Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:25:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1665.78 | 3258.87 | 3258.87 |
Net Site Energy | 1665.78 | 3258.87 | 3258.87 |
Total Source Energy | 3556.69 | 6958.17 | 6958.17 |
Net Source Energy | 3556.69 | 6958.17 | 6958.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 29.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.42 | 326.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 53.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 840.61 | 825.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 29.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 79.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 50.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 106.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.42 | 326.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 29.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 79.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 50.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 106.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.42 | 326.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 53.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 148.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 512.61 | 695.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 983.74 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1644.53 | 1614.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 148.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 512.61 | 695.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 983.74 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1644.53 | 1614.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 840.607 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 840.607 | 100.00 |
Total On-Site and Utility Electric Sources | 840.607 | 100.00 |
Total Electricity End Uses | 840.607 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4394.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 7.7280 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.0598 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.7280 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.0598 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.0912 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-11:09 | 08-JAN-06:40 | - | - | - | - | - | - | - | - | - | - | 03-JAN-07:00 |
Heating | 0.00 | 44407.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27319.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22726.43 | 11766.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3018.35 | 14849.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2014.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 64441.92 | 71023.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 44407.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27319.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21698.93 | 11766.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3018.35 | 14849.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 775.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1045.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 31.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 250.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 158.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1423.36 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 338.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.86 | 353.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 169.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2662.20 | 894.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 490.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 310.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 662.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.30 | 691.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 330.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5208.23 | 1749.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 62.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 490.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 310.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 662.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.30 | 691.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 330.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5208.23 | 1749.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.57 |
KITCHEN DIRECT AIR | 1.55 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 1.00 | 1.00 | 3.57 |
PSZ-AC_2:2 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.00 | 1.00 | 1.55 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.57 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.55 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.57 | 6105.56 |
PSZ-AC_2:2_ADDAQ FAN | 1.55 | 1661.84 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.57 | 3.57 | 3.57 | 2.36 | 73727.89 | 107821.38 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.55 | 1.55 | 1.55 | 1.03 | 33657.18 | 68279.29 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.57 | 1.79 | 2.38 | 73727.89 | 36863.94 | 0.763980 | 0.763980 |
PSZ-AC_2:2 COOLING COIL | 1.55 | 0.776525 | 1.04 | 33657.18 | 16828.59 | 0.745830 | 0.745830 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 107821.38 |
PSZ-AC_2:2 HEATING COIL | 68279.29 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 7.728 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 72.655 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.060 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1069.700 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2872.862 | 7.728 | 10.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2872.862 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1262.985 | 9.060 | 167.774 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1262.985 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.9751 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7915 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27839538E-12 | 0.12950115E-14 | -0.82783828E-13 | 0.80678130E-16 |
34 | 6 | 0.26299694E-07 | 0.26708830E-09 | 0.60445363E-08 | -0.12251052E-12 |
35 | 5 | -0.17799163E-03 | 0.23219762E-05 | -0.91701172E-04 | 0.59820023E-08 |
36 | 4 | 0.27786041 | 0.11458868E-02 | 0.94550742E-01 | -0.31566594E-04 |
37 | 3 | -6.9831405 | 0.35936545E-01 | -2.2549003 | 0.27621946E-01 |
38 | 2 | 39.936893 | 0.12912992 | 14.919868 | -0.32293676 |
39 | 1 | -79.829560 | 0.58809255E-01 | -28.831988 | 1.0633567 |
40 | 0 | 46.824343 | 0.11937857E-02 | 16.298779 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.449_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.449_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.449_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.552 | 2.552 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.67979E-002 | 0.16139 | 0.61739 | 0.61739 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12139 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.8898E-004 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.9713E-003 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.8440E-004 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.3052E-003 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.4870E-004 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.1330E-003 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 7.5380E-004 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.9092E-003 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2395E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.2853E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.5730E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.6274E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.0013E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.0220E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0806E-003 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.0808E-003 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0578E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0635E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.0529E-003 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.7749E-004 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.9515E-003 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.1777E-004 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.9092E-003 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.5380E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 40196.43394 | 48235.72073 | 2.97786 | 3.57343 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30000 | 8.23349E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 4711.39309 | 5653.67171 | 0.20577 | 1.33138 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | 3.80000 | 5.05843E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20584.16172 | 24700.99406 | 1.29421 | 1.55305 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 3.80000 | 5.05843E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 59045.44 | 3.57343 | 3.57343 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 57233.57 | 1.33138 | 1.33138 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 30827.05 | 1.55305 | 1.55305 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 52316.77 | 1.21700 | 1.21700 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.57343 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.55305 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.57343 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.57343 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.57343 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.57343 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.57343 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.57343 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.55305 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55305 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.55305 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.55305 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.55305 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.55305 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.57343 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.55305 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.57343 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.57343 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6105.56179 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.57343 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.57343 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.57343 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.35847 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.57343 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.78672 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.38229 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 73727.89000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36863.94500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76398 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76398 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 73727.89000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 107821.37659 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 107821.37659 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.55305 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.55305 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1661.83594 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.55305 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.55305 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.55305 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02501 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.55305 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77652 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03537 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33657.18000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16828.59000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74583 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74583 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33657.18000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68279.28574 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 68279.28574 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 71150.2 | 10.47 | 10.42 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 32541.0 | 11.59 | 11.53 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.975 | 0.851 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_EAST_0.25 | N/A | 2.552 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.975 | 0.851 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_SOUTH_0.25 | N/A | 2.552 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.975 | 0.851 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | N/A | 2.552 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.975 | 0.851 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.975 | 0.851 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.975 | 0.851 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 5.9222272638E-002 | 0.2227282119 | Pass | Pass | 4.9496174128E-002 | 0.1324679694 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2251125336 | 0.5535505786 | Pass | Pass | 6.3409860185E-002 | 0.3591625647 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2658127390 | 0.3108948384 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1316.94 | 120.99 | 1498.46 | 21.87 | 667.00 | 3625.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.851 | 0.975 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.851 | 0.975 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.851 | 0.975 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.851 | 0.975 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.851 | 0.975 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.851 | 0.975 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.449_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.552 | 0.251 | 0.276 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.449_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.552 | 0.251 | 0.276 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.449_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.552 | 0.251 | 0.276 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.552 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.552 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.7280 | 371.75 | 2872.86 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 61.05 | 0.0000 | Y | 32.92 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.0598 | 139.41 | 1262.99 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.59 | 0.0000 | Y | 17.21 |
Interior Lighting Total | 8.0912 | 511.15 | 4135.85 | 50.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 49.14 | 49.14 | 1.95 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.75 | 62.95 | 23.66 | |
Exterior Lighting Total | 2213.72 | 25.61 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 73727.89 | 56326.63 | 17401.26 | 0.76 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33657.18 | 25102.53 | 8554.65 | 0.75 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 71150.2 | 10.47 | 10.42 | ||||
PSZ-AC_2:2 COOLING COIL | 32541.0 | 11.59 | 11.53 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 107821.38 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 68279.29 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.57 | 6105.56 | 1708.60 | 1.00 | 1.19 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.55 | 1661.84 | 1070.05 | 1.00 | 1.36 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 40196.43 | 48235.72 | 129.75 | 2.978 | 3.573 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 23.99 | 0.00993 | 31.30 | 0.00823 | 1.331 | 0.00 |
KITCHEN | 20584.16 | 24700.99 | 177.19 | 1.294 | 1.553 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.01036 | 30.50 | 0.00823 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 4711.39 | 5653.67 | 15.21 | 0.206 | 1.331 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 23.46 | 0.00425 | 3.80 | 0.00506 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.57 | 3.57 | 1.33 | 1.33 | 3.5734 | 3.5734 | 3.5734 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.55 | 1.55 | 1.22 | 1.22 | 1.5530 | 1.5530 | 1.5530 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 73727.890 | 56326.633 | 3.573430 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 36863.94 | 32644.30 | 2.382287 | 26.71 | 17.79 | 0.00929652 | 11.39 | 11.34 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 55.8865 | 23.99 | 0.00992777 | 52.3563 | 40196.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 107821.377 | 107821.377 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | 107821.38 | 107821.38 | 3.573433 | 14.59 | 10.92 | 0.00676731 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 37.2577 | 21.00 | 0.00778207 | 49.3911 | 4703.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 33657.180 | 25102.535 | 1.553050 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 16828.59 | 16393.15 | 1.035367 | 29.51 | 18.23 | 0.00869305 | 11.91 | 11.56 | 0.00850000 | 30.50 | 0.00823222 | 18.19 | 117.5431 | 25.99 | 0.01036199 | 48.4851 | 20584.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 68279.286 | 68279.286 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 68279.29 | 68279.29 | 1.553049 | 2.98 | 2.98 | 0.00488398 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 78.3621 | 23.46 | 0.00425219 | 23.3690 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 73727.890 | 56326.633 | 3.573430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1218 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.573433 | 4.22300711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 36863.94 | 32644.30 | 1.0000 | 2.81533555 | 2.382287 | 26.71 | 17.79 | 0.00929652 | 50555.2 | 11.39 | 11.34 | 0.00850000 | 32878.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36863.94 | 31.30 | 0.00823349 | 18.45 | 1.33137743 | 55.8865 | 23.99 | 0.00992777 | 23.99 | 0.00992777 | 52.3563 | 40196.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 107821.377 | 107821.377 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.573433 | 4.22300711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | Sensible | 107821.38 | 107821.38 | 1.0000 | 4.22300711 | 3.573433 | 14.59 | 10.92 | 0.00676731 | 31770.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 107821.38 | 3.80 | 0.00505843 | 3.80 | 1.33137743 | 37.2577 | 21.00 | 0.00778207 | 21.00 | 0.00778207 | 49.3911 | 4703.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33657.180 | 25102.535 | 1.553050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0000 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.553049 | 1.83536028 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 16828.59 | 16393.15 | 1.0000 | 1.22357424 | 1.035367 | 29.51 | 18.23 | 0.00869305 | 51875.6 | 11.91 | 11.56 | 0.00850000 | 33417.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16828.59 | 30.50 | 0.00823222 | 18.19 | 1.21700195 | 117.5431 | 25.95 | 0.01036199 | 25.99 | 0.01036199 | 48.4851 | 20584.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68279.286 | 68279.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.553049 | 1.83536028 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 68279.29 | 68279.29 | 1.0000 | 1.83536028 | 1.553049 | 2.98 | 2.98 | 0.00488398 | 15233.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68279.29 | 3.80 | 0.00505843 | 3.80 | 1.21700195 | 78.3621 | 0.00 | 0.00425219 | 23.46 | 0.00425219 | 23.3690 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.57 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3440.83 | 3667.67 | 775.17 |
KITCHEN | 6199.33 | 5084.83 | 4349.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6242.67 | 6986.83 | 4394.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 1.17 | 0.00 | 0.00 |
KITCHEN | 0.00 | 141.33 | 0.00 | 0.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 142.00 | 0.00 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.703 | 0.915 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.015 | 0.022 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.163 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.560 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 38175282.44 | 0.00 | 38175282.44 | 7356357.85 | 45531640.29 | 41986318.57 | 1456.53 | 4381.30 | 2922.17 | 169.83 |
KITCHEN | 27768675.23 | 0.00 | 27768675.23 | 95086.41 | 27863761.63 | 38379373.44 | 8576.74 | 129.15 | 54.11 | 624.08 |
Total Facility | 65943957.66 | 0.00 | 65943957.66 | 7451444.26 | 73395401.92 | 80365692.01 | 8583.84 | 4400.97 | 2948.28 | 642.24 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.4518 | 0.0000 | 1.4518 | 0.2824 | 1.7343 | 1.3314 | 0.00 | 4269.28 | 2917.72 |
KITCHEN | 1.0367 | 0.0000 | 1.0367 | 0.0025 | 1.0391 | 1.2170 | 7013.01 | 129.00 | 44.99 |
Total Facility | 2.4885 | 0.0000 | 2.4885 | 0.2849 | 2.7734 | 2.5484 | 7013.01 | 4288.84 | 2936.69 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 53315778.94 | 0.00 | 53315778.94 | 41986318.57 | 1456.51 | 0.00 | 7303.49 | 169.80 |
PSZ-AC_2:2 | 38781748.30 | 0.00 | 38781748.30 | 38379373.44 | 1428.68 | 1.50 | 7329.82 | 624.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 2.0276 | 0.0000 | 2.0276 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4478 | 0.0000 | 1.4478 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 2543.74 | 448.80 | 4364.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 300.38 | 1088.63 | 6422.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.3059 | 2.0821 | 1.8597 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7082 | 1.4742 | 1.4426 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
Electricity:Building | 506.50 | 2873.83 | 01-JAN-01:20 | 28793.81 | 25-JAN-11:10 |
Electricity:Zone:DINING | 158.03 | 560.03 | 01-JAN-01:20 | 8723.27 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 499.57 | 2737.55 | 01-JAN-01:20 | 26650.71 | 25-JAN-11:10 |
InteriorLights:Electricity | 50.13 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 32.93 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 50.13 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 50.13 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 32.93 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 50.13 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 348.47 | 2313.80 | 01-JAN-01:20 | 20370.03 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.33 | 2147.51 | 01-JAN-01:10 | 17341.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 53.41 | 866.00 | 06-JAN-23:30 | 3219.34 | 15-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 122.34 | 1040.61 | 24-NOV-01:10 | 6475.44 | 19-AUG-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 15.00 | 0.00 | 01-JAN-11:10 | 1508.59 | 03-OCT-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 31.47 | 765.10 | 06-FEB-05:20 | 1076.23 | 12-JAN-14:10 |
ElectricityPurchased:Facility | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
ElectricityPurchased:Plant | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
Cogeneration:ElectricityPurchased | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
General:Cogeneration:ElectricityPurchased | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
ElectricityNet:Plant | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
Cogeneration:ElectricityNet | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
General:Cogeneration:ElectricityNet | 840.61 | 5101.97 | 30-MAR-00:30 | 64441.92 | 16-OCT-11:10 |
Electricity:HVAC | 186.15 | 0.00 | 01-JAN-01:10 | 34552.12 | 16-OCT-11:10 |
Fans:Electricity | 106.97 | 0.00 | 01-JAN-01:10 | 7232.58 | 16-OCT-11:10 |
General:Fans:Electricity | 106.97 | 0.00 | 01-JAN-01:10 | 7232.58 | 16-OCT-11:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 79.18 | 0.00 | 01-JAN-00:10 | 27319.54 | 16-OCT-11:10 |
General:Cooling:Electricity | 79.18 | 0.00 | 01-JAN-00:10 | 27319.54 | 16-OCT-11:10 |
ExteriorLights:Electricity | 25.61 | 0.00 | 01-JAN-07:00 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.61 | 0.00 | 01-JAN-07:00 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4741.75 | 08-MAR-07:20 |
Water Heater:WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4741.75 | 08-MAR-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-FEB-13:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-FEB-13:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 825.17 | 2758.01 | 01-JAN-01:10 | 71023.90 | 08-JAN-06:40 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 29.38 | 0.00 | 01-JAN-01:10 | 47195.98 | 08-JAN-07:00 |
Heating:NaturalGas | 29.38 | 0.00 | 01-JAN-01:10 | 47195.98 | 08-JAN-07:00 |
General:Heating:NaturalGas | 29.38 | 0.00 | 01-JAN-01:10 | 47195.98 | 08-JAN-07:00 |
NaturalGas:Plant | 326.00 | 947.76 | 01-JAN-01:10 | 23334.50 | 10-FEB-07:50 |
WaterSystems:NaturalGas | 326.00 | 947.76 | 01-JAN-01:10 | 23334.50 | 10-FEB-07:50 |
Water Heater:WaterSystems:NaturalGas | 326.00 | 947.76 | 01-JAN-01:10 | 23334.50 | 10-FEB-07:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 01-MAR-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1341.09 | 2943.75 | 27-DEC-01:10 | 154220.97 | 16-OCT-11:10 |
EnergyTransfer:Building | 723.84 | 1471.87 | 27-DEC-01:10 | 51671.57 | 16-OCT-11:10 |
EnergyTransfer:Zone:KITCHEN | 427.15 | 1471.87 | 27-DEC-01:10 | 24568.65 | 27-OCT-04:10 |
Refrigeration:EnergyTransfer | 151.08 | 2701.32 | 06-JAN-23:30 | 7834.84 | 17-JAN-04:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.54 | 1350.66 | 06-JAN-23:30 | 3917.42 | 17-JAN-04:40 |
General:Refrigeration:EnergyTransfer | 75.54 | 1350.66 | 06-JAN-23:30 | 3917.42 | 17-JAN-04:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.54 | 1350.66 | 06-JAN-23:30 | 3917.42 | 17-JAN-04:40 |
EnergyTransfer:Plant | 303.58 | 1471.87 | 27-DEC-01:10 | 17249.89 | 13-FEB-19:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.34 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 63.20 | 1305.30 | 06-FEB-05:20 | 2238.70 | 12-JAN-14:10 |
EnergyTransfer:Zone:DINING | 296.69 | 0.00 | 01-JAN-01:10 | 32211.38 | 16-OCT-12:00 |
Heating:EnergyTransfer | 0.02 | 0.00 | 01-JAN-00:10 | 2496.30 | 30-MAR-03:10 |
Heating:EnergyTransfer:Zone:DINING | 0.02 | 0.00 | 01-JAN-00:10 | 2496.30 | 30-MAR-03:10 |
General:Heating:EnergyTransfer | 0.02 | 0.00 | 01-JAN-00:10 | 2496.30 | 30-MAR-03:10 |
General:Heating:EnergyTransfer:Zone:DINING | 0.02 | 0.00 | 01-JAN-00:10 | 2496.30 | 30-MAR-03:10 |
Cooling:EnergyTransfer | 648.28 | 0.00 | 01-JAN-01:10 | 49083.54 | 16-OCT-12:00 |
Cooling:EnergyTransfer:Zone:DINING | 296.67 | 0.00 | 01-JAN-01:10 | 32211.38 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer | 648.28 | 0.00 | 01-JAN-01:10 | 49083.54 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:DINING | 296.67 | 0.00 | 01-JAN-01:10 | 32211.38 | 16-OCT-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 351.60 | 0.00 | 01-JAN-01:10 | 20716.57 | 27-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 351.60 | 0.00 | 01-JAN-01:10 | 20716.57 | 27-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 228.03 | 0.00 | 01-JAN-01:10 | 14640.62 | 26-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 228.03 | 0.00 | 01-JAN-01:10 | 14640.62 | 26-JAN-07:20 |
WaterSystems:PlantLoopHeatingDemand | 228.03 | 0.00 | 01-JAN-01:10 | 14640.62 | 26-JAN-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 228.03 | 0.00 | 01-JAN-01:10 | 14640.62 | 26-JAN-07:20 |
EnergyTransfer:HVAC | 313.67 | 0.00 | 01-JAN-01:10 | 90462.24 | 16-OCT-11:10 |
HeatingCoils:EnergyTransfer | 23.51 | 0.00 | 01-JAN-01:10 | 37756.79 | 08-JAN-07:00 |
CoolingCoils:EnergyTransfer | 290.16 | 0.00 | 01-JAN-00:10 | 90462.24 | 16-OCT-11:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 228.03 | 0.00 | 01-JAN-01:10 | 14640.62 | 26-JAN-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 228.03 | 0.00 | 01-JAN-01:10 | 14640.62 | 26-JAN-07:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.018 | -296.672 | 0.000 | 0.000 | 216.296 | 32.925 | 93.832 | 37.661 | 0.000 | 0.930 | 0.000 | 0.000 | -18.035 | 0.000 | -56.415 | -10.541 |
KITCHEN | 0.000 | 0.000 | 0.000 | -351.593 | 0.000 | 0.000 | 5.061 | 17.209 | 286.918 | 0.000 | 0.000 | 0.005 | 43.586 | 0.000 | 0.000 | 0.000 | -1.186 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.462 | 44.721 | 0.000 | 0.000 | 0.000 | -55.183 | -0.000 |
Total Facility | 0.000 | 0.000 | 0.018 | -648.265 | 0.000 | 0.000 | 221.357 | 50.134 | 380.750 | 37.661 | 0.000 | 11.397 | 88.307 | 0.000 | -18.035 | 0.000 | -112.784 | -10.541 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 30-SEP-03:01 | 0.00 | 0.00 | 0.00 | -66006.50 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 65542.52 | 0.00 | -512.67 | 0.00 | -3.38 | 0.00 |
KITCHEN | 27-OCT-03:01 | 0.00 | 0.00 | 0.00 | -58381.40 | 0.00 | 0.00 | 0.00 | 30.01 | 3472.64 | 0.00 | 0.00 | 0.00 | 55066.29 | 0.00 | -0.00 | 0.00 | -187.54 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-OCT-03:01 | 0.00 | 0.00 | 0.00 | -108425.75 | 0.00 | 0.00 | 0.00 | 110.04 | 4372.65 | 0.00 | 0.00 | 1216.73 | 103977.72 | 0.00 | -1146.63 | 0.00 | -104.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 30-MAR-04:01 | 0.00 | 0.00 | 12299.20 | 0.00 | 0.00 | 0.00 | 1179.04 | 80.03 | 2169.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1739.52 | 0.00 | -110.61 | -13878.03 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-MAR-04:01 | -24338.48 | 24338.48 | 12299.20 | -24338.48 | 0.00 | 0.00 | 1201.60 | 110.04 | 9082.62 | 0.00 | 0.00 | 589.69 | 2990.81 | 0.00 | -1739.52 | 0.00 | -195.96 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.5734 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.5734 | 0.3726 | 1.0000 | Not calculated | 1.3314 | 0.3726 | ||
PSZ-AC_2:2 | 1.5530 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5530 | 0.1176 | 1.0000 | Not calculated | 0.1826 | 0.1176 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.5734 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.5734 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3726 | ||
PSZ-AC_2:2 | 1.5530 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5530 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1176 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5734 | 3.5734 | 3.5734 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5530 | 1.5530 | 1.5530 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.5734 | 3.5734 | 3.5734 | 3.5734 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5530 | 1.5530 | 1.5530 | 1.5530 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5734 | 3.5734 | 3.5734 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5530 | 1.5530 | 1.5530 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.5734 | 3.5734 | 3.5734 | 3.5734 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5530 | 1.5530 | 1.5530 | 1.5530 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 29.38 | 47195.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 79.18 | 27319.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 50.13 | 3339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.61 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 106.97 | 7232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.42 | 4741.75 | 326.00 | 23334.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.00 | 1508.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.47 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 502.84 | 840.61 |
Natural Gas | 469.79 | 825.17 |
Additional | 0.00 | 0.00 |
Total | 972.63 | 1665.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.08 |
Space Heating | 0.00 |
Space Cooling | 154.90 |
Fans (All) | 209.28 |
Service Water Heating | 147.55 |
Receptacle Equipment | 879.26 |
Miscellaneous (All) | 1644.53 |
Subtotal | 1644.53 |
Natural Gas [MJ/m2] | |
Space Heating | 57.49 |
Service Water Heating | 637.78 |
Miscellaneous (All) | 1614.34 |
Subtotal | 1614.34 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.01 |
Space Heating | 1.76 |
Space Cooling | 4.75 |
Fans (All) | 6.42 |
Service Water Heating | 24.10 |
Receptacle Equipment | 55.18 |
Miscellaneous | 4.77 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7725.17 | 1031.50 | 3.33 | 0.00 | 0.00 |
ATTIC | 6166.83 | 820.67 | 697.00 | 985.00 | 90.50 |
Min | 6166.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1031.50 | 697.00 | 985.00 | 90.50 |
Average | 7550.67 | 617.39 | 233.44 | 328.33 | 30.17 |
Sum | 22652.00 | 1852.17 | 700.33 | 985.00 | 90.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7955.83 | 804.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 3931.83 | 4828.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 6203.17 | 1254.17 | 430.33 | 449.00 | 423.33 |
Min | 3931.83 | 804.17 | 0.00 | 0.00 | 0.00 |
Max | 7955.83 | 4828.17 | 430.33 | 449.00 | 423.33 |
Average | 6030.28 | 2295.50 | 143.44 | 149.67 | 141.11 |
Sum | 18090.83 | 6886.50 | 430.33 | 449.00 | 423.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 737083.67 | 87138.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7823.83 | 11409.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 737083.67 | 87138.33 | 0.00 | 0.00 | 0.00 |
Average | 248302.50 | 32849.17 | 0.00 | 0.00 | 0.00 |
Sum | 744907.50 | 98547.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231772E+11 | 25913.92 | 08-JAN-05:01 | 3.00 | 2.09 | 0.137995E+11 | 14050.13 | 14-JAN-19:40 | 17.00 | 9.90 |
February | 0.203652E+11 | 23143.47 | 05-FEB-05:01 | 5.83 | 2.15 | 0.123746E+11 | 13395.30 | 11-FEB-19:00 | 15.00 | 10.67 |
March | 0.224909E+11 | 21371.76 | 09-MAR-05:01 | 6.00 | 5.04 | 0.136168E+11 | 13779.92 | 18-MAR-18:19 | 14.67 | 13.07 |
April | 0.235840E+11 | 39916.07 | 27-APR-03:01 | 15.00 | 14.41 | 0.140218E+11 | 14050.47 | 29-APR-18:19 | 16.33 | 13.52 |
May | 0.239671E+11 | 45183.43 | 04-MAY-03:01 | 13.83 | 12.68 | 0.146847E+11 | 14050.15 | 27-MAY-18:19 | 16.00 | 12.43 |
June | 0.246211E+11 | 44606.68 | 23-JUN-03:01 | 16.00 | 13.03 | 0.147255E+11 | 14050.73 | 24-JUN-18:30 | 17.00 | 14.56 |
July | 0.281238E+11 | 48250.34 | 16-JUL-03:01 | 17.00 | 15.62 | 0.152161E+11 | 14050.98 | 29-JUL-18:40 | 19.00 | 18.37 |
August | 0.289174E+11 | 49927.73 | 09-AUG-03:01 | 17.83 | 16.64 | 0.154199E+11 | 14050.68 | 26-AUG-18:10 | 17.00 | 16.37 |
September | 0.262835E+11 | 66006.88 | 30-SEP-03:01 | 24.07 | 13.89 | 0.146855E+11 | 14050.82 | 30-SEP-18:00 | 21.00 | 17.71 |
October | 0.278823E+11 | 58382.99 | 17-OCT-03:01 | 16.83 | 8.48 | 0.150684E+11 | 14051.01 | 21-OCT-18:19 | 16.67 | 13.82 |
November | 0.234242E+11 | 45099.24 | 01-NOV-03:01 | 12.58 | 9.58 | 0.137751E+11 | 14050.28 | 18-NOV-19:19 | 16.33 | 12.15 |
December | 0.238378E+11 | 23434.68 | 19-DEC-13:00 | 26.00 | 11.60 | 0.138381E+11 | 14049.81 | 16-DEC-19:40 | 26.00 | 11.60 |
Annual Sum or Average | 0.296674E+12 | 0.171226E+12 | ||||||||
Minimum of Months | 0.203652E+11 | 21371.76 | 3.00 | 2.09 | 0.123746E+11 | 13395.30 | 14.67 | 9.90 | ||
Maximum of Months | 0.289174E+11 | 66006.88 | 26.00 | 16.64 | 0.154199E+11 | 14051.01 | 26.00 | 18.37 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292564E+11 | 56719.55 | 16-JAN-04:01 | 12.17 | 4.72 | 0.105423E+11 | 6930.43 | 25-JAN-11:50 | 18.00 | 12.95 |
February | 0.261424E+11 | 54225.79 | 03-FEB-04:01 | 13.00 | 4.05 | 0.952700E+10 | 6930.43 | 15-FEB-11:50 | 16.83 | 13.41 |
March | 0.292839E+11 | 51936.66 | 12-MAR-03:01 | 8.00 | 6.07 | 0.105418E+11 | 6930.44 | 17-MAR-10:00 | 17.00 | 13.94 |
April | 0.285470E+11 | 51094.63 | 02-APR-03:01 | 11.00 | 5.61 | 0.102313E+11 | 6930.43 | 18-APR-10:00 | 17.00 | 13.48 |
May | 0.297540E+11 | 53340.11 | 27-MAY-03:01 | 8.08 | 7.05 | 0.105792E+11 | 6930.44 | 08-MAY-10:00 | 8.08 | 7.05 |
June | 0.292661E+11 | 46111.40 | 13-JUN-03:01 | 11.83 | 10.73 | 0.102521E+11 | 6930.43 | 08-JUN-10:50 | 11.83 | 10.73 |
July | 0.309980E+11 | 42478.83 | 06-JUL-03:01 | 13.17 | 12.60 | 0.105923E+11 | 6930.40 | 17-JUL-10:00 | 23.00 | 18.43 |
August | 0.309840E+11 | 40774.99 | 22-AUG-03:01 | 16.00 | 13.58 | 0.105989E+11 | 6930.40 | 25-AUG-10:00 | 23.00 | 18.99 |
September | 0.294036E+11 | 47704.38 | 20-SEP-03:01 | 11.00 | 9.85 | 0.102501E+11 | 6937.21 | 29-SEP-10:00 | 36.00 | 17.91 |
October | 0.302649E+11 | 58437.19 | 27-OCT-03:01 | 11.50 | 4.84 | 0.105870E+11 | 6945.76 | 16-OCT-10:00 | 11.50 | 4.84 |
November | 0.284464E+11 | 54932.49 | 29-NOV-04:01 | 14.17 | 4.26 | 0.102236E+11 | 6930.44 | 14-NOV-11:00 | 14.17 | 4.26 |
December | 0.292560E+11 | 54591.60 | 19-DEC-04:11 | 16.00 | 5.15 | 0.105454E+11 | 6930.44 | 08-DEC-11:00 | 16.00 | 5.15 |
Annual Sum or Average | 0.351603E+12 | 0.124471E+12 | ||||||||
Minimum of Months | 0.261424E+11 | 40774.99 | 8.00 | 4.05 | 0.952700E+10 | 6930.40 | 8.08 | 4.26 | ||
Maximum of Months | 0.309980E+11 | 58437.19 | 16.00 | 13.58 | 0.105989E+11 | 6945.76 | 36.00 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8.83 | 8.36 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 | 11.35 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.63 | 6.62 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 | 8.61 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 | 12.03 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 | 15.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 | 17.20 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 14.83 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 | 17.39 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 | 11.07 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 | 5.44 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.00 | 0.00 | 7.63 | 5.44 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3743626.59 | 10491.79 | 07-JAN-05:03 | 6.50 |
February | 2571529.27 | 7774.36 | 10-FEB-05:03 | 6.83 |
March | 6545284.38 | 12299.67 | 30-MAR-04:01 | 4.48 |
April | 244890.70 | 2768.55 | 20-APR-04:05 | 9.00 |
May | 624579.54 | 5104.39 | 15-MAY-04:04 | 8.83 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 1191294.16 | 2445.00 | 30-SEP-04:02 | 23.88 |
October | 131558.43 | 1099.55 | 28-OCT-04:06 | 9.00 |
November | 714921.07 | 5825.29 | 18-NOV-05:04 | 8.00 |
December | 2564180.16 | 6413.40 | 13-DEC-05:02 | 6.83 |
Annual Sum or Average | 18331864.29 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 6545284.38 | 12299.67 | 23.88 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.298323E+10 | 2454.69 | 02-JAN-16:40 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.262162E+10 | 2454.69 | 01-FEB-17:19 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.284886E+10 | 2454.69 | 01-MAR-17:40 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.261487E+10 | 2454.69 | 01-APR-17:30 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.263904E+10 | 2454.69 | 01-MAY-18:19 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.254890E+10 | 2454.69 | 01-JUN-18:40 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.258856E+10 | 2454.69 | 01-JUL-18:49 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.269143E+10 | 2454.69 | 01-AUG-18:40 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.269114E+10 | 2454.69 | 01-SEP-17:30 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.284739E+10 | 2454.69 | 02-OCT-17:19 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.286377E+10 | 2454.69 | 01-NOV-16:49 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.298626E+10 | 2454.69 | 01-DEC-16:19 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.329250E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.254890E+10 | 2454.69 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.298626E+10 | 2454.69 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.145365E+10 | 885.05 | 02-JAN-10:09 | 0.275454E+11 | 17341.88 | 01-JAN-11:09 |
February | 0.131681E+10 | 885.05 | 01-FEB-10:09 | 0.248798E+11 | 17341.88 | 01-FEB-11:09 |
March | 0.147869E+10 | 885.05 | 01-MAR-10:09 | 0.275456E+11 | 17341.88 | 01-MAR-11:09 |
April | 0.141254E+10 | 885.05 | 01-APR-16:10 | 0.266569E+11 | 17341.88 | 01-APR-10:09 |
May | 0.146617E+10 | 885.05 | 01-MAY-09:09 | 0.275455E+11 | 17341.88 | 01-MAY-10:09 |
June | 0.142908E+10 | 885.05 | 01-JUN-09:09 | 0.266570E+11 | 17341.88 | 01-JUN-10:09 |
July | 0.144981E+10 | 885.05 | 01-JUL-16:10 | 0.275454E+11 | 17341.88 | 01-JUL-10:09 |
August | 0.147869E+10 | 885.05 | 01-AUG-09:09 | 0.275456E+11 | 17341.88 | 01-AUG-10:09 |
September | 0.141289E+10 | 885.05 | 01-SEP-09:09 | 0.266569E+11 | 17341.88 | 01-SEP-10:09 |
October | 0.145348E+10 | 885.05 | 02-OCT-09:09 | 0.275454E+11 | 17341.88 | 01-OCT-10:09 |
November | 0.140753E+10 | 885.05 | 01-NOV-09:09 | 0.266568E+11 | 17341.88 | 01-NOV-10:09 |
December | 0.144998E+10 | 885.05 | 01-DEC-10:09 | 0.275454E+11 | 17341.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.172093E+11 | 0.324326E+12 | ||||
Minimum of Months | 0.131681E+10 | 885.05 | 0.248798E+11 | 17341.88 | ||
Maximum of Months | 0.147869E+10 | 885.05 | 0.275456E+11 | 17341.88 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.298323E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17773711.30 | 0.624821E+10 |
February | 0.272721E+11 | 0.262162E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3029556.52 | 0.581198E+10 |
March | 0.305458E+11 | 0.284886E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668678E+10 |
April | 0.292871E+11 | 0.261487E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18670617.19 | 0.501806E+10 |
May | 0.303219E+11 | 0.263904E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507326E+10 |
June | 0.295292E+11 | 0.254890E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1763730.18 | 0.375890E+10 |
July | 0.300798E+11 | 0.258856E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102014E+09 | 0.269259E+10 |
August | 0.305458E+11 | 0.269143E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116989E+09 | 0.265248E+10 |
September | 0.292871E+11 | 0.269114E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224415E+09 | 0.355340E+10 |
October | 0.300980E+11 | 0.284739E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412817E+09 | 0.330328E+10 |
November | 0.290996E+11 | 0.286377E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18587066.85 | 0.560669E+10 |
December | 0.300798E+11 | 0.298626E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13961321.95 | 0.600924E+10 |
Annual Sum or Average | 0.356244E+12 | 0.329250E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930021E+09 | 0.564149E+11 |
Minimum of Months | 0.272721E+11 | 0.254890E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265248E+10 |
Maximum of Months | 0.305458E+11 | 0.298626E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412817E+09 | 0.668678E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.145365E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.08 | 0.122594E+09 |
February | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139785E+09 |
March | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149507E+09 |
April | 0.786997E+09 | 0.141254E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 13513.04 | 93000756.54 |
May | 0.814802E+09 | 0.146617E+10 | 0.225868E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112876E+09 |
June | 0.793501E+09 | 0.142908E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61287935.16 |
July | 0.808298E+09 | 0.144981E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 232165.20 | 43107013.44 |
August | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 172234.31 | 62887811.36 |
September | 0.786997E+09 | 0.141289E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1242154.96 | 56684777.31 |
October | 0.808786E+09 | 0.145348E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3014187.95 | 93046365.39 |
November | 0.781956E+09 | 0.140753E+10 | 0.218581E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 10497.58 | 0.121320E+09 |
December | 0.808298E+09 | 0.144998E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129599E+09 |
Annual Sum or Average | 0.957291E+10 | 0.172093E+11 | 0.265941E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 4684753.11 | 0.118570E+10 |
Minimum of Months | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43107013.44 |
Maximum of Months | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3014187.95 | 0.149507E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123302E+10 | 0.303226E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790929E+09 | 0.291908E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735856E+09 | 0.430972E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768920E+09 | 0.581387E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686347E+09 | 0.591737E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528665E+09 | 0.608942E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681413E+09 | 0.680133E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690305E+09 | 0.630874E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910656E+09 | 0.480184E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104624E+10 | 0.339056E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108811E+10 | 0.304745E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130161E+10 | 0.275150E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104621E+11 | 0.551831E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528665E+09 | 0.275150E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130161E+10 | 0.680133E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2454.69 | 02-JAN-16:40 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.77 | 18-JAN-12:55 | 9709.15 | 02-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2454.69 | 01-FEB-17:19 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.31 | 01-FEB-12:05 | 7964.04 | 04-FEB-19:55 |
March | 30255.31 | 04-MAR-19:10 | 2454.69 | 01-MAR-17:40 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 9186.02 | 29-MAR-20:00 |
April | 30255.31 | 01-APR-18:10 | 2454.69 | 01-APR-17:30 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.68 | 26-APR-13:00 | 7625.12 | 15-APR-18:53 |
May | 30255.31 | 06-MAY-18:10 | 2454.69 | 01-MAY-18:19 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 7424.21 | 13-MAY-18:53 |
June | 30255.31 | 03-JUN-18:10 | 2454.69 | 01-JUN-18:40 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.39 | 29-JUN-11:10 | 6204.95 | 06-JUN-18:53 |
July | 30255.31 | 01-JUL-18:10 | 2454.69 | 01-JUL-18:49 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.06 | 19-JUL-12:00 | 4965.06 | 07-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 2454.69 | 01-AUG-18:40 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2390.83 | 18-AUG-12:00 | 5589.12 | 21-AUG-19:55 |
September | 30255.31 | 02-SEP-18:10 | 2454.69 | 01-SEP-17:30 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6961.27 | 29-SEP-11:15 | 6191.04 | 14-SEP-19:00 |
October | 30255.31 | 07-OCT-18:10 | 2454.69 | 02-OCT-17:19 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7477.24 | 16-OCT-11:03 | 6806.17 | 07-OCT-18:53 |
November | 30255.31 | 04-NOV-18:10 | 2454.69 | 01-NOV-16:49 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1215.30 | 19-NOV-13:00 | 7525.84 | 04-NOV-18:10 |
December | 30255.31 | 02-DEC-19:10 | 2454.69 | 01-DEC-16:19 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.84 | 19-DEC-13:00 | 9010.44 | 28-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4965.06 | |||||
Maximum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7477.24 | 9709.15 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 885.05 | 02-JAN-10:09 | 14079.00 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14-JAN-11:02 | 497.48 | 02-JAN-03:00 |
February | 813.01 | 04-FEB-19:10 | 885.05 | 01-FEB-10:09 | 14079.00 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 526.66 | 25-FEB-03:00 |
March | 813.01 | 04-MAR-19:10 | 885.05 | 01-MAR-10:09 | 14079.00 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 432.41 | 29-MAR-02:00 |
April | 813.01 | 01-APR-18:10 | 885.05 | 01-APR-16:10 | 14079.00 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 3.90 | 26-APR-13:00 | 317.63 | 17-APR-03:00 |
May | 813.01 | 06-MAY-18:10 | 885.05 | 01-MAY-09:09 | 14079.00 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 324.13 | 26-MAY-03:40 |
June | 813.01 | 03-JUN-18:10 | 885.05 | 01-JUN-09:09 | 14079.00 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 230.19 | 07-JUN-01:00 |
July | 813.01 | 01-JUL-18:10 | 885.05 | 01-JUL-16:10 | 14079.00 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 9.67 | 31-JUL-13:00 | 185.57 | 13-JUL-02:55 |
August | 813.01 | 05-AUG-18:10 | 885.05 | 01-AUG-09:09 | 14079.00 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 7.79 | 17-AUG-14:00 | 151.70 | 29-AUG-03:00 |
September | 813.01 | 02-SEP-18:10 | 885.05 | 01-SEP-09:09 | 14079.00 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 38.30 | 29-SEP-13:25 | 200.14 | 02-SEP-01:40 |
October | 813.01 | 07-OCT-18:10 | 885.05 | 02-OCT-09:09 | 14079.00 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 57.41 | 16-OCT-10:23 | 398.24 | 11-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 885.05 | 01-NOV-09:09 | 14079.00 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 3.91 | 19-NOV-13:00 | 488.87 | 23-NOV-04:00 |
December | 813.01 | 02-DEC-19:10 | 885.05 | 01-DEC-10:09 | 14079.00 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 395.63 | 18-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 151.70 | ||||||
Maximum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 57.41 | 526.66 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2284.35 | 06-JAN-04:00 | 6237.29 | 30-JAN-11:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2065.51 | 01-FEB-02:40 | 6586.76 | 22-FEB-14:25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1862.71 | 20-MAR-03:55 | 8167.25 | 15-MAR-12:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.26 | 16-APR-00:55 | 8481.32 | 23-APR-12:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1676.27 | 16-MAY-24:00 | 8556.25 | 30-MAY-11:50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1686.74 | 18-JUN-01:50 | 8529.29 | 05-JUN-12:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.26 | 14-JUL-05:20 | 8108.25 | 15-JUL-13:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.77 | 24-AUG-04:03 | 7789.28 | 11-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1902.45 | 29-SEP-22:40 | 7235.61 | 02-SEP-12:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2328.77 | 16-OCT-06:52 | 6434.78 | 03-OCT-12:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.96 | 27-NOV-06:53 | 6147.36 | 04-NOV-12:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.39 | 26-DEC-05:00 | 5544.26 | 02-DEC-11:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.26 | 5544.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2328.77 | 8556.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25913.92 | 08-JAN-05:01 | 0.00 | 800.29 | 28800.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.34 |
February | 23143.47 | 05-FEB-05:01 | 0.00 | 800.29 | 28800.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 |
March | 21371.76 | 09-MAR-05:01 | 16808.50 | 800.29 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 |
April | 39916.07 | 27-APR-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45183.43 | 04-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 |
June | 44606.68 | 23-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48250.34 | 16-JUL-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49927.73 | 09-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.02 |
September | 66006.88 | 30-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 |
October | 58382.99 | 17-OCT-03:01 | 0.00 | 720.26 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 |
November | 45099.24 | 01-NOV-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.25 |
December | 23434.68 | 19-DEC-13:00 | 26893.61 | 1227.34 | 6509.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21371.76 | 0.00 | 720.26 | 6509.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66006.88 | 26893.61 | 1227.34 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.84 | 277.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56719.55 | 16-JAN-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 120.22 |
February | 54225.79 | 03-FEB-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 178.81 |
March | 51936.66 | 12-MAR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 138.08 |
April | 51094.63 | 02-APR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 222.09 |
May | 53340.11 | 27-MAY-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 168.06 |
June | 46111.40 | 13-JUN-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 158.24 |
July | 42478.83 | 06-JUL-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 |
August | 40774.99 | 22-AUG-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 73.51 |
September | 47704.38 | 20-SEP-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 103.85 |
October | 58437.19 | 27-OCT-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 187.54 |
November | 54932.49 | 29-NOV-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 164.82 |
December | 54591.60 | 19-DEC-04:11 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 279.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 40774.99 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | |
Maximum of Months | 58437.19 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 279.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.20 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1758.99 | 0.00 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843.70 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.24 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.65 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.62 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.50 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.71 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1028.45 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1165.55 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.11 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1758.99 | 92.24 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.674827E+11 | 47533.94 | 17-JAN-11:00 | 0.757382E+11 | 71023.90 | 08-JAN-06:40 |
February | 0.595702E+11 | 46748.60 | 01-FEB-11:00 | 0.663580E+11 | 49296.21 | 10-FEB-07:49 |
March | 0.661199E+11 | 45868.74 | 23-MAR-10:00 | 0.756673E+11 | 61847.93 | 30-MAR-06:10 |
April | 0.663925E+11 | 50404.38 | 26-APR-10:00 | 0.672889E+11 | 49523.78 | 01-APR-05:40 |
May | 0.683724E+11 | 46267.95 | 03-MAY-10:00 | 0.685680E+11 | 43423.51 | 06-MAY-10:00 |
June | 0.705019E+11 | 52113.52 | 29-JUN-10:00 | 0.648526E+11 | 43324.19 | 03-JUN-10:20 |
July | 0.789413E+11 | 55955.67 | 19-JUL-11:00 | 0.662965E+11 | 43255.28 | 08-JUL-10:20 |
August | 0.804407E+11 | 56863.90 | 14-AUG-10:00 | 0.665456E+11 | 43243.76 | 26-AUG-10:30 |
September | 0.731818E+11 | 62560.07 | 29-SEP-11:09 | 0.645442E+11 | 43318.37 | 30-SEP-10:20 |
October | 0.765582E+11 | 64441.92 | 16-OCT-11:09 | 0.675392E+11 | 43417.26 | 29-OCT-10:39 |
November | 0.653867E+11 | 46974.31 | 19-NOV-11:00 | 0.680234E+11 | 45786.94 | 05-NOV-05:40 |
December | 0.676590E+11 | 46916.87 | 19-DEC-11:00 | 0.737514E+11 | 55344.58 | 23-DEC-06:10 |
Annual Sum or Average | 0.840607E+12 | 0.825173E+12 | ||||
Minimum of Months | 0.595702E+11 | 45868.74 | 0.645442E+11 | 43243.76 | ||
Maximum of Months | 0.804407E+11 | 64441.92 | 0.757382E+11 | 71023.90 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.443688E+10 | 0.264118E+10 | 0.381711E+11 | 0.00 | 0.907044E+10 | 37879553.69 | 0.00 | 0.233020E+10 | 0.00 | 0.00 | 0.00 | 0.638563E+10 | 0.00 |
February | 0.393842E+10 | 0.221939E+10 | 0.344772E+11 | 0.00 | 0.812493E+10 | 34213790.43 | 0.00 | 0.991902E+09 | 0.00 | 0.00 | 0.00 | 0.577872E+10 | 0.00 |
March | 0.432755E+10 | 0.221615E+10 | 0.381714E+11 | 0.00 | 0.904844E+10 | 37879553.69 | 0.00 | 0.144465E+10 | 0.00 | 0.00 | 0.00 | 0.645484E+10 | 0.00 |
April | 0.402740E+10 | 0.190819E+10 | 0.369399E+11 | 0.00 | 0.864667E+10 | 36657632.61 | 0.00 | 0.424943E+10 | 0.00 | 0.00 | 0.00 | 0.619607E+10 | 0.00 |
May | 0.410521E+10 | 0.178663E+10 | 0.381712E+11 | 0.00 | 0.894300E+10 | 37879553.69 | 0.00 | 0.435670E+10 | 0.00 | 0.00 | 0.00 | 0.641731E+10 | 0.00 |
June | 0.397798E+10 | 0.164502E+10 | 0.369400E+11 | 0.00 | 0.875902E+10 | 36657632.61 | 0.00 | 0.842957E+10 | 0.00 | 0.00 | 0.00 | 0.623720E+10 | 0.00 |
July | 0.403836E+10 | 0.172117E+10 | 0.381711E+11 | 0.00 | 0.928896E+10 | 37879553.69 | 0.00 | 0.146588E+11 | 0.00 | 0.00 | 0.00 | 0.637204E+10 | 0.00 |
August | 0.417012E+10 | 0.187745E+10 | 0.381714E+11 | 0.00 | 0.934132E+10 | 37879553.69 | 0.00 | 0.157191E+11 | 0.00 | 0.00 | 0.00 | 0.645007E+10 | 0.00 |
September | 0.410403E+10 | 0.204367E+10 | 0.369399E+11 | 0.00 | 0.886657E+10 | 36657632.61 | 0.00 | 0.105059E+11 | 0.00 | 0.00 | 0.00 | 0.619523E+10 | 0.00 |
October | 0.430086E+10 | 0.235694E+10 | 0.381711E+11 | 0.00 | 0.918472E+10 | 37879553.69 | 0.00 | 0.115339E+11 | 0.00 | 0.00 | 0.00 | 0.637937E+10 | 0.00 |
November | 0.427130E+10 | 0.249527E+10 | 0.369398E+11 | 0.00 | 0.867243E+10 | 36657632.61 | 0.00 | 0.245568E+10 | 0.00 | 0.00 | 0.00 | 0.617800E+10 | 0.00 |
December | 0.443624E+10 | 0.269963E+10 | 0.381711E+11 | 0.00 | 0.902757E+10 | 37879553.69 | 0.00 | 0.250304E+10 | 0.00 | 0.00 | 0.00 | 0.637720E+10 | 0.00 |
Annual Sum or Average | 0.501344E+11 | 0.256107E+11 | 0.449435E+12 | 0.00 | 0.106974E+12 | 0.446001E+09 | 0.00 | 0.791789E+11 | 0.00 | 0.00 | 0.00 | 0.754217E+11 | 0.00 |
Minimum of Months | 0.393842E+10 | 0.164502E+10 | 0.344772E+11 | 0.00 | 0.812493E+10 | 34213790.43 | 0.00 | 0.991902E+09 | 0.00 | 0.00 | 0.00 | 0.577872E+10 | 0.00 |
Maximum of Months | 0.443688E+10 | 0.269963E+10 | 0.381714E+11 | 0.00 | 0.934132E+10 | 37879553.69 | 0.00 | 0.157191E+11 | 0.00 | 0.00 | 0.00 | 0.645484E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.705785E+10 | 0.00 | 0.287806E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.424829E+10 | 0.00 | 0.260713E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.694830E+10 | 0.00 | 0.288193E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.151415E+10 | 0.00 | 0.271621E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.117291E+10 | 0.00 | 0.274954E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 91693685.28 | 0.00 | 0.261483E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.263968E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.266459E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 30387658.43 | 0.00 | 0.259012E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.438758E+09 | 0.00 | 0.272008E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.243680E+10 | 0.00 | 0.269740E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.544570E+10 | 0.00 | 0.284060E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.293848E+11 | 0.00 | 0.326002E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.259012E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.705785E+10 | 0.00 | 0.288193E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3339.74 | 02-JAN-16:40 | 2213.72 | 01-JAN-06:10 | 24333.76 | 01-JAN-11:09 | 0.00 | 5010.24 | 08-JAN-06:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3339.74 | 01-FEB-17:19 | 2213.72 | 01-FEB-06:10 | 24333.76 | 01-FEB-11:09 | 0.00 | 4579.76 | 05-FEB-06:10 | 17.86 | 25-FEB-13:09 | 0.00 | 01-FEB-00:10 |
March | 3339.74 | 01-MAR-17:40 | 2213.72 | 01-MAR-06:10 | 24333.76 | 01-MAR-11:09 | 0.00 | 4775.49 | 30-MAR-05:10 | 17.86 | 23-MAR-08:20 | 0.00 | 01-MAR-00:10 |
April | 3339.74 | 01-APR-17:30 | 2213.72 | 01-APR-05:10 | 24333.76 | 01-APR-10:09 | 0.00 | 4559.17 | 01-APR-05:00 | 17.86 | 13-APR-08:09 | 0.00 | 01-APR-00:10 |
May | 3339.74 | 01-MAY-18:19 | 2213.72 | 01-MAY-18:30 | 24333.76 | 01-MAY-10:09 | 0.00 | 4386.26 | 14-MAY-04:00 | 17.86 | 31-MAY-14:39 | 0.00 | 01-MAY-00:10 |
June | 3339.74 | 01-JUN-18:40 | 2213.72 | 01-JUN-18:49 | 24333.76 | 01-JUN-10:09 | 0.00 | 4520.14 | 29-JUN-10:00 | 17.86 | 15-JUN-08:30 | 0.00 | 01-JUN-00:10 |
July | 3339.74 | 01-JUL-18:49 | 2213.72 | 01-JUL-18:00 | 24333.76 | 01-JUL-10:09 | 0.00 | 5933.59 | 19-JUL-11:00 | 17.86 | 11-JUL-09:39 | 0.00 | 01-JUL-00:10 |
August | 3339.74 | 01-AUG-18:40 | 2213.72 | 01-AUG-18:49 | 24333.76 | 01-AUG-10:09 | 0.00 | 6076.79 | 18-AUG-11:00 | 17.86 | 21-AUG-09:39 | 0.00 | 01-AUG-00:10 |
September | 3339.74 | 01-SEP-17:30 | 2213.72 | 01-SEP-05:10 | 24333.76 | 01-SEP-10:09 | 0.00 | 6902.60 | 29-SEP-11:00 | 17.86 | 05-SEP-10:20 | 0.00 | 01-SEP-00:10 |
October | 3339.74 | 02-OCT-17:19 | 2213.72 | 01-OCT-05:10 | 24333.76 | 01-OCT-10:09 | 0.00 | 7232.58 | 16-OCT-11:09 | 17.86 | 01-OCT-11:30 | 0.00 | 01-OCT-00:10 |
November | 3339.74 | 01-NOV-16:49 | 2213.72 | 01-NOV-05:10 | 24333.76 | 01-NOV-10:09 | 0.00 | 4459.09 | 05-NOV-05:00 | 17.86 | 11-NOV-11:39 | 0.00 | 01-NOV-00:10 |
December | 3339.74 | 01-DEC-16:19 | 2213.72 | 01-DEC-06:10 | 24333.76 | 01-DEC-11:09 | 0.00 | 4642.81 | 23-DEC-06:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 4386.26 | 17.86 | 0.00 | ||||||
Maximum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 7232.58 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 11834.60 | 18-JAN-12:00 | 0.00 | 0.00 | 0.00 | 4741.40 | 11-JAN-07:49 | 0.00 |
February | 10817.29 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 4740.43 | 27-FEB-07:00 | 0.00 |
March | 10228.12 | 23-MAR-11:09 | 0.00 | 0.00 | 0.00 | 4741.75 | 08-MAR-07:19 | 0.00 |
April | 14234.19 | 26-APR-11:09 | 0.00 | 0.00 | 0.00 | 4739.80 | 03-APR-06:40 | 0.00 |
May | 12361.17 | 04-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4739.61 | 10-MAY-06:10 | 0.00 |
June | 15630.37 | 29-JUN-11:09 | 0.00 | 0.00 | 0.00 | 4738.90 | 13-JUN-06:10 | 0.00 |
July | 20406.60 | 19-JUL-11:00 | 0.00 | 0.00 | 0.00 | 4737.25 | 24-JUL-06:19 | 0.00 |
August | 20804.35 | 18-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4737.10 | 21-AUG-06:19 | 0.00 |
September | 25943.48 | 29-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4737.82 | 18-SEP-06:19 | 0.00 |
October | 27319.54 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 4739.86 | 12-OCT-06:40 | 0.00 |
November | 11353.27 | 19-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4740.40 | 17-NOV-07:10 | 0.00 |
December | 11982.84 | 19-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4741.47 | 15-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10228.12 | 0.00 | 0.00 | 0.00 | 4737.10 | 0.00 | ||
Maximum of Months | 27319.54 | 0.00 | 0.00 | 0.00 | 4741.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 47533.94 | 17-JAN-11:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4121.19 | 17.86 | 0.00 | 10739.28 | 0.00 |
February | 46748.60 | 01-FEB-11:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 3959.76 | 17.86 | 0.00 | 10243.08 | 0.00 |
March | 45868.74 | 23-MAR-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 3982.92 | 17.86 | 0.00 | 9336.32 | 0.00 |
April | 50404.38 | 26-APR-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4322.12 | 17.86 | 0.00 | 13589.96 | 0.00 |
May | 46267.95 | 03-MAY-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4015.33 | 17.86 | 0.00 | 9687.30 | 0.00 |
June | 52113.52 | 29-JUN-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4520.14 | 17.86 | 0.00 | 14966.52 | 0.00 |
July | 55955.67 | 19-JUL-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 5933.59 | 17.86 | 0.00 | 20406.60 | 0.00 |
August | 56863.90 | 14-AUG-10:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 5267.08 | 17.86 | 0.00 | 18906.96 | 0.00 |
September | 62560.07 | 29-SEP-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 6880.91 | 17.86 | 0.00 | 25842.98 | 0.00 |
October | 64441.92 | 16-OCT-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7232.58 | 17.86 | 0.00 | 27319.54 | 0.00 |
November | 46974.31 | 19-NOV-11:00 | 1642.97 | 24333.76 | 0.00 | 0.00 | 4025.55 | 17.86 | 0.00 | 10461.40 | 0.00 |
December | 46916.87 | 19-DEC-11:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 3951.10 | 17.86 | 0.00 | 10381.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 45868.74 | 1642.97 | 22726.43 | 0.00 | 0.00 | 3951.10 | 17.86 | 0.00 | 9336.32 | 0.00 | |
Maximum of Months | 64441.92 | 2112.39 | 24333.76 | 0.00 | 0.00 | 7232.58 | 17.86 | 0.00 | 27319.54 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 47195.98 | 08-JAN-06:00 | 0.00 | 23272.68 | 30-JAN-07:40 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 25707.76 | 05-FEB-05:00 | 0.00 | 23334.50 | 10-FEB-07:49 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 35860.61 | 30-MAR-05:10 | 0.00 | 23006.75 | 03-MAR-07:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 24321.60 | 01-APR-05:00 | 0.00 | 22008.80 | 05-APR-06:19 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 16746.06 | 14-MAY-04:00 | 0.00 | 20705.03 | 01-MAY-18:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 6200.42 | 13-JUN-04:00 | 0.00 | 19393.30 | 01-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 18246.90 | 03-JUL-06:19 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 18135.06 | 31-AUG-06:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 3807.59 | 20-SEP-05:00 | 0.00 | 19002.51 | 29-SEP-18:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 11824.88 | 29-OCT-05:00 | 0.00 | 20172.18 | 25-OCT-18:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 19445.27 | 05-NOV-05:00 | 0.00 | 21956.34 | 30-NOV-07:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 28746.44 | 23-DEC-06:10 | 0.00 | 22808.55 | 28-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 18135.06 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 47195.98 | 0.00 | 23334.50 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.00 | 24.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.00 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.00 | 24.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 24.61 | 0.00 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.57 | 0.00 | 28.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.13 | 0.00 | 28.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.01 | 0.00 | 28.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.81 | 0.00 | 28.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 29.13 | 0.00 | 29.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 29.99 | 0.00 | 29.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 30.29 | 0.00 | 30.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 30.33 | 0.00 | 30.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 30.19 | 0.00 | 30.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 30.06 | 0.50 | 29.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.72 | 0.00 | 28.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.49 | 0.00 | 28.49 |
Annual Sum or Average | 0.00 | 0.00 | 141.33 | 29.70 | 0.50 | 29.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.01 | 0.00 | 28.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 30.33 | 0.50 | 30.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.50 | 21.60 | 119.33 | 21.99 | 15.33 | 21.91 |
February | 410.33 | 21.66 | 78.67 | 21.94 | 16.00 | 21.93 |
March | 455.50 | 21.41 | 109.33 | 21.78 | 10.67 | 21.71 |
April | 270.17 | 21.68 | 250.33 | 22.76 | 4.83 | 22.77 |
May | 254.17 | 21.77 | 284.00 | 22.92 | 2.00 | 22.92 |
June | 162.00 | 22.47 | 422.83 | 23.53 | 35.83 | 23.54 |
July | 241.83 | 23.61 | 539.50 | 23.82 | 199.67 | 23.82 |
August | 288.00 | 23.71 | 560.67 | 23.84 | 261.33 | 23.84 |
September | 196.50 | 23.16 | 455.50 | 23.70 | 108.17 | 23.72 |
October | 224.50 | 22.97 | 410.67 | 23.62 | 102.33 | 23.67 |
November | 330.17 | 21.84 | 154.17 | 22.45 | 7.67 | 22.44 |
December | 420.00 | 21.72 | 55.83 | 21.84 | 11.33 | 21.77 |
Annual Sum or Average | 3667.67 | 22.14 | 3440.83 | 22.97 | 775.17 | 23.02 |
Minimum of Months | 162.00 | 21.41 | 55.83 | 21.78 | 2.00 | 21.71 |
Maximum of Months | 455.50 | 23.71 | 560.67 | 23.84 | 261.33 | 23.84 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 351.83 | 23.54 | 433.33 | 24.40 | 206.83 | 24.71 |
February | 316.83 | 23.96 | 399.83 | 24.55 | 199.67 | 24.83 |
March | 353.33 | 23.51 | 418.83 | 24.25 | 199.67 | 24.57 |
April | 389.83 | 25.42 | 513.17 | 25.31 | 349.17 | 25.47 |
May | 417.33 | 25.58 | 551.83 | 25.44 | 384.83 | 25.58 |
June | 456.00 | 25.94 | 589.67 | 25.72 | 456.00 | 25.79 |
July | 551.83 | 25.92 | 609.00 | 25.86 | 551.83 | 25.88 |
August | 571.83 | 25.91 | 612.00 | 25.87 | 571.83 | 25.88 |
September | 476.67 | 25.93 | 587.50 | 25.79 | 476.67 | 25.83 |
October | 474.67 | 25.83 | 578.67 | 25.76 | 458.17 | 25.83 |
November | 381.00 | 24.76 | 472.00 | 25.07 | 292.67 | 25.28 |
December | 343.67 | 23.66 | 433.50 | 24.50 | 201.83 | 24.79 |
Annual Sum or Average | 5084.83 | 25.15 | 6199.33 | 25.30 | 4349.17 | 25.47 |
Minimum of Months | 316.83 | 23.51 | 399.83 | 24.25 | 199.67 | 24.57 |
Maximum of Months | 571.83 | 25.94 | 612.00 | 25.87 | 571.83 | 25.88 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.31632 | 43.95769 | 0.06040 | 7.40418 |
February | 551.00000 | 22.18176 | 47.43716 | 0.04395 | 6.87212 |
March | 612.00000 | 22.00200 | 51.33113 | 0.02232 | 7.16322 |
April | 590.00000 | 22.84332 | 53.08724 | 0.25694 | 8.14650 |
May | 611.00000 | 22.99062 | 52.22282 | -0.6764 | 17.50514 |
June | 592.00000 | 23.49185 | 56.84617 | -0.4600 | 11.05991 |
July | 609.00000 | 23.77382 | 61.25986 | -0.3012 | 7.61109 |
August | 612.00000 | 23.79525 | 62.99409 | -0.2739 | 7.22230 |
September | 590.00000 | 23.62712 | 58.39302 | -0.3779 | 9.26970 |
October | 610.00000 | 23.57434 | 48.84823 | 0.43489 | 10.18662 |
November | 591.00000 | 22.68065 | 44.77484 | 0.16779 | 7.45753 |
December | 609.00000 | 22.37735 | 38.92958 | 0.04791 | 6.97682 |
Annual Sum or Average | 7187.00000 | 22.97561 | 51.69448 | -0.0890 | 8.92319 |
Minimum of Months | 551.00000 | 22.00200 | 38.92958 | -0.6764 | 6.87212 |
Maximum of Months | 612.00000 | 23.79525 | 62.99409 | 0.43489 | 17.50514 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.80245 | 45.20763 | 0.63487 | 19.76972 |
February | 551.00000 | 23.95920 | 47.22627 | 0.68129 | 19.59352 |
March | 612.00000 | 23.60629 | 51.20799 | 0.62685 | 18.97049 |
April | 590.00000 | 24.77771 | 51.53754 | 0.92909 | 26.35815 |
May | 611.00000 | 24.98116 | 50.29982 | 0.29371 | 12.15682 |
June | 592.00000 | 25.53790 | 52.92152 | 0.51901 | 13.04167 |
July | 609.00000 | 25.80389 | 55.93628 | 0.65762 | 15.19639 |
August | 612.00000 | 25.82294 | 57.21704 | 0.66966 | 15.44869 |
September | 590.00000 | 25.65796 | 53.82301 | 0.57080 | 13.62199 |
October | 610.00000 | 25.51711 | 46.59917 | 1.09503 | 31.99609 |
November | 591.00000 | 24.54082 | 44.58825 | 0.81885 | 23.18888 |
December | 609.00000 | 23.93853 | 40.92744 | 0.63757 | 18.96840 |
Annual Sum or Average | 7187.00000 | 24.83274 | 49.80479 | 0.67740 | 19.01843 |
Minimum of Months | 551.00000 | 23.60629 | 40.92744 | 0.29371 | 12.15682 |
Maximum of Months | 612.00000 | 25.82294 | 57.21704 | 1.09503 | 31.99609 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.376342E+10 | 0.117271E+10 | 115.84 | 0.329353E+10 | 0.469896E+09 | 0.00 | 0.82 | 18-JAN-13:00 | 0.00 | 01-JAN-00:02 | 28352.35 | 18-JAN-13:00 | 28054.90 | 18-JAN-12:55 | 6898.68 | 17-JAN-13:00 | 8004.70 | 18-JAN-13:00 | 0.00 | 01-JAN-00:02 |
February | 0.117040E+10 | 0.374315E+09 | 50.38 | 0.104847E+10 | 0.121931E+09 | 0.00 | 0.73 | 01-FEB-12:10 | 0.00 | 01-FEB-00:05 | 24690.60 | 01-FEB-12:10 | 24479.87 | 01-FEB-12:05 | 4860.76 | 01-FEB-13:50 | 7144.53 | 01-FEB-12:10 | 0.00 | 01-FEB-00:05 |
March | 0.204239E+10 | 0.641560E+09 | 64.14 | 0.158858E+10 | 0.453811E+09 | 0.00 | 0.69 | 23-MAR-12:00 | 0.00 | 01-MAR-00:02 | 22936.46 | 22-MAR-13:00 | 18468.25 | 10-MAR-13:00 | 8015.58 | 22-MAR-13:00 | 6686.12 | 23-MAR-12:00 | 0.00 | 01-MAR-00:02 |
April | 0.661540E+10 | 0.205429E+10 | 188.13 | 0.499122E+10 | 0.162418E+10 | 0.00 | 1.00 | 27-APR-03:01 | 0.00 | 01-APR-00:01 | 72736.05 | 27-APR-03:01 | 38773.16 | 27-APR-03:01 | 33962.89 | 27-APR-03:01 | 19488.06 | 27-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.605814E+10 | 0.191179E+10 | 209.45 | 0.452041E+10 | 0.153773E+10 | 0.00 | 1.00 | 03-MAY-03:01 | 0.00 | 01-MAY-00:01 | 72736.05 | 25-MAY-03:01 | 46005.60 | 25-MAY-03:01 | 32287.39 | 03-MAY-03:01 | 19488.06 | 03-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.145230E+11 | 0.438405E+10 | 310.91 | 0.981890E+10 | 0.470406E+10 | 0.00 | 1.00 | 04-JUN-03:01 | 0.00 | 01-JUN-00:01 | 72736.05 | 27-JUN-03:01 | 49031.26 | 23-JUN-03:01 | 34857.98 | 29-JUN-03:01 | 19488.06 | 06-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.292923E+11 | 0.836112E+10 | 415.49 | 0.181097E+11 | 0.111827E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 74881.10 | 23-JUL-03:02 | 46036.36 | 10-JUL-03:01 | 40680.86 | 29-JUL-03:02 | 19648.83 | 23-JUL-03:02 | 0.00 | 01-JUL-00:01 |
August | 0.322895E+11 | 0.910536E+10 | 420.01 | 0.195415E+11 | 0.127480E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 75199.68 | 19-AUG-03:02 | 46221.26 | 22-AUG-03:01 | 42295.89 | 07-AUG-03:01 | 19672.43 | 19-AUG-03:02 | 0.00 | 01-AUG-00:01 |
September | 0.193110E+11 | 0.574289E+10 | 347.33 | 0.132481E+11 | 0.606286E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 74906.41 | 22-SEP-03:41 | 72736.05 | 30-SEP-04:00 | 40686.21 | 22-SEP-03:41 | 19650.70 | 22-SEP-03:41 | 0.00 | 01-SEP-00:01 |
October | 0.220762E+11 | 0.651896E+10 | 390.07 | 0.171229E+11 | 0.495329E+10 | 0.00 | 1.00 | 01-OCT-03:02 | 0.00 | 01-OCT-00:01 | 77045.45 | 05-OCT-03:01 | 72736.05 | 15-OCT-03:02 | 43254.07 | 01-OCT-03:41 | 19809.27 | 05-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.352499E+10 | 0.110520E+10 | 122.50 | 0.311747E+10 | 0.407521E+09 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 36326.31 | 01-NOV-03:01 | 26754.60 | 01-NOV-03:01 | 9571.71 | 01-NOV-03:01 | 9740.44 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.426427E+10 | 0.134079E+10 | 132.50 | 0.416516E+10 | 99107732.70 | 0.00 | 0.84 | 19-DEC-13:00 | 0.00 | 01-DEC-00:03 | 28998.91 | 19-DEC-13:00 | 28998.91 | 19-DEC-13:00 | 6139.23 | 07-DEC-13:00 | 8152.25 | 19-DEC-13:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.144931E+12 | 0.427130E+11 | 2766.74 | 0.100566E+12 | 0.443651E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.117040E+10 | 0.374315E+09 | 50.38 | 0.104847E+10 | 99107732.70 | 0.00 | 0.69 | 0.00 | 22936.46 | 18468.25 | 4860.76 | 6686.12 | 0.00 | |||||||
Maximum of Months | 0.322895E+11 | 0.910536E+10 | 420.01 | 0.195415E+11 | 0.127480E+11 | 0.00 | 1.00 | 0.00 | 77045.45 | 72736.05 | 43254.07 | 19809.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.432998E+10 | 0.115749E+10 | 194.84 | 0.350172E+10 | 0.828255E+09 | 0.00 | 1.00 | 05-JAN-04:01 | 0.00 | 01-JAN-00:02 | 33204.40 | 22-JAN-04:01 | 33204.40 | 15-JAN-04:01 | 18409.12 | 26-JAN-04:01 | 7960.73 | 14-JAN-04:42 | 0.00 | 01-JAN-00:02 |
February | 0.221354E+10 | 0.617587E+09 | 145.14 | 0.165984E+10 | 0.553707E+09 | 0.00 | 1.00 | 01-FEB-04:01 | 0.00 | 01-FEB-00:05 | 33204.40 | 01-FEB-04:42 | 33204.40 | 03-FEB-04:41 | 18765.37 | 13-FEB-04:01 | 7960.73 | 01-FEB-04:01 | 0.00 | 01-FEB-00:05 |
March | 0.297391E+10 | 0.803089E+09 | 143.52 | 0.203959E+10 | 0.934319E+09 | 0.00 | 1.00 | 02-MAR-04:01 | 0.00 | 01-MAR-00:02 | 33204.40 | 17-MAR-03:01 | 20518.64 | 12-MAR-03:01 | 18173.09 | 24-MAR-03:01 | 7960.73 | 03-MAR-04:41 | 0.00 | 01-MAR-00:02 |
April | 0.833838E+10 | 0.219514E+10 | 293.28 | 0.586843E+10 | 0.246996E+10 | 0.00 | 1.00 | 02-APR-03:01 | 0.00 | 01-APR-00:01 | 33204.40 | 16-APR-03:01 | 28862.14 | 02-APR-03:42 | 18164.89 | 13-APR-03:01 | 7960.73 | 02-APR-03:42 | 0.00 | 01-APR-00:01 |
May | 0.919692E+10 | 0.244491E+10 | 338.11 | 0.637604E+10 | 0.282089E+10 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 33204.40 | 25-MAY-03:42 | 31718.31 | 24-MAY-03:01 | 18296.73 | 05-MAY-03:01 | 7960.73 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.160415E+11 | 0.404552E+10 | 411.64 | 0.102399E+11 | 0.580155E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 33204.40 | 24-JUN-03:01 | 20356.75 | 23-JUN-03:01 | 19117.49 | 28-JUN-03:21 | 7960.73 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.261744E+11 | 0.629771E+10 | 485.15 | 0.152975E+11 | 0.108769E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 33489.42 | 23-JUL-03:11 | 23037.91 | 19-JUL-10:57 | 20611.67 | 24-JUL-03:01 | 7980.03 | 23-JUL-03:11 | 0.00 | 01-JUL-00:01 |
August | 0.276852E+11 | 0.661375E+10 | 491.68 | 0.157333E+11 | 0.119519E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 34674.91 | 14-AUG-10:53 | 23182.53 | 14-AUG-10:57 | 21611.33 | 07-AUG-03:01 | 8014.12 | 07-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.190792E+11 | 0.476298E+10 | 429.59 | 0.120093E+11 | 0.706998E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 33562.82 | 29-SEP-11:05 | 33562.82 | 29-SEP-11:05 | 19762.20 | 22-SEP-03:11 | 9168.50 | 29-SEP-10:57 | 0.00 | 01-SEP-00:01 |
October | 0.199501E+11 | 0.501496E+10 | 464.87 | 0.143752E+11 | 0.557492E+10 | 0.00 | 1.00 | 01-OCT-03:11 | 0.00 | 01-OCT-00:01 | 34764.83 | 01-OCT-03:52 | 33518.46 | 16-OCT-11:00 | 22600.30 | 01-OCT-03:52 | 9385.12 | 16-OCT-11:00 | 0.00 | 01-OCT-00:01 |
November | 0.496279E+10 | 0.135048E+10 | 249.32 | 0.385403E+10 | 0.110876E+10 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 33204.40 | 07-NOV-04:01 | 33204.40 | 29-NOV-04:42 | 19541.15 | 12-NOV-04:11 | 7960.73 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.428547E+10 | 0.116225E+10 | 203.23 | 0.398996E+10 | 0.295508E+09 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:03 | 33204.40 | 01-DEC-04:01 | 33204.40 | 19-DEC-04:11 | 17149.72 | 02-DEC-04:01 | 7960.73 | 01-DEC-04:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.145231E+12 | 0.364659E+11 | 3850.37 | 0.949448E+11 | 0.502866E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.221354E+10 | 0.617587E+09 | 143.52 | 0.165984E+10 | 0.295508E+09 | 0.00 | 1.00 | 0.00 | 33204.40 | 20356.75 | 17149.72 | 7960.73 | 0.00 | |||||||
Maximum of Months | 0.276852E+11 | 0.661375E+10 | 491.68 | 0.157333E+11 | 0.119519E+11 | 0.00 | 1.00 | 0.00 | 34764.83 | 33562.82 | 22600.30 | 9385.12 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.87 | 90.23 | 78.64 | 210.37 | 230.99 | 0.00 | 0.00 | 0.00 |
February | 178.19 | 81.54 | 96.65 | 208.67 | 209.15 | 0.00 | 0.00 | 0.00 |
March | 217.47 | 97.13 | 120.34 | 269.80 | 206.60 | 0.00 | 0.00 | 0.00 |
April | 277.21 | 139.09 | 138.12 | 384.95 | 171.86 | 0.00 | 0.00 | 0.00 |
May | 261.11 | 108.81 | 152.29 | 348.88 | 157.54 | 0.00 | 0.00 | 0.00 |
June | 259.78 | 112.78 | 147.00 | 368.19 | 128.41 | 0.00 | 0.00 | 0.00 |
July | 294.18 | 146.15 | 148.03 | 447.85 | 116.34 | 0.00 | 0.00 | 0.00 |
August | 290.76 | 154.53 | 136.23 | 447.14 | 120.33 | 0.00 | 0.00 | 0.00 |
September | 212.28 | 97.64 | 114.64 | 306.42 | 140.79 | 0.00 | 0.00 | 0.00 |
October | 187.09 | 96.03 | 91.06 | 277.68 | 156.39 | 0.00 | 0.00 | 0.00 |
November | 170.15 | 86.14 | 84.01 | 211.63 | 214.92 | 0.00 | 0.00 | 0.00 |
December | 163.57 | 91.17 | 72.41 | 203.21 | 232.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.69 | 108.65 | 115.04 | 307.76 | 173.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 163.57 | 81.54 | 72.41 | 203.21 | 116.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.18 | 154.53 | 152.29 | 447.85 | 232.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 574.01 | 421.41 | 152.60 | 864.98 | 311.64 | 0.00 | 0.00 | 0.00 |
February | 453.42 | 280.56 | 172.86 | 650.41 | 285.32 | 0.00 | 0.00 | 0.00 |
March | 361.63 | 176.16 | 185.47 | 512.00 | 292.93 | 0.00 | 0.00 | 0.00 |
April | 302.40 | 116.88 | 185.52 | 447.46 | 250.63 | 0.00 | 0.00 | 0.00 |
May | 213.06 | 25.80 | 187.26 | 254.24 | 230.39 | 0.00 | 0.00 | 0.00 |
June | 186.92 | 10.96 | 175.96 | 219.87 | 184.78 | 0.00 | 0.00 | 0.00 |
July | 197.13 | 21.08 | 176.05 | 270.61 | 165.96 | 0.00 | 0.00 | 0.00 |
August | 253.18 | 78.67 | 174.51 | 405.09 | 173.30 | 0.00 | 0.00 | 0.00 |
September | 347.67 | 172.72 | 174.95 | 561.10 | 198.96 | 0.00 | 0.00 | 0.00 |
October | 455.25 | 305.73 | 149.51 | 741.12 | 214.46 | 0.00 | 0.00 | 0.00 |
November | 552.98 | 391.80 | 161.18 | 832.65 | 288.34 | 0.00 | 0.00 | 0.00 |
December | 614.26 | 468.09 | 146.18 | 931.40 | 311.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.67 | 205.57 | 170.10 | 557.28 | 242.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.92 | 10.96 | 146.18 | 219.87 | 165.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 614.26 | 468.09 | 187.26 | 931.40 | 311.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.91 | 81.15 | 79.77 | 205.70 | 241.63 | 0.00 | 0.00 | 0.00 |
February | 192.18 | 88.83 | 103.35 | 237.47 | 214.83 | 0.00 | 0.00 | 0.00 |
March | 219.80 | 97.13 | 122.67 | 279.69 | 213.07 | 0.00 | 0.00 | 0.00 |
April | 302.93 | 157.49 | 145.44 | 430.86 | 174.71 | 0.00 | 0.00 | 0.00 |
May | 297.57 | 137.24 | 160.33 | 411.37 | 158.53 | 0.00 | 0.00 | 0.00 |
June | 315.16 | 157.37 | 157.79 | 459.91 | 125.91 | 0.00 | 0.00 | 0.00 |
July | 333.71 | 178.39 | 155.33 | 512.68 | 113.62 | 0.00 | 0.00 | 0.00 |
August | 313.14 | 169.56 | 143.58 | 485.29 | 120.60 | 0.00 | 0.00 | 0.00 |
September | 268.36 | 143.55 | 124.82 | 401.53 | 139.64 | 0.00 | 0.00 | 0.00 |
October | 206.14 | 112.95 | 93.19 | 313.81 | 159.71 | 0.00 | 0.00 | 0.00 |
November | 185.50 | 97.10 | 88.40 | 243.47 | 220.13 | 0.00 | 0.00 | 0.00 |
December | 163.17 | 87.24 | 75.92 | 211.61 | 242.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.76 | 125.82 | 120.94 | 349.99 | 176.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.91 | 81.15 | 75.92 | 205.70 | 113.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 333.71 | 178.39 | 160.33 | 512.68 | 242.48 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452289E+09 | 0.241665E+09 | 0.210625E+09 | 0.563463E+09 | 0.618691E+09 |
February | 0.431081E+09 | 0.197261E+09 | 0.233821E+09 | 0.504809E+09 | 0.505983E+09 |
March | 0.582479E+09 | 0.260162E+09 | 0.322317E+09 | 0.722620E+09 | 0.553347E+09 |
April | 0.718529E+09 | 0.360527E+09 | 0.358001E+09 | 0.997796E+09 | 0.445448E+09 |
May | 0.699345E+09 | 0.291440E+09 | 0.407905E+09 | 0.934451E+09 | 0.421961E+09 |
June | 0.673357E+09 | 0.292322E+09 | 0.381034E+09 | 0.954351E+09 | 0.332850E+09 |
July | 0.787937E+09 | 0.391451E+09 | 0.396486E+09 | 0.119951E+10 | 0.311593E+09 |
August | 0.778766E+09 | 0.413889E+09 | 0.364877E+09 | 0.119762E+10 | 0.322300E+09 |
September | 0.550237E+09 | 0.253088E+09 | 0.297150E+09 | 0.794244E+09 | 0.364923E+09 |
October | 0.501097E+09 | 0.257195E+09 | 0.243902E+09 | 0.743751E+09 | 0.418874E+09 |
November | 0.441035E+09 | 0.223279E+09 | 0.217756E+09 | 0.548537E+09 | 0.557064E+09 |
December | 0.438114E+09 | 0.244183E+09 | 0.193931E+09 | 0.544273E+09 | 0.623040E+09 |
Annual Sum or Average | 0.705427E+10 | 0.342646E+10 | 0.362781E+10 | 0.970542E+10 | 0.547608E+10 |
Minimum of Months | 0.431081E+09 | 0.197261E+09 | 0.193931E+09 | 0.504809E+09 | 0.311593E+09 |
Maximum of Months | 0.787937E+09 | 0.413889E+09 | 0.407905E+09 | 0.119951E+10 | 0.623040E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153742E+10 | 0.112870E+10 | 0.408730E+09 | 0.231677E+10 | 0.834707E+09 |
February | 0.109691E+10 | 0.678734E+09 | 0.418178E+09 | 0.157348E+10 | 0.690248E+09 |
March | 0.968579E+09 | 0.471815E+09 | 0.496764E+09 | 0.137135E+10 | 0.784585E+09 |
April | 0.783811E+09 | 0.302946E+09 | 0.480865E+09 | 0.115981E+10 | 0.649633E+09 |
May | 0.570672E+09 | 69109558.60 | 0.501563E+09 | 0.680963E+09 | 0.617086E+09 |
June | 0.484492E+09 | 28415816.11 | 0.456076E+09 | 0.569911E+09 | 0.478942E+09 |
July | 0.527981E+09 | 56459124.88 | 0.471522E+09 | 0.724801E+09 | 0.444502E+09 |
August | 0.678116E+09 | 0.210717E+09 | 0.467399E+09 | 0.108499E+10 | 0.464163E+09 |
September | 0.901151E+09 | 0.447684E+09 | 0.453467E+09 | 0.145437E+10 | 0.515710E+09 |
October | 0.121933E+10 | 0.818873E+09 | 0.400458E+09 | 0.198502E+10 | 0.574401E+09 |
November | 0.143334E+10 | 0.101555E+10 | 0.417782E+09 | 0.215824E+10 | 0.747368E+09 |
December | 0.164525E+10 | 0.125372E+10 | 0.391524E+09 | 0.249467E+10 | 0.834985E+09 |
Annual Sum or Average | 0.118471E+11 | 0.648272E+10 | 0.536433E+10 | 0.175744E+11 | 0.763633E+10 |
Minimum of Months | 0.484492E+09 | 28415816.11 | 0.391524E+09 | 0.569911E+09 | 0.444502E+09 |
Maximum of Months | 0.164525E+10 | 0.125372E+10 | 0.501563E+09 | 0.249467E+10 | 0.834985E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.430992E+09 | 0.217348E+09 | 0.213644E+09 | 0.550940E+09 | 0.647172E+09 |
February | 0.464924E+09 | 0.214889E+09 | 0.250035E+09 | 0.574482E+09 | 0.519725E+09 |
March | 0.588712E+09 | 0.260162E+09 | 0.328550E+09 | 0.749121E+09 | 0.570688E+09 |
April | 0.785186E+09 | 0.408205E+09 | 0.376981E+09 | 0.111678E+10 | 0.452859E+09 |
May | 0.797022E+09 | 0.367586E+09 | 0.429436E+09 | 0.110182E+10 | 0.424615E+09 |
June | 0.816894E+09 | 0.407896E+09 | 0.408997E+09 | 0.119209E+10 | 0.326358E+09 |
July | 0.893816E+09 | 0.477793E+09 | 0.416023E+09 | 0.137315E+10 | 0.304325E+09 |
August | 0.838711E+09 | 0.454142E+09 | 0.384569E+09 | 0.129980E+10 | 0.323006E+09 |
September | 0.695595E+09 | 0.372071E+09 | 0.323524E+09 | 0.104076E+10 | 0.361954E+09 |
October | 0.552123E+09 | 0.302513E+09 | 0.249610E+09 | 0.840510E+09 | 0.427768E+09 |
November | 0.480820E+09 | 0.251678E+09 | 0.229142E+09 | 0.631082E+09 | 0.570569E+09 |
December | 0.437029E+09 | 0.233674E+09 | 0.203355E+09 | 0.566772E+09 | 0.649457E+09 |
Annual Sum or Average | 0.778182E+10 | 0.396796E+10 | 0.381387E+10 | 0.110373E+11 | 0.557850E+10 |
Minimum of Months | 0.430992E+09 | 0.214889E+09 | 0.203355E+09 | 0.550940E+09 | 0.304325E+09 |
Maximum of Months | 0.893816E+09 | 0.477793E+09 | 0.429436E+09 | 0.137315E+10 | 0.649457E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1258.19 | 761.40 | 903.79 | 592.78 | 311.01 | 0.00 | 0.00 |
February | 1077.69 | 690.45 | 823.79 | 450.93 | 372.86 | 0.00 | 0.00 |
March | 1034.61 | 685.72 | 798.90 | 370.42 | 428.48 | 0.00 | 0.00 |
April | 1237.56 | 571.49 | 882.53 | 413.46 | 469.08 | 0.00 | 0.00 |
May | 988.27 | 520.24 | 771.74 | 271.85 | 499.89 | 0.00 | 0.00 |
June | 1026.05 | 417.18 | 761.86 | 281.11 | 480.75 | 0.00 | 0.00 |
July | 1213.80 | 378.58 | 825.02 | 345.62 | 479.40 | 0.00 | 0.00 |
August | 1322.29 | 399.00 | 857.08 | 402.76 | 454.32 | 0.00 | 0.00 |
September | 1254.53 | 464.87 | 828.31 | 413.91 | 414.41 | 0.00 | 0.00 |
October | 1318.84 | 516.78 | 848.47 | 514.70 | 333.77 | 0.00 | 0.00 |
November | 1266.28 | 701.90 | 908.64 | 575.04 | 333.60 | 0.00 | 0.00 |
December | 1321.47 | 762.09 | 941.01 | 646.50 | 294.51 | 0.00 | 0.00 |
Annual Sum or Average | 1194.22 | 571.87 | 846.12 | 440.04 | 406.08 | 0.00 | 0.00 |
Minimum of Months | 988.27 | 378.58 | 761.86 | 271.85 | 294.51 | 0.00 | 0.00 |
Maximum of Months | 1322.29 | 762.09 | 941.01 | 646.50 | 499.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336994E+10 | 0.203934E+10 | 0.242071E+10 | 0.158771E+10 | 0.832999E+09 | 0.00 | 0.00 |
February | 0.260715E+10 | 0.167034E+10 | 0.199292E+10 | 0.109088E+10 | 0.902034E+09 | 0.00 | 0.00 |
March | 0.277110E+10 | 0.183664E+10 | 0.213977E+10 | 0.992139E+09 | 0.114763E+10 | 0.00 | 0.00 |
April | 0.320775E+10 | 0.148130E+10 | 0.228753E+10 | 0.107168E+10 | 0.121585E+10 | 0.00 | 0.00 |
May | 0.264697E+10 | 0.139340E+10 | 0.206704E+10 | 0.728135E+09 | 0.133890E+10 | 0.00 | 0.00 |
June | 0.265952E+10 | 0.108132E+10 | 0.197474E+10 | 0.728635E+09 | 0.124611E+10 | 0.00 | 0.00 |
July | 0.325103E+10 | 0.101399E+10 | 0.220973E+10 | 0.925704E+09 | 0.128403E+10 | 0.00 | 0.00 |
August | 0.354161E+10 | 0.106868E+10 | 0.229559E+10 | 0.107875E+10 | 0.121685E+10 | 0.00 | 0.00 |
September | 0.325174E+10 | 0.120495E+10 | 0.214698E+10 | 0.107284E+10 | 0.107414E+10 | 0.00 | 0.00 |
October | 0.353238E+10 | 0.138413E+10 | 0.227255E+10 | 0.137858E+10 | 0.893970E+09 | 0.00 | 0.00 |
November | 0.328219E+10 | 0.181933E+10 | 0.235519E+10 | 0.149051E+10 | 0.864680E+09 | 0.00 | 0.00 |
December | 0.353943E+10 | 0.204119E+10 | 0.252039E+10 | 0.173158E+10 | 0.788810E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376608E+11 | 0.180346E+11 | 0.266831E+11 | 0.138771E+11 | 0.128060E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260715E+10 | 0.101399E+10 | 0.197474E+10 | 0.728135E+09 | 0.788810E+09 | 0.00 | 0.00 |
Maximum of Months | 0.354161E+10 | 0.204119E+10 | 0.252039E+10 | 0.173158E+10 | 0.133890E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638549E+10 | -0.622515E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160335367.3 | 81.22 | 0.00 | 0.00 |
February | 0.577869E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -144397481.5 | 81.22 | 0.00 | 0.00 |
March | 0.645466E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160794562.5 | 81.22 | 0.00 | 0.00 |
April | 0.619597E+10 | -0.604345E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152514022.7 | 81.22 | 0.00 | 0.00 |
May | 0.641719E+10 | -0.626016E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157031845.5 | 81.22 | 0.00 | 0.00 |
June | 0.623702E+10 | -0.608654E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150475220.6 | 81.22 | 0.00 | 0.00 |
July | 0.637185E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154771529.4 | 81.21 | 0.00 | 0.00 |
August | 0.644992E+10 | -0.629520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154711068.0 | 81.21 | 0.00 | 0.00 |
September | 0.619498E+10 | -0.604480E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150174136.2 | 81.21 | 0.00 | 0.00 |
October | 0.637936E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155549075.2 | 81.21 | 0.00 | 0.00 |
November | 0.617776E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153142042.7 | 81.22 | 0.00 | 0.00 |
December | 0.637704E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159971640.2 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754199E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.185387E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577869E+10 | -0.629520E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160794562.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645466E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144397481.5 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.211300E+11 | -0.202360E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -894016986.9 | 58.99 | 0.00 | 0.00 |
February | 0.191395E+11 | -0.183359E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -803653676.0 | 58.99 | 0.00 | 0.00 |
March | 0.211567E+11 | -0.202585E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -898205819.0 | 58.99 | 0.00 | 0.00 |
April | 0.198874E+11 | -0.190465E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -840908584.2 | 58.99 | 0.00 | 0.00 |
May | 0.200888E+11 | -0.192250E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -863792868.0 | 58.99 | 0.00 | 0.00 |
June | 0.190703E+11 | -0.182480E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -822338622.3 | 58.99 | 0.00 | 0.00 |
July | 0.192048E+11 | -0.183616E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843144291.5 | 58.99 | 0.00 | 0.00 |
August | 0.194065E+11 | -0.185639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -842603010.1 | 58.99 | 0.00 | 0.00 |
September | 0.188686E+11 | -0.180491E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -819510066.7 | 58.99 | 0.00 | 0.00 |
October | 0.198575E+11 | -0.190075E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -850015742.0 | 58.98 | 0.00 | 0.00 |
November | 0.197316E+11 | -0.188850E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -846632012.4 | 58.99 | 0.00 | 0.00 |
December | 0.208255E+11 | -0.199347E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -890832975.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.238367E+12 | -0.228152E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.102157E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.188686E+11 | -0.202585E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -898205819.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.211567E+11 | -0.180491E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -803653676.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.50 | 01-JAN-07:19 | 1014.63 | 25.54 | 156.33 | 276.50 | 1010.72 | 25.45 | 170.17 | 277.67 |
February | 279.67 | 0.52 | 0.50 | 01-FEB-07:30 | 1007.25 | 23.33 | 145.00 | 268.67 | 948.07 | 23.67 | 163.83 | 270.00 |
March | 338.17 | 0.53 | 0.50 | 01-MAR-06:00 | 938.42 | 21.34 | 141.33 | 319.50 | 909.55 | 20.95 | 132.33 | 321.17 |
April | 358.33 | 0.52 | 0.50 | 01-APR-05:00 | 817.14 | 20.15 | 82.50 | 336.00 | 895.74 | 20.13 | 98.83 | 338.00 |
May | 393.83 | 0.53 | 0.50 | 01-MAY-06:30 | 820.59 | 20.26 | 78.83 | 367.33 | 701.23 | 19.82 | 82.33 | 374.33 |
June | 381.00 | 0.53 | 0.50 | 01-JUN-06:30 | 940.06 | 21.38 | 80.67 | 362.50 | 611.16 | 19.66 | 67.33 | 364.67 |
July | 408.67 | 0.53 | 0.50 | 01-JUL-05:00 | 965.26 | 21.02 | 94.33 | 374.00 | 708.84 | 19.71 | 81.00 | 376.67 |
August | 390.67 | 0.53 | 0.50 | 01-AUG-06:00 | 847.20 | 19.79 | 68.83 | 359.83 | 896.77 | 19.82 | 92.67 | 362.67 |
September | 328.83 | 0.53 | 0.50 | 01-SEP-06:49 | 1023.98 | 19.95 | 63.50 | 310.33 | 757.01 | 20.37 | 110.17 | 310.33 |
October | 296.17 | 0.52 | 0.50 | 01-OCT-09:39 | 829.36 | 22.15 | 104.83 | 296.00 | 767.08 | 21.68 | 99.50 | 298.50 |
November | 300.00 | 0.53 | 0.50 | 01-NOV-06:49 | 982.20 | 25.37 | 168.83 | 280.17 | 964.16 | 25.03 | 181.33 | 277.67 |
December | 297.00 | 0.53 | 0.50 | 01-DEC-07:19 | 1003.45 | 26.02 | 149.83 | 278.33 | 1073.10 | 24.24 | 121.67 | 274.50 |
Annual Sum or Average | 4065.67 | 0.53 | 927.59 | 21.98 | 1334.83 | 3829.17 | 842.00 | 21.47 | 1401.17 | 3846.17 | ||
Minimum of Months | 279.67 | 0.52 | 0.50 | 817.14 | 19.79 | 63.50 | 268.67 | 611.16 | 19.66 | 67.33 | 270.00 | |
Maximum of Months | 408.67 | 0.53 | 0.50 | 1023.98 | 26.02 | 168.83 | 374.00 | 1073.10 | 25.45 | 181.33 | 376.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.518418E+10 | 29949.85 | 07-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336712E+10 | 26964.71 | 10-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.525560E+10 | 35515.13 | 30-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120629E+10 | 18860.99 | 20-APR-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.938324E+09 | 21718.91 | 14-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73354948.23 | 8987.09 | 13-JUN-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24310126.74 | 10183.87 | 20-SEP-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351006E+09 | 17209.86 | 28-OCT-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194399E+10 | 23320.76 | 18-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419450E+10 | 25680.69 | 13-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525560E+10 | 35515.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.462098E+09 | 18134.48 | 08-JAN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31509424.48 | 9001.77 | 09-FEB-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303039E+09 | 11348.88 | 08-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5028313.78 | 5530.77 | 01-APR-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5456903.23 | 3878.40 | 05-NOV-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162056E+09 | 9280.65 | 23-DEC-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.969187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.462098E+09 | 18134.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.376342E+10 | 0.329353E+10 | 28352.35 | 18-JAN-13:00 | 28041.02 | 0.00 |
February | 0.00 | 0.00 | 0.117040E+10 | 0.104847E+10 | 24690.60 | 01-FEB-12:10 | 24468.88 | 0.00 |
March | 0.00 | 0.00 | 0.204239E+10 | 0.158858E+10 | 22936.46 | 22-MAR-13:00 | 14920.89 | 0.00 |
April | 0.00 | 0.00 | 0.661540E+10 | 0.499122E+10 | 72736.05 | 27-APR-03:01 | 38773.16 | 0.00 |
May | 0.00 | 0.00 | 0.605814E+10 | 0.452041E+10 | 72736.05 | 25-MAY-03:01 | 46005.60 | 0.00 |
June | 0.00 | 0.00 | 0.145230E+11 | 0.981890E+10 | 72736.05 | 27-JUN-03:01 | 39312.71 | 0.00 |
July | 0.00 | 0.00 | 0.292923E+11 | 0.181097E+11 | 74881.10 | 23-JUL-03:02 | 35374.13 | 0.00 |
August | 0.00 | 0.00 | 0.322895E+11 | 0.195415E+11 | 75199.68 | 19-AUG-03:02 | 37701.94 | 0.00 |
September | 0.00 | 0.00 | 0.193110E+11 | 0.132481E+11 | 74906.41 | 22-SEP-03:41 | 34220.20 | 0.00 |
October | 0.00 | 0.00 | 0.220762E+11 | 0.171229E+11 | 77045.45 | 05-OCT-03:01 | 38888.18 | 0.00 |
November | 0.00 | 0.00 | 0.352499E+10 | 0.311747E+10 | 36326.31 | 01-NOV-03:01 | 26754.60 | 0.00 |
December | 0.00 | 0.00 | 0.426427E+10 | 0.416516E+10 | 28998.91 | 19-DEC-13:00 | 28998.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144931E+12 | 0.100566E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.117040E+10 | 0.104847E+10 | 22936.46 | 14920.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.322895E+11 | 0.195415E+11 | 77045.45 | 46005.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.432998E+10 | 0.350172E+10 | 33204.40 | 22-JAN-04:01 | 18807.69 | 0.00 |
February | 0.00 | 0.00 | 0.221354E+10 | 0.165984E+10 | 33204.40 | 01-FEB-04:42 | 30028.11 | 0.00 |
March | 0.00 | 0.00 | 0.297391E+10 | 0.203959E+10 | 33204.40 | 17-MAR-03:01 | 15920.68 | 0.00 |
April | 0.00 | 0.00 | 0.833838E+10 | 0.586843E+10 | 33204.40 | 16-APR-03:01 | 18178.38 | 0.00 |
May | 0.00 | 0.00 | 0.919692E+10 | 0.637604E+10 | 33204.40 | 25-MAY-03:42 | 19015.01 | 0.00 |
June | 0.00 | 0.00 | 0.160415E+11 | 0.102399E+11 | 33204.40 | 24-JUN-03:01 | 18994.83 | 0.00 |
July | 0.00 | 0.00 | 0.261744E+11 | 0.152975E+11 | 33489.42 | 23-JUL-03:11 | 13752.48 | 0.00 |
August | 0.00 | 0.00 | 0.276852E+11 | 0.157333E+11 | 34674.91 | 14-AUG-10:53 | 23174.31 | 0.00 |
September | 0.00 | 0.00 | 0.190792E+11 | 0.120093E+11 | 33562.82 | 29-SEP-11:05 | 33562.82 | 0.00 |
October | 0.00 | 0.00 | 0.199501E+11 | 0.143752E+11 | 34764.83 | 01-OCT-03:52 | 12164.53 | 0.00 |
November | 0.00 | 0.00 | 0.496279E+10 | 0.385403E+10 | 33204.40 | 07-NOV-04:01 | 20702.63 | 0.00 |
December | 0.00 | 0.00 | 0.428547E+10 | 0.398996E+10 | 33204.40 | 01-DEC-04:01 | 17134.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145231E+12 | 0.949448E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.221354E+10 | 0.165984E+10 | 33204.40 | 12164.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.276852E+11 | 0.157333E+11 | 34764.83 | 33562.82 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8017.08 | 15266.05 | 27-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 8041.19 | 15285.30 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 8025.51 | 15223.52 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7810.67 | 14953.31 | 03-APR-18:22 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 7640.55 | 14631.90 | 01-MAY-18:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 7503.17 | 14265.20 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 7318.57 | 13977.86 | 06-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 7393.80 | 13956.71 | 31-AUG-18:08 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 7426.44 | 14178.47 | 29-SEP-18:10 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7559.20 | 14520.38 | 30-OCT-18:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7748.26 | 14885.50 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 7904.68 | 15143.00 | 29-DEC-07:55 |
Annual Sum or Average | 0.00 | 7697.13 | ||||
Minimum of Months | 0.00 | 0.00 | 7318.57 | 13956.71 | ||
Maximum of Months | 0.00 | 0.00 | 8041.19 | 15285.30 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:02 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193539E+10 | 0.24 | 824.13 | 01-JAN-00:02 | 0.27 |
February | 0.173067E+10 | 0.23 | 824.13 | 01-FEB-00:05 | 0.27 |
March | 0.191536E+10 | 0.23 | 824.13 | 01-MAR-00:02 | 0.27 |
April | 0.186987E+10 | 0.23 | 824.13 | 01-APR-03:02 | 0.27 |
May | 0.194998E+10 | 0.24 | 824.13 | 01-MAY-01:35 | 0.27 |
June | 0.196926E+10 | 0.25 | 824.13 | 01-JUN-03:01 | 0.27 |
July | 0.206766E+10 | 0.25 | 824.13 | 01-JUL-01:00 | 0.27 |
August | 0.206890E+10 | 0.25 | 824.13 | 01-AUG-00:45 | 0.27 |
September | 0.198805E+10 | 0.25 | 824.13 | 01-SEP-01:05 | 0.27 |
October | 0.202975E+10 | 0.25 | 824.13 | 01-OCT-00:40 | 0.27 |
November | 0.187457E+10 | 0.24 | 824.13 | 01-NOV-01:25 | 0.27 |
December | 0.193069E+10 | 0.23 | 824.13 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.233301E+11 | 0.24 | |||
Minimum of Months | 0.173067E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.206890E+10 | 0.25 | 824.13 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.562718E+10 | 0.73 | 3459.80 | 07-JAN-05:03 | 1.08 |
February | 0.503793E+10 | 0.73 | 3358.38 | 10-FEB-05:03 | 1.05 |
March | 0.562976E+10 | 0.73 | 3648.89 | 30-MAR-04:01 | 1.10 |
April | 0.531655E+10 | 0.72 | 3083.05 | 20-APR-04:05 | 1.00 |
May | 0.548377E+10 | 0.72 | 3180.15 | 14-MAY-04:04 | 1.02 |
June | 0.528549E+10 | 0.72 | 4437.17 | 28-JUN-03:01 | 1.22 |
July | 0.550324E+10 | 0.73 | 5642.90 | 15-JUL-03:01 | 1.37 |
August | 0.551698E+10 | 0.73 | 6105.56 | 09-AUG-03:01 | 1.42 |
September | 0.531867E+10 | 0.73 | 6105.56 | 30-SEP-03:01 | 1.42 |
October | 0.551955E+10 | 0.73 | 6105.56 | 02-OCT-03:01 | 1.41 |
November | 0.534171E+10 | 0.72 | 3234.57 | 18-NOV-05:04 | 1.03 |
December | 0.559374E+10 | 0.73 | 3314.75 | 13-DEC-05:02 | 1.04 |
Annual Sum or Average | 0.651746E+11 | 0.73 | |||
Minimum of Months | 0.503793E+10 | 0.72 | 3083.05 | 1.00 | |
Maximum of Months | 0.562976E+10 | 0.73 | 6105.56 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150786E+10 | 0.47 | 1661.84 | 15-JAN-04:01 | 0.90 |
February | 0.135633E+10 | 0.47 | 1661.84 | 01-FEB-04:01 | 0.89 |
March | 0.150333E+10 | 0.47 | 1661.84 | 04-MAR-04:01 | 0.89 |
April | 0.146024E+10 | 0.47 | 1661.84 | 03-APR-03:01 | 0.89 |
May | 0.150926E+10 | 0.47 | 1661.84 | 01-MAY-03:01 | 0.89 |
June | 0.150427E+10 | 0.50 | 1661.84 | 01-JUN-03:01 | 0.89 |
July | 0.171807E+10 | 0.53 | 1661.84 | 01-JUL-03:01 | 0.89 |
August | 0.175544E+10 | 0.54 | 1661.84 | 01-AUG-03:01 | 0.89 |
September | 0.155985E+10 | 0.51 | 1661.84 | 01-SEP-03:01 | 0.89 |
October | 0.163542E+10 | 0.51 | 1661.84 | 01-OCT-03:11 | 0.89 |
November | 0.145614E+10 | 0.47 | 1661.84 | 01-NOV-03:01 | 0.89 |
December | 0.150314E+10 | 0.47 | 1661.84 | 01-DEC-04:01 | 0.89 |
Annual Sum or Average | 0.184693E+11 | 0.49 | |||
Minimum of Months | 0.135633E+10 | 0.47 | 1661.84 | 0.89 | |
Maximum of Months | 0.175544E+10 | 0.54 | 1661.84 | 0.90 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:02 | 5.36 | 5.36 | 49.91 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 49.97 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:02 | 5.36 | 5.36 | 49.87 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 52.28 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 52.37 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 52.94 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 52.97 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 53.08 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.75 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.16 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.65 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 50.44 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 49.87 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 53.16 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 49.91 | 59.90 | 8017.08 | 15266.05 | 27-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.97 | 58.46 | 8041.19 | 15285.30 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 49.87 | 58.80 | 8025.51 | 15223.52 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.85 | 50.85 | 7810.67 | 14953.31 | 03-APR-18:22 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 50.99 | 50.99 | 7640.55 | 14631.90 | 01-MAY-18:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.86 | 50.86 | 7503.17 | 14265.20 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.58 | 51.58 | 7318.57 | 13977.86 | 06-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.67 | 51.67 | 7393.80 | 13956.71 | 31-AUG-18:08 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.43 | 51.43 | 7426.44 | 14178.47 | 29-SEP-18:10 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 49.26 | 49.26 | 7559.20 | 14520.38 | 30-OCT-18:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.84 | 50.84 | 7748.26 | 14885.50 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.44 | 59.43 | 7904.68 | 15143.00 | 29-DEC-07:55 |
Annual Sum or Average | 0.00 | 7697.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.26 | 49.26 | 7318.57 | 13956.71 | ||
Maximum of Months | 0.00 | 0.00 | 51.67 | 59.90 | 8041.19 | 15285.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.679989E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.541224E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.627132E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.737084E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.739555E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.966954E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.138644E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.146223E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110616E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.120385E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.644691E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.693454E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.107888E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.541224E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.146223E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.266535E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.197392E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.230642E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.365539E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.395417E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.554979E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.801578E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.836919E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.632283E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.665038E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.280662E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.266538E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.549352E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.197392E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.836919E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.562718E+10 | 0.376342E+10 | 0.518418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503793E+10 | 0.117040E+10 | 0.336712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.562976E+10 | 0.204239E+10 | 0.525560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.531655E+10 | 0.661392E+10 | 0.120629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.548377E+10 | 0.605369E+10 | 0.938324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528549E+10 | 0.145080E+11 | 73354948.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.550324E+10 | 0.292497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.551698E+10 | 0.322608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.531867E+10 | 0.192796E+11 | 24310126.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.551955E+10 | 0.220224E+11 | 0.351006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534171E+10 | 0.352499E+10 | 0.194399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.559374E+10 | 0.426427E+10 | 0.419450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651746E+11 | 0.144754E+12 | 0.225387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.503793E+10 | 0.117040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.562976E+10 | 0.322608E+11 | 0.525560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150786E+10 | 0.432365E+10 | 0.462098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135633E+10 | 0.220834E+10 | 31509424.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150333E+10 | 0.297197E+10 | 0.303039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146024E+10 | 0.833629E+10 | 5028313.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150926E+10 | 0.919257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150427E+10 | 0.160358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171807E+10 | 0.261649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175544E+10 | 0.276653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155985E+10 | 0.190542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163542E+10 | 0.199110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145614E+10 | 0.495984E+10 | 5456903.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150314E+10 | 0.427558E+10 | 0.162056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184693E+11 | 0.145099E+12 | 0.969187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135633E+10 | 0.220834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175544E+10 | 0.276653E+11 | 0.462098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.562718E+10 | 0.00 | 0.00 | 0.00 | 0.117271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503793E+10 | 0.00 | 0.00 | 0.00 | 0.374315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.562976E+10 | 0.00 | 0.00 | 0.00 | 0.641560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.531655E+10 | 0.00 | 0.00 | 0.00 | 0.205429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.548377E+10 | 0.00 | 0.00 | 0.00 | 0.191179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528549E+10 | 0.00 | 0.00 | 0.00 | 0.438405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.550324E+10 | 0.00 | 0.00 | 0.00 | 0.836112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.551698E+10 | 0.00 | 0.00 | 0.00 | 0.910536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.531867E+10 | 0.00 | 0.00 | 0.00 | 0.574289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.551955E+10 | 0.00 | 0.00 | 0.00 | 0.651896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534171E+10 | 0.00 | 0.00 | 0.00 | 0.110520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.559374E+10 | 0.00 | 0.00 | 0.00 | 0.134079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651746E+11 | 0.00 | 0.00 | 0.00 | 0.427130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.503793E+10 | 0.00 | 0.00 | 0.00 | 0.374315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.562976E+10 | 0.00 | 0.00 | 0.00 | 0.910536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150786E+10 | 0.00 | 0.00 | 0.00 | 0.115749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135633E+10 | 0.00 | 0.00 | 0.00 | 0.617587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150333E+10 | 0.00 | 0.00 | 0.00 | 0.803089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146024E+10 | 0.00 | 0.00 | 0.00 | 0.219514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150926E+10 | 0.00 | 0.00 | 0.00 | 0.244491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150427E+10 | 0.00 | 0.00 | 0.00 | 0.404552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171807E+10 | 0.00 | 0.00 | 0.00 | 0.629771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175544E+10 | 0.00 | 0.00 | 0.00 | 0.661375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155985E+10 | 0.00 | 0.00 | 0.00 | 0.476298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163542E+10 | 0.00 | 0.00 | 0.00 | 0.501496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145614E+10 | 0.00 | 0.00 | 0.00 | 0.135048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150314E+10 | 0.00 | 0.00 | 0.00 | 0.116225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184693E+11 | 0.00 | 0.00 | 0.00 | 0.364659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135633E+10 | 0.00 | 0.00 | 0.00 | 0.617587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175544E+10 | 0.00 | 0.00 | 0.00 | 0.661375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288112E+11 | 132105.89 | 0.00 | 29073471.23 | 0.00 | 29896387.31 | 0.126836E+11 | 0.00 | 3.73 |
February | 0.259307E+11 | 0.00 | 0.00 | 17383197.50 | 0.00 | 21871476.46 | 0.117075E+11 | 0.00 | 3.67 |
March | 0.322364E+11 | 0.00 | 0.00 | 22365366.92 | 0.00 | 28465784.80 | 0.101475E+11 | 0.00 | 3.69 |
April | 0.175021E+11 | 7280460.95 | 0.00 | 58329011.24 | 0.00 | 2716650.20 | 0.177293E+11 | 0.00 | 3.88 |
May | 0.164760E+11 | 0.00 | 0.00 | 62242180.05 | 0.00 | 5682463.55 | 0.201607E+11 | 0.00 | 3.92 |
June | 0.820070E+10 | 49238367.61 | 0.00 | 86962996.98 | 0.00 | 0.00 | 0.201997E+11 | 0.00 | 4.09 |
July | 0.424466E+10 | 0.156380E+10 | 0.00 | 97651014.94 | 0.00 | 0.00 | 0.161301E+11 | 0.00 | 4.17 |
August | 0.353782E+10 | 0.189242E+10 | 0.00 | 97675510.76 | 0.00 | 0.00 | 0.153494E+11 | 0.00 | 4.17 |
September | 0.646651E+10 | 0.654624E+09 | 0.00 | 93146132.32 | 78299.86 | 0.00 | 0.195871E+11 | 0.00 | 4.11 |
October | 0.718666E+10 | 0.119160E+10 | 0.00 | 80101337.77 | 517580.77 | 1379513.73 | 0.189963E+11 | 0.00 | 4.08 |
November | 0.202111E+11 | 4103920.94 | 0.00 | 37204972.67 | 0.00 | 7054926.67 | 0.182830E+11 | 0.00 | 3.77 |
December | 0.267502E+11 | 0.00 | 0.00 | 32718881.24 | 0.00 | 24967303.63 | 0.138259E+11 | 0.00 | 3.74 |
Annual Sum or Average | 0.197554E+12 | 0.536320E+10 | 0.00 | 0.714854E+09 | 595880.63 | 0.122035E+09 | 0.194800E+12 | 0.00 | 3.92 |
Minimum of Months | 0.353782E+10 | 0.00 | 0.00 | 17383197.50 | 0.00 | 0.00 | 0.101475E+11 | 0.00 | 3.67 |
Maximum of Months | 0.322364E+11 | 0.189242E+10 | 0.00 | 97675510.76 | 517580.77 | 29896387.31 | 0.201997E+11 | 0.00 | 4.17 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139787E+11 | 0.00 | 0.00 | 60181482.52 | 0.00 | 0.00 | 0.286438E+11 | 0.00 | 7.45 |
February | 0.118180E+11 | 0.00 | 0.00 | 53825847.44 | 0.00 | 0.00 | 0.273789E+11 | 0.00 | 7.49 |
March | 0.162988E+11 | 0.00 | 0.00 | 57502948.48 | 0.00 | 0.00 | 0.270377E+11 | 0.00 | 7.48 |
April | 0.840326E+10 | 270514.53 | 0.00 | 0.102492E+09 | 0.00 | 0.00 | 0.288536E+11 | 0.00 | 7.53 |
May | 0.665717E+10 | 0.00 | 0.00 | 0.108424E+09 | 0.00 | 0.00 | 0.314881E+11 | 0.00 | 7.54 |
June | 0.183123E+10 | 3704665.55 | 0.00 | 0.122364E+09 | 0.00 | 0.00 | 0.280025E+11 | 0.00 | 7.70 |
July | 0.136760E+09 | 0.768990E+09 | 0.00 | 0.136550E+09 | 0.00 | 0.00 | 0.219647E+11 | 0.00 | 8.02 |
August | 79796262.29 | 0.926826E+09 | 0.00 | 0.138717E+09 | 0.00 | 0.00 | 0.204940E+11 | 0.00 | 8.10 |
September | 0.625771E+09 | 0.385174E+09 | 0.00 | 0.127011E+09 | 0.00 | 0.00 | 0.263425E+11 | 0.00 | 7.83 |
October | 0.263616E+10 | 0.359056E+09 | 0.00 | 0.115210E+09 | 0.00 | 0.00 | 0.253900E+11 | 0.00 | 7.80 |
November | 0.951848E+10 | 0.00 | 0.00 | 78072732.39 | 0.00 | 0.00 | 0.307953E+11 | 0.00 | 7.49 |
December | 0.131686E+11 | 0.00 | 0.00 | 63212482.91 | 0.00 | 0.00 | 0.295195E+11 | 0.00 | 7.45 |
Annual Sum or Average | 0.851527E+11 | 0.244402E+10 | 0.00 | 0.116356E+10 | 0.00 | 0.00 | 0.325911E+12 | 0.00 | 7.66 |
Minimum of Months | 79796262.29 | 0.00 | 0.00 | 53825847.44 | 0.00 | 0.00 | 0.204940E+11 | 0.00 | 7.45 |
Maximum of Months | 0.162988E+11 | 0.926826E+09 | 0.00 | 0.138717E+09 | 0.00 | 0.00 | 0.314881E+11 | 0.00 | 8.10 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.577945E+11 | 0.104211E+11 | 0.154842E+12 | 0.121732E+10 | 0.342944E+11 |
February | 0.720559E+11 | 0.103103E+11 | 0.140224E+12 | 0.683517E+09 | 0.250415E+11 |
March | 0.102744E+12 | 0.126898E+11 | 0.156287E+12 | 0.767307E+09 | 0.310874E+11 |
April | 0.144788E+12 | 0.119824E+11 | 0.132752E+12 | 0.195117E+10 | 0.454619E+11 |
May | 0.154261E+12 | 0.125756E+11 | 0.137244E+12 | 0.245909E+10 | 0.458919E+11 |
June | 0.154852E+12 | 0.109168E+11 | 0.112107E+12 | 0.270878E+10 | 0.641753E+11 |
July | 0.167935E+12 | 0.883613E+10 | 0.835336E+11 | 0.210466E+10 | 0.973035E+11 |
August | 0.151564E+12 | 0.802732E+10 | 0.775020E+11 | 0.190209E+10 | 0.102935E+12 |
September | 0.117035E+12 | 0.830805E+10 | 0.101982E+12 | 0.259676E+10 | 0.743547E+11 |
October | 0.789508E+11 | 0.706281E+10 | 0.103277E+12 | 0.264985E+10 | 0.782555E+11 |
November | 0.632190E+11 | 0.991829E+10 | 0.144951E+12 | 0.155531E+10 | 0.337294E+11 |
December | 0.517453E+11 | 0.994606E+10 | 0.153762E+12 | 0.127158E+10 | 0.344689E+11 |
Annual Sum or Average | 0.131694E+13 | 0.120995E+12 | 0.149846E+13 | 0.218674E+11 | 0.667000E+12 |
Minimum of Months | 0.517453E+11 | 0.706281E+10 | 0.775020E+11 | 0.683517E+09 | 0.250415E+11 |
Maximum of Months | 0.167935E+12 | 0.126898E+11 | 0.156287E+12 | 0.270878E+10 | 0.102935E+12 |