Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:24:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2402.86 | 4700.85 | 4700.85 |
Net Site Energy | 2402.86 | 4700.85 | 4700.85 |
Total Source Energy | 4535.73 | 8873.52 | 8873.52 |
Net Source Energy | 4535.73 | 8873.52 | 8873.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 613.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 162.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.52 | 392.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 61.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 927.04 | 1475.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 613.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 51.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.19 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 162.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.52 | 392.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 613.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 51.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 71.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.32 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 162.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.52 | 392.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 61.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 226.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 566.47 | 1968.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1020.28 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1813.63 | 2887.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 226.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 566.47 | 1968.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1020.28 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1813.63 | 2887.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 927.043 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 927.043 | 100.00 |
Total On-Site and Utility Electric Sources | 927.043 | 100.00 |
Total Electricity End Uses | 927.043 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3589.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 9.5182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.3127 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 9.4622 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.5182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.3127 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 9.4622 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 9.4622 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-17:00 | 10-JAN-21:19 | - | - | - | - | - | - | - | - | - | - | 05-JAN-07:00 |
Heating | 0.00 | 165776.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25387.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20661.14 | 16292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8057.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4316.28 | 30659.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2036.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 63684.18 | 212728.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 165776.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25387.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19293.56 | 16292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8057.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4316.28 | 30659.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 510.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 980.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 664.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 161.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 225.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 142.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1457.82 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 514.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.17 | 425.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2935.94 | 1599.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1300.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 316.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 440.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1006.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.91 | 832.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 379.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5743.77 | 3129.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1300.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 316.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 440.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 278.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2852.02 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1006.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.91 | 832.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 379.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5743.77 | 3129.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.12 |
KITCHEN DIRECT AIR | 1.78 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.12 | 4.12 | 4.12 | 4.12 | 4.12 | 4.12 | 1.00 | 1.000000 | 4.12 |
PSZ-AC_2:2 | 1.78 | 1.78 | 1.78 | 1.78 | 1.78 | 1.78 | 1.00 | 1.00 | 1.78 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.12 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.78 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.12 | 7046.38 |
PSZ-AC_2:2_ADDAQ FAN | 1.78 | 1905.17 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.12 | 4.12 | 4.12 | 2.72 | 80122.60 | 151398.57 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.78 | 1.78 | 1.78 | 1.18 | 38689.56 | 99935.47 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.12 | 2.06 | 2.75 | 80122.60 | 40061.30 | 0.788260 | 0.788260 |
PSZ-AC_2:2 COOLING COIL | 1.78 | 0.890228 | 1.19 | 38689.56 | 19344.78 | 0.745070 | 0.745070 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 151398.57 |
PSZ-AC_2:2 HEATING COIL | 99935.47 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 9.518 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 74.446 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.313 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.393 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3538.380 | 9.518 | 12.631 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3538.380 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1298.236 | 9.313 | 172.457 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1298.236 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.8794 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1426 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2431 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9031 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.935 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.036 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.28842413E-12 | 0.14163715E-14 | -0.83625437E-13 | 0.83302026E-16 |
34 | 6 | 0.27446597E-07 | 0.24415596E-09 | 0.62976823E-08 | -0.12863247E-12 |
35 | 5 | -0.18387070E-03 | 0.21059431E-05 | -0.94655602E-04 | 0.62291981E-08 |
36 | 4 | 0.28482235 | 0.10320537E-02 | 0.97050522E-01 | -0.32540306E-04 |
37 | 3 | -7.1212123 | 0.32167701E-01 | -2.2958568 | 0.28298028E-01 |
38 | 2 | 40.392481 | 0.11496341 | 15.088345 | -0.32800964 |
39 | 1 | -80.178917 | 0.52112252E-01 | -28.983173 | 1.0708012 |
40 | 0 | 46.824341 | 0.10529732E-02 | 16.295060 | |
41 | 7 | -0.29769246E-08 | -0.18967486E-14 | 0.17735324E-14 | -0.50565546E-16 |
42 | 6 | 0.41018669E-05 | 0.27270264E-08 | 0.31943096E-02 | -0.26796545E-04 |
43 | 5 | -0.28850807E-03 | 0.16127836E-05 | -0.22397690 | 0.19583774E-02 |
44 | 4 | 0.65943933E-02 | 0.73359200E-04 | 4.8337480 | -0.45305377E-01 |
45 | 3 | -0.57777404E-01 | 0.58296435E-03 | -38.045154 | 0.39891614 |
46 | 2 | 0.20497420 | 0.96924505E-03 | 116.53015 | -1.4185573 |
47 | 1 | -0.29573351 | 0.29504543E-03 | -143.93450 | 2.0494869 |
48 | 0 | 0.14415612 | 0.71556298E-05 | 60.838472 | |
49 | 7 | -0.17284864E-08 | -0.37804902E-15 | 0.73321507E-14 | -0.99177345E-16 |
50 | 6 | 0.68009956E-05 | 0.46606830E-08 | 0.31864372E-02 | -0.26730506E-04 |
51 | 5 | -0.48976058E-03 | 0.27623059E-05 | -0.22352946 | 0.19544281E-02 |
52 | 4 | 0.11270010E-01 | 0.12574428E-03 | 4.8262959 | -0.45233742E-01 |
53 | 3 | -0.98979995E-01 | 0.10001134E-02 | -38.003058 | 0.39845083 |
54 | 2 | 0.35147541 | 0.16637932E-02 | 116.44822 | -1.4174614 |
55 | 1 | -0.50731320 | 0.50715641E-03 | -143.88627 | 2.0486942 |
56 | 0 | 0.24734252 | 0.12206389E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.4731_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7446E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.2464E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6734E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9874E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4480E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.1632E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0758E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5500E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.1870E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.8282E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1082 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 0.1037 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.7642E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.6579E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.6281E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.6443E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0509E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4530E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6975E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2913E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8486E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2277E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6313E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0762E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 41211.20700 | 49453.44840 | 3.43672 | 4.12407 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 13352.54773 | 16023.05728 | 0.65438 | 1.33138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -27.60000 | 3.41898E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20973.47803 | 25168.17364 | 1.48371 | 1.78046 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 2052.76227 | 2463.31472 | 9.10152E-002 | 1.21700 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60000 | 3.41898E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 62053.06 | 4.12407 | 4.12407 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 95244.28 | 1.33138 | 1.33138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 33330.10 | 1.78046 | 1.78046 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 87062.07 | 1.21700 | 1.21700 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.12407 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.78046 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.12407 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.12407 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.12407 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.12407 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.12407 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.12407 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.78046 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.78046 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.78046 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.78046 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.78046 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.78046 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.12407 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.78046 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.12407 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.12407 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7046.37621 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.12407 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.12407 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.12407 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.72189 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.12407 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.06203 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.74938 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 80122.60000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 40061.30000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78826 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78826 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 80122.60000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 151398.57383 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 151398.57383 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.78046 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.78046 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1905.17298 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.78046 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.78046 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.78046 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.17510 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.78046 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.89023 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.18697 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38689.56000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19344.78000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74507 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74507 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38689.56000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 99935.47054 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 99935.47054 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 77135.2 | 10.36 | 10.32 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 37410.2 | 11.59 | 11.54 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | N/A | 2.689 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | N/A | 2.689 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | N/A | 2.689 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.143 | 0.138 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.879 | 0.777 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.243 | 0.230 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.5170969231E-002 | 0.3744446232 | Pass | Pass | 6.3014900220E-002 | 0.1380301460 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1249133113 | 0.5767663465 | Pass | Pass | 2.4857995338E-002 | 9.5125454005E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2764399707 | 0.2883559744 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 960.34 | 127.22 | 2214.66 | 19.84 | 600.43 | 3922.51 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.139 | 0.143 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.777 | 0.879 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.234 | 0.243 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.689 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.689 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.5182 | 371.75 | 3538.38 | LightsWired | LTG_SCH_DINING | 93.86 | 168.00 | 77.52 | 0.0000 | Y | 51.49 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.3127 | 139.41 | 1298.24 | LightsWired | LTG_SCH_KITCHEN | 80.88 | 168.00 | 80.41 | 0.0000 | Y | 19.60 |
Interior Lighting Total | 9.4622 | 511.15 | 4836.62 | 71.09 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3538.38 | 477.68 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.52 | AstronomicalClock | - | 49.11 | 49.11 | 1.93 | |
EXTERIOR_LIGHTS_B | 3124.83 | AstronomicalClock | - | 83.57 | 73.23 | 42.95 | |
Exterior Lighting Total | 3334.35 | 44.89 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 80122.60 | 63157.44 | 16965.16 | 0.79 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38689.56 | 28826.43 | 9863.13 | 0.75 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 77135.2 | 10.36 | 10.32 | ||||
PSZ-AC_2:2 COOLING COIL | 37410.2 | 11.59 | 11.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 151398.57 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 99935.47 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.55 | 1983.06 | 778.12 | 1.00 | 0.59 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.12 | 7046.38 | 1708.60 | 1.00 | 1.17 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.78 | 1905.17 | 1070.05 | 1.00 | 1.33 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 41211.21 | 49453.45 | 133.03 | 3.437 | 4.124 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00847 | 33.08 | 0.00631 | 1.331 | 0.00 |
KITCHEN | 20973.48 | 25168.17 | 180.54 | 1.484 | 1.780 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.00883 | 31.96 | 0.00630 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 13352.55 | 16023.06 | 43.10 | 0.654 | 1.331 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00781 | -27.60 | 0.00034 | 1.331 | 0.00 |
KITCHEN | 2052.76 | 2463.31 | 17.67 | 0.091 | 1.217 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00662 | -27.60 | 0.00034 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.12 | 4.12 | 1.33 | 1.33 | 4.1241 | 4.1241 | 4.1241 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.78 | 1.78 | 1.22 | 1.22 | 1.7805 | 1.7805 | 1.7805 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 80122.600 | 63157.441 | 4.124070 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40061.30 | 36561.85 | 2.749380 | 27.03 | 15.45 | 0.00777362 | 11.21 | 8.73 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 48.4246 | 23.99 | 0.00847351 | 39.9288 | 41183.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 151398.574 | 151398.574 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 151398.57 | 151398.57 | 4.124068 | 5.31 | 4.21 | 0.00539814 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 32.2831 | 21.00 | 0.00780863 | 44.1643 | 13351.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38689.560 | 28826.430 | 1.780460 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19344.78 | 19289.06 | 1.186973 | 31.26 | 16.24 | 0.00702815 | 11.80 | 8.99 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 102.5298 | 25.98 | 0.00882423 | 36.9029 | 20080.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 99935.471 | 99935.471 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:40:00 | 99935.47 | 99935.47 | 1.780457 | -13.04 | -13.04 | 0.00223394 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 68.3534 | 19.00 | 0.00632053 | 40.5604 | 1259.83 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 80122.600 | 63157.441 | 4.124070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2908 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.124068 | 4.34322094 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 40061.30 | 36561.85 | 1.0000 | 2.89548172 | 2.749380 | 27.03 | 15.45 | 0.00777362 | 46989.4 | 11.21 | 8.73 | 0.00700000 | 28915.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40061.30 | 33.40 | 0.00630683 | 16.37 | 1.33137743 | 48.4246 | 23.99 | 0.00847351 | 23.99 | 0.00847351 | 39.9288 | 41183.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 151398.574 | 151398.574 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.124068 | 4.34322094 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 151398.57 | 151398.57 | 1.0000 | 4.34322094 | 4.124068 | 5.31 | 4.21 | 0.00539814 | 18889.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 151398.57 | -27.60 | 0.00034190 | -27.60 | 1.33137743 | 32.2831 | 21.00 | 0.00780863 | 21.00 | 0.00780863 | 44.1643 | 13351.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38689.560 | 28826.430 | 1.780460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9050 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.780457 | 1.87507010 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19344.78 | 19289.06 | 1.0000 | 1.25004895 | 1.186973 | 31.26 | 16.24 | 0.00702815 | 49400.9 | 11.80 | 8.99 | 0.00700000 | 29519.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19344.78 | 33.40 | 0.00630683 | 16.37 | 1.21700195 | 102.5298 | 25.95 | 0.00882423 | 25.98 | 0.00882423 | 36.9029 | 20080.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99935.471 | 99935.471 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.780457 | 1.87507010 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:40:00 | Sensible | 99935.47 | 99935.47 | 1.0000 | 1.87507010 | 1.780457 | -13.04 | -13.04 | 0.00223394 | -7569.5 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99935.47 | -27.60 | 0.00034190 | -27.60 | 1.21700195 | 68.3534 | 18.41 | 0.00632053 | 19.00 | 0.00632053 | 40.5604 | 1259.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.12 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.78 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2964.33 | 5094.83 | 1518.33 |
KITCHEN | 4463.50 | 5942.00 | 3478.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4574.00 | 6782.50 | 3589.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 22.67 | 18.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 173.67 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 22.67 | 174.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.573 | 0.599 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.212 | 0.044 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.066 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.763 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 37699805.87 | 0.00 | 37699805.87 | 4958593.45 | 42658399.32 | 41986318.57 | 1438.90 | 5980.25 | 1340.85 | 346.21 |
KITCHEN | 31964705.24 | 0.00 | 31964705.24 | 218223.79 | 32182929.03 | 38379373.44 | 5998.53 | 2752.97 | 8.51 | 603.33 |
Total Facility | 69664511.11 | 0.00 | 69664511.11 | 5176817.24 | 74841328.35 | 80365692.01 | 5999.18 | 5982.16 | 1345.90 | 703.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.4236 | 0.0000 | 1.4236 | 0.1865 | 1.6101 | 1.3314 | 0.00 | 5861.51 | 1325.49 |
KITCHEN | 1.1922 | 0.0000 | 1.1922 | 0.0052 | 1.1974 | 1.2170 | 4484.65 | 2695.77 | 6.58 |
Total Facility | 2.6158 | 0.0000 | 2.6158 | 0.1917 | 2.8075 | 2.5484 | 4484.65 | 5863.36 | 1329.70 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 41813079.26 | 0.00 | 41813079.26 | 41986318.57 | 1438.41 | 0.10 | 7321.49 | 346.21 |
PSZ-AC_2:2 | 35451618.42 | 0.00 | 35451618.42 | 38379373.44 | 1433.18 | 1.32 | 7325.50 | 603.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.5790 | 0.0000 | 1.5790 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3222 | 0.0000 | 1.3222 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1232.25 | 327.51 | 5973.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 149.01 | 3181.30 | 4460.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.1133 | 1.7683 | 1.4769 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.3745 | 1.3457 | 1.3080 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
Electricity:Building | 548.26 | 4052.25 | 01-JAN-01:10 | 30253.07 | 02-JAN-11:10 |
Electricity:Zone:DINING | 176.65 | 991.88 | 01-JAN-01:10 | 9336.09 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 531.40 | 3643.21 | 01-JAN-01:10 | 27887.91 | 02-JAN-11:10 |
InteriorLights:Electricity | 71.09 | 557.53 | 04-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 51.49 | 395.98 | 04-JUN-05:00 | 3065.69 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 71.09 | 557.53 | 04-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 71.09 | 557.53 | 04-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 51.49 | 395.98 | 04-JUN-05:00 | 3065.69 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 71.09 | 557.53 | 04-JUN-05:00 | 4035.02 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 371.61 | 3060.37 | 01-JAN-01:10 | 21021.20 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.60 | 161.55 | 01-JAN-01:10 | 969.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.32 | 2970.72 | 01-JAN-01:10 | 24680.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.16 | 480.94 | 01-JAN-01:10 | 6993.92 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.19 | 1603.14 | 01-JAN-01:10 | 23313.05 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.16 | 2489.78 | 01-JAN-01:10 | 17686.72 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.03 | 1122.20 | 01-JAN-01:10 | 16319.14 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.20 | 1037.99 | 24-JAN-23:30 | 3437.19 | 07-SEP-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 120.31 | 1103.06 | 28-JAN-01:10 | 6475.75 | 04-JUL-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.53 | 0.00 | 01-JAN-11:10 | 1462.80 | 05-SEP-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 28.81 | 777.30 | 03-MAR-00:10 | 1076.23 | 02-MAY-12:20 |
ElectricityPurchased:Facility | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
ElectricityPurchased:Plant | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
Cogeneration:ElectricityPurchased | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
General:Cogeneration:ElectricityPurchased | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
ElectricityNet:Plant | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
Cogeneration:ElectricityNet | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
General:Cogeneration:ElectricityNet | 927.04 | 7342.70 | 28-JAN-01:10 | 63684.18 | 17-JUL-18:00 |
Electricity:HVAC | 213.58 | 0.00 | 01-JAN-01:10 | 33487.44 | 17-JUL-17:30 |
Fans:Electricity | 162.47 | 0.00 | 01-JAN-01:10 | 8558.14 | 10-JAN-23:10 |
General:Fans:Electricity | 162.47 | 0.00 | 01-JAN-01:10 | 8558.14 | 10-JAN-23:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 51.11 | 0.00 | 01-JAN-00:10 | 25422.49 | 17-JUL-17:30 |
General:Cooling:Electricity | 51.11 | 0.00 | 01-JAN-00:10 | 25422.49 | 17-JUL-17:30 |
ExteriorLights:Electricity | 44.89 | 0.00 | 01-JAN-08:20 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.89 | 0.00 | 01-JAN-08:20 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.19 | 18-APR-18:30 |
Water Heater:WaterSystems:Electricity | 75.52 | 0.00 | 01-JAN-01:10 | 4742.19 | 18-APR-18:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 03-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 03-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1475.81 | 2803.57 | 01-JAN-01:20 | 212728.43 | 10-JAN-21:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 613.32 | 0.00 | 01-JAN-01:10 | 189248.22 | 07-JAN-04:10 |
Heating:NaturalGas | 613.32 | 0.00 | 01-JAN-01:10 | 189248.22 | 07-JAN-04:10 |
General:Heating:NaturalGas | 613.32 | 0.00 | 01-JAN-01:10 | 189248.22 | 07-JAN-04:10 |
NaturalGas:Plant | 392.70 | 993.32 | 01-JAN-00:10 | 35098.63 | 16-FEB-07:20 |
WaterSystems:NaturalGas | 392.70 | 993.32 | 01-JAN-00:10 | 35098.63 | 16-FEB-07:20 |
Water Heater:WaterSystems:NaturalGas | 392.70 | 993.32 | 01-JAN-00:10 | 35098.63 | 16-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 05-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1721.09 | 3205.95 | 11-JAN-01:10 | 200972.58 | 11-JAN-04:20 |
EnergyTransfer:Building | 697.89 | 1602.98 | 11-JAN-01:10 | 62593.53 | 11-JAN-04:20 |
EnergyTransfer:Zone:KITCHEN | 431.17 | 1602.98 | 11-JAN-01:10 | 28285.73 | 20-OCT-04:10 |
Refrigeration:EnergyTransfer | 140.95 | 2714.01 | 24-JAN-23:10 | 7834.84 | 08-SEP-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.48 | 1357.01 | 24-JAN-23:10 | 3917.42 | 08-SEP-03:30 |
General:Refrigeration:EnergyTransfer | 70.48 | 1357.01 | 24-JAN-23:10 | 3917.42 | 08-SEP-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.48 | 1357.01 | 24-JAN-23:10 | 3917.42 | 08-SEP-03:30 |
EnergyTransfer:Plant | 350.09 | 1602.98 | 11-JAN-01:10 | 21505.84 | 27-FEB-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.26 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.22 | 1341.91 | 03-MAR-00:10 | 2238.70 | 02-MAY-12:20 |
EnergyTransfer:Zone:DINING | 266.72 | 0.00 | 01-JAN-01:10 | 60473.20 | 11-JAN-04:20 |
Heating:EnergyTransfer | 11.50 | 0.00 | 01-JAN-00:10 | 39290.81 | 11-JAN-04:20 |
Heating:EnergyTransfer:Zone:DINING | 11.48 | 0.00 | 01-JAN-00:10 | 39290.81 | 11-JAN-04:20 |
General:Heating:EnergyTransfer | 11.50 | 0.00 | 01-JAN-00:10 | 39290.81 | 11-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DINING | 11.48 | 0.00 | 01-JAN-00:10 | 39290.81 | 11-JAN-04:20 |
Cooling:EnergyTransfer | 615.91 | 0.00 | 01-JAN-01:10 | 49178.94 | 17-JUL-17:30 |
Cooling:EnergyTransfer:Zone:DINING | 255.24 | 0.00 | 01-JAN-01:10 | 31183.97 | 17-JUL-17:40 |
General:Cooling:EnergyTransfer | 615.91 | 0.00 | 01-JAN-01:10 | 49178.94 | 17-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:DINING | 255.24 | 0.00 | 01-JAN-01:10 | 31183.97 | 17-JUL-17:40 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1822.47 | 07-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1822.47 | 07-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 360.67 | 0.00 | 01-JAN-01:10 | 24456.45 | 20-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 360.67 | 0.00 | 01-JAN-01:10 | 24456.45 | 20-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 279.61 | 0.00 | 01-JAN-01:10 | 19194.64 | 16-FEB-07:30 |
PlantLoopHeatingDemand:Plant | 279.61 | 0.00 | 01-JAN-01:10 | 19194.64 | 16-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19194.64 | 16-FEB-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 279.61 | 0.00 | 01-JAN-01:10 | 19194.64 | 16-FEB-07:30 |
EnergyTransfer:HVAC | 673.11 | 0.00 | 01-JAN-01:10 | 151398.57 | 07-JAN-04:10 |
HeatingCoils:EnergyTransfer | 490.66 | 0.00 | 01-JAN-01:10 | 151398.57 | 07-JAN-04:10 |
CoolingCoils:EnergyTransfer | 182.45 | 0.00 | 01-JAN-00:10 | 85423.50 | 17-JUL-17:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19194.64 | 16-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 279.61 | 0.00 | 01-JAN-01:10 | 19194.64 | 16-FEB-07:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 11.480 | -255.239 | 0.000 | 0.000 | 229.878 | 51.493 | 93.867 | 47.833 | 0.000 | 1.934 | 0.001 | 0.000 | -35.877 | 0.000 | -77.114 | -68.256 |
KITCHEN | 0.000 | 0.000 | 0.022 | -360.658 | 0.000 | 0.000 | 6.133 | 19.596 | 297.703 | 0.000 | 0.000 | 0.021 | 41.078 | 0.000 | 0.000 | 0.000 | -3.894 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.226 | 26.798 | 0.000 | 0.000 | 0.000 | -33.023 | -0.000 |
Total Facility | 0.000 | 0.000 | 11.502 | -615.897 | 0.000 | 0.000 | 236.011 | 71.089 | 391.570 | 47.833 | 0.000 | 8.182 | 67.876 | 0.000 | -35.877 | 0.000 | -114.032 | -68.257 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 11-JAN-00:01 | 0.00 | 0.00 | 0.00 | -65905.54 | 0.00 | 0.00 | 1157.79 | 510.94 | 541.06 | 0.00 | 0.00 | 0.00 | 70219.53 | 0.00 | -5302.72 | 0.00 | -1221.06 | 0.00 |
KITCHEN | 27-JAN-05:01 | 0.00 | 0.00 | 0.00 | -59737.69 | 0.00 | 0.00 | 26.10 | 215.40 | 7253.89 | 0.00 | 0.00 | 0.00 | 52402.15 | 0.00 | -0.00 | 0.00 | -159.86 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-03:21 | 0.00 | 0.00 | 0.00 | -96142.10 | 0.00 | 0.00 | 0.00 | 672.49 | 4717.49 | 0.00 | 0.00 | 417.91 | 91698.43 | 0.00 | -1046.58 | 0.00 | -317.64 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-FEB-04:01 | 0.00 | 0.00 | 99479.93 | 0.00 | 0.00 | 0.00 | 0.00 | 510.94 | 901.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2105.75 | 0.00 | -1175.49 | -97611.40 |
KITCHEN | 20-NOV-05:05 | 0.00 | 0.00 | 17062.28 | 0.00 | 0.00 | 0.00 | 21.61 | 215.40 | 7253.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -98.99 | -24454.20 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-04:01 | 0.00 | 0.00 | 99479.93 | 0.00 | 0.00 | 0.00 | 0.00 | 672.49 | 4717.49 | 0.00 | 0.00 | 289.56 | 0.00 | 0.00 | -2105.75 | 0.00 | -1999.36 | -101054.37 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.1241 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.1241 | 0.3228 | 1.0000 | Not calculated | 1.3314 | 0.3228 | ||
PSZ-AC_2:2 | 1.7805 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.7805 | 0.1026 | 1.0000 | Not calculated | 0.1826 | 0.1026 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.1241 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.1241 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3228 | ||
PSZ-AC_2:2 | 1.7805 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.7805 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1026 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.1241 | 4.1241 | 4.1241 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7805 | 1.7805 | 1.7805 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.1241 | 4.1241 | 4.1241 | 4.1241 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.7805 | 1.7805 | 1.7805 | 1.7805 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.1241 | 4.1241 | 4.1241 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7805 | 1.7805 | 1.7805 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.1241 | 4.1241 | 4.1241 | 4.1241 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.7805 | 1.7805 | 1.7805 | 1.7805 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 613.32 | 189248.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 51.11 | 25422.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 71.09 | 4035.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.89 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.19 | 23313.05 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 162.47 | 8558.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.52 | 4742.19 | 392.70 | 35098.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.53 | 1462.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.81 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 521.52 | 927.04 |
Natural Gas | 469.79 | 1475.81 |
Additional | 0.00 | 0.00 |
Total | 991.30 | 2402.86 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 139.07 |
Space Heating | 0.00 |
Space Cooling | 99.99 |
Fans (All) | 317.86 |
Service Water Heating | 147.75 |
Receptacle Equipment | 900.54 |
Miscellaneous (All) | 1813.63 |
Subtotal | 1813.63 |
Natural Gas [MJ/m2] | |
Space Heating | 1199.88 |
Service Water Heating | 768.27 |
Miscellaneous (All) | 2887.22 |
Subtotal | 2887.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.96 |
Space Heating | 25.52 |
Space Cooling | 2.13 |
Fans (All) | 6.76 |
Service Water Heating | 19.49 |
Receptacle Equipment | 38.71 |
Miscellaneous | 4.43 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4894. | 8760. |
LTG_SCH_KITCHEN | 4218. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_SETBACK | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_SETBACK | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8644.83 | 115.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7488.17 | 471.17 | 389.83 | 402.67 | 8.17 |
Min | 7488.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 471.17 | 389.83 | 402.67 | 8.17 |
Average | 8297.67 | 195.44 | 129.94 | 134.22 | 2.72 |
Sum | 24893.00 | 586.33 | 389.83 | 402.67 | 8.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8475.17 | 284.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 7666.00 | 607.83 | 203.50 | 168.67 | 114.00 |
Min | 7666.00 | 3.17 | 0.00 | 0.00 | 0.00 |
Max | 8756.83 | 607.83 | 203.50 | 168.67 | 114.00 |
Average | 8299.33 | 298.61 | 67.83 | 56.22 | 38.00 |
Sum | 24898.00 | 895.83 | 203.50 | 168.67 | 114.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 823718.00 | 504.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 18460.50 | 772.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823718.00 | 772.50 | 0.00 | 0.00 | 0.00 |
Average | 280726.17 | 425.50 | 0.00 | 0.00 | 0.00 |
Sum | 842178.50 | 1276.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:24:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.864056E+10 | 65907.39 | 11-JAN-00:01 | -31.6 | -31.8 | 0.120019E+11 | 11278.34 | 14-JAN-19:00 | 9.40 | 3.77 |
February | 0.117148E+11 | 52318.23 | 04-FEB-00:01 | -21.0 | -21.3 | 0.109970E+11 | 12938.00 | 27-FEB-12:00 | 17.20 | 6.49 |
March | 0.157292E+11 | 54995.51 | 05-MAR-00:01 | -23.1 | -23.6 | 0.122345E+11 | 12620.55 | 14-MAR-11:00 | 14.40 | 6.37 |
April | 0.192020E+11 | 31035.67 | 28-APR-23:01 | -4.6 | -6.2 | 0.125519E+11 | 14050.30 | 22-APR-18:19 | -4.6 | -6.2 |
May | 0.230468E+11 | 28008.81 | 07-MAY-23:01 | -2.3 | -2.8 | 0.137182E+11 | 14051.24 | 20-MAY-18:00 | 22.80 | 13.54 |
June | 0.286986E+11 | 51604.74 | 23-JUN-00:41 | 18.48 | 10.89 | 0.144880E+11 | 14052.34 | 03-JUN-18:00 | 18.48 | 10.89 |
July | 0.343490E+11 | 51874.72 | 26-JUL-03:44 | 20.82 | 11.39 | 0.151520E+11 | 14051.52 | 01-JUL-18:10 | 20.82 | 11.39 |
August | 0.333750E+11 | 56971.45 | 05-AUG-01:21 | 17.50 | 9.44 | 0.151953E+11 | 14051.03 | 19-AUG-18:00 | 16.10 | 11.53 |
September | 0.280686E+11 | 54421.76 | 03-SEP-01:21 | 18.60 | 10.26 | 0.139520E+11 | 14050.92 | 23-SEP-18:40 | 16.50 | 9.82 |
October | 0.239858E+11 | 27969.99 | 21-OCT-04:01 | -1.0 | -1.9 | 0.133020E+11 | 14045.53 | 28-OCT-18:40 | 13.70 | 7.05 |
November | 0.171611E+11 | 44617.20 | 27-NOV-00:01 | -15.1 | -15.9 | 0.120353E+11 | 14046.94 | 04-NOV-18:10 | -15.1 | -15.9 |
December | 0.112698E+11 | 55621.73 | 29-DEC-00:01 | -23.6 | -23.9 | 0.120268E+11 | 11922.54 | 06-DEC-12:00 | -23.6 | -23.9 |
Annual Sum or Average | 0.255241E+12 | 0.157655E+12 | ||||||||
Minimum of Months | 0.864056E+10 | 27969.99 | -31.6 | -31.8 | 0.109970E+11 | 11278.34 | -23.6 | -23.9 | ||
Maximum of Months | 0.343490E+11 | 65907.39 | 20.82 | 11.39 | 0.151953E+11 | 14052.34 | 22.80 | 13.54 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271995E+11 | 59499.64 | 27-JAN-05:01 | -27.8 | -28.2 | 0.103934E+11 | 6845.23 | 14-JAN-11:00 | -27.8 | -28.2 |
February | 0.256621E+11 | 56401.13 | 01-FEB-05:01 | -25.0 | -25.2 | 0.939959E+10 | 6929.50 | 27-FEB-11:00 | 16.10 | 6.08 |
March | 0.292121E+11 | 49367.02 | 05-MAR-05:01 | -20.3 | -21.0 | 0.104080E+11 | 6882.41 | 14-MAR-10:00 | 12.80 | 5.58 |
April | 0.288306E+11 | 38531.86 | 07-APR-03:31 | 12.43 | 5.56 | 0.101238E+11 | 6931.57 | 07-APR-10:09 | 18.40 | 7.41 |
May | 0.305716E+11 | 52643.28 | 19-MAY-04:01 | 10.40 | 8.27 | 0.105051E+11 | 6931.61 | 19-MAY-10:30 | 21.10 | 13.12 |
June | 0.310767E+11 | 56947.53 | 20-JUN-04:01 | 7.15 | 4.77 | 0.102342E+11 | 6931.64 | 06-JUN-10:09 | 7.15 | 4.77 |
July | 0.331694E+11 | 56184.70 | 21-JUL-04:01 | 12.02 | 7.75 | 0.105889E+11 | 6931.65 | 07-JUL-10:00 | 12.02 | 7.75 |
August | 0.330499E+11 | 56269.64 | 04-AUG-04:01 | 10.10 | 6.74 | 0.105884E+11 | 6931.61 | 23-AUG-10:50 | 18.72 | 10.87 |
September | 0.314644E+11 | 53369.00 | 15-SEP-04:01 | 12.80 | 8.61 | 0.102061E+11 | 6931.61 | 07-SEP-10:39 | 12.80 | 8.61 |
October | 0.320524E+11 | 59633.17 | 20-OCT-04:01 | 4.13 | 1.44 | 0.104852E+11 | 6931.58 | 16-OCT-10:20 | 4.13 | 1.44 |
November | 0.295594E+11 | 45166.23 | 27-NOV-05:01 | -15.4 | -16.5 | 0.100958E+11 | 6925.65 | 17-NOV-11:00 | -15.4 | -16.5 |
December | 0.288224E+11 | 57420.60 | 29-DEC-05:01 | -25.0 | -25.3 | 0.103980E+11 | 6888.78 | 06-DEC-11:00 | -25.0 | -25.3 |
Annual Sum or Average | 0.360670E+12 | 0.123427E+12 | ||||||||
Minimum of Months | 0.256621E+11 | 38531.86 | -27.8 | -28.2 | 0.939959E+10 | 6845.23 | -27.8 | -28.2 | ||
Maximum of Months | 0.331694E+11 | 59633.17 | 12.80 | 8.61 | 0.105889E+11 | 6931.65 | 21.10 | 13.12 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.9 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 | -4.1 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 | 0.55 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 | 13.32 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 | 11.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 | 11.59 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 | 6.94 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 | 1.54 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.00 | 0.00 | -12.4 | -13.9 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.00 | 0.00 | 19.45 | 13.32 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548211E+10 | 90978.95 | 06-JAN-04:16 | -24.4 |
February | 0.181065E+10 | 99480.47 | 06-FEB-04:01 | -0.6 |
March | 0.111923E+10 | 96129.39 | 04-MAR-05:01 | -19.1 |
April | 0.196931E+09 | 47870.51 | 29-APR-03:02 | -6.9 |
May | 0.114099E+09 | 42502.47 | 08-MAY-03:02 | -2.7 |
June | 938622.59 | 7106.27 | 15-JUN-04:03 | 0.97 |
July | 42762.14 | 712.70 | 09-JUL-04:05 | 6.20 |
August | 146848.24 | 2447.47 | 18-AUG-04:03 | 7.20 |
September | 1687907.73 | 6977.81 | 19-SEP-04:01 | 2.20 |
October | 27612738.04 | 17552.11 | 10-OCT-03:02 | -4.1 |
November | 0.408109E+09 | 74646.87 | 28-NOV-04:01 | -5.9 |
December | 0.231845E+10 | 89152.73 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.114800E+11 | |||
Minimum of Months | 42762.14 | 712.70 | -25.0 | |
Maximum of Months | 0.548211E+10 | 99480.47 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9054943.59 | 16402.26 | 07-JAN-05:02 | -21.6 |
February | 2775527.30 | 11607.71 | 04-FEB-05:02 | -20.4 |
March | 3209244.66 | 13160.19 | 05-MAR-05:02 | -20.3 |
April | 604181.40 | 10069.69 | 29-APR-04:03 | -7.8 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 53362.85 | 848.75 | 21-OCT-04:04 | -1.0 |
November | 2147908.14 | 17077.27 | 20-NOV-05:05 | -1.7 |
December | 4185293.80 | 10614.03 | 31-DEC-05:02 | -24.7 |
Annual Sum or Average | 22030461.74 | |||
Minimum of Months | 0.00 | 0.00 | -24.7 | |
Maximum of Months | 9054943.59 | 17077.27 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.459791E+10 | 3065.69 | 02-JAN-16:30 | 0.106297E+11 | 6993.92 | 01-JAN-11:09 |
February | 0.405187E+10 | 3065.69 | 01-FEB-17:19 | 0.960102E+10 | 6993.92 | 01-FEB-11:09 |
March | 0.443207E+10 | 3065.69 | 01-MAR-18:10 | 0.106297E+11 | 6993.92 | 01-MAR-11:09 |
April | 0.414359E+10 | 3065.69 | 01-APR-18:30 | 0.102868E+11 | 6993.92 | 01-APR-10:09 |
May | 0.421449E+10 | 3065.69 | 01-MAY-19:30 | 0.106297E+11 | 6993.92 | 01-MAY-10:09 |
June | 0.403060E+10 | 3065.69 | 01-JUN-19:00 | 0.102868E+11 | 6993.92 | 01-JUN-10:09 |
July | 0.416148E+10 | 3065.69 | 01-JUL-20:19 | 0.106297E+11 | 6993.92 | 01-JUL-10:09 |
August | 0.426590E+10 | 3065.69 | 01-AUG-19:30 | 0.106297E+11 | 6993.92 | 01-AUG-10:09 |
September | 0.418537E+10 | 3065.69 | 01-SEP-19:10 | 0.102868E+11 | 6993.92 | 01-SEP-10:09 |
October | 0.441165E+10 | 3065.69 | 02-OCT-17:49 | 0.106297E+11 | 6993.92 | 01-OCT-10:09 |
November | 0.439801E+10 | 3065.69 | 01-NOV-17:10 | 0.102868E+11 | 6993.92 | 01-NOV-10:09 |
December | 0.459975E+10 | 3065.69 | 01-DEC-16:40 | 0.106297E+11 | 6993.92 | 01-DEC-11:09 |
Annual Sum or Average | 0.514927E+11 | 0.125156E+12 | ||||
Minimum of Months | 0.403060E+10 | 3065.69 | 0.960102E+10 | 6993.92 | ||
Maximum of Months | 0.459975E+10 | 3065.69 | 0.106297E+11 | 6993.92 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165581E+10 | 969.33 | 02-JAN-10:09 | 0.284656E+11 | 17686.72 | 01-JAN-11:09 |
February | 0.149975E+10 | 969.33 | 01-FEB-10:09 | 0.257108E+11 | 17686.72 | 01-FEB-11:09 |
March | 0.168217E+10 | 969.33 | 01-MAR-10:09 | 0.284657E+11 | 17686.72 | 01-MAR-11:09 |
April | 0.160889E+10 | 969.33 | 01-APR-16:10 | 0.275474E+11 | 17686.72 | 01-APR-10:09 |
May | 0.166899E+10 | 969.33 | 01-MAY-09:09 | 0.284656E+11 | 17686.72 | 01-MAY-10:09 |
June | 0.162595E+10 | 969.33 | 01-JUN-09:09 | 0.275474E+11 | 17686.72 | 01-JUN-10:09 |
July | 0.165212E+10 | 969.33 | 01-JUL-16:10 | 0.284656E+11 | 17686.72 | 01-JUL-10:09 |
August | 0.168217E+10 | 969.33 | 01-AUG-09:09 | 0.284657E+11 | 17686.72 | 01-AUG-10:09 |
September | 0.160928E+10 | 969.33 | 01-SEP-09:09 | 0.275474E+11 | 17686.72 | 01-SEP-10:09 |
October | 0.165561E+10 | 969.33 | 02-OCT-09:09 | 0.284656E+11 | 17686.72 | 01-OCT-10:09 |
November | 0.160288E+10 | 969.33 | 01-NOV-09:09 | 0.275473E+11 | 17686.72 | 01-NOV-10:09 |
December | 0.165232E+10 | 969.33 | 01-DEC-10:09 | 0.284656E+11 | 17686.72 | 01-DEC-11:09 |
Annual Sum or Average | 0.195960E+11 | 0.335159E+12 | ||||
Minimum of Months | 0.149975E+10 | 969.33 | 0.257108E+11 | 17686.72 | ||
Maximum of Months | 0.168217E+10 | 969.33 | 0.284657E+11 | 17686.72 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.459791E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140908E+11 |
February | 0.272721E+11 | 0.405187E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967687E+10 |
March | 0.305458E+11 | 0.443207E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903342E+10 |
April | 0.292871E+11 | 0.414359E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592188E+10 |
May | 0.303219E+11 | 0.421449E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29036840.24 | 0.481206E+10 |
June | 0.295292E+11 | 0.403060E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268823E+09 | 0.238345E+10 |
July | 0.300798E+11 | 0.416148E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805922E+09 | 0.120604E+10 |
August | 0.305458E+11 | 0.426590E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606310E+09 | 0.172692E+10 |
September | 0.292871E+11 | 0.418537E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223017E+09 | 0.331858E+10 |
October | 0.300980E+11 | 0.441165E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1380907.01 | 0.558308E+10 |
November | 0.290996E+11 | 0.439801E+10 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787091E+10 |
December | 0.300798E+11 | 0.459975E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114902E+11 |
Annual Sum or Average | 0.356244E+12 | 0.514927E+11 | 0.125156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193449E+10 | 0.771141E+11 |
Minimum of Months | 0.272721E+11 | 0.403060E+10 | 0.960102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120604E+10 |
Maximum of Months | 0.305458E+11 | 0.459975E+10 | 0.106297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805922E+09 | 0.140908E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.165581E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603402E+09 |
February | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459557E+09 |
March | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410407E+09 |
April | 0.786997E+09 | 0.160889E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286289E+09 |
May | 0.814802E+09 | 0.166899E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 331290.24 | 0.294481E+09 |
June | 0.793501E+09 | 0.162595E+10 | 0.227469E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2726027.59 | 0.171533E+09 |
July | 0.808298E+09 | 0.165212E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8082560.40 | 0.110038E+09 |
August | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 7282751.94 | 0.128492E+09 |
September | 0.786997E+09 | 0.160928E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 3077315.31 | 0.224134E+09 |
October | 0.808786E+09 | 0.165561E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295310E+09 |
November | 0.781956E+09 | 0.160288E+10 | 0.227468E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416713E+09 |
December | 0.808298E+09 | 0.165232E+10 | 0.235050E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494056E+09 |
Annual Sum or Average | 0.957291E+10 | 0.195960E+11 | 0.276753E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 21499945.48 | 0.389441E+10 |
Minimum of Months | 0.732850E+09 | 0.149975E+10 | 0.212304E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110038E+09 |
Maximum of Months | 0.820818E+09 | 0.168217E+10 | 0.235051E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8082560.40 | 0.603402E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549171E+09 | 0.136197E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450545E+09 | 0.165468E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570615E+09 | 0.267044E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480510E+09 | 0.312471E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359301E+09 | 0.422146E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313734E+09 | 0.474520E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456280E+09 | 0.483634E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530707E+09 | 0.401092E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538209E+09 | 0.254593E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674388E+09 | 0.179949E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637995E+09 | 0.115192E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664311E+09 | 0.900398E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622576E+10 | 0.330235E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313734E+09 | 0.900398E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674388E+09 | 0.483634E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3065.69 | 02-JAN-16:30 | 6993.92 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21479.95 | 10-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 3065.69 | 01-FEB-17:19 | 6993.92 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 18207.42 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 3065.69 | 01-MAR-18:10 | 6993.92 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 17522.82 | 04-MAR-19:55 |
April | 30255.31 | 01-APR-18:10 | 3065.69 | 01-APR-18:30 | 6993.92 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 9817.75 | 28-APR-19:53 |
May | 30255.31 | 06-MAY-18:10 | 3065.69 | 01-MAY-19:30 | 6993.92 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.65 | 20-MAY-17:10 | 8202.70 | 22-MAY-19:00 |
June | 30255.31 | 03-JUN-18:10 | 3065.69 | 01-JUN-19:00 | 6993.92 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2471.18 | 29-JUN-13:00 | 5704.17 | 16-JUN-11:10 |
July | 30255.31 | 01-JUL-18:10 | 3065.69 | 01-JUL-20:19 | 6993.92 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.74 | 17-JUL-17:03 | 3613.12 | 07-JUL-20:00 |
August | 30255.31 | 05-AUG-18:10 | 3065.69 | 01-AUG-19:30 | 6993.92 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3721.17 | 05-AUG-18:03 | 5009.19 | 17-AUG-12:00 |
September | 30255.31 | 02-SEP-18:10 | 3065.69 | 01-SEP-19:10 | 6993.92 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2955.18 | 02-SEP-17:03 | 6702.81 | 18-SEP-20:00 |
October | 30255.31 | 07-OCT-18:10 | 3065.69 | 02-OCT-17:49 | 6993.92 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.49 | 18-OCT-14:00 | 8281.39 | 31-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 3065.69 | 01-NOV-17:10 | 6993.92 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 12482.72 | 26-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 3065.69 | 01-DEC-16:40 | 6993.92 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 17634.82 | 29-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3613.12 | |||||
Maximum of Months | 30255.31 | 3065.69 | 6993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.74 | 21479.95 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 969.33 | 02-JAN-10:09 | 14422.89 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1088.73 | 06-JAN-00:10 |
February | 813.01 | 04-FEB-19:10 | 969.33 | 01-FEB-10:09 | 14422.89 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1039.55 | 17-FEB-04:10 |
March | 813.01 | 04-MAR-19:10 | 969.33 | 01-MAR-10:09 | 14422.89 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1187.27 | 17-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 969.33 | 01-APR-16:10 | 14422.89 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 865.05 | 27-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 969.33 | 01-MAY-09:09 | 14422.89 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 22.37 | 20-MAY-16:00 | 1721.34 | 22-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 969.33 | 01-JUN-09:09 | 14422.89 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 53.08 | 29-JUN-15:00 | 766.39 | 14-JUN-02:10 |
July | 813.01 | 01-JUL-18:10 | 969.33 | 01-JUL-16:10 | 14422.89 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 57.55 | 25-JUL-14:55 | 419.81 | 05-JUL-00:40 |
August | 813.01 | 05-AUG-18:10 | 969.33 | 01-AUG-09:09 | 14422.89 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 52.86 | 11-AUG-14:00 | 594.11 | 23-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 969.33 | 01-SEP-09:09 | 14422.89 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 53.80 | 02-SEP-13:55 | 972.76 | 12-SEP-02:50 |
October | 813.01 | 07-OCT-18:10 | 969.33 | 02-OCT-09:09 | 14422.89 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 724.21 | 31-OCT-03:50 |
November | 813.01 | 04-NOV-18:10 | 969.33 | 01-NOV-09:09 | 14422.89 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 991.36 | 28-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 969.33 | 01-DEC-10:09 | 14422.89 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1663.50 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 419.81 | ||||||
Maximum of Months | 813.01 | 969.33 | 14422.89 | 7874.59 | 0.00 | 0.00 | 0.00 | 57.55 | 1721.34 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3247.49 | 11-JAN-08:31 | 5738.38 | 29-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2066.09 | 05-FEB-23:53 | 5224.65 | 23-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.01 | 01-MAR-07:00 | 6027.42 | 07-MAR-14:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1363.29 | 11-APR-06:53 | 6981.67 | 22-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1351.09 | 13-MAY-04:00 | 8058.57 | 09-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.41 | 17-JUN-05:43 | 7010.89 | 03-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.59 | 03-JUL-14:40 | 7889.30 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.90 | 03-AUG-04:40 | 6878.11 | 03-AUG-12:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1700.01 | 02-SEP-03:51 | 6071.67 | 17-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.33 | 27-OCT-06:55 | 4499.30 | 06-OCT-12:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.99 | 21-NOV-08:65 | 4000.45 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1496.66 | 29-DEC-06:00 | 4250.93 | 29-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.41 | 4000.45 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3247.49 | 8058.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 65907.39 | 11-JAN-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.06 |
February | 52318.23 | 04-FEB-00:01 | 16808.50 | 6812.44 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.74 |
March | 54995.51 | 05-MAR-00:01 | 16808.50 | 6812.44 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997.41 |
April | 31035.67 | 28-APR-23:01 | 16808.50 | 6812.44 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.59 |
May | 28008.81 | 07-MAY-23:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.77 |
June | 51604.74 | 23-JUN-00:41 | 0.00 | 3576.59 | 3366.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.47 |
July | 51874.72 | 26-JUL-03:44 | 0.00 | 5109.42 | 12023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.66 |
August | 56971.45 | 05-AUG-01:21 | 0.00 | 3576.59 | 5049.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.68 |
September | 54421.76 | 03-SEP-01:21 | 0.00 | 3576.59 | 5049.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.03 |
October | 27969.99 | 21-OCT-04:01 | 0.00 | 5109.42 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.05 |
November | 44617.20 | 27-NOV-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.97 |
December | 55621.73 | 29-DEC-00:01 | 16808.50 | 5109.42 | 7214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27969.99 | 0.00 | 3576.59 | 3366.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.03 | |
Maximum of Months | 65907.39 | 16808.50 | 6812.44 | 28940.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 59499.64 | 27-JAN-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 159.86 |
February | 56401.13 | 01-FEB-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 58.77 |
March | 49367.02 | 05-MAR-05:01 | 0.00 | 1453.97 | 60787.11 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 60.51 |
April | 38531.86 | 07-APR-03:31 | 0.00 | 1292.42 | 28895.80 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 253.63 |
May | 52643.28 | 19-MAY-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.19 |
June | 56947.53 | 20-JUN-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 |
July | 56184.70 | 21-JUL-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 |
August | 56269.64 | 04-AUG-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 53.02 |
September | 53369.00 | 15-SEP-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 129.88 |
October | 59633.17 | 20-OCT-04:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 61.06 |
November | 45166.23 | 27-NOV-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 205.02 |
December | 57420.60 | 29-DEC-05:01 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38531.86 | 0.00 | 1292.42 | 28895.80 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59633.17 | 451.67 | 2154.03 | 67697.80 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 253.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.76 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.40 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.90 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.92 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.90 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.22 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.36 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.87 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.52 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.71 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.47 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.47 | 646.40 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.771731E+11 | 42810.63 | 09-JAN-11:09 | 0.243953E+12 | 212728.43 | 10-JAN-21:19 |
February | 0.683115E+11 | 42171.20 | 04-FEB-11:09 | 0.166506E+12 | 194767.16 | 03-FEB-04:19 |
March | 0.745640E+11 | 42260.75 | 04-MAR-11:09 | 0.157475E+12 | 194767.16 | 04-MAR-04:10 |
April | 0.713248E+11 | 43135.23 | 07-APR-18:00 | 0.106473E+12 | 108537.82 | 28-APR-06:19 |
May | 0.756192E+11 | 49153.40 | 20-MAY-16:10 | 0.950047E+11 | 99258.33 | 08-MAY-06:30 |
June | 0.794119E+11 | 55581.61 | 20-JUN-17:19 | 0.721344E+11 | 68495.89 | 16-JUN-06:00 |
July | 0.896867E+11 | 63684.18 | 17-JUL-17:00 | 0.703679E+11 | 46282.84 | 03-JUL-18:49 |
August | 0.870078E+11 | 58574.92 | 05-AUG-17:00 | 0.703516E+11 | 44559.62 | 01-AUG-18:30 |
September | 0.789259E+11 | 57951.36 | 02-SEP-17:10 | 0.738876E+11 | 67874.15 | 19-SEP-06:10 |
October | 0.754665E+11 | 46717.03 | 18-OCT-10:00 | 0.921492E+11 | 106134.24 | 10-OCT-06:49 |
November | 0.729941E+11 | 41491.09 | 26-NOV-11:20 | 0.130394E+12 | 194767.16 | 27-NOV-04:30 |
December | 0.765572E+11 | 42240.67 | 28-DEC-17:00 | 0.197117E+12 | 200712.46 | 29-DEC-08:50 |
Annual Sum or Average | 0.927043E+12 | 0.147581E+13 | ||||
Minimum of Months | 0.683115E+11 | 41491.09 | 0.703516E+11 | 44559.62 | ||
Maximum of Months | 0.896867E+11 | 63684.18 | 0.243953E+12 | 212728.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.625372E+10 | 0.503372E+10 | 0.390952E+11 | 0.00 | 0.154515E+11 | 37879553.69 | 0.00 | 1098609.49 | 0.00 | 0.00 | 0.00 | 0.639847E+10 | 0.00 |
February | 0.555161E+10 | 0.410936E+10 | 0.353119E+11 | 0.00 | 0.130179E+11 | 34213790.43 | 0.00 | 16568497.08 | 0.00 | 0.00 | 0.00 | 0.578973E+10 | 0.00 |
March | 0.611424E+10 | 0.393739E+10 | 0.390954E+11 | 0.00 | 0.139415E+11 | 37879553.69 | 0.00 | 1169727.87 | 0.00 | 0.00 | 0.00 | 0.646582E+10 | 0.00 |
April | 0.575248E+10 | 0.319180E+10 | 0.378342E+11 | 0.00 | 0.129066E+11 | 36657632.61 | 0.00 | 0.435906E+09 | 0.00 | 0.00 | 0.00 | 0.620603E+10 | 0.00 |
May | 0.588348E+10 | 0.277173E+10 | 0.390953E+11 | 0.00 | 0.132638E+11 | 37879553.69 | 0.00 | 0.287913E+10 | 0.00 | 0.00 | 0.00 | 0.642479E+10 | 0.00 |
June | 0.565656E+10 | 0.243549E+10 | 0.378342E+11 | 0.00 | 0.128244E+11 | 36657632.61 | 0.00 | 0.908161E+10 | 0.00 | 0.00 | 0.00 | 0.624049E+10 | 0.00 |
July | 0.581360E+10 | 0.261594E+10 | 0.390952E+11 | 0.00 | 0.134840E+11 | 37879553.69 | 0.00 | 0.167252E+11 | 0.00 | 0.00 | 0.00 | 0.637402E+10 | 0.00 |
August | 0.594808E+10 | 0.305112E+10 | 0.390954E+11 | 0.00 | 0.134079E+11 | 37879553.69 | 0.00 | 0.134913E+11 | 0.00 | 0.00 | 0.00 | 0.645277E+10 | 0.00 |
September | 0.579465E+10 | 0.353990E+10 | 0.378342E+11 | 0.00 | 0.128780E+11 | 36657632.61 | 0.00 | 0.740528E+10 | 0.00 | 0.00 | 0.00 | 0.620055E+10 | 0.00 |
October | 0.606727E+10 | 0.429350E+10 | 0.390952E+11 | 0.00 | 0.133152E+11 | 37879553.69 | 0.00 | 0.105647E+10 | 0.00 | 0.00 | 0.00 | 0.638932E+10 | 0.00 |
November | 0.600089E+10 | 0.471426E+10 | 0.378341E+11 | 0.00 | 0.133229E+11 | 36657632.61 | 0.00 | 16625712.89 | 0.00 | 0.00 | 0.00 | 0.618895E+10 | 0.00 |
December | 0.625207E+10 | 0.519177E+10 | 0.390952E+11 | 0.00 | 0.146590E+11 | 37879553.69 | 0.00 | 1094089.06 | 0.00 | 0.00 | 0.00 | 0.638971E+10 | 0.00 |
Annual Sum or Average | 0.710886E+11 | 0.448860E+11 | 0.460316E+12 | 0.00 | 0.162473E+12 | 0.446001E+09 | 0.00 | 0.511114E+11 | 0.00 | 0.00 | 0.00 | 0.755206E+11 | 0.00 |
Minimum of Months | 0.555161E+10 | 0.243549E+10 | 0.353119E+11 | 0.00 | 0.128244E+11 | 34213790.43 | 0.00 | 1094089.06 | 0.00 | 0.00 | 0.00 | 0.578973E+10 | 0.00 |
Maximum of Months | 0.625372E+10 | 0.519177E+10 | 0.390954E+11 | 0.00 | 0.154515E+11 | 37879553.69 | 0.00 | 0.167252E+11 | 0.00 | 0.00 | 0.00 | 0.646582E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.167723E+12 | 0.00 | 0.363303E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.970876E+11 | 0.00 | 0.333796E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.806682E+11 | 0.00 | 0.369067E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.336016E+11 | 0.00 | 0.342590E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.214149E+11 | 0.00 | 0.336901E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.264183E+10 | 0.00 | 0.308799E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.304353E+09 | 0.00 | 0.301639E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.578351E+09 | 0.00 | 0.298735E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.617790E+10 | 0.00 | 0.290971E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.209897E+11 | 0.00 | 0.312597E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.597908E+11 | 0.00 | 0.319908E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.122346E+12 | 0.00 | 0.348718E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.613324E+12 | 0.00 | 0.392702E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.304353E+09 | 0.00 | 0.290971E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.167723E+12 | 0.00 | 0.369067E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4035.02 | 02-JAN-16:30 | 3334.35 | 01-JAN-00:10 | 24680.63 | 01-JAN-11:09 | 0.00 | 8558.14 | 10-JAN-23:10 | 17.86 | 03-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4035.02 | 01-FEB-17:19 | 3334.35 | 01-FEB-00:10 | 24680.63 | 01-FEB-11:09 | 0.00 | 8010.82 | 01-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 4035.02 | 01-MAR-18:10 | 3334.35 | 01-MAR-00:10 | 24680.63 | 01-MAR-11:09 | 0.00 | 7887.13 | 04-MAR-23:30 | 17.86 | 02-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 4035.02 | 01-APR-18:30 | 3334.35 | 01-APR-05:10 | 24680.63 | 01-APR-10:09 | 0.00 | 6986.87 | 29-APR-05:10 | 17.86 | 13-APR-08:39 | 0.00 | 01-APR-00:10 |
May | 4035.02 | 01-MAY-19:30 | 3334.35 | 01-MAY-05:10 | 24680.63 | 01-MAY-10:09 | 0.00 | 6665.04 | 08-MAY-05:10 | 17.86 | 03-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 4035.02 | 01-JUN-19:00 | 3334.35 | 01-JUN-20:10 | 24680.63 | 01-JUN-10:09 | 0.00 | 6659.76 | 20-JUN-17:30 | 17.86 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 4035.02 | 01-JUL-20:19 | 3334.35 | 01-JUL-20:30 | 24680.63 | 01-JUL-10:09 | 0.00 | 8065.88 | 17-JUL-17:40 | 17.86 | 03-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 4035.02 | 01-AUG-19:30 | 3334.35 | 01-AUG-19:00 | 24680.63 | 01-AUG-10:09 | 0.00 | 7328.90 | 05-AUG-18:10 | 17.86 | 22-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 4035.02 | 01-SEP-19:10 | 3334.35 | 01-SEP-05:10 | 24680.63 | 01-SEP-10:09 | 0.00 | 6916.45 | 02-SEP-17:10 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 4035.02 | 02-OCT-17:49 | 3334.35 | 01-OCT-05:10 | 24680.63 | 01-OCT-10:09 | 0.00 | 6792.47 | 10-OCT-05:10 | 17.86 | 03-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 4035.02 | 01-NOV-17:10 | 3334.35 | 01-NOV-05:10 | 24680.63 | 01-NOV-10:09 | 0.00 | 7458.60 | 27-NOV-05:10 | 17.86 | 07-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 4035.02 | 01-DEC-16:40 | 3334.35 | 01-DEC-00:10 | 24680.63 | 01-DEC-11:09 | 0.00 | 8297.93 | 31-DEC-07:10 | 17.86 | 02-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 6659.76 | 17.86 | 0.00 | ||||||
Maximum of Months | 4035.02 | 3334.35 | 24680.63 | 0.00 | 8558.14 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 477.19 | 24-JAN-04:19 | 0.00 | 0.00 | 0.00 | 4741.41 | 31-JAN-07:49 | 0.00 |
February | 2229.03 | 27-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.89 | 03-FEB-19:49 | 0.00 |
March | 363.70 | 21-MAR-03:20 | 0.00 | 0.00 | 0.00 | 4742.11 | 07-MAR-07:49 | 0.00 |
April | 7054.48 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 4742.19 | 18-APR-18:30 | 0.00 |
May | 13101.59 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 4742.01 | 16-MAY-06:00 | 0.00 |
June | 18752.91 | 20-JUN-17:30 | 0.00 | 0.00 | 0.00 | 4740.80 | 09-JUN-06:30 | 0.00 |
July | 25422.49 | 17-JUL-17:30 | 0.00 | 0.00 | 0.00 | 4739.17 | 12-JUL-06:19 | 0.00 |
August | 22232.09 | 05-AUG-18:10 | 0.00 | 0.00 | 0.00 | 4740.57 | 18-AUG-06:19 | 0.00 |
September | 20982.65 | 02-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4741.01 | 20-SEP-06:49 | 0.00 |
October | 10076.99 | 18-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4742.09 | 03-OCT-18:00 | 0.00 |
November | 1784.89 | 17-NOV-04:19 | 0.00 | 0.00 | 0.00 | 4741.55 | 14-NOV-07:49 | 0.00 |
December | 320.59 | 08-DEC-04:19 | 0.00 | 0.00 | 0.00 | 4741.57 | 12-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 320.59 | 0.00 | 0.00 | 0.00 | 4739.17 | 0.00 | ||
Maximum of Months | 25422.49 | 0.00 | 0.00 | 0.00 | 4742.19 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 42810.63 | 09-JAN-11:09 | 3207.28 | 24680.63 | 0.00 | 0.00 | 8020.54 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 42171.20 | 04-FEB-11:09 | 2850.91 | 24680.63 | 0.00 | 0.00 | 7422.04 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 42260.75 | 04-MAR-11:09 | 2850.91 | 24680.63 | 0.00 | 0.00 | 7411.50 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 43135.23 | 07-APR-18:00 | 4035.02 | 19053.35 | 3334.35 | 0.00 | 5563.68 | 17.86 | 0.00 | 4598.60 | 0.00 |
May | 49153.40 | 20-MAY-16:10 | 3207.28 | 22268.94 | 0.00 | 0.00 | 5697.46 | 17.86 | 0.00 | 12925.41 | 0.00 |
June | 55581.61 | 20-JUN-17:19 | 3207.28 | 20661.14 | 0.00 | 0.00 | 6658.92 | 17.86 | 0.00 | 18742.46 | 0.00 |
July | 63684.18 | 17-JUL-17:00 | 3207.28 | 20661.14 | 0.00 | 0.00 | 8057.97 | 17.86 | 0.00 | 25387.13 | 0.00 |
August | 58574.92 | 05-AUG-17:00 | 3207.28 | 20661.14 | 0.00 | 0.00 | 6989.15 | 17.86 | 0.00 | 21443.02 | 0.00 |
September | 57951.36 | 02-SEP-17:10 | 3207.28 | 20661.14 | 0.00 | 0.00 | 6916.45 | 17.86 | 0.00 | 20982.65 | 0.00 |
October | 46717.03 | 18-OCT-10:00 | 3207.28 | 24680.63 | 0.00 | 0.00 | 5563.68 | 17.86 | 0.00 | 6883.09 | 0.00 |
November | 41491.09 | 26-NOV-11:20 | 2494.54 | 24680.63 | 0.00 | 0.00 | 7108.63 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 42240.67 | 28-DEC-17:00 | 4035.02 | 22268.94 | 3334.35 | 0.00 | 7691.44 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 41491.09 | 2494.54 | 19053.35 | 0.00 | 0.00 | 5563.68 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 63684.18 | 4035.02 | 24680.63 | 3334.35 | 0.00 | 8057.97 | 17.86 | 0.00 | 25387.13 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 189248.22 | 07-JAN-04:10 | 0.00 | 34738.49 | 25-JAN-19:49 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 189248.22 | 03-FEB-04:19 | 0.00 | 35098.63 | 16-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 189248.22 | 04-MAR-04:10 | 0.00 | 35034.43 | 01-MAR-19:30 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 82435.88 | 29-APR-05:10 | 0.00 | 33903.43 | 04-APR-06:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 62941.50 | 08-MAY-04:00 | 0.00 | 31974.57 | 03-MAY-06:40 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 42244.64 | 17-JUN-04:00 | 0.00 | 29322.89 | 01-JUN-06:30 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 14764.24 | 08-JUL-04:00 | 0.00 | 26370.10 | 03-JUL-18:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 15930.24 | 18-AUG-04:00 | 0.00 | 24646.88 | 01-AUG-18:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 40745.93 | 17-SEP-05:00 | 0.00 | 25962.50 | 29-SEP-06:49 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 70295.78 | 10-OCT-05:10 | 0.00 | 28684.79 | 31-OCT-06:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 189248.22 | 27-NOV-04:30 | 0.00 | 31418.69 | 30-NOV-19:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 189248.22 | 30-DEC-04:10 | 0.00 | 33472.12 | 28-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 14764.24 | 0.00 | 24646.88 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 189248.22 | 0.00 | 35098.63 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
February | 4.67 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
March | 4.33 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.17 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
May | 0.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.61 | 0.00 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.62 | 0.00 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.63 | 0.00 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.61 | 0.00 | 24.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.17 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
December | 3.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 22.67 | 19.67 | 0.00 | 19.67 | 18.00 | 21.86 | 0.00 | 21.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 20.33 | 0.00 | 20.33 | 6.83 | 24.63 | 0.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.78 | 0.00 | 26.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.98 | 0.00 | 26.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.78 | 0.00 | 26.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.14 | 0.00 | 27.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.72 | 0.00 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 28.13 | 0.00 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.45 | 0.00 | 28.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 28.43 | 0.00 | 28.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 28.10 | 0.00 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.49 | 0.00 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.25 | 0.00 | 27.25 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.77 | 0.00 | 26.77 |
Annual Sum or Average | 0.00 | 0.00 | 173.67 | 27.99 | 0.00 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.77 | 0.00 | 26.77 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.45 | 0.00 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.75 | 397.00 | 20.70 | 397.00 | 20.67 |
February | 550.83 | 20.88 | 241.67 | 20.75 | 241.67 | 20.68 |
March | 612.00 | 20.82 | 215.50 | 20.69 | 215.50 | 20.61 |
April | 533.00 | 21.21 | 86.33 | 21.02 | 86.33 | 20.87 |
May | 426.17 | 21.32 | 118.17 | 21.55 | 43.50 | 21.41 |
June | 187.17 | 21.65 | 297.33 | 23.05 | 8.33 | 23.03 |
July | 96.83 | 22.20 | 463.00 | 23.68 | 10.83 | 23.69 |
August | 131.00 | 21.88 | 391.67 | 23.46 | 0.83 | 23.45 |
September | 275.67 | 21.63 | 247.50 | 22.66 | 25.67 | 22.65 |
October | 482.33 | 21.29 | 52.50 | 21.23 | 35.00 | 21.10 |
November | 580.83 | 21.06 | 145.17 | 20.89 | 145.17 | 20.78 |
December | 609.00 | 20.77 | 308.50 | 20.69 | 308.50 | 20.64 |
Annual Sum or Average | 5094.83 | 21.10 | 2964.33 | 21.49 | 1518.33 | 21.32 |
Minimum of Months | 96.83 | 20.75 | 52.50 | 20.69 | 0.83 | 20.61 |
Maximum of Months | 612.00 | 22.20 | 463.00 | 23.68 | 397.00 | 23.69 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 19.08 | 441.83 | 19.05 | 441.83 | 19.03 |
February | 519.00 | 19.24 | 310.50 | 19.26 | 295.50 | 19.19 |
March | 603.33 | 19.39 | 281.33 | 19.28 | 277.83 | 19.22 |
April | 444.50 | 19.90 | 230.33 | 20.72 | 123.67 | 20.60 |
May | 452.17 | 21.75 | 323.17 | 22.81 | 196.00 | 23.05 |
June | 436.67 | 24.80 | 479.83 | 25.20 | 344.33 | 25.41 |
July | 487.33 | 25.80 | 578.33 | 25.75 | 469.33 | 25.82 |
August | 451.67 | 25.58 | 551.00 | 25.62 | 415.17 | 25.73 |
September | 425.83 | 23.82 | 416.50 | 24.59 | 279.83 | 24.90 |
October | 408.17 | 20.77 | 253.33 | 22.06 | 104.17 | 22.24 |
November | 497.17 | 19.58 | 246.67 | 19.92 | 180.33 | 19.78 |
December | 606.17 | 19.21 | 350.67 | 19.13 | 350.67 | 19.10 |
Annual Sum or Average | 5942.00 | 21.37 | 4463.50 | 22.05 | 3478.67 | 22.15 |
Minimum of Months | 408.17 | 19.08 | 230.33 | 19.05 | 104.17 | 19.03 |
Maximum of Months | 610.00 | 25.80 | 578.33 | 25.75 | 469.33 | 25.82 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.74953 | 16.79028 | -0.6644 | 15.32346 |
February | 551.00000 | 20.88379 | 20.21619 | -0.5519 | 12.79603 |
March | 612.00000 | 20.82076 | 21.81588 | -0.5322 | 12.07241 |
April | 590.00000 | 21.47481 | 27.10872 | -0.3088 | 9.31392 |
May | 611.00000 | 22.12524 | 30.91750 | -1.1503 | 36.57066 |
June | 592.00000 | 23.22702 | 37.83250 | -0.6459 | 17.33536 |
July | 609.00000 | 23.68568 | 40.13032 | -0.4264 | 10.52922 |
August | 612.00000 | 23.52360 | 36.40446 | -0.5159 | 13.03561 |
September | 590.00000 | 22.85969 | 37.84345 | -0.7728 | 22.37374 |
October | 610.00000 | 21.84356 | 29.69045 | -0.1474 | 7.87106 |
November | 591.00000 | 21.10754 | 23.42336 | -0.4232 | 10.37196 |
December | 609.00000 | 20.77367 | 19.21428 | -0.5994 | 13.54175 |
Annual Sum or Average | 7187.00000 | 21.92905 | 28.48428 | -0.5620 | 15.11860 |
Minimum of Months | 551.00000 | 20.74953 | 16.79028 | -1.1503 | 7.87106 |
Maximum of Months | 612.00000 | 23.68568 | 40.13032 | -0.1474 | 36.57066 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.08440 | 22.83190 | -0.7177 | 16.51503 |
February | 551.00000 | 19.52817 | 26.35756 | -0.5642 | 14.05102 |
March | 612.00000 | 19.44315 | 28.39539 | -0.5548 | 12.90320 |
April | 590.00000 | 21.03232 | 32.59156 | -0.1463 | 12.02373 |
May | 611.00000 | 22.41518 | 35.07298 | -0.7185 | 31.88343 |
June | 592.00000 | 24.65782 | 38.92250 | 0.09802 | 14.82932 |
July | 609.00000 | 25.49643 | 40.18260 | 0.42112 | 12.43154 |
August | 612.00000 | 25.23429 | 37.00785 | 0.30255 | 12.31764 |
September | 590.00000 | 23.89413 | 38.98176 | -0.1443 | 20.06419 |
October | 610.00000 | 21.90237 | 33.50584 | 0.11269 | 12.66686 |
November | 591.00000 | 20.29448 | 28.16796 | -0.3263 | 11.85484 |
December | 609.00000 | 19.22908 | 24.94311 | -0.6333 | 14.41344 |
Annual Sum or Average | 7187.00000 | 21.86394 | 32.27002 | -0.2378 | 15.51755 |
Minimum of Months | 551.00000 | 19.08440 | 22.83190 | -0.7185 | 11.85484 |
Maximum of Months | 612.00000 | 25.49643 | 40.18260 | 0.42112 | 31.88343 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 25010163.11 | 8523097.52 | 3.75 | 25010163.11 | 0.00 | 0.00 | 0.15 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 | 4810.28 | 27-FEB-14:00 | 4810.28 | 27-FEB-14:00 | 0.00 | 27-FEB-14:00 | 1614.48 | 27-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.728756E+09 | 0.239011E+09 | 39.00 | 0.726240E+09 | 2516411.73 | 0.00 | 0.44 | 07-APR-12:53 | 0.00 | 01-APR-00:01 | 14952.83 | 07-APR-12:53 | 14952.83 | 07-APR-12:53 | 377.14 | 24-APR-13:00 | 4674.39 | 07-APR-12:53 | 0.00 | 01-APR-00:01 |
May | 0.539795E+10 | 0.167627E+10 | 134.77 | 0.514346E+10 | 0.254491E+09 | 0.00 | 0.82 | 19-MAY-17:30 | 0.00 | 01-MAY-00:01 | 30514.30 | 19-MAY-17:30 | 29621.54 | 20-MAY-17:05 | 4190.28 | 21-MAY-03:15 | 8630.75 | 19-MAY-17:30 | 0.00 | 01-MAY-00:01 |
June | 0.185786E+11 | 0.550076E+10 | 305.06 | 0.169087E+11 | 0.166986E+10 | 0.00 | 1.00 | 20-JUN-17:03 | 0.00 | 01-JUN-00:01 | 79044.73 | 21-JUN-02:42 | 76229.69 | 21-JUN-00:42 | 28200.18 | 22-JUN-00:42 | 21178.34 | 21-JUN-00:42 | 0.00 | 01-JUN-00:01 |
July | 0.350851E+11 | 0.103232E+11 | 450.69 | 0.327752E+11 | 0.230995E+10 | 0.00 | 1.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:01 | 79407.53 | 19-JUL-02:62 | 79044.73 | 26-JUL-00:15 | 36516.78 | 01-JUL-01:22 | 21205.86 | 19-JUL-02:62 | 0.00 | 01-JUL-00:01 |
August | 0.279605E+11 | 0.828176E+10 | 400.02 | 0.269751E+11 | 0.985410E+09 | 0.00 | 1.00 | 01-AUG-00:09 | 0.00 | 01-AUG-00:01 | 79044.73 | 09-AUG-00:42 | 79044.73 | 07-AUG-02:53 | 25214.01 | 01-AUG-01:21 | 21178.34 | 01-AUG-00:41 | 0.00 | 01-AUG-00:01 |
September | 0.149799E+11 | 0.445647E+10 | 248.23 | 0.135278E+11 | 0.145218E+10 | 0.00 | 1.00 | 01-SEP-00:41 | 0.00 | 01-SEP-00:01 | 79044.73 | 01-SEP-01:21 | 79044.73 | 03-SEP-00:29 | 31448.63 | 07-SEP-00:41 | 21178.34 | 01-SEP-00:41 | 0.00 | 01-SEP-00:01 |
October | 0.185365E+10 | 0.593808E+09 | 65.47 | 0.184838E+10 | 5268490.12 | 0.00 | 0.65 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 | 23192.87 | 18-OCT-12:55 | 23192.87 | 18-OCT-12:55 | 653.33 | 19-OCT-04:00 | 6867.60 | 18-OCT-12:55 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.104609E+12 | 0.310798E+11 | 1646.99 | 0.979298E+11 | 0.667968E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.350851E+11 | 0.103232E+11 | 450.69 | 0.327752E+11 | 0.230995E+10 | 0.00 | 1.00 | 0.00 | 79407.53 | 79044.73 | 36516.78 | 21205.86 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 3618873.70 | 1098609.49 | 0.87 | 3100306.09 | 518567.61 | 0.00 | 0.23 | 24-JAN-04:08 | 0.00 | 01-JAN-00:01 | 3608.97 | 24-JAN-04:08 | 3204.73 | 24-JAN-04:08 | 498.21 | 13-JAN-04:10 | 1063.32 | 24-JAN-04:08 | 0.00 | 01-JAN-00:01 |
February | 26659582.95 | 8045399.57 | 5.04 | 26206318.02 | 453264.93 | 0.00 | 0.21 | 21-FEB-04:08 | 0.00 | 01-FEB-00:01 | 3311.43 | 21-FEB-04:08 | 2945.88 | 21-FEB-04:08 | 561.40 | 28-FEB-04:28 | 979.96 | 21-FEB-04:08 | 0.00 | 01-FEB-00:01 |
March | 3856963.75 | 1169727.87 | 1.07 | 3096637.12 | 760326.63 | 0.00 | 0.20 | 28-MAR-03:10 | 0.00 | 01-MAR-00:01 | 3108.26 | 28-MAR-03:10 | 2607.46 | 28-MAR-03:10 | 567.68 | 21-MAR-03:08 | 922.61 | 28-MAR-03:10 | 0.00 | 01-MAR-00:01 |
April | 0.683310E+09 | 0.196895E+09 | 61.83 | 0.664080E+09 | 19230024.42 | 0.00 | 1.00 | 07-APR-01:32 | 0.00 | 01-APR-00:01 | 38169.07 | 07-APR-03:31 | 33846.15 | 07-APR-03:31 | 5388.08 | 26-APR-03:52 | 9151.00 | 07-APR-03:31 | 0.00 | 01-APR-00:01 |
May | 0.449398E+10 | 0.120286E+10 | 169.56 | 0.413676E+10 | 0.357219E+09 | 0.00 | 1.00 | 14-MAY-00:42 | 0.00 | 01-MAY-00:01 | 38169.07 | 14-MAY-03:21 | 34336.40 | 29-MAY-02:62 | 13736.87 | 19-MAY-04:01 | 9151.00 | 14-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.140100E+11 | 0.358085E+10 | 347.13 | 0.123949E+11 | 0.161511E+10 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:01 | 38169.07 | 26-JUN-00:42 | 36802.66 | 21-JUN-00:06 | 20942.14 | 13-JUN-04:01 | 9151.00 | 01-JUN-03:21 | 0.00 | 01-JUN-00:01 |
July | 0.251956E+11 | 0.640200E+10 | 485.78 | 0.231425E+11 | 0.205311E+10 | 0.00 | 1.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:01 | 38169.07 | 19-JUL-01:03 | 37347.90 | 26-JUL-00:06 | 20664.08 | 01-JUL-02:42 | 9420.55 | 17-JUL-16:00 | 0.00 | 01-JUL-00:01 |
August | 0.202380E+11 | 0.520952E+10 | 443.56 | 0.190790E+11 | 0.115891E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:01 | 38169.07 | 06-AUG-00:04 | 38169.07 | 11-AUG-01:21 | 16125.48 | 14-AUG-03:21 | 9151.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.114645E+11 | 0.294881E+10 | 280.81 | 0.996348E+10 | 0.150105E+10 | 0.00 | 1.00 | 01-SEP-00:41 | 0.00 | 01-SEP-00:01 | 38169.07 | 04-SEP-00:15 | 36460.49 | 03-SEP-00:04 | 21590.93 | 08-SEP-03:21 | 9151.00 | 01-SEP-00:41 | 0.00 | 01-SEP-00:01 |
October | 0.166133E+10 | 0.462659E+09 | 90.63 | 0.159913E+10 | 62194954.91 | 0.00 | 1.00 | 01-OCT-01:22 | 0.00 | 01-OCT-00:01 | 38169.07 | 18-OCT-03:32 | 34314.51 | 19-OCT-00:42 | 10029.52 | 01-OCT-03:21 | 9151.00 | 13-OCT-03:21 | 0.00 | 01-OCT-00:01 |
November | 56587703.64 | 16625712.89 | 13.54 | 48876895.87 | 7710807.77 | 0.00 | 1.00 | 17-NOV-04:12 | 0.00 | 01-NOV-00:01 | 38169.07 | 17-NOV-04:12 | 28677.13 | 17-NOV-04:12 | 9491.95 | 17-NOV-04:12 | 9151.00 | 17-NOV-04:12 | 0.00 | 01-NOV-00:01 |
December | 3578842.00 | 1094089.06 | 1.25 | 2892602.44 | 686239.56 | 0.00 | 0.18 | 05-DEC-04:10 | 0.00 | 01-DEC-00:01 | 2803.91 | 05-DEC-04:10 | 2452.26 | 05-DEC-04:10 | 351.66 | 05-DEC-04:10 | 836.06 | 05-DEC-04:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.778410E+11 | 0.200316E+11 | 1901.06 | 0.710640E+11 | 0.677696E+10 | 0.00 | ||||||||||||||
Minimum of Months | 3578842.00 | 1094089.06 | 0.87 | 2892602.44 | 453264.93 | 0.00 | 0.18 | 0.00 | 2803.91 | 2452.26 | 351.66 | 836.06 | 0.00 | |||||||
Maximum of Months | 0.251956E+11 | 0.640200E+10 | 485.78 | 0.231425E+11 | 0.205311E+10 | 0.00 | 1.00 | 0.00 | 38169.07 | 38169.07 | 21590.93 | 9420.55 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 167.68 | 77.40 | 90.28 | 74.11 | 736.33 | 0.00 | 0.00 | 0.00 |
February | 262.68 | 131.30 | 131.38 | 179.48 | 534.39 | 0.00 | 0.00 | 0.00 |
March | 351.98 | 146.46 | 205.53 | 268.36 | 428.84 | 0.00 | 0.00 | 0.00 |
April | 447.97 | 222.55 | 225.42 | 426.69 | 298.64 | 0.00 | 0.00 | 0.00 |
May | 493.84 | 220.07 | 273.77 | 509.04 | 237.29 | 0.00 | 0.00 | 0.00 |
June | 638.27 | 328.39 | 309.88 | 767.77 | 155.17 | 0.00 | 0.00 | 0.00 |
July | 669.98 | 378.75 | 291.23 | 879.33 | 123.86 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 325.79 | 258.21 | 741.79 | 141.02 | 0.00 | 0.00 | 0.00 |
September | 412.72 | 213.11 | 199.61 | 465.51 | 210.83 | 0.00 | 0.00 | 0.00 |
October | 294.65 | 148.94 | 145.70 | 264.40 | 314.36 | 0.00 | 0.00 | 0.00 |
November | 187.70 | 87.70 | 100.00 | 115.98 | 451.47 | 0.00 | 0.00 | 0.00 |
December | 138.44 | 59.66 | 78.79 | 56.39 | 630.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 388.14 | 195.34 | 192.81 | 396.99 | 354.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.44 | 59.66 | 78.79 | 56.39 | 123.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 669.98 | 378.75 | 309.88 | 879.33 | 736.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 707.59 | 505.19 | 202.40 | 633.47 | 921.23 | 0.00 | 0.00 | 0.00 |
February | 888.97 | 635.89 | 253.08 | 890.41 | 679.50 | 0.00 | 0.00 | 0.00 |
March | 795.14 | 442.06 | 353.08 | 798.76 | 594.21 | 0.00 | 0.00 | 0.00 |
April | 654.38 | 316.67 | 337.71 | 692.06 | 437.82 | 0.00 | 0.00 | 0.00 |
May | 580.14 | 196.04 | 384.09 | 623.93 | 349.49 | 0.00 | 0.00 | 0.00 |
June | 568.61 | 163.87 | 404.74 | 701.81 | 238.63 | 0.00 | 0.00 | 0.00 |
July | 614.68 | 226.20 | 388.48 | 860.35 | 186.07 | 0.00 | 0.00 | 0.00 |
August | 721.93 | 358.91 | 363.02 | 978.55 | 211.46 | 0.00 | 0.00 | 0.00 |
September | 810.87 | 496.36 | 314.51 | 1011.02 | 302.58 | 0.00 | 0.00 | 0.00 |
October | 855.94 | 593.89 | 262.05 | 969.63 | 428.37 | 0.00 | 0.00 | 0.00 |
November | 773.27 | 559.79 | 213.47 | 789.50 | 567.35 | 0.00 | 0.00 | 0.00 |
December | 672.55 | 485.72 | 186.83 | 619.18 | 783.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.15 | 413.57 | 305.58 | 796.61 | 474.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 568.61 | 163.87 | 186.83 | 619.18 | 186.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 888.97 | 635.89 | 404.74 | 1011.02 | 921.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.46 | 61.33 | 90.13 | 67.48 | 754.40 | 0.00 | 0.00 | 0.00 |
February | 259.62 | 128.65 | 130.97 | 183.12 | 546.70 | 0.00 | 0.00 | 0.00 |
March | 330.78 | 121.92 | 208.85 | 249.40 | 440.66 | 0.00 | 0.00 | 0.00 |
April | 430.64 | 190.48 | 240.15 | 413.04 | 309.08 | 0.00 | 0.00 | 0.00 |
May | 532.59 | 243.38 | 289.21 | 568.61 | 244.43 | 0.00 | 0.00 | 0.00 |
June | 577.79 | 265.01 | 312.78 | 694.48 | 165.01 | 0.00 | 0.00 | 0.00 |
July | 592.11 | 298.97 | 293.14 | 782.73 | 133.61 | 0.00 | 0.00 | 0.00 |
August | 503.38 | 246.80 | 256.57 | 641.95 | 149.79 | 0.00 | 0.00 | 0.00 |
September | 405.53 | 205.04 | 200.50 | 467.03 | 220.43 | 0.00 | 0.00 | 0.00 |
October | 289.98 | 144.22 | 145.76 | 268.39 | 325.99 | 0.00 | 0.00 | 0.00 |
November | 205.24 | 101.99 | 103.25 | 149.39 | 461.66 | 0.00 | 0.00 | 0.00 |
December | 137.16 | 57.69 | 79.47 | 62.71 | 643.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.51 | 172.28 | 196.23 | 380.07 | 365.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.16 | 57.69 | 79.47 | 62.71 | 133.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 592.11 | 298.97 | 312.78 | 782.73 | 754.40 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.449111E+09 | 0.207299E+09 | 0.241812E+09 | 0.198506E+09 | 0.197218E+10 |
February | 0.635467E+09 | 0.317643E+09 | 0.317823E+09 | 0.434200E+09 | 0.129281E+10 |
March | 0.942754E+09 | 0.392271E+09 | 0.550483E+09 | 0.718769E+09 | 0.114860E+10 |
April | 0.116114E+10 | 0.576845E+09 | 0.584294E+09 | 0.110597E+10 | 0.774077E+09 |
May | 0.132270E+10 | 0.589426E+09 | 0.733278E+09 | 0.136342E+10 | 0.635551E+09 |
June | 0.165439E+10 | 0.851175E+09 | 0.803216E+09 | 0.199005E+10 | 0.402192E+09 |
July | 0.179448E+10 | 0.101445E+10 | 0.780027E+09 | 0.235520E+10 | 0.331749E+09 |
August | 0.156420E+10 | 0.872601E+09 | 0.691602E+09 | 0.198681E+10 | 0.377704E+09 |
September | 0.106977E+10 | 0.552376E+09 | 0.517398E+09 | 0.120660E+10 | 0.546465E+09 |
October | 0.789184E+09 | 0.398932E+09 | 0.390252E+09 | 0.708159E+09 | 0.841978E+09 |
November | 0.486515E+09 | 0.227308E+09 | 0.259207E+09 | 0.300620E+09 | 0.117022E+10 |
December | 0.370809E+09 | 0.159788E+09 | 0.211021E+09 | 0.151037E+09 | 0.168960E+10 |
Annual Sum or Average | 0.122405E+11 | 0.616011E+10 | 0.608041E+10 | 0.125193E+11 | 0.111831E+11 |
Minimum of Months | 0.370809E+09 | 0.159788E+09 | 0.211021E+09 | 0.151037E+09 | 0.331749E+09 |
Maximum of Months | 0.179448E+10 | 0.101445E+10 | 0.803216E+09 | 0.235520E+10 | 0.197218E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189520E+10 | 0.135311E+10 | 0.542098E+09 | 0.169668E+10 | 0.246742E+10 |
February | 0.215059E+10 | 0.153834E+10 | 0.612248E+09 | 0.215408E+10 | 0.164384E+10 |
March | 0.212969E+10 | 0.118400E+10 | 0.945686E+09 | 0.213939E+10 | 0.159153E+10 |
April | 0.169616E+10 | 0.820818E+09 | 0.875338E+09 | 0.179381E+10 | 0.113482E+10 |
May | 0.155383E+10 | 0.525084E+09 | 0.102875E+10 | 0.167114E+10 | 0.936086E+09 |
June | 0.147385E+10 | 0.424750E+09 | 0.104910E+10 | 0.181909E+10 | 0.618533E+09 |
July | 0.164635E+10 | 0.605846E+09 | 0.104050E+10 | 0.230437E+10 | 0.498368E+09 |
August | 0.193361E+10 | 0.961298E+09 | 0.972317E+09 | 0.262094E+10 | 0.566384E+09 |
September | 0.210178E+10 | 0.128656E+10 | 0.815222E+09 | 0.262056E+10 | 0.784284E+09 |
October | 0.229254E+10 | 0.159067E+10 | 0.701875E+09 | 0.259706E+10 | 0.114735E+10 |
November | 0.200430E+10 | 0.145099E+10 | 0.553316E+09 | 0.204637E+10 | 0.147057E+10 |
December | 0.180135E+10 | 0.130096E+10 | 0.500400E+09 | 0.165841E+10 | 0.209889E+10 |
Annual Sum or Average | 0.226793E+11 | 0.130424E+11 | 0.963685E+10 | 0.251219E+11 | 0.149581E+11 |
Minimum of Months | 0.147385E+10 | 0.424750E+09 | 0.500400E+09 | 0.165841E+10 | 0.498368E+09 |
Maximum of Months | 0.229254E+10 | 0.159067E+10 | 0.104910E+10 | 0.262094E+10 | 0.246742E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405671E+09 | 0.164273E+09 | 0.241397E+09 | 0.180750E+09 | 0.202058E+10 |
February | 0.628078E+09 | 0.311236E+09 | 0.316842E+09 | 0.443001E+09 | 0.132257E+10 |
March | 0.885957E+09 | 0.326561E+09 | 0.559395E+09 | 0.667980E+09 | 0.118025E+10 |
April | 0.111621E+10 | 0.493737E+09 | 0.622475E+09 | 0.107060E+10 | 0.801128E+09 |
May | 0.142650E+10 | 0.651873E+09 | 0.774627E+09 | 0.152296E+10 | 0.654675E+09 |
June | 0.149764E+10 | 0.686918E+09 | 0.810721E+09 | 0.180010E+10 | 0.427718E+09 |
July | 0.158591E+10 | 0.800768E+09 | 0.785139E+09 | 0.209647E+10 | 0.357871E+09 |
August | 0.134825E+10 | 0.661040E+09 | 0.687210E+09 | 0.171940E+10 | 0.401184E+09 |
September | 0.105114E+10 | 0.531452E+09 | 0.519691E+09 | 0.121055E+10 | 0.571365E+09 |
October | 0.776680E+09 | 0.386282E+09 | 0.390397E+09 | 0.718847E+09 | 0.873130E+09 |
November | 0.531988E+09 | 0.264355E+09 | 0.267634E+09 | 0.387219E+09 | 0.119663E+10 |
December | 0.367378E+09 | 0.154520E+09 | 0.212858E+09 | 0.167966E+09 | 0.172224E+10 |
Annual Sum or Average | 0.116214E+11 | 0.543301E+10 | 0.618839E+10 | 0.119858E+11 | 0.115293E+11 |
Minimum of Months | 0.367378E+09 | 0.154520E+09 | 0.212858E+09 | 0.167966E+09 | 0.357871E+09 |
Maximum of Months | 0.158591E+10 | 0.800768E+09 | 0.810721E+09 | 0.209647E+10 | 0.202058E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 657.59 | 2294.48 | 1026.73 | 643.92 | 382.81 | 0.00 | 0.00 |
February | 1159.83 | 1667.41 | 1411.27 | 895.84 | 515.42 | 0.00 | 0.00 |
March | 1272.37 | 1419.57 | 1477.90 | 710.44 | 767.46 | 0.00 | 0.00 |
April | 1478.30 | 992.05 | 1532.99 | 729.71 | 803.28 | 0.00 | 0.00 |
May | 1656.81 | 786.44 | 1606.57 | 659.49 | 947.08 | 0.00 | 0.00 |
June | 2126.10 | 520.85 | 1784.68 | 757.27 | 1027.41 | 0.00 | 0.00 |
July | 2499.54 | 420.67 | 1876.77 | 903.92 | 972.85 | 0.00 | 0.00 |
August | 2336.26 | 476.24 | 1809.31 | 931.50 | 877.81 | 0.00 | 0.00 |
September | 1916.81 | 707.09 | 1629.13 | 914.50 | 714.63 | 0.00 | 0.00 |
October | 1468.30 | 1034.61 | 1440.56 | 887.05 | 553.51 | 0.00 | 0.00 |
November | 974.64 | 1400.26 | 1166.21 | 749.48 | 416.73 | 0.00 | 0.00 |
December | 634.15 | 1953.34 | 948.16 | 603.07 | 345.09 | 0.00 | 0.00 |
Annual Sum or Average | 1516.78 | 1137.65 | 1475.81 | 781.19 | 694.62 | 0.00 | 0.00 |
Minimum of Months | 634.15 | 420.67 | 948.16 | 603.07 | 345.09 | 0.00 | 0.00 |
Maximum of Months | 2499.54 | 2294.48 | 1876.77 | 931.50 | 1027.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176129E+10 | 0.614554E+10 | 0.274999E+10 | 0.172468E+10 | 0.102531E+10 | 0.00 | 0.00 |
February | 0.280587E+10 | 0.403380E+10 | 0.341414E+10 | 0.216722E+10 | 0.124691E+10 | 0.00 | 0.00 |
March | 0.340793E+10 | 0.380216E+10 | 0.395840E+10 | 0.190284E+10 | 0.205556E+10 | 0.00 | 0.00 |
April | 0.383174E+10 | 0.257139E+10 | 0.397351E+10 | 0.189140E+10 | 0.208211E+10 | 0.00 | 0.00 |
May | 0.443760E+10 | 0.210639E+10 | 0.430304E+10 | 0.176638E+10 | 0.253666E+10 | 0.00 | 0.00 |
June | 0.551084E+10 | 0.135005E+10 | 0.462588E+10 | 0.196284E+10 | 0.266304E+10 | 0.00 | 0.00 |
July | 0.669478E+10 | 0.112672E+10 | 0.502673E+10 | 0.242106E+10 | 0.260567E+10 | 0.00 | 0.00 |
August | 0.625744E+10 | 0.127556E+10 | 0.484607E+10 | 0.249494E+10 | 0.235113E+10 | 0.00 | 0.00 |
September | 0.496837E+10 | 0.183278E+10 | 0.422270E+10 | 0.237039E+10 | 0.185231E+10 | 0.00 | 0.00 |
October | 0.393270E+10 | 0.277110E+10 | 0.385841E+10 | 0.237588E+10 | 0.148252E+10 | 0.00 | 0.00 |
November | 0.252626E+10 | 0.362947E+10 | 0.302281E+10 | 0.194265E+10 | 0.108016E+10 | 0.00 | 0.00 |
December | 0.169850E+10 | 0.523182E+10 | 0.253954E+10 | 0.161526E+10 | 0.924279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.478333E+11 | 0.358768E+11 | 0.465412E+11 | 0.246355E+11 | 0.219057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169850E+10 | 0.112672E+10 | 0.253954E+10 | 0.161526E+10 | 0.924279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.669478E+10 | 0.614554E+10 | 0.502673E+10 | 0.249494E+10 | 0.266304E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639847E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173304916.7 | 81.22 | 0.00 | 0.00 |
February | 0.578956E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155283101.7 | 81.22 | 0.00 | 0.00 |
March | 0.646582E+10 | -0.629384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171971965.3 | 81.22 | 0.00 | 0.00 |
April | 0.620586E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162391623.9 | 81.22 | 0.00 | 0.00 |
May | 0.642455E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164363197.7 | 81.22 | 0.00 | 0.00 |
June | 0.624033E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153735591.3 | 81.22 | 0.00 | 0.00 |
July | 0.637392E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156852218.5 | 81.22 | 0.00 | 0.00 |
August | 0.645261E+10 | -0.629520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157409492.3 | 81.22 | 0.00 | 0.00 |
September | 0.620028E+10 | -0.604481E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155468874.7 | 81.22 | 0.00 | 0.00 |
October | 0.638936E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165551326.4 | 81.22 | 0.00 | 0.00 |
November | 0.618879E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164177201.2 | 81.22 | 0.00 | 0.00 |
December | 0.638965E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172576047.1 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755192E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.195309E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.578956E+10 | -0.629520E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173304916.7 | 81.22 | 0.00 | 0.00 |
Maximum of Months | 0.646582E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153735591.3 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.271075E+11 | -0.260947E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101278E+10 | 58.99 | 0.00 | 0.00 |
February | 0.249378E+11 | -0.240344E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -903348026.7 | 58.99 | 0.00 | 0.00 |
March | 0.275692E+11 | -0.265686E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100062E+10 | 58.99 | 0.00 | 0.00 |
April | 0.255069E+11 | -0.245755E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -931357166.9 | 58.99 | 0.00 | 0.00 |
May | 0.249764E+11 | -0.240454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -930983182.0 | 58.99 | 0.00 | 0.00 |
June | 0.227873E+11 | -0.219351E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -852245983.8 | 58.99 | 0.00 | 0.00 |
July | 0.221343E+11 | -0.212721E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -862167097.9 | 58.99 | 0.00 | 0.00 |
August | 0.219065E+11 | -0.210392E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -867290966.7 | 58.99 | 0.00 | 0.00 |
September | 0.213519E+11 | -0.204840E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -867957941.3 | 58.99 | 0.00 | 0.00 |
October | 0.230193E+11 | -0.220776E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -941701244.5 | 58.99 | 0.00 | 0.00 |
November | 0.236847E+11 | -0.227370E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -947714615.1 | 58.99 | 0.00 | 0.00 |
December | 0.259291E+11 | -0.249231E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100607E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.290911E+12 | -0.279787E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.111242E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213519E+11 | -0.265686E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.101278E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275692E+11 | -0.204840E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -852245983.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.74 | 0.73 | 01-JAN-08:50 | 4042.91 | 33.09 | 173.33 | 232.00 | 4033.34 | 32.90 | 176.33 | 230.67 |
February | 275.00 | 0.74 | 0.73 | 01-FEB-08:20 | 3911.29 | 31.02 | 188.33 | 259.83 | 4199.31 | 31.87 | 198.67 | 260.33 |
March | 304.00 | 0.74 | 0.73 | 01-MAR-07:40 | 1953.10 | 22.41 | 136.00 | 325.83 | 2112.42 | 22.34 | 137.17 | 325.83 |
April | 325.17 | 0.74 | 0.73 | 01-APR-08:39 | 1950.91 | 19.84 | 59.67 | 356.50 | 1825.35 | 19.43 | 80.50 | 359.50 |
May | 385.83 | 0.74 | 0.73 | 01-MAY-05:00 | 2015.98 | 19.59 | 64.83 | 408.50 | 1869.79 | 19.34 | 73.50 | 409.17 |
June | 434.17 | 0.74 | 0.73 | 01-JUN-13:39 | 1843.48 | 20.49 | 96.83 | 435.00 | 1643.77 | 18.93 | 70.17 | 431.17 |
July | 417.33 | 0.74 | 0.73 | 01-JUL-06:40 | 2330.52 | 20.18 | 65.17 | 418.50 | 2074.46 | 19.31 | 65.50 | 425.00 |
August | 421.33 | 0.74 | 0.73 | 01-AUG-05:00 | 1737.85 | 18.89 | 63.67 | 400.67 | 1944.55 | 18.83 | 70.50 | 399.50 |
September | 352.17 | 0.74 | 0.73 | 01-SEP-06:30 | 1866.56 | 20.63 | 101.33 | 339.67 | 1876.55 | 20.29 | 97.83 | 339.67 |
October | 317.67 | 0.74 | 0.73 | 01-OCT-07:40 | 3025.61 | 27.42 | 178.33 | 304.83 | 2575.43 | 26.42 | 159.67 | 306.50 |
November | 269.50 | 0.74 | 0.73 | 01-NOV-07:49 | 4273.67 | 33.55 | 213.83 | 250.50 | 4182.69 | 33.24 | 207.33 | 251.33 |
December | 236.83 | 0.75 | 0.73 | 01-DEC-08:39 | 3236.03 | 33.53 | 183.50 | 230.67 | 3245.19 | 33.47 | 184.83 | 228.00 |
Annual Sum or Average | 3965.83 | 0.74 | 2531.74 | 23.98 | 1524.83 | 3962.50 | 2471.20 | 23.56 | 1522.00 | 3966.67 | ||
Minimum of Months | 226.83 | 0.74 | 0.73 | 1737.85 | 18.89 | 59.67 | 230.67 | 1643.77 | 18.83 | 65.50 | 228.00 | |
Maximum of Months | 434.17 | 0.75 | 0.73 | 4273.67 | 33.55 | 213.83 | 435.00 | 4199.31 | 33.47 | 207.33 | 431.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.841860E+11 | 151398.57 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.499978E+11 | 151398.57 | 01-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424585E+11 | 151398.57 | 03-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189773E+11 | 99848.06 | 28-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122155E+11 | 73621.39 | 08-MAY-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180474E+10 | 31727.30 | 15-JUN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242792E+09 | 18353.97 | 09-JUL-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.448855E+09 | 18689.51 | 18-AUG-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.399817E+10 | 30409.09 | 19-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122758E+11 | 54226.26 | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317471E+11 | 151398.57 | 12-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.624090E+11 | 151398.57 | 28-DEC-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.242792E+09 | 18353.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.841860E+11 | 151398.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.499924E+11 | 71497.37 | 29-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276723E+11 | 60760.96 | 04-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220761E+11 | 62178.64 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790390E+10 | 43367.61 | 29-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491645E+10 | 24540.49 | 06-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.308724E+09 | 15568.59 | 15-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 690447.90 | 574.06 | 08-JUL-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13825586.61 | 3926.09 | 17-AUG-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.944144E+09 | 15663.48 | 17-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.451601E+10 | 25773.58 | 21-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160855E+11 | 46983.93 | 12-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354676E+11 | 65109.65 | 31-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 690447.90 | 574.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499924E+11 | 71497.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 25010163.11 | 25010163.11 | 4810.28 | 27-FEB-14:00 | 4810.28 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.728756E+09 | 0.726240E+09 | 14952.83 | 07-APR-12:53 | 14952.83 | 0.00 |
May | 0.00 | 0.00 | 0.539795E+10 | 0.514346E+10 | 30514.30 | 19-MAY-17:30 | 28272.51 | 0.00 |
June | 0.00 | 0.00 | 0.185786E+11 | 0.169087E+11 | 79044.73 | 21-JUN-02:42 | 65563.25 | 0.00 |
July | 0.00 | 0.00 | 0.350851E+11 | 0.327752E+11 | 79407.53 | 19-JUL-02:62 | 45428.69 | 0.00 |
August | 0.00 | 0.00 | 0.279605E+11 | 0.269751E+11 | 79044.73 | 09-AUG-00:42 | 68930.01 | 0.00 |
September | 0.00 | 0.00 | 0.149799E+11 | 0.135278E+11 | 79044.73 | 01-SEP-01:21 | 68540.56 | 0.00 |
October | 0.00 | 0.00 | 0.185365E+10 | 0.184838E+10 | 23192.87 | 18-OCT-12:55 | 23192.87 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104609E+12 | 0.979298E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.350851E+11 | 0.327752E+11 | 79407.53 | 68930.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3618873.70 | 3100306.09 | 3608.97 | 24-JAN-04:08 | 3204.73 | 0.00 |
February | 0.00 | 0.00 | 26659582.95 | 26206318.02 | 3311.43 | 21-FEB-04:08 | 2945.88 | 0.00 |
March | 0.00 | 0.00 | 3856963.75 | 3096637.12 | 3108.26 | 28-MAR-03:10 | 2607.46 | 0.00 |
April | 0.00 | 0.00 | 0.683310E+09 | 0.664080E+09 | 38169.07 | 07-APR-03:31 | 33846.15 | 0.00 |
May | 0.00 | 0.00 | 0.449398E+10 | 0.413676E+10 | 38169.07 | 14-MAY-03:21 | 28536.67 | 0.00 |
June | 0.00 | 0.00 | 0.140100E+11 | 0.123949E+11 | 38169.07 | 26-JUN-00:42 | 25370.55 | 0.00 |
July | 0.00 | 0.00 | 0.251956E+11 | 0.231425E+11 | 38169.07 | 19-JUL-01:03 | 20521.55 | 0.00 |
August | 0.00 | 0.00 | 0.202380E+11 | 0.190790E+11 | 38169.07 | 06-AUG-00:04 | 33569.74 | 0.00 |
September | 0.00 | 0.00 | 0.114645E+11 | 0.996348E+10 | 38169.07 | 04-SEP-00:15 | 32828.14 | 0.00 |
October | 0.00 | 0.00 | 0.166133E+10 | 0.159913E+10 | 38169.07 | 18-OCT-03:32 | 34011.96 | 0.00 |
November | 0.00 | 0.00 | 56587703.64 | 48876895.87 | 38169.07 | 17-NOV-04:12 | 28677.13 | 0.00 |
December | 0.00 | 0.00 | 3578842.00 | 2892602.44 | 2803.91 | 05-DEC-04:10 | 2452.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.778410E+11 | 0.710640E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 3578842.00 | 2892602.44 | 2803.91 | 2452.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.251956E+11 | 0.231425E+11 | 38169.07 | 34011.96 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10200.22 | 19650.85 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10391.70 | 19774.76 | 17-FEB-19:50 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 10376.38 | 19800.70 | 01-MAR-07:28 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9939.24 | 19219.51 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9436.47 | 18386.41 | 01-MAY-18:12 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8922.66 | 17275.47 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8403.20 | 16294.47 | 03-JUL-06:44 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8316.62 | 15715.62 | 03-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8363.92 | 16089.96 | 29-SEP-18:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8703.44 | 17004.24 | 31-OCT-18:35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9231.59 | 18051.01 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9763.63 | 18984.98 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 9331.20 | ||||
Minimum of Months | 0.00 | 0.00 | 8316.62 | 15715.62 | ||
Maximum of Months | 0.00 | 0.00 | 10391.70 | 19800.70 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.445499E+10 | 0.61 | 1983.06 | 01-JAN-00:01 | 0.73 |
February | 0.403379E+10 | 0.61 | 1983.06 | 01-FEB-00:01 | 0.73 |
March | 0.447389E+10 | 0.61 | 1983.06 | 01-MAR-00:01 | 0.73 |
April | 0.453662E+10 | 0.64 | 1983.06 | 01-APR-04:01 | 0.72 |
May | 0.484080E+10 | 0.66 | 1983.06 | 01-MAY-04:01 | 0.72 |
June | 0.489232E+10 | 0.69 | 1983.06 | 01-JUN-00:05 | 0.73 |
July | 0.507594E+10 | 0.69 | 1983.06 | 01-JUL-00:03 | 0.72 |
August | 0.507311E+10 | 0.69 | 1983.06 | 01-AUG-00:03 | 0.72 |
September | 0.484538E+10 | 0.68 | 1983.06 | 01-SEP-00:03 | 0.72 |
October | 0.489892E+10 | 0.67 | 1983.06 | 01-OCT-00:08 | 0.73 |
November | 0.449093E+10 | 0.64 | 1983.06 | 01-NOV-03:15 | 0.73 |
December | 0.447568E+10 | 0.62 | 1983.06 | 01-DEC-00:01 | 0.73 |
Annual Sum or Average | 0.560924E+11 | 0.65 | |||
Minimum of Months | 0.403379E+10 | 0.61 | 1983.06 | 0.72 | |
Maximum of Months | 0.507594E+10 | 0.69 | 1983.06 | 0.73 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.872291E+10 | 1.01 | 7046.38 | 06-JAN-04:01 | 1.61 |
February | 0.713032E+10 | 0.96 | 7046.38 | 01-FEB-04:01 | 1.61 |
March | 0.751314E+10 | 0.94 | 7046.38 | 03-MAR-04:02 | 1.61 |
April | 0.662309E+10 | 0.87 | 4715.79 | 30-APR-22:58 | 1.32 |
May | 0.663676E+10 | 0.84 | 4610.87 | 23-MAY-05:38 | 1.30 |
June | 0.617877E+10 | 0.84 | 3704.54 | 15-JUN-04:03 | 1.15 |
July | 0.646771E+10 | 0.87 | 4476.02 | 17-JUL-17:27 | 1.28 |
August | 0.642724E+10 | 0.87 | 3937.19 | 05-AUG-18:08 | 1.19 |
September | 0.625946E+10 | 0.85 | 3667.73 | 19-SEP-04:01 | 1.14 |
October | 0.663473E+10 | 0.84 | 4083.70 | 05-OCT-04:01 | 1.22 |
November | 0.699282E+10 | 0.90 | 7046.38 | 12-NOV-04:02 | 1.61 |
December | 0.807532E+10 | 0.97 | 7046.38 | 28-DEC-04:08 | 1.61 |
Annual Sum or Average | 0.836623E+11 | 0.90 | |||
Minimum of Months | 0.617877E+10 | 0.84 | 3667.73 | 1.14 | |
Maximum of Months | 0.872291E+10 | 1.01 | 7046.38 | 1.61 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.227357E+10 | 0.61 | 1579.89 | 29-JAN-05:03 | 0.93 |
February | 0.185376E+10 | 0.57 | 1457.08 | 04-FEB-05:02 | 0.89 |
March | 0.195448E+10 | 0.56 | 1473.29 | 05-MAR-05:02 | 0.89 |
April | 0.174691E+10 | 0.55 | 1258.13 | 29-APR-04:03 | 0.82 |
May | 0.178622E+10 | 0.56 | 1905.17 | 19-MAY-04:01 | 1.00 |
June | 0.175334E+10 | 0.58 | 1905.17 | 06-JUN-04:01 | 1.00 |
July | 0.194039E+10 | 0.59 | 1905.17 | 07-JUL-04:01 | 1.00 |
August | 0.190752E+10 | 0.59 | 1905.17 | 01-AUG-04:01 | 1.00 |
September | 0.177312E+10 | 0.58 | 1905.17 | 05-SEP-03:21 | 1.00 |
October | 0.178157E+10 | 0.57 | 1905.17 | 20-OCT-04:01 | 1.01 |
November | 0.183913E+10 | 0.57 | 1299.49 | 12-NOV-05:03 | 0.84 |
December | 0.210798E+10 | 0.58 | 1506.82 | 31-DEC-05:02 | 0.90 |
Annual Sum or Average | 0.227180E+11 | 0.58 | |||
Minimum of Months | 0.174691E+10 | 0.55 | 1258.13 | 0.82 | |
Maximum of Months | 0.227357E+10 | 0.61 | 1905.17 | 1.01 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.75 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 46.73 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.65 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 50.46 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 50.93 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 51.63 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.78 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.53 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.61 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.76 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.02 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.64 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 46.65 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.61 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.75 | 59.93 | 10200.22 | 19650.85 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.73 | 59.32 | 10391.70 | 19774.76 | 17-FEB-19:50 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.65 | 59.05 | 10376.38 | 19800.70 | 01-MAR-07:28 |
April | 0.00 | 0.00 | 01-APR-00:01 | 48.61 | 48.61 | 9939.24 | 19219.51 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.00 | 49.00 | 9436.47 | 18386.41 | 01-MAY-18:12 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 49.67 | 49.67 | 8922.66 | 17275.47 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 49.98 | 49.98 | 8403.20 | 16294.47 | 03-JUL-06:44 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.11 | 50.11 | 8316.62 | 15715.62 | 03-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.42 | 50.42 | 8363.92 | 16089.96 | 29-SEP-18:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.18 | 48.18 | 8703.44 | 17004.24 | 31-OCT-18:35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.38 | 49.38 | 9231.59 | 18051.01 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.64 | 58.70 | 9763.63 | 18984.98 | 29-DEC-19:40 |
Annual Sum or Average | 0.00 | 9331.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.65 | 48.18 | 8316.62 | 15715.62 | ||
Maximum of Months | 0.00 | 0.00 | 50.42 | 59.93 | 10391.70 | 19800.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.872291E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.713884E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.751314E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.686210E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.831303E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.116795E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.167909E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.147090E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.107159E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.722854E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.699282E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.807532E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114742E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.686210E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.167909E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.227467E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.186180E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.195565E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194381E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.298909E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.533420E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.834239E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.711705E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.472193E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.224423E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.185576E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.210907E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.427496E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.185576E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.834239E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.872291E+10 | 0.00 | 0.841860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.713032E+10 | 25010163.11 | 0.499978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751314E+10 | 0.00 | 0.424585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662309E+10 | 0.728756E+09 | 0.189773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.663676E+10 | 0.539795E+10 | 0.122155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617877E+10 | 0.185487E+11 | 0.180474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.646771E+10 | 0.348795E+11 | 0.242792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.642724E+10 | 0.278253E+11 | 0.448855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.625946E+10 | 0.148731E+11 | 0.399817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.663473E+10 | 0.185365E+10 | 0.122758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699282E+10 | 0.00 | 0.317471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.807532E+10 | 0.00 | 0.624090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836623E+11 | 0.104132E+12 | 0.320762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.617877E+10 | 0.00 | 0.242792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.872291E+10 | 0.348795E+11 | 0.841860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.227357E+10 | 3618873.70 | 0.499924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185376E+10 | 26659582.95 | 0.276723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195448E+10 | 3856963.75 | 0.220761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174691E+10 | 0.682337E+09 | 0.790390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178622E+10 | 0.448786E+10 | 0.491645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175334E+10 | 0.139538E+11 | 0.308724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.194039E+10 | 0.250275E+11 | 690447.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190752E+10 | 0.201134E+11 | 13825586.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177312E+10 | 0.113837E+11 | 0.944144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178157E+10 | 0.164962E+10 | 0.451601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183913E+10 | 55289955.24 | 0.160855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210798E+10 | 3578842.00 | 0.354676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227180E+11 | 0.773912E+11 | 0.169898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174691E+10 | 3578842.00 | 690447.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227357E+10 | 0.250275E+11 | 0.499924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.872291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.713032E+10 | 0.00 | 0.00 | 0.00 | 8523097.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662309E+10 | 0.00 | 0.00 | 0.00 | 0.239011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.663676E+10 | 0.00 | 0.00 | 0.00 | 0.167627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617877E+10 | 0.00 | 0.00 | 0.00 | 0.550076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.646771E+10 | 0.00 | 0.00 | 0.00 | 0.103232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.642724E+10 | 0.00 | 0.00 | 0.00 | 0.828176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.625946E+10 | 0.00 | 0.00 | 0.00 | 0.445647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.663473E+10 | 0.00 | 0.00 | 0.00 | 0.593808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.807532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836623E+11 | 0.00 | 0.00 | 0.00 | 0.310798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.617877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.872291E+10 | 0.00 | 0.00 | 0.00 | 0.103232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.227357E+10 | 0.00 | 0.00 | 0.00 | 1098609.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185376E+10 | 0.00 | 0.00 | 0.00 | 8045399.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195448E+10 | 0.00 | 0.00 | 0.00 | 1169727.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174691E+10 | 0.00 | 0.00 | 0.00 | 0.196895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178622E+10 | 0.00 | 0.00 | 0.00 | 0.120286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175334E+10 | 0.00 | 0.00 | 0.00 | 0.358085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.194039E+10 | 0.00 | 0.00 | 0.00 | 0.640200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190752E+10 | 0.00 | 0.00 | 0.00 | 0.520952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177312E+10 | 0.00 | 0.00 | 0.00 | 0.294881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178157E+10 | 0.00 | 0.00 | 0.00 | 0.462659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183913E+10 | 0.00 | 0.00 | 0.00 | 16625712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210798E+10 | 0.00 | 0.00 | 0.00 | 1094089.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227180E+11 | 0.00 | 0.00 | 0.00 | 0.200316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174691E+10 | 0.00 | 0.00 | 0.00 | 1094089.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227357E+10 | 0.00 | 0.00 | 0.00 | 0.640200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.462956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600606E+11 | 0.00 | 0.00 | 3.58 |
February | 0.497174E+11 | 0.00 | 0.00 | 972570.08 | 0.00 | 0.256460E+11 | 0.109295E+10 | 0.00 | 3.58 |
March | 0.585996E+11 | 0.00 | 0.00 | 205412.42 | 0.00 | 0.162579E+11 | 0.259040E+09 | 0.00 | 3.58 |
April | 0.453670E+11 | 0.00 | 0.00 | 14455326.83 | 0.00 | 0.224057E+10 | 0.718290E+10 | 0.00 | 3.70 |
May | 0.339762E+11 | 20215566.48 | 0.00 | 42047434.45 | 0.00 | 0.150036E+10 | 0.129010E+11 | 0.00 | 3.90 |
June | 0.126030E+11 | 0.471440E+09 | 0.00 | 90133752.44 | 0.00 | 7010723.64 | 0.189315E+11 | 0.00 | 4.19 |
July | 0.553564E+10 | 0.167771E+10 | 0.00 | 0.115034E+09 | 0.00 | 1403672.00 | 0.157777E+11 | 0.00 | 4.24 |
August | 0.770880E+10 | 0.109075E+10 | 0.00 | 0.110218E+09 | 0.00 | 1296115.18 | 0.192464E+11 | 0.00 | 4.31 |
September | 0.187863E+11 | 0.664414E+09 | 0.00 | 62965963.01 | 0.00 | 9822534.17 | 0.177200E+11 | 0.00 | 4.10 |
October | 0.396344E+11 | 0.00 | 0.00 | 21526531.24 | 0.00 | 0.371744E+09 | 0.126245E+11 | 0.00 | 3.75 |
November | 0.546493E+11 | 0.00 | 0.00 | 2520304.55 | 0.00 | 0.676884E+10 | 0.443145E+10 | 0.00 | 3.56 |
December | 0.580462E+11 | 0.00 | 0.00 | 73659.04 | 0.00 | 0.313581E+11 | 0.362448E+09 | 0.00 | 3.59 |
Annual Sum or Average | 0.430919E+12 | 0.392453E+10 | 0.00 | 0.460154E+09 | 0.00 | 0.144224E+12 | 0.110530E+12 | 0.00 | 3.84 |
Minimum of Months | 0.553564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1296115.18 | 0.00 | 0.00 | 3.56 |
Maximum of Months | 0.585996E+11 | 0.167771E+10 | 0.00 | 0.115034E+09 | 0.00 | 0.600606E+11 | 0.192464E+11 | 0.00 | 4.31 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.905516E+11 | 0.00 | 0.00 | 192813.60 | 0.337081E+09 | 61885410.93 | 0.584111E+09 | 0.00 | 8.55 |
February | 0.637722E+11 | 0.00 | 0.00 | 1864872.96 | 0.295222E+09 | 31427528.61 | 0.242786E+10 | 0.00 | 8.50 |
March | 0.633035E+11 | 0.00 | 0.00 | 594360.67 | 0.397162E+09 | 19064050.98 | 0.175478E+10 | 0.00 | 8.54 |
April | 0.395607E+11 | 0.00 | 0.00 | 17470938.18 | 0.584950E+09 | 3106561.18 | 0.111078E+11 | 0.00 | 8.52 |
May | 0.295089E+11 | 17641499.77 | 0.00 | 50187740.79 | 0.239466E+09 | 0.00 | 0.183517E+11 | 0.00 | 8.62 |
June | 0.967114E+10 | 0.333825E+09 | 0.00 | 0.103589E+09 | 6582008.67 | 0.00 | 0.259253E+11 | 0.00 | 8.88 |
July | 0.346011E+10 | 0.389669E+09 | 0.00 | 0.141525E+09 | 0.00 | 0.00 | 0.242771E+11 | 0.00 | 9.03 |
August | 0.384236E+10 | 0.364296E+09 | 0.00 | 0.126740E+09 | 0.00 | 0.00 | 0.282842E+11 | 0.00 | 9.04 |
September | 0.137887E+11 | 0.168481E+09 | 0.00 | 76335819.00 | 9918342.31 | 0.00 | 0.239803E+11 | 0.00 | 8.86 |
October | 0.298451E+11 | 0.00 | 0.00 | 29968292.76 | 0.478835E+09 | 2053797.32 | 0.204621E+11 | 0.00 | 8.59 |
November | 0.486961E+11 | 0.00 | 0.00 | 7142840.92 | 0.432476E+09 | 16172852.58 | 0.984613E+10 | 0.00 | 8.50 |
December | 0.754800E+11 | 0.00 | 0.00 | 584382.03 | 0.267509E+09 | 33020359.11 | 0.204796E+10 | 0.00 | 8.58 |
Annual Sum or Average | 0.471481E+12 | 0.127391E+10 | 0.00 | 0.556196E+09 | 0.304920E+10 | 0.166731E+09 | 0.169049E+12 | 0.00 | 8.68 |
Minimum of Months | 0.346011E+10 | 0.00 | 0.00 | 192813.60 | 0.00 | 0.00 | 0.584111E+09 | 0.00 | 8.50 |
Maximum of Months | 0.905516E+11 | 0.389669E+09 | 0.00 | 0.141525E+09 | 0.584950E+09 | 61885410.93 | 0.282842E+11 | 0.00 | 9.04 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:24:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.240090E+11 | 0.174305E+11 | 0.308690E+12 | 0.00 | 0.481088E+11 |
February | 0.454945E+11 | 0.130598E+11 | 0.226242E+12 | 0.112099E+09 | 0.335076E+11 |
March | 0.858582E+11 | 0.134350E+11 | 0.227460E+12 | 228908.14 | 0.331212E+11 |
April | 0.945781E+11 | 0.106444E+11 | 0.181280E+12 | 0.113076E+10 | 0.280852E+11 |
May | 0.131750E+12 | 0.107777E+11 | 0.168210E+12 | 0.247655E+10 | 0.404970E+11 |
June | 0.145578E+12 | 0.830724E+10 | 0.121493E+12 | 0.378860E+10 | 0.692400E+11 |
July | 0.143984E+12 | 0.649083E+10 | 0.907576E+11 | 0.335909E+10 | 0.107944E+12 |
August | 0.119077E+12 | 0.648575E+10 | 0.106007E+12 | 0.410952E+10 | 0.900852E+11 |
September | 0.885993E+11 | 0.695729E+10 | 0.130573E+12 | 0.319817E+10 | 0.576115E+11 |
October | 0.504503E+11 | 0.886806E+10 | 0.180351E+12 | 0.153607E+10 | 0.276725E+11 |
November | 0.199205E+11 | 0.106672E+11 | 0.207179E+12 | 0.125491E+09 | 0.263887E+11 |
December | 0.110420E+11 | 0.140990E+11 | 0.266422E+12 | 0.00 | 0.381703E+11 |
Annual Sum or Average | 0.960340E+12 | 0.127223E+12 | 0.221466E+13 | 0.198366E+11 | 0.600432E+12 |
Minimum of Months | 0.110420E+11 | 0.648575E+10 | 0.907576E+11 | 0.00 | 0.263887E+11 |
Maximum of Months | 0.145578E+12 | 0.174305E+11 | 0.308690E+12 | 0.410952E+10 | 0.107944E+12 |