Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:25:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2329.88 | 4558.09 | 4558.09 |
Net Site Energy | 2329.88 | 4558.09 | 4558.09 |
Total Source Energy | 4315.79 | 8443.23 | 8443.23 |
Net Source Energy | 4315.79 | 8443.23 | 8443.23 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 608.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 127.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.52 | 392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 49.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 859.43 | 1470.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 608.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 63.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 127.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.52 | 392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 608.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 49.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 63.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.44 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 127.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.52 | 392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 49.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 494.48 | 1957.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 975.25 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1681.36 | 2876.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 494.48 | 1957.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 975.25 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1681.36 | 2876.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 859.431 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 859.431 | 100.00 |
Total On-Site and Utility Electric Sources | 859.431 | 100.00 |
Total Electricity End Uses | 859.431 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3517.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 9.5182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 10.6727 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.8331 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.8331 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.5182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 10.6727 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 9.8331 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 9.8331 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 9.8331 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-17:00 | 10-JAN-21:49 | - | - | - | - | - | - | - | - | - | - | 11-JAN-07:40 |
Heating | 0.00 | 170207.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25053.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2554.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20315.44 | 16292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6807.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4439.11 | 30647.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1606.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 60793.84 | 217146.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 170207.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25053.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2554.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19287.94 | 16292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6807.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4439.11 | 30647.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 441.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 970.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 659.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 156.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 200.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 142.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1423.36 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 403.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.16 | 425.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 155.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2721.82 | 1593.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1289.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 392.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 789.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.89 | 832.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 304.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5324.86 | 3118.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1289.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 392.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2784.61 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 789.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.89 | 832.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 304.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5324.86 | 3118.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.09 |
KITCHEN DIRECT AIR | 1.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.09 | 4.09 | 4.09 | 4.09 | 4.09 | 4.09 | 1.00 | 1.00 | 4.09 |
PSZ-AC_2:2 | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.00 | 1.000000 | 1.74 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.09 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.74 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.09 | 6994.63 |
PSZ-AC_2:2_ADDAQ FAN | 1.74 | 1865.84 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.09 | 4.09 | 4.09 | 2.70 | 79642.90 | 150789.63 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.74 | 1.74 | 1.74 | 1.15 | 38015.85 | 99014.05 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.09 | 2.05 | 2.73 | 79642.90 | 39821.45 | 0.786830 | 0.786830 |
PSZ-AC_2:2 COOLING COIL | 1.74 | 0.871848 | 1.16 | 38015.85 | 19007.92 | 0.744150 | 0.744150 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 150789.63 |
PSZ-AC_2:2 HEATING COIL | 99014.05 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 9.518 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 74.446 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 10.673 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1071.313 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3538.380 | 9.518 | 12.631 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3538.380 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1487.835 | 10.673 | 197.643 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1487.835 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7719 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1345 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2291 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.062 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.356 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.287 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.30221493E-12 | 0.42806226E-14 | -0.95155442E-13 | 0.15899766E-15 |
34 | 6 | 0.28727294E-07 | 0.21728364E-09 | 0.65803531E-08 | -0.13544055E-12 |
35 | 5 | -0.19039181E-03 | 0.18585303E-05 | -0.97925888E-04 | 0.65048812E-08 |
36 | 4 | 0.29248049 | 0.90406920E-03 | 0.99803377E-01 | -0.33617969E-04 |
37 | 3 | -7.2729408 | 0.27994057E-01 | -2.3408748 | 0.29041410E-01 |
38 | 2 | 40.892958 | 0.99469394E-01 | 15.273156 | -0.33358329 |
39 | 1 | -80.562512 | 0.44862081E-01 | -29.148912 | 1.0789757 |
40 | 0 | 46.824339 | 0.90199676E-03 | 16.291060 | |
41 | 7 | -0.31585163E-08 | -0.22597303E-14 | 0.15834007E-14 | -0.44811583E-16 |
42 | 6 | 0.38926816E-05 | 0.25726622E-08 | 0.31949392E-02 | -0.26801827E-04 |
43 | 5 | -0.27259256E-03 | 0.15209505E-05 | -0.22401268 | 0.19586932E-02 |
44 | 4 | 0.62224649E-02 | 0.69174334E-04 | 4.8343438 | -0.45311104E-01 |
45 | 3 | -0.54492574E-01 | 0.54963890E-03 | -38.048519 | 0.39895333 |
46 | 2 | 0.19328371 | 0.91376166E-03 | 116.53670 | -1.4186449 |
47 | 1 | -0.27884260 | 0.27809541E-03 | -143.93836 | 2.0495503 |
48 | 0 | 0.13591665 | 0.67534627E-05 | 60.838472 | |
49 | 7 | -0.18366387E-08 | -0.45273224E-15 | 0.66973396E-14 | -0.89481334E-16 |
50 | 6 | 0.64176182E-05 | 0.43906086E-08 | 0.31875387E-02 | -0.26739746E-04 |
51 | 5 | -0.46144041E-03 | 0.26013657E-05 | -0.22359208 | 0.19549808E-02 |
52 | 4 | 0.10613927E-01 | 0.11841222E-03 | 4.8273389 | -0.45243768E-01 |
53 | 3 | -0.93204934E-01 | 0.94170345E-03 | -38.008950 | 0.39851596 |
54 | 2 | 0.33095125 | 0.15665766E-02 | 116.45969 | -1.4176148 |
55 | 1 | -0.47767855 | 0.47741295E-03 | -143.89302 | 2.0488052 |
56 | 0 | 0.23289156 | 0.11519323E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.418_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.418_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.418_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.418_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.9412E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9362E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.8596E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7251E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6068E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6579E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1904E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1008E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.4639E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.1413E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.7726E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.3666E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.4368E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.3515E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.1278E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.1278E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6908E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6175E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.4025E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4361E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3500E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3612E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.1008E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1904E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 40905.99141 | 49087.18969 | 3.41149 | 4.09378 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 11922.07349 | 14306.48819 | 0.58428 | 1.33138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -27.60000 | 3.41898E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20540.49444 | 24648.59333 | 1.45308 | 1.74370 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 2052.84063 | 2463.40875 | 9.10188E-002 | 1.21700 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60000 | 3.41898E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 61702.95 | 4.09378 | 4.09378 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 95244.28 | 1.33138 | 1.33138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 32688.42 | 1.74370 | 1.74370 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 87062.07 | 1.21700 | 1.21700 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.09378 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.74370 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.09378 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.09378 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.09378 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.09378 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.09378 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.09378 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.74370 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.74370 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.74370 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.74370 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.74370 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.74370 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.09378 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.74370 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.09378 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.09378 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6994.63063 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.09378 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.09378 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.09378 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.70190 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.09378 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.04689 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.72919 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 79642.90000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 39821.45000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78683 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78683 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 79642.90000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 150789.62928 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 150789.62928 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.74370 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.74370 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1865.83781 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.74370 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.74370 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.74370 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.15084 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.74370 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.87185 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.16247 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38015.85000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19007.92500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74415 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74415 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38015.85000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 99014.04904 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 99014.04904 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 76677.7 | 10.37 | 10.32 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 36763.2 | 11.60 | 11.55 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_EAST_0.4 | N/A | 2.375 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_SOUTH_0.4 | N/A | 2.375 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_WEST_0.4 | N/A | 2.375 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.135 | 0.130 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.772 | 0.692 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.229 | 0.217 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.3626864320E-002 | 0.3632578335 | Pass | Pass | 6.8613465965E-002 | 0.1732860144 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1189125241 | 0.5434744844 | Pass | Pass | 2.5348776191E-002 | 8.3271426415E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2789347638 | 0.2906301449 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 949.46 | 126.48 | 2150.51 | 18.74 | 568.65 | 3813.86 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.132 | 0.135 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.692 | 0.772 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.221 | 0.229 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.418_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.375 | 0.401 | 0.442 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.418_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.375 | 0.401 | 0.442 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.418_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.375 | 0.401 | 0.442 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.375 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.375 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.5182 | 371.75 | 3538.38 | LightsWired | LTG_SCH_DINING | 92.56 | 168.00 | 63.55 | 0.0000 | Y | 42.21 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 10.6727 | 139.41 | 1487.83 | LightsWired | LTG_SCH_KITCHEN | 75.91 | 168.00 | 75.47 | 0.0000 | Y | 21.08 |
Interior Lighting Total | 9.8331 | 511.15 | 5026.21 | 63.29 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 3538.38 | 884.59 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 3538.38 | 884.59 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.52 | AstronomicalClock | - | 49.11 | 49.11 | 1.93 | |
EXTERIOR_LIGHTS_B | 3124.83 | AstronomicalClock | - | 83.57 | 73.23 | 42.95 | |
Exterior Lighting Total | 3334.35 | 44.89 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 79642.90 | 62665.42 | 16977.48 | 0.79 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38015.85 | 28289.49 | 9726.36 | 0.74 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 76677.7 | 10.37 | 10.32 | ||||
PSZ-AC_2:2 COOLING COIL | 36763.2 | 11.60 | 11.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 150789.63 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 99014.05 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.09 | 6994.63 | 1708.60 | 1.00 | 1.18 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.74 | 1865.84 | 1070.05 | 1.00 | 1.34 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 40905.99 | 49087.19 | 132.04 | 3.411 | 4.094 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.00848 | 33.24 | 0.00631 | 1.331 | 0.00 |
KITCHEN | 20540.49 | 24648.59 | 176.81 | 1.453 | 1.744 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.00887 | 31.96 | 0.00630 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 11922.07 | 14306.49 | 38.48 | 0.584 | 1.331 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00779 | -27.60 | 0.00034 | 1.331 | 0.00 |
KITCHEN | 2052.84 | 2463.41 | 17.67 | 0.091 | 1.217 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00665 | -27.60 | 0.00034 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.09 | 4.09 | 1.33 | 1.33 | 4.0938 | 4.0938 | 4.0938 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.74 | 1.74 | 1.22 | 1.22 | 1.7437 | 1.7437 | 1.7437 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 79642.900 | 62665.423 | 4.093780 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 39821.45 | 36340.10 | 2.729187 | 27.05 | 15.45 | 0.00777514 | 11.21 | 8.73 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 48.7829 | 23.99 | 0.00848326 | 39.9741 | 40887.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 150789.629 | 150789.629 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 150789.63 | 150789.63 | 4.093783 | 5.19 | 4.11 | 0.00536523 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 32.5219 | 21.00 | 0.00778630 | 44.0395 | 11920.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38015.850 | 28289.495 | 1.743700 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19007.92 | 19007.92 | 1.162467 | 31.41 | 16.26 | 0.00699172 | 11.80 | 8.98 | 0.00699172 | 33.40 | 0.00630683 | 16.37 | 104.6913 | 25.98 | 0.00887423 | 37.1090 | 19538.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 99014.049 | 99014.049 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:40:00 | 99014.05 | 99014.05 | 1.743697 | -13.66 | -13.66 | 0.00226021 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 69.7944 | 19.00 | 0.00669274 | 42.9242 | 1843.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 79642.900 | 62665.423 | 4.093780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2936 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.093783 | 4.31132618 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 39821.45 | 36340.10 | 1.0000 | 2.87421532 | 2.729187 | 27.05 | 15.45 | 0.00777514 | 47015.7 | 11.21 | 8.73 | 0.00700000 | 28915.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39821.45 | 33.40 | 0.00630683 | 16.37 | 1.33137743 | 48.7829 | 23.99 | 0.00848326 | 23.99 | 0.00848326 | 39.9741 | 40887.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 150789.629 | 150789.629 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.093783 | 4.31132618 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 150789.63 | 150789.63 | 1.0000 | 4.31132618 | 4.093783 | 5.19 | 4.11 | 0.00536523 | 18688.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 150789.63 | -27.60 | 0.00034190 | -27.60 | 1.33137743 | 32.5219 | 21.00 | 0.00778630 | 21.00 | 0.00778630 | 44.0395 | 11920.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38015.850 | 28289.495 | 1.743700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8373 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.743697 | 1.83635645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19007.92 | 19007.92 | 1.0000 | 1.22424001 | 1.162467 | 31.41 | 16.26 | 0.00699172 | 49456.5 | 11.80 | 8.98 | 0.00699172 | 29498.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19007.92 | 33.40 | 0.00630683 | 16.37 | 1.21700195 | 104.6913 | 25.94 | 0.00887423 | 25.98 | 0.00887423 | 37.1090 | 19538.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99014.049 | 99014.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.743697 | 1.83635645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:40:00 | Sensible | 99014.05 | 99014.05 | 1.0000 | 1.83635645 | 1.743697 | -13.66 | -13.66 | 0.00226021 | -8128.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99014.05 | -27.60 | 0.00034190 | -27.60 | 1.21700195 | 69.7944 | 18.56 | 0.00669274 | 19.00 | 0.00669274 | 42.9242 | 1843.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.09 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2844.83 | 5073.83 | 1366.33 |
KITCHEN | 4370.83 | 5982.33 | 3419.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4469.17 | 6808.83 | 3517.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 19.67 | 5.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 81.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 19.67 | 85.83 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.562 | 0.599 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.064 | 0.044 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.066 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.561 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 37442346.56 | 0.00 | 37442346.56 | 4958593.45 | 42400940.02 | 41986318.57 | 1451.42 | 6003.47 | 1305.11 | 228.93 |
KITCHEN | 31157339.19 | 0.00 | 31157339.19 | 218223.79 | 31375562.98 | 38379373.44 | 6585.84 | 2166.66 | 7.50 | 403.00 |
Total Facility | 68599685.76 | 0.00 | 68599685.76 | 5176817.24 | 73776503.00 | 80365692.01 | 6587.68 | 6004.47 | 1310.61 | 487.94 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.4201 | 0.0000 | 1.4201 | 0.1865 | 1.6066 | 1.3314 | 0.00 | 5886.71 | 1300.29 |
KITCHEN | 1.1750 | 0.0000 | 1.1750 | 0.0052 | 1.1802 | 1.2170 | 5060.25 | 2122.43 | 4.32 |
Total Facility | 2.5951 | 0.0000 | 2.5951 | 0.1917 | 2.7867 | 2.5484 | 5060.25 | 5887.71 | 1303.87 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 41527515.34 | 0.00 | 41527515.34 | 41986318.57 | 1451.10 | 0.10 | 7308.81 | 228.93 |
PSZ-AC_2:2 | 34556352.61 | 0.00 | 34556352.61 | 38379373.44 | 1448.65 | 0.68 | 7310.67 | 403.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.5750 | 0.0000 | 1.5750 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3032 | 0.0000 | 1.3032 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1106.88 | 313.92 | 5995.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 124.77 | 2483.72 | 4981.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.0991 | 1.7617 | 1.4769 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.3159 | 1.3409 | 1.2869 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
Electricity:Building | 519.66 | 3441.46 | 01-JAN-01:10 | 29031.14 | 02-JAN-11:10 |
Electricity:Zone:DINING | 167.32 | 983.90 | 01-JAN-01:10 | 9291.91 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 512.72 | 3305.18 | 01-JAN-01:10 | 26888.04 | 02-JAN-11:10 |
InteriorLights:Electricity | 63.29 | 467.71 | 28-MAY-05:00 | 4065.95 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 42.21 | 293.94 | 28-MAY-05:00 | 3023.33 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 63.29 | 467.71 | 28-MAY-05:00 | 4065.95 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 63.29 | 467.71 | 28-MAY-05:00 | 4065.95 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 42.21 | 293.94 | 28-MAY-05:00 | 3023.33 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 63.29 | 467.71 | 28-MAY-05:00 | 4065.95 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 352.34 | 2457.55 | 01-JAN-01:10 | 20527.60 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 21.08 | 173.76 | 01-JAN-01:10 | 1042.61 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 21.08 | 173.76 | 01-JAN-01:10 | 1042.61 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.44 | 2627.51 | 01-JAN-01:10 | 24333.76 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.33 | 2147.51 | 01-JAN-01:10 | 17341.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 49.07 | 852.60 | 24-JAN-23:30 | 3197.33 | 07-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 118.10 | 1032.99 | 28-JAN-01:10 | 6462.32 | 16-JUL-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 13.60 | 0.00 | 01-JAN-11:10 | 1510.03 | 01-SEP-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 28.53 | 765.07 | 12-DEC-06:00 | 1076.23 | 02-MAY-13:10 |
ElectricityPurchased:Facility | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
ElectricityPurchased:Plant | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
Cogeneration:ElectricityPurchased | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
General:Cogeneration:ElectricityPurchased | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
ElectricityNet:Plant | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
Cogeneration:ElectricityNet | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
General:Cogeneration:ElectricityNet | 859.43 | 6661.82 | 28-JAN-01:10 | 60793.84 | 17-JUL-18:00 |
Electricity:HVAC | 176.79 | 0.00 | 01-JAN-01:10 | 31903.24 | 17-JUL-17:30 |
Fans:Electricity | 127.35 | 0.00 | 01-JAN-01:10 | 7306.01 | 10-JAN-23:10 |
General:Fans:Electricity | 127.35 | 0.00 | 01-JAN-01:10 | 7306.01 | 10-JAN-23:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 49.44 | 0.00 | 01-JAN-00:10 | 25088.82 | 17-JUL-17:30 |
General:Cooling:Electricity | 49.44 | 0.00 | 01-JAN-00:10 | 25088.82 | 17-JUL-17:30 |
ExteriorLights:Electricity | 44.89 | 0.00 | 01-JAN-08:20 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.89 | 0.00 | 01-JAN-08:20 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.18 | 18-APR-18:30 |
Water Heater:WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.18 | 18-APR-18:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 03-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 03-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1470.45 | 2803.57 | 01-JAN-01:20 | 217146.78 | 10-JAN-21:50 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 608.01 | 0.00 | 01-JAN-01:10 | 188487.04 | 19-JAN-04:10 |
Heating:NaturalGas | 608.01 | 0.00 | 01-JAN-01:10 | 188487.04 | 19-JAN-04:10 |
General:Heating:NaturalGas | 608.01 | 0.00 | 01-JAN-01:10 | 188487.04 | 19-JAN-04:10 |
NaturalGas:Plant | 392.66 | 993.32 | 01-JAN-00:10 | 35112.15 | 15-FEB-07:20 |
WaterSystems:NaturalGas | 392.66 | 993.32 | 01-JAN-00:10 | 35112.15 | 15-FEB-07:20 |
Water Heater:WaterSystems:NaturalGas | 392.66 | 993.32 | 01-JAN-00:10 | 35112.15 | 15-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-JAN-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-JAN-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 11-JAN-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1686.20 | 2930.07 | 11-JAN-01:10 | 181459.19 | 29-JAN-05:00 |
EnergyTransfer:Building | 677.78 | 1465.04 | 11-JAN-01:10 | 58734.07 | 29-JAN-05:00 |
EnergyTransfer:Zone:KITCHEN | 411.88 | 1465.04 | 11-JAN-01:10 | 23614.91 | 25-NOV-12:00 |
Refrigeration:EnergyTransfer | 132.67 | 2620.87 | 10-JAN-23:10 | 7834.84 | 13-JUN-03:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.33 | 1310.43 | 10-JAN-23:10 | 3917.42 | 13-JUN-03:40 |
General:Refrigeration:EnergyTransfer | 66.33 | 1310.43 | 10-JAN-23:10 | 3917.42 | 13-JUN-03:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.33 | 1310.43 | 10-JAN-23:10 | 3917.42 | 13-JUN-03:40 |
EnergyTransfer:Plant | 345.95 | 1465.04 | 11-JAN-01:10 | 21338.26 | 27-FEB-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 11.95 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 54.38 | 1305.21 | 12-DEC-06:00 | 2238.70 | 02-MAY-13:10 |
EnergyTransfer:Zone:DINING | 265.90 | 0.00 | 01-JAN-01:10 | 56640.65 | 29-JAN-05:00 |
Heating:EnergyTransfer | 8.85 | 0.00 | 01-JAN-00:10 | 34207.19 | 11-JAN-04:20 |
Heating:EnergyTransfer:Zone:DINING | 8.83 | 0.00 | 01-JAN-00:10 | 34207.19 | 11-JAN-04:20 |
General:Heating:EnergyTransfer | 8.85 | 0.00 | 01-JAN-00:10 | 34207.19 | 11-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DINING | 8.83 | 0.00 | 01-JAN-00:10 | 34207.19 | 11-JAN-04:20 |
Cooling:EnergyTransfer | 602.60 | 0.00 | 01-JAN-01:10 | 48129.12 | 17-JUL-17:30 |
Cooling:EnergyTransfer:Zone:DINING | 257.07 | 0.00 | 01-JAN-01:10 | 30766.29 | 17-JUL-17:30 |
General:Cooling:EnergyTransfer | 602.60 | 0.00 | 01-JAN-01:10 | 48129.12 | 17-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:DINING | 257.07 | 0.00 | 01-JAN-01:10 | 30766.29 | 17-JUL-17:30 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1833.41 | 07-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1833.41 | 07-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 345.53 | 0.00 | 01-JAN-01:10 | 20383.68 | 25-NOV-12:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 345.53 | 0.00 | 01-JAN-01:10 | 20383.68 | 25-NOV-12:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 279.61 | 0.00 | 01-JAN-01:10 | 19198.64 | 17-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 279.61 | 0.00 | 01-JAN-01:10 | 19198.64 | 17-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19198.64 | 17-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19198.64 | 17-FEB-07:20 |
EnergyTransfer:HVAC | 662.47 | 0.00 | 01-JAN-01:10 | 150789.63 | 30-JAN-04:30 |
HeatingCoils:EnergyTransfer | 486.40 | 0.00 | 01-JAN-01:10 | 150789.63 | 30-JAN-04:30 |
CoolingCoils:EnergyTransfer | 176.07 | 0.00 | 01-JAN-00:10 | 84275.79 | 17-JUL-17:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19198.64 | 17-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19198.64 | 17-FEB-07:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 8.827 | -257.067 | 0.000 | 0.000 | 229.848 | 42.210 | 93.832 | 49.045 | 0.000 | 1.934 | 0.001 | 0.000 | -32.259 | 0.000 | -77.170 | -59.201 |
KITCHEN | 0.000 | 0.000 | 0.022 | -345.515 | 0.000 | 0.000 | 6.141 | 21.077 | 286.918 | 0.000 | 0.000 | 0.021 | 35.278 | 0.000 | 0.000 | 0.000 | -3.944 | -0.004 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.965 | 25.820 | 0.000 | 0.000 | 0.000 | -32.786 | -0.000 |
Total Facility | 0.000 | 0.000 | 8.849 | -602.581 | 0.000 | 0.000 | 235.989 | 63.288 | 380.750 | 49.045 | 0.000 | 8.921 | 61.099 | 0.000 | -32.259 | 0.000 | -113.900 | -59.205 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-SEP-03:01 | 0.00 | 0.00 | 0.00 | -77057.23 | 0.00 | 0.00 | 0.00 | 503.90 | 900.01 | 0.00 | 0.00 | 0.00 | 77081.37 | 0.00 | -1268.06 | 0.00 | -159.98 | 0.00 |
KITCHEN | 20-JUN-03:01 | 0.00 | 0.00 | 0.00 | -60161.61 | 0.00 | 0.00 | 0.00 | 173.76 | 3472.64 | 0.00 | 0.00 | 0.00 | 56672.15 | 0.00 | -0.00 | 0.00 | -156.94 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-SEP-03:01 | 0.00 | 0.00 | 0.00 | -127496.15 | 0.00 | 0.00 | 0.00 | 677.66 | 4372.65 | 0.00 | 0.00 | 434.81 | 123567.21 | 0.00 | -1268.06 | 0.00 | -288.11 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-MAR-05:01 | 0.00 | 0.00 | 95407.01 | 0.00 | 0.00 | 0.00 | 1341.90 | 671.87 | 2169.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3429.98 | 0.00 | -253.78 | -95906.91 |
KITCHEN | 07-JAN-05:02 | 0.00 | 0.00 | 16480.07 | 0.00 | 0.00 | 0.00 | 0.00 | 173.76 | 6912.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -172.13 | -23394.43 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAR-05:01 | -45986.34 | 45986.34 | 95407.01 | -45986.34 | 0.00 | 0.00 | 1370.01 | 903.55 | 9082.62 | 0.00 | 0.00 | 558.84 | 0.00 | 0.00 | -3429.98 | 0.00 | -411.09 | -57494.62 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.0938 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.0938 | 0.3252 | 1.0000 | Not calculated | 1.3314 | 0.3252 | ||
PSZ-AC_2:2 | 1.7437 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.7437 | 0.1047 | 1.0000 | Not calculated | 0.1826 | 0.1047 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.0938 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.0938 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3252 | ||
PSZ-AC_2:2 | 1.7437 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.7437 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1047 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.0938 | 4.0938 | 4.0938 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7437 | 1.7437 | 1.7437 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.0938 | 4.0938 | 4.0938 | 4.0938 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.7437 | 1.7437 | 1.7437 | 1.7437 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.0938 | 4.0938 | 4.0938 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7437 | 1.7437 | 1.7437 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.0938 | 4.0938 | 4.0938 | 4.0938 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.7437 | 1.7437 | 1.7437 | 1.7437 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 608.01 | 188487.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 49.44 | 25088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 63.29 | 4065.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.89 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 127.35 | 7306.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.52 | 4742.18 | 392.66 | 35112.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.60 | 1510.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.53 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 498.50 | 859.43 |
Natural Gas | 469.79 | 1470.45 |
Additional | 0.00 | 0.00 |
Total | 968.29 | 2329.88 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 123.81 |
Space Heating | 0.00 |
Space Cooling | 96.72 |
Fans (All) | 249.15 |
Service Water Heating | 147.74 |
Receptacle Equipment | 879.26 |
Miscellaneous (All) | 1681.36 |
Subtotal | 1681.36 |
Natural Gas [MJ/m2] | |
Space Heating | 1189.48 |
Service Water Heating | 768.18 |
Miscellaneous (All) | 2876.73 |
Subtotal | 2876.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.72 |
Space Heating | 26.10 |
Space Cooling | 2.12 |
Fans (All) | 5.47 |
Service Water Heating | 20.09 |
Receptacle Equipment | 39.45 |
Miscellaneous | 4.05 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4826. | 8760. |
LTG_SCH_KITCHEN | 3958. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8322.67 | 437.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 7485.83 | 468.50 | 388.50 | 408.17 | 9.00 |
Min | 7485.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 468.50 | 388.50 | 408.17 | 9.00 |
Average | 8189.50 | 301.94 | 129.50 | 136.06 | 3.00 |
Sum | 24568.50 | 905.83 | 388.50 | 408.17 | 9.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8141.67 | 618.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 7665.33 | 603.17 | 203.50 | 168.33 | 119.67 |
Min | 7665.33 | 10.83 | 0.00 | 0.00 | 0.00 |
Max | 8749.17 | 618.33 | 203.50 | 168.33 | 119.67 |
Average | 8185.39 | 410.78 | 67.83 | 56.11 | 39.89 |
Sum | 24556.17 | 1232.33 | 203.50 | 168.33 | 119.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 823797.33 | 424.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 18419.83 | 813.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823797.33 | 813.17 | 0.00 | 0.00 | 0.00 |
Average | 280739.06 | 412.61 | 0.00 | 0.00 | 0.00 |
Sum | 842217.17 | 1237.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:25:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.922950E+10 | 66046.73 | 11-JAN-00:01 | -31.6 | -31.8 | 0.120015E+11 | 11346.38 | 14-JAN-19:00 | 9.40 | 3.77 |
February | 0.122944E+11 | 52422.02 | 04-FEB-00:01 | -21.0 | -21.3 | 0.109962E+11 | 12937.53 | 27-FEB-12:00 | 17.20 | 6.49 |
March | 0.162437E+11 | 55105.23 | 05-MAR-00:01 | -23.1 | -23.6 | 0.122309E+11 | 12614.46 | 14-MAR-11:00 | 14.40 | 6.37 |
April | 0.195261E+11 | 31103.09 | 28-APR-23:01 | -4.6 | -6.2 | 0.125454E+11 | 14048.16 | 22-APR-18:10 | -4.6 | -6.2 |
May | 0.230853E+11 | 55245.42 | 20-MAY-03:01 | 14.22 | 9.93 | 0.137116E+11 | 14050.88 | 20-MAY-18:00 | 22.80 | 13.54 |
June | 0.282941E+11 | 68775.79 | 25-JUN-03:01 | 9.53 | 5.82 | 0.144911E+11 | 14051.43 | 03-JUN-18:00 | 9.53 | 5.82 |
July | 0.335952E+11 | 74863.63 | 15-JUL-03:01 | 15.22 | 10.41 | 0.151608E+11 | 14051.14 | 01-JUL-18:10 | 15.22 | 10.41 |
August | 0.327226E+11 | 76568.82 | 09-AUG-03:01 | 17.33 | 11.47 | 0.152065E+11 | 14050.65 | 19-AUG-18:00 | 16.10 | 11.53 |
September | 0.279216E+11 | 77073.64 | 03-SEP-03:01 | 15.03 | 8.71 | 0.139595E+11 | 14050.54 | 23-SEP-18:40 | 16.50 | 9.82 |
October | 0.243086E+11 | 28341.26 | 21-OCT-04:01 | -1.0 | -1.9 | 0.133039E+11 | 14046.46 | 28-OCT-18:30 | 13.60 | 6.97 |
November | 0.177899E+11 | 44693.15 | 27-NOV-00:01 | -15.1 | -15.9 | 0.120381E+11 | 14046.51 | 04-NOV-18:10 | -15.1 | -15.9 |
December | 0.120583E+11 | 55737.14 | 29-DEC-00:01 | -23.6 | -23.9 | 0.120280E+11 | 11920.22 | 06-DEC-12:00 | -23.6 | -23.9 |
Annual Sum or Average | 0.257069E+12 | 0.157673E+12 | ||||||||
Minimum of Months | 0.922950E+10 | 28341.26 | -31.6 | -31.8 | 0.109962E+11 | 11346.38 | -23.6 | -23.9 | ||
Maximum of Months | 0.335952E+11 | 77073.64 | 17.33 | 11.47 | 0.152065E+11 | 14051.43 | 22.80 | 13.54 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264851E+11 | 58535.55 | 27-JAN-05:01 | -27.8 | -28.2 | 0.103909E+11 | 6843.49 | 14-JAN-11:00 | -27.8 | -28.2 |
February | 0.248665E+11 | 55121.87 | 01-FEB-05:01 | -25.0 | -25.2 | 0.939691E+10 | 6927.84 | 27-FEB-11:00 | 16.10 | 6.08 |
March | 0.282352E+11 | 48459.38 | 05-MAR-05:01 | -20.3 | -21.0 | 0.104048E+11 | 6880.13 | 14-MAR-10:00 | 12.80 | 5.58 |
April | 0.277115E+11 | 47549.06 | 08-APR-03:01 | 8.30 | 3.71 | 0.101200E+11 | 6930.38 | 07-APR-10:09 | 8.30 | 3.71 |
May | 0.291584E+11 | 57540.39 | 31-MAY-03:01 | 8.72 | 5.88 | 0.105013E+11 | 6930.42 | 19-MAY-10:20 | 8.72 | 5.88 |
June | 0.293785E+11 | 60239.09 | 20-JUN-03:01 | 7.62 | 4.76 | 0.102316E+11 | 6930.45 | 06-JUN-10:09 | 7.62 | 4.76 |
July | 0.313319E+11 | 53901.90 | 12-JUL-03:01 | 10.27 | 5.20 | 0.105866E+11 | 6930.46 | 07-JUL-10:00 | 10.27 | 5.20 |
August | 0.312191E+11 | 58690.47 | 03-AUG-03:11 | 8.70 | 5.70 | 0.105862E+11 | 6930.42 | 23-AUG-10:50 | 18.72 | 10.87 |
September | 0.299623E+11 | 59125.91 | 24-SEP-03:01 | 7.02 | 5.27 | 0.102034E+11 | 6930.42 | 07-SEP-10:30 | 7.02 | 5.27 |
October | 0.306864E+11 | 58322.24 | 20-OCT-03:01 | 6.73 | 2.77 | 0.104817E+11 | 6930.39 | 16-OCT-10:09 | 6.73 | 2.77 |
November | 0.285228E+11 | 46219.20 | 05-NOV-03:01 | 8.22 | 3.39 | 0.100923E+11 | 6922.77 | 17-NOV-11:00 | 14.60 | 6.57 |
December | 0.279703E+11 | 56490.37 | 29-DEC-05:01 | -25.0 | -25.3 | 0.103953E+11 | 6886.42 | 06-DEC-11:00 | -25.0 | -25.3 |
Annual Sum or Average | 0.345528E+12 | 0.123391E+12 | ||||||||
Minimum of Months | 0.248665E+11 | 46219.20 | -27.8 | -28.2 | 0.939691E+10 | 6843.49 | -27.8 | -28.2 | ||
Maximum of Months | 0.313319E+11 | 60239.09 | 10.27 | 5.88 | 0.105866E+11 | 6930.46 | 18.72 | 10.87 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.9 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 | -4.1 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 | 0.55 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 | 13.32 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 | 11.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 | 11.59 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 | 6.94 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 | 1.54 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.00 | 0.00 | -12.4 | -13.9 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.00 | 0.00 | 19.45 | 13.32 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440877E+10 | 90516.14 | 09-JAN-04:51 | -27.2 |
February | 0.136346E+10 | 86890.26 | 01-FEB-04:01 | -25.0 |
March | 0.773108E+09 | 95404.93 | 06-MAR-05:01 | -18.4 |
April | 0.137440E+09 | 41095.99 | 29-APR-03:02 | -6.9 |
May | 73881356.30 | 36906.92 | 10-MAY-04:04 | -0.5 |
June | 3026682.52 | 9099.44 | 15-JUN-04:03 | 0.97 |
July | 5911887.37 | 18071.34 | 26-JUL-03:50 | 20.82 |
August | 6488879.47 | 17664.22 | 07-AUG-03:50 | 20.60 |
September | 3443499.87 | 11532.53 | 04-SEP-03:47 | 21.10 |
October | 15470656.73 | 14085.34 | 11-OCT-04:01 | -0.1 |
November | 0.277866E+09 | 58179.90 | 27-NOV-09:48 | -11.1 |
December | 0.175778E+10 | 87426.90 | 31-DEC-04:01 | -24.9 |
Annual Sum or Average | 0.882664E+10 | |||
Minimum of Months | 3026682.52 | 9099.44 | -27.2 | |
Maximum of Months | 0.440877E+10 | 95404.93 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8788709.83 | 16500.69 | 07-JAN-05:02 | -21.6 |
February | 3292011.32 | 12591.62 | 04-FEB-05:02 | -20.4 |
March | 3311732.38 | 14193.91 | 05-MAR-05:02 | -20.3 |
April | 613790.65 | 9158.43 | 29-APR-04:03 | -7.8 |
May | 85236.92 | 515.62 | 06-MAY-04:04 | -0.8 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 167378.51 | 2358.85 | 21-OCT-04:04 | -1.0 |
November | 1400719.55 | 9887.36 | 12-NOV-05:03 | -10.6 |
December | 4258342.40 | 10614.36 | 31-DEC-05:02 | -24.7 |
Annual Sum or Average | 21917921.57 | |||
Minimum of Months | 0.00 | 0.00 | -24.7 | |
Maximum of Months | 8788709.83 | 16500.69 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.401962E+10 | 3023.33 | 02-JAN-16:30 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.342931E+10 | 3023.33 | 01-FEB-17:19 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.365028E+10 | 3023.33 | 01-MAR-18:10 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.331585E+10 | 3023.33 | 01-APR-18:19 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.328349E+10 | 3023.33 | 01-MAY-19:30 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.306764E+10 | 3023.33 | 01-JUN-19:49 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.322794E+10 | 3023.33 | 01-JUL-20:19 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.334083E+10 | 3023.33 | 01-AUG-19:30 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.338937E+10 | 3023.33 | 01-SEP-19:10 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.367610E+10 | 3023.33 | 02-OCT-17:49 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.378197E+10 | 3023.33 | 01-NOV-17:10 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.402790E+10 | 3023.33 | 01-DEC-16:40 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.422103E+11 | 0.125110E+12 | ||||
Minimum of Months | 0.306764E+10 | 3023.33 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.402790E+10 | 3023.33 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.178099E+10 | 1042.61 | 02-JAN-10:09 | 0.275454E+11 | 17341.88 | 01-JAN-11:09 |
February | 0.161313E+10 | 1042.61 | 01-FEB-10:09 | 0.248798E+11 | 17341.88 | 01-FEB-11:09 |
March | 0.180935E+10 | 1042.61 | 01-MAR-10:09 | 0.275456E+11 | 17341.88 | 01-MAR-11:09 |
April | 0.173053E+10 | 1042.61 | 01-APR-16:10 | 0.266569E+11 | 17341.88 | 01-APR-10:09 |
May | 0.179517E+10 | 1042.61 | 01-MAY-09:09 | 0.275455E+11 | 17341.88 | 01-MAY-10:09 |
June | 0.174888E+10 | 1042.61 | 01-JUN-09:09 | 0.266570E+11 | 17341.88 | 01-JUN-10:09 |
July | 0.177703E+10 | 1042.61 | 01-JUL-16:10 | 0.275454E+11 | 17341.88 | 01-JUL-10:09 |
August | 0.180935E+10 | 1042.61 | 01-AUG-09:09 | 0.275456E+11 | 17341.88 | 01-AUG-10:09 |
September | 0.173094E+10 | 1042.61 | 01-SEP-09:09 | 0.266569E+11 | 17341.88 | 01-SEP-10:09 |
October | 0.178078E+10 | 1042.61 | 02-OCT-09:09 | 0.275454E+11 | 17341.88 | 01-OCT-10:09 |
November | 0.172406E+10 | 1042.61 | 01-NOV-09:09 | 0.266568E+11 | 17341.88 | 01-NOV-10:09 |
December | 0.177723E+10 | 1042.61 | 01-DEC-10:09 | 0.275454E+11 | 17341.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.210774E+11 | 0.324326E+12 | ||||
Minimum of Months | 0.161313E+10 | 1042.61 | 0.248798E+11 | 17341.88 | ||
Maximum of Months | 0.180935E+10 | 1042.61 | 0.275456E+11 | 17341.88 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.401962E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140945E+11 |
February | 0.272721E+11 | 0.342931E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967947E+10 |
March | 0.305458E+11 | 0.365028E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903405E+10 |
April | 0.292871E+11 | 0.331585E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592142E+10 |
May | 0.303219E+11 | 0.328349E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29036689.67 | 0.481205E+10 |
June | 0.295292E+11 | 0.306764E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268547E+09 | 0.238916E+10 |
July | 0.300798E+11 | 0.322794E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805789E+09 | 0.121952E+10 |
August | 0.305458E+11 | 0.334083E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606273E+09 | 0.173846E+10 |
September | 0.292871E+11 | 0.338937E+10 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222986E+09 | 0.332676E+10 |
October | 0.300980E+11 | 0.367610E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1380901.21 | 0.558629E+10 |
November | 0.290996E+11 | 0.378197E+10 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787503E+10 |
December | 0.300798E+11 | 0.402790E+10 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114937E+11 |
Annual Sum or Average | 0.356244E+12 | 0.422103E+11 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193401E+10 | 0.771704E+11 |
Minimum of Months | 0.272721E+11 | 0.306764E+10 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121952E+10 |
Maximum of Months | 0.305458E+11 | 0.402790E+10 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805789E+09 | 0.140945E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.178099E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601288E+09 |
February | 0.732850E+09 | 0.161313E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456870E+09 |
March | 0.820818E+09 | 0.180935E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407957E+09 |
April | 0.786997E+09 | 0.173053E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285852E+09 |
May | 0.814802E+09 | 0.179517E+10 | 0.225868E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 331284.34 | 0.299076E+09 |
June | 0.793501E+09 | 0.174888E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2723514.50 | 0.183513E+09 |
July | 0.808298E+09 | 0.177703E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8080270.66 | 0.125129E+09 |
August | 0.820818E+09 | 0.180935E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 7281537.93 | 0.141701E+09 |
September | 0.786997E+09 | 0.173094E+10 | 0.218582E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 3077039.21 | 0.233189E+09 |
October | 0.808786E+09 | 0.178078E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301811E+09 |
November | 0.781956E+09 | 0.172406E+10 | 0.218581E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415635E+09 |
December | 0.808298E+09 | 0.177723E+10 | 0.225867E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491483E+09 |
Annual Sum or Average | 0.957291E+10 | 0.210774E+11 | 0.265941E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 21493646.64 | 0.394350E+10 |
Minimum of Months | 0.732850E+09 | 0.161313E+10 | 0.204009E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125129E+09 |
Maximum of Months | 0.820818E+09 | 0.180935E+10 | 0.225869E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8080270.66 | 0.601288E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675243E+09 | 0.128942E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528232E+09 | 0.160454E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645453E+09 | 0.262943E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529386E+09 | 0.310500E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396935E+09 | 0.421263E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342067E+09 | 0.476102E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483046E+09 | 0.486528E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562438E+09 | 0.403116E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574161E+09 | 0.254263E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730121E+09 | 0.177813E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717405E+09 | 0.111791E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780878E+09 | 0.848649E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696537E+10 | 0.327858E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342067E+09 | 0.848649E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780878E+09 | 0.486528E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3023.33 | 02-JAN-16:30 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21479.95 | 10-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 3023.33 | 01-FEB-17:19 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 18207.42 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 3023.33 | 01-MAR-18:10 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 17522.82 | 04-MAR-19:55 |
April | 30255.31 | 01-APR-18:10 | 3023.33 | 01-APR-18:19 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 9817.74 | 28-APR-19:53 |
May | 30255.31 | 06-MAY-18:10 | 3023.33 | 01-MAY-19:30 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.65 | 20-MAY-17:10 | 8202.69 | 22-MAY-19:00 |
June | 30255.31 | 03-JUN-18:10 | 3023.33 | 01-JUN-19:49 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2471.18 | 29-JUN-13:00 | 5704.17 | 16-JUN-11:10 |
July | 30255.31 | 01-JUL-18:10 | 3023.33 | 01-JUL-20:19 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.75 | 17-JUL-17:03 | 3613.12 | 07-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 3023.33 | 01-AUG-19:30 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3721.17 | 05-AUG-18:03 | 5015.96 | 17-AUG-12:00 |
September | 30255.31 | 02-SEP-18:10 | 3023.33 | 01-SEP-19:10 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2955.18 | 02-SEP-17:03 | 6702.81 | 18-SEP-20:00 |
October | 30255.31 | 07-OCT-18:10 | 3023.33 | 02-OCT-17:49 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.49 | 18-OCT-14:00 | 8281.39 | 31-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 3023.33 | 01-NOV-17:10 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 12482.73 | 26-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 3023.33 | 01-DEC-16:40 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 17634.83 | 29-DEC-18:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3023.33 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3613.12 | |||||
Maximum of Months | 30255.31 | 3023.33 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.75 | 21479.95 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1042.61 | 02-JAN-10:09 | 14079.00 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1088.73 | 06-JAN-00:10 |
February | 813.01 | 04-FEB-19:10 | 1042.61 | 01-FEB-10:09 | 14079.00 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1031.75 | 17-FEB-04:10 |
March | 813.01 | 04-MAR-19:10 | 1042.61 | 01-MAR-10:09 | 14079.00 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1178.57 | 17-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 1042.61 | 01-APR-16:10 | 14079.00 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 852.65 | 27-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 1042.61 | 01-MAY-09:09 | 14079.00 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 22.37 | 20-MAY-15:58 | 1721.34 | 22-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 1042.61 | 01-JUN-09:09 | 14079.00 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 53.08 | 29-JUN-15:00 | 816.44 | 14-JUN-02:00 |
July | 813.01 | 01-JUL-18:10 | 1042.61 | 01-JUL-16:10 | 14079.00 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 57.55 | 25-JUL-14:55 | 454.41 | 05-JUL-01:00 |
August | 813.01 | 05-AUG-18:10 | 1042.61 | 01-AUG-09:09 | 14079.00 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 52.87 | 11-AUG-14:00 | 665.86 | 23-AUG-03:00 |
September | 813.01 | 02-SEP-18:10 | 1042.61 | 01-SEP-09:09 | 14079.00 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 53.80 | 02-SEP-13:55 | 1018.49 | 12-SEP-03:00 |
October | 813.01 | 07-OCT-18:10 | 1042.61 | 02-OCT-09:09 | 14079.00 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 707.08 | 31-OCT-03:40 |
November | 813.01 | 04-NOV-18:10 | 1042.61 | 01-NOV-09:09 | 14079.00 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 990.71 | 28-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 1042.61 | 01-DEC-10:09 | 14079.00 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1643.98 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1042.61 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 454.41 | ||||||
Maximum of Months | 813.01 | 1042.61 | 14079.00 | 7874.59 | 0.00 | 0.00 | 0.00 | 57.55 | 1721.34 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3394.07 | 11-JAN-08:31 | 5670.21 | 29-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.41 | 05-FEB-23:53 | 5210.61 | 23-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1896.01 | 01-MAR-07:00 | 6029.03 | 07-MAR-14:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1413.88 | 11-APR-06:53 | 7024.53 | 22-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.37 | 13-MAY-03:53 | 8062.41 | 09-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.24 | 17-JUN-05:53 | 7065.85 | 03-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1506.70 | 03-JUL-14:40 | 7934.84 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.45 | 03-AUG-04:40 | 6920.75 | 03-AUG-12:30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1770.71 | 02-SEP-03:51 | 6094.84 | 17-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1505.19 | 27-OCT-06:55 | 4507.82 | 06-OCT-12:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.10 | 21-NOV-08:15 | 3974.86 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1650.49 | 29-DEC-06:00 | 4167.45 | 29-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.24 | 3974.86 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3394.07 | 8062.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 66046.73 | 11-JAN-00:01 | 16808.50 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.72 |
February | 52422.02 | 04-FEB-00:01 | 16808.50 | 6718.68 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.10 |
March | 55105.23 | 05-MAR-00:01 | 16808.50 | 6718.68 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997.87 |
April | 31103.09 | 28-APR-23:01 | 16808.50 | 6718.68 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.78 |
May | 55245.42 | 20-MAY-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.08 |
June | 68775.79 | 25-JUN-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.36 |
July | 74863.63 | 15-JUL-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 |
August | 76568.82 | 09-AUG-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 |
September | 77073.64 | 03-SEP-03:01 | 0.00 | 5039.01 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.98 |
October | 28341.26 | 21-OCT-04:01 | 0.00 | 5039.01 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.16 |
November | 44693.15 | 27-NOV-00:01 | 16808.50 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.29 |
December | 55737.14 | 29-DEC-00:01 | 16808.50 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28341.26 | 0.00 | 5039.01 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | |
Maximum of Months | 77073.64 | 16808.50 | 6718.68 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 58535.55 | 27-JAN-05:01 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 160.58 |
February | 55121.87 | 01-FEB-05:01 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 |
March | 48459.38 | 05-MAR-05:01 | 0.00 | 1563.88 | 57631.93 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 60.38 |
April | 47549.06 | 08-APR-03:01 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 145.14 |
May | 57540.39 | 31-MAY-03:01 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 221.67 |
June | 60239.09 | 20-JUN-03:01 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 156.94 |
July | 53901.90 | 12-JUL-03:01 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 132.20 |
August | 58690.47 | 03-AUG-03:11 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59125.91 | 24-SEP-03:01 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 253.35 |
October | 58322.24 | 20-OCT-03:01 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 216.43 |
November | 46219.20 | 05-NOV-03:01 | 0.00 | 1737.64 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 212.42 |
December | 56490.37 | 29-DEC-05:01 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 46219.20 | 0.00 | 1563.88 | 32675.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60239.09 | 451.67 | 2316.86 | 64281.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 253.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.49 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.95 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.72 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.19 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.33 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.78 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.13 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.93 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.32 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.89 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.60 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.60 | 571.95 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.719797E+11 | 40522.66 | 10-JAN-17:10 | 0.242192E+12 | 217146.78 | 10-JAN-21:49 |
February | 0.635485E+11 | 40025.47 | 09-FEB-17:00 | 0.165990E+12 | 194005.98 | 03-FEB-04:19 |
March | 0.691978E+11 | 39796.74 | 04-MAR-11:09 | 0.157116E+12 | 194005.98 | 05-MAR-04:10 |
April | 0.658643E+11 | 41183.42 | 07-APR-18:00 | 0.106192E+12 | 108324.11 | 28-APR-06:19 |
May | 0.697065E+11 | 46231.93 | 20-MAY-16:10 | 0.948719E+11 | 100308.46 | 08-MAY-06:30 |
June | 0.732923E+11 | 52368.54 | 20-JUN-17:30 | 0.720001E+11 | 67705.17 | 16-JUN-06:00 |
July | 0.832148E+11 | 60793.84 | 17-JUL-17:00 | 0.703161E+11 | 46286.72 | 03-JUL-18:00 |
August | 0.806277E+11 | 55585.04 | 05-AUG-17:00 | 0.702893E+11 | 44581.97 | 01-AUG-18:30 |
September | 0.730767E+11 | 54812.59 | 02-SEP-17:19 | 0.737286E+11 | 71614.40 | 19-SEP-06:49 |
October | 0.697441E+11 | 44264.22 | 18-OCT-17:30 | 0.918474E+11 | 105871.83 | 10-OCT-06:00 |
November | 0.678006E+11 | 39258.23 | 27-NOV-17:10 | 0.129860E+12 | 194005.98 | 27-NOV-04:19 |
December | 0.713781E+11 | 40253.29 | 28-DEC-17:00 | 0.196048E+12 | 199033.71 | 29-DEC-08:50 |
Annual Sum or Average | 0.859431E+12 | 0.147045E+13 | ||||
Minimum of Months | 0.635485E+11 | 39258.23 | 0.702893E+11 | 44581.97 | ||
Maximum of Months | 0.832148E+11 | 60793.84 | 0.242192E+12 | 217146.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.580061E+10 | 0.503372E+10 | 0.381711E+11 | 0.00 | 0.126917E+11 | 37879553.69 | 0.00 | 593671.71 | 0.00 | 0.00 | 0.00 | 0.639856E+10 | 0.00 |
February | 0.504244E+10 | 0.410936E+10 | 0.344772E+11 | 0.00 | 0.105551E+11 | 34213790.43 | 0.00 | 14065284.26 | 0.00 | 0.00 | 0.00 | 0.578990E+10 | 0.00 |
March | 0.545963E+10 | 0.393739E+10 | 0.381714E+11 | 0.00 | 0.112139E+11 | 37879553.69 | 0.00 | 836974.11 | 0.00 | 0.00 | 0.00 | 0.646603E+10 | 0.00 |
April | 0.504638E+10 | 0.319180E+10 | 0.369399E+11 | 0.00 | 0.100974E+11 | 36657632.61 | 0.00 | 0.397497E+09 | 0.00 | 0.00 | 0.00 | 0.620609E+10 | 0.00 |
May | 0.507865E+10 | 0.277173E+10 | 0.381712E+11 | 0.00 | 0.102265E+11 | 37879553.69 | 0.00 | 0.276375E+10 | 0.00 | 0.00 | 0.00 | 0.642444E+10 | 0.00 |
June | 0.481652E+10 | 0.243549E+10 | 0.369400E+11 | 0.00 | 0.970181E+10 | 36657632.61 | 0.00 | 0.878855E+10 | 0.00 | 0.00 | 0.00 | 0.623956E+10 | 0.00 |
July | 0.500497E+10 | 0.261594E+10 | 0.381711E+11 | 0.00 | 0.102427E+11 | 37879553.69 | 0.00 | 0.162138E+11 | 0.00 | 0.00 | 0.00 | 0.637290E+10 | 0.00 |
August | 0.515018E+10 | 0.305112E+10 | 0.381714E+11 | 0.00 | 0.101605E+11 | 37879553.69 | 0.00 | 0.130727E+11 | 0.00 | 0.00 | 0.00 | 0.645166E+10 | 0.00 |
September | 0.512031E+10 | 0.353990E+10 | 0.369399E+11 | 0.00 | 0.979846E+10 | 36657632.61 | 0.00 | 0.717868E+10 | 0.00 | 0.00 | 0.00 | 0.619970E+10 | 0.00 |
October | 0.545688E+10 | 0.429350E+10 | 0.381711E+11 | 0.00 | 0.102197E+11 | 37879553.69 | 0.00 | 0.995210E+09 | 0.00 | 0.00 | 0.00 | 0.638908E+10 | 0.00 |
November | 0.550603E+10 | 0.471426E+10 | 0.369398E+11 | 0.00 | 0.105403E+11 | 36657632.61 | 0.00 | 10823031.00 | 0.00 | 0.00 | 0.00 | 0.618905E+10 | 0.00 |
December | 0.580513E+10 | 0.519177E+10 | 0.381711E+11 | 0.00 | 0.119067E+11 | 37879553.69 | 0.00 | 806339.10 | 0.00 | 0.00 | 0.00 | 0.638984E+10 | 0.00 |
Annual Sum or Average | 0.632877E+11 | 0.448860E+11 | 0.449435E+12 | 0.00 | 0.127355E+12 | 0.446001E+09 | 0.00 | 0.494373E+11 | 0.00 | 0.00 | 0.00 | 0.755168E+11 | 0.00 |
Minimum of Months | 0.481652E+10 | 0.243549E+10 | 0.344772E+11 | 0.00 | 0.970181E+10 | 34213790.43 | 0.00 | 593671.71 | 0.00 | 0.00 | 0.00 | 0.578990E+10 | 0.00 |
Maximum of Months | 0.580513E+10 | 0.519177E+10 | 0.381714E+11 | 0.00 | 0.126917E+11 | 37879553.69 | 0.00 | 0.162138E+11 | 0.00 | 0.00 | 0.00 | 0.646603E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.165959E+12 | 0.00 | 0.363331E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.965718E+11 | 0.00 | 0.333797E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.803069E+11 | 0.00 | 0.369091E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.333192E+11 | 0.00 | 0.342599E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.212828E+11 | 0.00 | 0.336893E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.252086E+10 | 0.00 | 0.308666E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.271461E+09 | 0.00 | 0.301449E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.523022E+09 | 0.00 | 0.298666E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.602612E+10 | 0.00 | 0.290899E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.206948E+11 | 0.00 | 0.312529E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.592536E+11 | 0.00 | 0.319942E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.121275E+12 | 0.00 | 0.348731E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.608005E+12 | 0.00 | 0.392659E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.271461E+09 | 0.00 | 0.290899E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.165959E+12 | 0.00 | 0.369091E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4065.95 | 02-JAN-16:30 | 3334.35 | 01-JAN-00:10 | 24333.76 | 01-JAN-11:09 | 0.00 | 7306.01 | 10-JAN-23:10 | 17.86 | 03-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4065.95 | 01-FEB-17:19 | 3334.35 | 01-FEB-00:10 | 24333.76 | 01-FEB-11:09 | 0.00 | 6994.63 | 01-FEB-04:19 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 4065.95 | 01-MAR-18:10 | 3334.35 | 01-MAR-00:10 | 24333.76 | 01-MAR-11:09 | 0.00 | 6994.63 | 04-MAR-04:10 | 17.86 | 02-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 4065.95 | 01-APR-18:19 | 3334.35 | 01-APR-05:10 | 24333.76 | 01-APR-10:09 | 0.00 | 5767.69 | 29-APR-05:10 | 17.86 | 13-APR-08:39 | 0.00 | 01-APR-00:10 |
May | 4065.95 | 01-MAY-19:30 | 3334.35 | 01-MAY-05:10 | 24333.76 | 01-MAY-10:09 | 0.00 | 5452.45 | 08-MAY-05:10 | 17.86 | 03-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 4065.95 | 01-JUN-19:49 | 3334.35 | 01-JUN-20:10 | 24333.76 | 01-JUN-10:09 | 0.00 | 5345.84 | 20-JUN-17:30 | 17.86 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 4065.95 | 01-JUL-20:19 | 3334.35 | 01-JUL-20:30 | 24333.76 | 01-JUL-10:09 | 0.00 | 6814.67 | 17-JUL-17:40 | 17.86 | 03-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 4065.95 | 01-AUG-19:30 | 3334.35 | 01-AUG-19:00 | 24333.76 | 01-AUG-10:09 | 0.00 | 6068.61 | 05-AUG-18:10 | 17.86 | 22-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 4065.95 | 01-SEP-19:10 | 3334.35 | 01-SEP-05:10 | 24333.76 | 01-SEP-10:09 | 0.00 | 5657.79 | 02-SEP-17:10 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 4065.95 | 02-OCT-17:49 | 3334.35 | 01-OCT-05:10 | 24333.76 | 01-OCT-10:09 | 0.00 | 5579.54 | 10-OCT-05:10 | 17.86 | 03-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 4065.95 | 01-NOV-17:10 | 3334.35 | 01-NOV-05:10 | 24333.76 | 01-NOV-10:09 | 0.00 | 6994.63 | 27-NOV-04:19 | 17.86 | 07-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 4065.95 | 01-DEC-16:40 | 3334.35 | 01-DEC-00:10 | 24333.76 | 01-DEC-11:09 | 0.00 | 7048.25 | 31-DEC-07:10 | 17.86 | 02-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4065.95 | 3334.35 | 24333.76 | 0.00 | 5345.84 | 17.86 | 0.00 | ||||||
Maximum of Months | 4065.95 | 3334.35 | 24333.76 | 0.00 | 7306.01 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 274.69 | 13-JAN-04:19 | 0.00 | 0.00 | 0.00 | 4741.45 | 25-JAN-19:19 | 0.00 |
February | 2055.26 | 27-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.75 | 24-FEB-07:49 | 0.00 |
March | 284.19 | 14-MAR-03:20 | 0.00 | 0.00 | 0.00 | 4741.77 | 16-MAR-18:19 | 0.00 |
April | 6888.79 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 4742.18 | 18-APR-18:30 | 0.00 |
May | 12818.79 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 4741.80 | 11-MAY-06:19 | 0.00 |
June | 18261.15 | 20-JUN-17:30 | 0.00 | 0.00 | 0.00 | 4741.14 | 15-JUN-06:49 | 0.00 |
July | 25088.82 | 17-JUL-17:30 | 0.00 | 0.00 | 0.00 | 4739.30 | 10-JUL-06:19 | 0.00 |
August | 21883.14 | 05-AUG-18:10 | 0.00 | 0.00 | 0.00 | 4738.98 | 02-AUG-06:00 | 0.00 |
September | 20640.78 | 02-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4741.12 | 20-SEP-06:49 | 0.00 |
October | 9869.68 | 18-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4741.97 | 31-OCT-18:30 | 0.00 |
November | 1587.92 | 08-NOV-04:49 | 0.00 | 0.00 | 0.00 | 4741.62 | 14-NOV-07:49 | 0.00 |
December | 318.59 | 05-DEC-04:19 | 0.00 | 0.00 | 0.00 | 4741.80 | 12-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 274.69 | 0.00 | 0.00 | 0.00 | 4738.98 | 0.00 | ||
Maximum of Months | 25088.82 | 0.00 | 0.00 | 0.00 | 4742.18 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 40522.66 | 10-JAN-17:10 | 4065.95 | 21922.77 | 3334.35 | 0.00 | 6802.25 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 40025.47 | 09-FEB-17:00 | 4065.95 | 21922.77 | 3334.35 | 0.00 | 6231.59 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 39796.74 | 04-MAR-11:09 | 2270.47 | 24333.76 | 0.00 | 0.00 | 6189.27 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 41183.42 | 07-APR-18:00 | 4065.95 | 18708.11 | 3334.35 | 0.00 | 4368.32 | 17.86 | 0.00 | 4535.47 | 0.00 |
May | 46231.93 | 20-MAY-16:10 | 2554.28 | 21922.77 | 0.00 | 0.00 | 4486.97 | 17.86 | 0.00 | 12644.47 | 0.00 |
June | 52368.54 | 20-JUN-17:30 | 2554.28 | 20315.44 | 0.00 | 0.00 | 5345.84 | 17.86 | 0.00 | 18261.15 | 0.00 |
July | 60793.84 | 17-JUL-17:00 | 2554.28 | 20315.44 | 0.00 | 0.00 | 6807.28 | 17.86 | 0.00 | 25053.74 | 0.00 |
August | 55585.04 | 05-AUG-17:00 | 2554.28 | 20315.44 | 0.00 | 0.00 | 5729.22 | 17.86 | 0.00 | 21090.85 | 0.00 |
September | 54812.59 | 02-SEP-17:19 | 2554.28 | 20315.44 | 0.00 | 0.00 | 5578.27 | 17.86 | 0.00 | 20294.56 | 0.00 |
October | 44264.22 | 18-OCT-17:30 | 4065.95 | 20315.44 | 3334.35 | 0.00 | 4368.32 | 17.86 | 0.00 | 6422.35 | 0.00 |
November | 39258.23 | 27-NOV-17:10 | 4065.95 | 21922.77 | 3334.35 | 0.00 | 5560.49 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 40253.29 | 28-DEC-17:00 | 4065.95 | 21922.77 | 3334.35 | 0.00 | 6461.38 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 39258.23 | 2270.47 | 18708.11 | 0.00 | 0.00 | 4368.32 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60793.84 | 4065.95 | 24333.76 | 3334.35 | 0.00 | 6807.28 | 17.86 | 0.00 | 25053.74 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 188487.04 | 19-JAN-04:10 | 0.00 | 34911.60 | 31-JAN-07:30 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 188487.04 | 03-FEB-04:19 | 0.00 | 35112.15 | 15-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 188487.04 | 05-MAR-04:10 | 0.00 | 35032.73 | 01-MAR-19:30 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 82009.08 | 29-APR-05:10 | 0.00 | 33899.47 | 04-APR-06:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 62774.64 | 08-MAY-05:10 | 0.00 | 32011.04 | 02-MAY-06:00 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 42240.59 | 17-JUN-04:00 | 0.00 | 29320.32 | 01-JUN-06:40 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 13583.66 | 08-JUL-04:00 | 0.00 | 26373.97 | 03-JUL-18:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 15454.99 | 18-AUG-04:00 | 0.00 | 24669.23 | 01-AUG-18:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 40264.29 | 17-SEP-05:00 | 0.00 | 25894.71 | 28-SEP-06:49 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 70138.09 | 10-OCT-05:10 | 0.00 | 28692.13 | 31-OCT-06:40 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 188487.04 | 27-NOV-04:19 | 0.00 | 31414.35 | 30-NOV-19:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 188487.04 | 30-DEC-04:19 | 0.00 | 33529.42 | 29-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 13583.66 | 0.00 | 24669.23 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 188487.04 | 0.00 | 35112.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
February | 5.67 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
March | 3.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
April | 0.50 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
May | 0.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.00 | 24.65 |
July | 0.17 | 20.39 | 0.00 | 20.39 | 1.33 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.80 | 0.00 | 24.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.73 | 0.00 | 24.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
December | 3.33 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
Annual Sum or Average | 19.67 | 19.53 | 0.00 | 19.53 | 5.33 | 20.64 | 0.00 | 20.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 20.43 | 0.00 | 20.43 | 1.83 | 24.80 | 0.00 | 24.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.84 | 0.00 | 26.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.81 | 0.00 | 26.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.80 | 0.00 | 26.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.40 | 0.00 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.32 | 0.00 | 28.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 29.73 | 0.00 | 29.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 30.41 | 0.00 | 30.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 30.33 | 0.00 | 30.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 29.99 | 0.00 | 29.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.90 | 0.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.37 | 0.00 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.76 | 0.00 | 26.76 |
Annual Sum or Average | 0.00 | 0.00 | 81.50 | 29.64 | 0.00 | 29.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.76 | 0.00 | 26.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 30.41 | 0.00 | 30.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.75 | 378.67 | 20.69 | 378.67 | 20.67 |
February | 550.83 | 20.88 | 219.50 | 20.75 | 219.50 | 20.67 |
March | 612.00 | 20.82 | 195.83 | 20.68 | 195.83 | 20.60 |
April | 535.67 | 21.22 | 71.67 | 21.03 | 71.67 | 20.89 |
May | 427.00 | 21.33 | 109.33 | 21.54 | 39.00 | 21.40 |
June | 185.50 | 21.67 | 297.17 | 23.07 | 8.33 | 23.06 |
July | 90.50 | 22.21 | 474.83 | 23.72 | 10.33 | 23.73 |
August | 123.00 | 21.85 | 406.83 | 23.51 | 0.83 | 23.50 |
September | 267.83 | 21.61 | 257.00 | 22.70 | 24.33 | 22.68 |
October | 482.17 | 21.30 | 44.50 | 21.24 | 28.33 | 21.11 |
November | 580.33 | 21.06 | 121.17 | 20.89 | 121.17 | 20.78 |
December | 609.00 | 20.78 | 268.33 | 20.68 | 268.33 | 20.62 |
Annual Sum or Average | 5073.83 | 21.09 | 2844.83 | 21.52 | 1366.33 | 21.35 |
Minimum of Months | 90.50 | 20.75 | 44.50 | 20.68 | 0.83 | 20.60 |
Maximum of Months | 612.00 | 22.21 | 474.83 | 23.72 | 378.67 | 23.73 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.08 | 422.83 | 19.05 | 422.83 | 19.03 |
February | 520.67 | 19.24 | 299.00 | 19.26 | 284.33 | 19.19 |
March | 604.33 | 19.37 | 266.00 | 19.27 | 264.00 | 19.20 |
April | 449.83 | 19.93 | 219.83 | 20.74 | 117.17 | 20.65 |
May | 456.00 | 21.75 | 321.00 | 22.81 | 194.17 | 23.08 |
June | 438.00 | 24.83 | 484.00 | 25.20 | 349.33 | 25.41 |
July | 495.50 | 25.83 | 582.00 | 25.75 | 480.17 | 25.82 |
August | 457.83 | 25.64 | 556.17 | 25.63 | 427.33 | 25.74 |
September | 434.50 | 23.88 | 420.17 | 24.60 | 290.50 | 24.91 |
October | 409.50 | 20.78 | 247.83 | 22.08 | 100.50 | 22.29 |
November | 499.67 | 19.58 | 229.83 | 19.92 | 166.50 | 19.79 |
December | 606.50 | 19.20 | 322.17 | 19.13 | 322.17 | 19.10 |
Annual Sum or Average | 5982.33 | 21.39 | 4370.83 | 22.08 | 3419.00 | 22.22 |
Minimum of Months | 409.50 | 19.08 | 219.83 | 19.05 | 100.50 | 19.03 |
Maximum of Months | 610.00 | 25.83 | 582.00 | 25.75 | 480.17 | 25.82 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.75140 | 16.79188 | -0.6412 | 14.63955 |
February | 551.00000 | 20.88552 | 20.21696 | -0.5350 | 12.33680 |
March | 612.00000 | 20.82112 | 21.82240 | -0.5199 | 11.73815 |
April | 590.00000 | 21.47349 | 27.11783 | -0.3023 | 9.12359 |
May | 611.00000 | 22.12456 | 30.93198 | -1.1469 | 36.32421 |
June | 592.00000 | 23.24084 | 37.82141 | -0.6435 | 17.12796 |
July | 609.00000 | 23.71880 | 40.07006 | -0.4164 | 10.22120 |
August | 612.00000 | 23.55830 | 36.35231 | -0.5041 | 12.63170 |
September | 590.00000 | 22.88102 | 37.79764 | -0.7612 | 21.93510 |
October | 610.00000 | 21.84966 | 29.69071 | -0.1404 | 7.73559 |
November | 591.00000 | 21.11245 | 23.42136 | -0.4102 | 10.07613 |
December | 609.00000 | 20.77631 | 19.21487 | -0.5797 | 13.01416 |
Annual Sum or Average | 7187.00000 | 21.93900 | 28.47269 | -0.5505 | 14.76618 |
Minimum of Months | 551.00000 | 20.75140 | 16.79188 | -1.1469 | 7.73559 |
Maximum of Months | 612.00000 | 23.71880 | 40.07006 | -0.1404 | 36.32421 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.07806 | 22.92375 | -0.6982 | 15.86453 |
February | 551.00000 | 19.50712 | 26.53079 | -0.5527 | 13.62210 |
March | 612.00000 | 19.41676 | 28.62008 | -0.5471 | 12.60095 |
April | 590.00000 | 20.98582 | 32.92002 | -0.1440 | 11.84189 |
May | 611.00000 | 22.37405 | 35.38832 | -0.7140 | 31.84221 |
June | 592.00000 | 24.65157 | 39.16801 | 0.11760 | 14.75637 |
July | 609.00000 | 25.50139 | 40.38655 | 0.44560 | 12.69428 |
August | 612.00000 | 25.24310 | 37.18985 | 0.32941 | 12.42606 |
September | 590.00000 | 23.88528 | 39.21137 | -0.1240 | 20.03533 |
October | 610.00000 | 21.86798 | 33.79662 | 0.11931 | 12.63219 |
November | 591.00000 | 20.25485 | 28.40899 | -0.3213 | 11.58192 |
December | 609.00000 | 19.21692 | 25.07220 | -0.6189 | 13.95275 |
Annual Sum or Average | 7187.00000 | 21.84495 | 32.49129 | -0.2242 | 15.34398 |
Minimum of Months | 551.00000 | 19.07806 | 22.92375 | -0.7140 | 11.58192 |
Maximum of Months | 612.00000 | 25.50139 | 40.38655 | 0.44560 | 31.84221 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 23391969.18 | 7972927.33 | 3.75 | 23391969.18 | 0.00 | 0.00 | 0.15 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 | 4689.79 | 27-FEB-14:00 | 4689.79 | 27-FEB-14:00 | 0.00 | 27-FEB-13:50 | 1575.10 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.700340E+09 | 0.229825E+09 | 37.67 | 0.697979E+09 | 2360578.79 | 0.00 | 0.44 | 07-APR-12:53 | 0.00 | 01-APR-00:01 | 14762.71 | 07-APR-12:53 | 14762.71 | 07-APR-12:53 | 365.13 | 24-APR-13:00 | 4618.12 | 07-APR-12:53 | 0.00 | 01-APR-00:01 |
May | 0.526550E+10 | 0.163705E+10 | 133.25 | 0.501028E+10 | 0.255216E+09 | 0.00 | 1.00 | 20-MAY-03:01 | 0.00 | 01-MAY-00:01 | 78571.49 | 20-MAY-03:01 | 61475.99 | 20-MAY-03:01 | 17095.50 | 20-MAY-03:01 | 21051.54 | 20-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.181849E+11 | 0.539013E+10 | 301.80 | 0.165213E+11 | 0.166363E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 78571.49 | 24-JUN-03:01 | 68511.14 | 25-JUN-03:01 | 32427.88 | 13-JUN-03:01 | 21051.54 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.343473E+11 | 0.101142E+11 | 440.62 | 0.320596E+11 | 0.228770E+10 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 78845.53 | 19-JUL-03:01 | 78359.35 | 26-JUL-03:58 | 29666.62 | 01-JUL-03:01 | 21072.34 | 19-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.273536E+11 | 0.810842E+10 | 388.76 | 0.263753E+11 | 0.978266E+09 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 78571.49 | 07-AUG-03:17 | 78571.49 | 07-AUG-03:47 | 25328.69 | 16-AUG-03:01 | 21051.54 | 04-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.146795E+11 | 0.437139E+10 | 244.05 | 0.132250E+11 | 0.145454E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 78571.49 | 26-SEP-03:01 | 75591.55 | 10-SEP-03:02 | 36216.65 | 08-SEP-03:41 | 21051.54 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.181161E+10 | 0.580878E+09 | 65.82 | 0.180594E+10 | 5667832.72 | 0.00 | 0.64 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 | 22840.35 | 18-OCT-12:55 | 22840.35 | 18-OCT-12:55 | 349.78 | 12-OCT-17:30 | 6772.54 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.102366E+12 | 0.304399E+11 | 1615.71 | 0.957188E+11 | 0.664738E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.343473E+11 | 0.101142E+11 | 440.62 | 0.320596E+11 | 0.228770E+10 | 0.00 | 1.00 | 0.00 | 78845.53 | 78571.49 | 36216.65 | 21072.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1957797.78 | 593671.71 | 0.57 | 1668131.03 | 289666.76 | 0.00 | 0.23 | 24-JAN-04:10 | 0.00 | 01-JAN-00:01 | 3565.10 | 24-JAN-04:10 | 3164.35 | 24-JAN-04:10 | 400.75 | 24-JAN-04:10 | 1050.10 | 24-JAN-04:10 | 0.00 | 01-JAN-00:01 |
February | 20106279.91 | 6092356.93 | 4.33 | 19699482.98 | 406796.93 | 0.00 | 0.21 | 21-FEB-04:08 | 0.00 | 01-FEB-00:01 | 3216.19 | 21-FEB-04:08 | 2860.15 | 21-FEB-04:08 | 914.65 | 28-FEB-04:05 | 952.31 | 21-FEB-04:08 | 0.00 | 01-FEB-00:01 |
March | 2752610.37 | 836974.11 | 0.92 | 2214062.63 | 538547.74 | 0.00 | 0.19 | 21-MAR-03:10 | 0.00 | 01-MAR-00:01 | 2794.98 | 21-MAR-03:10 | 2212.02 | 21-MAR-03:10 | 582.96 | 21-MAR-03:10 | 832.89 | 21-MAR-03:10 | 0.00 | 01-MAR-00:01 |
April | 0.581737E+09 | 0.167672E+09 | 52.14 | 0.568098E+09 | 13639081.27 | 0.00 | 1.00 | 07-APR-03:01 | 0.00 | 01-APR-00:01 | 37504.42 | 07-APR-03:01 | 33857.25 | 07-APR-03:01 | 5414.40 | 08-APR-03:01 | 8991.65 | 07-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.420272E+10 | 0.112670E+10 | 161.82 | 0.387584E+10 | 0.326879E+09 | 0.00 | 1.00 | 13-MAY-03:01 | 0.00 | 01-MAY-00:01 | 37504.42 | 14-MAY-03:41 | 33174.38 | 29-MAY-03:42 | 15232.74 | 19-MAY-03:01 | 8991.65 | 14-MAY-03:41 | 0.00 | 01-MAY-00:01 |
June | 0.132760E+11 | 0.339842E+10 | 340.20 | 0.117737E+11 | 0.150225E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 37504.42 | 12-JUN-03:21 | 28614.13 | 06-JUN-03:01 | 20408.69 | 13-JUN-03:31 | 8991.65 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.239559E+11 | 0.609953E+10 | 481.33 | 0.220949E+11 | 0.186105E+10 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 37504.42 | 20-JUL-03:55 | 34926.69 | 26-JUL-03:54 | 20118.42 | 01-JUL-03:01 | 9234.42 | 17-JUL-15:55 | 0.00 | 01-JUL-00:01 |
August | 0.192440E+11 | 0.496426E+10 | 440.32 | 0.182000E+11 | 0.104394E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 37504.42 | 01-AUG-03:01 | 37436.30 | 11-AUG-03:34 | 15976.41 | 14-AUG-03:11 | 8991.65 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.108971E+11 | 0.280729E+10 | 276.45 | 0.948272E+10 | 0.141437E+10 | 0.00 | 1.00 | 01-SEP-03:11 | 0.00 | 01-SEP-00:01 | 37504.42 | 01-SEP-03:51 | 33219.12 | 04-SEP-03:55 | 21482.71 | 08-SEP-03:41 | 8991.65 | 01-SEP-03:11 | 0.00 | 01-SEP-00:01 |
October | 0.148135E+10 | 0.414333E+09 | 83.26 | 0.143609E+10 | 45251480.75 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 37504.42 | 25-OCT-03:31 | 33739.75 | 19-OCT-03:51 | 16688.10 | 01-OCT-03:01 | 8991.65 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 37950848.07 | 10823031.00 | 10.03 | 32527787.72 | 5423060.34 | 0.00 | 1.00 | 05-NOV-03:01 | 0.00 | 01-NOV-00:01 | 37504.42 | 08-NOV-04:42 | 31926.92 | 08-NOV-04:42 | 5577.50 | 08-NOV-04:42 | 8991.65 | 08-NOV-04:42 | 0.00 | 01-NOV-00:01 |
December | 2624605.22 | 806339.10 | 1.06 | 2107711.25 | 516893.97 | 0.00 | 0.07 | 07-DEC-04:20 | 0.00 | 01-DEC-00:01 | 1085.19 | 07-DEC-04:20 | 914.34 | 05-DEC-04:20 | 279.53 | 07-DEC-04:20 | 332.00 | 07-DEC-04:20 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.737042E+11 | 0.189974E+11 | 1852.43 | 0.674896E+11 | 0.621456E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1957797.78 | 593671.71 | 0.57 | 1668131.03 | 289666.76 | 0.00 | 0.07 | 0.00 | 1085.19 | 914.34 | 279.53 | 332.00 | 0.00 | |||||||
Maximum of Months | 0.239559E+11 | 0.609953E+10 | 481.33 | 0.220949E+11 | 0.186105E+10 | 0.00 | 1.00 | 0.00 | 37504.42 | 37436.30 | 21482.71 | 9234.42 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 167.68 | 77.40 | 90.28 | 80.81 | 659.21 | 0.00 | 0.00 | 0.00 |
February | 262.68 | 131.30 | 131.38 | 189.55 | 477.06 | 0.00 | 0.00 | 0.00 |
March | 351.98 | 146.46 | 205.53 | 282.60 | 382.62 | 0.00 | 0.00 | 0.00 |
April | 447.97 | 222.55 | 225.42 | 439.68 | 266.34 | 0.00 | 0.00 | 0.00 |
May | 493.84 | 220.07 | 273.77 | 521.43 | 211.39 | 0.00 | 0.00 | 0.00 |
June | 638.27 | 328.39 | 309.88 | 775.64 | 139.59 | 0.00 | 0.00 | 0.00 |
July | 669.98 | 378.75 | 291.23 | 880.95 | 114.32 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 325.79 | 258.21 | 745.10 | 129.24 | 0.00 | 0.00 | 0.00 |
September | 412.72 | 213.11 | 199.61 | 473.06 | 190.60 | 0.00 | 0.00 | 0.00 |
October | 294.65 | 148.94 | 145.70 | 275.19 | 281.84 | 0.00 | 0.00 | 0.00 |
November | 187.70 | 87.70 | 100.00 | 124.18 | 403.23 | 0.00 | 0.00 | 0.00 |
December | 138.44 | 59.66 | 78.79 | 62.35 | 564.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 388.14 | 195.34 | 192.81 | 405.44 | 317.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.44 | 59.66 | 78.79 | 62.35 | 114.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 669.98 | 378.75 | 309.88 | 880.95 | 659.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 707.59 | 505.19 | 202.40 | 654.95 | 828.61 | 0.00 | 0.00 | 0.00 |
February | 888.97 | 635.89 | 253.08 | 913.50 | 610.55 | 0.00 | 0.00 | 0.00 |
March | 795.14 | 442.06 | 353.08 | 820.11 | 532.42 | 0.00 | 0.00 | 0.00 |
April | 654.38 | 316.67 | 337.71 | 707.77 | 390.46 | 0.00 | 0.00 | 0.00 |
May | 580.14 | 196.04 | 384.09 | 638.90 | 310.63 | 0.00 | 0.00 | 0.00 |
June | 568.61 | 163.87 | 404.74 | 711.20 | 213.71 | 0.00 | 0.00 | 0.00 |
July | 614.68 | 226.20 | 388.48 | 862.29 | 170.85 | 0.00 | 0.00 | 0.00 |
August | 721.93 | 358.91 | 363.02 | 980.99 | 193.02 | 0.00 | 0.00 | 0.00 |
September | 810.87 | 496.36 | 314.51 | 1018.95 | 273.30 | 0.00 | 0.00 | 0.00 |
October | 855.94 | 593.89 | 262.05 | 984.66 | 385.19 | 0.00 | 0.00 | 0.00 |
November | 773.27 | 559.79 | 213.47 | 808.49 | 510.29 | 0.00 | 0.00 | 0.00 |
December | 672.55 | 485.72 | 186.83 | 639.62 | 705.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.15 | 413.57 | 305.58 | 810.95 | 426.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 568.61 | 163.87 | 186.83 | 638.90 | 170.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 888.97 | 635.89 | 404.74 | 1018.95 | 828.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.46 | 61.33 | 90.13 | 72.71 | 675.32 | 0.00 | 0.00 | 0.00 |
February | 259.62 | 128.65 | 130.97 | 192.81 | 488.04 | 0.00 | 0.00 | 0.00 |
March | 330.78 | 121.92 | 208.85 | 262.79 | 392.98 | 0.00 | 0.00 | 0.00 |
April | 430.64 | 190.48 | 240.15 | 425.56 | 276.01 | 0.00 | 0.00 | 0.00 |
May | 532.59 | 243.38 | 289.21 | 580.23 | 217.75 | 0.00 | 0.00 | 0.00 |
June | 577.79 | 265.01 | 312.78 | 701.66 | 148.50 | 0.00 | 0.00 | 0.00 |
July | 592.11 | 298.97 | 293.14 | 783.36 | 122.86 | 0.00 | 0.00 | 0.00 |
August | 503.38 | 246.80 | 256.57 | 644.49 | 137.04 | 0.00 | 0.00 | 0.00 |
September | 405.53 | 205.04 | 200.50 | 473.05 | 198.69 | 0.00 | 0.00 | 0.00 |
October | 289.98 | 144.22 | 145.76 | 277.94 | 291.99 | 0.00 | 0.00 | 0.00 |
November | 205.24 | 101.99 | 103.25 | 157.27 | 412.68 | 0.00 | 0.00 | 0.00 |
December | 137.16 | 57.69 | 79.47 | 68.35 | 575.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.51 | 172.28 | 196.23 | 387.70 | 327.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.16 | 57.69 | 79.47 | 68.35 | 122.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 592.11 | 298.97 | 312.78 | 783.36 | 675.32 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.449111E+09 | 0.207299E+09 | 0.241812E+09 | 0.216443E+09 | 0.176563E+10 |
February | 0.635467E+09 | 0.317643E+09 | 0.317823E+09 | 0.458548E+09 | 0.115410E+10 |
March | 0.942754E+09 | 0.392271E+09 | 0.550483E+09 | 0.756922E+09 | 0.102480E+10 |
April | 0.116114E+10 | 0.576845E+09 | 0.584294E+09 | 0.113965E+10 | 0.690365E+09 |
May | 0.132270E+10 | 0.589426E+09 | 0.733278E+09 | 0.139660E+10 | 0.566186E+09 |
June | 0.165439E+10 | 0.851175E+09 | 0.803216E+09 | 0.201047E+10 | 0.361816E+09 |
July | 0.179448E+10 | 0.101445E+10 | 0.780027E+09 | 0.235954E+10 | 0.306207E+09 |
August | 0.156420E+10 | 0.872601E+09 | 0.691602E+09 | 0.199568E+10 | 0.346144E+09 |
September | 0.106977E+10 | 0.552376E+09 | 0.517398E+09 | 0.122618E+10 | 0.494026E+09 |
October | 0.789184E+09 | 0.398932E+09 | 0.390252E+09 | 0.737060E+09 | 0.754890E+09 |
November | 0.486515E+09 | 0.227308E+09 | 0.259207E+09 | 0.321872E+09 | 0.104517E+10 |
December | 0.370809E+09 | 0.159788E+09 | 0.211021E+09 | 0.167006E+09 | 0.151239E+10 |
Annual Sum or Average | 0.122405E+11 | 0.616011E+10 | 0.608041E+10 | 0.127860E+11 | 0.100217E+11 |
Minimum of Months | 0.370809E+09 | 0.159788E+09 | 0.211021E+09 | 0.167006E+09 | 0.306207E+09 |
Maximum of Months | 0.179448E+10 | 0.101445E+10 | 0.803216E+09 | 0.235954E+10 | 0.176563E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189520E+10 | 0.135311E+10 | 0.542098E+09 | 0.175421E+10 | 0.221935E+10 |
February | 0.215059E+10 | 0.153834E+10 | 0.612248E+09 | 0.220995E+10 | 0.147705E+10 |
March | 0.212969E+10 | 0.118400E+10 | 0.945686E+09 | 0.219659E+10 | 0.142604E+10 |
April | 0.169616E+10 | 0.820818E+09 | 0.875338E+09 | 0.183454E+10 | 0.101206E+10 |
May | 0.155383E+10 | 0.525084E+09 | 0.102875E+10 | 0.171124E+10 | 0.831995E+09 |
June | 0.147385E+10 | 0.424750E+09 | 0.104910E+10 | 0.184343E+10 | 0.553929E+09 |
July | 0.164635E+10 | 0.605846E+09 | 0.104050E+10 | 0.230957E+10 | 0.457614E+09 |
August | 0.193361E+10 | 0.961298E+09 | 0.972317E+09 | 0.262748E+10 | 0.516980E+09 |
September | 0.210178E+10 | 0.128656E+10 | 0.815222E+09 | 0.264112E+10 | 0.708388E+09 |
October | 0.229254E+10 | 0.159067E+10 | 0.701875E+09 | 0.263732E+10 | 0.103171E+10 |
November | 0.200430E+10 | 0.145099E+10 | 0.553316E+09 | 0.209560E+10 | 0.132268E+10 |
December | 0.180135E+10 | 0.130096E+10 | 0.500400E+09 | 0.171317E+10 | 0.189014E+10 |
Annual Sum or Average | 0.226793E+11 | 0.130424E+11 | 0.963685E+10 | 0.255742E+11 | 0.134479E+11 |
Minimum of Months | 0.147385E+10 | 0.424750E+09 | 0.500400E+09 | 0.171124E+10 | 0.457614E+09 |
Maximum of Months | 0.229254E+10 | 0.159067E+10 | 0.104910E+10 | 0.264112E+10 | 0.221935E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405671E+09 | 0.164273E+09 | 0.241397E+09 | 0.194738E+09 | 0.180877E+10 |
February | 0.628078E+09 | 0.311236E+09 | 0.316842E+09 | 0.466448E+09 | 0.118066E+10 |
March | 0.885957E+09 | 0.326561E+09 | 0.559395E+09 | 0.703849E+09 | 0.105257E+10 |
April | 0.111621E+10 | 0.493737E+09 | 0.622475E+09 | 0.110304E+10 | 0.715425E+09 |
May | 0.142650E+10 | 0.651873E+09 | 0.774627E+09 | 0.155410E+10 | 0.583219E+09 |
June | 0.149764E+10 | 0.686918E+09 | 0.810721E+09 | 0.181871E+10 | 0.384919E+09 |
July | 0.158591E+10 | 0.800768E+09 | 0.785139E+09 | 0.209816E+10 | 0.329065E+09 |
August | 0.134825E+10 | 0.661040E+09 | 0.687210E+09 | 0.172620E+10 | 0.367047E+09 |
September | 0.105114E+10 | 0.531452E+09 | 0.519691E+09 | 0.122615E+10 | 0.515001E+09 |
October | 0.776680E+09 | 0.386282E+09 | 0.390397E+09 | 0.744431E+09 | 0.782065E+09 |
November | 0.531988E+09 | 0.264355E+09 | 0.267634E+09 | 0.407646E+09 | 0.106968E+10 |
December | 0.367378E+09 | 0.154520E+09 | 0.212858E+09 | 0.183060E+09 | 0.154237E+10 |
Annual Sum or Average | 0.116214E+11 | 0.543301E+10 | 0.618839E+10 | 0.122265E+11 | 0.103308E+11 |
Minimum of Months | 0.367378E+09 | 0.154520E+09 | 0.212858E+09 | 0.183060E+09 | 0.329065E+09 |
Maximum of Months | 0.158591E+10 | 0.800768E+09 | 0.810721E+09 | 0.209816E+10 | 0.180877E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 704.44 | 2059.11 | 1026.73 | 643.92 | 382.81 | 0.00 | 0.00 |
February | 1216.43 | 1496.22 | 1411.27 | 895.84 | 515.42 | 0.00 | 0.00 |
March | 1328.73 | 1271.25 | 1477.90 | 710.44 | 767.46 | 0.00 | 0.00 |
April | 1527.26 | 887.07 | 1532.99 | 729.71 | 803.28 | 0.00 | 0.00 |
May | 1702.84 | 702.04 | 1606.57 | 659.49 | 947.08 | 0.00 | 0.00 |
June | 2155.57 | 468.86 | 1784.68 | 757.27 | 1027.41 | 0.00 | 0.00 |
July | 2506.59 | 388.02 | 1876.77 | 903.92 | 972.85 | 0.00 | 0.00 |
August | 2348.42 | 437.13 | 1809.31 | 931.50 | 877.81 | 0.00 | 0.00 |
September | 1942.06 | 639.58 | 1629.13 | 914.50 | 714.63 | 0.00 | 0.00 |
October | 1509.52 | 930.76 | 1440.56 | 887.05 | 553.51 | 0.00 | 0.00 |
November | 1022.00 | 1258.27 | 1166.21 | 749.48 | 416.73 | 0.00 | 0.00 |
December | 679.52 | 1755.41 | 948.16 | 603.07 | 345.09 | 0.00 | 0.00 |
Annual Sum or Average | 1555.20 | 1022.91 | 1475.81 | 781.19 | 694.62 | 0.00 | 0.00 |
Minimum of Months | 679.52 | 388.02 | 948.16 | 603.07 | 345.09 | 0.00 | 0.00 |
Maximum of Months | 2506.59 | 2059.11 | 1876.77 | 931.50 | 1027.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188677E+10 | 0.551513E+10 | 0.274999E+10 | 0.172468E+10 | 0.102531E+10 | 0.00 | 0.00 |
February | 0.294278E+10 | 0.361964E+10 | 0.341414E+10 | 0.216722E+10 | 0.124691E+10 | 0.00 | 0.00 |
March | 0.355886E+10 | 0.340491E+10 | 0.395840E+10 | 0.190284E+10 | 0.205556E+10 | 0.00 | 0.00 |
April | 0.395865E+10 | 0.229927E+10 | 0.397351E+10 | 0.189140E+10 | 0.208211E+10 | 0.00 | 0.00 |
May | 0.456089E+10 | 0.188036E+10 | 0.430304E+10 | 0.176638E+10 | 0.253666E+10 | 0.00 | 0.00 |
June | 0.558723E+10 | 0.121529E+10 | 0.462588E+10 | 0.196284E+10 | 0.266304E+10 | 0.00 | 0.00 |
July | 0.671365E+10 | 0.103927E+10 | 0.502673E+10 | 0.242106E+10 | 0.260567E+10 | 0.00 | 0.00 |
August | 0.629000E+10 | 0.117082E+10 | 0.484607E+10 | 0.249494E+10 | 0.235113E+10 | 0.00 | 0.00 |
September | 0.503382E+10 | 0.165779E+10 | 0.422270E+10 | 0.237039E+10 | 0.185231E+10 | 0.00 | 0.00 |
October | 0.404311E+10 | 0.249295E+10 | 0.385841E+10 | 0.237588E+10 | 0.148252E+10 | 0.00 | 0.00 |
November | 0.264903E+10 | 0.326144E+10 | 0.302281E+10 | 0.194265E+10 | 0.108016E+10 | 0.00 | 0.00 |
December | 0.182003E+10 | 0.470169E+10 | 0.253954E+10 | 0.161526E+10 | 0.924279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.490448E+11 | 0.322586E+11 | 0.465412E+11 | 0.246355E+11 | 0.219057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.182003E+10 | 0.103927E+10 | 0.253954E+10 | 0.161526E+10 | 0.924279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.671365E+10 | 0.551513E+10 | 0.502673E+10 | 0.249494E+10 | 0.266304E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639858E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173411553.2 | 81.22 | 0.00 | 0.00 |
February | 0.578972E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155433621.8 | 81.22 | 0.00 | 0.00 |
March | 0.646602E+10 | -0.629385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172163095.5 | 81.22 | 0.00 | 0.00 |
April | 0.620594E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162470015.5 | 81.22 | 0.00 | 0.00 |
May | 0.642429E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164109780.7 | 81.22 | 0.00 | 0.00 |
June | 0.623939E+10 | -0.608656E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152831872.5 | 81.21 | 0.00 | 0.00 |
July | 0.637272E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155635207.0 | 81.21 | 0.00 | 0.00 |
August | 0.645144E+10 | -0.629522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156222940.5 | 81.21 | 0.00 | 0.00 |
September | 0.619952E+10 | -0.604481E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154702107.8 | 81.22 | 0.00 | 0.00 |
October | 0.638909E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165279435.9 | 81.22 | 0.00 | 0.00 |
November | 0.618888E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164273112.3 | 81.22 | 0.00 | 0.00 |
December | 0.638979E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172720825.3 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755154E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.194925E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.578972E+10 | -0.629522E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173411553.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646602E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152831872.5 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.271085E+11 | -0.260947E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101376E+10 | 58.99 | 0.00 | 0.00 |
February | 0.249392E+11 | -0.240344E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -904728303.1 | 58.99 | 0.00 | 0.00 |
March | 0.275709E+11 | -0.265686E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100237E+10 | 58.99 | 0.00 | 0.00 |
April | 0.255076E+11 | -0.245755E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -932089559.1 | 58.99 | 0.00 | 0.00 |
May | 0.249741E+11 | -0.240455E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -928627833.6 | 58.99 | 0.00 | 0.00 |
June | 0.227790E+11 | -0.219351E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -843937536.1 | 58.99 | 0.00 | 0.00 |
July | 0.221233E+11 | -0.212720E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -851217606.5 | 59.00 | 0.00 | 0.00 |
August | 0.218958E+11 | -0.210393E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -856487914.9 | 58.99 | 0.00 | 0.00 |
September | 0.213449E+11 | -0.204839E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -861030224.6 | 58.99 | 0.00 | 0.00 |
October | 0.230171E+11 | -0.220778E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -939265499.6 | 58.99 | 0.00 | 0.00 |
November | 0.236855E+11 | -0.227370E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -948496204.2 | 58.99 | 0.00 | 0.00 |
December | 0.259305E+11 | -0.249231E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100740E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.290876E+12 | -0.279787E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.110894E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213449E+11 | -0.265686E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.101376E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275709E+11 | -0.204839E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843937536.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.50 | 01-JAN-08:50 | 4130.37 | 36.61 | 203.00 | 226.50 | 3832.11 | 34.58 | 185.33 | 222.83 |
February | 275.00 | 0.52 | 0.50 | 01-FEB-08:30 | 1512.57 | 26.63 | 194.67 | 255.67 | 1662.90 | 27.55 | 198.50 | 255.33 |
March | 304.00 | 0.52 | 0.50 | 01-MAR-07:49 | 1365.71 | 22.93 | 217.83 | 317.00 | 1565.55 | 23.10 | 215.50 | 316.83 |
April | 325.17 | 0.52 | 0.50 | 01-APR-08:39 | 1546.32 | 21.35 | 158.17 | 347.33 | 1477.52 | 21.36 | 164.33 | 350.00 |
May | 385.83 | 0.52 | 0.50 | 01-MAY-05:00 | 1335.41 | 22.36 | 207.33 | 398.17 | 1296.58 | 21.27 | 191.67 | 400.33 |
June | 434.17 | 0.53 | 0.50 | 01-JUN-13:39 | 1314.41 | 22.42 | 247.33 | 427.00 | 1475.28 | 20.92 | 192.00 | 421.67 |
July | 417.33 | 0.51 | 0.50 | 01-JUL-06:40 | 1467.34 | 22.12 | 219.33 | 411.00 | 1524.69 | 21.29 | 190.00 | 416.17 |
August | 421.33 | 0.52 | 0.50 | 01-AUG-05:00 | 1266.03 | 20.91 | 179.17 | 393.67 | 1417.92 | 20.83 | 174.50 | 395.00 |
September | 352.17 | 0.52 | 0.50 | 01-SEP-06:30 | 1313.21 | 21.47 | 174.50 | 332.67 | 1387.73 | 21.46 | 173.33 | 331.67 |
October | 317.67 | 0.52 | 0.50 | 01-OCT-08:09 | 1353.22 | 24.60 | 212.67 | 300.33 | 1178.87 | 24.47 | 209.50 | 300.00 |
November | 269.50 | 0.52 | 0.50 | 01-NOV-07:49 | 3047.21 | 34.27 | 234.67 | 249.33 | 3148.58 | 33.43 | 214.33 | 247.83 |
December | 236.83 | 0.54 | 0.50 | 01-DEC-08:39 | 3355.14 | 35.55 | 198.17 | 226.17 | 3489.77 | 35.96 | 205.33 | 221.50 |
Annual Sum or Average | 3965.83 | 0.52 | 1767.78 | 24.96 | 2446.83 | 3884.83 | 1814.41 | 24.51 | 2314.33 | 3879.17 | ||
Minimum of Months | 226.83 | 0.51 | 0.50 | 1266.03 | 20.91 | 158.17 | 226.17 | 1178.87 | 20.83 | 164.33 | 221.50 | |
Maximum of Months | 434.17 | 0.54 | 0.50 | 4130.37 | 36.61 | 247.33 | 427.00 | 3832.11 | 35.96 | 215.50 | 421.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.822874E+11 | 150789.63 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491546E+11 | 150789.63 | 01-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417022E+11 | 150789.63 | 03-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185410E+11 | 77772.95 | 29-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119769E+11 | 63992.52 | 10-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171204E+10 | 33616.74 | 15-JUN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.215937E+09 | 20736.50 | 08-JUL-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.404537E+09 | 21654.83 | 18-AUG-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.385442E+10 | 29988.24 | 17-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119407E+11 | 42720.11 | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309757E+11 | 150789.63 | 27-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.610048E+11 | 150789.63 | 15-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.215937E+09 | 20736.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822874E+11 | 150789.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.504799E+11 | 74725.77 | 29-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281029E+11 | 61781.45 | 04-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225433E+11 | 63246.89 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.811439E+10 | 42511.06 | 29-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.504939E+10 | 25150.19 | 06-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.304647E+09 | 15381.56 | 15-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1232063.66 | 3725.43 | 08-JUL-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13881259.85 | 4020.92 | 18-AUG-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.966477E+09 | 18590.41 | 17-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.461518E+10 | 27284.71 | 21-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164272E+11 | 46756.29 | 12-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360155E+11 | 65188.03 | 31-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1232063.66 | 3725.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504799E+11 | 74725.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23391969.18 | 23391969.18 | 4689.79 | 27-FEB-14:00 | 4689.79 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.700340E+09 | 0.697979E+09 | 14762.71 | 07-APR-12:53 | 14762.71 | 0.00 |
May | 0.00 | 0.00 | 0.526550E+10 | 0.501028E+10 | 78571.49 | 20-MAY-03:01 | 61475.99 | 0.00 |
June | 0.00 | 0.00 | 0.181849E+11 | 0.165213E+11 | 78571.49 | 24-JUN-03:01 | 57943.21 | 0.00 |
July | 0.00 | 0.00 | 0.343473E+11 | 0.320596E+11 | 78845.53 | 19-JUL-03:01 | 51555.45 | 0.00 |
August | 0.00 | 0.00 | 0.273536E+11 | 0.263753E+11 | 78571.49 | 07-AUG-03:17 | 78540.11 | 0.00 |
September | 0.00 | 0.00 | 0.146795E+11 | 0.132250E+11 | 78571.49 | 26-SEP-03:01 | 64093.16 | 0.00 |
October | 0.00 | 0.00 | 0.181161E+10 | 0.180594E+10 | 22840.35 | 18-OCT-12:55 | 22840.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.102366E+12 | 0.957188E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.343473E+11 | 0.320596E+11 | 78845.53 | 78540.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1957797.78 | 1668131.03 | 3565.10 | 24-JAN-04:10 | 3164.35 | 0.00 |
February | 0.00 | 0.00 | 20106279.91 | 19699482.98 | 3216.19 | 21-FEB-04:08 | 2860.15 | 0.00 |
March | 0.00 | 0.00 | 2752610.37 | 2214062.63 | 2794.98 | 21-MAR-03:10 | 2212.02 | 0.00 |
April | 0.00 | 0.00 | 0.581737E+09 | 0.568098E+09 | 37504.42 | 07-APR-03:01 | 33857.25 | 0.00 |
May | 0.00 | 0.00 | 0.420272E+10 | 0.387584E+10 | 37504.42 | 14-MAY-03:41 | 27388.65 | 0.00 |
June | 0.00 | 0.00 | 0.132760E+11 | 0.117737E+11 | 37504.42 | 12-JUN-03:21 | 18445.70 | 0.00 |
July | 0.00 | 0.00 | 0.239559E+11 | 0.220949E+11 | 37504.42 | 20-JUL-03:55 | 27308.49 | 0.00 |
August | 0.00 | 0.00 | 0.192440E+11 | 0.182000E+11 | 37504.42 | 01-AUG-03:01 | 22605.62 | 0.00 |
September | 0.00 | 0.00 | 0.108971E+11 | 0.948272E+10 | 37504.42 | 01-SEP-03:51 | 28994.83 | 0.00 |
October | 0.00 | 0.00 | 0.148135E+10 | 0.143609E+10 | 37504.42 | 25-OCT-03:31 | 32848.38 | 0.00 |
November | 0.00 | 0.00 | 37950848.07 | 32527787.72 | 37504.42 | 08-NOV-04:42 | 31926.92 | 0.00 |
December | 0.00 | 0.00 | 2624605.22 | 2107711.25 | 1085.19 | 07-DEC-04:20 | 805.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.737042E+11 | 0.674896E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1957797.78 | 1668131.03 | 1085.19 | 805.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.239559E+11 | 0.220949E+11 | 37504.42 | 33857.25 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10200.12 | 19656.22 | 31-JAN-19:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10391.75 | 19775.45 | 21-FEB-19:53 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 10376.34 | 19746.21 | 07-MAR-07:28 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9939.22 | 19220.54 | 03-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9436.40 | 18385.04 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8922.51 | 17271.61 | 02-JUN-18:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8403.36 | 16305.72 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8316.64 | 15712.97 | 03-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8364.14 | 16105.57 | 29-SEP-18:28 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8703.45 | 17004.01 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9231.47 | 18051.13 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9763.62 | 18988.92 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 9331.20 | ||||
Minimum of Months | 0.00 | 0.00 | 8316.64 | 15712.97 | ||
Maximum of Months | 0.00 | 0.00 | 10391.75 | 19775.45 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184725E+10 | 0.25 | 824.13 | 01-JAN-00:01 | 0.30 |
February | 0.167141E+10 | 0.25 | 824.13 | 01-FEB-00:01 | 0.30 |
March | 0.185241E+10 | 0.25 | 824.13 | 01-MAR-00:01 | 0.30 |
April | 0.182564E+10 | 0.26 | 824.13 | 01-APR-04:01 | 0.30 |
May | 0.191074E+10 | 0.26 | 824.13 | 01-MAY-04:01 | 0.30 |
June | 0.192226E+10 | 0.27 | 824.13 | 01-JUN-01:05 | 0.30 |
July | 0.205571E+10 | 0.28 | 824.13 | 01-JUL-00:30 | 0.30 |
August | 0.204467E+10 | 0.28 | 824.13 | 01-AUG-00:20 | 0.30 |
September | 0.192525E+10 | 0.27 | 824.13 | 01-SEP-00:40 | 0.30 |
October | 0.191193E+10 | 0.26 | 824.13 | 01-OCT-03:01 | 0.30 |
November | 0.181701E+10 | 0.26 | 824.13 | 01-NOV-03:35 | 0.30 |
December | 0.185330E+10 | 0.25 | 824.13 | 01-DEC-00:01 | 0.30 |
Annual Sum or Average | 0.226376E+11 | 0.26 | |||
Minimum of Months | 0.167141E+10 | 0.25 | 824.13 | 0.30 | |
Maximum of Months | 0.205571E+10 | 0.28 | 824.13 | 0.30 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.860739E+10 | 1.01 | 6994.63 | 06-JAN-04:01 | 1.61 |
February | 0.706075E+10 | 0.96 | 6994.63 | 01-FEB-04:01 | 1.61 |
March | 0.744016E+10 | 0.93 | 6994.63 | 03-MAR-04:02 | 1.61 |
April | 0.656306E+10 | 0.86 | 4216.83 | 21-APR-04:15 | 1.24 |
May | 0.658096E+10 | 0.84 | 4578.89 | 10-MAY-04:04 | 1.31 |
June | 0.610436E+10 | 0.82 | 5844.53 | 21-JUN-03:01 | 1.47 |
July | 0.634156E+10 | 0.83 | 6994.63 | 16-JUL-03:01 | 1.59 |
August | 0.630338E+10 | 0.82 | 6994.63 | 09-AUG-03:01 | 1.60 |
September | 0.617336E+10 | 0.82 | 6456.39 | 08-SEP-03:01 | 1.53 |
October | 0.657809E+10 | 0.84 | 3967.20 | 05-OCT-04:01 | 1.20 |
November | 0.692120E+10 | 0.90 | 6994.63 | 27-NOV-04:03 | 1.61 |
December | 0.797956E+10 | 0.97 | 6994.63 | 15-DEC-04:02 | 1.61 |
Annual Sum or Average | 0.826538E+11 | 0.88 | |||
Minimum of Months | 0.610436E+10 | 0.82 | 3967.20 | 1.20 | |
Maximum of Months | 0.860739E+10 | 1.01 | 6994.63 | 1.61 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223708E+10 | 0.61 | 1591.22 | 29-JAN-05:02 | 0.94 |
February | 0.182297E+10 | 0.57 | 1444.87 | 04-FEB-05:02 | 0.90 |
March | 0.192134E+10 | 0.56 | 1461.44 | 05-MAR-05:02 | 0.90 |
April | 0.170875E+10 | 0.54 | 1226.99 | 29-APR-04:03 | 0.82 |
May | 0.173475E+10 | 0.54 | 1865.84 | 19-MAY-03:01 | 1.00 |
June | 0.167519E+10 | 0.55 | 1865.84 | 01-JUN-03:01 | 1.00 |
July | 0.184546E+10 | 0.58 | 1865.84 | 01-JUL-03:01 | 1.00 |
August | 0.181248E+10 | 0.57 | 1865.84 | 01-AUG-03:01 | 1.00 |
September | 0.169985E+10 | 0.55 | 1865.84 | 01-SEP-03:11 | 1.00 |
October | 0.172967E+10 | 0.53 | 1865.84 | 01-OCT-03:01 | 1.01 |
November | 0.180207E+10 | 0.55 | 1274.99 | 12-NOV-05:03 | 0.84 |
December | 0.207381E+10 | 0.58 | 1483.38 | 31-DEC-05:02 | 0.91 |
Annual Sum or Average | 0.220634E+11 | 0.56 | |||
Minimum of Months | 0.167519E+10 | 0.53 | 1226.99 | 0.82 | |
Maximum of Months | 0.223708E+10 | 0.61 | 1865.84 | 1.01 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.84 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 46.43 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.62 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.44 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 50.97 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 51.98 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.91 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.28 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.71 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.99 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 51.76 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.64 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 46.43 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.71 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.84 | 59.93 | 10200.12 | 19656.22 | 31-JAN-19:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.43 | 59.70 | 10391.75 | 19775.45 | 21-FEB-19:53 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.62 | 58.99 | 10376.34 | 19746.21 | 07-MAR-07:28 |
April | 0.00 | 0.00 | 01-APR-00:01 | 48.62 | 48.62 | 9939.22 | 19220.54 | 03-APR-18:27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 48.98 | 48.98 | 9436.40 | 18385.04 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 49.36 | 49.36 | 8922.51 | 17271.61 | 02-JUN-18:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 49.81 | 49.81 | 8403.36 | 16305.72 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.04 | 50.04 | 8316.64 | 15712.97 | 03-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.41 | 50.41 | 8364.14 | 16105.57 | 29-SEP-18:28 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 47.71 | 47.71 | 8703.45 | 17004.01 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.01 | 50.01 | 9231.47 | 18051.13 | 30-NOV-19:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.64 | 58.65 | 9763.62 | 18988.92 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 9331.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.43 | 47.71 | 8316.64 | 15712.97 | ||
Maximum of Months | 0.00 | 0.00 | 50.41 | 59.93 | 10391.75 | 19775.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.860739E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.706872E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.744016E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.679288E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.821802E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.114945E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164558E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.144118E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105447E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.715897E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.692120E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.797956E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.113094E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.679288E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.164558E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.223767E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.182906E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192217E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.187643E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.286145E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.507361E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.794499E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.677674E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.450714E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.214401E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.181289E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.207461E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.410608E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181289E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.794499E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.860739E+10 | 0.00 | 0.822874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706075E+10 | 23391969.18 | 0.491546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744016E+10 | 0.00 | 0.417022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.656306E+10 | 0.700340E+09 | 0.185410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.658096E+10 | 0.526389E+10 | 0.119769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610436E+10 | 0.181660E+11 | 0.171204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.634156E+10 | 0.342812E+11 | 0.215937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.630338E+10 | 0.273187E+11 | 0.404537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.617336E+10 | 0.146448E+11 | 0.385442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657809E+10 | 0.181161E+10 | 0.119407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692120E+10 | 0.00 | 0.309757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797956E+10 | 0.00 | 0.610048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.826538E+11 | 0.102210E+12 | 0.313770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.610436E+10 | 0.00 | 0.215937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.860739E+10 | 0.342812E+11 | 0.822874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.223708E+10 | 1957797.78 | 0.504799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182297E+10 | 20106279.91 | 0.281029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192134E+10 | 2752610.37 | 0.225433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170875E+10 | 0.579930E+09 | 0.811439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173475E+10 | 0.419735E+10 | 0.504939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167519E+10 | 0.132668E+11 | 0.304647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184546E+10 | 0.239123E+11 | 1232063.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181248E+10 | 0.192232E+11 | 13881259.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169985E+10 | 0.108722E+11 | 0.966477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172967E+10 | 0.147555E+10 | 0.461518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180207E+10 | 36675697.68 | 0.164272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207381E+10 | 2624605.22 | 0.360155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220634E+11 | 0.735914E+11 | 0.172634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167519E+10 | 1957797.78 | 1232063.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223708E+10 | 0.239123E+11 | 0.504799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.860739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706075E+10 | 0.00 | 0.00 | 0.00 | 7972927.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.656306E+10 | 0.00 | 0.00 | 0.00 | 0.229825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.658096E+10 | 0.00 | 0.00 | 0.00 | 0.163705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610436E+10 | 0.00 | 0.00 | 0.00 | 0.539013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.634156E+10 | 0.00 | 0.00 | 0.00 | 0.101142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.630338E+10 | 0.00 | 0.00 | 0.00 | 0.810842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.617336E+10 | 0.00 | 0.00 | 0.00 | 0.437139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657809E+10 | 0.00 | 0.00 | 0.00 | 0.580878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.826538E+11 | 0.00 | 0.00 | 0.00 | 0.304399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.610436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.860739E+10 | 0.00 | 0.00 | 0.00 | 0.101142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.223708E+10 | 0.00 | 0.00 | 0.00 | 593671.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182297E+10 | 0.00 | 0.00 | 0.00 | 6092356.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192134E+10 | 0.00 | 0.00 | 0.00 | 836974.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170875E+10 | 0.00 | 0.00 | 0.00 | 0.167672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173475E+10 | 0.00 | 0.00 | 0.00 | 0.112670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167519E+10 | 0.00 | 0.00 | 0.00 | 0.339842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184546E+10 | 0.00 | 0.00 | 0.00 | 0.609953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181248E+10 | 0.00 | 0.00 | 0.00 | 0.496426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169985E+10 | 0.00 | 0.00 | 0.00 | 0.280729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172967E+10 | 0.00 | 0.00 | 0.00 | 0.414333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180207E+10 | 0.00 | 0.00 | 0.00 | 10823031.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207381E+10 | 0.00 | 0.00 | 0.00 | 806339.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220634E+11 | 0.00 | 0.00 | 0.00 | 0.189974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167519E+10 | 0.00 | 0.00 | 0.00 | 593671.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223708E+10 | 0.00 | 0.00 | 0.00 | 0.609953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.501167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558978E+11 | 0.00 | 0.00 | 3.57 |
February | 0.523159E+11 | 0.00 | 0.00 | 921223.85 | 0.00 | 0.231997E+11 | 0.106038E+10 | 0.00 | 3.57 |
March | 0.612848E+11 | 0.00 | 0.00 | 196221.71 | 0.00 | 0.136424E+11 | 0.229022E+09 | 0.00 | 3.58 |
April | 0.460350E+11 | 0.00 | 0.00 | 14188395.56 | 0.00 | 0.169370E+10 | 0.697259E+10 | 0.00 | 3.69 |
May | 0.343779E+11 | 20293209.14 | 0.00 | 41192633.44 | 0.00 | 0.115412E+10 | 0.127695E+11 | 0.00 | 3.89 |
June | 0.128361E+11 | 0.465984E+09 | 0.00 | 88758107.63 | 0.00 | 5456409.43 | 0.184973E+11 | 0.00 | 4.15 |
July | 0.586708E+10 | 0.166926E+10 | 4218.48 | 0.113634E+09 | 0.00 | 1457332.08 | 0.151044E+11 | 18620.60 | 4.14 |
August | 0.802385E+10 | 0.109195E+10 | 0.00 | 0.108454E+09 | 0.00 | 1549802.86 | 0.185919E+11 | 0.00 | 4.22 |
September | 0.187956E+11 | 0.662762E+09 | 0.00 | 62698304.36 | 0.00 | 8082357.73 | 0.175435E+11 | 0.00 | 4.05 |
October | 0.398265E+11 | 0.00 | 0.00 | 21413134.52 | 0.00 | 0.195854E+09 | 0.126056E+11 | 0.00 | 3.75 |
November | 0.559268E+11 | 0.00 | 0.00 | 2504272.85 | 0.00 | 0.541756E+10 | 0.443133E+10 | 0.00 | 3.55 |
December | 0.618435E+11 | 0.00 | 0.00 | 76074.07 | 0.00 | 0.274134E+11 | 0.363022E+09 | 0.00 | 3.58 |
Annual Sum or Average | 0.447250E+12 | 0.391026E+10 | 4218.48 | 0.454036E+09 | 0.00 | 0.128631E+12 | 0.108169E+12 | 18620.60 | 3.81 |
Minimum of Months | 0.586708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457332.08 | 0.00 | 0.00 | 3.55 |
Maximum of Months | 0.618435E+11 | 0.166926E+10 | 4218.48 | 0.113634E+09 | 0.00 | 0.558978E+11 | 0.185919E+11 | 18620.60 | 4.22 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.905712E+11 | 0.00 | 0.00 | 119316.68 | 0.202116E+09 | 61940249.95 | 0.505284E+09 | 0.00 | 8.50 |
February | 0.639203E+11 | 0.00 | 0.00 | 1473896.40 | 0.272660E+09 | 31820058.69 | 0.210900E+10 | 0.00 | 8.42 |
March | 0.637346E+11 | 0.00 | 0.00 | 361044.67 | 0.492242E+09 | 23696006.26 | 0.938042E+09 | 0.00 | 8.45 |
April | 0.406436E+11 | 0.00 | 0.00 | 15386030.99 | 0.412910E+09 | 7965602.38 | 0.996085E+10 | 0.00 | 8.35 |
May | 0.303250E+11 | 11731365.76 | 0.00 | 45967279.27 | 97945078.52 | 6568745.72 | 0.171036E+11 | 0.00 | 8.38 |
June | 0.978585E+10 | 0.406346E+09 | 0.00 | 96648904.13 | 18394544.17 | 0.00 | 0.247897E+11 | 0.00 | 8.50 |
July | 0.332137E+10 | 0.561197E+09 | 0.00 | 0.132718E+09 | 0.00 | 0.00 | 0.235517E+11 | 0.00 | 8.62 |
August | 0.376650E+10 | 0.549954E+09 | 0.00 | 0.118027E+09 | 0.00 | 0.00 | 0.273079E+11 | 0.00 | 8.61 |
September | 0.141521E+11 | 0.140374E+09 | 0.00 | 71060546.90 | 15388317.13 | 0.00 | 0.227761E+11 | 0.00 | 8.50 |
October | 0.306463E+11 | 0.00 | 0.00 | 26614517.27 | 0.371902E+09 | 4785163.08 | 0.188736E+11 | 0.00 | 8.35 |
November | 0.491757E+11 | 0.00 | 0.00 | 5765298.87 | 0.336906E+09 | 11819199.14 | 0.884462E+10 | 0.00 | 8.36 |
December | 0.752214E+11 | 0.00 | 0.00 | 376201.13 | 0.389144E+09 | 36164604.99 | 0.158735E+10 | 0.00 | 8.52 |
Annual Sum or Average | 0.475264E+12 | 0.166960E+10 | 0.00 | 0.514518E+09 | 0.260961E+10 | 0.184760E+09 | 0.158348E+12 | 0.00 | 8.46 |
Minimum of Months | 0.332137E+10 | 0.00 | 0.00 | 119316.68 | 0.00 | 0.00 | 0.505284E+09 | 0.00 | 8.35 |
Maximum of Months | 0.905712E+11 | 0.561197E+09 | 0.00 | 0.132718E+09 | 0.492242E+09 | 61940249.95 | 0.273079E+11 | 0.00 | 8.62 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:25:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.220308E+11 | 0.172347E+11 | 0.305590E+12 | 84193.37 | 0.465453E+11 |
February | 0.441161E+11 | 0.129281E+11 | 0.223437E+12 | 88367464.02 | 0.321866E+11 |
March | 0.845836E+11 | 0.133168E+11 | 0.223581E+12 | 88444.95 | 0.315802E+11 |
April | 0.937391E+11 | 0.105768E+11 | 0.174143E+12 | 0.107879E+10 | 0.263789E+11 |
May | 0.131088E+12 | 0.107565E+11 | 0.159352E+12 | 0.235509E+10 | 0.378457E+11 |
June | 0.145307E+12 | 0.833977E+10 | 0.114289E+12 | 0.358475E+10 | 0.652819E+11 |
July | 0.143953E+12 | 0.654850E+10 | 0.886284E+11 | 0.306870E+10 | 0.102322E+12 |
August | 0.118927E+12 | 0.652609E+10 | 0.103270E+12 | 0.391016E+10 | 0.850179E+11 |
September | 0.881043E+11 | 0.695082E+10 | 0.124225E+12 | 0.301438E+10 | 0.542580E+11 |
October | 0.495612E+11 | 0.881744E+10 | 0.169713E+12 | 0.152046E+10 | 0.254922E+11 |
November | 0.186768E+11 | 0.105632E+11 | 0.200996E+12 | 0.123583E+09 | 0.249274E+11 |
December | 0.936986E+10 | 0.139260E+11 | 0.263290E+12 | 0.00 | 0.368155E+11 |
Annual Sum or Average | 0.949457E+12 | 0.126485E+12 | 0.215051E+13 | 0.187445E+11 | 0.568652E+12 |
Minimum of Months | 0.936986E+10 | 0.652609E+10 | 0.886284E+11 | 0.00 | 0.249274E+11 |
Maximum of Months | 0.145307E+12 | 0.172347E+11 | 0.305590E+12 | 0.391016E+10 | 0.102322E+12 |