Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:24:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2049.52 | 4009.60 | 4009.60 |
Net Site Energy | 2049.52 | 4009.60 | 4009.60 |
Total Source Energy | 4462.68 | 8730.62 | 8730.62 |
Net Source Energy | 4462.68 | 8730.62 | 8730.62 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 180.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 199.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.45 | 323.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 64.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1075.85 | 973.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 180.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 199.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.19 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 159.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.45 | 323.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 30.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 180.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 199.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 71.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 159.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.45 | 323.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 64.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 851.41 | 985.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1026.35 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2104.76 | 1904.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 227.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 851.41 | 985.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1026.35 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2104.76 | 1904.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1075.854 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1075.854 | 100.00 |
Total On-Site and Utility Electric Sources | 1075.854 | 100.00 |
Total Electricity End Uses | 1075.854 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 25.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4642.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 9.5182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.3127 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.5182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.3127 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 9.4622 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-JUL-11:00 | 03-FEB-04:19 | - | - | - | - | - | - | - | - | - | - | 27-FEB-19:10 |
Heating | 0.00 | 153149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 34546.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 23072.84 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9216.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3131.63 | 13973.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2151.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 75343.53 | 171648.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 153149.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 34546.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21705.25 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9216.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3131.63 | 13973.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 195.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 631.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 225.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 142.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1457.82 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 505.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.96 | 350.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 203.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3407.23 | 1055.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 382.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1236.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 440.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 989.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.50 | 686.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 398.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6665.77 | 2064.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 382.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1236.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 440.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 989.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.50 | 686.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 398.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6665.77 | 2064.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.94 |
KITCHEN DIRECT AIR | 1.66 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.94 | 3.94 | 3.94 | 3.94 | 3.94 | 3.94 | 1.00 | 0.999989 | 3.94 |
PSZ-AC_2:2 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.00 | 1.00 | 1.66 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.94 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.66 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.94 | 6730.53 |
PSZ-AC_2:2_ADDAQ FAN | 1.66 | 1781.48 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.94 | 3.94 | 3.94 | 2.60 | 97819.98 | 129719.19 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.66 | 1.66 | 1.66 | 1.10 | 41342.54 | 86634.94 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.94 | 1.97 | 2.63 | 97819.98 | 48909.99 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.66 | 0.832432 | 1.11 | 41342.54 | 20671.27 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 129719.19 |
PSZ-AC_2:2 HEATING COIL | 86634.94 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 9.518 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 74.446 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.313 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.393 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3538.380 | 9.518 | 12.631 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3538.380 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1298.236 | 9.313 | 172.457 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1298.236 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7390 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27638744E-12 | 0.13692172E-14 | -0.80454349E-13 | 0.78568260E-16 |
34 | 6 | 0.25667740E-07 | 0.27924344E-09 | 0.59050449E-08 | -0.11914668E-12 |
35 | 5 | -0.17473551E-03 | 0.24386372E-05 | -0.90062287E-04 | 0.58456630E-08 |
36 | 4 | 0.27398001 | 0.12082630E-02 | 0.93158629E-01 | -0.31026392E-04 |
37 | 3 | -6.9061245 | 0.38026294E-01 | -2.2320589 | 0.27244997E-01 |
38 | 2 | 39.682701 | 0.13706054 | 14.825764 | -0.32010675 |
39 | 1 | -79.634567 | 0.62587550E-01 | -28.747502 | 1.0592017 |
40 | 0 | 46.824345 | 0.12738124E-02 | 16.300887 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.6141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0664E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.3770E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0155E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2219E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.1211E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.3157E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.8474E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.7553E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.2772E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.0124E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.7733E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.4491E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.8568E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.7409E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0251E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0352E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.1563E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.3080E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.3745E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.2156E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.8440E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.9519E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0268E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.8498E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 43490.68394 | 52188.82073 | 3.28264 | 3.93917 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.21000 | 1.44729E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 9184.30008 | 11021.16009 | 0.40829 | 1.33138 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | -6.30000 | 2.29779E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 21681.02988 | 26017.23586 | 1.38739 | 1.66486 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 67540.76 | 3.93921 | 3.93921 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 71913.52 | 1.33138 | 1.33138 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 36328.10 | 1.66486 | 1.66486 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 65735.60 | 1.21700 | 1.21700 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.93917 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.66486 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.93917 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.93917 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.93917 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.93917 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.93921 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.93921 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99999 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.66486 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.66486 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.66486 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.66486 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.66486 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.66486 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.93921 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.66486 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.93921 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.93921 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6730.52814 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.93921 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.93921 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.93921 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.59988 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.93921 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.96961 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.62614 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 97819.98000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 48909.99000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 97819.98000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 129719.18948 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 129719.18948 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.66486 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.66486 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1781.48309 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.66486 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.66486 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.66486 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09881 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.66486 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83243 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10991 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41342.54000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20671.27000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41342.54000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 86634.94385 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 86634.94385 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 95020.1 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40159.2 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | N/A | 3.491 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | N/A | 3.491 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | N/A | 3.491 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 5.5301896201E-002 | 0.2519635434 | Pass | Pass | 6.9487006307E-002 | 0.1779393066 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2148832745 | 0.4719296684 | Pass | Pass | 6.3136057597E-002 | 0.2404598823 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2259254832 | 0.2282109540 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1110.50 | 84.54 | 1000.11 | 15.38 | 1292.85 | 3503.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 3.491 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 3.491 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.5182 | 371.75 | 3538.38 | LightsWired | LTG_SCH_DINING | 93.86 | 168.00 | 77.60 | 0.0000 | Y | 51.54 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.3127 | 139.41 | 1298.24 | LightsWired | LTG_SCH_KITCHEN | 80.88 | 168.00 | 80.41 | 0.0000 | Y | 19.60 |
Interior Lighting Total | 9.4622 | 511.15 | 4836.62 | 71.14 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.52 | AstronomicalClock | - | 48.77 | 48.77 | 1.92 | |
EXTERIOR_LIGHTS_B | 3124.83 | AstronomicalClock | - | 83.77 | 73.27 | 42.98 | |
Exterior Lighting Total | 3334.35 | 44.90 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 97819.98 | 68579.63 | 29240.35 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41342.54 | 28984.43 | 12358.11 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 95020.1 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 40159.2 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 129719.19 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 86634.94 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.55 | 1983.06 | 778.12 | 1.00 | 0.59 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.94 | 6730.53 | 1708.60 | 1.00 | 1.18 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.66 | 1781.48 | 1070.05 | 1.00 | 1.34 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 43490.68 | 52188.82 | 140.39 | 3.283 | 3.939 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.01080 | 34.21 | 0.01447 | 1.331 | 0.00 |
KITCHEN | 21681.03 | 26017.24 | 186.63 | 1.387 | 1.665 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01031 | 33.55 | 0.01447 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9184.30 | 11021.16 | 29.65 | 0.408 | 1.331 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00761 | -6.30 | 0.00230 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.43 | 0.00207 | -6.30 | 0.00230 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.94 | 3.94 | 1.33 | 1.33 | 3.9392 | 3.9392 | 3.9392 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.66 | 1.66 | 1.22 | 1.22 | 1.6649 | 1.6649 | 1.6649 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 97819.980 | 68579.632 | 3.939210 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 48909.99 | 31805.10 | 2.626140 | 27.50 | 19.95 | 0.01203909 | 11.37 | 11.18 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 50.6971 | 23.98 | 0.01079572 | 55.8906 | 43467.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 129719.189 | 129719.189 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 129719.19 | 129719.19 | 3.939210 | 11.77 | 8.51 | 0.00581252 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 33.7981 | 21.00 | 0.00760690 | 47.4447 | 9178.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41342.540 | 28984.428 | 1.664860 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 20671.27 | 12960.32 | 1.109907 | 31.50 | 22.03 | 0.01335335 | 11.90 | 11.40 | 0.00850000 | 33.55 | 0.01447170 | 23.31 | 109.6490 | 25.99 | 0.01031439 | 47.4171 | 21681.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 86634.944 | 86634.944 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 86634.94 | 86634.94 | 1.664864 | -4.61 | -5.33 | 0.00224119 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 73.0992 | 19.83 | 0.00208739 | 14.1167 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 97819.980 | 68579.632 | 3.939210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.2201 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.939210 | 4.57333090 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 48909.99 | 31805.10 | 1.0000 | 3.04888693 | 2.626140 | 27.50 | 19.95 | 0.01203909 | 58359.7 | 11.37 | 11.18 | 0.00850000 | 32859.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48909.99 | 34.40 | 0.01447326 | 23.54 | 1.33137743 | 50.6971 | 23.98 | 0.01079572 | 23.98 | 0.01079572 | 55.8906 | 43467.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 129719.189 | 129719.189 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.939210 | 4.57333090 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 129719.19 | 129719.19 | 1.0000 | 4.57333090 | 3.939210 | 11.77 | 8.51 | 0.00581252 | 26493.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 129719.19 | -6.30 | 0.00229779 | -6.30 | 1.33137743 | 33.7981 | 21.00 | 0.00760690 | 21.00 | 0.00760690 | 47.4447 | 9178.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41342.540 | 28984.428 | 1.664860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.6632 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.664864 | 1.93286795 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 20671.27 | 12960.32 | 1.0000 | 1.28857560 | 1.109907 | 31.50 | 22.03 | 0.01335335 | 65834.5 | 11.90 | 11.40 | 0.00850000 | 33408.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20671.27 | 33.55 | 0.01447170 | 23.31 | 1.21700195 | 109.6490 | 25.96 | 0.01031439 | 25.99 | 0.01031439 | 47.4171 | 21681.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 86634.944 | 86634.944 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.664864 | 1.93286795 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 86634.94 | 86634.94 | 1.0000 | 1.93286795 | 1.664864 | -4.61 | -5.33 | 0.00224119 | 958.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86634.94 | -6.30 | 0.00229779 | -6.30 | 1.21700195 | 73.0992 | 0.00 | 0.00208739 | 19.83 | 0.00208739 | 14.1167 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 1.33 | 3.94 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 1.22 | 1.66 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4137.00 | 4929.50 | 2338.50 |
KITCHEN | 5524.83 | 6031.17 | 4553.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5610.00 | 7047.17 | 4642.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 3.83 | 97.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 317.67 | 0.00 | 25.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.83 | 319.00 | 0.00 | 25.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.607 | 0.918 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.817 | 0.034 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.067 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.072 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 38008411.82 | 0.00 | 38008411.82 | 7458787.86 | 45467199.68 | 41986318.57 | 1443.47 | 5749.79 | 1566.74 | 536.42 |
KITCHEN | 31215349.64 | 0.00 | 31215349.64 | 163473.78 | 31378823.41 | 38379373.44 | 6998.22 | 1724.70 | 37.08 | 948.97 |
Total Facility | 69223761.46 | 0.00 | 69223761.46 | 7622261.63 | 76846023.09 | 80365692.01 | 7011.61 | 5752.27 | 1600.74 | 985.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.4268 | 0.0000 | 1.4268 | 0.2844 | 1.7113 | 1.3314 | 0.00 | 5632.67 | 1554.33 |
KITCHEN | 1.1349 | 0.0000 | 1.1349 | 0.0039 | 1.1388 | 1.2170 | 5458.21 | 1713.07 | 15.72 |
Total Facility | 2.5618 | 0.0000 | 2.5618 | 0.2883 | 2.8501 | 2.5484 | 5458.21 | 5634.48 | 1568.92 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 51230100.02 | 0.00 | 51230100.02 | 41986318.57 | 1435.85 | 0.39 | 7323.76 | 536.42 |
PSZ-AC_2:2 | 42074029.19 | 0.00 | 42074029.19 | 38379373.44 | 1386.30 | 5.05 | 7368.65 | 948.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9232 | 0.0000 | 1.9232 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.5297 | 0.0000 | 1.5297 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1669.15 | 313.48 | 5740.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 264.83 | 2911.00 | 4960.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.4548 | 2.1174 | 1.7949 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.5388 | 1.6083 | 1.4966 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
Electricity:Building | 548.31 | 4052.25 | 01-JAN-01:10 | 30528.98 | 01-FEB-11:20 |
Electricity:Zone:DINING | 176.70 | 991.88 | 01-JAN-01:10 | 9507.78 | 01-FEB-11:20 |
Electricity:SpaceType:GENERAL | 531.45 | 3643.21 | 01-JAN-01:10 | 28163.83 | 01-FEB-11:20 |
InteriorLights:Electricity | 71.14 | 672.49 | 01-JAN-01:10 | 4035.02 | 02-JAN-17:20 |
InteriorLights:Electricity:Zone:DINING | 51.54 | 510.94 | 01-JAN-01:10 | 3065.69 | 02-JAN-17:20 |
InteriorLights:Electricity:SpaceType:GENERAL | 71.14 | 672.49 | 01-JAN-01:10 | 4035.02 | 02-JAN-17:20 |
LightsWired:InteriorLights:Electricity | 71.14 | 672.49 | 01-JAN-01:10 | 4035.02 | 02-JAN-17:20 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 51.54 | 510.94 | 01-JAN-01:10 | 3065.69 | 02-JAN-17:20 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 71.14 | 672.49 | 01-JAN-01:10 | 4035.02 | 02-JAN-17:20 |
Electricity:Zone:KITCHEN | 371.61 | 3060.37 | 01-JAN-01:10 | 21021.20 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.16 | 2489.78 | 01-JAN-01:10 | 17686.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.03 | 1122.20 | 01-JAN-01:10 | 16319.14 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 64.31 | 1038.00 | 26-JAN-23:30 | 3441.39 | 09-MAR-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 123.35 | 1103.45 | 12-FEB-01:10 | 6550.93 | 10-AUG-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 16.57 | 0.00 | 01-JAN-11:10 | 1462.66 | 07-JUL-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 30.89 | 777.32 | 27-JAN-00:50 | 1076.23 | 19-JAN-13:10 |
ElectricityPurchased:Facility | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
ElectricityPurchased:Plant | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
Cogeneration:ElectricityPurchased | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
General:Cogeneration:ElectricityPurchased | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
ElectricityNet:Plant | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
Cogeneration:ElectricityNet | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
General:Cogeneration:ElectricityNet | 1075.85 | 7343.09 | 12-FEB-01:10 | 75343.53 | 07-JUL-12:00 |
Electricity:HVAC | 359.30 | 0.00 | 01-JAN-01:10 | 43762.38 | 07-JUL-12:00 |
Fans:Electricity | 159.75 | 0.00 | 01-JAN-01:10 | 9216.14 | 07-JUL-12:00 |
General:Fans:Electricity | 159.75 | 0.00 | 01-JAN-01:10 | 9216.14 | 07-JUL-12:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 199.55 | 0.00 | 01-JAN-00:10 | 34546.24 | 07-JUL-12:00 |
General:Cooling:Electricity | 199.55 | 0.00 | 01-JAN-00:10 | 34546.24 | 07-JUL-12:00 |
ExteriorLights:Electricity | 44.90 | 0.00 | 01-JAN-07:50 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.90 | 0.00 | 01-JAN-07:50 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.45 | 0.00 | 01-JAN-01:10 | 4741.50 | 01-DEC-19:30 |
Water Heater:WaterSystems:Electricity | 75.45 | 0.00 | 01-JAN-01:10 | 4741.50 | 01-DEC-19:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 02-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 02-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 973.66 | 2803.57 | 01-JAN-01:10 | 171648.89 | 03-FEB-04:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 180.39 | 0.00 | 01-JAN-01:00 | 162148.99 | 03-FEB-04:30 |
Heating:NaturalGas | 180.39 | 0.00 | 01-JAN-01:00 | 162148.99 | 03-FEB-04:30 |
General:Heating:NaturalGas | 180.39 | 0.00 | 01-JAN-01:00 | 162148.99 | 03-FEB-04:30 |
NaturalGas:Plant | 323.49 | 993.32 | 01-JAN-00:10 | 27635.62 | 03-FEB-20:00 |
WaterSystems:NaturalGas | 323.49 | 993.32 | 01-JAN-00:10 | 27635.62 | 03-FEB-20:00 |
Water Heater:WaterSystems:NaturalGas | 323.49 | 993.32 | 01-JAN-00:10 | 27635.62 | 03-FEB-20:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 10-APR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 10-APR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 27-FEB-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1990.53 | 3207.37 | 12-FEB-01:10 | 192845.39 | 15-JUL-18:10 |
EnergyTransfer:Building | 776.14 | 1603.69 | 12-FEB-01:10 | 54313.03 | 08-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN | 459.84 | 1603.69 | 12-FEB-01:10 | 25887.22 | 06-OCT-04:10 |
Refrigeration:EnergyTransfer | 153.85 | 2714.12 | 26-JAN-23:30 | 7834.84 | 29-MAR-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 76.93 | 1357.06 | 26-JAN-23:30 | 3917.42 | 29-MAR-10:40 |
General:Refrigeration:EnergyTransfer | 76.93 | 1357.06 | 26-JAN-23:30 | 3917.42 | 29-MAR-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 76.93 | 1357.06 | 26-JAN-23:30 | 3917.42 | 29-MAR-10:40 |
EnergyTransfer:Plant | 301.48 | 1603.69 | 12-FEB-01:10 | 18731.20 | 19-JAN-19:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.49 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 61.44 | 1341.95 | 27-JAN-00:50 | 2238.70 | 19-JAN-13:10 |
EnergyTransfer:Zone:DINING | 316.30 | 0.00 | 01-JAN-01:10 | 32845.91 | 08-JUL-18:10 |
Heating:EnergyTransfer | 2.32 | 0.00 | 01-JAN-00:10 | 13300.27 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:DINING | 2.32 | 0.00 | 01-JAN-00:10 | 13300.27 | 13-FEB-04:10 |
General:Heating:EnergyTransfer | 2.32 | 0.00 | 01-JAN-00:10 | 13300.27 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.32 | 0.00 | 01-JAN-00:10 | 13300.27 | 13-FEB-04:10 |
Cooling:EnergyTransfer | 696.89 | 0.00 | 01-JAN-01:10 | 51499.40 | 08-JUL-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 313.98 | 0.00 | 01-JAN-01:10 | 32845.91 | 08-JUL-18:10 |
General:Cooling:EnergyTransfer | 696.89 | 0.00 | 01-JAN-01:10 | 51499.40 | 08-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 313.98 | 0.00 | 01-JAN-01:10 | 32845.91 | 08-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 485.00 | 12-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 485.00 | 12-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 382.91 | 0.00 | 01-JAN-01:10 | 22048.42 | 06-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 382.91 | 0.00 | 01-JAN-01:10 | 22048.42 | 06-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 224.56 | 0.00 | 01-JAN-01:10 | 16016.95 | 31-JAN-07:50 |
PlantLoopHeatingDemand:Plant | 224.56 | 0.00 | 01-JAN-01:10 | 16016.95 | 31-JAN-07:50 |
WaterSystems:PlantLoopHeatingDemand | 224.56 | 0.00 | 01-JAN-01:10 | 16016.95 | 31-JAN-07:50 |
General:WaterSystems:PlantLoopHeatingDemand | 224.56 | 0.00 | 01-JAN-01:10 | 16016.95 | 31-JAN-07:50 |
EnergyTransfer:HVAC | 912.90 | 0.00 | 01-JAN-01:00 | 131772.56 | 07-JUL-12:00 |
HeatingCoils:EnergyTransfer | 144.31 | 0.00 | 01-JAN-01:00 | 129719.19 | 03-FEB-04:30 |
CoolingCoils:EnergyTransfer | 768.59 | 0.00 | 01-JAN-00:10 | 131772.56 | 07-JUL-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 224.56 | 0.00 | 01-JAN-01:10 | 16016.95 | 31-JAN-07:50 |
WaterUse:WaterSystems:EnergyTransfer | 224.56 | 0.00 | 01-JAN-01:10 | 16016.95 | 31-JAN-07:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.322 | -313.974 | 0.000 | 0.000 | 218.999 | 51.540 | 93.867 | 33.500 | 0.000 | 10.543 | 0.001 | 0.000 | -24.139 | 0.000 | -57.273 | -15.386 |
KITCHEN | 0.000 | 0.000 | 0.001 | -382.908 | 0.000 | 0.000 | 5.365 | 19.596 | 297.703 | 0.000 | 0.000 | 0.058 | 62.226 | 0.000 | 0.000 | 0.000 | -2.040 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.227 | 36.386 | 0.000 | 0.000 | 0.000 | -43.613 | -0.001 |
Total Facility | 0.000 | 0.000 | 2.323 | -696.882 | 0.000 | 0.000 | 224.364 | 71.136 | 391.570 | 33.500 | 0.000 | 17.827 | 98.613 | 0.000 | -24.139 | 0.000 | -102.925 | -15.387 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 11-JUN-00:42 | 0.00 | 0.00 | 0.00 | -58677.81 | 0.00 | 0.00 | 0.00 | 510.94 | 360.71 | 0.00 | 0.00 | 0.00 | 58896.87 | 0.00 | -1050.24 | 0.00 | -40.47 | 0.00 |
KITCHEN | 28-FEB-05:01 | 0.00 | 0.00 | 0.00 | -61172.53 | 0.00 | 0.00 | 12.34 | 215.40 | 7253.89 | 0.00 | 0.00 | 0.00 | 53766.01 | 0.00 | -0.00 | 0.00 | -75.11 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUN-00:42 | 0.00 | 0.00 | 0.00 | -89174.52 | 0.00 | 0.00 | 0.00 | 672.49 | 2707.55 | 0.00 | 0.00 | 1087.43 | 85854.52 | 0.00 | -1050.24 | 0.00 | -97.23 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-FEB-05:01 | 0.00 | 0.00 | 81501.66 | 0.00 | 0.00 | 0.00 | 0.00 | 510.94 | 2164.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4172.41 | 0.00 | -382.07 | -79622.35 |
KITCHEN | 12-FEB-05:03 | 0.00 | 0.00 | 4844.89 | 0.00 | 0.00 | 0.00 | 0.00 | 161.55 | 7243.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -234.44 | -12015.12 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-05:01 | -42411.93 | 42411.93 | 81501.66 | -42411.93 | 0.00 | 0.00 | 0.00 | 672.49 | 9407.36 | 0.00 | 0.00 | 340.57 | 0.00 | 0.00 | -4172.41 | 0.00 | -635.47 | -44702.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.9392 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.9392 | 0.3380 | 1.0000 | Not calculated | 1.3314 | 0.3380 | ||
PSZ-AC_2:2 | 1.6649 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6649 | 0.1097 | 1.0000 | Not calculated | 0.1826 | 0.1097 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.9392 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.9392 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3380 | ||
PSZ-AC_2:2 | 1.6649 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6649 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1097 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9392 | 3.9392 | 3.9392 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6649 | 1.6649 | 1.6649 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.9392 | 3.9392 | 3.9392 | 3.9392 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6649 | 1.6649 | 1.6649 | 1.6649 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9392 | 3.9392 | 3.9392 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6649 | 1.6649 | 1.6649 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.9392 | 3.9392 | 3.9392 | 3.9392 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6649 | 1.6649 | 1.6649 | 1.6649 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 25.17 |
Number of hours not met | 25.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 180.39 | 162148.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 199.55 | 34546.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 71.14 | 4035.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.90 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.19 | 23313.05 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 159.75 | 9216.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.45 | 4741.50 | 323.49 | 27635.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.57 | 1462.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 30.89 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 524.62 | 1075.85 |
Natural Gas | 469.79 | 973.66 |
Additional | 0.00 | 0.00 |
Total | 994.41 | 2049.52 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 139.17 |
Space Heating | 0.00 |
Space Cooling | 390.40 |
Fans (All) | 312.52 |
Service Water Heating | 147.62 |
Receptacle Equipment | 900.54 |
Miscellaneous (All) | 2104.76 |
Subtotal | 2104.76 |
Natural Gas [MJ/m2] | |
Space Heating | 352.90 |
Service Water Heating | 632.86 |
Miscellaneous (All) | 1904.84 |
Subtotal | 1904.84 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.47 |
Space Heating | 8.80 |
Space Cooling | 9.74 |
Fans (All) | 7.79 |
Service Water Heating | 19.47 |
Receptacle Equipment | 45.38 |
Miscellaneous | 5.35 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4894. | 8760. |
LTG_SCH_KITCHEN | 4218. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8462.33 | 297.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 6302.50 | 654.67 | 585.67 | 720.50 | 496.67 |
Min | 6302.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 654.67 | 585.67 | 720.50 | 496.67 |
Average | 7841.61 | 317.44 | 195.22 | 240.17 | 165.56 |
Sum | 23524.83 | 952.33 | 585.67 | 720.50 | 496.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19016.50 | 216.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 216.50 | 0.00 | 0.00 | 0.00 |
Average | 281079.50 | 72.17 | 0.00 | 0.00 | 0.00 |
Sum | 843238.50 | 216.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 6836.00 | 1924.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 4560.67 | 4199.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 5743.50 | 1541.00 | 370.17 | 321.67 | 783.67 |
Min | 4560.67 | 1541.00 | 0.00 | 0.00 | 0.00 |
Max | 6836.00 | 4199.33 | 370.17 | 321.67 | 783.67 |
Average | 5713.39 | 2554.78 | 123.39 | 107.22 | 261.22 |
Sum | 17140.17 | 7664.33 | 370.17 | 321.67 | 783.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 635394.67 | 188827.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 9276.67 | 9956.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 635394.67 | 188827.33 | 0.00 | 0.00 | 0.00 |
Average | 214890.44 | 66261.22 | 0.00 | 0.00 | 0.00 |
Sum | 644671.33 | 198783.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118269E+11 | 36792.87 | 08-JAN-00:01 | -6.1 | -6.4 | 0.123130E+11 | 12938.97 | 31-JAN-12:50 | 19.03 | 13.61 |
February | 0.141535E+11 | 41669.45 | 12-FEB-00:01 | -9.5 | -11.2 | 0.117657E+11 | 14048.81 | 25-FEB-19:10 | 16.65 | 7.80 |
March | 0.221494E+11 | 46434.63 | 12-MAR-01:51 | 17.80 | 14.76 | 0.141540E+11 | 14050.30 | 11-MAR-19:00 | 17.80 | 14.76 |
April | 0.245998E+11 | 50212.35 | 14-APR-03:11 | 13.90 | 10.57 | 0.142445E+11 | 14051.53 | 15-APR-18:49 | 23.58 | 15.32 |
May | 0.298562E+11 | 49594.99 | 16-MAY-03:51 | 17.20 | 14.22 | 0.152454E+11 | 14051.36 | 20-MAY-18:10 | 24.85 | 18.26 |
June | 0.351223E+11 | 58687.20 | 11-JUN-00:42 | 19.60 | 11.43 | 0.149584E+11 | 14051.89 | 17-JUN-18:00 | 22.80 | 20.15 |
July | 0.379638E+11 | 39245.33 | 03-JUL-01:22 | 20.25 | 17.39 | 0.153068E+11 | 14051.68 | 29-JUL-18:00 | 21.70 | 21.70 |
August | 0.396033E+11 | 32759.31 | 19-AUG-00:04 | 27.62 | 23.01 | 0.155047E+11 | 14050.66 | 19-AUG-18:49 | 27.88 | 23.80 |
September | 0.325430E+11 | 44996.05 | 21-SEP-03:21 | 18.30 | 15.40 | 0.148320E+11 | 14052.31 | 30-SEP-18:30 | 16.95 | 15.24 |
October | 0.271370E+11 | 39079.70 | 01-OCT-02:31 | 17.50 | 17.18 | 0.144084E+11 | 14051.25 | 21-OCT-18:10 | 19.40 | 12.39 |
November | 0.215349E+11 | 35415.39 | 04-NOV-03:11 | 17.20 | 15.81 | 0.132509E+11 | 14050.31 | 04-NOV-18:49 | 18.48 | 16.58 |
December | 0.174861E+11 | 37064.16 | 13-DEC-04:11 | 17.20 | 15.25 | 0.125505E+11 | 12938.92 | 11-DEC-12:30 | 17.20 | 15.25 |
Annual Sum or Average | 0.313976E+12 | 0.168534E+12 | ||||||||
Minimum of Months | 0.118269E+11 | 32759.31 | -9.5 | -11.2 | 0.117657E+11 | 12938.92 | 16.65 | 7.80 | ||
Maximum of Months | 0.396033E+11 | 58687.20 | 27.62 | 23.01 | 0.155047E+11 | 14052.31 | 27.88 | 23.80 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301807E+11 | 48550.72 | 20-JAN-05:01 | 12.80 | 12.52 | 0.104260E+11 | 6931.59 | 31-JAN-11:00 | 17.20 | 13.29 |
February | 0.271979E+11 | 61172.39 | 28-FEB-05:01 | 10.60 | 5.93 | 0.946293E+10 | 6931.60 | 28-FEB-11:00 | 22.20 | 12.30 |
March | 0.308327E+11 | 56600.00 | 21-MAR-04:01 | 13.03 | 8.86 | 0.105465E+11 | 6931.64 | 28-MAR-10:50 | 17.62 | 15.30 |
April | 0.301410E+11 | 55314.60 | 11-APR-04:01 | 12.02 | 9.39 | 0.102330E+11 | 6931.65 | 24-APR-10:50 | 18.03 | 14.41 |
May | 0.325351E+11 | 55231.19 | 12-MAY-04:01 | 12.12 | 9.75 | 0.105949E+11 | 6931.64 | 01-MAY-10:50 | 12.12 | 9.75 |
June | 0.331931E+11 | 41950.04 | 09-JUN-04:01 | 14.32 | 9.21 | 0.102599E+11 | 6944.88 | 23-JUN-10:00 | 30.00 | 24.29 |
July | 0.348981E+11 | 31809.42 | 25-JUL-04:01 | 21.70 | 18.07 | 0.105986E+11 | 6951.54 | 07-JUL-10:50 | 21.70 | 18.07 |
August | 0.353722E+11 | 31705.38 | 25-AUG-04:01 | 19.90 | 18.10 | 0.106052E+11 | 6954.50 | 10-AUG-10:00 | 19.90 | 18.10 |
September | 0.330093E+11 | 52095.99 | 29-SEP-04:01 | 11.78 | 11.10 | 0.102559E+11 | 6935.58 | 07-SEP-10:00 | 11.78 | 11.10 |
October | 0.329930E+11 | 54494.95 | 06-OCT-04:01 | 7.70 | 7.70 | 0.105638E+11 | 6931.66 | 23-OCT-10:00 | 16.70 | 13.77 |
November | 0.311493E+11 | 54601.78 | 10-NOV-05:01 | 11.70 | 9.86 | 0.101859E+11 | 6931.63 | 06-NOV-11:00 | 11.70 | 9.86 |
December | 0.314119E+11 | 47993.47 | 12-DEC-05:01 | 12.80 | 12.80 | 0.104619E+11 | 6931.63 | 13-DEC-11:39 | 19.80 | 17.47 |
Annual Sum or Average | 0.382914E+12 | 0.124195E+12 | ||||||||
Minimum of Months | 0.271979E+11 | 31705.38 | 7.70 | 5.93 | 0.946293E+10 | 6931.59 | 11.70 | 9.75 | ||
Maximum of Months | 0.353722E+11 | 61172.39 | 21.70 | 18.10 | 0.106052E+11 | 6954.50 | 30.00 | 24.29 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 | 7.82 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 | 18.46 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.70 | 6.60 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124835E+10 | 64029.51 | 09-JAN-04:01 | -1.8 |
February | 0.753412E+09 | 81500.66 | 12-FEB-05:01 | -11.8 |
March | 9367041.35 | 11401.03 | 19-MAR-04:01 | 1.78 |
April | 3981279.89 | 38301.27 | 06-APR-04:04 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 |
June | 75909.88 | 286.50 | 26-JUN-04:04 | 23.30 |
July | 1180378.80 | 4449.74 | 07-JUL-04:03 | 25.22 |
August | 2605734.89 | 2625.95 | 04-AUG-04:03 | 23.90 |
September | 131002.36 | 616.65 | 27-SEP-04:04 | 22.80 |
October | 757938.20 | 5124.11 | 31-OCT-04:03 | 8.80 |
November | 41735718.68 | 17390.41 | 21-NOV-05:01 | -2.3 |
December | 0.260468E+09 | 45475.24 | 17-DEC-08:28 | -2.0 |
Annual Sum or Average | 0.232206E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.124835E+10 | 81500.66 | 25.22 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52894.05 | 514.74 | 06-JAN-05:04 | -4.0 |
February | 532563.91 | 4850.01 | 12-FEB-05:03 | -11.8 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 |
November | 91824.22 | 1530.40 | 22-NOV-05:04 | -2.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 677282.18 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 532563.91 | 4850.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.449309E+10 | 3065.69 | 02-JAN-17:19 | 0.106297E+11 | 6993.92 | 01-JAN-11:09 |
February | 0.406066E+10 | 3065.69 | 01-FEB-17:30 | 0.960102E+10 | 6993.92 | 01-FEB-11:09 |
March | 0.441839E+10 | 3065.69 | 01-MAR-18:19 | 0.106297E+11 | 6993.92 | 01-MAR-11:09 |
April | 0.415644E+10 | 3065.69 | 01-APR-18:30 | 0.102868E+11 | 6993.92 | 01-APR-10:09 |
May | 0.426597E+10 | 3065.69 | 01-MAY-19:19 | 0.106297E+11 | 6993.92 | 01-MAY-10:09 |
June | 0.413136E+10 | 3065.69 | 01-JUN-19:30 | 0.102868E+11 | 6993.92 | 01-JUN-10:09 |
July | 0.421583E+10 | 3065.69 | 01-JUL-19:19 | 0.106297E+11 | 6993.92 | 01-JUL-10:09 |
August | 0.432234E+10 | 3065.69 | 01-AUG-19:10 | 0.106297E+11 | 6993.92 | 01-AUG-10:09 |
September | 0.421666E+10 | 3065.69 | 01-SEP-18:40 | 0.102868E+11 | 6993.92 | 01-SEP-10:09 |
October | 0.441728E+10 | 3065.69 | 02-OCT-18:19 | 0.106297E+11 | 6993.92 | 01-OCT-10:09 |
November | 0.433942E+10 | 3065.69 | 01-NOV-17:30 | 0.102868E+11 | 6993.92 | 01-NOV-10:09 |
December | 0.450303E+10 | 3065.69 | 01-DEC-17:30 | 0.106297E+11 | 6993.92 | 01-DEC-11:09 |
Annual Sum or Average | 0.515405E+11 | 0.125156E+12 | ||||
Minimum of Months | 0.406066E+10 | 3065.69 | 0.960102E+10 | 6993.92 | ||
Maximum of Months | 0.450303E+10 | 3065.69 | 0.106297E+11 | 6993.92 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165581E+10 | 969.33 | 02-JAN-10:09 | 0.284656E+11 | 17686.72 | 01-JAN-11:09 |
February | 0.149975E+10 | 969.33 | 01-FEB-10:09 | 0.257108E+11 | 17686.72 | 01-FEB-11:09 |
March | 0.168217E+10 | 969.33 | 01-MAR-10:09 | 0.284657E+11 | 17686.72 | 01-MAR-11:09 |
April | 0.160889E+10 | 969.33 | 01-APR-16:10 | 0.275474E+11 | 17686.72 | 01-APR-10:09 |
May | 0.166899E+10 | 969.33 | 01-MAY-09:09 | 0.284656E+11 | 17686.72 | 01-MAY-10:09 |
June | 0.162595E+10 | 969.33 | 01-JUN-09:09 | 0.275474E+11 | 17686.72 | 01-JUN-10:09 |
July | 0.165212E+10 | 969.33 | 01-JUL-16:10 | 0.284656E+11 | 17686.72 | 01-JUL-10:09 |
August | 0.168217E+10 | 969.33 | 01-AUG-09:09 | 0.284657E+11 | 17686.72 | 01-AUG-10:09 |
September | 0.160928E+10 | 969.33 | 01-SEP-09:09 | 0.275474E+11 | 17686.72 | 01-SEP-10:09 |
October | 0.165561E+10 | 969.33 | 02-OCT-09:09 | 0.284656E+11 | 17686.72 | 01-OCT-10:09 |
November | 0.160288E+10 | 969.33 | 01-NOV-09:09 | 0.275473E+11 | 17686.72 | 01-NOV-10:09 |
December | 0.165232E+10 | 969.33 | 01-DEC-10:09 | 0.284656E+11 | 17686.72 | 01-DEC-11:09 |
Annual Sum or Average | 0.195960E+11 | 0.335159E+12 | ||||
Minimum of Months | 0.149975E+10 | 969.33 | 0.257108E+11 | 17686.72 | ||
Maximum of Months | 0.168217E+10 | 969.33 | 0.284657E+11 | 17686.72 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.449309E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130441E+11 |
February | 0.272721E+11 | 0.406066E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3686831.91 | 0.918572E+10 |
March | 0.305458E+11 | 0.441839E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54220365.08 | 0.599721E+10 |
April | 0.292871E+11 | 0.415644E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264479E+09 | 0.349244E+10 |
May | 0.303219E+11 | 0.426597E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785854E+09 | 0.179040E+10 |
June | 0.295292E+11 | 0.413136E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240709E+10 | 0.531246E+09 |
July | 0.300798E+11 | 0.421583E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297875E+10 | 0.465774E+09 |
August | 0.305458E+11 | 0.432234E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293352E+10 | 0.159637E+09 |
September | 0.292871E+11 | 0.421666E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982196E+09 | 0.119732E+10 |
October | 0.300980E+11 | 0.441728E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132735E+09 | 0.463843E+10 |
November | 0.290996E+11 | 0.433942E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 342718.65 | 0.692684E+10 |
December | 0.300798E+11 | 0.450303E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984374E+10 |
Annual Sum or Average | 0.356244E+12 | 0.515405E+11 | 0.125156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105429E+11 | 0.572729E+11 |
Minimum of Months | 0.272721E+11 | 0.406066E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159637E+09 |
Maximum of Months | 0.305458E+11 | 0.450303E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297875E+10 | 0.130441E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.165581E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370322E+09 |
February | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329213E+09 |
March | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 158779.48 | 0.225678E+09 |
April | 0.786997E+09 | 0.160889E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 523374.74 | 0.143033E+09 |
May | 0.814802E+09 | 0.166899E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2816849.54 | 94946183.83 |
June | 0.793501E+09 | 0.162595E+10 | 0.227469E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 16322027.68 | 49004756.53 |
July | 0.808298E+09 | 0.165212E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 16815931.36 | 32974253.03 |
August | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 16822045.71 | 22888130.70 |
September | 0.786997E+09 | 0.160928E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 3760221.50 | 53609600.40 |
October | 0.808786E+09 | 0.165561E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 416300.89 | 0.163484E+09 |
November | 0.781956E+09 | 0.160288E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224934E+09 |
December | 0.808298E+09 | 0.165232E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329756E+09 |
Annual Sum or Average | 0.957291E+10 | 0.195960E+11 | 0.276753E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 57635530.90 | 0.203984E+10 |
Minimum of Months | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22888130.70 |
Maximum of Months | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 16822045.71 | 0.370322E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562347E+09 | 0.235589E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485362E+09 | 0.222890E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580829E+09 | 0.353223E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597704E+09 | 0.448305E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495230E+09 | 0.542118E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523655E+09 | 0.505091E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576498E+09 | 0.531235E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633118E+09 | 0.487883E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821260E+09 | 0.335232E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622934E+09 | 0.293088E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700781E+09 | 0.213707E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626814E+09 | 0.192896E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722653E+10 | 0.436126E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485362E+09 | 0.192896E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821260E+09 | 0.542118E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3065.69 | 02-JAN-17:19 | 6993.92 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 19640.30 | 07-JAN-19:10 |
February | 30255.31 | 04-FEB-19:10 | 3065.69 | 01-FEB-17:30 | 6993.92 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.51 | 28-FEB-14:00 | 20642.72 | 11-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 3065.69 | 01-MAR-18:19 | 6993.92 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1537.98 | 30-MAR-17:03 | 10606.65 | 22-MAR-11:10 |
April | 30255.31 | 01-APR-18:10 | 3065.69 | 01-APR-18:30 | 6993.92 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2352.11 | 17-APR-17:03 | 9751.72 | 05-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 3065.69 | 01-MAY-19:19 | 6993.92 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3726.20 | 19-MAY-17:03 | 5131.47 | 09-MAY-19:53 |
June | 30255.31 | 03-JUN-18:10 | 3065.69 | 01-JUN-19:30 | 6993.92 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5579.97 | 06-JUN-17:10 | 3775.75 | 10-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 3065.69 | 01-JUL-19:19 | 6993.92 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6303.82 | 08-JUL-18:04 | 3497.58 | 28-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 3065.69 | 01-AUG-19:10 | 6993.92 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6194.47 | 01-AUG-17:10 | 1882.47 | 25-AUG-06:10 |
September | 30255.31 | 02-SEP-18:10 | 3065.69 | 01-SEP-18:40 | 6993.92 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4113.20 | 07-SEP-12:00 | 5142.62 | 28-SEP-19:20 |
October | 30255.31 | 07-OCT-18:10 | 3065.69 | 02-OCT-18:19 | 6993.92 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2588.57 | 10-OCT-17:06 | 8667.81 | 25-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 3065.69 | 01-NOV-17:30 | 6993.92 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.51 | 19-NOV-14:55 | 11656.04 | 21-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 3065.69 | 01-DEC-17:30 | 6993.92 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 15230.34 | 02-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1882.47 | |||||
Maximum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 6303.82 | 20642.72 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 969.33 | 02-JAN-10:09 | 14422.89 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1102.24 | 07-JAN-05:00 |
February | 813.01 | 04-FEB-19:10 | 969.33 | 01-FEB-10:09 | 14422.89 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1219.10 | 12-FEB-01:10 |
March | 813.01 | 04-MAR-19:10 | 969.33 | 01-MAR-10:09 | 14422.89 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 12.09 | 30-MAR-15:53 | 985.64 | 22-MAR-03:30 |
April | 813.01 | 01-APR-18:10 | 969.33 | 01-APR-16:10 | 14422.89 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 9.84 | 12-APR-14:00 | 417.11 | 06-APR-01:50 |
May | 813.01 | 06-MAY-18:10 | 969.33 | 01-MAY-09:09 | 14422.89 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 23.11 | 19-MAY-13:00 | 423.46 | 10-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 969.33 | 01-JUN-09:09 | 14422.89 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 66.75 | 06-JUN-14:00 | 325.03 | 07-JUN-03:20 |
July | 813.01 | 01-JUL-18:10 | 969.33 | 01-JUL-16:10 | 14422.89 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 49.04 | 22-JUL-13:53 | 291.30 | 28-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 969.33 | 01-AUG-09:09 | 14422.89 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 55.16 | 07-AUG-14:53 | 239.09 | 29-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 969.33 | 01-SEP-09:09 | 14422.89 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 26.38 | 06-SEP-11:55 | 275.55 | 30-SEP-04:00 |
October | 813.01 | 07-OCT-18:10 | 969.33 | 02-OCT-09:09 | 14422.89 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 13.34 | 10-OCT-15:53 | 672.79 | 28-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 969.33 | 01-NOV-09:09 | 14422.89 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 828.48 | 20-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 969.33 | 01-DEC-10:09 | 14422.89 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1421.50 | 17-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 239.09 | ||||||
Maximum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 66.75 | 1421.50 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.70 | 29-JAN-06:55 | 6248.40 | 10-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.63 | 09-FEB-08:42 | 6734.14 | 12-FEB-13:40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.18 | 03-MAR-04:41 | 8084.51 | 19-MAR-13:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.57 | 15-APR-07:12 | 8508.37 | 09-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1517.34 | 20-MAY-05:50 | 8488.72 | 17-MAY-13:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.59 | 11-JUN-06:03 | 7567.69 | 11-JUN-12:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1433.56 | 05-JUL-03:00 | 8168.40 | 03-JUL-13:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1510.28 | 10-AUG-05:20 | 8883.93 | 04-AUG-14:42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.52 | 15-SEP-07:23 | 7636.09 | 15-SEP-13:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.89 | 14-OCT-07:23 | 6559.85 | 13-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.72 | 23-NOV-07:30 | 5406.17 | 08-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1928.43 | 10-DEC-08:32 | 4872.85 | 10-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1433.56 | 4872.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.70 | 8883.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36792.87 | 08-JAN-00:01 | 16808.50 | 6812.44 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 840.16 |
February | 41669.45 | 12-FEB-00:01 | 16808.50 | 6812.44 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.21 |
March | 46434.63 | 12-MAR-01:51 | 0.00 | 3576.59 | 5049.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.36 |
April | 50212.35 | 14-APR-03:11 | 0.00 | 5109.42 | 12023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49594.99 | 16-MAY-03:51 | 0.00 | 5109.42 | 12023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.21 |
June | 58687.20 | 11-JUN-00:42 | 0.00 | 3065.65 | 2885.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 |
July | 39245.33 | 03-JUL-01:22 | 0.00 | 3065.65 | 4328.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32759.31 | 19-AUG-00:04 | 0.00 | 5109.42 | 4809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 69.23 | 0.00 |
September | 44996.05 | 21-SEP-03:21 | 0.00 | 3576.59 | 8416.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.29 |
October | 39079.70 | 01-OCT-02:31 | 0.00 | 4087.54 | 3847.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.33 |
November | 35415.39 | 04-NOV-03:11 | 0.00 | 4598.48 | 10821.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.13 |
December | 37064.16 | 13-DEC-04:11 | 0.00 | 4087.54 | 9618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32759.31 | 0.00 | 3065.65 | 2885.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58687.20 | 16808.50 | 6812.44 | 12023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 69.23 | 1533.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 48550.72 | 20-JAN-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 |
February | 61172.39 | 28-FEB-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 |
March | 56600.00 | 21-MAR-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 60.09 |
April | 55314.60 | 11-APR-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 55.29 |
May | 55231.19 | 12-MAY-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 |
June | 41950.04 | 09-JUN-04:01 | 361.34 | 1723.23 | 54158.24 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 |
July | 31809.42 | 25-JUL-04:01 | 316.17 | 1507.82 | 47388.46 | 22809.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 |
August | 31705.38 | 25-AUG-04:01 | 316.17 | 1507.82 | 47388.46 | 22809.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 |
September | 52095.99 | 29-SEP-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 |
October | 54494.95 | 06-OCT-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 59.67 |
November | 54601.78 | 10-NOV-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47993.47 | 12-DEC-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 33.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31705.38 | 316.17 | 1507.82 | 47388.46 | 22809.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61172.39 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.05 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.05 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.07 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.77 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.64 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.95 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.31 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.47 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.77 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.77 | 313.32 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.751438E+11 | 43481.84 | 31-JAN-18:10 | 0.142796E+12 | 126824.39 | 27-JAN-07:30 |
February | 0.684607E+11 | 48402.06 | 28-FEB-18:40 | 0.106559E+12 | 171648.89 | 03-FEB-04:19 |
March | 0.780636E+11 | 54629.52 | 30-MAR-18:00 | 0.799195E+11 | 77184.73 | 19-MAR-06:49 |
April | 0.808815E+11 | 53693.71 | 18-APR-10:00 | 0.699655E+11 | 80017.15 | 06-APR-06:10 |
May | 0.928826E+11 | 61600.14 | 30-MAY-10:00 | 0.668241E+11 | 43389.57 | 06-MAY-10:20 |
June | 0.105611E+12 | 71548.22 | 23-JUN-11:00 | 0.627489E+11 | 43092.41 | 03-JUN-10:30 |
July | 0.117624E+12 | 75343.53 | 07-JUL-11:00 | 0.634942E+11 | 42881.27 | 02-JUL-10:20 |
August | 0.122908E+12 | 73867.56 | 18-AUG-11:00 | 0.636649E+11 | 42845.37 | 27-AUG-10:39 |
September | 0.998433E+11 | 70125.61 | 06-SEP-11:00 | 0.623891E+11 | 43039.75 | 30-SEP-10:20 |
October | 0.841524E+11 | 64143.00 | 18-OCT-17:00 | 0.696274E+11 | 71991.94 | 26-OCT-06:10 |
November | 0.750083E+11 | 51936.97 | 27-NOV-18:10 | 0.799136E+11 | 102975.96 | 22-NOV-07:30 |
December | 0.752753E+11 | 48872.32 | 13-DEC-11:00 | 0.105762E+12 | 117849.92 | 18-DEC-07:40 |
Annual Sum or Average | 0.107585E+13 | 0.973664E+12 | ||||
Minimum of Months | 0.684607E+11 | 43481.84 | 0.623891E+11 | 42845.37 | ||
Maximum of Months | 0.122908E+12 | 75343.53 | 0.142796E+12 | 171648.89 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.614890E+10 | 0.454957E+10 | 0.390952E+11 | 0.00 | 0.136966E+11 | 37879553.69 | 0.00 | 0.167644E+09 | 0.00 | 0.00 | 0.00 | 0.639544E+10 | 0.00 |
February | 0.556040E+10 | 0.385128E+10 | 0.353119E+11 | 0.00 | 0.121046E+11 | 34213790.43 | 0.00 | 0.112112E+10 | 0.00 | 0.00 | 0.00 | 0.578479E+10 | 0.00 |
March | 0.610056E+10 | 0.388937E+10 | 0.390954E+11 | 0.00 | 0.129100E+11 | 37879553.69 | 0.00 | 0.417741E+10 | 0.00 | 0.00 | 0.00 | 0.645512E+10 | 0.00 |
April | 0.576533E+10 | 0.338986E+10 | 0.378342E+11 | 0.00 | 0.124147E+11 | 36657632.61 | 0.00 | 0.990568E+10 | 0.00 | 0.00 | 0.00 | 0.619700E+10 | 0.00 |
May | 0.593496E+10 | 0.317716E+10 | 0.390953E+11 | 0.00 | 0.130618E+11 | 37879553.69 | 0.00 | 0.195327E+11 | 0.00 | 0.00 | 0.00 | 0.641660E+10 | 0.00 |
June | 0.575731E+10 | 0.293172E+10 | 0.378342E+11 | 0.00 | 0.136126E+11 | 36657632.61 | 0.00 | 0.337199E+11 | 0.00 | 0.00 | 0.00 | 0.623731E+10 | 0.00 |
July | 0.586795E+10 | 0.308313E+10 | 0.390952E+11 | 0.00 | 0.148437E+11 | 37879553.69 | 0.00 | 0.426429E+11 | 0.00 | 0.00 | 0.00 | 0.637259E+10 | 0.00 |
August | 0.600452E+10 | 0.335521E+10 | 0.390954E+11 | 0.00 | 0.152591E+11 | 37879553.69 | 0.00 | 0.470030E+11 | 0.00 | 0.00 | 0.00 | 0.645062E+10 | 0.00 |
September | 0.582594E+10 | 0.360192E+10 | 0.378342E+11 | 0.00 | 0.131569E+11 | 36657632.61 | 0.00 | 0.277160E+11 | 0.00 | 0.00 | 0.00 | 0.619576E+10 | 0.00 |
October | 0.607290E+10 | 0.410944E+10 | 0.390952E+11 | 0.00 | 0.129669E+11 | 37879553.69 | 0.00 | 0.997559E+10 | 0.00 | 0.00 | 0.00 | 0.638296E+10 | 0.00 |
November | 0.594230E+10 | 0.431614E+10 | 0.378341E+11 | 0.00 | 0.125438E+11 | 36657632.61 | 0.00 | 0.297297E+10 | 0.00 | 0.00 | 0.00 | 0.618179E+10 | 0.00 |
December | 0.615535E+10 | 0.464160E+10 | 0.390952E+11 | 0.00 | 0.131772E+11 | 37879553.69 | 0.00 | 0.616986E+09 | 0.00 | 0.00 | 0.00 | 0.638452E+10 | 0.00 |
Annual Sum or Average | 0.711364E+11 | 0.448964E+11 | 0.460316E+12 | 0.00 | 0.159748E+12 | 0.446001E+09 | 0.00 | 0.199552E+12 | 0.00 | 0.00 | 0.00 | 0.754545E+11 | 0.00 |
Minimum of Months | 0.556040E+10 | 0.293172E+10 | 0.353119E+11 | 0.00 | 0.121046E+11 | 34213790.43 | 0.00 | 0.167644E+09 | 0.00 | 0.00 | 0.00 | 0.578479E+10 | 0.00 |
Maximum of Months | 0.615535E+10 | 0.464160E+10 | 0.390954E+11 | 0.00 | 0.152591E+11 | 37879553.69 | 0.00 | 0.470030E+11 | 0.00 | 0.00 | 0.00 | 0.645512E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.716497E+11 | 0.00 | 0.312469E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.422331E+11 | 0.00 | 0.282878E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.944635E+10 | 0.00 | 0.305734E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.363749E+10 | 0.00 | 0.277154E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.281833E+09 | 0.00 | 0.266426E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 21439300.65 | 0.00 | 0.241148E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.235945E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.237652E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 723023.33 | 0.00 | 0.237758E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.346628E+10 | 0.00 | 0.262614E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.139026E+11 | 0.00 | 0.273984E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.357475E+11 | 0.00 | 0.301143E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.180387E+12 | 0.00 | 0.323490E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.235945E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.716497E+11 | 0.00 | 0.312469E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4035.02 | 02-JAN-17:19 | 3334.35 | 01-JAN-00:10 | 24680.63 | 01-JAN-11:09 | 0.00 | 7126.84 | 14-JAN-07:10 | 17.86 | 02-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4035.02 | 01-FEB-17:30 | 3334.35 | 01-FEB-00:10 | 24680.63 | 01-FEB-11:09 | 0.00 | 7685.35 | 12-FEB-07:10 | 17.86 | 07-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 4035.02 | 01-MAR-18:19 | 3334.35 | 01-MAR-00:10 | 24680.63 | 01-MAR-11:09 | 0.00 | 6393.67 | 19-MAR-05:00 | 17.86 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 4035.02 | 01-APR-18:30 | 3334.35 | 01-APR-05:10 | 24680.63 | 01-APR-10:09 | 0.00 | 6463.37 | 06-APR-05:10 | 17.86 | 05-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 4035.02 | 01-MAY-19:19 | 3334.35 | 01-MAY-05:10 | 24680.63 | 01-MAY-10:09 | 0.00 | 6865.39 | 30-MAY-17:00 | 17.86 | 28-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 4035.02 | 01-JUN-19:30 | 3334.35 | 01-JUN-05:10 | 24680.63 | 01-JUN-10:09 | 0.00 | 8535.36 | 23-JUN-11:00 | 17.86 | 26-JUN-11:39 | 0.00 | 01-JUN-00:10 |
July | 4035.02 | 01-JUL-19:19 | 3334.35 | 01-JUL-05:10 | 24680.63 | 01-JUL-10:09 | 0.00 | 9216.14 | 07-JUL-11:00 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 4035.02 | 01-AUG-19:10 | 3334.35 | 01-AUG-05:10 | 24680.63 | 01-AUG-10:09 | 0.00 | 8838.39 | 18-AUG-11:00 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 4035.02 | 01-SEP-18:40 | 3334.35 | 01-SEP-05:10 | 24680.63 | 01-SEP-10:09 | 0.00 | 8334.80 | 06-SEP-11:00 | 17.86 | 04-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 4035.02 | 02-OCT-18:19 | 3334.35 | 01-OCT-05:10 | 24680.63 | 01-OCT-10:09 | 0.00 | 6670.04 | 18-OCT-17:19 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 4035.02 | 01-NOV-17:30 | 3334.35 | 01-NOV-05:10 | 24680.63 | 01-NOV-10:09 | 0.00 | 6766.39 | 22-NOV-07:10 | 17.86 | 21-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 4035.02 | 01-DEC-17:30 | 3334.35 | 01-DEC-00:10 | 24680.63 | 01-DEC-11:09 | 0.00 | 6950.63 | 18-DEC-07:10 | 17.86 | 02-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 6393.67 | 17.86 | 0.00 | ||||||
Maximum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 9216.14 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5494.60 | 31-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4741.33 | 27-JAN-19:49 | 0.00 |
February | 10972.91 | 28-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.31 | 03-FEB-19:49 | 0.00 |
March | 17005.45 | 30-MAR-17:19 | 0.00 | 0.00 | 0.00 | 4740.79 | 03-MAR-07:00 | 0.00 |
April | 16150.78 | 04-APR-17:19 | 0.00 | 0.00 | 0.00 | 4741.28 | 07-APR-06:30 | 0.00 |
May | 24348.28 | 30-MAY-17:00 | 0.00 | 0.00 | 0.00 | 4739.20 | 12-MAY-06:30 | 0.00 |
June | 31438.25 | 23-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4738.61 | 07-JUN-06:10 | 0.00 |
July | 34546.24 | 07-JUL-11:00 | 0.00 | 0.00 | 0.00 | 4736.92 | 13-JUL-18:19 | 0.00 |
August | 33758.52 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.66 | 15-AUG-18:19 | 0.00 |
September | 30238.67 | 06-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4738.45 | 14-SEP-06:00 | 0.00 |
October | 23893.03 | 18-OCT-17:19 | 0.00 | 0.00 | 0.00 | 4740.72 | 26-OCT-06:49 | 0.00 |
November | 12985.72 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4741.44 | 14-NOV-07:30 | 0.00 |
December | 11789.15 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4741.50 | 01-DEC-19:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5494.60 | 0.00 | 0.00 | 0.00 | 4736.66 | 0.00 | ||
Maximum of Months | 34546.24 | 0.00 | 0.00 | 0.00 | 4741.50 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 43481.84 | 31-JAN-18:10 | 4035.02 | 20661.14 | 3334.35 | 0.00 | 5387.87 | 17.86 | 0.00 | 3557.31 | 0.00 |
February | 48402.06 | 28-FEB-18:40 | 4035.02 | 20661.14 | 3334.35 | 0.00 | 5387.87 | 17.86 | 0.00 | 8592.63 | 0.00 |
March | 54629.52 | 30-MAR-18:00 | 4035.02 | 19053.35 | 3334.35 | 0.00 | 5469.05 | 17.86 | 0.00 | 16019.89 | 0.00 |
April | 53693.71 | 18-APR-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5517.02 | 17.86 | 0.00 | 14123.43 | 0.00 |
May | 61600.14 | 30-MAY-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 6126.59 | 17.86 | 0.00 | 20978.22 | 0.00 |
June | 71548.22 | 23-JUN-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 8535.36 | 17.86 | 0.00 | 31438.25 | 0.00 |
July | 75343.53 | 07-JUL-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 9216.14 | 17.86 | 0.00 | 34546.24 | 0.00 |
August | 73867.56 | 18-AUG-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 8838.39 | 17.86 | 0.00 | 33454.95 | 0.00 |
September | 70125.61 | 06-SEP-11:00 | 3207.28 | 23072.84 | 0.00 | 0.00 | 8334.80 | 17.86 | 0.00 | 30238.67 | 0.00 |
October | 64143.00 | 18-OCT-17:00 | 4035.02 | 20661.14 | 3334.35 | 0.00 | 6503.93 | 17.86 | 0.00 | 23253.70 | 0.00 |
November | 51936.97 | 27-NOV-18:10 | 4035.02 | 20661.14 | 3334.35 | 0.00 | 5387.87 | 17.86 | 0.00 | 12090.99 | 0.00 |
December | 48872.32 | 13-DEC-11:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5410.87 | 17.86 | 0.00 | 9094.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 43481.84 | 3207.28 | 19053.35 | 0.00 | 0.00 | 5387.87 | 17.86 | 0.00 | 3557.31 | 0.00 | |
Maximum of Months | 75343.53 | 4035.02 | 24680.63 | 3334.35 | 0.00 | 9216.14 | 17.86 | 0.00 | 34546.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 101931.41 | 08-JAN-04:30 | 0.00 | 27611.74 | 27-JAN-07:30 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 162148.99 | 03-FEB-04:30 | 0.00 | 27635.62 | 03-FEB-19:00 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 49305.87 | 19-MAR-05:00 | 0.00 | 26820.90 | 01-MAR-07:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 53523.63 | 06-APR-05:10 | 0.00 | 23978.56 | 03-APR-06:30 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 13895.82 | 11-MAY-05:00 | 0.00 | 20169.00 | 01-MAY-18:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 3052.91 | 10-JUN-05:10 | 0.00 | 17585.73 | 01-JUN-18:19 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 17273.37 | 03-JUL-18:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 17244.31 | 30-AUG-18:40 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 377.26 | 29-SEP-04:00 | 0.00 | 17509.68 | 29-SEP-06:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 42406.31 | 26-OCT-05:10 | 0.00 | 19587.41 | 31-OCT-18:40 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 70594.80 | 22-NOV-06:10 | 0.00 | 23775.49 | 29-NOV-07:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 80269.35 | 18-DEC-07:10 | 0.00 | 26500.22 | 29-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 17244.31 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 162148.99 | 0.00 | 27635.62 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
February | 1.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.62 | 0.00 | 24.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.00 | 24.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.58 | 0.00 | 24.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 24.71 | 0.00 | 24.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.75 | 0.00 | 24.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 24.67 | 0.00 | 24.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.62 | 0.00 | 24.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 19.75 | 0.00 | 19.75 | 97.33 | 24.51 | 0.00 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.30 | 0.00 | 20.30 | 31.00 | 24.75 | 0.00 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.26 | 0.00 | 27.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.55 | 0.00 | 27.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 27.71 | 0.00 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 28.02 | 0.00 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.41 | 0.00 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.60 | 1.00 | 28.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 28.23 | 12.00 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 28.30 | 11.83 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 28.73 | 0.33 | 28.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 28.19 | 0.00 | 28.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 27.72 | 0.00 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.31 | 0.00 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 317.67 | 28.16 | 25.17 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.26 | 0.00 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 28.73 | 12.00 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 593.00 | 20.92 | 181.67 | 20.83 | 179.33 | 20.77 |
February | 480.33 | 21.24 | 108.83 | 21.15 | 102.83 | 21.07 |
March | 400.33 | 21.65 | 146.33 | 22.14 | 26.17 | 22.11 |
April | 291.17 | 22.24 | 291.00 | 23.04 | 78.00 | 23.09 |
May | 246.17 | 23.34 | 518.00 | 23.74 | 182.67 | 23.75 |
June | 287.67 | 23.88 | 555.17 | 23.96 | 268.83 | 23.97 |
July | 436.83 | 23.99 | 609.00 | 23.99 | 436.83 | 23.99 |
August | 503.83 | 24.00 | 612.00 | 24.00 | 503.83 | 24.00 |
September | 329.00 | 23.85 | 552.67 | 23.94 | 303.33 | 23.95 |
October | 347.33 | 22.16 | 324.50 | 23.00 | 107.00 | 23.10 |
November | 430.50 | 21.59 | 127.83 | 21.95 | 63.00 | 21.99 |
December | 583.33 | 21.13 | 110.00 | 21.14 | 86.67 | 21.05 |
Annual Sum or Average | 4929.50 | 22.34 | 4137.00 | 22.92 | 2338.50 | 23.00 |
Minimum of Months | 246.17 | 20.92 | 108.83 | 20.83 | 26.17 | 20.77 |
Maximum of Months | 593.00 | 24.00 | 612.00 | 24.00 | 503.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 569.67 | 19.79 | 256.50 | 20.05 | 223.67 | 20.05 |
February | 438.00 | 20.93 | 294.50 | 21.76 | 200.33 | 21.86 |
March | 399.50 | 23.21 | 398.00 | 24.23 | 211.33 | 24.54 |
April | 423.83 | 25.04 | 502.83 | 25.27 | 356.67 | 25.45 |
May | 551.67 | 25.84 | 590.17 | 25.83 | 541.33 | 25.86 |
June | 564.50 | 26.00 | 588.83 | 25.98 | 564.50 | 25.99 |
July | 609.00 | 26.03 | 609.00 | 26.03 | 609.00 | 26.03 |
August | 612.00 | 26.04 | 612.00 | 26.04 | 612.00 | 26.04 |
September | 552.00 | 25.99 | 590.00 | 25.94 | 552.00 | 25.96 |
October | 442.17 | 24.91 | 500.67 | 25.14 | 357.00 | 25.36 |
November | 405.33 | 22.76 | 363.17 | 23.80 | 205.67 | 24.13 |
December | 463.50 | 20.34 | 219.17 | 21.10 | 119.83 | 21.15 |
Annual Sum or Average | 6031.17 | 24.05 | 5524.83 | 24.60 | 4553.33 | 24.82 |
Minimum of Months | 399.50 | 19.79 | 219.17 | 20.05 | 119.83 | 20.05 |
Maximum of Months | 612.00 | 26.04 | 612.00 | 26.04 | 612.00 | 26.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.00261 | 29.60085 | -0.4347 | 10.82138 |
February | 551.00000 | 21.58547 | 32.44396 | -0.2535 | 9.30983 |
March | 612.00000 | 22.44081 | 38.55907 | 0.04122 | 7.89263 |
April | 590.00000 | 23.10430 | 47.08758 | 0.27338 | 8.87778 |
May | 611.00000 | 23.71084 | 55.98086 | -0.3691 | 9.41382 |
June | 592.00000 | 23.93759 | 59.15193 | -0.2157 | 6.64730 |
July | 609.00000 | 23.99451 | 66.18137 | -0.1273 | 5.47604 |
August | 612.00000 | 24.00005 | 66.89891 | -0.1040 | 5.34218 |
September | 590.00000 | 23.89217 | 61.00389 | -0.2262 | 6.77331 |
October | 610.00000 | 22.91547 | 51.73841 | 0.29011 | 9.31682 |
November | 591.00000 | 22.22484 | 39.73849 | 0.01239 | 8.03445 |
December | 609.00000 | 21.25098 | 34.67601 | -0.2954 | 8.92849 |
Annual Sum or Average | 7187.00000 | 22.84418 | 48.69037 | -0.1171 | 8.06395 |
Minimum of Months | 551.00000 | 21.00261 | 29.60085 | -0.4347 | 5.34218 |
Maximum of Months | 612.00000 | 24.00005 | 66.89891 | 0.29011 | 10.82138 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.07795 | 35.82534 | -0.3416 | 12.85902 |
February | 551.00000 | 21.61566 | 36.82057 | 0.03083 | 15.21106 |
March | 612.00000 | 23.64344 | 40.36632 | 0.55012 | 18.81085 |
April | 590.00000 | 24.80492 | 46.52734 | 0.88367 | 26.26928 |
May | 611.00000 | 25.68315 | 52.45391 | 0.55751 | 14.21557 |
June | 592.00000 | 25.93638 | 55.48000 | 0.71935 | 17.01730 |
July | 609.00000 | 26.03263 | 60.59571 | 0.81301 | 19.48096 |
August | 612.00000 | 26.04122 | 61.20053 | 0.83007 | 20.03738 |
September | 590.00000 | 25.89184 | 55.45927 | 0.69892 | 16.30922 |
October | 610.00000 | 24.55783 | 49.65522 | 0.88151 | 26.24273 |
November | 591.00000 | 23.19618 | 41.09900 | 0.47806 | 18.21731 |
December | 609.00000 | 21.15684 | 39.09123 | -0.0399 | 11.78712 |
Annual Sum or Average | 7187.00000 | 24.06431 | 47.95528 | 0.50711 | 18.04626 |
Minimum of Months | 551.00000 | 20.07795 | 35.82534 | -0.3416 | 11.78712 |
Maximum of Months | 612.00000 | 26.04122 | 61.20053 | 0.88367 | 26.26928 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.102486E+09 | 34483896.72 | 8.06 | 77682776.72 | 24803640.00 | 0.00 | 0.26 | 31-JAN-14:00 | 0.00 | 01-JAN-00:01 | 10080.30 | 31-JAN-14:00 | 7928.56 | 31-JAN-14:00 | 2151.74 | 31-JAN-14:00 | 3300.67 | 31-JAN-14:00 | 0.00 | 01-JAN-00:01 |
February | 0.169467E+10 | 0.547903E+09 | 54.10 | 0.161763E+10 | 77037249.81 | 0.00 | 0.57 | 28-FEB-14:00 | 0.00 | 01-FEB-00:03 | 24296.49 | 28-FEB-14:00 | 22921.67 | 28-FEB-14:00 | 1549.32 | 28-FEB-19:40 | 7349.38 | 28-FEB-14:00 | 0.00 | 01-FEB-00:03 |
March | 0.750634E+10 | 0.229967E+10 | 153.11 | 0.553724E+10 | 0.196911E+10 | 0.00 | 1.00 | 12-MAR-01:51 | 0.00 | 01-MAR-00:03 | 96504.03 | 12-MAR-01:51 | 63913.50 | 31-MAR-00:42 | 37276.17 | 12-MAR-01:51 | 25856.18 | 12-MAR-01:51 | 0.00 | 01-MAR-00:03 |
April | 0.191992E+11 | 0.578631E+10 | 283.30 | 0.145140E+11 | 0.468522E+10 | 0.00 | 1.00 | 03-APR-00:31 | 0.00 | 01-APR-00:01 | 100819.53 | 03-APR-00:31 | 53445.61 | 22-APR-03:11 | 49901.84 | 03-APR-00:31 | 26178.29 | 03-APR-00:31 | 0.00 | 01-APR-00:01 |
May | 0.406950E+11 | 0.116362E+11 | 450.13 | 0.270518E+11 | 0.136431E+11 | 0.00 | 1.00 | 03-MAY-00:31 | 0.00 | 01-MAY-00:01 | 101090.51 | 26-MAY-00:42 | 67069.35 | 17-MAY-01:22 | 56607.81 | 26-MAY-00:42 | 26198.35 | 26-MAY-00:42 | 0.00 | 01-MAY-00:01 |
June | 0.751083E+11 | 0.204685E+11 | 608.38 | 0.464097E+11 | 0.286986E+11 | 0.00 | 1.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:01 | 104141.41 | 23-JUN-00:09 | 87487.11 | 11-JUN-00:42 | 63545.20 | 23-JUN-00:09 | 26426.94 | 23-JUN-00:09 | 0.00 | 01-JUN-00:01 |
July | 0.957633E+11 | 0.257215E+11 | 678.23 | 0.540089E+11 | 0.417544E+11 | 0.00 | 1.00 | 01-JUL-00:05 | 0.00 | 01-JUL-00:01 | 104662.51 | 28-JUL-00:09 | 57302.68 | 03-JUL-00:42 | 66114.12 | 28-JUL-00:09 | 26466.90 | 28-JUL-00:09 | 0.00 | 01-JUL-00:01 |
August | 0.107353E+12 | 0.284736E+11 | 700.68 | 0.575991E+11 | 0.497535E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:01 | 102652.72 | 25-AUG-00:42 | 54388.77 | 01-AUG-17:10 | 54058.87 | 25-AUG-00:42 | 26314.54 | 25-AUG-00:42 | 0.00 | 01-AUG-00:01 |
September | 0.599767E+11 | 0.164543E+11 | 556.24 | 0.343831E+11 | 0.255936E+11 | 0.00 | 1.00 | 01-SEP-00:09 | 0.00 | 01-SEP-00:01 | 100330.90 | 02-SEP-00:42 | 60739.52 | 21-SEP-02:62 | 52147.12 | 02-SEP-00:42 | 26142.12 | 02-SEP-00:42 | 0.00 | 01-SEP-00:01 |
October | 0.195977E+11 | 0.563815E+10 | 271.13 | 0.119911E+11 | 0.760665E+10 | 0.00 | 1.00 | 01-OCT-02:31 | 0.00 | 01-OCT-00:01 | 103277.99 | 02-OCT-00:42 | 51355.25 | 17-OCT-00:42 | 62217.63 | 02-OCT-00:42 | 26361.48 | 02-OCT-00:42 | 0.00 | 01-OCT-00:01 |
November | 0.453576E+10 | 0.143081E+10 | 121.73 | 0.300521E+10 | 0.153055E+10 | 0.00 | 1.00 | 04-NOV-03:11 | 0.00 | 01-NOV-00:01 | 48196.67 | 04-NOV-03:11 | 25324.81 | 04-NOV-03:11 | 22871.85 | 04-NOV-03:11 | 12923.32 | 04-NOV-03:11 | 0.00 | 01-NOV-00:01 |
December | 0.857842E+09 | 0.273794E+09 | 22.13 | 0.538137E+09 | 0.319705E+09 | 0.00 | 1.00 | 13-DEC-04:11 | 0.00 | 01-DEC-00:01 | 48196.67 | 13-DEC-04:11 | 27239.65 | 13-DEC-04:11 | 20957.02 | 13-DEC-04:11 | 12923.32 | 13-DEC-04:11 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.432390E+12 | 0.118765E+12 | 3907.22 | 0.256734E+12 | 0.175656E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.102486E+09 | 34483896.72 | 8.06 | 77682776.72 | 24803640.00 | 0.00 | 0.26 | 0.00 | 10080.30 | 7928.56 | 1549.32 | 3300.67 | 0.00 | |||||||
Maximum of Months | 0.107353E+12 | 0.284736E+11 | 700.68 | 0.575991E+11 | 0.497535E+11 | 0.00 | 1.00 | 0.00 | 104662.51 | 87487.11 | 66114.12 | 26466.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.454365E+09 | 0.133160E+09 | 29.95 | 0.285440E+09 | 0.168925E+09 | 0.00 | 1.00 | 20-JAN-02:22 | 0.00 | 01-JAN-00:01 | 40786.38 | 20-JAN-05:01 | 24504.43 | 31-JAN-04:31 | 21574.60 | 20-JAN-05:01 | 9952.96 | 20-JAN-05:01 | 0.00 | 01-JAN-00:01 |
February | 0.202099E+10 | 0.573219E+09 | 93.73 | 0.178196E+10 | 0.239036E+09 | 0.00 | 1.00 | 16-FEB-04:52 | 0.00 | 01-FEB-00:03 | 40786.38 | 17-FEB-05:01 | 33257.41 | 28-FEB-05:01 | 19236.96 | 17-FEB-05:01 | 9952.96 | 17-FEB-05:01 | 0.00 | 01-FEB-00:03 |
March | 0.706339E+10 | 0.187774E+10 | 234.92 | 0.518301E+10 | 0.188038E+10 | 0.00 | 1.00 | 01-MAR-03:42 | 0.00 | 01-MAR-00:03 | 40786.38 | 29-MAR-01:22 | 33970.49 | 11-MAR-03:02 | 19756.48 | 09-MAR-05:01 | 9952.96 | 01-MAR-04:21 | 0.00 | 01-MAR-00:03 |
April | 0.160625E+11 | 0.411938E+10 | 352.40 | 0.117574E+11 | 0.430517E+10 | 0.00 | 1.00 | 01-APR-00:42 | 0.00 | 01-APR-00:01 | 42289.28 | 03-APR-00:42 | 30045.29 | 15-APR-03:21 | 24842.22 | 23-APR-00:42 | 10055.32 | 03-APR-00:42 | 0.00 | 01-APR-00:01 |
May | 0.322581E+11 | 0.789658E+10 | 505.45 | 0.209167E+11 | 0.113414E+11 | 0.00 | 1.00 | 01-MAY-00:42 | 0.00 | 01-MAY-00:01 | 44079.61 | 31-MAY-00:03 | 27086.61 | 17-MAY-02:62 | 26252.54 | 31-MAY-00:03 | 10177.22 | 31-MAY-00:03 | 0.00 | 01-MAY-00:01 |
June | 0.555323E+11 | 0.132515E+11 | 636.49 | 0.340725E+11 | 0.214598E+11 | 0.00 | 1.00 | 01-JUN-00:03 | 0.00 | 01-JUN-00:01 | 45316.35 | 18-JUN-10:58 | 36496.75 | 11-JUN-00:07 | 30094.43 | 27-JUN-00:03 | 10682.32 | 22-JUN-16:55 | 0.00 | 01-JUN-00:01 |
July | 0.716556E+11 | 0.169214E+11 | 697.71 | 0.395568E+11 | 0.320988E+11 | 0.00 | 1.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:01 | 45316.35 | 25-JUL-11:00 | 34485.50 | 08-JUL-15:15 | 31670.48 | 27-JUL-00:03 | 11451.34 | 08-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.794290E+11 | 0.185295E+11 | 711.02 | 0.413341E+11 | 0.380948E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:01 | 45316.35 | 04-AUG-10:53 | 32938.26 | 02-AUG-16:20 | 30966.00 | 24-AUG-00:03 | 11137.32 | 01-AUG-15:05 | 0.00 | 01-AUG-00:01 |
September | 0.472693E+11 | 0.112618E+11 | 599.12 | 0.259398E+11 | 0.213294E+11 | 0.00 | 1.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:01 | 45316.35 | 07-SEP-10:40 | 27694.92 | 07-SEP-16:17 | 29229.28 | 17-SEP-00:03 | 10504.17 | 07-SEP-16:00 | 0.00 | 01-SEP-00:01 |
October | 0.174343E+11 | 0.433744E+10 | 339.26 | 0.101996E+11 | 0.723479E+10 | 0.00 | 1.00 | 01-OCT-00:42 | 0.00 | 01-OCT-00:01 | 45316.35 | 19-OCT-00:03 | 26644.77 | 14-OCT-01:22 | 31328.84 | 19-OCT-00:03 | 10266.42 | 19-OCT-00:03 | 0.00 | 01-OCT-00:01 |
November | 0.576318E+10 | 0.154216E+10 | 193.84 | 0.368862E+10 | 0.207456E+10 | 0.00 | 1.00 | 02-NOV-00:42 | 0.00 | 01-NOV-00:01 | 40786.38 | 04-NOV-00:42 | 25677.61 | 10-NOV-03:42 | 21824.96 | 05-NOV-00:42 | 9952.96 | 02-NOV-03:22 | 0.00 | 01-NOV-00:01 |
December | 0.125840E+10 | 0.343192E+09 | 46.63 | 0.721475E+09 | 0.536927E+09 | 0.00 | 1.00 | 12-DEC-04:21 | 0.00 | 01-DEC-00:01 | 40786.38 | 13-DEC-01:42 | 21703.49 | 13-DEC-01:42 | 22135.58 | 12-DEC-05:01 | 9952.96 | 12-DEC-05:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.336201E+12 | 0.807869E+11 | 4440.53 | 0.195437E+12 | 0.140764E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.454365E+09 | 0.133160E+09 | 29.95 | 0.285440E+09 | 0.168925E+09 | 0.00 | 1.00 | 0.00 | 40786.38 | 21703.49 | 19236.96 | 9952.96 | 0.00 | |||||||
Maximum of Months | 0.794290E+11 | 0.185295E+11 | 711.02 | 0.413341E+11 | 0.380948E+11 | 0.00 | 1.00 | 0.00 | 45316.35 | 36496.75 | 31670.48 | 11451.34 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.97 | 58.75 | 70.22 | 78.53 | 521.01 | 0.00 | 0.00 | 0.00 |
February | 161.79 | 87.09 | 74.70 | 147.20 | 422.83 | 0.00 | 0.00 | 0.00 |
March | 203.51 | 92.80 | 110.71 | 228.46 | 259.10 | 0.00 | 0.00 | 0.00 |
April | 245.99 | 112.24 | 133.76 | 353.01 | 200.00 | 0.00 | 0.00 | 0.00 |
May | 269.50 | 113.93 | 155.57 | 443.08 | 132.79 | 0.00 | 0.00 | 0.00 |
June | 278.76 | 116.72 | 162.04 | 534.34 | 80.64 | 0.00 | 0.00 | 0.00 |
July | 271.67 | 113.93 | 157.74 | 545.20 | 55.94 | 0.00 | 0.00 | 0.00 |
August | 249.00 | 98.72 | 150.28 | 507.95 | 46.20 | 0.00 | 0.00 | 0.00 |
September | 204.05 | 90.11 | 113.94 | 345.98 | 116.91 | 0.00 | 0.00 | 0.00 |
October | 174.59 | 90.87 | 83.72 | 224.54 | 246.20 | 0.00 | 0.00 | 0.00 |
November | 139.10 | 62.77 | 76.33 | 125.42 | 331.35 | 0.00 | 0.00 | 0.00 |
December | 120.75 | 55.00 | 65.74 | 76.81 | 424.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.18 | 91.06 | 113.11 | 301.72 | 235.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.75 | 55.00 | 65.74 | 76.81 | 46.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 278.76 | 116.72 | 162.04 | 545.20 | 521.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 427.66 | 296.89 | 130.77 | 480.05 | 650.02 | 0.00 | 0.00 | 0.00 |
February | 398.78 | 265.99 | 132.79 | 491.44 | 552.97 | 0.00 | 0.00 | 0.00 |
March | 365.45 | 192.07 | 173.38 | 504.11 | 367.67 | 0.00 | 0.00 | 0.00 |
April | 275.66 | 92.71 | 182.95 | 428.66 | 299.49 | 0.00 | 0.00 | 0.00 |
May | 221.44 | 27.75 | 193.69 | 369.35 | 200.48 | 0.00 | 0.00 | 0.00 |
June | 203.11 | 11.78 | 191.33 | 419.72 | 122.06 | 0.00 | 0.00 | 0.00 |
July | 203.77 | 14.21 | 189.56 | 449.38 | 82.61 | 0.00 | 0.00 | 0.00 |
August | 245.79 | 46.89 | 198.90 | 547.90 | 67.23 | 0.00 | 0.00 | 0.00 |
September | 277.29 | 108.36 | 168.94 | 503.80 | 168.67 | 0.00 | 0.00 | 0.00 |
October | 388.49 | 251.17 | 137.33 | 598.05 | 342.73 | 0.00 | 0.00 | 0.00 |
November | 423.71 | 282.57 | 141.14 | 577.26 | 446.24 | 0.00 | 0.00 | 0.00 |
December | 424.56 | 298.45 | 126.11 | 520.15 | 545.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 320.96 | 156.88 | 164.08 | 490.91 | 319.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.11 | 11.78 | 126.11 | 369.35 | 67.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.66 | 298.45 | 198.90 | 598.05 | 650.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.15 | 61.47 | 70.68 | 94.09 | 531.35 | 0.00 | 0.00 | 0.00 |
February | 151.34 | 70.93 | 80.41 | 146.47 | 443.22 | 0.00 | 0.00 | 0.00 |
March | 221.95 | 107.00 | 114.95 | 277.45 | 274.79 | 0.00 | 0.00 | 0.00 |
April | 250.09 | 114.33 | 135.76 | 372.48 | 211.63 | 0.00 | 0.00 | 0.00 |
May | 251.68 | 95.48 | 156.20 | 420.67 | 142.25 | 0.00 | 0.00 | 0.00 |
June | 264.43 | 101.78 | 162.65 | 515.33 | 87.46 | 0.00 | 0.00 | 0.00 |
July | 248.91 | 92.04 | 156.87 | 507.86 | 59.32 | 0.00 | 0.00 | 0.00 |
August | 244.47 | 91.39 | 153.08 | 500.81 | 48.37 | 0.00 | 0.00 | 0.00 |
September | 199.68 | 83.42 | 116.26 | 341.92 | 121.72 | 0.00 | 0.00 | 0.00 |
October | 177.72 | 92.39 | 85.33 | 246.20 | 260.54 | 0.00 | 0.00 | 0.00 |
November | 141.21 | 63.17 | 78.04 | 151.82 | 353.75 | 0.00 | 0.00 | 0.00 |
December | 116.99 | 51.29 | 65.71 | 92.46 | 447.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.30 | 85.45 | 114.85 | 306.50 | 247.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.99 | 51.29 | 65.71 | 92.46 | 48.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 264.43 | 114.33 | 162.65 | 515.33 | 531.35 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345444E+09 | 0.157367E+09 | 0.188077E+09 | 0.210323E+09 | 0.139547E+10 |
February | 0.391400E+09 | 0.210683E+09 | 0.180716E+09 | 0.356118E+09 | 0.102292E+10 |
March | 0.545088E+09 | 0.248562E+09 | 0.296526E+09 | 0.611920E+09 | 0.693986E+09 |
April | 0.637619E+09 | 0.290922E+09 | 0.346696E+09 | 0.915000E+09 | 0.518409E+09 |
May | 0.721816E+09 | 0.305138E+09 | 0.416679E+09 | 0.118676E+10 | 0.355665E+09 |
June | 0.722535E+09 | 0.302538E+09 | 0.419996E+09 | 0.138502E+10 | 0.209026E+09 |
July | 0.727645E+09 | 0.305143E+09 | 0.422502E+09 | 0.146026E+10 | 0.149833E+09 |
August | 0.666928E+09 | 0.264422E+09 | 0.402506E+09 | 0.136049E+10 | 0.123740E+09 |
September | 0.528901E+09 | 0.233574E+09 | 0.295328E+09 | 0.896789E+09 | 0.303042E+09 |
October | 0.467613E+09 | 0.243380E+09 | 0.224233E+09 | 0.601405E+09 | 0.659412E+09 |
November | 0.360540E+09 | 0.162696E+09 | 0.197844E+09 | 0.325090E+09 | 0.858847E+09 |
December | 0.323406E+09 | 0.147325E+09 | 0.176081E+09 | 0.205735E+09 | 0.113751E+10 |
Annual Sum or Average | 0.643893E+10 | 0.287175E+10 | 0.356719E+10 | 0.951491E+10 | 0.742786E+10 |
Minimum of Months | 0.323406E+09 | 0.147325E+09 | 0.176081E+09 | 0.205735E+09 | 0.123740E+09 |
Maximum of Months | 0.727645E+09 | 0.305143E+09 | 0.422502E+09 | 0.146026E+10 | 0.139547E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114544E+10 | 0.795192E+09 | 0.350247E+09 | 0.128578E+10 | 0.174102E+10 |
February | 0.964730E+09 | 0.643473E+09 | 0.321257E+09 | 0.118889E+10 | 0.133773E+10 |
March | 0.978821E+09 | 0.514444E+09 | 0.464377E+09 | 0.135020E+10 | 0.984764E+09 |
April | 0.714514E+09 | 0.240301E+09 | 0.474213E+09 | 0.111109E+10 | 0.776280E+09 |
May | 0.593102E+09 | 74328851.72 | 0.518773E+09 | 0.989275E+09 | 0.536971E+09 |
June | 0.526451E+09 | 30528923.97 | 0.495922E+09 | 0.108790E+10 | 0.316377E+09 |
July | 0.545781E+09 | 38056826.98 | 0.507724E+09 | 0.120362E+10 | 0.221264E+09 |
August | 0.658336E+09 | 0.125596E+09 | 0.532740E+09 | 0.146749E+10 | 0.180077E+09 |
September | 0.718740E+09 | 0.280857E+09 | 0.437883E+09 | 0.130585E+10 | 0.437180E+09 |
October | 0.104054E+10 | 0.672721E+09 | 0.367816E+09 | 0.160181E+10 | 0.917981E+09 |
November | 0.109826E+10 | 0.732413E+09 | 0.365843E+09 | 0.149626E+10 | 0.115666E+10 |
December | 0.113713E+10 | 0.799362E+09 | 0.337767E+09 | 0.139317E+10 | 0.146134E+10 |
Annual Sum or Average | 0.101218E+11 | 0.494727E+10 | 0.517456E+10 | 0.154813E+11 | 0.100677E+11 |
Minimum of Months | 0.526451E+09 | 30528923.97 | 0.321257E+09 | 0.989275E+09 | 0.180077E+09 |
Maximum of Months | 0.114544E+10 | 0.799362E+09 | 0.532740E+09 | 0.160181E+10 | 0.174102E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353943E+09 | 0.164644E+09 | 0.189299E+09 | 0.252009E+09 | 0.142317E+10 |
February | 0.366116E+09 | 0.171588E+09 | 0.194528E+09 | 0.354345E+09 | 0.107224E+10 |
March | 0.594471E+09 | 0.286592E+09 | 0.307879E+09 | 0.743123E+09 | 0.736003E+09 |
April | 0.648232E+09 | 0.296331E+09 | 0.351902E+09 | 0.965476E+09 | 0.548544E+09 |
May | 0.674113E+09 | 0.255745E+09 | 0.418367E+09 | 0.112674E+10 | 0.381005E+09 |
June | 0.685415E+09 | 0.263826E+09 | 0.421589E+09 | 0.133573E+10 | 0.226703E+09 |
July | 0.666673E+09 | 0.246508E+09 | 0.420165E+09 | 0.136025E+10 | 0.158879E+09 |
August | 0.654786E+09 | 0.244784E+09 | 0.410002E+09 | 0.134137E+10 | 0.129547E+09 |
September | 0.517572E+09 | 0.216230E+09 | 0.301341E+09 | 0.886267E+09 | 0.315505E+09 |
October | 0.476012E+09 | 0.247458E+09 | 0.228555E+09 | 0.659418E+09 | 0.697833E+09 |
November | 0.366028E+09 | 0.163739E+09 | 0.202289E+09 | 0.393520E+09 | 0.916920E+09 |
December | 0.313359E+09 | 0.137366E+09 | 0.175993E+09 | 0.247642E+09 | 0.119911E+10 |
Annual Sum or Average | 0.631672E+10 | 0.269481E+10 | 0.362191E+10 | 0.966588E+10 | 0.780545E+10 |
Minimum of Months | 0.313359E+09 | 0.137366E+09 | 0.175993E+09 | 0.247642E+09 | 0.129547E+09 |
Maximum of Months | 0.685415E+09 | 0.296331E+09 | 0.421589E+09 | 0.136025E+10 | 0.142317E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 554.83 | 1604.54 | 688.78 | 417.12 | 271.66 | 0.00 | 0.00 |
February | 708.17 | 1342.08 | 711.91 | 424.00 | 287.91 | 0.00 | 0.00 |
March | 967.51 | 859.06 | 790.91 | 391.87 | 399.04 | 0.00 | 0.00 |
April | 1116.47 | 673.44 | 771.75 | 319.27 | 452.47 | 0.00 | 0.00 |
May | 1214.25 | 456.66 | 742.62 | 237.16 | 505.46 | 0.00 | 0.00 |
June | 1457.63 | 278.41 | 746.30 | 230.28 | 516.01 | 0.00 | 0.00 |
July | 1496.42 | 191.85 | 724.35 | 220.17 | 504.18 | 0.00 | 0.00 |
August | 1552.68 | 157.82 | 739.27 | 237.01 | 502.26 | 0.00 | 0.00 |
September | 1181.85 | 397.45 | 681.02 | 281.89 | 399.13 | 0.00 | 0.00 |
October | 1039.95 | 820.63 | 740.80 | 434.42 | 306.38 | 0.00 | 0.00 |
November | 814.42 | 1091.25 | 704.02 | 408.51 | 295.52 | 0.00 | 0.00 |
December | 619.36 | 1347.94 | 662.30 | 404.74 | 257.56 | 0.00 | 0.00 |
Annual Sum or Average | 1062.29 | 765.45 | 725.44 | 333.39 | 392.05 | 0.00 | 0.00 |
Minimum of Months | 554.83 | 157.82 | 662.30 | 220.17 | 257.56 | 0.00 | 0.00 |
Maximum of Months | 1552.68 | 1604.54 | 790.91 | 434.42 | 516.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148605E+10 | 0.429760E+10 | 0.184483E+10 | 0.111720E+10 | 0.727623E+09 | 0.00 | 0.00 |
February | 0.171321E+10 | 0.324675E+10 | 0.172225E+10 | 0.102574E+10 | 0.696501E+09 | 0.00 | 0.00 |
March | 0.259139E+10 | 0.230090E+10 | 0.211838E+10 | 0.104960E+10 | 0.106878E+10 | 0.00 | 0.00 |
April | 0.289389E+10 | 0.174556E+10 | 0.200036E+10 | 0.827554E+09 | 0.117281E+10 | 0.00 | 0.00 |
May | 0.325225E+10 | 0.122312E+10 | 0.198903E+10 | 0.635212E+09 | 0.135382E+10 | 0.00 | 0.00 |
June | 0.377819E+10 | 0.721642E+09 | 0.193440E+10 | 0.596893E+09 | 0.133751E+10 | 0.00 | 0.00 |
July | 0.400801E+10 | 0.513856E+09 | 0.194010E+10 | 0.589708E+09 | 0.135039E+10 | 0.00 | 0.00 |
August | 0.415870E+10 | 0.422716E+09 | 0.198005E+10 | 0.634802E+09 | 0.134525E+10 | 0.00 | 0.00 |
September | 0.306336E+10 | 0.103018E+10 | 0.176521E+10 | 0.730662E+09 | 0.103455E+10 | 0.00 | 0.00 |
October | 0.278539E+10 | 0.219798E+10 | 0.198416E+10 | 0.116356E+10 | 0.820604E+09 | 0.00 | 0.00 |
November | 0.211097E+10 | 0.282852E+10 | 0.182482E+10 | 0.105885E+10 | 0.765975E+09 | 0.00 | 0.00 |
December | 0.165890E+10 | 0.361031E+10 | 0.177389E+10 | 0.108405E+10 | 0.689841E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335003E+11 | 0.241392E+11 | 0.228775E+11 | 0.105138E+11 | 0.123637E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148605E+10 | 0.422716E+09 | 0.172225E+10 | 0.589708E+09 | 0.689841E+09 | 0.00 | 0.00 |
Maximum of Months | 0.415870E+10 | 0.429760E+10 | 0.211838E+10 | 0.116356E+10 | 0.135382E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639541E+10 | -0.622515E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -170261371.0 | 81.22 | 0.00 | 0.00 |
February | 0.578459E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -150314407.0 | 81.22 | 0.00 | 0.00 |
March | 0.645515E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161291025.2 | 81.22 | 0.00 | 0.00 |
April | 0.619682E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153355093.6 | 81.22 | 0.00 | 0.00 |
May | 0.641646E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156280958.8 | 81.21 | 0.00 | 0.00 |
June | 0.623716E+10 | -0.608655E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150611617.7 | 81.22 | 0.00 | 0.00 |
July | 0.637242E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155328821.6 | 81.21 | 0.00 | 0.00 |
August | 0.645048E+10 | -0.629519E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155285512.7 | 81.21 | 0.00 | 0.00 |
September | 0.619548E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150665395.9 | 81.21 | 0.00 | 0.00 |
October | 0.638282E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159008404.7 | 81.22 | 0.00 | 0.00 |
November | 0.618170E+10 | -0.602460E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157102792.4 | 81.22 | 0.00 | 0.00 |
December | 0.638447E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167383122.3 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754530E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.188689E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.578459E+10 | -0.629519E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -170261371.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645515E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150314407.0 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.230156E+11 | -0.220308E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -984819805.2 | 58.99 | 0.00 | 0.00 |
February | 0.208374E+11 | -0.199797E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -857767643.1 | 58.99 | 0.00 | 0.00 |
March | 0.224721E+11 | -0.215694E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -902688201.1 | 58.98 | 0.00 | 0.00 |
April | 0.202327E+11 | -0.193840E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -848651074.3 | 58.99 | 0.00 | 0.00 |
May | 0.193057E+11 | -0.184488E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -856897402.6 | 58.99 | 0.00 | 0.00 |
June | 0.173403E+11 | -0.165169E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -823415782.4 | 58.98 | 0.00 | 0.00 |
July | 0.168480E+11 | -0.159998E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -848173823.6 | 58.99 | 0.00 | 0.00 |
August | 0.169878E+11 | -0.161401E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -847641018.1 | 58.98 | 0.00 | 0.00 |
September | 0.170701E+11 | -0.162462E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -823892207.2 | 58.98 | 0.00 | 0.00 |
October | 0.189935E+11 | -0.181117E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -881788463.7 | 58.99 | 0.00 | 0.00 |
November | 0.199853E+11 | -0.191024E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -882947699.0 | 58.99 | 0.00 | 0.00 |
December | 0.220985E+11 | -0.211400E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -958425798.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.235187E+12 | -0.224670E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.105171E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.168480E+11 | -0.220308E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -984819805.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.230156E+11 | -0.159998E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -823415782.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.74 | 0.73 | 01-JAN-08:50 | 1290.47 | 23.57 | 111.17 | 272.67 | 1287.26 | 22.79 | 94.17 | 272.33 |
February | 263.00 | 0.75 | 0.73 | 01-FEB-10:09 | 976.41 | 20.55 | 54.67 | 246.00 | 1089.58 | 20.66 | 62.67 | 245.83 |
March | 351.67 | 0.74 | 0.73 | 01-MAR-08:20 | 1096.36 | 18.45 | 31.17 | 328.00 | 1163.57 | 19.52 | 60.00 | 327.17 |
April | 369.33 | 0.74 | 0.73 | 01-APR-07:00 | 1159.83 | 17.72 | 2.50 | 344.50 | 1013.07 | 17.81 | 2.50 | 339.67 |
May | 407.00 | 0.74 | 0.73 | 01-MAY-06:00 | 1145.49 | 17.80 | 0.17 | 376.17 | 1134.55 | 17.88 | 0.33 | 376.83 |
June | 411.67 | 0.74 | 0.73 | 01-JUN-06:40 | 932.79 | 18.58 | 21.50 | 378.83 | 1134.68 | 17.65 | 0.00 | 377.50 |
July | 411.00 | 0.74 | 0.73 | 01-JUL-06:19 | 927.11 | 18.50 | 15.67 | 380.00 | 1133.95 | 17.76 | 0.00 | 380.83 |
August | 390.50 | 0.74 | 0.73 | 01-AUG-06:40 | 1212.95 | 18.35 | 9.33 | 364.33 | 1095.11 | 18.45 | 11.33 | 362.83 |
September | 298.50 | 0.75 | 0.73 | 01-SEP-07:10 | 1088.13 | 18.08 | 15.83 | 319.50 | 1041.30 | 18.32 | 23.50 | 317.83 |
October | 293.50 | 0.74 | 0.73 | 01-OCT-07:49 | 1270.38 | 20.46 | 68.50 | 294.67 | 1161.71 | 20.58 | 64.67 | 292.83 |
November | 299.00 | 0.75 | 0.73 | 01-NOV-07:00 | 1068.58 | 21.98 | 83.83 | 272.83 | 1119.87 | 23.66 | 105.00 | 274.33 |
December | 285.17 | 0.74 | 0.73 | 01-DEC-07:00 | 1770.86 | 24.78 | 129.17 | 266.33 | 1740.76 | 25.33 | 139.17 | 265.50 |
Annual Sum or Average | 4071.00 | 0.74 | 1147.85 | 19.65 | 543.50 | 3843.83 | 1166.71 | 19.74 | 563.33 | 3833.50 | ||
Minimum of Months | 263.00 | 0.74 | 0.73 | 927.11 | 17.72 | 0.17 | 246.00 | 1013.07 | 17.65 | 0.00 | 245.83 | |
Maximum of Months | 411.67 | 0.75 | 0.73 | 1770.86 | 24.78 | 129.17 | 380.00 | 1740.76 | 25.33 | 139.17 | 380.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412663E+11 | 129719.19 | 12-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248490E+11 | 129719.19 | 03-FEB-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.673136E+10 | 38023.97 | 19-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.245185E+10 | 66149.94 | 06-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225466E+09 | 14181.53 | 10-MAY-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17151440.52 | 2442.32 | 10-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 578418.66 | 301.81 | 29-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262388E+10 | 29958.18 | 26-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.923521E+10 | 78224.56 | 22-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224663E+11 | 125585.21 | 18-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412663E+11 | 129719.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160534E+11 | 34010.51 | 14-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893753E+10 | 47325.54 | 12-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.825719E+09 | 17415.91 | 19-MAR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.458138E+09 | 18795.08 | 06-APR-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149147E+09 | 18415.13 | 26-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188685E+10 | 31674.71 | 22-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.613163E+10 | 29735.12 | 04-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160534E+11 | 47325.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102486E+09 | 77682776.72 | 10080.30 | 31-JAN-14:00 | 7928.56 | 0.00 |
February | 0.00 | 0.00 | 0.169467E+10 | 0.161763E+10 | 24296.49 | 28-FEB-14:00 | 22921.67 | 0.00 |
March | 0.00 | 0.00 | 0.750634E+10 | 0.553724E+10 | 96504.03 | 12-MAR-01:51 | 59227.86 | 0.00 |
April | 0.00 | 0.00 | 0.191992E+11 | 0.145140E+11 | 100819.53 | 03-APR-00:31 | 50917.69 | 0.00 |
May | 0.00 | 0.00 | 0.406950E+11 | 0.270518E+11 | 101090.51 | 26-MAY-00:42 | 44482.70 | 0.00 |
June | 0.00 | 0.00 | 0.751083E+11 | 0.464097E+11 | 104141.41 | 23-JUN-00:09 | 40596.22 | 0.00 |
July | 0.00 | 0.00 | 0.957633E+11 | 0.540089E+11 | 104662.51 | 28-JUL-00:09 | 38548.40 | 0.00 |
August | 0.00 | 0.00 | 0.107353E+12 | 0.575991E+11 | 102652.72 | 25-AUG-00:42 | 48593.85 | 0.00 |
September | 0.00 | 0.00 | 0.599767E+11 | 0.343831E+11 | 100330.90 | 02-SEP-00:42 | 48183.78 | 0.00 |
October | 0.00 | 0.00 | 0.195977E+11 | 0.119911E+11 | 103277.99 | 02-OCT-00:42 | 41060.36 | 0.00 |
November | 0.00 | 0.00 | 0.453576E+10 | 0.300521E+10 | 48196.67 | 04-NOV-03:11 | 25324.81 | 0.00 |
December | 0.00 | 0.00 | 0.857842E+09 | 0.538137E+09 | 48196.67 | 13-DEC-04:11 | 27239.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.432390E+12 | 0.256734E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.102486E+09 | 77682776.72 | 10080.30 | 7928.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107353E+12 | 0.575991E+11 | 104662.51 | 59227.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.454365E+09 | 0.285440E+09 | 40786.38 | 20-JAN-05:01 | 19211.78 | 0.00 |
February | 0.00 | 0.00 | 0.202099E+10 | 0.178196E+10 | 40786.38 | 17-FEB-05:01 | 21549.42 | 0.00 |
March | 0.00 | 0.00 | 0.706339E+10 | 0.518301E+10 | 40786.38 | 29-MAR-01:22 | 22245.41 | 0.00 |
April | 0.00 | 0.00 | 0.160625E+11 | 0.117574E+11 | 42289.28 | 03-APR-00:42 | 20256.79 | 0.00 |
May | 0.00 | 0.00 | 0.322581E+11 | 0.209167E+11 | 44079.61 | 31-MAY-00:03 | 17827.08 | 0.00 |
June | 0.00 | 0.00 | 0.555323E+11 | 0.340725E+11 | 45316.35 | 18-JUN-10:58 | 21185.11 | 0.00 |
July | 0.00 | 0.00 | 0.716556E+11 | 0.395568E+11 | 45316.35 | 25-JUL-11:00 | 24900.46 | 0.00 |
August | 0.00 | 0.00 | 0.794290E+11 | 0.413341E+11 | 45316.35 | 04-AUG-10:53 | 23469.54 | 0.00 |
September | 0.00 | 0.00 | 0.472693E+11 | 0.259398E+11 | 45316.35 | 07-SEP-10:40 | 25079.69 | 0.00 |
October | 0.00 | 0.00 | 0.174343E+11 | 0.101996E+11 | 45316.35 | 19-OCT-00:03 | 13987.52 | 0.00 |
November | 0.00 | 0.00 | 0.576318E+10 | 0.368862E+10 | 40786.38 | 04-NOV-00:42 | 19911.82 | 0.00 |
December | 0.00 | 0.00 | 0.125840E+10 | 0.721475E+09 | 40786.38 | 13-DEC-01:42 | 21703.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.336201E+12 | 0.195437E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.454365E+09 | 0.285440E+09 | 40786.38 | 13987.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.794290E+11 | 0.413341E+11 | 45316.35 | 25079.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 8685.88 | 16608.22 | 30-JAN-19:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 8719.52 | 16606.85 | 03-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 8513.89 | 16352.26 | 01-MAR-19:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7940.51 | 15479.41 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 7351.28 | 14470.33 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6836.81 | 13292.50 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 6439.43 | 12423.83 | 03-JUL-18:45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 6491.65 | 12342.15 | 30-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 6732.49 | 13069.44 | 29-SEP-18:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7225.73 | 14300.11 | 31-OCT-18:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7832.24 | 15353.82 | 30-NOV-20:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 8354.21 | 16199.19 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 7587.21 | ||||
Minimum of Months | 0.00 | 0.00 | 6439.43 | 12342.15 | ||
Maximum of Months | 0.00 | 0.00 | 8719.52 | 16608.22 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.458110E+10 | 0.57 | 1983.06 | 01-JAN-00:01 | 0.66 |
February | 0.430963E+10 | 0.59 | 1983.06 | 01-FEB-00:03 | 0.66 |
March | 0.502408E+10 | 0.62 | 1983.06 | 01-MAR-00:03 | 0.66 |
April | 0.489101E+10 | 0.62 | 1983.06 | 01-APR-00:09 | 0.66 |
May | 0.507803E+10 | 0.62 | 1983.06 | 01-MAY-00:05 | 0.65 |
June | 0.491836E+10 | 0.62 | 1983.06 | 01-JUN-00:03 | 0.65 |
July | 0.508358E+10 | 0.62 | 1983.06 | 01-JUL-00:03 | 0.65 |
August | 0.508489E+10 | 0.62 | 1983.06 | 01-AUG-00:03 | 0.65 |
September | 0.491796E+10 | 0.62 | 1983.06 | 01-SEP-00:03 | 0.65 |
October | 0.506824E+10 | 0.63 | 1983.06 | 01-OCT-00:04 | 0.65 |
November | 0.483000E+10 | 0.62 | 1983.06 | 01-NOV-00:20 | 0.66 |
December | 0.477845E+10 | 0.59 | 1983.06 | 01-DEC-00:01 | 0.66 |
Annual Sum or Average | 0.585653E+11 | 0.61 | |||
Minimum of Months | 0.430963E+10 | 0.57 | 1983.06 | 0.65 | |
Maximum of Months | 0.508489E+10 | 0.63 | 1983.06 | 0.66 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.731980E+10 | 0.85 | 6730.53 | 12-JAN-04:02 | 1.46 |
February | 0.622845E+10 | 0.81 | 6730.53 | 03-FEB-04:10 | 1.46 |
March | 0.622856E+10 | 0.75 | 3875.94 | 19-MAR-04:01 | 1.10 |
April | 0.590398E+10 | 0.75 | 4751.54 | 06-APR-04:04 | 1.23 |
May | 0.610459E+10 | 0.78 | 3427.46 | 30-MAY-18:00 | 1.01 |
June | 0.631805E+10 | 0.85 | 4780.30 | 23-JUN-11:52 | 1.22 |
July | 0.691996E+10 | 0.88 | 5458.02 | 07-JUL-12:00 | 1.30 |
August | 0.713397E+10 | 0.89 | 5619.71 | 12-AUG-00:05 | 1.32 |
September | 0.609305E+10 | 0.83 | 4769.76 | 17-SEP-00:05 | 1.22 |
October | 0.613095E+10 | 0.76 | 4470.95 | 19-OCT-00:05 | 1.18 |
November | 0.610884E+10 | 0.76 | 4260.90 | 21-NOV-05:01 | 1.16 |
December | 0.671613E+10 | 0.80 | 6516.04 | 18-DEC-04:03 | 1.46 |
Annual Sum or Average | 0.772063E+11 | 0.81 | |||
Minimum of Months | 0.590398E+10 | 0.75 | 3427.46 | 1.01 | |
Maximum of Months | 0.731980E+10 | 0.89 | 6730.53 | 1.46 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179569E+10 | 0.51 | 1781.48 | 20-JAN-05:01 | 0.91 |
February | 0.156656E+10 | 0.51 | 1781.48 | 17-FEB-05:01 | 0.91 |
March | 0.165741E+10 | 0.52 | 1781.48 | 09-MAR-05:01 | 0.91 |
April | 0.161968E+10 | 0.52 | 1781.48 | 11-APR-04:01 | 0.91 |
May | 0.187916E+10 | 0.55 | 1781.48 | 04-MAY-04:01 | 0.91 |
June | 0.237616E+10 | 0.63 | 1781.48 | 02-JUN-03:21 | 0.91 |
July | 0.284012E+10 | 0.67 | 1781.48 | 01-JUL-00:03 | 0.90 |
August | 0.304021E+10 | 0.70 | 1781.48 | 01-AUG-00:03 | 0.90 |
September | 0.214586E+10 | 0.60 | 1781.48 | 01-SEP-03:21 | 0.90 |
October | 0.176768E+10 | 0.53 | 1781.48 | 02-OCT-00:03 | 0.90 |
November | 0.160497E+10 | 0.52 | 1781.48 | 03-NOV-04:01 | 0.91 |
December | 0.168257E+10 | 0.51 | 1781.48 | 12-DEC-05:01 | 0.91 |
Annual Sum or Average | 0.239761E+11 | 0.56 | |||
Minimum of Months | 0.156656E+10 | 0.51 | 1781.48 | 0.90 | |
Maximum of Months | 0.304021E+10 | 0.70 | 1781.48 | 0.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 49.00 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 49.28 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 49.44 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 52.37 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.19 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 53.57 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 53.75 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.28 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.21 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 52.83 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.20 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 49.37 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 49.00 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.28 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 49.00 | 59.92 | 8685.88 | 16608.22 | 30-JAN-19:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.28 | 58.81 | 8719.52 | 16606.85 | 03-FEB-20:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.44 | 58.83 | 8513.89 | 16352.26 | 01-MAR-19:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.26 | 50.26 | 7940.51 | 15479.41 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 51.04 | 51.04 | 7351.28 | 14470.33 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.11 | 52.11 | 6836.81 | 13292.50 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.84 | 51.84 | 6439.43 | 12423.83 | 03-JUL-18:45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.56 | 52.56 | 6491.65 | 12342.15 | 30-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.25 | 52.25 | 6732.49 | 13069.44 | 29-SEP-18:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 50.08 | 50.08 | 7225.73 | 14300.11 | 31-OCT-18:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.92 | 50.92 | 7832.24 | 15353.82 | 30-NOV-20:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 49.37 | 59.16 | 8354.21 | 16199.19 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 7587.21 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.00 | 50.08 | 6439.43 | 12342.15 | ||
Maximum of Months | 0.00 | 0.00 | 52.56 | 59.92 | 8719.52 | 16608.22 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.735429E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.677635E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.852823E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116903E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.177407E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.267865E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.326414E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.356075E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.225473E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117691E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.753965E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.698992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195971E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.677635E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.356075E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.192885E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213978E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.353515E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.573905E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.977573E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.156276E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.197615E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.215697E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134076E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.610512E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.314712E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.202577E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104763E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.192885E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.215697E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.731980E+10 | 0.102486E+09 | 0.412663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.622845E+10 | 0.169467E+10 | 0.248490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622856E+10 | 0.749697E+10 | 0.673136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590398E+10 | 0.191897E+11 | 0.245185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.610459E+10 | 0.406352E+11 | 0.225466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.631805E+10 | 0.750085E+11 | 17151440.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.691996E+10 | 0.957324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713397E+10 | 0.107349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.609305E+10 | 0.599177E+11 | 578418.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.613095E+10 | 0.195740E+11 | 0.262388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610884E+10 | 0.453576E+10 | 0.923521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671613E+10 | 0.857842E+09 | 0.224663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.772063E+11 | 0.432094E+12 | 0.109867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.590398E+10 | 0.102486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.731980E+10 | 0.107349E+12 | 0.412663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.179569E+10 | 0.453325E+09 | 0.160534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156656E+10 | 0.201856E+10 | 0.893753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165741E+10 | 0.702333E+10 | 0.825719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161968E+10 | 0.160015E+11 | 0.458138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187916E+10 | 0.321496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.237616E+10 | 0.554574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.284012E+10 | 0.716513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.304021E+10 | 0.794281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214586E+10 | 0.472209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176768E+10 | 0.173998E+11 | 0.149147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160497E+10 | 0.574515E+10 | 0.188685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168257E+10 | 0.125147E+10 | 0.613163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239761E+11 | 0.335801E+12 | 0.344424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156656E+10 | 0.453325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.304021E+10 | 0.794281E+11 | 0.160534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.731980E+10 | 0.00 | 0.00 | 0.00 | 34483896.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.622845E+10 | 0.00 | 0.00 | 0.00 | 0.547903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622856E+10 | 0.00 | 0.00 | 0.00 | 0.229967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590398E+10 | 0.00 | 0.00 | 0.00 | 0.578631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.610459E+10 | 0.00 | 0.00 | 0.00 | 0.116362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.631805E+10 | 0.00 | 0.00 | 0.00 | 0.204685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.691996E+10 | 0.00 | 0.00 | 0.00 | 0.257215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713397E+10 | 0.00 | 0.00 | 0.00 | 0.284736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.609305E+10 | 0.00 | 0.00 | 0.00 | 0.164543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.613095E+10 | 0.00 | 0.00 | 0.00 | 0.563815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610884E+10 | 0.00 | 0.00 | 0.00 | 0.143081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671613E+10 | 0.00 | 0.00 | 0.00 | 0.273794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.772063E+11 | 0.00 | 0.00 | 0.00 | 0.118765E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.590398E+10 | 0.00 | 0.00 | 0.00 | 34483896.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.731980E+10 | 0.00 | 0.00 | 0.00 | 0.284736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.179569E+10 | 0.00 | 0.00 | 0.00 | 0.133160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156656E+10 | 0.00 | 0.00 | 0.00 | 0.573219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165741E+10 | 0.00 | 0.00 | 0.00 | 0.187774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161968E+10 | 0.00 | 0.00 | 0.00 | 0.411938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187916E+10 | 0.00 | 0.00 | 0.00 | 0.789658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.237616E+10 | 0.00 | 0.00 | 0.00 | 0.132515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.284012E+10 | 0.00 | 0.00 | 0.00 | 0.169214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.304021E+10 | 0.00 | 0.00 | 0.00 | 0.185295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214586E+10 | 0.00 | 0.00 | 0.00 | 0.112618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176768E+10 | 0.00 | 0.00 | 0.00 | 0.433744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160497E+10 | 0.00 | 0.00 | 0.00 | 0.154216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168257E+10 | 0.00 | 0.00 | 0.00 | 0.343192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239761E+11 | 0.00 | 0.00 | 0.00 | 0.807869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156656E+10 | 0.00 | 0.00 | 0.00 | 0.133160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.304021E+10 | 0.00 | 0.00 | 0.00 | 0.185295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.485256E+11 | 0.00 | 0.00 | 2347432.92 | 0.00 | 0.178118E+11 | 0.254249E+10 | 0.00 | 3.58 |
February | 0.354795E+11 | 0.00 | 0.00 | 13517822.02 | 0.00 | 0.101107E+11 | 0.667901E+10 | 0.00 | 3.71 |
March | 0.264652E+11 | 0.175547E+09 | 0.00 | 37026140.18 | 0.00 | 0.162397E+09 | 0.129965E+11 | 0.00 | 3.91 |
April | 0.146765E+11 | 0.626145E+09 | 0.00 | 67503801.55 | 0.00 | 0.137922E+09 | 0.120797E+11 | 0.00 | 4.07 |
May | 0.506898E+10 | 0.522826E+10 | 0.00 | 60259254.66 | 836986.70 | 0.00 | 0.106246E+11 | 0.00 | 4.16 |
June | 0.118013E+10 | 0.214217E+11 | 0.00 | 26998796.50 | 20571637.03 | 0.00 | 0.378795E+10 | 0.00 | 3.99 |
July | 89529862.61 | 0.336407E+11 | 0.00 | 7477451.47 | 31323652.67 | 0.00 | 0.210498E+10 | 0.00 | 3.88 |
August | 0.00 | 0.403193E+11 | 0.00 | 2523888.46 | 48357600.67 | 0.00 | 0.511021E+09 | 0.00 | 3.84 |
September | 0.162146E+10 | 0.141063E+11 | 0.00 | 37265559.66 | 20571383.55 | 0.00 | 0.761374E+10 | 0.00 | 4.06 |
October | 0.179672E+11 | 0.252683E+10 | 0.00 | 47308232.73 | 236946.51 | 7210324.58 | 0.140570E+11 | 0.00 | 4.01 |
November | 0.289134E+11 | 32784197.13 | 0.00 | 27391708.46 | 0.00 | 0.104081E+10 | 0.134555E+11 | 0.00 | 3.87 |
December | 0.475100E+11 | 0.00 | 0.00 | 4847633.44 | 0.00 | 0.456548E+10 | 0.362124E+10 | 0.00 | 3.61 |
Annual Sum or Average | 0.227497E+12 | 0.118077E+12 | 0.00 | 0.334468E+09 | 0.121898E+09 | 0.338363E+11 | 0.900738E+11 | 0.00 | 3.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2347432.92 | 0.00 | 0.00 | 0.511021E+09 | 0.00 | 3.58 |
Maximum of Months | 0.485256E+11 | 0.403193E+11 | 0.00 | 67503801.55 | 48357600.67 | 0.178118E+11 | 0.140570E+11 | 0.00 | 4.16 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.541588E+11 | 0.00 | 0.00 | 7300768.79 | 0.149273E+09 | 5399819.48 | 0.593176E+10 | 0.00 | 8.08 |
February | 0.350380E+11 | 0.00 | 0.00 | 27014957.44 | 40384928.07 | 6497393.44 | 0.136884E+11 | 0.00 | 8.09 |
March | 0.168373E+11 | 0.00 | 0.00 | 65866595.30 | 0.00 | 0.00 | 0.253086E+11 | 0.00 | 8.17 |
April | 0.778734E+10 | 32184425.63 | 0.00 | 0.107359E+09 | 0.00 | 0.00 | 0.242523E+11 | 0.00 | 8.30 |
May | 0.168226E+10 | 0.309581E+10 | 0.00 | 0.118468E+09 | 0.00 | 0.00 | 0.175467E+11 | 0.00 | 8.77 |
June | 0.353519E+09 | 0.128311E+11 | 0.00 | 49150197.40 | 0.00 | 0.00 | 0.648729E+10 | 0.00 | 9.07 |
July | 2236646.32 | 0.216250E+11 | 0.00 | 13264943.57 | 0.00 | 0.00 | 0.163988E+10 | 0.00 | 9.25 |
August | 0.00 | 0.277967E+11 | 0.00 | 6231499.20 | 0.00 | 0.00 | 0.513002E+09 | 0.00 | 9.46 |
September | 0.138915E+09 | 0.920901E+10 | 0.00 | 61182837.33 | 0.00 | 0.00 | 0.101256E+11 | 0.00 | 8.98 |
October | 0.883355E+10 | 0.159754E+10 | 0.00 | 78776426.12 | 0.00 | 0.00 | 0.249426E+11 | 0.00 | 8.43 |
November | 0.197011E+11 | 0.00 | 0.00 | 52459223.23 | 21975194.78 | 2729111.91 | 0.236162E+11 | 0.00 | 8.14 |
December | 0.372827E+11 | 0.00 | 0.00 | 15116015.85 | 40797601.00 | 0.00 | 0.145360E+11 | 0.00 | 8.00 |
Annual Sum or Average | 0.181816E+12 | 0.761873E+11 | 0.00 | 0.602190E+09 | 0.252431E+09 | 14626324.83 | 0.168588E+12 | 0.00 | 8.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6231499.20 | 0.00 | 0.00 | 0.513002E+09 | 0.00 | 8.00 |
Maximum of Months | 0.541588E+11 | 0.277967E+11 | 0.00 | 0.118468E+09 | 0.149273E+09 | 6497393.44 | 0.253086E+11 | 0.00 | 9.46 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.565252E+11 | 0.178413E+11 | 0.216292E+12 | 0.228253E+09 | 0.317050E+11 |
February | 0.625996E+11 | 0.136866E+11 | 0.174244E+12 | 0.895527E+09 | 0.305526E+11 |
March | 0.995918E+11 | 0.115202E+11 | 0.152517E+12 | 0.204885E+10 | 0.439036E+11 |
April | 0.118153E+12 | 0.892194E+10 | 0.112657E+12 | 0.233929E+10 | 0.729028E+11 |
May | 0.131271E+12 | 0.606070E+10 | 0.611752E+11 | 0.216301E+10 | 0.122059E+12 |
June | 0.136929E+12 | 0.136617E+09 | -0.222189E+11 | 0.867771E+09 | 0.193041E+12 |
July | 0.127148E+12 | -0.258915E+10 | -0.716452E+11 | 0.465231E+09 | 0.239091E+12 |
August | 0.117095E+12 | -0.459431E+10 | -0.962351E+11 | 0.125439E+09 | 0.262516E+12 |
September | 0.862329E+11 | 0.650199E+09 | 0.545087E+10 | 0.140345E+10 | 0.160758E+12 |
October | 0.776967E+11 | 0.802531E+10 | 0.117368E+12 | 0.252812E+10 | 0.723364E+11 |
November | 0.514521E+11 | 0.108493E+11 | 0.159577E+12 | 0.190942E+10 | 0.365503E+11 |
December | 0.458028E+11 | 0.140299E+11 | 0.190926E+12 | 0.405879E+09 | 0.274318E+11 |
Annual Sum or Average | 0.111050E+13 | 0.845386E+11 | 0.100011E+13 | 0.153802E+11 | 0.129285E+13 |
Minimum of Months | 0.458028E+11 | -0.459431E+10 | -0.962351E+11 | 0.125439E+09 | 0.274318E+11 |
Maximum of Months | 0.136929E+12 | 0.178413E+11 | 0.216292E+12 | 0.252812E+10 | 0.262516E+12 |