Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:24:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2680.99 | 5244.97 | 5244.97 |
Net Site Energy | 2680.99 | 5244.97 | 5244.97 |
Total Source Energy | 7002.78 | 13699.95 | 13699.95 |
Net Source Energy | 7002.78 | 13699.95 | 13699.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 757.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 361.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.42 | 244.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 68.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1966.68 | 714.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 757.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 361.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 77.42 | 244.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 757.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 361.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 77.42 | 244.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 68.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2342.61 | 478.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1034.38 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3847.53 | 1397.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2342.61 | 478.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1034.38 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3847.53 | 1397.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1966.676 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1966.676 | 100.00 |
Total On-Site and Utility Electric Sources | 1966.676 | 100.00 |
Total Electricity End Uses | 1966.676 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 2066.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6786.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 20.6319 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.3949 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 18.1127 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 18.1127 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 20.6319 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.3949 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 18.1127 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 18.1127 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 18.1127 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-11:00 | 16-JAN-11:20 | - | - | - | - | - | - | - | - | - | - | 15-FEB-07:19 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 62768.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 23090.58 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13267.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3034.46 | 16753.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2211.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 112722.34 | 43001.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 62768.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21723.00 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13267.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3034.46 | 16753.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 590.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2399.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 533.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1146.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 245.18 | 265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 215.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6228.46 | 774.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4694.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2242.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 479.65 | 518.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 421.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 12185.12 | 1514.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4694.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2242.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 479.65 | 518.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 421.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 12185.12 | 1514.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 5.28 |
KITCHEN DIRECT AIR | 1.80 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 5.28 | 5.28 | 5.28 | 5.28 | 5.28 | 5.28 | 1.00 | 1.00 | 5.28 |
PSZ-AC_2:2 | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 | 1.00 | 1.00 | 1.80 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 5.28 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.80 | 1.50 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 5.28 | 9090.08 |
PSZ-AC_2:2_ADDAQ FAN | 1.80 | 1974.14 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 5.28 | 5.28 | 5.28 | 5.28 | 131104.69 | 134686.06 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.80 | 1.80 | 1.80 | 1.80 | 44789.74 | 64215.53 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 5.28 | 2.64 | 5.28 | 131104.69 | 65552.35 | 131104.69 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.80 | 0.901841 | 1.80 | 44789.74 | 22394.83 | 44789.74 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 134686.06 |
PSZ-AC_2:2 HEATING COIL | 64215.53 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 20.632 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 85.559 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.395 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.475 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 7669.876 | 20.632 | 27.379 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7669.876 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1588.510 | 11.395 | 211.016 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1588.510 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.342 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5109 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.20636098E-16 | 0.18100998E-15 | 0.17288268E-13 | -0.34766289E-16 |
24 | 3 | -0.71341822E-08 | 0.14427768E-06 | -0.58767875E-04 | 0.16137435E-12 |
25 | 2 | 0.62866063E-04 | 0.30866150E-02 | 1.1745480 | -0.77421164E-04 |
26 | 1 | -0.70719755E-01 | 0.78899699E-01 | -17.315014 | 0.34200793 |
27 | 0 | 0.20250090 | 0.49857543E-01 | 16.272369 | |
28 | 4 | 0.17288268E-13 | 0.18100998E-15 | 0.20636098E-16 | -0.34766289E-16 |
29 | 3 | -0.58767875E-04 | 0.14427768E-06 | -0.71341822E-08 | 0.16137435E-12 |
30 | 2 | 1.1745480 | 0.30866150E-02 | 0.62866063E-04 | -0.77421164E-04 |
31 | 1 | -17.315014 | 0.78899699E-01 | -0.70719755E-01 | 0.34200793 |
32 | 0 | 16.272369 | 0.49857543E-01 | 0.20250090 | |
33 | 6 | 0.21862767E-07 | 0.34448908E-09 | 0.50649605E-08 | -0.99069094E-13 |
34 | 5 | -0.15485004E-03 | 0.31008008E-05 | -0.80011323E-04 | 0.50225397E-08 |
35 | 4 | 0.24987207 | 0.15775750E-02 | 0.84530116E-01 | -0.27712185E-04 |
36 | 3 | -6.4266483 | 0.50820490E-01 | -2.0899201 | 0.24901095E-01 |
37 | 2 | 38.099035 | 0.18692275 | 14.237681 | -0.30248143 |
38 | 1 | -78.418483 | 0.86852168E-01 | -28.218840 | 1.0332909 |
39 | 0 | 46.824353 | 0.17981083E-02 | 16.314603 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.237 | 1.0416 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.744 | 0.2415 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 60284.98182 | 72341.97818 | 4.39966 | 5.27959 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 2312.65208 | 2775.18250 | 9.91749E-002 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 12.70000 | 9.15345E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 24284.17172 | 29141.00606 | 1.50307 | 1.80368 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 41.92700 | 1.07803E-002 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.50017 | 00:10:00 | 12.70000 | 9.15345E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 101709.31 | 5.27959 | 5.27959 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 43959.14 | 1.33138 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 58290.67 | 1.80368 | 1.80368 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 49532.31 | 1.50017 | 1.50017 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.27959 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.80368 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.27959 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.27959 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.27959 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 5.27959 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.27959 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 5.27959 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.80368 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.80368 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.80368 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.80368 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.80368 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.80368 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 5.27959 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.80368 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.27959 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.27959 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 9090.08153 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.27959 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.27959 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.27959 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.27959 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.27959 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.63979 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.27959 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 131104.69000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 65552.34723 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 131104.69000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 131104.69000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 134686.05595 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 134686.05595 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.80368 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.50017 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.80368 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1974.14057 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.80368 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.80368 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.80368 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.80368 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.80368 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90184 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.80368 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44789.74000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 22394.83486 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 44789.74000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44789.74000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64215.53428 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 64215.53428 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 127352.1 | 9.93 | 9.81 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 43507.7 | 10.12 | 9.99 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | N/A | 6.813 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | N/A | 6.813 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | N/A | 6.813 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.342 | 1.118 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 4.2418875817E-002 | 0.1290536975 | Pass | Pass | 6.8383618235E-002 | 0.2513736745 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2423546248 | 0.6771750389 | Pass | Pass | 0.1314414348 | 0.5134920356 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3194384215 | 0.2414897828 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 989.47 | -81.5 | -785.0 | 10.93 | 3505.91 | 3639.84 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.118 | 1.342 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 6.813 | 0.251 | 0.252 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 6.813 | 0.251 | 0.252 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 20.6319 | 371.75 | 7669.88 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 139.55 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.3949 | 139.41 | 1588.51 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 28.90 |
Interior Lighting Total | 18.1127 | 511.15 | 9258.39 | 168.45 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.85 | 83.85 | 72.06 | |
Exterior Lighting Total | 4578.48 | 72.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 131104.69 | 91914.88 | 39189.81 | 0.70 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44789.74 | 31401.19 | 13388.55 | 0.70 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 127352.1 | 9.93 | 9.81 | ||||
PSZ-AC_2:2 COOLING COIL | 43507.7 | 10.12 | 9.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 134686.06 | 0.79 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 64215.53 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1018.41 | 5.28 | 9090.08 | 1721.74 | 1.00 | 1.15 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.80 | 1974.14 | 1094.51 | 1.00 | 1.30 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.04 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.74 | 0.24 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 60284.98 | 72341.98 | 194.60 | 4.400 | 5.280 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 23.99 | 0.00849 | 42.70 | 0.01078 | 1.331 | 0.00 |
KITCHEN | 24284.17 | 29141.01 | 209.04 | 1.503 | 1.804 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.00863 | 41.93 | 0.01078 | 1.500 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 2312.65 | 2775.18 | 7.47 | 0.099 | 1.331 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 21.00 | 21.00 | 0.00819 | 12.70 | 0.00915 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.500 | 00:10:00 | 19.00 | 29.27 | 0.00762 | 12.70 | 0.00915 | 1.500 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 5.28 | 5.28 | 1.33 | 1.33 | 5.2796 | 5.2796 | 5.2796 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.80 | 1.80 | 1.50 | 1.50 | 1.8037 | 1.8037 | 1.8037 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 131104.690 | 91914.876 | 5.279590 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 131104.69 | 104090.84 | 5.279590 | 28.73 | 18.47 | 0.00906863 | 11.40 | 9.94 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 25.2174 | 23.99 | 0.00849091 | 45.7211 | 60278.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 134686.056 | 134686.056 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | 134686.06 | 134686.06 | 5.279586 | 18.91 | 14.45 | 0.00842929 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 25.2175 | 21.00 | 0.00818509 | 52.8729 | 2311.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 44789.740 | 31401.191 | 1.803680 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 44789.74 | 35055.72 | 1.803680 | 40.45 | 23.03 | 0.01048107 | 11.91 | 10.16 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 83.1728 | 25.99 | 0.00862132 | 41.2002 | 23453.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 64215.534 | 64215.534 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 64215.53 | 64215.53 | 1.803683 | 10.56 | 10.56 | 0.00889479 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 83.1726 | 29.27 | 0.00761633 | 30.0930 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 131104.690 | 91914.876 | 5.279590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6981 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 5.279586 | 6.35448327 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 131104.69 | 104090.84 | 1.0000 | 6.35448803 | 5.279590 | 28.73 | 18.47 | 0.00906863 | 52032.3 | 11.40 | 9.94 | 0.00700000 | 29110.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 131104.69 | 42.80 | 0.01078182 | 23.86 | 1.33137743 | 25.2174 | 23.98 | 0.00849091 | 23.99 | 0.00849091 | 45.7211 | 60278.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 134686.056 | 134686.056 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 5.279586 | 6.35448327 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | Sensible | 134686.06 | 134686.06 | 1.0000 | 6.35448327 | 5.279586 | 18.91 | 14.45 | 0.00842929 | 40376.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 134686.06 | 12.70 | 0.00915345 | 12.70 | 1.33137743 | 25.2175 | 21.00 | 0.00818509 | 21.00 | 0.00818509 | 52.8729 | 2311.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44789.740 | 31401.191 | 1.803680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3238 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.803683 | 2.17090338 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 44789.74 | 35055.72 | 1.0000 | 2.17090020 | 1.803680 | 40.45 | 23.03 | 0.01048107 | 67651.5 | 11.91 | 10.16 | 0.00700000 | 29631.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44789.74 | 42.80 | 0.01078182 | 23.86 | 1.50017041 | 83.1728 | 25.95 | 0.00862132 | 25.99 | 0.00862132 | 41.2002 | 23453.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64215.534 | 64215.534 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.803683 | 2.17090338 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 64215.53 | 64215.53 | 1.0000 | 2.17090338 | 1.803683 | 10.56 | 10.56 | 0.00889479 | 33034.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64215.53 | 12.70 | 0.00915345 | 12.70 | 1.50017041 | 83.1726 | 0.00 | 0.00761633 | 29.27 | 0.00761633 | 30.0930 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 7078.50 | 1889.67 | 1862.17 |
KITCHEN | 7156.33 | 6794.50 | 6786.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7156.33 | 6814.67 | 6786.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 78.00 | 0.00 | 6.00 |
KITCHEN | 0.00 | 2487.00 | 0.00 | 2066.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2532.50 | 0.00 | 2066.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.367 | 0.893 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 13.267 | 0.050 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.251 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 12.754 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35657340.25 | 0.00 | 35657340.25 | 7157620.58 | 42814960.83 | 41986318.57 | 1393.56 | 7366.44 | 0.00 | 374.17 |
KITCHEN | 41223599.59 | 0.00 | 41223599.59 | 212974.62 | 41436574.21 | 47309374.20 | 1362.53 | 7302.77 | 94.70 | 1095.81 |
Total Facility | 76880939.84 | 0.00 | 76880939.84 | 7370595.20 | 84251535.04 | 89295692.77 | 1426.37 | 7368.91 | 94.70 | 1199.32 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3315 | 0.0000 | 1.3315 | 0.2725 | 1.6040 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.5002 | 0.0000 | 1.5002 | 0.0056 | 1.5058 | 1.5002 | 0.00 | 7187.00 | 0.00 |
Total Facility | 2.8317 | 0.0000 | 2.8317 | 0.2781 | 3.1098 | 2.8315 | 0.00 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 51654742.08 | 0.00 | 51654742.08 | 41986318.57 | 1362.70 | 2.46 | 7394.84 | 374.17 |
PSZ-AC_2:2 | 59718191.58 | 0.00 | 59718191.58 | 47309374.20 | 1309.90 | 3.51 | 7446.59 | 1095.81 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9289 | 0.0000 | 1.9289 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 2.1732 | 0.0000 | 2.1732 | 1.5002 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 196.14 | 0.00 | 7365.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 6570.00 | 0.00 | 1712.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 2.1732 | 0.0000 | 2.1767 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
Electricity:Building | 646.02 | 4774.49 | 01-JAN-01:10 | 35397.39 | 02-JAN-11:10 |
Electricity:Zone:DINING | 264.83 | 1633.21 | 01-JAN-01:10 | 13902.52 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 629.17 | 4365.45 | 01-JAN-01:10 | 33032.24 | 02-JAN-11:10 |
InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.20 | 3141.27 | 01-JAN-01:10 | 21494.87 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 68.01 | 1165.74 | 02-JAN-23:30 | 3441.39 | 09-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 129.02 | 1259.61 | 13-FEB-01:10 | 6694.03 | 30-AUG-18:50 |
LowTempRefrigeration:Refrigeration:Electricity | 17.94 | 0.00 | 01-JAN-11:10 | 1532.35 | 18-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 33.22 | 858.33 | 01-JAN-05:20 | 1076.23 | 02-JAN-14:10 |
ElectricityPurchased:Facility | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
ElectricityPurchased:Plant | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
Cogeneration:ElectricityPurchased | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
General:Cogeneration:ElectricityPurchased | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
ElectricityNet:Plant | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
Cogeneration:ElectricityNet | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
General:Cogeneration:ElectricityNet | 1966.68 | 10612.57 | 13-FEB-01:10 | 112722.34 | 16-AUG-12:00 |
Electricity:HVAC | 1119.57 | 0.00 | 01-JAN-01:10 | 76035.64 | 16-AUG-12:00 |
Fans:Electricity | 361.92 | 0.00 | 01-JAN-01:10 | 13267.63 | 01-JAN-23:20 |
General:Fans:Electricity | 361.92 | 0.00 | 01-JAN-01:10 | 13267.63 | 01-JAN-23:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 757.65 | 0.00 | 01-JAN-00:10 | 62768.02 | 16-AUG-12:00 |
General:Cooling:Electricity | 757.65 | 0.00 | 01-JAN-00:10 | 62768.02 | 16-AUG-12:00 |
ExteriorLights:Electricity | 72.06 | 0.00 | 01-JAN-07:10 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 72.06 | 0.00 | 01-JAN-07:10 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 77.42 | 0.00 | 01-JAN-01:10 | 4790.29 | 09-JAN-07:20 |
Water Heater:WaterSystems:Electricity | 77.42 | 0.00 | 01-JAN-01:10 | 4790.29 | 09-JAN-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 714.31 | 2863.57 | 17-JAN-01:20 | 43001.69 | 16-JAN-11:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 244.52 | 1053.32 | 01-JAN-04:40 | 17418.39 | 11-JAN-08:00 |
WaterSystems:NaturalGas | 244.52 | 1053.32 | 01-JAN-04:40 | 17418.39 | 11-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 244.52 | 1053.32 | 01-JAN-04:40 | 17418.39 | 11-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3762.64 | 3774.19 | 20-JAN-01:10 | 254256.98 | 23-AUG-17:50 |
EnergyTransfer:Building | 1098.92 | 1887.09 | 20-JAN-01:10 | 68325.53 | 30-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 513.12 | 1887.09 | 20-JAN-01:10 | 27764.87 | 09-OCT-10:50 |
Refrigeration:EnergyTransfer | 168.33 | 3480.55 | 02-JAN-23:30 | 7834.84 | 10-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 84.17 | 1740.27 | 02-JAN-23:30 | 3917.42 | 10-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 84.17 | 1740.27 | 02-JAN-23:30 | 3917.42 | 10-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 84.17 | 1740.27 | 02-JAN-23:30 | 3917.42 | 10-JAN-11:40 |
EnergyTransfer:Plant | 244.55 | 1887.09 | 20-JAN-01:10 | 14769.42 | 09-JAN-20:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.73 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.43 | 1584.99 | 01-JAN-05:20 | 2238.70 | 02-JAN-14:10 |
EnergyTransfer:Zone:DINING | 585.80 | 0.00 | 01-JAN-01:10 | 48747.68 | 16-AUG-12:00 |
Heating:EnergyTransfer | 4.65 | 0.00 | 01-JAN-00:10 | 15061.18 | 23-JUL-23:10 |
Heating:EnergyTransfer:Zone:DINING | 4.65 | 0.00 | 01-JAN-00:10 | 15061.18 | 23-JUL-23:10 |
General:Heating:EnergyTransfer | 4.65 | 0.00 | 01-JAN-00:10 | 15061.18 | 23-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 4.65 | 0.00 | 01-JAN-00:10 | 15061.18 | 23-JUL-23:10 |
Cooling:EnergyTransfer | 1010.11 | 0.00 | 01-JAN-01:10 | 65349.39 | 20-JUL-17:30 |
Cooling:EnergyTransfer:Zone:DINING | 581.15 | 0.00 | 01-JAN-01:10 | 48747.68 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 1010.11 | 0.00 | 01-JAN-01:10 | 65349.39 | 20-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:DINING | 581.15 | 0.00 | 01-JAN-01:10 | 48747.68 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 428.96 | 0.00 | 01-JAN-01:10 | 24064.66 | 20-JUL-18:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 428.96 | 0.00 | 01-JAN-01:10 | 24064.66 | 20-JUL-18:50 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 160.39 | 0.00 | 01-JAN-01:10 | 12005.34 | 09-JAN-20:00 |
PlantLoopHeatingDemand:Plant | 160.39 | 0.00 | 01-JAN-01:10 | 12005.34 | 09-JAN-20:00 |
WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12005.34 | 09-JAN-20:00 |
General:WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12005.34 | 09-JAN-20:00 |
EnergyTransfer:HVAC | 2419.16 | 0.00 | 01-JAN-00:10 | 190665.01 | 08-AUG-03:10 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2419.16 | 0.00 | 01-JAN-00:10 | 190665.01 | 08-AUG-03:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12005.34 | 09-JAN-20:00 |
WaterUse:WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12005.34 | 09-JAN-20:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 4.650 | -581.150 | 0.000 | 0.000 | 206.112 | 139.549 | 93.957 | 60.167 | 0.000 | 51.701 | 45.267 | 0.000 | -12.116 | 0.000 | -8.136 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -428.951 | 0.000 | 0.000 | 4.357 | 28.902 | 297.857 | 0.000 | 0.000 | 0.750 | 97.759 | 0.000 | 0.000 | 0.000 | -0.674 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.118 | 26.325 | 0.000 | 0.000 | 0.000 | -39.443 | -0.000 |
Total Facility | 0.000 | 0.000 | 4.650 | -1010.102 | 0.000 | 0.000 | 210.469 | 168.451 | 391.814 | 60.167 | 0.000 | 65.568 | 169.351 | 0.000 | -12.116 | 0.000 | -48.253 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 23-MAR-03:01 | 0.00 | 0.00 | 0.00 | -107157.46 | 0.00 | 0.00 | 0.00 | 1150.48 | 905.12 | 0.00 | 0.00 | 0.00 | 106437.73 | 0.00 | -1307.14 | 0.00 | -28.73 | 0.00 |
KITCHEN | 01-JAN-04:01 | 0.00 | 0.00 | 0.00 | -60797.33 | 0.00 | 0.00 | 0.00 | 238.28 | 3821.48 | 0.00 | 0.00 | 0.00 | 56883.85 | 0.00 | -0.00 | 0.00 | -146.28 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-MAR-03:01 | 0.00 | 0.00 | 0.00 | -156172.07 | 0.00 | 0.00 | 0.00 | 1388.76 | 4726.60 | 0.00 | 0.00 | 1093.30 | 150347.64 | 0.00 | -1307.14 | 0.00 | -77.09 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-JUL-23:01 | 0.00 | 0.00 | 25582.07 | 0.00 | 0.00 | 0.00 | 973.97 | 1150.48 | 543.07 | 1809.39 | 0.00 | 381.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30440.87 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-23:01 | -14430.69 | 14430.69 | 25582.07 | -14430.69 | 0.00 | 0.00 | 996.44 | 1388.76 | 3382.99 | 1809.39 | 0.00 | 1513.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20242.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 5.2796 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 5.2796 | 0.2522 | 1.0000 | Not calculated | 1.3314 | 0.2522 | ||
PSZ-AC_2:2 | 1.8037 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8037 | 0.1012 | 1.0000 | Not calculated | 0.1826 | 0.1012 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 5.2796 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 5.2796 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2522 | ||
PSZ-AC_2:2 | 1.8037 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8037 | 0.1217 | 1.0000 | Not calculated | 0.1826 | 0.1012 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2796 | 5.2796 | 5.2796 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8037 | 1.8037 | 1.8037 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 5.2796 | 5.2796 | 5.2796 | 5.2796 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8037 | 1.8037 | 1.8037 | 1.8037 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2796 | 5.2796 | 5.2796 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8037 | 1.8037 | 1.8037 | No | 0.1826 | 0.1217 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 5.2796 | 5.2796 | 5.2796 | 5.2796 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8037 | 1.8037 | 1.8037 | 1.8037 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 511.15 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 2066.67 |
Number of hours not met | 2066.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 757.65 | 62768.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 168.45 | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.06 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 361.92 | 13267.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 77.42 | 4790.29 | 244.52 | 17418.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.94 | 1532.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.22 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 528.73 | 1966.68 |
Natural Gas | 469.79 | 714.31 |
Additional | 0.00 | 0.00 |
Total | 998.52 | 2680.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 329.55 |
Space Heating | 0.00 |
Space Cooling | 1482.24 |
Fans (All) | 708.05 |
Service Water Heating | 151.45 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 3847.53 |
Subtotal | 3847.53 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 478.37 |
Miscellaneous (All) | 1397.45 |
Subtotal | 1397.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.28 |
Space Heating | 0.00 |
Space Cooling | 28.26 |
Fans (All) | 13.50 |
Service Water Heating | 12.01 |
Receptacle Equipment | 34.71 |
Miscellaneous | 5.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3433. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7743.50 | 674.00 | 342.50 | 0.00 | 0.00 |
KITCHEN | 5316.50 | 2222.00 | 1127.33 | 94.17 | 0.00 |
ATTIC | 3592.50 | 1046.83 | 1510.33 | 1452.17 | 1158.17 |
Min | 3592.50 | 674.00 | 342.50 | 0.00 | 0.00 |
Max | 7743.50 | 2222.00 | 1510.33 | 1452.17 | 1158.17 |
Average | 5550.83 | 1314.28 | 993.39 | 515.44 | 386.06 |
Sum | 16652.50 | 3942.83 | 2980.17 | 1546.33 | 1158.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 820810.67 | 2186.33 | 1225.00 | 0.00 | 0.00 |
KITCHEN | 12849.67 | 3466.50 | 2611.67 | 305.17 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 820810.67 | 3466.50 | 2611.67 | 305.17 | 0.00 |
Average | 277886.78 | 1884.28 | 1278.89 | 101.72 | 0.00 |
Sum | 833660.33 | 5652.83 | 3836.67 | 305.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 5618.67 | 2922.83 | 218.50 | 0.00 | 0.00 |
KITCHEN | 1509.50 | 6484.17 | 701.33 | 65.00 | 0.00 |
ATTIC | 2775.00 | 2336.83 | 1251.00 | 765.50 | 1631.67 |
Min | 1509.50 | 2336.83 | 218.50 | 0.00 | 0.00 |
Max | 5618.67 | 6484.17 | 1251.00 | 765.50 | 1631.67 |
Average | 3301.06 | 3914.61 | 723.61 | 276.83 | 543.89 |
Sum | 9903.17 | 11743.83 | 2170.83 | 830.50 | 1631.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 608265.00 | 215266.33 | 690.67 | 0.00 | 0.00 |
KITCHEN | 3171.67 | 14031.67 | 1813.67 | 216.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 608265.00 | 215266.33 | 1813.67 | 216.00 | 0.00 |
Average | 203812.22 | 76432.67 | 834.78 | 72.00 | 0.00 |
Sum | 611436.67 | 229298.00 | 2504.33 | 216.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341736E+11 | 88250.98 | 29-JAN-04:01 | 22.42 | 15.30 | 0.152903E+11 | 14051.43 | 07-JAN-19:00 | 22.42 | 15.30 |
February | 0.328684E+11 | 82949.49 | 10-FEB-04:01 | 20.25 | 13.47 | 0.138696E+11 | 14051.43 | 11-FEB-19:10 | 19.33 | 13.92 |
March | 0.399896E+11 | 107152.38 | 23-MAR-03:01 | 22.67 | 13.25 | 0.155206E+11 | 14051.41 | 11-MAR-19:00 | 22.67 | 13.25 |
April | 0.440638E+11 | 98414.96 | 26-APR-03:01 | 23.10 | 12.40 | 0.149151E+11 | 14051.42 | 08-APR-18:10 | 23.10 | 12.40 |
May | 0.544928E+11 | 95721.34 | 10-MAY-03:01 | 30.03 | 16.53 | 0.154497E+11 | 14051.40 | 20-MAY-18:10 | 35.57 | 21.85 |
June | 0.561018E+11 | 73170.19 | 02-JUN-03:01 | 28.93 | 19.10 | 0.150321E+11 | 14051.41 | 10-JUN-18:10 | 35.83 | 26.14 |
July | 0.616954E+11 | 84291.82 | 04-JUL-03:01 | 30.08 | 16.17 | 0.153639E+11 | 14055.26 | 15-JUL-18:00 | 40.20 | 25.74 |
August | 0.638961E+11 | 69218.76 | 06-AUG-03:01 | 35.97 | 22.54 | 0.155741E+11 | 14054.58 | 05-AUG-18:49 | 35.97 | 22.54 |
September | 0.571914E+11 | 69465.56 | 02-SEP-03:01 | 30.92 | 22.67 | 0.149314E+11 | 14054.16 | 09-SEP-18:00 | 34.60 | 28.00 |
October | 0.539030E+11 | 90382.97 | 21-OCT-03:01 | 22.85 | 15.66 | 0.153532E+11 | 14051.40 | 28-OCT-18:00 | 29.10 | 22.33 |
November | 0.450465E+11 | 88567.75 | 05-NOV-03:01 | 21.98 | 15.88 | 0.148348E+11 | 14051.43 | 18-NOV-19:10 | 26.83 | 16.72 |
December | 0.377300E+11 | 91336.92 | 01-DEC-04:01 | 17.42 | 12.43 | 0.153164E+11 | 14051.45 | 23-DEC-19:00 | 22.00 | 19.30 |
Annual Sum or Average | 0.581152E+12 | 0.181451E+12 | ||||||||
Minimum of Months | 0.328684E+11 | 69218.76 | 17.42 | 12.40 | 0.138696E+11 | 14051.40 | 19.33 | 12.40 | ||
Maximum of Months | 0.638961E+11 | 107152.38 | 35.97 | 22.67 | 0.155741E+11 | 14055.26 | 40.20 | 28.00 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340304E+11 | 60856.39 | 01-JAN-04:01 | 13.75 | 9.25 | 0.105916E+11 | 6934.99 | 18-JAN-11:00 | 21.00 | 12.84 |
February | 0.308857E+11 | 56367.36 | 15-FEB-04:11 | 14.93 | 11.46 | 0.957227E+10 | 6934.94 | 23-FEB-11:50 | 27.17 | 16.22 |
March | 0.346676E+11 | 56399.03 | 07-MAR-04:11 | 14.87 | 12.01 | 0.106058E+11 | 6934.98 | 28-MAR-10:00 | 28.00 | 23.05 |
April | 0.345297E+11 | 51054.52 | 26-APR-03:01 | 23.10 | 12.40 | 0.102636E+11 | 6955.96 | 28-APR-10:00 | 40.00 | 18.54 |
May | 0.377151E+11 | 45611.56 | 05-MAY-03:21 | 26.35 | 16.50 | 0.106184E+11 | 7001.63 | 30-MAY-10:00 | 36.00 | 26.94 |
June | 0.366036E+11 | 36277.60 | 02-JUN-03:21 | 28.80 | 18.80 | 0.103265E+11 | 7021.60 | 09-JUN-10:50 | 38.63 | 27.06 |
July | 0.372188E+11 | 43150.63 | 03-JUL-03:21 | 29.50 | 17.11 | 0.107207E+11 | 7059.59 | 25-JUL-10:00 | 36.00 | 29.02 |
August | 0.374927E+11 | 26859.41 | 06-AUG-03:21 | 35.90 | 22.75 | 0.107466E+11 | 7062.46 | 08-AUG-10:00 | 35.80 | 29.24 |
September | 0.365837E+11 | 32951.69 | 26-SEP-03:21 | 26.55 | 20.56 | 0.103457E+11 | 7063.34 | 11-SEP-10:00 | 26.55 | 20.56 |
October | 0.382923E+11 | 42940.25 | 21-OCT-03:01 | 22.85 | 15.66 | 0.106214E+11 | 7014.46 | 07-OCT-10:50 | 22.85 | 15.66 |
November | 0.358011E+11 | 45113.22 | 26-NOV-04:01 | 17.58 | 14.78 | 0.102622E+11 | 6978.54 | 01-NOV-10:00 | 17.58 | 14.78 |
December | 0.351351E+11 | 54421.05 | 31-DEC-04:01 | 14.83 | 11.18 | 0.105979E+11 | 6934.97 | 18-DEC-11:00 | 14.83 | 11.18 |
Annual Sum or Average | 0.428956E+12 | 0.125273E+12 | ||||||||
Minimum of Months | 0.308857E+11 | 26859.41 | 13.75 | 9.25 | 0.957227E+10 | 6934.94 | 14.83 | 11.18 | ||
Maximum of Months | 0.382923E+11 | 60856.39 | 35.90 | 22.75 | 0.107466E+11 | 7063.34 | 40.00 | 29.24 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17.20 | 14.59 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 | 18.46 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 | 23.56 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 | 23.24 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 | 27.02 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 | 25.04 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 | 21.17 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 | 15.63 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.00 | 0.00 | 15.70 | 12.84 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3845532.07 | 2536.88 | 30-JAN-00:03 | 22.00 |
February | 25045828.92 | 5336.44 | 06-FEB-00:02 | 23.92 |
March | 0.123918E+09 | 11166.79 | 27-MAR-23:01 | 27.83 |
April | 0.326617E+09 | 12367.85 | 28-APR-23:01 | 28.83 |
May | 0.678078E+09 | 18941.86 | 11-MAY-23:01 | 33.00 |
June | 0.661475E+09 | 21917.03 | 08-JUN-23:01 | 34.83 |
July | 0.685444E+09 | 25578.10 | 20-JUL-23:01 | 37.67 |
August | 0.652513E+09 | 24788.71 | 05-AUG-23:01 | 37.00 |
September | 0.631227E+09 | 19272.25 | 04-SEP-23:01 | 33.22 |
October | 0.596718E+09 | 15187.09 | 05-OCT-23:01 | 30.67 |
November | 0.236429E+09 | 13694.74 | 01-NOV-23:01 | 29.50 |
December | 26292595.43 | 5146.85 | 12-DEC-00:02 | 23.90 |
Annual Sum or Average | 0.464760E+10 | |||
Minimum of Months | 3845532.07 | 2536.88 | 22.00 | |
Maximum of Months | 0.685444E+09 | 25578.10 | 37.67 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117915E+11 | 6902.89 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.106801E+11 | 6902.89 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.119793E+11 | 6902.89 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.114574E+11 | 6902.89 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.118854E+11 | 6902.89 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.115789E+11 | 6902.89 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.117653E+11 | 6902.89 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.119793E+11 | 6902.89 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.114602E+11 | 6902.89 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.117901E+11 | 6902.89 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.114146E+11 | 6902.89 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.117667E+11 | 6902.89 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.139549E+12 | 0.125277E+12 | ||||
Minimum of Months | 0.106801E+11 | 6902.89 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.119793E+11 | 6902.89 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.244214E+10 | 1429.66 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.221197E+10 | 1429.66 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.248103E+10 | 1429.66 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.237295E+10 | 1429.66 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.246159E+10 | 1429.66 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.239811E+10 | 1429.66 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.243671E+10 | 1429.66 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.248103E+10 | 1429.66 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.237352E+10 | 1429.66 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.244186E+10 | 1429.66 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.236408E+10 | 1429.66 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.243700E+10 | 1429.66 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.289020E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.221197E+10 | 1429.66 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.248103E+10 | 1429.66 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.117915E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61641992.57 | 0.278859E+10 |
February | 0.272721E+11 | 0.106801E+11 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410411E+09 | 0.190730E+10 |
March | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128039E+10 | 0.108469E+10 |
April | 0.292871E+11 | 0.114574E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311194E+10 | 0.282936E+09 |
May | 0.303219E+11 | 0.118854E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661059E+10 | 24363295.91 |
June | 0.295292E+11 | 0.115789E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739265E+10 | 2875017.82 |
July | 0.300798E+11 | 0.117653E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887047E+10 | 0.00 |
August | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913540E+10 | 0.00 |
September | 0.292871E+11 | 0.114602E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694353E+10 | 3379284.21 |
October | 0.300980E+11 | 0.117901E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510603E+10 | 38958583.68 |
November | 0.290996E+11 | 0.114146E+11 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238645E+10 | 0.298142E+09 |
December | 0.300798E+11 | 0.117667E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391551E+09 | 0.170508E+10 |
Annual Sum or Average | 0.356244E+12 | 0.139549E+12 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517010E+11 | 0.813632E+10 |
Minimum of Months | 0.272721E+11 | 0.106801E+11 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61641992.57 | 0.00 |
Maximum of Months | 0.305458E+11 | 0.119793E+11 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913540E+10 | 0.278859E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.244214E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 183793.21 | 0.146271E+09 |
February | 0.732850E+09 | 0.221197E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 4488743.70 | 0.147636E+09 |
March | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 16955604.39 | 95557306.03 |
April | 0.786997E+09 | 0.237295E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 41272730.54 | 54249606.95 |
May | 0.814802E+09 | 0.246159E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.103961E+09 | 13945506.23 |
June | 0.793501E+09 | 0.239811E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.119381E+09 | 8707659.05 |
July | 0.808298E+09 | 0.243671E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.139860E+09 | 1892411.32 |
August | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.138482E+09 | 1591578.44 |
September | 0.786997E+09 | 0.237352E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 94147000.64 | 8477578.57 |
October | 0.808786E+09 | 0.244186E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 65324093.09 | 22678793.40 |
November | 0.781956E+09 | 0.236408E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 23683669.48 | 55570982.94 |
December | 0.808298E+09 | 0.243700E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1800053.18 | 0.117154E+09 |
Annual Sum or Average | 0.957291E+10 | 0.289020E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.749540E+09 | 0.673733E+09 |
Minimum of Months | 0.732850E+09 | 0.221197E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 183793.21 | 1591578.44 |
Maximum of Months | 0.820818E+09 | 0.248103E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.139860E+09 | 0.147636E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110399E+10 | 0.259645E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799136E+09 | 0.269601E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110665E+10 | 0.341897E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109750E+10 | 0.369043E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111136E+10 | 0.410242E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101320E+10 | 0.388350E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996270E+09 | 0.401788E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104871E+10 | 0.371286E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112029E+10 | 0.336421E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129995E+10 | 0.309755E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128450E+10 | 0.249639E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113614E+10 | 0.236609E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131177E+11 | 0.394428E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799136E+09 | 0.236609E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129995E+10 | 0.410242E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 6902.89 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2196.43 | 23-JAN-14:00 | 4523.19 | 01-JAN-08:00 |
February | 30255.31 | 04-FEB-19:10 | 6902.89 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4369.40 | 06-FEB-14:00 | 4344.50 | 12-FEB-07:40 |
March | 30255.31 | 04-MAR-19:10 | 6902.89 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8325.39 | 27-MAR-11:03 | 3884.15 | 05-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 6902.89 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10412.58 | 28-APR-11:55 | 2925.94 | 01-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 6902.89 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10516.44 | 31-MAY-19:00 | 1218.92 | 01-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 6902.89 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10903.86 | 12-JUN-12:00 | 1026.63 | 22-JUN-08:00 |
July | 30255.31 | 01-JUL-18:10 | 6902.89 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12443.46 | 21-JUL-11:55 | 0.00 | 01-JUL-00:01 |
August | 30255.31 | 05-AUG-18:10 | 6902.89 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12711.72 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 30255.31 | 02-SEP-18:10 | 6902.89 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9872.08 | 26-SEP-12:00 | 263.59 | 25-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 6902.89 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8154.77 | 04-OCT-12:00 | 1418.90 | 29-OCT-07:00 |
November | 30255.31 | 04-NOV-18:10 | 6902.89 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5141.64 | 01-NOV-12:00 | 2730.28 | 26-NOV-07:10 |
December | 30255.31 | 02-DEC-19:10 | 6902.89 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2575.16 | 01-DEC-13:00 | 4413.84 | 31-DEC-07:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 6902.89 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2196.43 | 0.00 | |||||
Maximum of Months | 30255.31 | 6902.89 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 12711.72 | 4523.19 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1429.66 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 16.07 | 23-JAN-13:50 | 830.68 | 18-JAN-04:00 |
February | 813.01 | 04-FEB-19:10 | 1429.66 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 74.09 | 05-FEB-14:55 | 582.22 | 10-FEB-04:30 |
March | 813.01 | 04-MAR-19:10 | 1429.66 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 200.16 | 02-MAR-04:03 | 437.14 | 15-MAR-02:10 |
April | 813.01 | 01-APR-18:10 | 1429.66 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 194.60 | 28-APR-13:00 | 407.53 | 05-APR-00:50 |
May | 813.01 | 06-MAY-18:10 | 1429.66 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 546.70 | 21-MAY-13:00 | 198.62 | 02-MAY-02:00 |
June | 813.01 | 03-JUN-18:10 | 1429.66 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 302.24 | 09-JUN-03:10 | 246.38 | 06-JUN-04:00 |
July | 813.01 | 01-JUL-18:10 | 1429.66 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 376.68 | 13-JUL-23:30 | 138.52 | 07-JUL-03:20 |
August | 813.01 | 05-AUG-18:10 | 1429.66 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 405.95 | 01-AUG-24:00 | 151.73 | 08-AUG-04:00 |
September | 813.01 | 02-SEP-18:10 | 1429.66 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 208.94 | 13-SEP-03:51 | 172.48 | 28-SEP-03:20 |
October | 813.01 | 07-OCT-18:10 | 1429.66 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 174.46 | 19-OCT-14:55 | 278.06 | 20-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 1429.66 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 105.70 | 01-NOV-23:10 | 293.63 | 22-NOV-03:40 |
December | 813.01 | 02-DEC-19:10 | 1429.66 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 28.95 | 10-DEC-13:00 | 557.65 | 15-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1429.66 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 16.07 | 138.52 | ||||||
Maximum of Months | 813.01 | 1429.66 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 546.70 | 830.68 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.21 | 03-JAN-07:10 | 5386.04 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.02 | 15-FEB-07:42 | 5820.15 | 22-FEB-13:45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2335.59 | 27-MAR-06:43 | 6747.86 | 30-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.89 | 26-APR-06:00 | 6653.23 | 30-APR-12:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2499.15 | 04-MAY-07:51 | 6427.67 | 30-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.07 | 16-JUN-05:50 | 6223.76 | 08-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1742.94 | 04-JUL-04:40 | 6350.76 | 04-JUL-12:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.75 | 01-AUG-23:55 | 6271.74 | 30-AUG-11:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2458.92 | 30-SEP-07:41 | 5778.78 | 17-SEP-13:43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.23 | 29-OCT-04:55 | 5600.41 | 04-OCT-12:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.76 | 05-NOV-07:23 | 4918.67 | 07-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1657.20 | 19-DEC-05:00 | 5284.36 | 25-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.75 | 4918.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2499.15 | 6747.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 88250.98 | 29-JAN-04:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.71 |
February | 82949.49 | 10-FEB-04:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.75 |
March | 107152.38 | 23-MAR-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 |
April | 98414.96 | 26-APR-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
May | 95721.34 | 10-MAY-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 | 0.00 |
June | 73170.19 | 02-JUN-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 27.15 | 0.00 |
July | 84291.82 | 04-JUL-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 | 0.00 |
August | 69218.76 | 06-AUG-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 160.67 | 0.00 |
September | 69465.56 | 02-SEP-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 81.24 | 0.00 |
October | 90382.97 | 21-OCT-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.32 |
November | 88567.75 | 05-NOV-03:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 |
December | 91336.92 | 01-DEC-04:01 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 69218.76 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107152.38 | 0.00 | 11504.81 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 160.67 | 309.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 60856.39 | 01-JAN-04:01 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 146.28 |
February | 56367.36 | 15-FEB-04:11 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 200.16 |
March | 56399.03 | 07-MAR-04:11 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 84.53 |
April | 51054.52 | 26-APR-03:01 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
May | 45611.56 | 05-MAY-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 |
June | 36277.60 | 02-JUN-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 3.02 | 0.00 |
July | 43150.63 | 03-JUL-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 |
August | 26859.41 | 06-AUG-03:21 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 70.18 | 0.00 |
September | 32951.69 | 26-SEP-03:21 | 0.00 | 2144.49 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 21.26 |
October | 42940.25 | 21-OCT-03:01 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 |
November | 45113.22 | 26-NOV-04:01 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 179.48 |
December | 54421.05 | 31-DEC-04:01 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26859.41 | 0.00 | 1906.21 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60856.39 | 0.00 | 2382.77 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 70.18 | 200.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1066.35 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.55 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.45 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 968.26 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.59 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.99 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.62 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.55 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1019.80 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.73 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.25 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.55 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.127726E+12 | 77801.32 | 24-JAN-11:00 | 0.643930E+11 | 43001.69 | 16-JAN-11:20 |
February | 0.120679E+12 | 84009.89 | 07-FEB-12:00 | 0.576604E+11 | 42956.72 | 04-FEB-11:30 |
March | 0.140706E+12 | 91789.84 | 27-MAR-10:00 | 0.626060E+11 | 42794.63 | 04-MAR-11:39 |
April | 0.149838E+12 | 99026.08 | 28-APR-11:00 | 0.585925E+11 | 42557.78 | 01-APR-10:30 |
May | 0.176195E+12 | 104908.28 | 31-MAY-11:00 | 0.587070E+11 | 42229.38 | 06-MAY-10:09 |
June | 0.185631E+12 | 106958.56 | 09-JUN-11:00 | 0.555504E+11 | 42017.24 | 03-JUN-10:20 |
July | 0.204504E+12 | 108389.06 | 18-JUL-11:00 | 0.567855E+11 | 41916.91 | 29-JUL-10:20 |
August | 0.208494E+12 | 112722.34 | 16-AUG-11:00 | 0.575429E+11 | 42029.52 | 27-AUG-10:30 |
September | 0.188814E+12 | 106655.27 | 07-SEP-11:00 | 0.570305E+11 | 42302.41 | 30-SEP-10:09 |
October | 0.176117E+12 | 101563.48 | 06-OCT-17:00 | 0.608194E+11 | 42586.82 | 29-OCT-10:00 |
November | 0.150862E+12 | 95434.49 | 01-NOV-11:00 | 0.606607E+11 | 42818.71 | 26-NOV-11:30 |
December | 0.137111E+12 | 84585.26 | 05-DEC-18:19 | 0.639616E+11 | 42981.83 | 31-DEC-11:09 |
Annual Sum or Average | 0.196668E+13 | 0.714310E+12 | ||||
Minimum of Months | 0.120679E+12 | 77801.32 | 0.555504E+11 | 41916.91 | ||
Maximum of Months | 0.208494E+12 | 112722.34 | 0.643930E+11 | 43001.69 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.142337E+11 | 0.682651E+10 | 0.391293E+11 | 0.00 | 0.303834E+11 | 37879553.69 | 0.00 | 0.249453E+11 | 0.00 | 0.00 | 0.00 | 0.655947E+10 | 0.00 |
February | 0.128921E+11 | 0.592272E+10 | 0.353426E+11 | 0.00 | 0.274828E+11 | 34213790.43 | 0.00 | 0.279690E+11 | 0.00 | 0.00 | 0.00 | 0.593493E+10 | 0.00 |
March | 0.144603E+11 | 0.620292E+10 | 0.391293E+11 | 0.00 | 0.304757E+11 | 37879553.69 | 0.00 | 0.381099E+11 | 0.00 | 0.00 | 0.00 | 0.662570E+10 | 0.00 |
April | 0.138304E+11 | 0.562604E+10 | 0.378671E+11 | 0.00 | 0.295438E+11 | 36657632.61 | 0.00 | 0.510624E+11 | 0.00 | 0.00 | 0.00 | 0.636349E+10 | 0.00 |
May | 0.143470E+11 | 0.551066E+10 | 0.391293E+11 | 0.00 | 0.306967E+11 | 37879553.69 | 0.00 | 0.741455E+11 | 0.00 | 0.00 | 0.00 | 0.658932E+10 | 0.00 |
June | 0.139770E+11 | 0.519200E+10 | 0.378671E+11 | 0.00 | 0.299361E+11 | 36657632.61 | 0.00 | 0.865491E+11 | 0.00 | 0.00 | 0.00 | 0.639950E+10 | 0.00 |
July | 0.142020E+11 | 0.541726E+10 | 0.391293E+11 | 0.00 | 0.312518E+11 | 37879553.69 | 0.00 | 0.102025E+12 | 0.00 | 0.00 | 0.00 | 0.653302E+10 | 0.00 |
August | 0.144603E+11 | 0.567823E+10 | 0.391293E+11 | 0.00 | 0.312916E+11 | 37879553.69 | 0.00 | 0.105350E+12 | 0.00 | 0.00 | 0.00 | 0.660905E+10 | 0.00 |
September | 0.138337E+11 | 0.583756E+10 | 0.378671E+11 | 0.00 | 0.300240E+11 | 36657632.61 | 0.00 | 0.891635E+11 | 0.00 | 0.00 | 0.00 | 0.635521E+10 | 0.00 |
October | 0.142320E+11 | 0.640621E+10 | 0.391293E+11 | 0.00 | 0.307804E+11 | 37879553.69 | 0.00 | 0.731505E+11 | 0.00 | 0.00 | 0.00 | 0.655197E+10 | 0.00 |
November | 0.137787E+11 | 0.652159E+10 | 0.378671E+11 | 0.00 | 0.295829E+11 | 36657632.61 | 0.00 | 0.511096E+11 | 0.00 | 0.00 | 0.00 | 0.634449E+10 | 0.00 |
December | 0.142037E+11 | 0.692266E+10 | 0.391293E+11 | 0.00 | 0.304708E+11 | 37879553.69 | 0.00 | 0.340710E+11 | 0.00 | 0.00 | 0.00 | 0.654946E+10 | 0.00 |
Annual Sum or Average | 0.168451E+12 | 0.720644E+11 | 0.460716E+12 | 0.00 | 0.361920E+12 | 0.446001E+09 | 0.00 | 0.757651E+12 | 0.00 | 0.00 | 0.00 | 0.774156E+11 | 0.00 |
Minimum of Months | 0.128921E+11 | 0.519200E+10 | 0.353426E+11 | 0.00 | 0.274828E+11 | 34213790.43 | 0.00 | 0.249453E+11 | 0.00 | 0.00 | 0.00 | 0.593493E+10 | 0.00 |
Maximum of Months | 0.144603E+11 | 0.692266E+10 | 0.391293E+11 | 0.00 | 0.312916E+11 | 37879553.69 | 0.00 | 0.105350E+12 | 0.00 | 0.00 | 0.00 | 0.662570E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.244933E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.216219E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.227063E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.199799E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.188073E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.169377E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.168858E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.176431E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.184179E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.209197E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.220481E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.240619E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.00 | 0.00 | 0.244523E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.168858E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.244933E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8332.55 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13267.63 | 01-JAN-23:19 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 8332.55 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13267.63 | 01-FEB-08:39 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 8332.55 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13267.63 | 01-MAR-09:50 | 17.86 | 25-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 8332.55 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13267.63 | 01-APR-08:09 | 17.86 | 01-APR-09:50 | 0.00 | 01-APR-00:10 |
May | 8332.55 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13267.63 | 01-MAY-08:39 | 17.86 | 04-MAY-07:00 | 0.00 | 01-MAY-00:10 |
June | 8332.55 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13267.63 | 01-JUN-04:10 | 17.86 | 04-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 8332.55 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13267.63 | 01-JUL-04:40 | 17.86 | 02-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 8332.55 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13267.63 | 01-AUG-04:19 | 17.86 | 07-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 8332.55 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13267.63 | 01-SEP-04:10 | 17.86 | 01-SEP-23:10 | 0.00 | 01-SEP-00:10 |
October | 8332.55 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13267.63 | 01-OCT-04:19 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 8332.55 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13267.63 | 01-NOV-08:39 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 8332.55 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13267.63 | 01-DEC-08:39 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 8332.55 | 4578.48 | 24699.69 | 0.00 | 13267.63 | 17.86 | 0.00 | ||||||
Maximum of Months | 8332.55 | 4578.48 | 24699.69 | 0.00 | 13267.63 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 27469.71 | 24-JAN-12:00 | 0.00 | 0.00 | 0.00 | 4790.29 | 09-JAN-07:19 | 0.00 |
February | 34148.70 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 4789.04 | 13-FEB-07:19 | 0.00 |
March | 40853.54 | 27-MAR-11:09 | 0.00 | 0.00 | 0.00 | 4787.47 | 07-MAR-07:49 | 0.00 |
April | 49144.58 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 4784.17 | 05-APR-18:30 | 0.00 |
May | 54989.32 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4784.29 | 16-MAY-06:00 | 0.00 |
June | 56824.34 | 09-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4784.21 | 20-JUN-18:40 | 0.00 |
July | 58616.73 | 21-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4784.06 | 11-JUL-06:00 | 0.00 |
August | 62768.02 | 16-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4783.79 | 04-AUG-06:49 | 0.00 |
September | 57135.05 | 07-SEP-12:50 | 0.00 | 0.00 | 0.00 | 4783.94 | 07-SEP-06:00 | 0.00 |
October | 49331.70 | 07-OCT-18:00 | 0.00 | 0.00 | 0.00 | 4783.65 | 19-OCT-06:49 | 0.00 |
November | 45524.79 | 01-NOV-11:00 | 0.00 | 0.00 | 0.00 | 4784.39 | 22-NOV-07:49 | 0.00 |
December | 33985.02 | 05-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4788.47 | 18-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 27469.71 | 0.00 | 0.00 | 0.00 | 4783.65 | 0.00 | ||
Maximum of Months | 62768.02 | 0.00 | 0.00 | 0.00 | 4790.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 77801.32 | 24-JAN-11:00 | 8332.55 | 24699.69 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 25116.03 | 0.00 |
February | 84009.89 | 07-FEB-12:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 34148.70 | 0.00 |
March | 91789.84 | 27-MAR-10:00 | 8332.55 | 24699.69 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 38891.86 | 0.00 |
April | 99026.08 | 28-APR-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 49144.58 | 0.00 |
May | 104908.28 | 31-MAY-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 54989.32 | 0.00 |
June | 106958.56 | 09-JUN-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 56824.34 | 0.00 |
July | 108389.06 | 18-JUL-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 58234.94 | 0.00 |
August | 112722.34 | 16-AUG-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 62768.02 | 0.00 |
September | 106655.27 | 07-SEP-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 56518.41 | 0.00 |
October | 101563.48 | 06-OCT-17:00 | 8332.55 | 20676.91 | 4578.48 | 0.00 | 13267.63 | 17.86 | 0.00 | 48139.45 | 0.00 |
November | 95434.49 | 01-NOV-11:00 | 8332.55 | 23090.58 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 45524.79 | 0.00 |
December | 84585.26 | 05-DEC-18:19 | 8332.55 | 20676.91 | 4578.48 | 0.00 | 13267.63 | 17.86 | 0.00 | 31237.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 77801.32 | 8332.55 | 20676.91 | 0.00 | 0.00 | 13267.63 | 17.86 | 0.00 | 25116.03 | 0.00 | |
Maximum of Months | 112722.34 | 8332.55 | 24699.69 | 4578.48 | 0.00 | 13267.63 | 17.86 | 0.00 | 62768.02 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 17418.39 | 11-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 17366.80 | 01-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 17158.61 | 01-MAR-19:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 16798.63 | 03-APR-18:00 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 16469.61 | 01-MAY-18:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16166.04 | 01-JUN-18:19 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16017.31 | 31-JUL-06:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16199.95 | 31-AUG-18:40 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 16501.75 | 29-SEP-18:30 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 16882.39 | 31-OCT-18:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 17202.42 | 30-NOV-19:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 17387.73 | 29-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16017.31 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 17418.39 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.73 | 0.00 | 24.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.78 | 0.00 | 24.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.93 | 0.00 | 24.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.10 | 0.00 | 25.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.47 | 0.00 | 25.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 25.46 | 0.00 | 25.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.39 | 1.33 | 25.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 25.25 | 4.67 | 25.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.45 | 0.00 | 25.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.47 | 0.00 | 25.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.23 | 0.00 | 25.23 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.87 | 0.00 | 24.87 |
Annual Sum or Average | 0.00 | 0.00 | 78.00 | 25.23 | 6.00 | 25.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.73 | 0.00 | 24.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 25.47 | 4.67 | 25.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.60 | 0.00 | 30.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 30.73 | 0.00 | 30.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.89 | 0.00 | 30.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 30.18 | 7.67 | 29.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 | 28.45 | 93.17 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 399.33 | 28.51 | 360.00 | 28.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 568.00 | 29.42 | 516.33 | 29.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 595.00 | 29.68 | 543.00 | 29.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 457.83 | 28.86 | 414.67 | 28.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 154.83 | 28.73 | 117.17 | 28.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 29.81 | 14.67 | 29.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 30.82 | 0.00 | 30.82 |
Annual Sum or Average | 0.00 | 0.00 | 2487.00 | 29.22 | 2066.67 | 29.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 28.45 | 0.00 | 28.06 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 595.00 | 30.89 | 543.00 | 30.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.50 | 23.09 | 552.00 | 24.01 | 0.83 | 24.02 |
February | 9.17 | 24.63 | 528.67 | 24.08 | 4.17 | 24.10 |
March | 18.17 | 25.76 | 594.00 | 24.17 | 18.17 | 24.22 |
April | 45.83 | 25.88 | 586.50 | 24.30 | 45.83 | 24.41 |
May | 114.67 | 25.35 | 611.00 | 24.43 | 114.67 | 24.56 |
June | 291.33 | 24.57 | 592.00 | 24.37 | 291.33 | 24.42 |
July | 378.67 | 24.47 | 609.00 | 24.36 | 378.67 | 24.39 |
August | 400.00 | 24.45 | 612.00 | 24.36 | 400.00 | 24.38 |
September | 349.00 | 24.47 | 590.00 | 24.35 | 349.00 | 24.38 |
October | 181.67 | 24.81 | 610.00 | 24.37 | 181.67 | 24.46 |
November | 61.00 | 25.27 | 591.00 | 24.27 | 61.00 | 24.36 |
December | 20.67 | 24.61 | 602.33 | 24.10 | 16.83 | 24.12 |
Annual Sum or Average | 1889.67 | 24.63 | 7078.50 | 24.29 | 1862.17 | 24.35 |
Minimum of Months | 9.17 | 23.09 | 528.67 | 24.01 | 0.83 | 24.02 |
Maximum of Months | 400.00 | 25.88 | 612.00 | 24.43 | 400.00 | 24.56 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.17 | 25.90 | 587.33 | 25.68 | 457.50 | 25.77 |
February | 458.33 | 25.97 | 547.17 | 25.79 | 458.33 | 25.85 |
March | 546.50 | 25.99 | 612.00 | 25.91 | 546.50 | 25.93 |
April | 582.17 | 26.01 | 590.00 | 26.01 | 582.17 | 26.01 |
May | 611.00 | 26.26 | 611.00 | 26.26 | 611.00 | 26.26 |
June | 592.00 | 27.41 | 592.00 | 27.41 | 592.00 | 27.41 |
July | 609.00 | 28.81 | 609.00 | 28.81 | 609.00 | 28.81 |
August | 612.00 | 29.17 | 612.00 | 29.17 | 612.00 | 29.17 |
September | 590.00 | 27.91 | 590.00 | 27.91 | 590.00 | 27.91 |
October | 610.00 | 26.43 | 610.00 | 26.43 | 610.00 | 26.43 |
November | 587.67 | 26.03 | 591.00 | 26.03 | 587.67 | 26.03 |
December | 530.67 | 25.95 | 604.83 | 25.84 | 530.67 | 25.88 |
Annual Sum or Average | 6794.50 | 26.88 | 7156.33 | 26.81 | 6786.83 | 26.83 |
Minimum of Months | 458.33 | 25.90 | 547.17 | 25.68 | 457.50 | 25.77 |
Maximum of Months | 612.00 | 29.17 | 612.00 | 29.17 | 612.00 | 29.17 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.98578 | 47.77118 | 0.59204 | 12.67339 |
February | 551.00000 | 24.04333 | 50.81359 | 0.63923 | 13.83048 |
March | 612.00000 | 24.11432 | 48.39709 | 0.65491 | 14.33096 |
April | 590.00000 | 24.17794 | 51.72562 | 0.72037 | 16.33278 |
May | 611.00000 | 24.26011 | 54.08740 | 0.04375 | 6.44080 |
June | 592.00000 | 24.27914 | 61.49814 | 0.13353 | 6.95536 |
July | 609.00000 | 24.29065 | 63.98480 | 0.19171 | 7.40652 |
August | 612.00000 | 24.29553 | 65.35869 | 0.22462 | 7.60985 |
September | 590.00000 | 24.27781 | 64.08751 | 0.17446 | 7.23666 |
October | 610.00000 | 24.24481 | 57.99397 | 0.83888 | 20.40009 |
November | 591.00000 | 24.16789 | 54.23852 | 0.75412 | 17.32301 |
December | 609.00000 | 24.07077 | 52.05035 | 0.66516 | 14.53380 |
Annual Sum or Average | 7187.00000 | 24.18475 | 56.02309 | 0.46815 | 12.07480 |
Minimum of Months | 551.00000 | 23.98578 | 47.77118 | 0.04375 | 6.44080 |
Maximum of Months | 612.00000 | 24.29553 | 65.35869 | 0.83888 | 20.40009 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.37866 | 47.70398 | 1.10526 | 32.43883 |
February | 551.00000 | 25.62083 | 50.72565 | 1.19259 | 35.88552 |
March | 612.00000 | 25.82893 | 48.28123 | 1.23440 | 37.48663 |
April | 590.00000 | 26.00084 | 52.22241 | 1.33022 | 42.03662 |
May | 611.00000 | 26.26274 | 56.43789 | 0.96222 | 25.88892 |
June | 592.00000 | 27.41494 | 63.13452 | 1.42680 | 47.52462 |
July | 609.00000 | 28.81082 | 65.15895 | 1.93912 | 68.28263 |
August | 612.00000 | 29.17319 | 66.51424 | 2.08910 | 74.19759 |
September | 590.00000 | 27.90610 | 65.31719 | 1.62294 | 55.56952 |
October | 610.00000 | 26.43356 | 59.07273 | 1.54175 | 52.59048 |
November | 591.00000 | 26.02531 | 54.36595 | 1.37104 | 44.08973 |
December | 609.00000 | 25.72056 | 51.63083 | 1.23687 | 37.77628 |
Annual Sum or Average | 7187.00000 | 26.72265 | 56.74151 | 1.42273 | 46.21939 |
Minimum of Months | 551.00000 | 25.37866 | 47.70398 | 0.96222 | 25.88892 |
Maximum of Months | 612.00000 | 29.17319 | 66.51424 | 2.08910 | 74.19759 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.533103E+11 | 0.180123E+11 | 547.57 | 0.391318E+11 | 0.141786E+11 | 0.00 | 1.00 | 23-JAN-04:01 | 0.00 | 01-JAN-00:10 | 138496.25 | 30-JAN-04:01 | 103924.71 | 29-JAN-04:01 | 58185.61 | 30-JAN-04:01 | 37156.83 | 30-JAN-04:01 | 0.00 | 01-JAN-00:10 |
February | 0.589688E+11 | 0.196638E+11 | 517.83 | 0.420105E+11 | 0.169583E+11 | 0.00 | 1.00 | 06-FEB-04:01 | 0.00 | 01-FEB-00:05 | 141410.51 | 09-FEB-04:01 | 92884.27 | 10-FEB-04:01 | 63908.84 | 09-FEB-04:01 | 37392.17 | 09-FEB-04:01 | 0.00 | 01-FEB-00:05 |
March | 0.780080E+11 | 0.259296E+11 | 600.62 | 0.583157E+11 | 0.196923E+11 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 | 141706.02 | 29-MAR-03:01 | 129340.96 | 28-MAR-03:01 | 66512.50 | 29-MAR-03:01 | 37416.64 | 29-MAR-03:01 | 0.00 | 01-MAR-00:03 |
April | 0.102723E+12 | 0.335928E+11 | 591.91 | 0.740119E+11 | 0.287109E+11 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 143706.31 | 30-APR-03:01 | 115733.10 | 26-APR-03:01 | 87062.80 | 30-APR-03:02 | 37586.27 | 30-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.145305E+12 | 0.482659E+11 | 625.43 | 0.103308E+12 | 0.419975E+11 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 143706.31 | 02-MAY-03:01 | 122308.00 | 10-MAY-03:01 | 93267.51 | 30-MAY-03:01 | 40257.08 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.176505E+12 | 0.571772E+11 | 615.30 | 0.109438E+12 | 0.670671E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 143706.31 | 07-JUN-03:01 | 94710.12 | 16-JUN-03:01 | 98277.48 | 27-JUN-03:07 | 42039.85 | 09-JUN-12:00 | 0.00 | 01-JUN-00:01 |
July | 0.211942E+12 | 0.690262E+11 | 638.76 | 0.125414E+12 | 0.865278E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 143444.51 | 06-JUL-03:50 | 108204.95 | 04-JUL-03:01 | 99201.96 | 27-JUL-03:52 | 43643.18 | 18-JUL-12:05 | 0.00 | 01-JUL-00:01 |
August | 0.222208E+12 | 0.719270E+11 | 638.83 | 0.128447E+12 | 0.937607E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 143706.31 | 31-AUG-03:02 | 98906.83 | 06-AUG-03:01 | 101656.00 | 08-AUG-03:52 | 46768.04 | 10-AUG-13:00 | 0.00 | 01-AUG-00:01 |
September | 0.188398E+12 | 0.593590E+11 | 614.29 | 0.108754E+12 | 0.796437E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 143706.31 | 29-SEP-03:03 | 92107.56 | 02-SEP-03:01 | 100996.21 | 03-SEP-03:10 | 42806.18 | 07-SEP-12:50 | 0.00 | 01-SEP-00:01 |
October | 0.150020E+12 | 0.474496E+11 | 619.67 | 0.956805E+11 | 0.543393E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 143706.31 | 01-OCT-03:02 | 105272.78 | 21-OCT-03:01 | 102635.24 | 01-OCT-03:08 | 37586.27 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.105480E+12 | 0.337078E+11 | 592.19 | 0.714910E+11 | 0.339891E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 143706.31 | 03-NOV-03:01 | 101922.03 | 05-NOV-03:01 | 74067.62 | 08-NOV-04:01 | 37586.27 | 02-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.715090E+11 | 0.235642E+11 | 593.81 | 0.491431E+11 | 0.223659E+11 | 0.00 | 1.00 | 02-DEC-04:01 | 0.00 | 01-DEC-00:03 | 140824.27 | 06-DEC-04:01 | 97971.78 | 01-DEC-04:01 | 68003.77 | 06-DEC-04:01 | 37344.01 | 06-DEC-04:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.156438E+13 | 0.507675E+12 | 7196.20 | 0.100515E+13 | 0.559231E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.533103E+11 | 0.180123E+11 | 517.83 | 0.391318E+11 | 0.141786E+11 | 0.00 | 1.00 | 0.00 | 138496.25 | 92107.56 | 58185.61 | 37156.83 | 0.00 | |||||||
Maximum of Months | 0.222208E+12 | 0.719270E+11 | 638.83 | 0.128447E+12 | 0.937607E+11 | 0.00 | 1.00 | 0.00 | 143706.31 | 129340.96 | 102635.24 | 46768.04 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.216039E+11 | 0.693305E+10 | 504.50 | 0.149531E+11 | 0.665077E+10 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:10 | 45249.14 | 30-JAN-04:01 | 34835.52 | 18-JAN-04:01 | 23356.03 | 10-JAN-04:01 | 12279.59 | 30-JAN-04:01 | 0.00 | 01-JAN-00:10 |
February | 0.266274E+11 | 0.830520E+10 | 499.73 | 0.182043E+11 | 0.842306E+10 | 0.00 | 1.00 | 01-FEB-04:01 | 0.00 | 01-FEB-00:05 | 46839.19 | 09-FEB-04:01 | 35872.96 | 10-FEB-04:31 | 24602.55 | 03-FEB-04:01 | 12401.08 | 09-FEB-04:01 | 0.00 | 01-FEB-00:05 |
March | 0.396727E+11 | 0.121802E+11 | 621.37 | 0.294895E+11 | 0.101832E+11 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-01:01 | 47923.54 | 28-MAR-11:00 | 44632.54 | 27-MAR-10:55 | 27521.62 | 24-MAR-03:21 | 14538.45 | 27-MAR-10:55 | 0.00 | 01-MAR-00:03 |
April | 0.594032E+11 | 0.174696E+11 | 661.43 | 0.430670E+11 | 0.163362E+11 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 49094.89 | 29-APR-19:55 | 46040.78 | 28-APR-12:32 | 31371.78 | 30-APR-03:21 | 15948.30 | 28-APR-12:00 | 0.00 | 01-APR-00:01 |
May | 0.885316E+11 | 0.258796E+11 | 703.40 | 0.661937E+11 | 0.223380E+11 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 49094.89 | 18-MAY-03:01 | 46176.00 | 11-MAY-11:15 | 32173.89 | 24-MAY-03:32 | 15808.24 | 31-MAY-19:00 | 0.00 | 01-MAY-00:01 |
June | 0.102010E+12 | 0.293719E+11 | 684.79 | 0.662934E+11 | 0.357169E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 49094.89 | 25-JUN-07:54 | 46287.86 | 20-JUN-16:33 | 34493.35 | 08-JUN-03:33 | 15729.92 | 21-JUN-11:55 | 0.00 | 01-JUN-00:01 |
July | 0.111576E+12 | 0.329992E+11 | 710.25 | 0.716296E+11 | 0.399461E+11 | 0.00 | 1.00 | 01-JUL-00:08 | 0.00 | 01-JUL-00:01 | 49094.89 | 02-JUL-05:00 | 46315.66 | 20-JUL-18:42 | 33567.54 | 27-JUL-03:43 | 16718.90 | 21-JUL-12:00 | 0.00 | 01-JUL-00:01 |
August | 0.113053E+12 | 0.334232E+11 | 710.57 | 0.712920E+11 | 0.417607E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:01 | 49094.89 | 31-AUG-04:16 | 46080.29 | 15-AUG-18:27 | 34618.24 | 08-AUG-03:43 | 16631.99 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 0.105459E+12 | 0.298045E+11 | 686.04 | 0.621705E+11 | 0.432882E+11 | 0.00 | 1.00 | 01-SEP-00:06 | 0.00 | 01-SEP-00:01 | 49094.89 | 25-SEP-07:58 | 46176.00 | 13-SEP-11:33 | 34739.60 | 10-SEP-06:00 | 15379.94 | 26-SEP-12:00 | 0.00 | 01-SEP-00:01 |
October | 0.918329E+11 | 0.257009E+11 | 704.37 | 0.577960E+11 | 0.340369E+11 | 0.00 | 1.00 | 01-OCT-00:07 | 0.00 | 01-OCT-00:01 | 49094.89 | 07-OCT-08:23 | 44885.92 | 09-OCT-11:57 | 36113.76 | 07-OCT-03:01 | 14420.96 | 09-OCT-11:57 | 0.00 | 01-OCT-00:01 |
November | 0.605419E+11 | 0.174018E+11 | 664.01 | 0.400557E+11 | 0.204863E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 49094.89 | 02-NOV-20:20 | 35214.72 | 05-NOV-12:00 | 29554.06 | 08-NOV-04:21 | 13240.41 | 01-NOV-13:55 | 0.00 | 01-NOV-00:01 |
December | 0.344745E+11 | 0.105068E+11 | 570.77 | 0.222131E+11 | 0.122613E+11 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-01:01 | 46520.39 | 11-DEC-04:01 | 31898.32 | 01-DEC-04:01 | 26799.43 | 06-DEC-04:01 | 12376.65 | 11-DEC-04:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.854786E+12 | 0.249976E+12 | 7721.22 | 0.563358E+12 | 0.291428E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.216039E+11 | 0.693305E+10 | 499.73 | 0.149531E+11 | 0.665077E+10 | 0.00 | 1.00 | 0.00 | 45249.14 | 31898.32 | 23356.03 | 12279.59 | 0.00 | |||||||
Maximum of Months | 0.113053E+12 | 0.334232E+11 | 710.57 | 0.716296E+11 | 0.432882E+11 | 0.00 | 1.00 | 0.00 | 49094.89 | 46315.66 | 36113.76 | 16718.90 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.24 | 33.08 | 76.17 | 191.78 | 298.15 | 0.00 | 0.00 | 0.00 |
February | 119.25 | 32.44 | 86.81 | 249.94 | 251.63 | 0.00 | 0.00 | 0.00 |
March | 131.68 | 32.49 | 99.18 | 343.76 | 188.37 | 0.00 | 0.00 | 0.00 |
April | 160.26 | 46.63 | 113.64 | 539.35 | 117.73 | 0.00 | 0.00 | 0.00 |
May | 178.54 | 56.66 | 121.88 | 779.54 | 36.13 | 0.00 | 0.00 | 0.00 |
June | 175.27 | 53.64 | 121.62 | 827.22 | 13.03 | 0.00 | 0.00 | 0.00 |
July | 163.89 | 47.48 | 116.41 | 916.16 | 0.50 | 0.00 | 0.00 | 0.00 |
August | 167.55 | 51.48 | 116.07 | 928.35 | 0.53 | 0.00 | 0.00 | 0.00 |
September | 157.25 | 48.49 | 108.76 | 741.86 | 18.61 | 0.00 | 0.00 | 0.00 |
October | 142.71 | 46.52 | 96.19 | 564.93 | 59.20 | 0.00 | 0.00 | 0.00 |
November | 119.84 | 38.01 | 81.82 | 364.35 | 138.54 | 0.00 | 0.00 | 0.00 |
December | 97.26 | 26.96 | 70.30 | 199.74 | 247.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.66 | 42.87 | 100.79 | 555.71 | 113.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.26 | 26.96 | 70.30 | 191.78 | 0.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 178.54 | 56.66 | 121.88 | 928.35 | 298.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.22 | 125.94 | 143.28 | 620.81 | 405.82 | 0.00 | 0.00 | 0.00 |
February | 255.12 | 105.12 | 150.00 | 634.32 | 353.76 | 0.00 | 0.00 | 0.00 |
March | 212.98 | 60.83 | 152.15 | 599.11 | 273.68 | 0.00 | 0.00 | 0.00 |
April | 170.93 | 24.09 | 146.84 | 606.40 | 174.15 | 0.00 | 0.00 | 0.00 |
May | 141.47 | 4.45 | 137.02 | 739.02 | 53.52 | 0.00 | 0.00 | 0.00 |
June | 131.16 | 0.34 | 130.82 | 781.94 | 19.13 | 0.00 | 0.00 | 0.00 |
July | 131.56 | 1.62 | 129.93 | 952.30 | 0.71 | 0.00 | 0.00 | 0.00 |
August | 155.92 | 14.68 | 141.25 | 1050.36 | 0.68 | 0.00 | 0.00 | 0.00 |
September | 209.02 | 54.58 | 154.45 | 1021.92 | 26.36 | 0.00 | 0.00 | 0.00 |
October | 267.46 | 109.47 | 158.00 | 1021.16 | 83.29 | 0.00 | 0.00 | 0.00 |
November | 289.54 | 139.66 | 149.89 | 897.89 | 193.94 | 0.00 | 0.00 | 0.00 |
December | 265.84 | 129.93 | 135.91 | 676.13 | 340.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 208.06 | 63.99 | 144.06 | 801.18 | 159.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.16 | 0.34 | 129.93 | 599.11 | 0.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 289.54 | 139.66 | 158.00 | 1050.36 | 405.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.70 | 31.16 | 76.54 | 204.43 | 316.73 | 0.00 | 0.00 | 0.00 |
February | 122.89 | 35.34 | 87.55 | 270.66 | 265.34 | 0.00 | 0.00 | 0.00 |
March | 144.76 | 42.79 | 101.97 | 389.96 | 198.55 | 0.00 | 0.00 | 0.00 |
April | 158.10 | 44.20 | 113.90 | 529.62 | 125.42 | 0.00 | 0.00 | 0.00 |
May | 172.30 | 51.56 | 120.75 | 750.54 | 38.22 | 0.00 | 0.00 | 0.00 |
June | 178.03 | 56.10 | 121.93 | 826.20 | 13.55 | 0.00 | 0.00 | 0.00 |
July | 163.60 | 46.95 | 116.65 | 904.20 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 167.32 | 50.64 | 116.68 | 921.48 | 0.44 | 0.00 | 0.00 | 0.00 |
September | 159.46 | 50.05 | 109.41 | 739.75 | 18.69 | 0.00 | 0.00 | 0.00 |
October | 141.98 | 46.02 | 95.95 | 556.76 | 61.77 | 0.00 | 0.00 | 0.00 |
November | 122.25 | 40.22 | 82.02 | 379.01 | 150.29 | 0.00 | 0.00 | 0.00 |
December | 102.17 | 31.02 | 71.15 | 229.15 | 264.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.13 | 43.87 | 101.26 | 560.19 | 120.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.17 | 31.02 | 71.15 | 204.43 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 178.03 | 56.10 | 121.93 | 921.48 | 316.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292595E+09 | 88591740.02 | 0.204003E+09 | 0.513667E+09 | 0.798562E+09 |
February | 0.288488E+09 | 78468675.57 | 0.210019E+09 | 0.604662E+09 | 0.608739E+09 |
March | 0.352687E+09 | 87034111.03 | 0.265653E+09 | 0.920729E+09 | 0.504522E+09 |
April | 0.415406E+09 | 0.120858E+09 | 0.294548E+09 | 0.139799E+10 | 0.305162E+09 |
May | 0.478207E+09 | 0.151763E+09 | 0.326444E+09 | 0.208793E+10 | 96769704.35 |
June | 0.454294E+09 | 0.139043E+09 | 0.315251E+09 | 0.214417E+10 | 33770958.45 |
July | 0.438956E+09 | 0.127176E+09 | 0.311780E+09 | 0.245384E+10 | 1326035.80 |
August | 0.448769E+09 | 0.137889E+09 | 0.310880E+09 | 0.248649E+10 | 1411546.25 |
September | 0.407580E+09 | 0.125682E+09 | 0.281898E+09 | 0.192291E+10 | 48231968.63 |
October | 0.382236E+09 | 0.124591E+09 | 0.257645E+09 | 0.151312E+10 | 0.158559E+09 |
November | 0.310616E+09 | 98531158.60 | 0.212085E+09 | 0.944389E+09 | 0.359091E+09 |
December | 0.260513E+09 | 72217363.71 | 0.188296E+09 | 0.534973E+09 | 0.662295E+09 |
Annual Sum or Average | 0.453035E+10 | 0.135184E+10 | 0.317850E+10 | 0.175249E+11 | 0.357844E+10 |
Minimum of Months | 0.260513E+09 | 72217363.71 | 0.188296E+09 | 0.513667E+09 | 1326035.80 |
Maximum of Months | 0.478207E+09 | 0.151763E+09 | 0.326444E+09 | 0.248649E+10 | 0.798562E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.721087E+09 | 0.337320E+09 | 0.383767E+09 | 0.166278E+10 | 0.108695E+10 |
February | 0.617184E+09 | 0.254304E+09 | 0.362880E+09 | 0.153456E+10 | 0.855813E+09 |
March | 0.570435E+09 | 0.162918E+09 | 0.407518E+09 | 0.160464E+10 | 0.733030E+09 |
April | 0.443048E+09 | 62442176.30 | 0.380606E+09 | 0.157180E+10 | 0.451389E+09 |
May | 0.378913E+09 | 11912801.17 | 0.367000E+09 | 0.197940E+10 | 0.143354E+09 |
June | 0.339969E+09 | 885538.41 | 0.339084E+09 | 0.202678E+10 | 49572557.71 |
July | 0.352358E+09 | 4343994.19 | 0.348014E+09 | 0.255064E+10 | 1909767.76 |
August | 0.417627E+09 | 39313940.50 | 0.378313E+09 | 0.281330E+10 | 1833880.31 |
September | 0.541786E+09 | 0.141459E+09 | 0.400327E+09 | 0.264880E+10 | 68327160.14 |
October | 0.716376E+09 | 0.293193E+09 | 0.423182E+09 | 0.273506E+10 | 0.223079E+09 |
November | 0.750494E+09 | 0.361989E+09 | 0.388505E+09 | 0.232733E+10 | 0.502688E+09 |
December | 0.712026E+09 | 0.348005E+09 | 0.364021E+09 | 0.181096E+10 | 0.910796E+09 |
Annual Sum or Average | 0.656130E+10 | 0.201809E+10 | 0.454322E+10 | 0.252661E+11 | 0.502874E+10 |
Minimum of Months | 0.339969E+09 | 885538.41 | 0.339084E+09 | 0.153456E+10 | 1833880.31 |
Maximum of Months | 0.750494E+09 | 0.361989E+09 | 0.423182E+09 | 0.281330E+10 | 0.108695E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.288467E+09 | 83452173.69 | 0.205015E+09 | 0.547541E+09 | 0.848316E+09 |
February | 0.297294E+09 | 85491306.84 | 0.211802E+09 | 0.654787E+09 | 0.641920E+09 |
March | 0.387728E+09 | 0.114600E+09 | 0.273127E+09 | 0.104448E+10 | 0.531803E+09 |
April | 0.409786E+09 | 0.114555E+09 | 0.295230E+09 | 0.137278E+10 | 0.325094E+09 |
May | 0.461500E+09 | 0.138088E+09 | 0.323411E+09 | 0.201023E+10 | 0.102369E+09 |
June | 0.461449E+09 | 0.145417E+09 | 0.316032E+09 | 0.214152E+10 | 35119265.58 |
July | 0.438174E+09 | 0.125751E+09 | 0.312423E+09 | 0.242181E+10 | 1174644.84 |
August | 0.448163E+09 | 0.135646E+09 | 0.312517E+09 | 0.246808E+10 | 1171520.53 |
September | 0.413320E+09 | 0.129730E+09 | 0.283590E+09 | 0.191743E+10 | 48434437.53 |
October | 0.380277E+09 | 0.123271E+09 | 0.257006E+09 | 0.149123E+10 | 0.165440E+09 |
November | 0.316863E+09 | 0.104260E+09 | 0.212603E+09 | 0.982390E+09 | 0.389542E+09 |
December | 0.273664E+09 | 83093590.63 | 0.190571E+09 | 0.613742E+09 | 0.708422E+09 |
Annual Sum or Average | 0.457668E+10 | 0.138336E+10 | 0.319333E+10 | 0.176660E+11 | 0.379881E+10 |
Minimum of Months | 0.273664E+09 | 83093590.63 | 0.190571E+09 | 0.547541E+09 | 1171520.53 |
Maximum of Months | 0.461500E+09 | 0.145417E+09 | 0.323411E+09 | 0.246808E+10 | 0.848316E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 987.63 | 991.30 | 486.17 | 190.17 | 295.99 | 0.00 | 0.00 |
February | 1134.95 | 850.75 | 497.26 | 172.89 | 324.36 | 0.00 | 0.00 |
March | 1319.37 | 647.14 | 489.42 | 136.11 | 353.31 | 0.00 | 0.00 |
April | 1666.79 | 408.72 | 489.29 | 114.91 | 374.38 | 0.00 | 0.00 |
May | 2264.92 | 123.69 | 492.32 | 112.67 | 379.65 | 0.00 | 0.00 |
June | 2434.69 | 45.02 | 484.46 | 110.09 | 374.37 | 0.00 | 0.00 |
July | 2772.64 | 1.63 | 459.04 | 96.05 | 362.98 | 0.00 | 0.00 |
August | 2900.19 | 1.64 | 490.80 | 116.80 | 374.00 | 0.00 | 0.00 |
September | 2502.31 | 62.44 | 525.73 | 153.11 | 372.61 | 0.00 | 0.00 |
October | 2138.77 | 200.17 | 552.15 | 202.01 | 350.15 | 0.00 | 0.00 |
November | 1631.08 | 472.59 | 531.63 | 217.89 | 313.73 | 0.00 | 0.00 |
December | 1086.09 | 832.89 | 465.28 | 187.92 | 277.36 | 0.00 | 0.00 |
Annual Sum or Average | 1907.90 | 384.21 | 496.84 | 150.73 | 346.11 | 0.00 | 0.00 |
Minimum of Months | 987.63 | 1.63 | 459.04 | 96.05 | 277.36 | 0.00 | 0.00 |
Maximum of Months | 2900.19 | 991.30 | 552.15 | 217.89 | 379.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264527E+10 | 0.265511E+10 | 0.130215E+10 | 0.509364E+09 | 0.792786E+09 | 0.00 | 0.00 |
February | 0.274568E+10 | 0.205814E+10 | 0.120297E+10 | 0.418264E+09 | 0.784702E+09 | 0.00 | 0.00 |
March | 0.353380E+10 | 0.173331E+10 | 0.131085E+10 | 0.364552E+09 | 0.946298E+09 | 0.00 | 0.00 |
April | 0.432033E+10 | 0.105939E+10 | 0.126824E+10 | 0.297856E+09 | 0.970384E+09 | 0.00 | 0.00 |
May | 0.606636E+10 | 0.331295E+09 | 0.131862E+10 | 0.301764E+09 | 0.101686E+10 | 0.00 | 0.00 |
June | 0.631071E+10 | 0.116703E+09 | 0.125571E+10 | 0.285346E+09 | 0.970367E+09 | 0.00 | 0.00 |
July | 0.742624E+10 | 4359455.90 | 0.122949E+10 | 0.257271E+09 | 0.972216E+09 | 0.00 | 0.00 |
August | 0.776786E+10 | 4397792.28 | 0.131456E+10 | 0.312849E+09 | 0.100171E+10 | 0.00 | 0.00 |
September | 0.648599E+10 | 0.161845E+09 | 0.136269E+10 | 0.396870E+09 | 0.965815E+09 | 0.00 | 0.00 |
October | 0.572848E+10 | 0.536146E+09 | 0.147889E+10 | 0.541056E+09 | 0.937833E+09 | 0.00 | 0.00 |
November | 0.422776E+10 | 0.122496E+10 | 0.137797E+10 | 0.564780E+09 | 0.813193E+09 | 0.00 | 0.00 |
December | 0.290897E+10 | 0.223081E+10 | 0.124620E+10 | 0.503316E+09 | 0.742887E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.601674E+11 | 0.121165E+11 | 0.156683E+11 | 0.475329E+10 | 0.109150E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264527E+10 | 4359455.90 | 0.120297E+10 | 0.257271E+09 | 0.742887E+09 | 0.00 | 0.00 |
Maximum of Months | 0.776786E+10 | 0.265511E+10 | 0.147889E+10 | 0.564780E+09 | 0.101686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.655934E+10 | -0.622530E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -334042938.3 | 81.22 | 0.00 | 0.00 |
February | 0.593488E+10 | -0.563439E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -300493344.1 | 81.22 | 0.00 | 0.00 |
March | 0.662548E+10 | -0.629396E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -331519614.4 | 81.22 | 0.00 | 0.00 |
April | 0.636336E+10 | -0.604357E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -319794015.9 | 81.22 | 0.00 | 0.00 |
May | 0.658927E+10 | -0.626031E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -328961661.9 | 81.22 | 0.00 | 0.00 |
June | 0.639923E+10 | -0.608668E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -312550933.5 | 81.22 | 0.00 | 0.00 |
July | 0.653283E+10 | -0.621721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -315614041.8 | 81.22 | 0.00 | 0.00 |
August | 0.660896E+10 | -0.629532E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -313635304.9 | 81.22 | 0.00 | 0.00 |
September | 0.635499E+10 | -0.604493E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -310061831.0 | 81.22 | 0.00 | 0.00 |
October | 0.655194E+10 | -0.622393E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -328013915.1 | 81.22 | 0.00 | 0.00 |
November | 0.634430E+10 | -0.602471E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -319590635.1 | 81.22 | 0.00 | 0.00 |
December | 0.654931E+10 | -0.621721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -332096667.3 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.774139E+11 | -0.735675E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.384637E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.593488E+10 | -0.629532E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -334042938.3 | 81.22 | 0.00 | 0.00 |
Maximum of Months | 0.662548E+10 | -0.563439E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -300493344.1 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.174479E+11 | -0.165953E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -852538034.2 | 58.99 | 0.00 | 0.00 |
February | 0.153568E+11 | -0.145921E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -764670322.7 | 58.98 | 0.00 | 0.00 |
March | 0.160019E+11 | -0.151602E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -841680106.2 | 58.99 | 0.00 | 0.00 |
April | 0.138845E+11 | -0.130746E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -809875398.0 | 58.98 | 0.00 | 0.00 |
May | 0.128714E+11 | -0.120407E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -830673512.1 | 58.98 | 0.00 | 0.00 |
June | 0.114371E+11 | -0.106580E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -779119217.8 | 58.98 | 0.00 | 0.00 |
July | 0.113189E+11 | -0.105452E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -773633135.0 | 58.98 | 0.00 | 0.00 |
August | 0.119317E+11 | -0.111666E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -765145520.6 | 58.98 | 0.00 | 0.00 |
September | 0.126263E+11 | -0.118579E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -768414898.0 | 58.98 | 0.00 | 0.00 |
October | 0.145687E+11 | -0.137421E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -826545992.6 | 58.98 | 0.00 | 0.00 |
November | 0.155511E+11 | -0.147419E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -809262344.1 | 58.99 | 0.00 | 0.00 |
December | 0.170995E+11 | -0.162553E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -844140585.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.170096E+12 | -0.160430E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.966570E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.113189E+11 | -0.165953E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -852538034.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.174479E+11 | -0.105452E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -764670322.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.533103E+11 | 0.391318E+11 | 138496.25 | 30-JAN-04:01 | 80310.64 | 0.00 |
February | 0.00 | 0.00 | 0.589688E+11 | 0.420105E+11 | 141410.51 | 09-FEB-04:01 | 77501.67 | 0.00 |
March | 0.00 | 0.00 | 0.780080E+11 | 0.583157E+11 | 141706.02 | 29-MAR-03:01 | 75193.52 | 0.00 |
April | 0.00 | 0.00 | 0.102723E+12 | 0.740119E+11 | 143706.31 | 30-APR-03:01 | 57019.64 | 0.00 |
May | 0.00 | 0.00 | 0.145305E+12 | 0.103308E+12 | 143706.31 | 02-MAY-03:01 | 61381.23 | 0.00 |
June | 0.00 | 0.00 | 0.176505E+12 | 0.109438E+12 | 143706.31 | 07-JUN-03:01 | 74484.96 | 0.00 |
July | 0.00 | 0.00 | 0.211942E+12 | 0.125414E+12 | 143444.51 | 06-JUL-03:50 | 48030.91 | 0.00 |
August | 0.00 | 0.00 | 0.222208E+12 | 0.128447E+12 | 143706.31 | 31-AUG-03:02 | 54291.35 | 0.00 |
September | 0.00 | 0.00 | 0.188398E+12 | 0.108754E+12 | 143706.31 | 29-SEP-03:03 | 50550.49 | 0.00 |
October | 0.00 | 0.00 | 0.150020E+12 | 0.956805E+11 | 143706.31 | 01-OCT-03:02 | 53057.71 | 0.00 |
November | 0.00 | 0.00 | 0.105480E+12 | 0.714910E+11 | 143706.31 | 03-NOV-03:01 | 72376.59 | 0.00 |
December | 0.00 | 0.00 | 0.715090E+11 | 0.491431E+11 | 140824.27 | 06-DEC-04:01 | 72820.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156438E+13 | 0.100515E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.533103E+11 | 0.391318E+11 | 138496.25 | 48030.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222208E+12 | 0.128447E+12 | 143706.31 | 80310.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.216039E+11 | 0.149531E+11 | 45249.14 | 30-JAN-04:01 | 23326.51 | 0.00 |
February | 0.00 | 0.00 | 0.266274E+11 | 0.182043E+11 | 46839.19 | 09-FEB-04:01 | 23607.47 | 0.00 |
March | 0.00 | 0.00 | 0.396727E+11 | 0.294895E+11 | 47923.54 | 28-MAR-11:00 | 25887.59 | 0.00 |
April | 0.00 | 0.00 | 0.594032E+11 | 0.430670E+11 | 49094.89 | 29-APR-19:55 | 21031.91 | 0.00 |
May | 0.00 | 0.00 | 0.885316E+11 | 0.661937E+11 | 49094.89 | 18-MAY-03:01 | 23750.10 | 0.00 |
June | 0.00 | 0.00 | 0.102010E+12 | 0.662934E+11 | 49094.89 | 25-JUN-07:54 | 14743.60 | 0.00 |
July | 0.00 | 0.00 | 0.111576E+12 | 0.716296E+11 | 49094.89 | 02-JUL-05:00 | 20542.02 | 0.00 |
August | 0.00 | 0.00 | 0.113053E+12 | 0.712920E+11 | 49094.89 | 31-AUG-04:16 | 21175.01 | 0.00 |
September | 0.00 | 0.00 | 0.105459E+12 | 0.621705E+11 | 49094.89 | 25-SEP-07:58 | 15439.07 | 0.00 |
October | 0.00 | 0.00 | 0.918329E+11 | 0.577960E+11 | 49094.89 | 07-OCT-08:23 | 14330.99 | 0.00 |
November | 0.00 | 0.00 | 0.605419E+11 | 0.400557E+11 | 49094.89 | 02-NOV-20:20 | 24490.40 | 0.00 |
December | 0.00 | 0.00 | 0.344745E+11 | 0.222131E+11 | 46520.39 | 11-DEC-04:01 | 24207.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.854786E+12 | 0.563358E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.216039E+11 | 0.149531E+11 | 45249.14 | 14330.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113053E+12 | 0.716296E+11 | 49094.89 | 25887.59 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6660.75 | 12651.71 | 12-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6497.22 | 12507.65 | 02-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 6126.45 | 11944.79 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5511.34 | 10852.73 | 03-APR-18:43 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4964.83 | 9827.67 | 01-MAY-18:50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4583.50 | 8864.23 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4408.56 | 8384.13 | 31-JUL-18:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4639.69 | 9001.94 | 31-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5044.34 | 9942.65 | 29-SEP-18:13 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5598.55 | 11079.97 | 31-OCT-18:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6153.63 | 12048.58 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 6534.34 | 12573.14 | 29-DEC-07:53 |
Annual Sum or Average | 0.00 | 5555.16 | ||||
Minimum of Months | 0.00 | 0.00 | 4408.56 | 8384.13 | ||
Maximum of Months | 0.00 | 0.00 | 6660.75 | 12651.71 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.558435E+10 | 0.60 | 2203.40 | 01-JAN-00:10 | 0.63 |
February | 0.506090E+10 | 0.60 | 2203.40 | 01-FEB-00:05 | 0.63 |
March | 0.562674E+10 | 0.60 | 2203.40 | 01-MAR-00:03 | 0.63 |
April | 0.544063E+10 | 0.60 | 2203.40 | 01-APR-00:10 | 0.63 |
May | 0.562450E+10 | 0.60 | 2203.40 | 01-MAY-00:09 | 0.63 |
June | 0.545012E+10 | 0.60 | 2203.40 | 01-JUN-00:07 | 0.63 |
July | 0.563917E+10 | 0.60 | 2203.40 | 01-JUL-00:08 | 0.63 |
August | 0.564036E+10 | 0.60 | 2203.40 | 01-AUG-00:05 | 0.62 |
September | 0.545356E+10 | 0.60 | 2203.40 | 01-SEP-00:06 | 0.63 |
October | 0.562807E+10 | 0.60 | 2203.40 | 01-OCT-00:07 | 0.63 |
November | 0.544192E+10 | 0.60 | 2203.40 | 01-NOV-00:08 | 0.63 |
December | 0.562350E+10 | 0.60 | 2203.40 | 01-DEC-00:03 | 0.63 |
Annual Sum or Average | 0.662138E+11 | 0.60 | |||
Minimum of Months | 0.506090E+10 | 0.60 | 2203.40 | 0.62 | |
Maximum of Months | 0.564036E+10 | 0.60 | 2203.40 | 0.63 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.203274E+11 | 1.21 | 9090.08 | 01-JAN-10:23 | 1.41 |
February | 0.183710E+11 | 1.21 | 9090.08 | 01-FEB-08:38 | 1.40 |
March | 0.203557E+11 | 1.21 | 9090.08 | 01-MAR-08:23 | 1.40 |
April | 0.197383E+11 | 1.22 | 9090.08 | 01-APR-08:54 | 1.40 |
May | 0.205036E+11 | 1.22 | 9090.08 | 01-MAY-09:26 | 1.40 |
June | 0.199730E+11 | 1.22 | 9090.08 | 01-JUN-04:15 | 1.40 |
July | 0.208253E+11 | 1.21 | 9090.08 | 01-JUL-04:40 | 1.39 |
August | 0.208492E+11 | 1.21 | 9090.08 | 01-AUG-17:10 | 1.40 |
September | 0.200177E+11 | 1.22 | 9090.08 | 01-SEP-15:50 | 1.40 |
October | 0.205512E+11 | 1.22 | 9090.08 | 01-OCT-16:13 | 1.39 |
November | 0.197626E+11 | 1.22 | 9090.08 | 01-NOV-22:40 | 1.39 |
December | 0.203534E+11 | 1.21 | 9090.08 | 01-DEC-07:37 | 1.41 |
Annual Sum or Average | 0.241628E+12 | 1.21 | |||
Minimum of Months | 0.183710E+11 | 1.21 | 9090.08 | 1.39 | |
Maximum of Months | 0.208492E+11 | 1.22 | 9090.08 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.447169E+10 | 0.86 | 1974.14 | 05-JAN-19:50 | 0.89 |
February | 0.405093E+10 | 0.86 | 1974.14 | 04-FEB-24:00 | 0.89 |
March | 0.449327E+10 | 0.86 | 1974.14 | 08-MAR-08:32 | 0.89 |
April | 0.436480E+10 | 0.86 | 1974.14 | 07-APR-04:08 | 0.89 |
May | 0.456860E+10 | 0.86 | 1974.14 | 01-MAY-05:30 | 0.88 |
June | 0.451295E+10 | 0.86 | 1974.14 | 07-JUN-09:12 | 0.88 |
July | 0.478727E+10 | 0.85 | 1974.14 | 10-JUL-23:50 | 0.88 |
August | 0.480204E+10 | 0.85 | 1974.14 | 04-AUG-05:10 | 0.88 |
September | 0.455278E+10 | 0.86 | 1974.14 | 01-SEP-06:50 | 0.88 |
October | 0.460111E+10 | 0.86 | 1974.14 | 13-OCT-16:33 | 0.89 |
November | 0.437835E+10 | 0.86 | 1974.14 | 04-NOV-23:08 | 0.89 |
December | 0.449382E+10 | 0.86 | 1974.14 | 17-DEC-09:53 | 0.89 |
Annual Sum or Average | 0.540776E+11 | 0.86 | |||
Minimum of Months | 0.405093E+10 | 0.85 | 1974.14 | 0.88 | |
Maximum of Months | 0.480204E+10 | 0.86 | 1974.14 | 0.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 51.03 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 52.01 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 51.62 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 54.58 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 54.64 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 55.31 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 55.26 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 55.79 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 55.12 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 54.87 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 54.35 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 51.78 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 51.03 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.79 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 51.03 | 59.48 | 6660.75 | 12651.71 | 12-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 52.01 | 59.04 | 6497.22 | 12507.65 | 02-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.62 | 58.19 | 6126.45 | 11944.79 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.92 | 52.92 | 5511.34 | 10852.73 | 03-APR-18:43 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.34 | 53.34 | 4964.83 | 9827.67 | 01-MAY-18:50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 54.32 | 54.32 | 4583.50 | 8864.23 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.41 | 54.41 | 4408.56 | 8384.13 | 31-JUL-18:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 54.86 | 54.86 | 4639.69 | 9001.94 | 31-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 54.24 | 54.24 | 5044.34 | 9942.65 | 29-SEP-18:13 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 52.63 | 52.63 | 5598.55 | 11079.97 | 31-OCT-18:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.22 | 53.22 | 6153.63 | 12048.58 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.78 | 58.51 | 6534.34 | 12573.14 | 29-DEC-07:53 |
Annual Sum or Average | 0.00 | 5555.16 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.03 | 52.63 | 4408.56 | 8384.13 | ||
Maximum of Months | 0.00 | 0.00 | 54.86 | 59.48 | 6660.75 | 12651.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.383397E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.380348E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.462854E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.533311E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.687695E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.771502E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.898515E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.927762E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.793767E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.680009E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.534704E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.439176E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.749304E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.380348E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.927762E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.114047E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.123561E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166735E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218344E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.304482E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.338848E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.377865E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.382252E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.343572E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.303020E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.217801E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.150006E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.304053E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114047E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.382252E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.203274E+11 | 0.533103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183710E+11 | 0.589688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203557E+11 | 0.780080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197383E+11 | 0.102723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205036E+11 | 0.145305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199730E+11 | 0.176505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.208253E+11 | 0.211942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208492E+11 | 0.222208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200177E+11 | 0.188398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205512E+11 | 0.150020E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197626E+11 | 0.105480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203534E+11 | 0.715090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241628E+12 | 0.156438E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183710E+11 | 0.533103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208492E+11 | 0.222208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.447169E+10 | 0.216039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405093E+10 | 0.266274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449327E+10 | 0.396727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.436480E+10 | 0.594032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.456860E+10 | 0.885316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.451295E+10 | 0.102010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.478727E+10 | 0.111576E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.480204E+10 | 0.113053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.455278E+10 | 0.105459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460111E+10 | 0.918329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.437835E+10 | 0.605419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449382E+10 | 0.344745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.540776E+11 | 0.854786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.405093E+10 | 0.216039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.480204E+10 | 0.113053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.203274E+11 | 0.00 | 0.00 | 0.00 | 0.180123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183710E+11 | 0.00 | 0.00 | 0.00 | 0.196638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203557E+11 | 0.00 | 0.00 | 0.00 | 0.259296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197383E+11 | 0.00 | 0.00 | 0.00 | 0.335928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205036E+11 | 0.00 | 0.00 | 0.00 | 0.482659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199730E+11 | 0.00 | 0.00 | 0.00 | 0.571772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.208253E+11 | 0.00 | 0.00 | 0.00 | 0.690262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208492E+11 | 0.00 | 0.00 | 0.00 | 0.719270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200177E+11 | 0.00 | 0.00 | 0.00 | 0.593590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205512E+11 | 0.00 | 0.00 | 0.00 | 0.474496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197626E+11 | 0.00 | 0.00 | 0.00 | 0.337078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203534E+11 | 0.00 | 0.00 | 0.00 | 0.235642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241628E+12 | 0.00 | 0.00 | 0.00 | 0.507675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183710E+11 | 0.00 | 0.00 | 0.00 | 0.180123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208492E+11 | 0.00 | 0.00 | 0.00 | 0.719270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.447169E+10 | 0.00 | 0.00 | 0.00 | 0.693305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405093E+10 | 0.00 | 0.00 | 0.00 | 0.830520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449327E+10 | 0.00 | 0.00 | 0.00 | 0.121802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.436480E+10 | 0.00 | 0.00 | 0.00 | 0.174696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.456860E+10 | 0.00 | 0.00 | 0.00 | 0.258796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.451295E+10 | 0.00 | 0.00 | 0.00 | 0.293719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.478727E+10 | 0.00 | 0.00 | 0.00 | 0.329992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.480204E+10 | 0.00 | 0.00 | 0.00 | 0.334232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.455278E+10 | 0.00 | 0.00 | 0.00 | 0.298045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460111E+10 | 0.00 | 0.00 | 0.00 | 0.257009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.437835E+10 | 0.00 | 0.00 | 0.00 | 0.174018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449382E+10 | 0.00 | 0.00 | 0.00 | 0.105068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.540776E+11 | 0.00 | 0.00 | 0.00 | 0.249976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.405093E+10 | 0.00 | 0.00 | 0.00 | 0.693305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.480204E+10 | 0.00 | 0.00 | 0.00 | 0.334232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263873E+10 | 0.144095E+10 | 0.00 | 91303352.27 | 933797.62 | 0.00 | 0.146539E+11 | 0.00 | 3.61 |
February | 0.121849E+10 | 0.416348E+10 | 0.00 | 68265997.25 | 11194885.60 | 0.00 | 0.917586E+10 | 0.00 | 3.62 |
March | 0.789824E+09 | 0.903522E+10 | 0.00 | 56804083.76 | 34689282.00 | 0.00 | 0.625316E+10 | 0.00 | 3.65 |
April | 0.342386E+09 | 0.239555E+11 | 0.00 | 18845831.55 | 0.163212E+09 | 0.00 | 0.141900E+10 | 0.00 | 3.67 |
May | 34397043.38 | 0.509041E+11 | 0.00 | 6573977.58 | 0.829790E+09 | 0.00 | 32324173.59 | 0.00 | 3.72 |
June | 328259.61 | 0.765415E+11 | 0.00 | 2759296.48 | 0.162999E+10 | 0.00 | 7029291.42 | 0.00 | 3.80 |
July | 0.00 | 0.101607E+12 | 0.00 | 1910176.74 | 0.297410E+10 | 0.00 | 17156103.73 | 0.00 | 3.82 |
August | 0.00 | 0.108201E+12 | 0.00 | 295748.51 | 0.269135E+10 | 0.00 | 106019.75 | 0.00 | 3.82 |
September | 626573.57 | 0.851890E+11 | 0.00 | 1752514.75 | 0.177426E+10 | 0.00 | 3130383.09 | 0.00 | 3.78 |
October | 55283690.27 | 0.546437E+11 | 0.00 | 5964828.30 | 0.784992E+09 | 0.00 | 81821333.24 | 0.00 | 3.72 |
November | 0.391916E+09 | 0.245130E+11 | 0.00 | 16607023.04 | 0.136766E+09 | 0.00 | 0.932781E+09 | 0.00 | 3.66 |
December | 0.112048E+10 | 0.690318E+10 | 0.00 | 61943661.04 | 13964674.76 | 0.00 | 0.837802E+10 | 0.00 | 3.63 |
Annual Sum or Average | 0.659246E+10 | 0.547098E+12 | 0.00 | 0.333026E+09 | 0.110452E+11 | 0.00 | 0.409543E+11 | 0.00 | 3.71 |
Minimum of Months | 0.00 | 0.144095E+10 | 0.00 | 295748.51 | 933797.62 | 0.00 | 106019.75 | 0.00 | 3.61 |
Maximum of Months | 0.263873E+10 | 0.108201E+12 | 0.00 | 91303352.27 | 0.297410E+10 | 0.00 | 0.146539E+11 | 0.00 | 3.82 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288207E+10 | 97726483.71 | 0.00 | 0.104305E+09 | 0.00 | 0.00 | 0.284299E+11 | 0.00 | 11.02 |
February | 0.749959E+09 | 0.910982E+09 | 0.00 | 97563382.54 | 0.00 | 0.00 | 0.213465E+11 | 0.00 | 11.10 |
March | 0.173108E+09 | 0.272107E+10 | 0.00 | 0.105052E+09 | 0.00 | 0.00 | 0.169140E+11 | 0.00 | 11.18 |
April | 6345182.30 | 0.113050E+11 | 0.00 | 57189531.55 | 0.00 | 0.00 | 0.531763E+10 | 0.00 | 11.25 |
May | 0.00 | 0.319327E+11 | 0.00 | 11896571.08 | 0.00 | 0.00 | 0.543949E+09 | 0.00 | 11.48 |
June | 0.00 | 0.469988E+11 | 0.00 | 614415.66 | 0.00 | 0.00 | 10477784.48 | 0.00 | 11.94 |
July | 0.00 | 0.551312E+11 | 0.00 | 1109612.42 | 0.00 | 0.00 | 22470577.23 | 0.00 | 12.42 |
August | 0.00 | 0.563083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 |
September | 0.00 | 0.505709E+11 | 0.00 | 242582.78 | 0.00 | 0.00 | 621032.43 | 0.00 | 12.01 |
October | 0.00 | 0.353510E+11 | 0.00 | 11088372.23 | 0.00 | 0.00 | 0.616619E+09 | 0.00 | 11.53 |
November | 12812749.65 | 0.117814E+11 | 0.00 | 47409896.10 | 0.00 | 0.00 | 0.493032E+10 | 0.00 | 11.24 |
December | 0.460997E+09 | 0.186275E+10 | 0.00 | 96298483.54 | 6092.78 | 0.00 | 0.203948E+11 | 0.00 | 11.12 |
Annual Sum or Average | 0.428529E+10 | 0.304972E+12 | 0.00 | 0.532770E+09 | 6092.78 | 0.00 | 0.985273E+11 | 0.00 | 11.56 |
Minimum of Months | 0.00 | 97726483.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 |
Maximum of Months | 0.288207E+10 | 0.563083E+11 | 0.00 | 0.105052E+09 | 6092.78 | 0.00 | 0.284299E+11 | 0.00 | 12.45 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.548024E+11 | 0.444055E+10 | 0.951944E+11 | 0.683219E+10 | 0.123059E+12 |
February | 0.634211E+11 | 0.278891E+10 | 0.615994E+11 | 0.494576E+10 | 0.135391E+12 |
March | 0.862537E+11 | 0.134804E+10 | 0.401389E+11 | 0.436202E+10 | 0.181652E+12 |
April | 0.983760E+11 | -0.281012E+10 | -0.235267E+11 | 0.327204E+10 | 0.240551E+12 |
May | 0.109521E+12 | -0.810202E+10 | -0.106910E+12 | 0.471594E+09 | 0.337758E+12 |
June | 0.109573E+12 | -0.133011E+11 | -0.164936E+12 | -0.207020E+10 | 0.394589E+12 |
July | 0.107970E+12 | -0.173601E+11 | -0.203389E+12 | -0.561508E+10 | 0.456895E+12 |
August | 0.105636E+12 | -0.193545E+11 | -0.212361E+12 | -0.633184E+10 | 0.471861E+12 |
September | 0.868646E+11 | -0.158750E+11 | -0.180434E+12 | -0.255057E+10 | 0.412876E+12 |
October | 0.679696E+11 | -0.100049E+11 | -0.117587E+12 | -379468387.1 | 0.344230E+12 |
November | 0.510897E+11 | -0.438209E+10 | -0.273297E+11 | 0.267592E+10 | 0.242920E+12 |
December | 0.479901E+11 | 0.110911E+10 | 0.545723E+11 | 0.531576E+10 | 0.164128E+12 |
Annual Sum or Average | 0.989467E+12 | -0.815032E+11 | -0.784969E+12 | 0.109281E+11 | 0.350591E+13 |
Minimum of Months | 0.479901E+11 | -0.193545E+11 | -0.212361E+12 | -0.633184E+10 | 0.123059E+12 |
Maximum of Months | 0.109573E+12 | 0.444055E+10 | 0.951944E+11 | 0.683219E+10 | 0.471861E+12 |