Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:25:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2252.72 | 4407.14 | 4407.14 |
Net Site Energy | 2252.72 | 4407.14 | 4407.14 |
Total Source Energy | 4120.90 | 8061.96 | 8061.96 |
Net Source Energy | 4120.90 | 8061.96 | 8061.96 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 599.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 68.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 87.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.50 | 377.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 49.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 806.02 | 1446.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 599.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 68.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 87.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.50 | 377.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 599.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 68.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 49.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 87.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.50 | 377.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 49.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 147.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 452.37 | 1911.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 976.98 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1576.87 | 2830.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 147.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 452.37 | 1911.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 976.98 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1576.87 | 2830.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 806.023 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 806.023 | 100.00 |
Total On-Site and Utility Electric Sources | 806.023 | 100.00 |
Total Electricity End Uses | 806.023 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3998.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 7.7280 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.0598 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.7280 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.0598 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.0912 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-10:00 | 11-DEC-04:19 | - | - | - | - | - | - | - | - | - | - | 08-MAR-07:00 |
Heating | 0.00 | 169416.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22846.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24333.76 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4294.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3665.82 | 13931.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2560.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 59830.85 | 187873.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 169416.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22846.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 23306.26 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4294.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3665.82 | 13931.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1310.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1055.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 650.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 215.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1423.36 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 276.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.12 | 408.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 158.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2552.68 | 1568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1271.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 422.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 308.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 540.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.81 | 800.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 309.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4993.95 | 3068.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1271.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 422.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 308.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 540.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.81 | 800.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 309.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4993.95 | 3068.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.43 |
KITCHEN DIRECT AIR | 1.55 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.43 | 3.43 | 3.43 | 3.43 | 3.43 | 3.43 | 1.00 | 0.999992 | 3.43 |
PSZ-AC_2:2 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.00 | 1.00 | 1.55 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.43 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.55 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.43 | 3673.81 |
PSZ-AC_2:2_ADDAQ FAN | 1.55 | 1661.17 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.43 | 3.43 | 3.43 | 2.27 | 85257.47 | 135533.52 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.55 | 1.55 | 1.55 | 1.02 | 38550.34 | 89388.63 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.43 | 1.72 | 2.29 | 85257.47 | 42628.74 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.55 | 0.776211 | 1.03 | 38550.34 | 19275.17 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 135533.52 |
PSZ-AC_2:2 HEATING COIL | 89388.63 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 7.728 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 72.655 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.060 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1069.700 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2872.862 | 7.728 | 10.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2872.862 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1262.985 | 9.060 | 167.774 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1262.985 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.8145 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1372 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2338 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9937 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.210 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.201 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.29658941E-12 | 0.26287986E-14 | -0.96754960E-13 | 0.14534288E-15 |
34 | 6 | 0.28220461E-07 | 0.22806971E-09 | 0.64684832E-08 | -0.13284730E-12 |
35 | 5 | -0.18781637E-03 | 0.19571962E-05 | -0.96635164E-04 | 0.63958203E-08 |
36 | 4 | 0.28946386 | 0.95482371E-03 | 0.98718614E-01 | -0.33192652E-04 |
37 | 3 | -7.2131916 | 0.29641513E-01 | -2.3231458 | 0.28748621E-01 |
38 | 2 | 40.695896 | 0.10556174 | 15.200419 | -0.33138856 |
39 | 1 | -80.411495 | 0.47703793E-01 | -29.083695 | 1.0757574 |
40 | 0 | 46.824340 | 0.96099221E-03 | 16.292624 | |
41 | 7 | -0.30956576E-08 | -0.21303207E-14 | 0.16211864E-14 | -0.47943075E-16 |
42 | 6 | 0.39621431E-05 | 0.26242558E-08 | 0.31947295E-02 | -0.26800069E-04 |
43 | 5 | -0.27788690E-03 | 0.15515089E-05 | -0.22400076 | 0.19585881E-02 |
44 | 4 | 0.63462498E-02 | 0.70567942E-04 | 4.8341454 | -0.45309197E-01 |
45 | 3 | -0.55586032E-01 | 0.56073102E-03 | -38.047399 | 0.39894095 |
46 | 2 | 0.19717555 | 0.93224475E-03 | 116.53452 | -1.4186157 |
47 | 1 | -0.28446589 | 0.28372391E-03 | -143.93707 | 2.0495292 |
48 | 0 | 0.13865977 | 0.68942715E-05 | 60.838472 | |
49 | 7 | -0.17992014E-08 | -0.42643710E-15 | 0.60732754E-14 | -0.80508795E-16 |
50 | 6 | 0.65450224E-05 | 0.44811019E-08 | 0.31871723E-02 | -0.26736672E-04 |
51 | 5 | -0.47085772E-03 | 0.26548585E-05 | -0.22357125 | 0.19547969E-02 |
52 | 4 | 0.10832139E-01 | 0.12085242E-03 | 4.8269919 | -0.45240433E-01 |
53 | 3 | -0.95125865E-01 | 0.96112441E-03 | -38.006990 | 0.39849429 |
54 | 2 | 0.33777835 | 0.15989493E-02 | 116.45587 | -1.4175637 |
55 | 1 | -0.48753632 | 0.48725992E-03 | -143.89078 | 2.0487682 |
56 | 0 | 0.23769862 | 0.11769722E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | 38 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 39 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
3 | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | 40 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
4 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 41 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7288E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7275E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6237E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5096E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4695E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4892E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1312E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0458E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.2031E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.0586E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.1162E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.9413E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2397E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1847E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0714E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0714E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5606E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5149E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2963E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3494E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2711E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2922E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0458E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1312E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 38336.78381 | 46004.14057 | 2.86108 | 3.43329 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 10061.20591 | 12073.44709 | 0.44234 | 1.33138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | -16.30000 | 9.24091E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20439.38616 | 24527.26339 | 1.29369 | 1.55242 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 29.46300 | 1.33655E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 1484.47828 | 1781.37393 | 5.90450E-002 | 1.21700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -16.30000 | 9.24091E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 55210.97 | 3.43332 | 3.43332 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 88420.91 | 1.33138 | 1.33138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 29125.14 | 1.55242 | 1.55242 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 80824.88 | 1.21700 | 1.21700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.43329 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.55242 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.43329 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.43329 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.43329 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.43329 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.43332 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.43332 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99999 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.55242 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55242 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.55242 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.55242 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.55242 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.55242 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.43332 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.55242 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.43332 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.43332 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3673.81298 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.43332 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.43332 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.43332 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.26599 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.43332 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.71666 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.28888 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 85257.47000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 42628.73500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 85257.47000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 135533.51637 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 135533.51637 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.55242 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.55242 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1661.16516 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.55242 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.55242 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.55242 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02460 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.55242 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77621 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03495 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38550.34000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19275.17000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38550.34000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89388.62855 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 89388.62855 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 82817.2 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 37446.9 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.815 | 0.726 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | N/A | 2.153 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.815 | 0.726 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | N/A | 2.153 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.815 | 0.726 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | N/A | 2.153 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.137 | 0.133 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.815 | 0.726 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.815 | 0.726 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.815 | 0.726 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.234 | 0.221 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.7060045224E-002 | 0.4237810013 | Pass | Pass | 0.1091646441 | 0.2961642865 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 8.9990026831E-002 | 0.5232049034 | Pass | Pass | 2.7357844474E-002 | 8.6197136758E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1288559380 | 0.1202268997 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 981.74 | 122.05 | 2029.40 | 7.19 | 651.62 | 3792.01 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.726 | 0.815 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.726 | 0.815 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.726 | 0.815 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.134 | 0.137 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.726 | 0.815 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.726 | 0.815 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.726 | 0.815 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.225 | 0.234 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.153 | 0.381 | 0.420 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.153 | 0.381 | 0.420 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.153 | 0.381 | 0.420 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.153 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.153 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.7280 | 371.75 | 2872.86 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.50 | 0.0000 | Y | 32.62 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.0598 | 139.41 | 1262.99 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.59 | 0.0000 | Y | 17.21 |
Interior Lighting Total | 8.0912 | 511.15 | 4135.85 | 49.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 49.04 | 49.04 | 1.95 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.67 | 62.85 | 23.63 | |
Exterior Lighting Total | 2213.72 | 25.57 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 85257.47 | 59772.31 | 25485.16 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38550.34 | 27026.87 | 11523.47 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 82817.2 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 37446.9 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 135533.52 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 89388.63 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 3.43 | 3673.81 | 1070.05 | 1.00 | 1.25 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.55 | 1661.17 | 1070.05 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 38336.78 | 46004.14 | 123.75 | 2.861 | 3.433 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.01072 | 30.21 | 0.01337 | 1.331 | 0.00 |
KITCHEN | 20439.39 | 24527.26 | 175.94 | 1.294 | 1.552 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01044 | 29.46 | 0.01337 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 10061.21 | 12073.45 | 32.48 | 0.442 | 1.331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00755 | -16.30 | 0.00092 | 1.331 | 0.00 |
KITCHEN | 1484.48 | 1781.37 | 12.78 | 0.059 | 1.217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00546 | -16.30 | 0.00092 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.43 | 3.43 | 1.33 | 1.33 | 3.4333 | 3.4333 | 3.4333 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.55 | 1.55 | 1.22 | 1.22 | 1.5524 | 1.5524 | 1.5524 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 85257.470 | 59772.307 | 3.433320 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 42628.74 | 27803.43 | 2.288880 | 26.43 | 19.53 | 0.01174767 | 11.91 | 11.51 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 58.1672 | 23.99 | 0.01072201 | 56.1150 | 38333.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 135533.516 | 135533.516 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 135533.52 | 135533.52 | 3.433318 | 6.54 | 5.08 | 0.00497867 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 38.7782 | 21.00 | 0.00754685 | 47.6003 | 10059.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38550.340 | 27026.872 | 1.552420 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19275.17 | 12003.11 | 1.034947 | 28.70 | 20.93 | 0.01273396 | 11.91 | 11.51 | 0.00850000 | 29.46 | 0.01336548 | 21.59 | 117.5908 | 25.99 | 0.01044265 | 48.5337 | 20439.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 89388.629 | 89388.629 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 | 89388.63 | 89388.63 | 1.552422 | -8.81 | -8.81 | 0.00193474 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 78.3937 | 19.00 | 0.00560168 | 40.1176 | 1271.19 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 85257.470 | 59772.307 | 3.433320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6783 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.433318 | 4.03045938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 42628.74 | 27803.43 | 1.0000 | 2.68697417 | 2.288880 | 26.43 | 19.53 | 0.01174767 | 56517.6 | 11.91 | 11.51 | 0.00850000 | 33416.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42628.74 | 30.30 | 0.01336696 | 21.83 | 1.33137743 | 58.1672 | 23.98 | 0.01072201 | 23.99 | 0.01072201 | 56.1150 | 38333.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 135533.516 | 135533.516 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.433318 | 4.03045938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 135533.52 | 135533.52 | 1.0000 | 4.03045938 | 3.433318 | 6.54 | 5.08 | 0.00497867 | 19078.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 135533.52 | -16.30 | 0.00092409 | -16.30 | 1.33137743 | 38.7782 | 21.00 | 0.00754685 | 21.00 | 0.00754685 | 47.6003 | 10059.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38550.340 | 27026.872 | 1.552420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.5118 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.552422 | 1.82242774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19275.17 | 12003.11 | 1.0000 | 1.21495009 | 1.034947 | 28.70 | 20.93 | 0.01273396 | 61369.5 | 11.91 | 11.51 | 0.00850000 | 33417.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19275.17 | 29.46 | 0.01336548 | 21.59 | 1.21700195 | 117.5908 | 25.95 | 0.01044265 | 25.99 | 0.01044265 | 48.5337 | 20439.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89388.629 | 89388.629 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.552422 | 1.82242774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 | Sensible | 89388.63 | 89388.63 | 1.0000 | 1.82242774 | 1.552422 | -8.81 | -8.81 | 0.00193474 | -4047.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89388.63 | -16.30 | 0.00092409 | -16.30 | 1.21700195 | 78.3937 | 18.36 | 0.00560168 | 19.00 | 0.00560168 | 40.1176 | 1271.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.43 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3301.00 | 5487.67 | 1884.67 |
KITCHEN | 4753.67 | 6117.17 | 3843.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4908.17 | 7106.33 | 3998.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 17.00 | 4.50 | 0.00 | 0.00 |
KITCHEN | 0.00 | 99.67 | 0.00 | 0.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 17.00 | 102.67 | 0.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.443 | 0.596 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 9.177 | 0.044 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.046 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 8.413 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.14 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.17 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.32 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36433515.57 | 0.00 | 36433515.57 | 4914758.77 | 41348274.34 | 41986318.57 | 1451.78 | 5853.67 | 1454.55 | 239.14 |
KITCHEN | 28429699.21 | 0.00 | 28429699.21 | 215095.64 | 28644794.85 | 38379373.44 | 8324.03 | 386.19 | 49.78 | 452.37 |
Total Facility | 64863214.78 | 0.00 | 64863214.78 | 5129854.41 | 69993069.19 | 80365692.01 | 8328.33 | 5866.00 | 1484.71 | 547.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3802 | 0.0000 | 1.3802 | 0.1850 | 1.5652 | 1.3314 | 0.00 | 5747.83 | 1439.17 |
KITCHEN | 1.0681 | 0.0000 | 1.0681 | 0.0052 | 1.0732 | 1.2170 | 6763.69 | 379.68 | 43.63 |
Total Facility | 2.4483 | 0.0000 | 2.4483 | 0.1901 | 2.6385 | 2.5484 | 6763.69 | 5759.99 | 1464.90 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50208707.39 | 0.00 | 50208707.39 | 41986318.57 | 1450.64 | 0.08 | 7309.27 | 239.13 |
PSZ-AC_2:2 | 39179049.54 | 0.00 | 39179049.54 | 38379373.44 | 1431.05 | 0.52 | 7328.42 | 452.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9021 | 0.0000 | 1.9021 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4719 | 0.0000 | 1.4719 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1433.39 | 146.39 | 5846.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 269.40 | 1105.04 | 6264.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.1866 | 2.0221 | 1.8352 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.5924 | 1.5505 | 1.4601 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
Electricity:Building | 506.20 | 2873.83 | 01-JAN-01:20 | 28589.25 | 02-JAN-11:10 |
Electricity:Zone:DINING | 157.73 | 560.03 | 01-JAN-01:20 | 8723.27 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 499.27 | 2737.55 | 01-JAN-01:20 | 26446.15 | 02-JAN-11:10 |
InteriorLights:Electricity | 49.83 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 32.62 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 49.83 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 49.83 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 32.62 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 49.83 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 348.47 | 2313.80 | 01-JAN-01:20 | 20370.03 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.33 | 2147.51 | 01-JAN-01:10 | 17341.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 49.95 | 852.62 | 11-DEC-23:30 | 3219.34 | 08-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 118.97 | 1033.36 | 29-JAN-01:10 | 6476.01 | 26-AUG-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 13.80 | 0.00 | 01-JAN-11:10 | 1511.70 | 28-JUL-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 29.22 | 765.08 | 11-DEC-06:00 | 1076.23 | 12-MAR-13:10 |
ElectricityPurchased:Facility | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
ElectricityPurchased:Plant | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
Cogeneration:ElectricityPurchased | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
General:Cogeneration:ElectricityPurchased | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
ElectricityNet:Plant | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
Cogeneration:ElectricityNet | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
General:Cogeneration:ElectricityNet | 806.02 | 4973.98 | 06-FEB-01:30 | 59830.85 | 20-JUL-11:00 |
Electricity:HVAC | 155.28 | 0.00 | 01-JAN-01:10 | 30826.76 | 27-JUN-13:00 |
Fans:Electricity | 87.17 | 0.00 | 01-JAN-01:10 | 4811.44 | 27-JUN-13:00 |
General:Fans:Electricity | 87.17 | 0.00 | 01-JAN-01:10 | 4811.44 | 27-JUN-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 68.11 | 0.00 | 01-JAN-00:10 | 26015.32 | 27-JUN-13:00 |
General:Cooling:Electricity | 68.11 | 0.00 | 01-JAN-00:10 | 26015.32 | 27-JUN-13:00 |
ExteriorLights:Electricity | 25.57 | 0.00 | 01-JAN-08:00 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.57 | 0.00 | 01-JAN-08:00 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.50 | 0.00 | 01-JAN-01:10 | 4742.11 | 07-MAR-19:50 |
Water Heater:WaterSystems:Electricity | 75.50 | 0.00 | 01-JAN-01:10 | 4742.11 | 07-MAR-19:50 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1446.70 | 2758.01 | 12-MAR-00:10 | 187873.91 | 11-DEC-04:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 599.66 | 0.00 | 01-JAN-01:10 | 169416.90 | 04-JAN-04:30 |
Heating:NaturalGas | 599.66 | 0.00 | 01-JAN-01:10 | 169416.90 | 04-JAN-04:30 |
General:Heating:NaturalGas | 599.66 | 0.00 | 01-JAN-01:10 | 169416.90 | 04-JAN-04:30 |
NaturalGas:Plant | 377.25 | 947.76 | 01-JAN-00:10 | 33529.10 | 17-FEB-19:20 |
WaterSystems:NaturalGas | 377.25 | 947.76 | 01-JAN-00:10 | 33529.10 | 17-FEB-19:20 |
Water Heater:WaterSystems:NaturalGas | 377.25 | 947.76 | 01-JAN-00:10 | 33529.10 | 17-FEB-19:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 06-APR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 08-MAR-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1740.08 | 2931.09 | 07-FEB-01:10 | 161084.40 | 20-JUL-19:00 |
EnergyTransfer:Building | 666.38 | 1465.54 | 07-FEB-01:10 | 46309.73 | 21-JUL-11:10 |
EnergyTransfer:Zone:KITCHEN | 413.65 | 1465.54 | 07-FEB-01:10 | 23753.73 | 28-NOV-12:00 |
Refrigeration:EnergyTransfer | 136.97 | 2621.04 | 06-MAR-23:10 | 7834.84 | 02-JUN-03:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.48 | 1310.52 | 06-MAR-23:10 | 3917.42 | 02-JUN-03:10 |
General:Refrigeration:EnergyTransfer | 68.48 | 1310.52 | 06-MAR-23:10 | 3917.42 | 02-JUN-03:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.48 | 1310.52 | 06-MAR-23:10 | 3917.42 | 02-JUN-03:10 |
EnergyTransfer:Plant | 336.97 | 1465.54 | 07-FEB-01:10 | 20773.29 | 15-MAR-18:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.03 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 56.45 | 1305.25 | 11-DEC-06:00 | 2238.70 | 12-MAR-13:10 |
EnergyTransfer:Zone:DINING | 252.73 | 0.00 | 01-JAN-01:10 | 30318.64 | 31-JAN-21:20 |
Heating:EnergyTransfer | 4.74 | 0.00 | 01-JAN-00:10 | 15935.06 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:DINING | 4.72 | 0.00 | 01-JAN-00:10 | 15935.06 | 13-FEB-04:10 |
General:Heating:EnergyTransfer | 4.74 | 0.00 | 01-JAN-00:10 | 15935.06 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:DINING | 4.72 | 0.00 | 01-JAN-00:10 | 15935.06 | 13-FEB-04:10 |
Cooling:EnergyTransfer | 593.15 | 0.00 | 01-JAN-01:10 | 43394.52 | 21-JUL-12:00 |
Cooling:EnergyTransfer:Zone:DINING | 248.01 | 0.00 | 01-JAN-01:10 | 26718.15 | 21-JUL-12:00 |
General:Cooling:EnergyTransfer | 593.15 | 0.00 | 01-JAN-01:10 | 43394.52 | 21-JUL-12:00 |
General:Cooling:EnergyTransfer:Zone:DINING | 248.01 | 0.00 | 01-JAN-01:10 | 26718.15 | 21-JUL-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1170.13 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1170.13 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 345.15 | 0.00 | 01-JAN-01:10 | 20471.96 | 28-NOV-12:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 345.15 | 0.00 | 01-JAN-01:10 | 20471.96 | 28-NOV-12:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 268.49 | 0.00 | 01-JAN-01:10 | 18450.46 | 15-FEB-19:30 |
PlantLoopHeatingDemand:Plant | 268.49 | 0.00 | 01-JAN-01:10 | 18450.46 | 15-FEB-19:30 |
WaterSystems:PlantLoopHeatingDemand | 268.49 | 0.00 | 01-JAN-01:10 | 18450.46 | 15-FEB-19:30 |
General:WaterSystems:PlantLoopHeatingDemand | 268.49 | 0.00 | 01-JAN-01:10 | 18450.46 | 15-FEB-19:30 |
EnergyTransfer:HVAC | 736.73 | 0.00 | 01-JAN-01:10 | 135533.52 | 04-JAN-04:30 |
HeatingCoils:EnergyTransfer | 479.73 | 0.00 | 01-JAN-01:10 | 135533.52 | 04-JAN-04:30 |
CoolingCoils:EnergyTransfer | 257.00 | 0.00 | 01-JAN-00:10 | 105709.57 | 27-JUN-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 268.49 | 0.00 | 01-JAN-01:10 | 18450.46 | 15-FEB-19:30 |
WaterUse:WaterSystems:EnergyTransfer | 268.49 | 0.00 | 01-JAN-01:10 | 18450.46 | 15-FEB-19:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 4.722 | -248.007 | 0.000 | 0.000 | 229.714 | 32.625 | 93.832 | 37.083 | 0.000 | 1.082 | 0.002 | 0.000 | -24.932 | 0.000 | -75.698 | -50.421 |
KITCHEN | 0.000 | 0.000 | 0.019 | -345.135 | 0.000 | 0.000 | 6.029 | 17.209 | 286.918 | 0.000 | 0.000 | 0.010 | 39.049 | 0.000 | 0.000 | 0.000 | -4.099 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.996 | 28.140 | 0.000 | 0.000 | 0.000 | -34.136 | -0.000 |
Total Facility | 0.000 | 0.000 | 4.741 | -593.142 | 0.000 | 0.000 | 235.743 | 49.834 | 380.750 | 37.083 | 0.000 | 7.088 | 67.191 | 0.000 | -24.932 | 0.000 | -113.934 | -50.422 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 09-AUG-03:01 | 0.00 | 0.00 | 0.00 | -66386.05 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 66473.12 | 0.00 | -907.20 | 0.00 | -159.91 | 0.00 |
KITCHEN | 04-JUN-03:01 | 0.00 | 0.00 | 0.00 | -59276.49 | 0.00 | 0.00 | 0.00 | 30.01 | 3472.64 | 0.00 | 0.00 | 0.00 | 55868.19 | 0.00 | -0.00 | 0.00 | -94.35 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-AUG-03:01 | 0.00 | 0.00 | 0.00 | -108774.65 | 0.00 | 0.00 | 0.00 | 110.04 | 4372.65 | 0.00 | 0.00 | 685.60 | 104836.73 | 0.00 | -907.20 | 0.00 | -323.16 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 08-FEB-04:01 | 0.00 | 0.00 | 89725.07 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2315.77 | 0.00 | -1608.74 | -86780.60 |
KITCHEN | 26-FEB-05:03 | 0.00 | 0.00 | 11100.34 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 6895.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -156.27 | -17869.91 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-FEB-04:01 | 0.00 | 0.00 | 89725.07 | 0.00 | 0.00 | 0.00 | 0.00 | 110.04 | 4372.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2315.77 | 0.00 | -2954.05 | -88937.94 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.4333 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.4333 | 0.3878 | 1.0000 | Not calculated | 1.3314 | 0.3878 | ||
PSZ-AC_2:2 | 1.5524 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5524 | 0.1176 | 1.0000 | Not calculated | 0.1826 | 0.1176 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.4333 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.4333 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3878 | ||
PSZ-AC_2:2 | 1.5524 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5524 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1176 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4333 | 3.4333 | 3.4333 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5524 | 1.5524 | 1.5524 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.4333 | 3.4333 | 3.4333 | 3.4333 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5524 | 1.5524 | 1.5524 | 1.5524 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.4333 | 3.4333 | 3.4333 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5524 | 1.5524 | 1.5524 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.4333 | 3.4333 | 3.4333 | 3.4333 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5524 | 1.5524 | 1.5524 | 1.5524 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 599.66 | 169416.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 68.11 | 26015.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 49.83 | 3339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.57 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 87.17 | 4811.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.50 | 4742.11 | 377.25 | 33529.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.80 | 1511.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.22 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 499.39 | 806.02 |
Natural Gas | 469.79 | 1446.70 |
Additional | 0.00 | 0.00 |
Total | 969.17 | 2252.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 97.49 |
Space Heating | 0.00 |
Space Cooling | 133.25 |
Fans (All) | 170.53 |
Service Water Heating | 147.71 |
Receptacle Equipment | 879.26 |
Miscellaneous (All) | 1576.87 |
Subtotal | 1576.87 |
Natural Gas [MJ/m2] | |
Space Heating | 1173.16 |
Service Water Heating | 738.03 |
Miscellaneous (All) | 2830.26 |
Subtotal | 2830.26 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.21 |
Space Heating | 26.62 |
Space Cooling | 3.02 |
Fans (All) | 3.87 |
Service Water Heating | 20.10 |
Receptacle Equipment | 40.80 |
Miscellaneous | 3.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8222.33 | 524.33 | 13.33 | 0.00 | 0.00 |
ATTIC | 7380.67 | 514.50 | 473.00 | 372.00 | 19.83 |
Min | 7380.67 | 18.33 | 0.00 | 0.00 | 0.00 |
Max | 8741.67 | 524.33 | 473.00 | 372.00 | 19.83 |
Average | 8114.89 | 352.39 | 162.11 | 124.00 | 6.61 |
Sum | 24344.67 | 1057.17 | 486.33 | 372.00 | 19.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824201.00 | 21.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19232.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824201.00 | 21.00 | 0.00 | 0.00 | 0.00 |
Average | 281144.50 | 7.17 | 0.00 | 0.00 | 0.00 |
Sum | 843433.50 | 21.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7983.83 | 776.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6368.17 | 2391.17 | 0.67 | 0.00 | 0.00 |
ATTIC | 7262.83 | 940.33 | 261.33 | 181.33 | 114.17 |
Min | 6368.17 | 776.17 | 0.00 | 0.00 | 0.00 |
Max | 7983.83 | 2391.17 | 261.33 | 181.33 | 114.17 |
Average | 7204.94 | 1369.22 | 87.33 | 60.44 | 38.06 |
Sum | 21614.83 | 4107.67 | 262.00 | 181.33 | 114.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 754231.33 | 69990.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14003.33 | 5229.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 754231.33 | 69990.67 | 0.00 | 0.00 | 0.00 |
Average | 256078.22 | 25073.44 | 0.00 | 0.00 | 0.00 |
Sum | 768234.67 | 75220.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870911E+10 | 46436.05 | 31-JAN-21:11 | -11.2 | -12.4 | 0.119980E+11 | 10741.02 | 28-JAN-19:49 | -11.2 | -12.4 |
February | 0.774009E+10 | 51737.65 | 07-FEB-00:01 | -15.0 | -15.8 | 0.108693E+11 | 10741.02 | 25-FEB-19:00 | -6.7 | -7.8 |
March | 0.156001E+11 | 47190.62 | 07-MAR-00:01 | -11.8 | -12.6 | 0.124095E+11 | 12937.53 | 14-MAR-11:50 | 23.62 | 17.58 |
April | 0.195803E+11 | 34048.31 | 16-APR-23:01 | -2.9 | -4.7 | 0.121602E+11 | 14051.05 | 08-APR-18:49 | -2.9 | -4.7 |
May | 0.242414E+11 | 47079.18 | 24-MAY-03:01 | 16.88 | 13.98 | 0.140503E+11 | 14050.46 | 20-MAY-18:00 | 16.88 | 13.98 |
June | 0.281945E+11 | 58334.88 | 28-JUN-03:01 | 18.72 | 15.78 | 0.146403E+11 | 14051.39 | 10-JUN-18:49 | 18.72 | 15.78 |
July | 0.321252E+11 | 57975.82 | 26-JUL-03:01 | 20.60 | 16.69 | 0.152497E+11 | 14051.89 | 22-JUL-18:00 | 20.60 | 16.69 |
August | 0.320619E+11 | 66434.20 | 09-AUG-03:01 | 17.20 | 13.88 | 0.153698E+11 | 14051.13 | 12-AUG-18:10 | 22.85 | 16.10 |
September | 0.277325E+11 | 55966.38 | 18-SEP-03:01 | 11.52 | 10.07 | 0.142978E+11 | 14051.06 | 16-SEP-18:10 | 11.52 | 10.07 |
October | 0.236381E+11 | 30152.09 | 16-OCT-23:01 | -0.1 | -0.7 | 0.129314E+11 | 14050.07 | 21-OCT-18:19 | 16.13 | 12.19 |
November | 0.182845E+11 | 32491.89 | 24-NOV-00:01 | -1.8 | -2.5 | 0.118321E+11 | 14039.26 | 04-NOV-18:00 | -1.8 | -2.5 |
December | 0.101009E+11 | 53484.41 | 11-DEC-00:01 | -16.1 | -16.3 | 0.119992E+11 | 11352.51 | 01-DEC-12:00 | -16.1 | -16.3 |
Annual Sum or Average | 0.248009E+12 | 0.157808E+12 | ||||||||
Minimum of Months | 0.774009E+10 | 30152.09 | -16.1 | -16.3 | 0.108693E+11 | 10741.02 | -16.1 | -16.3 | ||
Maximum of Months | 0.321252E+11 | 66434.20 | 20.60 | 16.69 | 0.153698E+11 | 14051.89 | 23.62 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272822E+11 | 43742.88 | 10-JAN-05:01 | -13.3 | -14.3 | 0.103896E+11 | 6851.22 | 11-JAN-11:00 | 9.40 | 8.22 |
February | 0.243021E+11 | 44693.93 | 07-FEB-05:01 | -15.7 | -16.1 | 0.938510E+10 | 6826.44 | 22-FEB-11:00 | 6.70 | 2.27 |
March | 0.280651E+11 | 47688.51 | 17-MAR-03:01 | 11.02 | 10.40 | 0.104217E+11 | 6930.42 | 15-MAR-10:39 | 11.02 | 10.40 |
April | 0.278600E+11 | 47955.80 | 09-APR-03:01 | 12.12 | 10.59 | 0.101150E+11 | 6930.38 | 07-APR-10:00 | 12.12 | 10.59 |
May | 0.284846E+11 | 57423.40 | 18-MAY-03:01 | 9.40 | 6.45 | 0.105512E+11 | 6930.47 | 17-MAY-10:00 | 9.40 | 6.45 |
June | 0.292238E+11 | 59355.70 | 04-JUN-03:01 | 8.12 | 5.87 | 0.102470E+11 | 6930.47 | 01-JUN-10:30 | 8.12 | 5.87 |
July | 0.312938E+11 | 48044.63 | 12-JUL-03:11 | 13.70 | 11.54 | 0.105929E+11 | 6930.43 | 13-JUL-10:39 | 21.83 | 16.26 |
August | 0.314120E+11 | 50140.58 | 03-AUG-03:01 | 11.60 | 9.83 | 0.105973E+11 | 6930.46 | 30-AUG-10:20 | 17.97 | 17.50 |
September | 0.295950E+11 | 57282.88 | 05-SEP-03:01 | 7.12 | 6.58 | 0.102368E+11 | 6930.44 | 26-SEP-10:09 | 16.47 | 15.98 |
October | 0.303962E+11 | 53263.76 | 02-OCT-03:01 | 8.80 | 8.48 | 0.104869E+11 | 6930.45 | 12-OCT-10:50 | 17.70 | 14.38 |
November | 0.291597E+11 | 43748.22 | 05-NOV-03:01 | 15.10 | 11.96 | 0.100896E+11 | 6930.40 | 16-NOV-11:00 | 18.30 | 12.18 |
December | 0.280705E+11 | 46712.49 | 11-DEC-05:01 | -17.5 | -18.0 | 0.103902E+11 | 6909.75 | 01-DEC-11:50 | -17.5 | -18.0 |
Annual Sum or Average | 0.345145E+12 | 0.123503E+12 | ||||||||
Minimum of Months | 0.243021E+11 | 43742.88 | -17.5 | -18.0 | 0.938510E+10 | 6826.44 | -17.5 | -18.0 | ||
Maximum of Months | 0.314120E+11 | 59355.70 | 15.10 | 11.96 | 0.105973E+11 | 6930.47 | 21.83 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131178E+10 | 81959.06 | 24-JAN-04:01 | -11.7 |
February | 0.153016E+10 | 89731.61 | 08-FEB-04:01 | -6.8 |
March | 0.573638E+09 | 60741.48 | 06-MAR-04:02 | -11.1 |
April | 0.131034E+09 | 44258.24 | 17-APR-03:02 | -2.9 |
May | 3913225.98 | 10274.98 | 08-MAY-04:02 | 3.30 |
June | 525275.50 | 4450.23 | 04-JUN-04:05 | 7.12 |
July | 7095863.19 | 4362.82 | 19-JUL-23:02 | 26.60 |
August | 212407.69 | 804.64 | 13-AUG-23:03 | 24.32 |
September | 836014.95 | 8032.28 | 30-SEP-04:03 | 7.20 |
October | 17967733.35 | 23613.45 | 30-OCT-04:01 | -0.5 |
November | 0.103538E+09 | 42585.92 | 19-NOV-06:48 | 1.02 |
December | 0.104119E+10 | 76634.99 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.472190E+10 | |||
Minimum of Months | 212407.69 | 804.64 | -17.5 | |
Maximum of Months | 0.153016E+10 | 89731.61 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7194182.68 | 10269.78 | 26-JAN-05:03 | -7.3 |
February | 5601677.02 | 11109.89 | 26-FEB-05:03 | -7.4 |
March | 3476042.94 | 10779.66 | 05-MAR-05:03 | -10.7 |
April | 51802.63 | 863.38 | 03-APR-04:04 | -2.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 129903.62 | 2165.06 | 25-NOV-05:04 | -1.7 |
December | 2773654.26 | 10598.23 | 07-DEC-05:03 | -7.8 |
Annual Sum or Average | 19227263.15 | |||
Minimum of Months | 0.00 | 0.00 | -10.7 | |
Maximum of Months | 7194182.68 | 11109.89 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.304672E+10 | 2454.69 | 02-JAN-16:30 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.265669E+10 | 2454.69 | 01-FEB-16:49 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.279650E+10 | 2454.69 | 01-MAR-17:49 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.255081E+10 | 2454.69 | 01-APR-18:19 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.255754E+10 | 2454.69 | 01-MAY-19:10 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.242173E+10 | 2454.69 | 01-JUN-19:40 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.247059E+10 | 2454.69 | 01-JUL-19:40 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.260354E+10 | 2454.69 | 01-AUG-19:30 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.263193E+10 | 2454.69 | 01-SEP-18:30 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.283974E+10 | 2454.69 | 02-OCT-17:30 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.295569E+10 | 2454.69 | 01-NOV-16:49 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.309305E+10 | 2454.69 | 01-DEC-16:19 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.326245E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.242173E+10 | 2454.69 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.309305E+10 | 2454.69 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.145365E+10 | 885.05 | 02-JAN-10:09 | 0.275454E+11 | 17341.88 | 01-JAN-11:09 |
February | 0.131681E+10 | 885.05 | 01-FEB-10:09 | 0.248798E+11 | 17341.88 | 01-FEB-11:09 |
March | 0.147869E+10 | 885.05 | 01-MAR-10:09 | 0.275456E+11 | 17341.88 | 01-MAR-11:09 |
April | 0.141254E+10 | 885.05 | 01-APR-16:10 | 0.266569E+11 | 17341.88 | 01-APR-10:09 |
May | 0.146617E+10 | 885.05 | 01-MAY-09:09 | 0.275455E+11 | 17341.88 | 01-MAY-10:09 |
June | 0.142908E+10 | 885.05 | 01-JUN-09:09 | 0.266570E+11 | 17341.88 | 01-JUN-10:09 |
July | 0.144981E+10 | 885.05 | 01-JUL-16:10 | 0.275454E+11 | 17341.88 | 01-JUL-10:09 |
August | 0.147869E+10 | 885.05 | 01-AUG-09:09 | 0.275456E+11 | 17341.88 | 01-AUG-10:09 |
September | 0.141289E+10 | 885.05 | 01-SEP-09:09 | 0.266569E+11 | 17341.88 | 01-SEP-10:09 |
October | 0.145348E+10 | 885.05 | 02-OCT-09:09 | 0.275454E+11 | 17341.88 | 01-OCT-10:09 |
November | 0.140753E+10 | 885.05 | 01-NOV-09:09 | 0.266568E+11 | 17341.88 | 01-NOV-10:09 |
December | 0.144998E+10 | 885.05 | 01-DEC-10:09 | 0.275454E+11 | 17341.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.172093E+11 | 0.324326E+12 | ||||
Minimum of Months | 0.131681E+10 | 885.05 | 0.248798E+11 | 17341.88 | ||
Maximum of Months | 0.147869E+10 | 885.05 | 0.275456E+11 | 17341.88 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.304672E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127023E+11 |
February | 0.272721E+11 | 0.265669E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119467E+11 |
March | 0.305458E+11 | 0.279650E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7928904.66 | 0.924037E+10 |
April | 0.292871E+11 | 0.255081E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630124E+10 |
May | 0.303219E+11 | 0.255754E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5174383.88 | 0.384153E+10 |
June | 0.295292E+11 | 0.242173E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175377E+09 | 0.196718E+10 |
July | 0.300798E+11 | 0.247059E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484745E+09 | 0.790431E+09 |
August | 0.305458E+11 | 0.260354E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381248E+09 | 0.127253E+10 |
September | 0.292871E+11 | 0.263193E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27495311.01 | 0.269776E+10 |
October | 0.300980E+11 | 0.283974E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560486E+10 |
November | 0.290996E+11 | 0.295569E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723501E+10 |
December | 0.300798E+11 | 0.309305E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120980E+11 |
Annual Sum or Average | 0.356244E+12 | 0.326245E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108197E+10 | 0.756979E+11 |
Minimum of Months | 0.272721E+11 | 0.242173E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790431E+09 |
Maximum of Months | 0.305458E+11 | 0.309305E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484745E+09 | 0.127023E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.145365E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635953E+09 |
February | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673522E+09 |
March | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 432.87 | 0.418979E+09 |
April | 0.786997E+09 | 0.141254E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325285E+09 |
May | 0.814802E+09 | 0.146617E+10 | 0.225868E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2614.94 | 0.212644E+09 |
June | 0.793501E+09 | 0.142908E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1699805.59 | 0.157893E+09 |
July | 0.808298E+09 | 0.144981E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 4631417.01 | 96776192.80 |
August | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3618621.56 | 0.109750E+09 |
September | 0.786997E+09 | 0.141289E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 133649.66 | 0.150339E+09 |
October | 0.808786E+09 | 0.145348E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280886E+09 |
November | 0.781956E+09 | 0.140753E+10 | 0.218581E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372304E+09 |
December | 0.808298E+09 | 0.144998E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665050E+09 |
Annual Sum or Average | 0.957291E+10 | 0.172093E+11 | 0.265941E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 10086541.63 | 0.409938E+10 |
Minimum of Months | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96776192.80 |
Maximum of Months | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 4631417.01 | 0.673522E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502022E+09 | 0.123274E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368752E+09 | 0.174201E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612026E+09 | 0.274441E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434677E+09 | 0.361645E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528049E+09 | 0.426614E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432177E+09 | 0.465007E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451554E+09 | 0.472722E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450549E+09 | 0.407058E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671436E+09 | 0.301771E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564959E+09 | 0.195252E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574550E+09 | 0.108352E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405195E+09 | 0.103296E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599595E+10 | 0.341363E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368752E+09 | 0.103296E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671436E+09 | 0.472722E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2454.69 | 02-JAN-16:30 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 14689.31 | 30-JAN-19:00 |
February | 30255.31 | 04-FEB-19:10 | 2454.69 | 01-FEB-16:49 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 16198.87 | 06-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 2454.69 | 01-MAR-17:49 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 443.92 | 15-MAR-14:00 | 13836.24 | 06-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2454.69 | 01-APR-18:19 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 8464.57 | 16-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 2454.69 | 01-MAY-19:10 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 434.08 | 10-MAY-14:00 | 5131.28 | 06-MAY-18:53 |
June | 30255.31 | 03-JUN-18:10 | 2454.69 | 01-JUN-19:40 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2269.90 | 27-JUN-12:00 | 4920.29 | 13-JUN-12:00 |
July | 30255.31 | 01-JUL-18:10 | 2454.69 | 01-JUL-19:40 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2257.82 | 21-JUL-12:00 | 1970.90 | 06-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 2454.69 | 01-AUG-19:30 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.61 | 10-AUG-12:00 | 4172.75 | 30-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 2454.69 | 01-SEP-18:30 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 825.10 | 16-SEP-13:00 | 4409.93 | 28-SEP-17:30 |
October | 30255.31 | 07-OCT-18:10 | 2454.69 | 02-OCT-17:30 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 8247.87 | 16-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 2454.69 | 01-NOV-16:49 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9476.08 | 22-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 2454.69 | 01-DEC-16:19 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 16241.34 | 11-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1970.90 | |||||
Maximum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2269.90 | 16241.34 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 885.05 | 02-JAN-10:09 | 14079.00 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1833.56 | 12-JAN-05:00 |
February | 813.01 | 04-FEB-19:10 | 885.05 | 01-FEB-10:09 | 14079.00 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1814.30 | 13-FEB-04:10 |
March | 813.01 | 04-MAR-19:10 | 885.05 | 01-MAR-10:09 | 14079.00 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.63 | 15-MAR-14:00 | 1183.60 | 02-MAR-05:00 |
April | 813.01 | 01-APR-18:10 | 885.05 | 01-APR-16:10 | 14079.00 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1149.94 | 16-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 885.05 | 01-MAY-09:09 | 14079.00 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.96 | 14-MAY-15:00 | 443.01 | 30-MAY-02:00 |
June | 813.01 | 03-JUN-18:10 | 885.05 | 01-JUN-09:09 | 14079.00 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 40.02 | 27-JUN-12:55 | 705.36 | 13-JUN-03:00 |
July | 813.01 | 01-JUL-18:10 | 885.05 | 01-JUL-16:10 | 14079.00 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 88.18 | 21-JUL-03:10 | 554.91 | 06-JUL-02:00 |
August | 813.01 | 05-AUG-18:10 | 885.05 | 01-AUG-09:09 | 14079.00 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 42.47 | 13-AUG-13:00 | 360.03 | 27-AUG-03:00 |
September | 813.01 | 02-SEP-18:10 | 885.05 | 01-SEP-09:09 | 14079.00 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 10.01 | 16-SEP-13:00 | 648.92 | 29-SEP-03:40 |
October | 813.01 | 07-OCT-18:10 | 885.05 | 02-OCT-09:09 | 14079.00 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 657.75 | 07-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 885.05 | 01-NOV-09:09 | 14079.00 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1201.39 | 17-NOV-04:40 |
December | 813.01 | 02-DEC-19:10 | 885.05 | 01-DEC-10:09 | 14079.00 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1495.16 | 26-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 360.03 | ||||||
Maximum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 88.18 | 1833.56 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1419.12 | 06-JAN-03:50 | 4305.25 | 30-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.66 | 27-FEB-23:00 | 5909.49 | 08-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1552.02 | 08-MAR-07:13 | 6236.78 | 07-MAR-13:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.55 | 24-APR-05:40 | 7940.13 | 06-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1672.53 | 27-MAY-04:55 | 8261.16 | 26-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1252.87 | 04-JUN-05:15 | 8245.12 | 10-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1713.77 | 13-JUL-02:00 | 7869.34 | 03-JUL-12:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1299.48 | 12-AUG-03:10 | 7449.28 | 03-AUG-13:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1474.82 | 10-SEP-22:30 | 6427.24 | 03-SEP-12:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.64 | 02-OCT-06:15 | 5569.30 | 17-OCT-13:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.87 | 25-NOV-21:00 | 3945.11 | 24-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.85 | 16-DEC-08:00 | 3885.22 | 11-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.87 | 3885.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1713.77 | 8261.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 46436.05 | 31-JAN-21:11 | 168085.04 | 24546.88 | 43397.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9077.54 |
February | 51737.65 | 07-FEB-00:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1711.44 |
March | 47190.62 | 07-MAR-00:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.93 |
April | 34048.31 | 16-APR-23:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.69 |
May | 47079.18 | 24-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.38 |
June | 58334.88 | 28-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.19 |
July | 57975.82 | 26-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 |
August | 66434.20 | 09-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.91 |
September | 55966.38 | 18-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.06 |
October | 30152.09 | 16-OCT-23:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.43 |
November | 32491.89 | 24-NOV-00:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.84 |
December | 53484.41 | 11-DEC-00:01 | 16808.50 | 4091.24 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 30152.09 | 0.00 | 800.29 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 | |
Maximum of Months | 66434.20 | 168085.04 | 24546.88 | 43397.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9077.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 43742.88 | 10-JAN-05:01 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 135.21 |
February | 44693.93 | 07-FEB-05:01 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 316.36 |
March | 47688.51 | 17-MAR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 185.71 |
April | 47955.80 | 09-APR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 259.83 |
May | 57423.40 | 18-MAY-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 |
June | 59355.70 | 04-JUN-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 94.35 |
July | 48044.63 | 12-JUL-03:11 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 148.48 |
August | 50140.58 | 03-AUG-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 162.11 |
September | 57282.88 | 05-SEP-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 158.90 |
October | 53263.76 | 02-OCT-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 177.16 |
November | 43748.22 | 05-NOV-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 334.40 |
December | 46712.49 | 11-DEC-05:01 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 69.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 43742.88 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | |
Maximum of Months | 59355.70 | 451.67 | 300.11 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 334.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.36 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.85 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.71 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.27 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.98 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.10 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.25 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.64 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.17 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.40 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.85 | 17.25 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.641186E+11 | 36927.05 | 31-JAN-11:09 | 0.216318E+12 | 174890.28 | 04-JAN-04:30 |
February | 0.576711E+11 | 37056.71 | 06-FEB-11:20 | 0.203537E+12 | 181289.09 | 09-FEB-04:30 |
March | 0.635168E+11 | 44856.09 | 15-MAR-10:00 | 0.159112E+12 | 174890.28 | 07-MAR-04:19 |
April | 0.599465E+11 | 39493.31 | 08-APR-10:00 | 0.106994E+12 | 114632.22 | 17-APR-06:19 |
May | 0.638689E+11 | 44160.81 | 10-MAY-10:00 | 0.780795E+11 | 78096.35 | 01-MAY-06:19 |
June | 0.725962E+11 | 58959.03 | 27-JUN-11:00 | 0.690536E+11 | 46908.98 | 01-JUN-18:49 |
July | 0.858511E+11 | 59830.85 | 20-JUL-10:00 | 0.687441E+11 | 43871.22 | 05-JUL-18:30 |
August | 0.809183E+11 | 58512.45 | 10-AUG-11:00 | 0.686038E+11 | 43566.03 | 13-AUG-10:39 |
September | 0.688829E+11 | 53668.85 | 15-SEP-11:00 | 0.681594E+11 | 47136.19 | 30-SEP-05:19 |
October | 0.633485E+11 | 42316.66 | 11-OCT-17:40 | 0.916701E+11 | 101062.63 | 17-OCT-06:30 |
November | 0.611918E+11 | 38149.73 | 05-NOV-10:00 | 0.114477E+12 | 107614.45 | 24-NOV-07:30 |
December | 0.641122E+11 | 37032.65 | 11-DEC-11:09 | 0.201950E+12 | 187873.91 | 11-DEC-04:19 |
Annual Sum or Average | 0.806023E+12 | 0.144670E+13 | ||||
Minimum of Months | 0.576711E+11 | 36927.05 | 0.681594E+11 | 43566.03 | ||
Maximum of Months | 0.858511E+11 | 59830.85 | 0.216318E+12 | 187873.91 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.450037E+10 | 0.286300E+10 | 0.381711E+11 | 0.00 | 0.828381E+10 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639849E+10 | 0.00 |
February | 0.397350E+10 | 0.233494E+10 | 0.344772E+11 | 0.00 | 0.757350E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579107E+10 | 0.00 |
March | 0.427519E+10 | 0.223873E+10 | 0.381714E+11 | 0.00 | 0.763640E+10 | 37879553.69 | 0.00 | 0.696372E+09 | 0.00 | 0.00 | 0.00 | 0.646467E+10 | 0.00 |
April | 0.396335E+10 | 0.181654E+10 | 0.369399E+11 | 0.00 | 0.687328E+10 | 36657632.61 | 0.00 | 0.135250E+09 | 0.00 | 0.00 | 0.00 | 0.620633E+10 | 0.00 |
May | 0.402371E+10 | 0.158894E+10 | 0.381712E+11 | 0.00 | 0.678319E+10 | 37879553.69 | 0.00 | 0.241995E+10 | 0.00 | 0.00 | 0.00 | 0.642008E+10 | 0.00 |
June | 0.385081E+10 | 0.141391E+10 | 0.369400E+11 | 0.00 | 0.676738E+10 | 36657632.61 | 0.00 | 0.129022E+11 | 0.00 | 0.00 | 0.00 | 0.623766E+10 | 0.00 |
July | 0.392040E+10 | 0.149682E+10 | 0.381711E+11 | 0.00 | 0.736675E+10 | 37879553.69 | 0.00 | 0.238287E+11 | 0.00 | 0.00 | 0.00 | 0.637180E+10 | 0.00 |
August | 0.408223E+10 | 0.173931E+10 | 0.381714E+11 | 0.00 | 0.713051E+10 | 37879553.69 | 0.00 | 0.186618E+11 | 0.00 | 0.00 | 0.00 | 0.645014E+10 | 0.00 |
September | 0.404482E+10 | 0.201578E+10 | 0.369399E+11 | 0.00 | 0.666799E+10 | 36657632.61 | 0.00 | 0.856475E+10 | 0.00 | 0.00 | 0.00 | 0.619677E+10 | 0.00 |
October | 0.429321E+10 | 0.244195E+10 | 0.381711E+11 | 0.00 | 0.696048E+10 | 37879553.69 | 0.00 | 0.809870E+09 | 0.00 | 0.00 | 0.00 | 0.638852E+10 | 0.00 |
November | 0.436322E+10 | 0.267458E+10 | 0.369398E+11 | 0.00 | 0.698494E+10 | 36657632.61 | 0.00 | 93771637.56 | 0.00 | 0.00 | 0.00 | 0.618893E+10 | 0.00 |
December | 0.454303E+10 | 0.294668E+10 | 0.381711E+11 | 0.00 | 0.813857E+10 | 37879553.69 | 0.00 | 620934.87 | 0.00 | 0.00 | 0.00 | 0.639038E+10 | 0.00 |
Annual Sum or Average | 0.498339E+11 | 0.255712E+11 | 0.449435E+12 | 0.00 | 0.871668E+11 | 0.446001E+09 | 0.00 | 0.681132E+11 | 0.00 | 0.00 | 0.00 | 0.755048E+11 | 0.00 |
Minimum of Months | 0.385081E+10 | 0.141391E+10 | 0.344772E+11 | 0.00 | 0.666799E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579107E+10 | 0.00 |
Maximum of Months | 0.454303E+10 | 0.294668E+10 | 0.381714E+11 | 0.00 | 0.828381E+10 | 37879553.69 | 0.00 | 0.238287E+11 | 0.00 | 0.00 | 0.00 | 0.646467E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.141372E+12 | 0.00 | 0.350464E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.135372E+12 | 0.00 | 0.321272E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.838271E+11 | 0.00 | 0.353850E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.356028E+11 | 0.00 | 0.327784E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.606074E+10 | 0.00 | 0.321191E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.982250E+09 | 0.00 | 0.294587E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 19610417.12 | 0.00 | 0.288248E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 58269114.02 | 0.00 | 0.286459E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.155052E+10 | 0.00 | 0.279963E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.215757E+11 | 0.00 | 0.301948E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.449083E+11 | 0.00 | 0.309561E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.128335E+12 | 0.00 | 0.337152E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.599664E+12 | 0.00 | 0.377248E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 19610417.12 | 0.00 | 0.279963E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.141372E+12 | 0.00 | 0.353850E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3339.74 | 02-JAN-16:30 | 2213.72 | 01-JAN-06:10 | 24333.76 | 01-JAN-11:09 | 0.00 | 4276.22 | 10-JAN-06:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 3339.74 | 01-FEB-16:49 | 2213.72 | 01-FEB-06:10 | 24333.76 | 01-FEB-11:09 | 0.00 | 4466.95 | 07-FEB-07:10 | 17.86 | 23-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3339.74 | 01-MAR-17:49 | 2213.72 | 01-MAR-06:10 | 24333.76 | 01-MAR-11:09 | 0.00 | 4280.68 | 07-MAR-06:10 | 17.86 | 17-MAR-23:10 | 0.00 | 01-MAR-00:10 |
April | 3339.74 | 01-APR-18:19 | 2213.72 | 01-APR-05:10 | 24333.76 | 01-APR-10:09 | 0.00 | 3850.75 | 17-APR-05:00 | 17.86 | 10-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 3339.74 | 01-MAY-19:10 | 2213.72 | 01-MAY-05:10 | 24333.76 | 01-MAY-10:09 | 0.00 | 3514.81 | 01-MAY-05:10 | 17.86 | 18-MAY-11:39 | 0.00 | 01-MAY-00:10 |
June | 3339.74 | 01-JUN-19:40 | 2213.72 | 01-JUN-19:49 | 24333.76 | 01-JUN-10:09 | 0.00 | 4811.44 | 27-JUN-12:00 | 17.86 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 3339.74 | 01-JUL-19:40 | 2213.72 | 01-JUL-19:00 | 24333.76 | 01-JUL-10:09 | 0.00 | 4693.29 | 20-JUL-11:00 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 3339.74 | 01-AUG-19:30 | 2213.72 | 01-AUG-19:40 | 24333.76 | 01-AUG-10:09 | 0.00 | 4544.90 | 10-AUG-11:00 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 3339.74 | 01-SEP-18:30 | 2213.72 | 01-SEP-05:10 | 24333.76 | 01-SEP-10:09 | 0.00 | 3805.98 | 15-SEP-11:00 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 3339.74 | 02-OCT-17:30 | 2213.72 | 01-OCT-05:10 | 24333.76 | 01-OCT-10:09 | 0.00 | 3732.27 | 17-OCT-05:10 | 17.86 | 08-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 3339.74 | 01-NOV-16:49 | 2213.72 | 01-NOV-05:10 | 24333.76 | 01-NOV-10:09 | 0.00 | 3803.18 | 24-NOV-06:10 | 17.86 | 01-NOV-23:10 | 0.00 | 01-NOV-00:10 |
December | 3339.74 | 01-DEC-16:19 | 2213.72 | 01-DEC-06:10 | 24333.76 | 01-DEC-11:09 | 0.00 | 4536.99 | 11-DEC-05:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 3514.81 | 17.86 | 0.00 | ||||||
Maximum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 4811.44 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.41 | 05-JAN-07:49 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4741.97 | 28-FEB-07:49 | 0.00 |
March | 11664.52 | 15-MAR-17:19 | 0.00 | 0.00 | 0.00 | 4742.11 | 07-MAR-19:49 | 0.00 |
April | 5492.41 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 4741.83 | 24-APR-06:49 | 0.00 |
May | 12227.63 | 10-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4741.93 | 08-MAY-06:49 | 0.00 |
June | 26015.32 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 4740.51 | 14-JUN-06:49 | 0.00 |
July | 25113.35 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4738.79 | 07-JUL-06:19 | 0.00 |
August | 24421.70 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4739.40 | 31-AUG-06:19 | 0.00 |
September | 20318.14 | 15-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4740.53 | 06-SEP-06:19 | 0.00 |
October | 8863.68 | 11-OCT-17:10 | 0.00 | 0.00 | 0.00 | 4740.87 | 16-OCT-18:49 | 0.00 |
November | 3147.06 | 16-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4741.29 | 03-NOV-18:19 | 0.00 |
December | 343.53 | 15-DEC-04:19 | 0.00 | 0.00 | 0.00 | 4741.69 | 11-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4738.79 | 0.00 | ||
Maximum of Months | 26015.32 | 0.00 | 0.00 | 0.00 | 4742.11 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 36927.05 | 31-JAN-11:09 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4033.83 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 37056.71 | 06-FEB-11:20 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4262.99 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 44856.09 | 15-MAR-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 2958.12 | 17.86 | 0.00 | 9465.82 | 0.00 |
April | 39493.31 | 08-APR-10:00 | 1877.68 | 24333.76 | 0.00 | 0.00 | 2958.12 | 17.86 | 0.00 | 3710.90 | 0.00 |
May | 44160.81 | 10-MAY-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 2958.12 | 17.86 | 0.00 | 8859.15 | 0.00 |
June | 58959.03 | 27-JUN-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 4613.05 | 17.86 | 0.00 | 24798.28 | 0.00 |
July | 59830.85 | 20-JUL-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4294.57 | 17.86 | 0.00 | 22846.34 | 0.00 |
August | 58512.45 | 10-AUG-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 4544.90 | 17.86 | 0.00 | 24421.70 | 0.00 |
September | 53668.85 | 15-SEP-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 3805.98 | 17.86 | 0.00 | 20318.14 | 0.00 |
October | 42316.66 | 11-OCT-17:40 | 3339.74 | 20315.44 | 2213.72 | 0.00 | 2958.12 | 17.86 | 0.00 | 7564.46 | 0.00 |
November | 38149.73 | 05-NOV-10:00 | 1642.97 | 24333.76 | 0.00 | 0.00 | 2958.12 | 17.86 | 0.00 | 2600.14 | 0.00 |
December | 37032.65 | 11-DEC-11:09 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4086.28 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 36927.05 | 1642.97 | 20315.44 | 0.00 | 0.00 | 2958.12 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59830.85 | 3339.74 | 24333.76 | 2213.72 | 0.00 | 4613.05 | 17.86 | 0.00 | 24798.28 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 169416.90 | 04-JAN-04:30 | 0.00 | 33288.15 | 27-JAN-19:30 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 169416.90 | 05-FEB-04:19 | 0.00 | 33529.10 | 17-FEB-19:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 169416.90 | 07-MAR-04:19 | 0.00 | 33391.99 | 02-MAR-07:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 77546.75 | 17-APR-05:00 | 0.00 | 32115.05 | 03-APR-06:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 46802.66 | 01-MAY-05:10 | 0.00 | 30085.52 | 01-MAY-06:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 19946.97 | 14-JUN-04:49 | 0.00 | 27012.79 | 01-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 2325.72 | 03-JUL-04:49 | 0.00 | 23962.11 | 05-JUL-06:40 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 4776.37 | 31-AUG-04:00 | 0.00 | 22553.40 | 01-AUG-06:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 20764.56 | 30-SEP-05:00 | 0.00 | 24148.77 | 29-SEP-18:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 66538.90 | 17-OCT-05:10 | 0.00 | 27140.08 | 31-OCT-06:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 72930.87 | 24-NOV-06:10 | 0.00 | 29959.35 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 169416.90 | 10-DEC-04:30 | 0.00 | 32009.58 | 28-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 2325.72 | 0.00 | 22553.40 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 169416.90 | 0.00 | 33529.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
February | 5.33 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
March | 2.83 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
April | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.68 | 0.00 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.62 | 0.00 | 24.62 |
October | 0.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
November | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
December | 3.67 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
Annual Sum or Average | 17.00 | 19.96 | 0.00 | 19.96 | 4.50 | 20.94 | 0.00 | 20.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 20.42 | 0.00 | 20.42 | 2.00 | 24.68 | 0.00 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.91 | 0.00 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.31 | 0.00 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.38 | 0.00 | 28.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 30.14 | 0.00 | 30.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.52 | 0.17 | 30.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 30.55 | 0.00 | 30.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 30.05 | 0.00 | 30.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.16 | 0.00 | 28.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.33 | 0.00 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.79 | 0.00 | 26.79 |
Annual Sum or Average | 0.00 | 0.00 | 99.67 | 29.91 | 0.17 | 29.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.55 | 0.17 | 30.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.74 | 360.00 | 20.67 | 360.00 | 20.64 |
February | 551.00 | 20.74 | 309.00 | 20.67 | 309.00 | 20.63 |
March | 583.67 | 20.84 | 170.67 | 20.80 | 149.33 | 20.69 |
April | 573.83 | 21.11 | 66.50 | 20.95 | 62.67 | 20.80 |
May | 424.00 | 21.74 | 108.17 | 22.08 | 23.33 | 22.05 |
June | 256.50 | 22.86 | 410.50 | 23.54 | 127.33 | 23.60 |
July | 280.67 | 23.79 | 569.67 | 23.93 | 249.67 | 23.95 |
August | 217.33 | 23.44 | 529.33 | 23.83 | 157.83 | 23.86 |
September | 280.67 | 22.36 | 358.17 | 23.25 | 86.83 | 23.33 |
October | 520.67 | 21.15 | 89.17 | 21.31 | 28.83 | 21.19 |
November | 580.33 | 20.94 | 56.83 | 20.77 | 56.83 | 20.62 |
December | 609.00 | 20.75 | 273.00 | 20.65 | 273.00 | 20.60 |
Annual Sum or Average | 5487.67 | 21.37 | 3301.00 | 21.82 | 1884.67 | 21.77 |
Minimum of Months | 217.33 | 20.74 | 56.83 | 20.65 | 23.33 | 20.60 |
Maximum of Months | 610.00 | 23.79 | 569.67 | 23.93 | 360.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.04 | 410.67 | 19.03 | 410.67 | 19.02 |
February | 551.00 | 19.05 | 344.17 | 19.03 | 344.17 | 19.02 |
March | 562.00 | 19.62 | 296.67 | 19.88 | 258.50 | 19.88 |
April | 461.00 | 19.99 | 202.67 | 20.75 | 98.50 | 20.71 |
May | 350.83 | 23.86 | 446.33 | 24.58 | 216.83 | 24.87 |
June | 482.00 | 25.70 | 553.00 | 25.69 | 457.17 | 25.77 |
July | 569.83 | 25.99 | 609.00 | 25.93 | 569.83 | 25.95 |
August | 538.33 | 25.98 | 610.17 | 25.87 | 538.33 | 25.90 |
September | 439.17 | 25.51 | 531.50 | 25.50 | 401.67 | 25.63 |
October | 421.83 | 21.39 | 275.83 | 22.48 | 127.67 | 22.79 |
November | 526.00 | 19.75 | 160.00 | 20.18 | 110.00 | 20.19 |
December | 605.17 | 19.03 | 313.67 | 19.04 | 310.50 | 19.03 |
Annual Sum or Average | 6117.17 | 21.91 | 4753.67 | 22.59 | 3843.83 | 22.76 |
Minimum of Months | 350.83 | 19.03 | 160.00 | 19.03 | 98.50 | 19.02 |
Maximum of Months | 610.00 | 25.99 | 610.17 | 25.93 | 569.83 | 25.95 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.73869 | 21.67336 | -0.6031 | 13.49690 |
February | 551.00000 | 20.74280 | 21.84214 | -0.6021 | 13.48721 |
March | 612.00000 | 20.98459 | 30.96751 | -0.4254 | 10.74627 |
April | 590.00000 | 21.18258 | 36.76408 | -0.3109 | 8.71091 |
May | 611.00000 | 22.39945 | 42.64788 | -0.9665 | 28.03838 |
June | 592.00000 | 23.46555 | 52.07854 | -0.4735 | 12.37900 |
July | 609.00000 | 23.87970 | 60.41941 | -0.2422 | 7.05154 |
August | 612.00000 | 23.75429 | 55.75471 | -0.3154 | 8.28764 |
September | 590.00000 | 23.15852 | 52.72161 | -0.5699 | 15.10636 |
October | 610.00000 | 21.54285 | 42.51907 | -0.1453 | 7.73726 |
November | 591.00000 | 20.99431 | 34.77107 | -0.3726 | 9.19633 |
December | 609.00000 | 20.74828 | 25.49462 | -0.5629 | 12.51554 |
Annual Sum or Average | 7187.00000 | 21.97387 | 39.90854 | -0.4651 | 12.22992 |
Minimum of Months | 551.00000 | 20.73869 | 21.67336 | -0.9665 | 7.05154 |
Maximum of Months | 612.00000 | 23.87970 | 60.41941 | -0.1453 | 28.03838 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.04280 | 28.47432 | -0.6569 | 14.48172 |
February | 551.00000 | 19.04583 | 28.87584 | -0.6614 | 14.60240 |
March | 612.00000 | 19.94793 | 37.39960 | -0.3746 | 13.54267 |
April | 590.00000 | 20.88603 | 42.70234 | -0.1079 | 11.19457 |
May | 611.00000 | 23.99265 | 43.21732 | -0.1358 | 15.57645 |
June | 592.00000 | 25.38734 | 48.98745 | 0.43672 | 13.60920 |
July | 609.00000 | 25.87436 | 55.05784 | 0.68068 | 15.78676 |
August | 612.00000 | 25.76307 | 51.56370 | 0.61721 | 14.56082 |
September | 590.00000 | 25.06067 | 49.45604 | 0.33807 | 13.31778 |
October | 610.00000 | 22.06956 | 44.92076 | 0.23297 | 13.65198 |
November | 591.00000 | 20.23173 | 40.43897 | -0.2469 | 10.99923 |
December | 609.00000 | 19.06276 | 32.34766 | -0.6151 | 13.48711 |
Annual Sum or Average | 7187.00000 | 22.21636 | 42.02537 | -0.0375 | 13.74305 |
Minimum of Months | 551.00000 | 19.04280 | 28.47432 | -0.6614 | 10.99923 |
Maximum of Months | 612.00000 | 25.87436 | 55.05784 | 0.68068 | 15.78676 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.132774E+10 | 0.405903E+09 | 21.74 | 0.992979E+09 | 0.334757E+09 | 0.00 | 0.68 | 15-MAR-17:10 | 0.00 | 01-MAR-00:01 | 26731.60 | 14-MAR-13:00 | 20931.74 | 15-MAR-17:10 | 8637.04 | 14-MAR-11:45 | 7722.28 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.140645E+09 | 47198476.19 | 9.51 | 0.115817E+09 | 24827983.55 | 0.00 | 0.27 | 08-APR-13:00 | 0.00 | 01-APR-00:01 | 9404.55 | 08-APR-13:00 | 7617.31 | 08-APR-13:00 | 1787.25 | 08-APR-13:00 | 3066.77 | 08-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.372188E+10 | 0.118289E+10 | 120.61 | 0.295394E+10 | 0.767943E+09 | 0.00 | 1.00 | 24-MAY-03:01 | 0.00 | 01-MAY-00:01 | 84110.52 | 24-MAY-03:01 | 55323.83 | 24-MAY-03:01 | 28786.68 | 24-MAY-03:01 | 22535.61 | 24-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.260003E+11 | 0.745961E+10 | 372.16 | 0.165815E+11 | 0.941880E+10 | 0.00 | 1.00 | 02-JUN-03:01 | 0.00 | 01-JUN-00:01 | 92207.77 | 18-JUN-03:01 | 58847.35 | 03-JUN-03:01 | 50830.56 | 18-JUN-03:02 | 23144.88 | 18-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.513979E+11 | 0.141582E+11 | 519.53 | 0.301571E+11 | 0.212408E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 93452.32 | 16-JUL-03:01 | 53826.75 | 06-JUL-03:01 | 55369.87 | 16-JUL-03:01 | 23245.34 | 16-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.392312E+11 | 0.111085E+11 | 457.40 | 0.258012E+11 | 0.134300E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 93452.32 | 14-AUG-03:01 | 57779.50 | 13-AUG-03:01 | 55941.15 | 14-AUG-03:13 | 23245.34 | 14-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.160241E+11 | 0.473335E+10 | 295.97 | 0.997176E+10 | 0.605236E+10 | 0.00 | 1.00 | 08-SEP-03:01 | 0.00 | 01-SEP-00:01 | 90336.26 | 16-SEP-03:01 | 56203.82 | 23-SEP-03:01 | 50673.93 | 16-SEP-03:01 | 23000.31 | 16-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.106393E+10 | 0.347359E+09 | 54.23 | 0.790814E+09 | 0.273112E+09 | 0.00 | 0.52 | 11-OCT-17:10 | 0.00 | 01-OCT-00:01 | 19235.57 | 11-OCT-17:10 | 15164.69 | 11-OCT-13:00 | 4597.40 | 11-OCT-17:10 | 5888.80 | 11-OCT-17:10 | 0.00 | 01-OCT-00:01 |
November | 38463700.68 | 13078576.53 | 5.00 | 28168392.06 | 10295308.62 | 0.00 | 0.17 | 16-NOV-13:00 | 0.00 | 01-NOV-00:01 | 5698.96 | 16-NOV-13:00 | 4223.42 | 16-NOV-13:00 | 1475.55 | 16-NOV-13:00 | 1905.21 | 16-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.138946E+12 | 0.394560E+11 | 1856.14 | 0.873933E+11 | 0.515529E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.513979E+11 | 0.141582E+11 | 519.53 | 0.301571E+11 | 0.212408E+11 | 0.00 | 1.00 | 0.00 | 93452.32 | 58847.35 | 55941.15 | 23245.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.112439E+10 | 0.290470E+09 | 29.25 | 0.843180E+09 | 0.281205E+09 | 0.00 | 1.00 | 14-MAR-03:42 | 0.00 | 01-MAR-00:01 | 38031.74 | 17-MAR-03:01 | 26840.17 | 16-MAR-03:30 | 17961.95 | 17-MAR-03:01 | 9118.08 | 15-MAR-03:01 | 0.00 | 01-MAR-00:01 |
April | 0.306064E+09 | 88051289.04 | 29.85 | 0.238873E+09 | 67190936.17 | 0.00 | 1.00 | 08-APR-03:01 | 0.00 | 01-APR-00:01 | 38031.74 | 09-APR-03:01 | 21655.51 | 09-APR-03:01 | 16376.22 | 09-APR-03:01 | 9118.08 | 09-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.454191E+10 | 0.123706E+10 | 202.63 | 0.344530E+10 | 0.109661E+10 | 0.00 | 1.00 | 05-MAY-03:01 | 0.00 | 01-MAY-00:01 | 38031.74 | 29-MAY-03:32 | 30259.67 | 05-MAY-03:01 | 20405.69 | 29-MAY-03:01 | 9118.08 | 05-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.222591E+11 | 0.544256E+10 | 442.72 | 0.138395E+11 | 0.841962E+10 | 0.00 | 1.00 | 01-JUN-03:11 | 0.00 | 01-JUN-00:01 | 42255.76 | 27-JUN-10:43 | 25937.38 | 04-JUN-03:01 | 23609.34 | 18-JUN-03:22 | 9405.24 | 27-JUN-10:43 | 0.00 | 01-JUN-00:01 |
July | 0.412193E+11 | 0.967047E+10 | 576.57 | 0.233494E+11 | 0.178699E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 42255.76 | 16-JUL-02:13 | 25473.94 | 21-JUL-11:00 | 27150.55 | 20-JUL-21:00 | 9446.96 | 20-JUL-10:55 | 0.00 | 01-JUL-00:01 |
August | 0.313853E+11 | 0.755336E+10 | 526.57 | 0.200003E+11 | 0.113851E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 42255.76 | 14-AUG-03:32 | 25200.62 | 06-AUG-03:54 | 26646.51 | 14-AUG-03:53 | 9405.24 | 14-AUG-01:32 | 0.00 | 01-AUG-00:01 |
September | 0.152661E+11 | 0.383140E+10 | 371.61 | 0.917350E+10 | 0.609265E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 40199.66 | 16-SEP-03:01 | 24265.73 | 17-SEP-02:13 | 23356.95 | 16-SEP-03:01 | 9262.68 | 16-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.166551E+10 | 0.462510E+09 | 87.40 | 0.116946E+10 | 0.496047E+09 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 38031.74 | 13-OCT-03:01 | 28054.19 | 22-OCT-03:42 | 19398.55 | 01-OCT-03:01 | 9118.08 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.280875E+09 | 80693061.03 | 24.61 | 0.195441E+09 | 85433880.06 | 0.00 | 1.00 | 05-NOV-03:01 | 0.00 | 01-NOV-00:01 | 38031.74 | 27-NOV-04:01 | 28100.05 | 27-NOV-04:42 | 14424.01 | 05-NOV-03:01 | 9118.08 | 05-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 2052784.07 | 620934.87 | 0.40 | 1300799.08 | 751984.99 | 0.00 | 0.23 | 01-DEC-04:10 | 0.00 | 01-DEC-00:01 | 3518.66 | 01-DEC-04:10 | 2116.47 | 01-DEC-04:10 | 1402.20 | 01-DEC-04:10 | 1037.90 | 01-DEC-04:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.118051E+12 | 0.286572E+11 | 2291.62 | 0.722562E+11 | 0.457945E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.412193E+11 | 0.967047E+10 | 576.57 | 0.233494E+11 | 0.178699E+11 | 0.00 | 1.00 | 0.00 | 42255.76 | 30259.67 | 27150.55 | 9446.96 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.80 | 45.67 | 96.13 | 53.12 | 470.13 | 0.00 | 0.00 | 0.00 |
February | 209.35 | 63.41 | 145.93 | 96.28 | 441.79 | 0.00 | 0.00 | 0.00 |
March | 300.39 | 126.32 | 174.07 | 242.52 | 302.76 | 0.00 | 0.00 | 0.00 |
April | 395.42 | 174.66 | 220.76 | 392.00 | 210.70 | 0.00 | 0.00 | 0.00 |
May | 443.03 | 196.01 | 247.02 | 504.98 | 140.51 | 0.00 | 0.00 | 0.00 |
June | 494.37 | 218.28 | 276.09 | 620.27 | 95.09 | 0.00 | 0.00 | 0.00 |
July | 474.78 | 208.77 | 266.01 | 639.30 | 65.86 | 0.00 | 0.00 | 0.00 |
August | 428.83 | 179.63 | 249.20 | 564.02 | 87.70 | 0.00 | 0.00 | 0.00 |
September | 357.22 | 158.47 | 198.76 | 424.67 | 138.80 | 0.00 | 0.00 | 0.00 |
October | 242.27 | 100.08 | 142.19 | 225.30 | 217.28 | 0.00 | 0.00 | 0.00 |
November | 137.34 | 43.98 | 93.37 | 85.90 | 294.49 | 0.00 | 0.00 | 0.00 |
December | 110.64 | 22.92 | 87.72 | 26.91 | 462.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 311.74 | 128.49 | 183.25 | 324.17 | 242.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.64 | 22.92 | 87.72 | 26.91 | 65.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 494.37 | 218.28 | 276.09 | 639.30 | 470.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 462.28 | 269.98 | 192.30 | 379.43 | 600.67 | 0.00 | 0.00 | 0.00 |
February | 523.52 | 250.38 | 273.14 | 423.66 | 583.93 | 0.00 | 0.00 | 0.00 |
March | 643.29 | 361.41 | 281.88 | 654.29 | 411.74 | 0.00 | 0.00 | 0.00 |
April | 532.05 | 212.12 | 319.92 | 573.41 | 311.41 | 0.00 | 0.00 | 0.00 |
May | 469.17 | 138.31 | 330.86 | 548.89 | 207.06 | 0.00 | 0.00 | 0.00 |
June | 451.60 | 94.56 | 357.04 | 579.55 | 140.92 | 0.00 | 0.00 | 0.00 |
July | 459.02 | 108.74 | 350.28 | 651.74 | 97.32 | 0.00 | 0.00 | 0.00 |
August | 513.99 | 163.10 | 350.89 | 713.24 | 127.97 | 0.00 | 0.00 | 0.00 |
September | 601.64 | 291.98 | 309.66 | 771.00 | 199.54 | 0.00 | 0.00 | 0.00 |
October | 578.56 | 330.78 | 247.78 | 650.97 | 298.70 | 0.00 | 0.00 | 0.00 |
November | 415.00 | 234.81 | 180.19 | 408.37 | 391.79 | 0.00 | 0.00 | 0.00 |
December | 386.56 | 200.37 | 186.19 | 300.08 | 589.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 502.92 | 221.28 | 281.64 | 555.31 | 328.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 386.56 | 94.56 | 180.19 | 300.08 | 97.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 643.29 | 361.41 | 357.04 | 771.00 | 600.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.12 | 28.78 | 93.33 | 32.85 | 481.05 | 0.00 | 0.00 | 0.00 |
February | 198.30 | 51.36 | 146.94 | 84.24 | 450.46 | 0.00 | 0.00 | 0.00 |
March | 310.45 | 133.33 | 177.13 | 257.21 | 307.43 | 0.00 | 0.00 | 0.00 |
April | 378.47 | 155.05 | 223.42 | 375.03 | 217.33 | 0.00 | 0.00 | 0.00 |
May | 446.98 | 202.22 | 244.76 | 511.69 | 144.59 | 0.00 | 0.00 | 0.00 |
June | 538.62 | 253.10 | 285.52 | 684.30 | 99.02 | 0.00 | 0.00 | 0.00 |
July | 481.45 | 210.75 | 270.70 | 651.85 | 69.73 | 0.00 | 0.00 | 0.00 |
August | 435.23 | 184.49 | 250.74 | 576.06 | 91.45 | 0.00 | 0.00 | 0.00 |
September | 342.16 | 147.60 | 194.56 | 405.64 | 142.97 | 0.00 | 0.00 | 0.00 |
October | 222.81 | 78.92 | 143.88 | 202.96 | 222.38 | 0.00 | 0.00 | 0.00 |
November | 131.28 | 37.65 | 93.62 | 79.24 | 298.06 | 0.00 | 0.00 | 0.00 |
December | 113.59 | 24.47 | 89.12 | 30.72 | 464.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 310.63 | 126.01 | 184.62 | 325.61 | 248.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.59 | 24.47 | 89.12 | 30.72 | 69.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 538.62 | 253.10 | 285.52 | 684.30 | 481.05 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.379790E+09 | 0.122317E+09 | 0.257473E+09 | 0.142264E+09 | 0.125920E+10 |
February | 0.506452E+09 | 0.153413E+09 | 0.353039E+09 | 0.232913E+09 | 0.106879E+10 |
March | 0.804569E+09 | 0.338349E+09 | 0.466220E+09 | 0.649559E+09 | 0.810911E+09 |
April | 0.102493E+10 | 0.452727E+09 | 0.572199E+09 | 0.101607E+10 | 0.546131E+09 |
May | 0.118660E+10 | 0.524991E+09 | 0.661609E+09 | 0.135255E+10 | 0.376337E+09 |
June | 0.128140E+10 | 0.565778E+09 | 0.715619E+09 | 0.160774E+10 | 0.246464E+09 |
July | 0.127165E+10 | 0.559166E+09 | 0.712481E+09 | 0.171231E+10 | 0.176397E+09 |
August | 0.114857E+10 | 0.481109E+09 | 0.667459E+09 | 0.151068E+10 | 0.234906E+09 |
September | 0.925924E+09 | 0.410743E+09 | 0.515181E+09 | 0.110075E+10 | 0.359763E+09 |
October | 0.648901E+09 | 0.268063E+09 | 0.380837E+09 | 0.603451E+09 | 0.581961E+09 |
November | 0.355997E+09 | 0.113993E+09 | 0.242004E+09 | 0.222660E+09 | 0.763322E+09 |
December | 0.296343E+09 | 61390454.41 | 0.234953E+09 | 72082738.50 | 0.123844E+10 |
Annual Sum or Average | 0.983111E+10 | 0.405204E+10 | 0.577907E+10 | 0.102230E+11 | 0.766263E+10 |
Minimum of Months | 0.296343E+09 | 61390454.41 | 0.234953E+09 | 72082738.50 | 0.176397E+09 |
Maximum of Months | 0.128140E+10 | 0.565778E+09 | 0.715619E+09 | 0.171231E+10 | 0.125920E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123818E+10 | 0.723119E+09 | 0.515057E+09 | 0.101625E+10 | 0.160883E+10 |
February | 0.126651E+10 | 0.605724E+09 | 0.660786E+09 | 0.102492E+10 | 0.141264E+10 |
March | 0.172299E+10 | 0.968008E+09 | 0.754983E+09 | 0.175246E+10 | 0.110281E+10 |
April | 0.137906E+10 | 0.549825E+09 | 0.829236E+09 | 0.148627E+10 | 0.807171E+09 |
May | 0.125663E+10 | 0.370447E+09 | 0.886182E+09 | 0.147015E+10 | 0.554584E+09 |
June | 0.117055E+10 | 0.245105E+09 | 0.925449E+09 | 0.150218E+10 | 0.365271E+09 |
July | 0.122945E+10 | 0.291255E+09 | 0.938194E+09 | 0.174562E+10 | 0.260671E+09 |
August | 0.137668E+10 | 0.436851E+09 | 0.939826E+09 | 0.191034E+10 | 0.342747E+09 |
September | 0.155946E+10 | 0.756819E+09 | 0.802639E+09 | 0.199842E+10 | 0.517213E+09 |
October | 0.154963E+10 | 0.885969E+09 | 0.663657E+09 | 0.174355E+10 | 0.800044E+09 |
November | 0.107568E+10 | 0.608623E+09 | 0.467058E+09 | 0.105849E+10 | 0.101551E+10 |
December | 0.103536E+10 | 0.536658E+09 | 0.498704E+09 | 0.803736E+09 | 0.157892E+10 |
Annual Sum or Average | 0.158602E+11 | 0.697840E+10 | 0.888177E+10 | 0.175124E+11 | 0.103664E+11 |
Minimum of Months | 0.103536E+10 | 0.245105E+09 | 0.467058E+09 | 0.803736E+09 | 0.260671E+09 |
Maximum of Months | 0.172299E+10 | 0.968008E+09 | 0.939826E+09 | 0.199842E+10 | 0.160883E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.327073E+09 | 77095131.21 | 0.249978E+09 | 87992073.96 | 0.128845E+10 |
February | 0.479724E+09 | 0.124251E+09 | 0.355473E+09 | 0.203791E+09 | 0.108974E+10 |
March | 0.831520E+09 | 0.357099E+09 | 0.474421E+09 | 0.688899E+09 | 0.823410E+09 |
April | 0.981007E+09 | 0.401891E+09 | 0.579116E+09 | 0.972075E+09 | 0.563324E+09 |
May | 0.119718E+10 | 0.541622E+09 | 0.655558E+09 | 0.137051E+10 | 0.387278E+09 |
June | 0.139610E+10 | 0.656029E+09 | 0.740075E+09 | 0.177371E+10 | 0.256658E+09 |
July | 0.128953E+10 | 0.564475E+09 | 0.725052E+09 | 0.174591E+10 | 0.186777E+09 |
August | 0.116572E+10 | 0.494133E+09 | 0.671588E+09 | 0.154292E+10 | 0.244936E+09 |
September | 0.886883E+09 | 0.382579E+09 | 0.504304E+09 | 0.105142E+10 | 0.370588E+09 |
October | 0.596765E+09 | 0.211388E+09 | 0.385377E+09 | 0.543600E+09 | 0.595622E+09 |
November | 0.340266E+09 | 97599608.96 | 0.242667E+09 | 0.205402E+09 | 0.772581E+09 |
December | 0.304242E+09 | 65548565.70 | 0.238693E+09 | 82283882.81 | 0.124423E+10 |
Annual Sum or Average | 0.979601E+10 | 0.397371E+10 | 0.582230E+10 | 0.102685E+11 | 0.782360E+10 |
Minimum of Months | 0.304242E+09 | 65548565.70 | 0.238693E+09 | 82283882.81 | 0.186777E+09 |
Maximum of Months | 0.139610E+10 | 0.656029E+09 | 0.740075E+09 | 0.177371E+10 | 0.128845E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 406.99 | 1493.45 | 726.19 | 344.43 | 381.76 | 0.00 | 0.00 |
February | 555.25 | 1427.25 | 931.17 | 365.16 | 566.01 | 0.00 | 0.00 |
March | 1099.89 | 967.80 | 1254.14 | 621.06 | 633.07 | 0.00 | 0.00 |
April | 1303.40 | 702.41 | 1305.94 | 541.84 | 764.10 | 0.00 | 0.00 |
May | 1542.73 | 469.32 | 1359.17 | 536.54 | 822.64 | 0.00 | 0.00 |
June | 1867.29 | 318.20 | 1484.59 | 565.94 | 918.65 | 0.00 | 0.00 |
July | 1933.44 | 223.46 | 1415.26 | 528.26 | 887.00 | 0.00 | 0.00 |
August | 1843.93 | 297.72 | 1378.05 | 527.21 | 850.83 | 0.00 | 0.00 |
September | 1586.76 | 466.76 | 1301.03 | 598.05 | 702.98 | 0.00 | 0.00 |
October | 1063.21 | 722.34 | 1043.64 | 509.79 | 533.85 | 0.00 | 0.00 |
November | 555.14 | 965.97 | 683.62 | 316.44 | 367.18 | 0.00 | 0.00 |
December | 312.44 | 1471.15 | 610.79 | 247.76 | 363.03 | 0.00 | 0.00 |
Annual Sum or Average | 1175.91 | 790.59 | 1125.29 | 475.78 | 649.52 | 0.00 | 0.00 |
Minimum of Months | 312.44 | 223.46 | 610.79 | 247.76 | 363.03 | 0.00 | 0.00 |
Maximum of Months | 1933.44 | 1493.45 | 1484.59 | 621.06 | 918.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109007E+10 | 0.400005E+10 | 0.194504E+10 | 0.922531E+09 | 0.102251E+10 | 0.00 | 0.00 |
February | 0.134326E+10 | 0.345281E+10 | 0.225268E+10 | 0.883388E+09 | 0.136930E+10 | 0.00 | 0.00 |
March | 0.294594E+10 | 0.259215E+10 | 0.335908E+10 | 0.166346E+10 | 0.169562E+10 | 0.00 | 0.00 |
April | 0.337842E+10 | 0.182063E+10 | 0.338500E+10 | 0.140444E+10 | 0.198055E+10 | 0.00 | 0.00 |
May | 0.413204E+10 | 0.125702E+10 | 0.364041E+10 | 0.143706E+10 | 0.220335E+10 | 0.00 | 0.00 |
June | 0.484001E+10 | 0.824773E+09 | 0.384805E+10 | 0.146691E+10 | 0.238114E+10 | 0.00 | 0.00 |
July | 0.517852E+10 | 0.598528E+09 | 0.379062E+10 | 0.141490E+10 | 0.237573E+10 | 0.00 | 0.00 |
August | 0.493877E+10 | 0.797418E+09 | 0.369097E+10 | 0.141209E+10 | 0.227887E+10 | 0.00 | 0.00 |
September | 0.411288E+10 | 0.120985E+10 | 0.337227E+10 | 0.155014E+10 | 0.182212E+10 | 0.00 | 0.00 |
October | 0.284770E+10 | 0.193472E+10 | 0.279529E+10 | 0.136542E+10 | 0.142987E+10 | 0.00 | 0.00 |
November | 0.143893E+10 | 0.250379E+10 | 0.177194E+10 | 0.820216E+09 | 0.951729E+09 | 0.00 | 0.00 |
December | 0.836834E+09 | 0.394033E+10 | 0.163595E+10 | 0.663597E+09 | 0.972349E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.370834E+11 | 0.249321E+11 | 0.354873E+11 | 0.150042E+11 | 0.204831E+11 | 0.00 | 0.00 |
Minimum of Months | 0.836834E+09 | 0.598528E+09 | 0.163595E+10 | 0.663597E+09 | 0.951729E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517852E+10 | 0.400005E+10 | 0.384805E+10 | 0.166346E+10 | 0.238114E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639850E+10 | -0.622515E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173350512.6 | 81.22 | 0.00 | 0.00 |
February | 0.579097E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156682379.6 | 81.22 | 0.00 | 0.00 |
March | 0.646462E+10 | -0.629385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -170771635.1 | 81.22 | 0.00 | 0.00 |
April | 0.620620E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162727617.5 | 81.22 | 0.00 | 0.00 |
May | 0.641995E+10 | -0.626017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159782846.3 | 81.22 | 0.00 | 0.00 |
June | 0.623744E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150851862.9 | 81.21 | 0.00 | 0.00 |
July | 0.637169E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154578838.4 | 81.21 | 0.00 | 0.00 |
August | 0.645006E+10 | -0.629522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154837444.6 | 81.21 | 0.00 | 0.00 |
September | 0.619649E+10 | -0.604483E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151667286.5 | 81.21 | 0.00 | 0.00 |
October | 0.638852E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164713782.6 | 81.22 | 0.00 | 0.00 |
November | 0.618881E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164202648.6 | 81.22 | 0.00 | 0.00 |
December | 0.639025E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173181797.9 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755035E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193735E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579097E+10 | -0.629522E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173350512.6 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646462E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150851862.9 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.261731E+11 | -0.251599E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101319E+10 | 58.99 | 0.00 | 0.00 |
February | 0.240184E+11 | -0.231022E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -916138430.9 | 58.99 | 0.00 | 0.00 |
March | 0.264434E+11 | -0.254538E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -989659677.6 | 58.99 | 0.00 | 0.00 |
April | 0.244075E+11 | -0.234730E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -934496663.8 | 58.99 | 0.00 | 0.00 |
May | 0.238117E+11 | -0.229227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -888944056.1 | 58.99 | 0.00 | 0.00 |
June | 0.217340E+11 | -0.209082E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -825788052.2 | 58.99 | 0.00 | 0.00 |
July | 0.211598E+11 | -0.203184E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -841412244.4 | 58.99 | 0.00 | 0.00 |
August | 0.210186E+11 | -0.201748E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843803933.3 | 58.99 | 0.00 | 0.00 |
September | 0.205601E+11 | -0.197269E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -833195451.3 | 58.99 | 0.00 | 0.00 |
October | 0.222631E+11 | -0.213291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -934061914.8 | 58.99 | 0.00 | 0.00 |
November | 0.229400E+11 | -0.219920E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -947939914.5 | 58.99 | 0.00 | 0.00 |
December | 0.250990E+11 | -0.240874E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101159E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279629E+12 | -0.268648E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.109802E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.205601E+11 | -0.254538E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.101319E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.264434E+11 | -0.197269E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -825788052.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.53 | 0.50 | 01-JAN-08:00 | 1847.46 | 27.75 | 174.50 | 237.00 | 1798.01 | 27.63 | 179.83 | 238.67 |
February | 262.50 | 0.52 | 0.50 | 01-FEB-09:39 | 1183.55 | 24.91 | 211.00 | 249.50 | 1124.99 | 24.33 | 199.33 | 249.83 |
March | 339.33 | 0.52 | 0.50 | 01-MAR-07:30 | 1112.19 | 21.91 | 176.50 | 321.33 | 1176.23 | 22.23 | 186.83 | 322.00 |
April | 371.17 | 0.53 | 0.50 | 01-APR-06:49 | 1144.36 | 20.77 | 163.67 | 347.50 | 1151.19 | 20.76 | 160.50 | 347.00 |
May | 332.17 | 0.52 | 0.50 | 01-MAY-05:00 | 1162.96 | 21.14 | 159.50 | 384.17 | 1305.67 | 20.99 | 158.17 | 385.00 |
June | 430.67 | 0.52 | 0.50 | 01-JUN-06:10 | 1137.46 | 22.13 | 215.50 | 402.33 | 1239.72 | 20.79 | 195.33 | 401.17 |
July | 439.00 | 0.53 | 0.50 | 01-JUL-05:40 | 1074.62 | 21.97 | 215.83 | 404.00 | 1171.14 | 20.74 | 190.17 | 405.83 |
August | 406.00 | 0.52 | 0.50 | 01-AUG-06:10 | 1157.18 | 21.09 | 209.17 | 380.33 | 1117.08 | 21.09 | 203.50 | 376.00 |
September | 289.17 | 0.52 | 0.50 | 01-SEP-07:40 | 1302.19 | 21.95 | 175.17 | 321.83 | 1548.92 | 22.30 | 187.33 | 324.33 |
October | 314.33 | 0.52 | 0.50 | 01-OCT-07:19 | 1053.65 | 23.27 | 198.50 | 294.50 | 1074.21 | 23.33 | 195.00 | 293.50 |
November | 258.33 | 0.53 | 0.50 | 01-NOV-07:40 | 1087.11 | 26.44 | 176.33 | 231.67 | 1085.91 | 26.19 | 173.33 | 232.00 |
December | 230.67 | 0.52 | 0.50 | 01-DEC-08:09 | 2290.13 | 30.87 | 189.83 | 224.00 | 2348.45 | 31.32 | 198.83 | 225.00 |
Annual Sum or Average | 3928.50 | 0.52 | 1252.08 | 23.20 | 2265.50 | 3798.17 | 1304.21 | 22.92 | 2228.17 | 3800.33 | ||
Minimum of Months | 230.67 | 0.52 | 0.50 | 1053.65 | 20.77 | 159.50 | 224.00 | 1074.21 | 20.74 | 158.17 | 225.00 | |
Maximum of Months | 439.00 | 0.53 | 0.50 | 2290.13 | 30.87 | 215.83 | 404.00 | 2348.45 | 31.32 | 203.50 | 405.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.752438E+11 | 135533.52 | 04-JAN-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.713773E+11 | 135533.52 | 05-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466978E+11 | 135533.52 | 06-MAR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226108E+11 | 80612.23 | 17-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.455119E+10 | 36101.64 | 08-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.783134E+09 | 24509.44 | 04-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15688333.70 | 7638.93 | 03-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46615291.22 | 10125.98 | 31-AUG-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123972E+10 | 27889.33 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146210E+11 | 56110.21 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286189E+11 | 94342.75 | 24-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.694904E+11 | 135533.52 | 10-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335296E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15688333.70 | 7638.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.752438E+11 | 135533.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378536E+11 | 53873.38 | 10-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.369201E+11 | 56648.89 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203639E+11 | 55450.45 | 07-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587147E+10 | 30293.69 | 03-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.297398E+09 | 11346.90 | 07-MAY-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2666453.89 | 5244.01 | 14-JUN-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 701862.14 | 3843.47 | 30-SEP-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263954E+10 | 22397.83 | 17-OCT-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.730769E+10 | 30768.64 | 25-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331777E+11 | 53469.53 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.378536E+11 | 56648.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.132774E+10 | 0.992979E+09 | 26731.60 | 14-MAR-13:00 | 18344.77 | 0.00 |
April | 0.00 | 0.00 | 0.140645E+09 | 0.115817E+09 | 9404.55 | 08-APR-13:00 | 7617.31 | 0.00 |
May | 0.00 | 0.00 | 0.372188E+10 | 0.295394E+10 | 84110.52 | 24-MAY-03:01 | 55323.83 | 0.00 |
June | 0.00 | 0.00 | 0.260003E+11 | 0.165815E+11 | 92207.77 | 18-JUN-03:01 | 41393.00 | 0.00 |
July | 0.00 | 0.00 | 0.513979E+11 | 0.301571E+11 | 93452.32 | 16-JUL-03:01 | 38082.45 | 0.00 |
August | 0.00 | 0.00 | 0.392312E+11 | 0.258012E+11 | 93452.32 | 14-AUG-03:01 | 37589.46 | 0.00 |
September | 0.00 | 0.00 | 0.160241E+11 | 0.997176E+10 | 90336.26 | 16-SEP-03:01 | 39662.33 | 0.00 |
October | 0.00 | 0.00 | 0.106393E+10 | 0.790814E+09 | 19235.57 | 11-OCT-17:10 | 14638.18 | 0.00 |
November | 0.00 | 0.00 | 38463700.68 | 28168392.06 | 5698.96 | 16-NOV-13:00 | 4223.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138946E+12 | 0.873933E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.513979E+11 | 0.301571E+11 | 93452.32 | 55323.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.112439E+10 | 0.843180E+09 | 38031.74 | 17-MAR-03:01 | 20069.79 | 0.00 |
April | 0.00 | 0.00 | 0.306064E+09 | 0.238873E+09 | 38031.74 | 09-APR-03:01 | 21655.51 | 0.00 |
May | 0.00 | 0.00 | 0.454191E+10 | 0.344530E+10 | 38031.74 | 29-MAY-03:32 | 18309.31 | 0.00 |
June | 0.00 | 0.00 | 0.222591E+11 | 0.138395E+11 | 42255.76 | 27-JUN-10:43 | 23241.20 | 0.00 |
July | 0.00 | 0.00 | 0.412193E+11 | 0.233494E+11 | 42255.76 | 16-JUL-02:13 | 16301.63 | 0.00 |
August | 0.00 | 0.00 | 0.313853E+11 | 0.200003E+11 | 42255.76 | 14-AUG-03:32 | 15821.28 | 0.00 |
September | 0.00 | 0.00 | 0.152661E+11 | 0.917350E+10 | 40199.66 | 16-SEP-03:01 | 16842.71 | 0.00 |
October | 0.00 | 0.00 | 0.166551E+10 | 0.116946E+10 | 38031.74 | 13-OCT-03:01 | 19980.85 | 0.00 |
November | 0.00 | 0.00 | 0.280875E+09 | 0.195441E+09 | 38031.74 | 27-NOV-04:01 | 27770.55 | 0.00 |
December | 0.00 | 0.00 | 2052784.07 | 1300799.08 | 3518.66 | 01-DEC-04:10 | 2116.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118051E+12 | 0.722562E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.412193E+11 | 0.233494E+11 | 42255.76 | 27770.55 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9852.09 | 18951.04 | 30-JAN-19:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10007.51 | 19023.67 | 10-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9961.36 | 18971.01 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9514.80 | 18398.29 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9018.24 | 17590.68 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8527.43 | 16511.11 | 01-JUN-18:23 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8048.00 | 15580.78 | 03-JUL-06:46 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 7994.39 | 15081.36 | 02-AUG-18:16 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8072.42 | 15541.95 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8424.66 | 16474.13 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8944.89 | 17479.98 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9452.20 | 18361.53 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8978.84 | ||||
Minimum of Months | 0.00 | 0.00 | 7994.39 | 15081.36 | ||
Maximum of Months | 0.00 | 0.00 | 10007.51 | 19023.67 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184094E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.27 |
February | 0.166145E+10 | 0.23 | 824.13 | 01-FEB-00:01 | 0.27 |
March | 0.186530E+10 | 0.23 | 824.13 | 01-MAR-00:01 | 0.27 |
April | 0.182376E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.27 |
May | 0.192525E+10 | 0.24 | 824.13 | 01-MAY-03:02 | 0.27 |
June | 0.196555E+10 | 0.25 | 824.13 | 01-JUN-01:13 | 0.27 |
July | 0.208783E+10 | 0.25 | 824.13 | 01-JUL-00:55 | 0.27 |
August | 0.208348E+10 | 0.25 | 824.13 | 01-AUG-00:30 | 0.27 |
September | 0.194942E+10 | 0.25 | 824.13 | 01-SEP-01:45 | 0.27 |
October | 0.191722E+10 | 0.23 | 824.13 | 01-OCT-03:01 | 0.27 |
November | 0.182240E+10 | 0.23 | 824.13 | 01-NOV-03:02 | 0.27 |
December | 0.184478E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.227874E+11 | 0.24 | |||
Minimum of Months | 0.166145E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.208783E+10 | 0.25 | 824.13 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.453761E+10 | 0.58 | 3673.81 | 04-JAN-04:15 | 0.91 |
February | 0.416082E+10 | 0.58 | 3673.81 | 05-FEB-04:03 | 0.91 |
March | 0.405737E+10 | 0.53 | 3673.81 | 06-MAR-04:10 | 0.91 |
April | 0.354421E+10 | 0.49 | 2298.74 | 01-APR-04:01 | 0.71 |
May | 0.335425E+10 | 0.46 | 2056.67 | 08-MAY-04:02 | 0.67 |
June | 0.321417E+10 | 0.46 | 3673.81 | 18-JUN-03:01 | 0.89 |
July | 0.337213E+10 | 0.47 | 3673.81 | 05-JUL-03:01 | 0.89 |
August | 0.332306E+10 | 0.46 | 3673.81 | 07-AUG-03:01 | 0.89 |
September | 0.320368E+10 | 0.46 | 3673.81 | 15-SEP-03:01 | 0.89 |
October | 0.351825E+10 | 0.47 | 2382.09 | 30-OCT-04:01 | 0.73 |
November | 0.364134E+10 | 0.50 | 2649.40 | 19-NOV-06:48 | 0.77 |
December | 0.444041E+10 | 0.57 | 3673.81 | 10-DEC-04:10 | 0.91 |
Annual Sum or Average | 0.443673E+11 | 0.50 | |||
Minimum of Months | 0.320368E+10 | 0.46 | 2056.67 | 0.67 | |
Maximum of Months | 0.453761E+10 | 0.58 | 3673.81 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.190526E+10 | 0.53 | 1265.16 | 10-JAN-05:03 | 0.80 |
February | 0.175123E+10 | 0.54 | 1296.11 | 06-FEB-05:02 | 0.81 |
March | 0.171374E+10 | 0.50 | 1661.17 | 15-MAR-03:01 | 0.90 |
April | 0.150531E+10 | 0.48 | 1661.17 | 09-APR-03:01 | 0.90 |
May | 0.150369E+10 | 0.47 | 1661.17 | 11-MAY-03:01 | 0.90 |
June | 0.158765E+10 | 0.51 | 1661.17 | 01-JUN-03:11 | 0.90 |
July | 0.190680E+10 | 0.56 | 1661.17 | 01-JUL-03:01 | 0.90 |
August | 0.172397E+10 | 0.54 | 1661.17 | 01-AUG-03:01 | 0.90 |
September | 0.151490E+10 | 0.50 | 1661.17 | 01-SEP-03:01 | 0.90 |
October | 0.152501E+10 | 0.48 | 1661.17 | 01-OCT-03:01 | 0.90 |
November | 0.152120E+10 | 0.48 | 1661.17 | 05-NOV-03:01 | 0.90 |
December | 0.185339E+10 | 0.52 | 1260.66 | 26-DEC-05:03 | 0.80 |
Annual Sum or Average | 0.200122E+11 | 0.51 | |||
Minimum of Months | 0.150369E+10 | 0.47 | 1260.66 | 0.80 | |
Maximum of Months | 0.190680E+10 | 0.56 | 1661.17 | 0.90 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.98 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 47.22 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.75 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.81 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:05 | 5.36 | 5.36 | 51.39 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 52.15 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 52.42 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.56 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.58 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.85 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.68 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.86 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 46.75 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.58 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.98 | 59.93 | 9852.09 | 18951.04 | 30-JAN-19:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 47.22 | 59.18 | 10007.51 | 19023.67 | 10-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.75 | 59.64 | 9961.36 | 18971.01 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.03 | 49.03 | 9514.80 | 18398.29 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.47 | 49.47 | 9018.24 | 17590.68 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.06 | 50.06 | 8527.43 | 16511.11 | 01-JUN-18:23 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.17 | 50.17 | 8048.00 | 15580.78 | 03-JUL-06:46 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.43 | 50.43 | 7994.39 | 15081.36 | 02-AUG-18:16 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.07 | 51.07 | 8072.42 | 15541.95 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.52 | 48.52 | 8424.66 | 16474.13 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.19 | 50.19 | 8944.89 | 17479.98 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.86 | 59.82 | 9452.20 | 18361.53 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 8978.84 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.75 | 48.52 | 7994.39 | 15081.36 | ||
Maximum of Months | 0.00 | 0.00 | 51.07 | 59.93 | 10007.51 | 19023.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.453761E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.416082E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.446327E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.359141E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.453714E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.106738E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.175303E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.144315E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.793703E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.386561E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.365442E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.444041E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.838233E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.359141E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175303E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.190526E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.175123E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.200421E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.159336E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.274075E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.703021E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.115773E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.927734E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.534630E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.198752E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.160189E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.185402E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.486694E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159336E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.115773E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.453761E+10 | 0.00 | 0.752438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.416082E+10 | 0.00 | 0.713773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405737E+10 | 0.132774E+10 | 0.466978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354421E+10 | 0.140645E+09 | 0.226108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335425E+10 | 0.372017E+10 | 0.455119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.321417E+10 | 0.259325E+11 | 0.783134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337213E+10 | 0.512346E+11 | 15688333.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.332306E+10 | 0.391201E+11 | 46615291.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.320368E+10 | 0.159761E+11 | 0.123972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351825E+10 | 0.106393E+10 | 0.146210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364134E+10 | 38463700.68 | 0.286189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444041E+10 | 0.00 | 0.694904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443673E+11 | 0.138554E+12 | 0.335296E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.320368E+10 | 0.00 | 15688333.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.453761E+10 | 0.512346E+11 | 0.752438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.190526E+10 | 0.00 | 0.378536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175123E+10 | 0.00 | 0.369201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171374E+10 | 0.112250E+10 | 0.203639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150531E+10 | 0.306064E+09 | 0.587147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150369E+10 | 0.453420E+10 | 0.297398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158765E+10 | 0.221967E+11 | 2666453.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190680E+10 | 0.410056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172397E+10 | 0.312758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151490E+10 | 0.152229E+11 | 701862.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152501E+10 | 0.165744E+10 | 0.263954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152120E+10 | 0.279323E+09 | 0.730769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185339E+10 | 2052784.07 | 0.331777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200122E+11 | 0.117603E+12 | 0.144435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190680E+10 | 0.410056E+11 | 0.378536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.453761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.416082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405737E+10 | 0.00 | 0.00 | 0.00 | 0.405903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354421E+10 | 0.00 | 0.00 | 0.00 | 47198476.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335425E+10 | 0.00 | 0.00 | 0.00 | 0.118289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.321417E+10 | 0.00 | 0.00 | 0.00 | 0.745961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337213E+10 | 0.00 | 0.00 | 0.00 | 0.141582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.332306E+10 | 0.00 | 0.00 | 0.00 | 0.111085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.320368E+10 | 0.00 | 0.00 | 0.00 | 0.473335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351825E+10 | 0.00 | 0.00 | 0.00 | 0.347359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364134E+10 | 0.00 | 0.00 | 0.00 | 13078576.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443673E+11 | 0.00 | 0.00 | 0.00 | 0.394560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.320368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.453761E+10 | 0.00 | 0.00 | 0.00 | 0.141582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.190526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171374E+10 | 0.00 | 0.00 | 0.00 | 0.290470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150531E+10 | 0.00 | 0.00 | 0.00 | 88051289.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150369E+10 | 0.00 | 0.00 | 0.00 | 0.123706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158765E+10 | 0.00 | 0.00 | 0.00 | 0.544256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190680E+10 | 0.00 | 0.00 | 0.00 | 0.967047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172397E+10 | 0.00 | 0.00 | 0.00 | 0.755336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151490E+10 | 0.00 | 0.00 | 0.00 | 0.383140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152501E+10 | 0.00 | 0.00 | 0.00 | 0.462510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152120E+10 | 0.00 | 0.00 | 0.00 | 80693061.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185339E+10 | 0.00 | 0.00 | 0.00 | 620934.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200122E+11 | 0.00 | 0.00 | 0.00 | 0.286572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190680E+10 | 0.00 | 0.00 | 0.00 | 0.967047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.743235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231271E+11 | 0.00 | 0.00 | 3.57 |
February | 0.653288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257178E+11 | 0.00 | 0.00 | 3.58 |
March | 0.639885E+11 | 5852295.62 | 0.00 | 4277838.26 | 0.00 | 0.978063E+10 | 0.138818E+10 | 0.00 | 3.56 |
April | 0.512110E+11 | 0.00 | 0.00 | 3348998.08 | 0.00 | 0.163408E+10 | 0.312278E+10 | 0.00 | 3.59 |
May | 0.260357E+11 | 54619607.03 | 0.00 | 31313358.76 | 0.00 | 22693568.18 | 0.147200E+11 | 0.00 | 3.73 |
June | 0.881125E+10 | 0.302013E+10 | 0.00 | 61627564.33 | 3853348.86 | 3062219.47 | 0.143680E+11 | 0.00 | 3.93 |
July | 0.278216E+10 | 0.920063E+10 | 0.00 | 49160551.64 | 51342345.13 | 0.00 | 0.648719E+10 | 0.00 | 3.99 |
August | 0.434043E+10 | 0.476218E+10 | 0.00 | 71871844.34 | 23174661.73 | 0.00 | 0.117079E+11 | 0.00 | 3.96 |
September | 0.128558E+11 | 0.775006E+09 | 0.00 | 57253706.70 | 1196885.35 | 2980961.96 | 0.173330E+11 | 0.00 | 3.93 |
October | 0.440400E+11 | 0.00 | 0.00 | 11170741.67 | 0.00 | 78947009.04 | 0.786965E+10 | 0.00 | 3.63 |
November | 0.569608E+11 | 0.00 | 0.00 | 1426554.22 | 0.00 | 0.149347E+10 | 0.216274E+10 | 0.00 | 3.57 |
December | 0.740842E+11 | 0.00 | 0.00 | 12970.24 | 0.00 | 0.191369E+11 | 51764287.79 | 0.00 | 3.58 |
Annual Sum or Average | 0.484762E+12 | 0.178184E+11 | 0.00 | 0.291464E+09 | 79567241.07 | 0.809977E+11 | 0.792112E+11 | 0.00 | 3.72 |
Minimum of Months | 0.278216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
Maximum of Months | 0.743235E+11 | 0.920063E+10 | 0.00 | 71871844.34 | 51342345.13 | 0.257178E+11 | 0.173330E+11 | 0.00 | 3.99 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.790127E+11 | 0.00 | 0.00 | 47274.48 | 0.144577E+09 | 53629458.85 | 0.116848E+09 | 0.00 | 7.92 |
February | 0.738932E+11 | 0.00 | 0.00 | 58235.65 | 96050273.05 | 48389345.89 | 0.220841E+09 | 0.00 | 7.98 |
March | 0.579539E+11 | 0.00 | 2408295.21 | 7763366.71 | 27598206.96 | 24052573.95 | 0.448967E+10 | 408.63 | 7.61 |
April | 0.392266E+11 | 0.00 | 0.00 | 10358797.47 | 0.00 | 3050968.40 | 0.974686E+10 | 0.00 | 7.46 |
May | 0.136499E+11 | 0.00 | 0.00 | 58079336.08 | 0.00 | 0.00 | 0.277985E+11 | 0.00 | 7.48 |
June | 0.376321E+10 | 0.196689E+10 | 0.00 | 86443545.97 | 0.00 | 0.00 | 0.209811E+11 | 0.00 | 7.80 |
July | 0.529365E+09 | 0.562758E+10 | 0.00 | 81314499.29 | 0.00 | 0.00 | 0.112608E+11 | 0.00 | 8.29 |
August | 0.659920E+09 | 0.280792E+10 | 0.00 | 0.100655E+09 | 0.00 | 0.00 | 0.182703E+11 | 0.00 | 7.99 |
September | 0.522952E+10 | 0.338652E+09 | 0.00 | 81889034.30 | 0.00 | 0.00 | 0.252821E+11 | 0.00 | 7.67 |
October | 0.265620E+11 | 0.00 | 0.00 | 24920682.92 | 0.00 | 0.00 | 0.200231E+11 | 0.00 | 7.44 |
November | 0.434612E+11 | 0.00 | 0.00 | 6338037.39 | 0.00 | 2702496.44 | 0.678376E+10 | 0.00 | 7.46 |
December | 0.746999E+11 | 0.00 | 0.00 | 210914.87 | 63083151.72 | 30604760.64 | 0.309934E+09 | 0.00 | 7.87 |
Annual Sum or Average | 0.418641E+12 | 0.107410E+11 | 2408295.21 | 0.458079E+09 | 0.331309E+09 | 0.162430E+09 | 0.145284E+12 | 408.63 | 7.75 |
Minimum of Months | 0.529365E+09 | 0.00 | 0.00 | 47274.48 | 0.00 | 0.00 | 0.116848E+09 | 0.00 | 7.44 |
Maximum of Months | 0.790127E+11 | 0.562758E+10 | 2408295.21 | 0.100655E+09 | 0.144577E+09 | 53629458.85 | 0.277985E+11 | 408.63 | 8.29 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.245296E+11 | 0.159822E+11 | 0.281290E+12 | 0.00 | 0.395386E+11 |
February | 0.495781E+11 | 0.157192E+11 | 0.261381E+12 | 0.00 | 0.379616E+11 |
March | 0.819208E+11 | 0.135970E+11 | 0.227103E+12 | 72697032.27 | 0.348090E+11 |
April | 0.103930E+12 | 0.116063E+11 | 0.182172E+12 | 0.135272E+09 | 0.249319E+11 |
May | 0.135046E+12 | 0.962746E+10 | 0.149800E+12 | 0.116862E+10 | 0.334710E+11 |
June | 0.153651E+12 | 0.678489E+10 | 0.879637E+11 | 0.165270E+10 | 0.836994E+11 |
July | 0.140301E+12 | 0.371902E+10 | 0.285277E+11 | 0.526754E+09 | 0.140682E+12 |
August | 0.116212E+12 | 0.478025E+10 | 0.648505E+11 | 0.115961E+10 | 0.112817E+12 |
September | 0.832007E+11 | 0.601288E+10 | 0.113557E+12 | 0.182798E+10 | 0.613539E+11 |
October | 0.508002E+11 | 0.904008E+10 | 0.174153E+12 | 0.585522E+09 | 0.241507E+11 |
November | 0.211785E+11 | 0.989853E+10 | 0.189381E+12 | 64405101.55 | 0.217197E+11 |
December | 0.213906E+11 | 0.152866E+11 | 0.269218E+12 | 0.00 | 0.364790E+11 |
Annual Sum or Average | 0.981739E+12 | 0.122054E+12 | 0.202940E+13 | 0.719357E+10 | 0.651614E+12 |
Minimum of Months | 0.211785E+11 | 0.371902E+10 | 0.285277E+11 | 0.00 | 0.217197E+11 |
Maximum of Months | 0.153651E+12 | 0.159822E+11 | 0.281290E+12 | 0.182798E+10 | 0.140682E+12 |