-OCT-16:03 | 1547.16 | 08-OCT-14:00 | 5975.73 | 04-OCT-16:03 | 0.00 | 01-OCT-00:01 |
November | 0.229930E+09 | 80331694.79 | 5.83 | 0.161557E+09 | 68373428.22 | 0.00 | 0.23 | 04-NOV-14:00 | 0.00 | 01-NOV-00:01 | 15952.51 | 04-NOV-14:00 | 11543.02 | 04-NOV-14:00 | 4812.47 | 04-NOV-13:00 | 5518.04 | 04-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.897234E+11 | 0.294371E+11 | 1177.76 | 0.737552E+11 | 0.159682E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.343171E+11 | 0.110054E+11 | 363.15 | 0.280185E+11 | 0.629854E+10 | 0.00 | 1.00 | 0.00 | 84053.89 | 70463.96 | 35250.24 | 23680.14 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 66638652.61 | 21508987.08 | 8.61 | 45498264.93 | 21140387.68 | 0.00 | 1.00 | 13-JAN-04:21 | 0.00 | 01-JAN-00:01 | 34661.51 | 13-JAN-04:21 | 23566.52 | 13-JAN-04:21 | 11094.99 | 13-JAN-04:21 | 9021.71 | 13-JAN-04:21 | 0.00 | 01-JAN-00:01 |
February | 0.121383E+09 | 38504920.62 | 13.05 | 87373046.31 | 34009480.32 | 0.00 | 1.00 | 24-FEB-04:21 | 0.00 | 01-FEB-00:01 | 34661.51 | 24-FEB-04:21 | 19682.40 | 28-FEB-04:21 | 15377.01 | 24-FEB-04:21 | 9021.71 | 24-FEB-04:21 | 0.00 | 01-FEB-00:01 |
March | 0.160487E+09 | 50979025.58 | 14.06 | 0.127158E+09 | 33329603.61 | 0.00 | 1.00 | 09-MAR-01:42 | 0.00 | 01-MAR-00:01 | 34661.51 | 09-MAR-02:22 | 21737.90 | 09-MAR-03:02 | 17413.11 | 10-MAR-04:21 | 9021.71 | 09-MAR-01:42 | 0.00 | 01-MAR-00:01 |
April | 0.192175E+10 | 0.572987E+09 | 61.23 | 0.163183E+10 | 0.289927E+09 | 0.00 | 1.00 | 02-APR-03:21 | 0.00 | 01-APR-00:01 | 34661.51 | 03-APR-00:42 | 28698.69 | 02-APR-03:21 | 16133.81 | 14-APR-03:21 | 9021.71 | 02-APR-03:21 | 0.00 | 01-APR-00:01 |
May | 0.346898E+10 | 0.106280E+10 | 114.22 | 0.275913E+10 | 0.709844E+09 | 0.00 | 1.00 | 02-MAY-03:21 | 0.00 | 01-MAY-00:02 | 34661.51 | 07-MAY-03:21 | 26040.13 | 14-MAY-00:42 | 17449.82 | 07-MAY-00:42 | 9021.71 | 02-MAY-03:21 | 0.00 | 01-MAY-00:02 |
June | 0.624964E+10 | 0.191824E+10 | 215.66 | 0.519820E+10 | 0.105144E+10 | 0.00 | 1.00 | 02-JUN-03:21 | 0.00 | 01-JUN-00:01 | 34661.51 | 13-JUN-01:22 | 23618.72 | 10-JUN-03:21 | 16562.68 | 12-JUN-03:21 | 9021.71 | 02-JUN-03:21 | 0.00 | 01-JUN-00:01 |
July | 0.135153E+11 | 0.398340E+10 | 323.77 | 0.101513E+11 | 0.336406E+10 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 34661.51 | 10-JUL-01:22 | 26154.61 | 01-JUL-01:22 | 17644.61 | 16-JUL-03:21 | 9021.71 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 |
August | 0.178041E+11 | 0.515093E+10 | 368.82 | 0.132359E+11 | 0.456814E+10 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 34661.51 | 25-AUG-01:22 | 26467.95 | 15-AUG-00:42 | 18871.24 | 02-AUG-03:21 | 9021.71 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 |
September | 0.528708E+10 | 0.160744E+10 | 167.13 | 0.379629E+10 | 0.149079E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 34661.51 | 02-SEP-03:21 | 22274.45 | 21-SEP-03:21 | 18890.02 | 24-SEP-03:21 | 9021.71 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 |
October | 0.452992E+09 | 0.142930E+09 | 34.97 | 0.370882E+09 | 82110115.36 | 0.00 | 1.00 | 01-OCT-03:22 | 0.00 | 01-OCT-00:01 | 34661.51 | 27-OCT-03:21 | 26926.57 | 04-OCT-01:22 | 16598.86 | 06-OCT-03:21 | 9021.71 | 01-OCT-03:22 | 0.00 | 01-OCT-00:01 |
November | 0.294613E+09 | 91463731.90 | 14.93 | 0.186498E+09 | 0.108115E+09 | 0.00 | 1.00 | 03-NOV-03:21 | 0.00 | 01-NOV-00:01 | 34661.51 | 04-NOV-03:21 | 20354.83 | 27-NOV-04:22 | 17739.19 | 05-NOV-03:21 | 9021.71 | 03-NOV-03:21 | 0.00 | 01-NOV-00:01 |
December | 62184480.47 | 20197202.53 | 8.27 | 41223801.99 | 20960678.48 | 0.00 | 0.45 | 30-DEC-01:04 | 0.00 | 01-DEC-00:01 | 13398.53 | 30-DEC-01:04 | 8266.44 | 14-DEC-01:04 | 5477.67 | 30-DEC-01:04 | 4057.35 | 30-DEC-01:04 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.494051E+11 | 0.146614E+11 | 1344.75 | 0.376313E+11 | 0.117739E+11 | 0.00 | ||||||||||||||
Minimum of Months | 62184480.47 | 20197202.53 | 8.27 | 41223801.99 | 20960678.48 | 0.00 | 0.45 | 0.00 | 13398.53 | 8266.44 | 5477.67 | 4057.35 | 0.00 | |||||||
Maximum of Months | 0.178041E+11 | 0.515093E+10 | 368.82 | 0.132359E+11 | 0.456814E+10 | 0.00 | 1.00 | 0.00 | 34661.51 | 28698.69 | 18890.02 | 9021.71 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.72 | 22.98 | 68.73 | 21.74 | 490.27 | 0.00 | 0.00 | 0.00 |
February | 168.95 | 59.84 | 109.11 | 89.24 | 415.13 | 0.00 | 0.00 | 0.00 |
March | 253.21 | 91.82 | 161.39 | 187.80 | 324.52 | 0.00 | 0.00 | 0.00 |
April | 391.08 | 162.29 | 228.79 | 373.54 | 253.20 | 0.00 | 0.00 | 0.00 |
May | 416.41 | 144.99 | 271.42 | 424.07 | 211.15 | 0.00 | 0.00 | 0.00 |
June | 498.39 | 216.92 | 281.47 | 551.64 | 170.20 | 0.00 | 0.00 | 0.00 |
July | 464.80 | 208.97 | 255.83 | 539.76 | 152.61 | 0.00 | 0.00 | 0.00 |
August | 456.27 | 228.23 | 228.03 | 549.96 | 151.61 | 0.00 | 0.00 | 0.00 |
September | 337.89 | 156.11 | 181.78 | 356.88 | 208.57 | 0.00 | 0.00 | 0.00 |
October | 220.94 | 94.41 | 126.54 | 182.75 | 291.36 | 0.00 | 0.00 | 0.00 |
November | 108.12 | 30.62 | 77.51 | 46.00 | 383.21 | 0.00 | 0.00 | 0.00 |
December | 88.45 | 28.43 | 60.02 | 31.38 | 483.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.89 | 120.74 | 171.16 | 280.55 | 294.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.45 | 22.98 | 60.02 | 21.74 | 151.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 498.39 | 228.23 | 281.47 | 551.64 | 490.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 351.89 | 209.33 | 142.56 | 282.73 | 624.03 | 0.00 | 0.00 | 0.00 |
February | 541.51 | 335.98 | 205.53 | 514.23 | 541.91 | 0.00 | 0.00 | 0.00 |
March | 574.43 | 303.70 | 270.73 | 587.52 | 455.05 | 0.00 | 0.00 | 0.00 |
April | 606.99 | 260.50 | 346.48 | 661.09 | 371.72 | 0.00 | 0.00 | 0.00 |
May | 565.53 | 172.41 | 393.12 | 624.82 | 308.62 | 0.00 | 0.00 | 0.00 |
June | 511.68 | 136.94 | 374.73 | 568.59 | 252.62 | 0.00 | 0.00 | 0.00 |
July | 555.91 | 201.85 | 354.06 | 692.74 | 229.77 | 0.00 | 0.00 | 0.00 |
August | 592.65 | 272.32 | 320.33 | 767.95 | 225.87 | 0.00 | 0.00 | 0.00 |
September | 657.32 | 359.51 | 297.81 | 800.74 | 298.17 | 0.00 | 0.00 | 0.00 |
October | 594.60 | 364.04 | 230.57 | 656.25 | 397.71 | 0.00 | 0.00 | 0.00 |
November | 355.85 | 203.69 | 152.16 | 318.09 | 501.39 | 0.00 | 0.00 | 0.00 |
December | 372.43 | 240.85 | 131.59 | 341.90 | 627.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 523.15 | 254.59 | 268.55 | 568.29 | 402.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 351.89 | 136.94 | 131.59 | 282.73 | 225.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 657.32 | 364.04 | 393.12 | 800.74 | 627.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.73 | 29.07 | 68.66 | 31.58 | 492.99 | 0.00 | 0.00 | 0.00 |
February | 174.33 | 65.45 | 108.88 | 103.72 | 424.51 | 0.00 | 0.00 | 0.00 |
March | 244.21 | 82.57 | 161.65 | 185.85 | 336.67 | 0.00 | 0.00 | 0.00 |
April | 371.09 | 141.70 | 229.39 | 357.06 | 261.93 | 0.00 | 0.00 | 0.00 |
May | 478.43 | 194.78 | 283.65 | 515.67 | 213.82 | 0.00 | 0.00 | 0.00 |
June | 459.12 | 177.92 | 281.19 | 500.33 | 174.35 | 0.00 | 0.00 | 0.00 |
July | 567.56 | 298.25 | 269.32 | 691.56 | 158.59 | 0.00 | 0.00 | 0.00 |
August | 469.72 | 239.58 | 230.13 | 578.09 | 158.91 | 0.00 | 0.00 | 0.00 |
September | 383.76 | 184.60 | 199.16 | 430.95 | 214.41 | 0.00 | 0.00 | 0.00 |
October | 219.46 | 90.22 | 129.24 | 186.12 | 297.86 | 0.00 | 0.00 | 0.00 |
November | 108.68 | 30.90 | 77.79 | 49.58 | 388.49 | 0.00 | 0.00 | 0.00 |
December | 91.74 | 31.85 | 59.89 | 41.38 | 491.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 306.29 | 131.07 | 175.21 | 307.34 | 300.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.74 | 29.07 | 59.89 | 31.58 | 158.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 567.56 | 298.25 | 283.65 | 691.56 | 492.99 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245652E+09 | 61561044.54 | 0.184091E+09 | 58230223.36 | 0.131315E+10 |
February | 0.408732E+09 | 0.144775E+09 | 0.263958E+09 | 0.215898E+09 | 0.100428E+10 |
March | 0.678201E+09 | 0.245929E+09 | 0.432273E+09 | 0.503007E+09 | 0.869188E+09 |
April | 0.101368E+10 | 0.420647E+09 | 0.593035E+09 | 0.968210E+09 | 0.656307E+09 |
May | 0.111531E+10 | 0.388331E+09 | 0.726975E+09 | 0.113584E+10 | 0.565556E+09 |
June | 0.129182E+10 | 0.562255E+09 | 0.729563E+09 | 0.142984E+10 | 0.441164E+09 |
July | 0.124492E+10 | 0.559713E+09 | 0.685205E+09 | 0.144569E+10 | 0.408741E+09 |
August | 0.122206E+10 | 0.611302E+09 | 0.610761E+09 | 0.147302E+10 | 0.406065E+09 |
September | 0.875812E+09 | 0.404641E+09 | 0.471171E+09 | 0.925045E+09 | 0.540613E+09 |
October | 0.591771E+09 | 0.252855E+09 | 0.338916E+09 | 0.489471E+09 | 0.780381E+09 |
November | 0.280256E+09 | 79362648.67 | 0.200893E+09 | 0.119225E+09 | 0.993278E+09 |
December | 0.236900E+09 | 76143742.10 | 0.160757E+09 | 84040279.31 | 0.129525E+10 |
Annual Sum or Average | 0.920511E+10 | 0.380751E+10 | 0.539760E+10 | 0.884752E+10 | 0.927397E+10 |
Minimum of Months | 0.236900E+09 | 61561044.54 | 0.160757E+09 | 58230223.36 | 0.406065E+09 |
Maximum of Months | 0.129182E+10 | 0.611302E+09 | 0.729563E+09 | 0.147302E+10 | 0.131315E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.942510E+09 | 0.560680E+09 | 0.381831E+09 | 0.757258E+09 | 0.167140E+10 |
February | 0.131003E+10 | 0.812802E+09 | 0.497226E+09 | 0.124403E+10 | 0.131099E+10 |
March | 0.153857E+10 | 0.813443E+09 | 0.725123E+09 | 0.157362E+10 | 0.121881E+10 |
April | 0.157331E+10 | 0.675223E+09 | 0.898087E+09 | 0.171355E+10 | 0.963497E+09 |
May | 0.151471E+10 | 0.461791E+09 | 0.105292E+10 | 0.167352E+10 | 0.826612E+09 |
June | 0.132626E+10 | 0.354960E+09 | 0.971302E+09 | 0.147378E+10 | 0.654788E+09 |
July | 0.148895E+10 | 0.540637E+09 | 0.948315E+09 | 0.185544E+10 | 0.615427E+09 |
August | 0.158735E+10 | 0.729378E+09 | 0.857973E+09 | 0.205687E+10 | 0.604981E+09 |
September | 0.170377E+10 | 0.931848E+09 | 0.771924E+09 | 0.207551E+10 | 0.772861E+09 |
October | 0.159258E+10 | 0.975035E+09 | 0.617549E+09 | 0.175771E+10 | 0.106522E+10 |
November | 0.922367E+09 | 0.527969E+09 | 0.394397E+09 | 0.824490E+09 | 0.129961E+10 |
December | 0.997524E+09 | 0.645084E+09 | 0.352441E+09 | 0.915756E+09 | 0.167971E+10 |
Annual Sum or Average | 0.164979E+11 | 0.802885E+10 | 0.846909E+10 | 0.179215E+11 | 0.126839E+11 |
Minimum of Months | 0.922367E+09 | 0.354960E+09 | 0.352441E+09 | 0.757258E+09 | 0.604981E+09 |
Maximum of Months | 0.170377E+10 | 0.975035E+09 | 0.105292E+10 | 0.207551E+10 | 0.167971E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261754E+09 | 77866554.82 | 0.183887E+09 | 84571167.18 | 0.132043E+10 |
February | 0.421738E+09 | 0.158326E+09 | 0.263412E+09 | 0.250910E+09 | 0.102698E+10 |
March | 0.654097E+09 | 0.221145E+09 | 0.432952E+09 | 0.497781E+09 | 0.901725E+09 |
April | 0.961867E+09 | 0.367279E+09 | 0.594588E+09 | 0.925512E+09 | 0.678928E+09 |
May | 0.128142E+10 | 0.521689E+09 | 0.759729E+09 | 0.138118E+10 | 0.572688E+09 |
June | 0.119003E+10 | 0.461177E+09 | 0.728857E+09 | 0.129685E+10 | 0.451925E+09 |
July | 0.152016E+10 | 0.798820E+09 | 0.721343E+09 | 0.185228E+10 | 0.424770E+09 |
August | 0.125809E+10 | 0.641700E+09 | 0.616390E+09 | 0.154835E+10 | 0.425620E+09 |
September | 0.994702E+09 | 0.478491E+09 | 0.516211E+09 | 0.111703E+10 | 0.555744E+09 |
October | 0.587800E+09 | 0.241638E+09 | 0.346162E+09 | 0.498515E+09 | 0.797775E+09 |
November | 0.281708E+09 | 80084302.88 | 0.201624E+09 | 0.128517E+09 | 0.100697E+10 |
December | 0.245713E+09 | 85298439.52 | 0.160414E+09 | 0.110840E+09 | 0.131734E+10 |
Annual Sum or Average | 0.965908E+10 | 0.413351E+10 | 0.552557E+10 | 0.969234E+10 | 0.948091E+10 |
Minimum of Months | 0.245713E+09 | 77866554.82 | 0.160414E+09 | 84571167.18 | 0.424770E+09 |
Maximum of Months | 0.152016E+10 | 0.798820E+09 | 0.759729E+09 | 0.185228E+10 | 0.132043E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.76 | 1557.01 | 541.34 | 261.39 | 279.95 | 0.00 | 0.00 |
February | 656.94 | 1331.30 | 884.80 | 461.27 | 423.53 | 0.00 | 0.00 |
March | 930.61 | 1085.67 | 1071.86 | 478.09 | 593.77 | 0.00 | 0.00 |
April | 1355.79 | 850.95 | 1369.16 | 564.49 | 804.67 | 0.00 | 0.00 |
May | 1538.40 | 707.43 | 1460.36 | 512.18 | 948.19 | 0.00 | 0.00 |
June | 1595.18 | 571.80 | 1469.18 | 531.79 | 937.39 | 0.00 | 0.00 |
July | 1897.29 | 514.20 | 1588.27 | 709.07 | 879.21 | 0.00 | 0.00 |
August | 1869.44 | 509.83 | 1518.63 | 740.14 | 778.50 | 0.00 | 0.00 |
September | 1564.61 | 697.19 | 1378.97 | 700.22 | 678.74 | 0.00 | 0.00 |
October | 1000.23 | 962.03 | 1035.00 | 548.66 | 486.35 | 0.00 | 0.00 |
November | 383.11 | 1242.53 | 572.66 | 265.21 | 307.45 | 0.00 | 0.00 |
December | 367.40 | 1555.29 | 552.62 | 301.12 | 251.50 | 0.00 | 0.00 |
Annual Sum or Average | 1123.06 | 963.80 | 1121.33 | 506.40 | 614.92 | 0.00 | 0.00 |
Minimum of Months | 285.76 | 509.83 | 541.34 | 261.39 | 251.50 | 0.00 | 0.00 |
Maximum of Months | 1897.29 | 1557.01 | 1588.27 | 740.14 | 948.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.765369E+09 | 0.417029E+10 | 0.144992E+10 | 0.700107E+09 | 0.749809E+09 | 0.00 | 0.00 |
February | 0.158927E+10 | 0.322068E+10 | 0.214050E+10 | 0.111590E+10 | 0.102460E+10 | 0.00 | 0.00 |
March | 0.249255E+10 | 0.290786E+10 | 0.287086E+10 | 0.128052E+10 | 0.159035E+10 | 0.00 | 0.00 |
April | 0.351421E+10 | 0.220567E+10 | 0.354886E+10 | 0.146315E+10 | 0.208571E+10 | 0.00 | 0.00 |
May | 0.412046E+10 | 0.189477E+10 | 0.391144E+10 | 0.137181E+10 | 0.253963E+10 | 0.00 | 0.00 |
June | 0.413471E+10 | 0.148211E+10 | 0.380812E+10 | 0.137839E+10 | 0.242972E+10 | 0.00 | 0.00 |
July | 0.508171E+10 | 0.137724E+10 | 0.425403E+10 | 0.189917E+10 | 0.235486E+10 | 0.00 | 0.00 |
August | 0.500710E+10 | 0.136552E+10 | 0.406750E+10 | 0.198238E+10 | 0.208512E+10 | 0.00 | 0.00 |
September | 0.405548E+10 | 0.180712E+10 | 0.357429E+10 | 0.181498E+10 | 0.175931E+10 | 0.00 | 0.00 |
October | 0.267903E+10 | 0.257671E+10 | 0.277215E+10 | 0.146953E+10 | 0.130263E+10 | 0.00 | 0.00 |
November | 0.993014E+09 | 0.322065E+10 | 0.148433E+10 | 0.687416E+09 | 0.796914E+09 | 0.00 | 0.00 |
December | 0.984037E+09 | 0.416570E+10 | 0.148014E+10 | 0.806526E+09 | 0.673611E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.354169E+11 | 0.303943E+11 | 0.353621E+11 | 0.159699E+11 | 0.193923E+11 | 0.00 | 0.00 |
Minimum of Months | 0.765369E+09 | 0.136552E+10 | 0.144992E+10 | 0.687416E+09 | 0.673611E+09 | 0.00 | 0.00 |
Maximum of Months | 0.508171E+10 | 0.417029E+10 | 0.425403E+10 | 0.198238E+10 | 0.253963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.655898E+10 | -0.622530E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333680342.8 | 81.22 | 0.00 | 0.00 |
February | 0.593579E+10 | -0.563441E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -301385519.6 | 81.22 | 0.00 | 0.00 |
March | 0.662764E+10 | -0.629400E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333641541.3 | 81.22 | 0.00 | 0.00 |
April | 0.636643E+10 | -0.604360E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322826711.0 | 81.22 | 0.00 | 0.00 |
May | 0.659386E+10 | -0.626032E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333540762.1 | 81.22 | 0.00 | 0.00 |
June | 0.640941E+10 | -0.608671E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322700274.4 | 81.22 | 0.00 | 0.00 |
July | 0.655066E+10 | -0.621722E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333439919.9 | 81.22 | 0.00 | 0.00 |
August | 0.662878E+10 | -0.629533E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333447573.1 | 81.22 | 0.00 | 0.00 |
September | 0.636761E+10 | -0.604494E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322670077.8 | 81.22 | 0.00 | 0.00 |
October | 0.655748E+10 | -0.622396E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333521723.8 | 81.22 | 0.00 | 0.00 |
November | 0.634758E+10 | -0.602475E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -322831693.2 | 81.22 | 0.00 | 0.00 |
December | 0.655085E+10 | -0.621722E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -333637474.2 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.774951E+11 | -0.735677E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.392732E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.593579E+10 | -0.629533E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -333680342.8 | 81.22 | 0.00 | 0.00 |
Maximum of Months | 0.662878E+10 | -0.563441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -301385519.6 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.239874E+11 | -0.231364E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850943912.8 | 58.99 | 0.00 | 0.00 |
February | 0.218549E+11 | -0.210863E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -768582509.8 | 58.99 | 0.00 | 0.00 |
March | 0.241388E+11 | -0.232880E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850804271.3 | 58.99 | 0.00 | 0.00 |
April | 0.225670E+11 | -0.217439E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -823179894.8 | 58.99 | 0.00 | 0.00 |
May | 0.225298E+11 | -0.216794E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850400597.2 | 58.99 | 0.00 | 0.00 |
June | 0.210954E+11 | -0.202727E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -822673095.4 | 58.99 | 0.00 | 0.00 |
July | 0.209821E+11 | -0.201322E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -849899217.9 | 58.99 | 0.00 | 0.00 |
August | 0.210569E+11 | -0.202071E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -849849340.6 | 58.98 | 0.00 | 0.00 |
September | 0.204928E+11 | -0.196704E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -822411564.8 | 58.99 | 0.00 | 0.00 |
October | 0.217509E+11 | -0.209007E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850220238.1 | 58.99 | 0.00 | 0.00 |
November | 0.218698E+11 | -0.210467E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -823140074.0 | 58.99 | 0.00 | 0.00 |
December | 0.233826E+11 | -0.225318E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850753595.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265708E+12 | -0.255696E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.100129E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.204928E+11 | -0.232880E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -850943912.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.241388E+11 | -0.196704E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -768582509.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.813233E+11 | 78405.71 | 16-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.617995E+11 | 146057.35 | 18-FEB-08:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450545E+11 | 59939.55 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273141E+11 | 53212.66 | 19-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155113E+11 | 42750.50 | 11-MAY-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.482915E+10 | 34883.62 | 01-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154693E+10 | 23297.05 | 05-JUL-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120428E+10 | 24101.23 | 03-AUG-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.574892E+10 | 36358.06 | 27-SEP-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222137E+11 | 41544.03 | 13-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491474E+11 | 59556.77 | 11-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.724268E+11 | 112182.80 | 23-DEC-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.120428E+10 | 23297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.813233E+11 | 146057.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 40128905.60 | 36644806.86 | 7266.86 | 27-FEB-15:00 | 6816.57 | 0.00 |
March | 0.00 | 0.00 | 87589118.95 | 87576680.52 | 7842.19 | 18-MAR-16:00 | 7842.19 | 0.00 |
April | 0.00 | 0.00 | 0.318399E+10 | 0.297295E+10 | 46014.47 | 27-APR-17:10 | 41421.60 | 0.00 |
May | 0.00 | 0.00 | 0.595875E+10 | 0.497647E+10 | 38643.75 | 05-MAY-18:00 | 27968.43 | 0.00 |
June | 0.00 | 0.00 | 0.108735E+11 | 0.949497E+10 | 48586.49 | 28-JUN-17:10 | 44595.86 | 0.00 |
July | 0.00 | 0.00 | 0.248838E+11 | 0.202042E+11 | 84053.89 | 31-JUL-00:42 | 57111.47 | 0.00 |
August | 0.00 | 0.00 | 0.343171E+11 | 0.280185E+11 | 84053.89 | 25-AUG-00:09 | 58717.31 | 0.00 |
September | 0.00 | 0.00 | 0.965198E+10 | 0.731815E+10 | 44210.90 | 14-SEP-17:10 | 36641.82 | 0.00 |
October | 0.00 | 0.00 | 0.496663E+09 | 0.484119E+09 | 17356.82 | 04-OCT-16:03 | 17356.82 | 0.00 |
November | 0.00 | 0.00 | 0.229930E+09 | 0.161557E+09 | 15952.51 | 04-NOV-14:00 | 11543.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.897234E+11 | 0.737552E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.343171E+11 | 0.280185E+11 | 84053.89 | 58717.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 66638652.61 | 45498264.93 | 34661.51 | 13-JAN-04:21 | 23566.52 | 0.00 |
February | 0.00 | 0.00 | 0.121383E+09 | 87373046.31 | 34661.51 | 24-FEB-04:21 | 19284.49 | 0.00 |
March | 0.00 | 0.00 | 0.160487E+09 | 0.127158E+09 | 34661.51 | 09-MAR-02:22 | 21288.92 | 0.00 |
April | 0.00 | 0.00 | 0.192175E+10 | 0.163183E+10 | 34661.51 | 03-APR-00:42 | 19887.94 | 0.00 |
May | 0.00 | 0.00 | 0.346898E+10 | 0.275913E+10 | 34661.51 | 07-MAY-03:21 | 17732.88 | 0.00 |
June | 0.00 | 0.00 | 0.624964E+10 | 0.519820E+10 | 34661.51 | 13-JUN-01:22 | 18789.91 | 0.00 |
July | 0.00 | 0.00 | 0.135153E+11 | 0.101513E+11 | 34661.51 | 10-JUL-01:22 | 21975.64 | 0.00 |
August | 0.00 | 0.00 | 0.178041E+11 | 0.132359E+11 | 34661.51 | 25-AUG-01:22 | 20698.40 | 0.00 |
September | 0.00 | 0.00 | 0.528708E+10 | 0.379629E+10 | 34661.51 | 02-SEP-03:21 | 19195.52 | 0.00 |
October | 0.00 | 0.00 | 0.452992E+09 | 0.370882E+09 | 34661.51 | 27-OCT-03:21 | 18448.55 | 0.00 |
November | 0.00 | 0.00 | 0.294613E+09 | 0.186498E+09 | 34661.51 | 04-NOV-03:21 | 17673.85 | 0.00 |
December | 0.00 | 0.00 | 62184480.47 | 41223801.99 | 13398.53 | 30-DEC-01:04 | 7920.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.494051E+11 | 0.376313E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 62184480.47 | 41223801.99 | 13398.53 | 7920.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178041E+11 | 0.132359E+11 | 34661.51 | 23566.52 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9098.07 | 17382.01 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 9176.14 | 17435.04 | 08-FEB-19:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9154.40 | 17369.97 | 02-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 8849.22 | 16978.96 | 04-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 8555.25 | 16471.63 | 02-MAY-18:06 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8282.68 | 15854.29 | 01-JUN-06:45 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 7978.44 | 15300.79 | 03-JUL-18:15 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8006.24 | 15096.07 | 31-AUG-18:45 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8050.88 | 15433.75 | 29-SEP-18:18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8264.70 | 15949.81 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8580.94 | 16568.85 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 8872.86 | 17074.67 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8568.96 | ||||
Minimum of Months | 0.00 | 0.00 | 7978.44 | 15096.07 | ||
Maximum of Months | 0.00 | 0.00 | 9176.14 | 17435.04 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.564419E+10 | 0.61 | 2203.40 | 01-JAN-00:01 | 0.64 |
February | 0.509799E+10 | 0.61 | 2203.40 | 01-FEB-00:01 | 0.64 |
March | 0.564511E+10 | 0.61 | 2203.40 | 01-MAR-00:01 | 0.64 |
April | 0.546291E+10 | 0.61 | 2203.40 | 01-APR-00:04 | 0.64 |
May | 0.564494E+10 | 0.61 | 2203.40 | 01-MAY-00:05 | 0.64 |
June | 0.546349E+10 | 0.61 | 2203.40 | 01-JUN-00:04 | 0.64 |
July | 0.564604E+10 | 0.61 | 2203.40 | 01-JUL-00:03 | 0.64 |
August | 0.564636E+10 | 0.61 | 2203.40 | 01-AUG-00:03 | 0.64 |
September | 0.546400E+10 | 0.61 | 2203.40 | 01-SEP-00:03 | 0.64 |
October | 0.564529E+10 | 0.61 | 2203.40 | 01-OCT-00:04 | 0.64 |
November | 0.546277E+10 | 0.61 | 2203.40 | 01-NOV-00:04 | 0.64 |
December | 0.564468E+10 | 0.61 | 2203.40 | 01-DEC-00:01 | 0.64 |
Annual Sum or Average | 0.664678E+11 | 0.61 | |||
Minimum of Months | 0.509799E+10 | 0.61 | 2203.40 | 0.64 | |
Maximum of Months | 0.564636E+10 | 0.61 | 2203.40 | 0.64 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170532E+11 | 1.32 | 7634.05 | 02-JAN-14:30 | 1.56 |
February | 0.154017E+11 | 1.32 | 7634.05 | 01-FEB-05:30 | 1.56 |
March | 0.170408E+11 | 1.30 | 7634.05 | 01-MAR-10:18 | 1.57 |
April | 0.164899E+11 | 1.30 | 7634.05 | 01-APR-21:10 | 1.56 |
May | 0.170466E+11 | 1.30 | 7634.05 | 01-MAY-04:10 | 1.55 |
June | 0.165113E+11 | 1.32 | 7634.05 | 01-JUN-07:03 | 1.55 |
July | 0.171345E+11 | 1.38 | 7634.05 | 07-JUL-13:20 | 1.55 |
August | 0.172389E+11 | 1.39 | 7634.05 | 01-AUG-06:05 | 1.55 |
September | 0.165378E+11 | 1.34 | 7634.05 | 01-SEP-14:50 | 1.55 |
October | 0.170392E+11 | 1.30 | 7634.05 | 02-OCT-06:00 | 1.56 |
November | 0.164895E+11 | 1.30 | 7634.05 | 01-NOV-06:20 | 1.55 |
December | 0.170442E+11 | 1.31 | 7634.05 | 02-DEC-08:47 | 1.56 |
Annual Sum or Average | 0.201028E+12 | 1.32 | |||
Minimum of Months | 0.154017E+11 | 1.30 | 7634.05 | 1.55 | |
Maximum of Months | 0.172389E+11 | 1.39 | 7634.05 | 1.57 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.394186E+10 | 0.86 | 1743.90 | 13-JAN-05:03 | 0.91 |
February | 0.356641E+10 | 0.86 | 1743.90 | 15-FEB-05:05 | 0.91 |
March | 0.395597E+10 | 0.86 | 1743.90 | 09-MAR-12:00 | 0.91 |
April | 0.384183E+10 | 0.86 | 1743.90 | 01-APR-10:38 | 0.91 |
May | 0.398876E+10 | 0.86 | 1743.90 | 15-MAY-19:12 | 0.91 |
June | 0.388962E+10 | 0.86 | 1743.90 | 09-JUN-09:58 | 0.91 |
July | 0.405040E+10 | 0.86 | 1743.90 | 03-JUL-14:40 | 0.91 |
August | 0.408055E+10 | 0.86 | 1743.90 | 05-AUG-19:57 | 0.90 |
September | 0.390238E+10 | 0.86 | 1743.90 | 07-SEP-18:12 | 0.90 |
October | 0.398714E+10 | 0.86 | 1743.90 | 01-OCT-04:02 | 0.90 |
November | 0.384049E+10 | 0.86 | 1743.90 | 04-NOV-10:55 | 0.90 |
December | 0.394736E+10 | 0.86 | 1743.90 | 01-DEC-05:03 | 0.91 |
Annual Sum or Average | 0.469928E+11 | 0.86 | |||
Minimum of Months | 0.356641E+10 | 0.86 | 1743.90 | 0.90 | |
Maximum of Months | 0.408055E+10 | 0.86 | 1743.90 | 0.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 48.94 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 47.96 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 48.12 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 51.63 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 51.94 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 52.27 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 52.73 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.20 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.46 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 52.56 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.23 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 48.44 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 47.96 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.73 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 48.94 | 59.93 | 9098.07 | 17382.01 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 47.96 | 59.38 | 9176.14 | 17435.04 | 08-FEB-19:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 48.12 | 58.67 | 9154.40 | 17369.97 | 02-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.50 | 49.50 | 8849.22 | 16978.96 | 04-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 49.74 | 49.74 | 8555.25 | 16471.63 | 02-MAY-18:06 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.04 | 50.04 | 8282.68 | 15854.29 | 01-JUN-06:45 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.62 | 50.62 | 7978.44 | 15300.79 | 03-JUL-18:15 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.80 | 50.80 | 8006.24 | 15096.07 | 31-AUG-18:45 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.01 | 51.01 | 8050.88 | 15433.75 | 29-SEP-18:18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.31 | 48.31 | 8264.70 | 15949.81 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.52 | 50.52 | 8580.94 | 16568.85 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 48.44 | 59.58 | 8872.86 | 17074.67 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8568.96 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.96 | 48.31 | 7978.44 | 15096.07 | ||
Maximum of Months | 0.00 | 0.00 | 51.01 | 59.93 | 9176.14 | 17435.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.170532E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.154162E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.170722E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175505E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.190637E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.201879E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252800E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.282444E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.197695E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.172131E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.165699E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.170442E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.230465E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.154162E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.282444E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.396337E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.360491E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.400695E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.441482E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.505156E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.580786E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.803379E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.923148E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.550982E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.413007E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.393195E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.396755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.616541E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.360491E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.923148E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170532E+11 | 0.00 | 0.813233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154017E+11 | 40128905.60 | 0.617995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170408E+11 | 87589118.95 | 0.450545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164899E+11 | 0.318399E+10 | 0.273141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170466E+11 | 0.595875E+10 | 0.155113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165113E+11 | 0.108735E+11 | 0.482915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171345E+11 | 0.248838E+11 | 0.154693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172389E+11 | 0.343171E+11 | 0.120428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165378E+11 | 0.965198E+10 | 0.574892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170392E+11 | 0.496663E+09 | 0.222137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164895E+11 | 0.229930E+09 | 0.491474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170442E+11 | 0.00 | 0.724268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201028E+12 | 0.897234E+11 | 0.388120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154017E+11 | 0.00 | 0.120428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172389E+11 | 0.343171E+11 | 0.813233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.394186E+10 | 66638652.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356641E+10 | 0.121383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395597E+10 | 0.160487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384183E+10 | 0.192175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.398876E+10 | 0.346898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.388962E+10 | 0.624964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.405040E+10 | 0.135153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.408055E+10 | 0.178041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.390238E+10 | 0.528708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398714E+10 | 0.452992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384049E+10 | 0.294613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394736E+10 | 62184480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469928E+11 | 0.494051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.356641E+10 | 62184480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.408055E+10 | 0.178041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154017E+11 | 0.00 | 0.00 | 0.00 | 14469272.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170408E+11 | 0.00 | 0.00 | 0.00 | 31397352.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164899E+11 | 0.00 | 0.00 | 0.00 | 0.106061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170466E+11 | 0.00 | 0.00 | 0.00 | 0.201717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165113E+11 | 0.00 | 0.00 | 0.00 | 0.367660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171345E+11 | 0.00 | 0.00 | 0.00 | 0.814548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172389E+11 | 0.00 | 0.00 | 0.00 | 0.110054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165378E+11 | 0.00 | 0.00 | 0.00 | 0.323170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170392E+11 | 0.00 | 0.00 | 0.00 | 0.173928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164895E+11 | 0.00 | 0.00 | 0.00 | 80331694.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201028E+12 | 0.00 | 0.00 | 0.00 | 0.294371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172389E+11 | 0.00 | 0.00 | 0.00 | 0.110054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.394186E+10 | 0.00 | 0.00 | 0.00 | 21508987.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356641E+10 | 0.00 | 0.00 | 0.00 | 38504920.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395597E+10 | 0.00 | 0.00 | 0.00 | 50979025.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384183E+10 | 0.00 | 0.00 | 0.00 | 0.572987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.398876E+10 | 0.00 | 0.00 | 0.00 | 0.106280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.388962E+10 | 0.00 | 0.00 | 0.00 | 0.191824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.405040E+10 | 0.00 | 0.00 | 0.00 | 0.398340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.408055E+10 | 0.00 | 0.00 | 0.00 | 0.515093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.390238E+10 | 0.00 | 0.00 | 0.00 | 0.160744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398714E+10 | 0.00 | 0.00 | 0.00 | 0.142930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384049E+10 | 0.00 | 0.00 | 0.00 | 91463731.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394736E+10 | 0.00 | 0.00 | 0.00 | 20197202.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469928E+11 | 0.00 | 0.00 | 0.00 | 0.146614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.356641E+10 | 0.00 | 0.00 | 0.00 | 20197202.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.408055E+10 | 0.00 | 0.00 | 0.00 | 0.515093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114604E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101391E+11 | 0.00 | 0.00 | 7.05 |
February | 0.968149E+11 | 0.00 | 0.00 | 1246679.25 | 0.00 | 0.651614E+10 | 0.776209E+09 | 0.00 | 7.10 |
March | 0.945308E+11 | 0.00 | 0.00 | 1859640.63 | 0.00 | 0.639946E+09 | 0.208166E+10 | 0.00 | 7.06 |
April | 0.726090E+11 | 96640902.10 | 0.00 | 14336011.94 | 0.00 | 58862087.05 | 0.644469E+10 | 0.00 | 7.10 |
May | 0.564514E+11 | 30554197.52 | 0.00 | 34453340.94 | 0.00 | 65307338.35 | 0.132898E+11 | 0.00 | 7.17 |
June | 0.320464E+11 | 43959116.66 | 0.00 | 62852000.49 | 0.00 | 16801674.75 | 0.235429E+11 | 0.00 | 7.29 |
July | 0.207031E+11 | 0.133159E+10 | 0.00 | 93785261.90 | 0.00 | 0.00 | 0.242412E+11 | 0.00 | 7.37 |
August | 0.157821E+11 | 0.320995E+10 | 0.00 | 79041910.78 | 0.00 | 7373894.74 | 0.233259E+11 | 0.00 | 7.46 |
September | 0.353906E+11 | 61719778.68 | 0.00 | 56365091.10 | 0.00 | 12320948.11 | 0.224044E+11 | 0.00 | 7.27 |
October | 0.694955E+11 | 0.00 | 0.00 | 9127147.97 | 0.00 | 59700643.45 | 0.954776E+10 | 0.00 | 7.11 |
November | 0.954215E+11 | 0.00 | 0.00 | 1820982.09 | 0.00 | 0.553952E+09 | 0.164137E+10 | 0.00 | 7.06 |
December | 0.114591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335457E+10 | 0.00 | 0.00 | 7.04 |
Annual Sum or Average | 0.818440E+12 | 0.477441E+10 | 0.00 | 0.354888E+09 | 0.00 | 0.214241E+11 | 0.127296E+12 | 0.00 | 7.17 |
Minimum of Months | 0.157821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
Maximum of Months | 0.114604E+12 | 0.320995E+10 | 0.00 | 93785261.90 | 0.00 | 0.101391E+11 | 0.242412E+11 | 0.00 | 7.46 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 60186727.49 | 0.00 | 0.00 | 0.419051E+11 | 0.00 | 3.72 |
February | 2507217.52 | 0.00 | 0.00 | 63760151.19 | 0.00 | 0.00 | 0.387076E+11 | 0.00 | 4.25 |
March | 723768.47 | 0.00 | 0.00 | 88287819.57 | 0.00 | 0.00 | 0.448527E+11 | 0.00 | 4.96 |
April | 295725.19 | 0.00 | 0.00 | 0.102811E+09 | 0.00 | 0.00 | 0.435718E+11 | 0.00 | 6.05 |
May | 799629.76 | 0.00 | 0.00 | 0.125567E+09 | 0.00 | 0.00 | 0.456911E+11 | 0.00 | 7.41 |
June | 1605972.63 | 0.00 | 0.00 | 0.124745E+09 | 0.00 | 0.00 | 0.427947E+11 | 0.00 | 8.84 |
July | 2369571.84 | 265198.26 | 0.00 | 0.146212E+09 | 0.00 | 0.00 | 0.386164E+11 | 0.00 | 9.27 |
August | 1447708.01 | 8589817.67 | 0.00 | 0.130424E+09 | 0.00 | 0.00 | 0.338989E+11 | 0.00 | 9.17 |
September | 581441.42 | 0.00 | 0.00 | 0.118340E+09 | 0.00 | 0.00 | 0.430061E+11 | 0.00 | 8.65 |
October | 0.00 | 0.00 | 0.00 | 87746025.16 | 0.00 | 0.00 | 0.461953E+11 | 0.00 | 6.47 |
November | 0.00 | 0.00 | 0.00 | 65989109.38 | 0.00 | 0.00 | 0.424957E+11 | 0.00 | 4.91 |
December | 0.00 | 0.00 | 0.00 | 64824106.27 | 0.00 | 0.00 | 0.427282E+11 | 0.00 | 3.95 |
Annual Sum or Average | 10331034.83 | 8855015.93 | 0.00 | 0.117889E+10 | 0.00 | 0.00 | 0.504464E+12 | 0.00 | 6.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 60186727.49 | 0.00 | 0.00 | 0.338989E+11 | 0.00 | 3.72 |
Maximum of Months | 2507217.52 | 8589817.67 | 0.00 | 0.146212E+09 | 0.00 | 0.00 | 0.461953E+11 | 0.00 | 9.27 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.111962E+11 | 0.159389E+11 | 0.403986E+12 | 0.246788E+11 | 0.374025E+11 |
February | 0.293558E+11 | 0.138797E+11 | 0.341578E+12 | 0.240113E+11 | 0.324414E+11 |
March | 0.561201E+11 | 0.140539E+11 | 0.326291E+12 | 0.303803E+11 | 0.324167E+11 |
April | 0.949267E+11 | 0.130147E+11 | 0.269271E+12 | 0.314644E+11 | 0.358203E+11 |
May | 0.126870E+12 | 0.128935E+11 | 0.237289E+12 | 0.350861E+11 | 0.418271E+11 |
June | 0.130543E+12 | 0.112197E+11 | 0.186139E+12 | 0.348270E+11 | 0.483532E+11 |
July | 0.137303E+12 | 0.980615E+10 | 0.156245E+12 | 0.319706E+11 | 0.780646E+11 |
August | 0.106770E+12 | 0.754796E+10 | 0.133397E+12 | 0.278978E+11 | 0.937020E+11 |
September | 0.680358E+11 | 0.887662E+10 | 0.192204E+12 | 0.346250E+11 | 0.446246E+11 |
October | 0.425052E+11 | 0.109427E+11 | 0.262150E+12 | 0.341410E+11 | 0.265663E+11 |
November | 0.140637E+11 | 0.127182E+11 | 0.316821E+12 | 0.283426E+11 | 0.298079E+11 |
December | 0.686355E+10 | 0.144550E+11 | 0.382304E+12 | 0.261690E+11 | 0.357677E+11 |
Annual Sum or Average | 0.824554E+12 | 0.145347E+12 | 0.320767E+13 | 0.363594E+12 | 0.536794E+12 |
Minimum of Months | 0.686355E+10 | 0.754796E+10 | 0.133397E+12 | 0.240113E+11 | 0.265663E+11 |
Maximum of Months | 0.137303E+12 | 0.159389E+11 | 0.403986E+12 | 0.350861E+11 | 0.937020E+11 |