Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:25:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1914.95 | 3746.33 | 3746.33 |
Net Site Energy | 1914.95 | 3746.33 | 3746.33 |
Total Source Energy | 4432.40 | 8671.37 | 8671.37 |
Net Source Energy | 4432.40 | 8671.37 | 8671.37 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 29.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 346.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 25.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 130.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.40 | 283.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 54.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1131.35 | 783.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 29.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 346.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 25.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 130.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.40 | 283.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 29.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 346.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 49.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 25.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 130.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.40 | 283.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 54.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 146.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1080.39 | 613.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 985.99 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2213.32 | 1533.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 146.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1080.39 | 613.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 985.99 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2213.32 | 1533.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1131.347 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1131.347 | 100.00 |
Total On-Site and Utility Electric Sources | 1131.347 | 100.00 |
Total Electricity End Uses | 1131.347 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 777.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5899.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 7.7280 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.0598 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.0912 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.7280 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.0598 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.0912 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.0912 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-SEP-18:49 | 05-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 13-FEB-19:10 |
Heating | 0.00 | 75393.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38396.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18708.11 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9034.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4426.49 | 14739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1958.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 78095.82 | 103709.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 75393.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 38396.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 17680.61 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9034.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4426.49 | 14739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 688.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 32.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1096.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1423.36 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 411.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.80 | 307.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 172.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3582.97 | 849.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 63.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2146.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 307.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 805.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.17 | 602.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 338.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7009.59 | 1661.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 63.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2146.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 307.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 805.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.17 | 602.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 338.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7009.59 | 1661.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.81 |
KITCHEN DIRECT AIR | 1.59 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.81 | 3.81 | 3.81 | 3.81 | 3.81 | 3.81 | 1.00 | 0.999913 | 3.81 |
PSZ-AC_2:2 | 1.59 | 1.59 | 1.59 | 1.59 | 1.59 | 1.59 | 1.00 | 1.00 | 1.59 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.81 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.59 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.81 | 6507.04 |
PSZ-AC_2:2_ADDAQ FAN | 1.59 | 1703.77 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.81 | 3.81 | 3.81 | 2.51 | 94571.90 | 113875.25 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.59 | 1.59 | 1.59 | 1.05 | 39539.07 | 70233.14 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.81 | 1.90 | 2.54 | 94571.90 | 47285.95 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.59 | 0.796119 | 1.06 | 39539.07 | 19769.53 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 113875.25 |
PSZ-AC_2:2 HEATING COIL | 70233.14 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 7.728 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 72.655 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.060 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1069.700 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2872.862 | 7.728 | 10.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2872.862 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1262.985 | 9.060 | 167.774 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1262.985 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7390 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27638744E-12 | 0.13692172E-14 | -0.80454349E-13 | 0.78568260E-16 |
34 | 6 | 0.25667740E-07 | 0.27924344E-09 | 0.59050449E-08 | -0.11914668E-12 |
35 | 5 | -0.17473551E-03 | 0.24386372E-05 | -0.90062287E-04 | 0.58456630E-08 |
36 | 4 | 0.27398001 | 0.12082630E-02 | 0.93158629E-01 | -0.31026392E-04 |
37 | 3 | -6.9061245 | 0.38026294E-01 | -2.2320589 | 0.27244997E-01 |
38 | 2 | 39.682701 | 0.13706054 | 14.825764 | -0.32010675 |
39 | 1 | -79.634567 | 0.62587550E-01 | -28.747502 | 1.0592017 |
40 | 0 | 46.824345 | 0.12738124E-02 | 16.300887 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.537_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.053 | 3.053 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.537_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.053 | 3.053 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.537_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.053 | 3.053 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.537_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.053 | 3.053 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.38652E-002 | 0.16139 | 0.60641 | 0.60641 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.79195E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.38652E-002 | 0.16139 | 0.60641 | 0.60641 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.79195E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.38652E-002 | 0.16139 | 0.60641 | 0.60641 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.79195E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.38652E-002 | 0.16139 | 0.60641 | 0.60641 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.79195E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1141E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1019E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0437E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.6552E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.5472E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.2275E-003 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 7.5380E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.9092E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.5988E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4868E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.7512E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.6205E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.8134E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.7552E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0806E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.0808E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.1744E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.0285E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.4449E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.8493E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.7941E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.4374E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.9092E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.5380E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 43572.70757 | 52287.24908 | 3.17340 | 3.80808 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 33.74200 | 1.65361E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 4295.60331 | 5154.72397 | 0.18427 | 1.33138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 4.60000 | 5.25715E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 21489.23582 | 25787.08299 | 1.32687 | 1.59224 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 33.18900 | 1.65350E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 4.60000 | 5.25715E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 67427.73 | 3.80841 | 3.80841 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 56981.68 | 1.33138 | 1.33138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 35967.76 | 1.59224 | 1.59224 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 52086.52 | 1.21700 | 1.21700 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.80808 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.59224 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.80808 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.80808 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.80808 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.80808 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.80841 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.80841 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99991 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.59224 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.59224 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.59224 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.59224 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.59224 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.59224 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.80841 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.59224 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.80841 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.80841 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6507.04373 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.80841 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.80841 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.80841 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.51355 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.80841 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.90421 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.53894 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 94571.90000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 47285.95000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 94571.90000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 113875.24530 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 113875.24530 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.59224 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.59224 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1703.77031 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.59224 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.59224 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.59224 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05088 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.59224 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.79612 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06149 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39539.07000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19769.53500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39539.07000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 70233.14375 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 70233.14375 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 91865.0 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 38407.4 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_EAST_0.25 | N/A | 3.053 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_SOUTH_0.25 | N/A | 3.053 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.537_SHGC_WEST_0.25 | N/A | 3.053 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 6.6433628970E-002 | 0.1797864350 | Pass | Pass | 6.3465481204E-002 | 0.2595646187 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1881493612 | 0.5482987932 | Pass | Pass | 0.1368882190 | 0.5663183192 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4532072646 | 0.4524163546 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1175.79 | 8.84 | -30.5 | 11.32 | 2042.74 | 3208.25 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.537_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.053 | 0.251 | 0.276 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.537_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 3.053 | 0.251 | 0.276 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.537_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.053 | 0.251 | 0.276 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 3.053 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 3.053 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.7280 | 371.75 | 2872.86 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 60.06 | 0.0000 | Y | 32.39 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.0598 | 139.41 | 1262.99 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 72.59 | 0.0000 | Y | 17.21 |
Interior Lighting Total | 8.0912 | 511.15 | 4135.85 | 49.60 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2872.86 | 718.22 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 211.28 | AstronomicalClock | - | 48.73 | 48.73 | 1.93 | |
EXTERIOR_LIGHTS_B | 2002.44 | AstronomicalClock | - | 83.73 | 62.73 | 23.58 | |
Exterior Lighting Total | 2213.72 | 25.51 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 94571.90 | 66302.47 | 28269.43 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39539.07 | 27720.05 | 11819.02 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 91865.0 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 38407.4 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 113875.25 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 70233.14 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.81 | 6507.04 | 1708.60 | 1.00 | 1.18 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.59 | 1703.77 | 1070.05 | 1.00 | 1.35 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 43572.71 | 52287.25 | 140.65 | 3.173 | 3.808 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 23.98 | 0.01113 | 33.74 | 0.01654 | 1.331 | 0.00 |
KITCHEN | 21489.24 | 25787.08 | 184.98 | 1.327 | 1.592 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.01034 | 33.19 | 0.01654 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 4295.60 | 5154.72 | 13.87 | 0.184 | 1.331 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 21.00 | 21.00 | 0.00781 | 4.60 | 0.00526 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 24.43 | 0.00436 | 4.60 | 0.00526 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.81 | 3.81 | 1.33 | 1.33 | 3.8084 | 3.8081 | 3.8084 | 0.9999 | 1.0000 |
PSZ-AC_2:2 | 1.59 | 1.59 | 1.22 | 1.22 | 1.5922 | 1.5922 | 1.5922 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 94571.900 | 66302.468 | 3.808410 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 47285.95 | 27610.10 | 2.538940 | 27.45 | 21.04 | 0.01302087 | 11.42 | 11.42 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 52.4383 | 23.98 | 0.01113057 | 59.6776 | 43554.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 113875.245 | 113875.245 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | 113875.25 | 113875.25 | 3.808411 | 15.27 | 11.52 | 0.00691815 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 34.9589 | 21.00 | 0.00781091 | 50.4689 | 4290.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 39539.070 | 27720.051 | 1.592240 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 19769.53 | 10811.40 | 1.061493 | 31.48 | 23.58 | 0.01507469 | 11.94 | 11.73 | 0.00850000 | 33.19 | 0.01653504 | 24.94 | 114.6500 | 25.99 | 0.01033833 | 49.2516 | 21489.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 70233.144 | 70233.144 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 70233.14 | 70233.14 | 1.592238 | 3.52 | 3.52 | 0.00504556 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 76.4334 | 24.43 | 0.00435930 | 22.9966 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 94571.900 | 66302.468 | 3.808410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.0451 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.808411 | 4.58215353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 47285.95 | 27610.10 | 1.0000 | 3.05476856 | 2.538940 | 27.45 | 21.04 | 0.01302087 | 60809.5 | 11.42 | 11.42 | 0.00850000 | 32913.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47285.95 | 33.90 | 0.01653638 | 25.13 | 1.33137743 | 52.4383 | 23.98 | 0.01113057 | 23.98 | 0.01113057 | 59.6776 | 43554.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 113875.245 | 113875.245 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.808411 | 4.58215353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | Sensible | 113875.25 | 113875.25 | 1.0000 | 4.58215353 | 3.808411 | 15.27 | 11.52 | 0.00691815 | 32838.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 113875.25 | 4.60 | 0.00525715 | 4.60 | 1.33137743 | 34.9589 | 21.00 | 0.00781091 | 21.00 | 0.00781091 | 50.4689 | 4290.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39539.070 | 27720.051 | 1.592240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1032.8631 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.592238 | 1.91572848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 19769.53 | 10811.40 | 1.0000 | 1.27715364 | 1.061493 | 31.48 | 23.58 | 0.01507469 | 70219.8 | 11.94 | 11.73 | 0.00850000 | 33443.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19769.53 | 33.19 | 0.01653504 | 24.94 | 1.21700195 | 114.6500 | 25.96 | 0.01033833 | 25.99 | 0.01033833 | 49.2516 | 21489.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 70233.144 | 70233.144 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.592238 | 1.91572848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 70233.14 | 70233.14 | 1.0000 | 1.91572848 | 1.592238 | 3.52 | 3.52 | 0.00504556 | 16184.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70233.14 | 4.60 | 0.00525715 | 4.60 | 1.21700195 | 76.4334 | 0.00 | 0.00435930 | 24.43 | 0.00435930 | 22.9966 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 1.33 | 3.81 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 1.22 | 1.59 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 5599.17 | 5285.83 | 4019.50 |
KITCHEN | 6537.17 | 6407.17 | 5874.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6561.17 | 7096.67 | 5899.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.17 | 34.17 | 0.00 | 0.00 |
KITCHEN | 0.00 | 1033.33 | 0.00 | 777.33 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 1064.67 | 0.00 | 777.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.530 | 0.897 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.871 | 0.025 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.085 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.689 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 37116114.26 | 0.00 | 37116114.26 | 7230137.17 | 44346251.42 | 41986318.57 | 1439.37 | 6100.17 | 1220.46 | 287.75 |
KITCHEN | 30984706.71 | 0.00 | 30984706.71 | 119514.91 | 31104221.63 | 38379373.44 | 5534.41 | 3174.72 | 50.87 | 903.68 |
Total Facility | 68100820.97 | 0.00 | 68100820.97 | 7349652.08 | 75450473.05 | 80365692.01 | 5569.49 | 6102.88 | 1265.99 | 951.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3970 | 0.0000 | 1.3970 | 0.2767 | 1.6737 | 1.3314 | 0.00 | 5982.21 | 1204.79 |
KITCHEN | 1.1332 | 0.0000 | 1.1332 | 0.0029 | 1.1360 | 1.2170 | 4021.13 | 3161.52 | 4.35 |
Total Facility | 2.5302 | 0.0000 | 2.5302 | 0.2795 | 2.8097 | 2.5484 | 4021.13 | 5982.41 | 1209.09 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 53728762.14 | 0.00 | 53728762.14 | 41986318.57 | 1409.95 | 3.93 | 7346.12 | 287.75 |
PSZ-AC_2:2 | 44853476.61 | 0.00 | 44853476.61 | 38379373.44 | 1319.81 | 3.62 | 7436.57 | 903.68 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 2.0223 | 0.0000 | 2.0223 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6404 | 0.0000 | 1.6404 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1153.95 | 227.16 | 6093.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 298.96 | 4275.13 | 3516.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.5477 | 2.2432 | 1.9276 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.5600 | 1.7326 | 1.5485 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 393 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
Electricity:Building | 505.97 | 2873.83 | 01-JAN-01:20 | 28998.37 | 19-DEC-11:10 |
Electricity:Zone:DINING | 157.50 | 560.03 | 01-JAN-01:20 | 8723.27 | 02-JAN-17:40 |
Electricity:SpaceType:GENERAL | 499.03 | 2737.55 | 01-JAN-01:20 | 26855.27 | 19-DEC-11:10 |
InteriorLights:Electricity | 49.60 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 32.39 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 49.60 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 49.60 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 32.39 | 80.03 | 01-JAN-01:20 | 2454.69 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 49.60 | 110.04 | 01-JAN-01:20 | 3339.74 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 348.47 | 2313.80 | 01-JAN-01:20 | 20370.03 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.21 | 30.01 | 01-JAN-01:20 | 885.05 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.33 | 2147.51 | 01-JAN-01:10 | 17341.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 54.56 | 852.62 | 04-FEB-23:30 | 3219.34 | 12-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 123.47 | 1033.88 | 05-FEB-01:10 | 6558.63 | 22-JUL-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 15.32 | 0.00 | 01-JAN-11:10 | 1509.90 | 31-OCT-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 32.30 | 766.36 | 09-MAR-06:00 | 1076.23 | 01-JAN-02:00 |
ElectricityPurchased:Facility | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
ElectricityPurchased:Plant | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
Cogeneration:ElectricityPurchased | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
General:Cogeneration:ElectricityPurchased | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
ElectricityNet:Plant | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
Cogeneration:ElectricityNet | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
General:Cogeneration:ElectricityNet | 1131.35 | 5064.77 | 05-FEB-01:30 | 78095.82 | 09-SEP-18:50 |
Electricity:HVAC | 476.40 | 0.00 | 01-JAN-01:10 | 47512.67 | 09-SEP-18:10 |
Fans:Electricity | 130.02 | 0.00 | 01-JAN-01:10 | 9034.94 | 09-SEP-18:10 |
General:Fans:Electricity | 130.02 | 0.00 | 01-JAN-01:10 | 9034.94 | 09-SEP-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 346.38 | 0.00 | 01-JAN-00:10 | 38477.73 | 09-SEP-18:10 |
General:Cooling:Electricity | 346.38 | 0.00 | 01-JAN-00:10 | 38477.73 | 09-SEP-18:10 |
ExteriorLights:Electricity | 25.51 | 0.00 | 01-JAN-07:30 | 2213.72 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 25.51 | 0.00 | 01-JAN-07:30 | 2213.72 | 01-JAN-06:10 |
WaterSystems:Electricity | 75.40 | 0.00 | 01-JAN-01:10 | 4741.56 | 04-JAN-19:30 |
Water Heater:WaterSystems:Electricity | 75.40 | 0.00 | 01-JAN-01:10 | 4741.56 | 04-JAN-19:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 01-FEB-12:40 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 01-FEB-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 783.60 | 2758.01 | 01-JAN-01:10 | 103709.45 | 05-FEB-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 29.93 | 0.00 | 01-JAN-00:10 | 75393.07 | 05-FEB-07:10 |
Heating:NaturalGas | 29.93 | 0.00 | 01-JAN-00:10 | 75393.07 | 05-FEB-07:10 |
General:Heating:NaturalGas | 29.93 | 0.00 | 01-JAN-00:10 | 75393.07 | 05-FEB-07:10 |
NaturalGas:Plant | 283.89 | 947.76 | 01-JAN-01:10 | 19517.81 | 26-JAN-08:00 |
WaterSystems:NaturalGas | 283.89 | 947.76 | 01-JAN-01:10 | 19517.81 | 26-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 283.89 | 947.76 | 01-JAN-01:10 | 19517.81 | 26-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 13-MAR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 13-MAR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 28-APR-18:30 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 28-APR-18:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2519.77 | 2933.30 | 05-FEB-01:10 | 205569.54 | 09-SEP-18:10 |
EnergyTransfer:Building | 831.63 | 1466.65 | 05-FEB-01:10 | 52978.14 | 30-AUG-17:20 |
EnergyTransfer:Zone:KITCHEN | 453.37 | 1466.65 | 05-FEB-01:10 | 23849.57 | 03-JAN-05:10 |
Refrigeration:EnergyTransfer | 156.26 | 2621.06 | 04-FEB-23:30 | 7834.84 | 12-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.13 | 1310.53 | 04-FEB-23:30 | 3917.42 | 12-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 78.13 | 1310.53 | 04-FEB-23:30 | 3917.42 | 12-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.13 | 1310.53 | 04-FEB-23:30 | 3917.42 | 12-JAN-11:40 |
EnergyTransfer:Plant | 272.48 | 1466.65 | 05-FEB-01:10 | 16193.36 | 19-JAN-19:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.44 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 65.69 | 1309.09 | 09-MAR-06:00 | 2238.70 | 01-JAN-02:00 |
EnergyTransfer:Zone:DINING | 378.26 | 0.00 | 01-JAN-01:10 | 32985.43 | 09-SEP-18:10 |
Heating:EnergyTransfer | 0.66 | 0.00 | 01-JAN-00:10 | 12612.86 | 09-SEP-23:10 |
Heating:EnergyTransfer:Zone:DINING | 0.66 | 0.00 | 01-JAN-00:10 | 12612.86 | 09-SEP-23:10 |
General:Heating:EnergyTransfer | 0.66 | 0.00 | 01-JAN-00:10 | 12612.86 | 09-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 0.66 | 0.00 | 01-JAN-00:10 | 12612.86 | 09-SEP-23:10 |
Cooling:EnergyTransfer | 752.84 | 0.00 | 01-JAN-01:10 | 50623.21 | 30-AUG-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 377.60 | 0.00 | 01-JAN-01:10 | 32985.43 | 09-SEP-18:10 |
General:Cooling:EnergyTransfer | 752.84 | 0.00 | 01-JAN-01:10 | 50623.21 | 30-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 377.60 | 0.00 | 01-JAN-01:10 | 32985.43 | 09-SEP-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 60.42 | 05-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 60.42 | 05-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 375.24 | 0.00 | 01-JAN-01:10 | 20334.61 | 03-JAN-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 375.24 | 0.00 | 01-JAN-01:10 | 20334.61 | 03-JAN-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 194.36 | 0.00 | 01-JAN-01:10 | 13561.92 | 23-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 194.36 | 0.00 | 01-JAN-01:10 | 13561.92 | 23-JAN-08:00 |
WaterSystems:PlantLoopHeatingDemand | 194.36 | 0.00 | 01-JAN-01:10 | 13561.92 | 23-JAN-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 194.36 | 0.00 | 01-JAN-01:10 | 13561.92 | 23-JAN-08:00 |
EnergyTransfer:HVAC | 1415.66 | 0.00 | 01-JAN-00:10 | 144505.01 | 06-OCT-11:10 |
HeatingCoils:EnergyTransfer | 23.94 | 0.00 | 01-JAN-00:10 | 60314.46 | 05-FEB-07:10 |
CoolingCoils:EnergyTransfer | 1391.71 | 0.00 | 01-JAN-00:10 | 144505.01 | 06-OCT-11:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 194.36 | 0.00 | 01-JAN-01:10 | 13561.92 | 23-JAN-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 194.36 | 0.00 | 01-JAN-01:10 | 13561.92 | 23-JAN-08:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.657 | -377.598 | 0.000 | 0.000 | 211.332 | 32.389 | 93.832 | 40.186 | 0.000 | 18.804 | 19.765 | 0.000 | -12.495 | 0.000 | -26.872 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -375.235 | 0.000 | 0.000 | 4.883 | 17.209 | 286.918 | 0.000 | 0.000 | 0.076 | 67.074 | 0.000 | 0.000 | 0.000 | -0.925 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.359 | 40.446 | 0.000 | 0.000 | 0.000 | -49.805 | -0.000 |
Total Facility | 0.000 | 0.000 | 0.657 | -752.833 | 0.000 | 0.000 | 216.215 | 49.598 | 380.750 | 40.186 | 0.000 | 28.239 | 127.285 | 0.000 | -12.495 | 0.000 | -77.602 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 27-OCT-03:01 | 0.00 | 0.00 | 0.00 | -71826.80 | 0.00 | 0.00 | 0.00 | 80.03 | 900.01 | 0.00 | 0.00 | 0.00 | 72594.10 | 0.00 | -1493.73 | 0.00 | -253.61 | 0.00 |
KITCHEN | 03-JAN-04:01 | 0.00 | 0.00 | 0.00 | -63112.43 | 0.00 | 0.00 | 0.00 | 30.01 | 3472.64 | 0.00 | 0.00 | 0.00 | 59733.50 | 0.00 | -0.00 | 0.00 | -123.72 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-OCT-03:01 | 0.00 | 0.00 | 0.00 | -128495.75 | 0.00 | 0.00 | 0.00 | 110.04 | 4372.65 | 0.00 | 0.00 | 563.60 | 125408.24 | 0.00 | -1493.73 | 0.00 | -465.05 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-FEB-06:22 | 0.00 | 0.00 | 36532.71 | 0.00 | 0.00 | 0.00 | 2315.59 | 1090.97 | 2350.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2060.78 | 0.00 | -2094.69 | -38134.51 |
KITCHEN | 05-FEB-05:04 | 0.00 | 0.00 | 603.56 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 | 6895.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -87.79 | -7441.61 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-06:22 | -10445.86 | 10445.86 | 36532.71 | -10445.86 | 0.00 | 0.00 | 2383.60 | 1484.33 | 9753.88 | 0.00 | 0.00 | 827.09 | 0.00 | 0.00 | -2060.78 | 0.00 | -2120.01 | -36354.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.8081 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.8084 | 0.3496 | 1.0000 | Not calculated | 1.3314 | 0.3496 | ||
PSZ-AC_2:2 | 1.5922 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5922 | 0.1147 | 1.0000 | Not calculated | 0.1826 | 0.1147 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.8081 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.8081 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3496 | ||
PSZ-AC_2:2 | 1.5922 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5922 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1147 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8081 | 3.8081 | 3.8081 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5922 | 1.5922 | 1.5922 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.8081 | 3.8084 | 3.8081 | 3.8081 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5922 | 1.5922 | 1.5922 | 1.5922 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8081 | 3.8081 | 3.8081 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5922 | 1.5922 | 1.5922 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.8081 | 3.8081 | 3.8081 | 3.8081 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5922 | 1.5922 | 1.5922 | 1.5922 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 777.33 |
Number of hours not met | 777.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 29.93 | 75393.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 346.38 | 38477.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 49.60 | 3339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 25.51 | 2213.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 130.02 | 9034.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.40 | 4741.56 | 283.89 | 19517.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.32 | 1509.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.30 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 503.99 | 1131.35 |
Natural Gas | 469.79 | 783.60 |
Additional | 0.00 | 0.00 |
Total | 973.78 | 1914.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 97.03 |
Space Heating | 0.00 |
Space Cooling | 677.64 |
Fans (All) | 254.36 |
Service Water Heating | 147.51 |
Receptacle Equipment | 879.26 |
Miscellaneous (All) | 2213.32 |
Subtotal | 2213.32 |
Natural Gas [MJ/m2] | |
Space Heating | 58.55 |
Service Water Heating | 555.38 |
Miscellaneous (All) | 1533.01 |
Subtotal | 1533.01 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.59 |
Space Heating | 1.56 |
Space Cooling | 18.09 |
Fans (All) | 6.79 |
Service Water Heating | 18.76 |
Receptacle Equipment | 48.00 |
Miscellaneous | 4.20 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8147.17 | 611.00 | 1.83 | 0.00 | 0.00 |
KITCHEN | 6692.83 | 1846.67 | 220.50 | 0.00 | 0.00 |
ATTIC | 5248.67 | 751.00 | 800.83 | 1000.83 | 958.67 |
Min | 5248.67 | 611.00 | 1.83 | 0.00 | 0.00 |
Max | 8147.17 | 1846.67 | 800.83 | 1000.83 | 958.67 |
Average | 6696.22 | 1069.56 | 341.06 | 333.61 | 319.56 |
Sum | 20088.67 | 3208.67 | 1023.17 | 1000.83 | 958.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822698.33 | 1509.67 | 14.00 | 0.00 | 0.00 |
KITCHEN | 16029.33 | 3180.67 | 23.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822698.33 | 3180.67 | 23.00 | 0.00 | 0.00 |
Average | 279575.89 | 1563.44 | 12.33 | 0.00 | 0.00 |
Sum | 838727.67 | 4690.33 | 37.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 3606.17 | 5152.50 | 1.33 | 0.00 | 0.00 |
KITCHEN | 1904.00 | 6840.67 | 15.33 | 0.00 | 0.00 |
ATTIC | 3484.83 | 2842.17 | 621.67 | 498.17 | 1313.17 |
Min | 1904.00 | 2842.17 | 1.33 | 0.00 | 0.00 |
Max | 3606.17 | 6840.67 | 621.67 | 498.17 | 1313.17 |
Average | 2998.33 | 4945.11 | 212.78 | 166.06 | 437.72 |
Sum | 8995.00 | 14835.33 | 638.33 | 498.17 | 1313.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 346614.33 | 477596.00 | 11.67 | 0.00 | 0.00 |
KITCHEN | 4118.17 | 15109.33 | 5.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 346614.33 | 477596.00 | 11.67 | 0.00 | 0.00 |
Average | 116910.83 | 164235.11 | 5.72 | 0.00 | 0.00 |
Sum | 350732.50 | 492705.33 | 17.17 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238405E+11 | 56002.76 | 20-JAN-04:01 | 17.00 | 17.00 | 0.137581E+11 | 14048.86 | 28-JAN-19:10 | 15.83 | 13.00 |
February | 0.221503E+11 | 47652.25 | 26-FEB-04:01 | 14.32 | 14.24 | 0.129633E+11 | 14049.92 | 11-FEB-19:00 | 14.32 | 14.24 |
March | 0.253838E+11 | 50290.04 | 05-MAR-04:01 | 16.35 | 13.97 | 0.146594E+11 | 14051.54 | 18-MAR-18:49 | 21.88 | 20.63 |
April | 0.283319E+11 | 57227.08 | 21-APR-03:01 | 19.03 | 17.61 | 0.147642E+11 | 14050.13 | 22-APR-18:00 | 25.50 | 20.83 |
May | 0.362091E+11 | 50286.05 | 17-MAY-03:01 | 22.20 | 19.73 | 0.154232E+11 | 14050.15 | 06-MAY-18:00 | 22.20 | 19.73 |
June | 0.368785E+11 | 55756.57 | 07-JUN-03:01 | 21.10 | 18.25 | 0.150053E+11 | 14050.26 | 03-JUN-18:19 | 21.10 | 18.25 |
July | 0.387887E+11 | 37792.31 | 18-JUL-03:01 | 24.40 | 22.88 | 0.153259E+11 | 14050.29 | 29-JUL-18:30 | 28.60 | 25.47 |
August | 0.395321E+11 | 59118.12 | 20-AUG-03:01 | 23.53 | 17.99 | 0.155203E+11 | 14050.26 | 05-AUG-18:19 | 23.53 | 17.99 |
September | 0.361876E+11 | 49968.70 | 22-SEP-03:01 | 21.62 | 20.07 | 0.149025E+11 | 14318.09 | 09-SEP-18:49 | 21.62 | 20.07 |
October | 0.359074E+11 | 71842.96 | 27-OCT-03:01 | 14.17 | 7.88 | 0.152586E+11 | 14051.41 | 21-OCT-18:10 | 14.17 | 7.88 |
November | 0.283278E+11 | 66059.44 | 12-NOV-04:01 | 11.40 | 8.31 | 0.144390E+11 | 14051.15 | 25-NOV-19:19 | 17.17 | 13.54 |
December | 0.260621E+11 | 47490.96 | 16-DEC-04:01 | 20.17 | 20.17 | 0.141694E+11 | 14052.27 | 09-DEC-19:19 | 20.17 | 20.17 |
Annual Sum or Average | 0.377600E+12 | 0.176189E+12 | ||||||||
Minimum of Months | 0.221503E+11 | 37792.31 | 11.40 | 7.88 | 0.129633E+11 | 14048.86 | 14.17 | 7.88 | ||
Maximum of Months | 0.395321E+11 | 71842.96 | 24.40 | 22.88 | 0.155203E+11 | 14318.09 | 28.60 | 25.47 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303300E+11 | 63196.59 | 03-JAN-04:01 | 5.67 | 3.05 | 0.105290E+11 | 6930.41 | 11-JAN-11:00 | 19.00 | 13.78 |
February | 0.270631E+11 | 55770.51 | 12-FEB-04:01 | 14.80 | 8.64 | 0.953209E+10 | 6930.44 | 01-FEB-11:09 | 14.80 | 8.64 |
March | 0.299727E+11 | 56183.60 | 20-MAR-03:01 | 12.55 | 8.37 | 0.105691E+11 | 6930.42 | 23-MAR-10:00 | 19.40 | 14.77 |
April | 0.297296E+11 | 55716.14 | 11-APR-03:01 | 11.55 | 8.65 | 0.102514E+11 | 6933.99 | 28-APR-10:00 | 30.00 | 23.29 |
May | 0.327029E+11 | 30258.43 | 17-MAY-03:01 | 22.20 | 19.73 | 0.106002E+11 | 6972.20 | 26-MAY-10:00 | 31.10 | 25.83 |
June | 0.321379E+11 | 33050.22 | 07-JUN-03:01 | 21.10 | 18.25 | 0.102699E+11 | 6980.17 | 19-JUN-10:00 | 31.70 | 26.19 |
July | 0.332299E+11 | 23680.91 | 23-JUL-03:21 | 25.30 | 23.82 | 0.106216E+11 | 6990.20 | 03-JUL-10:00 | 25.30 | 23.82 |
August | 0.338567E+11 | 33468.01 | 20-AUG-03:01 | 23.53 | 17.99 | 0.106208E+11 | 6990.27 | 14-AUG-10:00 | 23.53 | 17.99 |
September | 0.323854E+11 | 29753.31 | 22-SEP-03:01 | 21.62 | 20.07 | 0.102662E+11 | 6973.28 | 18-SEP-10:50 | 21.62 | 20.07 |
October | 0.328494E+11 | 60653.03 | 28-OCT-03:01 | 11.83 | 6.09 | 0.106014E+11 | 7003.86 | 06-OCT-10:00 | 11.83 | 6.09 |
November | 0.301929E+11 | 61089.11 | 23-NOV-04:01 | 10.47 | 4.19 | 0.102396E+11 | 6946.11 | 02-NOV-10:50 | 10.47 | 4.19 |
December | 0.307908E+11 | 54954.10 | 01-DEC-04:11 | 12.00 | 9.99 | 0.105483E+11 | 6930.42 | 28-DEC-11:39 | 19.33 | 19.33 |
Annual Sum or Average | 0.375241E+12 | 0.124650E+12 | ||||||||
Minimum of Months | 0.270631E+11 | 23680.91 | 5.67 | 3.05 | 0.953209E+10 | 6930.41 | 10.47 | 4.19 | ||
Maximum of Months | 0.338567E+11 | 63196.59 | 25.30 | 23.82 | 0.106216E+11 | 7003.86 | 31.70 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 | 19.11 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 | 23.55 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.55 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4369002.06 | 9521.97 | 14-JAN-05:03 | 6.73 |
February | 36987816.99 | 36533.29 | 06-FEB-06:22 | 3.25 |
March | 1560812.57 | 6223.00 | 11-MAR-05:02 | 7.27 |
April | 3554816.79 | 3469.35 | 29-APR-23:03 | 25.50 |
May | 77407927.27 | 5818.49 | 02-MAY-23:02 | 26.93 |
June | 0.106534E+09 | 7870.32 | 28-JUN-23:02 | 28.22 |
July | 0.182435E+09 | 8036.88 | 04-JUL-23:02 | 28.30 |
August | 0.137800E+09 | 8223.23 | 24-AUG-23:02 | 28.52 |
September | 72423364.59 | 17131.97 | 09-SEP-23:01 | 33.88 |
October | 28555389.31 | 5528.40 | 13-OCT-23:02 | 26.83 |
November | 1203361.14 | 2430.14 | 01-NOV-23:03 | 24.75 |
December | 3443825.51 | 8261.93 | 20-DEC-05:02 | 4.67 |
Annual Sum or Average | 0.656275E+09 | |||
Minimum of Months | 1203361.14 | 2430.14 | 3.25 | |
Maximum of Months | 0.182435E+09 | 36533.29 | 33.88 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 36249.27 | 604.15 | 05-FEB-05:04 | -2.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 14.12 |
Annual Sum or Average | 36249.27 | |||
Minimum of Months | 0.00 | 0.00 | -2.2 | |
Maximum of Months | 36249.27 | 604.15 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.287383E+10 | 2454.69 | 02-JAN-17:40 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.255573E+10 | 2454.69 | 01-FEB-18:10 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.279429E+10 | 2454.69 | 01-MAR-17:00 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.259108E+10 | 2454.69 | 01-APR-18:19 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.263760E+10 | 2454.69 | 01-MAY-18:49 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.253161E+10 | 2454.69 | 01-JUN-19:10 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.258223E+10 | 2454.69 | 01-JUL-19:10 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.268169E+10 | 2454.69 | 01-AUG-19:19 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.263858E+10 | 2454.69 | 01-SEP-18:30 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.278137E+10 | 2454.69 | 02-OCT-18:19 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.279642E+10 | 2454.69 | 01-NOV-17:19 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.292436E+10 | 2454.69 | 01-DEC-17:30 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.323888E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.253161E+10 | 2454.69 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.292436E+10 | 2454.69 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.145365E+10 | 885.05 | 02-JAN-10:09 | 0.275454E+11 | 17341.88 | 01-JAN-11:09 |
February | 0.131681E+10 | 885.05 | 01-FEB-10:09 | 0.248798E+11 | 17341.88 | 01-FEB-11:09 |
March | 0.147869E+10 | 885.05 | 01-MAR-10:09 | 0.275456E+11 | 17341.88 | 01-MAR-11:09 |
April | 0.141254E+10 | 885.05 | 01-APR-16:10 | 0.266569E+11 | 17341.88 | 01-APR-10:09 |
May | 0.146617E+10 | 885.05 | 01-MAY-09:09 | 0.275455E+11 | 17341.88 | 01-MAY-10:09 |
June | 0.142908E+10 | 885.05 | 01-JUN-09:09 | 0.266570E+11 | 17341.88 | 01-JUN-10:09 |
July | 0.144981E+10 | 885.05 | 01-JUL-16:10 | 0.275454E+11 | 17341.88 | 01-JUL-10:09 |
August | 0.147869E+10 | 885.05 | 01-AUG-09:09 | 0.275456E+11 | 17341.88 | 01-AUG-10:09 |
September | 0.141289E+10 | 885.05 | 01-SEP-09:09 | 0.266569E+11 | 17341.88 | 01-SEP-10:09 |
October | 0.145348E+10 | 885.05 | 02-OCT-09:09 | 0.275454E+11 | 17341.88 | 01-OCT-10:09 |
November | 0.140753E+10 | 885.05 | 01-NOV-09:09 | 0.266568E+11 | 17341.88 | 01-NOV-10:09 |
December | 0.144998E+10 | 885.05 | 01-DEC-10:09 | 0.275454E+11 | 17341.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.172093E+11 | 0.324326E+12 | ||||
Minimum of Months | 0.131681E+10 | 885.05 | 0.248798E+11 | 17341.88 | ||
Maximum of Months | 0.147869E+10 | 885.05 | 0.275456E+11 | 17341.88 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.287383E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52536435.86 | 0.640070E+10 |
February | 0.272721E+11 | 0.255573E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96849998.58 | 0.476137E+10 |
March | 0.305458E+11 | 0.279429E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224742E+09 | 0.427607E+10 |
April | 0.292871E+11 | 0.259108E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728520E+09 | 0.187399E+10 |
May | 0.303219E+11 | 0.263760E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288397E+10 | 35187954.33 |
June | 0.295292E+11 | 0.253161E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341033E+10 | 29842937.43 |
July | 0.300798E+11 | 0.258223E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352768E+10 | 18628976.68 |
August | 0.305458E+11 | 0.268169E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330929E+10 | 72914234.97 |
September | 0.292871E+11 | 0.263858E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215397E+10 | 0.150991E+09 |
October | 0.300980E+11 | 0.278137E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183136E+10 | 0.930597E+09 |
November | 0.290996E+11 | 0.279642E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379746E+09 | 0.311853E+10 |
December | 0.300798E+11 | 0.292436E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204624E+09 | 0.520362E+10 |
Annual Sum or Average | 0.356244E+12 | 0.323888E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188036E+11 | 0.268724E+11 |
Minimum of Months | 0.272721E+11 | 0.253161E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52536435.86 | 18628976.68 |
Maximum of Months | 0.305458E+11 | 0.292436E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352768E+10 | 0.640070E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.145365E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12666.06 | 0.163232E+09 |
February | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 150815.48 | 0.117952E+09 |
March | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 554668.25 | 0.142228E+09 |
April | 0.786997E+09 | 0.141254E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2695375.25 | 63832600.26 |
May | 0.814802E+09 | 0.146617E+10 | 0.225868E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12317132.27 | 24712238.36 |
June | 0.793501E+09 | 0.142908E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 12664440.17 | 18535784.87 |
July | 0.808298E+09 | 0.144981E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12830597.57 | 15857541.36 |
August | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 14422854.34 | 27060622.51 |
September | 0.786997E+09 | 0.141289E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 10336788.94 | 33429249.43 |
October | 0.808786E+09 | 0.145348E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 9062690.23 | 73699478.27 |
November | 0.781956E+09 | 0.140753E+10 | 0.218581E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 883451.30 | 94827323.31 |
December | 0.808298E+09 | 0.144998E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 516552.30 | 0.149357E+09 |
Annual Sum or Average | 0.957291E+10 | 0.172093E+11 | 0.265941E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 76448032.16 | 0.924723E+09 |
Minimum of Months | 0.732850E+09 | 0.131681E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 12666.06 | 15857541.36 |
Maximum of Months | 0.820818E+09 | 0.147869E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 14422854.34 | 0.163232E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842804E+09 | 0.320387E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973093E+09 | 0.348005E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800206E+09 | 0.391002E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885143E+09 | 0.511014E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674425E+09 | 0.489722E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727682E+09 | 0.554404E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708581E+09 | 0.512385E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652662E+09 | 0.482139E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664013E+09 | 0.395368E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556863E+09 | 0.366202E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103322E+10 | 0.315376E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840554E+09 | 0.294514E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935925E+10 | 0.498052E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556863E+09 | 0.294514E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103322E+10 | 0.554404E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2454.69 | 02-JAN-17:40 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.71 | 02-JAN-13:00 | 11947.25 | 04-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2454.69 | 01-FEB-18:10 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.03 | 02-FEB-13:00 | 12814.43 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 2454.69 | 01-MAR-17:00 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.86 | 30-MAR-13:00 | 8741.58 | 09-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2454.69 | 01-APR-18:19 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4410.89 | 28-APR-13:00 | 6488.05 | 10-APR-19:53 |
May | 30255.31 | 06-MAY-18:10 | 2454.69 | 01-MAY-18:49 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5151.33 | 25-MAY-17:10 | 745.62 | 19-MAY-18:53 |
June | 30255.31 | 03-JUN-18:10 | 2454.69 | 01-JUN-19:10 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5379.95 | 13-JUN-17:03 | 913.22 | 07-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 2454.69 | 01-JUL-19:10 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5927.31 | 20-JUL-12:00 | 1117.46 | 11-JUL-19:55 |
August | 30255.31 | 05-AUG-18:10 | 2454.69 | 01-AUG-19:19 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6336.03 | 02-AUG-17:10 | 1995.30 | 16-AUG-19:00 |
September | 30255.31 | 02-SEP-18:10 | 2454.69 | 01-SEP-18:30 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7252.79 | 09-SEP-18:03 | 3007.07 | 07-SEP-17:53 |
October | 30255.31 | 07-OCT-18:10 | 2454.69 | 02-OCT-18:19 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5274.81 | 05-OCT-17:03 | 6532.69 | 27-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2454.69 | 01-NOV-17:19 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3272.83 | 02-NOV-11:55 | 7914.32 | 15-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 2454.69 | 01-DEC-17:30 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2732.78 | 13-DEC-14:00 | 11995.89 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.71 | 745.62 | |||||
Maximum of Months | 30255.31 | 2454.69 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7252.79 | 12814.43 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 885.05 | 02-JAN-10:09 | 14079.00 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 2.53 | 16-JAN-15:00 | 541.60 | 09-JAN-03:00 |
February | 813.01 | 04-FEB-19:10 | 885.05 | 01-FEB-10:09 | 14079.00 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 14.67 | 02-FEB-12:55 | 575.97 | 04-FEB-04:40 |
March | 813.01 | 04-MAR-19:10 | 885.05 | 01-MAR-10:09 | 14079.00 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 13.61 | 27-MAR-15:00 | 578.96 | 21-MAR-03:40 |
April | 813.01 | 01-APR-18:10 | 885.05 | 01-APR-16:10 | 14079.00 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 29.66 | 29-APR-15:53 | 401.16 | 02-APR-03:00 |
May | 813.01 | 06-MAY-18:10 | 885.05 | 01-MAY-09:09 | 14079.00 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 39.81 | 25-MAY-13:55 | 178.39 | 09-MAY-02:10 |
June | 813.01 | 03-JUN-18:10 | 885.05 | 01-JUN-09:09 | 14079.00 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 42.73 | 08-JUN-15:00 | 210.98 | 08-JUN-02:10 |
July | 813.01 | 01-JUL-18:10 | 885.05 | 01-JUL-16:10 | 14079.00 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 66.60 | 19-JUL-12:53 | 175.44 | 31-JUL-02:10 |
August | 813.01 | 05-AUG-18:10 | 885.05 | 01-AUG-09:09 | 14079.00 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 42.20 | 20-AUG-14:00 | 288.61 | 16-AUG-02:50 |
September | 813.01 | 02-SEP-18:10 | 885.05 | 01-SEP-09:09 | 14079.00 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 143.53 | 09-SEP-23:10 | 281.16 | 13-SEP-02:50 |
October | 813.01 | 07-OCT-18:10 | 885.05 | 02-OCT-09:09 | 14079.00 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 54.58 | 09-OCT-14:00 | 357.91 | 29-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 885.05 | 01-NOV-09:09 | 14079.00 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 11.84 | 02-NOV-15:00 | 386.57 | 09-NOV-04:00 |
December | 813.01 | 02-DEC-19:10 | 885.05 | 01-DEC-10:09 | 14079.00 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 12.24 | 13-DEC-14:30 | 600.14 | 20-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 2.53 | 175.44 | ||||||
Maximum of Months | 813.01 | 885.05 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 143.53 | 600.14 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1704.45 | 05-JAN-01:00 | 6898.98 | 21-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2185.47 | 10-FEB-07:53 | 7267.69 | 13-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2027.72 | 14-MAR-07:33 | 8085.38 | 13-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1901.99 | 11-APR-06:53 | 8660.78 | 21-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.25 | 02-MAY-23:00 | 8499.25 | 10-MAY-14:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1531.60 | 28-JUN-02:00 | 8494.04 | 28-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.55 | 15-JUL-05:00 | 8456.08 | 20-JUL-14:02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.60 | 31-AUG-06:20 | 8212.11 | 10-AUG-14:13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1519.36 | 01-SEP-06:45 | 7947.23 | 02-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.26 | 23-OCT-23:55 | 6927.94 | 02-OCT-13:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.03 | 23-NOV-07:25 | 6553.29 | 06-NOV-13:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2673.90 | 19-DEC-07:42 | 6428.78 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.26 | 6428.78 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2673.90 | 8660.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56002.76 | 20-JAN-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.56 |
February | 47652.25 | 26-FEB-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 |
March | 50290.04 | 05-MAR-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.37 |
April | 57227.08 | 21-APR-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.74 |
May | 50286.05 | 17-MAY-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.74 |
June | 55756.57 | 07-JUN-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.78 |
July | 37792.31 | 18-JUL-03:01 | 0.00 | 720.26 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
August | 59118.12 | 20-AUG-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 |
September | 49968.70 | 22-SEP-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 |
October | 71842.96 | 27-OCT-03:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.61 |
November | 66059.44 | 12-NOV-04:01 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.91 |
December | 47490.96 | 16-DEC-04:01 | 0.00 | 720.26 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 37792.31 | 0.00 | 720.26 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | |
Maximum of Months | 71842.96 | 0.00 | 800.29 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 63196.59 | 03-JAN-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 123.72 |
February | 55770.51 | 12-FEB-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 256.27 |
March | 56183.60 | 20-MAR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 266.09 |
April | 55716.14 | 11-APR-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 29.95 |
May | 30258.43 | 17-MAY-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 26.71 |
June | 33050.22 | 07-JUN-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 115.85 |
July | 23680.91 | 23-JUL-03:21 | 0.00 | 210.08 | 22872.64 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 |
August | 33468.01 | 20-AUG-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
September | 29753.31 | 22-SEP-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 |
October | 60653.03 | 28-OCT-03:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 211.79 |
November | 61089.11 | 23-NOV-04:01 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 |
December | 54954.10 | 01-DEC-04:11 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 176.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23680.91 | 0.00 | 210.08 | 22872.64 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | |
Maximum of Months | 63196.59 | 0.00 | 300.11 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 266.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.13 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.20 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.88 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.06 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.32 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.66 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.32 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1252.14 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.38 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.96 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1252.14 | 78.65 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.712431E+11 | 58110.02 | 19-JAN-11:00 | 0.772991E+11 | 84097.34 | 05-JAN-07:00 |
February | 0.667254E+11 | 56327.61 | 24-FEB-12:00 | 0.675395E+11 | 103709.45 | 05-FEB-07:10 |
March | 0.764471E+11 | 59249.17 | 07-MAR-11:39 | 0.705355E+11 | 77277.10 | 09-MAR-07:10 |
April | 0.831631E+11 | 65081.83 | 28-APR-16:10 | 0.624627E+11 | 43032.66 | 01-APR-10:39 |
May | 0.110737E+12 | 69602.90 | 24-MAY-11:09 | 0.629621E+11 | 42766.73 | 06-MAY-10:00 |
June | 0.111776E+12 | 72016.98 | 29-JUN-11:00 | 0.598483E+11 | 42578.02 | 04-JUN-10:30 |
July | 0.121933E+12 | 75044.24 | 18-JUL-11:09 | 0.610234E+11 | 42445.36 | 02-JUL-10:50 |
August | 0.119259E+12 | 72844.82 | 14-AUG-11:09 | 0.614496E+11 | 42492.92 | 27-AUG-10:50 |
September | 0.110738E+12 | 78095.82 | 09-SEP-18:49 | 0.602257E+11 | 42675.03 | 30-SEP-10:20 |
October | 0.103796E+12 | 75912.62 | 06-OCT-11:09 | 0.636106E+11 | 42908.35 | 29-OCT-10:39 |
November | 0.796269E+11 | 66513.49 | 07-NOV-12:00 | 0.638905E+11 | 43115.36 | 26-NOV-11:39 |
December | 0.759010E+11 | 63022.86 | 14-DEC-12:00 | 0.727546E+11 | 86282.07 | 21-DEC-07:10 |
Annual Sum or Average | 0.113135E+13 | 0.783602E+12 | ||||
Minimum of Months | 0.667254E+11 | 56327.61 | 0.598483E+11 | 42445.36 | ||
Maximum of Months | 0.121933E+12 | 78095.82 | 0.772991E+11 | 103709.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.432748E+10 | 0.255352E+10 | 0.381711E+11 | 0.00 | 0.963116E+10 | 37879553.69 | 0.00 | 0.573078E+10 | 0.00 | 0.00 | 0.00 | 0.638626E+10 | 0.00 |
February | 0.387254E+10 | 0.217423E+10 | 0.344772E+11 | 0.00 | 0.869704E+10 | 34213790.43 | 0.00 | 0.763630E+10 | 0.00 | 0.00 | 0.00 | 0.577788E+10 | 0.00 |
March | 0.427298E+10 | 0.220818E+10 | 0.381714E+11 | 0.00 | 0.964392E+10 | 37879553.69 | 0.00 | 0.111328E+11 | 0.00 | 0.00 | 0.00 | 0.645181E+10 | 0.00 |
April | 0.400362E+10 | 0.194406E+10 | 0.369399E+11 | 0.00 | 0.955542E+10 | 36657632.61 | 0.00 | 0.199864E+11 | 0.00 | 0.00 | 0.00 | 0.619347E+10 | 0.00 |
May | 0.410378E+10 | 0.183495E+10 | 0.381712E+11 | 0.00 | 0.116053E+11 | 37879553.69 | 0.00 | 0.438490E+11 | 0.00 | 0.00 | 0.00 | 0.641452E+10 | 0.00 |
June | 0.396069E+10 | 0.168107E+10 | 0.369400E+11 | 0.00 | 0.119874E+11 | 36657632.61 | 0.00 | 0.463444E+11 | 0.00 | 0.00 | 0.00 | 0.623541E+10 | 0.00 |
July | 0.403204E+10 | 0.178713E+10 | 0.381711E+11 | 0.00 | 0.134065E+11 | 37879553.69 | 0.00 | 0.533560E+11 | 0.00 | 0.00 | 0.00 | 0.636991E+10 | 0.00 |
August | 0.416038E+10 | 0.192792E+10 | 0.381714E+11 | 0.00 | 0.129547E+11 | 37879553.69 | 0.00 | 0.507949E+11 | 0.00 | 0.00 | 0.00 | 0.644854E+10 | 0.00 |
September | 0.405147E+10 | 0.205563E+10 | 0.369399E+11 | 0.00 | 0.118289E+11 | 36657632.61 | 0.00 | 0.450389E+11 | 0.00 | 0.00 | 0.00 | 0.619361E+10 | 0.00 |
October | 0.423485E+10 | 0.232639E+10 | 0.381711E+11 | 0.00 | 0.114324E+11 | 37879553.69 | 0.00 | 0.365148E+11 | 0.00 | 0.00 | 0.00 | 0.637787E+10 | 0.00 |
November | 0.420395E+10 | 0.241956E+10 | 0.369398E+11 | 0.00 | 0.956294E+10 | 36657632.61 | 0.00 | 0.158436E+11 | 0.00 | 0.00 | 0.00 | 0.617581E+10 | 0.00 |
December | 0.437434E+10 | 0.259735E+10 | 0.381711E+11 | 0.00 | 0.971347E+10 | 37879553.69 | 0.00 | 0.101509E+11 | 0.00 | 0.00 | 0.00 | 0.637631E+10 | 0.00 |
Annual Sum or Average | 0.495981E+11 | 0.255100E+11 | 0.449435E+12 | 0.00 | 0.130019E+12 | 0.446001E+09 | 0.00 | 0.346379E+12 | 0.00 | 0.00 | 0.00 | 0.754014E+11 | 0.00 |
Minimum of Months | 0.387254E+10 | 0.168107E+10 | 0.344772E+11 | 0.00 | 0.869704E+10 | 34213790.43 | 0.00 | 0.573078E+10 | 0.00 | 0.00 | 0.00 | 0.577788E+10 | 0.00 |
Maximum of Months | 0.437434E+10 | 0.259735E+10 | 0.381714E+11 | 0.00 | 0.134065E+11 | 37879553.69 | 0.00 | 0.533560E+11 | 0.00 | 0.00 | 0.00 | 0.645181E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.104440E+11 | 0.00 | 0.269553E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.730356E+10 | 0.00 | 0.241975E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.453569E+10 | 0.00 | 0.261001E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.125366E+09 | 0.00 | 0.237247E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.230624E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 57191.02 | 0.00 | 0.212356E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.211236E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.215499E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.216131E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 65929794.49 | 0.00 | 0.236450E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.936495E+09 | 0.00 | 0.243414E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.651822E+10 | 0.00 | 0.263367E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.299293E+11 | 0.00 | 0.283885E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.211236E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.104440E+11 | 0.00 | 0.269553E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3339.74 | 02-JAN-17:40 | 2213.72 | 01-JAN-06:10 | 24333.76 | 01-JAN-11:09 | 0.00 | 5359.67 | 05-JAN-06:10 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3339.74 | 01-FEB-18:10 | 2213.72 | 01-FEB-06:10 | 24333.76 | 01-FEB-11:09 | 0.00 | 5747.39 | 05-FEB-07:10 | 17.86 | 01-FEB-12:39 | 0.00 | 01-FEB-00:10 |
March | 3339.74 | 01-MAR-17:00 | 2213.72 | 01-MAR-06:10 | 24333.76 | 01-MAR-11:09 | 0.00 | 5681.06 | 30-MAR-11:00 | 17.86 | 15-MAR-09:20 | 0.00 | 01-MAR-00:10 |
April | 3339.74 | 01-APR-18:19 | 2213.72 | 01-APR-05:10 | 24333.76 | 01-APR-10:09 | 0.00 | 7030.76 | 28-APR-17:10 | 17.86 | 14-APR-10:30 | 0.00 | 01-APR-00:10 |
May | 3339.74 | 01-MAY-18:49 | 2213.72 | 01-MAY-05:10 | 24333.76 | 01-MAY-10:09 | 0.00 | 7752.47 | 24-MAY-11:20 | 17.86 | 12-MAY-10:30 | 0.00 | 01-MAY-00:10 |
June | 3339.74 | 01-JUN-19:10 | 2213.72 | 01-JUN-05:10 | 24333.76 | 01-JUN-10:09 | 0.00 | 8187.01 | 29-JUN-11:00 | 17.86 | 01-JUN-13:20 | 0.00 | 01-JUN-00:10 |
July | 3339.74 | 01-JUL-19:10 | 2213.72 | 01-JUL-05:10 | 24333.76 | 01-JUL-10:09 | 0.00 | 8714.80 | 18-JUL-17:00 | 17.86 | 03-JUL-13:09 | 0.00 | 01-JUL-00:10 |
August | 3339.74 | 01-AUG-19:19 | 2213.72 | 01-AUG-05:10 | 24333.76 | 01-AUG-10:09 | 0.00 | 8556.03 | 07-AUG-12:00 | 17.86 | 05-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 3339.74 | 01-SEP-18:30 | 2213.72 | 01-SEP-05:10 | 24333.76 | 01-SEP-10:09 | 0.00 | 9034.94 | 09-SEP-18:10 | 17.86 | 15-SEP-12:39 | 0.00 | 01-SEP-00:10 |
October | 3339.74 | 02-OCT-18:19 | 2213.72 | 01-OCT-05:10 | 24333.76 | 01-OCT-10:09 | 0.00 | 9034.94 | 06-OCT-11:09 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 3339.74 | 01-NOV-17:19 | 2213.72 | 01-NOV-05:10 | 24333.76 | 01-NOV-10:09 | 0.00 | 7275.34 | 07-NOV-12:00 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 3339.74 | 01-DEC-17:30 | 2213.72 | 01-DEC-06:10 | 24333.76 | 01-DEC-11:09 | 0.00 | 6518.88 | 14-DEC-12:00 | 17.86 | 12-DEC-14:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 5359.67 | 17.86 | 0.00 | ||||||
Maximum of Months | 3339.74 | 2213.72 | 24333.76 | 0.00 | 9034.94 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 21973.62 | 19-JAN-12:09 | 0.00 | 0.00 | 0.00 | 4741.56 | 04-JAN-19:30 | 0.00 |
February | 21587.57 | 24-FEB-12:00 | 0.00 | 0.00 | 0.00 | 4741.41 | 06-FEB-07:49 | 0.00 |
March | 23867.38 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 4740.51 | 09-MAR-07:49 | 0.00 |
April | 29442.73 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 4739.88 | 11-APR-06:40 | 0.00 |
May | 32630.78 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4736.87 | 19-MAY-18:30 | 0.00 |
June | 34240.28 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4736.69 | 01-JUN-18:00 | 0.00 |
July | 36759.72 | 22-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.90 | 20-JUL-06:00 | 0.00 |
August | 35345.38 | 24-AUG-17:00 | 0.00 | 0.00 | 0.00 | 4736.60 | 02-AUG-18:00 | 0.00 |
September | 38477.73 | 09-SEP-18:10 | 0.00 | 0.00 | 0.00 | 4736.68 | 22-SEP-18:30 | 0.00 |
October | 36765.39 | 06-OCT-11:09 | 0.00 | 0.00 | 0.00 | 4736.94 | 27-OCT-06:30 | 0.00 |
November | 29617.89 | 07-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4739.97 | 15-NOV-07:49 | 0.00 |
December | 26950.32 | 14-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4741.12 | 21-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 21587.57 | 0.00 | 0.00 | 0.00 | 4736.60 | 0.00 | ||
Maximum of Months | 38477.73 | 0.00 | 0.00 | 0.00 | 4741.56 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58110.02 | 19-JAN-11:00 | 2112.39 | 24333.76 | 0.00 | 0.00 | 4893.85 | 17.86 | 0.00 | 20714.51 | 0.00 |
February | 56327.61 | 24-FEB-12:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 5119.06 | 17.86 | 0.00 | 21587.57 | 0.00 |
March | 59249.17 | 07-MAR-11:39 | 2112.39 | 24333.76 | 0.00 | 0.00 | 5012.14 | 17.86 | 0.00 | 21561.33 | 0.00 |
April | 65081.83 | 28-APR-16:10 | 2112.39 | 21922.77 | 0.00 | 0.00 | 6896.71 | 17.86 | 0.00 | 29442.73 | 0.00 |
May | 69602.90 | 24-MAY-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7738.90 | 17.86 | 0.00 | 31809.75 | 0.00 |
June | 72016.98 | 29-JUN-11:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 8187.01 | 17.86 | 0.00 | 34240.28 | 0.00 |
July | 75044.24 | 18-JUL-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 8622.98 | 17.86 | 0.00 | 36335.70 | 0.00 |
August | 72844.82 | 14-AUG-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 8426.81 | 17.86 | 0.00 | 34327.70 | 0.00 |
September | 78095.82 | 09-SEP-18:49 | 3339.74 | 18708.11 | 2213.72 | 0.00 | 9034.94 | 17.86 | 0.00 | 38396.45 | 0.00 |
October | 75912.62 | 06-OCT-11:09 | 2112.39 | 22726.43 | 0.00 | 0.00 | 9034.94 | 17.86 | 0.00 | 36765.39 | 0.00 |
November | 66513.49 | 07-NOV-12:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 7275.34 | 17.86 | 0.00 | 29617.89 | 0.00 |
December | 63022.86 | 14-DEC-12:00 | 2112.39 | 22726.43 | 0.00 | 0.00 | 6518.88 | 17.86 | 0.00 | 26950.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 56327.61 | 2112.39 | 18708.11 | 0.00 | 0.00 | 4893.85 | 17.86 | 0.00 | 20714.51 | 0.00 | |
Maximum of Months | 78095.82 | 3339.74 | 24333.76 | 2213.72 | 0.00 | 9034.94 | 17.86 | 0.00 | 38396.45 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 56737.81 | 05-JAN-06:10 | 0.00 | 19517.81 | 26-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 75393.07 | 05-FEB-07:10 | 0.00 | 19193.64 | 01-FEB-07:30 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 47249.54 | 09-MAR-06:49 | 0.00 | 17821.66 | 02-MAR-19:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 13362.43 | 11-APR-05:00 | 0.00 | 17485.13 | 03-APR-18:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 17193.24 | 02-MAY-18:40 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 95.32 | 07-JUN-03:49 | 0.00 | 16924.33 | 01-JUN-18:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16722.54 | 03-JUL-18:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16809.87 | 30-AUG-18:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 17028.23 | 29-SEP-18:49 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 8472.72 | 28-OCT-05:00 | 0.00 | 17334.00 | 31-OCT-18:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 14027.55 | 15-NOV-06:49 | 0.00 | 17619.88 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 57785.70 | 21-DEC-06:00 | 0.00 | 18673.91 | 26-DEC-19:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16722.54 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 75393.07 | 0.00 | 19517.81 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 |
February | 0.17 | 20.37 | 0.00 | 20.37 | 0.33 | 23.21 | 0.00 | 23.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.61 | 0.00 | 24.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.64 | 0.00 | 24.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.81 | 0.00 | 24.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.88 | 0.00 | 24.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.97 | 0.00 | 24.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.01 | 0.00 | 25.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.96 | 0.00 | 24.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.92 | 0.00 | 24.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.72 | 0.00 | 24.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.68 | 0.00 | 24.68 |
Annual Sum or Average | 0.17 | 20.37 | 0.00 | 20.37 | 34.17 | 24.87 | 0.00 | 24.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 23.21 | 0.00 | 23.21 |
Maximum of Months | 0.17 | 20.37 | 0.00 | 20.37 | 5.17 | 25.01 | 0.00 | 25.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 29.37 | 0.00 | 29.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 29.80 | 0.00 | 29.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 29.85 | 0.00 | 29.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 30.23 | 1.33 | 30.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 28.91 | 24.67 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 145.67 | 27.76 | 120.00 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 290.83 | 27.69 | 257.50 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 224.83 | 27.70 | 193.33 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 132.33 | 28.06 | 105.33 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 101.17 | 28.39 | 73.67 | 28.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 30.08 | 1.50 | 29.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 29.97 | 0.00 | 29.97 |
Annual Sum or Average | 0.00 | 0.00 | 1033.33 | 28.07 | 777.33 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.69 | 0.00 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 290.83 | 30.23 | 257.50 | 30.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.33 | 21.95 | 222.50 | 22.46 | 127.83 | 22.58 |
February | 385.50 | 22.43 | 299.17 | 22.98 | 170.50 | 23.08 |
March | 393.33 | 22.55 | 313.33 | 23.14 | 161.67 | 23.26 |
April | 279.50 | 23.61 | 492.00 | 23.86 | 220.33 | 23.90 |
May | 482.83 | 24.14 | 611.00 | 24.12 | 482.83 | 24.13 |
June | 486.33 | 24.15 | 592.00 | 24.13 | 486.33 | 24.14 |
July | 603.33 | 24.14 | 609.00 | 24.14 | 603.33 | 24.14 |
August | 560.67 | 24.14 | 612.00 | 24.13 | 560.67 | 24.14 |
September | 569.67 | 24.11 | 590.00 | 24.11 | 569.67 | 24.11 |
October | 359.50 | 23.99 | 561.50 | 24.04 | 330.83 | 24.07 |
November | 287.50 | 23.03 | 404.67 | 23.60 | 158.50 | 23.68 |
December | 411.33 | 22.23 | 292.00 | 22.89 | 147.00 | 23.02 |
Annual Sum or Average | 5285.83 | 23.45 | 5599.17 | 23.75 | 4019.50 | 23.83 |
Minimum of Months | 279.50 | 21.95 | 222.50 | 22.46 | 127.83 | 22.58 |
Maximum of Months | 603.33 | 24.15 | 612.00 | 24.14 | 603.33 | 24.14 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.33 | 23.39 | 398.50 | 24.23 | 256.67 | 24.57 |
February | 444.17 | 24.38 | 438.00 | 24.83 | 343.50 | 25.05 |
March | 464.33 | 24.84 | 498.17 | 25.21 | 373.33 | 25.41 |
April | 528.67 | 25.95 | 577.00 | 25.89 | 524.67 | 25.92 |
May | 611.00 | 26.06 | 611.00 | 26.06 | 611.00 | 26.06 |
June | 592.00 | 26.25 | 592.00 | 26.25 | 592.00 | 26.25 |
July | 609.00 | 26.61 | 609.00 | 26.61 | 609.00 | 26.61 |
August | 612.00 | 26.42 | 612.00 | 26.42 | 612.00 | 26.42 |
September | 590.00 | 26.28 | 590.00 | 26.28 | 590.00 | 26.28 |
October | 580.00 | 26.19 | 605.17 | 26.16 | 576.67 | 26.18 |
November | 482.33 | 25.60 | 541.83 | 25.65 | 446.33 | 25.75 |
December | 456.33 | 24.39 | 464.50 | 24.85 | 339.33 | 25.12 |
Annual Sum or Average | 6407.17 | 25.65 | 6537.17 | 25.79 | 5874.50 | 25.90 |
Minimum of Months | 437.33 | 23.39 | 398.50 | 24.23 | 256.67 | 24.57 |
Maximum of Months | 612.00 | 26.61 | 612.00 | 26.61 | 612.00 | 26.61 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.39371 | 49.36971 | 0.12786 | 8.88946 |
February | 551.00000 | 22.86279 | 53.04302 | 0.26828 | 10.13577 |
March | 612.00000 | 23.03446 | 51.80948 | 0.29939 | 9.99868 |
April | 590.00000 | 23.79041 | 59.39925 | 0.55866 | 12.52613 |
May | 611.00000 | 24.10982 | 68.52892 | -0.0923 | 5.44636 |
June | 592.00000 | 24.12187 | 68.80262 | -0.0684 | 5.44895 |
July | 609.00000 | 24.14224 | 72.08215 | -0.0280 | 5.46714 |
August | 612.00000 | 24.12895 | 70.55020 | -0.0304 | 5.40553 |
September | 590.00000 | 24.10766 | 70.80260 | -0.0469 | 5.39354 |
October | 610.00000 | 23.98157 | 62.94606 | 0.68432 | 15.62275 |
November | 591.00000 | 23.48123 | 53.95534 | 0.46193 | 11.41030 |
December | 609.00000 | 22.77275 | 52.07540 | 0.25448 | 10.02778 |
Annual Sum or Average | 7187.00000 | 23.58009 | 61.15826 | 0.19812 | 8.80348 |
Minimum of Months | 551.00000 | 22.39371 | 49.36971 | -0.0923 | 5.39354 |
Maximum of Months | 612.00000 | 24.14224 | 72.08215 | 0.68432 | 15.62275 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.53111 | 49.37348 | 0.62216 | 21.78185 |
February | 551.00000 | 24.31299 | 51.26205 | 0.82481 | 27.21331 |
March | 612.00000 | 24.66517 | 50.01109 | 0.90268 | 28.15761 |
April | 590.00000 | 25.75519 | 55.22968 | 1.22664 | 37.55613 |
May | 611.00000 | 26.05540 | 63.11469 | 0.84059 | 20.40405 |
June | 592.00000 | 26.25464 | 63.65290 | 0.93174 | 24.37498 |
July | 609.00000 | 26.60531 | 65.74769 | 1.07766 | 31.00152 |
August | 612.00000 | 26.42449 | 64.46913 | 1.01769 | 28.14003 |
September | 590.00000 | 26.27853 | 63.71913 | 0.94764 | 25.06623 |
October | 610.00000 | 26.10295 | 57.95366 | 1.37863 | 44.93757 |
November | 591.00000 | 25.32594 | 50.96017 | 1.09831 | 33.27220 |
December | 609.00000 | 24.19185 | 50.50033 | 0.80496 | 26.07112 |
Annual Sum or Average | 7187.00000 | 25.46343 | 57.20255 | 0.97313 | 28.99857 |
Minimum of Months | 551.00000 | 23.53111 | 49.37348 | 0.62216 | 20.40405 |
Maximum of Months | 612.00000 | 26.60531 | 65.74769 | 1.37863 | 44.93757 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.112599E+11 | 0.323667E+10 | 153.36 | 0.641409E+10 | 0.484583E+10 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:10 | 97552.66 | 31-JAN-04:41 | 46591.65 | 30-JAN-04:01 | 57992.62 | 20-JAN-04:01 | 25315.03 | 31-JAN-04:41 | 0.00 | 01-JAN-00:10 |
February | 0.152502E+11 | 0.436079E+10 | 198.25 | 0.875587E+10 | 0.649429E+10 | 0.00 | 1.00 | 01-FEB-04:02 | 0.00 | 01-FEB-00:05 | 98893.00 | 03-FEB-04:41 | 46344.72 | 26-FEB-04:01 | 58275.26 | 03-FEB-04:41 | 25414.55 | 03-FEB-04:41 | 0.00 | 01-FEB-00:05 |
March | 0.231693E+11 | 0.654064E+10 | 278.37 | 0.137385E+11 | 0.943089E+10 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 | 101828.02 | 07-MAR-04:01 | 58122.59 | 05-MAR-04:01 | 60646.47 | 07-MAR-04:01 | 25637.81 | 07-MAR-04:01 | 0.00 | 01-MAR-00:03 |
April | 0.430769E+11 | 0.118848E+11 | 439.44 | 0.255366E+11 | 0.175403E+11 | 0.00 | 1.00 | 01-APR-03:02 | 0.00 | 01-APR-00:01 | 103662.05 | 28-APR-03:01 | 59510.47 | 18-APR-03:01 | 63588.80 | 29-APR-03:01 | 25784.91 | 28-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.102296E+12 | 0.267097E+11 | 611.24 | 0.547827E+11 | 0.475129E+11 | 0.00 | 1.00 | 01-MAY-03:02 | 0.00 | 01-MAY-00:01 | 103662.05 | 14-MAY-03:01 | 52048.84 | 12-MAY-03:01 | 66598.02 | 24-MAY-03:01 | 25784.91 | 02-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.109613E+12 | 0.284760E+11 | 592.43 | 0.580218E+11 | 0.515913E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 103662.05 | 04-JUN-03:02 | 53471.68 | 10-JUN-03:01 | 68012.32 | 30-JUN-03:01 | 25784.91 | 02-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.127866E+12 | 0.329475E+11 | 613.48 | 0.620770E+11 | 0.657887E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 103662.05 | 22-JUL-03:02 | 53975.81 | 20-JUL-12:00 | 68975.12 | 15-JUL-03:01 | 26401.73 | 22-JUL-17:10 | 0.00 | 01-JUL-00:01 |
August | 0.121210E+12 | 0.313353E+11 | 612.57 | 0.608128E+11 | 0.603972E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 103662.05 | 30-AUG-03:01 | 65264.39 | 20-AUG-03:57 | 69914.84 | 19-AUG-03:01 | 25784.91 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.106355E+12 | 0.274980E+11 | 593.55 | 0.516674E+11 | 0.546876E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 103662.05 | 15-SEP-03:01 | 57370.03 | 09-SEP-18:03 | 69185.44 | 02-SEP-03:01 | 28001.87 | 09-SEP-18:03 | 0.00 | 01-SEP-00:01 |
October | 0.857193E+11 | 0.224711E+11 | 546.36 | 0.448688E+11 | 0.408505E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 103662.05 | 07-OCT-03:01 | 83815.31 | 27-OCT-03:01 | 73612.76 | 07-OCT-03:01 | 26755.73 | 06-OCT-11:02 | 0.00 | 01-OCT-00:01 |
November | 0.340290E+11 | 0.937982E+10 | 368.65 | 0.190770E+11 | 0.149520E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 103662.05 | 01-NOV-03:01 | 66136.51 | 12-NOV-04:01 | 65997.00 | 03-NOV-03:02 | 25784.91 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.211954E+11 | 0.587355E+10 | 249.51 | 0.116891E+11 | 0.950635E+10 | 0.00 | 1.00 | 09-DEC-04:02 | 0.00 | 01-DEC-00:03 | 101735.61 | 17-DEC-04:01 | 45401.15 | 09-DEC-04:41 | 63758.87 | 17-DEC-04:01 | 25630.59 | 17-DEC-04:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.801040E+12 | 0.210714E+12 | 5257.23 | 0.417442E+12 | 0.383598E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.112599E+11 | 0.323667E+10 | 153.36 | 0.641409E+10 | 0.484583E+10 | 0.00 | 1.00 | 0.00 | 97552.66 | 45401.15 | 57992.62 | 25315.03 | 0.00 | |||||||
Maximum of Months | 0.127866E+12 | 0.329475E+11 | 613.48 | 0.620770E+11 | 0.657887E+11 | 0.00 | 1.00 | 0.00 | 103662.05 | 83815.31 | 73612.76 | 28001.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.102824E+11 | 0.249411E+10 | 220.84 | 0.552247E+10 | 0.475995E+10 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:10 | 40840.30 | 19-JAN-04:01 | 29764.56 | 03-JAN-04:31 | 26062.45 | 19-JAN-04:01 | 9474.32 | 19-JAN-04:01 | 0.00 | 01-JAN-00:10 |
February | 0.135315E+11 | 0.327551E+10 | 270.50 | 0.730109E+10 | 0.623045E+10 | 0.00 | 1.00 | 01-FEB-04:11 | 0.00 | 01-FEB-00:05 | 40933.79 | 03-FEB-04:11 | 32873.45 | 12-FEB-04:01 | 25718.33 | 03-FEB-04:51 | 9480.52 | 03-FEB-04:11 | 0.00 | 01-FEB-00:05 |
March | 0.191497E+11 | 0.459214E+10 | 353.98 | 0.109345E+11 | 0.821517E+10 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 | 42293.85 | 07-MAR-04:51 | 29595.38 | 04-MAR-04:01 | 26701.48 | 07-MAR-04:51 | 9572.07 | 07-MAR-04:51 | 0.00 | 01-MAR-00:03 |
April | 0.342546E+11 | 0.810161E+10 | 523.10 | 0.195799E+11 | 0.146747E+11 | 0.00 | 1.00 | 01-APR-03:11 | 0.00 | 01-APR-00:01 | 43339.52 | 28-APR-17:22 | 29344.88 | 10-APR-03:31 | 27516.75 | 29-APR-01:32 | 10115.18 | 28-APR-15:23 | 0.00 | 01-APR-00:01 |
May | 0.754211E+11 | 0.171393E+11 | 679.99 | 0.394609E+11 | 0.359603E+11 | 0.00 | 1.00 | 01-MAY-01:13 | 0.00 | 01-MAY-00:01 | 43339.52 | 19-MAY-18:02 | 29833.42 | 28-MAY-15:40 | 28222.53 | 18-MAY-01:32 | 10287.82 | 28-MAY-15:53 | 0.00 | 01-MAY-00:01 |
June | 0.784505E+11 | 0.178684E+11 | 670.30 | 0.407402E+11 | 0.377103E+11 | 0.00 | 1.00 | 01-JUN-01:32 | 0.00 | 01-JUN-00:01 | 43339.52 | 14-JUN-18:03 | 31466.31 | 14-JUN-14:00 | 28997.23 | 30-JUN-03:01 | 10418.11 | 14-JUN-14:10 | 0.00 | 01-JUN-00:01 |
July | 0.898129E+11 | 0.204085E+11 | 706.81 | 0.420728E+11 | 0.477401E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 43339.52 | 01-JUL-15:15 | 32543.40 | 08-JUL-12:00 | 29299.46 | 15-JUL-03:01 | 10652.79 | 21-JUL-15:53 | 0.00 | 01-JUL-00:01 |
August | 0.856057E+11 | 0.194596E+11 | 695.65 | 0.414795E+11 | 0.441262E+11 | 0.00 | 1.00 | 01-AUG-01:32 | 0.00 | 01-AUG-00:01 | 43339.52 | 04-AUG-19:33 | 34191.18 | 30-AUG-15:55 | 30502.84 | 19-AUG-03:01 | 10688.12 | 30-AUG-15:55 | 0.00 | 01-AUG-00:01 |
September | 0.775978E+11 | 0.175409E+11 | 663.56 | 0.357668E+11 | 0.418310E+11 | 0.00 | 1.00 | 01-SEP-00:53 | 0.00 | 01-SEP-00:01 | 43339.52 | 04-SEP-11:13 | 28085.80 | 09-SEP-16:55 | 29949.94 | 02-SEP-03:01 | 10705.92 | 09-SEP-16:53 | 0.00 | 01-SEP-00:01 |
October | 0.613780E+11 | 0.140437E+11 | 623.72 | 0.309387E+11 | 0.304394E+11 | 0.00 | 1.00 | 01-OCT-00:53 | 0.00 | 01-OCT-00:01 | 43339.52 | 05-OCT-18:55 | 33654.98 | 27-OCT-03:01 | 31664.48 | 07-OCT-03:45 | 10303.43 | 05-OCT-15:00 | 0.00 | 01-OCT-00:01 |
November | 0.272271E+11 | 0.646374E+10 | 438.58 | 0.147512E+11 | 0.124759E+11 | 0.00 | 1.00 | 01-NOV-01:32 | 0.00 | 01-NOV-00:01 | 43339.52 | 03-NOV-11:11 | 32998.61 | 23-NOV-04:01 | 29185.92 | 01-NOV-03:01 | 9756.76 | 01-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.179619E+11 | 0.427731E+10 | 317.86 | 0.936183E+10 | 0.860003E+10 | 0.00 | 1.00 | 01-DEC-04:11 | 0.00 | 01-DEC-00:03 | 43258.46 | 15-DEC-12:00 | 32683.47 | 18-DEC-04:01 | 28069.24 | 15-DEC-04:41 | 9628.44 | 15-DEC-12:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.590673E+12 | 0.135665E+12 | 6164.89 | 0.297910E+12 | 0.292763E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.102824E+11 | 0.249411E+10 | 220.84 | 0.552247E+10 | 0.475995E+10 | 0.00 | 1.00 | 0.00 | 40840.30 | 28085.80 | 25718.33 | 9474.32 | 0.00 | |||||||
Maximum of Months | 0.898129E+11 | 0.204085E+11 | 706.81 | 0.420728E+11 | 0.477401E+11 | 0.00 | 1.00 | 0.00 | 43339.52 | 34191.18 | 31664.48 | 10705.92 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.77 | 87.37 | 84.40 | 206.47 | 261.65 | 0.00 | 0.00 | 0.00 |
February | 191.85 | 92.62 | 99.23 | 242.36 | 224.16 | 0.00 | 0.00 | 0.00 |
March | 225.93 | 109.08 | 116.85 | 314.21 | 189.17 | 0.00 | 0.00 | 0.00 |
April | 247.58 | 111.89 | 135.69 | 394.55 | 121.90 | 0.00 | 0.00 | 0.00 |
May | 255.05 | 110.72 | 144.33 | 498.69 | 35.56 | 0.00 | 0.00 | 0.00 |
June | 258.18 | 102.29 | 155.90 | 522.23 | 31.20 | 0.00 | 0.00 | 0.00 |
July | 249.23 | 91.24 | 157.99 | 506.40 | 22.01 | 0.00 | 0.00 | 0.00 |
August | 229.80 | 79.07 | 150.72 | 463.23 | 31.91 | 0.00 | 0.00 | 0.00 |
September | 203.26 | 69.85 | 133.41 | 389.60 | 45.17 | 0.00 | 0.00 | 0.00 |
October | 201.17 | 84.95 | 116.21 | 362.07 | 80.12 | 0.00 | 0.00 | 0.00 |
November | 177.72 | 90.47 | 87.24 | 251.89 | 175.19 | 0.00 | 0.00 | 0.00 |
December | 140.21 | 63.60 | 76.61 | 174.89 | 233.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.72 | 91.06 | 121.66 | 361.20 | 120.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 140.21 | 63.60 | 76.61 | 174.89 | 22.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 258.18 | 111.89 | 157.99 | 522.23 | 261.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 535.66 | 382.22 | 153.44 | 790.37 | 345.58 | 0.00 | 0.00 | 0.00 |
February | 482.07 | 310.89 | 171.18 | 723.13 | 301.19 | 0.00 | 0.00 | 0.00 |
March | 314.80 | 144.87 | 169.92 | 481.82 | 271.05 | 0.00 | 0.00 | 0.00 |
April | 229.76 | 53.94 | 175.81 | 388.14 | 178.53 | 0.00 | 0.00 | 0.00 |
May | 176.73 | 8.71 | 168.02 | 382.80 | 50.29 | 0.00 | 0.00 | 0.00 |
June | 173.15 | 1.51 | 171.64 | 386.94 | 44.33 | 0.00 | 0.00 | 0.00 |
July | 181.03 | 2.97 | 178.07 | 403.12 | 30.74 | 0.00 | 0.00 | 0.00 |
August | 209.57 | 21.73 | 187.84 | 465.85 | 45.04 | 0.00 | 0.00 | 0.00 |
September | 256.98 | 68.41 | 188.57 | 523.10 | 63.53 | 0.00 | 0.00 | 0.00 |
October | 393.19 | 202.85 | 190.33 | 730.43 | 112.31 | 0.00 | 0.00 | 0.00 |
November | 510.27 | 352.77 | 157.50 | 814.49 | 237.39 | 0.00 | 0.00 | 0.00 |
December | 523.58 | 376.28 | 147.29 | 802.07 | 310.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 331.43 | 159.82 | 171.62 | 573.64 | 165.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.15 | 1.51 | 147.29 | 382.80 | 30.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 535.66 | 382.22 | 190.33 | 814.49 | 345.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.03 | 98.97 | 84.06 | 234.98 | 270.19 | 0.00 | 0.00 | 0.00 |
February | 207.71 | 105.31 | 102.40 | 278.22 | 231.59 | 0.00 | 0.00 | 0.00 |
March | 203.64 | 89.84 | 113.81 | 284.59 | 197.66 | 0.00 | 0.00 | 0.00 |
April | 253.18 | 116.34 | 136.84 | 409.13 | 125.36 | 0.00 | 0.00 | 0.00 |
May | 211.10 | 68.84 | 142.26 | 422.89 | 35.97 | 0.00 | 0.00 | 0.00 |
June | 234.26 | 82.20 | 152.06 | 479.20 | 31.84 | 0.00 | 0.00 | 0.00 |
July | 213.53 | 59.05 | 154.48 | 441.18 | 21.77 | 0.00 | 0.00 | 0.00 |
August | 215.78 | 65.61 | 150.18 | 441.12 | 32.33 | 0.00 | 0.00 | 0.00 |
September | 199.16 | 68.33 | 130.84 | 383.14 | 45.41 | 0.00 | 0.00 | 0.00 |
October | 204.36 | 88.54 | 115.82 | 371.53 | 82.89 | 0.00 | 0.00 | 0.00 |
November | 174.69 | 87.77 | 86.92 | 256.31 | 183.48 | 0.00 | 0.00 | 0.00 |
December | 167.47 | 88.79 | 78.67 | 227.05 | 236.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.54 | 84.76 | 120.78 | 352.73 | 123.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.47 | 59.05 | 78.67 | 227.05 | 21.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.18 | 116.34 | 154.48 | 479.20 | 270.19 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.460071E+09 | 0.234012E+09 | 0.226059E+09 | 0.553019E+09 | 0.700791E+09 |
February | 0.464120E+09 | 0.224067E+09 | 0.240053E+09 | 0.586317E+09 | 0.542285E+09 |
March | 0.605127E+09 | 0.292168E+09 | 0.312959E+09 | 0.841581E+09 | 0.506663E+09 |
April | 0.641737E+09 | 0.290024E+09 | 0.351714E+09 | 0.102267E+10 | 0.315974E+09 |
May | 0.683122E+09 | 0.296559E+09 | 0.386563E+09 | 0.133570E+10 | 95233754.16 |
June | 0.669209E+09 | 0.265125E+09 | 0.404084E+09 | 0.135362E+10 | 80864859.58 |
July | 0.667536E+09 | 0.244366E+09 | 0.423170E+09 | 0.135634E+10 | 58961850.41 |
August | 0.615489E+09 | 0.211794E+09 | 0.403695E+09 | 0.124073E+10 | 85466857.10 |
September | 0.526862E+09 | 0.181051E+09 | 0.345811E+09 | 0.100985E+10 | 0.117092E+09 |
October | 0.538802E+09 | 0.227535E+09 | 0.311267E+09 | 0.969762E+09 | 0.214606E+09 |
November | 0.460641E+09 | 0.234503E+09 | 0.226138E+09 | 0.652886E+09 | 0.454100E+09 |
December | 0.375530E+09 | 0.170339E+09 | 0.205190E+09 | 0.468439E+09 | 0.624799E+09 |
Annual Sum or Average | 0.670825E+10 | 0.287154E+10 | 0.383670E+10 | 0.113909E+11 | 0.379684E+10 |
Minimum of Months | 0.375530E+09 | 0.170339E+09 | 0.205190E+09 | 0.468439E+09 | 58961850.41 |
Maximum of Months | 0.683122E+09 | 0.296559E+09 | 0.423170E+09 | 0.135634E+10 | 0.700791E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143471E+10 | 0.102374E+10 | 0.410971E+09 | 0.211692E+10 | 0.925592E+09 |
February | 0.116622E+10 | 0.752103E+09 | 0.414119E+09 | 0.174941E+10 | 0.728633E+09 |
March | 0.843149E+09 | 0.388025E+09 | 0.455124E+09 | 0.129051E+10 | 0.725974E+09 |
April | 0.595525E+09 | 0.139814E+09 | 0.455711E+09 | 0.100606E+10 | 0.462753E+09 |
May | 0.473354E+09 | 23328503.82 | 0.450026E+09 | 0.102530E+10 | 0.134701E+09 |
June | 0.448817E+09 | 3923628.87 | 0.444894E+09 | 0.100294E+10 | 0.114905E+09 |
July | 0.484878E+09 | 7943441.78 | 0.476934E+09 | 0.107972E+10 | 82339982.96 |
August | 0.561325E+09 | 58208414.00 | 0.503116E+09 | 0.124774E+10 | 0.120639E+09 |
September | 0.666087E+09 | 0.177319E+09 | 0.488768E+09 | 0.135587E+10 | 0.164667E+09 |
October | 0.105311E+10 | 0.543326E+09 | 0.509782E+09 | 0.195639E+10 | 0.300811E+09 |
November | 0.132262E+10 | 0.914375E+09 | 0.408242E+09 | 0.211116E+10 | 0.615322E+09 |
December | 0.140234E+10 | 0.100783E+10 | 0.394514E+09 | 0.214826E+10 | 0.830643E+09 |
Annual Sum or Average | 0.104521E+11 | 0.503993E+10 | 0.541220E+10 | 0.180903E+11 | 0.520698E+10 |
Minimum of Months | 0.448817E+09 | 3923628.87 | 0.394514E+09 | 0.100294E+10 | 82339982.96 |
Maximum of Months | 0.143471E+10 | 0.102374E+10 | 0.509782E+09 | 0.214826E+10 | 0.925592E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.490222E+09 | 0.265083E+09 | 0.225140E+09 | 0.629380E+09 | 0.723673E+09 |
February | 0.502498E+09 | 0.254774E+09 | 0.247724E+09 | 0.673064E+09 | 0.560267E+09 |
March | 0.545437E+09 | 0.240621E+09 | 0.304817E+09 | 0.762254E+09 | 0.529404E+09 |
April | 0.656251E+09 | 0.301555E+09 | 0.354697E+09 | 0.106046E+10 | 0.324937E+09 |
May | 0.565400E+09 | 0.184372E+09 | 0.381028E+09 | 0.113266E+10 | 96350281.78 |
June | 0.607198E+09 | 0.213051E+09 | 0.394148E+09 | 0.124209E+10 | 82530315.88 |
July | 0.571924E+09 | 0.158165E+09 | 0.413759E+09 | 0.118167E+10 | 58319278.72 |
August | 0.577954E+09 | 0.175721E+09 | 0.402233E+09 | 0.118149E+10 | 86596899.62 |
September | 0.516228E+09 | 0.177099E+09 | 0.339129E+09 | 0.993100E+09 | 0.117698E+09 |
October | 0.547356E+09 | 0.237140E+09 | 0.310216E+09 | 0.995098E+09 | 0.222003E+09 |
November | 0.452790E+09 | 0.227488E+09 | 0.225302E+09 | 0.664356E+09 | 0.475586E+09 |
December | 0.448539E+09 | 0.237822E+09 | 0.210717E+09 | 0.608119E+09 | 0.632355E+09 |
Annual Sum or Average | 0.648180E+10 | 0.267289E+10 | 0.380891E+10 | 0.111237E+11 | 0.390972E+10 |
Minimum of Months | 0.448539E+09 | 0.158165E+09 | 0.210717E+09 | 0.608119E+09 | 58319278.72 |
Maximum of Months | 0.656251E+09 | 0.301555E+09 | 0.413759E+09 | 0.124209E+10 | 0.723673E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1195.78 | 841.37 | 890.46 | 568.56 | 321.90 | 0.00 | 0.00 |
February | 1213.07 | 726.30 | 881.63 | 508.82 | 372.81 | 0.00 | 0.00 |
March | 1056.84 | 634.08 | 744.37 | 343.79 | 400.57 | 0.00 | 0.00 |
April | 1174.64 | 408.62 | 730.52 | 282.17 | 448.35 | 0.00 | 0.00 |
May | 1302.34 | 119.78 | 642.87 | 188.27 | 454.61 | 0.00 | 0.00 |
June | 1386.73 | 105.73 | 665.60 | 186.00 | 479.60 | 0.00 | 0.00 |
July | 1349.89 | 73.72 | 643.79 | 153.25 | 490.54 | 0.00 | 0.00 |
August | 1369.06 | 108.14 | 655.16 | 166.41 | 488.74 | 0.00 | 0.00 |
September | 1294.34 | 152.61 | 659.40 | 206.59 | 452.82 | 0.00 | 0.00 |
October | 1459.58 | 270.88 | 798.71 | 376.34 | 422.37 | 0.00 | 0.00 |
November | 1303.47 | 576.85 | 862.67 | 531.01 | 331.67 | 0.00 | 0.00 |
December | 1181.79 | 757.28 | 831.25 | 528.67 | 302.58 | 0.00 | 0.00 |
Annual Sum or Average | 1274.29 | 396.20 | 749.69 | 335.63 | 414.06 | 0.00 | 0.00 |
Minimum of Months | 1056.84 | 73.72 | 642.87 | 153.25 | 302.58 | 0.00 | 0.00 |
Maximum of Months | 1459.58 | 841.37 | 890.46 | 568.56 | 490.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.320278E+10 | 0.225351E+10 | 0.238500E+10 | 0.152283E+10 | 0.862170E+09 | 0.00 | 0.00 |
February | 0.293467E+10 | 0.175707E+10 | 0.213284E+10 | 0.123094E+10 | 0.901896E+09 | 0.00 | 0.00 |
March | 0.283064E+10 | 0.169833E+10 | 0.199371E+10 | 0.920814E+09 | 0.107290E+10 | 0.00 | 0.00 |
April | 0.304466E+10 | 0.105913E+10 | 0.189351E+10 | 0.731392E+09 | 0.116212E+10 | 0.00 | 0.00 |
May | 0.348819E+10 | 0.320816E+09 | 0.172188E+10 | 0.504259E+09 | 0.121762E+10 | 0.00 | 0.00 |
June | 0.359439E+10 | 0.274040E+09 | 0.172522E+10 | 0.482100E+09 | 0.124313E+10 | 0.00 | 0.00 |
July | 0.361555E+10 | 0.197445E+09 | 0.172434E+10 | 0.410474E+09 | 0.131386E+10 | 0.00 | 0.00 |
August | 0.366688E+10 | 0.289632E+09 | 0.175477E+10 | 0.445724E+09 | 0.130904E+10 | 0.00 | 0.00 |
September | 0.335494E+10 | 0.395576E+09 | 0.170918E+10 | 0.535468E+09 | 0.117371E+10 | 0.00 | 0.00 |
October | 0.390934E+10 | 0.725514E+09 | 0.213927E+10 | 0.100800E+10 | 0.113126E+10 | 0.00 | 0.00 |
November | 0.337860E+10 | 0.149520E+10 | 0.223605E+10 | 0.137637E+10 | 0.859683E+09 | 0.00 | 0.00 |
December | 0.316532E+10 | 0.202830E+10 | 0.222641E+10 | 0.141599E+10 | 0.810422E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.401860E+11 | 0.124946E+11 | 0.236422E+11 | 0.105844E+11 | 0.130578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.283064E+10 | 0.197445E+09 | 0.170918E+10 | 0.410474E+09 | 0.810422E+09 | 0.00 | 0.00 |
Maximum of Months | 0.390934E+10 | 0.225351E+10 | 0.238500E+10 | 0.152283E+10 | 0.131386E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638613E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160950778.0 | 81.21 | 0.00 | 0.00 |
February | 0.577778E+10 | -0.563430E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -143475071.4 | 81.21 | 0.00 | 0.00 |
March | 0.645167E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157804052.1 | 81.21 | 0.00 | 0.00 |
April | 0.619335E+10 | -0.604346E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149893042.8 | 81.21 | 0.00 | 0.00 |
May | 0.641432E+10 | -0.626022E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154097533.9 | 81.21 | 0.00 | 0.00 |
June | 0.623524E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148648639.3 | 81.21 | 0.00 | 0.00 |
July | 0.636979E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152704707.5 | 81.21 | 0.00 | 0.00 |
August | 0.644835E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153144835.1 | 81.22 | 0.00 | 0.00 |
September | 0.619340E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148578553.2 | 81.21 | 0.00 | 0.00 |
October | 0.637785E+10 | -0.622384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154006339.7 | 81.21 | 0.00 | 0.00 |
November | 0.617560E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150981718.5 | 81.21 | 0.00 | 0.00 |
December | 0.637614E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159069073.1 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.753996E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.183335E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577778E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160950778.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645167E+10 | -0.563430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -143475071.4 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.196589E+11 | -0.187592E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -899712753.4 | 58.99 | 0.00 | 0.00 |
February | 0.176328E+11 | -0.168376E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -795156992.1 | 58.99 | 0.00 | 0.00 |
March | 0.189637E+11 | -0.180930E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -870626620.5 | 58.98 | 0.00 | 0.00 |
April | 0.171192E+11 | -0.163024E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -816777534.0 | 58.98 | 0.00 | 0.00 |
May | 0.165256E+11 | -0.156888E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -836882500.8 | 58.99 | 0.00 | 0.00 |
June | 0.151108E+11 | -0.143054E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -805468820.1 | 58.98 | 0.00 | 0.00 |
July | 0.149650E+11 | -0.141410E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -823989051.4 | 58.98 | 0.00 | 0.00 |
August | 0.153020E+11 | -0.144740E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -827978808.4 | 58.98 | 0.00 | 0.00 |
September | 0.154163E+11 | -0.146114E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -804903696.3 | 58.99 | 0.00 | 0.00 |
October | 0.169923E+11 | -0.161563E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -835934421.4 | 58.98 | 0.00 | 0.00 |
November | 0.176174E+11 | -0.167905E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -826852067.0 | 58.99 | 0.00 | 0.00 |
December | 0.191582E+11 | -0.182759E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -882314311.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.204462E+12 | -0.194435E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.100266E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.149650E+11 | -0.187592E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -899712753.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.196589E+11 | -0.141410E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -795156992.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.50 | 01-JAN-07:49 | 857.10 | 24.90 | 169.00 | 295.33 | 1055.04 | 25.86 | 181.83 | 293.50 |
February | 295.50 | 0.53 | 0.50 | 01-FEB-11:39 | 912.55 | 23.32 | 146.00 | 275.83 | 889.95 | 22.48 | 143.17 | 276.83 |
March | 296.00 | 0.53 | 0.50 | 02-MAR-12:39 | 926.12 | 20.68 | 104.17 | 321.17 | 907.78 | 20.23 | 88.67 | 319.00 |
April | 347.33 | 0.54 | 0.50 | 01-APR-07:40 | 794.13 | 19.58 | 78.83 | 330.83 | 766.73 | 19.68 | 86.67 | 329.17 |
May | 353.67 | 0.53 | 0.50 | 01-MAY-06:00 | 625.09 | 19.77 | 67.83 | 353.00 | 702.27 | 19.73 | 63.33 | 355.00 |
June | 394.00 | 0.54 | 0.50 | 01-JUN-06:40 | 619.67 | 19.44 | 63.00 | 355.67 | 662.64 | 19.39 | 52.50 | 353.67 |
July | 390.00 | 0.53 | 0.50 | 01-JUL-06:49 | 620.23 | 19.68 | 81.83 | 357.83 | 659.66 | 19.65 | 70.83 | 360.00 |
August | 380.83 | 0.53 | 0.50 | 01-AUG-07:10 | 696.61 | 19.83 | 101.33 | 346.00 | 749.93 | 19.84 | 93.83 | 348.83 |
September | 342.17 | 0.54 | 0.50 | 01-SEP-07:10 | 795.12 | 20.04 | 116.00 | 316.67 | 839.45 | 20.01 | 108.50 | 316.33 |
October | 330.00 | 0.52 | 0.50 | 01-OCT-07:10 | 868.05 | 21.48 | 157.17 | 311.00 | 935.35 | 22.39 | 180.33 | 306.83 |
November | 308.00 | 0.53 | 0.50 | 01-NOV-08:20 | 1043.69 | 24.47 | 173.00 | 284.00 | 853.60 | 24.30 | 161.83 | 286.17 |
December | 282.83 | 0.52 | 0.50 | 01-DEC-07:49 | 850.84 | 24.64 | 146.33 | 279.00 | 814.21 | 24.79 | 153.17 | 278.00 |
Annual Sum or Average | 4027.67 | 0.53 | 788.56 | 21.30 | 1404.50 | 3826.33 | 810.31 | 21.35 | 1384.67 | 3823.33 | ||
Minimum of Months | 282.83 | 0.52 | 0.50 | 619.67 | 19.44 | 63.00 | 275.83 | 659.66 | 19.39 | 52.50 | 276.83 | |
Maximum of Months | 394.00 | 0.54 | 0.50 | 1043.69 | 24.90 | 173.00 | 357.83 | 1055.04 | 25.86 | 181.83 | 360.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.717594E+10 | 36513.33 | 21-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.479468E+10 | 63134.41 | 05-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329662E+10 | 31135.59 | 09-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100293E+09 | 10689.94 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45752.81 | 152.51 | 07-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52743835.59 | 7539.76 | 28-OCT-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.748529E+09 | 15247.60 | 16-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462755E+10 | 38464.76 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717594E+10 | 63134.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117929E+10 | 21592.12 | 05-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104816E+10 | 30849.03 | 05-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331935E+09 | 20273.76 | 09-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 666807.86 | 579.30 | 16-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587026E+09 | 22361.87 | 21-DEC-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117929E+10 | 30849.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112599E+11 | 0.641409E+10 | 97552.66 | 31-JAN-04:41 | 40714.64 | 0.00 |
February | 0.00 | 0.00 | 0.152502E+11 | 0.875587E+10 | 98893.00 | 03-FEB-04:41 | 40617.74 | 0.00 |
March | 0.00 | 0.00 | 0.231693E+11 | 0.137385E+11 | 101828.02 | 07-MAR-04:01 | 41181.55 | 0.00 |
April | 0.00 | 0.00 | 0.430769E+11 | 0.255366E+11 | 103662.05 | 28-APR-03:01 | 42072.44 | 0.00 |
May | 0.00 | 0.00 | 0.102296E+12 | 0.547827E+11 | 103662.05 | 14-MAY-03:01 | 46414.55 | 0.00 |
June | 0.00 | 0.00 | 0.109613E+12 | 0.580218E+11 | 103662.05 | 04-JUN-03:02 | 42991.08 | 0.00 |
July | 0.00 | 0.00 | 0.127866E+12 | 0.620770E+11 | 103662.05 | 22-JUL-03:02 | 44333.61 | 0.00 |
August | 0.00 | 0.00 | 0.121210E+12 | 0.608128E+11 | 103662.05 | 30-AUG-03:01 | 43722.41 | 0.00 |
September | 0.00 | 0.00 | 0.106355E+12 | 0.516674E+11 | 103662.05 | 15-SEP-03:01 | 43441.49 | 0.00 |
October | 0.00 | 0.00 | 0.857193E+11 | 0.448688E+11 | 103662.05 | 07-OCT-03:01 | 30049.29 | 0.00 |
November | 0.00 | 0.00 | 0.340290E+11 | 0.190770E+11 | 103662.05 | 01-NOV-03:01 | 45647.19 | 0.00 |
December | 0.00 | 0.00 | 0.211954E+11 | 0.116891E+11 | 101735.61 | 17-DEC-04:01 | 37976.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.801040E+12 | 0.417442E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.112599E+11 | 0.641409E+10 | 97552.66 | 30049.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127866E+12 | 0.620770E+11 | 103662.05 | 46414.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102824E+11 | 0.552247E+10 | 40840.30 | 19-JAN-04:01 | 14777.86 | 0.00 |
February | 0.00 | 0.00 | 0.135315E+11 | 0.730109E+10 | 40933.79 | 03-FEB-04:11 | 15219.92 | 0.00 |
March | 0.00 | 0.00 | 0.191497E+11 | 0.109345E+11 | 42293.85 | 07-MAR-04:51 | 15592.37 | 0.00 |
April | 0.00 | 0.00 | 0.342546E+11 | 0.195799E+11 | 43339.52 | 28-APR-17:22 | 21786.63 | 0.00 |
May | 0.00 | 0.00 | 0.754211E+11 | 0.394609E+11 | 43339.52 | 19-MAY-18:02 | 17770.07 | 0.00 |
June | 0.00 | 0.00 | 0.784505E+11 | 0.407402E+11 | 43339.52 | 14-JUN-18:03 | 21504.78 | 0.00 |
July | 0.00 | 0.00 | 0.898129E+11 | 0.420728E+11 | 43339.52 | 01-JUL-15:15 | 17259.55 | 0.00 |
August | 0.00 | 0.00 | 0.856057E+11 | 0.414795E+11 | 43339.52 | 04-AUG-19:33 | 19443.42 | 0.00 |
September | 0.00 | 0.00 | 0.775978E+11 | 0.357668E+11 | 43339.52 | 04-SEP-11:13 | 17945.46 | 0.00 |
October | 0.00 | 0.00 | 0.613780E+11 | 0.309387E+11 | 43339.52 | 05-OCT-18:55 | 20877.98 | 0.00 |
November | 0.00 | 0.00 | 0.272271E+11 | 0.147512E+11 | 43339.52 | 03-NOV-11:11 | 21116.41 | 0.00 |
December | 0.00 | 0.00 | 0.179619E+11 | 0.936183E+10 | 43258.46 | 15-DEC-12:00 | 23505.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.590673E+12 | 0.297910E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.102824E+11 | 0.552247E+10 | 40840.30 | 14777.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.898129E+11 | 0.420728E+11 | 43339.52 | 23505.09 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7466.99 | 14190.28 | 24-JAN-19:30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7423.12 | 14159.10 | 02-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7218.62 | 13838.96 | 02-MAR-19:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6754.18 | 13147.79 | 03-APR-18:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6323.09 | 12331.87 | 01-MAY-18:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5985.77 | 11542.10 | 01-JUN-18:55 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5746.80 | 10955.01 | 03-JUL-18:33 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5870.84 | 11201.95 | 31-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 6103.63 | 11820.71 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6497.36 | 12720.78 | 31-OCT-18:33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6941.94 | 13501.49 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 7286.91 | 14052.18 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 6630.53 | ||||
Minimum of Months | 0.00 | 0.00 | 5746.80 | 10955.01 | ||
Maximum of Months | 0.00 | 0.00 | 7466.99 | 14190.28 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.195801E+10 | 0.23 | 824.13 | 01-JAN-00:10 | 0.26 |
February | 0.179372E+10 | 0.24 | 824.13 | 01-FEB-00:05 | 0.26 |
March | 0.199806E+10 | 0.24 | 824.13 | 01-MAR-00:03 | 0.26 |
April | 0.199784E+10 | 0.24 | 824.13 | 01-APR-00:40 | 0.26 |
May | 0.210314E+10 | 0.25 | 824.13 | 01-MAY-00:40 | 0.26 |
June | 0.204112E+10 | 0.25 | 824.13 | 01-JUN-00:20 | 0.26 |
July | 0.210590E+10 | 0.25 | 824.13 | 01-JUL-00:12 | 0.26 |
August | 0.210619E+10 | 0.25 | 824.13 | 01-AUG-00:19 | 0.26 |
September | 0.204239E+10 | 0.25 | 824.13 | 01-SEP-00:12 | 0.26 |
October | 0.209550E+10 | 0.25 | 824.13 | 01-OCT-00:12 | 0.26 |
November | 0.197501E+10 | 0.24 | 824.13 | 01-NOV-00:20 | 0.26 |
December | 0.198576E+10 | 0.24 | 824.13 | 01-DEC-00:03 | 0.26 |
Annual Sum or Average | 0.242026E+11 | 0.24 | |||
Minimum of Months | 0.179372E+10 | 0.23 | 824.13 | 0.26 | |
Maximum of Months | 0.210619E+10 | 0.25 | 824.13 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.606639E+10 | 0.73 | 6507.04 | 20-JAN-04:01 | 1.39 |
February | 0.542457E+10 | 0.72 | 5865.51 | 03-FEB-04:01 | 1.33 |
March | 0.595609E+10 | 0.72 | 6507.04 | 07-MAR-04:01 | 1.39 |
April | 0.573145E+10 | 0.72 | 6507.04 | 07-APR-03:01 | 1.39 |
May | 0.662402E+10 | 0.78 | 6507.04 | 02-MAY-03:01 | 1.39 |
June | 0.692938E+10 | 0.81 | 6507.04 | 01-JUN-03:01 | 1.39 |
July | 0.783621E+10 | 0.85 | 6507.04 | 01-JUL-03:01 | 1.38 |
August | 0.754887E+10 | 0.83 | 6507.04 | 01-AUG-03:01 | 1.38 |
September | 0.681171E+10 | 0.80 | 6507.04 | 01-SEP-03:01 | 1.38 |
October | 0.674001E+10 | 0.78 | 6507.04 | 01-OCT-03:01 | 1.39 |
November | 0.580444E+10 | 0.73 | 6507.04 | 01-NOV-03:01 | 1.39 |
December | 0.601429E+10 | 0.72 | 6507.04 | 11-DEC-04:01 | 1.39 |
Annual Sum or Average | 0.774874E+11 | 0.77 | |||
Minimum of Months | 0.542457E+10 | 0.72 | 5865.51 | 1.33 | |
Maximum of Months | 0.783621E+10 | 0.85 | 6507.04 | 1.39 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160676E+10 | 0.48 | 1703.77 | 01-JAN-04:01 | 0.88 |
February | 0.147874E+10 | 0.49 | 1703.77 | 01-FEB-04:11 | 0.87 |
March | 0.168976E+10 | 0.50 | 1703.77 | 01-MAR-04:01 | 0.88 |
April | 0.182613E+10 | 0.54 | 1703.77 | 01-APR-03:11 | 0.87 |
May | 0.287818E+10 | 0.67 | 1703.77 | 01-MAY-03:11 | 0.87 |
June | 0.301687E+10 | 0.70 | 1703.77 | 01-JUN-03:01 | 0.87 |
July | 0.346435E+10 | 0.74 | 1703.77 | 01-JUL-03:01 | 0.87 |
August | 0.329964E+10 | 0.72 | 1703.77 | 01-AUG-03:01 | 0.87 |
September | 0.297479E+10 | 0.70 | 1703.77 | 01-SEP-03:01 | 0.87 |
October | 0.259686E+10 | 0.63 | 1703.77 | 01-OCT-03:01 | 0.87 |
November | 0.178349E+10 | 0.52 | 1703.77 | 01-NOV-03:01 | 0.87 |
December | 0.171341E+10 | 0.50 | 1703.77 | 01-DEC-04:11 | 0.88 |
Annual Sum or Average | 0.283290E+11 | 0.60 | |||
Minimum of Months | 0.147874E+10 | 0.48 | 1703.77 | 0.87 | |
Maximum of Months | 0.346435E+10 | 0.74 | 1703.77 | 0.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 49.91 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 50.76 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 50.86 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 53.89 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.63 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 53.67 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 54.35 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 53.98 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.12 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.90 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.83 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 51.19 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 49.91 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.35 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.91 | 59.42 | 7466.99 | 14190.28 | 24-JAN-19:30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 50.76 | 58.55 | 7423.12 | 14159.10 | 02-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.86 | 58.59 | 7218.62 | 13838.96 | 02-MAR-19:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.80 | 51.80 | 6754.18 | 13147.79 | 03-APR-18:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 51.93 | 51.93 | 6323.09 | 12331.87 | 01-MAY-18:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.59 | 52.59 | 5985.77 | 11542.10 | 01-JUN-18:55 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.80 | 52.80 | 5746.80 | 10955.01 | 03-JUL-18:33 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.95 | 52.95 | 5870.84 | 11201.95 | 31-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.05 | 53.05 | 6103.63 | 11820.71 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 50.77 | 50.77 | 6497.36 | 12720.78 | 31-OCT-18:33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.48 | 52.48 | 6941.94 | 13501.49 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.19 | 58.77 | 7286.91 | 14052.18 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 6630.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.91 | 50.77 | 5746.80 | 10955.01 | ||
Maximum of Months | 0.00 | 0.00 | 53.05 | 59.42 | 7466.99 | 14190.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.930305E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.978536E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124967E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.176162E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.333337E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.354054E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.407837E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.388842E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.343097E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.292112E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151843E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.118878E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.288201E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.930305E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.407837E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.410087E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.475425E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.628190E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.992774E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.200175E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208853E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.238729E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.227592E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.205157E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.166405E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.824723E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.599072E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163994E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.410087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.238729E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.606639E+10 | 0.112473E+11 | 0.717594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542457E+10 | 0.152327E+11 | 0.479468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595609E+10 | 0.231218E+11 | 0.329662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573145E+10 | 0.429602E+11 | 0.100293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.662402E+10 | 0.102281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692938E+10 | 0.109599E+12 | 45752.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783621E+10 | 0.127866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.754887E+10 | 0.121192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681171E+10 | 0.106349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674001E+10 | 0.856782E+11 | 52743835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580444E+10 | 0.339856E+11 | 0.748529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601429E+10 | 0.211668E+11 | 0.462755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774874E+11 | 0.800679E+12 | 0.207964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542457E+10 | 0.112473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.783621E+10 | 0.127866E+12 | 0.717594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160676E+10 | 0.102677E+11 | 0.117929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147874E+10 | 0.135110E+11 | 0.104816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168976E+10 | 0.191256E+11 | 0.331935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182613E+10 | 0.341706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.287818E+10 | 0.753729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.301687E+10 | 0.784241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346435E+10 | 0.898084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.329964E+10 | 0.855877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.297479E+10 | 0.775851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259686E+10 | 0.613354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178349E+10 | 0.272122E+11 | 666807.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171341E+10 | 0.179408E+11 | 0.587026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283290E+11 | 0.590342E+12 | 0.314707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147874E+10 | 0.102677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.346435E+10 | 0.898084E+11 | 0.117929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.606639E+10 | 0.00 | 0.00 | 0.00 | 0.323667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542457E+10 | 0.00 | 0.00 | 0.00 | 0.436079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595609E+10 | 0.00 | 0.00 | 0.00 | 0.654064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573145E+10 | 0.00 | 0.00 | 0.00 | 0.118848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.662402E+10 | 0.00 | 0.00 | 0.00 | 0.267097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692938E+10 | 0.00 | 0.00 | 0.00 | 0.284760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783621E+10 | 0.00 | 0.00 | 0.00 | 0.329475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.754887E+10 | 0.00 | 0.00 | 0.00 | 0.313353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681171E+10 | 0.00 | 0.00 | 0.00 | 0.274980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674001E+10 | 0.00 | 0.00 | 0.00 | 0.224711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580444E+10 | 0.00 | 0.00 | 0.00 | 0.937982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601429E+10 | 0.00 | 0.00 | 0.00 | 0.587355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774874E+11 | 0.00 | 0.00 | 0.00 | 0.210714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542457E+10 | 0.00 | 0.00 | 0.00 | 0.323667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.783621E+10 | 0.00 | 0.00 | 0.00 | 0.329475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.160676E+10 | 0.00 | 0.00 | 0.00 | 0.249411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147874E+10 | 0.00 | 0.00 | 0.00 | 0.327551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168976E+10 | 0.00 | 0.00 | 0.00 | 0.459214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182613E+10 | 0.00 | 0.00 | 0.00 | 0.810161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.287818E+10 | 0.00 | 0.00 | 0.00 | 0.171393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.301687E+10 | 0.00 | 0.00 | 0.00 | 0.178684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346435E+10 | 0.00 | 0.00 | 0.00 | 0.204085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.329964E+10 | 0.00 | 0.00 | 0.00 | 0.194596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.297479E+10 | 0.00 | 0.00 | 0.00 | 0.175409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259686E+10 | 0.00 | 0.00 | 0.00 | 0.140437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178349E+10 | 0.00 | 0.00 | 0.00 | 0.646374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171341E+10 | 0.00 | 0.00 | 0.00 | 0.427731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283290E+11 | 0.00 | 0.00 | 0.00 | 0.135665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147874E+10 | 0.00 | 0.00 | 0.00 | 0.249411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.346435E+10 | 0.00 | 0.00 | 0.00 | 0.204085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291302E+11 | 0.114894E+10 | 0.00 | 25134778.26 | 0.00 | 24583589.59 | 0.989184E+10 | 0.00 | 3.77 |
February | 0.183744E+11 | 0.174648E+10 | 0.00 | 39348822.41 | 0.00 | 0.622776E+09 | 0.116175E+11 | 0.00 | 3.87 |
March | 0.170065E+11 | 0.339957E+10 | 0.00 | 43786607.25 | 0.00 | 11407998.76 | 0.115789E+11 | 0.00 | 3.92 |
April | 0.391225E+10 | 0.850189E+10 | 0.00 | 53425945.02 | 30507740.65 | 0.00 | 0.109623E+11 | 0.00 | 4.04 |
May | 69375818.51 | 0.387691E+11 | 0.00 | 3033543.17 | 0.335189E+09 | 0.00 | 16530598.54 | 0.00 | 3.67 |
June | 51642636.88 | 0.446879E+11 | 7914.72 | 2495870.99 | 0.453421E+09 | 0.00 | 57481848.04 | 157.71 | 3.69 |
July | 7656235.45 | 0.573299E+11 | 0.00 | 2802696.90 | 0.688508E+09 | 0.00 | 12422640.37 | 0.00 | 3.72 |
August | 65042878.62 | 0.510244E+11 | 0.00 | 3002467.12 | 0.562869E+09 | 0.00 | 37327307.81 | 0.00 | 3.70 |
September | 0.116258E+09 | 0.419718E+11 | 0.00 | 4792790.03 | 0.373391E+09 | 0.00 | 0.159240E+09 | 0.00 | 3.71 |
October | 0.179952E+10 | 0.302245E+11 | 0.00 | 23766488.03 | 0.250095E+09 | 0.00 | 0.502743E+10 | 0.00 | 3.84 |
November | 0.933051E+10 | 0.726187E+10 | 0.00 | 45728218.78 | 30251452.49 | 0.00 | 0.133406E+11 | 0.00 | 4.01 |
December | 0.213633E+11 | 0.378181E+10 | 0.00 | 29959152.77 | 3824459.41 | 0.166619E+09 | 0.110001E+11 | 0.00 | 3.87 |
Annual Sum or Average | 0.101227E+12 | 0.289848E+12 | 7914.72 | 0.277277E+09 | 0.272806E+10 | 0.825386E+09 | 0.737017E+11 | 157.71 | 3.82 |
Minimum of Months | 7656235.45 | 0.114894E+10 | 0.00 | 2495870.99 | 0.00 | 0.00 | 12422640.37 | 0.00 | 3.67 |
Maximum of Months | 0.291302E+11 | 0.573299E+11 | 7914.72 | 53425945.02 | 0.688508E+09 | 0.622776E+09 | 0.133406E+11 | 157.71 | 4.04 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187602E+11 | 0.810044E+09 | 0.00 | 52552788.36 | 7464603.10 | 0.00 | 0.193939E+11 | 0.00 | 7.74 |
February | 0.110443E+11 | 0.752153E+09 | 0.00 | 71831407.18 | 67771377.43 | 2812618.26 | 0.189548E+11 | 0.00 | 7.85 |
March | 0.868148E+10 | 0.210958E+10 | 0.00 | 74959996.82 | 0.00 | 0.00 | 0.209711E+11 | 0.00 | 7.93 |
April | 0.122469E+10 | 0.478188E+10 | 0.00 | 87881025.47 | 0.00 | 0.00 | 0.152396E+11 | 0.00 | 8.26 |
May | 0.00 | 0.268315E+11 | 0.00 | 2952451.37 | 0.00 | 0.00 | 0.253210E+09 | 0.00 | 9.09 |
June | 0.00 | 0.303021E+11 | 0.00 | 2338354.32 | 0.00 | 0.00 | 0.240139E+09 | 0.00 | 9.20 |
July | 0.00 | 0.396204E+11 | 0.00 | 23952.10 | 0.00 | 0.00 | 537087.46 | 0.00 | 9.35 |
August | 0.00 | 0.355024E+11 | 0.00 | 2087222.15 | 0.00 | 0.00 | 0.157216E+09 | 0.00 | 9.27 |
September | 0.00 | 0.304309E+11 | 0.00 | 4016154.36 | 0.00 | 0.00 | 0.264754E+09 | 0.00 | 9.21 |
October | 0.520070E+09 | 0.204652E+11 | 0.00 | 41215767.45 | 0.00 | 0.00 | 0.740218E+10 | 0.00 | 8.79 |
November | 0.428232E+10 | 0.514518E+10 | 0.00 | 75027664.56 | 0.00 | 0.00 | 0.196145E+11 | 0.00 | 8.08 |
December | 0.122636E+11 | 0.288044E+10 | 0.00 | 55960737.61 | 0.00 | 0.00 | 0.197595E+11 | 0.00 | 7.90 |
Annual Sum or Average | 0.567767E+11 | 0.199632E+12 | 0.00 | 0.470848E+09 | 75235980.53 | 2812618.26 | 0.122252E+12 | 0.00 | 8.56 |
Minimum of Months | 0.00 | 0.752153E+09 | 0.00 | 23952.10 | 0.00 | 0.00 | 537087.46 | 0.00 | 7.74 |
Maximum of Months | 0.187602E+11 | 0.396204E+11 | 0.00 | 87881025.47 | 67771377.43 | 2812618.26 | 0.209711E+11 | 0.00 | 9.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.747814E+11 | 0.101781E+11 | 0.136911E+12 | 0.115075E+10 | 0.509207E+11 |
February | 0.833883E+11 | 0.771549E+10 | 0.108172E+12 | 0.154564E+10 | 0.596385E+11 |
March | 0.101713E+12 | 0.792186E+10 | 0.101803E+12 | 0.171404E+10 | 0.779408E+11 |
April | 0.117147E+12 | 0.442756E+10 | 0.448171E+11 | 0.197638E+10 | 0.123726E+12 |
May | 0.119066E+12 | -0.452357E+10 | -0.910662E+11 | 15053250.86 | 0.249082E+12 |
June | 0.118072E+12 | -0.530891E+10 | -0.105818E+12 | 24026332.23 | 0.262105E+12 |
July | 0.121810E+12 | -0.811605E+10 | -0.140072E+12 | 22970343.20 | 0.299722E+12 |
August | 0.113985E+12 | -0.729339E+10 | -0.122792E+12 | 33716875.39 | 0.285614E+12 |
September | 0.945436E+11 | -0.596239E+10 | -0.101273E+12 | 45967961.53 | 0.253691E+12 |
October | 0.978235E+11 | -0.247907E+10 | -0.413123E+11 | 0.832768E+09 | 0.207761E+12 |
November | 0.673216E+11 | 0.444768E+10 | 0.715007E+11 | 0.230106E+10 | 0.999936E+11 |
December | 0.661412E+11 | 0.783485E+10 | 0.108677E+12 | 0.165651E+10 | 0.725421E+11 |
Annual Sum or Average | 0.117579E+13 | 0.884214E+10 | -0.304532E+11 | 0.113189E+11 | 0.204274E+13 |
Minimum of Months | 0.661412E+11 | -0.811605E+10 | -0.140072E+12 | 15053250.86 | 0.509207E+11 |
Maximum of Months | 0.121810E+12 | 0.101781E+11 | 0.136911E+12 | 0.230106E+10 | 0.299722E+12 |